18th Edition | July 31, 2017 Patient Safety Standards, Materials and Systems Guidelines Recommended by the New York State Office of Mental Health With respect to NYS-OMH operated facilities, these Guidelines apply solely to new construction and major renovation projects. Existing facili- ties should use these Guidelines as a reference document whenever they make improvements. Developed in association with

Patient Safety Standards, Materials and Systems Guidelines

  • Upload
    dodat

  • View
    276

  • Download
    13

Embed Size (px)

Citation preview

Page 1: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017

Patient Safety Standards,Materials and Systems GuidelinesRecommended by theNew York State Office of Mental HealthWith respect to NYS-OMH operated facilities, these Guidelines apply solely to new construction and major renovation projects. Existing facili-ties should use these Guidelines as a reference document whenever they make improvements.

Developed in association with

Page 2: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 2

Patient Safety Standards,Materials and Systems GuidelinesRecommended by theNew York State Office of Mental HealthTable of Contents Introduction Purpose

ApproachBest Practice 1980 to Early 1990’s1998JCAHOSentinelEventNotificationCurrent Best PracticeRisk ManagementRisk Assessment - Service providers shall perform

prior to utilizing this standard Nomenclature & ApplicabilityProduct Evaluation Process

Anti-Barricade Strategies

Seclusion Room Standards

Patient Safety Standards Materials & Systems

Division 01 | General Requirements Tamper Resistant Fasteners Division 07 | Thermal & Moisture Protection Security Sealants, Tamper Resistant Division 08 | Openings

Door Hardware, Door Top Sensors Door Hardware, Door Top Sensors, Alarm Visual

NotifiersDoor Hardware, Continuous HingesDoor Hardware, Locks & HandlesDoor Hardware, Lever HandlesDoor Hardware, Privacy ThumbturnsDoor Hardware, Door PullsDoor Hardware, Door StopsDoor Hardware, Door Closers Door Hardware, GasketingGlazing, GeneralGlazing, Exterior WindowsGlazing, Interior Windows

Division 08 | Openings (Continued)Glazing, Observation Mirrors Exterior WindowsAccess Doors

Division 09 | FinishesCeiling Assemblies, General Wall BaseCeilings

Division 10 | Specialties Shower & Privacy Curtains Closet Rods, Clothes & Towel Hooks Handrails & Grab Bars, General Handrails Toilet Accessories, Grab Bars Toilet Accessories, General Toilet Accessories, Soap Dispensers Toilet Accessories, Paper Towel Holders &

Dispensers Toilet Accessories, Hand Dryers Toilet Accessories, Toilet Tissue Holders &

Dispensers Toilet Accessories, Mirrors Window Treatments Artwork Frames Cabinet Hardware Signage Fire Extinguisher CabinetsDivision 12 | Furnishings Furniture, General FurnitureDivision 21 | Fire Suppression SprinklersDivision 22 | Plumbing

Lavatory Assemblies, General Lavatory Assemblies Lavatory Basins

Division 22 | Plumbing (Continued)Lavatory Pipe Enclosures Lavatory FaucetsLavatory Grid Strainers Toilets, GeneralToiletsToilet FlushometersToilet Flush Valve Covers Hydration StationsShower Heads Hand ShowersShower Controls & Activators

Division 23 | HVACHVAC, General Thermostats Diffusers & Grilles

Division 26 | ElectricalReceptacles & Switches, GeneralReceptacles & GFCI/AFCI Circuit Breakers Wall PlatesSensorsLight Fixtures, GeneralLight Fixtures, Lenses Light Fixtures, Interior, General, Surface Mounted Light Fixtures, Interior, General, Recessed Light Fixtures, Interior, Task LightingLight Fixtures, Interior, Night LightingLight Fixtures, Exit Signage

Division 27 | CommunicationsWireless Routers

ClocksDivision 28 | Electronic Safety & Security

Fire Alarm Components, GeneralFireAlarmComponents,NotificationDevices

Page 3: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 3

This document offers guidance with respect to patient safety features in the inpatient psychiatric environments throughout New York State. ItgrowsoutofthestandardsofnewconstructionfortheNewYorkStateOfficeofMentalHealth’s(NYS-OMH)inpatienthospitalsinordertoprovideguid-ance for:

w Existing NYS-OMH state-operated inpatient facilities w Psychiatric units in NYS-OMH licensed Article 28 general hospitals w NYS-OMH licensed Article 31 hospitals

This document is not intended to provide guidance for outpatient psychiatric facilities. Generally the risks associated with outpatient facilities may not war-rant special environmental precautions.

Introduction

Page 4: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 4

IntroductionPurpose

Thepurposeoftheseguidelinesistoprovideaselectionofmaterials,fixtures,andhardwarethattheNYS-OMHhasreviewedandsupportsforusewithininpatient psychiatric units to further the agency’s goal of reducing the risk of harm to individuals in inpatient settings. Utilization of any of these products is not mandatory.

TheNYS-OMHwouldbepleasedtoevaluateotherproductsidentifiedbyhospitals. Many of the items in this document represent the current state of the art. It is anticipated that additional or more effective products will continue to be developed. The NYS-OMH intends to periodically update these guidelines to keep current with these changes, but the hospitals also have an obligation to continue to review products that will assist in this goal. The items selected here represent styles and properties of products that help lower patient risk while on an inpatient psychiatric unit. However, installation of these products will not eliminate all risks.

Page 5: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 5

IntroductionApproach

OMH supports a multi-directed approach to the reduction of patient harm on inpatient psychiatric units including the following:

w Completion of a patient risk assessmentw Completion of a physical plant risk assessmentw Ongoing staff training to ensure awareness of potential risks on unitsw Installation of products in all patient areas that reduce riskw Routine inspections of inpatient psychiatric units to ensure safety levels are maintained

Additional and more detailed information on some of the items found in these standards may be available from NYS-OMH.

ByprovidingtheseguidelinestheNewYorkStateOfficeofMentalHealthneitherendorsesnorpromotesanyproductormanufacturer.OMHdoesnotguarantee the performance of any product. OMH recognizes that it is not possible to evaluate all products that are for sale. Under these circumstances it is at NYS-OMH’s discretion which products are selected for review.

Theabsenceofanyproductfromtheguidelinesdoesnotnecessarilymeanthattheproductisunsafeorunacceptableforuse(refertotheparagraphsthatfollow).IfahealthcarefacilityhasinstalledproductsthatwerepreviouslyrecommendedinanearliereditionofthePatientSafetyStandards(PSS)butareno longer listed in the PSS, it is the responsibility of the health care facility to reassess that product to determine whether its continued use is consistent with that hospital’s safety risk assessment policies.

Itiscrucialthathospitalmanagerscompleteriskassessmentsthatgobeyondtheselectionofthematerials,furnishings,andfixturesfoundinthesePatientSafetyStandards.TheFacilitiesGuidelinesInstitute(FGI),“2010GuidelinesfortheConstructionofHospitalsandOutpatientFacilities”providesclear,detaileddirectionregardingahospital’sresponsibilitytobeincompliancewithpatientsafetyrequirements.Section1.2-3SafetyRiskAssessment(SRA)andAppendixA1.2-3covergeneralriskassessmentprocedures.Section1.2-3.6andAppendixA1.2-3.6,BehavioralandMentalHealth(PsychiatricPatientInjuryandSuicidePrevention)provideadditionalguidanceforhealthcareprovidersservingthispopulation.

Within this larger construct, the selection of products to be used in the built environment is but one component of risk management policies and procedures that every healthcare facility is responsible for developing and maintaining.

Page 6: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 6

IntroductionBest Practice 1980 to Early 1990’s

Focus Above the Waist

Thereductionofselfharmincidentsisoftenamatteroflifeordeath.Suicideattemptsusingaligature(e.g.strangulation)arethemostprevalentformofself harm. This was initially addressed in modern hospital design by strongly focusing on the elimination of ligature attachment points that were above the waist line.

Above the Waist Ligature Attachment Points:

w Fastenersw Door Hingesw Door Closersw Windows & Vision Panelsw Access Doorsw Ceiling Systemsw Shower & Privacy Curtainsw Clothes & Towel Hooksw Closet Barsw Mirrorsw Toilet Partitionsw Window Treatmentsw Bulletin Boardsw Picture Hanging Systemsw Cabinet Hardwarew Sprinklerheadsw Showerheadsw Medical Gas Enclosuresw HVAC Devices & Coversw Thermostatsw Electrical Receptaclesw Light Fixturesw Fire Alarm Components

Page 7: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 7

Introduction1998 JCAHO Sentinel Event Notification

TheJointCommissiononAccreditationofHealthcareOrganizations(JCAHO)surveysreflectamandateforanaggressiveproactiveapproachtotheelimi-nation of risks to patient safety.

November 6, 1998 - Sentinel Event Alert, Issue 7:Inpatient Suicides: Recommendations for Prevention

“SincetheJointCommissionenacteditsSentinelEventPolicytwoyearsago,theAccreditationCommitteeoftheJointCommission’sBoardofCommis-sioners has reviewed 65 cases related to inpatient suicides. A root cause analysis was completed for each of the events reviewed. Most of the suicides occurredinpsychiatrichospitals(34),followedbygeneralhospitals(27)andresidentialcarefacilities(4).Ofthosecasesingeneralhospitals,14occurredin psychiatric units, 12 in medical/surgical units and one in the emergency room.

Inseventy-fivepercentofthecases,themethodofsuicidewashanginginabathroom,bedroom,orcloset.Twentypercentofthesuicidesresultedfrompatientsjumpingfromarooforwindow.”

The Joint CommissionIssue 7 - November 6, 1998

Page 8: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 8

IntroductionCurrent Best Practice

Focus Everywhere

Today, all behavioral healthcare facilities, whether new or existing, are required to meet comprehensive accreditation standards to ensure that the risks to patient safety are minimized. Principles that support patient safety strategies avoid systems, assemblies and materials that can be weaponized, yield sharp edges, or provide ligature points in all locations accessible to patients.

Additional Ligature Attachment Points to Consider:

w Caulk & Sealantsw Door Handlesw Door Bumpersw Rubber Basew Trim Strips between Assembliesw Toilet Accessoriesw Grab Barsw Fire Extinguisher & Hose Cabinetsw Furniturew Lavatoriesw Lavatory Faucetsw Lavatory Valvesw Toilet Seatsw Toilet Flush Valvesw Shower Controls & Activatorsw Plumbing Traps & Piping

Page 9: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 9

IntroductionRisk Management

Risk Management, Not Risk EliminationAIA Guidelines for the Design and Construction of Healthcare Facilities, 2010 Edition, Appendix

A1.2 Environment of CareA safe environment is critical; however, no environment can be entirely safe and free of risk. The majority of persons who attempt suicide suffer from a treatable mental disorder or a substance abuse disorder or both. Patients of inpatient psychiatric treatment facilities are considered at high risk for suicide; the environment should avoid physical hazards while maintaining a therapeutic environment. The built environment, no matter how well it is designed and constructed, cannot be relied upon as an absolute preventive measure. Staff awareness of their environment, the latent risks of that environment, and the behavior risks and needs of the patients served in the environment are absolute necessities. Different organizations and different patient populations will require greater or lesser tolerance for risk.

Page 10: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 10

IntroductionRisk Assessment

High Risk approved products are safe for all locations. Though High Risk products may be safe for all areas, they may not be appropriate for all areas. In many cases the High Risk product will look too institutional for the area. Determining an individual room’s risk assignment will depend on a room by room RiskAssessmentofallareasofthefacilitywhichhasbeenconductedspecificallyforeachfacilityusingthathospitalorsystem’sownriskassessmenttool.Thefollowingaretypicalgroupingsofroombyrisk.Eachhospital’sassessmentmayvarybaseduponpatientprofile,staffing,orunitgeography.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Typical High Risk Areas

Patientisdifficulttomanage,orriskofsolitaryand/orunsuperviseduse: w Patient Bedrooms w Bathrooms & Toilet Rooms w Seclusion Rooms w Comfort Rooms w Specialcaretobetakeninon-unitpatientspaceswithceilingslessthan9’-0”abovefinishedfloor

Typical Medium Risk Areas

Patient access is controlled, or use is supervised with no solitary and/or unsupervised use: w Living Rooms w Dining Rooms w Group Rooms w Corridors

Typical Low Risk Areas

No patient use or constantly supervised: w Medication Rooms w Offices w Clean & Soiled Utility Rooms

Page 11: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 11

IntroductionNomenclature & Applicability

Notes like this on each page will identify additional considerations that are applicable, and also will identify alternative products that are acceptable as minimum standards for Article 31 hospitals, Article 28 hospitals, and as existing conditions in state-operated hospitals.

Accepted by OMHItems with this symbol constitute a best practice for all existing facilities and a minimum standard for new construction and renovationprojectsatNYS-OMH’sstate-operatedinpatienthospitals.Unlessalternativesareidentifiedinthenotessectionofthepage, such items are also minimum standards for Article 31 and Article 28 hospitals.

Under NYS-OMH EvaluationItems with this symbol are currently being assessed by NYS-OMH for suitability in NYS inpatient psychiatric hospitals or units.

RetrofitItems with this symbol are not suitable for use in new construction but are acceptable for renovation in NYS inpatient psychiatric hospitals or units.

Use with CautionItems with this symbol might be suitable for certain inpatient environments; however, they should be used with caution. Some of theseitemshaveinstitutionalcharacteristicsthatarenotappropriateforanenvironmentthatiscertifiedbytheJointCommission,whichrequiresnon-institutionalfittingsandfixtures.Othersitemshaveinherentrisksthatmustbeevaluatedfortheirappropriateness for the intended application. Typically, the associated notes describe why the device is to be used with caution.

NYS-OMH RejectedItems with this symbol are unsuitable for use in new construction or renovation in NYS inpatient psychiatric hospitals or units.

Gold SealItems with this symbol have withstood paper clip testing in addition to all other applicable testing methods.

Page 12: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 12

IntroductionProduct Evaluation Process

NYS-OMH evaluates products for inclusion into its Patient Safety Standards using a variety of criteria. These criteria fall into two categories; Primary Criteria and Secondary Criteria.

Primary Criteria

w Ligature Resistance: Loopingw Ligature Resistance: Wedgingw Cuttingw Jumpingw Tamper Resistancew Weaponizationw Contraband Storagew PICA/Ingestion

Secondary Criteria

w Ligature Resistance by combining a ligature with other readily available objectsw LigatureResistancethatistheresultoftheconfigurationinwhichaproductisinstalledw Codes & Regulationsw Therapeutic Environment & Appearancew Constructibilityw Durabilityw Maintenance

Thepresenceofpaperclipsineventhemostrigorouslymonitoredinpatientenvironmentisdifficulttocontrol.Becausepaperclipsmaybeavailabletopatients, tests for product inclusion in the OMH Patient Safety Standards include an attempt to utilize paper clips in concert with other objects to develop ligature on tested items. It should be assumed that almost anything in the patient environment can be compromised by a paper clip; for those items that withstand the ligature testing with use of paper clips, a product may be accepted by OMH and receive a special notation indicating that it has withstood such testing methods. indicates a product withstanding paper clip testing in addition to all other applicable methods of testing and is appropriate for use in high risk areas.

As is written on page 4 of this document, a much more comprehensive assessment of risk in the patient environment is always necessary in order to meet the spirit of the Patient Safety Standard recommendations.

The availability of safe products for the inpatient environment is a growing and evolving market. New products are routinely introduced by manufacturers. Products that were once accepted by NYS-OMH in previous versions of the Patient Safety Standard may be rejected or phased out in future versions in light of new products or new knowledge about their risks. For more information about the NYS-OMH Product Evaluation Process, contact NYS-OMH.

Page 13: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 13

Anti-Barricade Strategies

An unintended consequence of providing more patient privacy is the increased opportunity for a patient to use a bedroom or bathroom door as a barricade. Solutions range from direct penetration of the door by force to using advanced door systems that can be opened outward in an emergency situation. The directsolutionismoreeconomicalatfirst,butwillrequirereplacementofthedoor.Theadvanceddoortechnologydoesnotharmthedoor,butsignificantlyincreases the initial construction cost. The ten options listed below span this continuum.

Page 14: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 14

Anti-Barricade Strategies

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Accurate Lock & Hardwarewww.accuratelockandhardware.com

Keyed Emergency StopADL-CEK, ADL-OEKDouble lip strikes with keyed emergency stop. Designed to restrict and protect against unauthorized outswinging door. Key locks emergency stop into projected position.

Anti-Barricade Hardware | Constructibility NotesAdd compression seal at jamb and strike edge of doors for privacy. May be omitted on private bathroom doors opening into private bedrooms. Doors that are not steel or solid core require reinforcing for top and bottom pivots.

Anti-Barricade Hardware | Code NotesFor corridor doors, verify Life Safety Code requirements to limit passage of smoke. Specify appropriate gap tolerances at top and jambs.

Cautions:w A non-locking hospital stop may allow patients to depress the stop and swing the door in the opposite direction. Overpronation of the door in this direction has, in some instances, resulted in patients breaking the door.w Small hospital stops that concentrate the door closing pressure on a small surface area have been known to

result in breakage of structural composite lumber doors when doors are slammed by patients.w In situ evaluation reveals that the use of a single rescue stop in line with the latch is insufficient in acting as a

reliable stop when a door is being subjected to abuse (i.e. being repeatedly slammed). It is recommended that at least two stops be used: one at the top 1/3 point along the height of the door and one at the bottom 1/3 point along the height of the door to better distribute the force of the slamming along the door stile.

McKinneywww.mckinneyhinge.com

DS-6 Emergency StopUsed to convert double acting doors hung on center pivots to single acting doors. Emergency release allows door to swing open in the opposite direction.

Page 15: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 15

Anti-Barricade Strategies

Royde & Tucker Ltd.www.ratman.co.uk

Emergency StopH131-105Used in conjunction with a pivot set. The release device can be depressed to allow the door to open outward and allow access to the room.

Note: Allows for wedging ligature.

Anti-Barricade Hardware | Constructibility NotesAdd compression seal at jamb and strike edge of doors for privacy. May be omitted on private bathroom doors opening into private bedrooms. Doors that are not steel or solid core require reinforcing for top and bottom pivots.

Anti-Barricade Hardware | Code NotesFor corridor doors, verify Life Safety Code requirements to limit passage of smoke. Specify appropriate gap tolerances at top and jambs.

Cautions:w A non-locking hospital stop may allow patients to depress the stop and swing the door in the opposite direction. Overpronation of the door in this direction has, in some instances, resulted in patients breaking the door.w Small hospital stops that concentrate the door closing pressure on a small surface area have been known to

result in breakage of structural composite lumber doors when doors are slammed by patients.w In situ evaluation reveals that the use of a single rescue stop in line with the latch is insufficient in acting as a

reliable stop when a door is being subjected to abuse (i.e. being repeatedly slammed). It is recommended that at least two stops be used: one at the top 1/3 point along the height of the door and one at the bottom 1/3 point along the height of the door to better distribute the force of the slamming along the door stile.

Page 16: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 16

Anti-Barricade Strategies

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Rixsonwww.rixson.com

340 Center Hung Top PivotCenter hung, non-handed walking beam-type hinge. Fully concealed when door is closed.

117-3/4 Center Hung Pivot SetFully concealed, parallel arm, non-handed. Can be coordinated with a concealed overhead closer.

Cautions:w Double swinging doors can’t be fire

rated.w Use only at doors where needed as

part of an anti-barricade strategy.

Anti-Barricade Hardware | Constructibility NotesRefertomanufacturer’sdatawhenusingremovablestopsinfireratedassemblies.

Anti-Barricade Hardware | Code NotesFor corridor doors, verify Life Safety Code requirements to limit passage of smoke. Specify appropriate gap tolerances at top and jambs.

Caution: All hinges inherently carry risk.

Page 17: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 17

Anti-Barricade Strategies

Alternate Removable Stop

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Pemkowww.pemko.com

Emergency Stop (ERS)Pemko Continuous Swing-Away Door-stop provides emergency outward opening operation of doors that normally open inwards. The stop hinge has a hospital tip, unlocks by a tool and swings open with an integral grab handle.

Caution: Emergency Stop only has one latching point towards the top of the stop.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Pemkowww.pemko.com

Double Swing Hinge (Geared-Style)Alternate Hinge Option for use with EmergencyStop(ERS)

Caution: Double Swing must be mounted with gears facing out into the corridor.

Pemkowww.pemko.com

Double Swing Hinge (Barrel-Style)Alternate Hinge Option for use with EmergencyStop(ERS)

Page 18: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 18

Anti-Barricade Strategies

Kingsway Groupwww.kingswaygroupglobal.com

Swing StopKG 205/206 Anti-Barricade Door Stop, HardwoodKG 207/208 Anti-Barricade Door Stop, Aluminum

Kingsway Groupwww.kingswaygroupglobal.com

Swing HingeKG202

Page 19: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 19

Anti-Barricade Strategies

Laidlawwww.laidlawdirect.com

Swing Away Stop

Note: Potential for looping with this hardware. Stop is not continuous and creates a ligature point.

Page 20: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 20

Anti-Barricade Strategies

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Wood Wicket Door

Custom Wood Wicket DoorMultiple Manufacturers

Cautions:w Manufacturing and Installation toler-

ances may result in a wedgeable gap between door leaf and wicket leaf.

w The primary door leaf’s integrity is inherently compromised with the introduction of a wicket door, making it susceptible to breakage.

Anti-Barricade Hardware | General NotesWicket door swings out allowing access from corridor. Primary door requires continuous hinges with hospital tips.

Anti-Barricade Hardware | Code NotesDoor is not fire rated unless specifically tested and approved by the authority having jurisdiction.

Door, Hallway Side Lock & Handle Concealed Hinge

Page 21: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 21

Anti-Barricade Strategies

Anti-Barricade Hardware | General NotesPrimary door requires continuous hinges with hospital tips. Edge bevel may need to be increased. Edge strip shall be securely fastened.Anti-Barricade Hardware | Constructibility NotesCustom screw length is required to reach solid material on door edge.Anti-Barricade Hardware | Code NotesManufacturermustverifythefireratingofthedoor.

Ceco Doorwww.cecodoor.com

Medallion BH-PRA, Behavioral Healthcare Patient Room Access Door

Currieswww.curries.com

47 Series BH-PRA, Behavioral Healthcare Patient Room Access Door

Fleming Door Productswww.flemingdoor.com

Wicket DoorHollow metal construction.

Page 22: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 22

Anti-Barricade Strategies

Construction Specialtieswww.c-sgroup.com

Wicket DoorAcrovyn Barrier Resistant DoorBonded SCL core 5-ply construction.

Note: OMH does not promote the use of plastic clad laminate doors.

Anti-Barricade Hardware | General NotesPrimary door requires continuous hinges with hospital tips. Edge bevel may need to be increased. Edge strip shall be securely fastened.Anti-Barricade Hardware | Constructibility NotesCustom screw length is required to reach solid material on door edge.Anti-Barricade Hardware | Code NotesManufacturermustverifythefireratingofthedoor.

Page 23: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 23

Anti-Barricade Strategies

Secondary Door in Sidelite Frame

Inswinging Main Door andOutswinging SideLite Door with Center Mullion

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Double Leaf Door withInactive Leaf

Inswinging Active Main Door and Outswinging Inactive DoorProvidekeyedflushboltsactivatedfromcorridor side on top and bottom of the inactive leaf.

Caution: Door configuration may require special installation requirements when utilizing Door Top Sensor protection.

AssemblyThis assembly uses a hollow metal frame sidelite with an out-swinging panel for an-ti-barricade.Thenormal-usedoorisfittedwith anti-ligature door hardware and has a full hollow metal stop. The sidelite panel can be made of wood or hollow metal and beoutfittedwithakeyeddeadboltonthecorridor side.

Page 24: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 24

Anti-Barricade StrategiesBathrooms

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Iveshttp://us.allegion.com

Ives RL32 Roller Latch withASA Strike

Caution: Provide strike plate without lip.

Rockwood Manufacturing Companywww.rockwoodmfg.com

592 Roller Latch with 161 Strike

Caution: Provide strike plate without lip.

Anti-Barricade Hardware | General NotesIdeally,provideexternalkeyedlockingandligatureresistantprivacylatchingwithexternalanti-barricadeoverride(typicallyfoundininstitutionalprivacylatchsets)foremergencyaccess.Therearefewauxiliarylatchesorlatchsetsthatcanprovideallfour levels of functionality.

While we recommend use of the roller latch for en suite bathroom doors, there may be occasions where a lever latch set could be used, with the following cautions:w A“Dormitory”functionispreferredbecauseitprovidessimultaneousretractionofthelatchboltandprivacylockbolt.It’s

not currently available with ligature resistant trim except from Accurate Lock and Hardware.w An“Institutional”function(availablewithligatureresistanttrim)providesprivacy,butdoesnotprovidetheabilitytolockthe

user out of the room except from Accurate Lock and Hardware.w A“Classroom”function(availablewithligatureresistanttrim)providestheabilitytolocktheuseroutoftheroom,butdoes

not provide privacy. Anti-Barricade Hardware | Code NotesDo not use the roller latch on corridor doors; to be used only for en suite bathroom doors.

Page 25: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 25

Anti-Barricade StrategiesBathrooms

Kingsway Groupwww.kingswaygroupglobal.com

KGDS05 Override Washroom Door Set with Classic Grip HandleAnti-Barricade Indicator Lockset with Internal Thumb Turn Pull & External Anti-Ligature Pull Handle with Safe Sure Mechanism

Note: Roller latch is loopable.

Page 26: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 26

Anti-Barricade StrategiesBathrooms

Norva Plastics, Inc.www.norvaplastics.com

Toilet Partitions, Sentinel Event Reduction (SER) Door with Sloped TopUse only in suite or gang bathrooms. Never use in bathrooms shared between two bedrooms. Expanded PVC door can be painted with Lexan paint to match desired color scheme. To be used with roller latch hardware.

Cautions:w Equip with flexible fire rated material.w Maintain large 3” gaps to prevent

wedging.w Velcro may be used as a latching

mechanism but should be limited to a small piece so as to not provide a a tie-off ligature point.

w Can’t be latched (privacy caution).

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Norva Plastics, Inc.www.norvaplastics.com

Toilet Partitions, Sentinel Event Reduction (SER) Door with Collapsible Top

Note: Privacy can’t be achieved with this option. OMH has rejected this product as it contains features that may allow injury to patients including pinched fingers, and if the collapsible edge malfunctions, it provides a ligature point. Also, since the top portion of the door is hollow, the design allows for the possibility of contraband to be placed in the top of the door.

Page 27: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 27

Seclusion Room Standards

General NotesAvoid protrusions and outside corners in Seclusion Rooms. Use polycarbon-ate mirrors for visibility in the corners of room adjacent to the door. The Gold Medal Padding System is recommend-ed on vertical and horizontal surfaces including the door, door frame, window jambs and stool; however, the use of padding is not mandatory. Provide hardware with immediate positive latching(SlamLockFunction).ProvideCremone bolts, multi-bolt or multiple face mounted magnetic locks on exterior ofSeclusionRoom(frameandangleatedgeofdoor)withuninterruptablepowersupply.

Installation NotesThe shear lock alignment is critical for proper function. Shear locks have a ten-dency to become misaligned over time.

Code NotesProvideaonehourfireratingatSeclu-sion Suites. Refer to FGI Guidelines for otherspecificrequirements.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Securitechwww.securitech.com

Multi-Point Deadbolt Mortise Lock

Select lock function from options below:USL-K3-IHB2:(slam)Latches upon closure.Key only projects/retracts bolts and latch.Exterior side of door has freely rotating lever/pull.Interior cylinder optional.UML-K3-IHB2:Does not latch upon closure.Key only projects/retracts bolts.Exterior side of door has freely rotating lever/pull.Interior cylinder optional.

Marathon EngineeringCorporationwww.goldmedalsafetypadding.com

Gold Medal Safety PaddingResinous coating is scuff-resistant and long lasting. Padding material is uniform and smooth with no cracks or open seams.

DuraVision Mirror Systemswww.correctionsmirror.com

Polycarbonate MirrorQuarter dome polycarbonate mirror. Ligature resistant connections and tamper resistant fasteners.

Cautionsw Do not provide electrical switches or receptacles.w Use hinges, sprinklerheads, louvers, grilles, and light fixtures recommended elsewhere in this document.w Windows should either be flush with the inside face of the wall or provided with supplemental polycarbonate shielding or detention screens flush with the

inside face of the room.

Page 28: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 28

Patient Safety Standards Materials & Systems

Page 29: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 29

Division 01 | General Requirements

Page 30: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 30

Division 01 | General RequirementsTamper Resistant Fasteners

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Torx Fastenerwww.acument.com

Tamper Resistant Fasteners

ISO Standard 10664 fasteners.

Bryce Fastenerwww.brycefastener.com

Tamper Resistant Fasteners

Custom fasteners.

General NotesTamper resistant fasteners are to be used for all fasteners exposed to view on every product and assembly acces-sible in the inpatient environment, and should be noted explicitly in the con-struction documents.

Performance CriteriaAll fasteners accessible to patients shall be tamper resistant of the hexalobular (6-lobed),pinreject,internaldrivesys-tem, meeting ISO Standard 10664.

AlternatesMinimum standard for facilities other than NYS operated: 2-pin spanner head fasteners.

Additional NotesMcGard and Bryce are just two among many acceptable manufacturers of tamper resistant fasteners relying on limited distribution tools or custom keyed fasteners. Generally custom tooled fasteners like McGard will cost more than stock fasteners.

Page 31: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 31

Division 07 | Thermal & Moisture Protection

Page 32: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 32

Division 07 | Thermal & Moisture ProtectionSecurity Sealants, Tamper Resistant

General NotesPicking and Pica behaviors can impact sealant choices. Consider security grade sealants at inpatient areas. Tam-per resistant sealants are suitable for supervised locations. Tamper resistant sealantsaregenerallyflexible,abrasionresistant and highly tenacious. They’re usually based on urethane or silicone sealant technology, in both one and two-component formulas.

Performance CriteriaASTM C290.

Installation NotesAll sealants must be installed per manu-facturer’s recommendations for ventila-tion, safety and cure times.

Additional NotesSome sealants may not be suitable for use where contact with food may occur. Some sealants may have VOC or other chemical content that generates odors and fumes during curing. All sealants must be reviewed for potential impact on occupants prior to use.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Sika Corporationwww.usa.sika.com

Sikaflex 11FC One-component, gun grade, moisture cure, polyurethane based elastomeric sealant.

Sikaflex 2 C NS TG Two-component, premium grade, polyure-thane based elastomeric sealant.

Pecora Corporationwww.pecora.com

DynaFlex Two-component, non-sag, elastomeric poly-urethane joint sealant.

DynaFlex SCOne-component, non-sag elastomeric poly-urethane joint sealant.

Master Builders Solutionswww.master-builders-solutions.basf.us

MasterSeal CR 195One-component, moisture-curing, aliphatic, non-sag, polyurethane sealant.

Dow Corningwww.dowcorning.com

995 Silicone Structural SealantOne-component, silicone sealant.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 33: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 33

Division 08 | Openings

Page 34: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 34

Division 08 | OpeningsDoor Hardware, Door Top Sensors

Door Control Services, Inc.www.doorcontrolservices.com

Top Door AlarmTop Door Alarm is a custom-manufactured alert system that can be installed on new or existing applications. A photoelectric sensor detects ligature ahead of pressure applica-tion. This product produces a visible light beam that may be disturbing to patients. It should be noted that beam is continuously visible to patients, especially when bedroom is dark.

Caution: Use with caution in a double leaf door configuration with an inactive leaf.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

General NotesAn electric transfer hinge is required. Refer to the continuous hinges in this document. Alarm annunciation may be visual and/or audio, located at the door and/or nurse’s station. Installing alarm resets at the alarmed doors will require staff response to the alarm location.

Installation NotesFor the Top Door Alarm photoelectric sensors are positioned on the door frame and on the door within anti-ligature casings. This ensures maximum coverage by detecting the presence of any foreign objects interrupting the thru-beams between the transmitters and receivers.

Additional NotesTwoconfigurationsofthephotoelectricsensor type of system are offered;ConfigurationA:TwosetsofAlarmLightSensors for top door detection. ConfigurationB:OnesetofAlarmLightSensors for bottom door detection.

The Door Switchwww.thedoorswitch.com

The Door SwitchTop of door, weight pressure activated sen-sor that extends above the door.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 35: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 35

Division 08 | OpeningsDoor Hardware, Door Top Sensors

Stanley Security Solutions| Grainger Industrial Supplywww.stanleysecuritysolutions.comwww.grainger.com

SEDA (Stanley Emergency Door Alarms) | LISA (Ligature-Resistant Door Alarm)A pressure activated switch, mounted on the faceofadoor,providesnotificationwhena foreign object passes over the door and adownwardpressureisapplied.Notifica-tion is sent to a console indicating where a response is required.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 36: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 36

Division 08 | OpeningsDoor Hardware, Door Top Sensors, Alarm Visual Notifiers

Cooper Industrieswww.cooperindustries.com

Cooper Eaton Series RSSBMulti-color candela, ceiling mount installa-tiononly.Notifiersshallbeceilingmounted.

Gentex Corporationwww.gentex.com

Gentex GCSB24PCW StrobeMulti-color candela, wall or ceiling mount installation. A mechanical attachment or setscrewisrequiredforthecover.Notifiersshall be ceiling mounted.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 37: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 37

Division 08 | OpeningsDoor Hardware, Continuous Hinges

General NotesContinuous hinges are recommended for all inswinging and outswinging doors within inpatient units.

Performance CriteriaSpecifyHospitalTips(HT)toeliminateligature point at top of hinge.

Installation NotesPrepare and reinforce door frame in strict compliance with hardware manu-facturer’s written instructions and instal-lation templates.

Additional NotesArchitectural steel and stainless steel barrel type continuous hinges distribute door weight and stress along the full length of the door and frame.

Caution: All hinges inherently carry risk due to multiple joints between moving parts, and extremely low ac-ceptable tolerances. Consistent quali-ty in manufacturing may be difficult to achieve and should be inspected in the field.

Architectural BuildersHardware Mfg. Inc.www.abhmfg.com

A500-HTStainless steel pin & barrel, full mortise, full concealed edge mount with hospital tip.HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

PBB, Inc.www.pbbinc.com

CH51-HT SS Pin & Barrel SeriesStainless steel pin & barrel, full mortise, edge mount with hospital tip.

Markar ArchitecturalProductswww.markar.com

FM300-HTEdge mount stainless steel.FS301-HT & FS301-HTFullsurfaceflushmountstainlesssteel.Canbe installed in existing doors.

Page 38: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 38

General NotesContinuous hinges are recommended for all inswinging and outswinging doors within inpatient units.

Performance CriteriaSpecifyHospitalTips(HT)toeliminateligature point at top of hinge.

Installation NotesPrepare and reinforce door frame in strict compliance with hardware manu-facturer’s written instructions and instal-lation templates.

Additional NotesArchitectural steel and stainless steel barrel type continuous hinges distribute door weight and stress along the full length of the door and frame.

Caution: All hinges inherently carry risk due to multiple joints between moving parts, and extremely low ac-ceptable tolerances. Consistent quali-ty in manufacturing may be difficult to achieve and should be inspected in the field.

Division 08 | OpeningsDoor Hardware, Continuous Hinges

Stanley Security Solutionswww.stanleydoorhinges.com

LifeSpan 600 Series641-HT-Standard DutySteelfor1/8”insetdoors.651-HT-Standard DutyStainlesssteelfor1/8”insetdoors.

Hospital Tip

Page 39: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 39

Division 08 | OpeningsDoor Hardware, Locks & Handles

General NotesNot all door hardware manufacturer’s provide an institutional privacy function and not all institutional privacy functions are ligature resistant.

Specifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Beveled latchbolts can be compromised, permitting access to rooms and there-fore should never be used on doors to potentially hazardous locations such as electrical rooms and housekeeping closets.

Specify a 2-piece stainless steel mechanical anti-friction latchbolt for staff-only rooms and other areas identi-fiedaslowormediumrisk.

Additional NotesSee the Anti-Barricade Strategies pages for additional information relative to hardware functions on locksets and deadlatches.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Accurate Lock & Hardwarewww.accuratelockandhardware.com

Crescent Handle (CH) & 9100 Mor-tise Lockset

Accurate Lock & Hardwarewww.accuratelockandhardware.com

Crescent Handle (CH-CYL) & Cylindrical Lockset

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Accurate Lock & Hardwarewww.accuratelockandhardware.com

9100ALP Push Plate with Mortise Lockset

Page 40: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 40

Division 08 | OpeningsDoor Hardware, Locks & Handles

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

TownSteel Architectural Hardware Manufacturingwww.townsteel.com

MRX-A Mortise Lock with Ligature Resistant Trim-ArchHorizontal and vertical. Specify with anti-lig-ature thumb turn.

Sargentwww.sargentlock.com

BHW Trim (Mortise)The BHW style door trim is not a traditional lever design and can be safely used in a high risk environment.

Caution: Installation tolerances must be tight to ensure proper operation. Adjust-ments shall be made in the field.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

General NotesNot all door hardware manufacturer’s provide an institutional privacy function and not all institutional privacy functions are ligature resistant.

Specifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Beveled latchbolts can be compromised, permitting access to rooms and there-fore should never be used on doors to potentially hazardous locations such as electrical rooms and housekeeping closets.

Specify a 2-piece stainless steel mechanical anti-friction latchbolt for staff-only rooms and other areas identi-fiedaslowormediumrisk.

Additional NotesSee the Anti-Barricade Strategies pages for additional information relative to hardware functions on locksets and deadlatches. HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

TownSteel Architectural Hardware Manufacturingwww.townsteel.com

CRX-A Cylindrical Lock with Liga-ture Resistant Trim-ArchHorizontal and vertical. Specify with anti-lig-ature thumb turn.

Page 41: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 41

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Corbin Russwin www.corbinrusswin.com

Anti-Harm Knob HSS (Mortise)

Caution: Cone shaped door knobs and thumb turns do not comply with ADA requirements for graspability.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Marks USAhttp://marksusa.com

Institutional Life Safety Mortise 5SS50 Series Lockset

Caution: Cone shaped door knobs and thumb turns do not comply with ADA requirements for graspability.

Division 08 | OpeningsDoor Hardware, Locks & Handles

Accurate Lock & Hardwarewww.accuratelockandhardware.com

Cylindrical Deep Detent Safety Knob (CDDSK)

Caution: Cone shaped door knobs and thumb turns do not comply with ADA requirements for graspability.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Schlagehttp://us.allegion.com

SK1 Ligature Resistant Knob(Cylindrical)

Caution: Cone shaped door knobs and thumb turns do not comply with ADA re-quirements for graspability.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

General NotesNot all door hardware manufacturer’s provide an institutional privacy function and not all institutional privacy functions are ligature resistant.

Specifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Beveled latchbolts can be compromised, permitting access to rooms and there-fore should never be used on doors to potentially hazardous locations such as electrical rooms and housekeeping closets.

Specify a 2-piece stainless steel mechanical anti-friction latchbolt for staff-only rooms and other areas identi-fiedaslowormediumrisk.

Additional NotesSee the Anti-Barricade Strategies pages for additional information relative to hardware functions on locksets and deadlatches.

Page 42: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 42

Division 08 | OpeningsDoor Hardware, Locks & Handles

General NotesNot all door hardware manufacturer’s provide an institutional privacy function and not all institutional privacy functions are ligature resistant.

Specifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Beveled latchbolts can be compromised, permitting access to rooms and there-fore should never be used on doors to potentially hazardous locations such as electrical rooms and housekeeping closets.

Specify a 2-piece stainless steel mechanical anti-friction latchbolt for staff-only rooms and other areas identi-fiedaslowormediumrisk.

Additional NotesSee the Anti-Barricade Strategies pages for additional information relative to hardware functions on locksets and deadlatches.

TownSteel Architectural Hardware Manufacturingwww.townsteel.com

CRX-K Ligature Resistant Trim Knob (Cylindrical)

Caution: Cone shaped door knobs and thumb turns do not comply with ADA requirements for graspability.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 43: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 43

Division 08 | OpeningsDoor Hardware, Locks & Handles

General NotesNot all door hardware manufacturer’s provide an institutional privacy function and not all institutional privacy functions are ligature resistant.

Specifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Beveled latchbolts can be compromised, permitting access to rooms and there-fore should never be used on doors to potentially hazardous locations such as electrical rooms and housekeeping closets.

Specify a 2-piece stainless steel mechanical anti-friction latchbolt for staff-only rooms and other areas identi-fiedaslowormediumrisk.

Additional NotesSee the Anti-Barricade Strategies pages for additional information relative to hardware functions on locksets and deadlatches.

Corbin Russwin | Sargentwww.corbinrusswin.comwww.sargentlock.com

HPSK Push/Pull Paddle | 8200 Mortise Lock with Push/Pull ALPSimilar to Corbin Russwin HP3000 & Sar-gent HP Series Bored Lock, both cylinder locks.

Note: A wedge point can be created in the gap required for operational clearance of the paddle. This wedge point can occur when paddles are mounted in either the up, down or side positions.

Sargentwww.sargentlock.com

Anti-Harm Knob BHD (Mortise)

Note: A ligature point can be established between the knob and escutcheon plate.

Corbin Russwin www.corbinrusswin.com

BHSS Trim (Mortise)The BHSS style door trim is not a traditional lever design.

Page 44: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 44

Caution: Lever style door trim is not appropriate for high risk areas. It is nearly impossible to completely avoid ligature opportunities with lever style door trim, even if designed to be ligature resistant. At best, lever style door trim is only appropriate for medium and low risk areas.

Division 08 | OpeningsDoor Hardware, Lever Handles

Page 45: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 45

Division 08 | OpeningsDoor Hardware, Lever Handles

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Corbin Russwin | Sargentwww.corbinrusswin.comwww.sargentlock.com

BLSS Trim | BHL Trim (Mortise)Whether Locked or Unlocked, this lever set “Free-Wheels”upanddownonboththekeyed and non-keyed sides of the door. This“Free-Wheeling”actionisstandardondouble cylinder functions.

Caution: Earbuds can be easily looped around lever handle and remain in place due to friction.

Best Access Systems|Grainger Industrial Supplywww.bestaccess.comwww.grainger.com

Ligature Resistant Lever Set SPSL Series| LISL/LISE (Mortise)Theligatureresistantleverhandle“free-wheels”inbothdirectionsonbothsidesof the door whether the door is locked or unlocked.Proprietaryfinishresistsloopingby earbuds.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

General NotesNot all door hardware manufacturer’s provide an institutional privacy function and not all institutional privacy functions are ligature resistant.

Specifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Beveled latchbolts can be compromised, permitting access to rooms and there-fore should never be used on doors to potentially hazardous locations such as electrical rooms and housekeeping closets.

Specify a 2-piece stainless steel mechanical anti-friction latchbolt for staff-only rooms and other areas identi-fiedaslowormediumrisk.

Additional NotesSee the Anti-Barricade Strategies pages for additional information relative to hardware functions on locksets and deadlatches. HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Schlagehttp://us.allegion.com

Anti-Ligature Lever SL1 Series & L9000 Mortise LocksWhether Locked or Unlocked, this lever set “Free-Wheels”upanddownonboththekeyed and non-keyed sides of the door. This “Free-Wheeling”actionisstandardondou-ble cylinder functions.

Caution: Earbuds can be easily looped around lever handle and remain in place due to friction.

TownSteel Architectural Hardware Manufacturingwww.townsteel.com

Ligature Resistant Lever Set TRXL Series (Cylindrical)Whether Locked or Unlocked, this lever set “Free-Wheels”upanddownonboththekeyed and non-keyed sides of the door. This “Free-Wheeling”actionisstandardondou-ble cylinder functions.

Caution: Earbuds can be easily looped around lever handle and remain in place due to friction.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 46: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 46

Division 08 | OpeningsDoor Hardware, Lever Handles

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Marks USAhttp://marksusa.com

Institutional Life Safety Mortise5SS19 Series Lockset

Caution: Earbuds can be easily looped around lever handle and remain in place due to friction.

Marks USAhttp://marksusa.com

Institutional Life Safety Cylindrical Lockset, Series 195SS

Caution: Earbuds can be easily looped around lever handle and remain in place due to friction.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

General NotesNot all door hardware manufacturer’s provide an institutional privacy function and not all institutional privacy functions are ligature resistant.

Specifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Beveled latchbolts can be compromised, permitting access to rooms and there-fore should never be used on doors to potentially hazardous locations such as electrical rooms and housekeeping closets.

Specify a 2-piece stainless steel mechanical anti-friction latchbolt for staff-only rooms and other areas identi-fiedaslowormediumrisk.

Additional NotesSee the Anti-Barricade Strategies pages for additional information relative to hardware functions on locksets and deadlatches.

Page 47: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 47

Division 08 | OpeningsDoor Hardware, Lever Handles

General NotesNot all door hardware manufacturer’s provide an institutional privacy function and not all institutional privacy functions are ligature resistant.

Specifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Beveled latchbolts can be compromised, permitting access to rooms and there-fore should never be used on doors to potentially hazardous locations such as electrical rooms and housekeeping closets.

Specify a 2-piece stainless steel mechanical anti-friction latchbolt for staff-only rooms and other areas identi-fiedaslowormediumrisk.

Additional NotesSee the Anti-Barricade Strategies pages for additional information relative to hardware functions on locksets and deadlatches.

TownSteel Architectural Hardware Manufacturingwww.townsteel.com

Ligature Resistant Lever Set MRXL Series (Mortise)

Whether Locked or Unlocked, this lever set “Free-Wheels”upanddownonboththekeyed and non-keyed sides of the door. This “Free-Wheeling”actionisstandardondou-ble cylinder functions.

Note: A variety of ligatures can be looped on lever resulting in downward ligatures.

Page 48: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 48

Division 08 | OpeningsDoor Hardware, Privacy Thumbturns

General NotesInstitutional Privacy Locksets utilize privacy thumbturns. There are 5 key criteria for a successful assembly. Listed below each product are notes identify-ing whether each criterion is met. The criteria are as follows:

wLigature resistancewRelease of lock upon door closurewOutside key override of thumbturnwOutside locking of door by keywADA compliance

Performance CriteriaSpecifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Additional NotesSee the Anti-Barricade Strategies pages for additional information relative to hardware functions on locksets and deadlatches.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Accurate Lock & Hardwarewww.accuratelockandhardware.com

ALT-ADA Thumb Turn

wLigature resistantwLock releases upon closing doorwOutside key overrides thumbturnwOutside key locks doorwADA compliant

Schlagehttp://us.allegion.com

Anti-Ligature Thumb Turn SL1

wLigature resistantwLock does not release upon closing doorwOutside key overrides thumbturnwOutside key locks doorwADA compliant

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Caution: Due to manufacturing tolerances, some samples allow for looping behind thumbturn.

Corbin Russwin | Sargentwww.corbinrusswin.comwww.sargentlock.com

Behavioral Health Thumbturn for use with Corbin Russwin & Sar-gent Ligature Resistant Trims

wLigature resistantwLock releases upon use of inner leverwOutside key does not override thumbturnwOutside key locks doorwADA compliant

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 49: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 49

Division 08 | OpeningsDoor Hardware, Privacy Thumbturns

General NotesInstitutional Privacy Locksets utilize privacy thumbturns. There are 5 key criteria for a successful assembly. Listed below each product are notes identify-ing whether each criterion is met. The criteria are as follows:

wLigature resistancewRelease of lock upon door closurewOutside key override of thumbturnwOutside locking of door by keywADA compliance

Performance CriteriaSpecifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Additional NotesSee the Anti-Barricade Strategies pages for additional information relative to hardware functions on locksets and deadlatches.

Marks USAhttp://marksusa.com

Life Safety Thumb Turn GL

wLigature resistance - UNKNOWNwUNKNOWN if lock releases upon closing doorwUNKNOWN if outside key overrides thumb-turnwUNKNOWN if outside key locks doorwNOT ADA compliant

Page 50: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 50

Division 08 | OpeningsDoor Hardware, Privacy Thumbturns

General NotesInstitutional Privacy Locksets utilize privacy thumbturns. There are 5 key criteria for a successful assembly. Listed below each product are notes identify-ing whether each criterion is met. The criteria are as follows:

wLigature resistancewRelease of lock upon door closurewOutside key override of thumbturnwOutside locking of door by keywADA compliance

Performance CriteriaSpecifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Additional NotesSee the Anti-Barricade Strategies pages for additional information relative to hardware functions on locksets and deadlatches.

Corbin Russwin | Sargentwww.corbinrusswin.comwww.sargentlock.com

BLSS | 130KBH ThumbturnFor Use with BLSS | BHL Trim

Note: A shoelace can be easily slid behind the thumbturn to present ligature opportunity.

TownSteel Architectural Hardware Manufacturingwww.townsteel.com

Anti Ligature Thumb Turn

Note: A shoelace can be easily slid behind the thumbturn to present ligature opportunity.

Stanley/Best Access Systemswww.bestaccess.com

Female Patient Privacy Thumb Turn LTF

Note: A shoelace can be easily slid behind the thumbturn to present ligature opportunity.

Page 51: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 51

Division 08 | OpeningsDoor Hardware, Pulls

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Performance CriteriaSpecifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Kingsway Groupwww.kingswaygroupglobal.com

KG30 Easy Grip Pull Handle on Back Plate

Kingsway Groupwww.kingswaygroupglobal.com

KG40 Ergogrip Pull Handle on Back Plate

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kingsway Groupwww.kingswaygroupglobal.com

KG61 Classic Grip Pull Handle

Page 52: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 52

Division 08 | OpeningsDoor Hardware, Pulls

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Performance CriteriaSpecifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Accurate Lock & Hardwarewww.accuratelockandhardware.com

Crescent Pull (CP) Rigid Handle

Accurate Lock & Hardwarewww.accuratelockandhardware.com

Accurate Recessed ADA Pull (U700IAL)

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 53: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 53

Division 08 | OpeningsDoor Hardware, Pulls

Performance CriteriaSpecifytamperresistant,flushmountedset screws. A recessed set screw shaft provides a ligature opportunity for the stiff end of a shoelace.

Kingsway Groupwww.kingswaygroupglobal.com

KG70 Face Fixed Recessed Pull Handle

Note: Pull handle can be wedged with a knot to create a downward ligature opportunity.

Rockwood ManufacturingCompanywww.rockwoodmfg.com

D89 - Heavy Duty Security Flush Pull

Note: Depth and profile of recess does not provide adequate functionality.

Page 54: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 54

Division 08 | OpeningsDoor Hardware, Stops

General NotesWall mounted door stops should be se-lected based upon door knob/lever type and should be mechanically fastened to resist twist off. Stops should be installed with solid wood blocking behind and with a construction adhesive applied to the backside of the base plate prior to mechanical attachment with tamper resistant fasteners. Sealant should be applied around the perimeter of the stop.

Caution: Traditional style door stops do not have concealed fasteners with a clamping ring to secure the stop. These can be removed by hand and ingested.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kingsway Groupwww.kingswaygroupglobal.com

KG182 Wall Mounted Door StopSolid stainless steel surround with high pres-sure rubber dome. Security screws pass through the rubber part to ensure it can’t be removed.

Kingsway Groupwww.kingswaygroupglobal.com

KG183 Large Rubber Wall Mount-ed Door StopSolid high pressure domed rubber door stop.

Page 55: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 55

Division 08 | OpeningsDoor Hardware, Closers

General Notes

Mount closers on public side of doors to rooms with patient access, or on the secure side of doors that need to au-tomatically lock or latch, such as Store Rooms, Soiled Utility Rooms, and doors with card access readers.

Consider use of concealed closers where risk assessment indicates that surface mounted closers are not accept-able.

Performance CriteriaSpecifygaptoleranceattoptobe1/8”maximum. Doors with concealed clos-ers that are intended to receive door top sensors must use a face mounted sen-sortoavoidconflictwiththecloserarm.

Additional NotesRequired use of closers is greatly re-duced by NFPA 101: Life Safety Code for sprinklered buildings.

Caution: All closers inherently carry risk. Do not use closers unless required by code.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Rixsonwww.rixson.com

51 Series Offset Floor CloserFully concealed, single acting, handed.For use with top pivot hinge.

Note: Fully concealed closers have no readily visible or accessible components.

Note: Floor closers require special preparation.

Rixsonwww.rixson.com

700 Series Overhead Concealed CloserDouble-acting, non-handed closer concealed in door frame head.For use with bottom pivot hinge.

Note: Fully concealed closers have no readily visible or accessible components.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 56: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 56

Division 08 | OpeningsDoor Hardware, Closers

General Notes

Mount closers on public side of doors to rooms with patient access, or on the secure side of doors that need to au-tomatically lock or latch, such as Store Rooms, Soiled Utility Rooms, and doors with card access readers.

Consider use of concealed closers where risk assessment indicates that surface mounted closers are not accept-able.

Performance CriteriaSpecifygaptoleranceattoptobe1/8”maximum. Doors with concealed clos-ers that are intended to receive door top sensors must use a face mounted sen-sortoavoidconflictwiththecloserarm.

Additional NotesRequired use of closers is greatly re-duced by NFPA 101: Life Safety Code for sprinklered buildings.

Caution: All closers inherently carry risk. Do not use closers unless required by code.

Sargentwww.sargentlock.com

268/269 Series Overhead Concealed CloserFully concealed closer body in frame head. Fully concealed track in door. Track arm is only visible when door is open.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

LCNhttp://us.allegion.com

4510T SMOOTHEE Series CloserHeavy duty track closer.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 57: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 57

Division 08 | OpeningsDoor Hardware, Gasketing

General NotesNYS-OMH discourages the use of perfo-rated anti-ligature gasketing because it can easily be torn off, creating an ongo-ing maintenance concern and reducing the life safety compliance of the physical buildings.

Pemkowww.pemko.com

290AV Perimeter Gasketing Aluminum with Vinyl InsertFastenerstobeinstalled1”fromendsandat6”oncenter,maximum.HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Pemkowww.pemko.com

303AV Perimeter Gasketing Aluminum with Vinyl InsertFastenerstobeinstalled1”fromendsandat6”oncenter,maximum.HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Pemkowww.pemko.com

303APK Perimeter GasketingAluminum with Thermal Plastic Elastomer InsertFastenerstobeinstalled1”fromendsandat6”oncenter,maximum.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Pemkowww.pemko.com

316AV Perimeter Gasketing Aluminum with Vinyl InsertFastenerstobeinstalled1”fromendsandat6”oncenter,maximum.HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 58: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 58

Division 08 | OpeningsDoor Hardware, Gasketing

General NotesNYS-OMH discourages the use of perfo-rated anti-ligature gasketing because it can easily be torn off, creating an ongo-ing maintenance concern and reducing the life safety compliance of the physical buildings.

Pemkowww.pemko.com

2891AV Perimeter Gasketing Aluminum with Vinyl InsertFastenerstobeinstalled1”fromendsandat6”oncenter,maximum.HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 59: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 59

Division 08 | OpeningsGlazing, General

General Notes

The following are risks and performance criteria to consider when specifying glazing in both supervised and unsupervised areas that are accessible to patients. All windows and glazing in areas accessible to patients should be evaluated as part of the facility risk assessment. Windows and glazing in areas that are not routinely accessibletopatients,butmaybecomeaccessibletopatients(e.g.astaffofficethatisleftunlocked,orastaffofficethatislaterconvertedtoaConsultRoomorBedroom)should also be considered as part of the facility risk assessment. Windows and glazing that are considered a risk to patients for the behaviors listed below should be constructed in accordance with this standard. The design of the entire window and glazing system must be considered.

Polycarbonateglazingprovidesthebestprotectionforthepatientagainsttheriskslistedbelow.Laminatedsafetyglazing,otherthanthelaminatespecificallyidentifiedinthis standard, should be used with caution. Glazing products other than polycarbonate or laminated safety glazing should never be used in patient areas. The NYS-OMH does not permit the use of wire glass in its facilities.

Escape

Exterior windows, interior windows, and glazing are a primary target for patients trying to escape. Windows and glazing in both supervised and unsupervised areas provide potential opportunities for patients to escape. It is critical to consider the design of the entire window, together with the installation in wall openings, when designing to prevent elopement.

Jumping

Patients will jump in order to hurt themselves, or push others through window openings in order to hurt others. Jumping is a concern for spaces accessible to patients above grade level.

Ingesting

Patientswilleatthingsforavarietyofreasons,includingawishtocausethemselvespersonalharm.Polycarbonateorlaminatedglazingprotectedwithasurfacefilmshould always be used in patient accessible areas. Even small fragments that can come from tempered or laminated glazing can cause severe internal injuries or death. When considering using laminated glazing, care must be taken to select glazing that meets the following criteria:

w Thelaminatedglazingshouldwhollyresistthebreakage(penetration)oftheglazingpanel. w The laminated glazing should wholly retain broken glass in a manner that prevents dislodging from the interlayer.

Laceration

Patients will cut themselves. Glass presents an obvious opportunity for such behavior. When considering using laminated glazing, care must be taken to select glazing that meets the following criteria:

w Thelaminatedglazingshouldwhollyresistthebreakage(penetration)oftheglazingpanel. w The laminated glazing should wholly retain broken glass in a manner that prevents dislodging from the interlayer. w The laminated glazing should prevent access to the sharp edges of broken glass, even if they are retained on the interlayer.

(continuedonthenextpage)

Page 60: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 60

Division 08 | OpeningsGlazing, General

Weaponizing

Patients will use objects in their environment to harm others. Glass presents an obvious opportunity for such behavior. When considering using laminated glazing, care must be taken to select glazing that meets the following criteria:

w Thelaminatedglazingshouldwhollyresistthebreakage(penetration)oftheglazingpanel. w The laminated glazing should wholly retain broken glass in a manner that prevents dislodging from the interlayer. w The laminated glazing should prevent access to the sharp edges of broken glass, even if they are retained on the interlayer.

Theglassindustry’sstandardtestforpenetrationandimpactresistanceforlaminatedglassisconductedonaverysmallunit(approximately24”square),andisdesignedtoapproximatepotentialforincidentalharmfromaccidentalimpact.Similarperformancetothetestsampleshouldnotbeexpectedona4’-0”x6’-0”window.NewYorkState requires the use of the AAMA A501.8 Standard Test Method for Determination of Resistance to Human Impact of Window Systems Intended for Use in Psychiatric Applications.

Note:Iftheintentionistospecifylaminatedglazinginawindowunit,confirmthattheselectedwindow(s)havepassedtheaforementionedimpacttestingwiththespecifiedlaminatedglazing.

Page 61: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 61

Division 08 | OpeningsGlazing, Exterior Windows, Polycarbonate Glazing

General NotesGlazing products other than polycarbon-ate or laminated safety glazing should never be used in patient areas.

In all patient areas where the applicable codes and regulatory authority per-mit the use of polycarbonate glazing, polycarbonate glazing provides the best protection for the patient against the pre-viously listed risks.

Sabic Innovative Plasticswww.sabic-ip.com

FOR USE AS INNERMOST SUR-FACE OF EXTERIOR WINDOWS

Lexan SL-4855 Polycarbonate Glazing1/2”thickwithMarguardII-UVcoating.Specify MR15 with 15 year warranty.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Sheffield Plastics Inc.www.sheffieldplastics.com

FOR USE AS INNERMOST SURFACE OF EXTERIOR WINDOWS

Makrolon 15 PolycarbonateGlazing1/2”thick.UsewithNYS-OMH15yearwarranty.

Page 62: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 62

Division 08 | OpeningsGlazing, Exterior Windows, Laminated Safety Glazing

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Oldcastle Building Envelopewww.oldcastlebe.com

FOR USE AS OUTERMOST SUR-FACE OF EXTERIOR WINDOWS

Laminated Security Glazing3/8”thick.Intendedforuseatgrade,courtyards or porches with supervised patient access as an exterior lite in an insulatedglazingunitwhereeither1/2”polycarbonateor3/8”ArmorProtectPlus161000 already provides primary patient safety from inside the building.

No. 1 Surface: 3/16”heat-strengthenedglassNo. 2 Surface: 0.060”PVBinterlayerNo. 3 Surface: 3/16”heat-strengthenedglass

Caution: Do not use in any area where patients may be left unsupervised.

Oldcastle Building Envelopewww.oldcastlebe.com

FOR USE AS INNERMOST SURFACE OF EXTERIOR WINDOWS

ArmorProtect Plus 161000Laminated Security Glazing3/8”thick.3Mfilmisscratchableandmaybe removed from the laminated glass panelandnewfilminstalledbytrainedmaintenance staff. Curing time for the filminstallationistwoweeksminimum.Maintenance staff should be advised to keep spare stock that is fully cured to eliminate downtime.Installinframeswitha1”continuousedgebiteifdryglazedor1/2”continuous edge bite if silicone glazed.

No. 1 Surface: 5/32”heat-strengthenedglassNo. 2 Surface: 0.090”DupontSentryGlasPlus interlayerNo. 3 Surface: 5/32”heat-strengthenedglassNo. 4 Surface: 3MUltraS600anti-spallfilminstalled to edge of glass

Caution: Wet-glazing compounds and cleaning agents have been known to compromise the integrity of the interlayer, and care should be taken with their use. Care should be taken to properly identify the tin side of the glass and to handle it according to manufacturers’ instructions.

General NotesGlazing products other than polycarbon-ate or laminated safety glazing should never be used in patient areas.

Laminated safety glazing, other than the laminatespecificallyidentified,shouldbe used with caution. HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 63: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 63

Division 08 | OpeningsGlazing, Interior Windows, Non-Rated

Oldcastle Building Envelopewww.oldcastlebe.com

ArmorProtect Plus 161000Laminated Security Glazing3/8”thick.3Mfilmisscratchableandmaybe removed from the laminated glass panelandnewfilminstalledbytrainedmaintenance staff. Curing time for the filminstallationistwoweeksminimum.Maintenance staff should be advised to keep spare stock that is fully cured to eliminate down time. Install in hollow metal frames witha1”continuousedgebiteifdryglazedor1/2”continuousedgebiteifsiliconeglazed.

No. 1 Surface:3MUltraS600anti-spallfilminstalled

to edge of glassNo. 2 Surface:

5/32”heat-strengthenedglassNo. 3 Surface:

0.090”DuPontSentryGlasPlus interlayerNo. 4 Surface:

5/32”heat-strengthenedglassNo. 5 Surface:

3MUltraS600anti-spallfilminstalledto edge of glass

Caution: Wet-glazing compounds and cleaning agents have been known to compromise the integrity of the interlayer, and care should be taken with their use. Care should be taken to properly identify the tin side of the glass and to handle it according to manufacturers’ instructions.

Sabic Innovative Plasticswww.sabic-ip.com

Lexan SL-4855 Polycarbonate Glazing3/8”or1/2”thickwithMarguardII-UVcoating. Specify MR15 with a 15 year warranty. Install in hollow metal frames with a1”continuousedgebite.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Sheffield Plastics Inc.www.sheffieldplastics.com

Makrolon 15 PolycarbonateGlazing1/2”thick.UsewithNYS-OMH15yearwarranty. Install in hollow metal frames with a1”continuousedgebite.

General NotesGlazing products other than polycarbon-ate or laminated safety glazing should never be used in patient areas.

Laminated safety glazing, other than the laminatespecificallyidentified,shouldbe used with caution.

3/8”polycarbonateisrecommendedwhere ingesting, laceration, and weap-onization are the risks to be mitigated.

1/2”polycarbonateisrecommendedwhere escape or jumping are the risks to be mitigated.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 64: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 64

Division 08 | OpeningsGlazing, Interior Windows, Non-Rated

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

DuPontwww.dupont.com

Spallshield CPET FilmHard-coatedPETfilmhelpsstoptheshoweringofsmallglassparticles(called“spall”)thatcanoccurwhenconventionalglass fails.

General NotesFilms are used on interior glazing be-tweenspacesonthesamefloorleveland only when the use of polycarbonate is impractical.

Anti-spallfilmsaredesignedtobeap-plied to conventional glazing to prevent showering of shards in the event of failure. Films may prevent off-sharding, laceration, weaponizing, and ingestion. Anti-spallfilmsmayprovideacost-ef-fective safety improvement for pre-ex-isting conventional glazing materials by increasing the penetration resistance of any thickness of glass.

Each facility shall conduct their own risk assessment to determine the appropri-atenessoffilmapplicationsforuseintheirspecificsituations.

Performance CriteriaExtendfilmtoedgeofglazingbeyondthe face of the glazing bead/stop.

3Mwww.3m.com

Ultra S600 Film3Mfilmisscratchable.Whendamaged,itmay be removed from the glass panel and newfilminstalledbytrainedmaintenancestaff.Curingtimeforthefilminstallationis two weeks minimum. Exact curing time shouldbeverifiedwiththemanufacturer.Maintenance staff should be advised to keep spare stock that is fully cured to eliminate down time.

General Cautions:w Applied films do not provide security.w Films shall not be used in NYS-OMH facilities to

prevent escape or jumping.w Films are not for use at interior glazing one or

more stories above the adjacent floor space. w Films are not for use at any upper story exterior

glazing.w Films are not for use at exterior glazing facing

non-secure open spaces.

Page 65: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 65

Division 08 | OpeningsGlazing, Interior Windows, Non-Rated

General NotesFilms are used on interior glazing be-tweenspacesonthesamefloorleveland only when the use of polycarbonate is impractical.

Anti-spallfilmsaredesignedtobeap-plied to conventional glazing to prevent showering of shards in the event of failure. Films may prevent off-sharding, laceration, weaponizing, and ingestion. Anti-spallfilmsmayprovideacost-ef-fective safety improvement for pre-ex-isting conventional glazing materials by increasing the penetration resistance of any thickness of glass.

Each facility shall conduct their own risk assessment to determine the appropri-atenessoffilmapplicationsforuseintheirspecificsituations.

Performance CriteriaExtendfilmtoedgeofglazingbeyondthe face of the glazing bead/stop.

Madicowww.safetyshield.com

Safetyshield 1500 FilmHighstrengthglazingfilmappliedtotheexposed surface of glass reduces glass breakage and holds broken glass in place until glazing can be replaced.

General Cautions:w Applied films do not provide security.w Films shall not be used in NYS-OMH facilities to

prevent escape or jumping.w Films are not for use at interior glazing one or

more stories above the adjacent floor space. w Films are not for use at any upper story exterior

glazing.w Films are not for use at exterior glazing facing

non-secure open spaces.

Page 66: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 66

Division 08 | OpeningsGlazing, Interior Windows, Fire Rated

General NotesDo not use wire glazing in new applica-tions.

Existing wire glazing should be removed and replaced with safety glazing, or protected with either an aftermarket van-dalresistantprotectivefilmorsurfacemounted3/8”polycarbonateonfaceofglazing accessible to patients.

Code NotesFor 1 Hour Openings:Use3/8”polycarbonateinconjunctionwithsprinklerheadsand5/8”stopswhere the authority having jursidiction will accept NYS-OMH’s Warnock Hersey test(nottestedperASTMF1233).ORProvidefire-ratedglazingcladwith1/4”polycarbonate on each side accessible to patients.

For Greater than 1 Hour Openings:FireLite and FireLite PLUS products can be used.

Technical Glass Productswww.fireglass.com

FireLite PLUS5/16”thicklaminated,polished,firerated,and impact safety rated glazing. Listed for use in doors, sidelites, and transoms with fireratingrequirementsrangingfrom20minutes to 3 hours.

Caution: FireLite PLUS was the safest ceramic glazing tested. However, all the FireLite products produced shards of glass by impact.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

FireLite PLUS FireLite NT Standard FireLite NT Premium

Page 67: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 67

Division 08 | OpeningsGlazing, Interior Windows, Fire Rated

SaftiFirstwww.safti.com

SuperLite Fire Rated Glazing1/4”monolithicsafetyandpositivepressurefireratedglazing.Foruseinwood,hollowmetal,aluminumoranyequallyfireratedframing systems.

Traditionalfireratedglasswithatough,durablefireratedsafetyfilmappliedtomeet the highest impact safety standard, CPSC 16CFR 1201 Cat. II, which requires withstanding 400 ft. lbs. due to accidental impact.

Notes:w These products are rejected because

of breakage and shard production.w These products are not tested per

ASTM F1233 and therefore are not considered Security Glazing.

w Impact safety ratings do not equal security ratings.

w While these products have many ap-plications as Safety Impact Glazing, such as in schools and public build-ings, they are not intended for special populations where security is also required.

General NotesDo not use wire glazing in new applica-tions.

Existing wire glazing should be removed and replaced with safety glazing, or protected with either an aftermarket van-dalresistantprotectivefilmorsurfacemounted3/8”polycarbonateonfaceofglazing accessible to patients.

Code NotesFor 1 Hour Openings:Use3/8”polycarbonateinconjunctionwithsprinklerheadsand5/8”stopswhere the authority having jursidiction will accept NYS-OMH’s Warnock Hersey test(nottestedperASTMF1233).ORProvidefire-ratedglazingcladwith1/4”polycarbonate on each side accessible to patients.

For Greater than 1 Hour Openings:FireLite and FireLite PLUS products can be used.

Page 68: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 68

Division 08 | OpeningsGlazing, Observation Mirrors

Plaskolite, Inc.www.plaskolite.com

See-Thru MirrorTwo-way observation polycarbonate mirror, 0.236”thickminimum.Productissemi-transparent.HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Installation NotesInstallation Option 1:Install glazing in a hollow metal frame withglazingstopsthatprovidea5/8”continuous edge bite.

Installation Option 2:Install glazing in a hollow metal frame withglazingstopsthatprovidea1/2”continuous edge bite with structural silicone sealant at the full perimeter.

Transparency Reflectivity

Page 69: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 69

Division 08 | OpeningsExterior Windows

General NotesSeetheNYS-OMHSpecificationGuide-line for 085653 Security Windows for additional information.

Performance CriteriaAlternate minimum standard for facil-ities other than the newly constructed NYS-OMH operated: Provide detention screen, or windows with sash, frame, and glazing capable of withstanding 2,000 ft-lb impact loads from a 1 foot diameter impact object without breach, dislodging or breakage. The use of alternative window treatments identi-fiedelsewhereinthisdocumentareanoption to integral blinds.

Caution: wExercise caution when window size exceeds 4’-0” x 6’-0”.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Britplaswww.britplas.com

Safevent Windows

New Exterior Window ApplicationsHorizontal Sliders. Sliding window assembly with perforated metal screen. Install with operable slider on the exterior. Comply with2,000ft-lbimpacttestasspecifiedbyNYS-OMH and AAMA 501.8 Standard Test Method for Determination of Resistance to Human Impact of Window Systems Intended for Use in Psychiatric Applications.w No security screens required. w Provide4”openingrestrictionfor

operable windows.w Provide one of the following for interior

glazing. When specifying laminated glazing,firstverifythatthewindowhaspassed the above referenced impact test with laminated glazing.

s 1/2”polycarbonatewith1”continuous edge bite, dry glazed for interior glazing.

s Glass-clad polycarbonate.w Provide ligature resistant manual

window operator or electric operator. w Provide concealed operable blinds with

ligature resistant operator.w SeeNYS-OMHSpecificationGuideline

for 085653 Security Windows for acceptable locking mechanisms.

Window Operator - Manual Knob|Lock

View from Interior - Screen on left panel

Page 70: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 70

Division 08 | OpeningsExterior Windows

General NotesSeetheNYS-OMHSpecificationGuide-line for 085653 Security Windows for additional information.

Performance CriteriaAlternate minimum standard for facil-ities other than the newly constructed NYS-OMH operated: Provide detention screen, or windows with sash, frame, and glazing capable of withstanding 2,000 ft-lb impact loads from a 1 foot diameter impact object without breach, dislodging or breakage. The use of alternative window treatments identi-fiedelsewhereinthisdocumentareanoption to integral blinds.

Cautions:w Exercise caution when window

size exceeds 4’-0” x 6’-0”.w Windows with casement sashes

can be easily looped.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Graham ArchitecturalProductswww.grahamwindows.com

S6300 Series Human Impact Window

New Exterior Window ApplicationsComply with 2,000 ft-lb impact test as specifiedbyNYS-OMHandAAMA501.8Standard Test Method for Determination of Resistance to Human Impact of Window Systems Intended for Use in Psychiatric Applications.w Casement,projectedorfixed.w No security screens required. w Provide4”openingrestrictionfor

operable windows.w Provide1/2”polycarbonatewith1”

continuous edge bite, dry glazed for interior glazing.

w Provide concealed operable blinds with ligature resistant operator.

w SeeNYS-OMHSpecificationGuidelinefor 085653 Security Windows for acceptable locking mechanisms.

Page 71: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 71

Division 08 | OpeningsExterior Windows

General NotesSeetheNYS-OMHSpecificationGuide-line for 085653 Security Windows for additional information.

Performance CriteriaAlternate minimum standard for facil-ities other than the newly constructed NYS-OMH operated: Provide detention screen, or windows with sash, frame, and glazing capable of withstanding 2,000 ft-lb impact loads from a 1 foot diameter impact object without breach, dislodging or breakage. The use of alternative window treatments identi-fiedelsewhereinthisdocumentareanoption to integral blinds.

Cautions:w Exercise caution when window

size exceeds 4’-0” x 6’-0”.w Windows with casement sashes

can be easily looped.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Oldcastle Building Envelopewww.oldcastlebe.com

Pinnacle Series 64P & 66PModuline Windows

New Exterior Window ApplicationsPinnacle Series Moduline Windows, 64P; 31/4”forusewith1/4”exteriorglazing,or66P;4”forusewith1”exteriorinsulatedglazing. Comply with 2,000 ft-lb impact test asspecifiedbyNYS-OMHandAAMA501.8Standard Test Method for Determination of Resistance to Human Impact of Window Systems Intended for Use in Psychiatric Applications.w No security screens required.w External insect screens are available. w Provide4”openingrestrictionfor

operable windows.w Provide1/2”polycarbonatewith1”

continuous edge bite, dry glazed for interior glazing.

w Provide concealed operable blinds with ligatureresistantoperator(e.g.blindtiltcontrolknobor1/8”verticalthumbwheeltilter).

w SeeNYS-OMHSpecificationGuidelinefor 085653 Security Windows for acceptable locking mechanisms.

Caution: Do not use low profile, side mount angled or vertical mount angled operators for concealed operable blinds because they create ligature points.

Blind OperatorsTilt Control Knob Vertical Thumb Wheel

Page 72: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 72

Division 08 | OpeningsExterior Windows

General NotesSeetheNYS-OMHSpecificationGuide-line for 085653 Security Windows for additional information.

Performance CriteriaAlternate minimum standard for facil-ities other than the newly constructed NYS-OMH operated: Provide detention screen, or windows with sash, frame, and glazing capable of withstanding 2,000 ft-lb impact loads from a 1 foot diameter impact object without breach, dislodging or breakage. The use of alternative window treatments identi-fiedelsewhereinthisdocumentareanoption to integral blinds.

Cautions:w Exercise caution when window

size exceeds 4’-0” x 6’-0”.w Windows with casement sashes

can be easily looped.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Wausau Window & WallSystemswww.wausauwindow.com

4000i-DT Psychiatric Windows2187-DT SEAL TM Windows

New Exterior Window Applications4000i-DTin-projectedcasementandfixedunits.w No security screens required.w External insect screens are available.

Retrofit Exterior Window Applications2187-DT SEAL TM can be installed over existing in-place windows, or as part of aluminum storefront or curtain wall installation.

New & Retrofit Exterior Window ApplicationsComply with 2,000 ft-lb impact test as specifiedbyNYS-OMHandAAMA501.8Standard Test Method for Determination of Resistance to Human Impact of Window Systems Intended for Use in Psychiatric Applications.w Provide4”openingrestrictionfor

operable windows.w Provide1/2”polycarbonatewith1”

continuous edge bite, dry glazed for interior glazing.

w Provide concealed operable blinds with ligatureresistantoperator(e.g.blindtiltcontrolknob).

w SeeNYS-OMHSpecificationGuide-line for 085653 Security Windows for acceptable locking mechanisms.

Caution: Do not use low profile, side mount angled or vertical mount angled operators for concealed operable blinds because they create ligature points.

Blind OperatorTilt Control Knob

Page 73: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 73

Division 08 | OpeningsAccess Doors

General NotesAvoid the use of access doors in patient areas to the greatest extent possible, particularly in unsupervised areas such as patient bedrooms and bathrooms.

Installation NotesAccess door frames shall be 16 gauge steel. Access door shall be 20 gauge steel,weldedpantype.Doorflangeshallbe1”wideminimum,forembed-ment in drywall compound. Hinges shall be continuous. Base metal shall be steel with primer coat of rust inhibitive electrostatic powder baked gray enamel or stainless steel.

Theaccessdoormaybefilledwithfirerated insulation. The door shall be auto-matic closing, self-latching and contain an interior latch release.

Locks shall be mortise slam latch with keyed cylinder. All locks shall be keyed alike.

Cendrexwww.cendrex.com

PF Series Fire Rated Access Doors

J. L. Industrieswww.jlindustries.com

FDWB Fire Rated Access Panel

Page 74: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 74

Division 09 | Finishes

Page 75: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 75

Division 09 | FinishesCeiling Assemblies, General

Ceililng Assemblies

The Designer should determine ceilings that are required to have an STC rating or Special Acoustic properties. Ceiling heights should be evaluated based on patient population and risk levels. Frequent accessibility to MEP items above the ceiling and vulnerability to access door should be considered when selecting a ceiling system.

•OMHCeilingAssembly1:1layer1/2”or5/8”drywallwithmetalframing/suspensionsystem. wProvide Type-X or Type-C drywall where part of a rated assembly. wProvide water resistant drywall at locations exposed to moisture.

•OMHCeilingAssembly2:1layer5/8”VeryHighImpact(VH1)abuseresistantdrywallwithmetalframing/suspensionsystem. wProvide additional layers of Type-X or Type-C drywall between VH1 drywall and metal support system where part of a rated assembly.

•OMHCeilingAssembly3:3/4”suspendedacoustictileonintermediatedutysuspensionsystem. wHold down clips are not recommended for use with this ceiling assembly. They can become dislodged over time and used as weapons.

•OMHCeilingAssembly4:ClassAFRP(Kemlite)CeilingPanelwithFRPsuspensionsystemand12gaugestainlesssteelwire. wHold down clips are not recommended for use with this ceiling assembly.

• OMH Ceiling Assembly 5: Metal Panel Security System

• OMH Ceiling Assembly 6: Tectum Inc. Continuous steel reinforced, corridor spanned, Security Ceiling Panels with tegular edges and concealed suspension components. wMustHaveArmstrongPrelude15/16”maincarrierandcustomsecuritystrapswith20gaugesteelwallchannels.

Page 76: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 76

Division 09 | FinishesWall Base

General NotesUse only heat welded integral cove base,solidwoodorprefinishedrubber/PVC base.

Installation NotesIntegral Cove Base: Adhere base to wall. Provide tamper resistant sealant along the top edge of base.

Wood and rubber Wall Base: Adhere and mechanically fasten base to wall. Fasteners shall be screwed into wood blocking,countersunkandfilled.

Caution: Do not specify conventional commercial vinyl or rubber wall base in patient areas. These products are easily removable, presenting risk of weaponization.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Custom Wood Base

Custom Designed Wood BaseSolid3/4”hardwoodwitheasedorbullnosetop and corners. Provide tamper resistant sealantatjointbetweenfloorandbase,base and wall surface.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Johnsonitewww.johnsonite.com

Millwork Contoured Wall BaseThermoplastic solid rubber base. Various profilesrangeinheightfrom21/2”to6”high,1/4”to3/8”thick.

Page 77: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 77

Division 09 | FinishesWall Base

Flexcowww.flexcofloors.com

Health Design Wall BaseThermoplasticrubberbasetapersfrom1/8”thicktoadjacentfloorthickness.Allseamsare heat welded.

Johnsonitewww.johnsonite.com

SCC-XX-A Cove Cap MouldingVinylcovecapmouldingaccessoryfor1/8”cove base material.

Note: Material can be pulled out of place in installation and weaponized.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

General NotesUse only heat welded integral cove base,solidwoodorprefinishedrubber/PVC base.

Installation NotesIntegral Cove Base: Adhere base to wall. Provide tamper resistant sealant along the top edge of base.

Wood and rubber Wall Base: Adhere and mechanically fasten base to wall. Fasteners shall be screwed into wood blocking,countersunkandfilled.

Caution: Do not specify conventional commercial vinyl or rubber wall base in patient areas. These products are easily removable, presenting risk of weaponization.

Page 78: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 78

Division 09 | FinishesCeilings

General NotesCeiling panels are not removable and access doors need to be installed to pro-vide access above the ceiling.

Installation NotesAll ceiling panels are to be mechanically fastened with tamper resistant fasteners, even interlocking panels.

Specifiershallselectsteelgaugebasedonfinishedceilingheightsandrisklev-els of installation areas.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Armstrongwww.armstrong.com

Metalworks Linear Ceiling SystemSolid or perforated electrogalvanized steel, 0.028”thick,ClassAperASTME84.Wash-able, scrubbable, impact resistant, and soil resistant. Access doors can be cut into the assembly.

Rockfonwww.rockfon.com

Securline Metal Plank Security Ceiling SystemSolid or perforated galvanized steel, 12 to 18 gauge, Class A per ASTM E84. Over-lapping planks with heavy duty channels, standardsize1’-10”.Washablebakedonenamelfinish.Optionalacousticalpadsavailable. Access doors can be cut into the assembly.

Page 79: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 79

Division 09 | FinishesCeilings

Accurate Ceiling Systemswww.accurateperforating.com

Sentry Plank Ceiling SystemSolidorperforated1’x10’,1’-6”x10’,or2’ x 10’ overlapping metal planks with an exposed heavy duty perimeter wall channel. Available in 12, 14, 16, 18, and 20 gauge steel or .040 aluminum. Planks are wash-ablewithbaked-onenamelfinish.

General NotesCeiling panels are not removable and access doors need to be installed to pro-vide access above the ceiling.

Installation NotesAll ceiling panels are to be mechanically fastened with tamper resistant fasteners, even interlocking panels.

Specifiershallselectsteelgaugebasedonfinishedceilingheightsandrisklev-els of installation areas.

typi

cal c

eilin

g pl

ank

EXISTING WALL

14 GA. GALVANIZED WALL CHANNEL CLIPCENTERED IN PANEL TYP.

SECURITY CEILING PANEL (SEE GENERAL NOTES)

TEK SCREWS 24" (MAX) O.C. FIRST & LAST TEK SCREWSTO BE LOCATED 2" (MAX) IN FROM END OF PANEL

FASTENER 24" (MAX) O.C. TYPE AS REQ’D BY WALL CONSTRUCTION

WALL C-CHANNEL (OR OPTIONAL L-MOULDING WITH SECURITY SCREWS)

1"21

2"

ACOUSTICAL SECURITY CEILING PANEL (SEE GENERAL NOTES FOR PERFORATION PATTERN AND MATERIAL SPECIFICATION)

1"211"

21

3" 42

12"

14 GA. STEEL WALL MOULDING WITH “C” MOULDING HOLDDOWN (OR OPTIONAL L-MOULDING) AT EACH PLANK. SECURE TO WALL WITH DRILLED-IN ANCHORS 16" O.C.

FACTORY-PUNCHED HOLES FOR SELF-TAPPING SCREWSTO INTERLOCK PLANKS. FASTENERS 24" O.C.

Accurate’s plank wall and ceiling systems are available in solid or perforated 16-gauge to 12-gauge galvanized steel (or stainless steel). The galvanized plank shall be white powder coat paint finish (stainless steel planks shall be #4 satin finish). Sizes shall be 12-24" widths and up to 12' lengths. Panels can be custom sized upon request.

plank wall and ceiling systems

3636 S. Kedzie Avenue | ChiCAgo, illinoiS 60632 1.800.621.0273 | T 773.254.3232 | F 773.254.9453 | www.ACCurATeperForATing.Com

isom

etri

c vi

eww

all m

oldi

ng d

etai

l

Page 80: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 80

Division 10 | Specialties

Page 81: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 81

Division 10 | SpecialtiesShower & Privacy Curtains

General NotesUsers shall perform a risk assessment to determine their options for shower and privacy curtains.

Performance CriteriaMaterial tests should include verifying fabrics in both wet and dry conditions, which can affect asphyxiation.

Installation NotesSpecify breathable fabric material for shower and privacy curtains.

Recessed ceiling track shall run continu-ously between walls. Surface mounted ceiling track shall run continuously be-tween walls, or be installed with secure end caps. Fill all joints between sections of track with tamper resistant sealant to reduce opportunities for ligature.

Cautions:w End caps can create opportunity

for a wedge ligature.w A looping point can be created

in curtain tracks when an object,such as a penny, is inserted intothe track.

w The breakaway weight for curtaincarriers may exceed the limits atwhich self-harm can be induced.Carriers can be ganged togetherto increase the release weight.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

InPro Corporationwww.inprocorp.com

Clickeze Ultra Cubicle TrackExtruded aluminum track provides heavy duty strength. For use with Clickeze acces-sories.

Clickeze Whisper Cubicle TrackExtruded PVC track allows for noise reduc-tion during curtain movement. For use with Clickeze accessories.

Whisper TrackUltra Track

Caution: Potential looping point at curtain tracks.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Construction Specialties, Inc.www.c-sgroup.com

Breakaway Carrier #975PHook on carrier is designed to pop out of the axle when approximately 22 lbs. of pressure is applied to the hook, and can be reused.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

InPro Corporationwww.inprocorp.com

Clickeze Pop Out CarrierHook on carrier releases, allowing the cur-tain to fall, and disengages at approximate-ly 10 lbs. of pressure. For use with both Clickeze Ultra and Whisper Curtain Tracks.

Page 82: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 82

Division 10 | SpecialtiesShower & Privacy Curtains

Imperial Fastener Companywww.imperialfastener.com

IFC-69 Break-A-Way Track &IFC-79 Break-A-Way TrackThe IFC-69 ceiling mounted and IFC-79 wall mountedtracksareusedwith“SafetyTabs”that attach to box pleated window draperies or shower curtains.

Notes:w Velcro on “Safety Tabs” creates a tie

off ligature point.w IFC-79 wall mounted curtain track can

be continuously looped end to end.

AFS Securitywww.afs-securitysystems.com

Kestrel MovatrackMovatrack curtain suspension system utilizes magnetic wall brackets where the track meets the wall, and ceilings brackets with suspension hangers at ceilings. Under excess loads, the suspension hangers sepa-rate from the ceiling brackets.

Note: Loose parts can be ingested and ease of disassembly is likely to be a nuisance to staff.

IFC-79 Break-A-Way Track

IFC-69 Break-A-Way Track

General NotesUsers shall perform a risk assessment to determine their options for shower and privacy curtains.

Performance CriteriaMaterial tests should include verifying fabrics in both wet and dry conditions, which can affect asphyxiation.

Installation NotesSpecify breathable fabric material for shower and privacy curtains.

Recessed ceiling track shall run continu-ously between walls. Surface mounted ceiling track shall run continuously be-tween walls, or be installed with secure end caps. Fill all joints between sections of track with tamper resistant sealant to reduce opportunities for ligature.

Cautions:w End caps can create opportunity

for a wedge ligature.w A looping point can be created

in curtain tracks when an object, such as a penny, is inserted into the track.

w The breakaway weight for curtain carriers may exceed the limits at which self-harm can be induced. Carriers can be ganged together to increase the release weight.

Page 83: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 83

Division 10 | SpecialtiesShower & Privacy Curtains

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Architexwww.architex-ljh.com

Rx Privacy CurtainMade with 100% Avora polyester, Style #5/2019717-1000.

Arc|Comwww.arc-com.com

Options CurtainCustomizable textiles to increase durability andfireresistance.Stainrepellent.

General NotesUsers shall perform a risk assessment to determine their options for shower and privacy curtains.

Performance CriteriaMaterial tests should include verifying fabrics in both wet and dry conditions, which can affect asphyxiation.

Installation NotesSpecify breathable fabric material for shower and privacy curtains.

Recessed ceiling track shall run continu-ously between walls. Surface mounted ceiling track shall run continuously be-tween walls, or be installed with secure end caps. Fill all joints between sections of track with tamper resistant sealant to reduce opportunities for ligature.

Cautions:w End caps can create opportunity

for a wedge ligature.w A looping point can be created

in curtain tracks when an object, such as a penny, is inserted into the track.

w The breakaway weight for curtain carriers may exceed the limits at which self-harm can be induced. Carriers can be ganged together to increase the release weight.

Page 84: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 84

Division 10 | SpecialtiesShower & Privacy Curtains

Standard Textilewww.standardtextile.com

Perfect Panel Curtains

Note: Ganging of multiple snaps along the curtain track can create a ligature point.

General NotesUsers shall perform a risk assessment to determine their options for shower and privacy curtains.

Performance CriteriaMaterial tests should include verifying fabrics in both wet and dry conditions, which can affect asphyxiation.

Installation NotesSpecify breathable fabric material for shower and privacy curtains.

Recessed ceiling track shall run continu-ously between walls. Surface mounted ceiling track shall run continuously be-tween walls, or be installed with secure end caps. Fill all joints between sections of track with tamper resistant sealant to reduce opportunities for ligature.

Cautions:w End caps can create opportunity

for a wedge ligature.w A looping point can be created

in curtain tracks when an object, such as a penny, is inserted into the track.

w The breakaway weight for curtain carriers may exceed the limits at which self-harm can be induced. Carriers can be ganged together to increase the release weight.

Page 85: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 85

Division 10 | SpecialtiesCloset Rods, Clothes & Towel Hooks

Code Notes2010FGI“GuidelinesfortheCon-struction of Hospitals and Outpatient Facilities”requiresthat;“Shelvesforfolded garments shall be used instead of arrangementsforhanginggarments.”

Laidlawwww.laidlawdirect.com

Orbis Coat Hook 81.AL8.03Anti-ligature spherical casing. Hook can support the weight of a small coat but releases under downward applied load.

Note: Hook can be tied off to form a ligature point.

American Specialties, Inc.www.americanspecialties.com

123 Square Clothes Hook

Oddball Industrieswww.oddballindustries.com

SP-6 Clothes/Towel HookSP-6A Clothes/Towel Hook with adjustable tension release Note: Hook can be tied off to form a ligature point.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kingsway Groupwww.kingswaygroupglobal.com

KG180 Coat HookStainless steel surround. Rubber hook re-leases under downward applied load.

Norva Plastics, Inc.www.norvaplastics.com

Polyethylene Hook

Caution: Hook can be tied off to form a side ligature point. Installation location should be considered to prevent a sec-ond point of ligature.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 86: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 86

Division 10 | SpecialtiesCloset Rods, Clothes & Towel Hooks

Bradley Corporationwww.bradleycorp.com

Model SA36 Tension Towel Hook Note: Hook can be tied off to form a ligature point.

Healthgear Contractswww.healthgear.co.uk

Detsafe PH130003 Note: Hook can be tied off to form a ligature point.

HenkelHookwww.henkelhook.com

HenkelHook Note: Hook can be wedged to create a ligature point.

AFS Securitywww.afs-securitysystems.com

K507 Coat Hook Note: Loose parts can be ingested and ease of disassembly is likely to be a nuisance to staff.

Code Notes2010FGI“GuidelinesfortheCon-struction of Hospitals and Outpatient Facilities”requiresthat;“Shelvesforfolded garments shall be used instead of arrangementsforhanginggarments.”

Page 87: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 87

Division 10 | SpecialtiesCloset Rods, Clothes & Towel Hooks

Whitehall Manufacturingwww.whitehallmfg.com

BestCare Clothing & Towel HolderWH1830 Note: Hook can be tied off to form a ligature point.

Willoughby Industries, Inc.www.willoughby-ind.com

CTH-4 Clasp Type Towel Hook

Notes: w Hooks can be tied off of to form a

ganged ligature pointw Clasp style hook allow for wedging

opportunities

Norixwww.norix.com

Towel Hook Note: Hook can be tied off with a loop to form a ligature point.

Oddball Industrieswww.oddballindustries.com

SP-1 Closet “Bar”

Note: Hangers may be ganged together to increase breakaway weight.

Code Notes2010FGI“GuidelinesfortheCon-struction of Hospitals and Outpatient Facilities”requiresthat;“Shelvesforfolded garments shall be used instead of arrangementsforhanginggarments.”

Page 88: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 88

Division 10 | SpecialtiesHandrails & Grab Bars, General

General NotesNearly all handrails and grab bars are subject to possible wedge ligature with a shoe or other object.

Grab bars should only be installed where required by code.

Installation NotesVerify that all handrails and grab bars are installed per the manufacturer’s installation instructions. Proper installa-tion is critical in order for tight tolerances between the multiple product pieces.

Sealantmayberequiredtofillvoidsaround the perimeter of handrails and grab bars depending on installation substrate.

Caution: Traditional code compliant handrails and grab bars create obvious ligature opportunities.

Page 89: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 89

Division 10 | SpecialtiesHandrails

General NotesAll handrails are subject to possible wedge ligature with a shoe or other object.

Installation NotesVerify that all handrails are installed per the manufacturer’s installation instruc-tions. Proper installation is critical in order for tight tolerances between the multiple product pieces.

Sealantmayberequiredtofillvoidsaround the perimeter of handrails and grab bars depending on installation substrate.

Additional NotesThe inside of handrails with continuous mounting brackets are susceptible to the collection of debris.

Caution: Traditional code compliant handrails create obvious ligature opportunities.

Construction Specialties, Inc.www.c-sgroup.com

HRB-20CMHLN Acrovyn 4000 HandrailHandrail/bumper guard with psychiatric continuous bracket enclosure, to address safety issues for patients eliminating the gap between the wall and handrail. Meets safety codes with ADA and ANSI compliance.

Caution: Cover is easily removable and can be broken or weaponized.

Pawling Corporationwww.pawling.com

BR-400CS Series Handrail6-1/4”highvinylhandrail.Suicideresistantdesign to minimize leverage and looping with radius corners. Aluminum tube with lasercut1/8”aluminumclosureplates.Continuous secure bracket.

Caution: Cover is easily removable and can be broken or weaponized.

Page 90: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 90

Division 10 | SpecialtiesHandrails

Pawling Corporationwww.pawling.com

BR-500 Series Handrail5-1/2”highvinylhandrail.Suicidalresistantdesign to minimize leverage and looping with radius corners. Aluminum tube with lasercut1/8”aluminumclosureplates.Continuous secure bracket.

Caution: Cover is easily removable and can be broken or weaponized.

General NotesAll handrails are subject to possible wedge ligature with a shoe or other object.

Installation NotesVerify that all handrails are installed per the manufacturer’s installation instruc-tions. Proper installation is critical in order for tight tolerances between the multiple product pieces.

Sealantmayberequiredtofillvoidsaround the perimeter of handrails and grab bars depending on installation substrate.

Additional NotesThe inside of handrails with continuous mounting brackets are susceptible to the collection of debris

Caution: Traditional code compliant handrails create obvious ligature opportunities.

Wallguardwww.wallguard.com

2021S Handrail5-1/2”high,12’-0”continuoussecuritybrack-etandmountingsystem.ClassAfireratingand ADA compliant. Provide manufacturer’s continuousaluminumtubewithlasercut1/8”thick aluminum closure plates at corners and mechanically fastened. Colored cover shall be installed with 3M Fastbond 30 water based contact adhesive to prevent removal.

Caution: Cover is easily removable and can be broken or weaponized.

Page 91: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 91

Division 10 | SpecialtiesToilet Accessories, Grab Bars

General NotesAll grab bars are subject to possible wedge ligature with a shoe or other ob-ject. Grab bars should only be installed where required by code.

Performance CriteriaSpecify SS Type 316 stainless steel for wet locations when available.

Installation NotesVerify that all grab bars are installed per the manufacturer’s installation instruc-tions. Proper installation is critical in order for tight tolerances between the multiple product pieces.

Provide continuous blocking. Be atten-tive to potential moment arm issues on existing installations without continuous blocking.

Sealantmayberequiredtofillvoidsaround the perimeter of grab bars de-pending on the installation substrate.

Additional NotesSpecialty grab bars may be handed in only one direction when installed verti-cally.

Cautions:w Traditional code compliant grab bars

create obvious ligature opportunities.w ICRA notes potential infection control

problem at end closure plates.w Drainage holes at end caps create

potential ligature opportunities with paper clips.

Kingsway Groupwww.kingswaygroupglobal.com

Grab Rail KG250/KG251Horizontal and vertical mounting. Painted extruded aluminum, 600 mm long. Provide sealant at the full perimeter to pre-vent end to end looping.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Northwest SpecialtyHardwarewww.northwestsh.com

NW Security Bar

Cascade SpecialtyHardwarewww.cascadesh.com

Safebar Grab Bar

Securing Cosmoswww.securingcosmos.com

811-S03 SafeSupport SR Safe-T Grab BarSpecialty self-draining end caps are avail-able from manufacturers and should be specified.Providesealantatthefullperime-ter to prevent end to end looping.

Caution: Horizontal and vertical mounting are acceptable but may permit wedge ligature with a shoe or other object.

Page 92: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 92

Division 10 | SpecialtiesToilet Accessories, Grab Bars

General NotesAll grab bars are subject to possible wedge ligature with a shoe or other ob-ject. Grab bars should only be installed where required by code.

Performance CriteriaSpecify SS Type 316 stainless steel for wet locations when available.

Installation NotesVerify that all grab bars are installed per the manufacturer’s installation instruc-tions. Proper installation is critical in order for tight tolerances between the multiple product pieces.

Provide continuous blocking. Be atten-tive to potential moment arm issues on existing installations without continuous blocking.

Sealantmayberequiredtofillvoidsaround the perimeter of grab bars de-pending on the installation substrate.

Additional NotesSpecialty grab bars may be handed in only one direction when installed verti-cally.

Cautions:w Traditional code compliant grab bars

create obvious ligature opportunities.w ICRA notes potential infection control

problem at end closure plates.w Drainage holes at end caps create

potential ligature opportunities with paper clips.

Willoughby Industries, Inc.www.willoughby-ind.com

AntiSuicide Grab Bar Modified with End CapsASGB-X-ODD-MODSpecialty self-draining end caps are avail-able from manufacturers and should be specified.Providesealantatthefullperime-ter to prevent end to end looping.

Caution: Horizontal and vertical mounting are acceptable but may permit wedge ligature with a shoe or other object.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 93: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 93

Division 10 | SpecialtiesToilet Accessories, Grab Bars

General NotesAll grab bars are subject to possible wedge ligature with a shoe or other ob-ject. Grab bars should only be installed where required by code.

Performance CriteriaSpecify SS Type 316 stainless steel for wet locations when available.

Installation NotesVerify that all grab bars are installed per the manufacturer’s installation instruc-tions. Proper installation is critical in order for tight tolerances between the multiple product pieces.

Provide continuous blocking. Be atten-tive to potential moment arm issues on existing installations without continuous blocking.

Sealantmayberequiredtofillvoidsaround the perimeter of grab bars de-pending on the installation substrate.

Additional NotesSpecialty grab bars may be handed in only one direction when installed verti-cally.

Cautions:w Traditional code compliant grab bars

create obvious ligature opportunities.w ICRA notes potential infection control

problem at end closure plates.w Drainage holes at end caps create

potential ligature opportunities with paper clips.

Whitehall Manufacturingwww.whitehallmfg.com

1110-2 24” Ligature ResistantGrab Bar Note: This product may allow end to end looping ligature.

Whitehall Manufacturingwww.whitehallmfg.com

1109-1 24” Ligature ResistantGrab Bar Note: This product may allow end to end looping ligature.

Whitehall Manufacturingwww.whitehallmfg.com

Best-Care WH1140 Ligature Resistant ADA Compliant Grab Bar with V-Closure Strip

Note: Drainage holes permit ligatures.

Page 94: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 94

Division 10 | SpecialtiesToilet Accessories, Grab Bars

General NotesAll grab bars are subject to possible wedge ligature with a shoe or other ob-ject. Grab bars should only be installed where required by code.

Performance CriteriaSpecify SS Type 316 stainless steel for wet locations when available.

Installation NotesVerify that all grab bars are installed per the manufacturer’s installation instruc-tions. Proper installation is critical in order for tight tolerances between the multiple product pieces.

Provide continuous blocking. Be atten-tive to potential moment arm issues on existing installations without continuous blocking.

Sealantmayberequiredtofillvoidsaround the perimeter of grab bars de-pending on the installation substrate.

Additional NotesSpecialty grab bars may be handed in only one direction when installed verti-cally.

Cautions:w Traditional code compliant grab bars

create obvious ligature opportunities.w ICRA notes potential infection control

problem at end closure plates.w Drainage holes at end caps create

potential ligature opportunities with paper clips.

Willoughby Industries, Inc.www.willoughby-ind.com

Anti Suicide Grab BarModified for OGSASGB-X-OGS-MOD Note: This product may allow end to end looping ligature.

Securing Cosmoswww.securingcosmos.com

811-S38 SafeSupport SR Draining Grab BarHorizontal mounting.

Note: Drainage slot permits ligature.

American Specialties, Inc.www.americanspecialties.com

0165 Grab Bar with Drain Holes Note: This product may allow end to end looping ligature.

Page 95: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 95

Division 10 | SpecialtiesToilet Accessories, General

General Notes

Some product categories offer few patient safe solutions that have been approved for use in NYS-OMH facilities. One such category is toilet accessories. Many manufacturers of soap dispensers, paper towel dispensers and toilet tissue dispensers/holders market their products as appropriate for use in high risk environments. Upon testing many products, NYS-OMH has determined that they often present opportunities for self-harm.

Failure Modes

Because these product types dispense disposable products, many of them make use of slots or holes. This allows for wedging and tying, providing opportunities for downward ligature.

Infection Control

There exist some inherent problems with options that present a patient safe solution, one of which is risk of infection. Paper towel and toilet tissue shelves and holders whichdonotsecurethedisposableproductsallowittofallonthefloor,renderingitcontaminated.Userscannotbepreventedfromusingthecontaminatedproducts;thisleads many facilities to disallow the use of shelves and holders.

Best In Class

It is the responsibility of each facility to determine, based on their own risk assessment, how best to address these needs. Some options in this Standard will appeal more thanothersbasedonpastexperienceandknowledgeofaparticularpatientpopulation.Thedecisiontoutilizeaproductnotedas“Rejected”or“UsewithCaution”mayinfact be the best solution for a facility, provided that it understands the risks involved and has a plan to manage those risks as best as possible.

Page 96: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 96

Division 10 | SpecialtiesToilet Accessories, Soap Dispensers

General NotesBest practice advocates the use of re-cessed toilet accessories.

Performance CriteriaQuality control of toilet accessories is importantandoftendifficulttocontrol.Samples should be requested as part of the submittal process.

Caution: Soap dispensers with flat tops or push levers provide a loopable ligature.

Gojo Industrieswww.gojo.com

LTX Behavioral Health Dispensing System Stainless steel Soap dispensing unit specif-ically designed for behavioral health envi-ronments with delayed time output, inhibited access interior, and sloped and rounded exterior.

Caution: Dispenser area allows for wedg-ing opportunities.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kingsway Groupwww.kingswaygroupglobal.com

KG06 Liquid Soap Dispenser

Stainless steel surface mounted liquid soap dispenser. Soap automatically dispenses from this battery operated unit.

Caution: Dispenser area allows for wedg-ing opportunities.

Page 97: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 97

Division 10 | SpecialtiesToilet Accessories, Soap Dispensers

General NotesBest practice advocates the use of re-cessed toilet accessories.

Performance CriteriaQuality control of toilet accessories is importantandoftendifficulttocontrol.Samples should be requested as part of the submittal process.

Caution: Soap dispensers with flat tops or push levers provide a loopable ligature.

American Specialties, Inc.www.americanspecialties.com

5002 Soap Dispenser Notes:w Product has sharp components.w Provides multiple ligature points.w Projects 1/2” from face of wall.

American Specialties, Inc.www.americanspecialties.com

9326 Soap Dispenser Note: This product provides a loopable ligature.

Bobrickwww.bobrick.com

B-26607 Soap Dispenser Note: This product provides a loopable ligature.

Gojo Industrieswww.gojo.com

ADX-12 Security Enclosure Note: This product provides wedging opportunities.

Page 98: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 98

Division 10 | SpecialtiesToilet Accessories, Soap Dispensers

General NotesBest practice advocates the use of re-cessed toilet accessories.

Performance CriteriaQuality control of toilet accessories is importantandoftendifficulttocontrol.Samples should be requested as part of the submittal process.

Caution: Soap dispensers with flat tops or push levers provide a loopable ligature.

Opsbox/Archer Manufacturingwww.vandalproof.org

Ops 1-Touch DispenserVandal Proof Foaming Dispenser Notes:w Activator allows for wedging

opportunities.w Provides ligature points.

Page 99: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 99

Division 10 | SpecialtiesToilet Accessories, Paper Towel Holders & Dispensers

General NotesBest practice advocates the use of re-cessed toilet accessories.

Performance CriteriaQuality control of toilet accessories is importantandoftendifficulttocontrol.Samples should be requested as part of the submittal process.

Installation NotesRecessed paper towel shelves require blocking on sides of shelf at wall studs and shall be mechanically through to blocking.

Specify wall thickness as required.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

American Specialties, Inc.www.americanspecialties.com

0412 Recessed Shelf22 gauge type 304 stainless steel with a No. 4satinfinish.Install with tamper resistant fasteners. Provide tamper resistant sealant atflangeperimeter.

Whitehall Manufacturingwww.whitehallmfg.com Best-Care WH1820FA Recessed Shelf16 gauge type 304 stainless steel with a sat-infinishorpowdercoatedwhitefinish.Installwith tamper resistant fasteners. Provide tamperresistantsealantatflangeperimeter.

Page 100: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 100

General NotesBest practice advocates the use of re-cessed toilet accessories.

Performance CriteriaQuality control of toilet accessories is importantandoftendifficulttocontrol.Samples should be requested as part of the submittal process.

Division 10 | SpecialtiesToilet Accessories, Paper Towel Holders & Dispensers

Georgia-Pacificwww.gppro.com

59466 enMotion Semi-Recessed Paper Towel DispenserSemi-recessed automated touchless paper towel dispenser.

Notes:w Loopable flat top allows ligature.w Serrated metal strip allows wedging

opportunity for downward ligature and potential for weaponization.

Georgia-Pacificwww.gppro.com

56620 Combination Folded Paper Towel DispenserCombination C-fold/multifold paper towel dispenser.

Notes:w Loopable flat top allows ligature.w Slotted dispenser allows wedging

opportunity for downward ligature.

Page 101: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 101

General NotesBest practice advocates the use of re-cessed toilet accessories.

Performance CriteriaQuality control of toilet accessories is importantandoftendifficulttocontrol.Samples should be requested as part of the submittal process.

Division 10 | SpecialtiesToilet Accessories, Paper Towel Holders & Dispensers

American Specialties, Inc.www.americanspecialties.com

0457 Recessed Paper TowelDispenser22 gauge type 304 stainless steel with a satinfinish.

Note: Slotted dispenser allows wedging opportunity for downward ligature.

Opsbox/Archer Manufacturingwww.vandalproof.org

Supreme Multi-Purpose Paper Towel Dispenser

Notes:w Slot allow for wedging opportunities.w Provides ligature points.

Page 102: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 102

Division 10 | SpecialtiesToilet Accessories, Hand Dryers

General NotesBest practice advocates the use of re-cessed toilet accessories.

Performance CriteriaQuality control of toilet accessories is importantandoftendifficulttocontrol.Samples should be requested as part of the submittal process.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

American Specialties, Inc.www.americanspecialties.com

0198MH SafeDri Recessed Mounted Sensor Hand Dryer18 gauge type 304 stainless steel cover and hand dryer chamber over automatic hand dryer with infrared sensor. Air intake pulls from stud space or plenum.

World Dryerwww.worlddryer.com

SLIMdri Hand DryerSurface-mounted ADA compliant hand dryer.

Caution: Vent area allows for looping opportunities.

Page 103: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 103

Bradley Corporationwww.bradleycorp.com

SA12 Recessed Toilet Tissue Roll Holder (Front Mounted)16 gauge type 304 stainless steel with a satinfinish.

Note: Joint between rim and faceplate plate permits looping.

General NotesBest practice advocates the use of re-cessed toilet accessories.

Performance CriteriaQuality control of toilet accessories is importantandoftendifficulttocontrol.Samples should be requested as part of the submittal process.

Installation NotesFront mounted models should be installed with tamper resistant fasten-ers. Back mounted models can only be installed on accessible chase walls.

Cautions:w Potential hazard with loose toilet

tissue rolls which can be lodgedin toilets.

w Potential infection control issuewith loose toilet tissue rollswhich can be easily dropped onthe floor.

w Toilet tissue holders with spindlesmay allow a downward ligatureby tying off to the spindles if theydon’t release when more than theacceptable amount of force isapplied (greater than 11 lbs.).

Division 10 | SpecialtiesToilet Accessories, Toilet Tissue Holders & Dispensers

Whitehall Manufacturingwww.whitehallmfg.com

1840-FA Recessed Toilet Paper Roll Holder (Front Mounted)14 gauge type 304 stainless steel with a satinfinishorwhiteenamelfinish.HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

American Specialties, Inc.www.americanspecialties.com

110-13 Recessed Toilet Paper RollHolder (Front Mounted)14 gauge type 304 stainless steel with a satinfinish.

Page 104: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 104

Division 10 | SpecialtiesToilet Accessories, Toilet Tissue Holders & Dispensers

General NotesBest practice advocates the use of re-cessed toilet accessories.

Performance CriteriaQuality control of toilet accessories is importantandoftendifficulttocontrol.Samples should be requested as part of the submittal process.

Installation NotesFront mounted models should be installed with tamper resistant fasten-ers. Back mounted models can only be installed on accessible chase walls.

Cautions:w Potential hazard with loose toilet

tissue rolls which can be lodged in toilets.

w Potential infection control issue with loose toilet tissue rolls which can be easily dropped on the floor.

w Toilet tissue holders with spindles may allow a downward ligature by tying off to the spindles if they don’t release when more than the acceptable amount of force is applied (greater than 11 lbs.).

Kingsway Groupwww.kingswaygroupglobal.com

Recessed Toilet RollHolder KG13

Caution: Break away weight is 16 lbs and exceeds recommended.

Cascade SpecialtyHardwarewww.cascadesh.com

C-400 Safety Toilet Paper Holder

Caution: Break away weight is 18 lbs and exceeds recommended.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Whitehall Manufacturingwww.whitehallmfg.com Best-Care WH1845B Ligature-Resistant Spindle ButtonRecessed Toilet Paper Holder

Kingsway Groupwww.kingswaygroupglobal.com

Surface Mount KG03 Toilet Roll Holder

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 105: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 105

Kingsway Groupwww.kingswaygroupglobal.com

Surface Mounted Toilet Tissue Dispenser Note: Slotted dispenser allows wedging opportunity for downward ligature.

Division 10 | SpecialtiesToilet Accessories, Toilet Tissue Holders & Dispensers

General NotesBest practice advocates the use of re-cessed toilet accessories.

Performance CriteriaQuality control of toilet accessories is importantandoftendifficulttocontrol.Samples should be requested as part of the submittal process.

Installation NotesFront mounted models should be installed with tamper resistant fasten-ers. Back mounted models can only be installed on accessible chase walls.

Cautions:w Potential hazard with loose toilet

tissue rolls which can be lodged in toilets.

w Potential infection control issue with loose toilet tissue rolls which can be easily dropped on the floor.

w Toilet tissue holders with spindles may allow a downward ligature by tying off to the spindles if they don’t release when more than the acceptable amount of force is applied (greater than 11 lbs.).

American Specialties, Inc.www.americanspecialties.com

0262 Surface Mounted Folded Toi-let Tissue Cabinet Note: Slotted dispenser allows wedging opportunity for downward ligature.

Whitehall Manufacturingwww.whitehallmfg.com Best-Care WH1845 & WH1845FA Recessed Auto-Release Toilet Pa-per Holder

Note: Spindles can be tied off to form a ligature point.

Northwest SpecialtyHardwarewww.northwestsh.com

NW 611 Toilet Paper Holder Note: Spindle can be tied off to form a ligature point.

Page 106: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 106

Division 10 | SpecialtiesToilet Accessories, Toilet Tissue Holders & Dispensers

General NotesBest practice advocates the use of re-cessed toilet accessories.

Performance CriteriaQuality control of toilet accessories is importantandoftendifficulttocontrol.Samples should be requested as part of the submittal process.

Installation NotesFront mounted models should be installed with tamper resistant fasten-ers. Back mounted models can only be installed on accessible chase walls.

Cautions:w Potential hazard with loose toilet

tissue rolls which can be lodged in toilets.

w Potential infection control issue with loose toilet tissue rolls which can be easily dropped on the floor.

w Toilet tissue holders with spindles may allow a downward ligature by tying off to the spindles if they don’t release when more than the acceptable amount of force is applied (greater than 11 lbs.).

Bobrickwww.bobrick.com

B-52891 MatrixSeries Jumbo Roll Toilet Tissue Dispenser Notes:w Plastic spindle can create a down-

ward ligature and can be broken into small shards and weaponized.

w Vision slot allows wedging opportu-nity for downward ligature

Morcon, Inc.

MO-M1007 Morcon Surface Mount-ed Metal Dispenser Note: Frame and spindles create an op-portunity for downward ligature.

Bobrickwww.bobrick.com

B-5288 Surface Mounted Multi-Roll Toilet Tissue Dispenser Note: Plastic spindle can create a down-ward ligature and can be broken into small shards and weaponized.

Page 107: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 107

Division 10 | SpecialtiesToilet Accessories, Mirrors

General NotesOnly polycarbonate glazing is recom-mended for use in patient bathrooms.

American Specialties, Inc.www.americanspecialties.com

0600 Angle Frame Mirror18 gauge type 304 stainless steel with satin finish.Concealedhangingbracketthatlocks onto top and bottom of frame by tam-per resistant screws.

Note: Ligature point can be established across the top of mirror due to squared edge and finish of stainless steel frame.

Sabic Innovative Plasticswww.sabic-ip.com

Royal Adhesives & Sealantswww.royaladhesives.com

Frameless PolycarbonateWall to Wall MirrorLexanDura-Mir,0.25”(6mm)polycarbon-ate. Install with Gunther ULTRA/BOND Mirror Mastic from wall to wall and from top of sink backsplash to ceiling.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Behavioral Safety Productswww.besafeprod.com

Ligature Resistant Stainless Steel Framed Mirror FM160Polishedstainlesssteelmirrorwith#8finish.18”x24”hardwoodframe.

Oddball Industrieswww.oddballindustries.com

SP-8 Mirror Guard

Note: Mirror guard has sharp edges and does not sit flush to profile of mirror.

Page 108: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 108

Division 10 | SpecialtiesWindow Treatments

General NotesUsers shall perform a risk assessment to determine their options for shower and privacy curtains.

Performance CriteriaMaterial tests should include verifying fabrics in both wet and dry conditions, which can affect asphyxiation.

Installation NotesSpecify breathable fabric material for shower and privacy curtains.

Recessed ceiling track shall run continu-ously between walls. Surface mounted ceiling track shall run continuously be-tween walls, or be installed with secure end caps. jambs. Fill all joints between sections of track with tamper resistant sealant to reduce opportunities for ligature.

Cautions:w End caps can create opportunity

for a wedge ligature.w A looping point can be created

in curtain tracks when an object,such as a penny, is inserted intothe track.

w The breakaway weight for curtaincarriers may exceed the limits at which self-harm can be induced. Carriers can be ganged together to increase the release weight.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

InPro Corporationwww.inprocorp.com

Clickeze Ultra Cubicle TrackExtruded aluminum track provides heavy duty strength. For use with Clickeze acces-sories.

Clickeze Whisper Cubicle TrackExtruded PVC track allows for noise reduc-tion during curtain movement. For use with Clickeze accessories.

Whisper TrackUltra Track

Caution: Potential looping point at curtain tracks.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Construction Specialties, Inc.www.c-sgroup.com

Breakaway Carrier #975PHook on carrier is designed to pop out of the axle when approximately 22 lbs. of pressure is applied to the hook, and can be reused.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

InPro Corporationwww.inprocorp.com

Clickeze Pop Out CarrierHook on carrier releases, allowing the cur-tain to fall, and disengages at approximate-ly 10 lbs. of pressure. For use with both Clickeze Ultra and Whisper Curtain Tracks.

Page 109: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 109

Division 10 | SpecialtiesWindow Treatments

Imperial Fastener Companywww.imperialfastener.com

IFC-69 Break-A-Way Track &IFC-79 Break-A-Way TrackThe IFC-69 ceiling mounted and IFC-79 wall mountedtracksareusedwith“SafetyTabs”that attach to box pleated window draperies or shower curtains.

Notes:w Velcro on “Safety Tabs” creates a tie

off ligature point.w IFC-79 wall mounted curtain track can

be continuously looped end to end.

IFC-79 Break-A-Way Track

IFC-69 Break-A-Way Track

WebbShadewww.webbshade.com

WebbLok ShadesThe IFC-69 ceiling mounted and IFC-79 wall mountedtracksareusedwith“SafetyTabs”that attach to box pleated window draperies or shower curtains.

Note: This product provides many potential ligature points.

General NotesUsers shall perform a risk assessment to determine their options for shower and privacy curtains.

Performance CriteriaMaterial tests should include verifying fabrics in both wet and dry conditions, which can affect asphyxiation.

Installation NotesSpecify breathable fabric material for shower and privacy curtains.

Recessed ceiling track shall run continu-ously between walls. Surface mounted ceiling track shall run continuously be-tween walls, or be installed with secure end caps. jambs. Fill all joints between sections of track with tamper resistant sealant to reduce opportunities for ligature.

Cautions:w End caps can create opportunity

for a wedge ligature.w A looping point can be created

in curtain tracks when an object, such as a penny, is inserted into the track.

w The breakaway weight for curtain carriers may exceed the limits at which self-harm can be induced. Carriers can be ganged together to increase the release weight.

Page 110: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 110

Division 10 | SpecialtiesWindow Treatments

Securing Hospitalswww.securinghospitals.com

845-S86 SafeSupport SR Window ShadesThe 845-S86 wall mounted tracks are used with“SafetyTabs”thatattachtoboxpleatedwindow draperies or shower curtains.

Note: This product provides many potential ligature points.

General NotesUsers shall perform a risk assessment to determine their options for shower and privacy curtains.

Performance CriteriaMaterial tests should include verifying fabrics in both wet and dry conditions, which can affect asphyxiation.

Installation NotesSpecify breathable fabric material for shower and privacy curtains.

Recessed ceiling track shall run continu-ously between walls. Surface mounted ceiling track shall run continuously be-tween walls, or be installed with secure end caps. jambs. Fill all joints between sections of track with tamper resistant sealant to reduce opportunities for ligature.

Cautions:w End caps can create opportunity

for a wedge ligature.w A looping point can be created

in curtain tracks when an object, such as a penny, is inserted into the track.

w The breakaway weight for curtain carriers may exceed the limits at which self-harm can be induced. Carriers can be ganged together to increase the release weight.

Page 111: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 111

Division 10 | SpecialtiesArtwork Frames

Behavioral Safety Productswww.besafeprod.com

Ligature Resistant Art Frame #AF550Multiple frame sizes available. Select prints from online library of 60 prints, to be matted like a typical picture frame, but positioned behind1/8”polycarbonateglazing.Followmanufacturer’s installation instructions.

Note: Polycarbonate cover breaks under impact.

Page 112: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 112

Division 10 | SpecialtiesCabinet Hardware

Performance CriteriaFor cabinet and dresser doors and drawers, provide either ligature resistant pullsorintegralrecessedflushpulls.

Installation NotesProvide non-loopable ligature resistant, tamper resistant security grade hard-ware. Ensure cabinet hinge pin is not removable(tackweldorcap).

Caution: Single point fasteners pose twist off hazard. Specify set screw or embed fastener in pick proof sealant.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Accurate Lock & Hardwarewww.accuratelockandhardware.com

CP-CAB Crescent Cabinet Pull

Doug Mockett & Company, Inc.www.mockett.com

DP74C Radiused Finger Grip Pull

Page 113: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 113

Division 10 | SpecialtiesCabinet Hardware

Performance CriteriaFor cabinet and dresser doors and drawers, provide either ligature resistant pullsorintegralrecessedflushpulls.

Installation NotesProvide non-loopable ligature resistant, tamper resistant security grade hard-ware. Ensure cabinet hinge pin is not removable(tackweldorcap).

Caution: Single point fasteners pose twist off hazard. Specify set screw or embed fastener in pick proof sealant.

Top Knobs Decorwww.topknobsdecor.com

M495 Somerset Cup PullZincalloywithGermanBronzefinish.

Note: Recess creates an opportunity for wedging.

Hafelewww.hafeleamericas.com

158.80 Flush PullHigh quality polyamide. Multiple sizes and colors available.

Note: Recess creates an opportunity for wedging.

Sugatsune America, Inc.www.sugatsune.com

UT-105/S Cabinet Pull

Notes: wThe cabinet pull is installed by pres-

sure fit. Therefore it can be forcibly removed and parts ingested.

w There are also looping ligature op-portunities between the pull and the substrate.

Page 114: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 114

Division 10 | SpecialtiesSignage

Installation NotesSignage systems should be mechani-cally fastened to substrate with tamper resistant fasteners. Double stick tape and Velcro are not acceptable.

King Architectural Productswww.king-ap.com

KMS Series Signage*Tamper resistant locking; Top, bottom, pan-elprofilesandcopycoversareheldinplaceby manufacturer’s standard concealed lock-ing pin. Specify two locking pins per sign.

Caution: Edges of metal profile pieces can be sharp.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

2/90 Sign Systemswww.290signs.com

Custom Patient Safe Signage

Thermoplastic frame, fully adhered to ther-moplastic backpanel. Clear polycarbonate insert lens. Mechanically fasten to blocking with tamper resistant screws.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 115: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 115

Division 10 | SpecialtiesSignage

Installation NotesSignage systems should be mechani-cally fastened to substrate with tamper resistant fasteners. Double stick tape and Velcro are not acceptable.

ASI Sign Systems, Inc.www.asisignage.com

Interior 20 Modular Signage

Note: Signage stands slightly off face of substrate and presents a finger pull opportunity.

2/90 Sign Systemswww.290signs.com

Flxsigns

Note: The Flxsign is highly susceptible to vandalism and can potentially be used as a weapon.

Page 116: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 116

Division 10 | SpecialtiesFire Extinguisher Cabinets

General NotesLocate only in supervised areas.

Installation NotesSee NYS-OMH Guidelines for strategies tomaintainwallassemblyfireratingsatrecessed cabinets.

Code NotesNFPA10requireslockingfireextinguish-ercabinetstoincludea“meansofemer-gencyaccess”.Manufacturersinterpretthis in various ways, including:

- Full lock with staff assigned keys.- Break-away latch/lock with resetta-

ble tongue.- Break-away latch/lock with non-re-

settable tongue.

Carefully review non-resettable products before specifying, as actual damage may be caused to the latch/lock mecha-nism during emergency access. Repair may be simple or complex depending on thespecificproduct.

Caution:Fire extinguisher cabinets are tested primarily for abuse-resistance and may be loopable at cabinet/door joint.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Activar ConstructionProducts Group, Inc.www.activarcpg.com

JL Industries Cosmopolitan Series Fire Extinguisher Cabinet

Note: Cabinet quality is not abuse or tamper resistant and presents many sharp edges.

Larsen’s Manufacturing Com-panywww.larsensmfg.com

Architectural Series 2712 FireExtinguisher CabinetStainless steel tub with a continuous hinge. Specifyfullyrecessedcabinetwithflattrim,or semi-recessed cabinet with rolled edge trim & door w/o handle. Specify mortise lock with keyed cylinder.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Larsen’s Manufacturing Companywww.larsensmfg.com

DECS 2409-R4 Fire Extinguisher Cabinet

Page 117: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 117

Division 12 | Furnishings

Page 118: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 118

Division 12 | FurnishingsFurniture, General

General Notes

Furniture with doors and drawers, such as wardrobes and dressers, will pose a potential ligature risk. Since there are no viable ligature resistant solutions, it is highly recommended that doors and drawers are not provided for wardrobes, dressers, closet units, etc. unless their use is regulated by staff controlled locks. When considering if the use of wardrobes, dressers or closet units is desired or appropriate, best practice requires each new facility to complete a risk assessment for all spaces and furnishings.Patientprivacyrightsmayalsoinformdecisionsabouttheneedforspecificfurnishings.

Doors & Drawers Guidelines

w Provide locks for all doors and drawers, allowing staff to control access by at-risk patients when necessary. w Provide doors with continuous hinges and hospital tips. w Providedoorswithrecessedligatureresistantfingerpulls.Ifavailable,continuousintegralfingerpullscanalsobeprovided. w Providedrawerswithrecessedligatureresistantfingerpulls,stops,andlocks. w For high risk patients, consider the use of built-in closets with door top ligature sensors.

Wardrobe & Closet Unit Guidelines

w Recesswardrobesandclosetunits,ormakecontinuoustoundersideofceilingsorsoffitsabove. w Whenit’snotpossibletomakerecessedunitsormakethemcontinuoustoundersideofceilingsorsoffitsabove,provideslopedtops. w Provide collapsible coat hooks. Closet rods and j-bars are not acceptable. w Requirementsofthe2010FGIGuidelinesstate:“Shelvesforfoldedgarmentsshallbeusedinsteadofarrangementsforhanginggarments.”

Platform Bed Guidelines

NYS-OMH has the following platform bed requirements: w Bedsmustbeplatformtypewithflushsidepanels,headboardsandfootboards,withnooverlappinglipsbetweenmembers. w Platformbedsshallbesix-sidedandhaveanenclosedbottom,orbefive-sidedandboltedtothefloor. w Providesolidwoodor3/4”plywoodpanelswithveneer.Particleboardandplasticlaminatearenotacceptable. w All members, both exposed and internal, shall be sealed with three layers of polyurethane. w Internal construction shall consist of at least two intermediate supports. Acceptable support materials are wood and metal. w All top and edge joints shall be sealed with tamper resistant sealant. w Providenoexposedfasteners,exceptwhenfasteningbedtothefloor. w Glides and adjustable feet are not acceptable. Felt pads only. w Exercise caution with platform beds that have restraints. These should be removed in all patient rooms unless one-on-one supervision is provided. w Each facility must perform their own risk assessment to evaluate all products.

Manufacturers must be able to customize their bed construction to comply with all NYS-OMH platform bed requirements. Beds that do not comply will be rejected by NYS-OMH.

Page 119: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 119

Division 12 | FurnishingsFurniture

Adden Furniture, Inc.www.addenfurniture.com

Roommate CasegoodsSolid oak planked panels with chamfered edges.Durablefinishwithreplaceableparts. Exposed surfaces are coated with catalyzedfinishresistanttoimpact.Finishis impervious to harsh chemical solutions such as wax strippers, paint and nail polish removers, and most commonly used an-ti-bacterial cleaning agents.

General NotesWood platform beds shall be 6-sided and all joints shall be sealed with tamper-resistant sealant.

Caution: Furniture with doors and drawers, such as wardrobes and dressers, will pose a potential ligature risk.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Agati Furniturewww.agati.com

Altra Forma CollectionChildren’s furniture manufactured with vinyl and fabric covered molded foam.

Page 120: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 120

Division 12 | FurnishingsFurniture

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Blockhouse Company, Inc.www.blockhouse.com

CS CasegoodsSolid oak planked panels with chamfered edges.Durablefinishwithreplaceableparts. Exposed surfaces are coated with catalyzedfinishresistanttoimpact.Finishis impervious to harsh chemical solutions such as wax strippers, paint and nail polish removers, and most commonly used an-ti-bacterial cleaning agents.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Flaghouse, Inc.www.flaghouse.com

Soft Rocker

General NotesWood platform beds shall be 6-sided and all joints shall be sealed with tamper-resistant sealant.

Caution: Furniture with doors and drawers, such as wardrobes and dressers, will pose a potential ligature risk.

Page 121: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 121

Division 12 | FurnishingsFurniture

Hill-Romwww.hill-rom.com

Harbor Glen Specialty Furniture SeriesSolidoakconstruction.Durablefinishwithreplaceable parts.HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Bedside Cabinet

Chest Desk

Nemschoffwww.nemschoff.com

Behavioral Health CasegoodsSolid wood construction with chamfered edges and continuous hinges. Non-remov-able drawers on roller guides. Finish is resistant to heavy use and harsh cleaning.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

General NotesWood platform beds shall be 6-sided and all joints shall be sealed with tamper-resistant sealant.

Caution: Furniture with doors and drawers, such as wardrobes and dressers, will pose a potential ligature risk.

Page 122: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 122

Division 12 | FurnishingsFurniture

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Savoy Contract Furniturewww.savoyfurniture.com

Homestead CollectionSolid wood mortise and tenon construction. All critical joints are supported with cleats and corner blocks added for strength. All drawers are full English dovetail with an inset bottom and replaceable fronts.

Norix Group, Inc.www.norix.com

Attenda BedCast molded polyethylene, weighted con-tinuously, with a minimal number of seams. Durablefinishwithreplaceableparts.Ifbedis not bolted down, plug mounting holes with tamper resistant fasteners.

Cautions:w Safe for use, though not appropriate

for all applications.w Use with caution at Article 28 and

Article 31 Hospitals.w Do not provide restraint rings. They

provide a looping ligature.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

General NotesWood platform beds shall be 6-sided and all joints shall be sealed with tamper-resistant sealant.

Caution: Furniture with doors and drawers, such as wardrobes and dressers, will pose a potential ligature risk.

Page 123: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 123

Division 21 | Fire Suppression

Page 124: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 124

Division 21 | Fire SuppressionSprinklers

General NotesMinimize removable parts.

Installation NotesSpecify no accessible parts that activate the sprinkler system when vandalized.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Tyco Fire Protection Productswww.tyco-fire.com

Raven Institutional SprinklersPendant and horizontal sidewall heads. Standard, Quick Response & Extended Cov-erage. Stainless steel escutcheons avail-able for installation in wet or damp areas.

Tyco Fire Protection Productswww.tyco-fire.com

Model TFP PH2 Sprinklers

Reliable Automatic Sprinkler Co., Inc.www.reliablesprinkler.com

Model XL Quick ResponseInstitutional Sprinkler

Cautions:w A portion of the sprinkler head proj-

ects below the sprinkler head enclo-sure and is accessible to patients; tampering may activate sprinkler.

w Removable parts create a potential safety hazard for ingestion and weap-onization.

w Break away weight is 50 lbs. and ex-ceeds recommended.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 125: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 125

Division 21 | Fire SuppressionSprinklers

General NotesMinimize removable parts.

Installation NotesSpecify no accessible parts that activate the sprinkler system when vandalized.

Viking Group Inc.www.vikinggroupinc.com

VK410 Pendant & VK412 Sidewall Institutional Flush Sprinklers

Note: The heat sensor projects below the sprinkler head enclosure and is acces-sible to patients. Damage to the heat sensor activates the system.

Page 126: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 126

Division 22 | Plumbing

Page 127: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 127

Division 22 | PlumbingLavatory Assemblies, Generals

General Notes

Lavatoriesinthefollowingsectionarespecifiedassystems.Individualcomponents,usedeitherindependentlyofthesystemtheyarespecifiedwith,orcombinedwithothersystems,maynotbeligatureresistant.Specifiersshouldtakecaretoutilizeproductsinconcerttocreatesystemsthataresafeforinstallationcondition(e.g.inanicheasopposedtofreestanding)andcombinationsofcomponentsthatmakeafunctionalandsafesystem.Thesecomponentsinclude:

w Activators & Actuatorsw Basinsw Countertopsw Faucetsw Fixturesw Mirrorsw Niche Lavatoriesw Pipe Enclosures

Ligature

Onlyfixedstrainersshouldbeused.Donotusepop-updrains.Careshouldbetakentospecifyligatureresistant strainers.

AppearanceFacilities are encouraged to utilize lavatories and toilets made of materials other than stainless steel that supportatherapeuticenvironment.Ifstainlesssteelfixturesarepreferredbyafacility,theyshouldbespecifiedwithapowdercoatedfinish.

Page 128: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 128

Division 22 | PlumbingLavatory Assemblies

Installation NotesUse of lavatories with engaged vanity counters are ligature resistant only when engaged side to side by knee walls or niches.

Code NotesProvide ADA compliant handicapped accessiblelavatoryassemblyconfigura-tions where required.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

NYS-OMH Standard Lavatory Assembly

Custom Solid Surface Lavatory with Integral Sink Bowl & PipeEnclosureNiche mounted solid surface vanity counter with integral solid surface sink bowl and deck mounted Behavioral Safety Products Ligature Resistant Sensor Faucet #SF370. Removable integral solid surface pipe enclo-sure below mounted with tamper resistant fasteners.

Page 129: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 129

Installation NotesUse of lavatories with engaged vanity counters are ligature resistant only when engaged side to side by knee walls or niches.

Code NotesProvide ADA compliant handicapped accessiblelavatoryassemblyconfigura-tions where required.

Division 22 | PlumbingLavatory Assemblies

Whitehall Manufacturingwww.whitehallmfg.com WH3775 Solid Surface Wall-Hung LavatoryShown with fully accessible powder-coated stainless steel pipe enclosure, deck-mount-ed dual-temp push-button conical faucet. Availablewithoutoverflowhole.

Page 130: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 130

General NotesSolid surface integral, countertop mounted and undermount lavatories are all acceptable when part of an assembly that is itself designed to be non-loopable.

Installation NotesUse of lavatories with engaged vanity counters are ligature resistant only when engaged side to side by knee walls or niches.

Code NotesProvide ADA compliant handicapped accessiblelavatoryassemblyconfigura-tions where required.

Division 22 | PlumbingLavatory Basins

American Standardwww.americanstandard-us.com

Rondolyn Countertop SinkHigh gloss stain resistant vitreous china sink.Specifywithoutoverflow.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

American Standardwww.americanstandard-us.com

Mezzo Countertop SinkSelfrimmingfinefireclaysemi-countertopsink.Specifywithoutoverflow.

Page 131: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 131

Division 22 | PlumbingLavatory Pipe Enclosures

General NotesCustom fabrications can be viable alternatives and, when properly detailed, may be preferable to premanufactured enclosures.

Installation NotesSpecify tamper resistant fasteners. HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

IPS Corporationwww.ipscorp.com

Truebro Lav Shield Model #2018

Cautions:w Pipe enclosure will conceal exposed

plumbing piping, but is used with wall mounted lavatory that poses looping opportunity.

w Careful scribing to underside of lavatory is required for a proper fit and sealant joint

Page 132: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 132

Division 22 | PlumbingLavatory Faucets

General NotesFaucets must be considered as part of the entire assembly.

Installation NotesSpecify projecting spouts only when the lavatory is positioned so that the lateral ligaturehangisnotpossible(i.e.re-cessedinaniche).

Behavioral Safety Productswww.besafeprod.com

Ligature Resistant Sensor Faucet #SF370Deck mounted faucet is a single temperature faucetwithoutcontrols.Itmaybespecifiedas hard-wired or with a 4-year battery.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Behavioral Safety Productswww.besafeprod.com

Ligature Resistant Metering Faucet #SF380Deck mounted faucet is a dual temperature faucet with push button con-trols.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Whitehall Manufacturingwww.whitehallmfg.com

Best Care Ligature Resistant Sen-sor Activated Faucet #WH3375-SODeck mounted faucet is a single tempera-ture faucet without controls. Designed to retrofitontoexisting4”center-setlavatorydecks.

Page 133: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 133

General NotesFaucets must be considered as part of the entire assembly.

Installation NotesSpecify projecting spouts only when the lavatory is positioned so that the lateral ligaturehangisnotpossible(i.e.re-cessedinaniche).

Division 22 | PlumbingLavatory Faucets

Whitehall Manufacturingwww.whitehallmfg.com Best Care Conical Ligature Resistant Faucets Deck mounted conical faucet may be spec-ifiedwithorwithoutdeckplate.Specifyoneof the following, with appropriate control valve assembly.3373 - Single temperature with Hemispheric air-controlled button3374 - Dual temperature with Hemispheric air-controlled buttons3373-PPZ - Single temp with Piezo button 3374-PPZ - Dual temp with Piezo buttons.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 134: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 134

Kohler Co.www.kohler.com

K-922 Laminar Faucet

Note: This product’s recess presents opportunity for wedge ligature.

General NotesFaucets must be considered as part of the entire assembly.

Installation NotesSpecify projecting spouts only when the lavatory is positioned so that the lateral ligaturehangisnotpossible(i.e.re-cessedinaniche).

Division 22 | PlumbingLavatory Faucets

Page 135: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 135

Division 22 | PlumbingLavatory Grid Strainers

Typical Grid Strainer & DrainNote: Typical grid strainers are rejected because ligature can be created by threading a ligature item through the perforations and be hung over the lavatory or vanity edge.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Oddball Industrieswww.oddballindustries.com

SP-11-GDK Grid Drain KitEffective drainage is achieved with the included air vent. Air introduction valve may not meet all local codes.

Caution: Although drainage holes are half the diameter as typical grid strainers, making threading of a thin ligature diffi-cult, a paper clip can be woven through the perforations creating a tie off oppor-tunity.

Page 136: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 136

Division 22 | PlumbingToilets, General

General Notes

Toiletslocatedininpatientareasshallbespecifiedaseither3.5gallonsperflush(gpf)blowoutor1.6gpfsiphonjet.Theyareequallyeffectiveinforcingmatterthroughthe trap and clearing the bowl.

Blowout Toilets

Blowout toilets are designed to clear the bowl with a high volume of water discharged from the bowl rim. Although these toilets are louder than siphon jet toilets, it has been noted that the higher volume of water allows matter to be forced further down the waste piping system. Wall mounted 3.5 gpf blowout toilets should not be installed back to back due to possible blow back. Please note that 3.5 gpf blowout toilets may not be permissible by code in all jurisdictions, and should be evaluated before selecting this option.

w Provides high velocity and jet action w Noisy

Siphon Jet Toilets

Siphon jet toilets are designed with an incorporated water jet in the trapway that forces matter through the trap by creating suction in the bowl to pull the contents through aswell.Siphonjetsaremanufacturedwith1.1,1.28and1.6gpfandmustbepairedwiththeappropriateflushvalve.Currentlythe1.6gpfmodelsarerecommendeddueto evaluation and acceptance of performance.

w Economical water usage w More commonly used due to quiet actions

Page 137: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 137

Division 22 | PlumbingToilets

General NotesDue to the possibility of inappropriate behavior, 3.5 gpf blowout toilets and 1.6 gpf siphon jet toilets are recommended.

Installation NotesThewallsurfacemustbeflushwiththetoilet to avoid gaps that can become ligature points.

Specify standard toilets with heavy duty carriers. Specify bariatric toilets with bariatric carriers. Coordinate with manufacturersforspecificcarriermodelspecifications.

Code Notes3.5 gpf blowout toilets may not be per-missible by code in all jurisdictions, and should be evaluated before selecting this option.

Cautions:w Both wall and floor mounted toi-

lets must be provided with com-plete closure between the toilet and wall to reduce ligature oppor-tunities.

w Toilet seats that are not integral with the bowl create ligature op-portunities.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

American Standardwww.americanstandard-us.com Afwall ToiletWall mounted, back spud, 1.6 gpf siphon jet.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Behavioral Safety Productswww.besafeprod.com

Ligature Resistant Toilet #TN690Floor mounted, back spud, 1.6 gpf siphon jet with integral seat.

Page 138: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 138

General NotesDue to the possibility of inappropriate behavior, 3.5 gpf blowout toilets and 1.6 gpf siphon jet toilets are recommended.

Installation NotesThewallsurfacemustbeflushwiththetoilet to avoid gaps that can become ligature points.

Specify standard toilets with heavy duty carriers. Specify bariatric toilets with bariatric carriers. Coordinate with manufacturersforspecificcarriermodelspecifications.

Code Notes3.5 gpf blowout toilets may not be per-missible by code in all jurisdictions, and should be evaluated before selecting this option.

Cautions:w Both wall and floor mounted toi-

lets must be provided with com-plete closure between the toilet and wall to reduce ligature oppor-tunities.

w Toilet seats that are not integral with the bowl create ligature op-portunities.

Division 22 | PlumbingToilets

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kohler Co.www.kohler.com

Kingston K-4323 ToiletWall mounted, back spud, 1.6 gpf siphon jet with detachable seat.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kohler Co.www.kohler.com

Sifton K-4460-C ToiletWall mounted, back spud, 3.5 gpf blowout with detachable seat.

Page 139: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 139

General NotesDue to the possibility of inappropriate behavior, 3.5 gpf blowout toilets and 1.6 gpf siphon jet toilets are recommended.

Installation NotesThewallsurfacemustbeflushwiththetoilet to avoid gaps that can become ligature points.

Specify standard toilets with heavy duty carriers. Specify bariatric toilets with bariatric carriers. Coordinate with manufacturersforspecificcarriermodelspecifications.

Code Notes3.5 gpf blowout toilets may not be per-missible by code in all jurisdictions, and should be evaluated before selecting this option.

Cautions:w Both wall and floor mounted toi-

lets must be provided with com-plete closure between the toilet and wall to reduce ligature oppor-tunities.

w Toilet seats that are not integral with the bowl create ligature op-portunities.

Division 22 | PlumbingToilets

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Intersanwww.intersan.us

CWC150-AST ToiletCWC156-AST ToiletSolid surface back-to-wall toilet with non-moving integral seat.HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kohler Co.www.kohler.com

Anglesey K-4396 ToiletFloor mounted, back spud, 1.6 gpf siphon jet with detachable seat.

Page 140: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 140

General NotesDue to the possibility of inappropriate behavior, 3.5 gpf blowout toilets and 1.6 gpf siphon jet toilets are recommended.

Installation NotesThewallsurfacemustbeflushwiththetoilet to avoid gaps that can become ligature points.

Specify standard toilets with heavy duty carriers. Specify bariatric toilets with bariatric carriers. Coordinate with manufacturersforspecificcarriermodelspecifications.

Code Notes3.5 gpf blowout toilets may not be per-missible by code in all jurisdictions, and should be evaluated before selecting this option.

Cautions:w Both wall and floor mounted toi-

lets must be provided with com-plete closure between the toilet and wall to reduce ligature oppor-tunities.

w Toilet seats that are not integral with the bowl create ligature op-portunities.

Division 22 | PlumbingToilets

Zurnwww.zurn.com

Z5647-BWL ToiletFloor mounted, back spud, 1.6 gpf siphon jet with hinged seat.

Note: Toilet fails and breaks under heavy use.

Whitehall Manufacturingwww.kohler.com

WH2142 ToiletFloor mounted, powder coated stainless steel toilet with ligature resistant ABS toilet seat.

Note: Interior of toilet should be powder coated white for use at NYS-OMH Facili-ties.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 141: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 141

Division 22 | PlumbingToilet Flushometers

General NotesConcealedflushvalveswithremoteinfrared sensor controls reduce looping ligature opportunities.

Access doors and infrared sensor cover plates are to be fully recessed so that facesareflushwiththeadjacentfinishmaterials. This is in order to avoid ex-posed sharp corners, potential picking at edges and possible ligature points.

WhenconflictswithADArequiredgrabbars occur, provide offset concealed flushvalves.

Installation NotesIfwallfinishisceramictile,provideanaccess door with plaster frame to allow thedoorinstallationtobeflushwiththeceramic tile surface.

Manufacturer supplied infrared cover plates may be designed for surface mounting and may require customization toprovideaflushinstallation.

Acceptableflushvalvemanufacturersindicate an ability to assemble offset installationstoavoidconflictswithgrabbars. Verify with each manufacturer the specificrequirementsforoffsetplumbingextensions, access door size and posi-tioning, and remote infrared sensor con-nections and cover plate dimensions.

NYS-OMH StandardConcealed Flush ValveAssembly

Concealed Flush Valve Assembly with Remote Infrared SensorIllustration shows and American Standard Afwall Toilet with an offset Sloan Flush Valve.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 142: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 142

Division 22 | PlumbingToilet Flushometers

General NotesConcealed flush valves with remote infrared sensor controls reduce looping ligature opportunities.

Access doors and infrared sensor cover plates are to be fully recessed so that faces are flush with the adjacent finish materials. This is in order to avoid ex-posed sharp corners, potential picking at edges and possible ligature points.

When conflicts with ADA required grab bars occur, provide offset concealed flush valves.

Installation NotesIf wall finish is ceramic tile, provide an access door with plaster frame to allow the door installation to be flush with the ceramic tile surface.

Manufacturer supplied infrared cover plates may be designed for surface mounting and may require customization to provide a flush installation.

Acceptable flush valve manufacturers indicate an ability to assemble offset installations to avoid conflicts with grab bars. Verify with each manufacturer the specific requirements for offset plumbing extensions, access door size and posi-tioning, and remote infrared sensor con-nections and cover plate dimensions.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Sloan Valve Companywww.sloanvalve.com

Royal Optima 143 ES-SFlushometerConcealed sensor operated, back spud, wall mounted flushometer.

Sloan Valve Companywww.sloanvalve.com

Regal Model 154 FlushometerConcealed push button activated, back spud, floor mounted flushometer.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Zurnwww.zurn.com

ZER6152AV Flush ValveAquaSense AV concealed sensor operated, battery powered flush valve.

Sloan Valve Companywww.sloanvalve.com

Royal Optima Sensor Activated Flushometer 152-3.5 ESS WBConcealed sensor operated, back spud, wall mounted flushometer with accessible wall box.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 143: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 143

Division 22 | PlumbingToilet Flush Valve Covers

General NotesFlush valve covers are only recommendedforretrofittingexistingfixtures.

Caution: Confirm that the flush valve covers fit the existing flush valve assemblies well enough to allow for free operation of the equipment, without providing a potential ligature point through the opening for the flushing mechanism.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Behavioral Safety Productswww.besafeprod.com

Ligature Resistant Flush Valve Cover #FV600

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Whitehall Manufacturingwww.whitehallmfg.com

WH2802 Sloped Top Ligature Resistant Flush Valve Cover16 gauge type 304 stainless steel with pow-dercoatedfinish.Canbecustomsizedandprepped. Provide powder coated tamper resistant fasteners.

Page 144: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 144

Division 22 | PlumbingToilet Flush Valve Covers

General NotesFlush valve covers are only recommendedforretrofittingexistingfixtures.

Caution: Confirm that the flush valve covers fit the existing flush valve assemblies well enough to allow for free operation of the equipment, without providing a potential ligature point through the opening for the flushing mechanism.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Norva Plasticswww.norvaplastics.com ABS High-Impact Toilet Plumbing CoverHigh-impact solid surface, customized to specifications.

Caution: Careful scribing to fixture is required for a proper fit and sealant joint

Page 145: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 145

Division 22 | PlumbingHydration Stations

General NotesA remote cooler is required for chill-ed water dispensing and a drainage system is required for waste water.

The top of the hydration station access door must be sloped.

Installation NotesDrain grilles must be securely fastened with tamper resistant fasteners. Integral cup dispensers must be securely fastenedtothefillingstationhousing.

Filtrine ManufacturingCompanywww.filtrine.com

B103-C2-HR16 gauge type 304 stainless steel with a sat-infinish.Hingedaccessdoorwithaslopedtopandkeyedlock.Fitsin4”cavitywall.

Note: Sharp corners and raw metal edg-es present opportunity for self-harm.

Whitehall Manufacturingwww.whitehallmfg.com

BF3 Pushbutton Semi-recessed Bottle FillerType304stainlesssteelwithasatinfinishand hinged access door with a sloped top.

Page 146: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 146

Division 22 | PlumbingShower Heads

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Chicago Faucetswww.chicagofaucets.com

621-CP Institutional Shower Head

Oddball Industrieswww.oddballindustries.com

SP-7 Shower Head

Moenhttp://pro.moen.com

M-Dura 8292

Oddball Industrieswww.oddballindustries.com

SP-7TF Tub Filler

Speakman Companywww.speakmancompany.com

S-2460-AF Shower Head

Behavioral Safety Productswww.besafeprod.com

SH330 Shower Head

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 147: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 147

Division 22 | PlumbingShower Heads

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Willoughby Industries, Inc.www.willoughby-ind.com CSH Ligature Resistant HeadAssembly

Whitehall Manufacturingwww.whitehall-mfg.com

CSH Conical Ligature Resistant Shower Head

Galvin Engineeringwww.galvinengineering.com #40691 Shower Rose 65Chrome plated Safe-Cell vandal resistant shower head.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 148: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 148

Division 22 | PlumbingShower Heads

Kohler Co.www.kohler.com

K-8022 Water Tile

Note: Ligature and wedging oppor-tunities are created by the operating clearance required to allow shower head directional adjustment.

Powerswww.powerscontrols.com

141 381 Institutional Shower Head

Note: Tie off ligature opportunity at end of shower head.

Deltawww.deltafaucet.com

060793A Vandal Resistant Wall Mounting Shower Head

Note: Tie off ligature opportunity at end of shower head.

Symmons Industries, Inc.www.symmons.com 4-150 Shower Head (Institutional Type)

Note: Plastic Nozzle is easily removable and product does not fasten tightly to the wall, allowing ligature.

Page 149: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 149

Division 22 | PlumbingHand Showers

General NotesHand showers must be installed in addition to a primary ligature resistant shower head.

Whenafixedshowerheadandhandshower are both used, provide either a ligature resistant diverter valve or separate ligature resistant control systemsforeachfixture.

Code NotesOnly provide hand showers where required by code. Review and under-stand ANSI A117.1-2003, Section 608.6 exception,whichallowsasecondfixedshower head in lieu of hand shower in specificsituations.

Caution:Tie-off ligature opportunity exists at hose bib. Hand showers shall be installed on wall as low as permissible by regulations to minimize risk.

Oddball Industrieswww.oddballindustries.com

SP-7WC Quick Connect Hand ShowerHand held shower with quick disconnect adapter.

Caution:Tie-off ligature opportunity exists at hose bib. Hand showers shall be installed on wall as low as permissible by regulations to minimize risk.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Intersanwww.intersan.us

40707 Quick Release Handheld ShowerHand held shower with anti-ligature quick connect wall connection.

Page 150: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 150

Division 22 | PlumbingShower Controls & Activators

Armstrong International, Inc.www.armstronginternational.com

BrainWave Water Temperature ControlStainlesssteelfaceplateistobespecifiedfor all NYS-OMH facilities. Provide tamper resistant sealant at perimeter of plate.Touchlesson/offflowcontrol.Touchless temperature adjustment

Cautions:w Control buttons are plastic and have

the potential to be damaged.w Product can be specified with a

plastic cover by facilities other thanNYS-OMH, but should be used withcaution due to the increased potentialto be damage.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

General NotesBestpracticerecommendsflowcontrolbyresident,butwithcontrolled(lim-ited)flowtime.Variousmechanismsand controllers can provide this option; some are factory set and some can be adjusted by staff. Review and select products accordingly.

Best practice also recommends tem-perature control by resident. Several of the acceptable mechanisms don’t provide this option. Review and select products accordingly.

Installation NotesWhen both shower heads and hand showers are provided, specify either a diverter valve or separate shower con-trols for both.

Behavioral Safety Productswww.besafeprod.com

Ligature Resistant Shower Valve, Handle & Escutcheon Plate #SV230

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Intersanwww.intersan.us

50140 Ligature Resistant Shower Diverter

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 151: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 151

Division 22 | PlumbingShower Controls & Activators

General NotesBestpracticerecommendsflowcontrolbyresident,butwithcontrolled(lim-ited)flowtime.Variousmechanismsand controllers can provide this option; some are factory set and some can be adjusted by staff. Review and select products accordingly.

Best practice also recommends tem-perature control by resident. Several of the acceptable mechanisms don’t provide this option. Review and select products accordingly.

Installation NotesWhen both shower heads and hand showers are provided, specify either a diverter valve or separate shower con-trols for both.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Leonard Valve Companywww.leonardvalve.com

4500 LR Series AquatrolPressure actuated mixing valve.

Caution: This product does not meet ADA requirements for graspability.

Niekamp Tool Companywww.niekampinc.com

SSK-1022E Suicide Prevention Shower Handle

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Powerswww.powerscontrols.com

Sloanwww.sloanvalve.com

447 InfraredHydroGuard ESP infrared sensor shower control.

Powerswww.powerscontrols.com

447 PiezoHydroGuard ESP pushbutton sensor shower control.

Page 152: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 152

Division 22 | PlumbingShower Controls & Activators

General NotesBestpracticerecommendsflowcontrolbyresident,butwithcontrolled(lim-ited)flowtime.Variousmechanismsand controllers can provide this option; some are factory set and some can be adjusted by staff. Review and select products accordingly.

Best practice also recommends tem-perature control by resident. Several of the acceptable mechanisms don’t provide this option. Review and select products accordingly.

Installation NotesWhen both shower heads and hand showers are provided, specify either a diverter valve or separate shower con-trols for both.

Symmons Industries, Inc.www.symmons.com 420 Series Showeroff Metering Showering System

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Whitehall Manufacturingwww.whitehall-mfg.com

SV16 Ligature Resistant Shower ControlTri-lever handle, temperature/pressure bal-ancing mixing valve.

Whitehall Manufacturingwww.whitehall-mfg.com

PBH Hemispherical PushbuttonSpecify with appropriate control valve as-sembly, one or two button options.Two buttons allows three preset tempera-tures(cold,warm&lukewarm).

Whitehall Manufacturingwww.whitehall-mfg.com

Ligature Resistant ShowerDiverterTri-lever handle diverter.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 153: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 153

Division 22 | PlumbingShower Controls & Activators

General NotesBestpracticerecommendsflowcontrolbyresident,butwithcontrolled(lim-ited)flowtime.Variousmechanismsand controllers can provide this option; some are factory set and some can be adjusted by staff. Review and select products accordingly.

Best practice also recommends tem-perature control by resident. Several of the acceptable mechanisms don’t provide this option. Review and select products accordingly.

Installation NotesWhen both shower heads and hand showers are provided, specify either a diverter valve or separate shower con-trols for both.

Oddball Industrieswww.oddballindustries.com

SP-10A Shower Mixing Valve

Cautions:w This product does not meet ADA re-

quirements for graspability.w Difficult to operate when wet.

Oddball Industrieswww.oddballindustries.com

SP-12B Diverter Valve

Caution: A tamper resistant fastener is not included and may be available for this product. A conventional fastener may be installed and filled with tamper resistant sealant if tamper resistant fas-tener is unavailable.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Willoughbywww.willoughby-ind.com

Electronic Piezo Switch

Page 154: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 154

Division 22 | PlumbingShower Controls & Activators

General NotesBestpracticerecommendsflowcontrolbyresident,butwithcontrolled(lim-ited)flowtime.Variousmechanismsand controllers can provide this option; some are factory set and some can be adjusted by staff. Review and select products accordingly.

Best practice also recommends tem-perature control by resident. Several of the acceptable mechanisms don’t provide this option. Review and select products accordingly.

Installation NotesWhen both shower heads and hand showers are provided, specify either a diverter valve or separate shower con-trols for both.

Bradley Corporationwww.bradleycorp.com

HSC95 Ligature Resistant Front-Mounted Panel Shower

Note: Looping ligature opportunity at the shower control knob.

Page 155: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 155

Division 22 | PlumbingShower Controls & Activators

General NotesBestpracticerecommendsflowcontrolbyresident,butwithcontrolled(lim-ited)flowtime.Variousmechanismsand controllers can provide this option; some are factory set and some can be adjusted by staff. Review and select products accordingly.

Best practice also recommends tem-perature control by resident. Several of the acceptable mechanisms don’t provide this option. Review and select products accordingly.

Installation NotesWhen both shower heads and hand showers are provided, specify either a diverter valve or separate shower con-trols for both.

Symmons Industries, Inc.www.symmons.com B-40904-1 Recessed ShowerActivator

Note: Recessed shower activator is loop-able and does not meet the ADA require-ments for graspability.

Page 156: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 156

Division 23 | HVAC

Page 157: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 157

Division 23 | HVAC HVAC, General

General NotesCO2 sensors are not currently available in any ligature resistant form and should only be used where accessible to patients in low or medium risk areas. CO2 sensors may be installed within ducts in high risk areas, but this will not qualify for the USGBC’s LEED credits for high occupancy mechanically ventilated spaces.

Generally, ceiling mounted diffusers and grilles are more resistant to tampering, while wall mounted elements provide more structural support for heavy and deep correction-grade assemblies.

Diffusers & GrillesThe selection of diffusers and grilles must be carefully considered in light of all relevant patient risk criteria, mechanical performance requirements, and the installed substrate. Louver and grilleopeningsizeandspacingisacriticalconsiderationforstructuralperformance,airflowandligatureresistance.Themostsecureandligatureresistantassembliesaretypicallyveryheavy, requiring careful consideration for structural support and the sequence of construction.

The selection of radiator covers must be carefully considered with respect to all relevant patient risk criteria, mechanical performance requirements, and the installed substrate. Perforated radiator covers pose a particular risk as they can be looped by a thin shoelace or similar object. Because these enclosures are typically surface mounted, careful consideration must be given to the installation conditions at these covers to prevent wedging/looping opportunities at the installed substrate. Tamper resistant sealant should be utilized to close all gaps at perimeter of enclosure.

Diffusers and grilles should be securely mounted in place using tamper resistant fasteners. Diffusers and grilles, and all accessible elements of the housing should be attached to permanentlyaffixedconcealedbackanglesthatarepartoftheassembly,ortowallorceilingframingelements.Becauseoftheinherentvariationsinthemanufacturingprocess,specifiersshouldprocuresamplesofdiffuserspriortospecifying.Variationsinfinishalongwithmanufacturingtoleranceshavecausedunsafeinstallationsinsomeproductswhereotherinstancesofthe same line have achieved safe installations.

EscapeWhere escape is a primary risk criterion, diffusers and grilles should be reduced in size to the greatest extent possible. If diffusers and grilles are required to be large enough to allow passage, they should be securely mounted in place using welded joints and/or tamper resistant fasteners. Diffusers and grilles, and all accessible elements of the housing should be attached to wall or ceiling framing elements and to the ductwork. Face plate construction should be thick enough to resist impact assaults and should not be removable, except with special tamper resistant fastener tools. Passage restrictors should be permanently welded in the sleeve housing within the assemblies.

Ligature ResistanceWhereligatureresistanceisaprimaryriskcriterion,diffusersandgrillesshouldbespecificallydesignedwithcloselyspacedweldeddeep“S”and“Z”shapedvanesthatpreventlooping,ortheyshouldbeprotectedbyheavygaugemetalfaceplateswithsmall,tightlyspaced,perforatedholes.Perforatedgrilleswithholesnolargerthan1/8”indiameteronstaggeredcentershavebeen tested and have resisted looping.

Perforateddiffusers,grillesandradiatorcoversutilizingtheindustrystandardof3/16”holeon9/32”spacingposeaparticularriskastheycanbeeasilyloopedbyathinshoelaceorsimilarobject.Becausethesedevicesareprevalentinexistinginpatientenvironments,theyareidentifiedinthisdocumentasACCEPTEDinmediumriskenvironmentsandnotedwithspecificUSE WITH CAUTION language. It should be noted that smaller holes and tighter spacing of holes, and heavier gauge metal plate are also available from several manufacturers as standard options. OMH will continue to perform additional testing on perforated grilles and diffusers and is researching alternative solutions. The risk of utilizing these devices shall be noted and evaluated by each facility.

Concealing ContrabandWhere concealing contraband is a primary risk criterion, diffusers and grilles should be reduced in size to the greatest extent possible and securely mounted in place using tamper resistant fasteners. Diffusers and grilles, and all accessible elements of the housing should be attached to wall or ceiling framing elements. Face plate construction should be thick enough to resist impact assaults and should not be removable, except with special tamper resistant fastener tools.

Page 158: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 158

Division 23 | HVACThermostats

General NotesUsecoversand/orflatplatedigitalther-mostats in high risk areas.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Automated LogicCorporationwww.automatedlogic.com

Sensor Thermostat, Plate AL-C/10K-2-SP with Logo

Kelewww.kele.com

KTP Series Stainless Steel Flush-Mount Thermistor and RTD Sensors

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 159: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 159

Division 23 | HVACDiffusers & Grilles

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

General NotesNYS-OMH standard hole size for perforatedgrillesis3/16”diametermaximum to reduce loopability.

Performance CriteriaEngineer back of systems to accommo-date free area requirements.

Anemostatwww.anemostat.com

Maximum Security Diffusers SSV22, SSV23 & SSV26SV432-FM

Behavioral Safety Productswww.besafeprod.com

Ligature Resistant Exhaust/Supply Grille #EG450Designed to replace existing grilles that are not ligature resistant. 11 gauge aluminum with1/8”roundholes.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 160: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 160

Division 23 | HVACDiffusers & Grilles

General NotesNYS-OMH standard hole size for perforatedgrillesis3/16”diametermaximum to reduce loopability.

Performance CriteriaEngineer back of systems to accommo-date free area requirements.

Anemostatwww.anemostat.com

Models ASSG & ASSG-RR Extra Heavy Duty Grilles

Caution: Perforated diffusers, grilles and radiator covers pose a particular risk as they can be easily looped by a thin shoelace or similar object.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Carnes Companywww.carnes.com

Model RSPA Series Sleeved Secu-rity Ceiling DiffuserFace and sleeve are 12 gauge hot rolled steel. Core has 12 gauge hot rolled steel louvers. Choice off 1-4-way blow patterns. 1-1/2x1-1/2x1/8”steelanglesareprovid-edasstandardinfourloosepiecesforfieldwelding. Mounting sleeve is for installation inCMUwallsonly.Specifywith1”flangeand only as ceiling mounted. Do not mount in walls. Louver blades are sharp and also create a wedging opportunity.

Page 161: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 161

General NotesNYS-OMH standard hole size for perforatedgrillesis3/16”diametermaximum to reduce loopability.

Performance CriteriaEngineer back of systems to accommo-date free area requirements.

Division 23 | HVACDiffusers & Grilles

Kees, Inc.www.kees.com

SEG-9SP3 Security GrilleFaceis3/16”steelstitchweldedtosleevewith1”faceflange.Holepatternis3/16”roundholesonstaggered9/32”centers.Twopartpolyurethanefinishinsideandout.1x1x3/16”steelanglesareprovidedasstandardintwoloosepiecesforfieldweld-ing. Available in aluminum and stainless steel.

Caution: Perforated diffusers, grilles and radiator covers pose a particular risk as they can be easily looped by a thin shoelace or similar object.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Carnes Companywww.carnes.com

Model RSPA51 Suicide Deterrent Security R&G

Tituswww.titus-hvac.com

SG-SD Maximum Security Suicide Deterrent GrilleFaceandsleeveare3/16”hotrolledsteel.Holepatternis3/16”roundholesonstag-gered9/32”centers.2x2x3/16”steelan-gles are provided as standard in four loose piecesforfieldwelding.Mountingsleeveisfor installation in CMU walls only. Specify with1”flange.

Caution: Perforated diffusers, grilles and radiator covers pose a particular risk as they can be easily looped by a thin shoelace or similar object.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 162: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 162

General NotesNYS-OMH standard hole size for perforatedgrillesis3/16”diametermaximum to reduce loopability.

Performance CriteriaEngineer back of systems to accommo-date free area requirements.

Division 23 | HVACDiffusers & Grilles

Kees, Inc.www.kees.com

SEG-9LS3VH Security DiffuserFace is 10 gauge steel stitch welded to sleevewith1”faceflange.Holepatternis3/16”roundholesonstaggered9/32”cen-ters.Twopartpolyurethanefinishinsideandout.Maximumsinglepiecesectionis48”inlength. Available in aluminum and stainless steel.

Caution: Perforated diffusers, grilles and radiator covers pose a particular risk as they can be easily looped by a thin shoelace or similar object.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 163: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 163

Division 26 | Electrical

Page 164: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 164

Division 26 | ElectricalReceptacles & Switches, General

General Notes

In new construction or substantial renovations, where arc fault and ground fault interruption are both provided, provide electrical cover plates that are either thermoplastic nylon or metal. In minor renovation projects, where providing arc fault and ground fault interruption are beyond the scope of the project, provide only metal electrical cover plates. In all cases fasten cover plates to receptacle with tamper resistant fasteners that are accepted in the NYS-OMH Patient Safety Standards. Two fasteners are recommended, though not required, for all cover plates.

Accidental or Deliberate Self-Harm

Provide tamper resistant receptacles with arc fault and ground fault interruption in all patient accessible areas of all psychiatric hospitals and wards.

Tamper Resistant Receptacles

Tamper resistant receptacles do not provide an adequate level of protection against self-harm alone. Tamper resistant electrical receptacles are designed to prevent accidental electrical self-harm to toddlers and small children. They are not designed to protect against intentional self-harm due to deliberate attack by adults. The protective measures of a tamper resistant receptacle can be easily defeated by older children and adults. Once defeated, electrical self-harm can be induced by either arc orgroundfault.Arcfaultself-harmcanbeinducedbyholdingtwoinsulatedconductors(e.g.paperclipswhileholdingtheminflexibleplasticorrubberasaninsulator)andbendingthemcloseenoughtogethertogetanelectricalcurrenttoarcbetweenthem,perhapsinanefforttocreateacigarettelighterorstartafire.Groundfaultself-harmcanbeinducedbygroundingoneself(e.g.tothefloor)whileholdingoneconductor(i.e.,paperclips)inthehotsideofthereceptacle,causingtheelectricalcurrenttoflowthrough oneself to the ground.

AFCI (Arc Fault Circuit Interrupter) & GFCI (Ground Fault Circuit Interrupter) Protection

Dual function circuit interrupters utilize both GFCI and AFCI detection technology. GFCI protection guards against ground faults, and are an effective means of preventing electricalshocks.AFCIprotectionguardsagainstdamageorfireswhichcanresultfromarcingandsparkingthatcanarisefromdeterioratedwires,poorconnectionsandbreaches in wire insulation.

Page 165: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 165

Division 26 | ElectricalReceptacles & GFCI/AFCI Circuit Breakers

General NotesSee comments on previous general notes page.

Provide dual function circuit breakers for all circuits with devices in patient acces-sible areas.

Circuit breakers are located within se-cure electrical panels beyond the patient environment. They are included in this document because they enhance the patient safety of the built environment.

Caution: Provide tamper resistant receptacles with arc fault and ground fault interruption in all patient acces-sible areas of all psychiatric hospi-tals.

Eatonwww.cooperindustries.com

TR8200 Series Hospital GradeReceptaclesTamper resistant.

Hubbellwww.hubbell-wiring.com

HBL8600 Series Extra Heavy Duty Hospital Grade ReceptaclesTamper resistant.

Legrandwww.legrand.us

PTTR62HW Series Extra Heavy DutyHospital Grade ReceptaclesTamper resistant.

Levitonwww.leviton.com

8200-SG Series Tamper Resistant Receptacles

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Eatonwww.cooperindustries.com

CHF Circuit Breaker

General Electricwww.geindustrial.com

Dual Function Circuit Breaker

Schneider Electricwww.schneider-electric.com

QO Dual Function Circuit Breakers

Siemenswww.usa.siemens.com

Dual Function Circuit Breaker

Page 166: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 166

Division 26 | ElectricalWall Plates

General NotesThermoplastic nylon wall plates are rec-ommended.Theyaremoreflexiblethanthermoset(urea)productsandhaveashinier,glossyfinish.Moldedthermo-plastic nylon wall plates also perform for maximum resistance to impact, abra-sion, fading and discoloration. Nylon is resistant to stresses associated with high abuse applications.

Polycarbonate is a thermoset plastic, so doesn’t perform as well in this applica-tion.

Installation NotesNylon is pliable so it should be installed in a bed of tamper proof sealant.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Hubbellwww.hubbell-wiring.com

Nylon Wall Plates

Legrandwww.legrand.us

Unbreakable Nylon Wall Plates

Levitonwww.leviton.com

Unbreakable Nylon Wall Plates

Hubbellwww.hubbell-wiring.com

Metal Wall Plates

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 167: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 167

General NotesThermoplastic nylon wall plates are rec-ommended.Theyaremoreflexiblethanthermoset(urea)productsandhaveashinier,glossyfinish.Moldedthermo-plastic nylon wall plates also perform for maximum resistance to impact, abra-sion, fading and discoloration. Nylon is resistant to stresses associated with high abuse applications.

Polycarbonate is a thermoset plastic, so doesn’t perform as well in this applica-tion.

Installation NotesNylon is pliable so it should be installed in a bed of tamper proof sealant.

Division 26 | ElectricalWall Plates

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kenall Manufacturingwww.kenall.com

Mighty Mac WSP/WPP Series Wall Plates

Caution: Intended for use in OMH facil-ities only when other alternatives are considered unsuitable due to excessive tampering by patients.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Morlitewww.morlitesystems.com

CSWP & SPW Series High Abuse/Security Cast Wall Plates

Caution: Intended for use in OMH facil-ities only when other alternatives are considered unsuitable due to excessive tampering by patients.

Page 168: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 168

Division 26 | ElectricalSensors

General NotesInfrared detection is not suitable for bathrooms with partitions and rooms with cubicles. Ultrasonic detection is more suitable for these locations.

Ceiling mounted sensors are preferable to wall mounted sensors.

Watt Stopperwww.wattstopper.com

CI-200 Series Passive Infrared Ceiling Sensor

Note: Plastic dome covering sensor is not tamper resistant and a wedge point can be established. Mounting escutcheon is not me-chanically fastened and a wedge point can be established behind it if it is not installed flushtosubstrate.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Concealite Architectural Productswww.concealite.com

SpaceStation Series 2000 Occu-pancy Lighting Control SystemSpaceStation operates at 120 or 277 VAC and utilizes super high frequency technolo-gy to control lighting based on occupancy. It sends out electromagnetic waves that bounce off nearby surfaces, and uses the Doppler principle to analyze changes in the return waves to detect motion in the area.

Detects movement within a room when installed above suspended ceilings, gypsum board and decorative wood ceilings. Occu-pancy sensor is completely concealed from view, and installation requires no visible ceiling penetration.

Page 169: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 169

Division 26 | ElectricalLight Fixtures, General

Performance Criteria

Provide lighting that meets the following criteria:

w Lighting;Highefficiency,maintainingvisualperformancewhereapplicable.Providedimmableballastsasrequired.w Lamps;NYS-OMHstandardisF32T8lampsduetotheirhighefficiency,performance,reliability,andcosteffectiveness.w Diffuser|Lens;Provide1/8”thickminimumpolycarbonateprismaticortranslucentlens.Lensframerequiresenoughedgebiteinordertoretainthelensduring

maximumdeflection.Fastenlensorlensframewithtwotamperresistantfastenersminimum.Donotpassfastenersthroughpolycarbonatelensmaterial.w Housing; To be unbreakable.w Exposedfasteners;Tobetamperresistantwithfinishtomatchhousing.w Switching;AllSeclusionRoomlighting,bothforchildrenandadults,istobedimmable.Dimmableballastscanbeinstalledinretrofitsituations.w Maintenance;Specifyfixtureswithstandardreplacementparts,lampsandballasts.Considertheminimumnumberofsecurityfastenersrequiredfor

patient safety without creating unnecessary labor for relamping.w Approvals;UnderwritersLaboratories(UL)andothersasapplicable.

Installation Notes

Installlightfixturesflushwithsubstrate.Itiscriticaltoensuretherearenogapsforgraspabilityorligaturetie-off.Anyremaininggapsshallbefilledwithtamperresistantsealant.

Coordinateshowerlightfixtureinstallationwithwallorceilingfinish.Escutcheonplatesdonotsitflatonceramicwalltilesoracousticceilingtiles.Therecommendedinstallation method for ceramic wall tile is to install square or rectangular escutcheon plates directly to the substrate surface, then to trim ceramic wall tile up to the escutcheon plates.

Additional Notes

Verifyphotometricsoflightfixtureswithpolycarbonatelensesduringtheprojectdesign.

TheOfficeofMentalHealthLightingStandardsHandbookisintendedforusebyPlantSupervisorsatfacilitiesasareferenceguidewhenreplacinglightfixtures.TheHandbookdetailswhichenergysavingoptionsmaybebestforeachapplication.ItisimportanttoalsoreferencetheOfficeofMentalHealthPatientSafetyStandardGuidelineswhenreplacingorspecifyinglightfixturesinpatientareas.OMHreinforcestheimportanceofpatientsafetybeforeenergyefficiencyintheirfacilitiesinallpa-tient areas.

Page 170: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 170

General NotesSee comments on previous general notes page.

Division 26 | ElectricalLight Fixtures, Lenses

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Behavioral Safety Productswww.besafeprod.com

Impact Resistant PrismaticPolycarbonate Light Lenses #PL640Lenses are to be installed in an existing fixtureframe.Iftheexistingframewillnotadequately secure the lens, it is recommend-ed to install the tamper resistant fasteners through the frame and lens.

Page 171: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 171

Division 26 | ElectricalLight Fixtures, Interior, General, Surface Mounted

General NotesSee comments on previous general notes page.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Eatonwww.cooperindustries.com

Fail-Safe FUSL LED Sloped Sided Confinement

Lighting: Up & down light configurations.Lamps: LEDDiffuser|Lens: Two lens. Prismatic poly-carbonate on fixture side. Clear polycarbon-ate on environmental side. Secured with thru-studs.Housing: Clamshell design combines die formed 14 gauge cold rolled steel body with continuous welded and ground ends to form a one piece, doorless housing. Continuous concealed piano hinge with welded pin end to prevent removal.Switching; On/off integral switches.Approvals: ETL damp label.Options: Fluorescent night light,tamper resistant fasteners.Finish: Standard white high reflectance poly-ester powder coat finish.

Kenall Manufacturingwww.kenall.com

Enviroseal ES5 Linear Wraparound

Lighting: Linear fluorescent.Lamps: T5 & T8. 4’ fixtures also available with T5HO & LED.Diffuser|Lens: 0.125” pearlescent or clear polycarbonate, smooth exterior, linear pris-matic interior.Housing: One piece, seam welded 20 gauge cold rolled steel.Approvals: UL, cUL & optional IP65 certifi-cation.Options: LED night light with night level con-trol. IP65 option provided with linear silicone gasket to seal lens frame to housing. Must specify tamper resistant fasteners to secure lens in housing.Finish: Brushed stainless steel or white powder coat.

Page 172: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 172

Division 26 | ElectricalLight Fixtures, Interior, General, Surface Mounted

General NotesSee comments on previous general notes page.

Kenall Manufacturingwww.kenall.com

WCBU Mighty Mac

Lighting:Linearfluorescent,CFL&LED.Up&downlightconfigurations.Lamps: Two aperture.Diffuser|Lens: Two lens. Prismatic poly-carbonateonfixtureside.Clearpolycarbon-ate on environmental side. Secured with tamper resistant fasteners. Need to specify with polycarbonate.Housing: 14 gauge cold rolled steel or stain-less steel.Approvals: UL & cUL.Options: LED night light with night level control.

Caution: Fixture shall not be installed in a vertical orientation.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kenall Manufacturingwww.kenall.com

MedMaster Behavioral Health MMAC14, MMAC22, MMAC24

Lighting:Linearfluorescent&LED.Lamps: T5, T5HO & T8.Diffuser|Lens:Specify1/8”-3/8”polycarbon-ate with tamper resistant fasteners.Housing: 14, 16 & 18 gauge cold rolled steel or stainless steel, spot welded. Door is one piece die formed with corners continuously seam welded and smooth, no post grinding, and tamper resistant fasteners.Approvals: UL, cUL & IP65.Options: LED night light with night level control.

MMAC22 - 2 x 2’

Page 173: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 173

Division 26 | ElectricalLight Fixtures, Interior, General, Surface Mounted

General NotesSee comments on previous general notes page.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Luminaire LightingCorporationwww.luminairelighting.com

VPF-4 Series, VPF-8 Series,VPF-12 Series

Lighting: Fluorescent & LED.Diffuser|Lens: UV stabilized opal polycar-bonate with infrared prisms.Housing: Marine grade heat treated extrud-edaluminum,chemicallyprimedandfin-ished with polyester powder coat.Approvals: UL & cUL, damp label, wet op-tional.Options: Photoelectric switch, tamper resis-tant fasteners, and battery backup system.Finish: Available in black, white, gray, bronze or custom color.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Luminaire LightingCorporationwww.luminairelighting.com

WM11, WM12, WM13

Lighting: LED.Diffuser|Lens: Two lens. Prismatic poly-carbonate inner lens. Clear polycarbonate outer lens. Secured to housing with vertically adjustable Z-brackets with internally weld-ed stainless steels studs and heavy duty hardware.Housing: One piece die formed 14 gauge cold rolled steel with continuously welded smooth corners and seams, and fully re-cessed tamper resistant security screws with cage nuts.Approvals: UL & cUL.Options; Fuse and fuse holder, amber LED nightlightwithfieldadjustablelevels,fulllength hinge, downlight only, uplight only, TORX®headbitforConfinementSeries.Finish: Available in black, white, bronze, gray, or silver.

Page 174: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 174

Division 26 | ElectricalLight Fixtures, Interior, General, Surface Mounted

General NotesSee comments on previous general notes page.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Luminaire LightingCorporationwww.luminairelighting.com

CM12, CM13, CM14

Lighting: LEDDiffuser | Lens: Two lens. Prismatic poly-carbonate inner lens. Clear polycarbonate outer lens. Secured to housing with vertically adjustable Z-brackets with internally weld-ed stainless steels studs and heavy duty hardware.Housing: One piece die formed 14 gauge cold rolled steel with continuously welded smooth corners and seams, and fully re-cessed tamper resistant security screws with cage nuts. Approvals: UL, cULOptions: Fuse and fuse holder, amber LED nightlightwithfieldadjustablelevels,fulllengthhinge,TORX®headbitforConfine-ment Series.Finish: Available in black, white, bronze, gray, or silver.

Kenall Manufacturingwww.kenall.com

MightyMac SSA, SSB, SSC, SSD Series

Lighting: CFL or LED.Diffuser|Lens: Prismatic polycarbonate inner lens and clear polycarbonate outer lens.Housing: One piece die formed prime grade material 12, 14, or 16 gauge steel continu-ously seam welded. Clamshell housing with completely concealed internal dropslot piano hinge.Approvals: UL, cUL listed for damp loca-tions.Options: Wet location listing, night light, dimming.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 175: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 175

Division 26 | ElectricalLight Fixtures, Interior, General, Surface Mounted

General NotesSee comments on previous general notes page.

Kenall Manufacturingwww.kenall.com

Millenium Stretch MLHA8, MLHA12

Lighting: CFL or LED.Diffuser|Lens: UV stabilized high impact extruded clear or pearlescent polycarbonate. Smooth exterior, linear prismatic interior with0.156”nominalthickness.Lenssecurelypositioned in body channels and end caps, and locked in place with tamper resistant fasteners.Housing: Marine grade aluminum extruded body with die cast end caps with polyester powdercoatfinish.Approvals: UL, cUL, & IP64.Options: Continuous row joiner band, tamper resistant fasteners, and dimming.Select rounded end caps.

Note:Thelenshasa1/8”graspableedgeand is pin connected in two points which are exposed. The edge could allow a person to hangoffthefixture,butitwillnotsupporttheweight.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Luminaire LightingCorporationwww.luminairelighting.com

Anyx 13, Anyx 17 & Aria Series

Lighting: CFL & LED. Diffuser|Lens: One piece injection molded UVstabilizedprismaticpolycarbonate,1/8”minimum thickness, clear or opal. Secured to base plate by trim and silicone O-rings. Reflectorisdieformedheavygaugespecu-lar aluminum.Housing: One piece injection molded UV stabilized polycarbonate, mechanically inter-locked to lens. Approvals: UL, cUL, wet label.Finish: Available in black, white, gray, bronze or custom color.

ARV13

Page 176: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 176

Division 26 | ElectricalLight Fixtures, Interior, General, Surface Mounted

General NotesSee comments on previous general notes page.

Kenall Manufacturingwww.kenall.com

Ranger Striplight

Lighting: Fluorescent.Lamps: T8.Diffuser|Lens: One piece extruded clear pris-matic impact blend acrylic. Two white nylon fasteners secure lens in baseplate channel.Housing: One piece 20 gauge cold rolled steel baseplate and end caps. Baseplate provided with six point mounting holes.Approvals: UL, cUL, wet label.

Note: Wedging ligature opportunity at lens and housing.

Legion Lighting Co., Inc.www.legionlighting.com

Vandalex Series 19

Lighting: Fluorescent.Lamps: T8.Diffuser|Lens: Polycarbonate.Housing: Die formed 16 gauge cold rolled steel.Approvals: UL, cUL, wet label.

Note: Wedging ligature opportunity at lens and housing.

Page 177: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 177

General NotesSee comments on previous general notes page.

Division 26 | ElectricalLight Fixtures, Interior, General, Surface Mounted

Luminaire LightingCorporationwww.luminairelighting.com

Swoop 610 Series

Note: Presents opportunity for downward ligature in both vertical and horizontal orientation.

Luminaire LightingCorporationwww.luminairelighting.com

Supermax SM-12

Note: Shoelace can be wedged between housing and lens, creating downward ligature opportunity.

Page 178: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 178

General NotesSee comments on previous general notes page.

Division 26 | ElectricalLight Fixtures, Interior, General, Recessed

Eatonwww.cooperindustries.com

Fail-Safe ENW/C/V HS Encounter Series

Lighting: LEDDiffuser | Lens: Two lens. Optical grade acrylic inner lens. Clear polycarbonate pro-tective outer lens attached with continuously applied adhesive around perimeter. Lens gasket with viscoelastic acrylic polymer and double sided adhesive. Electronic driver, single circuit, 0-10V 10% dimmable. Housing: High Security. Vandal resistant with closed cell polyvinyl chloride gasket on back-side. Approvals: UL, cULus, CSA, wet label, RoHOS compliant, IESNA LM-79 compliant, LM-80 standard compliance, IP66 rated, Class 100 ISO5-8, NSF2 listedOptions: Emergency driver, CCEA compli-ant, gasket around perimeter of bottom edge of lens to seal fixture to T-Grid, gasket on back side of housing, 1% dimmable.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Eatonwww.cooperindustries.com

Fail-Safe FMR HS LED Recessed Flange Confinement

Lighting: LEDDiffuser | Lens: Two lens. Prismatic polycar-bonate inner lens. Clear polycarbonate outer lens. Lens secured by thru-studs and verti-cally adjustable internal CRS hold-downs. Housing: High Security. 16 gauge die-formed cold rolled steel body with welded corners. Contains 2 stainless steel aircraft cables to attach door to housing. Concealed piano hinge. Stainless steel tamper resis-tant T20 Torx screws with center pin reject standard. Allen-head screws with center pin reject optional.Approvals: Damp label, wet optional.Options: Emergency battery pack, linear LED night light dimmable, fuse and hold-er, continuous piano hinge, wet location, anti-microbial matte white finish; swing-out brackets, yoke mounting frame; natural brushed finish; polyester powder coat finish.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 179: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 179

General NotesSee comments on previous general notes page.

Division 26 | ElectricalLight Fixtures, Interior, General, Recessed

Kenall Manufacturingwww.kenall.com

Mighty Mac RCA, RCB, RCC, RCD Series

Lighting: T5, T8, T5H0Lamps: 26W quad CF. Dimmable.Diffuser|Lens: Two lens. Prismatic poly-carbonateonfixtureside.Clearpolycar-bonate on environmental side. Specify with tamper resistant fasteners. Need to specify with polycarbonate.Housing: 14 & 16 gauge stainless steel, or 12, 14, 16 & 18 gauge cold rolled steel.Approvals: UL, cUL, wet label.Options: LED night light with night level control.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kenall Manufacturingwww.kenall.com

MedMaster Behavioral Health MMAC 14, MMAC22 & MMAC24

Lighting:Linearfluorescent&LED.Lamps: T5, T5HO & T8.Diffuser|Lens:Specify1/8”-3/8”polycarbon-ate with tamper resistant fasteners.Housing: 14, 16 & 18 gauge cold rolled steel or stainless steel, spot welded. Door is one piece die formed with corners continuously seam welded and smooth, no post grinding, and tamper resistant fasteners.Approvals: UL, cUL, wet label.Options: LED night light with night level control.

MMAC22 - 2 x 2’

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 180: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 180

Division 26 | ElectricalLight Fixtures, Interior, General, Recessed

General NotesSee comments on previous general notes page.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

New Star Lightingwww.newstarlighting.com

Confinement Series37M and 57M Models

Lighting: Fluorescent & LED.Diffuser|Lens: Clear polycarbonate outer lens & prismatic polycarbonate inner lens. Lenssecuredby“Z”retainerswithweldstudsspaced6”apartformaximumstrength.Provide tamper resistant fasteners in white powdercoatedfinish.Housing: Die formed, seam welded and ground smooth. Approvals: UL.Options: LED night light, & cUL wet label.Finish: Available in white.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

New Star Lightingwww.newstarlighting.com

StarTile 11-14MX Surface

Lighting: LED.Diffuser|Lens: Polycarbonate lens with graphics. Housing: Extruded aluminum frame encased in a 14 gauge cold rolled steel frame with bevelededgestodeflecttheforceofimpact.Approvals: Wet listed, ETL listed.Options: Custom Graphics.Finish: Polyester powdercoat.

Caution: Installation of flat substrate will be important with sealant around entire perimeter. Wall mount is rejected. For ceiling mount only.

Page 181: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 181

Division 26 | ElectricalLight Fixtures, Interior, General, Recessed

General NotesSee comments on previous general notes page.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Selux Corporationwww.selux.com

M125 Series

Lighting: LED. Lamps: Single or double, standard driver. Dali dimming.Diffuser|Lens: Sateen polycarbonate.Housing: Continuous extruded aluminum, up to 4’ long. Die cast aluminum end caps made from low copper marine grade alumi-num alloy. Install with suspension brackets, rotating cross bars, or perimeter mount. Specify with tamper resistant fasteners.Approvals: IP65 & IK10.Finish: Available in white, black, silver and custom colors.

Page 182: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 182

Division 26 | ElectricalLight Fixtures, Interior, General, Recessed

General NotesSee comments on previous general notes page.

Philips Day-Britewww.daybritelighting.com

Attune Series

Lighting: Fluorescent.Lamps: T5, T5HO & T8.Diffuser|Lens: Acrylic.Housing: One piece die formed embossed steel.Approvals: UL, cUL, wet label.Options: Dimmable.

Note: A polycarbonate lens is no longer available as an option.

Page 183: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 183

Pixi Lightingwww.pixilighting.com

Flatlight Luminaire

Lighting: LED.Diffuser|Lens: Acrylic.Housing:notconfirmed.Approvals: Type IC rated, RoHS compliant.Options: none.

Notes: w Edges of housing allow for ligature. w Gasketing material can be picked and

removed.

Division 26 | ElectricalLight Fixtures, Interior, General, Recessed

General NotesSee comments on previous general notes page.

Legion Lighting Co., Inc.www.legionlighting.com

Securlume Series 672

Lighting: Fluorescent.Lamps: T5, T5HO & T8.Diffuser|Lens:(RFL)Prismaticpolycarbon-ate.Housing: 20 gauge cold rolled steel with captive tamper resistant fasteners.Approvals: UL, cUL, damp and wet label, & IP55.Options: Dimming T12 & slimline lamps available. Consult with manufacturer.

Note: Fixture provides multiple ligature points and is not tamper resistant.

Page 184: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 184

Division 26 | ElectricalLight Fixtures, Interior, General, Recessed

General NotesSee comments on previous general notes page.

Eatonwww.cooperindustries.com

Failsafe SGI LED

Lighting: LEDDiffuser|Lens: 0.375” thick polycarbonate. Housing: Die-formed aluminum. Door can be steel or aluminum. Fully gasketed.Approvals: UL and CUL listed for damp locations.Options: Wet location listing under covered ceiling optional. Dimmable.

Note: Light fixture housing construction at flange corners can be manipulated overtime. Gasket at lens and door comes out after repeated wedging and tamper-ing.

Page 185: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 185

Division 26 | ElectricalLight Fixtures, Interior, Task Lighting

General NotesSee comments on previous general notes page.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kenall Manufacturingwww.kenall.com

Millenium HADL Series Downlight LED

Lighting: 6” aperture LED.Diffuser|Lens: Symmetric diffusion inner lens with .125” clear polycarbonate outer lens. Lens sealed to trim with continuous lens retention system.Housing: .050” seam welded aluminumApprovals: UL, IP65.Options: Dimming, range of color tempera-tures available.Finish: Trim available in white, black, brushed aluminum or custom colors.

Eatonwww.cooperindustries.com

Fail-Safe FFLD6A 6” Vandal Resis-tant LED Downlight

Lighting: LED.Diffuser|Lens: Two stage reflector system with inner and outer clear or prismatic flush polycarbonate lenses.Housing: Die cast aluminum. 1-1/2” deep collar accommodates ceiling materials up to 2”. Extruded aluminum heat sink conducts heat away from the LED module. Approvals: IP66Options: Anti-microbial paint, dimming, nata-torium finish.Finish: Powder coated matte white.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 186: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 186

Division 26 | ElectricalLight Fixtures, Interior, Task Lighting

General NotesSee comments on previous general notes page.

V2 Lighting Groupwww.v2LightingGroup.com

LED Nano Recessed Light

Lighting: LED, 3 watt.Diffuser|Lens: Polycarbonate.Housing; Aluminum body with stainless steel components.Approvals: ETL Listed, conforms to UL Stan-dards 2108, 8750; Non-IC Rated.Options: Listed for wet locations.Finish:Anodizedbaseandpowercoatfinish.

Caution: Only basic mode is acceptable without tilt options. Tilt options are easily unscrewed from below installation sub-strate/ceiling.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kurtzonwww.kurtzon.com

Recessed Sealed 6” Aperture LED Downlight, LED VLPBD

Lighting: LEDDiffuser|Lens:Clearnon-prismatic0.125”virgin polycarbonate silicone sealed to IP-65. Whiteellipticalgroovedbafflecontrolsstraylight. Housing: Stainless steel body and spun alu-minumhousingandplasterframe.0.80”alu-minum or 16 gauge stainless steel formed door frame with continuous lens hold down and Torx tamper-proof fasteners. Approvals: IP65 rated for dust and water ingress, wet label, Chicago Plenum rated.Options: Remote mount battery pack, radio frequencyinterferencefilter,allenheadtam-per resistant screws.Finish: Antimicrobial white polyester powder coat on doorframe. Satin polished on stain-less steel trims.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 187: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 187

Division 26 | ElectricalLight Fixtures, Interior, Task Lighting

General NotesSee comments on previous general notes page.

Kenall Manufacturingwww.kenall.com

Stratalume UC Series, UCSL

Lighting: CFLDiffuser|Lens: Shock resistant borosilicate glassisstandard.Specify0.125”prismaticpolycarbonate lens held in place by two stainless steel tamper resistant fasteners.Housing:1.1”profile,20gaugecoldrolledsteel. White TGIC polyester powder coat finish.Approvals: UL, cUL, wet label.Options: Integral OC Sensor

Note: Ballast must be modified to fit.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

The Kirlin Companywww.kirlinlighting.com

VRR Vandal Resistant Downlight

Lighting: CFL, LEDDiffuser|Lens:Prismatic3/16”highstrengthacrylicabove1/4”clearpolycarbonate.SpecularAlzakaluminumreflector.Con-tinuousringsecureslenstotrimwithflushcenter pin, tamper resistant fasteners and captive nuts. Vandal resistant smooth seamlesstaperedaluminumself-flangedflaretrim.Housing: Aluminum & acrylic enameled. Approvals: UL, cUL, wet label.Options:8or10”Finish: Trim available in white, black or cus-tom colors.

Page 188: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 188

Division 26 | ElectricalLight Fixtures, Interior, Task Lighting

General NotesSee comments on previous general notes page.

Designplan Lighting, Inc.www.designplan.com

Resistant Downlights RDD, RDO, RDP, & RDW Vandal

Lighting: LED.Diffuser|Lens:3/16”polycarbonateupperlens with cone. Housing: 18 gauge zinc coated steel body and low copper alloy die cast trim ring.Approvals: ETL listed IP65 wet label.Options: Concrete pour housing available.Finish: Cone available in white, black and specularfinishes.Trimringavailableinwhiteand black. Provide tamper resistant fasten-ers.

Note: Installation may allow gasketing to be compromised.

Designplan Lighting, Inc.www.designplan.com

RDL/RHL Downlight

Lighting: RDL- CFL; RHL- H1DDiffuser|Lens:3/16”UVstabilizedpoly-carbonate lens. Trim ring is mechanically attached to body. Specify polycarbonate diffuser and tamper resistant fasteners.Housing: 18 gauge zinc coated steel body with polyester powder coat.Approvals: ETL listed IP55 wet label.Options: Concrete pour housing available.Finish: Available in 18 colors and custom colors.

Note: Installation may allow gasketing to be compromised.

Page 189: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 189

Kenall Manufacturingwww.kenall.com

Millenium Regressed Downlight HRDL Series - Non IC Rated - LED and CFL

Lighting: LED or CFL.Diffuser|Lens:Aluminumspunreflector,regresseddiffuser.125”polycarbonatelenswith LED, tempered glass with CFL.Housing: 18 gauge die formed corrosion resistant steel with adjustable collar. Heat sink with LED.Approvals: UL, cUL, IP64.Options: Emergency battery backup. Dim-ming with LED.Finish:Aluminumwithwhiteacrylicfinish.

Note: Tempered glass lens is easily cracked.

Division 26 | ElectricalLight Fixtures, Interior, Task Lighting

General NotesSee comments on previous general notes page.

Kenall Manufacturingwww.kenall.com

Millenium HADL Series DownlightCFL

Lighting: CFL.Diffuser|Lens:Maximumthickness0.625”polycarbonate with sealed trim.Housing:.050”aluminumwithwhiteTGICpolyesterpowdercoatfinish.Approvals: UL, cUL, wet label.Options:6”&8”aperture.Finish: Clear specular, clear semi-specular, champagne gold.

Note: A wedge ligature can be created with a thin shoelace at the lens and trim ring.

Page 190: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 190

Division 26 | ElectricalLight Fixtures, Interior, Task Lighting

General NotesSee comments on previous general notes page.

Eatonwww.cooperindustries.com

Fail-Safe FLD6A LED Downlight

Lighting: LED.Diffuser|Lens: Clear or opal polycarbonate. Housing: Die-cast aluminum.Approvals: CSA, Non-IC rated.Options: Dimming, range of color tempera-tures available.Finish: Face plates available in specular clear, gloss white or matte white.

Note: A wedge ligature can be created with a thin shoelace at the lens and trim ring.

Page 191: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 191

Division 26 | ElectricalLight Fixtures, Interior, Night Lighting

General NotesSee comments on previous general notes page.

Amber colored LEDs are recommended at patient bedrooms.

Night lights are recommended to be recessed at approximately 12” -18” above finish floor for proper use and to minimize potential ligature risk.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Eatonwww.cooperindustries.com

Fail-Safe MSN & MCL Night Lights

Lighting: LED.Lamps: 120/277V. MCL & MSN provide 30 lumens. Diffuser|Lens: Specify tamper resistant fasteners.Housing: Fits into a standard junction box, die cast aluminum face plates.Approvals: ETL & UL.Options: LED available in clear, red, blue, & amber.Finish: Face plates available in white, black or brushed nickel.

Caution: MCL and MSN have an acrylic lens.

MSN MCL

The Kirlin Companywww.kirlinlighting.com

MNS-05924 Square StepLight LED

Lighting: LEDLamps: 120-277V standard. 3500 K stan-dard. 13V DC max. and 4 watt fixed output. Electronically stabilized.Diffuser|Lens: 2” diameter translucent white 1/8” polycarbonate lens, gasketed. Housing: 4” x 2-1/4” standard octagon galvanized steel outlet box with gasketed rustproof aluminum trim faceplate. Specify with tamper resistant screws.Approvals: UL, C-UL, damp or dry, Type IC approved for direct contact with insulationOptions: other voltage input, remote emer-gency inverter for 100% of rated lumens, LED blue/ green/ orange/ amber/ yellow/ custom filtersFinish: White finish standard. Optional col-ors.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 192: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 192

Division 26 | ElectricalLight Fixtures, Interior, Night Lighting

General NotesSee comments on previous general notes page.

Amber colored LEDs are recommended at patient bedrooms.

Night lights are recommended to be recessedatapproximately12”-18”abovefinishfloorforproperuseandtominimize potential ligature risk.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kenall Manufacturingwww.kenall.com

MedMaster SoftStep Steplight

Lighting: LED. Dimmable.Diffuser|Lens: Polycarbonate, clear or pearlescent.Housing: 18 gauge cold rolled steel or stain-less steel.Approvals: UL & cUL.Options: LED available in white, red, blue, & amber.

Kenall Manufacturingwww.kenall.com

MedMaster SoftStep Contour Steplight, MCSL

Lighting: LED.Diffuser|Lens: Pearlescent polycarbonate.Housing;Diecastaluminum.Reflectorisdie cast aluminum with integral heat sink.Approvals: UL, cUL, & NSF.Options: LED available in white, red, blue, & amber. IP64 label.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 193: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 193

Division 26 | ElectricalLight Fixtures, Interior, Night Lighting

General NotesSee comments on previous general notes page.

Amber colored LEDs are recommended at patient bedrooms.

Night lights are recommended to be recessedatapproximately12”-18”abovefinishfloorforproperuseandtominimize potential ligature risk.

Philips Alkcowww.lightingproducts.philips.com

WayGlo WG2H

Lighting: LED.Diffuser|Lens: Acrylic.Housing: 18 gauge galvanized steel.Approvals: ETL & CETL, wet label.Options: LED available in white & amber.Finish: Face plate is available in white, black or aluminum.

Note: Acrylic lens can be easily broken into small shards.

Page 194: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 194

Barron Lighting Groupwww.barronltg.com

Exitronix Emergency LightingV900 Series Edge-Lit Exit, V902R

Lighting: LED.Lamps: 120/277V, test button battery back-up.Diffuser|Lens: Clear acrylic with leveled let-tering for maximum light output. Exit letters are6”highwith3/4”stroke.Housing: Extruded aluminum supplied with galvanized steel adjustable bar hanger assembly.Approvals: UL, cUL, wet label.Options: LED available in red or green. LED night light with night level control. IP65 label.

Division 26 | ElectricalLight Fixtures, Exit Signage

General NotesSee comments on previous general notes page.

Must be positively and mechanically at-tached,notfrictionfit.SpecifyULlisted924(NEC,NFPA70)andmountflushtowalls or ceilings. Specify fully recessed housing.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kenall Manufacturingwww.kenall.com

Millenium Metrex METSR SeriesExit Light (Recessed)

Lighting: LED.Diffuser|Lens:.188”thickclearpoly-carbonate.Housing: 20 gauge CRS one piece welded construction.Approvals: UL, cUL, wet location, NFPA.Options: LED available in red or green.Housing available in painted white, black or brushed stainless steel.

Page 195: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 195

Division 26 | ElectricalLight Fixtures, Exit Signage

General NotesSee comments on previous general notes page.

Must be positively and mechanically at-tached,notfrictionfit.SpecifyULlisted924(NEC,NFPA70)andmountflushtowalls or ceilings. Specify fully recessed housing.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Philips Chloridewww.lightingproducts.philips.com

60 Series Max All Purpose Exit

Lighting: LED.Diffuser|Lens: Injection molded polycarbon-ate.Housing: Premium die cast aluminum with recessed mounting.Approvals: UL 924, UL, wet label, NFPA, IBC, BOCA, & OSHA illumination standards.Options; LED available in red or green.

Page 196: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 196

Division 26 | ElectricalLight Fixtures, Exit Signage

General NotesSee comments on previous general notes page.

Must be positively and mechanically at-tached,notfrictionfit.SpecifyULlisted924(NEC,NFPA70)andmountflushtowalls or ceilings. Specify fully recessed housing.

Kenall Manufacturingwww.kenall.com

Millenium Metrex METSW SeriesExit Light (Wall Mount)

Lighting: LED.Diffuser|Lens: UV stabilized, high impact, .120”thickinjectionmoldedclearpolycar-bonate.Housing: High impact injection molded poly-carbonate.Approvals: UL, cUL, wet listed, NFPA.Options: LED available in red or green. Black or white housing.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Kenall Manufacturingwww.kenall.com

Millenium Metrex METDU SeriesExit Light (Wall and Ceiling Mount)

Lighting: LED.Diffuser|Lens: Injection molded clear poly-carbonate captive with center pin fasteners.Housing: High impact injection molded poly-carbonate.Approvals: UL, cUL, wet listed, NFPA.Options: LED available in red or green.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 197: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 197

Division 26 | ElectricalLight Fixtures, Exit Signage

General NotesSee comments on previous general notes page.

Must be positively and mechanically at-tached,notfrictionfit.SpecifyULlisted924(NEC,NFPA70)andmountflushtowalls or ceilings. Specify fully recessed housing.

Kenall Manufacturingwww.kenall.com

Mighty Mac MMEX SeriesExit Light (Wall and Ceiling Mount)

Lighting: LED.Diffuser|Lens:.188”thickclearpolycarbon-ate.Housing: One piece die formed 14 gauge steel continuously seam welded.Approvals: UL, cUL, wet listed, NFPA.Options: Single or double faced, LED avail-able in red or green.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Page 198: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 198

General NotesSee comments on previous general notes page.

Must be positively and mechanically at-tached,notfrictionfit.SpecifyULlisted924(NEC,NFPA70)andmountflushtowalls or ceilings. Specify fully recessed housing.

Barron Lighting Groupwww.barronltg.com

S900 Series Edge-Lit Exit

Lighting: LED.Diffuser|Lens: Clear acrylic with leveled let-tering for maximum light output. Exit letters are6”highwith3/4”stroke.Housing: Extruded aluminum supplied with galvanized steel adjustable bar hanger assembly.Approvals: ETL.Options:SelfTest/SelfDiagnostics(G2)available. LED available in red or green.

Note: Pivoting feature creates looping ligature opportunity.

Philips Chloridewww.lightingproducts.philips.com

Caliber Series Edge Lit Exit

Lighting: LED.Diffuser|Lens: High impact acrylic, silk screened.Housing: Premium die cast aluminum with recessed mounting.Approvals: UL 924, UL, wet label, NFPA, IBC, BOCA, & OSHA illumination standards.Options: LED available in red or green.

Note: Lens is not mechanically fastened into housing. Fixture installation has inherit ligature risks.

Division 26 | ElectricalLight Fixtures, Exit Signage

Page 199: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 199

Division 26 | ElectricalLight Fixtures, Exit Signage

General NotesSee comments on previous general notes page.

Must be positively and mechanically at-tached,notfrictionfit.SpecifyULlisted924(NEC,NFPA70)andmountflushtowalls or ceilings. Specify fully recessed housing.

Philips Chloridewww.lightingproducts.philips.com

CE-11500 SC Series Exit Light

Lighting: LED Diffuser|Lens: No lens provided. Housing: Two piece diecast aluminum with chevron cutoouts.Approvals: UL listed, NFPA 70, NFPA 101, NEMA.Options: Red or green letters. Finish: Epoxy based powder coat paint or brushed aluminum.

Note: Cutout letters/chevrons allow ac-cess to interior of fixture.

Philips Chloridewww.lightingproducts.philips.com

CE-11500 SC Series Recessed Exit Light

Lighting: LED. Diffuser|Lens: Polycarbonate/Lens. Housing: Two-piece die cast aluminum with 18 gauge recessed back box and vandal resistant lens.Approvals: UL listed, NFPA 70, NFPA 101, NEMA.Options: Red or green letters.Finish: Epoxy based powder coat paint or brushed aluminum.

Note: Lens does not sit flush inside re-cessed back box for tight and secure fit.

Page 200: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 200

Division 27 | Communications

Page 201: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 201

Division 27 | CommunicationsWireless Routers

Installation Notes

Wireless routers shall be mounted above the ceiling systems in medium and high risk areas.

Wireless routers can be mounted below the ceiling systems in low risk areas.

Page 202: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 202

Division 27 | CommunicationsClocks

Primex Wirelesswww.primexwireless.com

XR Series TransmittersTransmitters wirelessly synchronize time for analog and digital clocks, timers, and other time receivers throughout the facility. Spec-ify GPS.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Installation NotesIt is recommended to specify recessed wall clocks with polycarbonate lenses.

Page 203: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 203

Division 28 | Electronic Safety & Security

Page 204: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 204

Division 28 | Electronic Safety & SecurityFire Alarm Components, General

General Notes

Firealarmnotificationdevicesarerequiredtobeceilingmountedinhighriskareas.

Itisrecommendedthatfirealarmnotificationdevicesbeceilingmountedinmediumriskareas.

Page 205: Patient Safety Standards, Materials and Systems Guidelines

18th Edition | July 31, 2017 205

Division 28 | Electronic Safety & SecurityFire Alarm Components, Notification Devices

General NotesFire alarm notification devices are required to be ceiling mounted in high risk areas.

It is recommended that fire alarm notification devices be ceiling mounted in medium risk areas.

Caution:Device covers are susceptible to abuse and can be looped/weaponized.

Tyco SimplexGrinnellwww.tycosimplexgrinnell.com

TrueAlert Addressable Notification Appliances, Series 49AVWall and ceiling mounted. Multi-electronic horn & strobe combinations.HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Edwards Signalingwww.edwards-signals.com

EGC-SVM Series NotificationAppliances

Caution: The curved return against the ceiling presents a potential ligature op-portunity.

HIGHRISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS

Tyco SimplexGrinnellwww.tycosimplexgrinnell.com

2099 Series Manual Fire Alarm StationSingle action with institutional cover, key operated only.HIGH

RISK AREAS

MEDIUMRISK AREAS

LOWRISK AREAS