All images courtesy of Data Aire Inc. BY STEVE WELLANDER, CM www.rsesjournal.com 22 RSES Journal DECEMBER 2012 The first in a three-part series, this feature will discuss data-center A/C systems, includ- ing equipment design, environmental control, types of heat rejection, economizers, humidity control and more. DATA CENTERS: T he modern data center presents unique challenges to the service techni- cian. The data centers, with all of the electrical equipment (servers, un- interruptible power supplies and storage units), produce heat. A typical data center can have hundreds of racks in the room, and each rack can have up to 42 servers. A typical data center also has a cooling density (heat load) of 50 W to 150 W per sq ft. A small data center sized for 5,000 sq ft is equal to 66 tons of cooling at the low end and 198 tons of cooling at the high end. Server rooms operate 24 hours a day, seven days a week, 365 days a year. The design of the cooling equipment for a data center is to operate under these conditions. If the computer room air-conditioner, or CRAC units, were an automobile running at 50 mph, the equivalent mileage for the CRAC unit would be 438,000 at the end of one year. These units do need regular mainte- nance if they are to operate trouble free. Most CRAC manufacturers recom- mend at least a monthly inspection of the units with a more thorough main- tenance completed on a quarterly basis. Heat removal The CRAC units are designed differently than comfort air-conditioning systems. The biggest differ- ence is the sensible heat ratio. For comfort air-con- ditioning, the heat ratio is 60%–70%—that is, the coil/air flow is designed to remove 30%–40% latent heat load (moisture) and 60%–70% sensible heat load. The CRAC unit is designed for 85%–95% sen- sible heat load and 5%–15% latent load. These units will remove the high sensible heat load produced by the electronic equipment in a data center. The CRAC units also have the ability to control the humidity levels to the space. The units can add humidity with a humidifier that is built into the unit. The interior of a DX CRAC unit. What Technicians Need to Know Part 1

Part 1 Data Centers - rses.org · the first in a three-part series, this feature will discuss data-center a/C systems, ... cooling as primary means of cooling. ... 1.5 HP for all

  • Upload
    letram

  • View
    217

  • Download
    0

Embed Size (px)

Citation preview

All images courtesy of Data Aire Inc.

B y S t e v e W e l l a n d e r , C M

w w w . r s e s j o u r n a l . c o m22 RSES Journal DECEMBER 2012

the first in a three-part

series, this feature will

discuss data-center

a/C systems, includ-

ing equipment design,

environmental control,

types of heat rejection,

economizers, humidity

control and more.

Data Centers:

The modern data center presents unique challenges to the service techni-cian. The data centers, with all of the electrical equipment (servers, un-interruptible power supplies and storage units), produce heat. A typical

data center can have hundreds of racks in the room, and each rack can have up to 42 servers. A typical data center also has a cooling density (heat load) of 50 W to 150 W per sq ft. A small data center sized for 5,000 sq ft is equal to 66 tons of cooling at the low end and 198 tons of cooling at the high end.

Server rooms operate 24 hours a day, seven days a week, 365 days a year. The design of the cooling equipment for a data center is to operate under these conditions. If the computer room air-conditioner, or CRAC units, were an automobile running at 50 mph, the equivalent mileage for the CRAC unit would be 438,000 at the end of one year. These units do need regular mainte-nance if they are to operate trouble free. Most CRAC manufacturers recom-mend at least a monthly inspection of the units with a more thorough main-

tenance completed on a quarterly basis.

Heat removalThe CRAC units are designed differently than comfort air-conditioning systems. The biggest differ-ence is the sensible heat ratio. For comfort air-con-ditioning, the heat ratio is 60%–70%—that is, the coil/air flow is designed to remove 30%–40% latent heat load (moisture) and 60%–70% sensible heat load. The CRAC unit is designed for 85%–95% sen-sible heat load and 5%–15% latent load. These units will remove the high sensible heat load produced by the electronic equipment in a data center.

The CRAC units also have the ability to control the humidity levels to the space. The units can add

humidity with a humidifier that is built into the unit. the interior of

a dX CraC unit.

What Technicians Need to Know

Part 1

DECEMBER 2012 RSES Journal 23w w w . r s e s j o u r n a l . c o m

a typical data center can have hundreds of racks in the room, and each rack can have up to 42 servers. a small data center sized for 5,000 sq ft is equal to 66 tons of cooling at the low end and 198 tons of cooling at the high end.

The system also can dehumidify the room with the cooling coil activated to remove the excessive moisture in the space.

The units will clean the air continuously through the high-efficiency air filters and the system design of the blower operating all of the time. The air filters will remove any dust or contaminates that circulate in the air of the controlled space.

CRAC units have several options to remove the heat from a data room. A direct-expansion unit, with air-cooled, wa-ter-cooled or glycol-cooled condensing, is one option. Larger floor and ceiling units typically have one to four stages of cooling. Smaller units (less than 5 tons) are generally single-stage units.

Another option uses chilled water to remove heat. The units have a chilled-water coil used to remove the heat from the space. Smaller ceiling CRAC units will generally have a zone valve to control the water flow through the coil via the

microprocessor. Most floor-mount-ed CRAC units will have modulat-ing chilled-water valves. This allows the controller to regulate the chilled water through the coil to match the heat load of the space.

A third type is a hybrid unit that features both chilled-water and direct-expansion coils in the same cabinet. The idea is that the sys-tem can use chilled water from the

building during the day when the building is occupied. Then, when the chiller shuts down for nights, weekends and holi-days, the system automatically switches over to the DX mode of operation.

Glycol-cooled systems use a fluid cooler for the heat rejec-tion for the compressor. Technicians need to be aware that there are several benefits and limitations to using a fluid cool-er. The benefits include flexible location choices of the fluid cooler vs. the CRAC unit with an air-cooled condenser. An air-cooled condenser presents limitations on how far below the evaporator it can be located. The limit for most manufac-turers’ air-cooled condensers is 10 ft–20 ft below the evapo-rator section. With a fluid cooler, there are no limitations on how far below the evaporator the fluid cooler can be located, other than general fluid-piping rules.

Another benefit to using a fluid cooler is that in areas with cold ambient, the cold glycol fluid can be used in an

w w w . r s e s j o u r n a l . c o m24 RSES Journal DECEMBER 2012

this shows the piping end of a CraC unit.   

a CraC control module automates the day-to-day processes of the data center.

economizer mode to remove the heat from the data center without the use of the compressors. The CRAC unit is built with both a DX coil and a chilled-water/glycol coil. With the use of a switchover thermostat, the system can optimize the use of the “free cooling” from the cold glycol solution.

With both the chilled-water units with DX cooling and glycol unit with economizer coils, there is an option for com-pressor supplement to the chilled water of glycol. These sys-tems can be set up to operate the chilled water or glycol cooling as primary means of cooling. If the temperature con-tinues to rise, the compressor(s) are cycled to supplement the cooling needs for the space.

air treatmentIn addition to the means of heat removal, there are other components for treating the air in the space, including hu-midification to add moisture to the space if the room gets too dry. There are several styles of humidifiers available from different manufacturers. Some of the more common are the electrode steam generators, infrared humidifiers, ultrasonic humidifiers and immersion humidifiers. Be sure to check the type of humidifier unit being serviced and refer to the manu-facturer’s installation, operation and maintenance informa-tion. All humidifiers are designed to have the same results—they add moisture to the controlled space.

CRAC units also have the means to dehumidify if the rel-ative humidity in the space is high. The humidity is removed by cycling the cooling via the DX or chilled-water coil. The temperature difference between the air over the coil and the cooler coil temperature will wring out the moisture from the air.

The CRAC unit is also equipped with “reheat” to help with dehumidification. The intent of the reheat feature is to cycle for a short amount of time to help stabilize the tem-perature in the space during dehumidification. During the dehumidification process, the room can become colder than desired. Remember, the primary design of the system is to remove sensible heat. If the heat load is not balanced with the cooling, this will result in a colder-than-desired space temperature. The design of the reheat is to temper the air leaving the coil to improve the dehumidification cycle.

Another function of the CRAC is to continuously clean the air in the space. Since the blower is operating 24/7, high-efficiency air filters are often used to clean the air. There are differing levels of efficiency for the air filters, which a MERV number indicates. In general the higher the MERV number, the higher the efficiency and the more

DECEMBER 2012 RSES Journal 25w w w . r s e s j o u r n a l . c o m

www.embraco.com/apps/troubleshootingQR code generated on http://qrcode.littleidiot.be

Compatible with iPhone and Android.

EMBRACO’S NEW MOBILE APPLICATION IS EASY TO USE AND HELPS YOU SOLVE MECHANICAL AND ELECTRICAL PROBLEMS IN LESS TIME. SCAN THE QR CODE PROVIDED TO DOWNLOAD YOUR FREE APP.

Also, we can help you significantly reduce inventory onyour shelves and in your truck with our new optimizedproduct portfolio. Go to www.embraco.com and downloadthe new brochure.

Embraco is the global leader in commercial refrigeration compressors. We offer innovative, quality and low energy consumption solutions with products from 1/12 HP to 1.5 HP for all refrigeration applications: LBP, MBP and HBP.

NOW TROUBLESHOOT FROM YOUR PHONE

REFRIGERATION SYSTEM ISSUES?

TroubleshootingApp

Circle Reader Service No. 59

restrictive the air filter is. It is very important to re-place the air filter with the same MERV-rated air filter that came with the units. Most units are designed to a specification for pressure drape and cfm output. These specifications spell out the MERV rating for the air filter and the external static pressure for the CRAC unit. The blower drive set is based on this furnished information plus the internal static of the CRAC unit. If the filter rating is increased or decreased, the end user may not get the required performance.

Editor’s Note: Be sure to check out the January 2013 issue of RSES Journal for the second part of this three-part feature series.

Steve Wellander, CM, is the Service Manager for Data Aire Inc. and conducts up to six training sessions per year on Data Aire equipment in Orange, CA. He also is an MSAC Member and provides answers for the monthly MSAC Hotline column in RSES Journal. He can be reached via e-mail at [email protected]. For more information, visit www.dataaire.com.

With both the chilled-water units with DX cooling and

glycol unit with economizer coils, there is an option for compressor supplement to the chilled water of glycol.