94
Second Correlating Revision No. 60-NFPA 101-2016 [ Detail ] 38.3.4.5 Risk Analysis for Mass Notification. 38.3.4.5.1 A risk analysis in accordance with Section 9.14 shall be performed for business occupancies requiring a fire alarm system in accordance with 38.3.4.1 to determine whether a mass notification system is required. Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Dec 06 10:27:22 EST 2016 Committee Statement Committee Statement: Revisions intended for consistency with format of other occupancy chapters Second Revision No. 6501-NFPA 101-2016 [Detail] National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 72 12/13/2016 9:32 AM Page 1 of 94

Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 60-NFPA 101-2016 [ Detail ]

38.3.4.5 Risk Analysis for Mass Notification.

38.3.4.5.1

A risk analysis in accordance with Section 9.14 shall be performed for business occupancies requiring a fire alarm systemin accordance with 38.3.4.1 to determine whether a mass notification system is required.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Dec 06 10:27:22 EST 2016

Committee Statement

Committee Statement: Revisions intended for consistency with format of other occupancy chapters

Second Revision No. 6501-NFPA 101-2016 [Detail]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 72 12/13/2016 9:32 AM

Page 1 of 94

Page 2: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 61-NFPA 101-2016 [ Detail ]

38.3.4.5.2*

A risk analysis in accordance with Section 9.14 shall be performed for business occupancies containing a classroom where thebuilding is owned, rented, leased, or operated by a college or university to determine whether a mass notification system is required.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Dec 06 10:30:48 EST 2016

Committee Statement

Committee Statement: Revisions intended for consistency with format of other occupancy chapters

Second Revision No. 6502-NFPA 101-2016 [Detail]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 72 12/13/2016 9:32 AM

Page 2 of 94

Page 3: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ]

Replace the term "delayed egress electrically locking system" with "delayed egress electrical locking system" throughoutthe Code.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 08:14:17 EST 2016

Committee Statement

CommitteeStatement:

It is noted that Correlating Committee Note (CCN)-4 was inadvertently not converted to a public comment. This Global SCR isneeded for consistency with the revision of the term in Ch. 7 via CCN-7 (PC-8). See 12.2.2.2.3; 13.2.2.2.3; 14.2.2.2.3.1;15.2.2.2.3.1; 16.2.2.2.3.1; 17.2.2.2.3.1; 18.2.2.2.4; 19.2.2.2.4; 20.2.2.2.8; 21.2.2.2.8; 28.2.2.2.2.2; 29.2.2.2.2.2; 30.2.2.2.2.2;31.2.2.2.2.2; 32.2.2.5.5.1; 32.3.2.2.2; 33.2.2.5.5.1; 33.3.2.2.2; 36.2.2.2.5; 37.2.2.2.5; 38.2.2.2.6; 39.2.2.2.6; 40.2.2.2.2;42.2.2.2.2 (all references to NFPA 101 2nd Draft ballot version)).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 72 12/13/2016 9:32 AM

Page 3 of 94

Page 4: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 2-NFPA 101-2016 [ Section No. 3.3.155.1 ]

3.3.155.1 Flame Spread Index.

A comparative measure, expressed as a dimensionless number, derived from visual measurements of the spread of flame versustime for a material tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of BuildingMaterials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Burning Building Materials. (SAF-INT)

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 08:59:51 EST 2016

Committee Statement

Committee Statement: Editorial correction.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 72 12/13/2016 9:32 AM

Page 4 of 94

Page 5: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 3-NFPA 101-2016 [ New Section after 3.3.175 ]

3.3.175.1* Open Mall Councourse.

A mall concourse that either (1) has 50 percent or more of the total area of the solid mall concourse perimeter walls and solid roofarea open to the atmosphere with openings distributed uniformly over the length of the mall concourse, or (2) has an approvedopen mall concourse engineering analysis.

Supplemental Information

File Name Description

101_SCR-3_Attachment.docx New A.3.3.175.1

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 09:23:30 EST 2016

Committee Statement

CommitteeStatement:

The SCR copies the definitions of 'open mall concourse' and 'enclosed mall concourse' to Ch. 3 from 36.4.4.2. (Seeattachment for A.3.3.175.1.) In 36.4.4.2(4)(a) and 37.4.4.2(4)(a), editorially add parenthetical reference: "(See 3.3.175.1)." In36.4.4.2(4)(b) and 37.4.4.2(4)(b), add parenthetical reference: "(See 3.3.175.2)."

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 72 12/13/2016 9:32 AM

Page 5 of 94

Page 6: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

A.3.3.175.1 Open Mall Concourse.

An open mall concourse is permitted to serve as the public way provided the open mall concourse

meets the definition of public way in accordance with this Code.

It is intended that the open mall concourse be designed, constructed, and arranged to permit the

natural venting of smoke and other products of combustion to the outside air through openings in the

walls, roof, or combination thereof of the mall concourse.

The solid area of the mall concourse walls and the horizontal projection of the solid area of any roof

structures, including shade structures, awnings, and canopies, that cover the mall concourse should be

summed to determine the aggregate area of solid construction associated with the mall concourse. A

mall concourse can be considered an open mall concourse where at least 50 percent of the aggregate

area of solid construction is open to the atmosphere. Open areas can include entrances to the mall

concourse (e.g., barred gates that allow air to pass through versus an entrance storefront), clearstory

spaces between the mall building (structure that houses tenants) and the roof above, and openings in

the roof assembly. For the openings to be effective, they must also be distributed uniformly over the

length of the mall concourse. Caution must be exercised in the design and construction so as to not

create areas of possible congestion for smoke and hot gases to accumulate, such as a pitched (steep

slope) roof assembly within the mall concourse.

Roof assemblies are permitted to have holes or open areas that represent openings to the outside. The

roof assembly is also permitted to consist of a structure or assembly that allows the venting of the mall

concourse. Examples of these vented roof structures include a roof trellis or an exposed roof structural

frame only with no roofing materials. Structures that would permit the omission of automatic sprinkler

protection, in accordance with NFPA 13, could be included to serve as open space for the purposes of

the calculation of areas open to the outside air. Caution should be taken not to allow vegetation to grow

into and around these structures that could reduce or impede the venting capabilities.

Page 6 of 94

Page 7: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 6-NFPA 101-2016 [ Section No. 7.1.6.5 ]

7.1.6.5* Grab Bars for Bathtubs, Bathtub-Shower Combinations, and Showers.

7.1.6.5.1 General.

7.1.6.5.1.1

Where required by Chapters 11 through 43 , new bathtubs, bathtub-shower combinations, or showers,for use by occupants,shall be provided with grab bars complying with 7.1.6.5.2 through 7.1.6.5.5 , except as otherwise permitted for showersin 7.1.6.5.1.2 , with all dimensions referring to the centerline of the grab bar unless otherwise stipulated.

7.1.6.5.1.2*

Where a dedicated shower does not expose users to changes in elevation exceeding 0.5 in. (13 mm), as described in 7.1.6.2 ,and it provides slip resistance for all surfaces when wet, as a foreseeable condition described in 7.1.6.4 , the requirements of7.1.6.5.2 through 7.1.6.5.5 shall apply only if grab bars are installed.

7.1.6.5.2 Vertical Grab Bar.

A vertical grab bar shall be provided either installed on the control end wall of the bathtub, bathtub-shower combination, or showeras specified in 7.1.6.5.2.1 or as a free-standing external pole as specified in 7.1.6.5.2.2 .

7.1.6.5.2.1* Vertical Grab Bar on Control.End Wall.

A vertical grab bar, with

a minimum length of

24 in. (610 mm), and i ts lower end between 36 and 39 in. (915 and 990 mm) above the finished floor,

shall be installed on the entry/egress side of the control end wall of the bathtub, bathtub-shower combination, or shower unit.

The grab bar shall be located at least 6 in. (150 mm), measured horizontally, from any shower curtain rod fixing point on thewall.

(A)

A vertical grab bar, with a minimum length of 24 in. (610 mm), and its lower end between 36 and 39 in. (915 and 990 mm) abovethe finished floor, shall be installed on the entry/egress side of the control end wall of the bathtub, bathtub-shower combination, orshower unit.

(B)

The grab bar shall be located at least 6 in. (150 mm), measured horizontally, from any shower curtain rod fixing point on the wall.

7.1.6.5.2.2* Vertical Grab Bar as Free Standing, Vertical Pole.

A vertical, pole-type grab bar fixed to the floor and either the room ceiling or an adjacent wall

shall be installed outside of the bathtub, bathtub-shower combination, or shower unit .

within 6 in. (150 mm), measured horizontally, outside of the outer edge of the bathtub, bathtub-shower combination, orshower and

within 30 in. (760 mm), measured horizontally, of the vertical plane of the control end wall if there is such a wall.

7.1.6.5.3 Back Wall Grab Bar.

For bathtubs and bathtub-shower combinations bounded on three sides by walls, a grab bar shall be provided on the back walleither as a diagonal grab bar as specified in 7.1.6.5.3.1 or as a horizontal grab bar as specified in 7.1.6.5.3.2 .

7.1.6.5.3.1* Diagonal Grab Bar on Back Wall.

Diagonal grab bars shall have a length of not less than 24 in. (600 mm).

Diagonal grab bars shall be located so the higher end is closest to the control end wall.

Diagonal grab bars shall be located a maximum of 12 in. (305 mm) from the control end wall.

Diagonal grab bars shall be located 25 in. (635 mm) minimum and 27 in. (685 mm) maximum above the rim of the bathtub.

Diagonal grab bars shall be located so the lower end is 8 in. (203 mm) minimum and 10 in. (254 mm) maximum above therim of the bathtub.

Diagonal grab bars shall be located 28 in. (711 mm) minimum and 30 in. (760 mm) maximum from the control end wall.

A diagonal grab bar shall be installed on the back wall

(A)

A diagonal grab bar shall be installed on the back wall with a minimum length of 24 in. (600 mm) with its higher end placed closerto the control end wall and located a maximum of 12 in. (305 mm) from the control end wall, with a height of 25 to 27 in. (635 to685 mm) above rim of the bathtub.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 72 12/13/2016 9:32 AM

Page 7 of 94

Page 8: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

(B)

The lower end of the diagonal grab bar shall be located at a height of 8 to 10 in. (205 to 255 mm) above the rim of the bathtub and28 to 30 in. (710 to 760 mm) from the control end wall.

7.1.6.5.3.2 Horizontal Grab Bar on Back Wall.

A horizontal grab bar

shall be installed on the back wall at a height of 8 to10 in. (205 to 255 mm) above the bathtub rim with .

one end located a maximum of 12 in. (305 mm) from the control end wall and the other end located a maximum of 24 in.(610 mm) from the opposite, or head, end of the bathtub.

7.1.6.5.4* Grab Bar Details.

7.1.6.5.4.1

Grab bars shall be circular in cross section with a minimum diameter of 1 1 ⁄4 in. (32 mm) and a maximum diameter of 2 in. (51mm).

7.1.6.5.4.2

If attached to a wall, the grab bar shall provide a minimum clearance of 1 1 ⁄2 in. (38 mm) for hand grasp.

7.1.6.5.4.3

The size and clearance dimensions required by 7.1.6.5.4.1 and 7.1.6.5.4.2 shall be provided, as a minimum, within the heightrequirements range and the minimum length requirements range of the other provisions of 7.1.6.5 .

7.1.6.5.5 Grab Bar Structural Loading.

Grab bars shall be designed and constructed to the structural loading conditions in accordance with the building code.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 10:59:35 EST 2016

Committee Statement

CommitteeStatement:

The SCR deletes 7.1.6.5 (and associated Annex A text) in its entirety. Grab bar criteria is to be maintained in Ch. 24. Thefollowing paragraphs are revised to reference Ch. 24 via additional SCRs: 12.2.1.2; 14.2.1.5; 16.2.1.1; 26.2.4; 28.2.1.4;30.2.1.3; 32.2.2.7; 36.2.1.6; 38.2.1.5; 40.2.1.3; 42.2.1.3. Grab bars are not considered part of the means of egress, thereforeprovisions do not belong in Ch. 7. The group of related SCRs achieves the needed correlation.

Committee Comment No. 5002-NFPA 101-2016 [Section No. 7.1.6.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 72 12/13/2016 9:32 AM

Page 8 of 94

Page 9: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 19-NFPA 101-2016 [ Section No. 7.2.1.5.10.7 ]

7.2.1.5.10.7

Two releasing operations shall be permitted for educational occupancy classroom doors secured against unwanted entry inaccordance with the provisions of Chapter 15 .

7.2.1.5.10.7

Where permitted by Chapters 11 through 43 , two releasing operations shall be permitted for doors secured against unwantedentry.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:09:42 EST 2016

Committee Statement

CommitteeStatement:

The revision is needed for consistency with several occupancy chapters, which permit two door-releasing operations toaccommodate hardware to prevent unwanted entry.

Second Revision No. 5001-NFPA 101-2016 [Section No. 7.2.1.5.10.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 72 12/13/2016 9:32 AM

Page 9 of 94

Page 10: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 20-NFPA 101-2016 [ Section No. 7.3.1.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 72 12/13/2016 9:32 AM

Page 10 of 94

Page 11: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

7.3.1.2* Occupant Load Factor.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 72 12/13/2016 9:32 AM

Page 11 of 94

Page 12: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

The occupant load in any building or portion thereof shall be not less than the number of persons determined by dividing the floorarea assigned to that use by the occupant load factor for that use as specified in Table 7.3.1.2, Figure 7.3.1.2(a) , and Figure7.3.1.2(b). Where both gross and net area figures are given for the same occupancy, calculations shall be made by applying thegross area figure to the gross area of the portion of the building devoted to the use for which the gross area figure is specified andby applying the net area figure to the net area of the portion of the building devoted to the use for which the net area figure isspecified.

Table 7.3.1.2 Occupant Load Factor

Use (ft2/person)a (m2/person)a

Assembly Use

Concentrated use, without fixed seating 7 net 0.65 net

Less concentrated use, without fixed seating 15 net 1.4 net

Bench-type seating 1 person/18 linear in.1 person/455 linearmm

Fixed seating Use number of fixed seatsUse number of fixedseats

Waiting spaces See 12.1.7.2 and 13.1.7.2.See 12.1.7.2 and13.1.7.2.

Kitchens 100 9.3

Library stack areas 100 9.3

Library reading rooms 50 net 4.6 net

Swimming pools 50 (water surface) 4.6 (water surface)

Swimming pool decks 30 2.8

Exercise rooms with equipment 50 4.6

Exercise rooms without equipment 15 1.4

Stages 15 net 1.4 net

Lighting and access catwalks, galleries, gridirons 100 net 9.3 net

Casinos and similar gaming areas 11 1

Skating rinks 50 4.6

Business Use (other than below) 100 9.3

Concentrated Business Usef 50 4.6

Air Airport traffic control tower observation levels 40 3.7

Day-Care Use 35 net 3.3 net

Detention and Correctional Use 120 11.1

Educational Use

Classrooms 20 net 1.9 net

Shops, laboratories, vocational rooms 50 net 4.6 net

Health Care Use

Inpatient treatment departments 240 22.3

Sleeping departments 120 11.1

Ambulatory health care 150 13

Industrial Use

General and high hazard industrial 100 9.3

Special-purpose industrial NA NA

Mercantile Use

Sales area on street floorb,c 30 2.8

Sales area on two or more street floorsc 40 3.7

Sales area on floor below street floorc 30 2.8

Sales area on floors above street floorc 60 5.6

Floors or portions of floors used only for offices See business use. See business use.

Floors or portions of floors used only for storage, receiving, and shipping,and not open to general public

300 27.9

Mall structuresdPer factors applicable to use of

spacee

Residential Use

Hotels and dormitories 200 18.6

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 72 12/13/2016 9:32 AM

Page 12 of 94

Page 13: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Use (ft2/person)a (m2/person)a

Apartment buildings 200 18.6

Board and care, large 200 18.6

Storage Use

In storage occupancies NA NA

In mercantile occupancies 300 27.9

In other than storage and mercantile occupancies 500 46.5

NA: Not applicable. The occupant load is the maximum probable number of occupants present at any time.

aAll factors are expressed in gross area unless marked “net.”

bFor the purpose of determining occupant load in mercantile occupancies where, due to differences in the finished ground level ofstreets on different sides, two or more floors directly accessible from streets (not including alleys or similar back streets) exist, each

such floor is permitted to be considered a street floor. The occupant load factor is one person for each 40 ft2 (3.7 m2) of gross floorarea of sales space.

cFor the purpose of determining occupant load in mercantile occupancies with no street floor, as defined in 3.3.271, but with accessdirectly from the street by stairs or escalators, the floor at the point of entrance to the mercantile occupancy is considered the streetfloor.

dFor any food court or other assembly use areas located in the mall concourse that are not included as a portion of the grossleasable area of the mall structure, the occupant load is calculated based on the occupant load factor for that use as specified inTable 7.3.1.2. The remaining mall concourse area is not required to be assigned an occupant load.

eThe portions of the mall concourse that are considered a pedestrian way and not used as gross leasable area are not required tobe assessed an occupant load based on Table 7.3.1.2. However, means of egress from a mall pedestrian way concourse arerequired to be provided for an occupant load determined by dividing the gross leasable area of the mall structure building (notincluding anchor stores buildings ) by the appropriate lowest whole number occupant load factor from Figure 7.3.1.2(a) or Figure7.3.1.2(b).

Each individual tenant space is required to have means of egress to the outside or to the mall concourse based on occupant loadscalculated by using the appropriate occupant load factor from Table 7.3.1.2.

Each individual anchor store is required to have means of egress independent of the mall concourse.

fSee A.7.3.1.2.

Figure 7.3.1.2(a) Mall Structure Occupant Load Factors (U.S. Customary Units).

Figure 7.3.1.2(b) Mall Structure Occupant Load Factors (SI Units).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 72 12/13/2016 9:32 AM

Page 13 of 94

Page 14: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:14:13 EST 2016

Committee Statement

CommitteeStatement:

The term 'air traffic control tower' was replaced by 'airport traffic control tower' via a Global FR, but was inadvertentlymissed in Table 7.3.1.2. The revisions to Footnote 'e' are needed for correlation with changes to Chapters 36 and 37.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 72 12/13/2016 9:32 AM

Page 14 of 94

Page 15: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 55-NFPA 101-2016 [ Section No. 7.12.1 ]

7.12.1

Hazardous materials that are stored, used, or stored handled , and that are also classified as high-hazard contents in accordancewith 6.2.2, shall comply with Section 7.11.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 21 09:45:56 EST 2016

Committee Statement

Committee Statement: Revision for consistency with other hazardous materials provisions.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 72 12/13/2016 9:32 AM

Page 15 of 94

Page 16: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 21-NFPA 101-2016 [ Section No. 8.3.4.1.3 ]

8.3.4.1.3

Penetrations shall be installed be protected in accordance with by a tested system, and installed and maintained in accordance withthe manufacturer’s instructions.

Supplemental Information

File Name Description

101_SCR-21_8.3.4.1.3.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:25:17 EST 2016

Committee Statement

Committee Statement: Editorial correction needed as indicated in the ballot abstention by Koffel.

Committee Comment No. 2507-NFPA 101-2016 [Section No. 8.3.4.1.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 72 12/13/2016 9:32 AM

Page 16 of 94

Page 17: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

8.3.4.1.3

Penetrations shall be protected in accordance withby a tested system, andwhich shall be installed

and maintained in accordance with the manufacturer’s instructions.

Page 17 of 94

Page 18: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 22-NFPA 101-2016 [ Section No. 8.4.4.2 ]

8.4.4.2

Where designs take transmission of vibrations into consideration, any vibration isolation shall meet one of the following conditions:

It shall be provided on either side of the smoke partition.

It shall be designed for the specific purpose.

Where vibration isolation of equipment or systems is employed, the vibration restraint(s) shall be located outside of the partition,wall, or floor assembly through which the equipment or systems pass.

Supplemental Information

File Name Description

101_SCR-22_8.4.4.2.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:30:41 EST 2016

Committee Statement

Committee Statement: Editorial revision intended for consistency with 8.3.4.5.

Committee Comment No. 2510-NFPA 101-2016 [Section No. 8.4.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 72 12/13/2016 9:32 AM

Page 18 of 94

Page 19: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

8.4.4.2 Vibration Isolation Equipment or Systems.

Where the vibration isolation of equipment or systems areis employed, the vibration restraint(s)

shall be located outside of the partition, wall, or floor assembly for which the equipment or

systems are passingpass through.

Page 19 of 94

Page 20: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 23-NFPA 101-2016 [ Section No. 8.5.6.7 ]

8.5.6.7

Where designs take transmission of vibrations into consideration, any vibration isolation shall meet one of the following conditions:

It shall be provided on either side of the smoke barrier.

It shall be designed for the specific purpose.

Where vibration isolation of equipment or systems is employed, the vibration restraint(s) shall be located outside of the partition,wall, or floor assembly through which the equipment or systems pass.

Supplemental Information

File Name Description

101_SCR-23_8.5.6.7.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:37:51 EST 2016

Committee Statement

Committee Statement: Editorial revision intended for consistency with 8.3.4.5.

Committee Comment No. 2513-NFPA 101-2016 [Section No. 8.5.6.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 72 12/13/2016 9:32 AM

Page 20 of 94

Page 21: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

8.5.6.7 Vibration Isolation Equipment or Systems.

Where the vibration isloation of equipment or systems areis employed, the vibration restraint(s)

shall be located outside of the partition, wall, or floor assembly for which the equipment or

systems are passingpass through.

Page 21 of 94

Page 22: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 56-NFPA 101-2016 [ Section No. 8.7.3.1 ]

8.7.3.1

Where required by the provisions of Chapters 11 through 43, occupancies with storage, use, and handling of hazardous materialsshall comply with the following codes unless otherwise modified by other provisions of this Code: NFPA 30, NFPA 54, NFPA 55,NFPA 58, NFPA 400, and NFPA 495.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 21 09:47:51 EST 2016

Committee Statement

Committee Statement: Revision for consistency with other hazardous materials provisions.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 72 12/13/2016 9:32 AM

Page 22 of 94

Page 23: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 24-NFPA 101-2016 [ Section No. 9.11.4 ]

9.11.4* Integrated Systems Fire Protection and Life Safety System Test .

Where required by Chapters 11 through 43, and where two or more fire protection or life safety systems are integrated with otherbuilding systems and equipment , the integrated systems shall be tested system shall be tested to verify the proper operation andfunction of such systems in accordance with NFPA 4.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:40:59 EST 2016

Committee Statement

Committee Statement: The revision is needed for compliance with Manual of Style to mandate the integrated system test.

Second Revision No. 1002-NFPA 101-2016 [Section No. 9.11.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 72 12/13/2016 9:32 AM

Page 23 of 94

Page 24: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 25-NFPA 101-2016 [ Section No. 10.2.8.1 ]

10.2.8.1

Other than as required in 10.2.4 10.3.9 , where an approved automatic sprinkler system is installed in accordance with Section 9.7,Class C interior wall and ceiling finish materials shall be permitted in any location where Class B is required, and Class B interiorwall and ceiling finish materials shall be permitted in any location where Class A is required.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:44:47 EST 2016

Committee Statement

Committee Statement: Editorial correction; 10.3.9 deleted by SCR-26.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 72 12/13/2016 9:32 AM

Page 24 of 94

Page 25: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 26-NFPA 101-2016 [ Section No. 10.3.9 ]

10.3.9 Specific Materials.

10.3.9.1 Textile Wall and Textile Ceiling Materials.

The use of textile materials on walls or ceilings shall comply with one of the following conditions:

Textile materials meeting the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method forSurface Burning Characteristics of Building Materials , or ANSI/UL 723, Standard for Test for Surface BurningCharacteristics of Building Materials , using the specimen preparation and mounting method of ASTM E2404, StandardPractice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or CeilingCoverings, Facings and Veneers, to Assess Surface Burning Characteristics, (see 10.2.3 ), shall be permitted on the wallsor ceilings of rooms or areas protected by an approved automatic sprinkler system.

Textile materials meeting the requirements of Class A when tested in accordance with ASTM E84 or ANSI/UL 723, using thespecimen preparation and mounting method of ASTM E2404 (see 10.2.3 ), shall be permitted on partitions that do notexceed three-quarters of the floor-to-ceiling height or do not exceed 8 ft (2440 mm) in height, whichever is less.

Textile materials meeting the requirements of Class A when tested in accordance with ASTM E84 or ANSI/UL 723, using thespecimen preparation and mounting method of ASTM E2404 (see 10.2.3 ) , shall be permitted to extend not more than 48in. (1220 mm) above the finished floor on ceiling-height walls and ceiling-height partitions.

Previously approved existing installations of textile material meeting the requirements of Class A when tested in accordancewith ASTM E84 or ANSI/UL 723 (see 10.2.3 ) shall be permitted to be continued to be used.

Textile materials shall be permitted on walls and partitions where tested in accordance with NFPA 265 . (See 10.2.3.1 .)

Textile materials shall be permitted on walls, partitions, and ceilings where tested in accordance with NFPA 286 . (See10.2.3.1 .)

10.3.9.2 Expanded Vinyl Wall and Expanded Vinyl Ceiling Materials.

The use of expanded vinyl wall or expanded vinyl ceiling materials shall comply with one of the following conditions:

Materials meeting the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method forSurface Burning Characteristics of Building Materials , or ANSI/UL 723, Standard for Test for Surface BurningCharacteristics of Building Materials , using the specimen preparation and mounting method of ASTM E2404 , StandardPractice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or CeilingCoverings, Facings and Veneers, to Assess Surface Burning Characteristics, to Assess Surface Burning Characteristics(see 10.2.3 ), shall be permitted on the walls or ceilings of rooms or areas protected by an approved automatic sprinklersystem.

Materials meeting the requirements of Class A when tested in accordance with ASTM E84 or ANSI/UL 723, using thespecimen preparation and mounting method of ASTM E2404 (see 10.2.3 ), shall be permitted on partitions that do notexceed three-quarters of the floor-to-ceiling height or do not exceed 8 ft (2440 mm) in height, whichever is less.

Materials meeting the requirements of Class A when tested in accordance with ASTM E84 or ANSI/UL 723, using thespecimen preparation and mounting method of ASTM E2404 (see 10.2.3 ), shall be permitted to extend not more than 48in. (1220 mm) above the finished floor on ceiling-height walls and ceiling-height partitions.

Previously approved existing installations of materials meeting the requirements for the occupancy involved, when tested inaccordance with ASTM E84 or ANSI/UL 723 (see 10.2.3 ), shall be permitted to be continued to be used.

Materials shall be permitted on walls and partitions where tested in accordance with NFPA 265 . (See 10.2.4.4 .)

Materials shall be permitted on walls, partitions, and ceilings where tested in accordance with NFPA 286 . (See 10.2.3.1 .)

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:47:42 EST 2016

Committee Statement

Committee During the reorganization of Chapter 10, this section was inadvertently duplicated. The new, revised, correct language

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 72 12/13/2016 9:32 AM

Page 25 of 94

Page 26: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Statement: is shown in 10.2.4.4.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 72 12/13/2016 9:32 AM

Page 26 of 94

Page 27: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 27-NFPA 101-2016 [ New Section after 11.8.4.2 ]

11.8.4.3 Risk Analysis for Mass Notification Systems.

For high-rise buildings with a total occupant load of 5000 or more persons, or where the floor of an occupiable story is greater than420 ft (128 m) above the lowest level of fire department vehicle access, a risk analysis in accordance with Section 9.14 shall beperformed to determine whether a mass notification system is required.

Supplemental Information

File Name Description

101_SCR-27_11.8.4.3.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:50:17 EST 2016

Committee Statement

Committee Statement: The revision is intended for consistency with the format of other chapters.

Committee Comment No. 3002-NFPA 101-2016 [New Section after 11.8.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 72 12/13/2016 9:32 AM

Page 27 of 94

Page 28: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

11.8.4.3 Risk Analysis for Mass Notification Systems.

For high-rise buildings with a total occupant load of 5000 or more persons, or where the floor of

an occupiable story is greater than 420 ft (128 m) above the lowest level of fire department

vehicle access, a risk analysis for mass notification systems shall be provided in accordance with

Section 9.14 shall be performed to determine if a mass notification system is required.

Page 28 of 94

Page 29: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 7-NFPA 101-2016 [ Section No. 12.2.1.2 ]

12.2.1.2

Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with theprovisions of 24.2.8 7.1.6.5 .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 11:17:34 EST 2016

Committee Statement

Committee Statement: The revision is needed for consistency with SCR-6, which deletes 7.1.6.5.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 72 12/13/2016 9:32 AM

Page 29 of 94

Page 30: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 28-NFPA 101-2016 [ Section No. 12.3.4.5 ]

12.3.4.5 Risk Analysis for Mass Notification Systems.

A risk analysis for mass notification systems shall be provided in accordance with Section 9.14in shall be performed for newassembly occupancies with an occupant load of 500 or more to determine whether a mass notification system is required .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:53:30 EST 2016

Committee Statement

Committee Statement: The revision is intended for consistency with the format of other occupancy chapters.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 72 12/13/2016 9:32 AM

Page 30 of 94

Page 31: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 8-NFPA 101-2016 [ Section No. 14.2.1.5 ]

14.2.1.5

Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with theprovisions of 24.2.8 7.1.6.5 .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 11:21:50 EST 2016

Committee Statement

Committee Statement: The revision is needed for consistency with SCR-6, which deletes 7.1.6.5.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 72 12/13/2016 9:32 AM

Page 31 of 94

Page 32: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 29-NFPA 101-2016 [ Section No. 14.2.2.2.4 ]

14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry.

The locking means is approved.

(1) The locking means can shall be capable of being engaged without opening the door.

(2) The unlocking and unlatching from the classroom side of the door can be accomplished without the use of a key or tool , tool, orspecial knowledge or effort .

(3) The unlocking and unlatching requires releasing mechanism shall open the door leaf with not more than one releasingoperation.

(4) The releasing mechanism for unlocking and unlatching means are mounted shall be located at a height not less than 34 in.(865 mm) and not exceeding 48 in. (1220 mm) above the finished floor.

(5) Locks, if remotely engaged, can shall be unlocked unlockable from the classroom side of the door without the use of a key,tool, or special knowledge or effort .

(6) The door is shall be capable of being unlocked and opened from outside the room by staff with the necessary key or othercredential.

(7) The locking means does shall not modify the door closer, panic hardware, or fire exit hardware.

(8) Modifications to fire door assemblies, including door hardware, shall be in accordance with NFPA 80.

(9) The emergency action plan, required by 14.7.1, addresses shall address the use of the locking and unlocking means fromwithin and outside the room.

(10) Staff is shall be drilled in the engagement and release of the locking means, from within and outside the room, as part of theemergency egress drills required by 14.7.2.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:56:47 EST 2016

Committee Statement

Committee Statement: The revision is intended for compliance with the Manual of Style.

Committee Comment No. 2011-NFPA 101-2016 [Section No. 14.2.2.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 72 12/13/2016 9:32 AM

Page 32 of 94

Page 33: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 30-NFPA 101-2016 [ Section No. 15.2.2.2.4 ]

15.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry.

Classroom doors shall be permitted to be locked to prevent unwanted entry provided that the locking means is approved and all ofthe following conditions are met:

The locking means is approved.

(1) The locking means can shall be capable of being engaged without opening the door.

(2) The unlocking and unlatching from the classroom side of the door can be accomplished without the use of a key or tool , tool, orspecial knowledge or effort .

(3) The unlocking and unlatching requires releasing mechanism shall open the door leaf with not more than two releasingoperations.

(4) The releasing mechanism for unlocking and unlatching means are mounted shall be located at a height not less than 34 in.(865 mm) and not exceeding 48 in. (1220 mm) above the finished floor.

(5) Locks, if remotely engaged, can shall be unlocked unlockable from the classroom side of the door without the use of a key,tool, or special knowledge or effort .

(6) The door is shall be capable of being unlocked and opened from outside the room by staff with the necessary key or othercredential.

(7) The locking means does shall not modify the door closer, panic hardware, or fire exit hardware.

(8) Modifications to fire door assemblies, including door hardware, shall be in accordance with NFPA 80.

(9) The emergency action plan, required by 15.7.1 14.7.1 , addresses shall address the use of the locking and unlocking meansfrom within and outside the room.

(10) Staff is shall be drilled in the engagement and release of the locking means, from within and outside the room, as part of theemergency egress drills required by 15.7.2 14.7.2 .

Supplemental Information

File Name Description

101_SCR-30_15.2.2.2.4.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 14:10:41 EST 2016

Committee Statement

Committee Statement: The revision is intended for compliance with the Manual of Style.

Committee Comment No. 2005-NFPA 101-2016 [Section No. 15.2.2.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 72 12/13/2016 9:32 AM

Page 33 of 94

Page 34: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

15.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry.

Classroom doors shall be permitted to be locked to prevent unwanted entry provided that the

locking means is approved and all of the following conditions are met:

1.

2. The locking means shall be capable of being engaged without opening the door.

3. The unlocking and unlatching from the classroom side of the door can be accomplished

without the use of a key, tool, or special knowledge or effort.

4. The releasing mechanism shall open the door leaf with not more than two releasing

operations.

5. The releasing mechanism for unlocking and unlatching shall be located at a height not

less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor.

6. Locks, if remotely engaged, shall be unlockable from the classroom side of the door

without the use of a key, tool, or special knowledge or effort.

7. The door isshall be capable of being unlocked and opened from outside the room with the

necessary key or other credential.

8. The locking means doesshall not modify the door closer, panic hardware, or fire exit

hardware.

9. Modifications to fire door assemblies, including door hardware, shall be in accordance

with NFPA 80.

10. The emergency action plan, required by 15.7.1, shall address the use of the locking and

unlocking means from within and outside the room.

11. Staff isshall be drilled in the engagement and release of the locking means, from within

and outside the room, as part of the emergency egress drills required by 15.7.2.

Page 34 of 94

Page 35: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 9-NFPA 101-2016 [ Section No. 16.2.1.1 ]

16.2.1.1

Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with theprovisions of 24.2.87.1.6.5 .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 11:26:55 EST 2016

Committee Statement

Committee Statement: The revision is needed for consistency with SCR-6, which deletes 7.1.6.5.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 72 12/13/2016 9:32 AM

Page 35 of 94

Page 36: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 31-NFPA 101-2016 [ New Section after 16.2.2.2.5 ]

16.2.2.2.6 Classroom Door Locking to Prevent Unwanted Entry.

Classroom doors shall be permitted to be locked to prevent unwanted entry provided that the locking means is approved and all ofthe following conditions are met:

(1) The locking means shall be capable of being engaged without opening the door.

(2) The unlocking and unlatching from the classroom side of the door can be accomplished without the use of a key, tool, orspecial knowledge or effort.

(3) The releasing mechanism shall open the door leaf with not more than one releasing operation.

(4) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and notexceeding 48 in. (1220 mm) above the finished floor.

(5) Locks, if remotely engaged, shall be unlockable from the classroom side of the door without the use of a key, tool, or specialknowledge or effort.

(6) The door shall be capable of being unlocked and opened from outside the room with the necessary key or other credential.

(7) The locking means shall not modify the door closer, panic hardware, or fire exit hardware.

(8) Modifications to fire door assemblies, including door hardware, shall be in accordance with NFPA 80.

(9) The emergency action plan, required by 16.7.1 , shall address the use of the locking and unlocking means from within andoutside the room.

(10) Staff shall be drilled in the engagement and release of the locking means, from within and outside the room, as part of theemergency egress drills required by 16.7.2 .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 14:14:06 EST 2016

Committee Statement

Committee Statement: The revision is intended for compliance with the Manual of Style.

Committee Comment No. 2007-NFPA 101-2016 [New Section after 16.2.2.2.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 72 12/13/2016 9:32 AM

Page 36 of 94

Page 37: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 32-NFPA 101-2016 [ New Section after 17.2.2.2.5 ]

17.2.2.2.6 Classroom Door Locking to Prevent Unwanted Entry.

Classroom doors shall be permitted to be locked to prevent unwanted entry provided that the locking means is approved and all ofthe following conditions are met:

(1) The locking means shall be capable of being engaged without opening the door.

(2) The unlocking and unlatching from the classroom side of the door can be accomplished without the use of a key, tool, orspecial knowledge or effort.

(3) The releasing mechanism shall open the door leaf with not more than two releasing operations.

(4) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and notexceeding 48 in. (1220 mm) above the finished floor.

(5) Locks, if remotely engaged, shall be unlockable from the classroom side of the door without the use of a key, tool, or specialknowledge or effort.

(6) The door shall be capable of being unlocked and opened from outside the room with the necessary key or other credential.

(7) The locking means shall not modify the door closer, panic hardware, or fire exit hardware.

(8) Modifications to fire door assemblies, including door hardware, shall be in accordance with NFPA 80 .

(9) The emergency action plan, required by 17.7.1 , shall address the use of the locking and unlocking means from within andoutside the room.

(10) Staff shall be drilled in the engagement and release of the locking means, from within and outside the room, as part of theemergency egress drills required by 17.7.2 .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 14:16:29 EST 2016

Committee Statement

Committee Statement: The revision is intended for compliance with the Manual of Style.

Committee Comment No. 2008-NFPA 101-2016 [New Section after 17.2.2.2.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 72 12/13/2016 9:32 AM

Page 37 of 94

Page 38: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 33-NFPA 101-2016 [ Section No. 17.3.2.6 ]

17.3.2.6 Hazardous Materials.

Where hazardous materials are present stored , used, or handled, the provisions of 8.7.3.1 shall apply.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 14:18:22 EST 2016

Committee Statement

Committee Statement: The revision is intended to correlate with other hazardous materials provisions.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 72 12/13/2016 9:32 AM

Page 38 of 94

Page 39: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 34-NFPA 101-2016 [ Section No. 19.3.7.1 ]

19.3.7.1*

Smoke barriers shall be provided to divide every story used for sleeping rooms for more than 30 patients into not less than twosmoke compartments (see 19.2.4.4), and the following also shall apply:

(1) The size of any such smoke compartment shall comply with one of the following:

(a) Smoke compartments shall not exceed 22,500 ft2 (2100 m2).

(b) Where compliant with the provisions of 18.3.7.1(4) and where the building is sprinklered in accordance with 19.3.5.8,

hospital smoke compartments where all sleeping rooms are configured for only one patient shall not exceed 40,000 ft2

(3720 m2) where all sleeping rooms are configured for only one patient. Suites in accordance with 19.2.5.7 shall bepermitted where every occupiable sleeping room within the suite is configured for only one patient .

Where compliant with the provisions of 18.3.7.1(5) and where the building is sprinklered in accordance with 19.3.5.8 ,

hospital smoke compartments without patient sleeping rooms shall not exceed 40,000 ft 2 (3720 m 2 ).

(2) The travel distance from any point to reach a door in the required smoke barrier shall not exceed 200 ft (61 m).

(3) Where neither the length nor width of the smoke compartment exceeds 150 ft (46 m), the travel distance to reach the smokebarrier door shall not be limited.

(4) The area of an atrium separated in accordance with 8.6.7 shall not be limited in size.

Supplemental Information

File Name Description

101_SCR-34_19.3.7.1.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 14:29:08 EST 2016

Committee Statement

Committee Statement: Editorial revision for clarity as indicated in Koffel's affirmative with comment ballot.

Committee Comment No. 4005-NFPA 101-2016 [Section No. 19.3.7.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 72 12/13/2016 9:32 AM

Page 39 of 94

Page 40: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

19.3.7.1*

Smoke barriers shall be provided to divide every story used for sleeping rooms for more than 30

patients into not less than two smoke compartments (see 19.2.4.4), and the following also shall

apply:

1. The size of any such smoke compartment shall comply with one of the following:

1. Smoke compartments shall not exceed 22,500 ft2 (2100 m2).

2. Where the building is sprinklered in accordance with 19.3.5.8, hospital smoke

compartments shall not exceed 40,000 ft2 (3720 m2) where all sleeping rooms are

configured for only one patient, in which case suites. Suites in accordance with

19.2.5.7 shall be permitted where every occupiable sleeping room within the suite

is configured for only one patient.

2. The travel distance from any point to reach a door in the required smoke barrier shall not

exceed 200 ft (61 m).

3. Where neither the length nor width of the smoke compartment exceeds 150 ft (46 m), the

travel distance to reach the smoke barrier door shall not be limited.

4. The area of an atrium separated in accordance with 8.6.7 shall not be limited in size.

Page 40 of 94

Page 41: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 35-NFPA 101-2016 [ New Section after 22.3.2.5 ]

22.3.2.6 Hazardous Materials.

Where hazardous materials are stored, used, or handled, the provisions of 8.7.3.1 shall apply.

Supplemental Information

File Name Description

101_SCR-35_22.3.2.6.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 14:31:59 EST 2016

Committee Statement

Committee Statement: The revision is intended to correlate with other occupancy chapters by referencing 8.7.3.1 specifically.

Committee Comment No. 1503-NFPA 101-2016 [New Section after 22.3.2.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 72 12/13/2016 9:32 AM

Page 41 of 94

Page 42: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

22.3.2.6 Hazardous Materials.

Where hazardous materials are stored, used, or handled, the provisions of 8.7.3.1 shall apply.

Page 42 of 94

Page 43: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 36-NFPA 101-2016 [ New Section after 23.3.2.5 ]

23.3.2.6 Hazardous Materials.

Where hazardous materials are stored, used, or handled, the provisions of 8.7.3.1 shall apply.

Supplemental Information

File Name Description

101_SCR-36_23.3.2.6.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 14:35:03 EST 2016

Committee Statement

Committee Statement: Revision intended to correlate with other occupancy chapters by referencing 8.7.3.1 specifically.

Committee Comment No. 1504-NFPA 101-2016 [New Section after 23.3.2.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 72 12/13/2016 9:32 AM

Page 43 of 94

Page 44: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

23.3.2.6 Hazardous Materials.

Where hazardous materials are stored, used, or handled, the provisions of 8.7.3.1 shall apply.

Page 44 of 94

Page 45: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 59-NFPA 101-2016 [ New Section after 24.2.7.2 ]

24.2.8* Grab Bars for Bathtubs, Bathtub-Shower Combinations, and Showers.

24.2.8.1 General.

24.2.8.1.1

New bathtubs, bathtub-shower combinations, and showers shall be provided with grab bars unless otherwise permitted by24.2.8.1.2 .

24.2.8.1.2*

Grab bars shall not be required in showers where the transition from the room floor to the shower floor does not exceed 0.5 in. (13mm) in height and all shower surfaces are slip resistant when wet.

24.2.8.1.3

Where provided, grab bars shall comply with 24.2.8.2 through 24.2.8.4 .

24.2.8.1.4

All dimensions shall be measured to the centerline of the grab bar unless otherwise stated.

24.2.8.2* Vertical Grab Bar or Pole.

A vertical grab bar shall be provided on the control end wall or the end wall opposite the control end wall of the bathtub or bathtub-shower combination in accordance with 24.2.8.2.1 , or shall be provided as a vertical pole in accordance with 24.2.8.2.3 . Forshowers, either a vertical grab bar that is usable by a person stepping into and out of the shower enclosure in accordance with24.2.8.2.2 , or a vertical pole in accordance with 24.2.8.2.3 , shall be provided.

24.2.8.2.1* Bathtub End Wall Vertical Grab Bars.

End wall vertical grab bars for bathtubs shall comply with all of the following:

(1) Vertical grab bars shall have a length of not less than 36 in. (914 mm).

(2) Vertical grab bars shall be located between 24 in. (610 mm) and 27 in. (686 mm) above the finished floor, measured to thelower end.

(3) Vertical grab bars shall be installed at the end that is least obstructed for entry and egress.

(4) Vertical grab bars shall be located between 9 in. (228 mm) and 12 in. (305 mm) from the open entry and egress side of thebathtub or bathtub-shower combination, measured horizontally from the exterior plane of the bathtub or bathtub-showercombination.

24.2.8.2.2 Shower Grab Bars.

Vertical grab bars for showers shall comply with all of the following:

(1) Vertical grab bars shall have a length of not less than 24 in. (610 mm).

(2) Vertical grab bars shall be located between 36 in. (914 mm) and 39 in. (991 mm) above the finished floor, measured to thelower end.

24.2.8.2.3* Vertical Poles.

Vertical, pole-type grab bars shall be fixed to the floor or to the bathtub and either the room ceiling or an adjacent wall and shallcomply with all of the following:

(1) Poles shall be located within 6 in. (150 mm), measured horizontally, of the outside or outer edge of the bathtub, bathtub-shower combination, or shower.

(2) Poles shall be located within 30 in. (760 mm), measured horizontally, of the vertical plane of the control end wall of a bathtubor bathtub-shower combination.

24.2.8.3 Back Wall Grab Bar.

For bathtubs and bathtub-shower combinations bounded on two or three sides by walls, a diagonal grab bar in accordance with24.2.8.3.1 or horizontal grab bar in accordance with 24.2.8.3.2 shall be provided on the back wall.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 72 12/13/2016 9:32 AM

Page 45 of 94

Page 46: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

24.2.8.3.1* Back Wall Diagonal Grab Bars.

Diagonal grab bars shall comply with all of the following:

(1) Diagonal grab bars shall have a length of not less than 24 in. (600 mm).

(2) Diagonal grab bars shall be located so the higher end is closest to the control end wall.

(3) Higher ends of diagonal grab bars shall be located a maximum of 12 in. (305 mm) from the control end wall.

(4) Higher ends of diagonal grab bars shall be located 25 in. (635 mm) minimum and 27 in. (685 mm) maximum above the rim ofthe bathtub.

(5) Lower ends of diagonal grab bars shall be located 8 in. (203 mm) minimum and 10 in. (254 mm) maximum above the rim ofthe bathtub.

24.2.8.3.2 Back Wall Horizontal Grab Bars.

Horizontal grab bars shall comply with all of the following:

(1) Horizontal grab bars shall be located 8 in. (205 mm) minimum and 10 in. (255 mm) maximum above the bathtub rim.

(2) Horizontal grab bars shall be located so one end is 12 in. (305 mm) maximum from the control end wall and the other end islocated 24 in. (610 mm) maximum from the opposite, or head, end of the bathtub.

24.2.8.4* Grab Bar Details.

24.2.8.4.1

Grab bars shall be circular in cross section with a minimum diameter of 1 1 ⁄4 in. (32 mm) and a maximum diameter of 2 in. (51mm).

24.2.8.4.2

Where attached to a wall, grab bars shall provide a clearance for hand grasp of 1 1 ⁄2 in. (38 mm) minimum.

24.2.8.4.3

Grab bars shall be designed and constructed to the structural loading conditions in accordance with the building code.

Supplemental Information

File Name Description

101_SCR-59_Attachment.docx Revised A.24.2.8 text

101_SCR-59_A.24.2.8.docx Shows legislative changes from SCR. For staff use.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 22 11:55:06 EST 2016

Committee Statement

CommitteeStatement:

No change to 24.2.8. See attachment for revised A.24.2.8 text. Revision to correlate with SCR-6, which deletes7.1.6.5.

Committee Comment No. 6014-NFPA 101-2016 [New Section after 24.2.7.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 72 12/13/2016 9:32 AM

Page 46 of 94

Page 47: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

A.24.2.8 The grab bars required by 24.2.8 are designed to improve safety of showering and bathing by ambulatory users, typically entering and exiting a bath, bathtub-shower combination, or shower facility for showering while standing, or for other forms of bathing that can entail transition to/from a crouching or sitting position. For grab bar requirements appropriate for other uses and users, especially users with disabilities, refer to the requirements in ICC/ANSI A117.1, Accessible and Usable Buildings and Facilities. Generally, the grab bars specified for this Code will not interfere with other grab bars installed in accordance with the requirements of ICC/ANSI A117.1 and they can contribute to meeting the requirements of ICC/ANSI A117.1 and vice versa. For example, combination vertical and horizontal grab bars (e.g., in an L configuration), as addressed by ICC/ANSI A117.1, can meet the requirements of this Code for a vertical grab bar. Similarly, requirements for a horizontal grab bar on the back wall are compatible. Dimensions for the height of grab bars are based on typical, mass-produced bathtubs with a wall height above the finished floor of about 15 in. (380 mm) and the bottom of the bathtub within 1 to 2 in. (25 to 51 mm) of the finished floor elevation. Adjustments to stipulated grab bar height limits and ranges, referenced to the bath tub rim, should be considered for bath tubs having higher walls and, thus, rim heights, above the bottom of the tub and, possibly, also the wall height above the finished floor. ICC/ANSI A117.1 references grab bar height dimensions to the bathtub rim and, for consistency with this widely used ANSI standard, that convention is maintained in this Code. A.24.2.8.2 The requirements within this section provide design options for points of control when entering and/or exiting a bathtub or shower. Points of control are critical to providing guidance and stability to an occupant much the same as a handrail provides on stairs. The different points of control specified by this section, wall mounted grabs or vertical poles, provide options for compliance in a wide range of conditions. It is important to note that only one point of control is required for entry and egress transfers. The use of a vertical pole is not required and is offered as an option to wall mounted grab bars. A.24.2.8.1.2 The provision of 24.2.8.1.2 is intended to ensure that grab bars, if provided voluntarily (i.e., as nonrequired) for dedicated showers, meet the requirements of 24.2.8, so that something appearing to be a grab bar can effectively perform as one. However, such grab bars would only be considered nonrequired in the case of dedicated showers not involving misstep and fall dangers addressed by 7.1.6.2 and 7.1.6.4. This means that walking surfaces must be at least as safe, in terms of underfoot conditions, as any other portion of the means of egress (where, for example, handrails are not required) for users not having mobility disabilities. This would require exceptionally careful choice

Page 47 of 94

Page 48: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

and maintenance of underfoot materials as well as very effective control of water within and adjacent to the dedicated shower facility. A.24.2.8.2.1 Grab bars located where they interfere with sealing or with a shower curtain against escape of water — especially to the floor surface outside the shower facility — might introduce safety problems in the form of greatly reduced slip resistance of the walking surface, which could violate this Code. This can be avoided with a 6 in. (150 mm) horizontal separation between the shower curtain rod and the grab bar. It is assumed that other forms of water control, such as an installed enclosure, will not interfere with the use of grab bars. A.24.2.8.2.3 A free-standing pole, satisfying requirements for a grab bar can offer flexibility in placement, for example, within the close quarters of a small bathroom where there is a water closet adjacent to the bathing facility and a single grab bar can serve both facilities. Where the bathing facility is free standing, without walls, especially with large soaking tubs, including those on pedestals, the vertical pole–type grab bar is especially useful. The pole also can solve attachment problems where walls are nonexistent or difficult to use for installing conventional, wall-mounted grab bars. A.24.2.8.3.1 Using the midpoints of the distance ranges and the minimum distance from the control end wall results in a 45-degree angle for the diagonal grab bar. Such a diagonal grab bar (or alternatively, a horizontal grab bar fairly similar to the option provided by 24.2.8.3.1, which meets requirements of ICC/ANSI A117.1, Standard for Accessible and Usable Buildings and Facilities) was found suitable in tests performed of several grab bar options with 103 independent-living seniors with an average age of 70. (“Evaluation of Optimal Bath Grab Bar Placement for Seniors,” by H. Sveistrup, D. Lockett, N. Edwards, and F. Aminzadeh, University of Ottawa with funding by Canada Mortgage and Housing Corporation, 2003.) A.24.2.8.5.4 The best-performing grab bars are in the middle third of the permitted range for circular diameter. For some grab bar designs, with undulations and other surface geometry features to improve slip resistance for users’ hands, these dimensions will be nominal with small variations depending on where measurements are taken. Children and others with smaller hands will be able to use the diameters within the lower part of the permitted range. When using a free-standing pole for a grab bar, structural considerations, especially for stiffness, might dictate using diameters in the upper part of the permitted range.

Page 48 of 94

Page 49: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Note that a minimum clearance between the grab bar and an adjacent surface is specified. With grab bars, especially horizontal ones, on which large, downward loads are imposed by the arms of users, there is some concern about people’s hands slipping into the clear space; however, this can occur even with an absolute 1.5 in. (38 mm) clearance, as some standards specify and most grab bar designs provide. Thus the main difference in the end result is where, along its length, the arm gets wedged behind the grab bar, not the complete prevention of this happening at all.

Page 49 of 94

Page 50: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 10-NFPA 101-2016 [ New Section after 26.2.3.6 ]

26.2.4* Grab Bars for Bathtubs, Bathtub-Shower Combinations, and Showers.

Where new bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with theprovisions of 24.2.8 .

26.2.4.1 General.

26.2.4.1.1

New bathtubs, bathtub-shower combinations, and showers shall be provided with grab bars unless otherwise permitted by26.2.4.1.2 .

26.2.4.1.2*

Grab bars shall not be required in showers where the transition from the room floor to the shower floor does not exceed 0.5 in. (13mm) in height and all shower surfaces are slip resistant when wet.

26.2.4.1.3

Where provided, grab bars shall comply with 26.2.4.2 through 26.2.4.4 .

26.2.4.1.4

All dimensions shall be measured to the centerline of the grab bar unless otherwise stated.

26.2.4.2* Vertical Grab Bar or Pole.

A vertical grab bar shall be provided on the control end wall or the end wall opposite the control end wall of the bathtub or bathtub-shower combination in accordance with 26.2.4.2.1 , or shall be provided as a vertical pole in accordance with 26.2.4.2.3 . Forshowers, either a vertical grab bar that is usable by a person stepping into and out of the shower enclosure in accordance with26.2.4.2.2 , or a vertical pole in accordance with 26.2.4.2.3 , shall be provided.

26.2.4.2.1* Bathtub End Wall Vertical Grab Bars.

End wall vertical grab bars for bathtubs shall comply with all of the following:

Vertical grab bars shall have a length of not less than 36 in. (914 mm).

Vertical grab bars shall be located between 24 in. (610 mm) and 27 in. (686 mm) above the finished floor, measured to thelower end.

Vertical grab bars shall be installed at the end that is least obstructed for entry and egress.

Vertical grab bars shall be located between 9 in. (228 mm) and 12 in. (305 mm) from the open entry and egress side of thebathtub or bathtub-shower combination, measured horizontally from the exterior plane of the bathtub or bathtub-showercombination.

26.2.4.2.2 Shower Grab Bars.

Vertical grab bars for showers shall comply with all of the following:

Vertical grab bars shall have a length of not less than 24 in. (610 mm).

Vertical grab bars shall be located between 36 in. (914 mm) and 39 in. (991 mm) above the finished floor, measured to thelower end.

26.2.4.2.3* Vertical Poles.

Vertical, pole-type grab bars shall be fixed to the floor or to the bathtub and either the room ceiling or an adjacent wall and shallcomply with all of the following:

Poles shall be located within 6 in. (150 mm), measured horizontally, of the outside or outer edge of the bathtub, bathtub-shower combination, or shower.

Poles shall be located within 30 in. (760 mm), measured horizontally, of the vertical plane of the control end wall of a bathtubor bathtub-shower combination.

26.2.4.3 Back Wall Grab Bar.

For bathtubs and bathtub-shower combinations bounded on two or three sides by walls, a diagonal grab bar in accordance with26.2.4.3.1 or horizontal grab bar in accordance with 26.2.4.3.2 shall be provided on the back wall.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 72 12/13/2016 9:32 AM

Page 50 of 94

Page 51: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

26.2.4.3.1* Back Wall Diagonal Grab Bars.

Diagonal grab bars shall comply with all of the following:

Diagonal grab bars shall have a length of not less than 24 in. (600 mm).

Diagonal grab bars shall be located so the higher end is closest to the control end wall.

Higher ends of diagonal grab bars shall be located a maximum of 12 in. (305 mm) from the control end wall.

Higher ends of diagonal grab bars shall be located 25 in. (635 mm) minimum and 27 in. (685 mm) maximum above the rim ofthe bathtub.

Lower ends of diagonal grab bars shall be located 8 in. (203 mm) minimum and 10 in. (254 mm) maximum above the rim ofthe bathtub.

26.2.4.3.2 Back Wall Horizontal Grab Bars.

Horizontal grab bars shall comply with all of the following:

Horizontal grab bars shall be located 8 in. (205 mm) minimum and 10 in. (255 mm) maximum above the bathtub rim.

Horizontal grab bars shall be located so one end is 12 in. (305 mm) maximum from the control end wall and the other end islocated 24 in. (610 mm) maximum from the opposite, or head, end of the bathtub.

26.2.4.4* Grab Bar Details.

26.2.4.4.1

Grab bars shall be circular in cross section with a minimum diameter of 1 1 ⁄4 in. (32 mm) and a maximum diameter of 2 in. (51mm).

26.2.4.4.2

Where attached to a wall, grab bars shall provide a clearance for hand grasp of 1 1 ⁄2 in. (38 mm) minimum.

26.2.4.4.3

Grab bars shall be designed and constructed to the structural loading conditions in accordance with the building code.

Supplemental Information

File Name Description

101_SCR-10_26.2.4-includes_annex.1480359970204-GH.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 11:33:20 EST 2016

Committee Statement

Committee Statement: The revision is intended for consistency with SCR-6. The Ch. 26 criteria are identical to Ch. 24.

Committee Comment No. 6015-NFPA 101-2016 [New Section after 26.2.3.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 72 12/13/2016 9:32 AM

Page 51 of 94

Page 52: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

26.2.4* Grab Bars for Bathtubs, Bathtub-Shower Combinations, and Showers.

Where new bathtubs, bathtub-shower combinations, or showers are present, grab bars

shall be provided in accordance with the provisions of 24.2.8.

A.26.2.4

See A.7.1.6.5A.24.2.8.

26.2.4.1 General.

26.2.4.1.1

New bathtubs, bathtub-shower combinations, and showers shall be provided with grab bars unless otherwise permitted by 26.2.4.1.2.

26.2.4.1.2*

Grab bars shall not be required in showers where the transition from the room floor to the shower floor does not exceed 0.5 in. (13 mm) in height and all shower surfaces are slip resistant when wet.

A.26.2.4.1.2

See A.7.1.6.5.1.2.

26.2.4.1.3

Where provided, grab bars shall comply with 26.2.4.2 through 26.2.4.4.

26.2.4.1.4

All dimensions shall be measured to the centerline of the grab bar unless otherwise stated.

26.2.4.2* Vertical Grab Bar or Pole.

A vertical grab bar shall be provided on the control end wall or the end wall opposite the control end wall of the bathtub or bathtub-shower combination in accordance with 26.2.4.2.1, or shall be provided as a vertical pole in accordance with 26.2.4.2.3. For showers, either a vertical grab bar that is usable by a person stepping into and out of the shower enclosure in accordance with 26.2.4.2.2, or a vertical pole in accordance with 26.2.4.2.3, shall be provided.

A.26.2.4.2

The requirements within this section provide design options for points of control when entering and/or exiting a bathtub or shower. Points of control are critical to providing guidance and stability to an occupant much the same as a handrail provides on stairs. The different points of control specified by this section, wall-mounted grabs or vertical poles, provide options for compliance in a wide range of conditions. It is important to note that only one point of control is required for entry and egress transfers. The use of a vertical pole is not required and is offered as an option to wall-mounted grab bars.

26.2.4.2.1* Bathtub End Wall Vertical Grab Bars.

Formatted: Highlight

Formatted: Highlight

Formatted: Highlight

Page 52 of 94

Page 53: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

A.26.2.4.2.1

See A.7.1.6.5.2.1.

End wall vertical grab bars for bathtubs shall comply with all of the following:

(1) Vertical grab bars shall have a length of not less than 36 in. (914 mm).

(2) Vertical grab bars shall be located between 24 in. (610 mm) and 27 in. (686 mm) above the finished floor, measured to the lower end.

(3) Vertical grab bars shall be installed at the end that is least obstructed for entry and egress.

(4) Vertical grab bars shall be located between 9 in. (228 mm) and 12 in. (305 mm) from the open entry and egress side of the bathtub or bathtub-shower combination, measured horizontally from the exterior plane of the bathtub or bathtub-shower combination.

26.2.4.2.2 Shower Grab Bars.

Vertical grab bars for showers shall comply with all of the following:

(1) Vertical grab bars shall have a length of not less than 24 in. (610 mm).

(2) Vertical grab bars shall be located between 36 in. (914 mm) and 39 in. (991 mm) above the finished floor, measured to the lower end.

26.2.4.2.3* Vertical Poles.

Vertical, pole-type grab bars shall be fixed to the floor or to the bathtub and either the room ceiling or an adjacent wall and shall comply with all of the following:

(1) Poles shall be located within 6 in. (150 mm), measured horizontally, of the outside or outer edge of the bathtub, bathtub-shower combination, or shower.

(2) Poles shall be located within 30 in. (760 mm), measured horizontally, of the vertical plane of the control end wall of a bathtub or bathtub-shower combination.

A.26.2.4.2.3

See A.7.1.6.5.2.2.

26.2.4.3 Back Wall Grab Bar.

For bathtubs and bathtub-shower combinations bounded on two or three sides by walls, a diagonal grab bar in accordance with 26.2.4.3.1 or horizontal grab bar in accordance with 26.2.4.3.2 shall be provided on the back wall.

26.2.4.3.1* Back Wall Diagonal Grab Bars.

Diagonal grab bars shall comply with all of the following:

(1) Diagonal grab bars shall have a length of not less than 24 in. (600 mm).

(2) Diagonal grab bars shall be located so the higher end is closest to the control end wall.

Formatted: Highlight

Formatted: Highlight

Page 53 of 94

Page 54: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

(3) Higher ends of diagonal grab bars shall be located a maximum of 12 in. (305 mm) from the control end wall.

(4) Higher ends of diagonal grab bars shall be located 25 in. (635 mm) minimum and 27 in. (685 mm) maximum above the rim of the bathtub.

(5) Lower ends of diagonal grab bars shall be located 8 in. (203 mm) minimum and 10 in. (254 mm) maximum above the rim of the bathtub.

A.26.2.4.3.1

See A.7.1.6.5.3.1.

26.2.4.3.2 Back Wall Horizontal Grab Bars.

Horizontal grab bars shall comply with all of the following:

(1) Horizontal grab bars shall be located 8 in. (205 mm) minimum and 10 in. (255 mm) maximum above the bathtub rim.

(2) Horizontal grab bars shall be located so one end is 12 in. (305 mm) maximum from the control end wall and the other end is located 24 in. (610 mm) maximum from the opposite, or head, end of the bathtub.

26.2.4.4* Grab Bar Details.

A.26.2.4.4

See A.7.1.6.5.4.

26.2.4.4.1

Grab bars shall be circular in cross section with a minimum diameter of 11⁄4 in. (32 mm) and a maximum diameter of 2 in. (51 mm).

26.2.4.4.2

Where attached to a wall, grab bars shall provide a clearance for hand grasp of 11⁄2 in. (38 mm) minimum.

26.2.4.4.3

Grab bars shall be designed and constructed to the structural loading conditions in accordance with the building code.

Formatted: Highlight

Formatted: Highlight

Page 54 of 94

Page 55: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 11-NFPA 101-2016 [ Section No. 28.2.1.4 ]

28.2.1.4

Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with theprovisions of 24.2.87.1.6.5 .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 12:14:32 EST 2016

Committee Statement

Committee Statement: The revision is needed for consistency with SCR-6, which deletes 7.1.6.5.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 72 12/13/2016 9:32 AM

Page 55 of 94

Page 56: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 37-NFPA 101-2016 [ New Section after 28.3.4.3.6 ]

28.3.4.4 Risk Analysis for Mass Notification.

28.3.4.4.1

A risk analysis in accordance with Section 9.14 shall be performed for grades K through 12, college, or university dormitorieswith an occupant load greater than 100 to determine whether a mass notification is required.

28.3.4.4.2

Applicable portions of an existing risk analysis shall be permitted to be used when a new building is added to the campus.

Supplemental Information

File Name Description

101_SCR-37_28.3.4.4.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 14:38:53 EST 2016

Committee Statement

Committee Statement: The revision is intended to correlate with the format of other occupancy chapters.

Committee Comment No. 6010-NFPA 101-2016 [New Section after 28.3.4.3.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 72 12/13/2016 9:32 AM

Page 56 of 94

Page 57: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

28.3.4.4 Risk Analysis for Mass Notification.

28.3.4.4.1

A risk analysis for mass notification in accordance with Section 9.14 shall be

conductedperformed for grade K through 12, college, or university dormitories with an

occupant load greater than 100 to determine if a mass notification system is required.

28.3.4.4.2

Applicable portions of an existing risk analysis shall be permitted to be used when a new

building is added to the campus.

Page 57 of 94

Page 58: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 38-NFPA 101-2016 [ Section No. 28.3.5.3 ]

28.3.5.3

Where an automatic sprinkler system is installed, either for total or partial building coverage, the system shall be in accordance withSection 9.7, as modified by 28.3.5.4. In buildings hotel or dormitory occupancies up to and including four or fewer stories in heightthat are located-in buildings and not exceeding 60 ft (18.3 m) in height above grade plane, systems in accordance with NFPA 13Rshall be permitted.

28.3.5.3.1

Where located in a building of Type III, Type IV, or Type V construction designed in accordance with 4.6.3(5) and where the roofassembly is located more than 55 ft (17 m) above the lowest level of required fire department vehicle access, attics shall complywith 28.3.5.3.1.1 , 28.3.5.3.1.2 , and one of the following:

(1) Attics shall be provided with sprinkler protection.

(2) Attics shall be constructed with noncombustible materials.

(3) Attics shall be constructed with fire-retardant-treated wood.

(4) Attics shall be filled with noncombustible insulation.

28.3.5.3.1.1

The height of the roof assembly shall be determined by measuring the distance from the lowest level of required fire departmentvehicle access adjacent to the building to the eave of the highest pitched roof, the intersection of the highest roof to the exteriorwall, or the top of the highest parapet, whichever yields the greatest distance.

28.3.5.3.1.2

Required fire department vehicle access roads used in 28.3.5.3.1.1 shall include only those roads that are necessary forrequired fire department vehicle access in compliance with the fire code.

Supplemental Information

File Name Description

101_SCR-38_28.3.5.3.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 14:44:22 EST 2016

Committee Statement

Committee Statement: Revisions intended for compliance with the Manual of Style.

Committee Comment No. 6007-NFPA 101-2016 [Section No. 28.3.5.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 72 12/13/2016 9:32 AM

Page 58 of 94

Page 59: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

28.3.5.3

Where an automatic sprinkler system is installed, either for total or partial building coverage, the

system shall be in accordance with Section 9.7, as modified by 28.3.5.4. In hotel or dormitory

occupancies up to and including four stories in height, that are located in buildings and not

exceeding 60 ft (18.3 m) in height above grade plane, systems in accordance with NFPA 13R

shall be permitted.

28.3.5.3.1

Where located in a building of Type III, Type IV, or Type V construction designed in accordance

with 4.6.3(5), and where the roof assembly is located more than 55 ft (16,764 mmfeet (17 m)

above the lowest level of required fire department vehicle access, attics shall comply with

28.3.5.3.1.1, 28.3.5.3.1.2, and one of the following:

1. Attics shall be provided with sprinkler protection.

2. Attics shall be constructed with noncombustible materials.

3. Attics shall be constructed with fire-retardant-treated wood.

4. Attics shall be filled with noncombustible insulation.

28.3.5.3.1.1

The height of the roof assembly shall be determined by measuring the distance from the lowest

level of required fire department vehicle access adjacent to the building to the eave of the highest

pitched roof, the intersection of the highest roof to the exterior wall, or the top of the highest

parapet, whichever yields the greatest distance.

28.3.5.3.1.2

Required fire department vehicle access roads used in 28.3.5.3.1.1 shall include only those roads

that are necessary for required fire department vehicle access in compliance with the fire code.

Page 59 of 94

Page 60: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 12-NFPA 101-2016 [ Section No. 30.2.1.3 ]

30.2.1.3

Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with theprovisions of 24.2.87.1.6.5 .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 12:22:22 EST 2016

Committee Statement

Committee Statement: Revision is needed for consistency with SCR-6, which deletes 7.1.6.5.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 72 12/13/2016 9:32 AM

Page 60 of 94

Page 61: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 39-NFPA 101-2016 [ Section No. 30.3.5.2 ]

30.3.5.2

Where an automatic sprinkler system is installed, either for total or partial building coverage, the system shall be installed inaccordance with Section 9.7, as modified by 30.3.5.3 and 30.3.5.4. In buildings apartment buildings up to and including four orfewer stories in height and , that are located in buildings not exceeding 60 ft (18.3 m) in height above grade plane, systems inaccordance with NFPA 13R shall be permitted.

30.3.5.2.1

Where located in a building of Type III, Type IV, or Type V construction designed in accordance with 4.6.3(5) and where the roofassembly is located more than 55 ft (17 m) above the lowest level of required fire department vehicle access, attics shall complywith 30.3.5.2.1.1 , 30.3.5.2.1.2 , and one of the following:

(1) Attics shall be provided with sprinkler protection.

(2) Attics shall be constructed with noncombustible materials.

(3) Attics shall be constructed with fire-retardant-treated wood

(4) Attics shall be filled with noncombustible insulation

30.3.5.2.1.1

The height of the roof assembly shall be determined by measuring the distance from the lowest level of required fire departmentvehicle access adjacent to the building to the eave of the highest pitched roof, the intersection of the highest roof to the exteriorwall, or the top of the highest parapet, whichever yields the greatest distance.

30.3.5.2.1.2

Required fire department vehicle access roads used in 30.3.5.2.1.1 shall include only those roads that are necessary forrequired fire department vehicle access in compliance with the fire code.

Supplemental Information

File Name Description

101_SCR-39_30.3.5.3.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 14:51:33 EST 2016

Committee Statement

Committee Statement: Revisions for compliance with the Manual of Style.

Committee Comment No. 6013-NFPA 101-2016 [Section No. 30.3.5.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 72 12/13/2016 9:32 AM

Page 61 of 94

Page 62: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

30.3.5.3

Where an automatic sprinkler system is installed, either for total or partial building coverage, the

system shall be in accordance with Section 9.7, as modified by 30.3.5.4. In hotel or dormitory

occupanciesapartment buildings up to and including four stories in height, that are located in

buildings not exceeding 60 ft (18.3 m) in height above grade plane, systems in accordance with

NFPA 13R shall be permitted.

30.3.5.3.1

Where located in a building of Type III, Type IV, or Type V construction designed in

accordance with Section 4.6.3(5), and where the roof assembly is located more than 55 ft (16,764

mmfeet (17 m) above the lowest level of required fire department vehicle access, attics shall

comply with 30.3.5.3.1.1, 30.3.5.3.1.2, and one of the following:

1. Provide Attics shall be provided with sprinkler protection .

2. Construct the attic usingAttics shall be constructed with noncombustible materials .

3. Construct the attic usingAttics shall be constructed with fire-retardant-treated wood .

4. Fill the atticAttics shall be filled with noncombustible insulation .

30.3.5.3.1.1

The height of the roof assembly shall be determined by measuring the distance from the lowest

level of required fire department vehicle access adjacent to the building to the eave of the highest

pitched roof, the intersection of the highest roof to the exterior wall, or the top of the highest

parapet, whichever yields the greatest distance.

30.3.5.3.1.2

Required fire department vehicle access roads used in 30.3.5.3.1.1 shall include only those roads

that are necessary for required fire department vehicle access in compliance with the fire code.

Page 62 of 94

Page 63: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 13-NFPA 101-2016 [ Section No. 32.2.2.7 ]

32.2.2.7

Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with theprovisions of 24.2.87.1.6.5 .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 12:26:22 EST 2016

Committee Statement

Committee Statement: The revision is needed for consistency with SCR-6, which deletes 7.1.6.5.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 72 12/13/2016 9:32 AM

Page 63 of 94

Page 64: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 40-NFPA 101-2016 [ Section No. 32.2.3.4.1 ]

32.2.3.4.1 General.

A manual fire alarm system shall be provided in accordance with Section 9.6.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 14:58:06 EST 2016

Committee Statement

CommitteeStatement:

No other occupancy chapter mandates the installation of a "manual fire alarm system," which is not defined. Rather, theinitiation means are specified in an "initiation" sub-section. Also see SCR-41.

Second Revision No. 504-NFPA 101-2016 [Section No. 32.2.3.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 72 12/13/2016 9:32 AM

Page 64 of 94

Page 65: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 41-NFPA 101-2016 [ Section No. 32.2.3.4.2 ]

32.2.3.4.2 Initiation.

Initiation of the required fire alarm system shall be by one of the following means:

Manual means in accordance with 9.6.2.1(1)

Automatic sprinkler system that complies with 9.6.2.1(3) and provides protection throughout the building

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 15:00:02 EST 2016

Committee Statement

CommitteeStatement:

The revision re-inserts the initiation sub-section and maintains the requirement for manual initiation, which is consistentwith the intent of SR-504 and SR-505. Also see SCR-40.

Committee Comment No. 505-NFPA 101-2016 [Section No. 32.2.3.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 72 12/13/2016 9:32 AM

Page 65 of 94

Page 66: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 14-NFPA 101-2016 [ Section No. 32.3.2.1.3 ]

32.3.2.1.3

Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with theprovisions of 24.2.87.1.6.5 .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 12:28:32 EST 2016

Committee Statement

Committee Statement: The revision is needed for consistency with SCR-6, which deletes 7.1.6.5.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 72 12/13/2016 9:32 AM

Page 66 of 94

Page 67: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 54-NFPA 101-2016 [ Section No. 32.3.3.6.2 ]

32.3.3.6.2*

Sleeping rooms shall be separated from all spaces, other than adjacent sleeping rooms, adjacent bathrooms, or lounge areas, andbathrooms directly accessible from the sleeping rooms, by walls complying with 32.3.3.6.3 through 32.3.3.6.6.

Supplemental Information

File Name Description

101_SCR-54_Attachment.docx Revised A.32.3.3.6.2

101_SCR-54_A.32.3.3.6.2.docx Shows legislative changes from SCR. For staff use

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 21 09:39:33 EST 2016

Committee Statement

CommitteeStatement:

No change to 32.3.3.6.2. See attachment for revised A.32.3.3.6.2. Revision needed for consistency with 32.3.3.6.2 asraised by Rickard's negative ballot comment.

Committee Comment No. 507-NFPA 101-2016 [Section No. 32.3.3.6.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 72 12/13/2016 9:32 AM

Page 67 of 94

Page 68: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

A.32.3.3.6.2

The purpose of this requirement is to protect sleeping rooms from a fire that occurs in an area that is

outside of the sleeping room or suite of sleeping rooms such as corridors, housekeeping closets, IT

rooms, electrical/mechanical rooms, libraries, offices, conference rooms, quiet rooms and medication

rooms, washer/dryer rooms, common work rooms, common lounges, and common bathrooms. Lounges

and bathrooms Bathrooms that can only be accessed directly from the sleeping room or suite of

sleeping rooms can be considered part of the sleeping room or suite enclosure and, therefore, those

rooms only should meet the requirements of 32.3.3.6.3 through 32.3.3.6.6 where those room walls

either abut a corridor or abut a room other than a sleeping room.

Page 68 of 94

Page 69: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 42-NFPA 101-2016 [ Section No. 32.3.3.8.3 ]

32.3.3.8.3*

Compliance with 9.2.3 shall not be required where all of the following conditions are met:

(1) Residential or commercial cooking equipment in a single kitchen per smoke compartment is used to prepare meals for 30 orfewer persons.

(2) The portion of the board and care facility served by the cooking facility is limited to 30 beds and is separated from other portionsof the board and care facility by a smoke barrier constructed in accordance with 32.3.3.7.9 and with 32.3.3.7.14 through32.3.3.7.22.

(3) The cooktop or range is equipped with a range hood of a width at least equal to the width of the cooking surface, with greasebaffles or other grease-collecting and clean-out capability.

(4)

(5) The hood systems that are not ducted to the exterior additionally have a charcoal filter to remove smoke and odor.

(6) The cooktop or range complies with all of the following:

(a) The cooktop or range is protected with a fire suppression system listed in accordance with ANSI/UL 300, Standard for FireTesting of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, or is tested and meets allrequirements of UL 300A, Extinguishing System Units for Residential Range Top Cooking Surfaces, in accordance with theapplicable testing document's scope.

(b) A manual release of the extinguishing system is provided in accordance with Section 10.5 of NFPA 96.

(c) An interlock is provided to turn off all sources of fuel and electrical power to the cooktop or range when the suppressionsystem is activated.

(7)

(8)

(9) Portable fire extinguishers in accordance with NFPA 96 are located in all kitchen areas.

(10)

(11) Procedures for the use, inspection, testing, and maintenance of the cooking equipment are in accordance with Chapter 11 ofNFPA 96, and the manufacturer’s instructions are followed.

(12)

(13) The smoke alarms required by 32.3.3.8.3(12) are permitted to be located outside the kitchen area where such placement isnecessary for compliance with the 20 ft (6.1 m) minimum distance criterion.

(14) A single system smoke detector is permitted to be installed in lieu of the smoke alarms required in 32.3.3.8.3(12), provided thefollowing criteria are met:

(a) The detector is located not closer than 20 ft (6.1 m) and not farther than 25 ft (7.6 m) from the cooktop or range.

(b) The detector is permitted to initiate a local audible alarm signal only.

(c) The detector is not required to initiate a buildingwide occupant notification signal.

(d) The detector is not required to notify emergency forces.

(e) The local audible signal initiated by the detector is permitted to be silenced and reset by a button on the detector or by aswitch installed within 10 ft (3.0 m) of the system smoke detector.

(f) System smoke detectors that are required by other sections of the chapter to be installed in corridors or spaces open to thecorridor are not used to meet the requirements of 32.3.3.8.3(12) and are located not closer than 25 ft (7.6 m) to thecooktop or range.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

* The hood systems have a minimum airflow of 500 cfm (14,000 L/min).

* The use of solid fuel for cooking is prohibited.

* Deep-fat frying is prohibited.

* A switch meeting all of the following is provided:

(a) A locked switch, or a switch located in a restricted location, is provided within the cooking facility that deactivates thecooktop or range.

(b) The switch is used to deactivate the cooktop or range whenever the kitchen is not under staff supervision.

(c) The switch is on a timer, not exceeding a 120-minute capacity, that automatically deactivates the cooktop or range,independent of staff action.

* No less No fewer than two ac-powered photoelectric smoke alarms, interconnected in accordance with 9.6.2.10.3 andequipped with a silence feature, are located not closer than 20 ft (6.1 m) and not farther than 25 ft (7.6 m) from the cooktop orrange.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

50 of 72 12/13/2016 9:32 AM

Page 69 of 94

Page 70: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

City:

State:

Zip:

Submittal Date: Fri Nov 18 15:03:40 EST 2016

Committee Statement

Committee Statement: The term 'fewer' in Item (12) is correct when referring to countable items.

Committee Comment No. 518-NFPA 101-2016 [Section No. 32.3.3.8.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

51 of 72 12/13/2016 9:32 AM

Page 70 of 94

Page 71: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 43-NFPA 101-2016 [ Section No. 33.2.3.4.1 ]

33.2.3.4.1 Fire Alarm Systems.

A manual fire alarm system shall be provided in accordance with Section 9.6, unless the provisions of 33.2.3.4.1.1 or 33.2.3.4.1.2are met.

33.2.3.4.1.1

A fire alarm system shall not be required where interconnected smoke alarms complying with 33.2.3.4.4 33.2.3.4.3 33.2.3.4.4 andnot less than one manual fire alarm box per floor arranged to continuously sound the smoke detector alarms are provided.

33.2.3.4.1.2

Other manually activated continuously sounding alarms acceptable to the authority having jurisdiction shall be permitted in lieu of afire alarm system.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 15:07:21 EST 2016

Committee Statement

CommitteeStatement:

No other occupancy chapter mandates the installation of a "manual fire alarm system," which is not defined. Rather, theinitiation means are specified in an "initiation" sub-section. Also see SCR-44.

Second Revision No. 512-NFPA 101-2016 [Section No. 33.2.3.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

52 of 72 12/13/2016 9:32 AM

Page 71 of 94

Page 72: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 44-NFPA 101-2016 [ Section No. 33.2.3.4.2 ]

33.2.3.4.2 Initiation.

Where a fire alarm system is required by 33.2.3.4.1 , initiation shall be by one of the following means:

Manual means in accordance with 9.6.2.1(1)

Automatic sprinkler system that complies with 9.6.2.1(3) and provides protection throughout the building.

33.2.3.4.2 Initiation.

Initiation of the required fire alarm system shall be by manual means in accordance with 9.6.2.1(1) .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 15:10:09 EST 2016

Committee Statement

CommitteeStatement:

The revision re-inserts the initiation sub-section and maintains the requirement for manual initiation, which is consistentwith the intent of SR-512 and SR-513. Also see SCR-43.

Committee Comment No. 513-NFPA 101-2016 [Section No. 33.2.3.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

53 of 72 12/13/2016 9:32 AM

Page 72 of 94

Page 73: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 4-NFPA 101-2016 [ Section No. 36.1.4.2 ]

36.1.4.2 Special Definitions.

A list of special terms used in this chapter follows:

(1) Anchor Building. See 3.3.37.2.

(2) Bulk Merchandising Retail Building. See 3.3.37.4.

(3) Enclosed Mall Concourse. See 3.3.175.2 .

(4) Food Court. See 3.3.51.2

(5) Gross Leasable Area. See 3.3.22.3.

(6) Major Tenant. See 3.3.174.

(7) Mall Concourse. See 3.3.175.

(8) Mall Structure. See 3.3.282.4.

(9) Open Mall Concourse . See 3.3.175.1 .

(10) Open-Air Mercantile Operation. See 3.3.205.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 10:20:36 EST 2016

Committee Statement

Committee Statement: The SCR is intended for consistency with SCR-3.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

54 of 72 12/13/2016 9:32 AM

Page 73 of 94

Page 74: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 15-NFPA 101-2016 [ New Section after 36.2.1.5 ]

36.2.1.6 Grab Bars for Bathtubs, Bathtub-Shower Combinations, and Showers.

36.2.1.6.1

Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with theprovisions of 24.2.8 .

36.2.1.6.2

The provisions of 36.2.1.6.1 shall not apply to display bathtubs, bathtub-shower combinations, or showers.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 12:45:54 EST 2016

Committee Statement

Committee Statement: The revision is needed for consistency with SCR-6, which deletes 7.1.6.5.

Committee Comment No. 5502-NFPA 101-2016 [New Section after 36.2.1.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

55 of 72 12/13/2016 9:32 AM

Page 74 of 94

Page 75: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 45-NFPA 101-2016 [ New Section after 36.4.4.7.4 ]

36.4.4.7.5 Risk Analysis for Mass Notification.

A risk analysis in accordance with Section 9.14 shall be performed for new mall structures to determine whether a massnotification system is required.

Supplemental Information

File Name Description

101_SCR-45_36.4.4.7.5.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 15:17:15 EST 2016

Committee Statement

Committee Statement: Revisions intended for consistency with format of other occupancy chapters.

Committee Comment No. 5509-NFPA 101-2016 [New Section after 36.4.4.7.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

56 of 72 12/13/2016 9:32 AM

Page 75 of 94

Page 76: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

36.4.4.7.5 Risk Analysis for Mass Notification.

Mall structures shall conduct aA risk analysis in accordance with Section 9.14 shall be

performed for new mall structures to determine the need forif a mass notification system in

accordance with Section 9.14is required.

Page 76 of 94

Page 77: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 5-NFPA 101-2016 [ Section No. 37.1.4.2 ]

37.1.4.2 Special Definitions.

A list of special terms used in this chapter follows:

(1) Anchor Building. See 3.3.37.2.

(2) Bulk Merchandising Retail Building. See 3.3.37.4.

(3) Enclosed Mall Concourse . See 3.3.175.2 .

(4) Gross Leasable Area. See 3.3.22.3.

(5) Major Tenant. See 3.3.174.

(6) Mall Concourse. See 3.3.175.

(7) Mall Structure. See 3.3.282.4.

(8) Open Mall Concourse . See 3.3.175.1 .

(9) Open-Air Mercantile Operation. See 3.3.205.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 10:27:12 EST 2016

Committee Statement

Committee Statement: The SCR is intended for consistency with SCR-3.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

57 of 72 12/13/2016 9:32 AM

Page 77 of 94

Page 78: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 46-NFPA 101-2016 [ Section No. 37.3.2.3 ]

37.3.2.3* Hazardous Materials.

Where hazardous materials are present stored, used, or handled, the provisions of 8.7.3.1 shall apply.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 15:21:19 EST 2016

Committee Statement

Committee Statement: Revision intended to correlate with other occupancy chapters.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

58 of 72 12/13/2016 9:32 AM

Page 78 of 94

Page 79: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 16-NFPA 101-2016 [ New Section after 38.2.1.4 ]

38.2.1.5 Grab Bars for Bathtubs, Bathtub-Shower Combinations, and Showers.

38.2.1.5.1

Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with theprovisions of 24.2.8 .

38.2.1.5.2

The provisions of 38.2.1.5.1 shall not apply to display bathtubs, bathtub-shower combinations, or showers.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 12:49:08 EST 2016

Committee Statement

Committee Statement: The revision is needed for consistency with SCR-6, which deletes 7.1.6.5.

Committee Comment No. 5503-NFPA 101-2016 [New Section after 38.2.1.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

59 of 72 12/13/2016 9:32 AM

Page 79 of 94

Page 80: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 48-NFPA 101-2016 [ New Section after 38.2.2.2.1 ]

38.2.2.2.2* Door Locking to Prevent Unwanted Entry.

Where approved, doors, other than those complying with 38.2.11.2 , shall be permitted to be locked to prevent unwanted entryprovided that all of the following conditions are met:

(1) The locking means shall be capable of being engaged without opening the door.

(2) The unlocking and unlatching operation from the egress side of the door shall be accomplished without the use of a key, tool,or special knowledge or effort.

(3) The releasing mechanism shall open the door leaf with not more than one releasing operation.

(4) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and notexceeding 48 in. (1220 mm) above the finished floor.

(5) Locks, if remotely engaged, shall be unlockable from the egress side of the door without the use of a key, tool, or specialknowledge or effort.

(6) The door shall be capable of being unlocked and opened from outside the room with the necessary key or other credential.

(7) The locking means shall not modify the door closer, panic hardware, or fire exit hardware.

(8) Modifications to required fire door assemblies, including door hardware, shall be in accordance with NFPA 80 .

Supplemental Information

File Name Description

101_SCR-48_38.2.2.2.2.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 15:26:48 EST 2016

Committee Statement

Committee Statement: Revision for compliance with Manual of Style.

Committee Comment No. 5507-NFPA 101-2016 [New Section after 38.2.2.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

60 of 72 12/13/2016 9:32 AM

Page 80 of 94

Page 81: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

38.2.2.2.2* Door Locking to Prevent Unwanted Entry.

Where approved, doors, other than those complying with 38.2.11.2, shall be permitted to be

locked to prevent unwanted entry provided that all of the following conditions are met:

(1) The locking means shall be capable of being engaged without opening the door.

(2) The unlocking and unlatching operation from the egress side of the door shall be

accomplished without the use of a key, a or tool, or special knowledge or effort.

(3) The releasing mechanism shall open the door leaf with not more than one releasing operation.

(4) The releasing mechanism for unlocking and unlatching shall be located at a height not less

than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor.

(5) Locks, if remotely engaged, shall be unlockable from the egress side of the door without the

use of a key, a tool, or special knowledge or effort.

(6) The door isshall be capable of being unlocked and opened from outside the room with the

necessary key or other credential.

(7) The locking means doesshall not modify the door closer, panic hardware, or fire exit

hardware.

(8) Modifications to required fire door assemblies, including door hardware, shall be in

accordance with NFPA 80.

Page 81 of 94

Page 82: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 47-NFPA 101-2016 [ Section No. 38.2.11.3 ]

38.2.11.3* Hazardous Materials.

Where hazardous materials are stored, used, or handled, the provisions of 7.12.2 shall apply.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 15:24:11 EST 2016

Committee Statement

Committee Statement: Revision intended to correlate with other occupancy chapters.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

61 of 72 12/13/2016 9:32 AM

Page 82 of 94

Page 83: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 50-NFPA 101-2016 [ New Section after 39.2.2.2.1 ]

39.2.2.2.2* Door Locking to Prevent Unwanted Entry.

Where approved, doors, other than those complying with 39.2.11.2 , shall be permitted to be locked to prevent unwanted entryprovided that all of the following conditions are met:

(1) The locking means shall be capable of being engaged without opening the door.

(2) The unlocking and unlatching operation from the egress side of the door shall be accomplished without the use of a key, tool,or special knowledge or effort.

(3) The releasing mechanism shall open the door leaf with not more than two releasing operations.

(4) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and notexceeding 48 in. (1220 mm) above the finished floor.

(5) Locks, if remotely engaged, shall be unlockable from the egress side of the door without the use of a key, tool, or specialknowledge or effort.

(6) The door shall be capable of being unlocked and opened from outside the room with the necessary key or other credential.

(7) The locking means shall not modify the door closer, panic hardware, or fire exit hardware.

(8) Modifications to required fire door assemblies, including door hardware, shall be in accordance with NFPA 80 .

Supplemental Information

File Name Description

101_SCR-50_39.2.2.2.2.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 21 09:28:18 EST 2016

Committee Statement

CommitteeStatement:

Revisions for compliance with the Manual of Style. Also Item 3, which would require not more than one releasing operation,conflicts with Item 4, which permits two operations. It appears that Item 3 was intended to apply to the installation of newhardware on existing doors; this situation is addressed by Ch. 43, which will require such installation to comply with Ch. 38.

Committee Comment No. 5508-NFPA 101-2016 [New Section after 39.2.2.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

62 of 72 12/13/2016 9:32 AM

Page 83 of 94

Page 84: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

39.2.2.2.2* Door Locking to Prevent Unwanted Entry.

Where approved, doors, other than those complying with 39.2.11.2, shall be permitted to be locked to prevent unwanted entry provided that all of the following conditions are met:

(1) The locking means shall be capable of being engaged without opening the door.

(2) The unlocking and unlatching operation from the egress side of the door shall be accomplished without the use of a key, aor tool, or special knowledge or effort.

(3) The releasing mechanism shall open the door leaf with not more than one two releasing operationoperations.

(4) For existing doors, the releasing mechanism shall open the door leaf with not more than two releasing operations.

(45) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor.

(65) Locks, if remotely engaged, shall be unlockable from the egress side of the door without the use of a key, a tool, or special knowledge or effort.

(67) The door is shall be capable of being unlocked and opened from outside the room with the necessary key or other credential.

(87) The locking means does shall not modify the door closer, panic hardware, or fire exit hardware.

(98) Modifications to required fire door assemblies, including door hardware, shall be in accordance with NFPA 80.

Page 84 of 94

Page 85: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 17-NFPA 101-2016 [ New Section after 40.2.1.2 ]

40.2.1.3

Newly installed bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars inaccordance with the provisions of 24.2.8 .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 12:54:30 EST 2016

Committee Statement

Committee Statement: The revision is needed for consistency with SCR-6, which deletes 7.1.6.5.

Committee Comment No. 4502-NFPA 101-2016 [New Section after 40.2.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

63 of 72 12/13/2016 9:32 AM

Page 85 of 94

Page 86: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 51-NFPA 101-2016 [ Section No. 40.2.11.3 ]

40.2.11.3 Hazardous Materials.

Where hazardous materials are stored, used, or handled, the provisions of 7.12.2 shall apply.

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 21 09:31:33 EST 2016

Committee Statement

Committee Statement: Revision intended to correlate with other occupancy chapters.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

64 of 72 12/13/2016 9:32 AM

Page 86 of 94

Page 87: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 18-NFPA 101-2016 [ New Section after 42.2.1.2 ]

42.2.1.3

Newly installed bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars inaccordance with the provisions of 24.2.8 .

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 18 13:01:40 EST 2016

Committee Statement

Committee Statement: The revision is needed for consistency with SCR-6, which deletes 7.1.6.5.

Committee Comment No. 4503-NFPA 101-2016 [New Section after 42.2.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

65 of 72 12/13/2016 9:32 AM

Page 87 of 94

Page 88: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 52-NFPA 101-2016 [ Section No. 42.3.2 ]

42.3.2 Protection from Hazards.

Where hazardous materials are stored, used, or handled, the provisions of 8.7.3.1 shall apply. (See also Section 8.7 .)

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 21 09:33:44 EST 2016

Committee Statement

Committee Statement: Revision intended to correlate with other occupancy chapters.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

66 of 72 12/13/2016 9:32 AM

Page 88 of 94

Page 89: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 53-NFPA 101-2016 [ Section No. A.4.8.2.1 ]

A.4.8.2.1

Items to be considered in preparing an emergency action plan should include the following:

(1) Purpose of plan

(2) Building description, including certificate of occupancy

(3) Appointment, organization, and contact details of designated building staff to carry out the emergency duties

(4) Identification of events (man-made and natural) considered life safety hazards impacting the building

(5) Responsibilities matrix (role-driven assignments)

(6) Policies and procedures for those left behind to operate critical equipment

(7) Specific procedures to be used for each type of emergency

(8) Requirements and responsibilities for assisting people with disabilities

(9) Procedures for accounting for employees

(10) Training of building staff, building emergency response teams, and other occupants in their responsibilities

(11) Documents, including diagrams, showing the type, location, and operation of the building emergency features, components, andsystems

(12) Practices for controlling life safety hazards in the building

(13) Inspection and maintenance of building facilities that provide for the safety of occupants

(14) Conducting fire and evacuation drills

(15) Interface between key building management and emergency responders

(16) Names or job titles of persons who can be contacted for further information or explanation of duties

(17) Post-event (including drill) critique/evaluation, as addressed in Chapter 9 5.14 of of NFPA 1600

(18) Means to update the plan, as necessary

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 21 09:35:51 EST 2016

Committee Statement

Committee Statement: Updates cross-reference to NFPA 1600.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

67 of 72 12/13/2016 9:32 AM

Page 89 of 94

Page 90: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Second Correlating Revision No. 57-NFPA 101-2016 [ Section No. A.7.6 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

68 of 72 12/13/2016 9:32 AM

Page 90 of 94

Page 91: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

A.7.6

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

69 of 72 12/13/2016 9:32 AM

Page 91 of 94

Page 92: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Table A.7.6 is a compilation of the requirements of the individual occupancy chapters (Chapters 12 through 42) for permissiblelength of common path of travel, dead-end corridors, and travel distance to not less than one of the required exits.

A dead end exists where an occupant enters a corridor thinking there is an exit at the end and, finding none, is forced to retrace thepath traveled to reach a choice of egress travel paths. Although relatively short dead ends are permitted by this Code, it is betterpractice to eliminate them wherever possible, as they increase the danger of persons being trapped in case of fire. Compliance withthe dead-end limits does not necessarily mean that the requirements for remoteness of exits have been met. Such lack ofcompliance is particularly true in small buildings or buildings with short public hallways. Adequate remoteness can be obtained insuch cases by further reducing the length of dead ends. (See also A.7.5.1.5.)

Common Path Limit

Sprinklered

Board and Care

Large, new 75 23

...

Travel Distance Limit

Sprinklered

Board and Care

Large, new 250 76

Table A.7.6 Common Path, Dead-End, and Travel Distance Limits (by occupancy)

Common Path Limit Dead-End Limit Travel Distan

Type ofOccupancy

Unsprinklered Sprinklered Unsprinklered Sprinklered Unsprinklered

ft m ft m ft m ft m ft m

Assembly

New 20/75 6.1/23a 20/75 6.1/23a 20 6.1b 20 6.1b 200 61c

Existing 20/75 6.1/23a 20/75 6.1/23a 20 6.1b 20 6.1b 200 61c

Educational

New 75 23 100 30 20 6.1 50 15 150 46

Existing 75 23 100 30 20 6.1 50 15 150 46

Day Care

New 75 23 100 30 20 6.1 50 15 150 46d

Existing 75 23 100 30 20 6.1 50 15 150 46d

Health Care

New NA NA 100 30 NA NA 30 9.1 NA NA

Existing NR NR NR NR NR e 30 e NR e 9

1 e NR e 30 e NR e 9.1 e 150 46d

AmbulatoryHealth Care

New 75 23 f 23 100 30 f 30 20 6.1 50 15 150 46

Existing 75 23 f 23 100 30 f 30 50 15 50 15 150 46

Detention andCorrectional

New — UseCondition II, III,IV

50 15 100 30 50 15 50 15 150 46d

New — UseCondition V

50 15 100 30 20 6.1 20 6.1 150 46d

Existing — UseCondition II, III,IV, V

50 15g 100 30g NR NR NR NR 150 46d

Residential

One- andtwo-familydwellings

NR NR NR NR NR NR NR NR NR NR

Lodging orrooming houses

NR NR NR NR NR NR NR NR NR NR

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

70 of 72 12/13/2016 9:32 AM

Page 92 of 94

Page 93: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Common Path Limit Dead-End Limit Travel Distan

Type ofOccupancy

Unsprinklered Sprinklered Unsprinklered Sprinklered Unsprinklered

ft m ft m ft m ft m ft m

Hotels anddormitories

New 35 10.7h,i 50 15h,i 35 10.7 50 15 175 53d,j

Existing 35 10.7h 50 15h 50 15 50 15 1 175 53d,i j

Apartmentbuildings

New 35 10.7h 50 15h 35 10.7 50 15 175 53d,j

Existing 35 10.7h 50 15h 50 15 50 15 175 53d,j

Board and care

Small, new andexisting

NR NR NR NR NR NR NR NR NR NR

Large, new NA NA 75 23i NA NA 30 9.1 NA NA

Large, existing 110 33 160 49 50 15 50 15 175 53d,j

Mercantile

Class A, B, C

New 75 23 100 30 20 6.1 50 15 150 46

Existing 75 23 100 30 50 15 50 15 150 46

Open air, newand existing

NR NR NR NR 0 0 0 0 NR NR

Mall

New 75 23 100 30 20 6.1q 50 15q 150 46 4

Existing 75 23 100 30 50 15q 50 15q 150 46 4

Business

New 75 23l 100 30l 20 6.1 50 15 200 61

Existing 75 23l 100 30l 50 15 50 15 200 61

Industrial

General 50 15 100 30 50 15 50 15 200 61 m 61 n

Special purpose 50 15 100 30 50 15 50 15 300 91

High hazard0 footnote

r0 footnote

r0 footnote

r0 footnote

r0 footnote

r0 footnote

r0 footnote

r0 footnote r 0 NA 0 NA

Aircraft servicinghangars, finishedground level floor

50 15o 100 30o 50 15o 50 15o footnotem

footnote mfo

Aircraft servicinghangars,mezzanine floor

50 15o 75 23o 50 15o 50 15o 75 23

Storage

Low hazard NR NR NR NR NR NR NR NR NR NR

Ordinary hazard 50 15 100 30 50 15 100 30 200 61

High hazard0 footnote

r0 footnote

r0 footnote

r0 footnote

r0 footnote

r0 footnote

r0 footnote

r0 footnote r 75 23

Parking

structures, openp 50 15 50 15 50 15 50 15 300 91

Parkingstructures,enclosed

50 15 50 15 50 15 50 15 150 46

Aircraft storagehangars, finishedground level floor

50 15o 100 30o 50 15o 50 15o footnotem

footnote mfo

Aircraftservicing storagehangars,mezzanine floor

50 15o 75 23o 50 15o 50 15o 75 23

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

71 of 72 12/13/2016 9:32 AM

Page 93 of 94

Page 94: Page 1 of 94 - National Fire Protection Association...Second Correlating Revision No. 1-NFPA 101-2016 [ Global Input ] Replace the term "delayed egress electrically locking system"

Common Path Limit Dead-End Limit Travel Distan

Type ofOccupancy

Unsprinklered Sprinklered Unsprinklered Sprinklered Unsprinklered

ft m ft m ft m ft m ft m

Undergroundspaces in grainelevators

50 15o 100 30o 50 15o 100 30o 200 61

NR: No requirement. NA: Not applicable.

aFor common path serving >50 persons, 20 ft (6.1 m); for common path serving ≤50 persons, 75 ft (23 m).

bDead-end corridors of 20 ft (6.1 m) permitted; dead-end aisles of 20 ft (6.1 m) permitted.

cSee Chapters 12 and 13 for special considerations for smoke-protected assembly seating in arenas and stadia.

dThis dimension is for the total travel distance, assuming incremental portions have fully utilized their permitted maximums. Fortravel distance within the room, and from the room exit access door to the exit, see the appropriate occupancy chapter.

eSee 19.2.5.2.

f See business occupancies, Chapters 38 and 39.

gSee Chapter 23 for special considerations for existing common paths.

hThis dimension is from the room/corridor or suite/corridor exit access door to the exit; thus, it applies to corridor common path.

iSee the appropriate occupancy chapter for requirements for second exit access based on room area.

jSee the appropriate occupancy chapter for special travel distance considerations for exterior ways of exit access.

kSee 36.4.4 and 37.4.4 for special travel distance considerations in covered malls considered to be pedestrian ways mallconcourses .

lSee Chapters 38 and 39 for special common path considerations for single-tenant spaces.

mSee Chapters 40 and 42 for special requirements on spacing of doors in aircraft hangars.

nSee Chapter 40 for industrial occupancy special travel distance considerations.

oSee Chapters 40 and 42 for special requirements if high hazard conditions exist.

pSee 42.8.2.6.2 for special travel distance considerations in open parking structures.

q See 36.4.4 and 37.4.4 for special dead- end considerations in mall concourses.

r See 7.11.4 for high hazard contents areas.

Supplemental Information

File Name Description

101_SCR-57_A.7.6.docx Shows legislative changes from SCR

Submitter Information Verification

Submitter Full Name: Gregory Harrington

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 21 09:52:26 EST 2016

Committee Statement

Committee Statement: Updates to Table A.7.6 to correlate with applicable occupancy chapters.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

72 of 72 12/13/2016 9:32 AM

Page 94 of 94