40
PDRP-1001/PDRP-1001A DELUGE PREACTION CONTROL PANEL Doc.# 50734 ECN 97-514 ZONE 1 ZONE 2 WATERFLOW SUPERVISORY AC POWER SYSTEM ALARM RELEASE SUPERVISORY SYSTEM TROUBLE TONE SILENCE ALARM SILENCE ALARM ACTIVATE RESET CIRCUIT TROUBLE POWER TROUBLE ALARM SILENCED A Pittway Company

PDRP-1001/PDRP-1001A - System Sensor Canada · SYSTEM ALARM RELEASE SUPERVISORY ... NFPA 16 Deluge Foam-Water Sprinkler and Foam-Water Spray Systems ... PDRP-1001/PDRP-1001A Installation

Embed Size (px)

Citation preview

PDRP-1001/PDRP-1001A

D E L U G E ■■■■■ P R E A C T I O N C O N T R O L P A N E L

Doc.# 50734 ECN 97-514

ZONE 1

ZONE 2

WATERFLOW

SUPERVISORY

AC POWER

SYSTEM ALARM

RELEASE

SUPERVISORY

SYSTEMTROUBLE

TONESILENCE

ALARMSILENCE

ALARMACTIVATE RESET

CIRCUITTROUBLE

POWERTROUBLE

ALARMSILENCED

A Pittway Company

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

2

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

3

Table of ContentsI NFPA Standards ..............................................................4II Additional Information ...................................................4

1.0 The PDRP-1001/PDRP-1001A ....................................................... 51.1 Features ........................................................................................................ 51.2 Circuits .......................................................................................................... 51.3 Optional Boards ............................................................................................ 71.4 Remote Annunciator ..................................................................................... 81.5 Optional Meters ............................................................................................. 81.6 Specifications................................................................................................ 9

2.0 System Operation .........................................................................112.1 System Status LEDs ................................................................................... 112.2 Control Switches ......................................................................................... 122.3 Zone Status LEDs ....................................................................................... 122.4 Supervisory ................................................................................................. 132.5 Zone Disable .............................................................................................. 132.6 Last Event Recall ........................................................................................ 13

3.0 Installation Procedure ..................................................................143.1 General ....................................................................................................... 143.2 Initiating Device Circuits ............................................................................. 153.3 4-Wire Smoke Detector Connections .......................................................... 163.4 Output Circuits ............................................................................................ 173.5 Power .......................................................................................................... 183.6 Optional Modules ........................................................................................ 203.7 Dip Switch Location and Descriptions ........................................................ 253.8 Setting Mode of Operation .......................................................................... 26

Appendix A: Power Calculations ......................................................27Appendix B: Device Compatibility Chart .........................................29Appendix C: NFPA Standard Specific Requirements ....................33Troubleshooting Table ........................................................................38

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

4

I NFPA StandardsThis control panel complies with the following NFPA standards:NFPA 13 Sprinkler SystemsNFPA 15 Water Spray SystemsNFPA 16 Foam-Water Deluge and Foam-Water Spray SystemsNFPA 72 Central Station Signaling Systems (Automatic, Manual, and Waterflow). ProtectedPremises Unit (Requires NOTI-FIRE 911AC DACT or MS5012 Slave Communicator).*NFPA 72 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems.NFPA 72 Auxiliary (Automatic, Manual, and Waterflow) Fire Alarm Systems. (Requires 4XTM.)NFPA 72 Remote Station (Automatic, Manual, and Waterflow) Fire Alarm Systems. (Requires4XTM or NOTI•FIRE 911AC DACT.) *

* Applications which require the NOTI-FIRE 911AC is not FM approved.

II Additional Information Note: Before proceeding, the installer should be familiar with the following documents and standards:

NFPA Standards:NFPA 13 Installation of Sprinkler SystemsNFPA 15 Water Spray Fixed SystemsNFPA 16 Deluge Foam-Water Sprinkler and Foam-Water Spray SystemsNFPA 72 Installation, Maintenance, and Use of Central Station Signaling SystemsNFPA 72 Local, Auxiliary, Remote Station and Proprietary Fire Alarm SystemsNFPA 72 Automatic Fire DetectorsNFPA 72 Installation, Maintenance, and Use of Notification Appliances for Fire Alarm SystemsNFPA 72 Testing Procedures for Signaling Systems

Underwriters Laboratories Documents:UL 38 Manually Actuated Signaling BoxesUL 217 Smoke Detectors, Single and Multiple StationUL 228 Door Closers - Holders for Fire Alarm SystemsUL 268 Smoke Detectors for Fire Alarm SystemsUL 268A Smoke Detectors for Duct ApplicationsUL 346 Waterflow Indicators for Fire Alarm SystemsUL 464 Audible Signaling AppliancesUL 521 Heat Detectors for Fire Alarm SystemsUL 864 Standard for Control Units for Fire Alarm SystemsUL 1481 Power Supplies for Fire Alarm SystemsUL 1638 Visual Signaling AppliancesUL 1971 Signaling Devices for the Hearing ImpairedCAN/ULC-S524-M91 Standard for Installation of Fire Alarm SystemsCAN/ULC-S527-M87 Standard for Control Units for Fire Alarm Systems

Other:NEC Article 300 Wiring MethodsNEC Article 760 Fire Alarm SystemsApplicable Local and State Building CodesRequirements of the Local Authority Having JurisdictionNotifier Device Compatibility Document, 15378.ADA Americans with Disabilities Act

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

5

1.0 The PDRP-1001/PDRP-1001A

1.1 Features

• Microprocessor-controlled• Alarm and trouble resound• Four Style B/D Initiating Device Circuits• Two Style Y/Z Notification Appliance Circuits• Two Style Y Release Circuits• General alarm and trouble relays• Optional module for 4 zone/function relays (4XZM)• Optional transmitter module (4XTM). Complies with

NFPA 72 Auxiliary and Remote Station Fire AlarmSystems.

• Optional volt/amp meter module (4XMM)• Optional supervised remote annunciator

(RZA-4X). Requires LED Interface Module (4XLM)• Optional digital communicator (NOTI•FIRE 911AC).*• Complies with NFPA 72 Central Station and NFPA 72

Remote Station Fire Alarm Systems.• Designed for sprinkler standards NFPA 13, 15, and 16.• Disable/enable controls per initiating zone.• Last Event Recall• Battery/Earth fault supervision• Fuse protection on all Notification/Release Circuits

• RMS regulated output power, 2.25 amps• 7 amp/hour to 15 amp/hour battery options,

up to 90 hours standby• Resettable and non-resettable regulated

power outputs• Extensive transient protection• Watchdog timer to supervise microproces-

sor (includes MICRO FAIL LED)• Output circuits protected against false

activations.• Slide-in zone identification labels• Steel cabinet 14.5" wide by 16" high by 5"

deep• Dead-front dress panel option (DP-4X)• Trim ring for flush mount between 16" center

studs (TR-4XR)• Cross-zone (double-interlock) option• Municipal Box output.• Interface Module (4XLM)• Dual hazard operation• Adjustable discharge timer

* Applications which require the NOTI-FIRE 911AC is not FM approved.

1.2 CircuitsInput CircuitsManual Release/Detector Circuit 1 (Style B/D)Detector Circuit 2 (Style B/D)Waterflow (Style B/D)Supervisory (Style B/D)

Output circuits (optional auxiliary relay module (4XZM) tracks these four circuits)Alarm/Waterflow Bell (Style Y/Z)Waterflow/Supervisory Bell (Style Y/Z)Releasing Circuit 1 (Style Y)Supervisory Bell/Release Circuit 2 (Style Y)

Front Panel Control SwitchesSwitch 1 Tone SilenceSwitch 2 Alarm SilenceSwitch 3 Alarm ActivateSwitch 4 System Reset

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

6

Figure 1.0-1: PDRP-1001/PDRP-1001A Installation Diagram

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

7

1.3 Optional Boards

The PDRP-1001/PDRP-1001A has mounting slots for two option boards. Any two of the three optionmodules may be installed.

Transmitter Module (4XTM NOTIFIER)The Transmitter Module provides a supervised output for local energymunicipal box transmitter (for NFPA 72-1993 Auxiliary Fire Alarm System)and alarm and trouble reverse polarity circuits (for NFPA 72-1993 RemoteStation Fire Alarm System). Also included is a DISABLE switch and disabletrouble LED.

As a jumper option, the alarm reverse polarity circuit will open on trouble if no alarmexists.

LED Interface Module (4XLM NOTIFIER)The LED Interface Module supports the RZA-4X Remote Annunciatormodule. Annunciator wiring is supervised for open conditions by this module.The Annunciator Driver Module mounts to the main board, occupying one ofthe two option connectors.

Zone Relay Module (4XZM NOTIFIER)The Zone Relay module provides Form-C contacts for the following:

• Alarm/Waterflow Bell• Waterflow/Supervisory Bell• Releasing Circuit 1• Supervisory Bell/Release Circuit 2• System Alarm• System Trouble

As a jumper option, the first four relays described above can be made silenceable.

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

8

LED Interface Module (4XLM NOTIFIER)Maximum voltage/current, each output: 27.6V/8mA.

Note: Outputs are power limited.

Zone Relay Module (4XZM NOTIFIER)Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).

1.4 Remote Annunciator

Remote Annunciator (RZA-4X NOTIFIER)The Remote Annunciator mounts on a standard single-gang box, and provides LEDindication of the following:

• Alarm/Waterflow Bell (red)• Waterflow/Supervisory Bell (red)• Releasing Circuit 1 (red)• Supervisory Bell/Release Circuit 2 (red)• System Trouble LED (yellow)

A Local Trouble Sounder and Silence Switch are also provided. All LED wiring issupervised for open conditions. Any open condition will cause the System TroubleLED to illuminate.

Note: The Remote Annunciator requires the use of an LED Interface module (4XLM).

1.5 Optional Meters

Voltage, Current Meters (4XMM NOTIFIER)The Meter Module provides a voltmeter to measure the voltage across thebatteries and an ammeter to measure the charging current to the batteries. Themeters are provided as a assembly that mounts to the lower left corner of thecabinet.

Transmitter Module (4XTM NOTIFIER)

For Local Energy Municipal Box service (NFPA 72 Auxiliary Fire Alarm System)Supervisory current: 5.0 mA.Trip current: 0.35 amps (subtracted from Notification Appliance power).Coil Voltage: 3.65 VDC.Coil resistance: 14.6 ohms.Maximum allowable wire resistance between panel and trip coil: 3 ohms.Municipal Box wiring can leave the building.

For Remote Station service (NFPA 72 Remote Station Fire Alarm System):Maximum load for each circuit: 10 mA.Reverse polarity output voltage: 24 VDC.Remote Alarm and Remote Trouble wiring can leave the building.

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

9

AC CircuitBreaker

1.6 Specifications

AC PowerFor PDRP-1001/PDRP-1001A: 120 VAC, 50/60 Hz, 1.2 ampsWire size: minimum #14 AWG with 600V insulation

Battery (lead acid only)Maximum Charging Circuit: 27.6V, 1.5 ampsMaximum Battery Capacity: 15 AH. (Batteries larger than 12 AH require Notifier#BB-17 or other UL listed battery cabinet.)

Initiating Device CircuitsPower-limited circuitryOperation: Style B (Class B)/ Style D (Class A)Normal Operating Voltage: 24 VDC (ripple = 1.0V peak-to-peak)Alarm current: 15 mA minimumShort circuit current: 40 mA maximumMaximum detector current in standby: 2 mA (max) per zoneMaximum loop resistance: 200 ohmsEnd-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252 UL listed)Detector loop current is sufficient to ensure operation of one alarmed detector per zone.Supervisory current: 5 mA (including end-of-line resistor)

Notification Appliance and Releasing CircuitsPower-limited circuitryMaximum allowable voltage drop due to wiring: 2 VDCNormal Operating Voltage: 24 VDCTotal current available to all external devices: 2.25 amps.Maximum signaling current per circuit: 1.5 ampsEnd-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252 UL listed)

Alarm and Trouble RelaysDry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).All relays must be connected to a power-limited power supply.

Four-wire Smoke Detector PowerUp to 200 mA is available for powering 4-wire smoke detectors.Maximum ripple voltage: 1.0 V p/p

Non-resettable PowerTotal DC current available from this output is up to 200 mA (subtracted from four-wire smoke power).Maximum ripple voltage: 1.0 V p/p

RMS Regulated PowerTotal DC current available for powering external devices is 0.5 amp (subtracted from 2.25amps available to notification appliance circuits).Maximum ripple voltage: 100 mV p/p

Note : For device compatibility data, refer to the Device Compatibility Chart, Appendix B.

P1 P2 P3 P4

Output Circuit PTCs

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

10

Cabinet = 5.375"Backbox = 4.750"

Door = 16.125"Backbox = 16"

Door = 14.625"Backbox = 14.5"

Figure 1.6-1: Cabinet Dimensions

Optional Trim RingTR-4XR

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

11

2.0 System Operation

2.1 System Status LEDs

Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been acknowledged (TONEor ALARM SILENCE), at which point the LED will illuminate steadily.

AC POWERGreen LED that illuminates steadily to indicatepresence of AC power.

SYSTEM ALARMRed LED that flashes when an alarm occurs.

RELEASERed LED that illuminates steadily when releaseoccurs. After theDischarge Timer has expired, the LED will flash.

SUPERVISORYYellow LED that flashes upon activation of asupervisory device (such as tamper switch) onZone 4.

SYSTEM TROUBLEYellow LED that flashes for any trouble condition,including those associated with option boards.

CIRCUIT TROUBLEYellow LED that flashes for trouble conditions onoutput circuits (notification and releasing circuits).

ALARM SILENCEDYellow LED that illuminates steadily when theALARM SILENCE switch has been pushed afteran alarm.

POWER TROUBLEYellow LED that flashes for low or disconnectedbatteries and earth fault conditions.

BATTYellow LED that illuminates steadily onmotherboard when battery is low or not detected(not visible through door).

EARTHYellow LED that illuminates steadily onmotherboard during a ground fault condition (notvisible through door).

MICRO FAILYellow LED that illuminates on motherboard whenwatchdog timer detects microprocessor failure(not visible through door).

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

12

2.2 Control Switches

Tone SilenceAcknowledge alarms, troubles and supervisories. The panel has alarmand trouble resound with LED flash of new conditions. The flashingtrouble LED(s) illuminate steadily on TONE SILENCE and the piezosounder silences. A second trouble will resound the piezo. The piezo hasthree distinct sounds for alarm, trouble, and supervisory. Trouble condi-tions are self restoring. Alarms and supervisories latch and requireRESET to clear.

Alarm SilenceAcknowledge for alarms and supervisories. The ALARM SILENCEswitch will silence the local piezo, change any flashing alarm LEDs tosteady, and turn off the notification appliance circuits (not the ReleasingCircuits) . The “ALARM SILENCED” LED will illuminate. Alarm silenceis a latching function and requires a RESET to clear.

Note: Releasing Circuits will turn off only if Discharge timer criteria is satisfiedsee "Setting Mode of Operation".

Alarm ActivateThe ALARM ACTIVATE switch may be used to activate NotificationAppliance Circuits. ALARM ACTIVATE also activates the SystemAlarm relay. ALARM ACTIVATE is a latching function. Pressing ALARMSILENCE silences the notification appliance circuits and System AlarmRelay and lights the Alarm Silenced LED. Pressing RESET returns thesystem to normal.

System ResetThe RESET switch breaks power to all initiating device circuits, 4-wiresmoke power and option boards and will clear any activated outputcircuits. If any alarm or trouble still exists after reset, they will reactivatethe panel. Holding RESET down will perform a LAMP TEST function andwill activate the piezo sounder.

2.3 Zone Status LEDs

The alarm and/or trouble LED(s) will flash until theevent(s) has been acknowledged (TONE orALARM SILENCE), at which point the LED(s) willilluminate steadily. ZONE 1

ZONE 2

WATERFLOW

SUPERVISORY

ALARM LED

TROUBLE LED

ALARM LED

TROUBLE LED

ALARM LED

TROUBLE LED

(NOT USED)

TROUBLE LED

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

13

2.4 Supervisory

Zone 4 is always used for monitoring supervisory devices (such as valve tamper switches). A short circuiton this zone (activation of a N.O. contact) will cause the supervisory LED and the zone 4 yellow LED to flash.The piezo sounder will generate a unique Pressing TONE SILENCE will silence the piezo and cause thesupervisory LED to illuminate steadily, but the Zone 4 Trouble LED will continue to flash. Supervisorysignals latch and require RESET to clear. The ALARM SILENCE switch will silence the piezo, cause thesupervisory LED to illuminate steadily and turn off the Supervisory Notification Appliance Circuit. An opencircuit on Zone 4 will be reported as a zone trouble.

2.5 Zone Disable

If a zone has been disabled, an alarm that occurs on that zone will flashthe red zone LED, but neither the piezo nor any output circuit will activate.If both power sources are removed from the system, all zones will be re-enabled upon restoration of power. Disable status will be lost.

The Zone Disable routine makes use of the four panel switches as follows:

1) Press and hold in the TONE SILENCE switch.

2) With the TONE SILENCE switch held in, press (in sequence) the ALARMSILENCE switch, the ALARM ACTIVATE switch, and then the RESETswitch.

3) The Zone 1 Alarm LED will flash.

4) To disable Zone 1, press the RESET switch. The Zone 1 yellow LED will light to show that the zone is disabled.

Note: The RESET switch toggles disable status for the selected zone.

5) To select the next zone, press the ALARM SILENCE switch.

6) To select the previous zone, press the ALARM ACTIVATE switch.

7) When disable selections are complete, release the TONE SILENCE switch.

If any zone has been disabled, the trouble relay will activate and System Trouble LED will flash.

2.6 Last Event Recall

Last Event Recall allows the user to display the previous panel status. The Last Event Recall makes useof the four panel switches as follows:

1) Press and hold in the TONE SILENCE switch.

2) With the TONE SILENCE switch held in, press (in sequence) the RESETswitch, the ALARM ACTIVATE switch, and then the ALARM SILENCE switch.

3) Last Event is displayed.

4) Release the TONE SILENCE switch to return to normal operation.

Note: To clear the Last Event buffer, press RESET twice.

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

14

3.1 General

Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area in which extreme temperatures are not encountered. The location should be readily accessiblewith sufficient room for easy installation and maintenance. Locate the top of the cabinet approximately fivefeet above the floor with the hinge mounting on the left. Determine the number of conductors required forthe devices to be employed. Pull required conductors into the box through the knockout provided. All wiringshould be in accordance with the National and/or Local codes for fire alarm systems.

UL Power Limited Wiring RequirementsPower limited and non-power limited circuit wiring must remain separated in the cabinet. All power limitedcircuit wiring must remain at least 0.25" away from any non-power limited circuit wiring. Furthermore, allpower limited circuit wiring and non-power limited circuit wiring must enter and exit the cabinet throughdifferent knockouts and/or conduits. A typical wiring diagram for the PDRP-1001/PDRP-1001A is shownbelow.

3.0 Installation Procedure

Figure 3.1-1: Typical Wiring Diagram for UL Power-Limited Requirements

PC Board

AC Power PowerLimitedCircuit

Non-PowerLimitedCircuit

Initiating CircuitsBell Circuits

Relays

Power LimitedCircuits

Non-PowerLimited Circuits

Power LimitedCircuits

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

15

3.2 Initiating Device Circuits

ZonesWire all alarm initiating devices sequentially for proper supervision. Initiating devices include: heat,photoelectric, and ionization type detectors; and waterflow alarm devices. Refer to the Device CompatibilityChart, Appendix B.

Notes:1) Observe polarity when connecting polarized devices.2) All circuits are supervised and power limited.3) Leave Dummy Load (provided) on all unused circuits.

Figure 3-2: Ffffff

Figure 3.2-1: Example of Initiating Device Circuits

IN #1 IN #2 IN #3 IN #41 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

B+ A+ A- B- B+ A+ A- B- B+ A+ A- B- B+ A+ A- B-TB4

Style BInitiating Device

Circuit

Style DInitiating Device

Circuit

HeatDetector

Two-wireSmoke Detector

ManualRelease

Normally OpenWaterflowDevices orPressureSwitches

Normally OpenTamper Switches

or PressureSwitches

+ -

+ -

+-

+

-

+ -

+ -

Style BSupervisory

Circuit

4.7K, 1/2-Watt(NOTIFIER part # 71252,

UL listed)

4.7K, 1/2-Watt(NOTIFIER part # 71252,

UL listed)

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

16

Notes on Style B and Style D field wiring:1) The Power Supervision Relay coil leads must be connected to the last detector base 24V screw terminals.2) Calculation of the maximum allowable resistance in the 24VDC detector power wiring:

Where:

RMAX

is the maximum resistance of the 24V wires.

VOM

is the minimum operating voltage of the detector or end-of-line relay, whichever is

greater, in volts.

N is the total number of detectors on the 24V supply loop.

IS is the detector current in standby.

NA is the number of detectors on the 24V power loop which must function at the same

time in alarm.

IS is the detector current in alarm.

IR is the end-of-line relay current.

3.3 4-Wire Smoke Detector Connections

24 VDC (+)

Common (-)

IDC(+)

IDC(-)

Red

Black

24 VDC (+)

Common (-)

IDC(+)

IDC(-)

UL-listed 24 VDCFour-Wire Smoke Detectors

UL Listed4.7K, 1/2-Watt

ELR

TB1

1 2 3 4

+ -TB4

1 2 3 4

B+ A+ A- B-

+24VR

A maximum of 200mA is available from the+24VDC 4-wire smoke detector power cir-cuit on TB1 terminals 3 and 4. Any power thatis drawn from the +24VDC Non-ResettablePower on TB2 terminals 1 and 2 must besubtracted from available 4-wire detectorpower. See Sections "Specifications" and"Power".

IN #1Style B Initiating Device Circuit

Initiating Device Circuits 1, 2, 3, or 4can be used. Style D wiring can also beemployed.

ListedPower

SupervisionRelay

Refer to the Device Compatibility Chart (Appendix B), for suitable 4-wire smoke detectors.

Figure 3.3-1: Diagram of connections for a 4-Wire Smoke Detector

RMAX

= (20.6 - VOM

)

(N x IS) + (N

A x I

A) + (I

R)

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

17

3.4 Output CircuitsNotification Appliance CircuitsThis control panel can provide two Style Y/Z Notification Appliance Circuits and two Style Y ReleasingCircuits (see Section "Dip Switch Location and Descriptions" for DIP switch configuration). Each circuitis capable of 1.5 amps of current. Total current drawn from all four circuits cannot exceed 2.25 amps. Referto the Device Compatibility Chart, Appendix B. Circuits are supervised and power-limited.

Note: Wiring must be configured to maintain a minimum voltage of 20.4V on release circuits. Calculation of maximum allowable resistance:

RMAX

= 20.6V - 20.4V

IS

Where: RMAX

= maximum allowable resistance of wiring IS = solenoid current

3 4 5 6 7 8 9 10 11 12 13 14 15 16

Polarized Bell

Polarized Strobe

Polarized Horn

B+ A+ A- B- B+ A+ A- B- NC B+ B- NC B+ B-

Style ZNotification

Appliance Circuit

Style YNotification

Appliance Circuit

B+ A+ A- B- B+ A+ A- B- B+ B- B+

4.7K, 1/4-WattUL-listed End-of-Line device

Dummy Load all unusedNotification Appliance Circuits

Dummy Load all unusedReleasing Circuits

4.7K, 1/2-Watt(part # 71252, UL listed)

4.7K, 1/4-WattUL-listed End-of-Line device

TB2

UL listed & FM approvedSolenoid Release Valves(see Device Compatibility

Document)

Releasing Circuits

No

Con

nect

ion

No

Con

nect

ion

Figure 3.4-1: Notification Appliance Circuits

OUT #1 OUT #2 OUT #3 OUT #4

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

18

3.5 Power

CAUTION: Several different sources of power can be connected to this panel. Disconnectall sources of power before servicing. The panel and associated equipment may bedamaged by removing and/or inserting cards, modules, or interconnecting cables whilethis unit is energized.

This output is not suitable forpowering devices requiring fil-tered, regulated DC power.

The combined current draws from the Resettable and Non-Resettableoutputs cannot exceed 200 mA.

Alarm RelayOne Form-C dry alarm contact is provided in the basic panel for controlling supplementary devices. It israted 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive) and is non-silenceable when an alarm occurs.See below for terminal location.

Trouble RelayOne Form-C dry trouble contact is provided in the basic panel for controlling supplementary devices. Itis rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive) and will silence when trouble condition iscleared. See below for terminal location.

Note: The alarm and trouble Form-C dry contact relays must be power limited relays. Theymust be wired from one of the 24V power limited terminals as shown in the figure belowor a comparable UL listed power limited power supply.

ALARM TROUBLENO NC C NO NC C

Alarm Trouble

Figure 3.4-2: Alarm/Trouble Coils and Contacts.

+24VU +24VR +24VNR + - + - + -

- -

-

- -

-

- -

-or or

1 2 3 4 5 61 2 3 4 1 2

TB1TB2

TB3

RMS-Regulated Power24 VDC power for inductive-typedevices such as door holders canbe connected to TB1 terminals 1(+)and 2 (-).

+24VU +24VR +24VNR + - + - + -

4-Wire Smoke Detector Power24 VDC filtered, regulated, resettablepower for 4-wire smoke detectors canbe obtained from TB1 Terminals 3 (+)and 4 (-).

Non-resettable Power24 VDC filtered, regulated, non-reset-table power can be drawn from TB2Terminals 1 (+) and 2 (-).

1 2 3 4

Figure 3.5-1: Diagram of Power Terminals

TB11 2

TB2

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

19

Voltmeter/AmmeterTo monitor battery voltage and battery charging current, a 4XMM (NOTIFIER) is required. To install thepower meter module, remove the jumper labeled "AMP" and connect cable assembly P2 to pin connectorJ2 and cable assembly P3 to pin connector J3 on the main board. Secure the 4XMM to the backbox withthe two screws provided. On some models, it will be necessary to install the meter bracket with the nutsand bolts provided.

J2

J3

AC PowerPrimary power required for the PDRP-1001/PDRP-1001A panel is 120 VAC, 50/60 Hz, 1.2 amps.Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC)and/or local codes. Use #14 AWG or larger wire with 600 volt rating.

Battery PowerObserve polarity when connecting battery. Connect battery cable to J9 on the main board using the plug-in connector provided. See Appendix A for calculation of correct battery rating.

CAUTION: Batteries contain sulfuric acid which can cause severe burns to the skin andeyes, and can destroy fabrics. If contact is made with sulfuric acid, immediately flush skinor eyes with water for 15 minutes and seek immediate medical attention.

Figure 3.5-2: Diagram of the 4XMM Voltmeter Connected to the Main Board

J9

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

20

3.6 Optional Modules

The fire control panel has two module connectors - J5 and J8. Three modules are available for the paneland they can be used in any combination, including duplicate modules. The corresponding option jumpermust be cut before installation of an optional module, to enable module supervision.

J7

J8

OPT1 JumperCut to installmodule on J5.

Notes:1) Optional 4XLM module for an RZA-4X Annunciator must be installed on J7 and J8 only.2) 4XTM and 4XZM modules can be installed in either location.

Figure 3.6-1: Optional Panel Modules

OPT2 JumperCut to installmodule on J8.

J4

J5

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

21

Installing Option ModulesInsert the two stand-offs (provided) into the holes located on the right-side edge of the main board. Carefullyalign the pins on the main board with J1 and/or J2 on the option board. Insert screw through the optionboard until it is secured on the stand-offs. Affix the terminal identification labels provided with the optionmodules as shown below.

Stand-offs

Option Board(4XZM shown)

MainBoard

Figure 3.6-2: Installing Option Modules

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

22

Transmitter Module -- 4XTM (NOTIFIER)Polarities shown in activated positions. The wiring of this module must follow the requirements as specifiedin the "General" Section, "UL Power Limited Wiring Requirements."

Push the disconnect switch down to prevent unwanted activation of the Municipal Box during testing of thecontrol panel. The Disconnect LED will remain illuminated while the Municipal Box is disconnected. TheSystem Trouble LED will indicate disconnected and/or Open Circuit conditions on the Municipal Box.Cutting the TBL jumper will allow the alarm reverse polarity circuit to open on trouble, if no alarm exists.

* Dummy load terminals 6 and 7 (4.7K, 1/4 W resistor)if Municipal Box is not connected.

Note: Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.

+-+-

+-

Remote Alarm

Remote Trouble

1234567

}

TBL Jumper

DisconnectLED

DisconnectSwitch

}

}

}

}Power Limited Circuit

Non-Power Limited Circuit

No Connection

Municipal Box *

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

23

Zone Relay Module -- 4XZM (NOTIFIER)Non-power limited and power limited wiring must have a minimum distance of 0.25" wire to wire. If thismodule is used to drive non-power limited and power limited circuits, please follow the instructions below:

Relay #1 through #4 will activate with Out-put #1 through #4 and remain latchedunless jumper "LATCH" is cut.

OR

1) Skip a set of dry contacts to maintain the 0.25" required space between power limited and non-powerlimited circuits. The wiring of this module must follow the requirements as specified in the "General"Section, "UL Power Limited Wiring Requirements".

2) If this module is needed to drive power limited and non-power limited relays that are next to each other,refer to the figure below showing a typical connection:

NONCC

NONCC

NONCC

NONCC

}}}}

no connection

Relay #1

Relay #2

Relay #3

Relay #4

}}}}

power limitedcircuit

power limitedcircuit

non-powerlimited circuit

non-powerlimited circuit

Note : Refer to the Protected Premises Unit label, located on the door of the control panel, to indicate if any drycontacts are to be sued as non-power limited dry contacts.

Use Disable switch todisconnect the relays

Relay #1

Relay #2

Relay #3

Relay #4

Alarm

Trouble

}}}}}}

NONCCNONCC

123456789101112131415161718

NONCCNONCCNONCCNONCC

Cut jumper for non-latching(silenceable) relay operation

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

24

Side View

Front View

Single-gang Box

Connect to correspondingterminals of RZA-4X RemoteAnnunciator.

+24VOut #1Out #2Out #3Out #4System TroubleSoundResound

12345678

The wiring of this module must follow the requirements as specified in the Section "UL Power Limited WiringRequirements."

LED Interface Module -- 4XLM (NOTIFIER)

Figure 3.6-3: LED Interface Module --4XLM

Note: Make wiring connections with system power off. Maximum wire impedance is 50 ohm per wiring connection.

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

25

DIP Switches

Switch 1: Cross-ZoneSwitch 2: Dual Hazard

1 2 3 4 5 6ON

Switch 3: Discharge timerSwitch 4: Discharge timerSwitch 5: Discharge timerSwitch 6: Not Used

Slide Switch to "ON" position to selectthe desired options (refer to the Section"Setting Mode of Operation".)

Micro Fail LEDBattery FailLED

Ground Fault LED

3.7 Dip Switch Location and Descriptions

For DIP switch settings, refer to the Section "Setting Mode of Operation."

Note: The Reset key must depressed after any switch configuration has been made.

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

26

Switch 1Switch 2

Mode #1Single Hazard

Two Zone

Mode #3Dual Hazard

Combined Release

Mode #4Dual HazardSplit Release

Mode #2Single HazardCross Zone

Switch 6

OFFOFF

Outputs 1 and 3- activatedby an alarm on either Zone1 or 2.

Output 2 -activated by awaterflow alarm onZone 3 .

Output 4- activated by asupervisory condition onZone 4.

ONON

Output 1- activated by analarm on either Zone 1 orZone 2 or a waterflowalarm on Zone 3 .

Output 2 -activated by asupervisory condition onZone 4.

Output 3 -activated by analarm on Zone 1 .

Output 4 -activated by analarm on Zone 2 .

ONOFF

Output 1- activated by analarm on either Zone 1or Zone 2 .

Output 2 -activated by awaterflow alarm onZone 3 .

Output 3- activated byalarms on both Zone 1and Zone 2 .

Output 4- activated by asupervisory condition onZone 4.

OFFON

Output 1- activated by analarm on either Zone 1 orZone 2 or a waterflowalarm on Zone 3 .

Output 2 -activated by asupervisory condition onZone 4 .

Output 3 and 4 -activatedby an alarm on either Zone1 or Zone 2.

Note: Zones 1 and 2 refer to Initiating Device Circuits 1 and 2.

For NFPA 13 and 15 applications Timer must be set to DISABLED.For NFPA 16 applications, Timer may be set to 10 MINUTES or 15 MINUTES.

Discharge Timer Notes:1) Timer will always start at Zone 2 normal to alarm transition. Upon time-out, corresponding release circuits will shut off.2) Zone 1 will always override timer shutoff (except for Mode #4 - Split Release).

15 Minutes

ONONON

10 Minutes

ONONOFF

Disabled

OFFOFFOFF

Switch 3Switch 4Switch 5

3.8 Setting Mode of Operation

Basic ProgramSelect the desired mode of operation and set SW1 DIP switches 1 and 2 per the appropriate column.

Discharge TimerSelect the desired Discharge Timer setting by setting SW1 DIP switches 3, 4 and 5.

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

27

a. Two-wire detector heads

b. Four-wire detector heads

c. End of Line Relays

d. Add lines a, b, & c for subtotal

Table A-1: Standby Battery Requirements

The Standby Battery Current figure obtained in Table A - 1 represents the amount of current that must besupplied by the secondary power source (batteries) to sustain control panel operation for one hour.

Note: The control panel will support the installation of one or two optional modules, including two of the same type of module.

Basic Control Panel 88 mAControl panel with AC power off, System Trouble LED and audible trouble sounder on.

If using a 4XZM Zone Relay Module1 [ ] X 8 mA =

If using a 4XTM Transmitter Module, add 11 mA

If using the Reverse Polarity Alarm output, add 5 mA

If using the Reverse Polarity Trouble output, add 5 mA

If using a 4XLM/RZA-4X Driver/Annunciator combination:1

[ ] X 19 mA =

If using a 4XMM Meter Module, add 1 mA

If using the Noti•Fire 911AC DACT, add 30 mA

X =

X =

X 25.0 mA =

Add last column for Standby Battery Current : and continue to Table A-2.

+Place subtotal here

TotalCurrent

Numberin use

DeviceCurrent

(see Appendix B for data)

Appendix A: Power Calculations

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

28

Notes:1) Alarm amp-hours assumes a maximum system draw of 3 amps in alarm for 5 minutes (0.25 amp/hour) or for

10 minutes(0.5 amp/hour).

2) NFPA 72 Central Station and Local and Proprietary Fire Alarm Systems require 24 hours of standby.3) NFPA 72 Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby.

5) The battery charger in this panel will charge a maximum of 15 amp/hour of batteries within 48 hours (7 amp/hour minimum). Batteries larger than 12 amp/hour will require a UL listed battery cabinet (e.g. Notifier BB-17).

Table A-2: Ampere-Hour Calculations

amps X hours =

Enter 0.25 for 5 minutes in alarm or0.5 for 10 minutes in alarm

Add Standby and Alarm amp/hours =

Select a battery with an equal or greater amp/hour rating than the figure obtained in Table A-2.Batteries must be lead-acid type.

PS-1270 12-volt, 7 amp/hour (two required)PS-12120 12-volt, 12 amp/hour (two required)

Standbyamp/hours

Alarmamp/hours

Total amp/hoursneeded

+

Standby Battery Current Standby TimeConvert the total from Table 1 24, 60, or 90 hoursto amps and enter here

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

29

ledoM epyT )Am(tnerruC089-MF elgnis,tnuoMroolF 86

699-MF gniriWecafruS 86

899-MF gniriWdelaecnoC 86

A051HD tnuoMroolF 69

A451HD tnuoMhsulF 69

A851HD tnuoMecafruS 69

24 VDC Door Holders

UL Listed 24 VDC Relays

RODNEV LEDOM )Am(TNERRUC

rosneSmetsyS B617-77A 02

&stcudorPriADTL,slortnoC

C/101-RMC/102-RM

5153

FM-Approved Releasing Devices(Notifier's RP-1001)

Solenoid Group [A]Skinner solenoid valve Model LV2LBX25, 24 VDC, 11 WATTS,458 mA, 1/2 in. NPS, 5/8 in. orifice.

Solenoid Group [B] These valves are interchangeable.ASCO solenoid valve Model T8210A107, 24 VDC, 16.8 Watts,700 mA, 1/2 in. NPS, 5/8 in. orifice.ASCO solenoid valve Model R8210A107, 24 VDC, 16.8 Watts,700 mA, 1/2 in. NPS, 5/8 in. orifice.ASCO solenoid valve Model 8210A107, 24 VDC, 16.8 Watts, 700mA, 1/2 in. NPS, 5/8 in. orifice.

Solenoid Group [C]Star Sprinkler Corp. Solenoid P/N 5550, 24 VDC, part of ModelD deluge valve.

Kidde-Fenwal Electric Control HeadP/N 890181; 24V, 2.0AmpsKidde-Fenwal Electric Control HeadP/N 899175; 24V, 2.0AmpsKidde-Fenwal Electric Control Head Stackable (XP)P/N 48650001; 24V, 0.2AmpsKidde-Fenwal Electric and Cable Op Control Head (XP)P/N 897494; 24V, 1.5Amps, 33 Watts

Refer to the FM approval guide for automatic water controlvalves which are compatible with solenoids listed above.

UL Listed Four-Wire Smoke Detectors

esaB/rotceteDekomS epyTrotceteDybdnatSxaM)Am(tnerruC

tnerruCmralA)Am(

4242rosneSmetsyS cirtceleotohP 01.0 14

HT4242rosneSmetsyS cirtceleotohP 01.0 14

1542rosneSmetsyS cirtceleotohP 01.0 93

)esaBB204B/htiw(HT1542rosneSmetsyS cirtceleotohP 01.0 93

4241rosneSmetsyS noitazinoI 01.0 14

)esaBB204B/w(1541rosneSmetsyS noitazinoI 01.0 93

2142rosneSmetsyS cirtceleotohP 21.0 77

TA2142rosneSmetsyS cirtceleotohP 21.0 85

HT2142rosneSmetsyS cirtceleotohP 21.0 77

BT42/2132rosneSmetsyS cirtceleotohP 21.0 05

PL211BrosneSmetsyS esaB 21.0 63

PL411BrosneSmetsyS esaB ----- -----

B404BrosneSmetsyS esaB ----- -----

4246rosneSmetsyS maeBdetcejorP 01 4.82

ICDCA004HDrosneSmetsyS tcuDnoitazinoI 52 59

PCDCA004HDrosneSmetsyS tcuDcirtceleotohP 52 59

42/2111rosneSmetsyS noitazinoI 50.0 05

42/2112rosneSmetsyS cirtceleotohP 50.0 05

B42/2112rosneSmetsyS cirtceleotohP 50.0 56

T42/2112rosneSmetsyS 531/wcirtceleotohP o lamrehT 50.0 05

BRST42/2112rosneSmetsyS531/wcirtceleotohP o lamrehT

yaleRyrosivrepuS51 54

Appendix B: Device Compatibility

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

30

ROSNESMETSYS detaR²egatloV

RWFCD

deretliFCD

rednuoScinortcelED42/21-AMrosneSmetsyS CDV42 37 64

ebortS42SSrosneSmetsyS CDV42 * 03

ebortSOL42SSrosneSmetsyS CDV42 54 52

)egieb-CBOL42SS(ebortSgnilieCCOL42SSrosneSmetsyS CDV42 54 52

ebortSM42SSrosneSmetsyS CDV42 521 57

ebortSgnilieCCM42SSrosneSmetsyS CDV42 521 57

ebortS/rednuoScinortcelED42SSAMrosneSmetsyS CDV42 811 17

ebortS/rednuoScinortcelEOL42SSAMrosneSmetsyS CDV42 811 17

ebortS/rednuoSgnilieCcinortcelECOL42SSAMrosneSmetsyS CDV42 811 17

snelogeuFhtiwebortS/rednuoScinortcelEALOL42SSAMrosneSmetsyS CDV42 811 17

ebortS/rednuoScinortcelEM42SSAMrosneSmetsyS CDV42 891 121

ebortS/rednuoSgnilieCcinortcelECM42SSAMrosneSmetsyS CDV42 891 121

rednuoSR004AProsneSmetsyS CDV42 * 51

ebortSno-ddAOL42SProsneSmetsyS CDV42 54 52

ebortSgnilangiSADA5142SSrosneSmetsyS CDV42 09 57

ebortSgnilangiSADA5742SSrosneSmetsyS CDV42 002 071

ebortSgnilangiSADA01142SSrosneSmetsyS CDV42 542 012

ebortSgnilangiSADA575142SSrosneSmetsyS CDV42 021 39

tiucriC.hcnyShtiwebortSgnilangiSSADA5142SSrosneSmetsyS CDV42 521 601

tiucriC.hcnyShtiwebortSgnilangiSSADA575142SSrosneSmetsyS CDV42 081 511

ebortSgnilangiS/rednuoSADA5142SSAMrosneSmetsyS CDV42 361 121

ebortSgnilangiS/rednuoSADA5742SSAMrosneSmetsyS CDV42 372 612

ebortSgnilangiS/rednuoSADA01142SSAMrosneSmetsyS CDV42 813 652

ebortSgnilangiS/rednuoSADA575142SSAMrosneSmetsyS CDV42 391 931

.tkC.hcnyS/webortSgnilangiS/rednuoSSADA5142SSAMrosneSmetsyS CDV42 361 121

.tkC.hcnyS/webortSgnilangiS/rednuoSSADA575142SSAMrosneSmetsyS CDV42 391 931

ebortS/rednuoS-iniMADA5142SProsneSmetsyS CDV42 011 09

ebortS/rednuoS-iniMADA5742SProsneSmetsyS CDV42 531 801

ebortS/rednuoS-iniMADA575142SProsneSmetsyS CDV42 531 801

ebortS/rednuoS-iniMADA01142SProsneSmetsyS CDV42 042 522

UL Listed Notification AppliancesControl panels supplying Special Application (FWR, Filtered) power must use the notification appliances, relays or doorholders listed in the corresponding tables.

Notes:1) All currents are in Milliamperes and worst case average.2) Nominal Operating voltage.3) Refer to installation instructions for more information.4) * Contact manufacture for currents.

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

31

Notes:1) All currents are in Milliamperes and

worst case average.2) Nominal Operating voltage.3) Refer to installation

instructions for more information.4) * Contact manufacture for currents.

UL Listed Notification AppliancesControl panels supplying Special Application (FWR, Filtered) power must use the notification appliances, relays or doorholders listed in the corresponding tables.

ROSNESMETSYS detaR²egatloV

RWFCD

deretliFCD

ebortSgnilangiS/rekaepSADA5142R1PSrosneSmetsyS CDV42 09 57

ebortSgnilangiS/rekaepSADA5742R1PSrosneSmetsyS CDV42 002 071

ebortSgnilangiS/rekaepSADA01142R1PSrosneSmetsyS CDV42 542 012

ebortSgnilangiS/rekaepSADA575142R1PSrosneSmetsyS CDV42 021 39

ebortSgnilangiS/rekaepSADA5142R4VrosneSmetsyS CDV42 09 57

ebortSgnilangiS/rekaepSADA5742R4VrosneSmetsyS CDV42 002 071

ebortSgnilangiS/rekaepSADA01142R4VrosneSmetsyS CDV42 542 012

ebortSgnilangiS/rekaepSADA575142R4VrosneSmetsyS CDV42 021 39

ellirgdnuor"8,ebortS/rekaepSgnilieCCOL42W001PSrosneSmetsyS CDV42 54 52

ellirgerauqs"5,ebortS/rekaepSOL42R101PSrosneSmetsyS CDV42 54 52

ellirgerauqs"5,ebortS/rekaepSM42R101PSrosneSmetsyS CDV42 521 57

ellirgdnuor"8,ebortS/rekaepSgnilieCCM42W001PSrosneSmetsyS CDV42 521 57

enoTlacinahceMhtiwnroHtrelAitluMHE42/21AMrosneSmetsyS CDV42/CDV21 46/02 34/83

ebortS/enoTlacinahceMhtiwnroHtrelAitluMOL42HEAMrosneSmetsyS CDV42 901 86

ebortS/enoTlacinahceMhtiwnroHtrelAitluMCOL42HEAMrosneSmetsyS CDV42 901 86

ebortS/enoTlacinahceMhtiwnroHtrelAitluMALOL42HEAMrosneSmetsyS CDV42 351 69

ebortS/enoTlacinahceMhtiwnroHtrelAitluMM42HEAMrosneSmetsyS CDV42 981 811

ebortS/enoTlacinahceMhtiwnroHtrelAitluMCM42HEAMrosneSmetsyS CDV42 981 811

ebortS/enoTlacinahceMhtiwnroHtrelAitluMADA5121HEAMrosneSmetsyS CDV21 042 191

ebortS/enoTlacinahceMhtiwnroHtrelAitluMADA575121HEAMrosneSmetsyS CDV21 013 642

ebortS/enoTlacinahceMhtiwnroHtrelAitluMADA5142HEAMrosneSmetsyS CDV42 872 612

ebortS/enoTlacinahceMhtiwnroHtrelAitluMADA5742HEAMrosneSmetsyS CDV42 372 612

ebortS/enoTlacinahceMhtiwnroHtrelAitluMADA575142HEAMrosneSmetsyS CDV42 343 172

ebortS/enoTlacinahceMhtiwnroHtrelAitluMADA01142HEAMrosneSmetsyS CDV42 813 652

ebortS/enoTlacinahceMhtiwnroHtrelAitluMSADA5142HEAMrosneSmetsyS CDV42 891 251

ebortS/enoTlacinahceMhtiwnroHtrelAitluMSADA575142HEAMrosneSmetsyS CDV42 352 142

nroHtrelArtcepS21HrosneSmetsyS CDV21 52 41

nroHtrelArtcepS24HrosneSmetsyS 3 CDV42 24 73

ebortStrelArtcepS5121SrosneSmetsyS CDV21 951 331

ebortStrelArtcepS575121SrosneSmetsyS CDV21 281 861

ebortStrelArtcepS5142SrosneSmetsyS 3 CDV42 241 38

ebortStrelArtcepS575142SrosneSmetsyS 3 CDV42 231 67

ebortStrelArtcepS5742SrosneSmetsyS 3 CDV42 071 541

ebortStrelArtcepS01142SrosneSmetsyS 3 CDV42 022 961

ebortS/nroHtrelArtcepS5121ProsneSmetsyS CDV21 371 441

ebortS/nroHtrelArtcepS575121ProsneSmetsyS CDV21 691 971

ebortS/nroHtrelArtcepS5142ProsneSmetsyS 3 CDV42 561 49

ebortS/nroHtrelArtcepS575142ProsneSmetsyS 3 CDV42 771 111

ebortS/nroHtrelArtcepS5742ProsneSmetsyS 3 CDV42 512 081

ebortStrelArtcepS01142ProsneSmetsyS 3 CDV42 562 412

ADA5121PRrosneSmetsyS A etalPebortStiforteR CDV21 002 071

ADA575121PRrosneSmetsyS A etalPebortStiforteR CDV21 042 552

ADA5142PRrosneSmetsyS A etalPebortStiforteR CDV42 09 57

ADA575142PRrosneSmetsyS A etalPebortStiforteR CDV42 021 39

ADA5742PRrosneSmetsyS A etalPebortStiforteR CDV42 002 071

ADA01142PRrosneSmetsyS A etalPebortStiforteR CDV42 542 012

trelArtcepS42HrosneSmetsyS CDV42 24 73

ebortStrelArtcepS5142SrosneSmetsyS 3 CDV42 241 38

ebortStrelArtcepS575142SrosneSmetsyS 3 CDV42 231 67

ebortStrelArtcepS5742SrosneSmetsyS 3 CDV42 071 541

ebortStrelArtcepS01142SrosneSmetsyS 3 CDV42 022 961

ebortS/nroHtrelArtcepS5142SrosneSmetsyS 3 CDV42 561 49

ebortS/nroHtrelArtcepS575142SrosneSmetsyS 3 CDV42 771 111

ebortS/nroHtrelArtcepS5742SrosneSmetsyS 3 CDV42 512 081

ebortS/nroHtrelArtcepS01142ProsneSmetsyS 3 CDV42 562 412

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

32

forebmuNrePsrotceteD

enoZ

ledoM.teD

DIrotceteD

epyTledoMesaB

esaBDI

ybdnatStnerruC

)Au(1001-PRDP

0041rosneSmetsyS A noitazinoI a/n a/n 001 02

1541rosneSmetsyS A noitazinoI B604B/B104B A 021 1/51

HD1581rosneSmetsyS A noitazinoI CD1581HD A 021 51

0042rosneSmetsyS A cirtceleotohP a/n a/n 021 51

TIA0042rosneSmetsyS A nroH/lamrehTdetalosI/otohP a/n a/n 021 1

TA0042rosneSmetsyS A nroH/lamrehT/otohP a/n a/n 021 1

HT0042rosneSmetsyS A lamrehT/otohP a/n a/n 021 51

1542rosneSmetsyS A cirtceleotohP B604B/B104B A 021 1/51

HT1542rosneSmetsyS A lamrehT/otohP B604B/B104B A 021 1/51

HD1582rosneSmetsyS A cirtceleotohP CD1582HD A 021 51

HD1541rosneSmetsyS A noitazinoI 004-HD A 021 51

1542rosneSmetsyS A cirtceleotohP 004-HD A 021 51

T0032rosneSmetsyS A lamrehT/otohP a/n a/n 021 51

0081rosneSmetsyS A noitazinoI a/n a/n 001 a/n

B1581rosneSmetsyS A noitazinoI B101B A 021 a/n

B1581rosneSmetsyS A noitazinoI B701B A 021 a/n

0082rosneSmetsyS A cirtceleotohP a/n a/n 021 a/n

HT0082rosneSmetsyS A lamrehT/otohP a/n a/n 021 a/n

B1582rosneSmetsyS A cirtceleotohP B101B A 021 a/n

B1582rosneSmetsyS A cirtceleotohP B701B A 021 a/n

HTB1582rosneSmetsyS A lamrehT/otohP B101B A 021 a/n

HTB1582rosneSmetsyS A lamrehT/otohP B701B A 021 a/n

1511rosneSmetsyS A noitazinnoI PL611B/PL011B/104B A 021 1/51/51

1512rosneSmetsyS A cirtceleotohP PL611B/PL011B/104B A 021 1/51/51

UL Listed, Compatible Two-Wire Smoke Detectors for Notifier Control Panels

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

33

PDRP-1001/PDRP-1001A Control Panel containing the main control board, cabinet (backbox and door),main supply transformer and power supply.

Batteries (refer to Appendix A for Standby Power Requirements).

Initiating Devices - connected to one of the control panel's Initiating Device Circuits.

Notification Appliances - connected to one of the control panel's Notification Appliance Circuits.

Releasing Devices - connected to one of the control panel's Releasing Circuits.

The following additional equipment is needed for compliance with the NFPA standards listed below:

NFPA 72 Signaling Systems for Central Station Service (Protected Premises Unit)NOTI-FIRE 911AC DACT* - for connection to a compatible listed Central Station DACR or ProtectedPremises Receiving Unit. This unit must be installed as outlined in Figure C-1A.

NFPA 72 Auxiliary Fire Alarm System4XTM Transmitter Module for connection to a compatible listed Local Energy Municipal Box. This unit mustbe installed as outlined in Figure C-2.

NFPA 72 Remote Station Fire Alarm System4XTM Transmitter Module for connection to the Fire•Lite RS82-9 Remote Station Receiver. See FigureC-3 for installation instructions for this unit...

OR

NOTI-FIRE 911AC DACT * or Fire•Lite MS-5012- For connection to a compatible listed remote stationDACR. This unit must be installed as outlined in Figure C-1A.

* Applications which require the NOTI-FIRE 911AC or the Potter EFT-C are not FM approved.

Appendix C: NFPA Standard-Specific Requirements

The fire control panel has been designed for use in commercial, industrial, and institutional applications andmeets the requirements for service under the National Fire Protection Association (NFPA) Standardsoutlined in this appendix. The minimum system components required for compliance with the appropriateNFPA standard are listed below.

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

34

Figure C-1A: NFPA 72 Signaling Systems for Central Station Service(ProtectedPremises Unit) and Remote Station Protective Service

NOTI-FIRE 911AC DACT* - for connection to a Central Station Receiver or Protected Premises ReceivingUnit. This unit must be installed as illustrated below. For additional information on the 911AC, refer todocument 74-06200-005.

All connections between the FACP and 911AC must be in conduit, less than 20' in length in the same room.* This application using the NOTI-FIRE 911AC is not FM approved.

Note on STD DACT:Place jumper over pins 2 & 3,marked DACT, whenemploying a DACT. Thisdirects the control panel totransmit all trouble conditionsexcept AC LOSS.

draobrehtoM CA119

mralA 1-3BT 7dna6

yllamronnepo

stcatnoc

3-3BT 9dna8

elbuorT 4-3BT 01

yllamronnepo

stcatnoc

6-3BT 11

yrosivrepuS 21-1BTMZX4 21

yllamronnepo

stcatnoc

ot6-3BTrepmuj01-1BTMZX4

STD DACTJP-1

To CentralStation

Supervisory

Alarm

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

35

Figure C-1B: NFPA 72 Signaling Systems for Central Station Service

Program the Fire•Lite MS-5012 for slave application. Reference the Installation Manual for additionalinformation.

TBTB4TB3

AC Wiring for DACT/FACPmust be connected to thesame circuit.

draobrehtoM 2105-SM

mralA 1-3BT 2-2BT

3-3BT 1-2BT

elbuorT 4-3BT 4-2BT

6-3BT 3-2BT

yrosivrepuS 01-1BTMZX4 01-2BT

21-1BTMZX4 9-2BT

7

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

36

Figure C-2: NFPA 72 Auxiliary Fire Alarm System

All connections are power limited and supervised. This application is not suitable for separate transmissionof sprinkler supervisory or trouble conditions.

Note: Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms.

NOTIFIER 4XTMTransmitter Module(activated polarities

shown)

+

-

Municipal Box Circuit

GamewellModel M34-56Local EnergyMunicipal Box6

7

+ -

Note: Municipal Box wiring can leave the building.

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

37

Figure C-3: NFPA 72 Remote Station Fire Alarm System

Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatibleratings. All connections are power limited and supervised with the exception of the reverse polarity loop.Supervision of the loop is the responsibility of the receiver.

+ - + -

Remote Trouble

Remote Alarm1234

NOTIFIER 4XTMTransmitter Module

(activated polarities shown)

Note: Remote Alarm and Remote Trouble wiring can leave the building.

Fire•Lite RS82-9Remote Station Receiver

UL listed

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

38

Troubleshooting TableMOTPMYS MELBORP NOITULOS

noDELrewoPCA

noDELelbuortmetsyS

noDELelbuorttiucriC elbuorttiucricecnailppanoitacifitoN

.1 rof3BT(.snoitcennocreporprof2BTkcehCBX4 )slenap

.2 llatsnidnagniriwdleifllaevomeRrofkcehC.tiucrictuptuotaRLEymmud

,)V3.2-lamroN(,tissorcaegatlovyrosivrepus.draobtiucricecalper,tsisrepmelborpfi

.3 gniriwdleiftcennocer,RLEymmuddevomeR,V5-elbuort(;tuptuossorcaegatloverusaemdna

.)V0trohs.4 .ecivedtsaltaRLErofkcehC.5 .gniriwdleifkcehC

nmulocthgirehtfoynAgnihsalfsDELwolley

elbuorttiucricnepoenozgnitaitinI

.1 .snoitcennocreporprof4BTkcehC

.2 dnaelbuortnienozrofgniriwdleifevomeRrofK2.2;V42rofK7.4(RLEymmudllatsni

.draobtiucricecalper,tsisrepmelborpfI.)V21.3 .ecivedtsaltaRLErofkcehC.4 .gniriwdleifkcehC

nmulocthgirehtfoynAnoydaetssDELwolley

elbasidenoZ .1 .launamnoitallatsnikcehC

noDELelbuortrewoP

elbuortyrettaBDELwolleyttaB

no

rognissiMdetcennocsiD

.1 .snoitcennocyrettabkcehC

egamadrowoLyrettab

.1 regrahcssorcaegatlovkcehc,seirettabevomeR,)V21rofV01-8;V42rofV91ot71(tuptuo

.draobtiucricecalperesiwrehto.2 taegatlovyrettaberusaem,seirettabtcennoceR

fo%58nahtsselsiegatlovfI.slanimretyrettab.sruoh84rofegrahcotmehtwolla,egatlovdetar

.3 .seirettabecalper,tsisrepmelborpfI

elbuorttluafdnuorGnoDELwolleyhtraE

.1 dnalenapniammorfgniriwdleifevomeRymmudllatsnI.)dellatsnifi()s(eludomlanoitpo

.)V21rofK2.2;V42rofK7.4(RLE.2 .sdaelyrettabhtobevomeR.3 emitehttatiucricenotcennoc,sraelcelbuortfI

.melborpehttniopnipot.4 .draobtiucricecalper,raelct'nseodelbuortfI

MTX4noDELwolleYno

MTX4.1 1WShctiwstcennocsidxoBlapcinuMevoM.pu

tucrepmuj2TPO,1TPO.1 firepmujecalperro)s(eludomlanoitpollatsnI

.desutonsi)s(eludom

tiucricnepoxoBlapicinuM.1 noitpoxoBlapcinuMfidaolymmudllatsnI

.desut'nsi.2 .gniriwxoBlapcinuMkcehC

nosDELdernmulocthgirehtfoynA gniriwtiucricgnitaitininotrohS.1 fI.RLEllatsnidnagniriwdleifevomeR

deriwyltcerrocniroytluafrofkool,sraelcelbuort.secived

MTX4nohctiwsxoBlapicinuMgnitcennocsiDelbuortaetaerctonseod

t'nsiseludomlanoitporofrepmuJtuc

.1 .2TPOro1TPOrepmujdetaicossatuC

,mralarofetavitcat'nseodDELdetaicossa:MZX4snoitidnocyrosivrepusroelbuort

elbuorteludomlanoitpO.1 .dellatsniylreporpsieludomerusekaM.2 ehtotMZX4no1WShctiwselbasidevoM

.tfel

roelbuort,mralarofdnuost'nseodozeipX4-AZRsnoitidnocyrosivrepus

MLX4.1 nodellatsnisieludomMLX4tahterusekaM

.8Jdna7J.2 .gniriwdleifkcehC

noDELwolleyliaForciM degamadrossecorporciM .1 .draobtiucricecalpeR

noyatssDELX4-AZRllAroirpdevomert'nsawrewoP

noitallatsni.1 .tesermetsystiH

ffoDELrewoPCAnoDELelbuortmetsyS

rewopniamfossoL.1 rof1BT(.)5BT(rewopgnimocnikcehC BX4

)slenap

rekaerbtiucricdegamaD .1 .draobtiucricecalpeR

noDELwolleyliaForciM degamadrossecorporciM .1 .draobtiucricecalpeR

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

39

NOTES

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97

40

SYSTEM SENSOR® warrants its products to be free from defects in materials andworkmanship for eighteen (18) months from the date of manufacture, under normaluse and service. Products are date stamped at time of manufacture. The sole andexclusive obligation of SYSTEM SENSOR® is to repair or replace, at its option, free ofcharge for parts and labor, any part which is defective in materials or workmanshipunder normal use and service. For products not under SYSTEM SENSOR® manufacturingdate-stamp control, the warranty is eighteen (18) months from date of original purchaseby SYSTEM SENSOR®'s distributor unless the installation instructions or catalog setsforth a shorter period, in which case the shorter period shall apply. This warranty isvoid if the product is altered, repaired or serviced by anyone other than SYSTEM SENSOR®

or its authorized distributors or if there is a failure to maintain the products and systemsin which they operate in a proper and workable manner. In case of defect, phoneSYSTEMS SENSOR'S® toll free number 800-SENSOR2 (736-7672) for a Return Authorizationnumber, send defective units postage prepaid to: SYSTEM SENSOR®, Repair Department,RA #__________, 3825 Ohio Avenue, St. Charles, Il 60174. Please include a notedescribing the malfunction and suspected cause of failure.

This writing constitutes the only warranty made by SYSTEM SENSOR® with respect to itsproducts. SYSTEM SENSOR® does not represent that its products will prevent any loss byfire or otherwise, or that its products will in all cases provide the protection for whichthey are installed or intended. Buyer acknowledges that SYSTEM SENSOR® is not aninsurer and assumes no risk for loss or damages or the cost of any inconvenience,transportation, damage, misuse, abuse, accident or similar incident.

SYSTEM SENSOR® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OFMERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISEWHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDERNO CIRCUMSTANCES SHALL SYSTEM SENSOR® BE LIABLE FOR ANY LOSS OF ORDAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISINGOUT OF THE USE OF, OR INABILITY TO USE SYSTEM SENSOR® PRODUCTS.FURTHERMORE, SYSTEM SENSOR® SHALL NOT BE LIABLE FOR ANY PERSONALINJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULTOF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.

This warranty replaces all previous warranties and is the only warranty made by SYSTEM

SENSOR®. No increase or alteration, written or verbal, of the obligation of this warrantyis authorized.

Limited Warranty

A Division of Pittway3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495