34
Performa No. Particulars Remarks/Report SoP 001 Fatal & Non Fatal Accident Report Yearly Report SoP 002 Action taken report for safety measures complied for the accidents occurred Yearly Report SoP 003 Register for compiling the complaints classificationwise Yearly Report SoP 004 Actons or steps carried out by distribution licensee towards public awareness in the year Yearly Report SoP 005 Action taken report by the Redressal Committee Yearly Report SoP 006 Failure of Distribution Transformer. Yearly Report SoP 007 Failure of Power Transformer. Not Pertaining to DISCOMs SoP 008 Sample Test result for Neutral Voltage Yearly Report SoP 009 Sample result for Voltage Variations Yearly Report SoP 010 Sample Test result for Harmonics Yearly Report SoP 011 A System Average Interruption Frequency Index (SAIFI) Yearly Report SoP 011 B System Average Interruption Duration Index (SAIDI) Yearly Report SoP 011 C Momentary Average Interruption Frequency Index (MAIFI) Yearly Report SoP 012 System Losses at EHT / 11 KV and below Yearly Report SoP 013 Meter Faults Yearly Report SoP 014 Statement Showing the AT&C losses, Collection Efficiency and Billing Efficiency Reports Yearly Report SoP 015 Release of New Connections Yearly Report SoP 016 Compensation Details Yearly Report INDEX

Performa No. Particulars Remarks/Report - Uttar … SOP Report 2012-13.pdf · Performa No. Particulars Remarks/Report ... SoP 008 Sample Test result for Neutral Voltage Yearly Report

  • Upload
    doannhu

  • View
    231

  • Download
    0

Embed Size (px)

Citation preview

Performa No. Particulars Remarks/Report

SoP 001 Fatal & Non Fatal Accident Report Yearly Report

SoP 002 Action taken report for safety measures complied for the accidents occurred Yearly Report

SoP 003 Register for compiling the complaints classificationwise Yearly Report

SoP 004 Actons or steps carried out by distribution licensee towards public awareness in the year Yearly Report

SoP 005 Action taken report by the Redressal Committee Yearly Report

SoP 006 Failure of Distribution Transformer. Yearly Report

SoP 007 Failure of Power Transformer. Not Pertaining to DISCOMs

SoP 008 Sample Test result for Neutral Voltage Yearly Report

SoP 009 Sample result for Voltage Variations Yearly Report

SoP 010 Sample Test result for Harmonics Yearly Report

SoP 011 A System Average Interruption Frequency Index (SAIFI) Yearly Report

SoP 011 B System Average Interruption Duration Index (SAIDI) Yearly Report

SoP 011 C Momentary Average Interruption Frequency Index (MAIFI) Yearly Report

SoP 012 System Losses at EHT / 11 KV and below Yearly Report

SoP 013 Meter Faults Yearly Report

SoP 014 Statement Showing the AT&C losses, Collection Efficiency and Billing Efficiency Reports Yearly Report

SoP 015 Release of New Connections Yearly Report

SoP 016 Compensation Details Yearly Report

INDEX

FH NFH FH FA NFH FH FA NFH

1 Sabarmati1 1 1 2 3 14 23 15

2 Mehsana0 2 4 1 3 20 13 11

3 Palanpur0 1 1 1 0 10 10 5

4 Himatnagar0 0 1 2 0 19 24 12

TOTAL 1 4 7 6 6 63 70 43

Uttar Gujarat Vij Company Ltd ,Mehsana

Performa - SOP 001 : Fatal and Non-fatal Accident report for the year 2012-13

NUMBER OF ACCIDENTS FOR THE YEAR (APRIL-12 TO MARCH-13)

Sr. No. Name of area

No.of accidents in the quarterCumulative since the first

quarter of the current FY

yearDepartmental Outsider

C:\Users\ubchauhan5032\Desktop\YEARLY SOP Report 2012-13.xls

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

1 HMT Chorivad

1) Panchal

Pravinkumar

Keshavlal & 2)

Zala Ratansinh

Kansinh

NFH Dept 17.04.12 Chorivad Bhiloda

Maintenence Of 11 kv Akshar jgy feeder was arranged. Necessary line clear was

taken. Loc between 34&35 one 11 kv Goral feeder was crossing. Clearance

between these two feeders was about half feet, whily carrying out tree cutting tree

branch fallen on Akshar JGY feeder due to that conductor jumped and touch with

Goral AG feeder. Hence, return power came momentarily on Akshar JGY feeder.

Due to this two helpers working on SS gentry,got shocked.Goral fdr LC was not

taken by supervisor

CEI Report not received

field offices are

instructed to such type

of location is rectified by

providing Guarding &

proper clearance

maintenance

No

2 HMT Isari

Asari

Bhurabhai

Nathabhai,

Helper

NFH Dept 10.5.12 Meghraj Modasa

To attend the complain of No Power & to repair the Jumper,the Victim climed on

live line of 11 KV Sarkilimdi Jgy feeder whereas he got managed the LC permit on

11 KV Galpur Jgy feeder being under impression of 11 KV Galpur feeder. He

touched the live line and non fatal accident occured.

CEI Report not received

Line staff were educated to

conform the line must be

made off before starting of

work. Also proper earthing

must be done on both the side

of the section in which work

has to be done

No

3 HMT Punasan

Pravinbhai K

Kharadi

Vill.Helper

Baman

NFH Dept 6.9.12 Gambhoi Hmt

While attending the PF of vavdi JGY fdr Shri P K Kharadi,Victim by blunder tried to

isolate AB switch of 11kv Himatpur Agr feeder by hand without using operating rod

instead of 11kv Vavdi JGY with illusion that the said vavdi feeder is isolated from

initial position and there was 3 ph power supply on himatpur agr feeder so his

hand comes into induction zone and fall down to earth & got injuries

CEI Report not received

Inform to linestaff to avoid this

type of miskate in future &

use safety equipments while

working on line & line on

which work has to carried out

and also nearby line must be

made dead by earthing on

both the side

No

4 HMT Waghpur

H M

Prajapati,Line

Helper

FH Dept 9.9.12 Prantij Hmt

For attending the complain of broken LT cond.of Surykund TC loc.at vill.waghpur,

on stringing the top side conductor,the said conductor in the earlier span comes up

due to tension through stringing and touches with live conductor of 11kv line of

Galteshwar agr fdr.which is crossing in the said span and the victim got electric

shock due to this touching of LT line to the live 11kv line conductor and fall down

and got injuries.Then after during the further treatment at Appolo hospital the

victim got died on dated;30.9.12

CEI Report not received Particular HT&LT

crossing is removedNo

5 HMT Savgadh

Sureshbhai

Dungarbhai

Varsat

FH O/S 4.04.12 M'pura Hmt

On construction side of Tanishk Bunglows at vill Savagsh after Temp. conn.,Temp

LT line on iron pipe with cable is laid in the party premises & Light & other switch is

fixed on said iron pipes,the victim while going to drinking the water from water tap

adjacent to the iron pipe,came into the contact to the said pipe & got electric

shock through the pipe due to any reason and immediately hospitalised & during

treatment the victim get dead thereafter

CEI Report not received

Consumers was awared

for the installation of

ELCB in his premisesNo

6 HMT Bhiloda

Sharma

Nishanbhai

Shantilal

NFH O/S 12.04.12 Bhiloda-1 BhilodaOn dated 12.04.12 at time 18:30 o'clock victim was climed up on neem tree to take

neem flowers suddenly the tree branch was broken and victim fallen down with the

tree branch on 11kv Bhiloda Urban feeder and got shocked.

victim climbed on neem

tree branch which is

touched with live 11 kv

line & got electrocuted.

periodically Tree cutting

should be done by field

office.

Yes,it is

complied

Maintenance & tree

cutting carried outNo

7 HMT Hmt

Mehta

Manishaben

Hemantkumar

FH O/S 30.04.12 Hmt(T) Hmt

The out going cable feeding the supply from starter to motor was damaged &

insulation is opened ,the same is in contact with metal box holding the starter,so

while starting the same submersible motor at home ,on operating the starter by

vicitim the leakage current flows into the box through damaged insulation part of

cable & box became electrcally charged and the vicitm came into this charged box

& got electric shock

leackage current passes

due to opening of

insulation of submersible

cable due to rushing of

cable at galvenise box

consumer shold take

care to keep the

electric appliances in

healthy contdition for

safety

Yes,it is

complied

safety awareness

programme arrangedNo

8 HMT Lusadiya

1).Suvera

Eliyabhai

Chimanbhai &

2). Suvera

Hermeshbhai

Timotibhai

NFH O/S 18.5.12 Bhiloda-2 Bhiloda

1).Two conductor of JGY LT line & 11 KV lusadiya AG fdr line touch & fixed with

eachother , so that short circuit the LT network & meter & service & wiring at

consumer end. During that incident both victim was gone to switched off the main

switch of own house wiring at that time both victim are came in contact in electric

shock& met with NFH accident.While detail verification of site observed that from

anautohirised source that an out sider while removing anauthorsied lungariya from

ground, Due to force that LT conductor of JGY feeder was jumped & touched with

11 KV AG Lusadiya Feeder

Two conductor of JGY

LT line & 11 KV lusadiya

AG fdr line touch & fixed

with eachother , so that

short circuit the LT

network & meter &

service & wiring at

consumer end. During

that incident both victim

was gone to switched off

the main switch of own

house wiring at that time

both victim are came in

contact in electric shock

Guarding is required

between LT line & HT

line

Yes,it is

complied

field offices are

instructed to such type

of location is rectified by

providing Guarding &

proper clearance

maintenance

No

9 HMT Jitpur

Jayeshbhai

Sureshbhai

Valand

FH O/S 24.5.12 Choila TalodVictim try to start the table fan in his home and he used open ended wires without

pin plug to switch Board. During switched on the Table Fan victim came in contact

with open ends of wire and got electocuted & resulted into fatal accident.

CEI Report not received

Consumers was awared

for the installation of

ELCB in his premisesNo

10 HMT Kashipura

GITABEN

GIRISHBHAI

PATEL

FH O/S 10.06.12 Bayad Talod

The victim was came in the direct contact of the live part on the three pin plug pin

male contact while going to fix plug in female contact for starting the single phase

motor by temporary cable at his residence.The victim got electric shock and

died.The accident has occured in private premises of the resedential

connection.The police department has informed very late regarding accident prior

to that no intimation was given by anyone to sdn office.

CEI Report not received

Consumers was awared

for the installation of

ELCB in his premisesNo

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

11 HMT Butal

Dipak

Jayantibhai

Vaghari at

17.00

FH O/S 13.6.12 Dhansura Talod

Looking the site of accident it is found that a service wire is passing from LT line

to victim premise at meter. From meter to approximately 4 to 5 ft away service

phase wire is opened by removing insulation for the purpose of theft also found

spark spot on the phase wire. The height of accident location is approximately 5ft

above from the ground level. As per discussed with the relatives of victim he tried

to protect his house from the rain so he provide TADPATREE at the roof of house

and at that time he may came in contact at with open phase wire of service and

got electrical shocked & fatal accident occured.

victim he tried to protect

his house from the rain

so he provide

TADPATREE at the roof

of house and at that time

he may came in contact

at with open phase wire

of service ,removing

insulation for the purpose

of theft

According to the rule

no. 30 of the

Electricity act 1956,

all the field officers

are instructed to take

care of all the electric

parts which are

under the consumer

premises.

Yessafety awareness

programme arranged for

consumer No

12 HMT Gopalpura

VIJAYBHAI

BABUBHAI

KHANT

FH O/S 20.06.12 Bayad Talod

At village gopalpura real stone industry con no: 23657/00002/0 khant vijaybhai

babubhai was making welding to new structure of quarry works and directly

contact with live welding wire and got electric shock and met with fatal accident

and died.The accident has occured in private premises of the industrial

connection.

khant vijaybhai babubhai

was making welding to

new structure of quarry

works and directly

contact with live welding

wire and got electric

shock

According to the rule

no. 30 of the

Electricity act 1956,

all the field officers

are instructed to take

care of all the electric

parts which are

under the consumer

premises.

Yessafety awareness

programme arrangedNo

13 HMT Helodar

Patel

Nischalkumar

Sureshbhai

FH O/S 4.7.12 Malpur Modasa

The said accident place is a cattle shad with roof is made of iron roof sheet, other

iron rod and iron grill is fixed on the place of accident. The cattle shed is siyuated

back of the resident. It is 35 mtr far away. A private yellow alluminium two core pvc

cable is laid down from resident to cattke shed over head for ltg. purpose the

phage wire's inulation is damage where it touch with cattle shed iron roof sheet.

Leakage current flow from open alluminium wire to iron roof sheet, iron rod & iron

grill. A victim touch with this iron grill & got electrical accident & fallen into the

cement open water filled tank & died on the spot.

CEI Report not received

Consumers was awared

for the installation of

ELCB in his premisesNo

14 HMT Karoli

Sohilbhai

Isubbhai

Ganchi(Chad

di)

FH O/S 8.07.12 Dhansura Talod

The Driver parked his truck under HT Line, meantime victim climbed on cabin of

the truck and stood on cabin to see whether greet in truck was filled properly, at

that time he came in contact with HT line passing over the cabin and got

electroculated and died. The hight of both PSC poles from top of the Pole to the

ground is 20 Ft.and 20.4 ft.respectively. At the accident point ground clearance

reduced due to filling of quarry waste. Sag of line conductor is found satisfactory at

accident location.

CEI Report not received

People was awared to inform the

concern SDO while working

nearer to the electeric line

.Notice issued to Arbuda Quarry

pvt.ltd vide letter no

2821/10.7.12

No

15 HMT Kankrol

Parmar

Rangusinh

Udesinh

NFH O/S 18.7.12 Hmt® Hmt

The victim was working as labour on the under construction building of shri Patel

Dharmeshbhai Gordhanbhai at loc.19,Shyam sunder soc.,Kankrol Hmt.While

dropping the iron road from 2nd floor to ground ,he came into the contact with live

cond. of 11kv line of Nikunj Urban fdr passing nearby through touching of of the

said iron road to the live cond uctor and got electric shocked and same time he fell

down from the 2nd floor to the ground and got injured.

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

16 HMT KathvadaUnknown

personFH O/S 11.8.12 Talod-2 Talod

The site of fatal accident of human unknown person at village Kathvada Ta.Talod

was visited on Dt.11/8/12. on inspection of Ag.Conne.of Shri Ambalal Danabhai

Patel having of Load of 10HP. The consu.having conne.from tapping pole of X'mer

to his own private box. the box having three fuses where three phases came.

among three phases the consumer has used red and blank flexible wires. the rewd

wire is taken from incoming of blue phase. and black is neutral wire. which goes

to the holder of a lamp. the lamp is provided on wooden sticks. due to rainy season

the wooden stick fallen on the ten wire fencing of the farm. the red phase touches

the top most wire of fencing and current is distributed through whole fencing area.

the UNKNOWN PERSON came near the fencing area which is around one sixty

meters from the existing conne. of the consumer. the UNKNOWN PERSON

touches the fencing wire and met with fatal accident on spot.

current is distributed

through whole fencing

area due to unauthorised

work by AG consumer.

the UNKNOWN

PERSON came near the

fencing area,met with

fatal accident

According to the rule

no. 30 of the

Electricity act 1956,

all the field officers

are instructed to take

care of all the electric

parts which are

under the consumer

premises.

Yessafety awareness

programme arrangedNo

17 HMTNava

Bakarpu,Prantij

1.Ranjitsinh

Halusinh Zala

2.Mukesh

Balusinh

Pramar

NFH O/S 4.9.12 Prantij Hmt

HT Pole of balisan Agr feeder was broken & during rectification work of said line

,While stringing of the conductor of Balisana agr fdr by the victims the top

conductor on stringing came into contact with live conductor of Raslod agr. Feeder

which is crossed to said Balisana agr. after the three span from this location.

CEI Report not received

field offices are

instructed to such type

of location is rectified by

providing Guarding &

proper clearance

maintenance

No

18 HMT Juna untarda

Parmar

Subhashsinh

Bhavansinh

FH O/S 05.09.12 Talod-2 Talod

The house bathroom construction was going on under the 11 KV Ag Limb feeder

without any kind of information to sdn office.During that time victim went to the

said site to watch the work & came in contact with live wire & met with fatal

accident.

The house bathroom

construction was going

on under the 11 KV Ag

Limb feeder without any

kind of information to sdn

office.During that time

victim went to the said

site to watch the work &

came in contact with live

wire

Avoid any type of

work nearer or below

the electric line and

maintain the safe

distance between the

electric line and any

type of construction.

Yes

The accident has

occurred due to the

victim's own mistake

No

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

19 HMT Aambagam

Smt. Khant

Savitaben

Vitthalbhai

NFH O/S 15.9.12 Bayad Talod

Victim has extended insulated wire from his house to outsider room from above

iron roof.Because of iron roof the insulated wire insulation was broken & the iron

roof became live conductor.The same iron roof was connected with GI wire for

cloth dry.Mean time while removing the dust by victim with the help of tagara

putted on his head.The tagara was contaced with this GI wire.So the leakage

current flows from iron roof to GI wire & NFH accident occured.

CEI Report not received Victim himself responsible No

20 HMT Rajpur

Tarar

radhabhai

jemabhai

FA(Buffalo) 31.5.12 Dhansura TalodDue to heavy wind tree branches fallen on LT line. Then LT line got shorted & one

wire broken & fallen on the buffalo & met with fatal accident

Accident occurred due to

snapping of the LT line

conductor due to fallen

of the tree on the live LT

line

periodically Tree cutting

should be done by field

office.

Yes,it is

complied

Maintenance & tree

cutting carried out

5000

21 HMT Modasa

Bharvad

Jayeshbhai

Manekbhai

FA (Cow) 11.6.12 Modasa-T ModasaIn 11 KV Modasa Urban Feeder, the bird nest is on LT line Girder Pole. Due to rain

the nest became wet and the leakage current flows through the Pole. Meanwhile

the Cow came in contact with this pole & got electric shocked & died.

CEI Report not received 2000

22 HMT Moyad

Rathod

Kiritsinh

Natwarsinh

FA(Buffalo) 14.6.12 Salal HMT

At vill:Moyad(Nathaji) on loc. Of Sump vali T/C the said buffalo was passing

through the Double pole structure & touched to MMB of DTC meter .In the said

DTC Meter incoming cable was fired due to some reason & PT cable of R-phase

was opened & touched to MMB so the current is leakged through PT cable to MMB

of DTC meter. Mean time the said buffalo e passing under the structure of TC &

came into contact to the said electrically charged MMB & got electric shocked.

Due to leakage current

passes from MMB box to

earthing wire to victim.

Maintenance of LT line

& Fencing is required

surrounding at

transformer center

Yes,it is

complied

Such type of location is

rectified by providing

fencingNo

23 HMT SonisarZala hathisinh

KansinhFA(Buffalo) 31.8.12 Talod-2 Talod

Due to Cyclone HT pole of Sonisar fdr is broken & conductor snapped on the

ground. Mean while buffalo passing near that conductor & came in contact with

live wire, got shocked & died.

CEI Report not receivedMaintenance carried

out5000

24 HMT Alana

Desai

Shaharbhai

Mashabhai

FA( Baby

Buffalo)10.9.2012 Choila Talod

Due to water works body short leakage current coming to transformer center.Mean

time Babybuffalow was passing & came in contact with trnsformer neutral wire &

died on the spot.

CEI Report not received No

25 HMT JAYALA

Kharadi

Natvarbhai

Vechatbhai

(owner)

FA(Buffalo) 9.7.12 Bhiloda-1 Bhiloda

Due to very heavy wind pressure, an LT line of 11KV Virpur JGY feeder was

touched to telephone line. A stay is at the 1st pole of this telephone line. And due

to leakge path goes through telephone line to stay, a buffalo(female) was came in

contact with this stay wire and got electrocuted.

leakage current passes

due to gethering LT wire

& telephone wire through

iron telephone pole &

stay wire.

Guarding is required

between Telephone

line & company's LT

line

Yes,it is

complied

Such type of location is

rectified by providing

Guarding5000

26 HMT

JUNA

AAKODIYA

(DEMAI)

Zala Gitaben

JeshingbhaiFA(Buffalo) 13.7.12 Bayad Talod

On dtd. 13/7/2012, A buffalo of Zala Gitaben Jeshingbhai at:village : Juna

Aakodiya (Demai) Ta: Bayad came at near village transformer center & broken G.I.

wire of transformer neutral earthing by horn, hence leakage current of neutral

earthing passing througn the body & accident occurred as fatal.

Leakage current passes

in neutral wire due to

unbalancing load.

Fencing is required

surrounding at

transformer center

Yes,it is

complied

Such type of location is

rectified by providing

fencingNo

27 HMTNanasamera

Tarar

Nanjibhai

Becharbhai

TARAR

NANAJIBHAI

BECHARBHA

I

FA(Buffalo) 16.7.12 Bhiloda-2 BHILODADue to cyclone the LT conductor slipout from LT shackle insulator & leakage

current flow from D-clamp to earth wire & buffalo came in contact with earth wire

got shocked & died.

CEI Report not receivedMaintenance carried

outNo

28 HMT Khalikpur

Patel

Rakeshbhai

Rameshbhai

FA(Buffalo) 7.08.12 Modasa-T ModasaIN 3P4W LT line Due to rain the momentary leakage current might have passed

through earth wire.Mean while the buffalo came in contact with this earth wire &

got electric shocked & died.

CEI Report not receivedMaintenance carried

outNo

29 HMT Kolavada

Patel

Manguben

Nathabhai

FA(Buffalo) 11.08.12 Modasa-T Modasa

In Transformer center Due to rain & The street light phase touch to the neutral

and the momentary leakage current flows through neutral to earthing wire.Mean

while the buffalo came in contact with this earth wire & got electric shocked &

died.

CEI Report not receivedMaintenance carried

outNo

30 HMTHafsabad

Chhapra

Makwana

Kiritbhai

Ramanbhai

FA(Buffalo) 15.08.12 Modasa-T Modasa Due to rain the momentary leakage current might have passed through earth wire

at Transformer center.Mean while the buffalo came in contact with this earth wire

& got electric shocked & died.

CEI Report not receivedMaintenance carried

out5000

31 HMT Desaipura

Solanki

Sursinh

Nansinh

FA(Buffalo) 4.9.12 Sathamba TalodDue to heavy wind & rain L.V four line wire (440 V) were break down , mean time

Buffalo was passing near that line & came in contact with live wire & met with fatal

accident.

CEI Report not receivedMaintenance carried

outNo

32 HMTNavalpur(Ranas

an)

Smt.Bhuriben

Bhavansinh

Makawana

FA(Buffalo) 15.9.12 Gambhoi Hmt

As reported, due some reason the piece of centing wire fallen between B-phase

& neutral on lt side so leakage current flows through the earthing wire of x'mer

centre.Mean time the victimise buffalo passing nearby the TC & came into

contact with this earthing wire through its horn and got electric shocked and died.

CEI Report not receivedMaintenance carried

outNo

33 HMT Punsari

Barot

Mohanbhai

Trikambhai

FA(Buffalo) 8.8.12 Talod-2 Talod

The site for fatal accident to Buffalo of Shri Barot Mohanbhai Trikambhai At

,Village : Punsari ,Ta:- Talod was visited on Dt.:-08.08.12 . On Inspection of

L.T. Line the Incoming Service Wire Which is Connected to Streetlight

Fixtures Which is Opened and Touched to the Sideclamp (fixture Clamp)

and leakage Current Passed Through Pole – There was light rain on date:-

08.08.12 – Night hours and pole surface land was wet in condition- Due to

momentarily touching of Open incoming Service wire to Fixtures Clamp at

that time Buffalo Nearby pole might have got electrocuted and fatal

accident occurred.

leackage current passes

from service wire to

street lighrt fixtures

through iron road of

deterioted psc pole at

bottom side.

periodically

maintenance is

required for service

wire & street light

fixture.

Yes,it is

rectified

Maintenance carried

out10000

34 HMT Meghraj

Bharvad

Mayurbhai

Rajubhai

FA(Buffalo) 15.09.12 Meghraj ModasaConnection of Sh. Devabhai Karmabhai's house was fell down during rainy season

with meter,mmb & wall . After that due to broken service wire and buffalo was

touched with the service wire, hence fatal animal accident occur.

CEI Report not received

Service wire was

replaced by new

service wire

No

35 HMTLalji na

Pahadiya

Khant

Pratapbhai

Bhemabhai

FA(Buffalo) 07.09.12 Malpur Modasa

Due to short ckt in electrical instrument(fan) in the house of sh. Patel Haribhai

Moghabhai,leakage current flows to the LT line and Transformer centre earthing

and meantime buffalo was touched with the earth wire, hence fatal animal

accident occur.

CEI Report not received

Consumers was awared

for the installation of

ELCB in his premises5000

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

36 HMTVantada(Kabola

)

Chauhan

Sabaji MalajiFA(Bullock) 6.7.12 Modasa-R Modasa

Due to heavy cyclone & rain , one LT conductor of 11 KV Gadha AG feeder has

been snapped & the Bullock was came in contact with this live conductor and got

shocked and died.

accident occurred due to

touch with the broken LT

line live wire

periodically

maintenance is

required

Yes,it is

rectified

Maintenance carried

outNo

37 HMT AnjanaPatel Abalal

ShababhaiFA(Bullock) 12.7.12 Talod-1 Talod

Bullock is died due to electrical or not it is not justified. So after getting pm report

actual reason wii be justified.CEI Report not received No

38 HMT Dhansura

Rabari

Nikulbhai

Sankabhai

FA(Cow

,Goat)04.07.12 Dhansura Talod

At the time of rain falling leakage current passed from deterioted service wire to

girder pole and that time cows was sitted near the girder pole and the fatal

accident occurred

CEI Report not receivedMaintenance carried

outNo

39 HMT Hmt

Rabari

Karamshibhai

Nagjibhai

FA(Cow) 7.9.12 Hmt(T) Hmt

At " khada vistar" of mehtapura area, the compound wall of nagarpalica garden fall

on a supoort pole of LT line & the LT pole broken and 1ph 3w lT line also broken &

Live conductor of said LT line fall down and lies on the ground, same time the

victimised cow came into contact with this live broken conductor and got electric

shock and died

CEI Report not receivedMaintenance carried

out2000

40 HMT Gambhirpura

Rabari

Somabhai

Lilabhai

FA(Cow) 11.9.12 Idar-T IdarDue to heavy rain and wind Lt pole B-phase jumper touched to D-clamp so,

leakage current passsing through pole to earth wire. Meantime cow came in

contact of leakege path current and animal(cow) fatal accident occurred.

CEI Report not receivedMaintenance carried

outNo

41 MSH Kharna

Arvindbhai

kavabhai

Asari, ALM

NFH Dept 19.06.12 Gozariya Vijapur

A single phase two wire LT line was there on 10 mtr PSC Pole just near the

Kharna-Amarpura bus stand over the road crossing of Gozariya-Gandhinagar

Highway. Also 11 KV Boru Ag Dom feeder emanating from 66 KV boru s/s was

crossing the single phase two wire LT line. On dated 19/6/12, a programme was

given to remove the 8 mtr nacked psc pole just near the 10 mtr psc pole at Kharna-

Amarpura bus stand. On the said 10 mtr psc pole two service wire was connected.

To remove the nacked pole, the service wire was removed. After removing nacked

pole victim shri A K Asari climbed on 10 mtr psc pole to reconeect the service wire.

The ground staff had binded the single phase service with 2 core service wire and

gave to Shri A.K.Asari . He had hold the service and tried to bind with 10 meter

PSC pole. During Binding work jerk took place and GI wire of single phase service

touched to conductor of 11 KV Boru AG feeder and victim felt down and met with

non-fatal electrical accident.

Due to the some jerk

recieved by A K Asari,

a GI wire binded with

the service wire was

touched to the 11 KV

Boru feeder and victim

got electric shock and

fallen on the groung.

Take the Line clear of

the nearby electric

line before the

starting of the work

and use safety

equipments while

working on the line.

Yes

Inform to linestaff to

avoid this

type of miskate in

future & use safety

equipments while

working on line & line

on which work has to

carried out and also

nearby line must be

made dead by

earthing on both the

side

No

42 MSH Charup

Non fatal

Electrical

Accident

occurred to

D.R.Bhagora

Helper

NFH Dept 6.07.12 Jangral Patan

The work for conversion LT line for street light connection under MP/MLA fund at

Village Charup was Alloted to Sub Division gang under supervision of N.S.Patel

Line Inspector They have isolated the LT line before starting the work. Our helper

Shree D.R.Bhagora was on pole for stringing of conductor. while stringing work at

10:45 AM, the new conductor Jumped and came in inductin zone of 11KV Balva

JGY Feeder which is passing over the LT line. our Helper had got Electric shock

and fall down on ground. He injured on his left shoulder and admitted to Janta

Hospital, PATAN for treatment.

CEI Report not received

All the line staff was

informerd to work with

safety equipments onlyNo

43 MSH Soneripura

Harjivandas

Shankarlal

Rathod,

Helper

NFH Dept 11.07.12 Dhinoj Mehsana

According to the details, the accident took place on Dt. 11/7/12 at 11:30 AM

approx. The Victim Shri. H.S.Rathod went to Shri.Patel Jayntibhai Ambaram's

house at Soneripura for attending No Power Complaint. He checked the

connection and found no supply at the out going terminals of the meter. Revealing

the service might be faulty, he climbed on the roof of house. He checked the

service line and found it broken somewhere under the insulation. He detected the

exact place of breakage and cut the cable skillfully, to prepare for the new joint. He

started applying joint and made a first joint at the neutral. While providing Lt tap on

the joint to the phase - which was live at the time,- suddenly and accidentally, he

touched the live part of the phase wire. As he was standing on the iron sheet roof,

he received electrical shock and fell down there only, shouting for the help.

CEI Report is not

received

Victim & other line

staff were instructed

to use safety tools

while working & also

given the guideline

regarding safety

awareness

No

44 MSH Amarpura

1. Ganpat A

Patel(Helper)

2. Dilip D

Sadhu(Helper

NFH Dept 13.07.12 Kadi-2 Kadi

For givining single phase service wire to LT line near t/c center for releasing

lighting connection, service wire was connected to the first pole from the t/c center

& other end was pulled up by the helper who was climbed on the DP structure for

connecting it to the LT stud of the t/c,During this course said naked end of the

service jumped upward and touched the live HT line. And hence HT power passed

through the service cable to LT line side where two victims had climbed on the two

sequenceal poles, one for giving service wire on the first pole and other for binding

LT shackle, who were met electric current.

CEI Report is not received

Inform to linestaff to avoid this

type of miskate in future &

use safety equipments while

working on line & line on

which work has to carried out

and also nearby line must be

made dead by earthing on

both the side

No

45 MSH Madrisana

Jyantibhai

Maganbhai

Asari(V/S

Helper)

NFH Dept 1.09.12 Detroj Kadi

On dated 1/9/2012, a victim shri Jyantibhai Maganbhai Asari Village helper

climbed on Madrisana villlage T/C for repairing of some fault on lt side of

transformer centre at village madrisana. Before climbing on transformer centre

victim removed the 11 KV fuse link of transformer. Then after while repairing of LT

lug of LT Bushing of transfome, Victim's right hand toched to the 11 KV bushing of

transformer. Thus a not fatal electrical accident took place.

CEI Report is not received

Inform to linestaff to avoid this

type of miskate in future &

use safety equipments while

working on line & line on

which work has to carried out

and also nearby line must be

made dead by earthing on

both the side

No

46 MSH Vareda

Smt. Vijuben

Chhanaji

Thakor

FH O/S 14.04.12 Patan-R Patan

The victim Shrimati Vijuben Chenaji aged 37 years(aprox) resi. of Vareda Ta.

Patan she was living at farm of Shree Chemaji Ravaji Thakor Ag. Conn.

No.24410/00077/6. as per eye witness oral statement there is our transformer

center at consumer premises. The water was logged near by transformer. The

victim was passed thought the logged water & got Electrocuted due to leakage

current and died. but Dy.Engr. of Patan(R) S/dn has visited the accident site but no

sign of leakage current is found.

leakage current passes

in the T/C earthing wire

due to short ckt in party's

motor fault

This can be avoided by

providing quality

earthing at T/C center

.The neutral & body

earthing is also

provided separately at

T/C center

Yes,it is

complied

Quality earthing may be

provided at each

Transformer No

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

47 MSH Mansa

Thakor

Kishanbhai

Chunthaji

FH O/S 13.06.12 Mansa Vijapur

A single phase commercial connection having consumer no. 21601/05457/2 in

favour of shri Thakor Rameshbhai Ishvarji has given to Pan Parlour. The wiring of

the tube light from the left hand holder to starter was connected by open joint wire.

On dated 13.06.12 at about 11:50 PM, there was a heavy rain and this open joint

touches to the tube light patti and so it became live. Also the bottom surface of the

pan parlour was become wet due to heavy rain and suddenly victim's head came

in contact with this live patti and so victim got electric shock and died.

An insulation of the

electric wire giving

power to the tube light

inside the victim's

parlour was damaged

and have in naked

condition. This open

part of the wire was

touched to the iron

patti of the tube light

fixture. A victim's head

came in contact with

the iron patti and

hence got electric

shock.

To install the ELCB in

every residential and

commercial

installtion.

Yes

Consumer was

suggested to rectify

the wiring of his shop

No

48 MSH Ajol

Divakar

Rameshbhai

Balrambhai

FH O/S 4.07.12 Lodra Vijapur

At village Ajol, there is “ Pearl villa “ housing scheme developed by private party.

The site is on Ajol-Lodra Road –Right-hand side. The scheme is under

construction. He has made plotting & houses are being constructed. He has

developed common Amenities like internal road, garden, st. light, C. C .TV

Camera etc. The victim was doing the work of painting on Tabular poles which are

erected for C C.TV Camera on the side of main internal road. The victim was doing

this work using sliding ladder. To get proper height he had tied four bamboos on

four legs of ladder and put this structure on the tractor trolley. The victim has

climbed up on trolley and holds the structure. While driver was driving the tractor.

One 11 KV Veda Ag. Feeder passes through these primacies and cross the

internal road. As soon as, the tractor along with trolly passed under our electric

line, the top portion of structure touched the 11 KV line & victim meet with fatal

electrical accident. Here it is to inform that total height of the moving structured

with tractor was measured about 22 ft. Distance between lower condition of 11 KV

line & RCC road is 19 ft 4 inch. The RCC road is newly constructed with refilling of

earth about 1 ft from original ground level.

An alluminium ladder

was arranged on the

tracter trolley for

painting approximately

30 feet height of the

pole. While adjusting

the location of the

ladder by moving the

tractor the upper part

of the ladder touched

to the 11 KV Veda line

and hence victim gor

electric shock.

Avoid any type of

work nearer or below

the electric line and

maintain the safe

distance between the

electric line and any

type of construction.

Yes

The accident has

occurred due to the

victim's own mistake

No

49 MSHChaveli, Sardar

Avas

Shri

Jayantibhai

Ramsibhai

Raval

Aged

about 50

Years

FH O/S

5/7/2012 at

about

19:30 Hrs

Chanasma Patan

On Dated 05/07/2012 a late night telephonic message received from a local

person by Dy Engineer that a human fatal accident is occurred at village Chaveli

Ta:- Chanasma. On dated 06/07/2012 the Deputy Engineer of Chanasma has

visited the site & found that the accident was occured to Shri Jayantibhai

Ramsibhai Raval in the premises of Shri Raval Rameshbhai Vithalbhai. As per the

Raval Rameshbhai Vithalbhai statement the accident occured while fixing the bulb

on holder & died. While site inspection no any leakage of current or any sign of

electrical accident has been noted. The Dy Engr has visited the doctor of PHC

Lanva who has carried out the post mortom The doctor has personnelly told that

he is not be able to say any thing about perfect cause of death hence he has send

some sample to FSL for further investigation for detail report of cause of accident.

At this time we should wait for P.M.Report before concluding the cause of accident

CEI Report not received

Consumers was awared

for the installation of

ELCB in his premisesNo

50 MSH Jepur

Senma

Mangalbhai

dhudabhai

FH O/S 13.07.12 Vijapur Vijapur

Consmer single phase service cable 2.5 mm2 Cable was passing through metal

sheet of roof.At the junction point of cable & metal sheet insulation of service cable

was breaked(Punctured) by birds/khiskoli.The nest was made by birds at this

place. Due to rainy seasson the nest & surrounding area was wet.At the house of

victim the varagani of iron wire was binded one side at metal sheet & other side

with wooden limb.Leakage curruent was passing through breaked cable to

varagani throgh wetnest The victim came in contact with varani & elecrocute.

A single phase

connection was given

to Shri Mangalbhai by

Vijapur S/Dn ,UGVCL,

whose consumer no.

is 21717/00751/1. The

insulation of the 2 core

2.5 mm2 service wire

might be damaged

either by long service

life or by birds. So that

the live service wire

was came in contact

with the iron Patra. An

iron wire was also

binded with this iron

patra for cloth hanging

purpose. So that a

leakage current was

also passing through

this iron wire. While

taking towel from this

According to the rule

no. 30 of the

Electricity act 1956,

all the field officers

are instructed to take

care of all the electric

parts which are

under the consumer

premises.

Yes

Service wire was

replaced by new

service wire

No

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

51 MSH

Silver Ozon flat,

near Avsar

Party Plot

Shri

Shubhashbhai

Ruplal Damor

FH O/S 25.06.12 Mehsana Ind. Mehsana

For construction of new residential flat scheme, a 3-phase temporary connection

was given to Silver Ozon by Mehsana Ind. S/Dn. On dated 25/06/2012 at the site

of Silver Ozon, Shri Shubhashbhai Ruplal Damor was cutting the mild steel bars

with the help of electric cutter. The wire of this electric cutter had the open joint

nearer to the elctric cutter machine and said joint may be opened. Hence the mild

steel bars might be touch to the said open joint and hence victim might have got

electric shock and died. The occurance of the said accident was informed by the

Electric Inspector. As no one from the silver ozon site had informed regarding the

accident, the said accident is reported very late.

On dtd. 25/6/2012,

victim shri

Shubhashbhai Ruplal

Damor was working to

cut the iron saliya with

the help of hitachi

make 2.0 KW single

phase electric cutter

machine. The said

maching was supplied

by two core flexible

cable wire, which have

open live joint. So

while working, victim

might have came in

contact with this open

live joint and got an

electric shock.

According to the rule

no. 30 of the indian

electricity act 1956,

all the field officers

are instructed to

aware all the

consumers to make

their electric goods

with electic safety.

safety

measures

adopted by

the party.

safety measures

adopted by the party.No

52 MSHHinglachahcar

Chowk,Patan

Bhangi

Hareshbhai

Dahyabhai &

Bhangi

Dilipbhai

Saburbhai

NFH O/S 7.08.12 Patan City-1 Patan

Bhangi Hareshbhai Dahyabhai age 30 years & Bhangi Dilipbhai Saburbhai age 40

years both are Safai kamdar. On dated 7/8/12, both these victims were engaged

for removal of Hording nearer to Hinglachachar transformer centre. The said

hording was fitted with bamboo. While removing the hording victims lost his

balance and so the hording get contacted with DO fuse of Hinglachachar

transformer centre and thus non fatal accident occured.

CEI Report not received

People was awared to

inform the concern SDO

while working nearer to

the electeric line

No

53 MSH DetrojKhumaji

Jugaji Thakor FH O/S 23.09.12 Detroj Kadi

AT Village Detroj (Gayatrinagar) shri Khumaji Jugaji Thakor (outsider) was taking

bath at outside of his house in open space. A steel wire was install for cloth

hanging which was passing over open space.When shri Khumaji touch with this

steel wire he feel current & met with fatal electrical accident. Steel wire was fit with

steel pipe.Steel pipe was fit below steel roof.Steel roof was touchig with service

line support wire( Alluminium wire).This support wire other end was fit with psc

pole.It is posibility that from that support wire current was leakage from pole to

steel wire .

CEI Report is not received

Consumer was instructed to

use non conductive wire for

cloth hanging purpose ans

also service wire has been

replaced

No

54 MSH Kadi

Buffalow of

Shri Jyantiji

Babuji Thakor

FA(Buffalo) 15.04.12 Kadi R-2 Kadi

Due to some fault in submersible motor there is a leakage current flowing in

neutral & earthing of TC when the load is running(Motor is ON), but in case of No

Load condition ( Motor is OFF) there is no any leakage current flowing through the

neutral & earthing of TC. Thus during running of motor & load, a buffalo passed

nearby the TC and came in contact with earthing wire of TC and got electrocuted &

died.

CEI Report is not received

Consumer was intructed to

repair the motor and also TC

earthing has been reactivatedNo

55 MSH Dadhana

FA to

Buffalow total

Thee nos

Edels & Two

nos of Child

buffalow Of

Vishnubha

Narshibha

Zala

FA ( 3 NO.

OF Buffalo &

2 NO. OF

Child buffalo)

11/06/2012

, At 6.15

AM

Detroj kadi

on dt: 11/06/2012 morning at 6:15 AM three buffalo & two child buffalow passing

from a farm. Where a conductor of 11kv Vincchan (Ag) feeder was sanp & was fall

on ground. All 5 buffelow concact with live conductor & met with fatal electrical

accident. The owner of buffelow is Vishnubha Narshibha Zala Vill:Dadhana

tal:Mandal

An 11 KV Vinchhan Ag feeder

was passing nearer to the

Gidhabhai Parsottambhai

Patel's farm. On dated

11/6/2012, shri vishnubha

Narsinh Zala was passing from

this area with three nos. Od

edels and two nos. of child

buffalo. The conductor of the

sais feeder was broken

between pole no. 189/36/13

and 189/36/14 and lying on the

ground. While passing from

this area all these five animals

came in contact with this live

11 KV conductor and died.

As per the regulation no. 41

of the electricity act 2010,

proper earthing shuld be

done and also periodic

maintenance of the line

should be done.

YesLT line conductor of that

portion has been replacedNo

56 MSH Gambhu

FA to 2 No.s

of CAMEL of

Rabari

Bharatbhai

Chhaganbhai

FA(2 no.OF

camel)

14.06.12 at

8.amBechraji kadi

At site verification 3 phase 4 wire LT line goes to w/w connection. At the second

number of LT pole LT conductors broken due to heavy cyclone and rain in village.

One phase conductor and neutral conductor were found broken and laying on the

ground. During site verifaction one phase condutor found under the body of two

camel. Due to heavy rain, ground under the LT line was wet and at that time camel

passes through broken conductor so at that time there is a chance of leakage

current on ground so camel may be electroculated.

CEI Report is not receivedMaintenance of the LT line

has been doneNo

57 MSH Jangral

Cow of Shri

Rameshbhai

Kesharbhai

Rabari

FA (cow)

21.06.12 at

about

16:30 Hrs

Jangral Patan

11 Kv morpa Ag feeder give Power Supply to agriculture consumers of village

morpa.vagdod.&vadani.under jangral s/dn . At the time of incidant, conductor of 11

kv morpa feeder is broken due to pin punchar on loc no-6. When conductor fall

down on ground level, at that time 11 KV Morpa feeder is tripped. After snapping

of conductor , cow pass through between loc. no. 5 & 6 of 11 kv morpa feeder &

becomes in contact with brocken conductor. At that time second times try of 11 kv

morpa feeder is taken from 66 kv Jangral S/s. and hence current pass through cow

and fetal accident occured.

CEI Report not receivedMaintenance carried

outNo

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

58 MSH Vijapur

Rabari

Ishwarbhai

Mafabhai

FA(Cow) 16.06.12 Vijapur Vijapur

B phase of L T line was shorted with Channel fitted on LT railpole due to centing

wire placed by bird on the fabrication.Hence leakage current flow through rail to

ground.due to rain ground was wet.the cow came in this area and meet with

elecrocute.

A LT line was passing

nearer to the Chhabila

Hanumanji Temple in

the Bhatwada area.

On the said LT line on

the pole no.

MVR/VJN/15/01/00105

a centring wire was

placed and this

centring wire was in

touch with the cross

arm of the girder pole

and hence electric

current was passing

from the girder pole. A

cow of the owner

came in contact with

the said girder pole

and hence got electric

shock and died.

Field offices were

instructed to carry out

periodic maintenance

of the electric line.

YesMaintenance of the

line has been doneNo

59 MSH

Mehsana Town,

Near Eklavya

Society

Owner of

Buffalo Shri

Mukeshbhai

Harjibhai

Rabari

FA(Buffalo)5/7/2012 at

9:30 AMMehsana City Mehsana

ON DATED 05/07/2011 9:30 AM, AT EKALAVYANAGAR SOCIETY ON LT LINE

POLE WHICH IS NEAR TRANSFORMER CENTER ,DUE TO LEAKAGE

CURRENT FOUND ON EARTHING OF LT LINE POLE AND THE BUFFALO CAME

IN CONTACT WITH THE LEAKAGE CURRENT THE FATAL ACCIDENT

OCCURRED.

CEI Report is not

received

LT line maintenance

has been carried outNo

60 MSH Khakhadi

Two No. of

buffalo of

Thakor Kalaji

Natvarji &

Thakor

Alpeshji Dinaji

FA(Buffalo)15/08/12 at

10:40 HrsHarij Patan

The two nos of buffalo came nearer to W/W transformer centre of village khakhadi

and horn of one of the buffalo got fixed with the stay wire of the said transformer

centre. So the buffalo tried to remove its horn from the stay wire and while doing

so the anchor rod of the stay wire came out so the stay wire became loose and

suddenly it touched to the incoming jumpers of the transformer centre and the

buffalo got electrocuted. The another buffalo near by also came in contact with the

electrocuted buffalo and so it also got electrocuted and so both the buffallo died on

the spot.

CEI Report not receivedN/A as CEI report is not

received

N/A as CEI

report is

not

received

New stay and earthing

providedNo

61 MSH VidajShri Vaghela

Kaluji AnadujiFA(Buffalo) 14.09.12 Kadi R-1 Kadi

At village-Vidaj, under Kadi-1 sub division, on dated-14-09-2012, at between 1:30

to 2:30 P.M., bufffalow of Waghela Kaluji Anduji was dead near water works T/C of

vidaj village. This office has visited the site on 15-9-2012, but at that time no

leakage was found at that transformer center. Also the dead body of bufflow was

not there, so the exact reason for the death of buffalow can be concluded after

P.M. Report.

CEI Report is not receivedEarthing of the W/W TC has

been reactivatedNo

62 MSH

Tulsidham

Society

Common

Plot,Mehsana

No One FA(Cow)

10.07.12 at

appro.

21:15 Hrs

MSH-Ind MehsanaAnimal fatal accident occurred to cow due to leakage current passed through st.

ltg. Fixture, which became short circuited due to rainy water falling from the exit

pipe of nearby house terrace - to earthing wire & got electrocuted.

CEI Report is not

received

Mehsana,

Nagarpalika was

instructed to change

their faulty fixture

No

63 MSH Sonvad

Shri Thakor

Becharji

Gandaji

FA(Cow) 7.09.12 Kadi R-1 Kadi

At village-Sonvad, Taluka-Kadi, on dated :- 07-09-2012, at between 4:00 to 4:30

p.m., buffalo of Thakor Becharji Gandaji was passing from pastured land for

grazing. Conductor of 1-ph. 2 wire L.T. line toward Indirapara Vistar was broken

due to heavy rain and wind. Due to continuous rain Land was wet and some water

was accumulated a there place. Buffalo comes in contact with live wire and it got

electriculated & died on the spot.

CEI Report is not receivedMaintenance of the LT line

has been doneNo

64 MSH Vasai

Shri

Bhikhabhai

Ramabhai

Rabari

FA(Cow) 25.08.12 Gozariya Vijapur

Due to some fault in 11 KV Vasai Jgy feede, conductor were broken at seven

different locations and due to this fault, lt line cable giving supply to vasai railway

staiton was short circuited . Therefore a leackege current was passing from neutral

of the transformer and at the same time a cow was passing near from this

transformer centre and due leakage current the cow got electrocuted and died.

A leakage current was

passing from the

neutral of the

transformer due to the

lt line cable fired, so

the cow of the Rabari

Bhikhabhai Ramabhai

Rabari came in

contact with the

transformer neutral

and got electric shock

and died.

All the field offices

were instructed to

carry out double pole

earthing of the

transformer centre

Yes

Faulty cable has been

replaced and also

earthing of the tc has

been reactivated

No

65 MSH Khareda

Shri Savdanji

Sardarji

Thakor

FA(Cow) 10.09.12 Jangral Patan

On Dated 10.09.12 at about 12:30 hours the 11KV conductor of 11KV Untwada

feeder was broken near by Agriculture Consumer at Village Khareda due to fault

on 11KV feeder at Loc. No 103.The Conductor was fall down on

ground.Meanwhile a cow of Shree Thakor Savdanji Sardarji of village Khareda

was passed near by the conductor and came in contact with live conductor. Hence

It got electrocuted and died immediately.

CEI Report not receivedLine conductor of that portion

has been replacedNo

66 PLN Brahmadvada

Premaram

Koslaram

Chaudhary-25

years old

FH O/S

25.02.12

reporting

dated

30.04.12

Sidhpur-Rural SidhpurWhile victim was climbed on a water tank (which is located under the 11kv

Zamzam feeder )to clean the dust with use of iron pipe ,the pipe may be came in

contact to the line & he falls to earth.The accident to know by police station

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

67 PLN Ambaji

(1) Devubhai

Shaileshbhai

Joshi, Age-8

years, (2)

Hariben

Shaileshbhai

Joshi, Age 10

years

FH O/S 13.06.12 Palanpur-2 Palanpur

There is a compound wall around Vahivatdar sri bunglow. North and west side of

bunglow there is a fencing on compound wall. On that fencing two nos of tubelight

fixture directly fitted with angle of fencing. one of that tubelight fixture short and

leakage current pass on that fencing. At the time of accident above two children

contact with that fencing and electrocuted.

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

68 PLN Ranpur a vas

Dangi

Dineshkumar

Amarsingh-50

years old

NFH O/S 15.07.12Deesa-Rural-

1Deesa-1

A Fatal accident occurred to victim at Ranpur a vas during replacement of fail

Distribution Transformer of consumer named Koli Bijolji Jagmalji, at that time

victim come with contact with live line & got electrical shock.

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

69 PLN Vajegadh

Shri

Pravinbhai

Ashokbhai

sharma-24

years old

FH O/S 08.08.12 Tharad DeesaA fatal accident occurred to victim at vajegadh village ,while victim was fitting the

Hindustan petrolium signboard without switchoff the power at that time signboard

wire broken and tought with signboard angle & got shocked .

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

70 PLN

Place:-

Jayotindra

International

Factory

premises,, At

Vill:Jagana

(1) Rajendra

Jagdishbhai

Rajput-Fatal

Human & (2)

Kalubhai

Gulabbhai

Pathan-

Nonfatal

Human

FH O/S 17.08.12Palanpur-

RuralPalanpur-1

On dated:17-08-2012,Time:17:45 hours While doing colourworks in factoty of

Jayotindra International AT Vill:Jagana,Tal:palanpur by Labours Named

Rajendra(urfe Farute) Jagdishbhai Rajput & Kalubhai Gulabbhai Pathan by using

alliminium ladder And this ladder sliped and touched to live conductor of 11 kv

Swati feeder and this two persons are electocuted and met with Fatal & Non-Fatal

Human Electric Accident.

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

71 PLN Vedancha

Shri

Maheshkumar

Karsanbhai

Bhangi.

NFH O/S 18.08.12 Gadh Palanpur-2Victim him self climbed on Village T/C at village vedancha & got electrocuted and

met with Non-Fatal Human Electric Accident.CEI Report not received

Consumers were educated to

avoid direct or indirect contact

with the elecric lineNo

72 PLN

At-Deesa

city,N.R.Park

society

Smt.

Ramilaben

Rameshbhai

mali

FH O/S 2.09.12 Deesa City Deesa-1Victim came with contact of Leakage current ,which is flow on electric motor

pump and found victim died due to internal fault of motor.CEI Report not received

Consumer was informed to

check out the proper house

wiring of his premisesNo

73 PLN Mamana

Prajapati

Gangaram

Hemrajbhai-

55 years old

FH O/S 11.09.12 WAV Deesa-1A Fatal accident occurred to victim,while victim entered plug socket in his house

and found victim came with contact of plug wire which insulation is open and got

electric shock.

CEI Report not receivedConsumer was informed to

check out the proper house

wiring of his premisesNo

74 PLN ATARNESH

Owner of

Buffalows shri

RAUMA

RAGHUBHAI

MELUBHAI-2

nos buffalows

FA (2 No.of

buffalo)3.06.12 VARAHI

RADHANP

UR

In this matter one phase of 11 kv naliya ag fdr is snaped due to salty area at that

time two buffalo s are passing from there & snaped conductor is falling down on

two buffalos are coming contact with wire and get shocked and immediatly died at

place.

CEI Report not receivedMaintenance carried

out

10000

75 PLN Baspa

Owner of

Buffalows shri

-9 nos

buffalows

FA (9 no. of

Buffalo)7.06.12 Sami

RADHANP

UR

H.T. line one phase conductor broken and fall on ground near baspa village of 11

kv khodiyar jgy feeder eminating from sami s/s& 9 nos buffalows came into

contact with live conductor and expired on the spot. at that time this feeder not

tripped.

CEI Report not receivedMaintenance carried

out

76 PLN Bavarda

Owner of

Cow- Shri

AYAR RANI

BEN

DUDABHAI

FA(Cow) 13/6/2012 VarahiRadhanpu

r

IN THIS MATTER LT LINE OF SINGLE TWO WIRE OF VILLEGE TC OF

BAVARDA IS SNAPED WITH POLE DUE TO HEAVY CYCLONE . AT THAT TIME

SINGLE PHASE TWO WIRE FALL ON COW & COW WAS EXPIRED

IMMEDETIALLY.

CEI Report not receivedMaintenance carried

out

5000

77 PLN GOTRAKA

Owner of

camel

JEMALBHAI

VARJANGBH

AI RABARI

FA(Camel) 17.07.12 VARAHIRADHANP

UR

IN THIS MATTER A GROUP OF CAMEL'S OF MALDHARI PASSING THROUGH

ON GOTRAKA -CHHANIYATAR ROAD GOING AT HOME VILL. RAU TA. RAPAR

AT THAT TIME ONE OF THE CAMEL TRYING TO EAT LEAVES OF KHIJDO

THEN ITS MOUTH CAME IN CONTACT WITH ONE OF THE LIVE COND. OF 11

KV GOTRKA AG FEEDER & GOT ELECTRICAL SHOCKED & DIED AT THAT

TIME.

CEI Report not receivedMaintenance carried

out

5000

78 PLN Unava

Shri Rabari

Motibhai

Kurabhai

FA(Cow) 04.07.12 Unjha-Rural Sidhpur

A Fatal accident occurred to Cow due to leakage current flow surrounding T/C &

Cow come near current flow area near T/C, At site observed Motor of w/w

connection found short ,so leakage current flow through neutral of Transformer.&

got electrical shock

CEI Report not receivedMaintenance carried

outNo

79 PLN Arniwada

Owner of

COW- shri

Bhil

Bhagvanbhai

Haribhai

FA(Cow) 13.07.12 IQBALGADHPALANPU

R-2

A Fatal accident occurred to COW due to broken conductor of 11kv Awala AG

Feeder near P.H.Patel T/C at village Arniwada & fallown on ground while cow

came with contact of broken conductor & got electrical shock.

CEI Report not receivedMaintenance carried

out

5000

80 PLN Suigam

Owner of

COW- shri

Rabari

Maghabhai

Kalabhai

FA(Cow) 10.09.12 WAV Deesa-1A Fatal accident occurred to Cow due to Snnapping of LT conductor in village

suigam & cow came with contact of broken conductor and got electric shock.CEI Report not received

Maintenance carried

outNo

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

81 SBT Dehgam

Rabari

Karmenbhai

Kalyanbhai

FA(Buffalo) -6.7.12 at

12.30hrsDehgam T

Gandhinag

ar

Insulation of AB cable broken,Due to this live wire touched to D-clamp.Which was

earthed by GI wire.Due to this leakage current pass through GI wire.CEI Report not received

Maintenance carried

outNo

82 SBT Kathwada

Shri Shailesh

Lalabhai

damor

(V/S helper).

NFH Dept 14.04.12 Bareja Sabarmati

On dtd. 14.4.12, program of T/C replacement was given and Shri H R Waghela

ALM was the supervisor. Shri D.K.BHAGORA had gone to isolate the switch and

Shri H R Waghela and Shri D.K.BHAGORA were communicating, meanwhile Shri

S L Damor(victim) due to some misunderstanding (as per other present staff

nivedan) climbed on T/C structure before the AB switch was isolated. Suddenly

Shri S L Damor fallen from T/C structure to ground victim may came in contact

with live contacts of HT line or may be victim came in induction zone & due to that

accident occurred to Shri S L Damor (V/S helper).

CEI Report not received

Inform to linestaff to avoid this

type of miskate in future &

use safety equipments while

working on line & line on

which work has to carried out

and also nearby line must be

made dead by earthing on

both the side

No

83 SBT Dhandhuka

Shri Parmar

Popatbhai

Somabhai ,

V/S Helper

NFH Dept 04.05.12 Dhandhuka Bavla

On Dated 04.05.2012, Heavy wind flow passed through Dhandhuka at 6.00 pm.

Due to it 11 kv feeders were tripped. Among these feeders, 11 kv zanzarka feeder

was also tripped. Shri R.S.Ganderi (LI), Shri R.K.Ninama (v/s Helper),Shri

H.L.Pandor(v/s Helper),Shri P.S.Parmar(v/s Helper), went to attend fault on 11 kv

zanzarka feeder. First they cut the 1st AB switch on Limbadi road and charged

zanzarka feeder from S/S and after testing at AB switch they found one phase was

not coming.So, they were making patrolling from first AB swith to towards jaliya

S/S.While petrolling they found that one zamper was burnt on 42' gurder pole,

which is shackle pole in the compound of D.A.ENGLISH medium highschool near

S/S. Also two nos of feeders are passing on these shackle pole. The one burnt

jumpure found on upper side feeder of shackle pole, which was 11kv Zanzarka

feeder. All of them discussed about taking line clear of two feeders to repaire burnt

jumper. Shri R.S.Ganderi took line clears of 11 kv Zanzarka feeder & 11 kv Rojka

feeder on mobile phone. Actually, upper feeder is 11 kv zanzarka feeder and lower

is 11 kv zankhi feeder of 66 kv jaliya S/S. Shri P.S.parmar climed on shackle pole

for repairing of jumper & falled down. immediately sent him to RMS hospital and

then shifted to CIMS ahmedabad.

Wrong feeder LC taken

by Supervisor ,not use

safety tools & not proper

earthing on working

place

As per the regulation

no. 41 of the electricity

act 2010, proper

earthing shuld be done

& egulation no. 19 use

safety equipments

while working on the

line.

Inform to linestaff to avoid this

type of miskate in future &

use safety equipments while

working on line & line on

which work has to carried out

and also nearby line must be

made dead by earthing on

both the side

No

84 SBT

HK FINECHEM

URBAN FDR'S

GANRTY NEAR

SANAND SS

Harshandbhai

Parsottambha

i Vegada

NFH Dept

08.05.12

AT @

11.00 HRS

Sanand-1 Bopal

During maintenance of HK Finechem fdr, H P Vegada was working on Cross

boundary switch of Gantry of HK Finechem feeder and suddenly electric power

came in the 11 kv line and he was burnt at palmer(b/h palm) of left hand . He was

taken for treatment at hospital. . Electric power might be came from any generator

of consumer end.

CEI Report not received

Explanation asked to A

C patel ALM vide letter

no

Sanand/Tech/2278/21.0

5.12

No

85 SBT Valad

(1)Shri.

Santoshkuma

r Khanabhai

Charel,(2)Shri

.Ismailmiya

K Parmar

NFH Dept 21.05.12 Chiloda-1 G 'nagarAlthough the L.C. on 11KV Limbadiya AG feeder taken but the outsider cut the tree

which fallen on 11Kv line & the top part jumping and touch with conductor of

132KV Chiloda Ranasan line & Accident occurred.

outsider cut the tree

which fallen on 11Kv

line & the top part

conductor broken

&jumping and touch with

conductor of 132KV

Chiloda Ranasan line

which is above the 11 kv

line

periodically Tree cutting

should be done by field

office.

Yes,it is

rectified

Maintenance carried

outNo

86 SBT Chaloda

SHRI.CHAND

RAKANT

LAXMANBHA

I PANDAV ,

Helper

NFH DEPT 21.07.12 Dholka ( R ) Bavla

SHRI.CHANDRAKANT LAXMANBHAI PANDAV WORKING IN DHOLKA(R)SUBDIVISON

AS HELPAR AT VILLAGE CHALODA .WORKING ON LT LINE HIS LEFT HAND

TOUCHED 11KV H.T LINE FEEDAR CONDUCTOR OF KHANSARI(BADARKHA)

FEEDAR NEAR TO LT LINE AND MATE WITH MINOURE NON FATAL ACCIDENT AT

16:40 P.M ON 21-JULY-2012

WORKING ON LT LINE

HIS LEFT HAND

TOUCHED 11KV H.T LINE

FEEDAR CONDUCTOR

OF

KHANSARI(BADARKHA)

FEEDAR NEAR TO LT

LINE

Take the Line clear of

the nearby electric

line before the

starting of the work

and use safety

equipments while

working on the line.

Inform to linestaff to

use safety

equipments while

working on line and

also nearby line must

be made dead

No

87 SBT Kanotar

Shri

B.V.Ghatiya ,

Helper

NFH Dept 12.8.12 Koth Bavla

During attending Kalyangadh JGY Feeder Fault work, on disconnecting the AB

Switch behind Bhamsara village by keeping one helper there and near Kanotar

village a doutful Transformer without D.O. Unit, Shri B.V.Ghantiya, Helper was

isolating the Transformer from H.T. Line a returned current passed through his

right hand and and went out from his right thigh. This incidence was occured

during disconnecting the last Jumper (B Phase) of H.T. from Transformer Centre

and only Y Phase had given earth by earthing rod.

CEI Report not received

As per MRI report

taken, we have issued

notice to the BSNL

Company for return

power which is shown in

his DTC meter

No

88 SBT

Kathwada (

Shed no.c-65

Zaveri estate)

Shri

Rakeshbhai

Rameshbhai

Parmar

NFH O/S 12.04.12 Kujad SBT

The victim was working as a labour for work of digging of dranage line , on dt

12.04.12 at aprox. 11:00 am the victim was standing near the transformer centre

and same time the work of digging dranage line was going on . A metal rod was

laying near the T/C , when the victim put the metal rod from one side to other side

accidently one end of rod came in contact with live portion of D.O. of T/C .

Another end of rod was hold by the victim hence he got electric shock and fell on

ground.

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

89 SBT Palwada

Shri.

Arvindbhai

Revabhai

Raval (NFH)

& Shri.

Rameshji

Jugnathsinh

Dabhi (NFH)

NFH O/S 12.04.12 Bavla Ind Bopal

High stringing of AB (Areal bunch) conductor and removal of LT open conductor in

LT span where 11 kv Moraiya feeder line crossing, During stringing of LT line

came in contact with 11 KV Moraiya feeder line and both the victims got

electrocuted shock.

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

90 SBT Sagdalpur

SHRI

FULARAM .N

.DAMOR O/S

FH O/S 20.5.12 Rakhiyal G' nagar

On date 20.5.12 at approx 19:00 hrs the victim was sprinkling the water to the

bricks in umiya mojek tiles factory by 1 phase motor during sprinkling the pipe

from motor was remove at that time the victim was trying to fit the pipe of wet

motor and he direct contact with leakage current of faulty internal wiring motor and

got shocked and fatel accident occured.

victim was trying to fit the

pipe of wet motor and he

direct contact with

leakage current of faulty

internal wiring motor

To install the ELCB in

every residential and

commercial

installtion.

YesConsumers was awared

for the installation of

ELCB in his premisesNo

91 SBT Uvarsad

(1)Shree.Nare

shbhai

Manganbhai

Dantani(Cond

uctor),(2)

Chetanbhai

Chhababhai

Dantani(Drive

r)

NFH O/S 23.5.12 Adalaj G' nagar

On dt.23.5.12 approx. 10:30 am truck with hydrolick jack had came to contact with

11 kv HT line of preksha feeder coming from Adalaj s/s & at the time of uploading

the sand electric current flow due to hydrolick dumper to 11kv line & victim got

electric shock at time & NFH accident occured.

truck with hydrolick jack

had came to contact

with 11 kv HT line of

preksha feeder coming

from Adalaj s/s & at the

time of uploading the

sand electric current

flow due to hydrolick

dumper to 11kv line

Accident occurred due to

lack of knowledge of Victim

Victim

responsible

Consumers were educated to

avoid direct or indirect contact

with the elecric lineNo

92 SBT Dhanaj

Jayantibhai

Bababhai

Parmar(45

years)

FH O/S

06.06.12

@

12:30hrs

Santej Kalol

outsider Victim had climbed on T/C structure of ONGC well in village Dhanaj to

repair H.G. Fuse of outgoing jumper of horngap fuse at T/C center & Victim had

remove the D.O. fuse.While binding the jumper, binding wire touched the upper

bushing D.O.fuse & Victim got electric shock & fell on the plinth below T/C

structure.R.G.Nai Vs helper was supervising the work.First Victim was shifted to

Kalol & than Ahmedabad Civil hospital where he was declare dead.

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

93 SBT Changodar

Shri.Anilbhai

Danaji Thakor

(30 years)

FH O/S

11.06.12

@

10:10hrs

Changodar Bopal

On dated 11.06.12 ,a dumper truck GJ-1 BV 1924 came with sand filled trolly at

the 37/1,Ashawmegh ind.Estate in the premises of HT connection Sun Electro

Grovers,HT 18504 to unload the sand as the construction work inside the factory is

going on at 10.00 AM.After unloading the sand using hydraulic system,the driver

tried to drive his truck in forward direction towards gate keeping the hydraulic

system rod in upholding position so the upper part of the trolly trepped in one live

conductor of 11KV Satluj feeder.Then driver of the truck jumped from the truck

while cleaner of the truck tried to come down by keeping one foot on ground & one

hand with handle of cabin of the truck.The electric current passed from conductor

to truck body to the victim's body and to ground.At the same time the

cleaner(victim) got electrocuted and at the same time feeder was tripped at 10:10

AM.Victim died at 10:55 after hospitalization during treatment.

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

94 SBT

Swastik

Residency

,Manipur

Shri.Rakeshb

hai

Rameshbhai

Raval,14

years

FH O/S16.6.12 at

12:00 Hrs.Bopal Bopal

On dated16.6.12 at about 12=00 Hrs. (noon) a 14 year old boy Shri. Rakeshbhai

Rameshbhai Raval of village Manipur Ta. Sanand was passing near House No:18

of Swastik Residency ,opposite Manipur Primary school somehow came in contact

with MSP of Swastik Residency supplying power to its consumers.It was raining

and due to leakage current on MSP(metal box) the victim got electrocuted and

died.

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

95 SBT BarejadiVijaybhai K

TadviFH O/S

30.06.12

@ 09:30 Barejadi sabarmati

on 30.06.2012, at about 9:30 am, the victim & other 4 persons passed through this

road in vehicle no. GJ 9V 7321 near the well of Jasvantsinh N Waghela. One

conductor at this location having very low hight from ground and the driver

(Pravinbhai G Bharvad) has seen the conductor but anyhow the vehicle came in

contact with live conductor and instantly the vehicle stopped & driver could not

restart the vehicle. So victim & other 4 person tried to came down from the vehicle

but victim could not balance his body while came down & his left hand touched the

dala (rear part of vehicle) & fallen on the ground & got electrocuted. One of them

named Jigneshbhai R Tadvi tried to save the victim but he himself got electrocuted

but found ok later. The other 4 persons came down safely.

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

96 SBT Kathwada

Shri

Rakeshbhai

Hakuji Thakor

NFH O/S

Reporting

date

5.07.12

Kujad Sabarmati

There is no intimation about the accident to Sub-Division office. On dtd. 5.7.12,

AEI informed telephonically to DE, Kujad S/Dn who carried out site inspection on

6.7.12. Victim was doing work of roff fitting in Shed No. 55, Tribhuvan Estate

Kathwada. The Plastic roof/Shed is made of plastic material with metallic thread

inside. Victim climed the iron gate to fix the roof which came in contact with live

cond of 11KV Tribhuvan feeder due to which he got shock and fell on ground

injuring himself. Furthr no tripping of feeder was recorded in S/S from 4-5 PM

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

97 SBT Trent

Govindbhai

Akhuji

Waghela

FH O/S8.7.12 at

16:40 PMMandal Sabarmati

A human fatal accident had occurred to Shri..Govindbhai Akhuji Waghela(outsider

labour of contractor of Hemali electricals)lived in Village:Robas,Ta.Dessa,Age;20

Approx due to come in contact with live wire of 1phase 2 wire LT line at village

Trent Ta. Mandal around 12:30 noon.He was replacing armoured service at

kumbharvas (trent village) without removing DO of bhaktinagar village T/C.

CEI Report not receivedConsumers were educated to

avoid direct or indirect contact

with the elecric lineNo

98 SBT GODHAVI

ROSHANSIN

G M

RATHOD

NFH O/S

09.07.2012

@ 6.30

AM

SANAND I BOPALSecurity gard of Zaydus centre with the iron road about 5ft long,one side with huq

touch the 11KV line of nidharad JGY feeder by iron rod when trying to jump the

wall with the fencing.

Security gard of Zaydus

centre with the iron road

about 5ft long,one side

with huq touch the 11KV

line of nidharad JGY

feeder by iron rod when

trying to jump the wall

with the fencing.

Victim responsibleVictim

responsible

Consumers were educated to

avoid direct or indirect contact

with the elecric lineNo

99 SBT Dehgam

Smt Minaben

sanjaybhai

shah Age 36

yrs

FH O/S 8.8.12 Dehgam(T)Gandhinag

ar

Victim Smt. Minaben Sanjaybhai Shah was while putting clothes on steel wire for

drying ,got Electrict shock & died, in deatil investigation it was found that, due to

defect in freez & internal wiring , leakage current passed through galvanise sheet

on roof of house,which was supported by the pipe, to which steel wire was tied.

CEI Report not receivedConsumer was informed to

check out the proper house

wiring of his premisesNo

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

100 SBTBHAGUJINA

MUVADA

VIJAYSINH

R. ZALAFH O/S 20.9.12 RAKHIYAL

Gandhinag

ar

On dated 20-09-2012 at 22:00 hours Shri Vijaysinh has gone to river for loading

sand in tractor. After few hours one villager focusing the torchlight on tractor hence

the victim and other young boys understand that the government officer ( royalty

officer ) are coming, hence the all boys to ran away from river and at that time Shri

Vijaysinh was also ran away and might be contact with live fencing wire that

provided in farm of Hathisinh Dulsinh Zala which is near by river for saving the

crops from the Neel cow and victim got electric shock.

CEI Report not received

Consumers were

educated to avoid direct

or indirect contact with

the elecric line or

equipment

No

101 SBT Bakrol

Shri

Khumansinh

Agarsinh

Chauhan

FA(Buffalo)

19.03.12

reporting

late

Changodar Bopal

On dated 20.3.2012, police station ,Aslali has inform to S/Dn office that a fatal

animal accident occurred to a buffalo at village: Bakrol ondated 19.3.12. DE,

Changodar has visited the site on 20.3.2012. As per owner's statement buffalo

died due to conact with stay wire (Stay insulator was bypassed)of Ag T/C which

was tied there near T/C. On date of site visit no any leakage current found on stay

wire.

CEI Report not receivedMaintenance carried

outNo

102 SBT VIRAMGAM

Shri Kanabhai

Vasibhai

rabari

FA(Cow)

16/6/2012

@10:30P

M

VIRAMGAM

TOWNKALOL

An electrical Accident 16.6.12 at 10.30 pm hrs occure to a cow of shri Kanabhai

Vasibhai rabari at Viramgam near V choksi bazar . Their is Leakage Current in LT

Round Pole due to Faulty Street Light Fixture.When cow was passing near the LT

Round Pole due to sarounding wet area due to monsoon electrical fatal Animal

accident occured.(City-2 Feeder,66KVFulwadi S/S)

Their is Leakage Current

in LT Round Pole due

to Faulty Street Light

Fixture

As per CEA regulation 12

,periodically maintenance

should be done by field

office.

Yes,it is

rectified

Maintenance carried

out2000

103 SBT Tintoda Nanpura

Shri.Dayaji

Gabhaji

Thakor

FA(Buffalo) 16.6.12 AdalajGandhinag

ar

BUFFLOW CONTECT WITH TRANSFORMER STRUCTURE AND GOT

ELECTIRC SHOCK AND DIED.(11KV Moti Adaraj feeder/63KVA TC Nanpura-

Tintoda road)

CEI Report not receivedMaintenance carried

outNo

104 SBT kathwada gidc unknown cow

/ no ownerFA(Cow) 16.6.12 naroda Sabarmati

Due to switch short at plot no 378 con no 26002014446 return power come to

transformer earthig through neutral & cow come in contact with earthing wire of

transformer & get shocked

CEI Report not receivedMaintenance carried

outNo

105 SBT Vadsar

Vaghjibhai

Maljibhai

Rabari

FA ( He-

Buffalo)26.09.12 Santej Kalol

Fatal Animal Accident occurred to A He- buffalo, due to current passing through

Stay wire touching with live jumper ,Due to less clearance between stay wire &

jumper.(Only 3 inches)

CEI Report not receivedMaintenance carried

out5000

106 SBT BOPAL

SURESHBHA

I

BHIKHABHAI

BHARVAD

FA (2 no.s of

Buffalo)09.09.12 BOPAL BOPAL

DUE TO HEAVY RAIN & WIND PRESSURE CONDUCTOR OF LT LINE IS

SNAPPED & FELL DOWN ON BARBERED WIRE OF FENCINGOF THE PLOT.

THE BUFALLOWS GRAZING IN THE PLOT CAME IN CONTACT WITH THE

LEAKAGE CURRENT & DIED ON THE SPOT

CEI Report not receivedMaintenance carried

outNo

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

107 SBT Shilaj

GAFURBHAI

NAGARBHAI

RABARI&DE

VABHAI

SURABHAI

BHARVAD

FA (1

No.Cow & 1

no. Buffallo )

13.08.12 Bopal BopalTHERE WAS LEAKAGE CURRENT IN EARTHING WIRE OF TRANSFORMER

CENTRE OF TEMP. CONN. SO WHILE PASSING NEAR BY THE T/C, TWO

ANIMAL COME IN CONTACT WITH EARTH WIRE & DIED ON SPOT

CEI Report not receivedMaintenance carried

outNo

108 SBT Kalol(T) No owner

FA To 2

nos,of

ox(Akhala)

12.8.12 at

3.15 AMKalol(T) Kalol

Fatal Animal Accident to Two nos. of Ox occurred, due to a leakage current found

on LT Line tubular steel pole due to streetlight fixture fault

leakage current found on

LT Line tubular steel pole

due to streetlight fixture

fault

As per CEA regulation 12

,periodically maintenance

should be done by field

office.

Yes,it is

rectified

Maintenance carried

outNo

109 SBT Kathwada GIDC

Karmanbhai

talajabhai

Rabari

FA( 2 nos of

Cow)29.09.12 Naroda Sabarmati

as per investigation report due to LT pole broken by pvt vehicle no GJ - 18 8438

opp. Plot no:489 & LT conductor snapped & 2nos of Cows came in contact of live

wire ,got electrolucted & died

CEI Report not receivedMaintenance carried

outNo

110 SBT RampurShri.Juhabhai

P.BharwadFA(Buffalo) 3.07.12 Dhodaka Bavla

At about 16:00PM group of buffallows passing near to pole quarelled with each

other and collide with pole and due to impact LT line pole (1Ph 2wire) fallen down

& also line broken .The buffalow passing nearby came in contact with line and met

with the accident.

group of buffallows

passing near to pole

quarelled with each other

and collide with pole and

due to impact LT line

pole (1Ph 2wire) fallen

down & also line broken

.The buffalow passing

nearby came in contact

with line

As per CEA regulation 12

,periodically maintenance

should be done by field

office.

Yes,it is

rectified

Maintenance carried

outNo

111 SBT Aakru

Mundhva

Harjibhai

Jadavbhai

FA(Buffalo) 04.07.12 Dhandhuka Bavla

Due to heavy rain and cyclone one LT conductor broken down and laid down at

the road,Same time buffalow and other buffalow came outside of the house due to

cyclone .Buffalow came in contact with live LT wire which is laid down on the road

and got shock.

one LT conductor broken

, laid down on the

road,Buffalow came in

contact with live LT wire

As per the regulation no. 41

of the electricity act 2010,

proper earthing shuld be

done and also periodic

maintenance of the line

should be done.

YesMaintenance carried

out5000

112 SBTDehgam ITI

Road

Bhemanbhai

Hirabhai

Rabari

FA(Buffalo)15.7.12 @

10:30amDehgam T Sabarmati

Insulation of R-ph of pvc cable passing from LT bushingof transformer to LT line

take off pole was worn out.which was touching to the support angle of

transformer.as all metal parts of transformers were earthed but the earth wire was

broken from ground and was tied with stay wire of tranformer centre. due to this

current passed in stay wire & as buffalo came in to contact with stay wire and died.

CEI Report not receivedMaintenance carried

outNo

113 SBT Chankheda

Rabari

Somabhai

Lilabhai

FA(Buffalo)13.8.2012

16.30 HRSChankheda

Gandhinag

ar

Due to failure of earthing retuned power came on neutral. So when the buffalow

came in contact with the earthing wire she got electric shocked and died.CEI Report not received

Maintenance carried

outNo

114 SBT khoraj

shri

Yasinmiya

Rasulmiya

Malek

FA(Buffalo) 17.8.12 AdalajGandhinag

ar

L T line live conductor snapped due to tree fallen on LT line & live wire falled on

buffalow which was bound under LT line.CEI Report not received

Maintenance carried

outNo

115 SBT Dholka

Anishbhai

Ushmanbhai

Vora

FA(Buffalo) 11.09.12 Dholka-T BavlaLooking to the situation of site , it is found that LT wire broken due to big branch of

tree fallen due to heavy wind and buffalow came in connect to live LT wire and

got electrocuted & died

CEI Report not receivedMaintenance carried

out10000

116 SBT VadsarRajaji Mathurji

ThakorFA(Buffalo) 08.09.12 Santej Kalol

Fatal Animal Accident occurred to A buffelo, due to current passing through

fencing, through live conductor ,snapped from line, due to service cable of nearby

AG consumer fired'

CEI Report not receivedMaintenance carried

outNo

117 SBT Viramgam

Cow of

Bhathibhai

Lilabhai Desai

& Goat of Tai

Abbas

Gulamrasul

FA(Cow) 04.07.12viramgam

TownSabarmati

There was Leakage Current in LT Round Pole due to open joint of streetlight

connection which touched LT round pole & flew current, The cow & Goat passing

near the LT Round Pole touched Lt round pole, fatal Animal accident occured.

There was Leakage

Current in LT Round

Pole due to open joint of

streetlight connection

which touched LT round

pole

As per CEA regulation 12

,periodically maintenance

should be done by field

office.

Yes,it is

rectified

Maintenance carried

outNo

118 SBT GIDC,Chhatral

Prabhatbhai

Jesangbhai

Rabari

FA(Cow)

10/7/2012

At 12.00

PM

Chhatral KalolNeutral leakege current of LT Consumer was returned to x'mer centre The rain

was continuing & A Crowd of cows were passes near the x'mer centre.One of

those cow touches to the X'mer centre & got electrocuted & died

CEI Report not receivedMaintenance carried

outNo

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

119 HMT Dhamboliya

1)Gadasha

Bachubhai

Thavaraji-Fatal

2)Gadasha

Jagdishbhai

Virajibhai-Non fatal

FH & NFH O/S 1.10.12 Bhiloda-2 Bhiloda

Both victim were working themselves on LT network .Both are outsider and are not authorised to work

on distribution network.while working on LT network they came in live contact in distribution line and

met with Fatal and Non fatal accident respectively.

CEI Report is awaited

Consumers were educated to

avoid direct or indirect contact

with the elecric line

No

120 HMT Akrund

Amarsinh J.

Makwana(Assi.

L.M.)

NFH Dept 5.10.12 Dhansura Talod

At the location of the 11kv Akrund AG Feeder loc.no.154/17 where accident occurred ,66kv Dhansura-

Ambaliyara line is passing over the said 11kv line at loc.no.154/20 & on the Dt.when accident

occurred Amp.loading on 66kv line is high and ambient temp.was arround 35Cent.,due to the loading

& temp.effect conductor of 66kv line might have lowered.When victim climbed on the pole for repairing

of jumper at loc.no.154/17 during this time 66kv conductor may lowering & due to this ,distance

between 66kv & 11kv line may reduce & victim might have come in induction zone at that time and

further resulting electrocution and victim falling on the ground & accident may occured.At the same

time 66kv line tripping is observed.This is our primary observation,detail investigation report finally

given after taking nivedan of victim.

CEI Report is awaitedSdn has lower the 11 kv line

after the incidentNo

121 HMT Ambabar

Baranda

Champaben

Prakashbhai

FH O/S 2.10.12 Bhiloda-2 Bhiloda

In consumer premises,leakage current came through in house damage wiring at load side.Victim while

working her house ,she came in contact with internal private wiring of her premises and got

Electrocuted.

CEI Report is awaited

Consumer was informed to

check out the proper house

wiring of his premises

No

122 HMT Jesingpur

Chauhan Ramsinh

Movatsinh,Village

helper

NFH Dept 12.10.12 Bhiloda-2 s/dn Bhiloda

Victim has climbed on dead 11 kV line of Mehru JGY feeder, which was having two spans. He has

climbed on second and last pole of this line for removing 11 kv pin insulator. While he tested the

power supply by back palm of right hand, group of birds which were sit on tapping pole, fly away due

to which top conductor vibrated & momentary current passed to right hand back palm. It is reported

that victim was not fallen from pole. There was no any serious injury except burns on palm of right

hand & chest. He is already discharged from hospital on same day.

CEI Report is awaited

Dead spans removed

immediately. Warning memo

issued to victim.

No

123 HMT VasnirelManjuben Surabhai

ZalaFH O/S 22.10.12 Choila Talod

The Victim was washing clothes in her premises and for that she used electric motor to lift water.After

washing clothes she forgot to switch off the switch first & By mistake she touched to the open live wire

of motor And electrocuted & She died after some medical treatment...

CEI Report is awaited

Consumer was informed to

check out the proper house

wiring of his premises

No

124 HMT ModasaAkramhusen K

JamadarFH O/S 20.10.12 Mod-Town Modasa

Victim was cleaning the top of truck cabin. Truck was parked under 11 kv line of college fdr. Victim'

head was came in to contact with 11 kv line.The distance is 15 ft between ground and

line(vertical).The cause of low distanc is earth filling due to digging of gutter & RCC road during last

year . there was no T.T. of college fdr.

CEI Report is awaited

Consumers were educated to

avoid direct or indirect contact

with the elecric line

No

125 HMT Savagadh

FH to Kiranbhai

manubhai palasva

& NFH

toTufanbhai

Rupsinhbhai

Dindor

FH & NFH O/S 2.11.12 Mehtapura Himatnagar

To release New Ind connection two nos pole required to erect for transformer centre.one pole was

erected by the gang while digging pit for second pole stone come in pit so location of pit changed

which was near to 11KV feeder line.pole was erected by the victim(Labour of contractor)in the pit.while

adjusting the pole in the pit, pole was tilted & touched/came in induction zone of nearby Dhandha

Urban live feeder conductor. So current might have passed through G.I. wire of the pole. The victim

holding pole for work got electric shock and died while other get electric shock but survived with minor

injury of burnt.

CEI Report is awaited

Explanation asked to concern

helper by

MSD/2352/dtd:.3.11.12 all the

line staff has been awared

accordingly.

No

126 HMT Hathikhant Na Muvada

Khant Bhailalbhai

Somabhai Age; 16

Years

NFH O/S 1.12.12 Bayad Talod

At the time of removing mobile charger from the plug at the same time pin insulator of do unit fired on

jgy village transformer & leakage current passed through earth to neutral wire to village consumer

installation.So that Victim got electrocuted & injured on right hand finger & also bottom side of leg.

CEI Report is awaited Necessary maintance done No

127 HMT Salal

Gavariya

Navganbhai

Rameshbhai 12

years old

NFH O/S 6.12.12 Salal Hmt

The incident occurred at market yard vali TC at vill. Salal,while making attemp of catching kite, victim

climbed up from said transformer & he any how unknowingly came into contact with HT bushing

through his hand and got electric shock .

CEI Report is awaited

Consumers were educated to

avoid direct or indirect contact

with the elecric line

No

128 HMT Nanasamera Owner -Suvera

Mukesh BabuFA(Cow) 17.12.12 Bhiloda-2 Bhiloda

Due to pin puncture 11 kv conductor of Galpur JGY fdr snapped.Meantime cow passing near that

conductor & came in contact with that wire & got electrocuted.

Due to pin puncture 11 kv

conductor of Galpur JGY fdr

snapped

As per CEA regulation 12

,periodically maintenance

should be done by field

office.

Yes,it is

compliedRestringing of conductor done No

129 HMT ZanzariSolanki Makanbhai

SomabhaiFH O/S 27.12.12 Choila Talod

A tractor was parked near by 11 kv line of fdr narsipurAg to pull out motor from bore and while raising

trolly by mistake of driver it came in contact with HT line victim got electrocuted & died.CEI Report is awaited

Consumers were educated to

avoid direct or indirect contact

with the elecric line

No

130 HMT Jaswantpura

Khant

Dineshkumar

Madhusingh

FH O/S 30.12.12 Bayad Talod

At the consumer premises due to body short of 3 ph motor of conveyer belt,leakage current passing

through the whole metal fabrication of conveyer belt. When victim touched the same fabrication he

was electrocuted.

CEI Report is awaitedConsumers were educated for

install ELCB in his premises.No

131 HMT Lei

Owner -Patel

Sureshbhai

Maganbhai

FA(Bullock) 15.2.13 Idar-T IdarDue to Heavy Cyclone & Rain Conductor broken. Meanwhile bullock came in Contact of Live LT

Conductor & got died.

Accident occurred due to touch

with the broken LT line live wire

As per CEA regulation 12

,periodically maintenance

should be done by field

office.

Yes,it is

rectifiedRestringing of conductor done No

132 HMT BayadAshiben Abdulbhai

MalparaFH O/S 25.3.13 Bayad Talod

While victim was connecting 1ph electric motor through 1 ph-2wire cable at one side male pin at plug

side & other at motor side.During such type of connection , victim came in contact with live part of

wire & got electroculated & met with fatal accident.

CEI Report is awaitedConsumers were educated for

install ELCB in his premises.No

133 HMT HimatpurOwner -Ninama

Jivaji MehajiFA(Cow) 15.2.13 Bhiloda-2 Bhiloda

Due to Heavy Cyclone & Rain pin insulator punctured & Conductor broken and fallen down on

ground. Meanwhile cow came in Contact of Live Conductor & got died.

Due to pin puncture ,live

conductor snapped on Cow.

As per CEA regulation 12

,periodically maintenance

should be done by field

office.

Yes,it is

rectifiedRestringing of conductor done No

134 MSH Khadalpur

Patel

Mahendrabhai

Manilal Age 52

years

FH O/S 1.10.12 Visnagar-1 Visnagar

Ag connection of Shree Panchal Atmaram Madhavlal Ag Conn no 21104/00259/0 Khadalpur 52 HP

is located on 11 kv Chhogala feeder eminating from 66kv Umata s/s.This AG connection is given on

100 kva transformer center & 3 phase Power supply schedule is 23.15 to 9.15. AG premises (ordi) is

about 8to9 meter away from transformer center . On 1-10-2012 in morning at about 8.00 hrs Shri

Mahendrabhai Manilal Patel bore operator is to start the motor by starter for doing piyat in AG land.

By site inspection & investigation No body was present in AG premises (ordi) at the time of incident

but looking to the site Shri Mahendrabhai Manibhai Patel came in AG primises( Ordi) for reparing or

to start the starter. Window cover of starter is found open & black spots found on below side of starter

window cover it may be Shri Mahendrabhai Manibhai came in contact of Live wire & he got electric

shock& he fell down on the ground& thus Fatal electrical accident occured.By site verification incident

occured in party's Own premises by his mistake.

CEI Report is awaited

Consumers were educated to

use proper size of and proper

rating of starter(electric

appliances) in his premises

No

135 MSH MadhiPatel Veenitkumar

JyantibhaiFH O/S 1.10.12 Ladol Vijapur

Due to wrong sequence of phase and neutral in consumer's installation the phase is live in off

condition of switches hence while plugging of single phase water pump victim's hand came in contact

to plug pin and accident took place.

Phase wire was direct in the

switch board of the victim's

house due to this in both the

ON-OFF position of the swich

current was coming in the twi

pin plug

As per CEA Regulation 29

,consumer should get wiring

of house through licences

contractor .

Yes,it is

rectified

Consumer was informed to

check out the proper house

wiring of his premises

No

136 MSH Mehsana

Kantibhai

Shankarbhai

Rathod,Age 25

years

FH O/S21.09.12

(reporting late)Mehsana Highway Mehsana

Victim was working on iron structure at modhera circle for providing hording for advertisement & while

working on iron structure ,his back side touched to the live open LT conductor passing just 3 feet

away from the structure and got electric shock and met with the fatal accident. Information about the

accident was recieved from electrical inspector mehsana.

During the work of removal of

hording victim's body came in

contact with the electric line.

Not suggested

Maintain proper safe

clearance from the electric

line while working nearer to

the electric line

No

137 MSH Mehsana

Shokhaliben

Kalubhai Damor,

Age 46 years

FH O/S29.09.12

(reporting late)Mehsana Highway Mehsana

Victim might have gone for toilet on open ground of ST compound at modhera circle at where

consumer's armour cable having joints at 4 different places was lying open on the ground. While

passing through this area victim might came in contact with the live open joint and got electric shock

and dead on the spot. Information about the accident was recieved from the letter of Mehsana B

Division police station.

CEI Report is awaited

Consumer was informed to

insulate open joint of the

electric cable and use only

standard guage of electric

wires only.

No

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

138 MSH AlusanaMukeshji Ganpatji

ThakorFH O/S 8.10.12 Kadi R-1 Kadi

At corridor of his house, refrigerator was there. He has put his mobile for charging on refrigerator.

Victim tried to collect his mobile from there, and due to any leakage current on refrigerator, he got

electroculated. His family member brought him to nearer hospital for treatment, and there he got died.

So, the reason for the death of Victim is due to leakage current came from faulty refrigerator and also

there were no any protection for earth leakage current.

CEI Report is awaitedConsumer was educated to

install ELCB in his premises.No

139 MSH Pindharrupa

Goswami

Bharatpuri

Ishvarpuri

FH O/S 7.10.12 Dhinoj Mehsana

Victim kept his camel cart below the neem tree nearer to Gokulnagar Society at Pinddharpura. An 11

KV Pinddharpura Ag feeder was passing just 4-5 feet away from this neem tree. Victim climbed on the

neem tree for cutting the fresh neem tree branches. After cutting on of the fresh neem tree branch,

victim had holded on end of the freshly cut neem tree branch and the other leafy end of the branch

came in contact with the 11 KV line, causing a path for flow of leakage current. So victim got an

electric shock and died.

Victim climbed on tree for

cutting the fresh neem tree

branches. During victim had

holded on end of the freshly cut

neem tree branch and the other

leafy end of the branch came in

contact with the 11 KV

line.Accident occurred due to

lack of knowledge of Victim

Accident occurred due to

lack of knowledge of Victim

Branches of the neem tree

was cut down in order to

maintain proper clearance

between tree branches and

electric line

No

140 MSH DenapAlpeshji Chehraji

ThakorFH O/S

26.09.12(repor

ting late)Visnagar-1 Visnagar

As per the statement of victim's father, his son came from the school on dtd. 26/09/2012 about 15:00

hrs. and touched the switch of light and he fell down on the floor and died. During investigation, an

open switch board was found in victim's house. Also there was no any leakage current and any sign of

burning spot on switch board or on wall of the house. So it was the suspicious case for electrical

accident and we can only conclude the cause of the death after recieving the PM report. On reciept of

the PM report on dtd. 10/10/2012, it was concluded that the death has occured due to cardiac arrest

due to electric shock.

CEI Report is awaitedConsumers were educated for

install ELCB in his premises.No

141 MSH NarsinhpuraSenma Mehulbhai

ChandubhaiFH O/S 12.11.12 Kadi R-1 Kadi

Victim's brother was sprinkling water on wall of his shed and the victim was near water tank. The

water pipe from electric motor came out and the motor failed down to wet land near water tank. The

insulation of phase wire connected to shocket of motor was cut and water was spread on motor and

to earth. Victim tried to reinstall the water pipe connection, and due to leakage current, he got shock.

Then victim was transferred to Hospital where he got died. Morever, ON-OFF switch of switch board

to which the plug of motor was connected was not working properly, means even in OFF position,

phase was ON.

CEI Report is awaited

Consumer was educated to

use only standrd electric wire

and standard elctric switch

board with ELCB installed in

the premises.

No

142 MSH MehsanaThakor Motiji

MadhajiFH O/S 23.11.12 Vadnagar Juna Aspa

On dt 23-11-2012 D.E Kheralu visited the place of Fatal accident occurred to Shri Motiji Madhaji

Thakor at Juna Aspa village. A single phase lighting connection was existing in r/oShri Somaji

Bhikhaji Thakor conn no 22612/00342/8 given by 2 core 2.5mm2 yellow colour pvc cable . A house of

Shri Somaji Bhikhaji Thakor & a house of Shri Motiji Madhaji Thakor is located near to each other .

There is no Lighting connection in Motiji Madhaji Thakor's house. A illegal connection was taken from

Somaji BhikhajiThakor's house by flexible wire approximate 10 mtr. 12 watt lamp was connected. The

flexible wire was jointed& broken & comes from the door in his house. It is asummed that Shri Motiji

Madhaji open the door & by mistake he touch the broken flexible wire & he got the electric shock & fell

down on ground .There is no any Eye wittness at the time of accident .Near by people Shri Jehaji

Dhulaji Thakor might have seen the accident & they made a notice of it then theycame & call 108 &

brought him at Vadnagar Civil hospital & Doctor has declared he is died & sends the dead body for

Post mortem. During visiting the place of accident panchnama done. For An illlegal connection given

by Somaji Bhikaji Thakor a pannelty bill isssued to him.We have checked the UGVCL installation with

line tester that there is no any leakage current on MMB, or on wall at consumer premises. There is no

any spot of burns at consumer premises or on door

CEI Report is awaited

Consumers were educated to

use only proper guage wire of

standard

No

143 MSH MehsanaKum. Vaibhaviben

Rameshbhai DarjiNFH O/S

25.12.12 (late

reporting ) Mehsana IND Mehsana

A 200 KVA Distribution transformer is existing nearer the wall between Ratnadeep and Bhairavkripa

society. The height of the wall is up to the DO fuse link of the transformer centre. Hence the distance

between the Do fuse link and the wall is approximately 3.5 feet. On Dtd. 25.12.2012 at 16:25 pm,Kum.

Vaibhaiben R Darji returning from Ratnadeep Society, she climbed on Said Society's wall & crosses

towards Bhairavkrupa Society and at that time she touches 11 KV live wire from DO fuse to

transformer bushing & got electric shock & fallen down on ground.

CEI Report is awaited

On the top of the wall broken

glass pieses are fixed with

cement by contractor of

Ratnadeep society so that

now onwards nobody climb up

on said wall. As well as Do

fuse direction change from

wall side to open space side

on Dtd.10.01.2013

No

144 MSH Khanusa

Senma Jasubhai

Punjabhai,worker

of contractor's

gang

NFH O/S 22.01.13 Vijapur Vijapur

On Dt;- 22/01/13 line stringing work was arranged. On this day the 11 kv chadasana feeder 3-phase

power supply time started from 12:30 to 22:30. So, line clear by shree D.B. Tadvi has been taken of

this feeder at 9.55 a.m , earthing at work place on feeder has carried out & started the work on this

feeder of removing old line . But victim Shree senma Jasubhai Punjabhai, worker of contractor's gang

climbed on pole of 11 kv Vihar feeder , location no 11, having 3- phase supply starting from 3:45 to

13:45 p.m So, non fatal electrical occured to the victim at 10:35A.M. with heavy flash over occure &

one jumper on sub station gantry switch was burned.

CEI Report is awaited

Conform the line must be

dead before executing any

work in the electric line

No

145 MSH Vasai

Owner -Rabari

Jivanbhai

Mankabhai

FA(Cow) 15.02.13 Gozariya Vijapur

A single phase service line with GI wire giving power supply to school was short circuited. Therefore a

leakage current passing through GI wire, which was touched the LT line & girder pole. A cow was

passing near girder pole and due to leakage current got electrocuted and died.

Due to leakage current passes

from Girder pole due to

damage of insulation of single

phase service line .

As per CEA regulation 12

,periodically maintenance

should be done by field

office.

Yes,it is

rectified

Deteriorated service wire has

been replaced by by new

service cable with new GI

Wire and binding

No

146 MSH Vajapur

Thakor Dineshbhai

Mafaji,Electrical

Assistant

NFH Dept 25.02.13 Satlasana Visnagar

Shri D. M. Thakor during jumpering work on new 11 kv line of Mumanvas Ag feeder for releasing

new Ag connection at Vajapur Ag area .During that time victim came in 11 kv power induction zone

and he fall down on ground.

During investigation actually matter is found that,they have cut off the AB switch of wrong section

tape line. So power is continue from existing line and D. M. Thakor had not done proper earthing at

working place and not use any safety equipments. Hence the non fatal accident is occurred to Shri

D.M. Thakor during jumpering work.

CEI Report is awaited

Line staff were educated to

conform the line must be

made off before starting of

work. Also proper earthing

must be done on both the side

of the section in which work

has to be dong

No

147 MSH SurajThakor Rinkiben

RajujiFH O/S 18.02.13 Kadi-2 Kadi

Detail report will follow ,but as per primary report; victim was hanging the clothes on metal wire, which

was tide between the LT pole & 'chabutara' appr. 15 to 20 feet away from LT pole and got electric

shock. Reason may be the leakage current, which may be comes from the channel wire having weak

insulation tide on the same LT pole to earth wire and from earth wire to metal wire, on which the victim

was working.

CEI Report is awaited

Sharapanch of gram

panchayat was instructed to

caary out the mainenance and

to replace the electric wire of

the strret light fixture. Also,

Consumer was wducated to

not tide the metal wire with the

electric pole or nearer to

electric pole.

No

148 MSH Tintodan

Prafulbhai

Bharatbhai

Kher,Village Helper

Tintodan

NFH Dept 11.01.13 Kukarwada VijapurWhen victim was climbed on psc pole for attending the 1Q Lighting complain at that time victim

came in contact with live part of the cable & get shocked.CEI Report is awaited

Line staff ws educted to use

safety equipments while

working on the electric line

also they were instructed to

make the line dead before

starting of the work.

No

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

149 MSH DagawadiyaSohanbhai

Martabhai DamorFH O/S 24.01.13 Kukarwada Vijapur

on dtd. 23.1.13 , in the farm of Chaudhary Jashubhai D., Vill. Dagawadia, Ta:Vijapur, Di: Mehsana, a

victim was stacking down the column pipe in the bore, completing the work,the roller (Charkhi) of

boring apparatus touch the 11 kv Umiya feeder. Due to this a victim Damor Sohanbhai Martabhai was

operate the appratus came in contact with 11 kv line and current passes through lower part of

stomach and admitted to hospital at Visnagar. the incident occured on dtd 23.1.13 & police inform us

on dtd.24.1.13 at 5.00 P.M.

CEI Report is awaited

Consumers was educated to

avoid any work below the

electric line and carry out their

work with safe clearance from

the electric line

No

150 MSH BiliyaThakor Bharatji

Mahendraji NFH O/S 8.03.13 Ladol Vijapur

An eight year old, victim climbed on transformer centre of telephone exchange and hold jumper on

bushing side &spark shown on channel of support & jumper ,got electrocuted ,met with non fatal

accident.

CEI Report is awaited

people were educated to avoid

direct or indirect contact with

electric line

No

151 MSH Badarpur

Vaghari

Sureshbhai

Motibhai

FH O/S 20.03.13 Vadanagar Visangar

Victim self climbed on PSC Shackle pole ( near Rajebhai Ibrahimbhai Dharkhad farm)

of 11 KVBadarpur jgy feeder emanating from 66 KV Vadnagar Sub Station. He touched to

jumper of live Line & got shocked. CEI Report is awaited

Consumers were educated to

avoid direct or indirect contact

with the elecric line

No

152 MSH HarijThakor Anilbhai

ManajiFH O/S 20.03.13 Harij Patan

While carrying out masonry work of new house of Desai Hargovanbhai Bababhai, victim tried to

remove cotton string (used for Kadiya kam) lying on the conductor of 11kv Dantarvada Ag feeder.

While doing so he came in contact with live conductor and got electrocuted & met with fatal accident.

CEI Report is awaited

Consumer was awared to

maintain safe clearance from

the electric line and avoid

direct or indirect contact with

the electric line

No

153 PLN Kundi

Damor Sankarbhai

Khatarabhai-V/S

Helper

NFH Dept 12.10.12 Dhanera-2 Deesa-2While victim was attending complain of consumer ,he climbed on pole without switch off the power &

came in to the contact of live 3-phase 4-wire LT Line conductor and got electric shock.C.E.I report is awaited

Memo issue vide letter no-

UGVCL/Dhanera-

2/Tech/accident/8373/15-10-

2012 dtd, and required action

under process

No

154 PLN AT-Makadchampa

owner : Parmar

Jagabhai

Galbabhai

FA(Buffalo) 13-10-2012 AMBAJI PALANPUR-2

At Makadchampa, Agriculture consumer sri Parmar Mohanbhai Panabhai has 5 hp conection. & Ag

consumer no is 71030502714. His motor is short. so Return leakage current flow into 3 phase 4 wire

LT to Transformer from 3 ph elecric motor. He buffalow is contact with transformer Earthing (GI) wire

and got electocuted.

C.E.I report is awaited Use ISI Mark motor 5000

155 PLN Sidhpur.

Prajapati Gopalbhai

Kantilal-42 years &

Prajapati

Jyotsnaben

Gopalbhai-40 years

FH O/S 3.11.12 Sidhpur-City Sidhpur

smt. Jyotsnaben gopalbhai prajapati ( outsider) aged approx. 40 years,at 27 of k.b. complex society

b/h vishwas hotel, sidhpur highway was carrying approx. 22 feet long iron box pipe for some work.

While she was lifting/carrying the iron box pipe near compound wall of height approx. Five feet of her

residence, due to approx 22 feet length of that pipe, one side end of the iron box pipe was out of the

wall whose top side touched to 11kv ankvi ag. Feeder, which is passing out side the compound wall

approx. Five feet away from 11kv line and ground clearance of that 11kv line is approx. 19 feet.

Electric current passed through the iron box pipe & she got electoculated. Her husband shri

gopalbhai kantilal prajapati (outsider) aged about 42 years old rushed to save her & he also got

electoculated. Thus couple got electoculated & died on the spot. It is found that there was tripping on

11kv ag. Ankvi feeder at 8:42 a.m. & spark spots were found on the top end of the iron box pipe.

C.E.I report is awaited

Consumer was awared to

maintain safe clearance from

the electric line and avoid

direct or indirect contact with

the electric line

No

156 PLN Delwada

Thakor Bhikhiben

Ganeshji-27 years

old

FH O/S 6.11.12 Deodar-1 Radhanpur A Fatal electrical accident occurred to victim,while victim came with contact of broken LT line

conductor,which conductor found broken and follown on ground and got electric shock.C.E.I report is awaited Maintenance work carried out No

Sr

no.Circle

Location of

accident

Details of

victim/owner

Type of

Accident

FH/NFH /FA

Dept

/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI

Remedies suggested by CEI /

EI/ AEI in various cases

Whether the

remedy

suggested is

complied

Action taken to avoid

recurrence of such Accident.Compensation Paid

1 2 9 3 4 5 7 8 11

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12TO MARCH-13)

Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred

157 PLN Maktupur

Makwana Dipak

kumar

Parshottambhai-42

years old

NFH O/S 2.11.12 Unjha-Rural Sidhpur

A Non Fatal electrical accident occurred to outsider,while victim Repairing of Street light in

sardarnagar society at that time he was came with contact of LT line Phase wire conductor and fall

down on ground and got electric shock.

C.E.I report is awaited

Consumers were educated to

avoid direct or indirect contact

with the elecric line

No

158 PLN Radhanpur

Shivabhai

Ramsingbhai

Nirashrit-16 years

old

FH O/S 17.11.12 Radhanpur Radhanpur

Victim was climbed on the village water tank and was going to pull water through bucket and rope

from village water tank. Neutral conductor among the single phase two wire LT line passing over said

water tank was snapped. The victim came in contact with the snapped conductor and got

electrocuted.

C.E.I report is awaited Maintenance work carried out No

159 PLN Yavarpura

Owner -Shri

Harijan Bheraji

Kavaji

FA(Buffalo) 5.12.12 Dhanera-1 Deesa-2A Fatal accident occurred to Buffalo due to Snnapping of 11 kv Jadiyali feeder conductor on buffalo &

she came with contact of broken conductor and got electric shock.C.E.I report is awaited Maintenance work carried out No

160 PLN Manka

SHRIMALI

DIPAKKUMAR

RAMCHANDBHAI-

Helper s/dn gang

NFH Dept 2.01.13 Jalotara Palanpur-2

victim while climbed on T/Cstructure for getting the details of existing transformer by reading name

plate,which is fixed on the x'mer body. Mean while he touched with T/C's HT side bushing's stud &

got shocked & met with non fatal accident.

C.E.I report is awaited

Issue warning memo to

supervisor & victim due to not

follow of safety measure vide

letter no-

UGVCL/Jalotra/accident/est/9

68 & 970 dt-25-3-2013.

No

161 PLN Village-Dantiwada

owner of Buffalow :

Rabari Hamirbhai

Zalabhai

FA(Buffalo) 7.02.13 Dantiwada PALANPUR-1

A buffallow of Rabari Hamirbhai Zalabhai of Vill-Dantiwada came in to Contact with loose Stay wire  of

AB Swich(Loc No-86/10) of 11 KV Dantiwada JGY Feeder whose stay insulator broken & Stay wire

touch to live Jumper of said AB Switch, So 11 KV Line current passed through Stay wire to Buffallow

&  electrocuted and met with Fatal Electrical Accident.

C.E.I report is awaited Maintenance work carried out 5000

162 PLN Lakhani

Kanbi Ambabhai

Ramabhai-38 years

old

FH O/S

20.08.12

(reporting date

22.03.13)

Lakhani Deesa-2

On dated 28-8-2012 at 1.00 PM victim got electrical accident due to tough his finger on the top of fuse

at the time of fitting the fuse on fuse board in his own premises(Ag connection electric room) & got

died on the spot at accident location.

C.E.I report is awaitedConsumer was educated to

install ELCB in his premises.No

163 SBT ChankhedaManish Muljibhai

Jadav, Age:25 YrsFH O/S 14.10.12 Chankheda Gandhinagar

A boradband cable(GTPL) was passing over the HT line (11 KV IOC feeder) but the distance between

high tension line and boradband cable was very less (it was just hanging over high tension line). So

when the boradband cable came in contact with HT line and at the time 11 KV supply was passed

through the broadband cable to the consumer premises.At that time victim came in contact with the

computer and got shocked.

C.E.I report is awaited

Instruction given to all line

staff to use safety tools and

tackles and disconnect power

supply before attend complain

to avoid accident

No

164 SBT Akru

Mr.Pravinbhai

Valabhai Katara,

Helper (v/s)

FH Dept 24.10.12 Dhandhuka Bavla

The victim was working on LT pole to rectify Lighting complain of Mr.Laljibhai Bhojabhai Mundhva and

while working, came in to the contact of live LT Line conductor and got electric shock & he fell down

on the ground from the pole and met with fatal accident

C.E.I report is awaitedNew stay and earthing

providedNo

165 SBT KERALA

owner -

Govindbhai

Dhunabhai

Bharvad

FA(Buffalo)

11.09.12 AT

10:00 AM

(Late reporting)

Bavla(ind) Bopal

Due to deteriorated and melted insulation of twin core service wire of single phase connection of shri

c.d.patel at nursery of forest deptt., phase-neutral wire get short ckted so leakage current passed

through neutral wire to earthing wire of t/c. A buffalo passing nearby t/c came in contact with leakage

current and got electrocuted.C.E.I report is awaited Maintenance work carried out No

166 SBT Uvarsad

FH to Shankarbhai

Prabhabhai

Marvadi Apprx,

Age:20 Yrs, Nfh to

Kishanbhai

Chatrabhai

Marvadi , Apprx,

Age:18 Yrs

FH & NFH O/S 23.11.12 Adalaj Gandhinagar

At the time of preparation of decorative gate at Karnavati Dental colledge, the victim , Kishanbhai C.

Marvadi touch with live conductor of 11 KV Preksha feeder and got electric shock and his right hand

burns and hospitalised. And other victim Shri Shankarbhai P. Marvadi standing for support of iron pole

also got electrucution and died. Distance from 11 kv line to ground is 17.9 mtr.

C.E.I report is awaited90% channel cable wire

removedNo

167 SBT Nana ChilodaAnil Sogaji Thakor

Age:-18yearsFH O/S 24.12.12 Chiloda-1 Gandhinagar

Truck (dumpher) which is fully filled up with send, driver park his dumper to unload the send exectaly

under the 11 kv aeronetic feeder live line, and also at the location 66 kv line is crossing over 11kv

aeronetic feeder. While victim try to stand up on the fully send filled dumper, he come in contact with

live 11kv aeronetic feeder wire and due to this electrical accident occured.

C.E.I report is awaited

Consumers were educated to

avoid direct or indirect contact

with the elecric line

No

168 SBT Giramtha

Owner -Buffalo of

Kokilaben B

Parmar

F A(Buffalo) 26.12.12 Bareja SabarmatiNeutral wire of single phase two wire LT line broken (due to deteritoted condition) in front of house of

Rajuhai and Kokilaben parmar and buffalo came in contact with live wire and got electrocuted.C.E.I report is awaited

periocally service wire at

consumer premises &

replaced it if required

No

169 SBT HarsoliBaldevbhai

Bhikhabhai rabariNFH O/S 15.01.13 , Dehgam-R Gandhinagar

On dt 15.01.13, late evening, victim was standing on terrace for flying kite .The 22 KV Vasna Rathod

JGY feeder is passing nearbt it.Victim came in contact with live conductor by operating some means

of object & got shocked

C.E.I report is awaited

Consumers were educated to

avoid direct or indirect contact

with the elecric line

No

170 SBT Kalol(East)

Shri

Mukundchandra

Tulsidas Rathod,

Helper VS

FH Dept 19.01.13 Kalol-1 Kalol

While climbing upon the pole for Disconnection of lighting connection ,he came in contact with iron

wire surround with TV channel,cable wire passing through this pole.on investigation it was found that

the return current came from faulty internal wiring of lighting connection of shri V.M. Chauhan & got

shocked.

C.E.I report is awaited

All the channel cable wires

are removed from UGVCL

network under Kalol

D.O.juridiction

No

171 SBT Moti Bhoyan

Shri Ajitsinh

Jasubhai

Darbar(Helper of K-

1 S/D)35 year

NFH Dept 31.01.13 Santej Kalol

The victim was working on the 11 kv Arvind Ind.feeder of Santej S/dn during mass maintenance

program.During this work victim came in contact with leakage current & met with NFH accident. The

leakege current passing through transformer of temporory connection of M/S Arvind LTD due to faulty

change over switch of D G Set of this connection.

C.E.I report is awaited

Approval of DG Set is carried

out as per letter

no.UGVCL/KLD/TECH/Acc/2

388dated 1.3.2013

No

172 SBT Thuleta

(1) Kanchanben

Prabhubhai K Patel

age 30 years (2)

Babo Prahubhai K

Patel age 3years

NFH O/S 5.2.13 Vgm-R SBTDue to Snapping of conductor(AB Cable) at village T/C Thuleta on victicms passing on road and get in

contact with live wireC.E.I report is awaited

LT AB CABLE work is

providedNo

173 SBT Vasna RathodLilaben

Lalsangbhai DamorFH O/S 22.2.13 Dehgam-R Gandhinagar

In the morning @9 to 9-30,the victim went on roof of kacha house to call her husband ,who was

working in the field of Prajapati Kodarbhai Jethabhai,The 22 kv line of Vatva feeder was passing from

the angle of the the rooftop,the victim came into contact with 22 kv conductor and

electrocuted.Victims got burns on left hand and body parts.

C.E.I report is awaited

party has applied for line

shifting & estimate paid &

work is also completed to

avoid the accident

No

174 SBT PansarShri Babubhai

Punjabhai RavarNFH O/S 12.03.13 Kalol-2 Kalol

Victim self climbed on village t/c structure & touched live conductor of D.o. unit & got electrocuted &

fell down ,met with nonfatal accident. C.E.I report is awaited

Consumers were educated to

avoid direct or indirect contact

with the elecric line

No

175 SBT Bhimtalav

Owner -Chauhan

Jerambhai

Talsibhai

FA(Buffalo) 20.03.13 Dhandhuka Bavla

Suddenly buffallo run and passed between DP centre so touched with stay wire. Due to snatching,

corrosive stay came out with neutral earth wire of T/C came out from ground which touched to

buffallo ,got electrocuted and died.

C.E.I report is awaitedMaintenance carried and

deteriorated LT wire replacedNo

176 SBT Dhendhu

Owner -Shri

Thakor Ranchhodji

Khodaji

FA ( Calf) 12.03.13 Nardipur KalolDue to unknown reason, hay stock lying under 11 KV line, got fired,due to heat & flame of said fire,A

calf tied near there,died. C.E.I report is awaited LT Cable provided No

Within 50% of

stipulated time

Within stipulated

time

Upto double the

stipulated time

More than double

the stipulated time

1 2 3 4 5 6 7 8 9 10

A(i) 85 179665 179750 96799 81128 201 1600 179728 22

A(ii) 1 32823 32824 18857 13808 133 26 32824 0

A(iii) 13 12789 12802 7732 4787 4 277 12800 2

B(i) 5 5587 5592 4212 1308 2 70 5592 0

B(ii) 2 4922 4924 2341 2574 0 9 4924 0

C(i) 0 14980 14980 9419 5545 8 8 14980 0

C(ii) 1 6367 6368 3933 2383 0 51 6367 1

D(i) 0 10753 10753 6785 3952 0 16 10753 0

D(ii) 0 2405 2405 1468 932 0 5 2405 0

E(i) 14 6745 6759 3183 3299 9 263 6754 5

E(ii) 0 3358 3358 2191 1096 0 68 3355 3

F(i) 0 1668 1668 993 667 0 8 1668 0

F(ii) 2 1668 1670 995 667 0 8 1670 0

F(iii) 1 2757 2758 2095 660 0 3 2758 0

F(iv) 0 7996 7996 4405 3582 0 9 7996 0

G 0 1660 1660 1037 612 0 11 1660 0

H 6 19320 19326 8362 10645 9 302 19318 8

Total 130 315463 315593 174807 137645 366 2734 315552 41

Complaints

received during

the Year

Total complaints

YEAR 2012-13 ( APRIL-12 TO MARCH-13)

Balance

complaints to be

redressed (4) - (9)

Uttar Gujarat Vij Company Ltd

Performa SoP 003 B:

APPENDIX - B

REGISTER FOR COMPILING THE COMPLAINTS CLASSIFICATIONWISE

In stipulated time Beyond stipulated time

No.of complaints redressed during the month

Total (5) to

(8)

Classification

Pending

complaintof

previous

Month

Sr. No.Actons or steps carried out by distribution licensee towards

public awareness in the quarter

Likely number of

consumers

influenced

Details about media

1 2 3

1 Display board of SOP at circle, Division & S/Dn 345898 Notice Board

2 Display board of Name of information officers under RTI Act 2005 at

Circle,Division,Sub- division offices. 199766 Notice Board

3Consumer care centers

334883Verbal & Notice Board

at CCC

4 Advertisement through Daily News papers 1801100 Daily News papers

5Pamphlets distributed among public

261399 Pamphlets

6Advertisement through slide in TV / Banners

92391 T V Channels

7 On Uttar Gujarat Vij Company Ltd Web site 210636 Internet

8 Through Regular Energy Bill 6646895 Energy Bill

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12 TO MARCH-13)

Performa SoP 004

Sr. No. MonthDate of meeting

conducted

No. of complaints

registered at the meeting

No. of complaints

pending at the end of

the meeting

10.04.2012 17 7

13.04.2012 9 2

17.04.2012 7 1

21.04.2012 8 4

15.05.2012 13 13

16.05.2012 9 9

29.05.2012 8 8

30.05.2012 8 8

14.06.2012 5 0

16.06.2012 13 4

28.06.2012 6 1

30.06.2012 4 1

10.07.2012 5 1

13.07.2012 2 0

24.07.2012 6 2

26.07.2012 2 0

09.08.2012 6 0

16.08.2012 13 2

23.08.2012 11 1

31.08.2012 7 1

11.09.2012 5 1

18.09.2012 9 0

25.09.2012 4 0

29.09.2012 4 0

10.10.2012 2 1

12.10.2012 2 0

03.11.2012 3 0

12.11.2012 2 0

22.11.2012 4 0

05.12.2012 3 1

11.12.2012 5 0

18.12.2012 4 1

31.12.2012 7 0

17.01.2013 3 0

24.01.2013 4 2

30.01.2013 6 2

16.02.2013 5 2

21.02.2013 4 1

26.02.2013 5 0

08.03.2013 9 2

22.03.2013 3 0

26.03.2013 8 3

NB.: Total Sittings in a Year - 42 Nos.

Uttar Gujarat Vij Company Ltd

YEAR 2012-13( APRIL-12 TO MARCH-13)

Performa SoP 005 B: Action taken report by the Redressal Committee

March'13

1 Apr-12

2 May'12

3 June'12

12

9

10

11

November'12

December'12

January'13

February'13

4

5

6

7

8

August'12

September'12

October'12

July'12

Sr.

No.Class

No. of existing Distribution

transformer at the start of the

quarter / year

01.04.2012

No.of Distribution

transformers added

during the quarter / year

(April-12 to March-13)

Tota number of

Distribution

transformers As on

30.03.2013

Total number of

Distribution

tranformer failed

(Three months)

% failure rate of

Distribution

transformer

A B C=A+B D H= (D) * 100/C

1 11KV 131983 16796 148779 10083 6.78

2 22KV 532 -141 391 130 33.25

143301 16655 149170 10213 6.85

Uttar Gujarat Vij Company Ltd

Performa SOP 006 : Failure of Distribution Transformer.

YEAR 2012-13( APRIL-12 TO MARCH-13)

Total

-1 -2 -3 -4 -5 -6

Sample Size % age compliance

(Numbers) (6) = (5)*100/(3)

LT consumers  2%

1 Domestic 757706   2% 10923 1.44

2 Commercial 83435   2% 374 0.45

3 Industrial 14609   2% 65 0.44

4 Agricultural 138717   2% 2492 1.80

5 Public water works 4501   2% 28 0.62

HT consumers

6 HT Industrial 504   2% 1 0.20

Uttar Gujarat Vij Company Ltd

YEAR 2012-13( APRIL-12 TO MARCH-13)

Performa SoP 008: Sample Test result for Neutral Voltage

Compliance Sample Test Report for Neutral Voltage

Sr. No Category of consumersStandard specified

in regulation

Deviation of results from

the sample test (Numbers)

1 2 3 4 5

% age compliance

% age compliance

(5) = (4)*100/(2)

Low Voltage 718073 +6% to -6% 2457 0.34

High Voltage 782 +6% to -9% 3 0.38

Extra High Voltage 9 +10% to -10% 0 0

Uttar Gujarat Vij Company Ltd

YEAR 2012-13( APRIL-12 TO MARCH-13)

Performa 09: Compliance Sample Test Report for voltage variations

Voltage LevelSample Size

(numbers)

Limit or

prescribed

standard

Deviation of results

from the sample test

(Numbers)

-1 -2 -3 -4 -5 -6

Limit or

standard

prescribed

Deviation

of results

from the

%age

compliance

(6) =

(5)*100/(3)

1 LT consumers 22542 3.50% 310 1.38

2 HT consumers 148 3.00% 3 2.03

3 EHT consumers 7 3.00% 0 0

Uttar Gujarat Vij Company Limted

Performa SoP 010: Sample Test result for Harmonics

Compliance Sample Test Report for Harmonics

Sr. NoCategory of

consumers

Sample

size

(Numbers)

YEAR 2012-13 ( APRIL-12 TO MARCH-13)

Sr.

NoMonth

Ni - Number of

Customers for each

sustained

interruptions (in

numbers)

NT - Total No of

customers served

(in Numbers)

CI = ∑ NiSAIFI = ∑Ni/Nt

(Monthly SAIFI)

1 2 3 4 5 6= 5 / 4

1 Apr-12 217540 352707 745134 2.11

2 May-12 232421 355907 784509 2.20

3 Jun-12 284242 354833 1772779 5.00

4 Jul-12 298263 360644 1763039 4.89

5 Aug-12 297879 363015 1651669 4.55

6 Sep-12 298072 363554 1633383 4.49

7 Oct-12 258438 363554 1097596 3.02

8 Nov-12 272976 363669 1099093 3.02

9 Dec-12 244862 366363 1008605 2.75

10 Jan-13 260722 366794 1037755 2.83

11 Feb-13 276197 368458 1069875 2.90

12 Mar-13 269415 369221 958278 2.60

Sr.

NoMonth

Ri =

Restoration Time for

each sustained

interruption event

(in hours)

Ni - Number of

interrupted

Customers for each

sustained

interruption event

(in numbers)

Ri* Ni -

Total customer

interrution Duration

NT - Total No of

customers served

(in Numbers)

Customer Intt.

Duration CMI =

∑Ri*Ni

SAIDI =

∑Ri*Ni/Nt

(Monthly

SAIDI)

1 2 3 4 5 = 3 * 4 6 7 8= 7 / 6

1 Apr-12 8332:10 217540 352707 1490225:54 4:13

2 May-12 8081:44 232421 355907 1487178:11 4:10

3 Jun-12 14285:12 284242 354833 2863150:57 8:04

4 Jul-12 16394:15 298263 360644 3258903:50 9:02

5 Aug-12 13966:55 297879 363015 2832593:17 7:48

6 Sep-12 14028:32 298072 363554 2498967:20 6:52

7 Oct-12 9443:07 258438 363554 1837560:39 5:03

8 Nov-12 9521:13 272976 363669 1876359:08 5:09

9 Dec-12 10718:53 244862 366363 2369787:09 6:28

10 Jan-13 9246:17 260722 366794 1938151:40 5:17

11 Feb-13 10642:54 276197 368458 2105518:59 5:42

12 Mar-13 12070:37 269415 369221 2209809:45 5:59

Sr.

NoMonth

IMi =

Number of

Momentary

interruptions for the

month

(in numbers)

Nmi =

Total no of

customers for each

momentary

interruptions

(in numbers)

Imi =Nmi

Number of customer

Mementary

interruptions

(in numbers)

Nt -

Total no of customers

served

(in numbers)

Customer Intt.

∑Imi*Nmi

MAIFI=

∑Imi*Nmi/

Nt

1 2 3 4 5 6 = 3 * 4 7 8= 7 / 6

1 Apr-12 7907 308548 352707 1328916 3.77

2 May-12 7481 300023 355907 1168681 3.28

3 Jun-12 10440 275132 354833 1733456 4.89

4 Jul-12 12059 327131 360644 2118454 5.87

5 Aug-12 12997 333478 363015 2122334 5.85

6 Sep-12 13017 338279 363554 2183824 6.01

7 Oct-12 9846 334852 363554 1587325 4.37

8 Nov-12 8150 333504 363669 1773439 4.88

9 Dec-12 7950 306888 366363 1422617 3.88

10 Jan-13 7412 321364 366794 1340693 3.66

11 Feb-13 7363 331658 368458 1380167 3.75

12 Mar-13 7711 339199 369221 1338108 3.62

Uttar Gujarat Vij Company Ltd YEAR 2012-13( APRIL-12 TO MARCH-13)

SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for AG. Dominant category

SoP 011 - B : System Average Interrruption Duration Index (SAIDI) for AG. Dominant category

SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for AG. Dominant category

Sr.

NoMonth

Ni - Number of

Customers for

each sustained

interruptions (in

numbers)

NT - Total No of

customers

served

(in Numbers)

CI = ∑ Ni

SAIFI =

∑Ni/Nt

(Monthly

SAIFI)

1 2 3 4 5 6= 5 / 4

1 Apr-12 1250303 1651263 3051239 1.85

2 May-12 1275762 1651155 2683933 1.63

3 Jun-12 1530394 1654296 7126866 4.31

4 Jul-12 1474263 1652334 7701226 4.66

5 Aug-12 1417874 1653528 5865305 3.55

6 Sep-12 1452872 1660899 6476368 3.90

7 Oct-12 1267508 1660899 3933156 2.37

8 Nov-12 1120129 1663951 3235577 1.94

9 Dec-12 1084425 1664564 2662340 1.60

10 Jan-13 1263962 1665235 6258057 3.76

11 Feb-13 1310246 1667422 3889687 2.33

12 Mar-13 1171242 1668144 4955938 2.97

Sr.

NoMonth

Ri =

Restoration Time

for each

sustained

interruption

event

(in hours)

Ni - Number of

interrupted

Customers for

each sustained

interruption

event

(in numbers)

Ri* Ni -

Total customer

interrution

Duration

NT - Total

No of

customers

served

(in

Numbers)

Customer Intt.

Duration CMI =

∑Ri*Ni

SAIDI =

∑Ri*Ni/Nt

(Monthly

SAIDI)

1 2 3 4 5 = 3 * 4 6 7 8= 7 / 6

1 Apr-12 2653:29 1250303 1651263 6669620:53 4:02

2 May-12 2066:03 1275762 1651155 3862046:39 2:20

3 Jun-12 3768:39 1530394 1654296 10116321:14 6:06

4 Jul-12 3604:03 1474263 1652334 9445183:41 5:42

5 Aug-12 4282:02 1417874 1653528 5399164:00 3:15

6 Sep-12 2673:44 1452872 1660899 6957669:29 4:11

7 Oct-12 2420:23 1267508 1660899 6053698:31 3:38

8 Nov-12 1727:37 1120129 1663951 4095261:06 2:27

9 Dec-12 1503:29 1084425 1664564 3346737:16 2:00

10 Jan-13 2395:45 1263962 1665235 8527953:54 5:07

11 Feb-13 2526:27 1310246 1667422 6173072:05 3:42

12 Mar-13 1741:14 1171242 1668144 7972718:47 4:46

Sr.

NoMonth

IMi =

Number of

Momentary

interruptions for

the month

(in numbers)

Nmi =

Total no of

customers for

each

momentary

interruptions

(in numbers)

Imi =Nmi

Number of

customer

Mementary

interruptions

(in numbers)

Nt -

Total no of

customers

served

(in

numbers)

Customer Intt.

∑Imi*Nmi

MAIFI=

∑Imi*Nmi/

Nt

1 2 3 4 5 6 = 3 * 4 7 8= 7 / 6

1 Apr-12 4764 1657207 1651263 13594535 8.23

2 May-12 4309 1616072 1651155 11499334 6.96

3 Jun-12 5519 1637028 1654296 14119115 8.53

4 Jul-12 5683 1635484 1652334 14553114 8.81

5 Aug-12 5487 1629703 1653528 14265783 8.63

6 Sep-12 5526 1646752 1660899 14728104 8.87

7 Oct-12 6214 1626925 1660899 11956102 7.20

8 Nov-12 3694 1625316 1663951 10852188 6.52

9 Dec-12 3690 1551209 1664564 9930602 5.97

10 Jan-13 3780 1605885 1665235 10384037 6.24

11 Feb-13 3611 1584400 1667422 9994886 5.99

12 Mar-13 3565 1608686 1668144 9631916 5.77

Uttar Gujarat Vij Company Ltd YEAR 2012-13( APRIL-12 TO MARCH-13)

SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for JGY category

SoP 011 - B : System Average Interrruption Duration Index (SAIDI) for JGY category

SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for JGY category

Sr.

NoMonth

Ni - Number of

Customers for each

sustained

interruptions (in

numbers)

NT - Total No of

customers served

(in Numbers)

CI = ∑ NiSAIFI = ∑Ni/Nt

(Monthly SAIFI)

1 2 3 4 5 6= 5 / 4

1 Apr-12 528168 720403 1497481 2.08

2 May-12 646169 722613 1828019 2.53

3 Jun-12 684794 722264 3106066 4.30

4 Jul-12 660008 724201 2941149 4.06

5 Aug-12 623299 767959 2432841 3.17

6 Sep-12 575319 769011 2588769 3.37

7 Oct-12 582954 769011 1722098 2.24

8 Nov-12 451821 769011 1377466 1.79

9 Dec-12 468523 770957 1272703 1.65

10 Jan-13 615667 569501 2071001 3.64

11 Feb-13 571040 799948 1878755 2.35

12 Mar-13 475158 811179 1649380 2.03

Sr.

NoMonth

Ri =

Restoration Time for

each sustained

interruption event

(in hours)

Ni - Number of

interrupted Customers

for each sustained

interruption event

(in numbers)

Ri* Ni -

Total customer

interrution

Duration

NT - Total No of

customers

served

(in Numbers)

Customer Intt.

Duration CMI =

∑Ri*Ni

SAIDI =

∑Ri*Ni/Nt

(Monthly

SAIDI)

1 2 3 4 5 = 3 * 4 6 7 8= 7 / 6

1 Apr-12 1461:54 528168 720403 1955934:20 2:42

2 May-12 2472:50 646169 722613 3503654:51 4:50

3 Jun-12 2652:07 684794 722264 3520167:44 4:52

4 Jul-12 2771:51 660008 724201 2420496:34 3:20

5 Aug-12 1566:35 623299 767959 1983908:46 2:35

6 Sep-12 2122:10 575319 769011 2193741:47 2:51

7 Oct-12 1952:17 582954 769011 2366889:20 3:04

8 Nov-12 1292:49 451821 769011 1554239:34 2:01

9 Dec-12 1195:48 468523 770957 1054347:51 1:22

10 Jan-13 2260:36 615667 569501 2800236:22 4:55

11 Feb-13 1910:55 571040 799948 2303157:45 2:52

12 Mar-13 1459:36 475158 811179 1726028:01 2:07

Sr.

NoMonth

IMi =

Number of Momentary

interruptions for the

month

(in numbers)

Nmi =

Total no of customers

for each momentary

interruptions

(in numbers)

Imi =Nmi

Number of

customer

Mementary

interruptions

(in numbers)

Nt -

Total no of

customers

served

(in numbers)

Customer Intt.

∑Imi*Nmi

MAIFI=

∑Imi*Nmi/

Nt

1 2 3 4 5 6 = 3 * 4 7 8= 7 / 6

1 Apr-12 1607 702458 720403 3509677 4.87

2 May-12 1410 710524 722613 3120062 4.32

3 Jun-12 1988 730883 722264 4210166 5.83

4 Jul-12 1762 698703 724201 3424372 4.73

5 Aug-12 1834 709168 767959 3141341 4.09

6 Sep-12 1892 684507 769011 3423996 4.45

7 Oct-12 1558 674398 769011 2972238 3.87

8 Nov-12 1335 669610 769011 2380603 3.10

9 Dec-12 1452 661950 770957 2970519 3.85

10 Jan-13 1577 691753 569501 2184817 3.84

11 Feb-13 1341 726677 799948 2806699 3.51

12 Mar-13 1327 694615 811179 2352300 2.90

JGY was repeated in component of MAIFI figure earlier.

Uttar Gujarat Vij Company Ltd

YEAR 2012-13 ( APRIL-12 TO MARCH-13)

SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for Other than AG & JGY

SoP 011 - B : System Average Interrruption Duration Index (SAIDI) forOther than AG & JGY category

SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for Other than AG & JGY

Sr.

NoMonth

Ni - Number of

Customers for

each sustained

interruptions (in

numbers)

NT - Total No of

customers

served

(in Numbers)

CI = ∑ Ni

SAIFI =

∑Ni/Nt

(Monthly

SAIFI)

1 2 3 4 5 6= 5 / 4

1 Apr-12 1996011 2765956 5293854 1.91

2 May-12 2154352 2771258 5296461 1.91

3 Jun-12 2499430 2772976 12005711 4.33

4 Jul-12 2432534 2778762 12405414 4.46

5 Aug-12 2239052 2784502 9949815 3.57

6 Sep-12 2326063 2793464 10698520 3.83

7 Oct-12 2108900 2793464 6752850 2.42

8 Nov-12 1844926 2796631 5712136 2.04

9 Dec-12 1797810 2801884 4943648 1.76

10 Jan-13 2140351 2832038 9366813 3.31

11 Feb-13 2157483 2835828 6838317 2.41

12 Mar-13 1915815 2847822 7563596 2.66

Sr.

NoMonth

Ri =

Restoration Time

for each

sustained

interruption

event

(in hours)

Ni - Number of

interrupted

Customers for

each sustained

interruption

event

(in numbers)

Ri* Ni -

Total customer

interrution Duration

NT - Total

No of

customers

served

(in

Numbers)

Customer Intt.

Duration CMI =

∑Ri*Ni

SAIDI =

∑Ri*Ni/Nt

(Monthly

SAIDI)

1 2 3 4 5 = 3 * 4 6 7 8= 7 / 6

1 Apr-12 12447:34 1996011 2765956 10115781:08 3:39

2 May-12 12620:38 2154352 2771258 8852879:42 3:11

3 Jun-12 20705:59 2499430 2772976 16499639:56 5:57

4 Jul-12 22770:10 2432534 2778762 15124584:06 5:26

5 Aug-12 19815:33 2239052 2784502 10215666:04 3:40

6 Sep-12 18824:27 2326063 2793464 11650378:37 4:10

7 Oct-12 13815:48 2108900 2793464 10258148:31 3:40

8 Nov-12 12541:39 1844926 2796631 7525859:48 2:41

9 Dec-12 13418:10 1797810 2801884 6770872:17 2:25

10 Jan-13 13902:39 2140351 2832038 13266341:56 4:41

11 Feb-13 15080:16 2157483 2835828 10581748:50 3:43

12 Mar-13 15271:28 1915815 2847822 11908556:34 4:10

Sr.

NoMonth

IMi =

Number of

Momentary

interruptions for

the month

(in numbers)

Nmi =

Total no of

customers for

each momentary

interruptions

(in numbers)

Imi =Nmi

Number of customer

Mementary

interruptions

(in numbers)

Nt -

Total no of

customers

served

(in

numbers)

Customer Intt.

∑Imi*Nmi

MAIFI=

∑Imi*Nmi/

Nt

1 2 3 4 5 6 = 3 * 4 7 8= 7 / 6

1 Apr-12 14278 2668213 2765956 18433128 6.662 May-12 13246 2626619 2771258 15788077 5.703 Jun-12 18024 2683329 2772976 20062737 7.244 Jul-12 19584 2661318 2778762 20095940 7.235 Aug-12 20343 2672349 2784502 19529458 7.016 Sep-12 20435 2669538 2793464 20335924 7.287 Oct-12 16067 2636175 2793464 16515665 5.918 Nov-12 13179 2628430 2796631 15006230 5.379 Dec-12 13092 2520047 2801884 14323738 5.11

10 Jan-13 12769 2619002 2832038 13909547 4.9111 Feb-13 12315 2642735 2835828 14181752 5.0012 Mar-13 12603 2642500 2847822 13322324 4.68

Uttar Gujarat Vij Company Ltd YEAR 2012-13( APRIL-12 TO MARCH-13)

SoP 011 - B : System Average Interrruption Duration Index (SAIDI) for UGVCL as a whole

SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for UGVCL as a whole

SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for UGVCL as a whole

1

iEnergy Delivered into EHT / 11 KV and LT Distribution

System from EHT / 11 KV SS (Mus)A 17863.21

ii Energy Sold (Billed) EHT direct sales (Mus) B 1199.16

iii Energy Sold (Billed) in the 11 KV LT system (Mus) C 14150.46

iv Total Sales (Mus) (B+C) 15349.62

v Losses (Mus) {(A) - (B+C)} 2513.59

vi % Losses {(A) - (B+C)} X 100 / (A) 14.07

Uttar Gujarat Vij Company Ltd ,Mehsana

QUARTER :-Yearly April-12 to March-13

YEAR :-2012-13

Performance SoP 012 - System Losses at EHT / 11 KV and below

SoP 012 - CALCULATION OF SYSTEM LOSSES AT EHT / 11 KV

Losses in 11 KV System and Connected Equipment

Consumer

Category

No. of faulty meters

at the start of the

quarter / year

No. of faulty

meters added

during the quarter

/ year

Total No. of

defective / faulty

meter

No. of faulty Meters

repaired and

replaced

No. of faulty meters

pending at the end

of the quarter/year

1 2 3=2+1 4 5=3-4

Single Phase 4739 58323 63062 62108 954

Three Phase 12 7314 7326 7293 33

H.T. 0 43 43 43 0

Uttar Gujarat Vij Company Ltd

Performa SOP 013 : Meter faults

YEAR 2012-13( APRIL-12 TO MARCH-13)

Qtr. MonthsUnits input

(Mus)

Units Billed

(Mus)

Billing

Efficiency

Revenue

Billed

(Rs. Crore)

Revenue

Collected (Rs.

Crore)**

Collection

Efficiency % *

Business

EfficiencyATC Loss %

A B C=(B/A)*100 D E F=(E/D)*100 G=(C*F)/100 H=100-G

April'12 1559 1222 78.396 481 506 100.00 78.40 21.60

May'12 1588 1235 77.730 454 421 92.65 72.02 27.98

June'12 1392 1259 90.504 527 566 100.00 90.50 9.50

Sub Total 4539 3716 81.875 1461 1492 100.00 81.87 18.13

July'12 1297 1053 81.245 453 446 98.60 80.11 19.89

Aug.'12 1217.55 1047 85.988 493 454 92.05 79.15 20.85

Sept.'12 1045.38 1019 97.454 450 545 100.00 97.45 2.55

Sub Total 3560 3119.17 87.627 1396 1445 100.00 87.63 12.37

Oct.'12 1628.415 1359.79 83.504 485 487 100.00 83.50 16.50

Nov.'12 1539.955 1388.32 90.153 417 486 100.00 90.15 9.85

Dec.'12 1693.835 1396.84 82.466 468 520 100.00 82.47 17.53

Sub Total 4862.205 4144.94 85.248 1370 1492 100.00 85.25 14.75

Jan'13 1662.038 1453.53 87.455 423 405 95.88 83.85 16.15

Feb'13 1511.995 1462.78 96.745 478 559 100.00 96.75 3.25

Mar.'13 1727.466 1453.20 84.123 486 549 100.00 84.12 15.88

Sub Total 4901.499 4369.51 89.146 1387 1513 100.00 89.15 10.85

V Grand Total 17861.91 15349.63 85.935 5614 5942 100.00 85.93 14.07

*

**

III

IV

The details are provisional. Revenue collection is as per window collection.

Uttar Gujarat Vij Company Ltd ,MehsanaQUARTER :-Yearly April-12 to March-13

YEAR :-2012-13

Performa SoP 014: Statement Showing the ATC losses, collection efficiency and Billing Efficiency

I

II

Collection efficiency above 100% is taken as 100%

Consumer Category

Total No. of

consumers

connected As on

March-13

Total New

application

received at the

end of the quarter

/ year

No. of release of

connections in the

quarter / year

No. of pending applications for

release of new connections in

the quarter / year Paid & Pending

Domestic 2298488 57535 51353 512

GLP 19209 8463 380 33

NGRP & LTMD 267930 7053 12399 221

Agriculture (Total) 245079 90874 5515 1363

Industrial HT 2511 228 275 33

Uttar Gujarat Vij Company Ltd ,Mehsana

Performa SOP 015 : Release of New connection : Status as on 31.03.13

YEAR 2012-13( APRIL-12 TO MARCH-13)

Sr. No. Event Compensation

No. of cases where

compensation was given

(in numbers)

Amt.of compensation paid

(in Rs.)

Duty to provide supply

a) New connection

b) Additional load

c) Temporary supply

d) Shifting service

connection

e) Transfer of service

connection

f) Change in tariff category

of consumer

2 Complaints in billing Rs.50 for non reply within

the period prescribed in

Regulations

3 Replacement of metersLT Rs.25 per day of delay

maximum Rs.2,500 and HT

Rs. 250 per day of delay

maximum of Rs. 5,000/-

4 Interruption of supply LT Rs.25 for every 6 hrs. of

delay maximum of Rs.500

and HT Rs. 50 for every 6

hrs. delay maximum Rs.

1000

5 Voltage fluctuations and

complaintsRs.50 for failure to visit or

convey findings wihin the

stipulated period

6 Responding to consumers

complaints

Rs. 25 for each day of delay

maximum Rs. 500

7 Grievance Handling Rs. 25 for failure in handling

grievance.

TOTAL :- …NIL… ……NIL…..

Rs.50 per day of delay from

the limit specified in the

performance regulations

1

Uttar Gujarat Vij Company Ltd ,Mehsana

Performa SoP 016 : Compensation details

COMPENSATION DETAILS

YEAR 2012-13( APRIL-12 TO MARCH-13)