21
19-11-2014 PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER PARTIEL DISCHARGES (PD) PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINGER AGENDA INTRODUKTION IMPREGNERINGSPROCESSEN STATOR VIKLINGER HULRUM & HULLER ISOLATIONEN BASISVIDEN OM PD DETEKTERING AF PD PD-MÅLERESULTATER OG RAPPORTERING RAMBØLL´S PD MÅLEOPGAVER

Partiel discharges generators and motors

  • Upload
    ramboll

  • View
    237

  • Download
    3

Embed Size (px)

DESCRIPTION

 

Citation preview

Page 1: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

Title slide

PARTIEL DISCHARGES (PD) PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINGER

AGENDA • INTRODUKTION • IMPREGNERINGSPROCESSEN • STATOR VIKLINGER • HULRUM & HULLER • ISOLATIONEN • BASISVIDEN OM PD • DETEKTERING AF PD • PD-MÅLERESULTATER OG RAPPORTERING • RAMBØLL´S PD MÅLEOPGAVER

Page 2: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

Hvad kan måling af partielle udladninger (PD) bruges til

• Indgår som værktøj til forebyggende vedligehold

• Værktøj til overvågning af ens generator stator tilstand på

løbende basis

• Stator viklings problemer står for mere end 40% af alle

generator/motor fejl

• Startende fejl kan opdages I tide og den grundlæggende årsag

kan identificeres på et tidligt stadie

• Forebyggende tiltag kan foretages med væsentlig lavere

omkostninger til følge end ved fejl

• PD måling kan foretages både på eksisterende og nye maskiner

INTRODUKTION

Content slide

Page 3: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

INTRODUKTION

Content slide

Problem

Page 4: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

• VPI (Vacuum Pressure Impregnation, VPI) Individuelle viklinger

• GVIP(Global Vacuum Pressure Impregnation)

IMPRENERINGSPROCESSEN

Content slide

Page 5: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

Typer af isolering

STATOR VIKLINGER

Content slide

Roebel-bar Multi-turn coil

Page 6: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

HULRUM OG HULLER

Content slide

Problem

Hulrum & Huller

Page 7: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

ISOLATIONEN

Content slide

Page 8: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

Eluft=Vluft/dluft=3kV/mm

Ved en 13,8kV maskine, 21 viklinger, 3 turn

1. Fase til jord: 13,8kV/ √3=7967V

2. Volt/vinding: 7967V/21=379V/vinding

3. Volt/turn: 379V/3=126V/turn

ISOLATIONEN

Content slide

N

F=7967V

Page 9: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

BASISVIDEN OM PD

Content slide

Problem

Hulrum & Huller

Partielle

udladninger (PD)

Page 10: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

PD kan deles op i 3 overordnet kategorier

• Korona udladninger

• Overflade udladninger

• Interne udladninger i hulrum/sprækker

BASISVIDEN OM PD

Content slide

Page 11: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

PD EKSEMPLER

Content slide

Page 12: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

STATOR FEJL

Content slide

Page 13: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

• Kostbar og omfattende reparation af generatoren

• I værste fald udskiftning af generatoren

• Eventuelle følgeskader

• Uplanlagt udetid og drifttab

KONSEKVENSEN VED STATOR FEJL

Content slide

Page 14: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

DETEKTERING AF PD

Content slide

Problem

Hulrum & Huller

Partielle

udladninger

PD detektering

Page 15: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

DETEKTERING AF PD

Content slide

Kapacitive koblerer 80pF Stator Slot Couplers (SSC)

Page 16: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

DETEKTERING AF PD (MÅLESTED)

Content slide

Page 17: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

PD er defineret til at have en stigtid på 1-5ns

Xc(60Hz)=1/2Pi(60Hz)80pF=33MΩ

Xc(83MHz)=1/2Pi(83MHz)80pF=24Ω

DETEKTERING AF PD

Content slide

Page 18: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

FORTOLKNING AF PD MÅLERESULTATER

Content slide

Page 19: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

Ingen +- PD dominans, PD I isolationsmaterialet

FORTOLKNING AF PD MÅLERESULTATER

Content slide

Page 20: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

STATOR FEJL MEKANISMER

Content slide

Page 21: Partiel discharges generators and motors

19-11-2014

PD I ELEKTRISKE ROTERENDE MASKINERS STATOR VIKLINER

PD MÅLEOPGVER UDFØRT AF RAMBØLL

Content slide

Asnæsværket 2 ASVB2MKA10_1

Asnæsværket 5 ASVB5MKA10

Avedøreværket 1 AVV51MKA10

Avedøreværket 2 AVV521MKA10

Avedøreværket 2 AVV522MKA10

Avedøreværket 2 AVV52MKA10

Enstedværket 3 ENVB3MKA10

Enstedværket 3 ENVB3MKA10

Esbjergværket 3 ESVB3MKA10

H.C. Ørsted Værket 7 HCV7MKA01

H.C. Ørsted Værket 8 HCV8MKA01

Herningværket 1 HEVM1MKA10

Horsens KVV 1 HOV1MKA01

Horsens KVV 2 HOV2MKA01

Kyndbyværket 21 KYV16512

Kyndbyværket 22 KYV17512

Måbjergværket MBVMKA01

Skærbækværket 3 SKVB3MKA10

Skærbækværket 3 SKVB3MKA10

Studstrupværket 3 SSVB3MKA10

Studstrupværket 4 SSVB4MKA10

Studstrupværket 4 SSVB4MKA10