11
DIESEL GENERATOR SET STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness. Image shown may not reflect actual package. FEATURES FUEL/EMISSIONS STRATEGY • Low Fuel consumption FULL RANGE OF ATTACHMENTS • Wide range of bolt-on system expansion attachments, factory designed and tested • Flexible packaging options for easy and cost effective installation SINGLE-SOURCE SUPPLIER • Fully prototype tested with certified torsional vibration analysis available WORLDWIDE PRODUCT SUPPORT • Cat dealers provide extensive post sale support including maintenance and repair agreements • Cat dealers have over 1,800 dealer branch stores operating in 200 countries • The Cat® S•O•S SM program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products CAT ® C18 ATAAC DIESEL ENGINE • Utilizes ACERT™ Technology • Reliable, rugged, durable design • Field-proven in thousands of applications worldwide • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight • Electronic controlled governor CAT GENERATOR • Matched to the performance and output characteristics of Cat engines • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time • UL 1446 Recognized Class H insulation CAT EMCP 4 CONTROL PANELS • Simple user friendly interface and navigation • Scalable system to meet a wide range of customer needs • Integrated Control System and Communications Gateway

STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

  • Upload
    lythien

  • View
    294

  • Download
    6

Embed Size (px)

Citation preview

Page 1: STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

DIESEL GENERATOR SET

STANDBY484 ekW 605 kVA50 Hz 1500 rpm 400 VoltsCaterpillar is leading the power generationmarketplace with Power Solutions engineeredto deliver unmatched flexibility, expandability,reliability, and cost-effectiveness.

Image shown may notreflect actual package.

FEATURES

FUEL/EMISSIONS STRATEGY• Low Fuel consumption

FULL RANGE OF ATTACHMENTS• Wide range of bolt-on system expansion

attachments, factory designed and tested• Flexible packaging options for easy and cost

effective installation

SINGLE-SOURCE SUPPLIER• Fully prototype tested with certified torsional

vibration analysis available

WORLDWIDE PRODUCT SUPPORT• Cat dealers provide extensive post sale support

including maintenance and repair agreements• Cat dealers have over 1,800 dealer branch stores

operating in 200 countries• The Cat® S•O•SSM program cost effectively detects

internal engine component condition, even thepresence of unwanted fluids and combustionby-products

CAT ® C18 ATAAC DIESEL ENGINE• Utilizes ACERT™ Technology• Reliable, rugged, durable design• Field-proven in thousands of applications

worldwide• Four-stroke-cycle diesel engine combines

consistent performance and excellent fueleconomy with minimum weight

• Electronic controlled governor

CAT GENERATOR• Matched to the performance and output

characteristics of Cat engines• Load adjustment module provides engine relief

upon load impact and improves load acceptanceand recovery time

• UL 1446 Recognized Class H insulation

CAT EMCP 4 CONTROL PANELS• Simple user friendly interface and navigation• Scalable system to meet a wide range of

customer needs• Integrated Control System and Communications

Gateway

Page 2: STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

STANDBY 484 ekW 605 kVA50 Hz 1500 rpm 400 Volts

FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT

System Standard OptionalAir Inlet • Air cleaner

Cooling • Package mounted radiator

Exhaust • Exhaust flange outlet [ ] Industrial [ ] Residential [ ] Critical Mufflers

Fuel • Primary fuel filter with integral water separator• Secondary fuel filters• Fuel priming pump

Generator • Matched to the performance and outputcharacteristics of Cat engines

• Load adjustment module provides engine relief uponload impact and improves laod acceptance andrecovery time

• IP23 protection

[ ] Oversize and premium generators[ ] Permanent magnet excitation (PMG)[ ] Internal excited (IE)[ ] Anti-condensation space heaters

Power Termination • Bus bar [ ] Circuit breakers, UL listed[ ] Circuit breakers, IEC compliant

Control Panel • EMCP 4 Genset Controller [ ] EMCP 4.2[ ] EMCP 4.3[ ] EMCP 4.4[ ] Local and remote annuniciator modules[ ] Load share module[ ] Digital I/O module[ ] Remote monitoring software

Mounting • Rubber vibration isolators

Starting/Charging • 24 volt starting motor• Batteries

[ ] Battery chargers[ ] Oversize batteries[ ] Jacket water heater[ ] Heavy duty starting system[ ] Charging alternator

General • Paint - Caterpillar Yellow except rails and radiatorsgloss black

The following options are based on regional andproduct configuration:

[ ] Seismic Certification per Applicable Building Codes:IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007[ ] UL 2200 package[ ] EU Certificate of Conformance (CE)[ ] CSA Certification[ ] EEC Declaration of Conformity[ ] Narrow, wide or skid base[ ] Sound attenuated, weather protective or high

ambient weather protective enclosures[ ] Single or dual wall integral fuel tanks[ ] Single or dual wall sub-base fuel tanks[ ] Integral & sub-base UL listed dual wall fuel tanks[ ] Automatic transfer switches (ATS)

February 08 2013 14:16 PM2

Page 3: STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

STANDBY 484 ekW 605 kVA50 Hz 1500 rpm 400 Volts

SPECIFICATIONS

CAT GENERATOR

Frame size................................................................ LC6114GExcitation........................................................ Self ExcitationPitch.............................................................................. 0.6667Number of poles...................................................................4Number of bearings...................................... Single bearingNumber of Leads.............................................................. 012Insulation....................... UL 1446 Recognized Class H withtropicalization and antiabrasion- Consult your Caterpillar dealer for available voltagesIP Rating.........................................................Drip Proof IP23Alignment.............................................................. Pilot ShaftOverspeed capability........................................................150Wave form Deviation (Line to Line)................................. 2%Voltage regulator................................Three phase sensingVoltage regulation............Less than +/- 1/2% (steady state)Less than +/- Ω% (w/ 3% speed change)

CAT DIESEL ENGINE

C18 ATAAC, I-6, 4-Stroke Water-cooled DieselBore........................................................ 145.00 mm (5.71 in)Stroke....................................................... 183.00 mm (7.2 in)Displacement.........................................18.13 L (1106.36 in3)Compression Ratio....................................................... 14.5:1Aspiration......................................... Air-to-Air Aftercooled Fuel System.................................... Electronic unit injectionGovernor Type................ Caterpillar ADEM control system

CAT EMCP 4 SERIES CONTROLS

EMCP 4 controls including:- Run / Auto / Stop Control- Speed and Voltage Adjust- Engine Cycle Crank- 24-volt DC operation- Environmental sealed front face- Text alarm/event descriptions

Digital indication for:- RPM- DC volts- Operating hours- Oil pressure (psi, kPa or bar)- Coolant temperature- Volts (L-L & L-N), frequency (Hz)- Amps (per phase & average)- ekW, kVA, kVAR, kW-hr, %kW, PF (4.2 only)

Warning/shutdown with common LED indication of:- Low oil pressure- High coolant temperature- Overspeed- Emergency stop- Failure to start (overcrank)- Low coolant temperature- Low coolant level

Programmable protective relaying functions:- Generator phase sequence- Over/Under voltage (27/59)- Over/Under Frequency (81 o/u)- Reverse Power (kW) (32) (4.2 only)- Reverse reactive power (kVAr) (32RV)- Overcurrent (50/51)

Communications:- Four digital inputs (4.1)- Six digital inputs (4.2 only)- Four relay outputs (Form A)- Two relay outputs (Form C)- Two digital outputs- Customer data link (Modbus RTU) (4.2 only)- Accessory module data link (4.2 only)- Serial annunciator module data link (4.2 only)- Emergency stop pushbutton

Compatible with the following:- Digital I/O module- Local Annunciator- Remote CAN annunciator- Remote serial annunciator

February 08 2013 14:16 PM3

Page 4: STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

STANDBY 484 ekW 605 kVA50 Hz 1500 rpm 400 Volts

TECHNICAL DATA

Open Generator Set - - 1500 rpm/50 Hz/400 Volts DM9826Low Fuel Consumption

Generator Set Package PerformanceGenset Power rating @ 0.8 pfGenset Power rating with fan

605 kVA484 ekW

Fuel Consumption100% load with fan75% load with fan50% load with fan

122.7 L/hr 32.4 Gal/hr92.0 L/hr 24.3 Gal/hr64.0 L/hr 16.9 Gal/hr

Cooling System1

Air flow restriction (system)Air flow (max @ rated speed for radiator arrangement)Engine Coolant capacity with radiator/exp. tankEngine coolant capacityRadiator coolant capacity

0.12 kPa 0.48 in. water645 m≥/min 22778 cfm81.8 L 21.6 gal20.8 L 5.5 gal61.0 L 16.1 gal

Inlet AirCombustion air inlet flow rate 31.6 m≥/min 1115.9 cfm

Exhaust SystemExhaust stack gas temperatureExhaust gas flow rateExhaust flange size (internal diameter)Exhaust system backpressure (maximum allowable)

553.8 º C 1028.8 º F92.1 m≥/min 3252.5 cfm203 mm 8 in10.0 kPa 40.2 in. water

Heat RejectionHeat rejection to coolant (total)Heat rejection to exhaust (total)Heat rejection to aftercoolerHeat rejection to atmosphere from engineHeat rejection to atmosphere from generator

157 kW 8929 Btu/min449 kW 25535 Btu/min76 kW 4322 Btu/min84 kW 4777 Btu/min30.3 kW 1723.2 Btu/min

Alternator2

Motor starting capability @ 30% voltage dipFrameTemperature Rise

1227 skVALC6114G163 º C 293 º F

Lube SystemSump refill with filter 38.0 L 10.0 gal

Emissions (Nominal)3

NOx mg/nm3CO mg/nm3HC mg/nm3PM mg/nm3

3762.8 mg/nm≥656.7 mg/nm≥3.2 mg/nm≥12.6 mg/nm≥

1 For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing restriction from factory.2 Generator temperature rise is based on a 40º C (104º F) ambient per NEMA MG1-32. Some packages may have oversized generatorswith a different temperature rise and motor starting characteristics.3 Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 formeasuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77ºF, 28.42 in HG and number 2 diesel fuelwith 35º API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engineto engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use valuesbased on a weighted cycle.

February 08 2013 14:16 PM4

Page 5: STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

STANDBY 484 ekW 605 kVA50 Hz 1500 rpm 400 Volts

RATING DEFINITIONS AND CONDITIONS

Meets or Exceeds International Specifications: AS1359,CSA, IEC60034-1, ISO3046, ISO8528, NEMA MG 1-22,NEMA MG 1-33, UL508A, 72/23/EEC, 98/37/EC,2004/108/ECStandby - Output available with varying load for theduration of the interruption of the normal source power.Average power output is 70% of the standby powerrating. Typical operation is 200 hours per year, withmaximum expected usage of 500 hours per year.

Ratings are based on SAE J1349 standard conditions.These ratings also apply at ISO3046 standard conditions.

February 08 2013 14:16 PM5

Page 6: STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

STANDBY 484 ekW 605 kVA50 Hz 1500 rpm 400 Volts

DIMENSIONS

Package DimensionsLengthWidthHeight

Information notavailable at this time.

NOTE: For reference only - do not use forinstallation design. Please contactyour local dealer for exact weightand dimensions. (GeneralDimension Drawing #3728295).

www.Cat-ElectricPower.com

2013 CaterpillarAll rights reserved.

Materials and specifications are subject to change without notice.The International System of Units (SI) is used in this publication.

CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow," the"Power Edge" trade dress, as well as corporate and product identity used

herein, are trademarks of Caterpillar and may not be used withoutpermission.

21376420

Performance No.: DM9826

Feature Code: C18DE4Z

Gen. Arr. Number: 2476121

Source: U.S. Sourced

February 08 2013

6

Page 7: STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

LEHE0380-03 Page 1 of 2

C18 Sound Attenuated Enclosures50 Hz / 60 HzThese sound attenuated, factory installed enclosures incorporate internally mounted super critical level silencers, designed for safety and aesthetic value on integral fuel tank base or optional dual wall integral fuel tank base for total fluid containment. These enclosures are of extremely rugged construction to withstand exposure to the elements and provide weather protection.

Image shown may not reflect actual configuration.

Enclosures

Robust/Highly Corrosion Resistant Construction• Factory installed on integral fuel tank base• Environmentally friendly, polyester powder baked paint• 1.6 mm (0.063 in) galvanized steel • All round overhanging base to protect enclosure• High-grade engineering thermoplastic corner posts for protection• Compression door latches giving solid door seal• Zinc plated or black coated stainless steel fasteners• Internally mounted super critical exhaust silencing system

Excellent Access• Large cable entry area for installation ease• Accommodates rear mounted breaker and control panel• Double doors on both sides• Vertically hinged doors with solid bar door stays to hold doors open at 135° rotation• Lube oil and coolant drains pipes to exterior of enclosure and terminated drain valves• Radiator fill cover

Security and Safety• Lockable access doors which give full access to control panel and breaker• Cooling fan and battery charging alternator fully guarded• Fuel fill, oil fill and battery can only be reached via lockable access• Externally mounted emergency stop button• Designed for spreader-bar lifting to ensure safety• Control panel viewing window• Stub-up area is rodent proof

Options• Caterpillar yellow or white paint• Integral dual wall fuel tank base for total fluid containment (fuel, oil and coolant)

Features

Page 8: STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

Enclosures

Model kVA ekW SB/PP LWA

Sound Pressure Levels dBA

Air Flow Rate

Ambient

Capability at

100% Load*1m (3.3 ft) 7m (23 ft)

75%

Load

100%

Load

75%

Load

100%

Load m3/s cfm °C °F

50 Hz

DE605E0550 440 PP 105 82 82 72 72 5.6 11866 43 109

605 484 SB 105 82 83 72 72 5.6 11866 46 115

DE660E0600 480 PP 105 82 83 72 72 5.6 11866 41 106

660 528 SB 105 82 83 72 73 5.6 11866 43 109

DE715E0650 520 PP 105 82 83 72 73 5.6 11866 36 97

715 572 SB 105 82 83 72 73 5.6 11866 41 106

60 Hz

DE550SE0625 500 PP – 84 84 73 74 7.8 16563 47 117

688 550 SB – 84 84 73 74 7.8 16563 48 118

DE600SE0681 545 PP – 84 84 73 74 7.8 16563 42 108

750 600 SB – 84 84 73 74 7.8 16563 43 109

*Ambient capability measured with the Cat extended life coolant at sea level.

Enclosure Package Operating Characteristics

5320 (209.4”)1920 (75.6’’)

2289 (”9

0.1”)

2289 (90.1”)

Approximate weight of enclosure package: 5952 kg (13122 lb). Exact weight is dependent on options. Enclosure weight includes: sound attenuated enclosure, exhaust system, base and generator set.

LEHE0380-03 (10/16)

Materials and specifications are subject to change without notice.CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,

the “Power Edge” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.

www.cat.com/electricpower©2016 Caterpillar

All rights reserved.

Page 9: STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

C18

572 ekW/ 715 kVA

50 Hz/ 1500 rpm/ 400 V

Image shown may not reflect actual configuration

Metric English

Package Performance

Genset Power Rating with Fan @ 0.8 Power Factor 572 ekW

Genset Power Rating 715 kVA

Aftercooler (Separate Circuit) N/A N/A

Fuel Consumption

100% Load with Fan 146.1 L/hr 38.6 gal/hr

75% Load with Fan 108.0 L/hr 28.5 gal/hr

50% Load with Fan 73.2 L/hr 19.3 gal/hr

25% Load with Fan 41.1 L/hr 10.9 gal/hr

Cooling System¹

Engine Coolant Capacity 20.8 L 5.5 gal

Inlet Air

Combustion Air Inlet Flow Rate 37.8 m³/min 1334.7 cfm

Max. Allowable Combustion Air Inlet Temp 52 ° C 125 ° F

Exhaust System

Exhaust Stack Gas Temperature 570.4 ° C 1058.8 ° F

Exhaust Gas Flow Rate 111.8 m³/min 3946.1 cfm

Exhaust System Backpressure (Maximum Allowable) 10.0 kPa 40.0 in. water

TSS-EM1390-00-GS-EPG-10189985.pdf © 2016 Caterpillar All Rights Reserved Page 1 of 3

ELECTRIC POWER - Technical Spec Sheet

572 ekW/ 715 kVA/ 50 Hz/ 1500 rpm/ 400 V/ 0.8 Power Factor

Rating Type: STANDBY Fuel Strategy: LOW FUEL CONSUMPTION

STANDARD

C18

Page 10: STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

DEFINITIONS AND CONDITIONS

1. For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing restriction from factory.

2. UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator temperature rise is based on a 40° C ambient per NEMA MG1-32.

3. Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and number 2 diesel fuel with 35° API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.

Heat Rejection

Heat Rejection to Jacket Water 181 kW 10278 Btu/min

Heat Rejection to Exhaust (Total) 548 kW 31158 Btu/min

Heat Rejection to Aftercooler 109 kW 6196 Btu/min

Heat Rejection to Atmosphere from Engine 90 kW 5120 Btu/min

Heat Rejection to Atmosphere from Generator 31 kW 1769 Btu/min

Alternator²

Motor Starting Capability @ 30% Voltage Dip 2055 skVA

Current 1032 amps

Frame Size A3355L4

Excitation SE

Temperature Rise 150 ° C

Emissions (Nominal)³

NOx 2982.3 mg/Nm³ 6.1 g/hp-hr

CO 347.9 mg/Nm³ 0.7 g/hp-hr

HC 3.8 mg/Nm³ 0.0 g/hp-hr

PM 8.7 mg/Nm³ 0.0 g/hp-hr

TSS-EM1390-00-GS-EPG-10189985.pdf © 2016 Caterpillar All Rights Reserved Page 2 of 3

ELECTRIC POWER - Technical Spec Sheet

572 ekW/ 715 kVA/ 50 Hz/ 1500 rpm/ 400 V/ 0.8 Power Factor

Rating Type: STANDBY Fuel Strategy: LOW FUEL CONSUMPTION

STANDARD

C18

Page 11: STANDBY 484 ekW 605 kVA 50 Hz 1500 rpm 400 Volts Panel • EMCP 4 Genset Controller [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4 [ ] Local and remote annuniciator modules [ ] Load share

Applicable Codes and Standards:

AS1359, CSA C22.2 No100-04, UL142,UL489, UL869, UL2200, NFPA37, NFPA70, NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, ISO8528, NEMA MG1-22,NEMA MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.

Note: Codes may not be available in all model configurations. Please consult your local Cat Dealer representative for availability.

Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions

Fuel Rates are based on fuel oil of 35º API [16º C (60º F)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when used at 29º C (85º F) and weighing 838.9 g/liter (7.001 lbs/U.S. gal.). Additional ratings may be available for specific customer requirements, contact your Cat representative for details. For information regarding Low Sulfur fuel and Biodiesel capability, please consult your Cat dealer.

www.Cat-ElectricPower.com

STANDBY:Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.

The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, ADEM, EUI, S•O•S, "Caterpillar Yellow" and the "Power Edge" trade dress, as well as corporate

and product identity used herein, are trademarks of Caterpillar and may not be used without permission.

Performance No.: EM1390-00Feature Code: C18DEAPGenerator Arrangement: 5027420

Source Country: U.K.

Date: 09/05/2016

TSS-EM1390-00-GS-EPG-10189985.pdf © 2016 Caterpillar All Rights Reserved Page 3 of 3

ELECTRIC POWER - Technical Spec Sheet

572 ekW/ 715 kVA/ 50 Hz/ 1500 rpm/ 400 V/ 0.8 Power Factor

Rating Type: STANDBY Fuel Strategy: LOW FUEL CONSUMPTION

STANDARD

C18