AIR CONDITIONERS TECHNICAL & SERVICE MANUAL Models PEFY-P20VMA(L)-E, PEFY-P25VMA(L)-E, PEFY-P32VMA(L)-E, PEFY-P40VMA(L)-E, PEFY-P50VMA(L)-E, PEFY-P63VMA(L)-E PEFY-P71VMA(L)-E PEFY-P80VMA(L)-E PEFY-P100VMA(L)-E PEFY-P125VMA(L)-E PEFY-P140VMA(L)-E 2012

PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

AIR CONDITIONERS

TECHNICAL & SERVICE MANUALModels PEFY-P20VMA(L)-E,

PEFY-P25VMA(L)-E,PEFY-P32VMA(L)-E,PEFY-P40VMA(L)-E,PEFY-P50VMA(L)-E,PEFY-P63VMA(L)-E

PEFY-P71VMA(L)-EPEFY-P80VMA(L)-EPEFY-P100VMA(L)-EPEFY-P125VMA(L)-EPEFY-P140VMA(L)-E

2012

Page 2: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

ii

HWE0812B GB

Safety PrecautionsRead before installation and performing electrical work

Symbol explanations

Thoroughly read the following safety precautions prior to installation.Observe these safety precautions for your safety.This equipment may have adverse effects on the equipment on the same power supply system.Contact the local power authority before connecting to the system.

WARNINGThis symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or death.

CAUTIONThis symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or dam-age to the unit.

Indicates an action that must be avoided.

Indicates important instructions.

Indicates a parts that requires grounding.

Indicates that caution must be taken with rotating parts. (This symbol is on the main unit label.) <Color: Yellow>

Indicates that the parts that are marked with this symbol pose a risk of electric shock. (This symbol is on the main unit label.) <Color: Yellow>

WARNINGCarefully read the labels affixed to the main unit.

WARNING

Ask your dealer or a qualified technician to install the unit.

Improper installation by the user may result in water leak-age, electric shock, or fire.

Properly install the unit on a surface that can withstand its weight.

Unit installed on an unstable surface may fall and cause in-jury.

Only use specified cables. Securely connect each cable so that the terminals do not carry the weight of the cable.

Improperly connected cables may produce heat and start a fire.

Take appropriate safety measures against wind gusts and earthquakes to prevent the unit from toppling over.

Improper installation may cause the unit to topple over and cause injury or damage to the unit.

Only use accessories (i.e., air cleaners, humidifiers, electric heaters) recommended by Mitsubishi Electric.

Do not make any modifications or alterations to the unit. Consult your dealer for repair.

Improper repair may result in water leakage, electric shock, or fire.

Do not touch the heat exchanger fins with bare hands.

The fins are sharp and pose a risk of cuts.

In the event of a refrigerant leak, thoroughly ventilate the room.

If gaseous refrigerant leaks out and comes in contact with an open flame, toxic gases will be generated.

Properly install the unit according to the instructions in the Installation Manual.

Improper installation may result in water leakage, electric shock, or fire.

Have all electrical work performed by an authorized electri-cian according to the local regulations and the instructions in this manual. Use a dedicated circuit.

Insufficient power supply capacity or improper installation of the unit may result in malfunctions of the unit, electric shock, or fire.

0000001526.book i ページ 2012年9月13日 木曜日 午後7時14分

Page 3: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

iiHWE0812B GB

Precautions for handling units for use with R410A

WARNING

Keep electrical parts away from water.

Wet electrical parts pose a risk of electric shock, smoke, or fire.

Securely attach the control box cover.

If the cover is not installed properly, dust or water may infil-trate and pose a risk of electric shock, smoke, or fire.

Only use the type of refrigerant that is indicated on the unit when installing or relocating the unit.

Infiltration of any other types of refrigerant or air into the unit may adversely affect the refrigerant cycle and may cause the pipes to burst or explode.

When installing the unit in a small space, take appropriate precautions to prevent leaked refrigerant from reaching the limiting concentration.

Leaked refrigerant gas will displace oxygen and may cause oxygen starvation. Consult your dealer before installing the unit.

Consult your dealer or a qualified technician when moving or reinstalling the unit.

Improper installation may result in water leakage, electric shock, or fire.

After completing the service work, check for a refrigerant leak.

If leaked refrigerant is exposed to a heat source, such as a fan heater, stove, or electric grill, toxic gases will be gener-ated.

Do not try to defeat the safety features of the unit.

Forced operation of the pressure switch or the temperature switch by defeating the safety features for these devices, or the use of accessories other than the ones that are recom-mended by Mitsubishi Electric may result in smoke, fire, or explosion.

Consult your dealer for proper disposal method.

Do not use a leak detection additive.

CAUTION

Do not use the existing refrigerant piping.

A large amount of chlorine that may be contained in the re-sidual refrigerant and refrigerator oil in the existing piping may cause the refrigerator oil in the new unit to deteriorate.

Use refrigerant piping materials made of phosphorus deox-idized copper. Keep the inner and outer surfaces of the pipes clean and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and moisture.

Contaminants in the refrigerant piping may cause the refrig-erator oil to deteriorate.

Store the piping materials indoors, and keep both ends of the pipes sealed until immediately before brazing. (Keep el-bows and other joints wrapped in plastic.)

Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate or cause the compressor to malfunction.

Use a small amount of ester oil, ether oil, or alkyl benzene to coat flares and flanges.

Infiltration of a large amount of mineral oil may cause the re-frigerator oil to deteriorate.

Charge the system with refrigerant in the liquid phase.

If gaseous refrigerant is drawn out of the cylinder first, the composition of the remaining refrigerant in the cylinder will change and become unsuitable for use.

Only use R410A.

The use of other types of refrigerant that contain chloride may cause the refrigerator oil to deteriorate.

Use a vacuum pump with a check valve.

If a vacuum pump that is not equipped with a check valve is used, the vacuum pump oil may flow into the refrigerant cy-cle and cause the refrigerator oil to deteriorate.

Prepare tools for exclusive use with R 410A. Do not use the following tools if they have been used with the conventional refrigerant: gauge manifold, charging hose, gas leak detec-tor, check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.

If the refrigerant or the refrigerator oil that may be left on these tools are mixed in with R410A, it may cause the refrigerator oil in the new system to deteriorate. Infiltration of water may cause the refrigerator oil to deteriorate.Leak detectors for conventional refrigerants will not detect an R410A leak because R410A is free of chlorine.

Do not use a charging cylinder.

If a charging cylinder is used, the composition of the refrigerant in the cylinder will change and become unsuitable for use.

Exercise special care when handling tools for use with R410A.

Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate.

0000001526.book ii ページ 2012年9月13日 木曜日 午後7時14分

Page 4: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

CONTENTS

HWE0812B GB

I Features[1] Features.................................................................................................................................... 1

II Components and Functions[1] Components and Functions...................................................................................................... 2

III Specfications[1] Specifications............................................................................................................................ 4

1.Specfications .......................................................................................................................... 42.Electrical component specifications........................................................................................ 7

IV Outlines and Dimensions[1] Outlines and Dimensions.......................................................................................................... 8[2] Service Space......................................................................................................................... 10

V Wiring Diagram[1] Wiring Diagram ....................................................................................................................... 11

VI Refrigerant System Diagram[1] Refrigerant system diagram.................................................................................................... 13

VII Troubleshooting[1] Troubleshooting ...................................................................................................................... 14

1.Check methods..................................................................................................................... 142.DC fan motor (fan motor/indoor control board)..................................................................... 183.Address switch setting .......................................................................................................... 194.Voltage test points on the control board ............................................................................... 205.Dipswitch setting (Factory setting)........................................................................................ 21

VIII Disassembly Procedure[1] Disassembly Procedure.......................................................................................................... 24

1.Control box ........................................................................................................................... 242.Thermistor (Intake air) .......................................................................................................... 253.Drainpan ............................................................................................................................... 264.Thermistor (Gas pipe) (Liquid pipe) ...................................................................................... 275.Fan and fan motor ................................................................................................................ 286.Heat exchanger .................................................................................................................... 29

0000001526.book 1 ページ 2012年9月13日 木曜日 午後7時14分

Page 5: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

HWE0812B GB

0000001526.book 2 ページ 2012年9月13日 木曜日 午後7時14分

Page 6: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ I Features ]

- 1 -HWE0812B GB

I Features

[1] Features

Model Cooling capacity/Heating capacity

kW

PEFY-P20VMA(L)-E 2.2/2.5

PEFY-P25VMA(L)-E 2.8/3.2

PEFY-P32VMA(L)-E 3.6/4.0

PEFY-P40VMA(L)-E 4.5/5.0

PEFY-P50VMA(L)-E 5.6/6.3

PEFY-P63VMA(L)-E 7.1/8.0

PEFY-P71VMA(L)-E 8.0/9.0

PEFY-P80VMA(L)-E 9.0/10.0

PEFY-P100VMA(L)-E 11.2/12.5

PEFY-P125VMA(L)-E 14.0/16.0

PEFY-P140VMA(L)-E 16.0/18.0

0000001526.book 1 ページ 2012年9月13日 木曜日 午後7時14分

Page 7: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ II Components and Functions ]

- 2 -HWE0812B GB

II Components and Functions

[1] Components and Functions1. Indoor (Main) Unit

2. Remote Controller[PAR-21MAA]Once the operation mode is selected, the unit will remain in the selected mode until changed.

(1) Remote Controller Buttons

Keep the remote controller out of direct sunlight to ensure accurate measurement of room temperature.The thermistor at the lower right-hand section of the remote controller must be free from obstructions to ensure accurate mea-surement of room temperature.

(1) In case of rear inlet (2) In case of bottom inlet

1 [Set Temperature] Button 7 [Vane Control] Button2 [Timer Menu] Button 8 [Ventilation] Button

[Monitor/Set] Button [Operation] Button3 [Mode] Button 9 [Check/Clear] Button

[Back] Button 10 [Test Run] Button4 [Timer On/Off] Button 11 [Filter] Button

[Set Day] Button [ ] Button5 [Louver] Button 12 [ON/OFF] Button

[Operation] Button 13 Position of built-in room thermistor6 [Fan Speed] Button 14 [Set Time] Button

Air inlet

Air outlet Air outlet

Air inlet

0000001526.book 2 ページ 2012年9月13日 木曜日 午後7時14分

Page 8: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ II Components and Functions ]

- 3 -HWE0812B GB

(2) Remote Controller Display

A Current time/Timer time I Louver swing

B Centralized control indicator J Ventilation

C Timer OFF indicator K Filter sign

D Timer mode indicator L Sensor position

E Operation mode display: COOL, DRY, AUTO, FAN, HEAT

M Room temperature

F Function mode indicator N Vane setting

G Preset temperature O Fan speed

H Power indicator P Operation lamp

0000001526.book 3 ページ 2012年9月13日 木曜日 午後7時14分

Page 9: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ III Specfications ]

- 4 -HWE0812B GB

III Specfications

[1] Specifications

1. Specfications

*1 <Cooling> Indoor temperature: 27°CDB/19°CWB (81°FDB/66°FWB) Outdoor temperature: 35°CDB (95°FDB) <Heating> Indoor temperature: 20°CDB (68°FWB) Outdoor temperature: 7°CDB/6°CWB (45°FDB/43°FWB)*2 Figures in the parentheses indicate drainpump-less Model (L).

Model PEFY-P20VMA(L)-E

PEFY-P25VMA(L)-E

PEFY-P32VMA(L)-E

PEFY-P40VMA(L)-E

Power supply Voltage V 1-phase 220-230-240

Frequency Hz 50/60

Cooling capacity *1 kW 2.2 2.8 3.6 4.5

Heating capacity *1 kW 2.5 3.2 4.0 5.0

Power consumption *2 Cooling kW 0.06(0.04) 0.07(0.05) 0.09(0.07)

Heating kW 0.04(0.04) 0.05(0.05) 0.07(0.07)

Current consumption *2 Cooling A 0.53(0.42) 0.55(0.44) 0.64(0.53)

Heating A 0.42(0.42) 0.44(0.44) 0.53(0.53)

External finish Galvanized

Dimensions Height mm 250

Width mm 700 900

Depth mm 732

Net weight *2 kg 23(22) 26(25)

Heat exchanger Cross fin(Aluminium fin and copper tube)

Fan Type Sirocco fan x 1

Airflow rate (Low-Mid-High)

m3/min 6.0-7.5-8.5 7.5-9.0-10.5 10.0-12.0-14.0

External static pressure

Pa 35/50/70/100/150

Motor Output kW 0.085

Air filter PP Honeycomb fabric (washable)

Refrigerant pipe dimensions

Gas (Brazed connection)

mm[in.] ø12.7[ø1/2]

Liquid (Brazed connection)

mm[in.] ø6.35[ø1/4]

Drain pipe dimensions mm[in.] O.D. 32[1-1/4]

Operating noise(Low-Mid-High) 35Pa dB (A) 23-24-25 23-25-28 23-26-29

50Pa 23-25-26 23-26-29 23-27-30

70Pa 23-26-28 24-27-30 24-28-31

100Pa 24-27-30 25-28-32 26-29-33

150Pa 25-30-34 28-32-36 29-33-37

35Pa 26-27-28 28-30-34

50Pa 26-28-29 28-30-34

70Pa 26-29-31 29-32-36

100Pa 27-30-33 29-33-37

150Pa 28-33-37 31-35-40 32-36-40

Measurement location 1

Aux. duct

* Measured in anechoic room.

2m 2m

1.5m

* Measured in anechoic room.

2m 1m

Aux. duct

1.5m

Measurement location 2

0000001526.book 4 ページ 2012年9月13日 木曜日 午後7時14分

Page 10: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ III Specfications ]

- 5 -HWE0812B GB

*1 <Cooling> Indoor temperature: 27°CDB/19°CWB (81°FDB/66°FWB) Outdoor temperature: 35°CDB (95°FDB) <Heating> Indoor temperature: 20°CDB (68°FWB) Outdoor temperature: 7°CDB/6°CWB (45°FDB/43°FWB)*2 Figures in the parentheses indicate drainpump-less Model (L).

Model PEFY-P50VMA(L)-E

PEFY-P63VMA(L)-E

PEFY-P71VMA(L)-E

PEFY-P80VMA(L)-E

Power supply Voltage V 1-phase 220-230-240

Frequency Hz 50/60

Cooling capacity *1 kW 5.6 7.1 8.0 9.0

Heating capacity *1 kW 6.3 8.0 9.0 10.0

Power consumption *2 Cooling kW 0.11(0.09) 0.12(0.10) 0.14(0.12)

Heating kW 0.09(0.09) 0.10(0.10) 0.12(0.12)

Current consumption *2 Cooling A 0.74(0.63) 1.01(0.90) 1.15(1.04)

Heating A 0.63(0.63) 0.90(0.90) 1.04(1.04)

External finish Galvanized

Dimensions Height mm 250

Width mm 900 1100

Depth mm 732

Net weight *2 kg 26(25) 32(31)

Heat exchanger Cross fin(Aluminium fin and copper tube)

Fan Type Sirocco fan x 1

Sirocco fan x 2

Airflow rate (Low-Mid-High)

m3/min 12.0-14.5-17.0

13.5-16.0-19.0

14.5-18.0-21.0

External static pressure

Pa 35/50/70/100/150

Motor Output kW 0.085 0.121

Air filter PP Honeycomb fabric (washable)

Refrigerant pipe dimensions

Gas (Brazed con-nection)

mm[in.] ø12.7[ø1/2] ø15.88[ø5/8]

Liquid (Brazed connection)

mm[in.] ø6.35[ø1/4] ø9.52[ø3/8]

Drain pipe dimensions mm[in.] O.D. 32[1-1/4]

Operating noise(Low-Mid-High) 35Pa dB (A) 24-28-31 25-28-32 26-29-33

50Pa 25-29-32 25-29-33 26-29-34

70Pa 26-30-33 26-30-34 26-30-35

100Pa 27-31-34 27-31-35 29-33-37

150Pa 29-34-38 32-37-41

35Pa 28-31-35 29-32-35 30-33-37

50Pa 28-32-35 29-32-36 30-34-38

70Pa 29-33-37 30-33-38 31-36-39

100Pa 30-34-38 31-35-39 33-37-41

150Pa 32-37-41 33-38-41 36-41-44

Measurement location 1

Aux. duct

* Measured in anechoic room.

2m 2m

1.5m

* Measured in anechoic room.

2m 1m

Aux. duct

1.5m

Measurement location 2

0000001526.book 5 ページ 2012年9月13日 木曜日 午後7時14分

Page 11: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ III Specfications ]

- 6 -HWE0812B GB

*1 <Cooling> Indoor temperature: 27°CDB/19°CWB (81°FDB/66°FWB) Outdoor temperature: 35°CDB (95°FDB) <Heating> Indoor temperature: 20°CDB (68°FWB) Outdoor temperature: 7°CDB/6°CWB (45°FDB/43°FWB)*2 Figures in the parentheses indicate drainpump-less Model (L).

Model PEFY-P100VMA(L)-E

PEFY-P125VMA(L)-E

PEFY-P140VMA(L)-E

Power supply Voltage V 1-phase 220-230-240

Frequency Hz 50/60

Cooling capacity *1 kW 11.2 14.0 16.0

Heating capacity *1 kW 12.5 16.0 18.0

Power consumption *2 Cooling kW 0.24(0.22) 0.34(0.32) 0.36(0.34)

Heating kW 0.22(0.22) 0.32(0.32) 0.34(0.34)

Current consumption *2 Cooling A 1.47(1.36) 2.05(1.94) 2.21(2.10)

Heating A 1.36(1.36) 1.94(1.94) 2.10(2.10)

External finish Galvanized

Dimensions Height mm 250

Width mm 1400 1600

Depth mm 732

Net weight *2 kg 42(41) 46(45)

Heat exchanger Cross fin(Aluminium fin and copper tube)

Fan Type Sirocco fan x 2

Airflow rate (Low-Mid-High)

m3/min 23.0-28.0-33.0 28.0-34.0-40.0 29.5-35.5-42.0

External static pressure

Pa 35/50/70/100/150

Motor Output kW 0.244

Air filter PP Honeycomb fabric (washable)

Refrigerant pipe dimensions

Gas (Brazed con-nection)

mm[in.] ø15.88[ø5/8]

Liquid (Brazed connection)

mm[in.] ø9.52[ø3/8]

Drain pipe dimensions mm[in.] O.D. 32[1-1/4]

Operating noise(Low-Mid-High) 35Pa dB (A) 28-32-36 31-35-39 31-35-40

50Pa 28-33-37 32-36-40 33-37-42

70Pa 30-35-39 32-37-41 34-38-43

100Pa 31-36-40 33-39-42 35-39-44

150Pa 33-38-43 37-40-44 37-41-45

35Pa 31-36-40 35-40-44 36-41-45

50Pa 32-37-41 35-40-44 36-41-45

70Pa 33-38-42 37-41-45 38-42-46

100Pa 35-39-43 38-42-46 39-43-47

150Pa 37-42-45 39-44-47 40-45-48

Measurement location 1

Aux. duct

* Measured in anechoic room.

2m 2m

1.5m

* Measured in anechoic room.

2m 1m

Aux. duct

1.5m

Measurement location 2

0000001526.book 6 ページ 2012年9月13日 木曜日 午後7時14分

Page 12: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ III Specfications ]

- 7 -HWE0812B GB

2. Electrical component specifications

Component Sym-bol

PEFY-P20VMA(L)-E

PEFY-P25VMA(L)-E

PEFY-P32VMA(L)-E

Room temperature thermistor

TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

Fuse FUSE 250V 6.3A

Fan motor 8-pole, Output 85W SIC-70CW-D885-1

Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)

Power supply terminal block

TB2 (L, N, ) 250V 20A

Transmission terminal block

TB5TB15 (1, 2) 250V 15A, (M1, M2, S) 250V 20A

Drain float switch DS Open/short detectionInitial contact resistance 500 mΩ or less

Component Sym-bol

PEFY-P40VMA(L)-E

PEFY-P50VMA(L)-E

PEFY-P63VMA(L)-E

PEFY-P71VMA(L)-E

PEFY-P80VMA(L)-E

Room temperature thermistor

TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

Fuse FUSE 250V 6.3A

Fan motor 8-pole, Output 85W SIC-70CW-D885-2

8-pole, Output 121W SIC-70CW-D8121-1

Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)

Power supply terminal block

TB2 (L, N, ) 250V 20A

Transmission terminal block

TB5TB15

(1, 2) 250V 15A, (M1, M2, S) 250V 20A

Drain float switch DS Open/short detectionInitial contact resistance 500 mΩ or less

Component Sym-bol

PEFY-P100VMA(L)-E PEFY-P125VMA(L)-E PEFY-P140VMA(L)-E

Room temperature thermistor

TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ

Fuse FUSE 250V 6.3A

Fan motor 8-pole, Output 244W SIC-101CW-D8244-1

Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)

Power supply terminal block

TB2 (L, N, ) 250V 20A

Transmission terminal block

TB5TB15 (1, 2) 250V 15A, (M1, M2, S) 250V 20A

Drain float switch DS Open/short detectionInitial contact resistance 500 mΩ or less

0000001526.book 7 ページ 2012年9月13日 木曜日 午後7時14分

Page 13: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ IV Outlines and Dimensions ]

- 8 -HWE0812B GB

IV Outlines and Dimensions

[1] Outlines and Dimensions1. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA-E

Note 1 Use M10 suspension bolts. (not supplied)2 Provide an access door for maintenance at the bottom.3 The dimensions in the table are those of the PEFY-P63, 71, 80, 100, 125, 140VMA-E models, which have 2

fans. The PEFY-P20~50VMA-E model have 1 fans.

4 To connect an intake duct, uninstall the air filter on the unit, and install a locally procured air filter on the intake duct on the intake side.

1558

1358

1500

1300

7Mo

del

A66

080

0

1200

700

754

900

954

860

9E 11

D 1060

C

1100

B 1154

PEFY

-P14

0VMA

-EPE

FY-P

100,1

25VM

A-E

PEFY

-P63

,71,80

VMA-

EPE

FY-P

40, 5

0VMA

-EPE

FY-P

20,25

,32VM

A-E

1400

1600

1454

1654

1500

1700

1360

1560

14 16

1000

1000F

858

800

G 658

1058

600

1480

1280

55

300

150

44 49

800

1000

260

LK 33

0

JH 1200

1500

1700

54 5432

037

0

544M

780

4

N 990

121210P 10 10ø1

5.88

ø9.52

ø12.7

ø6.35

Gas p

ipe1

Liquid

pipe

2

650 -10

(Actua

l leng

th)

Less

than

300m

m

Less than 700mm

Drain

hose

(I.D.ø

32)

<acce

ssory>

Air F

ilter

G 21

A

B (Suspension bolt pitch)

C

23

Air

inlet

L6J

KK x (M - 1) = N

P - ø2.9

40

D (Duct) 20 100

57

73

10

643

(Sus

pens

ion bo

lt pitc

h)

10030100 x (E - 1) = F

5815

Susp

ensio

n bolt

hole

4 - 1

4 x 30

Slot

2 x E

- ø2

.9 Air

outle

t

250

40

33122

178(Duct)23

1023

832

700732

136

67 356

100

41217

2 1

Contr

ol bo

xRe

friger

ant p

iping

Braz

ing co

nnec

tion (

liquid

)

Refrig

eran

t pipi

ngBr

azing

conn

ectio

n (ga

s)

Drain

pump

Term

inal b

lock (

Powe

r sou

rce)

Term

inal b

lock (

Tran

smiss

ion)

Drain

pipe

(O.D

.ø32

)(S

ponta

neou

s dra

ining

)

Drain

pipe

(O.D

. ø32

)

2 x 2

- ø2.9

210

18

112

1111

2

KJ

112

P - ø

2.9

11 112

JK

L6

JK

K x (

M - 1

) = N

0000001526.book 8 ページ 2012年9月13日 木曜日 午後7時14分

Page 14: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ IV Outlines and Dimensions ]

- 9 -HWE0812B GB

2. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMAL-E

Note 1 Use M10 suspension bolts. (not supplied)2 Provide an access door for maintenance at the bottom.3 The dimensions in the table are those of the PEFY-P63, 71, 80, 100, 125, 140VMAL-E models, which have

2 fans. The PEFY-P20~50VMAL-E model have 1 fans.

4 To connect an intake duct, uninstall the air filter on the unit, and install a locally procured air filter on the intake duct on the intake side.

1558

1358

1500

1300

7M

odel

A66

080

0

1200

700

754

900

954

860

9E 11

D 1060

C

1100

B 1154

PEFY

-P14

0VM

AL-E

PEFY

-P10

0,12

5VM

AL-E

PEFY

-P63

,71,

80VM

AL-E

PEFY

-P40

, 50V

MAL

-EPE

FY-P

20,2

5,32

VMAL

-E

1400

1600

1454

1654

1500

1700

1360

1560

14 16

1000

1000F

858

800

G 658

1058

600

1480

1280

55

300

150

44 49

800

1000

260

LK 33

0

JH 1200

1500

1700

54 5432

037

0

544M

780

4

N 990

121210P 10 10ø1

5.88

ø9.5

2

ø12.

7ø6

.35

Gas p

ipe1

Liquid

pipe

2

250

40

33122

21

23

178(Duct)23

10

3270

0732

136

67 356

100

217

643

(Sus

pens

ion bo

lt pitc

h) A

ir Fi

lter

Cont

rol b

oxRe

frige

rant

pipi

ngBr

azing

conn

ectio

n (liq

uid)

Refri

gera

nt p

iping

Braz

ing co

nnec

tion

(gas

)Te

rmina

l bloc

k (Po

wer s

ourc

e)

Term

inal b

lock (

Tran

smiss

ion)

Drain

pipe

(O.D

.ø32

)2

x 2 -

ø2.9

2 1

(Actu

al len

gth)

320 -10

J 6P - ø2.9

D (Duct)

210

18

G

A

B (Suspension bolt pitch)

C

100 x (E - 1) = F

Air

outle

tAi

rinl

et

Susp

ensio

n bo

lt hole

4 -

14 x

30 S

lot2

x E -

ø2.9

Drain

hose

(I.D.

ø32)

<acc

esso

ry>

K x (M - 1) = NKLK

112

1111

2

24

20 100

57

7310

10030

15

J

K x (

M - 1

) = N

KJ

6L

KJ

11211

P - ø

2.9

112

0000001526.book 9 ページ 2012年9月13日 木曜日 午後7時14分

Page 15: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ IV Outlines and Dimensions ]

- 10 -HWE0812B GB

[2] Service Space1.PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA(L)-E

Secure enough access space to allow for the maintenance, inspection, and replacement of the motor, fan, drain pump, heat exchanger, and electric box in one of the following ways.Select an installation site for the indoor unit so that its maintenance access space will not be obstructed by beams or other objects.(1) When a space of 300 mm or more is available below the unit between the unit and the ceiling (Fig. 1)• Create access door 1 and 2 (450 × 450 mm each) as shown in Fig. 2.(Access door 2 is not required if enough space is available below the unit for a maintenance worker to work in.)

(2) When a space of less than 300 mm is available below the unit between the unit and the ceiling (At least 20 mm of space should be left below the unit as shown in Fig. 3.)• Create access door 1 diagonally below the electric box and access door 3 below the unit as shown in Fig. 4.or• Create access door 4 below the electric box and the unit as shown in Fig. 5.

Elec

tric b

ox

Ceiling

Min. 300 mm

Min. 10 mm

View

ed fr

om

the

direc

tion

of th

e ar

row

A

Acce

ss do

or 2 (

450 ×

450)

Ceilin

g beam

Intak

e air

Supp

ly air

Elec

tric b

ox

Ceilin

g

Min. 20 mm

Min.10 mm

View

ed fr

om

the

direc

tion

of th

e ar

row

B

Ceilin

g beam

Acce

ss do

or 3

Intak

e air

Supp

ly air

700

450

475

450

R 50~1

5045

0

450

100~

200

Botto

m o

f indo

or u

nit

Maint

enan

ce ac

cess

spac

e

Min. 3

00 m

m

(View

ed fr

om

the

direc

tion

of

the

arro

w A)

Acce

ss do

or 2

(450

× 45

0)

Acce

ss do

or 1

(450

× 45

0)

Q

Elec

tric b

ox

Acce

ss do

or 3

Q 50

S

777

450 100~

200

Maint

enan

ce ac

cess

spac

e

Botto

m of

indoo

r unit

Elec

tric b

ox

(View

ed fr

om th

e dir

ectio

n of

th

e ar

row

B)

Acce

ss do

or 1

(450

× 45

0)

450

47570

050

Min. 3

00 m

m

777

T

50

50Q

700

Maint

enan

ce ac

cess

spac

e

Botto

m of

indoo

r unit

Electri

c box

Min. 3

00 m

m

(View

ed fr

om th

e dir

ectio

n of

th

e ar

row

B)

Acce

ss do

or 4

Fig.

1

Fig.

3

Fig.

2

Fig.

4Fi

g. 5

PE

FY-P

20,2

5,32

VM

A(L

)-E

PE

FY-P

40,5

0VM

A(L

)-E

PE

FY-P

63,7

1,80

VM

A(L

)-E

PE

FY-P

100,

125V

MA

(L)-

EP

EFY

-P14

0VM

A(L

)-E

Q 700

900

1100

1400

1600

S 800

1000

1200

1500

1700

T 1300

1500

1700

2000

2200

R50

~150

150~

250

250~

350

400~

500

500~

600

(mm

)M

odel

Uni

t: m

m

0000001526.book 10 ページ 2012年9月13日 木曜日 午後7時14分

Page 16: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ V Wiring Diagram ]

- 11 -HWE0812B GB

V Wiring Diagram

[1] Wiring Diagram1. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA(L)-E

2 1

INSI

DE S

ECTI

ON

OF

CONT

ROL

BOX

FUSE

(16A

)

BREA

KER

(16A

)

PULL

BOX

TO N

EXT I

NDOO

R UN

IT

TO M

A RE

MOTE

CO

NTRO

LLER

TO O

UTDO

OR U

NIT

BC C

ONTR

OLLE

RRE

MOTE

CON

TROL

LER

P.B.

21

TB15

2 1

TB2

NL

S (S

HIEL

D)

M2 M1

TB5

ACL

21

1 3

35

1

X10

U

DC2

80-3

40V

Rect

ifier c

ircui

t

U

(Red

)

X01

CNP

F01

DSA

ZNR0

2

CND

ZNR0

1

(Blue

)

Drain

pump

Fan m

otor

53

21

44

45

67

12

11

23

(Blue

)CN

XB1

CNMF

CNXA

1CN

XC1

ONLY

FOR

PEF

Y-P·

VMA-

E

MS 3~

M 1~

I.B.

1

431 2

21542 3

CN4F

(Blue

)CN

XA2

CN52

CN20

CN41

CN51

CNXB

2

CNXC

2(R

ed)

CN44

(Gre

en)

1 2 4321 3 4

1 2

13

(Blac

k)

(Red

)

CN3A

(Blue

)

(Red

)

CN2A

LED1

LED2

CN27

SWE

CN90

CN10

5

CN2M

(Blue

)ONOF

FSW

3

SW2

SW1

1 2 43

CN4F

TH21

A

FSTH

23TH

22t°

FOR

PEFY

-P·V

MA-E

REFE

R TO

"A" F

OR P

EFY-

P·VM

AL-E

21 653 4

CN60

CN32

SWA

SW4

SW11

SW12

SW14

SWC

SW5

POW

ER S

UPPL

YAC

220-

240V

50

,60Hz

M LEV

0000001526.book 11 ページ 2012年9月13日 木曜日 午後7時14分

Page 17: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ V Wiring Diagram ]

- 12 -HWE0812B GB

Table.1 SYMBOL EXPLANATION

SYM-BOL

NAME SYM-BOL

NAME SYM-BOL

NAME

I.B. Indoor controller board CN32 Connector (Remote switch) SW2 (I.B.)

Switch (for capacity code)

P.B. Power supply board CN41 Connector (HA terminal-A) SW3 (I.B.)

Switch (for mode selection)

TB2 Power source terminal block CN51 Connector (Centrally control) SW4(I.B.)

Switch (for model selection)

TB5 Transmission terminal block CN52 Connector (Remote indica-tion)

SW5(I.B.)

Switch (for mode selection)

TB15 Transmission terminal block CN90 Connector (Wireless) SWE(I.B.)

Connector (emergency opera-tion)

F01 Fuse AC 250V 6.3A CN105 Connector (IT terminal) SW11(I.B.)

Switch (1s digit address set)

ZNR01,02

Varistor CN2A Connector (0-10V Analog in-put)

SW12(I.B.)

Switch (10ths digit address set)

DSA Arrester FS Float switch SW14(I.B.)

Switch (BRANCH No.)

X01 Aux. relay TH21 Thermistor (inlet air temp.de-tection)

SWA(I.B.)

Switch (for static pressure se-lection)

X10 Aux. relay TH22 Thermistor (piping temp.de-tection / liguid)

SWC(I.B.)

Switch (for static pressure se-lection)

ACL AC reactor (Power factor im-provement)

TH23 Thermistor (piping temp. de-tection / gas)

CN27 Connector (Damper) SW1(I.B.)

Switch (for mode selection)

Note 1 Wiring to TB2, TB5, and TB15 indicated by the double-dashed lines is on-site work.2 terminal block, connector.

0000001526.book 12 ページ 2012年9月13日 木曜日 午後7時14分

Page 18: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VI Refrigerant System Diagram ]

- 13 -HWE0812B GB

VI Refrigerant System Diagram

[1] Refrigerant system diagram

(A) Gas pipe thermistor TH23

(B) Gas pipe

(C) Liquid pipe

(D) Brazed connections

(E) Strainer (#100 mesh)

(F) Linear expansion valve

(G) Liquid pipe thermistor TH22

(H) Heat exchanger

(I) Room temperature thermistor TH21

Capacity PEFY-P20, 25, 32, 40, 50VMA(L)-E

PEFY-P63, 71, 80, 100, 125, 140VMA(L)-E

Gas pipe ø12.7 [1/2] ø15.88 [5/8]

Liquid pipe ø6.35 [1/4] ø9.52 [3/8]

(H)

(I)

(F)

(E)(E)

(C)

(G)

(A)

(D)

(B)

0000001526.book 13 ページ 2012年9月13日 木曜日 午後7時14分

Page 19: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VII Troubleshooting ]

- 14 -HWE0812B GB

VII Troubleshooting

[1] Troubleshooting

1. Check methods1. Component and check points(1) Thermistor

Room temperature thermistor (TH21)Liquid pipe thermistor (TH22)Gas pipe thermistor (TH23)Disconnect the connector and measure the resistance between terminals with a tester.(Ambient temperature 10°C - 30°C)

1) Thermistor characteristic graph

(2) Fan motor (CNMF)Refer to the page on "DC fan motor (fan motor/indoor control board)."

(3) Linear expansion valveDisconnect the connector, and measure the resistance between terminals with a tester.Refer to the next page for details.

Normal Abnormal

4.3kΩ - 9.6kΩ Open or short

(Refer to the thermistor characteristic graph below.)

Low-temperature thermistorRoom temperature thermistor (TH21)Liquid pipe thermistor (TH22)Gas pipe thermistor (TH23)Drain sensor (DS)

Thermistor R0 = 15 kΩ 3%Multiplier of B = 3480 kΩ 2%

0°C 15kΩ10°C 9.6kΩ20°C 6.3kΩ25°C 5.2kΩ30°C 4.3kΩ40°C 3.0kΩ

(A) Temperature (°C)

(B) Resistance (kΩ)

Normal Abnormal

1-5 2-6 3-5 4-6 Open or shortWhite-Red Yellow-Brown Orange-Red Blue-Brown

200 kΩ 10%

(A) Brown (D) Orange

(B) Red (E) Yellow

(C) Blue (F) White

Rt = 15 exp 3480( ) 1273+t

1273

0

10

20

30

40

50

-20 -10 0 10 20 30 40 50

(A)

(B)

1 2 3 4 5 6

LEV

M

(A)

(B)

(C)

(D)

(E)

(F) CN60

0000001526.book 14 ページ 2012年9月13日 木曜日 午後7時14分

Page 20: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VII Troubleshooting ]

- 15 -HWE0812B GB

1) Summary of linear expansion valve (LEV) operationThe LEV is operated by a stepping motor, which operates by receiving a pulse signal from the indoor control board.The LEV position changes in response to the pulse signal.

Indoor control board and LEV connection

Pulse signal output and valve operation

The output pulse changes in the following order:When the valve closes 1 -> 2 -> 3 -> 4 -> 1When the valve opens 4 -> 3 -> 2 -> 1 -> 4When the valve position remains the same, all output signals will be OFF.If any output signal is missing or if the signal remains ON, the motor vibrates and makes clicking noise.

(A) Brown (F) White

(B) Red (G) Control board

(C) Blue (H) Connection (CN60)

(D) Orange (I) Drive circuit

(E) Yellow (J) Linear expansion valve

Phase number

Output pulse1 2 3 4

ø1 ON OFF OFF ONø2 ON ON OFF OFFø3 OFF ON ON OFFø4 OFF OFF ON ON

4

3

6

5

2

1

(G)

(H)

(I)

(J) (A)

(A)

(B)

(B)

(C)

(C)

(D)

(D) (E)

(E)

(F) (F)

12VDC

M

4

6

2 3

5 1

0000001526.book 15 ページ 2012年9月13日 木曜日 午後7時14分

Page 21: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VII Troubleshooting ]

- 16 -HWE0812B GB

2) LEV operation

When the power is turned on, a pulse signal of 2200 pulses is output (valve closure signal), to bring the valve to position A.When the valve is operating normally, it is free of vibration noise. If the valve locks or when it goes from point E to A in the figure, it makes louder noise than would be heard when there is an open phase. Check for abnormal sound/vibration by placing the metal tip of a screwdriver against the valve and the handle side against your ear.

3) Troubleshooting

(a) Close

(b) Open

(c) Fully open valve (2000 pulses)

(d) No. of pulses

(e) Extra tightning (80 - 100 pulse)

(f) Valve opening degree(f)

(a)

(b)

(e)

(d)

(c)

Symptom Checking Criteria Remedy

Circuit failure on the microcomputer

Disconnect the connectors on the control board, and connect LEDs to test the cir-cuit as shown below.

Pulse signals are output for 10 seconds when the main power is turned on. If there are LEDs that do not light up at all or remain lit after the pulses are turned off, there is a problem with the driving circuit.

Replace the in-door control board if driving circuit failure is detected.

Locked LEV The motor will idle and make small clicking noise if it is run while the LEV is locked. If this clicking noise is heard both when the valve is fully closed and while it is being opened, it indicates a problem.

Replace the LEV.

Disconnected or shorted LEV motor coils

easure the resistance between the coils with a tester (red-white, red-orange, brown-yellow, brown-blue). The normal range of resistance is 150 Ω 10%

Replace the LEV.

654321

1 k LED

0000001526.book 16 ページ 2012年9月13日 木曜日 午後7時14分

Page 22: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VII Troubleshooting ]

- 17 -HWE0812B GB

(4) Drain-up mechanismMeasure the resistance between the terminals with a tester. (coil temperature 20°C)

(5) Drain float switch (CN4F)Disconnect the connector, and measure the resistance between terminals with a tester.

Valve closure fail-ure (leaky valve)

To check the LEV on the indoor unit, check the indoor unit liquid pipe temperature that appears on the operation monitor on the outdoor unit's multi control board while operating the indoor unit in question in the FAN mode and the other indoor units in the cooling mode.

Replace the LEV if the amount of leakage is great.

(A) Termistor (TH21)

Normally, the LEV is fully closed while the unit is in the FAN mode. If the valve is leaky, liquid pipe thermistor reading will be lower than normal. If it is significantly lower than the inlet temperature on the remote controller, valve closure failure is suspected. If the amount of leakage is insignificant, replacement of LEV is unnec-essary unless it is causing a problem.

Misconnections of connectors or con-tact failure

Perform a visual check for disconnected connectors.Perform a visual check of lead wire color.

Disconnect the connectors on the control board and perform a continuity test.

Symptom Checking Criteria Remedy

(A)

LEV

Normal Abnormal

340 Ω Open or short

(A) Moving part

(B) Switch

(C) Magnet

Position of the moving part Normal Abnormal

Up Short (any position but short)

Down Open (any position but open)

13

1234

(A)

(A)

(B)(C)

0000001526.book 17 ページ 2012年9月13日 木曜日 午後7時14分

Page 23: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VII Troubleshooting ]

- 18 -HWE0812B GB

2. DC fan motor (fan motor/indoor control board)1. CAUTION

A high voltage is applied to the connector for connection to the fan motor (CNMF). Do not unplug the connector CNMF with the unit energized to avoid damage to the indoor control board and fan motor.

2. TroubleshootingSymptom: Indoor unit fan does not run.

Check fan motor connector contact (CNMF).

Replace the indoor control board.

Replace the indoor control board.

Fix the connection.

Yes

No

Yes

No

Yes

No

Check the fan motor position thermistor signal.Get the motor to make a full rotation or more, and measure the voltage at the test point VFG.(same with the voltage between fan connector 7 (+) and 4(-))

Is the fan motor connector (CNMF) fully inserted?

Is the voltage within the normal range?

Replace the motor.Are 0VDC and 15VDC displayed alternately?

Check the power supply.Measure the voltage at the indoor control board.

310 - 340VDC (same with the voltage between fan connector 1 (+) and 4(-))

15VDC (same with the voltage between fan connector 5 (+) and 4(-)) 1 - 6.5VDC (same with the voltage between fan connector 6 (+) and 4(-))

[Values for Vsp are the values that are measured with the fan motor in operation. Vsp is 0V when the fan motor is stopped.]

VDCPower supply voltage

0000001526.book 18 ページ 2012年9月13日 木曜日 午後7時14分

Page 24: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VII Troubleshooting ]

- 19 -HWE0812B GB

3. Address switch settingMake sure that power to the unit is turned off.

1. When using an ME remote controller, set the address with the rotary switches (SW11, SW12).Address setting is not required when the unit remote controller is used.On-site address setting is required for the indoor units to run.

2. Address settings vary in different systems.Refer to the section on address setting in the outdoor unit installation manual.

3. Address is set with a combination of SW12 (10's digit) and SW11 (1's digit).To set the address to "3," set SW12 to "0" and SW11 to "3."To set the address to "25," set SW 12 to "2" and SW 11 to "5."

(A) Indoor unit control board

(B) Factory setting

ONOFF

SW4

(A)

(B)Please see the WIRING LABEL on the control box.

body7.fm 19 ページ 2012年9月19日 水曜日 午前11時56分

Page 25: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VII Troubleshooting ]

- 20 -HWE0812B GB

4. Voltage test points on the control board1. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA(L)-E

F01 Fuse(AC 250V 6.3A)

CND Power supply voltage (220 - 240VAC)

CN2M For M-NET transmission cable connection (24 - 30VDC)

SWE Emergency operation

SW2 Capacity setting

SW4 Function setting

SW3 Function setting

CN32 Remote start/stop adapter

CN3A For MA remote controller cable connection (10 - 13 VDC (Between 1 and 3.))

CN52 Remote display

CN51 Centralized control

CN41 JAMA standard HA terminal A

CN44 Thermistor (liquid/gas tempera-ture)

CN4F Float thermistor

CN20 Thermistor (Inlet temperature)

CNMF Fan motor output1 - 4: 310 - 340 VDC5 - 4: 15 VDC6 - 4: 0 - 6.5 VDC7 - 4: Stop 0 or 15 VDC

Run 7.5 VDC(0 - 15 pulse)

CNP Drain-up mechanism output (200VAC)

(*1)

VFG Voltage on the (-) side of PC51 and C25(Same with the voltage between 7 (+) and 4 (-) of CNMF)

VCC Voltage between the C25 pins 15 VDC(Same with the voltage between 5 (+) and 4 (-) of CNMF)

Vsp Voltage between the C53 pins0VDC (with the fan stopped)1 - 6.5VDC (with the fan in opera-tion)(Same with the voltage between 6 (+) and 4 (-) of CNMF)

CN3A

CN2M

SW4

CND

F01

CN32Indoor controller board

Power supply board

SW3

PC51(*1)

CN41CN51CN52

CN20

CN4FCN44

C25(*1)

C53(*1)

CNMF

SWESW2

CNP

0000001526.book 20 ページ 2012年9月13日 木曜日 午後7時14分

Page 26: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VII Troubleshooting ]

- 21 -HWE0812B GB

5. Dipswitch setting (Factory setting)1. Function setting(1) SW1

1) Adress board

(2) SW3

1) Indoor control boardDipswitch settings must be made while the unit is stopped.

Switch position Function Switch setting

ON OFF

1 Active Thermistor (Intake air thermistor)

Built-in thermistor on the remote controller

Indoor unit

2 Filter clogging detection Available Unavailable

3 Filter life 2500 hr 100 hr

4 Outdoor air intake Enabled Disabled

5 Remote display Thermo-ON signal Fan output

6 Humidifier operation During heating mode During heating operation

7 Fan speed Low Very low

8 Fan speed at heating Thermo-OFF Preset fan speed Follows the setting of SW1-7

9 Auto restart after power failure Enabled Disabled

10 Power start/stop Enabled Disabled

Factory setting

Switch position Function Switch setting

ON OFF

1 Unit type Cooling only Heat pump

2 - - -

3 - - -

4 - - -

5 - - -

6 - - -

7 - - -

8 Heating 4-deg up Disabled Enabled

9 - - -

10 - - -

Factory setting

PEFY-P25, 40, 63, 71, 80, 100, 125, 140VMA(L)-EPEFY-P20VMA(L)-E PEFY-P32, 50VMA(L)-E

0000001526.book 21 ページ 2012年9月13日 木曜日 午後7時14分

Page 27: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VII Troubleshooting ]

- 22 -HWE0812B GB

2. Capacity code setting(1) SW21) Indoor control board

Dipswitch settings must be made while the unit is stopped.Factory settingThe switches are set to correspond to the unit capacity.

3. Model setting(1) SW41) Indoor control board

Dipswitch settings must be made while the unit is stopped.

Note: Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller off). There is no need to power cycle the unit.

4. Power voltage setting(1) SW51) Indoor control board

Dipswitch settings must be operated with the main power turned OFF.

Factory settingPlease see the WIRING LABEL on the control box.

Factory settingPlease see the WIRING LABEL on the control box.

Set SW5 to 240V side when the power supply is 240 volts.When the power supply is 220 and 230 volts, set SW5 to 220V side.

PEFY-P25VMA(L)-EPEFY-P20VMA(L)-E PEFY-P32VMA(L)-E PEFY-P40VMA(L)-E

PEFY-P50VMA(L)-E PEFY-P63VMA(L)-E PEFY-P71VMA(L)-E PEFY-P80VMA(L)-E

PEFY-P100VMA(L)-E PEFY-P125VMA(L)-E PEFY-P140VMA(L)-E

body7.fm 22 ページ 2012年9月19日 水曜日 午前11時53分

Page 28: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VII Troubleshooting ]

- 23 -HWE0812B GB

5. External static pressure(1) SWA, SWC1) Indoor control board

Note: Changes that are made to the dipswitches SWA and SWC immediately become effective regardless of the unit's operation status (RUN/STOP) or the remote controller status (ON/OFF).

6. 1s and 10ths digits(1) SW11, SW12 (Rotary switch)

The use of a network remote controller (PAR-F27MEA) requires address setting. 1) Indoor control board

Address settings must be made while the unit is stopped.

7. Connection No. setting(1) SW14 (Rotary switch)

This switch is used when the unit connected to an R2 series of outdoor unit. 1) Indoor control board

Note: Changes to the dipswitches SW11, SW12, SW14, and SW15 must be made while the unit is stopped and the remote controller is OFF.

All models Factory setting

Factory setting

Factory setting

35Pa

1 2 3

SWA SWC

50Pa

1 2 3

SWA SWC

70Pa

1 2 3

SWA SWC

100Pa

1 2 3

SWA SWC

150Pa

123

SWA SWC1

2

1

2

1

2

1

2

1

2

1 2 3

SWA SWC

1

2

0000001526.book 23 ページ 2012年9月13日 木曜日 午後7時14分

Page 29: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VIII Disassembly Procedure ]

- 24 -HWE0812B GB

VIII Disassembly Procedure

[1] Disassembly Procedure

1. Control boxExercise caution when removing heavy parts.

1. Removing the control box cover(1) Remove the three fixing screws on the cover (A) to re-

move it.

Fig.1

Fig.2

(A)

0000001526.book 24 ページ 2012年9月13日 木曜日 午後7時14分

Page 30: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VIII Disassembly Procedure ]

- 25 -HWE0812B GB

2. Thermistor (Intake air)Exercise caution when removing heavy parts.

1. Remove the control box cover according to the procedure in section [1].

2. Remove the thermistor.(1) Pull out the thermistor holder (B) and thermistor (C) on

the control box.

Fig.3

(B), (C)

0000001526.book 25 ページ 2012年9月13日 木曜日 午後7時14分

Page 31: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VIII Disassembly Procedure ]

- 26 -HWE0812B GB

3. DrainpanExercise caution when removing heavy parts.

1. Removing the filter and the bottom plate(1) Push down the tab on the filter, and pull out the filter in

the direction of the arrow 1.(2) Remove the fixing screws on the bottom plate (D), (E) to

remove it.

Fig.4

2. Removing the drainpan(1) Pull out the drain pan in the direction of the arrow 2.

Fig.5

NoteDrain the water out of the drain pan before removing it.

(D) (E)

0000001526.book 26 ページ 2012年9月13日 木曜日 午後7時14分

Page 32: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VIII Disassembly Procedure ]

- 27 -HWE0812B GB

4. Thermistor (Gas pipe) (Liquid pipe)Exercise caution when removing heavy parts.

1. Remove the drain pan according to the procedure in sec-tion [1].

2. Removing the Heat exchanger cover(1) Remove the four fixing screws on the heat exchanger cov-

er (F) to remove it.

Fig.6

3. Removing the thermistor(1) Remove the thermistor (G) from the thermistor holder (H)

on the copper tube.

Thermistor sizeLiquid pipe: ø8mmGas pipe: ø6mm

Fig.7

(F)

HEX

(G), (H)

0000001526.book 27 ページ 2012年9月13日 木曜日 午後7時14分

Page 33: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VIII Disassembly Procedure ]

- 28 -HWE0812B GB

5. Fan and fan motorExercise caution when removing heavy parts.

1. Removing the filter and the bottom plate(1) Push down the tab on the filter, and pull out the filter in the

direction of the arrow 1.(2) Remove the fixing screws on the bottom plate (J) to re-

move it.

Fig.8

(a) Tab

2. Removing the fan casing (bottom half)(1) Squeeze the tabs on the fan casing to remove it in the di-

rection of arrow 2.

Fig.9

3. Removing the motor cable(1) Remove the motor cable threw the rubber bush.4. Removing the fan motor and the Sirocco fan(1) Remove the two motor fixing screws to remove the motor

and the Sirocco fan in the direction of arrow 3.

Fig.10

(2) Remove the four fan case fixing screws to take the top half of the fan casing off.

Fig.11

(J)

(a)

0000001526.book 28 ページ 2012年9月13日 木曜日 午後7時14分

Page 34: PEFY-P20VMA(L)-E, PEFY-P71VMA(L)-E PEFY-P25VMA(L)-E, …planetaklimata.com.ua/...Electric_PEFY-P_VMA-E_Service_Manual_Eng.pdf · HWE0812B ii GB Precautions for handling units for

[ VIII Disassembly Procedure ]

- 29 -HWE0812B GB

6. Heat exchangerExercise caution when removing heavy parts.

1. Remove the drain pan according to the procedure in section [1].

2. Remove the heat exchanger cover according to the proce-dure in section [4] 2.

3. Removing the cover(1) Remove the five fixing screws on the cover (K) to remove it.

Fig.12

(K) Pipe support plate

4. Removing the Heat exchanger(1) Remove the fixing screws on the heat exchanger (M) to re-

move it.

Fig.13

(K)

(M)

0000001526.book 29 ページ 2012年9月13日 木曜日 午後7時14分