BPL Telecom Private Limited11th KM, Bannerghatta Road, Arakere, Bangalore - 560 076.Ph: +91-80-2648 4314/4348/4350/4388/0209Business Enquiry: [email protected] Service: [email protected]
BPL PFE Series - The on-line UPS with Active Input Power Factor enhancement.
BPL PFE 101 (1Ø/1Ø) 10kVABPL PFE 301 (3Ø/1Ø) 10kVA - 40kVABPL PFE 303 (3Ø/3Ø) 10kVA - 40kVA
Applications: IT Majors, Data Centres, Cloud Service Providers, Computer Labs, Browsing & Internet CentresSurveillance Cameras & Equipment, Telecom & Networking Equipment with Fax, POS Devices, Critical & Emergency LightingHealth Care Systems, Operation Theatres, Diagnosis Equipment, Lifesaving Equipment, Treadmill & Gym,Educational Institutions, Printing Machines, Photocopiers, Digital Colour Labs, Recording Studios, Home Theatres.
BPL SCN - The on-line UPS specifically designed for MRI and CT Scanner applications of any make.BPL SCN (3Ø/3Ø) 60kVA - 150kVA
BPL IAN Series - The on-line UPS (with 0.9PF & <10% THDi) designed for Industrial Applications.BPL IAN 303 (3Ø/3Ø) 60kVA - 240kVA
Applications: CNC, Laser Cutting Machine, Automotive Manufacturing, Metal Smelting, Extrusion, Annealing, Kiln, Industrial Ovens, Tetra Packing Industry, Chemical Process, Oil & Gas Pipeline Control, Conveyors, Escalators and Material Lifts, Stone Crusher, Tiller, Centralised Air Conditioners and Pharmaceutical Industry.
BPL GSS Series - The Grid Sharing Solar UPS with MPPT 10kW - 100kW
Applications: Agricultural Pumps and Others, Educational Institutions, Hospitals, Industrial Applications.
ETHERNET
POWER
BPL UPSin the Enterprise Environment
TDM PBX
BPL Analog Stations
Trunk Line
Analoglines
Trunklines
BPL FXO
BPL FXS
BPL Digital Stations
POSTerminals
Non-POESwitch
POE Switch
BPL Security Camera
BPL-IP-PBX
ETHERNET (LAN)
BPL SIP Phone
BPL AnalogPhones
BPL IP Conference Phone
ROUTER
Colour Printer& Scanner
Fax Terminal Projector
PC / LAPTOP / BPL THIN CLIENT
CENTRAL SERVER
• BPLEquipment istobehandledbyacompetentperson
• ProperBiasingoftheUPSbeforeconnectingthebattery is a must
• AlwaysuseRubberHandGloves&Shoes• Useproperearthingtoavoidshocks• Disconnectthebattery,powerinputanddischarge
all components before disconnecting the module• Usetagforeveryinputandoutput
CAUTION
Loop Start TK
Release Version July 1302 V02
Grid Sharing / Hybrid SOLAR UPS
Grid Sharing SOLAR UPS• Excellent load sharing between Solar and
Grid• Ensures 100% utilisation of Solar power
by using a highly efficient built-in MPPT Converter
• Rugged Industrial grade IGBT inverter withcomplete galvanic isolation ensures high quality power delivery
• Higher efficiency battery charger ensuresextended battery life by providing temperature compensation and float cum boost charging
The primary source of power of the BPL Grid Sharing Solar UPS is Solar Power, the total load is shared between Solar & Grid during the mains availability and between solar & Battery during mains power failure. The UPS output gives conditioned power without change over & is ideal for critical applications. When solar power is adequate to cater to the load demand, no power is drawn from the Grid and the solar power would take care of Battery charging, any short fall in solar power availability, the deficit power is drawn either from Grid or Battery.
BPL Grid Sharing Solar UPS comes with high efficiency of conversion of Solar energy, the output of MPPT is fed to the intelligent power sharing module which ensures maximum power utilization from the solar Panel. 1 KW of Solar Power (Which needs a floor space of 3m X 3m) will save approximately 5 Units of Electricity per day.
Featured products:Solar INVTS specially designed for irrigation pump sets. Three phase solar INVTS for industrial application, farm houses, resorts, lifts and emergency lighting systems without battery and grid.
Application-specific solar UPS for:•Educationalinstitutions•CT,MRIandultrasoundscanners
Solar Panel Grid / Mains Power
MPPT Converter
BATTERY
Temperature compensated
Float cum Boost Charger
Power monitoring and Sharing Mode
IGBT Inverter with Galvanic isolation
OUTPUT
Indigenous Design as per international standards ensures value for investment with long product life.
SALIENT FEATURES• BPL power conditioning UPS Systems reduce wear
and tear on expensive equipment connected to your power supply and prevent break-downs
• Process lossesdue tounexpectedpower stoppagesare eliminated
• Our robustproductseliminate theneedfor frequentmaintenance and minimise disruption of work
• BPLUPSSystemsarehighlyefficientandreducethetotal cost of ownership
BPL Telecom, an early Indian pioneer in Communications and Power Sector Electronics now brings you a range of power conditioning solutions and on-line UPS systems. Our products are supported by trained sales and service teams spread across the country. We can respond to your needs at short notice to provide you with a solution that meets your specific needs.
BPL IAN Model (60 KVA to 240 KVA)• InputPF0.9and<10%THDi• Activeparallelredundancycompatible• Temperature compensated Float cum Boost Charger
for longer battery life• RemotepowermonitoringbyourServiceTeam• Solar ready models - Solar power capacity can be
upgraded in phases
Overall efficiency on 100% load 90 - 93%
Operating ambient temp 0 - 40ºC
Enclouser protection grade IP - 20
Testing standard As per IEC 62040 - 3
Charge type CCCV
Charging current standard 0 - 20A
Inverter protectionAdvanced electronic protection for device safety backed up with MCBs / MCCBs and fast acting fuses, high speed pulse by pulse electronic device protection, over voltage / under voltage protection, electronic over current trip with reset and manual bypass
Software Interface - optional UPS manager-PC/Network interface and mobile phone interface
Load redundancy - optional Cross load sharing-active parallel redundancy (CLS - APR)
Inverter type IGBT based MPWM with instantaneous sine wave control
Power factor 0.8 lag
Nominal Voltage 400V Phase-Phase : 230V Ph-Neutral
Balanced / Unbalanced load (±1%), 120º ± 0.5º regulation & phase shift
Frequency 50Hz ± 0.1%
Wave form True sine wave
Linear load and Non - linear load harmonic distrotion < 2%, < 6%
Transient response Remains within ± 5% & recover to normal within 20 msec
Over load capacity 100% continues / 125% - 1min / 150% - 5sec
Nominal output current / phase 60kVA - 70A / 80kVA-93A / 100kVA-115A 120kVA-140A / 150kVA-173A / 200kVA-231A / 240kVA-278A
Crest factor 3 : 1
Type 12-Pulse rectifier
Voltage regulation (±)1%
Ripple Voltage < 2% without battery
Converter protectionAdvanced electronic protection for device safety backed up with
MCBs/MCCBs and fast acting fuses
TECHNICAL SPECIFICATION - BPL IAN UPS
RECTIFIER
INPUT
INVT
CHARGER
EFFICIENCY
Input voltage 415V AC (3 Phase & Neutral)
Input voltage window 330- 470V
Input frequency 50Hz ± 10%
Input current harmonics With <10% THDi the input PF is improved and reduces the burden on the input power source
Input power factor > 0.9
Power walk in Soft start for 0 - 20 seconds walk-in
Technology Double conversion On-line with the latest MPWM technology using IGBT
Rating 60KVA - 240kVA
DC Bus 360V DC
MODEL BPL PFE Series BPL SCN (CT & MRI Scanners)
RATING 10 kVA (1Ø -1Ø) 10 - 40kVA (3Ø-1Ø) 10 - 40kVA (3Ø - 3Ø) 60 - 150kVA (3Ø - 3Ø)
DC BUS 192V 360V
TECHNOLOGY Double conversion On-line with the latest MPWM technology using IGBT
INVERTER TYPE IGBT based MPWM with instantaneous sine wave control
POWER FACTOR 0.8 lag
NOMINAL VOLTAGE 220 VAC / 230 VAC 220VAC / 230VAC 400 V Ph- Ph :230V Ph - Neutral 200V Ph - Ph : 115V Ph - Neutral
REGULATION ( ± ) 1% ( ± ) 1% Balanced & unbalanced load
FREQUENCY 50 Hz ± 0.1Hz
WAVE FORM True Sine wave
TOTAL HARMONIC LINEAR LOAD < 2%
DISTORTION NON LINEAR LOAD < 6% < 5% < 6%
TRANSIENT RESPONSE Remains within +/- 5 % & recover to normal within 20msec
OVER LOAD CAPACITY
100% Continuous
125% 1 Minute
150% 5 Seconds
NOMINAL OUTPUT CURRENT 34.8A 70A 23A - 35A 140A - 346A
CREST FACTOR 3:1 4:1
MODE OF OPERATION Designed for continuous operation
ISOLATION True online with complete galvanic isolation I/P to O/P galvanic isolation
INVERTER PROTECTION Advanced Electronic Protection for device safety backed up with MCB’s & fast acting fuses, high speed pulse by pulse electronic device protection over voltage / under voltage protection, Electronic over current trip with reset.
MANUAL BYPASS Provided
OVERALL EFFICIENCY @100% LOAD > 87% > 90% >88% > 93%
ALARMS Input / Low / Fail, Output overload, Over temperature, Battery low
LED INDICATIONS Mains on, Charger on, Inverter on, Battery Low, Overload, Inverter Trip
USER FRIENDLY LCD DISPLAY Input Voltage, Output voltage, Load percentage, Output frequency, Battery voltage
CHARGER TYPE CVCC CCCV
ENCLOUSER PROTECTION GRADE IP - 20
COOLING Forced air
ACOUSTIC NOISE LEVEL <60db @ 1.5 meter
AMBIENT TEMPERATURE 0 to 40 Deg C
STORAGE TEMPERATURE -10 to 70 Deg C
HUMIDITY Up to 95% RH Non condensing
ALTITUDE <3000 feet above sea level(without derating)
TESTING STANDARD As per IEC 62040 - 3
SOFTWARE INTERFACE-OPTIONAL UPS manager-PC/network/GSM
CONNECTIVITY-OPTIONAL Via RS-232 for a single PC or RJ 45 connector for multiple PC
TYPE IGBT based full bridge 6 Pulse/12 Pulse
VOLTAGE REGULATION ( ± ) 1%
RIPPLE VOLTAGE < 2% without battery
CONVERTER PROTECTION Advanced Electronic Protection for device safety backed up with MCB’s & fast acting fuses
INPUT VOLTAGE 230V AC 1Ø 415V AC 3Ø & N
INPUT WINDOW 170 - 270V 330 - 470V
INPUT FREQUENCY 50Hz ± 10%
INPUT PFC @ 100% LOAD 0.99 >0.90 >0.95 >0.9
POWER WALK IN Soft start for 0-20 seconds power walk-in
INPUT
Note: Specifications are indicative of our standard models and are subject to change without notice.Note: Specifications are indicative of our standard models and are subject to change without notice.
MODEL BPL GSS 101 BPL GSS 301 BPL GSS 303
TECHNOLOGY MPPT based Grid sharing solar technology
RATING 1Ø Input - 1Ø Output 3Ø Input - 1Ø Output 3Ø Input - 3Ø Output
CAPACITY 10kW 10kW ~ 40kW 10kW ~ 100kW
DC BUS 192V 192V - 360V 360V
TECHNICAL SPECIFICATIONS - BPL GSS SERIES GRID SHARING SOLAR UPS
UTILITY POWER INPUT
PROTECTIONS
EFFICIENCY AS PER IEC 61683
MUTI-FUNCTIONAL SOLAR LCD ENERGY METER
INVT
INVT
RECTIFIER
TECHNICAL SPECIFICATIONS - BPL PFE & SCN SERIES UPS
BATTERY
SOLAR INPUT
INPUT VOLTAGE 230V -1Ø 415V - 3Ø - 4 Wire 415V - 3Ø -4 Wire
INPUT VOLTAGE WINDOW 170 - 270V 330 - 470V 330 - 470V
INDICATES FOLLOWING PARAMETERS •SolarVoltage•SolarCurrent•SolarPower•SolarEnergygenerated(Generated&deliveredtoLoad) •InputVoltage•OutputVoltage•BatteryVoltage•LoadCurrent
•UnderVoltage/Overvoltage•OverTemperature•BatteryLow•OverLoad•ShortCircuit
ENCLOSURE PROTECTION IP-20
INVERTER TYPE IGBT based MPWM with instantaneous Sine wave Control
POWER FACTOR 0.8 lag
NOMINAL VOLTAGE 230V / 50Hz 230V / 50Hz 400V / 50Hz
REGULATION-BALANCED LOAD ( ± ) 1% ( ± ) 1% ( ± ) 1%
REGULATION-UNBALANCED LOAD NA NA ( ± ) 1%
UNBALANCED LOAD PHASE SHIFT NA NA 120º ± 0.5º
OVER LOAD CAPACITY 125% for 1 Minute : 150% for 10 Seconds
CREST FACTOR 3:1
BATTERY TYPE SMF / TUBULAR
CHARGER TYPE Float cum Boost / CCCV
TEMPERATURE COMPENSATION 5 mv / Cell / ºC variation
CHARGING CURRENT 0 - 30A 0 - 40A 0 - 50A
OPERATING MPPT VOLTAGE 150V - 180V 180V - 330V 330V
MAXIMUM PANEL CURRENT 50A 100A 250A
REVERSE POLARITY PROTECTION Short Circuit Diode
BACK FEED PROTECTION Protected using reverse diode
MPPT EFFICIENCY 96% ( Peak)
CONFIGURATION Grid Sharing
SHARING METHOD Parallel Operation of Solar and Grid Power
SHARING PERCENTAGE 0 - 100% depending on the availability of solar power against the power Demand of the load.
OVERALL EFFICIENCY- 100 % LOAD 90% 92% 93%
TESTING STANDARD As per IEC 62040 - 3 / IEC 61683