35
PASOLINK V4 LCT Training Manual NEC NEC Cooperation Cooperation

Pasolink Lct Menu

Embed Size (px)

Citation preview

Page 1: Pasolink Lct Menu

PASOLINK V4 LCT Training Manual

NEC CooperationNEC Cooperation

Page 2: Pasolink Lct Menu

CONTENTSCONTENTS

2

Part1 Part1

Part2Part2

Part3Part3

LCT CONNECTION LCT CONNECTION

ALL MENUSALL MENUS

ITEMS MEANING IN MENUSITEMS MEANING IN MENUS & HOW TO USE IT& HOW TO USE IT

PASOLINK Introduction

Page 3: Pasolink Lct Menu

TARGETSTARGETS

KNOW HOW TO LOGIN LCTKNOW HOW TO LOGIN LCT

KNOW ITEMS MEANING IN MENUSKNOW ITEMS MEANING IN MENUS

KNOW HOW TO USE ITEMS IN MENUSKNOW HOW TO USE ITEMS IN MENUS

3PASOLINK Introduction

Page 4: Pasolink Lct Menu

LCT CONNECTION (1)

The Pasolink equipment can be configured controlled and monitored locally using the Local Craft Terminal (LCT). Using the LCT it is possible to monitor the local Indoor Unit and related Out Door Unit

A personal computer can be used as the LCT and terminal software like windows Hyper terminal can be used to communicate with the IDU.

The terminal software, communications parameters should be set as follows

Bits per second 9600 Data bits 8 Parity None Stop bits 2 Flow Control Hardware Emulation VT100 Video Terminal

Transmission Add CR/LE at end of line: yes Local Echo: No

(Send line ends with line feeds: yes)* (Echo typed characters locally: No)* Receiving

CR : No Return to the right edge : Yes Force incoming data to 7-bit ASCII: No (Append line feed to incoming line feeds :no)* (Force incoming data to 7-bit ASCII: No)* (Wrap lines that exceed terminal width: Yes)** Settings for Windows Hyper Terminal

PASOLINK Introduction 4

Page 5: Pasolink Lct Menu

LCT CONNECTION (2)

The Remote Pasolink equipment (opposite station ) can be configured controlled and monitored from the local IDU using the Local Craft Terminal (LCT). Connect the LCT to the NMS/RA port. Using the LCT it is possible to monitor the Remote Indoor Unit and related Out Door Unit

Remote configuring/monitoring is not possible when the PM card is mounted or during HBER alarm condition.

A personal computer can be used as the LCT and terminal software like windows Hyper terminal can be used to communicate with the IDU.

The terminal software, communications parameters should be set as follows:

Bits per second 9600 Data bits 8 Parity None Stop bits 2 Flow Control Hardware Emulation VT100 Video Terminal Transmission Add CR/LE at end of line: yes Local Echo:

No (Send line ends with line feeds: yes)* (Echo typed characters locally: No)* Receiving

CR : No Return to the right edge : Yes Force incoming data to 7-bit ASCII: No (Append line feed to incoming line feeds :no)* (Force incoming data to 7-bit ASCII: No)* (Wrap lines that exceed terminal width: Yes)** Settings for Windows Hyper Terminal

PASOLINK Introduction 5

Page 6: Pasolink Lct Menu

PASOLINK Introduction 6

HYPER-TERMINAL SETTING

Page 7: Pasolink Lct Menu

PASOLINK Introduction7

LCT--MENUS

Password:

Password Change:

1.Setting

2.Maintenance

3.Monitoring

4.Exit

Setting

1.Bit rate (16x2MB) 2. AIS RCVD alarm/status 3. AIS SEND alarm/status 4. TX/RX frequency 5. TX power ctrl 6. Main channel usage 1-16 7. BER alarm threshold 8. Frame ID 9. WS channel usage 10. DSC1 11. DSC2 12. DEM invert 13. Alarm table 14. Next items 00. Menu 99. Exit

Maintenance

Maintenanc

eM

onitoring

1. MAINT 2. FE loop back ctrl 1-16 3. NE loop back ctrl 1-16 4. BER ALM >> AIS 5. CW 6. Power mute 7. ATPC manual ctrl 00. Menu 99. Exit

(1+0)

(1+1)

1. Monitoring voltage 2. Monitoring voltage (con mode) 3. Alarm/Status 4. Inventory 00. Menu 99. Exit

1. to 5. same as 1+06. Power mute1 7. Power mute2 8. TX SW ctrl 9. RX SW ctrl10. ATPC manual ctrl 00. & 99. same as 1+0

TX power

ctrl

1. ATPC/MTPC2. MTPC TX power3. ATPC TX power range 4. ODU ALM mode 5. RX threshold 00. Menu 99. Exit

Next

Item 1. System configuration 2. LAN setting3. Channel usage error 00. Menu 99. Exit

LAN

setting

1. Port1 setting2. Port2 setting3. FE link down00. Menu99. Exit

Alarm

Table

INPUT LOSS AIS RCVDAIS SEND OUTPUT LOSS WS INPUT LOSS WS AIS RCVD WS AIS SENDWS OUTPUT LOSS LAN INTFC ALM TX CLK LOSS RX CLK LOSS FSYNC ALMHIGH BER ALM LOW BER ALM BER ALMMOD ALMDEM ALMOPR ALMTX PWR ALM RX LEV ALM APC 1 ALMAPC2 ALMIF INPUT ALM MAINTTX SELRX S ELMDP CPU ALM

IDU

O

DU

INPUT LOSS 1-16CHANNEL USAGE ERROR 1-16AIS RCVD 1-16 AIS SEND 1-16 OUTPUT LOSS 1-16LAN INTFC ALM WS INPUT LOSS WS AIS RCVD WS AIS SENDWS OUTPUT LOSSTX CLK LOSSRX CLK LOSS FSYNC ALMHIGH BER ALM LOW BER ALM BER ALMMOD ALMDEM ALMMDP CPU ALM

TX PWR ALM RX LEV ALM APC 1 ALM APC2 ALM IF INPUT ALM MUTE TX FREQ CH RX FREQ CH

IDU

O

DU

Manufactured date Software version Bit rate Option module Manufactured date Software version Bit rate RF band Sub band Start frequency Shift frequency Serial number CH separation

1.Thoughtput

2.Mode

3.Flow ctrl

4.Framing

5.CAS

6.CRC

7.Collion Report

00.Menu

99.Exit

Port setting

TX power :*.** RX level :*.**

Page 8: Pasolink Lct Menu

LCT MAIN MENU

Connect the LCT PC to the IDU LA Port or RA port using a RS232-C cable. Open the communication software ( eg. Hyper-Terminal).

Press the “CTRL” and “D” keys at the same time

LCT MAIN MENU

LCT main menu has the following main functions.

Setting: Local configuration of IDU and ODU

Maintenance: IDU and ODU maintenance functions

Monitoring: Pasolink Alarm / Status Monitoring function

From the LCT main menu and sub-menus select “99. EXIT” to close the LCT program.

From the sub menus, select “00.Menu” to display the LCT main menu

After data is entered to cancel or go back to higher level menu, press ESC

PASOLINK Introduction 8

Password :********Change Password? (No:0/Yes:1) :1 New Password :********New Password (Re-enter) : * * * * * * * *

1. Setting2. Maintenance3. Monitoring99. ExitSelect Function No. :

Page 9: Pasolink Lct Menu

PASOLINK Introduction 9

SETTING MENU

SETTING menu is used to Configure/setup the Pasolink IDU and ODU locally.

Current setting for each menu item is shown in brackets.

1. Setting2. Maintenance3. Monitoring4. ExitSelect Function No:

Press 1 and Enter

Setting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (alarm)3. AIS SEND alarm/status (alarm)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used: UUNN NNNN UUNN

NNNN)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00.Menu99.ExitSelect Item No. :

Note: The Items shown on the Setting menu depends on the optional hardware mounted and the configuration.

Page 10: Pasolink Lct Menu

PASOLINK Introduction 10

BIT RATE SETTING

Setting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (alarm)3. AIS SEND alarm/status (alarm)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used:

UUNN NNNN UUNN NNNN)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00.Menu99.ExitSelect Item No. :

1. Bit rate (transmission capacity) (4x2MB) Bit rate (2x2:0 / 4x2:1 / 8x2:2 / 16x2:3) : 2

Changing the bit rate will cause temporary communication loss until the bit rate of the opposite site is changed.

The buzzer may be issued until then.

Press any key to continue ... Press ESC key to quit

Press 1 and Enter

Two types of IDUs:

Fixed bit rate(4x2MB) : the bit rate is automatically detected and set in IDU.

Variable bit rate : the selection is 2MBx2, 2MBx4, 2MBx8 or 2MBx16 . Enter the number corresponding to the bit rate required and press the ENTER key Note: The IDU has two type of 2Mb input

connections. 75 ohm unbalance or 120 ohm balanced .

Page 11: Pasolink Lct Menu

PASOLINK Introduction 11

ALARM INDICATION SIGNAL (AIS) SETTING

Setting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (status)3. AIS SEND alarm/status (status)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used: UUNN

NNNN UUNN NNNN)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00. Menu99. ExitSelect Item No. :

2. AIS RCVD alarm/status (status)AIS RCVD alarm/status

(status:0 /alarm :1)

3. AIS SEND alarm/status (alarm)AIS SEND alarm/status

(status:0 /alarm :1 )

Press 2 and Enter

Press 3 and Enter

Note:

When AIS SEND is set to “alarm” , and AIS is sent out the front panel IDU alarm LED lights. When AIS SEND is set to “status” and AIS is sent out, no alarm indication is initiated.

When AIS RCVD is set to “alarm” , on reception of AIS the front panel IDU alarm LED lights. When AIS RCVD is set to “status” on reception of AIS no alarm indication is initiated.

Page 12: Pasolink Lct Menu

PASOLINK Introduction 12

TX/RX FREQUENCY SETTING

Setting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (status)3. AIS SEND alarm/status (status)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used: UUNN

NNNN UUNN NNNN)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00. Menu99. ExitSelect Item No. :

4. TX/RX Frequency (4ch)

TX/RX frequency (0-255ch):1

4. TX/RX Frequency ( No.1:4ch/No.2:10ch)

1. No.1 TX/RX Frequency (4ch)

2. No.2 TX/RX Frequency (10ch)

Press 4 and Enter1+0 or 1+1 Hot Standby Configuration

1+1 Twin Path Configuration

This menu item is used to configure the ODU transmit and receive frequencies. The ODU frequency band information is shown in the label attached to it.

Page 13: Pasolink Lct Menu

PASOLINK Introduction 13

TX POWER CONTROL (1)

Setting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (status)3. AIS SEND alarm/status (status)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used: UUNN NNNN

UUNN NNNN)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00. Menu99. ExitSelect Item No. :

TX power ctrl (ATPC) 1. ATPC/MTPC (ATPC) 2. MTPC TX power (0dB) 3. ATPC TX power range (MAX : 0dB / MIN : -30dB) 4. ODU ALM mode (hold) 5. RX threshold (-55dBm) 00. Menu 99. ExitSelect Item No.

Press 5 and Enter 1. ATPC/MTPC (ATPC)ATPC/MTPC (MTPC:0 /

ATPC:1) :0

2.MTPC TX power (0dB)MTPC TX power (-30 to

0dB) :-5

3. ATPC TX power range (MAX :0 to /MIN:-15 dB):-5

Min power(-30 to -5dB):-20ATPC/MTPC MODE SELECTION

This menu item select the TX PWR Control mode to be used.

MTPC TX PWR defines the ODU output power in MTPC mode. The value entered is the attenuation level in dB from the maximum ODU output power.

ATPC range defines the maximum and minimum transmission power during the ATPC operation.

Page 14: Pasolink Lct Menu

PASOLINK Introduction 14

TX POWER CONTROL (2)

Setting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (status)3. AIS SEND alarm/status (status)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used:

UUNN NNNN UUNN NNNN)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00. Menu99. ExitSelect Item No. : 5

TX power ctrl (ATPC) 1. ATPC/MTPC (ATPC) 2. MTPC TX power (0dB) 3. ATPC TX power range (MAX : 0dB / MIN :

-30dB) 4. ODU ALM mode (hold) 5. RX threshold (-55dBm) 00. Menu 99. ExitSelect Item No.: 4

Press 5 and Enter

4. ODU ALM mode (hold)

ODU ALM mode (MAX: 0/min:1/hold:hold:2):1

5. RX threshold (-55dBm)

RX threshold(-80 to -30 55dBm)

RX THRESHOLDWhen the monitored RX signal level falls

below this level, a control signal is sent to the opposite station to initiate the ATPC function

From the “TX power ctrl menu”, select [5] and press Enter.

ODU ALARM MODEThis menu item defines the ODU

transmit power level when ATPC control communication between IDU and ODU fails. In MTPC mode this setting is ignored.

MAX: Power is controlled to ATPC Max level

MIN : Power is controlled to ATPC Min level

HOLD: Power is maintained at current level

Page 15: Pasolink Lct Menu

PASOLINK Introduction 15

MAIN CHANNEL USAGE

#: Indicates the channels that are restricted by hardware limitations, bit rate setting or selected for LAN signal transmission. U: Indicates when the channel is used for E1 transmission. N: Indicates when the channel is not used. Inhibits alarm.

The variable bit rate type IDUs are either 16MB/s or 32Mb/s rate. In 16Mb/s type the selection is 2MBx2, 2MBx4 or 2MBx8 and 32Mb/s type the selection is 2MBx2, 2MBx4, 2MBx8 or 2MBx16. The display will show the rate selection accordingly.

Setting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (status)3. AIS SEND alarm/status (status)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used:

UNNN #### #### ####)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00. Menu99. ExitSelect Item No. : 5

Main channel usage 1-16 ( 1:used 2:not used 3:not used 4: not used 5:N/A 6:N/A

7:N/A 8:N/A 9:N/A 10:N/A 11:N/A 12:N/A 13:N/A 14:N/A 15:N/A 16:N/A )

Select channel No. :2Channel 2 (used: 0/not used;1):0

Press 6 and Enter

Select the channel number and select:“0” and Enter to use the channel for E1 transmission“1” and Enter not to use the channel for E1 transmission.

N/A” indicates the channels that are not available for E1 transmission due to 10/100 Base-T LAN assignment or hardware restrictions

Page 16: Pasolink Lct Menu

PASOLINK Introduction

BER ALM POINT & FRAME ID

Setting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (status)3. AIS SEND alarm/status (status)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used:

UNNN #### #### ####)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00. Menu99. ExitSelect Item No. : 5

8. Frame ID(2)Input ID No. (0-7): 17. BER alarm threshold (10-4)

BER alarm threshold (10-3:0 / 10-4:1 / 10-5:2 / 10-6:3) :

Press 7 and Enter

Press 8 and Enter

FRAME IDSelect item No.This item defines the

Frame ID of the transmit/receive signal. The Frame ID is used at the receive station to identify the correct receive signal.

As a signal with a different Frame ID cannot be received, the Frame ID of the opposite station should be set to the same ID number.

BER ALARM THRESHOLDWhen excessive BER is detected, the

IDU insert AIS into the data streams sent to the MUX equipment. Threshold value for AIS insertion can be selected as 1 x 10-3, 1 x 10-4, 1 x 10-5 or 1 x10-6. In the (1+1) Hot standby system, both

No.1 and No.2 channels should have the same Frame ID. The number of Frame IDs, which can be set, is eight (ID0 to ID7).

Page 17: Pasolink Lct Menu

PASOLINK Introduction 17

DSC ASSIGNMENT Setting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (status)3. AIS SEND alarm/status (status)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used:

UNNN #### #### ####)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00. Menu99. ExitSelect Item No. : 5

10. DSC1 (232)

DSC1( 232:0 / 64k: 1 ): 0

11. DSC2 (232)

DSC2( 232:0 / 422:1 /485(TERM):/485 ( NON TERM): :3):0 Press 10 and Enter

Press 11 and Enter

DSC1 default setting is 9.6Kbps RS232C interface. A 64Kbps G703 interface card or V11 interface card are available as an option.

DSC2 can be used as a 9.6Kbps interface with RS232C / RS 422 / RS485 interface selectable.

Pasolink V4 uses six service channels in its radio overhead frame as shown in the table.

Page 18: Pasolink Lct Menu

PASOLINK Introduction 18

WS CHANNEL USAGE & DEM INVERT

Setting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (status)3. AIS SEND alarm/status (status)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used:

UNNN #### #### ####)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00. Menu99. ExitSelect Item No. : 5

12.DEM invert (off)DEM invert (off:0 / on:1) :

9. WS channel usage (not used)WS Channel usage (used:0 / not used:1) : 0

WS CHANNEL USAGEThe WS option is applicable only on the 16x2 MB system with WS

INTFC mounted. In this case if WS E1 channel is not used, set this to not use inhibit alarms.

When the WS INTFC module (optional) is not mounted, this menu item is not displayed.

DEM INVERTWhen the ODU receive signal is down converted the signal sent

to the IDU may have a normal or inverted spectrum.

Note: 8GHz 728MHz shift-E7426B / E9747B,F

7GHz 161MHz shift-G6583A,B / G6584A,B

7GHz 154MHz shift-G6583E,F / G6584E,F

8GHz all Types –G6585,G6586,G3362,G3363

For the listed ODUs select DEM invert ON

Page 19: Pasolink Lct Menu

PASOLINK Introduction 19

ALARM TABLESetting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (status)3. AIS SEND alarm/status (status)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used:

UUNN NNNN UUNN NNNN)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00. Menu99. ExitSelect Item No. : 5

This menu item defines the external relay outputs. The alarms are sent out through four relays(1 +0) or six relays(1 +1). Multiple alarms can be assigned to any relay and alarms can be assigned to multiple relays.

C1 C2 C3 C4 C5 C6 1.INPUT LOSS OUT OUT --- --- --- --- 2.AIS RCVD --- --- --- --- --- --- 3.AIS SEND --- --- --- --- --- --- 4.OUTPUT LOSS --- --- OUT OUT --- --- 5.TX CLK LOSS OUT --- --- --- --- ---- ---larm table 2/3 C1 C2 C3 C4 C5 C6 9.FSYNC ALM1 --- --- OUT --- --- --- 11.HIGH BER ALM1 --- --- OUT --- --- --- 12.HIGH BER ALM2 --- --- --- OUT --- --- 13.LOW BER ALM1 --- --- --- --- --- --- 15.BER ALM --- --- OUT --- OUT --- 17.MOD ALM1 OUT --- --- --- --- --- 19.DEM ALM1 --- --- OUT --- --- --- 21.OPR ALM1 OUT --- OUT --- --- ---

23.TX PWR ALM OUT --- --- --- --- --- 25.RX LEV ALM1 --- --- OUT --- --- --- - - - - - - - 33.MAINT MASK MASK MASK MASK MASK OUT

Page 20: Pasolink Lct Menu

PASOLINK Introduction 20

NEXT ITEMS MENU Setting1. Bit rate (1 6x2MB)2. AIS RCVD alarm/status (status)3. AIS SEND alarm/status (status)4. TX/RX frequency (4ch)5. TX power ctrl (ATPC)6. Main channel usage 1 - 16 (used:

UUNN NNNN UUNN NNNN)7. BER alarm threshold (10-3)8. Frame ID (1)9. WS channel usage (on)1 0.DSC1 (232)11 .DSC2 (232)12.DEM invert (off) 13.Alarm table14.Next items00. Menu99. ExitSelect Item No. : 5

Next item1.System configuration 2. LAN setting3. Channel usage error 00. Menu 99. ExitSelect Item No. : 5

Press 14 and Enter

1. System Configuration (Hot standby)

System configuration (1+0 expandable: 0 / Hot standby: 1/ Twin path: 2)

Press 1 and Enter

System Configuration menu item appears only in (1+1) systems.

1. Channel usage error (not report)

Channel usage error (report: 0 / not report :1); 0

Press 3 and Enter

When a main channel or WS channel is selected as not used, and the 2MB or WS interface detects a 2MB signal at the input, This item defines whether to report or not to report this condition as an alarm event.

(1+0) expandable configuration is selected when in an (1+1) hardware configuration only one channel IDU and ODU is equipped or used. Other channel alarms are inhibited.

(1+1) Hot standby only one channel is transmitted at a time but receive from both channels and select one.(1+1) Twin Path both channels transmit and use two different frequencies.

Page 21: Pasolink Lct Menu

PASOLINK Introduction 21

NEXT ITEMS MENU-LAN SETTING

Next item1.System configuration 2. LAN setting3. Channel usage error 00. Menu 99. ExitSelect Item No. : 5

LAN

setting

1. Port1 setting2. Port2 setting3. FE link down00. Menu99. Exit

Port setting

1.Thoughtput

2.Mode

3.Flow ctrl

4.Framing

5.CAS

6.CRC

7.Collion Report

00.Menu

99.Exit

Port setting Port setting

Throughout = 2MB Framing = ON

Throughout = 2MB Framing = OFF

Throughout > 2MB

Throughput setting

0. Disable

1. 2M

2. 4M

3. 8M

4. 16M

5. 32M M

ode Setting

0. AUTONEG (Auto-MDI/MDIX)1.10M-Half (MDI)2.10M-Full (MDI)3.100M-Half (MDI)4.100M Full (MDI)5 .10M-Half (MDIX)6.10M-Full (MDIX)7.100M-Half (MDIX)8.100M Full (MDIX)00. Menu 99. Exit

1.Thoughtput

2.Mode

3.Flow ctrl

4.Framing

5.Collion Report

00.Menu

99.Exit

1.Thoughtput

2.Mode

3.Flow ctrl

4.Collion Report

00.Menu

99.Exit

Page 22: Pasolink Lct Menu

PASOLINK Introduction 22

Applicable Traffic Channels - 1

Page 23: Pasolink Lct Menu

PASOLINK Introduction 23

Applicable Traffic Channels - 2

Page 24: Pasolink Lct Menu

PASOLINK Introduction 24

LAN PORT SETTING (1)1. LAN setting 1.Port1 setting (2M) 2.Port2 setting (disable) 3.FE link down (enable) 00. Menu 99. Exit Select item No. :

Press 1 or 2 and Enter 1. Port 1 setting1. Throughput (2M)2 .Mode(AUTONEG(AUTO-MDI/MDIX))3. Flow ctrl (off)4. Framing (on)5. CAS (on)6. CRC (on)7. Collision report (report)00. Menu99. Exit1. Throughput (disable)

Throughput (disable:0 / 2M:1 / 4M:2 / 8M:3 / 16M:4 / 32M:5) :1

Select the rate for each LAN Ports, Depending on the selection the No. of channels for E1 data are decided. See the table in the next page.

3. Flow Ctrl (off)

Flow ctrl (off: 0/ on:1):1

4. Framing (off)Framing ( off : 0 / on : 1 ) :

5. CAS (off)

CSC( off: 0/ on: 1)

Select whether to use Framing or not. Applies only when 2M is selected as throughput for the Port.

Select whether to use flow control or not

Applies when Port throughput is set to 2MB with Framing ON. If CAS is ON LAN data is also sent in TS16. IF CAS is off then LAN data is not sent in TS16.

Page 25: Pasolink Lct Menu

PASOLINK Introduction 25

LAN PORT SETTING (2)1. LAN setting 1.Port1 setting (2M) 2.Port2 setting (disable) 3.FE link down (enable) 00. Menu 99. Exit Select item No. :

Press 1 or 2 and Enter 1. Port 1 setting1. Throughput (2M)2 .Mode(AUTONEG(AUTO-MDI/MDIX))3. Flow ctrl (off)4. Framing (on)5. CAS (on)6. CRC (on)7. Collision report (report)00. Menu99. Exit

6. CRC (off)

CRC( off: 0/ on: 1)

Applies when Port throughput is set to 2MB with Framing ON.

7. Collision report (report)Collision Report( report :0 / not report : 1)

2. Mode (10M-HALF(MDI))

Mode AUTONEG (AUTO -MDI/MDIX) :0

10M-HALF(MDI) :1 / 10M-FULL(MDI) :2

100M-HALF(MDI) :3 / 100M-FULL(MDI) :4

10M-HALF(MDIX) :5 / 10M-FULL(MDIX) :6

1 00M-HALF(MDIX):7 / 1 00M-FULL(MDIX):8

Select No. :2

3. FE link down (disable)

FE link down (disable :0 / enable :1):

Page 26: Pasolink Lct Menu

PASOLINK Introduction 26

MAINTENANCE1. Setting2. Maintenance3. Monitoring4. ExitSelect Function No:

Maintenance 1. MAINT (NORM) 2. FE loop back ctrl 1-16 (ctrl:---- ---- ---- ----) (ans :---- ---- ---- ----) 3. NE loop back ctrl 1-16 (ctrl:---- ---- ---- ----) (ans :---- ---- ---- ----) 4. BER ALM >> AIS (on) 5. CW (off) 6. Power mute1 (off) 7. Power mute2 (off) 8. TX SW ctrl (AUTO) 9. RX SW ctrl (AUTO) 10. ATPC manual ctrl (off) 00. Menu 99. Exit

The Maintenance Menu is used to carry out the following functions.

Maintenance ON/OFF Far end loop back Near end loop back Transmit CW carrierStop Transmission (Mute) BER AIS insertion ON/OFFTX and RX manual switching(1+1)Manual ATPC control

The maintenance items 7, 8, and 9 applies to (1+ 1) configurationIf TX power control mode is MTPC menu item 10 is not displayed

To display the “Maintenance” menu, press [2] and [Enter] from the LCT main menu.

The first item in the maintenance menu shows the status of the maintenance mode (Normal or MAINT).

MAINT (Normal:0 / MAINT:1) : 0When the maintenance mode is “on”, or any of the maintenance

control items are “on”, the front panel “MAINT” LED (amber) lights.

Page 27: Pasolink Lct Menu

PASOLINK Introduction 27

FE LOOP-BACKMaintenance 1. MAINT (NORM) 2. FE loop back ctrl 1-16 (ctrl:---- ---- ---- ----) (ans :---- ---- ---- ----) 3. NE loop back ctrl 1-16 (ctrl:---- ---- ---- ----) (ans :---- ---- ---- ----) 4. BER ALM >> AIS (on) 5. CW (off) 6. Power mute1 (off) 7. Power mute2 (off) 8. TX SW ctrl (AUTO) 9. RX SW ctrl (AUTO) 10. ATPC manual ctrl (off) 00. Menu 99. Exit

2. FE loop back ctrl 1-16(1:off 2:off 3:off 4:off 5:off 6:off 7:off 8:off 9:off 10:off 11:off

12:off 13:off 14:off 15:off 16:off)Select channel No. : 1

Channel 1 (off: 0 / on: 1): 0

2. FE loop back ctrl 1-16 ( ctrl:*--# --z---- ---- )

(ans : *--- ---- ---- ---- )

This menu is used to create a Far End loopback at the main interface of the opposite station IDU.

Press [2] and [Enter] from the Maintenance Menu to display the “FE Loopback control” menu.

The FE Loopback status of channels 1 to 16 are displayed. Select the channel No: to be controlled and press Enter.

Press:[1] and [Enter] to switch Loopback on [0] and [Enter] to switch Loopback of

* An asterisk on the “cont” line indicates that the loopback control is sent to the selected channel* An asterisk on the “ans” line indicates that the loopback control was successfully carried out on the selected channelz A “z” on the “cont” line indicates that the loopback control was initiated from the opposite station IDU# E1 channel is inhibited by hardware restrictions or LAN signal transmission usage

Page 28: Pasolink Lct Menu

PASOLINK Introduction 28

NE LOOP-BACKMaintenance 1. MAINT (NORM) 2. FE loop back ctrl 1-16 (ctrl:---- ---- ---- ----) (ans :---- ---- ---- ----) 3. NE loop back ctrl 1-16 (ctrl:---- ---- ---- ----) (ans :---- ---- ---- ----) 4. BER ALM >> AIS (on) 5. CW (off) 6. Power mute1 (off) 7. Power mute2 (off) 8. TX SW ctrl (AUTO) 9. RX SW ctrl (AUTO) 10. ATPC manual ctrl (off) 00. Menu 99. Exit

3. NE loop back ctrl 1-16(1:off 2:off 3:off 4:off 5:off 6:off 7:off 8:off 9:off 10:off 1 1:off

12:off 13:off 14:off 15:off 16:off) Select channel No. : 1 Channel 1 (off:0 / on:1) : 0

NEAR END LOOPBACK CONTROLFrom this menu, it is possible to create a near end loopback at the

main interface of the local station IDU.Press [3] and [Enter] from the Maintenance Menu to display the

“NE Loopback control” The NE Loopback status of channels 1 to 16 are displayed. Select

the channel No: to be controlled and press Enter.

Page 29: Pasolink Lct Menu

PASOLINK Introduction 29

BER ALM & CW Maintenance 1. MAINT (NORM) 2. FE loop back ctrl 1-16 (ctrl:---- ---- ----

----) (ans :---- ---- ---- ----) 3. NE loop back ctrl 1-16 (ctrl:---- ---- ---- ----) (ans :---- ---- ---- ----) 4. BER ALM >> AIS (on) 5. CW (off) 6. Power mute1 (off) 7. Power mute2 (off) 8. TX SW ctrl (AUTO) 9. RX SW ctrl (AUTO) 10. ATPC manual ctrl (off) 00. Menu 99. Exit

4.BER AIS on/off (on)

BER AIS on/off (off:0 / on:1) 1

Press [4] and [Enter] from the Maintenance Menu to display the BER ALM AIS control.

Press: [0] and [Enter] to disable BER AIS insertion [1] and [Enter] to enable BER AIS insertion

BER ALM >> AISBER AIS From this maintenance menu item, it is possible to

disable BER AIS insertion for all channels.

5. CW (off)

CW(off:0 / on:1) :1

CWFrom this menu item, it is possible to transmit an un

modulated carrier.To display the “CW” control, press [5] and [Enter] from

the maintenance menu. MOD CW control is displayed.

Press: [1] and [Enter] to transmit a CW carrier[0] and [Enter] stop transmitting a CW carrier

Page 30: Pasolink Lct Menu

PASOLINK Introduction 30

OTHER MAINT FUNCTIONSMaintenance 1. MAINT (NORM) 2. FE loop back ctrl 1-16 (ctrl:---- ---- ---- ----) (ans :---- ---- ---- ----) 3. NE loop back ctrl 1-16 (ctrl:---- ---- ---- ----) (ans :---- ---- ---- ----) 4. BER ALM >> AIS (on) 5. CW (off) 6. Power mute1 (off) 7. Power mute2 (off) 8. TX SW ctrl (AUTO) 9. RX SW ctrl (AUTO) 10. ATPC manual ctrl (off) 00. Menu 99. Exit

6.Power mute (off) Power mute (off:0 / on: 1) : 0

POWER MUTE1 OR 2(1+1)From this maintenance menu item, it is possible

to switch off the ODU output power.Press [6] and [Enter] from the Maintenance Menu

to display the Power Mute control.Press: [0] and [Enter] to select mute off[1] and [Enter] to select mute onMaintenance menu reappear to select any other

maintenance item

ATPC manual ctrl (off)ATPC manual ctrl (off:0 / on:1) :1 ATPC

current (-5dB)ATPC current (-30 to 0dB) :-10

ATPC manual ctrlFrom this menu item, it is possible to change the ATPC

set TX power manually.To display the ATPC manual ctrl, press [10] and [Enter]

from the maintenance menu.Press: [1] and [Enter] to select ATPC manual controlEnter the attenuation required to get the TX power

required.

Page 31: Pasolink Lct Menu

PASOLINK Introduction 31

MONITORING Monitoring

1. Monitoring voltage 2. Monitoring voltage

(continuous mode) 3. Alarm/Status 4. Inventory 00. Menu

1. Setting2. Maintenance3. Monitoring4. ExitSelect Function No:

Monitoring voltage TX power1 :4.10V (< -5dB) RX level1 :2.37V ( -61dBm) TX power2 :*.** RX level2 :*.**

2. Monitoring voltage (continuous mode) Time stamp (1min:0 / 1sec:1):1

Press any key to start...The monitoring menu is used to

monitor the equipment for preventive maintenance purposes. This menu provides monitoring of the Transmit and Receive signal levels. Equipment status and alarm can also be monitored from this menu. Inventory list provides details of the modules in the equipment

Press [3] and [Enter] from the LCT main Menu to display the Monitoring menu.

DATA (Monitoring voltages)Measured input / TX output

RF signal levels are displayed. The metering range for each measurement is given in the table above. TX output power is given as the detector voltage and attenuation used in dB. RX signal level is given as AGC voltage and in dBm

METER READING OF ODU PARAMETERS Transmitter Power 0 to 4.6 V DCReceiving Level 0.8 to 4.4V DC (Depend on the Transmitter Power and the

Receiving Signal level )

Page 32: Pasolink Lct Menu

PASOLINK Introduction 32

ALARM/STATUS MONITORING Monitoring1. Monitoring voltage 2. Monitoring voltage

(continuous mode) 3. Alarm/Status 4. Inventory 00. MenuSelect item No. : 3

Monitoring of alarm/status 1/2 IDU INPUT LOSS 1-16 (alarm:---- ---- ---- ----) CHANNEL USAGE ERROR 1-16 (alarm:---- ---- ----

----) AIS RCVD 1-16 (alarm:---- ---- ---- ----) AIS SEND 1-16 (alarm:---- ---- ---- ----) OUTPUT LOSS 1-16 (alarm:---- ---- ---- ----) TX CLK LOSS (alarm:-/-) RX CLK LOSS (alarm:-/-) FSYNC ALM (alarm:-/-) HIGH BER ALM ( alarm:-/-) LOW BER ALM (alarm:-/-) BER ALM (alarm:-/-)Press any key to continue…Monitoring of alarm/status 2/2

3. Monitoring of alarm/status 2/2MOD ALM (alarm:-/-) DEM ALM (alarm:-/-) OPR ALM ) (alarm:-/-) MDP CPU ALM (alarm:-/*) ODU TX PWR ALM (alarm:-/-) RX LEV ALM ) (alarm:-/-) APC1 ALM (alarm:-/-) APC2 ALM (alarm:-/-) IF INPUT ALM (alarm:-/-) MUTE (on) TX/RX FREQ CH (1ch )

Press 3 and ENTER

The IDU and ODU alarms and status information can be viewed form this menu item. Alarm condition is indicated by “*” and normal condition by “-“.

Page 33: Pasolink Lct Menu

ALARMSIF Input ALM IF input level in the ODU below (approximately)-

63dBm. STATUS INFORMATIONMUTEODU output mute on/off statusTX/RX Frequency CHChannel number corresponding to the ODU

transmit/receiver frequencyIDU AlarmsInput loss 1 – 16In the 2MB interface, loss of 2MB input signal

detected. Alarm indicated for each channel. Channel Usage Error 1 -16 In the 2MB

interface,2MB channel# is toUsed and a signal is detected at the inputAIS RCVD 1-16In the 2MB interface, AIS (all”1”) received from

MUX equipment or Back-to-back 2MB connection. Alarm indicated for each channel.

AIS Send 1-16In the 2MB interface, AIS sent to MUX equipment or

back-to-back 2MB connection. Alarm indicated for each channel.

Output loss 1 -16In the 2MB interface, loss of received 2MB signal from

the demodulator side. Alarm indicated for each channel.

LAN INTFC ALMWhen the WS channel usage is set to not used and

there is a 2MB signal at the input WS input loss In the optional WS interface card, loss of WS input

signalWS Channel Usage ErrorWhen the WS channel usage is set to “not used” and

signal is detected at the WS input.WS AIS RCVDIn the optional WS interface card, AIS detected in the

WS input signal.WS AIS sendIn the optional WS interface card, AIS is sent out as

the WS

PASOLINK Introduction 33

Page 34: Pasolink Lct Menu

ALARMSWS output loss In the optional WS interface card, Receive WS

signal not detected from the demodulator.TX CLK lossLoss of TX clock, in the 2 MB interface.RX CLK lossLoss of RX clock in the 2 MB interface. FSYNC ALMLoss of RX frame synchronization at the RX

DPU. HIGH BER ALMWhen the receive BER is > 10-3LOW BER ALMWhen the receive BER is > 10-6BER ALMBER alarm point for inserting AIS. Alarm trigger

point can be selectable from (10-3, 10-4, 10-5 and 10-6)

MOD ALMModulator 850 MHz PLL oscillator loop unlock

condition.DEM ALMRX carrier not synchronized or lost.OPR ALMCommunication error between ODU and IDU ODU ALARMS TX Power ALMTransmitter output power decreased by 3 to 5

dBRX Level ALM Receive level below squelch levelAPC1 ALMODU 1st local oscillator APC unlock alarmAPC2 ALMODU 2st local oscillator APC unlock alarm

PASOLINK Introduction 34

Page 35: Pasolink Lct Menu

PASOLINK Introduction 35

INVENTORY Monitoring1. Monitoring voltage 2. Monitoring voltage

(continuous mode) 3. Alarm/Status 4. Inventory 00. MenuSelect item No. : 3

IDU SW UNIT Serial number 4023 Manufactured date DEC/2005 Software version (ROM/RAM) (1.20/2.40) Bit rate 2/4/8/16x2MB Option module PM CARDInventory 2/4 IDU No.1 MD UNIT Serial number 12650 Manufactured date DEC/2005 Software version (ROM/RAM) (1.2/2.49) No.2 MD UNIT

No.1 ODU Serial number 16352 Manufactured date OCT/2005 Software version (ROM/RAM) (1.02/2.03) Bit rate 17/34MB RF band 13GHz High Sub band A Start frequency 13020.500MHz Shift frequency 266MHz CH separation 1.750MHz

Press 4 and ENTER

This menu item gives the IDU and ODU module information as given in the figure. The figure gives the inventory information for a (1+1) configuration