Upload
cheshankar
View
221
Download
0
Embed Size (px)
Citation preview
8/13/2019 PE Soltns for PQ Problems
1/12
Review
Power-electronic solutions to power quality problems
Ambra Sanninoa,*, Jan Svensson b, Tomas Larsson c
a Department of Electric Power Engineering, Chalmers University of Technology, SE-41296 Gothenburg, Swedenb ABB Utilities, Light Competence Center, Gothenburg, Sweden
c ABB Utilities, Vasteras, Sweden
Abstract
In this paper, an overview of power-electronic based devices for mitigation of power quality phenomena is given. The concept ofcustom power is highlighted. Both devices for mitigation of interruptions and voltage dips (sags) and devices for compensation of
unbalance, flicker and harmonics are treated. The attention is focused on medium-voltage applications. Details about field
experience are given and recent research results are reported. It is shown that custom power devices provide in many cases higher
performance compared with traditional mitigation methods. However, the choice of the most suitable solution depends on the
characteristics of the supply at the point of connection, the requirements of the load and economics.
# 2003 Elsevier Science B.V. All rights reserved.
Keywords: Power quality; Power electronics; Custom power
1. Introduction
Power quality phenomena include all possible situa-tions in which the waveform of the supply voltage
(voltage quality) or load current (current quality)
deviate from the sinusoidal waveform at rated frequency
with amplitude corresponding to the rated rms value for
all three phases of a three-phase system. The wide range
of power quality disturbances covers sudden, short-
duration deviations, e.g. impulsive and oscillatory
transients, voltage dips (or sags), short interruptions,
as well as steady-state deviations, such as harmonics and
flicker[1]. One can also distinguish, based on the cause,
between disturbances related to the quality of the supply
v
oltage and those related to the quality of the currenttaken by the load.
To the first class belong, among others, voltage dips
and interruptions, mostly caused by faults in the power
system. These disturbances may cause tripping of
sensitive electronic equipment with disastrous con-
sequences in industrial plants, where tripping of critical
equipment can bear the stoppage of the whole produc-
tion, with high costs associated [2]. One can say that in
this case it is the source that disturbs the load. To a voidconsistent money losses, industrial customers often
decide to install mitigation equipment to protect their
plants from such disturbances.
The second class covers phenomena due to low
quality of the current drawn by the load. In this case,
it is the load that disturbs the source. A typical example
is current harmonics drawn by disturbing loads like
diode rectifiers, or unbalanced currents drawn by
unbalanced loads. A more complicated case is light
flicker, which is caused by voltage fluctuations, in turn
caused by rapidly varying loads supplied by a weak
network.Customers do not experience any direct production
loss related to the occurrence of these power quality
phenomena. But poor quality of the current taken by
many customers together will ultimately result in low
quality of the power delivered to other customers: e.g.
both harmonics and unbalanced currents ultimately
cause distortion and, respectively, unbalance in the
voltage as well. Therefore, proper standards are issued
to limit the quantity of harmonic currents, unbalance
and/or flicker that a load may introduce, e.g. [3]. To
comply with limits set by the standards, customers often
have to install mitigation equipment. The need for
* Corresponding author. Tel.: /46-31-772-1631; fax: /46-31-772-
1633.
E-mail addresses: [email protected] (A.
Sannino), [email protected] (J. Svensson), tomas.x.larsson
@se.abb.com(T. Larsson).
Electric Power Systems Research 66 (2003) 71/82
www.elsevier.com/locate/epsr
0378-7796/03/$ - see front matter# 2003 Elsevier Science B.V. All rights reserved.
doi:10.1016/S0378-7796(03)00073-7
mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]8/13/2019 PE Soltns for PQ Problems
2/12
devices for mitigation of the second class of phenomena
is thus induced by regulatory effort.
For both reasons described above, there is a growing
interest in equipment for mitigation of power quality
disturbances, especially in newer devices based on power
electronics called custom power devices [4,5], able to
deliver customized solutions to power quality problems.This paper provides an overview of power-electronic
based devices to be installed at medium-voltage level for
mitigation of power quality phenomena. According to
the above classification, there are two major classes of
mitigation equipment. Reactive power compensation
and harmonic cancellation devices are mostly connected
in shunt at the load bus, with the purpose of injecting a
current to correct the current taken by the load.
Mitigation of flicker will be treated in Section 2 and
harmonic filtering in Section 3. Voltage dips and
interruption mitigation devices are normally connected
between the supply and the load, in order to correct thesupply voltage. These devices are described inSection 4.
Conclusions are finally drawn inSection 5.
2. Flicker mitigation
Arc furnace operation has traditionally been the cause
of flicker problems on medium-voltage and high-voltage
systems. Lately, wind turbines have also been reported
to cause this phenomenon [6]. For flicker mitigation, a
number of different methods are available, which differ
in performance, feasibility and cost [7]. Electrical
methods for flicker reduction deal with the arc furnacecurrent and can be grouped in direct and indirect
methods. The direct methods include apparatus that
alter the arc furnace current directly and are connected
in series with the furnace. Indirect methods do not
intervene on the arc furnace current, but tackle its
effects indirectly with a mitigating device connected in
parallel with the furnace by injecting compensating
current.
A method to reduce flicker is selecting carefully the
arc furnace power in-feed. Special transformer config-
urations for furnace supply have been used for flicker
reduction [8,9]. Reinforcing the grid is an effectivemeans of flicker mitigation but it is expensive and,
therefore, sometimes adopted when a future expansion
of the arc furnace plant is foreseen. The reinforcement
may, however, not always be possible due to environ-
mental impact.
With a so-called dimmer inserted in series with the
arc furnace, its current can to some extent be controlled
[10]. The dimmer is a series device equipped with anti-
parallel thyristors and a series reactor. The disadvantage
is the slow response time and the high harmonic content.
Due to the high rating of the device, it also becomes
rather costly.
Series capacitors have also been investigated and
installed for this purpose [11]. A capacitor in series
with the arc furnace with a proper value of capacitance
is capable of canceling the reactance between the source
and the arc furnace. However, the risk of sub-synchro-
nous resonance (SSR) for series compensated lines has
contributed to reluctance to install series capacitors.Moreover, the influence of the resistance of the grid is
not taken into account.
By inserting a linear reactor in series with the arc
furnace, the short-circuit current of the furnace is
reduced thanks to the higher total impedance. Further-
more, increased reactance in the circuit means larger
phase shifts between voltage and current and thereby a
more stable electric arc. However, the series reactor
must be selected with care since high values of the series
impedance will reduce the furnace power and thereby
the steel production rate. Saturable reactors in series
have also been used to quickly cut current peaks due tofor instance short-circuit in the arc furnace[12].
However, the most used devices for flicker mitigation
are by far the static var compensator (SVC) and the D-
Statcom, described in the following.
2.1. Static var compensator (SVC)
An SVC can be used for ac voltage control by
generation and absorption of reactive power by means
of passive elements. It can also be used for balancing
unsymmetrical loads. As shown in Fig. 1, it is normally
constituted by one thyristor controllable reactor (TCR)and a number of thyristor switched capacitor (TSC)
branches[13]. The value of the reactance of the inductor
is changed continuously by controlling the firing angle
of the thyristors, while each capacitor can only be
switched on and off at the instants corresponding to the
current zero crossings, in order to avoid inrush currents
in the capacitors. With this arrangement, the SVC can
generate continuously variable reactive power in a
Fig. 1. Principle scheme of an SVC.
A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8272
8/13/2019 PE Soltns for PQ Problems
3/12
specified range, and the size of the TCR is limited to the
rating of one TSC branch. Obviously, the size of the
reactor limits the power that can be absorbed in the
inductive range.
The SVC can be found in applications such as power
line compensation[14], compensation of railway feeding
system[15], reducing disturbance from rolling mills[16]and arc furnace compensation [17] (both for reactive
power supply and for flicker mitigation). The ability to
absorb changes in reactive power makes to some extent
the SVC suitable for flicker reduction. In this case, the
SVC normally consists of a TCR branch with a filter (no
TSC). An SVC installed together with an arc furnace not
only reduces the flicker, but also, thanks to the stabilized
ac voltage, increases the steel production and its quality
[18]. However, the ability of the SVC to mitigate flicker
is limited by its low speed of response.
2.2. D-Statcom
Among the advantages of using forced-commutated
converters are the ability of both produce and consume
active and reactive power. The active power can also be
controlled independently of the reactive power and vice
versa. Moreover, using a voltage source converter (VSC)
with pulse-width modulation (PWM) gives a faster
converter control, which is needed for flicker mitigation
purposes.
To reduce harmonics and switching losses per valve
when using gate turn-off thyristors (GTOs), a number of
possible converter schemes have been proposed, like 12-
pulse, 24-pulse, 36-pulse [19]or even 48-pulse [20]. Forexample, a 12-pulse connection can be achieved with
two converter bridges connected in parallel via two
transformers, one star- and one delta-connected.
A forced-commutated VSC with PWM operation
today seems to be the most suitable apparatus for
flicker mitigation purposes [21]. Recent progresses in
voltage and current ratings of the valves allow using
integrated gate bipolar transistors (IGBTs) with high
switching frequencies, which further improves the speed
of response. A shunt-connected VSC mounting IGBTs
and operated with PWM is normally referred to as
Statcom or D-Statcom, as it is normally installed atdistribution levels [5]. Manufacturers commercializing
this product with different names have realized a
number of successful installations in the latest years
[22,23].
In the study reported in[24], the VSC is found to be
superior to other flicker mitigation methods such as the
SVC and the series saturable reactor. Using an SVC, the
PST (flicker) value of the voltage at the entrance of the
arc furnace plant, initially set to 3.8, could be reduced to
2.4 or approximately 60% of its initial value. Combining
the SVC with a saturable reactor in the studied system,
unity PST could be reached. A disadvantage, however,
was that the active power of the arc furnace was reduced
by about 20%. With a VSC with proper control
algorithm, a PST equal to 0.65 could be reached. This
corresponds to a decrease of more than 80%. Field
measurements have been performed to verify the
performance [25,26]. In Fig. 2, the reactive current of
the arc furnace and the response of the mitigation deviceare shown for a steel manufacturer operating a 31.5/37.8
MVA electrical arc furnace together with a ladle furnace
rated 5.9/7.7 MVA [26]. The current from the device
clearly follows the arc furnace current. The result is a
consistent mitigation of the flicker (by about 3.5 times)
with the device in operation, as shown by the flicker
measurements ofFig. 3, carried out in accordance with
the IEC method[27].
3. Harmonics mitigation
In order to remove current harmonics from the grid,
passive or active shunt-filters are used. Passive filters for
harmonic reduction provide low impedance paths for
current harmonics. Thus, the current harmonics flow
into the shunt filters instead of back to the supply. The
passive filter consists of series LC filters tuned for
specific harmonics, normally combined with a high-
pass filter used to eliminate the rest of the higher-order
current harmonics. The drawbacks with passive filters
are that they are strongly dependent on the system
impedance, which depends on the distribution network
configuration and the loads. Therefore, the system
impedance, which changes continuously, strongly influ-ences the filtering characteristics. In the worst case an
unwanted resonance can occur between the filter and the
system. This may cause the passive filter to act as a
sink for harmonic currents from other sources in the
grid. Therefore, the passive filter can be overloaded by a
current higher than the rated value. Finally, the
capacitors of the passive filter produce reactive power,
which may not necessarily be needed for power factor
correction.
A shunt active filter consists of a controllable voltage
source behind a reactance acting as a current source.
The VSC based shunt active filter is by far the mostcommon type used today, due to its well-known
topology and straightforward installation procedure. It
consists of a dc-link capacitor, power electronic switches
and filter inductors between the VSC and the grid (Fig.
4). The operation of shunt active filters is based on
injection of current harmonics in phase with the load
current harmonics, thus eliminating the harmonic con-
tent of the line current.
When using active filters, it is possible to choose the
current harmonics to be filtered and the degree of
attenuation. The size of the VSC can be limited by
using selective filtering and removing only those current
A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /82 73
8/13/2019 PE Soltns for PQ Problems
4/12
harmonics that exceed a certain level, e.g. the level set in
IEEE Std. 519-1992 [3]. Together with the active
filtering, it is also possible to control the power factor
by injecting or absorbing reactive power from the load.
A common active filtering method is based on using
the instantaneous active and reactive power [28]. This
method detects all non-sinusoidal components and,
when it is implemented with a hysteresis current con-
troller, allows obtaining good filtering performance.
However, the hysteresis current controller has thedisadvantages of a varying switching frequency, which
produces a continuous harmonics spectrum. When the
instantaneous active and reactive power method is
implemented together with sub-oscillated PWM [29]
and vector current control[30], an inferior performance
is obtained when the switching frequency is low. This
may be desired in order to keep the switching losses
down. The low performance is caused by the response
time of the current controlled VSC, which leads to a
phase shift between the reference currents and the
output currents. Various methods for compensating
for phase shifts have been presented, e.g. [31].
Selective active filtering can be based on variousmethods. Some of the proposed selective active filters
use bandpass filters to extract individual current har-
monics[32]. Unfortunately, this method results in phase
Fig. 2. Reactive current of the arc furnace and the compensator (SVC light).
Fig. 3. Flicker levels with and without mitigation with VSC-based compensator for the electrical arc furnace (EAF) in Hagfors, Sweden[26].
A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8274
8/13/2019 PE Soltns for PQ Problems
5/12
shifts, which reduce the filtering performance. A better
solution is to use a Fourier series to determine individual
harmonics [31]. Another method uses synchronously
rotating coordinate system for each of the individual
current harmonics [33]. Several methods have beenanalyzed and compared in[34].
4. Mitigation of voltage dips and short interruptions
Short-duration, shallow dips can be mitigated by
improving equipment tolerance characteristics [35/37].
Long-duration, deep dips and interruptions can be
avoided by changing structure and/or operation of the
power system [38]. However, for industrial customers,
who do not normally have access to system or equip-
ment improvement, the installation of additional miti-gation equipment is often the only option left to achieve
the desired quality of supply at the system-load inter-
face.
Traditional devices described in [2] include motor-
generator sets, which use the rotational energy stored in
a flywheel to provide power to the load during the dip,
and constant voltage, or ferro-resonant, transformers
(CVTs). More modern equipment based on power
electronics will be described here. The static series
compensator (SSC) and the static transfer switch
(STS) are analyzed more in detail. Other devices are
also briefly described.
4.1. Static series compensator
The SSC is a VSC connected in series on the
distribution feeder, which provides a controllable
source, whose voltage adds to the source voltage to
obtain the desired load voltage. Depending on the type
of control implemented, it is possible to use the
additional voltage source to correct supply voltage
unbalance, perform load voltage regulation, compensate
for voltage dips and cancel low-order supply voltage
harmonics. The principle of series injection for dip
compensation is depicted in the phasor diagram of
Fig. 5 where Vsag; Vinj; Vload and Iload are the phasors
of supply voltage affected by dip, injected voltage, load
voltage and current, respectively.
Manufacturers that are pioneering this technology
with the name of dynamic voltage restorer (DVR)
have realized installations, among others, at a yarn
manufacture[39], semiconductor plants[40,41], a utility
feeder serv
ing industrial and commercial customers inCanada [42], a large paper mill in Scotland [43]. The
compensation system is installed at medium voltage
level and protected loads have typical ratings between
0.5 MVA and around 21 MVA [40]. This solution,
although costly, is very attractive for large sensitive
industrial customers, as it allows for protection of the
entire plant through the installation of only one device.
However, being a series device, this compensator has the
obvious disadvantage of not protecting the load against
interruptions [44]. Moreover, sensitive loads inside the
plant will not be protected against dips originating
within the plant.
One possible configuration that realizes the series-
injection principle is shown in Fig. 6. The converter
generates the proper voltage to be injected for compen-
sation, and therefore, will often be required to operate
with unbalanced switching functions for the three
phases. The converter is normally a three-phase two-
level VSC with IGBTs[39], but also the use of a three-
Fig. 4. Principle scheme of active filtering using VSC.
Fig. 5. Phasor diagram of the series injection principle.
Fig. 6. Scheme of series compensator for voltage dip mitigation.
A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /82 75
8/13/2019 PE Soltns for PQ Problems
6/12
phase three-level neutral-point-clamped (NPC) conver-
ter mounting integrated gate-commutated thyristors
(IGCTs) has been reported in a DVR by a major
manufacturer [41]. The valves on the three legs of the
converter are switched independently of each other,
normally according to a PWM pattern, with high
switching frequency. This ensures fast response and asmooth voltage waveform. The voltage rating of the
converter dictates the maximum injected voltage, which
is thus the maximum (three-phase) dip magnitude that
can be compensated for. Existing DVRs are usually
sized for 50% maximum voltage injection.
A second-order LC filter is normally inserted in
between the converter and the transformer to cancel
high-frequency harmonic components in the converter
output voltage. Another configuration proposed in-
cludes a line-side filter composed by the leakage
inductance of the injection transformer combined with
a capacitor on the line-side of the transformer [41].However, with this configuration the capacitor must be
sized for the higher system voltage and the series
transformer must be sized for the total rms current,
including harmonics[45].
The controller of the SSC can be designed to
compensate for voltage dips by only providing reactive
power, i.e. by injecting a voltage in quadrature with the
load current. However, it is shown in [46] that the
compensation capability of the device is very limited in
these conditions, especially for high values of the power
factor. Therefore, an energy storage device is normally
connected to the dc bus of the converter to provide the
energy necessary for the compensation. Commerciallyavailable DVRs use large capacitor banks for energy
storage [40]. A SSC unit utilizing superconducting
magnetic energy storage (SMES) technology installed
in 1997 is mentioned in[47]. The device is rated at 750
kVA and provides 2.4 MJ of stored energy. No details
are known on field experience. Experimental results on a
prototype are presented in[48]. The problem with a wide
application of SMES is at present the very high cost.
The capacity of the energy storage device has a big
impact on the compensation capability of the system, as
it ultimately determines the ride-through time for the
load. A method for minimizing the size of the necessaryenergy storage device has been recently proposed in[49].
The availability of high-capacity storage at reasonable
cost is a key factor for widespread application of this
technology.
A controller for the SSC designed in the rotating dq-
reference frame, which can achieve fast response and
handle transients properly, has been proposed in [50].
However, this controller is designed under the assump-
tion of symmetrical supply voltages, i.e. it only works
with balanced dips. The controller proposed in [51]
implements a fast technique for positive and negative
sequence detection and thereby is able to compensate for
unbalanced dips. Moreover, the effect of the converter
output filter, which causes voltage drop and phase shift
in the fundamental component of the injected voltage, is
taken into account and compensated for in the con-
troller presented in [51] by using a back-calculation of
the voltage drop, known the filter parameters. An
alternative is to apply a feedback of the capacitorvoltage, as done for example in [50]. Even better
transient performance is obtained by adding another
loop that controls the current through the converter
valves as in[52]. The principle of series injection can also
be applied to cancellation of low-order supply voltage
harmonics. To do this, the controller must be able to
deal with other frequencies than the fundamental. A
controller based on several rotating frames is proposed
in[53].
An interesting case study presented in[54]involves an
industrial facility that produces microprocessors for the
personal computer industry starting from pure siliconwafers. In 12 months before the installation of the SSC,
the plant had experienced 14 voltage dips that were
capable of adversely affecting production. The semi-
conductor plant is served by three 69 kV lines feeding
two transformers and the total plant load is about 45
MVA. Two independent SSCs, each rated 6 MVA at
12.47 kV with 1800 kJ of stored energy, were installed
inside the semiconductor plant, one on each of the two
12.47 kV feeders. Monitoring performed after installa-
tion revealed that the SSCs compensated for over 72
power quality disturbances that could have caused
process interruptions for the end-user. To demonstrate
the performance, a measured three-phase dip down to65% occurring on the grid and the resulting load voltage
due to SSC operation are shown in Fig. 7.
4.2. Static transfer switch
The STS consists of two three-phase static switches,
each constituted in turn by two anti-parallel thyristors
per phase (Fig. 8). Normally, the static switch on the
primary source is fired regularly, while the other one is
off. In the event of a voltage disturbance, the STS is
used to transfer the load from the preferred source to an
alternative healthy source [55]. This results in a veryeffective way of mitigating the effects of both interrup-
tions and voltage dips by limiting their duration as seen
by the load. The success of the STS is mainly due to its
rather low cost compared with other solutions. A
requirement is that a secondary in-feed, independent
from the main source (e.g. a feeder to another substa-
tion), must be available. Therefore, this solution is
particularly attractive for installations that already
have mechanical transfer systems, where upgrading to
a static system does not require major changes in the
layout of the distribution system. Formerly available
only for low voltages, STS systems are now advertized
A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8276
8/13/2019 PE Soltns for PQ Problems
7/12
for higher voltages and load ratings, which make them
suitable for high-power industrial applications: they
would be capable to protect loads up to 35 MVA
supplied at a voltage as high as 35 kV [56]. The
application of a 15 kV, 600 A STS to an automotive
component plant is described in detail in [57].
Note, however, that the STS cannot protect against
dips originating in the transmission system, which will
also affect the alternative supply. Yet, a significant
improvement can be achieved in the performance of the
industrial system against faults at distribution level,
which normally cause long duration dips and short
interruptions.
The load will still see a disturbance during the interval
in which the transfer takes place, therefore, it must be
completed so quickly that the duration of the resulting
disturbance at the load terminals is short enough not to
cause equipment trips.
The STS can ensure a fast response due to the
phenomenon of fast switching, usually referred to as
Make-Before-Break switching (MBB). This takes
place when the thyristors of the secondary-source static
switch are fired, thus initiating the transfer, before thecurrent through the primary-source switch has reached
zero. Depending on the circuit conditions, a current
starts flowing in the secondary-source switch in a
direction such that it forces the primary-source switch
to turn off very quickly. Transfer times of less than one
quarter of cycle are quite common for MBB transfer
[55].
An example of the dip mitigation performance of the
STS is given inFig. 9(a) which shows the source voltages
together with the response of the detection system,
denoted as fault signal, for a 70% dip (single-phase).
The dip is detected in about 1 ms and the transfer occursimmediately after. As a result, only a notch ofvery short
duration affects the load voltage (Fig. 9(b)).
However, MBB transfer must be inhibited when this
would lead to a circulating current between the two
sources, thus spreading the fault to the healthy portion
of the system. In this case, the control system must
inhibit firing and wait until the current through the
thyristors in the faulted source switch has become zero,
thus realizing a slow or Break-Before-Make transfer
(BBM). This result is accomplished by monitoring the
load current, together with the voltages of the two
sources.
Fig. 7. Measured three-phase dip on grid side (top) and load voltage (bottom) due to SSC operation, from[5].
Fig. 8. Structure of the STS (single-phase scheme).
A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /82 77
8/13/2019 PE Soltns for PQ Problems
8/12
The performance of the STS concerning transfer time
has been analyzed in [58,59]. Results presented allow
concluding that in general the speed of operation of a
STS is high enough to realize a seamless transfer for
sensitive loads. Note, however, that the transfer time
increases even more in case of regenerative load, e.g.
induction motors [60,61]. In industrial plants with high
percentage of rotating load, a specific performance
study could be needed to assess the actual improvement
obtained with installation of the STS.
4.3. Other voltage dip/interruption mitigation devices
Electronic tap changers (Fig. 10) can be mounted on a
dedicated transformer for the sensitive load, in order to
change its turns ratio according to changes in the input
voltage [62]. This device, called static voltage regulator
(SVR) [5], is placed between the supply and the load.
Part of the secondary winding supplying the load is
divided into a number of sections, which are connected
or disconnected by fast static switches, thus allowing
regulation of the secondary voltage in steps. This should
allow the output voltage to be brought back to a higher
level than 90% of nominal value, even for severe voltage
dips. Thyristor-based switches, which can only be turned
on once per cycle, are used; therefore, the compensation
is accomplished with a time delay of at least one half-
cycle. No existing installations are known to date.
A standard solution for low-power equipment is
constituted by the UPS (Uninterruptible Power Supply),
which consists of a diode rectifier followed by an
inverter (Fig. 11). The energy storage device is usuallya battery block connected to the dc link. During normal
operation, power coming from the ac supply is rectified
and then inverted. The batteries remain in standby mode
and only serve to keep the dc bus voltage constant.
During a voltage dip or interruption, the energy released
by the battery block maintains the voltage at the dc bus.
Depending on the storage capacity, the battery block
can supply the load for minutes or even hours. Low cost,
simple operation and control have made the UPS the
standard solution for low-power equipment like com-
puters. For higher-power loads the costs associated with
conversion losses and maintenance of the batteriesbecome too high and this solution no longer appears
to be economically feasible.
Note that, although based on power electronics, the
UPS due to its low-power/low-voltage ratings is not a
Fig. 9. (a) Source voltages and fault signal, (b) load voltage and current for a 70% dip.
Fig. 10. SVR. Fig. 11. Uninterruptible power supply.
A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8278
8/13/2019 PE Soltns for PQ Problems
9/12
custom power device according to the definition given
in[5], which covers devices installed in 1 kV through 38
kV distribution systems. However, it is listed here for
completeness.
A static shunt compensator, normally used for flicker
mitigation and active filtering purposes, equipped with
an isolation switch for disconnection from the distribu-tion feeder, results in the backup source ofFig. 12, also
called Backup Stored Energy System (BSES) [5]. This
constitutes an alternative to the UPS to avoid high
steady-state losses due to the energy conversions as the
load power increases. As soon as a disturbance is
detected, the sensitive load is isolated from the power
system by a static switch and supplied by the VSC. For
storing the necessary energy, batteries (Transportable
Battery Energy Storage System, TBESS [63]) or small-
size SMES systems can be used [64]. The main advan-
tages of SMES as compared with the batteries are the
reduced size and lower maintenance requirements.It has been pointed out that the necessity of an energy
storage device of adequate capacity is the biggest
limitation for the SSC. An alternative is to h ave a
second converter connected to the line upstream of the
series compensator to supply the dc bus (Fig. 13). In this
way, energy is transferred to the dc bus continuously.
On the other hand, power coming from the line will be
greatly reduced during a dip. This rectifying stage must
be properly designed to operate correctly with reduced
(and possibly unbalanced) input voltage during the dip
(note that this problem is overcome if the rectifier is
placed on the load side as in [42], but at the expenses ofincreased rating of the SSC). By choosing a shunt-
connected VSC instead of a simple diode rectifier for
this purpose, other control and regulation functions, e.g.
active current filtering or flicker mitigation, can be
performed, thus realizing a multi-purpose compensa-
tor. This concept has been proposed with the name of
unified power quality conditioner (UPQC) [65].
The device ofFig. 14is obtained by a combination of
a STS and a SSC in series. Total protection can thus be
obtained against interruptions and voltage dips, with the
STS taking care of interruptions and dips originated by
faults in the distribution system, which are long and
deep [1] and would deplete the energy storage of theSSC. The SSC will instead compensate for the voltage
dips originated by faults in the transmission systems,
which the STS cannot handle. Note that transmission-
system dips are normally short and shallow[1]. Hence,
the size of the energy storage of the SSC can be greatly
reduced, with a consequent reduction of the cost of the
device.
5. Conclusions
In this paper, an overview of the use of powerelectronics for mitigating power quality phenomena
has been given. The concept of custom power has
been highlighted. Advantages and drawbacks of several
custom power devices have been pointed out. Both
shunt devices, protecting the source from the load, and
series devices, protecting the load from the source, have
been covered. Details about field experience have been
given and recent research results have been reported.
It has been shown that custom power devices provide
in many cases higher performance compared with
traditional mitigation methods. However, the choice of
the most suitable solution depends ultimately on theFig. 12. Backup power source.
Fig. 13. Scheme of the unified power quality conditioner (UPQC).
Fig. 14. Single-phase scheme of a combined STS/SSC.
A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /82 79
8/13/2019 PE Soltns for PQ Problems
10/12
characteristics of the supply at the point of connection,
the requirements of the load and economics, i.e. the
customer value added by the installation of a power-
electronics based device.
Acknowledgements
The work of Ambra Sannino was supported by a
Marie Curie Fellowship of the European Community
program IHP under contract number HPMF-CT-2000-
00922 and partly also by ELFORSK, Sweden under
Elektra project no. 3378.
References
[1] M.H.J. Bollen, Understanding Power Quality Problems: VoltageSags and Interruptions, IEEE Press, New York, 1999.
[2] M.F. McGranaghan, D.R. Mueller, M.J. Samotyj, Voltage sags
in industrial systems, IEEE Trans. Ind. Applic. 29 (2) (1993) 397/
403.
[3] IEEE recommended practices and requirements for harmonic
control in electrical power systems, IEEE Std 519-1992, 12 April
1993.
[4] N. Hingorani, Introducing custom power, IEEE Spectrum 32 (6)
(1995) 41/48.
[5] IEEE P1409 Distribution Custom Power Task Force, Trial use
guide for application of power electronics for power quality
improvement on distribution systems rated 1/38 kV, Draft 9,
January 24, 2003.
[6] T. Thiringer, Power quality measurements performed on a low-
voltage grid equipped with two wind turbines, IEEE Trans.Energy Conversion 11 (3) (1996) 601/606.
[7] C. Poumarede, X. Lombard, P.G. Therond, S. Saadate, M.
Zouiti, A. Ekstrom, T. Larsson, Present and future flicker
mitigation techniques, CIGRE Regional Meeting on Power
Quality*/Assessment of Impact, 10/11 September 1997, New
Delhi, India, pp. VI 13/24.
[8] T.J.E. Miller, Reactive Power Control in Electric Systems, Wiley,
1982.
[9] O. Todnem, Lysbueovner, Compendium from the Norwegian
Technical University, Trondheim, September 1983, in Norwegian.
[10] J.A. Mulcahy, H.A. Kojori D. Burn, V. Scaini, A new technology
for the control of AC electric arc furnaces, Fifth European
Electric Steel Congress, Paris, 19/23 June 1995.
[11] B. King, K.J. Olejniczak, An evaluation of static var compensa-
tion strategies for voltage flicker mitigation in electric distribution
systems, Seventh International Conference on Harmonics and
Power Quality, Las Vegas, 1996, pp. 6/11.
[12] P. Samuelsson, G. Gensini, G. Mavridis, Danarc technology for
electric arc furnaces, Iron Steel Eng. 72 (6) (1995) 21/25.
[13] N. Hingorani, L. Gyugyi, Understanding FACTS, IEEE Press,
New York, 2000.
[14] D.L. Dickmander, B.H. Thorvaldsson, G.A. Stromberg, D.L.
Osborn, A.E. Poitras, D.A. Fisher, Control system design and
performance verification for the Chester, Maine static var
compensator, IEEE Trans. Power Deliv. 7 (3) (1992) 1492/1503.
[15] M. Goto, T. Nakamura, Y. Mochinaga, Y. Ishii, Static negative-
phase-sequence current compensator for railway power supply
system, International Conference on Electric Railways in a United
Europe, 1995, pp. 78/82.
[16] A. Werme, P. Hyvonen, R. Grunbaum, Improved power quality
and economy by rolling mill by means of an SVC, Steel Times
International, March 1998, pp.44/46.
[17] H. Frank, K. Pettersson, Raising the production of arc furnaces
by stabilizing the voltage with thyristor switched capacitors,
ASEA J. 50 (1) (1977) 9/16.
[18] R. Grunbaum, T. Gustafsson, T. Johansson, U. Olsson, Energy
and environmental savings in steel making by means of SVCLight, 2000 Electric Furnace Conference Proceedings.
[19] Y. Sumi, Y. Harumoto, T. Hasegawa, M. Yano, K. Ikeda, T.
Matsuura, New static var control using force-commutated con-
verters, IEEE Trans. Power Apparatus Syst. PAS-100 (9) (1981)
4216/4224.
[20] C. Schauder, M. Gernhardt, E. Stacey, T. Lemak, L. Gyugyi,
T.W. Cease, A. Edris, Operation of /// 100 MVAr TVA
STATCON, IEEE Trans. Power Deliv. 12 (4) (1997) 1805/1811.
[21] T. Larsson, A PWM-operated voltage source converter for flicker
mitigation, European Power Electronics Conference EPE, Trond-
heim, Norway, September 8/10, 1996, pp.3.1016/3.1020.
[22] T. Larsson, R. Grunbaum, B. Ratering-Schnitzler, SVC light: a
utilitys aid to restructuring its grid, IEEE Power Engineering
Society Winter Meeting, 2000, vol. 4, pp. 2577/2581.
[23] G.F. Reed, J.E. Greaf, T. Matsumoto, Y. Yonehata, M. Takeda,T. Aritsuka, Y. Hamasaki, F. Ojima, A.P. Sidell, R.E. Chervus,
C.K. Nebecker, Application of a 5 MVA, 4.16 kV D-STATCOM
system for voltage flicker compensation at Seattle Iron and
Metals, IEEE Power Engineering Society Winter Meeting, 2000,
vol. 3, pp. 1605/1611.
[24] T. Larsson, Voltage source converters for mitigation of flicker
caused by arc furnaces, Ph.D. thesis, ISSN 1100/1631, TRITA-
EHE 9801, Royal Institute of Technology, Stockholm, Sweden,
May 1998.
[25] R. Grunbaum, T. Gustafsson, T. Johansson, SVC Light: A
Powerful Flicker Mitigator, Iron & Steel Society, Pittsburgh,
USA, 1999.
[26] R. Grunbaum, T. Johansson, U. Olsson, SVC light: evaluation of
first installation at Hagfors, Sweden, Cigre session 2000, 13/14/36-
03.[27] IEC 61 000-4-15, Electromagnetic Compatibility (EMC). Part 4:
Testing and Measurements Techniques*/Section 15: Flicker-
meter. Functional and design specifications, Bureau Central
Commission Electrotechnique International, Geneva, Switzer-
land, November 1997.
[28] H. Akagi, Y. Kanazawa, A. Nabae, Instantaneous reactive power
compensators comprising switching devices without energy sto-
rage components, IEEE Trans. Ind. Applic. IA-20 (1984) 625/
630.
[29] J. Holtz, Pulsewidth modulation for electronic power conversion,
Proc. IEEE 82 (1994) 1194/1214.
[30] R. Ottersten, J. Svensson, Vector current controlled voltage
source converter*/deadbeat control and saturation strategies,
IEEE Trans. Power Electron. 17 (2) (2002) 279/285.
[31] F. Abrahamsen, A. David, Adjustable speed drive with active
filtering capability for harmonic current compensation, in Proc.
IEEE PESC95 Atlanta, GA, June 18/22, 1995, vol. 2, pp. 1137/
1143.
[32] M. Nowak, R. Barlik, P. Grochal, Three phase line converter with
optimising influence on power system, in: Proceedings of Sixth
European Conference Power Electronics and Applications
(EPE95), Seville, Spain, September 19/21, 1995, vol. 2, pp.
534/539.
[33] S.-G. Jeong, M.-H. Woo, DSP-based active power filter with
predictive current control, IEEE Trans. Ind. Electron. 44 (1997)
329/336.
[34] J. Svensson, R. Ottersten, Shunt active filtering ofvector current-
controlled VSC at a moderate switching frequency, IEEE Trans.
Ind. Applic. 35 (5) (1999) 1083/1090.
A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8280
8/13/2019 PE Soltns for PQ Problems
11/12
8/13/2019 PE Soltns for PQ Problems
12/12
grid-connected converters, wind power and power
quality.
Tomas Larsson received his M.Sc. degree and Ph.D
degree from the Royal Institute of Technology, Stock-
holm, Sweden in 1991 and 1998, respectively. Since
March 1998 he is working for ABB where he mainly has
been involved in system design for projects dealing with
reactive power compensation. His interests include
voltage source converters in power quality applications,
in particular flicker mitigation.
A. Sannino et al. / Electric Power Systems Research 66 (2003) 71 /8282