Upload
trinhnhi
View
222
Download
3
Embed Size (px)
Citation preview
53
Chapter 3
PARAMETRIC STUDIES FOR HEAT EXCHANGERS
3.1 INTRODUCTION
This chapter discusses in detail the methodology considered for the thermal design of the
heat exchangers: an evaporator, a suction line heat exchanger and a gas cooler in three
separate parts. The operating parameters of the heat exchangers are determined using
transcritical CO2 vapour compression cycle. The equations are solved using Engineering
Equation Solver (EES) [Kli 10]. Primarily, the heat exchangers are designed through
parametric study in EES. Further IMSTA ART based on finite volume technique has been
used to evaluate the performance of the heat exchangers. At the end, the heat exchangers are
optimized using IMST ART. The finalized geometric configurations were then released for
manufacturing. The first part deals with a fin and tube evaporator, the second part discusses
a suction line heat exchanger (SLHX) and third part describes a gas cooler for the CO2
transcritical air conditioning system.
3.2 EVAPORATOR
The evaporator is the heat absorbing fin and tube type heat exchanger used for the cooling
and dehumidification of room air. The effectiveness-NTU method has been employed for
the thermal design of the plain-fin and tube evaporator. For the better understanding of CO2
evaporation heat transfer, the two-phase ‘flow pattern’ based phenomenological boiling heat
transfer and frictional pressure drop models have been used.
The analytical modeling of the plain-fin and tube evaporator is explained in details below.
The CO2 refrigerant flows through tubes expanded against the fins and air flows over the
tube-bank and fins assembly in cross-flow arrangement.
Following are assumptions considered in parametric analysis of heat exchangers.
steady state heat transfer between the fluids
CO2 is considered as a pure substance
pressure drop is assumed negligible for thermal design calculations
no internal heat generation in the evaporator
heat loss to or from the surroundings is negligible
uniform distribution of refrigerant and air flows
54
condensation of water vapor in ambient air on evaporator surface is negligible
tube-to-tube conduction through fins is neglected
longitudinal heat conduction is not considered
3.2.1 Mathematical model description
The simulation has been done for plain and fin tube type evaporator using EES. The one-
dimensional equations are solved in EES. The geometry of the plain and fin type evaporator
has been defined in the program. The thermo-physical properties of refrigerant and air are
calculated with the help of in-built fluid property database REFPROP [LHM 07].
For parametric evaluation, the ‘Effectiveness-NTU’ method is employed. The overall
conductance (UA) has been evaluated through finding out individual thermal resistance in
the heat flow path. From knowledge of ‘UA’ and minimum heat capacity rate, number of
transfer units (NTU) are calculated, which is in turn give the evaporator effectiveness. The
actual evaporator capacity has been estimated from the effectiveness and maximum heat
transfer units possible between both fluids.
For constant evaporator capacity, the evaporator geometry is finalized iteratively such that
the superheated refrigerant (CO2) temperature at evaporator exit does not exceed 20oC over
a range of ambient air temperatures. Finally, the refrigerant (CO2) side two-phase and
ambient air-side pressure drops are calculated.
The overall conductance ‘UA’ of the evaporator is inverse of the total thermal resistance
between refrigerant (CO2) and air, ‘Rtotal’, which can be found by summing all of the
thermal resistances in series as follows,
where, ‘Rin’ is the convection resistance between refrigerant CO2 and inner tube surface,
‘Rf,in’ is refrigerant side fouling resistance, ‘Rcond’ is the tube-wall conduction resistance,
and ‘Rout’ is resistance between air and the outer surface of the plain-fins and tubes.
The resistance between refrigerant (CO2) and tube inside surface can be represented as,
Where, is the average heat transfer coefficient of refrigerant. The refrigerant side heat
transfer coefficient calculation procedure is explained in section 3.8. ‘Di’ is the tube inner
diameter found as,
55
‘Do’ is the tube outer diameter, is the tube wall thickness, Wc is the length of heat
exchanger normal to air flow direction, and Nt is total number of tubes found as,
Where, Nt,c is number of tube columns, and Nt,r is number of tube rows. The tube wall
conduction thermal resistance is found as,
Where, ktube is the tube material thermal conductivity. The resistance between air and the
outer surface of the heat exchanger ‘Rout’ can be expressed in terms of an overall surface
efficiency, , as follows,
Where, At,2 is total heat transfer surface area available on air side which is the sum of finned
i.e. secondary surface area As, and un-finned tube surface i.e. primary surface area Ap.
These areas are found as follows,
Where, is fin thickness, and Nfin is the number of fins found as,
Where, Pfin is fin spacing (or fin pitch).
Where, Hc and Lc are the height and depth of heat exchanger core respectively and are
calculated by equation 3.10 and 3.11.
Where, Pt and Pl are the transverse and longitudinal tube spacing respectively. The average
heat transfer coefficient on air-side is found as follows,
56
Where, jc is Colburn j-factor - the dimensionless heat transfer coefficient of air, cph is
specific heat of air, Prh is Prandtl number of air.
The air-side heat transfer coefficient calculation procedure is given in section 3.9 of this
chapter. In equation (3.12), is the mass flux of air, which is found as,
Where, is the mass flow rate of air, and is the minimum free flow area available
on air side determined by equation 3.14.
The overall surface efficiency is related to the fin efficiency and calculated by
equation 3.15.
The fin efficiency calculation procedure is outlined in detail, in section 3.10.
The refrigerant side fouling resistance is found as,
Where, Ffoul is the refrigerant side fouling factor.
Once, an overall conductance UA of the evaporator is found from equations (3.1), (3.2),
(3.5), (3.6), and (3.16) then number of transfer units ‘NTU’ is calculated by equation 3.17.
Where, Cmin is the minimum heat capacity rate.
57
In evaporation heat transfer, heat capacity rate of the hot fluid is usually taken as the
minimum. Also, for evaporative heat transfer, the heat capacity rate ratio (Cr = Cmin/Cmax)
becomes equal to zero. Hence, effectiveness of the evaporator is found as,
Once effectiveness is found, the capacity of evaporator is calculated as follows,
Where, Th,i and Tc,i are the inlet temperatures of hot and cold fluids respectively. Then,
outlet temperature of hot fluid Th,o is found from following heat balance,
The enthalpy of refrigerant at outlet hc,o is found from the knowledge of heat balance on
refrigerant side as follows,
Now the enthalpy of CO2 at outlet is compared with the saturation enthalpy hc, sat of
refrigerant. If ( ), CO2 is still in the two-phase region.
In such a case mass flow rate of CO2 and/or volume flow rate of air is adjusted till the
refrigerant at outlet is in superheated vapor condition.
If ( ), the refrigerant (CO2) is in superheat region.
The temperature of superheated refrigerant CO2 at an evaporator exit is calculated from
equation below,
In equation 3.22, hc,sat and Tc,sat are enthalpy and temperature of refrigerant vapor, and the
only unknown is the outlet temperature of refrigerant Tc,o.
In this way, the capacity of an evaporator for given geometry and thermo-physical
properties of fluids, is calculated using the effectiveness-NTU method of heat exchanger
design.
The details of thermal design of evaporator are briefly explained in form of a flowchart
given in Figure 3.1.
58
Figure 3.1: Flowchart for thermal design of an evaporator
3.2.2 Flow patterns during co2 evaporation
Flow patterns are very important in understanding the very complex two-phase flow
phenomena and heat transfer trends in flow boiling. To predict the local flow patterns in a
channel, a flow pattern map is used. Cheng et al. [CRQT 08] has developed flow boiling
Is, 50 ≤ Ġc ≤ 1500 kg/s-m2?
Calculate: Ġh, Ġc,
Start
Read known geometry of evaporator: Do, δtube, Pt, Pl, Nt,r, Nt,c, Wc, δfin, Pfin
Calculate remainder geometry of the evaporator: Di, Nt, Hc, Lc, Lt, Nfin
Read upstream air parameters: Th,i, Ph,i, rhh,i, cph,i, ρh,i, μh,i, kh,i, Prh,i,
Calculate: Afr, At, and Amf on both fluid sides, and βHx of evaporator
Read refrigerant inlet parameters: Tc,i, Pc,i, xc,i, cpc,i, ρc,i, , hc,i, hc,sat
Calculate: Rcond, Rin, uh,f, uh,c, ReDo, RePl, jc, ,
ηfin, ηout, Rout, Rf,in, Rtotal, UA, NTU, ε, Th,o, Tc,o
Adjust
NO
Adjust
and/or
No
End
Is, 9 ≤ Tc,o ≤ 20 oC ?
Display Results
59
heat transfer model based on the Cheng–Ribatski–Wojtan–Thome CO2 flow pattern map
[CRWT 06]. This model accurately predicts changes of trends in flow boiling data, which
indicates the flow patterns such as onset of dry-out and onset of mist flow. In the present
study, the physical properties of CO2 have been obtained from built-in fluid property
function of EES. Based on the quality of CO2 at evaporator inlet (xc,i) and the mass flux
(Ġc), the flow patterns in the flow passage are first determined from the updated flow-
pattern map. In this model accurately accounted the transitions in flow patterns such as
annular flow to dryout (A–D), dryout to mist flow (D–M) and intermittent flow to bubbly
flow (I–B) transition curves.
The void fraction ‘ε’ and dimensionless geometrical parameters ALD, AVD, hLD and PiD used
in the flow pattern map are defined in the equations 3.23 to equation 3.27. Here, ALD is
dimensionless cross-sectional area occupied by liquid phase [-], AVD is dmensionless cross-
sectional area occupied by vapor phase [-], hLD is dimensionless vertical height of liquid
phase of refrigerant [-] and PiD is dimensionless perimeter of interface of vapour and liquid
phase.
Where, the stratified angle, θstrat (which is the same as θdry of Figure 3.2) is calculated using
the equation (3.28) proposed by Biberg, [CRQT 08],
60
Figure 3.2: Stratified two-phase flow in a horizontal channel
The stratified-wavy to intermittent and annular flow (SW–I/A) transition boundary has been
calculated with the Kattan–Thome–Favrat criterion [CRQT 08] as,
Where, the liquid Froude number FrL and the liquid Weber number WeL are defined by
equation 3.30.
Then, the stratified-wavy flow region is subdivided into three zones according the criteria
by Wojtan et al. [CRQT 08],
Ġc > Ġwavy(xIA) gives the slug zone;
Ġstrat < Ġc < Ġwavy(xIA) and x < xIA give the slug/stratified-wavy zone;
x ≥ xIA gives the stratified-wavy zone.
The stratified to stratified-wavy flow (S–SW) transition boundary is calculated with the
Kattan–Thome–Favrat criterion [CRQT 08],
For the new flow pattern map: Ġstrat = Ġstrat(xIA) at x < xIA.
61
The intermittent to annular flow (I–A) transition boundary is calculated with the Cheng–
Ribatski–Wojtan–Thome criterion [CRWT 06] as,
Then, the transition boundary is extended down to its intersection with Ġstrat.
The annular flow to dryout region (A–D) transition boundary is calculated with the new
modified criterion of Wojtan et al. [CRQT 08] based on the dryout data of CO2 in this study
as,
Which, is extracted from the new dryout inception equation in the study as,
The vapor Weber number WeV, vapor Froude number FrV,Mori defined by Mori et al.
[MYOK 00], and the critical heat flux qcrit as per Kutateladze correlation [CRQT 08] are
calculated,
The dryout region to mist flow (D–M) transition boundary is calculated with the news
criterion developed by Cheng et al. [CRQT 08] based on the dryout completion data for
CO2 as,
62
Which, is extracted from the dryout completion equation developed by Cheng et al. [CRQT
08] for Ġmist calculation from,
The intermittent to bubbly flow (I–B) transition boundary is calculated with the criterion,
which arises at very high mass velocities and low qualities as shown in equation 3.41.
If Ġc > ĠB and x < xIA, then the flow is bubbly flow (B). The following conditions are
applied to the transitions in the high vapor quality range,
If Ġstrat(x) ≥ Ġdryout(x), then Ġdryout(x) = Ġstrat(x)
If Ġwavy(x) ≥ Ġdryout(x), then Ġdryout(x) = Ġwavy(x)
If Ġdryout(x) ≥ Ġmist(x), then Ġdryout(x) = Ġmist(x)
3.2.3 CO2 - side heat transfer coefficient
Once the flow patterns present along the flow path are identified, the local heat transfer
coefficients for respective flow patterns are calculated by the procedure outlined below. An
updated general flow boiling heat transfer model based on flow patterns developed by
Cheng et al. [CRT 08] has been used to calculate the local and average heat transfer
coefficients for evaporation heat transfer of CO2. The detailed procedure is given below.
The Kattan–Thome–Favrat general equation for the local flow boiling heat transfer
coefficients htp in a horizontal tube is used as the basic flow boiling expression which is as,
Where, θdry is the dry angle as shown in Figure 3.3 as follows,
63
Figure 3.3: Schematic diagram of liquid film thickness δ, and dry angle θdry [CRT 08]
The dry angle θdry defines the flow structures and the ratio of the tube perimeter in contact
with liquid and vapor. In stratified flow, θdry equals the stratified angle θstrat calculated from
equation (3.28). In annular (A), intermittent (I) and bubbly (B) flows, θdry = 0.
For stratified-wavy flow, θdry varies from zero up to its maximum value θstrat. Stratified-
wavy flow is subdivided into three subzones (slug, slug/stratified- wavy and stratified-
wavy) to determine θdry. For slug zone (slug), the high frequency slugs maintain a
continuous thin liquid layer on the upper tube perimeter. Thus, similar to the intermittent
and annular flow regimes, one has θdry = 0 [CRT 08].
For stratified-wavy zone (SW), the following equation is proposed,
For slug-stratified wavy zone (Slug + SW), the following interpolation between the other
two regimes is proposed for x < xIA,
The vapor phase heat transfer coefficient on the dry perimeter hV is calculated with the
Dittus–Boelter correlation assuming tubular flow in the tube as follows,
Where, the vapor phase Reynolds number ReV is defined as follows,
64
The heat transfer coefficient on the wet perimeter hwet is calculated with an asymptotic
model that combines the nucleate boiling and convective boiling heat transfer contributions
to flow boiling heat transfer by the third power as follows,
Where, hnb, S and hcb are respectively nucleate boiling heat transfer coefficient, nucleate
boiling heat transfer suppression factor and convective boiling heat transfer coefficient and
are determined in the following equations.
The nucleate boiling heat transfer coefficient hnb is calculated with the Cheng–Ribatski–
Wojtan–Thome [CRWT 06] nucleate boiling correlation for CO2 which is a modification of
the Cooper correlation, as follows,
The Cheng–Ribatski–Wojtan–Thome [CRWT 06] nucleate boiling heat transfer suppression
factor S for CO2 is applied to reduce the nucleate boiling heat transfer contribution due to
the thinning of the annular liquid film.
Furthermore for non-circular channels, if Deq > 7.53 mm, then set Deq = 7.53 mm (use
instead of Di for non-circular channels in the equations). The liquid film
thickness ‘δ’ shown in Figure 3.3 is calculated with the expression proposed by El Hajal et
al. [CRT 08] as follows,
Where, the cross sectional area occupied by liquid phase of refrigerant, AL = A (1-ε), based
on the equivalent diameter (Di for circular channels) as shown in Figure 3.2. When the
liquid occupies more than one-half of the cross-section of the tube at low vapor quality,
equation 3.51 would yield a value of δ > Deq/2, which is not geometrically realistic.
65
Hence, whenever equation 3.51 gives δ > Deq/2, δ is set equal to Deq/2 (occurs when ε <
0.5). The liquid film δIA is calculated with equation 3.51 at the intermittent (I) to annular
flow (A) transition. (Note: Deq for non-circular channels, Di for circular channels)
The convective boiling heat transfer coefficient hcb is calculated with the following
correlation,
Where, the liquid film Reynolds number Reδ is defined as,
The void fraction ε is calculated from equation 3.23.
The heat transfer coefficient in mist flow is calculated by a new correlation developed as a
result of modification of the correlation by Groeneveld [CRT 08], with a new lead constant
and a new exponent on ReH according to CO2 experimental data as follows,
Where, the homogeneous Reynolds number ReH and the correction factor Y are calculated
as follows,
The heat transfer coefficient in the dry-out region is calculated by a linear interpolation
proposed by Wojtan-Ursenbacher-Thome as follows [CRT 08],
Where, htp(xdi) is the two-phase heat transfer coefficient calculated with equation 3.42 at the
dry-out inception quality xdi and hM(xde) is the mist flow heat transfer coefficient calculated
with equation 3.54 at the dry-out completion quality xde. Dry-out inception quality xdi and
dry-out completion quality xde are respectively calculated from equation 3.35 and equation
3.40.
66
The vapor Weber number Wev and the vapor Froude number FrV,Mori defined by Mori et al.
[MYOK 00] are calculated from equation 3.36 and equation 3.37, and the critical heat flux
qcrit is calculated with the Kutateladze correlation from equation 3.38. If xde is not defined at
the mass velocity being considered, it is assumed that xde = 0.999.
A heat transfer model for bubbly flow was added by Cheng et al. [CRT 08] to the model for
the sake of completeness. In absence of any data, the heat transfer coefficients in bubbly
flow regime are calculated by the same method as that in the intermittent flow.
3.2.4 Air-side heat transfer coefficient
The work of McQuiston and Parker [Ste 03] is used to evaluate the air-side convective heat
transfer coefficient for a plain-fin and tube heat exchanger with multiple depth-rows of
staggered tubes. The model is developed for dry coils. The heat transfer coefficient is based
on the Colburn j-factor, which is defined as,
Substituting the appropriate values for the Stanton number, Sth, gives the following
relationship for the air-side convective heat transfer coefficient,
Where, cph is the specific heat of air, and Ġair is the mass flux of air through the minimum
flow area which is expressed as,
The minimum free flow area, Amf,2, is calculated from equation 3.14.
McQuiston and Parker used a plain-fin and tube heat exchanger with 4 depth-rows as the
baseline model, and for this model defined the Colburn j-factor as,
and the parameter JP is defined as,
Where, At is the tube outside surface area, and At,2 is the total air side heat transfer surface
area (fin area plus tube area). The Reynolds number, ReDo in the above expression is based
67
on the tube outside diameter, Do, and the mass flux of air, Ġair. The area ratio can be
expressed as,
where Pl is the tube spacing parallel to the air flow (longitudinal), Pt is the tube spacing
normal to the air flow (transverse), Lc is the depth of the evaporator in the direction of the
air flow, Dh is the hydraulic diameter defined as,
and ζ is the ratio of the minimum free-flow area to the frontal area,
The j-factor for heat exchangers with four or fewer depth-rows can then be found using the
following correlation,
Where, z is the number of depth-rows of tubes, and RePl is the air-side Reynolds number
based on the longitudinal tube spacing,
3.2.5 Fin analysis to determine fin efficiency
The plain-fin and tube heat exchangers are widely used in several domains such as heating,
ventilating, refrigeration and air conditioning systems. In practical application of air-to-
refrigerant heat exchangers, the dominant resistance is on the air-side and improving the
accuracy of the analysis of the air-side heat transfer is required by the growing demand of
high performance heat transfer surfaces [PC 03].
The fin performance is commonly expressed in terms of heat transfer coefficient and fin
efficiency, which is defined as the ratio of the actual fin heat transfer rate to the heat transfer
rate that would exist if the entire fin surface was at the base temperature. This case is the
one providing the maximum heat transfer rate because this corresponds to the maximum
driving potential (temperature difference) for the convection heat transfer. Many
68
experimental studies are available in the open literature to characterize the air-side heat
transfer performance for several types of fins used in finned tube heat exchangers. The
established correlations are used for design, rating and modeling of heat exchangers. What
is observed in nearly all published papers is that, whatever the fin type (plain, louvered,
slit), the fin efficiency calculation is always performed by analytical methods derived from
circular fin analysis [PC03].
The analytical circular fin analysis involves a number of assumptions, known as ideal fin
assumptions, which need to be addressed. These assumptions are:
one-dimensional radial conduction,
steady state conditions,
radiation heat transfer negligible,
constant fin conductivity,
constant heat transfer coefficient over the entire fin,
fin base temperature is assumed to be constant,
thermal contact resistance between the prime surface and the fin is negligible,
the surrounding fluid is assumed at constant temperature.
Among the ideal fin assumptions, the first one should be carefully considered because the
actual fin geometry used in plain-fin and tube heat exchanger differs significantly from the
plain circular fin shape. Fin efficiency equations for dry plain circular fins under the
aforementioned assumptions are reported in many handbooks [PC 03]. The analytical
solution for a circular fin, which is the same as for an angular sector of circular fin with
adiabatic fin tip is given by following equation,
Where, In and Kn are the modified Bessel functions of first and second kind.
Several studies have been performed in order to simplify this circular fin efficiency
formulation by avoiding the use of modified Bessel functions. Among all the
approximations, the Schmidt approximation is the most widely used one. Hong and Webb
[PC 03] propose to slightly modify the Schmidt equation (equation 3.69 and 3.70) by using
a modified φ parameter φm (equation 3.71) in equation 3.69, in order to obtain better
accuracy.
69
With this modification, the error between the analytical solution (equation 3.68) and the
approximation does not exceed 2% over the practical range of conditions rf/ro ≤ 6 and m(rf –
ro) ≤ 2.5.
Figure 3.4: Unit cells for inline and staggered tube layouts with plain fins.
Plain-fin and tube heat exchangers are generally composed of continuous flat plate fins. The
fins are metal sheets pierced through the tube bank. The tube lay-out is either inline or
staggered configuration. In order to express the fin efficiency of the continuous plain fins,
the fin is divided in unit cells. Considering that all the tubes are at the same temperature, the
adiabatic zones of the fins determine the unit cells, as presented in Figure 3.4. The
considered fin shape is rectangular for the inline configuration and hexagonal for the
staggered lay-out. Two methods are used in order to calculate the efficiency of these
rectangular or hexagonal fins from the circular fin efficiency with adiabatic fin tip
condition. The most accurate method is the sector method. Nevertheless, being simpler and
more widely used, the equivalent circular fin method is used in this thesis.
70
Gardner and Schmidt [PC 03], in their respective studies, have shown that in the case of
rectangular and hexagonal fins, the fin efficiency could be treated as a circular fin, by
considering an equivalent circular fin radius. For the calculation of the equivalent circular
radius, two approaches are possible. The first one consists in considering a circular fin
having the same surface area as the rectangular or hexagonal fin. The other method is the
Schmidt method in which correlations are developed in order to find an equivalent circular
fin having the same fin efficiency as the rectangular fin (equation 3.72) or the hexagonal fin
(equation 3.73).
Equations 3.69), equation 3.71, and equation 3.73 are used to calculate the fin efficiency of
plain-fins for staggered tube layout.
3.2.6 CO2 - side two-phase pressure drop
A new two-phase frictional pressure drop model for CO2 is developed by Cheng et al.
[CRQT 08] This model has incorporated the updated CO2 flow pattern map, which is used
to calculate two-phase pressure drop during evaporation of CO2. This is a phenomenological
two-phase frictional pressure drop model, which is intrinsically related to the flow patterns.
Based on quality and mass flux of CO2 refrigerant at the evaporator inlet, first the two-phase
flow patterns possible along the flow path are decided as aforementioned in section 3.7. The
total pressure drop is the sum of the static pressure drop (gravity pressure drop), the
momentum pressure drop (acceleration pressure drop) and the frictional pressure drop,
For horizontal channels, the static pressure drop equals zero. The momentum pressure drop
is calculated as,
71
CO2 frictional pressure drop model for annular flow (A) [CRQT 08]: The basic equation is
the same as that of the Moreno Quibén and Thome pressure drop model as,
Where, the two-phase flow friction factor of annular flow fA is calculated by equation 3.77.
This correlation is thus different from that of the Moreno Quibén and Thome pressure drop
model. The mean velocity of the vapor phase uc,v is calculated by equation 3.78.
The void fraction ‘ε’ is calculated using equation 3.23. The vapor phase Reynolds number
ReV and the liquid phase Weber number WeL are based on the mean liquid phase velocity
uc,l .
CO2 frictional pressure drop model for slug and intermittent flow (Slug + I) [CRQT 08]
To avoid jump in the pressure drops between these two flow patterns, the Moreno Quibén
and Thome pressure drop model is updated as given in equation 3.82.
Where, ΔpA is calculated with equation 3.76 and the single-phase frictional pressure drop
considering the total vapor–liquid two-phase flow as liquid flow ΔpLO is calculated by
equation 3.83.
72
The friction factor is calculated with the Blasius equation as,
Where, Reynolds number ReLO is calculated as,
CO2 frictional pressure drop model for stratified-wavy flow (SW) [CRQT 08]: The equation
is kept the same as that of the Moreno Quibén and Thome pressure drop model as,
Where, the two-phase friction factor of stratified-wavy flow fSW is calculated with the
following interpolating expression (a modification of that used in the Moreno Quibén and
Thome pressure drop model) based on the CO2 database as,
and the dimensionless dry angle θ*dry is defined as,
For θdry in the stratified-wavy regime (SW), the following equation is proposed,
The single-phase friction factor of the vapor phase fV is calculated as,
Where, the vapor Reynolds number is calculated with equation (3.79).
CO2 frictional pressure drop model for slug-stratified wavy flow (Slug + SW) [CRQT 08]:
The authors propose to avoid any jump in the pressure drops between these two flow
patterns and to updated the Moreno Quibén and Thome pressure drop model as,
73
Where, ΔpLO and ΔpSW are calculated with equation 3.83 and 3.86 respectively.
CO2 frictional pressure drop model for mist flow (M) [CRQT 08]:
The following expression is kept the same as that in the Moreno Quibén and Thome
pressure drop model as,
The homogenous density ρc,h is defined as,
Where, the homogenous void fraction εh is calculated as,
And the friction factor of mist flow fM was correlated according to the CO2 experimental
data, which is different from that in the Moreno Quibén and Thome pressure drop model by
equation 3.95.
The mist flow Reynolds number is defined as,
Where, the homogenous dynamic viscosity is calculated as proposed by Cicchitti et al.
[CLSS 60] in equation 3.97.
The constants in equation (3.95) are quite different from those in the Blasius equation.
According to Cheng et al. [CRQT 08], the reason is possibly because there are limited
experimental data in mist flow in the database and also perhaps a lower accuracy of these
experimental data. Therefore, Cheng et al. [CRQT 08] feel the need for more accurate
74
experimental data in mist flow to further verify this correlation or modify it if necessary in
the future.
CO2 frictional pressure drop model for dryout region (D) [CRQT 08]:
The linear interpolating expression is kept the same as that in the Moreno Quibén–Thome
pressure drop model as,
Where, Δptp(xdi) is the frictional pressure drop at the dryout inception quality xdi and is
calculated with equation 3.76 for annular flow or with equation 3.86 for stratified-wavy
flow, and ΔpM(xde) is the frictional pressure drop at the dryout completion quality xde and is
calculated with equation 3.92. xdi and xde are calculated with equations 3.35 and 3.40
respectively.
CO2 frictional pressure drop model for stratified flow (S) [CRQT 08]:
The Cheng et al. [CRQT 08] found that no data fell into this flow regime but for
completeness, they kept the method the same as that in the Moreno Quibén and Thome
pressure drop model as,
Where, the mean velocity of the vapor phase uc,v is calculated with equation 3.78 and the
two-phase friction factor of stratified flow is calculated as,
The single-phase friction factor of the vapor phase fV and the two-phase friction factor of
annular flow fA are calculated with equation 3.90 and equation 3.77 respectively, and the
dimensionless stratified angle θ*strat is defined as,
Where, the stratified angle θstrat is calculated with equation 3.28.
Where, ΔpLO and are calculated with equation 3.83 and 3.99 respectively.
75
CO2 frictional pressure drop model for bubbly flow (B) [CRQT 08]: In their study, the
authors found no data available for this regime but keeping consistency with the frictional
pressure drops in the neighboring regimes and following the same format as the others
without creating a jump at the transition (there is no such a model in the Moreno Quibén
and Thome pressure drop model), the following expression is proposed as,
Where, ΔpLO and ΔpA are calculated with equation 3.83 and 3.76 respectively.
According to Cheng et al. [CRQT 08], further experimental data are needed to verify or
modify this model for bubbly flow regime.
3.2.7 Air-side pressure drop
According to Rich, the air-side pressure drop can be divided into two components, the
pressure drop due to the tubes, Δptubes, and the pressure drop due to the fins, Δpfin. The work
of Rich [Wri 00] is used to evaluate the air-side pressure drop due to the fins, which is
expressed as,
where, ffins is the fin friction factor, vm is the mean specific volume of air, Ġh is mass flux of
air, As is the finned (secondary) surface area, and Amf,2 is the air-side minimum free flow
area. In experimental tests, Rich found that the friction factor is dependent on the Reynolds
number, but it is independent of the fin spacing for fin density between 3 and 14 fins per
inch. In this range of fin density, Rich expresses the fin friction factor as,
Where, the Reynolds number RePl is based on the tube longitudinal spacing, Pl,
To determine the pressure drop over the tubes, the relationships developed by Kim-Youn-
Webb [Jia 03] are used. The tube-side friction factor and pressure drop is expressed as,
76
where, Pt is tube transverse pitch, Do is tube outside diameter, At,o is tube outside surface
area, and ReDo is air-side Reynolds number based on tube outside diameter found as,
3.2.8 Modification in IMST ART for evaporator
The geometry of an evaporator finalized using Engineering Equation Solver (EES) [Kli 10]
is further modified in IMST ART [CGMB 02]. The geometry and performance parameters
of individual components have an effect on the system energy performance. In case of an
evaporator, the parameters like air side pressure drop, refrigerant pressure drop, refrigerant
flow circuits, tube longitudinal and lateral pitch, overall refrigerant charge, refrigerant side
pressure drop etc. have effect on the system overall performance parameters. The geometry
of an evaporator is further fine tuned through the parametric simulation study to achieve
maximum energy performance of the system for the rated conditions.
3.3 SUCTION LINE HEAT EXHANGER (SLHX)
A SLHX is used to transfer heat from supercritical high pressure and temperature CO2 to
subcritical low pressure and low temperature CO2. The transfer of heat results in the cooling
of the supercritical gas or liquid and heating of the subcritical CO2 vapor. This transfer of
the heat has impact on the performance of the transcritical CO2 cycle. The literature review
has shown that a SLHX in the cycle increases the Coefficient of Performance (COP) of the
cycle in the range 5% to 10%.
This part focuses on developing the mathematical iterative method to predict the heat
transfer coefficient as well as pressure drop for a straight tube in tube type heat exchanger.
Further, the CFD model to predict the heat transfer as well as pressure drop between the
subcritical and supercritical CO2 in a straight tube in tube type heat exchanger has been
discussed.
77
The actual flow arrangement of a SLHX is shown in Figure 3.5. The SLHX is a straight
tube in tube counter flow type heat exchanger. The subcritical CO2 refrigerant flows in the
core and supercritical CO2 refrigerant flows in the annulus.
Figure 3.5: Tube in tube type suction line heat exchanger
For simulation of SLHX, the available data are inlet temperatures sides supercritical and
subcritical, mass flow rates on both the sides, working pressure on both the sides and
standard sizes of the diameters.
Following assumptions are considered for the evaluation of various parameters of SLHX.
CO2 is considered as a pure fluid.
Negligible pressure drop
Heat exchanger operates under steady state conditions.
No heat generation in the heat exchanger.
Heat losses to or from the surroundings are negligible.
Longitudinal heat conduction in the fluid and in the wall is not considered.
3.3.1 Mathematical model
A computer code has been developed in Engineering Equation Solver (EES) to study effects
of geometry and operating parameters on the thermal performance of a SLHX. EES
calculates the thermo-physical properties with respect to pressure and temperature using in-
build fundamental equations of state for CO2. EES solves equations by Newton - Raphson
iterative method [Kli 10]. To consider the variation of thermo-physical properties, the entire
length of a SLHX has been divided equally into several discrete segments (∆L) as shown in
Figure 3.6. At each segment, outlet temperature is calculated based on the outlet
temperature and pressure of the previous segment. The outlet temperature of first segment is
considered as the inlet temperatures to the next segment, in this manner it repeats until the
to expansion valve
(supercritical CO2 outlet)
to compressor
(subcritical CO2
outlet)
from gas cooler
(supercritical CO2 inlet) from
receiver/evaporator
(subcritical CO2 inlet)
78
last segment of the tube. This has helped in grabbing accurately the fast changing properties
of CO2 in the computer program.
Fig. 3.6: Mathematical model of a SLHX
3.3.2 Simulation
Figure 3.7 provides an algorithm that needs to provide input parameters: inner diameter of
core tube and outer tube, outer diameter of core tube, operating mass flow rates and
pressures of both the sides, inlet temperature of supercritical CO2. An algorithm is required
to guess outlet temperature of subcritical CO2 to begin the iterations of the program. This
program first calculates the length of the each segment and then it calculates fluid
properties, Reynolds numbers, friction factors, heat transfer coefficients and overall heat
transfer coefficient with respect to temperatures and pressures for each segment. Finally, it
calculates the overall heat transfer for the entire length of a SLHX.
This program differs in working out Nusselt numbers for the subcritical and supercritical
CO2. The research work has evaluated different correlations for Nusselt numbers for both
the subcritical and supercritical CO2.
1. Petukhov and Kirillov et al. correlation for subcritical region
Equation 3.110 [Petukhov and Kirillov et al] predicts the heat transfer coefficient for single-
phase, forced convective, turbulent flow in a smooth pipe in the range of 0.5< Pr < 2000 and
3000 < Re < 5× 106
with 10% accuracy [K03].
Where,
supercritical
co2 inlet
temperature
assume
subcritical co2
outlet
temperature
supercritical co2 flow
(annular side)
subcritical co2 flow
(inner side)
inner tube thickness
79
Figure 3.7: Flow chart for thermal calculations
Input for IHE: Dimensions (di, do, Di), Mass Flow Inlets (mc, mh), Operating
Pressures (Pc, Ph), Temperatures (Tc,i, Th,i, Tw), Length Spacing (∆L)
Calculate: Areas (A, Ac, Ah),
Calculate: Fluid Properties (i.e. µc,i, µh,i, µw,i ,ρc,i, ρh,i ,ρw,i ,Cpc,i, Cph,i,
Cpwi, Prc,i, Prh,i) for i=1 to i= n
Calculate: Velc,i, Velh,i, Velw,i ,Rec,i, Reh,i ,Rew,i ,fc,i, fh,i ,Nuc,i, Nuh,i,
Nuw,i, hc,i, hh,i, U,i for i=1 to i= n
Calculate Outlet Temperatures using LMTD: Tc, i+1, Th, i+1 for i=1 to i= n
No
Yes
Guess Tc,i
Length [i] = (i-1)*∆L
Stop
End Loop
If Tc, i+n = 283 K
duplicate i = 1, n
80
2. Pitla et al. correlation for supercritical region
The correlation of Pitla et al. [PGR 01] has been used to predict the heat transfer coefficient
of supercritical CO2 during in-tube cooling. The correlation is given in Equation 3.111.
Where, Gnielinski correlation is used to calculate both Nusselt numbers Nuwall and Nubulk.
Here, subscripts ‘wall’ and ‘bulk’ represent that properties are evaluated at wall temperature
and bulk flow temperature respectively.
Where,
3. Chang et al. correlation for supercritical region
The correlation of Chang et al. [SP 05] has been used to evaluate the heat transfer
coefficient and pressure drop during gas cooling process of CO2 in supercritical region. The
authors have provided the separated correlations for region above and below the pseudo-
critical temperature (Tb/Tpc >1 and Tb/Tpc ≤ 1) on the thermodynamic property chart for
CO2.
The predicted heat transfer coefficient by new proposed correlation is within the accuracy of
10% with the experiment data.
The outlet temperatures of each segment are calculated by equating LMTD and energy
balance equations as shown by equations 3.114 and 3.115 respectively.
The outlet temperatures of first segment are considered as inlet temperature to the next
segment. In this manner, calculation repeats until the nth
segment and finally at segment i =
n, the gives the outlet temperature of the supercritical CO2 and inlet temperature of the
subcritical CO2. If temperature of the subcritical CO2 at i = n is equal to the guess
81
temperature of the subcritical CO2, then solution stops else need to adjust the guess value of
the outlet temperature of the subcritical CO2 at i = 1.
Figure 3.8: Flow chart for the pressure drop calculations
3.3.3 Pressure drop in a SLHX
An algorithm shown in Figure 3.8 provides the basic structure of the program to calculate
Reynold number and friction factor at bulk temperatures on the entire length of a SLHX.
This program uses Filonenko friction factor correlation for subcritical region and Petrov -
Popov friction factor correlation for supercritical region.
1. Filonenko's friction factor for subcritical region
Filonenko friction factor correlation 3.116 is widely used for the turbulent gas flow in
smooth tubes.
2. Petrov and Popov friction factor for supercritical region
Calculate: Heat Transfer & cross
sections Areas (A, Ac, Ah),
Calculate: Fluid & Solid Properties
Calculate: Velc, Velh, Velw, Rec, Reh, Rew, c, h
Calculate Pressure Drop ( )
Inputs: Dimensions (di, do, Di), Mass Flow Inlets (mc, mh), Operating Pressures
(Pc, Ph), Inlet, Outlet & wall Temperatures (Tc,i, Tc,o, Th,i, Th,o, Tw), Length (L)
Stop
82
Petrov and Popov calculated the friction factor of CO2 cooled in the supercritical conditions
in the range of Rewall = 1.4×104 -7.9×10
5 and Rebulk = 3.1×10
4- 8×10
5. Petrov and Popov
obtained an interpolation equation 3.117 of the friction factor.
ρ
ρ
Where fw, the friction factor is calculated by Filonenko Eqution 3.116 [Fil 48] at tube wall
temperature and the exponent ‘s’ is given by,
… (3.118)
3.3.4 Numerical model
A SLHX is numerically modeled using Computation Fluid Dynamic (CFD) technique. CFD
is a technique to solve the set of nonlinear highly coupled partial differential equations to
governing the fluid flow and associated phenomenon like heat transfer, combustion, particle
interaction etc.
Figure 3.9: CFD Process
Viscous
Model
Boundary
Conditions
Initial
Conditions
Convergent
Limit
Contours
Precisions
(single/
double)
Numerical
Scheme
Vectors
Streamlines
Verification
Geometry
Select
Geometry
Geometry
Parameters
Physics Mesh Solve Post-
Processing
Compressible
ON/OFF
Flow
properties
Unstructured Steady/
Unsteady Forces
Report
XY Plot
Domain
Shape and
Size
Heat
Transfer
ON/OFF Structured
Iterations/
Steps
Validation
Reports
83
Figure 3.9 shows in detail the process of CFD. First the geometry has to be created with the
consideration of some CFD modeling constraints. This geometry then needs to be meshed.
Meshing or grid generation is a process in which the domain of interest is discretized in the
finite volumes. Appropriate models, such as the k – turbulence models, boundary
conditions and solver parameters are assigned as per the analysis requirements. Solver
solves the various governing equations iteratively to attain the defined convergence criteria.
The continuity, energy and momentum balance equations basically solved using CFD
algorithm.
3.3.5 Numerical simulation for a SLHX
For this study, the geometric model was created in commercial CAD software - Ideas. The
tubes having inner diameters of core and outer tubes are 5 mm and 10.92 mm respectively
with 0.5 mm wall thickness. The length of a SLHX was used 1 m. The pre-processing
software Gambit was used to mesh the computational model of a SLHX. The unstructured
non-uniform mesh with 2.9 105 cells are used to discretize the main computational model
as shown in Figures 3.10 and 3.11.
The boundary conditions are define as follows,
1. Mass flow inlet – for both subcritical and supercritical refrigerant inlets
2. Pressure outlet – for both subcritical and supercritical refrigerant outlets
3. Fluid domain – for both subcritical and supercritical refrigerants
4. Solid domain – for thickness of the inner pipe
5. Wall with no slip – rest of the surfaces
Figure 3.10: Isometric view of enlarged CFD model
84
Figure 3.11: Side view of CFD model
The double precision solver scheme was used for simulations. The convection term in the
governing equations was modeled with the bounded second-order upwind scheme. The
SIMPLE scheme is used for coupling the pressure and the velocity field. The thermo-
physical properties of the subcritical and supercritical CO2 were taken as a function of
temperature and pressure in the form of polynomial equations.
Under turbulent flow conditions, the standard k–ε model was employed with standard wall
functions. The numerical solution converged when the residuals for all equations below the
1e-05. Simulations were done at operating pressures ranging from 95 to 115 bar and the
mass flow rate ranging from 0.011 kg/s to 0.017 kg/s to find out the outlet temperatures and
pressure drops of a SLHX.
3.4 GAS COOLER
The fin and tube gas cooler is used to reject heat to the atmosphere in CO2 air conditioning
system. This chapter discusses in detail the methodology adopted for the simulation and
design of the fin and tube gas cooler. The simulation is worked out for predicting the heat
transfer as well as pressure drops for a plain fin and tube gas cooler using different
correlations. Finally, IMST ART for further fine tuning the geometrical configuration of the
gas cooler.
The simulation has been carried for parametric simulation of a fin and tube gas cooler with
analytical correlations for refrigerant CO2 and air. Further, optimization of the geometry of
a gas cooler for maximum heat rejection capacity by single parameter at one time marching
method has been worked out.
85
3.4.1 ANALYTICAL MODEL
The parameters of a fin and tube gas cooler are evaluated in Microsoft Office Excel
Spreadsheet program. The actual flow arrangement of the fin and tube gas cooler for air
conditioning system with CO2 as a refrigerant is shown in Figure 3.12, which is single pass,
unmixed-unmixed, four pass – three circuit staggered tube arrangement fin and tube gas
cooler. The transcritical CO2 refrigerant flows through the tubes and it is cooled by the
atmospheric air. The schematic arrangement of fin spacing and frontal plain fin and tube gas
cooler view is as shown in Figure 3.13.
Figure 3.12: Staggered tube layout of a gas cooler
(a) Fin spacing arrangement (b) Four pass - three circuit staggered
tube gas cooler arrangement
Figure 3.13: Frontal view of a fin and tube gas cooler
86
Figure 3.14: Flow chart for simulation of heat transfer coefficient
The assumptions made are: CO2 is considered as a pure fluid, a gas cooler is a four pass
with three-circuit cross flow, both fluids unmixed, staggered tube heat exchanger, steady
state processes in the gas cooler, no internal heat generation in the heat exchanger and
NTU-ε method is considered for the thermal design.
The algorithms of evaluation of heat transfer coefficient and pressure drop in gas cooler are
shown in Figure 3.14 and Figure 3.15 respectively. Microsoft Office Excel spread sheets are
used to carry out the 1-D calculation for fin and tube gas cooler. The Thermo-physical
Input parameters: PGC; L1; L2; L3; ID; OD;
Pt; Pl; Nt; mair; mref; Fd; Fs; tf
Estimate thermo physical
Properties for CO2 and air
Calculate surface geometric properties for air
side: Core volume; Ao; Amin air; At
Calculate surface geometric properties for fin
side: Core volume; Asf; Nf; Lf; M; ɸ; Re/rt
Evaluate:
ηFin; ηo
Estimate: Vair; Gair: Reair;
Dh; Vref; Gref; Reref
Determine: Colburn j
factor and Nusselt number
Calculate:
HTC and OHTC
Evaluate: Uo; NTU; ɛ
87
properties for transcritical CO2 are taken from NIST database [LHM 07]. The operating
conditions considered for the base line gas cooler are as per Table 6.1 and the geometry of
the base case gas cooler model is given in Table 6.2. Table 6.3 provides the summary of
different correlations with their range for geometrical parameter to which they are
applicable. This study has provided evaluation of different correlations for geometrical
parameters namely tube diameter, longitudinal tube spacing, transverse tube spacing, fin
spacing and number of tube rows with respect to present simulation study as shown in
Figure 3.16.
To calculate the overall air side fin surface efficiency for a plain-fin and tube heat
exchanger with multiple rows of staggered tubes arrangement, hexagonal fin into circular
shape to avoid cumbersome numerical conversion required to solve the equations.
Figure 3.15: Flow chart for simulation of pressure drop
3.25.1 Fin Analysis
For calculation of the overall air side fin surface efficiency (ηo), for a fin and tube heat
exchanger with multiple rows of staggered tubes the correlation of Creed Taylor [Tay 04]
Input parameters: PGC; L1; L2; L3; ID; OD;
Pt; Pl; Nt; mair; mref; Fd; Fs; tf
Estimate thermo physical
Properties for CO2 and air
Calculate surface geometric properties for air
side: Core volume; Ao; Amin air; At
Calculate surface geometric properties for
refrigerant side: Core volume; Ai; Amin; As
Estimate: Vair; Gair: Reair;
Dh; Vref; Gref; Reref
Determine friction factor f
and Nusselt number
Calculate: ∆p
88
has been used and hexagonal shaped fins as shown in Figure 3.16. The shape of fin has
been modified from hexagonal to circular as shown in Figure 3.17 to avoid cumbersome
numerical correlation required to solve the equations.
Fig. 3.16 Configuration for staggered tube along with hexagonal fins
Figure 3.17 Cross section for continuous circular fins
The air side fin efficiency calculated by equation 3.126.
fin
o fin
o
Aη =1- 1- η
A … (3.126)
The fin efficiency of a circular fin is calculated using equation 3.127.
t
fin
t
tanh mrφη =
mrφ … (3.127)
Pdiag
89
Where, m is the standard extended surface parameter, which is defined as,
o
fin f
2hm =
k .t … (3.128)
The fin efficiency parameter for a circular fin, φ is calculated using equation 3.129.
e e
t t
R Rφ= -1 1+0.35ln
r r
… (3.129)
Where, the equivalent circular fin radius, Re, is calculated using equation 3.130.
t
e l
tt t
XR X2= 1.27 -0.3
Xr r2
… (3.130)
2tdiag l
PP = + P
2
… (3.131)
Rich correlation [Ric 73] is considered to work out air side heat transfer coefficient for the
simulation of air side plain fin and tube gas cooler.
... (3.132)
Air side Nusselt number is calculated by using most familiar Colburn’s equation 3.133.
Colburn
0.3333
u e rN = j.R .P … (3.133)
Based on the experimental data on gas cooling of supercritical carbon dioxide, Yoon et al.
suggested an empirical correlation using the modified form of Dittus-Bolter’s correlation.
The correlation (equation 3.133) suggested by Yoon have an average deviation of 1.6%, the
absolute average deviation of 12.7% and the RMS deviation of 20.2%.
.
0.14, 0.69, 0.66, 0.......
0.013, 1.0, 0.05, 1.6.......
n
pcb c
u e r
pc
pc
N = a.R P
a b c n T T
a b c n T T
… (3.134)
Rich developed plain fin coil correlations for Fanning friction factor based on data from
eight coil configurations (equation 3.135).
-0.5f = 1.70.R ..........3 N 14fins/inr e fL … (3.135)
airR
-0.35j = 0.195* Re
90
3.4.2 Refrigerant side pressure drop
Petukhov’s correlation given in Equation 3.136 is used to calculate the friction factor.
-2
f = 0.790lnR -1.64e … (3.136)
Table 3.1 Operating conditions of baseline gas cooler
Inlet air temperature [oC] 40 Mass flow rate of air [kg/sec] 0.26
Refrigerant inlet temp. [oC] 106 Velocity of air [m/sec] 2.55
Refrigerant outlet temp. [oC] 42 Mass flow rate of refrigerant [kg/sec] 0.0069
Inlet refrigerant pressure [bar] 90 Velocity of refrigerant [m/sec] 0.9254
Table 3.2 Geometry of base case gas cooler
Tube inner diameter [mm] 4.75 Tube material Cu
Tube length [mm] 550 Fin material Al
Transverse tube spacing [mm] 25 Fin spacing [mm] 1.37
Longitudinal tube spacing [mm] 18 Fin density [fpi] 16
Number of tube rows [nos.] 4 Fin thickness [mm] 1.27
3.5 SUMMARY
The thermal design of plain-fin and tube evaporator is done using Effectiveness-NTU
method. The two-phase flow pattern based phenomenological boiling heat transfer and
frictional pressure drop models are used to study CO2 evaporation. The air-side heat transfer
coefficient was calculated using the work of McQuiston and Parker, while the air-side
pressure drop was calculated using the works of Rich and Kim-Youn-Web. The efficiency
of plain-fins was calculated by equivalent annular fin method using Schmidt approximation.
The variation in the thermo-physical properties of CO2 have been grabbed accurately in the
mathematical as well as numerical model. Petukhov and Kirillov et al. correlations are used
for the heat transfer analysis of the subcritical CO2 flow. Pitla et al. and Cheng et al.
correlations are used for the heat transfer study of the supercritical CO2 flow. CFD has also
considered for analysis of heat transfer across a tube in tube type straight SLHX. The
pressure drop study for supercritical and subcritical CO2 flow is carried out using Petrov and
Popov friction factor and Filonenko's friction factor correlations respectively.
91
A gas cooler is simulated used Microsoft Excel spreadsheet program through one -
dimensional equations. Rich correlations are used for the heat transfer and the pressure drop
study on the air side. Yoon et al. correlation is used refrigerant side heat transfer study and
Petukhon correlation is considered for refrigerant side pressure analysis.
The heat exchangers built through parametric study are later on fine tuned for the
performance and rating in IMST ART considering the overall performance study of the CO2
system.
***