The Walker Group Architecture, Inc PO Box 541, New Bern, NC 28563 252.636.8778 (PHONE) 252.636.8992 (FAX) WALKER GROUP i n c o r p o r a t e d the ARCHITECTURE DISCLOSURE OF INFORMATION CONTRACTOR SHALL COMPLY AS FOLLOWS: (A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS- (1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR (2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE (B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE. (C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZ TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER. 02/24/2020 ROAD SIDE DIRECTION OF TRAFFIC ADDITIONAL GROUND RODS (WHEN REQUIRED) PLAN ALWAYS CONNECT THE POLE GROUND LEAD(S) DIRECTLY TO THE NEUTRAL- ENSURE THAT THE COPPER CONDUCTOR WILL ALWAYS BE BELOW THE ALUMINUM. CONNECTOR NEUTRAL COPPERWELD STAPLES (TYP.) GROUND WIRE POLE ELEVATION GROUND ROD PLASTIC OR FIBER MOLDING GALVANIZED STAPLES (TYPICAL) FINISHED GRADE #4 BARE COPPER POLE OH-41 JUNE 2002 SKETCH DATE STYLE GROUND 24" MIN. 10'-0" MIN. 10'-0" MIN. 24" 12" 8'-0" MIN. 18" MAX. 8'-0 MIN. (FROM 24'-4" TO 16'-4" ABOVE GRADE) ALTERNATE GROUND WIRE POSITION. (USE WHEN MULTIPLE GROUNDING SYSTEMS ARE REQUIRED.) (SEE NOTE 4) 1. 2. 3. NOTES USE ADDITIONAL GROUND RODS, WHEN REQUIRED, TO OBTAIN RESISTANCE VALUE, AS REQUIRED BY IEEE C2. MAKE GROUNDING CONNECTIONS TO ALL EQUIPMENT ON POLE AS REQUIRED BY IEEE C2. FOR SYSTEMS OTHER THAN 4 WIRE, MULTI- GROUNDED, USE SEPARATE GROUNDING CONDUCTORS AND ELECTRODES FOR PRIMARY AND SECONDARY SYSTEM DEVICE CONNECTIONS. #4 600V INSULATED COPPER GROUNDING CONDUCTOR REQUIRED ON PRIMARY SYSTEM WHEN SEPARATE SYSTEMS ARE REQUIRED. 4. AF-1 APRIL 2015 GENERAL ARC FLASH WARNING LABEL SKETCH DATE STYLE NOTES: 1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT TO WARN OF ARC FLASH HAZARDS. 2. THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH THE FIGURE. 3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE EQUIPMENT. 4. THE SIZE OF THE LABEL SHALL BE MINIMUM: EQUIPMENT TYPE HEIGHT WIDTH INDOOR 2" 3" OUTDOOR 3" 4.5" 5. A DOWNLOADABLE WINDOWS METAFILE IS AVAILABLE ON THE WHOLE BUILDING DESIGN GUIDE WEBSITE ( WWW.WDBG.ORG) FOR USE IN A LABEL MAKING MACHINE. A. THE FILE IS LOCATED ON THE "NAVFAC CADD DETAILS" PAGE. TO NAVIGATE TO THIS LOCATION, FOLLOW: HOME > DOCUMENTS & REFERENCES > CCB > CADD LIBRARY > NAVFAC CADD RESOURCES > NAVFAC CADD DETAILS. B. ALTERNATIVELY, TYPE IN THE FOLLOWING ADDRESS IN INTERNET EXPLORER: HTTP://WWW.WBDG.ORG/CCB/BROWSE_CAT.PHP?C=232 WIDTH HEIGHT (SEE NOTE 1) SERVICE CAP CLAMP TYPE SECONDARY CONDUCTOR NEUTRAL OR TOP GRADE FINISHED GALVANIZED STEEL CONDUIT-SIZE AS INDICATED SEE NOTE 3 SEE NOTE 2 CONDUIT LOCATION OF TRAFFIC DIRECTION ROAD SIDE POSITION RISER ALTERNATE POSITION RISER POLE 1. 2. 3. DIRECT BURIED CABLE DIRECT BURIED CONDUIT TYPE C OH-35 JUNE 2002 (SIZE & TYPE AS INDICATED) CONDUIT RISER SKETCH DATE STYLE TYPE A CONCRETE ENCASED CONDUIT TYPE B 18" MIN. 37 35 36 35 36 38 6 33 34 2" MIN. NOTES ON CONDUIT RISER FOR PRIMARY CIRCUITS, ELIMINATE SERVICE CAP AND PROVIDE GROUNDING TYPE INSULATING BUSHING. BOND CONDUIT TO POLE GROUND AND SYSTEM NEUTRAL (IF EXISTING). SEE GROUNDING NOTES ON SKETCH OH-41. SPACE STRAPS AT MAXIMUM OF 4' INTERVALS. 1'-6" O.C. 3" MINIMUM FINISHED GRADE DUCTBANK MARKING TAPE 3000 P.S.I. CONCRETE P.V.C. CONDUIT SIZE AS INDICATED LEVELING BLOCKS AT BASE SPACERS 24" MIN. EQUAL EQUAL 3" MINIMUM SEPARATION (TYP.) BASE SPACERS (TYP.) NOTE: # OF DUCTS SHALL BE AS INDICATED ON PLANS. 3" SECONDARY TRANSFORMER BOX GRADE TERMINATIONS LOW VOLTAGE CABLE CURRENT TRANSFORMERS (800/5) 3-POLE FUSE BLOCK SECONDARY CIRCUIT WHD #4/0 BARE MIN 2'-0" GRADE. PAD. MIN 18" BELOW FINISHED ENCIRCLING ENTIRE CONCRETE #4/0 BARE COPPER GROUND LOOP 600V INSULATION CORNER OF PAD. OF 4, 1 AT EACH GROUND ROD, TYP GROUND PAD (TYP OF 2) #4/0, 600V INSULATION PRIMARY CIRCUIT CONNECTOR LOAD BREAK PRIMARY NEUTRAL BUSHING INSERT BREAK OIL SWITCH 2 POSITION LOAD CURRENT-LIMITING OIL-IMMERSED PRIMARY COMPARTMENT ARRESTERS SURGE TRANSFORMER BUSHING WELL X0 BAYONET OIL-IMMERSED EXPULSION FUSES FUSES CABLE WELL TRANSFORMER BOX, SEE DETAIL THIS SHEET. G G G G GROUND ROD - 3/4" x 10' CONNECT TO CONDUCTORS BY EXOTHERMIC WELD (TYP) PAD MOUNTED COMPARTMENTAL TYPE TRANSFORMER (SECURE TO TRANSFORMER BOX PER MANUFACTURER'S RECOMMENDATION). SECONDARY NEUTRAL GROUND NO. 4/0 AWG CU MINIMUM TRANSFORMER SECTION EXOTHERMIC WELD (TYP) EQUIPMENT GROUND OUTGOING SECONDARY CONDUIT(S) (NUMBER AS NOTED ON PLANS) PRIMARY CONDUIT NUMBER AS NOTED ON PLANS EXTEND GRAVEL FILL A MINIMUM OF ONE FOOT BEYOND PAD ON ALL SIDES. WELL COMPACTED GRAVEL SUBSURFACE SHALL BE 6 INCHES THICK EXTEND PAD A MINIMUM OF 8 INCHES BEYOND UNIT ON ALL SIDES PAD MOUNTED TRANSFORMER DETAIL NOT TO SCALE TYPICAL PAD MOUNTED COMPARTMENTAL TRANSFORMER DETAIL NOT TO SCALE COMPARTMENT X 10" 10" 6" 9" 18" 2-1/2" 18" 29" 29" 5" 18" TRANSFORMER BOX DETAIL (DETAIL BASED ON PARKING BUMPER COMAPNY STANDARD DETAILS) CONCRETE ENCASED DUCTBANK - DETAIL 'A' NOT TO SCALE CONNECTOR LOOP FEED WATTHOUR DEMAND METER: TO CONFORM TO BASE STANDARDS. ITRON V&I CS3 SERIES METER. PRIMARY JUNCTION ENCLOSURE CONCRETE 14" 14" PLAN SIDE ELEVATION FRONT ELEVATION DEAD FRONT MODULE 'U' STRAPS SUPPLIED WITH MODULE. MOUNT 'U' STRAPS CLAMPS (6) SUPPLIED WITH ENCLOSURE) OVER 'U' STRAPS TO SECURE TO MODULE. DEAD FRONT BUSHING WELL INSERT CONNECTOR. UNDERGROUND PRIMARY CONDUIT UNDERGROUND PRIMARY CONDUIT PRIMARY CABLES FINISHED GRADE CONCRETE 18" 23" 62" DEAD FRONT PARKING STAND DEAD FRONT MODULE GROUND LUG (TYPICAL OF 3) CONCRETE GRADE TOP IN OPENED POSITION. LIFTING LUGS (TYPICAL FOR 4) GROUND LINE, DO NOT FILL INTERIOR OF ENCLOSURE. 46-1/4" 3" 32" 41" THREE PHASE, FULLY DEAD FRONT, 2-WAY SECTIONALIZING PEDESTAL WITH 15KV, 600 AMP RATINGS. PROVIDE INDUSTRY STANDARD DEAD FRONT JUNCTION MODULES AND ELBOWS CONFORMING TO ANSI/IEEE 386. UNIT SHALL BE DESIGNED FOR DIRECT BURIAL WITH THE JUNCTION MODULES MOUNTED ABOVE GROUND LINE. PEDESTAL SHALL BE IN CONFORMANCE WITH ANSI C57.12.28 ENCLOSURE IS A ONE PIECE METAL UNIT WITH SWING UP TOP. CABLES/CONDUIT SHALL ENTER/EXIT SO THAT LOAD BREAK ELBOWS AND CABLES MAY BE OPERATED FROM FEED THRUS ON PARKING STANDS OR JUNCTIONS. DO NOT INSTALL CONDUIT BENDS TO TRAIN ELBOWS. THIS SHALL ALLOW MORE CABLE MOVEMENT AND FREEDOM FOR FUTURE SWITCHING. INCOMING CABLES SHALL BE PROPERLY PHASED AND LABELED BEFORE THEY ARE POSITIONED AS SHOWN. ENCLOSURE WILL ACCEPT THREE PRIMARY JUNCTION MODULES. DO NOT INSTALL PRIMARY JUNCTION MODULES WITH WALL MOUNTING BRACKETS. ENCLOSURE SHALL BE CORROSION RESISTANT AND SHALL BE FABRICATED OF STAINLESS STEEL CONFORMING TO ASTM A 167, TYPE 304 OR 304L. PAINT ENCLOSURE MUNSELL 7GY3.29/1.5 GREEN. PAINT COATING SYSTEM SHALL COMPLY WITH NEMA C57.12.28. THE MUNSELL COLOR NOTATION IS SPECIFIED IN ASTM D 1535. PROVIDE 15 KV 600 AMP ELBOW CONNECTOR FOR EACH TERMINATION. PROVIDE FAULT INDICATORS ON EACH OUTPUT. 1. 2. 3. 4. 5. 6. 7. NOTES: PAD MOUNT PRIMARY TAP BOX DETAIL NOT TO SCALE

PAD MOUNTED TRANSFORMER DETAIL GENERAL ARC FLASH …

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PAD MOUNTED TRANSFORMER DETAIL GENERAL ARC FLASH …

The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)

WALKERGROUP

i n c o r p o r a t e d

the

ARCHITECTURE

DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

02/24/2020

ROAD SIDE

DIRECTIONOF TRAFFIC

ADDITIONALGROUND RODS(WHEN REQUIRED)

PLAN

ALWAYS CONNECT THE POLE GROUNDLEAD(S) DIRECTLY TO THE NEUTRAL-ENSURE THAT THE COPPER CONDUCTORWILL ALWAYS BE BELOW THE ALUMINUM.

CONNECTOR

NEUTRAL COPPERWELD STAPLES (TYP.)

GROUNDWIRE

POLE

ELEVATION

GROUND ROD

PLASTIC OR FIBER MOLDINGGALVANIZED STAPLES (TYPICAL)

FINISHEDGRADE

#4 BARECOPPER

POLE

OH-41JUNE 2002SKETCH DATE STYLE

GROUND

24"MIN.

10'-0"MIN.

10'-0"MIN.

24"

12"

8'-0"MIN.

18"MAX.

8'-0 MIN.(FROM 24'-4"

TO 16'-4"ABOVE GRADE)

ALTERNATE GROUND WIREPOSITION. (USE WHENMULTIPLE GROUNDINGSYSTEMS ARE REQUIRED.)

(SEE NOTE 4)

1.

2.

3.

NOTES

USE ADDITIONAL GROUND RODS, WHEN REQUIRED,TO OBTAIN RESISTANCE VALUE, AS REQUIRED BYIEEE C2.MAKE GROUNDING CONNECTIONS TO ALL EQUIPMENTON POLE AS REQUIRED BY IEEE C2.FOR SYSTEMS OTHER THAN 4 WIRE, MULTI-GROUNDED, USE SEPARATE GROUNDING CONDUCTORS AND ELECTRODES FOR PRIMARYAND SECONDARY SYSTEM DEVICE CONNECTIONS.#4 600V INSULATED COPPER GROUNDINGCONDUCTOR REQUIRED ON PRIMARY SYSTEMWHEN SEPARATE SYSTEMS ARE REQUIRED.

4.

AF-1APRIL 2015

GENERAL ARC FLASH WARNING LABELSKETCH DATE STYLE

NOTES:

1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT TO WARN OF ARCFLASH HAZARDS.

2. THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH THE FIGURE.

3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE TO QUALIFIEDPERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THEEQUIPMENT.

4. THE SIZE OF THE LABEL SHALL BE MINIMUM:

EQUIPMENT TYPE HEIGHT WIDTH INDOOR 2" 3" OUTDOOR 3" 4.5"

5. A DOWNLOADABLE WINDOWS METAFILE IS AVAILABLE ON THE WHOLE BUILDING DESIGN GUIDEWEBSITE (WWW.WDBG.ORG) FOR USE IN A LABEL MAKING MACHINE.

A. THE FILE IS LOCATED ON THE "NAVFAC CADD DETAILS" PAGE. TO NAVIGATE TO THISLOCATION, FOLLOW: HOME > DOCUMENTS & REFERENCES > CCB > CADD LIBRARY >NAVFAC CADD RESOURCES > NAVFAC CADD DETAILS.

B. ALTERNATIVELY, TYPE IN THE FOLLOWING ADDRESS IN INTERNET EXPLORER:HTTP://WWW.WBDG.ORG/CCB/BROWSE_CAT.PHP?C=232

WIDTH

HEIGHT

(SEE NOTE 1)SERVICE CAPCLAMP TYPE

SECO

NDAR

Y CO

NDUC

TOR

NEUT

RAL

OR T

OP

GRADEFINISHED

GALVANIZED STEEL CONDUIT-SIZE AS INDICATED

SEE NOTE 3

SEE NOTE 2

CONDUIT LOCATION

OF TRAFFICDIRECTION

ROAD SIDEPOSITIONRISERALTERNATEPOSITION

RISERPOLE

1.

2.

3.

DIRECT BURIEDCABLE

DIRECT BURIEDCONDUIT

TYPE C

OH-35JUNE 2002

(SIZE & TYPE AS INDICATED)CONDUIT RISER

SKETCH DATE STYLE

TYPE A

CONCRETE ENCASEDCONDUIT

TYPE B

18" MIN.

37

35

36

35

36

38

6

3334

2"MIN.

NOTES ON CONDUIT RISER FOR PRIMARY CIRCUITS, ELIMINATE SERVICE CAPAND PROVIDE GROUNDING TYPE INSULATING BUSHING.BOND CONDUIT TO POLE GROUND AND SYSTEM NEUTRAL (IF EXISTING).SEE GROUNDING NOTES ON SKETCH OH-41.SPACE STRAPS AT MAXIMUM OF 4' INTERVALS.

1'-6" O.C.

3" MINIMUM

FINISHED GRADE

DUCTBANK MARKING TAPE

3000 P.S.I. CONCRETEP.V.C. CONDUIT SIZEAS INDICATED

LEVELING BLOCKSAT BASE SPACERS

24" M

IN.EQUAL

EQUAL

3" MINIMUMSEPARATION(TYP.)

BASE SPACERS

(TYP.)

NOTE: # OF DUCTS SHALL BE AS INDICATED ON PLANS.

3"

SECONDARY

TRANSFORMER BOXGRADE

TERMINATIONSLOW VOLTAGE CABLE

CURRENT TRANSFORMERS (800/5)3-POLE FUSE BLOCK

SECONDARY CIRCUIT

WHD

#4/0 BARE

MIN2'-0"

GRADE.PAD. MIN 18" BELOW FINISHEDENCIRCLING ENTIRE CONCRETE #4/0 BARE COPPER GROUND LOOP

600V INSULATION

CORNER OF PAD.OF 4, 1 AT EACHGROUND ROD, TYP

GROUND PAD (TYP OF 2)

#4/0, 600VINSULATIONPRIMARY CIRCUIT

CONNECTORLOAD BREAK PRIMARY NEUTRALBUSHING INSERT

BREAK OIL SWITCH2 POSITION LOAD

CURRENT-LIMITINGOIL-IMMERSED

PRIMARY COMPARTMENT

ARRESTERSSURGE

TRANSFORMERBUSHING WELL

X0

BAYONET OIL-IMMERSEDEXPULSION FUSES

FUSES

CABLE WELL

TRANSFORMER BOX, SEE DETAIL THIS SHEET.

G

G

G

G GROUND ROD - 3/4" x 10' CONNECTTO CONDUCTORS BY EXOTHERMICWELD (TYP)

PAD MOUNTED COMPARTMENTAL TYPETRANSFORMER (SECURE TO TRANSFORMERBOX PER MANUFACTURER'SRECOMMENDATION).

SECONDARY NEUTRAL GROUND NO.4/0 AWG CU MINIMUM

TRANSFORMERSECTION

EXOTHERMIC WELD (TYP)

EQUIPMENT GROUND

OUTGOING SECONDARY CONDUIT(S)(NUMBER AS NOTED ON PLANS)

PRIMARY CONDUITNUMBER AS NOTED ONPLANS

EXTEND GRAVEL FILL AMINIMUM OF ONE FOOTBEYOND PAD ON ALL SIDES.WELL COMPACTED GRAVELSUBSURFACE SHALL BE 6INCHES THICK

EXTEND PAD A MINIMUM OF 8INCHES BEYOND UNIT ON ALLSIDES

PAD MOUNTED TRANSFORMER DETAILNOT TO SCALE

TYPICAL PAD MOUNTED COMPARTMENTAL TRANSFORMER DETAILNOT TO SCALE

COMPARTMENT

X10" 10"

6"

9" 18"2-1/2"18"

29"

29"

5"

18"

TRANSFORMER BOX DETAIL

(DETAIL BASED ON PARKING BUMPER COMAPNY STANDARD DETAILS)

CONCRETE ENCASED DUCTBANK - DETAIL 'A'NOT TO SCALE

CONNECTORLOOP FEED

WATTHOUR DEMAND METER: TOCONFORM TO BASESTANDARDS. ITRON V&I CS3SERIES METER.

PRIMARYJUNCTIONENCLOSURE

CONCRETE

14"

14"

PLAN

SIDE ELEVATION

FRONT ELEVATION

DEAD FRONT MODULE

'U' STRAPS SUPPLIED WITHMODULE.

MOUNT 'U' STRAPS CLAMPS (6)SUPPLIED WITH ENCLOSURE) OVER 'U'STRAPS TO SECURE TO MODULE.

DEAD FRONT BUSHING WELLINSERT CONNECTOR.

UNDERGROUNDPRIMARY CONDUIT

UNDERGROUNDPRIMARY CONDUIT

PRIMARY CABLES

FINISHED GRADE

CONCRETE

18"

23"

62"

DEAD FRONT PARKINGSTAND

DEAD FRONT MODULE

GROUND LUG (TYPICAL OF3)

CONCRETE

GRADE

TOP IN OPENEDPOSITION.

LIFTING LUGS(TYPICAL FOR 4)GROUND LINE, DO NOT FILL

INTERIOR OF ENCLOSURE.

46-1/4"3"

32"

41"

THREE PHASE, FULLY DEAD FRONT, 2-WAY SECTIONALIZING PEDESTAL WITH15KV, 600 AMP RATINGS. PROVIDE INDUSTRY STANDARD DEAD FRONTJUNCTION MODULES AND ELBOWS CONFORMING TO ANSI/IEEE 386. UNIT SHALLBE DESIGNED FOR DIRECT BURIAL WITH THE JUNCTION MODULES MOUNTEDABOVE GROUND LINE. PEDESTAL SHALL BE IN CONFORMANCE WITH ANSIC57.12.28 ENCLOSURE IS A ONE PIECE METAL UNIT WITH SWING UP TOP.

CABLES/CONDUIT SHALL ENTER/EXIT SO THAT LOAD BREAK ELBOWS ANDCABLES MAY BE OPERATED FROM FEED THRUS ON PARKING STANDS ORJUNCTIONS.

DO NOT INSTALL CONDUIT BENDS TO TRAIN ELBOWS. THIS SHALL ALLOW MORECABLE MOVEMENT AND FREEDOM FOR FUTURE SWITCHING.

INCOMING CABLES SHALL BE PROPERLY PHASED AND LABELED BEFORE THEYARE POSITIONED AS SHOWN.

ENCLOSURE WILL ACCEPT THREE PRIMARY JUNCTION MODULES. DO NOTINSTALL PRIMARY JUNCTION MODULES WITH WALL MOUNTING BRACKETS.

ENCLOSURE SHALL BE CORROSION RESISTANT AND SHALL BE FABRICATED OFSTAINLESS STEEL CONFORMING TO ASTM A 167, TYPE 304 OR 304L. PAINTENCLOSURE MUNSELL 7GY3.29/1.5 GREEN. PAINT COATING SYSTEM SHALLCOMPLY WITH NEMA C57.12.28. THE MUNSELL COLOR NOTATION IS SPECIFIED INASTM D 1535.

PROVIDE 15 KV 600 AMP ELBOW CONNECTOR FOR EACH TERMINATION.PROVIDE FAULT INDICATORS ON EACH OUTPUT.

1.

2.

3.

4.

5.

6.

7.

NOTES:

PAD MOUNT PRIMARY TAP BOX DETAILNOT TO SCALE

Page 2: PAD MOUNTED TRANSFORMER DETAIL GENERAL ARC FLASH …

1

2

3

4

5

6

7

8

E

E

E E

1

1

1 1

11

2

2

2

HEAT PUMP208V, 1PH

HEAT PUMP208V, 1PH

HEAT PUMP208V, 3PH

HEAT PUMP208V, 3PH

33

E4

1 (TYP)

57

6

8

The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)

WALKERGROUP

i n c o r p o r a t e d

the

ARCHITECTURE

DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

02/24/2020

NDEMOLITION FLOOR PLANSCALE: 1/8" = 1'-0"

NDEMOLITION MEZZANINE FLOOR PLANSCALE: 1/8" = 1'-0"

1

2

3

4

5

6

7

REMOVE EXISTING LIGHT FIXTURE, EXISTING CIRCUITING TO REMAIN ANDBE REUSED.

EXISTING BUILDING TO BE DEMOLISHED COMPLETELY, SEE ARCHITECTURALPLANS.

REMOVE EXISTING AHU CONNECTION IN ATTIC SPACE.

REMOVE EXISTING WATER HEATER CONNECTION.

REMOVE EXISTING PANEL, EXISTING BRANCH CIRCUIT TO REMAIN AND BERECONNECTED TO NEW PANEL.

EXISTING LIGHTING CONTROL PANEL TO REMAIN.

EXISTING TELEPHONE SERVICE TO REMAIN.

NOTES THIS SHEET

Page 3: PAD MOUNTED TRANSFORMER DETAIL GENERAL ARC FLASH …

1

2

3

4

5

6

7

8

20 CF

E F G H

0.5

B.1 B.7BA C D

I J K L M N O P

OC

D

V

VD

VV

D

DO

O

D

V

V

OS

OS

OSV V

O

VA

A

A

A

A

A

A

C

C

C

E E E

C

C

D D

E E

B BF F

A A

CC

EE

A

A

A

A

E

K

F

F

ALA-3

ALA-1 ALA-33

C 2

E 2C 2

G 2 H 2

J4 C

C C

1 TYP.

1 TYP.

1 TYP.

311BABYSITTING

309MECH./ ELEC.

310TELECOM

308OFFICE

307OFFICE

301VESTIBULE

305MEN'S

306WOMEN'S

304

FELLOWSHIPHALL

314KITCHEN

313PANTRY

302CORRIDOR

303JAN.

312UNISEX O

5

F F

F

F

J 2 TYP

TORECEPTACLECIRCUIT

110MECH.

106VESTIBULE

107UNISEX

105ALTAR

108STORAGE

109CORRIDOR

104CHAPEL

102STORAGE

103CONFESSIONAL

101VESTIBULE 1

8

1

The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)

WALKERGROUP

i n c o r p o r a t e d

the

ARCHITECTURE

DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

02/24/2020

NNEW WORK FIRST FLOOR PLANSCALE: 1/8" = 1'-0"

NNEW WORK MEZZANINE FLOOR PLANSCALE: 1/8" = 1'-0"

1

2

3

4

5

RELAMP EXISTING INCANDESCENT LAMPS WITH LED LAMPS (SIX LAMPS PERFIXTURE)

CONNECT TO EXISTING CIRCUIT RETAINED DURING DEMOLITION.

ROUTE CIRCUIT THROUGH TIME CLOCK AND PHOTOCELL, FOR CONTROL.

INTERCEPT EXISTING LIGHTING CIRCUIT AND EXTEND AS INDICATED.

INVERTER FOR "ETERNAL FLAME" LIGHT. 1000W, 120V, 1PH. INTERCEPTEXISTING CIRCUIT AND EXTEND TO INVERTER AND EXISTING CIRCUITBREAKER.

NOTES THIS SHEET

STYLE NO. VOLTAGE MOUNTING NOTESFIXTURESYMBOL

NUMBER ANDTYPE OF LAMPS

LIGHTING FIXTURE SCHEDULE

NL-2, 2x4 LED UNIVERSAL RECESSED

SURFACE, WALL 8'-0" AFFLEDNL-67

NL-63 LED SURFACE; UNIVERSAL

UNIVERSAL

UNIVERSAL

FIXTURE LUMENS MUST BE 4800, 38 WATTS, FULLY DIMMABLE DRIVER TO 1%, USING 0-10 VCD CONTROLS. PROVIDEEMERGENCY BATTERY WHERE INDICATED

FIXTURE LUMENS MUST BE 3300, 26 WATTS, NON-DIMMABLE DRIVER. PROVIDE EMERGENCY BATTERY WHERE INDICATED.

FIXTURE LUMENS MUST BE 4800, 32 WATTS. NON-DIMMABLE DRIVER.

FIXTURE LUMENS MUST BE 4000, 38 WATTS, NON-DIMMABLE DRIVER.

FIXTURE LUMENS MUST BE 3000. 35 WATTS, NON-DIMMABLE DRIVER, PROVIDE EMERGENCY BATTERY WHERE INDICATED.

FIXTURE LUMENS MUST BE 2000, 26 WATTS, NON-DIMMABLE DRIVER.

FIXTURE LUMENS MUST BE 3300, 26 WATTS, NON-DIMMABLE DRIVER.

FIXTURE LUMENS MUST BE 4800, 38 WATTS, NON-DIMMABLE DRIVER.

PROVIDE FIXTURE WITH TWO TYPE E HEADS, POLYCARBONATE WHITE HOUSING

PROVIDE FIXTURE WITH WHITE HOUSING AND VOLTMETER.

PROVIDE FIXTURE WITH WHITE HOUSING AND VOLTMETER. PROVIDE SINGLE FACE, RED LETTERING. UNIVERSALMOUNTING.

MOUNT FIXTURE TO SIDE OF BEAM. CONNECT TO EXISTING CIRCUIT. PROVIDE WITH LED LAMP 3,000 LUMENS, 6" DIAMETERFIXTURE. PROVIDE DIMMABLE LED DRIVER TO 10%, DRIVER SHALL BE COMPATIBLE WITH THE EXISTING LINE VOLTAGEDIMMING SYSTEM.

FIXTURE LUMENS MUST BE 1320, 17 WATTS. NON-DIMMABLE DRIVER.

1

2

3

4

1

10

11

2

5

NL-2, 2X2 LED UNIVERSAL RECESSED

3NL-5, 1X4 LED UNIVERSAL SURFACE

NL-10, 1x4 LED UNIVERSAL SURFACE, 6" ABOVE MIRROR 4

6

NL-19 LED UNIVERSAL RECESSED 5

6SHEET E-501 LED UNIVERSAL SURFACE, CEILING

7NL-7 LED UNIVERSAL SURFACE, 6" ABOVE MIRROR

NL-5, 2x4 LED UNIVERSAL SURFACE 8

7

8

9

10

11

NL-54 LED SURFACE; WALL 8'-0"UNIVERSAL 9

SEE DETAIL

12

NL-20, MODIFIEDLED UNIVERSAL SURFACE 12

NL-5, 1X2 LED UNIVERSAL SURFACE 13

13

A

B

C

D

E

F

G

H

J

K

& TYPE

Page 4: PAD MOUNTED TRANSFORMER DETAIL GENERAL ARC FLASH …

1

2

3

4

5

6

7

8

20 CF

E F G H

0.5

B.1 B.7BA C D

I J K L M N O P

AC-1

388MCA, 208V, 3PH

600A-3P, NF, 4X

MDP-38; 3 #750 KCMIL,

1 #2 GND - 4"C.

E

GFI GFI GFI

GFI

GFI

MDP

MDA

VFD

E

E

EE

E

E

VAV-2

120V, 1PH

VAV-3

120V, 1PH

VAV-1

120V, 1PH

VAV-5

120V, 1PH

VAV-4

120V, 1PH

GFI

GFI GFI

GFI

GFI

GFI GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

EWC

ALA

MDA-4

ALA-14

MDA-6

ALA-12

MDA-37; 3 #8, 1

#10 GND - 1"C.

ALA-4

MDA-2

ALA-2

E

E

MDA-1

30A-2P, FU @ 15, 4X

DSS-1B

9A, 208V, 1PH

CONTROL AND

POWER CABLE

ALA-6

ALA-8

ALA-10

ALA-24

ALA-19

VAV-6

120V, 1PH

MDA-12

ALA-23

ALA-25; 3 #6, 1 #6 GND

- 3/4"C.

ALA-21

WP

M

TO LIGHT

CIRCUIT

EF-2

120V, 1PH

ALA-16

E

VAV-7

120V, 1PH

MDA-14

EF-3

120V, 1PH

MDA-26

MDA-10 MDA-8

ALA-22

ALA-20

ALA-18

E

WH-1

9KW, 208V, 3PH

MDA-32; 3 #10, 1 #10

GND - 3/4"C.

60A-3P, NF

M

HWRP-1

120V, 1PH

MDA-30

MDP-4

MDP-2

MDP-10

MDP-8

MDP-6

WP

WP WP

WP

VAV-8

120V, 1PH

E

MDA-16

MDA-5

MDA-7

MDA-9

GFI

CLA

FACP

CLA-22

EF-1

120V, 1PH

TO LIGHT

CLA-20

E

LIFT STATION

TWO 2HP, 208V, 3PH

MDA-31, 3 #10,

1#10GND IN 3/4"C

CLA-26

A

E-201

MDA-24

EF-5

120V, 1PH

DSS-1A

E

UH-2

3KW,208V, 1PH

MDA-20

110

MECH.

106

VESTIBULE

107

UNISEX

105

ALTAR

108

STORAGE

109

CORRIDOR

104

CHAPEL

102

STORAGE

103

CONFESSIONAL

101

VESTIBULE

M

M

M M

M

M

M

M

M/WP

311

BABYSITTING

309

MECH./ ELEC.

310

TELECOM

308OFFICE

307

OFFICE

301

VESTIBULE

305

MEN'S

306

WOMEN'S

304

FELLOWSHIP

HALL

314

KITCHEN

313

PANTRY

302

CORRIDOR

E E

E

M M

M

MDA-30

1

2

2

3

E

M

E

M

MDA-18

VAV-9

120V, 1PH

4

RECIR PUMP

120V, 1PH

B-1

120V, 1PH

E

M

E

M

VFD

VFD

B-2

120V, 1PH

SHWP-1

3/4HP, 208V, 3PH

SHWP-2

3/4HP, 208V, 3PH

VFD

MDP

MDP-12

MDP-3

MDP-5

MDP-13

MDP-19

MDP-1

MDP-31, 3 #6,

1 #10 GND-3/4"C

AHU-1

10 HP, 208V, 3PH

E

E

E

E

M

MM

UH-1

120V, 1PH

M

MDP-7

EF-4

120V, 1PH

WP

E

WH-2

1.6KW, 120V, 1PH

MDP-9

MDP-14

DDC PANEL, 120V

M

M

M

MDP-16

DAMPER

120V, 1PH

DAMPER

120V, 1PH

TO LIGHTS

E

MDP-11

5

The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)

WALKERGROUP

i n c o r p o r a t e d

the

ARCHITECTURE

DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

02/24/2020

1/8" = 1'-0"

0 4' 16'8'

NNEW WORK FIRST FLOOR PLANSCALE: 1/8" = 1'-0"

NENLARGED PLAN - MECHANICAL ROOMSCALE: 1/4" = 1'-0"

1/4" = 1'-0"

0 2' 8'4'

A

E-201

1

2

3

4

5

AHU-2: 7.5HP, 208V, 3PH

DAMPER: 120V, 1PH.

HOOD: 120V, 1PH.

PROVIDE PANEL IN SAME LOCATION AS REMOVED PANEL. RECONNECT

EXISTING CIRCUITS TO PANEL.

GAS SHUT OFF VALVE CONNECTION, 120V, 1PH.

NOTES THIS SHEET

Page 5: PAD MOUNTED TRANSFORMER DETAIL GENERAL ARC FLASH …

The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)

WALKERGROUP

i n c o r p o r a t e d

the

ARCHITECTURE

DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

02/24/2020

REVISED: AUGUST 2004 NL-67LIGHTING PLATE:

DECORATIVE EMERGENCY LIGHTING UNIT

MR16 HALOGEN LAMPS MUST BE 5 WATTS, HIGH-OUTPUT OR AS INDICATED IN

HOUSING - UV STABLE, FLAME-RATED, HIGH-IMPACT THERMOPLASTIC IN WHITE ORBLACK TEXTURED FINISH.

INTERNAL COMPONENTS - FULLY AUTOMATIC, SOLID STATE, CONSTANT VOLTAGE,CURRENT-LIMITED BATTERY CHARGER; MAINTENANCE-FREE LEAD-ACID BATTERY;

EXTERIOR HOUSING INDICATORS - LED AC-ON INDICATOR AND INTEGRAL TEST SWITCH.

LAMP HEADS - UV STABLE, FLAME RATED POLYCARBONATE THERMOPLASTIC.

MOUNTING - DIRECTLY TO 4" OCTAGONAL OR SQUARE OUTLET BOX.

CERTIFICATION - UL LISTED AND LABELED. COMPLIES WITH UL 924 AND NFPA 101

OPTIONS - VOLTMETER, VANDAL-RESISTANT SHIELD, SELF-DIAGNOSTIC/TESTING7.

6. REQUIREMENTS. LISTED FOR DAMP LOCATIONS.

LUMINAIRE REQUIREMENTS:

1.

3.

5.

4.

2.

AND BUILT-IN OVERLOAD AND LOW-VOLTAGE BATTERY PROTECTION.

13"NOMINAL

NOMINAL5"

MAX. DEPTH4" NOMINAL

ELECTRONICS AND WIRE GUARD.

LIGHTING FIXTURE SCHEDULE.

HOUSING - DIE-CAST ALUMINUM OR HIGH-IMPACT, UV-STABILIZED, INJECTION-MOLDED

LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. RED OR GREEN LETTERS

FINISH (ON CAST ALUMINUM HOUSING ONLY) - TEXTURED POWDER COAT FINISHOPTIONS INCLUDE WHITE, WHITE WITH BRUSHED ALUMINUM FACE, BLACK, OR BLACK

EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT TYPE BATTERY CHARGER WITH

MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR END-OF-FIXTURE

ILLUMINATION - PROVIDED BY RED, GREEN OR WHITE HIGH-OUTPUT LEDS INSIDE

1.

2.

3.

4.

5.

6.

LUMINAIRE REQUIREMENTS:

REVISED: AUGUST 2004 NL-63

MOUNTING.

THERMOPLASTIC. SINGLE OR DOUBLE-FACED AS INDICATED.

AS INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT, RIGHT OR BOTH

MAINTENANCE-FREE, NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND

LIGHTING PLATE:

LED EXIT SIGN

13"NOMINAL

NOMINAL9"

WITH BRUSHED ALUMINUM FACE.

DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING AS REQUIRED.

TEST SWITCH.

OF FIXTURE HOUSING. PROVIDE POLYSTYRENE DIFFUSER IN COLOR INDICATED WITH FREQUENCY-MATCHED SILKSCREEN COATING FOR MAXIMUM LED LIGHT OUTPUT.

CERTIFICATION - UL LISTED AND CERTIFIED FOR DAMP LOCATIONS.7.

REMOTE EMERGENCY LIGHTING UNITS

LAMPS AND FINISHES MUST BE COMPATIBLEWITH PRIMARY UNIT WITH WHICH USED.

FOR USE WITH BATTERY UNIT

1.

NOTES:

TYPE - C

REMOTE FIXTURES

TYPE - E

TYPE - D

TYPE - A TYPE - B

SKETCH DATE JUNE 2002 STYLE NL-54

SURFACE LED WRAPAROUNDREVISED: APRIL 2016 NL-5LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FORRIGIDITY; ENDCAPS SAME MATERIAL AS HOUSING, SECURED WITH TABS, SCREWS ORRIVETS. OPTIONAL LENGTHS OF 2FT OR 4FT.

2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITHHIGH-REFLECTANCE, WHITE POLYESTER POWDER COAT, PAINTED AFTER FABRICATION.

3. LENS - 100% VIRGIN ACRYLIC, CLEAR PRISMATIC DIFFUSER WITH MINIMUM 0.1 INCHTHICKNESS, CONTINUOUSLY SUPPORTED ALONG SIDES OF LUMINAIRE.

4. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500KCCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FORCOLOR CONSISTENCY, AND MINIMUM EFFICACY OF 95 LUMENS/WATT. INITIAL LUMENOUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.

5. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONICDISTORTION. OPTIONAL STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.

6. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPEDWITH EMERGENCY BATTERY BACK-UP.

7. MOUNTING - SURFACE ON CEILING OR SUSPENDED.

8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THATMAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE ACERTAIN MANUFACTURER OR PREFERENCE.

DIRECT/INDIRECT FLUORESCENT TROFFERREVISED: APRIL 2016 NL-2LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FORRIGIDITY; ENDCAPS SECURED WITH TABS, SCREWS OR RIVETS. OPTIONAL SIZES OF 2FTx 2FT AND 2FT x 4FT AVAILABLE.

2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITHHIGH-REFLECTANCE, BAKED WHITE ENAMEL OR POLYESTER POWDER COAT.

3. REFLECTORS - TWO-PIECE CURVED ALUMINUM WITH MATTE WHITE FINISH.

4. DIFFUSE BASKET - WHITE PERFORATED OR ACRYLIC.

5. LIGHT SOURCE - LINEAR T8, T5 OR TT5 WITH QUANTITY AND WATTAGE AS INDICATED INLUMINAIRE SCHEDULE. 3500K CCT UON; MINIMUM CRI OF 80.

6. BALLAST - PROGRAMMED-START, CLASS P, THERMALLY-PROTECTED, < 20% TOTALHARMONIC DISTORTION, HIGH POWER FACTOR (> 0.9), ELECTRONIC TYPE WITH 'A' SOUNDRATING. DIMMING OPTION AVAILABLE.

7. CERTIFICATIONS - UL 1598, DAMP LOCATION, UL 924 WHEN EQUIPPED WITH EMERGENCYBATTERY BACK-UP.

8. MOUNTING - RECESSED IN SOLID OR ACOUSTICAL TILE CEILING.

9. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THATMAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE ACERTAIN MANUFACTURER OR PREFERENCE.

WALL MOUNTED FLUORESCENTREVISED: APRIL 2016 NL-10LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FORRIGIDITY; END CAPS SAME MATERIAL AS HOUSING, SECURED WITH TABS, SCREWS ORRIVETS. WHITE ENAMEL FINISH APPLIED AFTER FABRICATION. OPTIONAL LENGTHS OF 2FT, 3 FT OR 4 FT.

2. LENS - ACRYLIC PRISMATIC (CLEAR PRISMATIC PATTERN A12) OR WHITE OPAL, WITHMINIMUM THICKNESS OF 0.125 IN.

3. LIGHT SOURCE - LINEAR T8, T5 OR T5HO FLUORESCENT TUBES WITH QUANTITY ANDCHARACTERISTICS AS INDICATED IN LUMINAIRE SCHEDULE.

4. BALLAST - PROGRAMMED-START, CLASS P, THERMALLY-PROTECTED, HIGH POWERFACTOR (>0.9), ELECTRONIC TYPE WITH <20% THD AND 'A' SOUND RATING.

5. CERTIFICATION - UL 1598, DAMP LOCATION, UL 924 WHEN EQUIPPED WITH EMERGENCYBATTERY BACK-UP.

6. MOUNTING - SURFACE ON WALL.

7. OPTIONS - EMERGENCY BACK-UP, <10% THD BALLAST, DOWNLIGHT COMPONENT ONLY.

8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THATMAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE ACERTAIN MANUFACTURER OR PREFERENCE.

LED RECESSED DOWNLIGHTREVISED: APRIL 2016 NL-19LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, OR FORGED ALUMINUM WITH HEAT SINK.DRIVER MUST BE ACCESSIBLE FROM BOTTOM OF LUMINAIRE. PROVIDE T-BAR HANGERSFOR INSTALLATION IN ACOUSTICAL TILE CEILINGS OR TABS WHEN MOUNTING IN HARDCEILINGS.

2. REFLECTOR AND TRIM - SPECIFICATION GRADE, LOW IRRIDESCENT, SPECULARALUMINUM REFLECTOR WITH METALLIC OR PAINTED TRIM RING..

3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500KCCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FORCOLOR CONSISTENCY, AND MINIMUM EFFICACY OF 90 LUMENS/WATT. INITIAL LUMENOUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.

4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONICDISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.

5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPEDWITH EMERGENCY BATTERY BACK-UP.

6. MOUNTING - RECESSED IN HARD OR ACOUSTICAL TILE CEILING.

7. OPTIONS - EMERGENCY BATTERY BACK-UP, WALL-WASH TRIM, IC RATED FOR DIRECTCONTACT WITH INSULATION, VARIOUS APERTURE DIAMETERS, AND VARIOUS GLASSLENSES.

8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THATMAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE ACERTAIN MANUFACTURER OR PREFERENCE.

LED INDUSTRIAL STRIPREVISED: APRIL 2016 NL-7LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR RIGIDITYAND SPECULAR ALUMINUM OR HIGHLY-REFLECTIVE PAINTED STEEL REFLECTORS.OPTIONAL LENGTHS OF 4FT OR 8FT.

2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITHHIGH-REFLECTANCE, WHITE POLYESTER POWDER COAT, PAINTED AFTER FABRICATION.

3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500KCCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FORCOLOR CONSISTENCY, AND MINIMUM EFFICACY OF 100 LUMENS/WATT. INITIAL LUMENOUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.

4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONICDISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.

5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPEDWITH EMERGENCY BATTERY BACK-UP.

6. MOUNTING - SURFACE ON CEILING OR SUSPENDED.

7. OPTIONS - WIRE GUARD, CHAIN, STEM OR SWIVEL STEM HANGERS.

8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THATMAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE ACERTAIN MANUFACTURER OR PREFERENCE.

INDICATELENGTH

SURFACE MOUNTTYPE A

PENDANT MOUNTTYPE B

WALL MOUNTTYPE C

LAMP OPTIONS

2 F13/T4 DOUBLE TWIN TUBE COMPACT FLUORESCENT LAMPS.

2 F26/T4 DOUBLE TWIN TUBE COMPACT FLUORESCENT LAMPS.

LUMINAIRE REQUIREMENTS

HOUSING - ALUMINUM .050"± THICK WITH WHITE ACRYLIC ENAMELEDFINISH. PROVIDE INTERNAL GREEN GROUNDING SCREW.

REFLECTOR - SPECULAR ALUMINUM.

BALLAST - HIGH POWER FACTOR ( > .9) ELECTROMAGNETIC BALLAST.

LENS TRIM RING - ALUMINUM WITH WHITE ACRYLIC ENAMELEDFINISH.

REGRESS - 1" MATTE BLACK FROM TRIM RING UP TO LENS.

LENS - FLAT PRISMATIC GLASS.

1.

2.

1.

2.

3.

4.

5.

6.

7.

8.

9.

SKETCH DATE JUNE 2002 STYLE NL-20

ROUND-SURFACE, PENDANT OR WALL MOUNTCOMPACT FLUORESCENT - INTERIOR/EXTERIOR

MINIMUM FIXTURE EFFICIENCY - 60%.

MINIMUM SPACING CRITERIA: 1.2

HOUSING DIMENSIONS - 12" DIA. ±1" X 6" HIGH ±1".

FIXTURE SHALL HAVE UL LABEL FOR WET OR DAMP LOCATIONSAS INDICATED.

10.

DETAIL BASED ON LITHONIA LIGHTING, "VR4" SERIES

LUMINAIRE DESCRIPTION:

1. HOUSING MUST BE 0.054" THICK (MINIMUM) MARINE GRADE ALUMINUMBACK PLATE.

2. HOUSING MUST BE FULLY GASKETED AROUND LENS, AND BETWEENLUMINAIRE AND CEILING, WITH DOUBLE BAKED NEOPRENE GASKETS.PROVIDE INTERNAL GREEN GROUNDING SCREW.

3. LENS MUST BE PRISMATIC POLYCARBONATE HELD IN PLACE WITH 4STAINLESS STEEL SCREWS.

4. MOUNT BACK PLATE TO CEILING WITH (4) 1/4"Ø SCREWS OR ANCHORS.

5. PROVIDE WIRING COMPARTMENT SUITABLE FOR USE WITH 60°C WIREINSULATION.

6. FIXTURE MUST BE UL LISTED FOR WET LOCATIONS.

TYPE LAMP # LAMP TYPE INPUT WATTS VOLTAGE MOUNTING

SURFACE, CEILING120/27726LEDNA

CEILING-MOUNTED VANDAL-RESISTANT LUMINAIRE

12"

8"

LIGHTING DETAIL F - LED

Page 6: PAD MOUNTED TRANSFORMER DETAIL GENERAL ARC FLASH …

The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)

WALKERGROUP

i n c o r p o r a t e d

the

ARCHITECTURE

DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

02/24/2020

PANELMDP

800A MCB208/120V3P, 4W

22 KAIC

PANELCLA

200A MLO208/120V3P, 4W

22 KAIC

PANELMDA

225A MCB208/120V3P, 4W

22 KAIC

PANELALA

150A MLO208/120V3P, 4W

22 KAIC

ELECTRICAL LOAD SUMMARYLOAD CONNECTED DEMAND DEMAND

DESCRIPTION LOAD FACTOR LOAD LIGHTING 17.1 KVA 100% 17.1 KVA EXTERIOR LIGHTING 3.0 KVA 100% 3.0 KVA RECEPTACLES 21.9 KVA NOTE - 116.0 KVA AIR CONDITIONING 168.3 KVA 100% 168.3 KVA HEATING 13.9 KVA 100% 13.9 KVA VENTILATION 2.0 KVA 100% 2.0 KVA MISCELLANEOUS 6.9 KVA 100% 6.9 KVA KITCHEN EQUIP. 10.6 KVA 100% 10.6 KVA WATER HEATER 15.7 KVA 100% 15.7 KVA

TOTAL 259.3 KVA 253.4 KVANOTES:1. 1st 10 KVA @ 100%, REMAINDER @ 50%

PANELBOARD MDP SCHEDULESEE POWER RISER DIAGRAM FOR RATINGS

LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED

BOILER #1 4.5 20/1P 1 2 20/1P 10.0 HEAT TRACEBOILER #2 4.5 20/1P 3 4 20/1P 10.0 HEAT TRACERECIRC PUMPS 7.0 20/1P 5 6 20/1P 10.0 HEAT TRACEEF/UH 3.0 20/1P 7 8 20/1P 10.0 HEAT TRACEWH-2 13.8 20/1P 9 10 20/1P 10.0 HEAT TRACEGAS VALVE 1.5 20/1P 11 12 20/1P 3.0 RECEPTACLESSHWP-1 3.5 20/3P 13 14 20/1P 3.0 DDC

3.5 16 20/1P 5.0 DAMPERS3.5 18 20/1P SPARE

SHWP-2 3.5 20/3P 19 20 20/1P SPARE3.5 22 20/1P SPARE

3.5 24 20/1P SPAREPANEL CLA 92.5 200/3P 25 26 20/1P SPARE

70.0 28 20/1P SPARE90.0 30 20/1P SPARE

AHU-1 30.8 60/3P 31 32 225/3P 197.2 PANEL MDA30.8 201.6

30.8 138.6SPD 60/3P 37 38 450/3P 388.0 CHILLER

388.0388.0

TOTAL 137.8 126.1 136.3 608.2 614.6 539.6 TOTALTOTAL CONNECTED AMPS A: 746.0 B: 740.7 C: 675.9

PANELBOARD CLA SCHEDULESEE POWER RISER DIAGRAM FOR RATINGS

LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED

LTG/RECEPT LEFT 5.0 20/1P 1 2 20/1P 10.0 STEEPLE LIGHTSLTG/RECEPT CONFESS 5.0 20/1P 3 4 20/1P 5.0 LTG/RECEPT STORAGERECEPT - LOFT 5.0 20/1P 5 6 20/1P 5.0 LTG/RECEPT ATTICWATER HTR STORAGE 12.0 20/1P 7 8 20/1P 5.0 LTG/RECEPT FOYERLTG/RECEPT STORAGE 5.0 20/1P 9 10 20/1P SPARELTG/RECEPT RIGHT 5.0 20/1P 11 12 20/1P 5.0 LTG ELEC & TOILETRECEPT - STORAGE 5.0 20/1P 13 14 20/1P 5.0 LTG - BACK HALLTRACK - BACK STAGE 5.0 20/1P 15 16 20/1P 5.0 TRACK LIGHTINGTRACK - CNR STAGE 5.0 20/1P 17 18 20/1P SPARERECEPT - BACK STAGE 5.0 20/1P 19 20 20/1P 1.5 RECEPT - TOILETRECEPT - BACK STAGE 5.0 20/1P 21 22 20/1P 5.0 FIRE ALARMDIMMER PANEL 35.0 60/3P 23 24 40/1P 30.0 WATER HEATER

35.0 26 20/1P 9.0 RECEPT -ALTER35.0 28 20/1P SPARE

SPARE 20/1P 29 30 20/1P SPARESPARE 20/1P 31 32 20/1P SPARESPARE 20/1P 33 34 20/1P SPARESPARE 20/1P 35 36 20/1P SPARESPARE 20/1P 37 38 20/1P SPARESPARE 20/1P 39 40 20/1P SPARESPARE 20/1P 41 42 20/1P SPARE

TOTAL 62.0 55.0 50.0 30.5 15.0 40.0 TOTALTOTAL CONNECTED AMPS A: 92.5 B: 70.0 C: 90.0

PANELBOARD MDA SCHEDULESEE POWER RISER DIAGRAM FOR RATINGS

LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED

TELE RM AC 9.0 15/2P 1 2 20/1P 5.8 VAV-1DSS-A & B 9.0 4 20/1P 5.8 VAV-2RECEPT - TEL ROOM 3.0 20/1P 5 6 20/1P 5.8 VAV-3RECEPT - TEL ROOM 3.0 20/1P 7 8 20/1P 5.8 VAV-4RECEPT - TEL ROOM 4.5 20/1P 9 10 20/1P 5.8 VAV-5SPARE 20/1P 11 12 20/1P 5.8 VAV-6SPARE 20/1P 13 14 20/1P 5.8 VAV-7SPARE 20/1P 15 16 20/1P 5.8 VAV-8SPARE 20/1P 17 18 20/1P 5.8 VAV-9SPARE 20/1P 19 20 20/2P 14.4 UH-2SPARE 20/1P 21 14.4SPARE 20/1P 23 24 20/1P 3.0 EF-4SPARE 20/1P 25 26 20/1P 2.4 EF-3SPARE 20/1P 27 28 20/1P 3.0 DAMPERSSPARE 20/1P 29 30 20/1P 2.7 HW RECIRC PUMPLIFT STATION 18.7 30/3P 31 32 40/3P 25.0 WH-1

18.7 25.018.7 25.0

AHU-2 24.2 50/3P 37 38 150/3P 83.1 PANEL ALA24.2 85.4

24.2 44.6TOTAL 54.9 56.4 45.9 142.3 145.2 92.7 TOTAL

TOTAL CONNECTED AMPS A: 197.2 B: 201.6 C: 138.6

PANELBOARD ALA SCHEDULESEE POWER RISER DIAGRAM FOR RATINGS

LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED

LIGHTING 7.5 20/1P 1 2 20/1P 7.5 RECEPT - 311LIGHTING 4.9 20/1P 3 4 20/1P 6.0 RECEPT - 311EXTERIOR LIGHTING 4.0 20/1P 5 6 20/1P 3.0 RECEPT - 311EXTERIOR LIGHTING 4.1 20/1P 7 8 20/1P 3.0 RECEPT - 311EXTERIOR LIGHTING 12.5 20/1P 9 10 20/1P 4.5 RECEPT - 311EXTERIOR LIGHTING 4.1 20/1P 11 12 20/1P 10.5 RECEPT - 307SPARE 20/1P 13 14 20/1P 7.5 RECEPT - 308SPARE 20/1P 15 16 20/1P 10.5 RECEPT - TOILETSSPARE 20/1P 17 18 20/1P G 12.5 REECPT - EWCRECEPT - KIT 314 12.5 20/1P 19 20 20/1P 6.0 RECETP - 304RECEPT - KIT 314 3.0 20/1P 21 22 20/1P 9.0 RECETP - 304RECEPT - KIT 314 3.0 20/1P 23 24 20/1P 7.5 RECETP - 304OVEN 35.0 50/2P 25 26 20/1P SPARE

35.0 28 20/1P SPARESPARE 20/1P 29 30 20/1P SPARESPARE 20/1P 31 32 20/1P SPARESPARE 20/1P 33 34 20/1P SPARESPARE 20/1P 35 36 20/1P SPARESPARE 20/1P 37 38 20/1P SPARESPARE 20/1P 39 40 20/1P SPARESPARE 20/1P 41 42 20/1P SPARE

TOTAL 59.1 55.4 11.1 24.0 30.0 33.5 TOTALTOTAL CONNECTED AMPS A: 83.1 B: 85.4 C: 44.6

G - INDICATED GFI CIRCUIT BREAKER

POWER RISER DIAGRAMNOT TO SCALE

SERVICE GROUND:1 #6 - 1/2"C TO GROUND ROD1 #3/0 - 1/2"C TO WATER SERVICE1 #3/0 - 1/2"C TO BUILDING STEEL1 #3/0 - 1/2"C TO REBAR IN SLAB

SERVICE GROUND:1 #6 - 1/2"C TO GROUND ROD1 #2 - 1/2"C TO WATER SERVICE1 #2 - 1/2"C TO BUILDING STEEL1 #2 - 1/2"C TO REBAR IN SLAB

4 #1/0, 1 #6 GND - 2"C

4 - #4/0, 1 #4 GND - 2-1/2"C

4 #3/0, 1 #6 GND - 2-1/2"C

TWO 4" CONDUITS WITH4- 600 KCMIL IN EACH CONDUIT AND ONESPARE 4"C TO TRANSFORMER

SPD

4 #6, 1 #8 GND - 3/4"C

CC

TC

PSITE LIGHTING CONTACTOR:6 POLE, 120V, 20A.CONTROL MUST BEPHOTOCELL ON,TIME CLOCK OFF

TO SITE LIGHTINGCIRCUITS

SEE PRIMARY ONE-LINEDIAGRAM SHEET ES102FOR CONTINUATION

Name: Service Transformer "X" * Type: 120/208, 3p, 150kVASource N/A Impedance (%Z) 2Voltage 208 KVA 150Phase 3 Full Load Amps 417Voltage Fluctuation: 1.05Multiplier 50.00 Fault Current 21885

Name: Panel MDP * Conductor Size: 600KCMILSource: Service Transformer "X" Material: CopperVoltage 208 Conduit Type: Non-MagneticPhase 3 5 Voltage Rating: Up To 5KVAvailable Fault Current 21885 Constant 25000Multiplier 0.846 Conductors/Phase: 2Fault Current 18515 Length (ft): 50Load (Amps): 630 1.1 Voltage Drop (%) 1.1 (0.5%)

Name: Panel "CLA" * Conductor Size: #3/0Source: Panel MDP Material: CopperVoltage 208 Conduit Type: MagneticPhase 3 7 Voltage Rating: Up To 5KVAvailable Fault Current 18515 Constant 10638Multiplier 0.580 Conductors/Phase: 1Fault Current 10741 Length (ft): 50Load (Amps): 160 1.3 Voltage Drop (%) 1.3 (0.6%)Name: Panel "MDA" * Conductor Size: #4/0Source: Panel MDP Material: CopperVoltage 208 Conduit Type: Non-MagneticPhase 3 5 Voltage Rating: Up To 5KVAvailable Fault Current 18515 Constant 13514Multiplier 0.467 Conductors/Phase: 1Fault Current 8654 Length (ft): 100Load (Amps): 180 2.3 Voltage Drop (%) 2.3 (1.1%)Name: Panel "ALA" * Conductor Size: #1/0Source: Panel "MDA" Material: CopperVoltage 208 Conduit Type: MagneticPhase 3 7 Voltage Rating: Up To 5KVAvailable Fault Current 8654 Constant 7692Multiplier 0.914 Conductors/Phase: 1Fault Current 7913 Length (ft): 10Load (Amps): 120 0.3 Voltage Drop (%) 0.3 (0.1%)