Panel Zone and Rigid Offsets •
5
• Added by Truly Guzman, last edited by Truly Guzman on May 26, 2011
ETABS has the capability to model both, rigid offsets and Panel zones. In order to illustrate the
correct use of both options the following simple examples have been created, all frames have
the same steel frame sections and a lateral load of 10kips applied at the top floor, the rigid
offsets and panel zone have been modified as follows:
Model 1.- Default rigid offsets , rigid zone
factor 0, No panel zone
X-Deflection= 0.133in
This model is the simplest one, and
represents the higher bound for deflections
(conservative) but the lower bound for
moments.
Model 2.- Default rigid offsets, rigid zone
factor 1, No panel zone
X-Deflection=0.104in
This model assume fully rigid offsets,
reports the smallest deflection which is
generally unconservative and is not
recommended. Results for moments are
the highest of the four models
(conservative)
Model 3.- Default rigid offsets, rigid zone
factor 0, Panel zone from column
X-Deflection=0.152in
This model assumes no rigid zone and
panel zone modeled based on column
properties. Deflections are extremely high
due to the fact that flexibility is being
duplicated at joints. Moment is the smallest
of the four models, and is also not
recommended due to unconservative
results.
Model 4.- Default rigid offsets, rigid zone
factor 1, Panel zone from column
X-Deflection=0.128in
This model has fully rigid offsets, and panel
zone modeled based on column properties.
In this case flexibility of joint is correctly
modeled. Results for deflections report a
value in between the upper and lower
bound. Moments as well indicate a good fit
in between extreme bounds. Therefore; this
is generally the best modeling assumption.
NOTES:
• If the first model would be modeled using the user defined lengths option as 0,0 for rigid
offsets instead of default based on connectivity, results will be identical except for the
fact that moments will be reported at end of elements (not a column/beam face)
• A fully rigid zone should never be used in steel frames, usually for concrete frames a
value of 0.5 is recommended. Which I turn indicates that 50% of the actual offset will be
consider rigid
• Rigidity will only affect bending in the 3 axis of the frame, not torsion, not axial
properties.