PE Soltns for PQ Problems

Embed Size (px)

Citation preview

  • 8/13/2019 PE Soltns for PQ Problems

    1/12

    Review

    Power-electronic solutions to power quality problems

    Ambra Sanninoa,*, Jan Svensson b, Tomas Larsson c

    a Department of Electric Power Engineering, Chalmers University of Technology, SE-41296 Gothenburg, Swedenb ABB Utilities, Light Competence Center, Gothenburg, Sweden

    c ABB Utilities, Vasteras, Sweden

    Abstract

    In this paper, an overview of power-electronic based devices for mitigation of power quality phenomena is given. The concept ofcustom power is highlighted. Both devices for mitigation of interruptions and voltage dips (sags) and devices for compensation of

    unbalance, flicker and harmonics are treated. The attention is focused on medium-voltage applications. Details about field

    experience are given and recent research results are reported. It is shown that custom power devices provide in many cases higher

    performance compared with traditional mitigation methods. However, the choice of the most suitable solution depends on the

    characteristics of the supply at the point of connection, the requirements of the load and economics.

    # 2003 Elsevier Science B.V. All rights reserved.

    Keywords: Power quality; Power electronics; Custom power

    1. Introduction

    Power quality phenomena include all possible situa-tions in which the waveform of the supply voltage

    (voltage quality) or load current (current quality)

    deviate from the sinusoidal waveform at rated frequency

    with amplitude corresponding to the rated rms value for

    all three phases of a three-phase system. The wide range

    of power quality disturbances covers sudden, short-

    duration deviations, e.g. impulsive and oscillatory

    transients, voltage dips (or sags), short interruptions,

    as well as steady-state deviations, such as harmonics and

    flicker[1]. One can also distinguish, based on the cause,

    between disturbances related to the quality of the supply

    v

    oltage and those related to the quality of the currenttaken by the load.

    To the first class belong, among others, voltage dips

    and interruptions, mostly caused by faults in the power

    system. These disturbances may cause tripping of

    sensitive electronic equipment with disastrous con-

    sequences in industrial plants, where tripping of critical

    equipment can bear the stoppage of the whole produc-

    tion, with high costs associated [2]. One can say that in

    this case it is the source that disturbs the load. To a voidconsistent money losses, industrial customers often

    decide to install mitigation equipment to protect their

    plants from such disturbances.

    The second class covers phenomena due to low

    quality of the current drawn by the load. In this case,

    it is the load that disturbs the source. A typical example

    is current harmonics drawn by disturbing loads like

    diode rectifiers, or unbalanced currents drawn by

    unbalanced loads. A more complicated case is light

    flicker, which is caused by voltage fluctuations, in turn

    caused by rapidly varying loads supplied by a weak

    network.Customers do not experience any direct production

    loss related to the occurrence of these power quality

    phenomena. But poor quality of the current taken by

    many customers together will ultimately result in low

    quality of the power delivered to other customers: e.g.

    both harmonics and unbalanced currents ultimately

    cause distortion and, respectively, unbalance in the

    voltage as well. Therefore, proper standards are issued

    to limit the quantity of harmonic currents, unbalance

    and/or flicker that a load may introduce, e.g. [3]. To

    comply with limits set by the standards, customers often

    have to install mitigation equipment. The need for

    * Corresponding author. Tel.: /46-31-772-1631; fax: /46-31-772-

    1633.

    E-mail addresses: [email protected] (A.

    Sannino), [email protected] (J. Svensson), tomas.x.larsson

    @se.abb.com(T. Larsson).

    Electric Power Systems Research 66 (2003) 71/82

    www.elsevier.com/locate/epsr

    0378-7796/03/$ - see front matter# 2003 Elsevier Science B.V. All rights reserved.

    doi:10.1016/S0378-7796(03)00073-7

    mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]
  • 8/13/2019 PE Soltns for PQ Problems

    2/12

    devices for mitigation of the second class of phenomena

    is thus induced by regulatory effort.

    For both reasons described above, there is a growing

    interest in equipment for mitigation of power quality

    disturbances, especially in newer devices based on power

    electronics called custom power devices [4,5], able to

    deliver customized solutions to power quality problems.This paper provides an overview of power-electronic

    based devices to be installed at medium-voltage level for

    mitigation of power quality phenomena. According to

    the above classification, there are two major classes of

    mitigation equipment. Reactive power compensation

    and harmonic cancellation devices are mostly connected

    in shunt at the load bus, with the purpose of injecting a

    current to correct the current taken by the load.

    Mitigation of flicker will be treated in Section 2 and

    harmonic filtering in Section 3. Voltage dips and

    interruption mitigation devices are normally connected

    between the supply and the load, in order to correct thesupply voltage. These devices are described inSection 4.

    Conclusions are finally drawn inSection 5.

    2. Flicker mitigation

    Arc furnace operation has traditionally been the cause

    of flicker problems on medium-voltage and high-voltage

    systems. Lately, wind turbines have also been reported

    to cause this phenomenon [6]. For flicker mitigation, a

    number of different methods are available, which differ

    in performance, feasibility and cost [7]. Electrical

    methods for flicker reduction deal with the arc furnacecurrent and can be grouped in direct and indirect

    methods. The direct methods include apparatus that

    alter the arc furnace current directly and are connected

    in series with the furnace. Indirect methods do not

    intervene on the arc furnace current, but tackle its

    effects indirectly with a mitigating device connected in

    parallel with the furnace by injecting compensating

    current.

    A method to reduce flicker is selecting carefully the

    arc furnace power in-feed. Special transformer config-

    urations for furnace supply have been used for flicker

    reduction [8,9]. Reinforcing the grid is an effectivemeans of flicker mitigation but it is expensive and,

    therefore, sometimes adopted when a future expansion

    of the arc furnace plant is foreseen. The reinforcement

    may, however, not always be possible due to environ-

    mental impact.

    With a so-called dimmer inserted in series with the

    arc furnace, its current can to some extent be controlled

    [10]. The dimmer is a series device equipped with anti-

    parallel thyristors and a series reactor. The disadvantage

    is the slow response time and the high harmonic content.

    Due to the high rating of the device, it also becomes

    rather costly.

    Series capacitors have also been investigated and

    installed for this purpose [11]. A capacitor in series

    with the arc furnace with a proper value of capacitance

    is capable of canceling the reactance between the source

    and the arc furnace. However, the risk of sub-synchro-

    nous resonance (SSR) for series compensated lines has

    contributed to reluctance to install series capacitors.Moreover, the influence of the resistance of the grid is

    not taken into account.

    By inserting a linear reactor in series with the arc

    furnace, the short-circuit current of the furnace is

    reduced thanks to the higher total impedance. Further-

    more, increased reactance in the circuit means larger

    phase shifts between voltage and current and thereby a

    more stable electric arc. However, the series reactor

    must be selected with care since high values of the series

    impedance will reduce the furnace power and thereby

    the steel production rate. Saturable reactors in series

    have also been used to quickly cut current peaks due tofor instance short-circuit in the arc furnace[12].

    However, the most used devices for flicker mitigation

    are by far the static var compensator (SVC) and the D-

    Statcom, described in the following.

    2.1. Static var compensator (SVC)

    An SVC can be used for ac voltage control by

    generation and absorption of reactive power by means

    of passive elements. It can also be used for balancing

    unsymmetrical loads. As shown in Fig. 1, it is normally

    constituted by one thyristor controllable reactor (TCR)and a number of thyristor switched capacitor (TSC)

    branches[13]. The value of the reactance of the inductor

    is changed continuously by controlling the firing angle

    of the thyristors, while each capacitor can only be

    switched on and off at the instants corresponding to the

    current zero crossings, in order to avoid inrush currents

    in the capacitors. With this arrangement, the SVC can

    generate continuously variable reactive power in a

    Fig. 1. Principle scheme of an SVC.

    A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8272

  • 8/13/2019 PE Soltns for PQ Problems

    3/12

    specified range, and the size of the TCR is limited to the

    rating of one TSC branch. Obviously, the size of the

    reactor limits the power that can be absorbed in the

    inductive range.

    The SVC can be found in applications such as power

    line compensation[14], compensation of railway feeding

    system[15], reducing disturbance from rolling mills[16]and arc furnace compensation [17] (both for reactive

    power supply and for flicker mitigation). The ability to

    absorb changes in reactive power makes to some extent

    the SVC suitable for flicker reduction. In this case, the

    SVC normally consists of a TCR branch with a filter (no

    TSC). An SVC installed together with an arc furnace not

    only reduces the flicker, but also, thanks to the stabilized

    ac voltage, increases the steel production and its quality

    [18]. However, the ability of the SVC to mitigate flicker

    is limited by its low speed of response.

    2.2. D-Statcom

    Among the advantages of using forced-commutated

    converters are the ability of both produce and consume

    active and reactive power. The active power can also be

    controlled independently of the reactive power and vice

    versa. Moreover, using a voltage source converter (VSC)

    with pulse-width modulation (PWM) gives a faster

    converter control, which is needed for flicker mitigation

    purposes.

    To reduce harmonics and switching losses per valve

    when using gate turn-off thyristors (GTOs), a number of

    possible converter schemes have been proposed, like 12-

    pulse, 24-pulse, 36-pulse [19]or even 48-pulse [20]. Forexample, a 12-pulse connection can be achieved with

    two converter bridges connected in parallel via two

    transformers, one star- and one delta-connected.

    A forced-commutated VSC with PWM operation

    today seems to be the most suitable apparatus for

    flicker mitigation purposes [21]. Recent progresses in

    voltage and current ratings of the valves allow using

    integrated gate bipolar transistors (IGBTs) with high

    switching frequencies, which further improves the speed

    of response. A shunt-connected VSC mounting IGBTs

    and operated with PWM is normally referred to as

    Statcom or D-Statcom, as it is normally installed atdistribution levels [5]. Manufacturers commercializing

    this product with different names have realized a

    number of successful installations in the latest years

    [22,23].

    In the study reported in[24], the VSC is found to be

    superior to other flicker mitigation methods such as the

    SVC and the series saturable reactor. Using an SVC, the

    PST (flicker) value of the voltage at the entrance of the

    arc furnace plant, initially set to 3.8, could be reduced to

    2.4 or approximately 60% of its initial value. Combining

    the SVC with a saturable reactor in the studied system,

    unity PST could be reached. A disadvantage, however,

    was that the active power of the arc furnace was reduced

    by about 20%. With a VSC with proper control

    algorithm, a PST equal to 0.65 could be reached. This

    corresponds to a decrease of more than 80%. Field

    measurements have been performed to verify the

    performance [25,26]. In Fig. 2, the reactive current of

    the arc furnace and the response of the mitigation deviceare shown for a steel manufacturer operating a 31.5/37.8

    MVA electrical arc furnace together with a ladle furnace

    rated 5.9/7.7 MVA [26]. The current from the device

    clearly follows the arc furnace current. The result is a

    consistent mitigation of the flicker (by about 3.5 times)

    with the device in operation, as shown by the flicker

    measurements ofFig. 3, carried out in accordance with

    the IEC method[27].

    3. Harmonics mitigation

    In order to remove current harmonics from the grid,

    passive or active shunt-filters are used. Passive filters for

    harmonic reduction provide low impedance paths for

    current harmonics. Thus, the current harmonics flow

    into the shunt filters instead of back to the supply. The

    passive filter consists of series LC filters tuned for

    specific harmonics, normally combined with a high-

    pass filter used to eliminate the rest of the higher-order

    current harmonics. The drawbacks with passive filters

    are that they are strongly dependent on the system

    impedance, which depends on the distribution network

    configuration and the loads. Therefore, the system

    impedance, which changes continuously, strongly influ-ences the filtering characteristics. In the worst case an

    unwanted resonance can occur between the filter and the

    system. This may cause the passive filter to act as a

    sink for harmonic currents from other sources in the

    grid. Therefore, the passive filter can be overloaded by a

    current higher than the rated value. Finally, the

    capacitors of the passive filter produce reactive power,

    which may not necessarily be needed for power factor

    correction.

    A shunt active filter consists of a controllable voltage

    source behind a reactance acting as a current source.

    The VSC based shunt active filter is by far the mostcommon type used today, due to its well-known

    topology and straightforward installation procedure. It

    consists of a dc-link capacitor, power electronic switches

    and filter inductors between the VSC and the grid (Fig.

    4). The operation of shunt active filters is based on

    injection of current harmonics in phase with the load

    current harmonics, thus eliminating the harmonic con-

    tent of the line current.

    When using active filters, it is possible to choose the

    current harmonics to be filtered and the degree of

    attenuation. The size of the VSC can be limited by

    using selective filtering and removing only those current

    A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /82 73

  • 8/13/2019 PE Soltns for PQ Problems

    4/12

    harmonics that exceed a certain level, e.g. the level set in

    IEEE Std. 519-1992 [3]. Together with the active

    filtering, it is also possible to control the power factor

    by injecting or absorbing reactive power from the load.

    A common active filtering method is based on using

    the instantaneous active and reactive power [28]. This

    method detects all non-sinusoidal components and,

    when it is implemented with a hysteresis current con-

    troller, allows obtaining good filtering performance.

    However, the hysteresis current controller has thedisadvantages of a varying switching frequency, which

    produces a continuous harmonics spectrum. When the

    instantaneous active and reactive power method is

    implemented together with sub-oscillated PWM [29]

    and vector current control[30], an inferior performance

    is obtained when the switching frequency is low. This

    may be desired in order to keep the switching losses

    down. The low performance is caused by the response

    time of the current controlled VSC, which leads to a

    phase shift between the reference currents and the

    output currents. Various methods for compensating

    for phase shifts have been presented, e.g. [31].

    Selective active filtering can be based on variousmethods. Some of the proposed selective active filters

    use bandpass filters to extract individual current har-

    monics[32]. Unfortunately, this method results in phase

    Fig. 2. Reactive current of the arc furnace and the compensator (SVC light).

    Fig. 3. Flicker levels with and without mitigation with VSC-based compensator for the electrical arc furnace (EAF) in Hagfors, Sweden[26].

    A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8274

  • 8/13/2019 PE Soltns for PQ Problems

    5/12

    shifts, which reduce the filtering performance. A better

    solution is to use a Fourier series to determine individual

    harmonics [31]. Another method uses synchronously

    rotating coordinate system for each of the individual

    current harmonics [33]. Several methods have beenanalyzed and compared in[34].

    4. Mitigation of voltage dips and short interruptions

    Short-duration, shallow dips can be mitigated by

    improving equipment tolerance characteristics [35/37].

    Long-duration, deep dips and interruptions can be

    avoided by changing structure and/or operation of the

    power system [38]. However, for industrial customers,

    who do not normally have access to system or equip-

    ment improvement, the installation of additional miti-gation equipment is often the only option left to achieve

    the desired quality of supply at the system-load inter-

    face.

    Traditional devices described in [2] include motor-

    generator sets, which use the rotational energy stored in

    a flywheel to provide power to the load during the dip,

    and constant voltage, or ferro-resonant, transformers

    (CVTs). More modern equipment based on power

    electronics will be described here. The static series

    compensator (SSC) and the static transfer switch

    (STS) are analyzed more in detail. Other devices are

    also briefly described.

    4.1. Static series compensator

    The SSC is a VSC connected in series on the

    distribution feeder, which provides a controllable

    source, whose voltage adds to the source voltage to

    obtain the desired load voltage. Depending on the type

    of control implemented, it is possible to use the

    additional voltage source to correct supply voltage

    unbalance, perform load voltage regulation, compensate

    for voltage dips and cancel low-order supply voltage

    harmonics. The principle of series injection for dip

    compensation is depicted in the phasor diagram of

    Fig. 5 where Vsag; Vinj; Vload and Iload are the phasors

    of supply voltage affected by dip, injected voltage, load

    voltage and current, respectively.

    Manufacturers that are pioneering this technology

    with the name of dynamic voltage restorer (DVR)

    have realized installations, among others, at a yarn

    manufacture[39], semiconductor plants[40,41], a utility

    feeder serv

    ing industrial and commercial customers inCanada [42], a large paper mill in Scotland [43]. The

    compensation system is installed at medium voltage

    level and protected loads have typical ratings between

    0.5 MVA and around 21 MVA [40]. This solution,

    although costly, is very attractive for large sensitive

    industrial customers, as it allows for protection of the

    entire plant through the installation of only one device.

    However, being a series device, this compensator has the

    obvious disadvantage of not protecting the load against

    interruptions [44]. Moreover, sensitive loads inside the

    plant will not be protected against dips originating

    within the plant.

    One possible configuration that realizes the series-

    injection principle is shown in Fig. 6. The converter

    generates the proper voltage to be injected for compen-

    sation, and therefore, will often be required to operate

    with unbalanced switching functions for the three

    phases. The converter is normally a three-phase two-

    level VSC with IGBTs[39], but also the use of a three-

    Fig. 4. Principle scheme of active filtering using VSC.

    Fig. 5. Phasor diagram of the series injection principle.

    Fig. 6. Scheme of series compensator for voltage dip mitigation.

    A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /82 75

  • 8/13/2019 PE Soltns for PQ Problems

    6/12

    phase three-level neutral-point-clamped (NPC) conver-

    ter mounting integrated gate-commutated thyristors

    (IGCTs) has been reported in a DVR by a major

    manufacturer [41]. The valves on the three legs of the

    converter are switched independently of each other,

    normally according to a PWM pattern, with high

    switching frequency. This ensures fast response and asmooth voltage waveform. The voltage rating of the

    converter dictates the maximum injected voltage, which

    is thus the maximum (three-phase) dip magnitude that

    can be compensated for. Existing DVRs are usually

    sized for 50% maximum voltage injection.

    A second-order LC filter is normally inserted in

    between the converter and the transformer to cancel

    high-frequency harmonic components in the converter

    output voltage. Another configuration proposed in-

    cludes a line-side filter composed by the leakage

    inductance of the injection transformer combined with

    a capacitor on the line-side of the transformer [41].However, with this configuration the capacitor must be

    sized for the higher system voltage and the series

    transformer must be sized for the total rms current,

    including harmonics[45].

    The controller of the SSC can be designed to

    compensate for voltage dips by only providing reactive

    power, i.e. by injecting a voltage in quadrature with the

    load current. However, it is shown in [46] that the

    compensation capability of the device is very limited in

    these conditions, especially for high values of the power

    factor. Therefore, an energy storage device is normally

    connected to the dc bus of the converter to provide the

    energy necessary for the compensation. Commerciallyavailable DVRs use large capacitor banks for energy

    storage [40]. A SSC unit utilizing superconducting

    magnetic energy storage (SMES) technology installed

    in 1997 is mentioned in[47]. The device is rated at 750

    kVA and provides 2.4 MJ of stored energy. No details

    are known on field experience. Experimental results on a

    prototype are presented in[48]. The problem with a wide

    application of SMES is at present the very high cost.

    The capacity of the energy storage device has a big

    impact on the compensation capability of the system, as

    it ultimately determines the ride-through time for the

    load. A method for minimizing the size of the necessaryenergy storage device has been recently proposed in[49].

    The availability of high-capacity storage at reasonable

    cost is a key factor for widespread application of this

    technology.

    A controller for the SSC designed in the rotating dq-

    reference frame, which can achieve fast response and

    handle transients properly, has been proposed in [50].

    However, this controller is designed under the assump-

    tion of symmetrical supply voltages, i.e. it only works

    with balanced dips. The controller proposed in [51]

    implements a fast technique for positive and negative

    sequence detection and thereby is able to compensate for

    unbalanced dips. Moreover, the effect of the converter

    output filter, which causes voltage drop and phase shift

    in the fundamental component of the injected voltage, is

    taken into account and compensated for in the con-

    troller presented in [51] by using a back-calculation of

    the voltage drop, known the filter parameters. An

    alternative is to apply a feedback of the capacitorvoltage, as done for example in [50]. Even better

    transient performance is obtained by adding another

    loop that controls the current through the converter

    valves as in[52]. The principle of series injection can also

    be applied to cancellation of low-order supply voltage

    harmonics. To do this, the controller must be able to

    deal with other frequencies than the fundamental. A

    controller based on several rotating frames is proposed

    in[53].

    An interesting case study presented in[54]involves an

    industrial facility that produces microprocessors for the

    personal computer industry starting from pure siliconwafers. In 12 months before the installation of the SSC,

    the plant had experienced 14 voltage dips that were

    capable of adversely affecting production. The semi-

    conductor plant is served by three 69 kV lines feeding

    two transformers and the total plant load is about 45

    MVA. Two independent SSCs, each rated 6 MVA at

    12.47 kV with 1800 kJ of stored energy, were installed

    inside the semiconductor plant, one on each of the two

    12.47 kV feeders. Monitoring performed after installa-

    tion revealed that the SSCs compensated for over 72

    power quality disturbances that could have caused

    process interruptions for the end-user. To demonstrate

    the performance, a measured three-phase dip down to65% occurring on the grid and the resulting load voltage

    due to SSC operation are shown in Fig. 7.

    4.2. Static transfer switch

    The STS consists of two three-phase static switches,

    each constituted in turn by two anti-parallel thyristors

    per phase (Fig. 8). Normally, the static switch on the

    primary source is fired regularly, while the other one is

    off. In the event of a voltage disturbance, the STS is

    used to transfer the load from the preferred source to an

    alternative healthy source [55]. This results in a veryeffective way of mitigating the effects of both interrup-

    tions and voltage dips by limiting their duration as seen

    by the load. The success of the STS is mainly due to its

    rather low cost compared with other solutions. A

    requirement is that a secondary in-feed, independent

    from the main source (e.g. a feeder to another substa-

    tion), must be available. Therefore, this solution is

    particularly attractive for installations that already

    have mechanical transfer systems, where upgrading to

    a static system does not require major changes in the

    layout of the distribution system. Formerly available

    only for low voltages, STS systems are now advertized

    A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8276

  • 8/13/2019 PE Soltns for PQ Problems

    7/12

    for higher voltages and load ratings, which make them

    suitable for high-power industrial applications: they

    would be capable to protect loads up to 35 MVA

    supplied at a voltage as high as 35 kV [56]. The

    application of a 15 kV, 600 A STS to an automotive

    component plant is described in detail in [57].

    Note, however, that the STS cannot protect against

    dips originating in the transmission system, which will

    also affect the alternative supply. Yet, a significant

    improvement can be achieved in the performance of the

    industrial system against faults at distribution level,

    which normally cause long duration dips and short

    interruptions.

    The load will still see a disturbance during the interval

    in which the transfer takes place, therefore, it must be

    completed so quickly that the duration of the resulting

    disturbance at the load terminals is short enough not to

    cause equipment trips.

    The STS can ensure a fast response due to the

    phenomenon of fast switching, usually referred to as

    Make-Before-Break switching (MBB). This takes

    place when the thyristors of the secondary-source static

    switch are fired, thus initiating the transfer, before thecurrent through the primary-source switch has reached

    zero. Depending on the circuit conditions, a current

    starts flowing in the secondary-source switch in a

    direction such that it forces the primary-source switch

    to turn off very quickly. Transfer times of less than one

    quarter of cycle are quite common for MBB transfer

    [55].

    An example of the dip mitigation performance of the

    STS is given inFig. 9(a) which shows the source voltages

    together with the response of the detection system,

    denoted as fault signal, for a 70% dip (single-phase).

    The dip is detected in about 1 ms and the transfer occursimmediately after. As a result, only a notch ofvery short

    duration affects the load voltage (Fig. 9(b)).

    However, MBB transfer must be inhibited when this

    would lead to a circulating current between the two

    sources, thus spreading the fault to the healthy portion

    of the system. In this case, the control system must

    inhibit firing and wait until the current through the

    thyristors in the faulted source switch has become zero,

    thus realizing a slow or Break-Before-Make transfer

    (BBM). This result is accomplished by monitoring the

    load current, together with the voltages of the two

    sources.

    Fig. 7. Measured three-phase dip on grid side (top) and load voltage (bottom) due to SSC operation, from[5].

    Fig. 8. Structure of the STS (single-phase scheme).

    A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /82 77

  • 8/13/2019 PE Soltns for PQ Problems

    8/12

    The performance of the STS concerning transfer time

    has been analyzed in [58,59]. Results presented allow

    concluding that in general the speed of operation of a

    STS is high enough to realize a seamless transfer for

    sensitive loads. Note, however, that the transfer time

    increases even more in case of regenerative load, e.g.

    induction motors [60,61]. In industrial plants with high

    percentage of rotating load, a specific performance

    study could be needed to assess the actual improvement

    obtained with installation of the STS.

    4.3. Other voltage dip/interruption mitigation devices

    Electronic tap changers (Fig. 10) can be mounted on a

    dedicated transformer for the sensitive load, in order to

    change its turns ratio according to changes in the input

    voltage [62]. This device, called static voltage regulator

    (SVR) [5], is placed between the supply and the load.

    Part of the secondary winding supplying the load is

    divided into a number of sections, which are connected

    or disconnected by fast static switches, thus allowing

    regulation of the secondary voltage in steps. This should

    allow the output voltage to be brought back to a higher

    level than 90% of nominal value, even for severe voltage

    dips. Thyristor-based switches, which can only be turned

    on once per cycle, are used; therefore, the compensation

    is accomplished with a time delay of at least one half-

    cycle. No existing installations are known to date.

    A standard solution for low-power equipment is

    constituted by the UPS (Uninterruptible Power Supply),

    which consists of a diode rectifier followed by an

    inverter (Fig. 11). The energy storage device is usuallya battery block connected to the dc link. During normal

    operation, power coming from the ac supply is rectified

    and then inverted. The batteries remain in standby mode

    and only serve to keep the dc bus voltage constant.

    During a voltage dip or interruption, the energy released

    by the battery block maintains the voltage at the dc bus.

    Depending on the storage capacity, the battery block

    can supply the load for minutes or even hours. Low cost,

    simple operation and control have made the UPS the

    standard solution for low-power equipment like com-

    puters. For higher-power loads the costs associated with

    conversion losses and maintenance of the batteriesbecome too high and this solution no longer appears

    to be economically feasible.

    Note that, although based on power electronics, the

    UPS due to its low-power/low-voltage ratings is not a

    Fig. 9. (a) Source voltages and fault signal, (b) load voltage and current for a 70% dip.

    Fig. 10. SVR. Fig. 11. Uninterruptible power supply.

    A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8278

  • 8/13/2019 PE Soltns for PQ Problems

    9/12

    custom power device according to the definition given

    in[5], which covers devices installed in 1 kV through 38

    kV distribution systems. However, it is listed here for

    completeness.

    A static shunt compensator, normally used for flicker

    mitigation and active filtering purposes, equipped with

    an isolation switch for disconnection from the distribu-tion feeder, results in the backup source ofFig. 12, also

    called Backup Stored Energy System (BSES) [5]. This

    constitutes an alternative to the UPS to avoid high

    steady-state losses due to the energy conversions as the

    load power increases. As soon as a disturbance is

    detected, the sensitive load is isolated from the power

    system by a static switch and supplied by the VSC. For

    storing the necessary energy, batteries (Transportable

    Battery Energy Storage System, TBESS [63]) or small-

    size SMES systems can be used [64]. The main advan-

    tages of SMES as compared with the batteries are the

    reduced size and lower maintenance requirements.It has been pointed out that the necessity of an energy

    storage device of adequate capacity is the biggest

    limitation for the SSC. An alternative is to h ave a

    second converter connected to the line upstream of the

    series compensator to supply the dc bus (Fig. 13). In this

    way, energy is transferred to the dc bus continuously.

    On the other hand, power coming from the line will be

    greatly reduced during a dip. This rectifying stage must

    be properly designed to operate correctly with reduced

    (and possibly unbalanced) input voltage during the dip

    (note that this problem is overcome if the rectifier is

    placed on the load side as in [42], but at the expenses ofincreased rating of the SSC). By choosing a shunt-

    connected VSC instead of a simple diode rectifier for

    this purpose, other control and regulation functions, e.g.

    active current filtering or flicker mitigation, can be

    performed, thus realizing a multi-purpose compensa-

    tor. This concept has been proposed with the name of

    unified power quality conditioner (UPQC) [65].

    The device ofFig. 14is obtained by a combination of

    a STS and a SSC in series. Total protection can thus be

    obtained against interruptions and voltage dips, with the

    STS taking care of interruptions and dips originated by

    faults in the distribution system, which are long and

    deep [1] and would deplete the energy storage of theSSC. The SSC will instead compensate for the voltage

    dips originated by faults in the transmission systems,

    which the STS cannot handle. Note that transmission-

    system dips are normally short and shallow[1]. Hence,

    the size of the energy storage of the SSC can be greatly

    reduced, with a consequent reduction of the cost of the

    device.

    5. Conclusions

    In this paper, an overview of the use of powerelectronics for mitigating power quality phenomena

    has been given. The concept of custom power has

    been highlighted. Advantages and drawbacks of several

    custom power devices have been pointed out. Both

    shunt devices, protecting the source from the load, and

    series devices, protecting the load from the source, have

    been covered. Details about field experience have been

    given and recent research results have been reported.

    It has been shown that custom power devices provide

    in many cases higher performance compared with

    traditional mitigation methods. However, the choice of

    the most suitable solution depends ultimately on theFig. 12. Backup power source.

    Fig. 13. Scheme of the unified power quality conditioner (UPQC).

    Fig. 14. Single-phase scheme of a combined STS/SSC.

    A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /82 79

  • 8/13/2019 PE Soltns for PQ Problems

    10/12

    characteristics of the supply at the point of connection,

    the requirements of the load and economics, i.e. the

    customer value added by the installation of a power-

    electronics based device.

    Acknowledgements

    The work of Ambra Sannino was supported by a

    Marie Curie Fellowship of the European Community

    program IHP under contract number HPMF-CT-2000-

    00922 and partly also by ELFORSK, Sweden under

    Elektra project no. 3378.

    References

    [1] M.H.J. Bollen, Understanding Power Quality Problems: VoltageSags and Interruptions, IEEE Press, New York, 1999.

    [2] M.F. McGranaghan, D.R. Mueller, M.J. Samotyj, Voltage sags

    in industrial systems, IEEE Trans. Ind. Applic. 29 (2) (1993) 397/

    403.

    [3] IEEE recommended practices and requirements for harmonic

    control in electrical power systems, IEEE Std 519-1992, 12 April

    1993.

    [4] N. Hingorani, Introducing custom power, IEEE Spectrum 32 (6)

    (1995) 41/48.

    [5] IEEE P1409 Distribution Custom Power Task Force, Trial use

    guide for application of power electronics for power quality

    improvement on distribution systems rated 1/38 kV, Draft 9,

    January 24, 2003.

    [6] T. Thiringer, Power quality measurements performed on a low-

    voltage grid equipped with two wind turbines, IEEE Trans.Energy Conversion 11 (3) (1996) 601/606.

    [7] C. Poumarede, X. Lombard, P.G. Therond, S. Saadate, M.

    Zouiti, A. Ekstrom, T. Larsson, Present and future flicker

    mitigation techniques, CIGRE Regional Meeting on Power

    Quality*/Assessment of Impact, 10/11 September 1997, New

    Delhi, India, pp. VI 13/24.

    [8] T.J.E. Miller, Reactive Power Control in Electric Systems, Wiley,

    1982.

    [9] O. Todnem, Lysbueovner, Compendium from the Norwegian

    Technical University, Trondheim, September 1983, in Norwegian.

    [10] J.A. Mulcahy, H.A. Kojori D. Burn, V. Scaini, A new technology

    for the control of AC electric arc furnaces, Fifth European

    Electric Steel Congress, Paris, 19/23 June 1995.

    [11] B. King, K.J. Olejniczak, An evaluation of static var compensa-

    tion strategies for voltage flicker mitigation in electric distribution

    systems, Seventh International Conference on Harmonics and

    Power Quality, Las Vegas, 1996, pp. 6/11.

    [12] P. Samuelsson, G. Gensini, G. Mavridis, Danarc technology for

    electric arc furnaces, Iron Steel Eng. 72 (6) (1995) 21/25.

    [13] N. Hingorani, L. Gyugyi, Understanding FACTS, IEEE Press,

    New York, 2000.

    [14] D.L. Dickmander, B.H. Thorvaldsson, G.A. Stromberg, D.L.

    Osborn, A.E. Poitras, D.A. Fisher, Control system design and

    performance verification for the Chester, Maine static var

    compensator, IEEE Trans. Power Deliv. 7 (3) (1992) 1492/1503.

    [15] M. Goto, T. Nakamura, Y. Mochinaga, Y. Ishii, Static negative-

    phase-sequence current compensator for railway power supply

    system, International Conference on Electric Railways in a United

    Europe, 1995, pp. 78/82.

    [16] A. Werme, P. Hyvonen, R. Grunbaum, Improved power quality

    and economy by rolling mill by means of an SVC, Steel Times

    International, March 1998, pp.44/46.

    [17] H. Frank, K. Pettersson, Raising the production of arc furnaces

    by stabilizing the voltage with thyristor switched capacitors,

    ASEA J. 50 (1) (1977) 9/16.

    [18] R. Grunbaum, T. Gustafsson, T. Johansson, U. Olsson, Energy

    and environmental savings in steel making by means of SVCLight, 2000 Electric Furnace Conference Proceedings.

    [19] Y. Sumi, Y. Harumoto, T. Hasegawa, M. Yano, K. Ikeda, T.

    Matsuura, New static var control using force-commutated con-

    verters, IEEE Trans. Power Apparatus Syst. PAS-100 (9) (1981)

    4216/4224.

    [20] C. Schauder, M. Gernhardt, E. Stacey, T. Lemak, L. Gyugyi,

    T.W. Cease, A. Edris, Operation of /// 100 MVAr TVA

    STATCON, IEEE Trans. Power Deliv. 12 (4) (1997) 1805/1811.

    [21] T. Larsson, A PWM-operated voltage source converter for flicker

    mitigation, European Power Electronics Conference EPE, Trond-

    heim, Norway, September 8/10, 1996, pp.3.1016/3.1020.

    [22] T. Larsson, R. Grunbaum, B. Ratering-Schnitzler, SVC light: a

    utilitys aid to restructuring its grid, IEEE Power Engineering

    Society Winter Meeting, 2000, vol. 4, pp. 2577/2581.

    [23] G.F. Reed, J.E. Greaf, T. Matsumoto, Y. Yonehata, M. Takeda,T. Aritsuka, Y. Hamasaki, F. Ojima, A.P. Sidell, R.E. Chervus,

    C.K. Nebecker, Application of a 5 MVA, 4.16 kV D-STATCOM

    system for voltage flicker compensation at Seattle Iron and

    Metals, IEEE Power Engineering Society Winter Meeting, 2000,

    vol. 3, pp. 1605/1611.

    [24] T. Larsson, Voltage source converters for mitigation of flicker

    caused by arc furnaces, Ph.D. thesis, ISSN 1100/1631, TRITA-

    EHE 9801, Royal Institute of Technology, Stockholm, Sweden,

    May 1998.

    [25] R. Grunbaum, T. Gustafsson, T. Johansson, SVC Light: A

    Powerful Flicker Mitigator, Iron & Steel Society, Pittsburgh,

    USA, 1999.

    [26] R. Grunbaum, T. Johansson, U. Olsson, SVC light: evaluation of

    first installation at Hagfors, Sweden, Cigre session 2000, 13/14/36-

    03.[27] IEC 61 000-4-15, Electromagnetic Compatibility (EMC). Part 4:

    Testing and Measurements Techniques*/Section 15: Flicker-

    meter. Functional and design specifications, Bureau Central

    Commission Electrotechnique International, Geneva, Switzer-

    land, November 1997.

    [28] H. Akagi, Y. Kanazawa, A. Nabae, Instantaneous reactive power

    compensators comprising switching devices without energy sto-

    rage components, IEEE Trans. Ind. Applic. IA-20 (1984) 625/

    630.

    [29] J. Holtz, Pulsewidth modulation for electronic power conversion,

    Proc. IEEE 82 (1994) 1194/1214.

    [30] R. Ottersten, J. Svensson, Vector current controlled voltage

    source converter*/deadbeat control and saturation strategies,

    IEEE Trans. Power Electron. 17 (2) (2002) 279/285.

    [31] F. Abrahamsen, A. David, Adjustable speed drive with active

    filtering capability for harmonic current compensation, in Proc.

    IEEE PESC95 Atlanta, GA, June 18/22, 1995, vol. 2, pp. 1137/

    1143.

    [32] M. Nowak, R. Barlik, P. Grochal, Three phase line converter with

    optimising influence on power system, in: Proceedings of Sixth

    European Conference Power Electronics and Applications

    (EPE95), Seville, Spain, September 19/21, 1995, vol. 2, pp.

    534/539.

    [33] S.-G. Jeong, M.-H. Woo, DSP-based active power filter with

    predictive current control, IEEE Trans. Ind. Electron. 44 (1997)

    329/336.

    [34] J. Svensson, R. Ottersten, Shunt active filtering ofvector current-

    controlled VSC at a moderate switching frequency, IEEE Trans.

    Ind. Applic. 35 (5) (1999) 1083/1090.

    A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8280

  • 8/13/2019 PE Soltns for PQ Problems

    11/12

  • 8/13/2019 PE Soltns for PQ Problems

    12/12

    grid-connected converters, wind power and power

    quality.

    Tomas Larsson received his M.Sc. degree and Ph.D

    degree from the Royal Institute of Technology, Stock-

    holm, Sweden in 1991 and 1998, respectively. Since

    March 1998 he is working for ABB where he mainly has

    been involved in system design for projects dealing with

    reactive power compensation. His interests include

    voltage source converters in power quality applications,

    in particular flicker mitigation.

    A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8282