Upload
others
View
8
Download
0
Embed Size (px)
Citation preview
The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)
WALKERGROUP
i n c o r p o r a t e d
the
ARCHITECTURE
DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
ROAD SIDE
DIRECTIONOF TRAFFIC
ADDITIONALGROUND RODS(WHEN REQUIRED)
PLAN
ALWAYS CONNECT THE POLE GROUNDLEAD(S) DIRECTLY TO THE NEUTRAL-ENSURE THAT THE COPPER CONDUCTORWILL ALWAYS BE BELOW THE ALUMINUM.
CONNECTOR
NEUTRAL COPPERWELD STAPLES (TYP.)
GROUNDWIRE
POLE
ELEVATION
GROUND ROD
PLASTIC OR FIBER MOLDINGGALVANIZED STAPLES (TYPICAL)
FINISHEDGRADE
#4 BARECOPPER
POLE
OH-41JUNE 2002SKETCH DATE STYLE
GROUND
24"MIN.
10'-0"MIN.
10'-0"MIN.
24"
12"
8'-0"MIN.
18"MAX.
8'-0 MIN.(FROM 24'-4"
TO 16'-4"ABOVE GRADE)
ALTERNATE GROUND WIREPOSITION. (USE WHENMULTIPLE GROUNDINGSYSTEMS ARE REQUIRED.)
(SEE NOTE 4)
1.
2.
3.
NOTES
USE ADDITIONAL GROUND RODS, WHEN REQUIRED,TO OBTAIN RESISTANCE VALUE, AS REQUIRED BYIEEE C2.MAKE GROUNDING CONNECTIONS TO ALL EQUIPMENTON POLE AS REQUIRED BY IEEE C2.FOR SYSTEMS OTHER THAN 4 WIRE, MULTI-GROUNDED, USE SEPARATE GROUNDING CONDUCTORS AND ELECTRODES FOR PRIMARYAND SECONDARY SYSTEM DEVICE CONNECTIONS.#4 600V INSULATED COPPER GROUNDINGCONDUCTOR REQUIRED ON PRIMARY SYSTEMWHEN SEPARATE SYSTEMS ARE REQUIRED.
4.
AF-1APRIL 2015
GENERAL ARC FLASH WARNING LABELSKETCH DATE STYLE
NOTES:
1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT TO WARN OF ARCFLASH HAZARDS.
2. THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH THE FIGURE.
3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE TO QUALIFIEDPERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THEEQUIPMENT.
4. THE SIZE OF THE LABEL SHALL BE MINIMUM:
EQUIPMENT TYPE HEIGHT WIDTH INDOOR 2" 3" OUTDOOR 3" 4.5"
5. A DOWNLOADABLE WINDOWS METAFILE IS AVAILABLE ON THE WHOLE BUILDING DESIGN GUIDEWEBSITE (WWW.WDBG.ORG) FOR USE IN A LABEL MAKING MACHINE.
A. THE FILE IS LOCATED ON THE "NAVFAC CADD DETAILS" PAGE. TO NAVIGATE TO THISLOCATION, FOLLOW: HOME > DOCUMENTS & REFERENCES > CCB > CADD LIBRARY >NAVFAC CADD RESOURCES > NAVFAC CADD DETAILS.
B. ALTERNATIVELY, TYPE IN THE FOLLOWING ADDRESS IN INTERNET EXPLORER:HTTP://WWW.WBDG.ORG/CCB/BROWSE_CAT.PHP?C=232
WIDTH
HEIGHT
(SEE NOTE 1)SERVICE CAPCLAMP TYPE
SECO
NDAR
Y CO
NDUC
TOR
NEUT
RAL
OR T
OP
GRADEFINISHED
GALVANIZED STEEL CONDUIT-SIZE AS INDICATED
SEE NOTE 3
SEE NOTE 2
CONDUIT LOCATION
OF TRAFFICDIRECTION
ROAD SIDEPOSITIONRISERALTERNATEPOSITION
RISERPOLE
1.
2.
3.
DIRECT BURIEDCABLE
DIRECT BURIEDCONDUIT
TYPE C
OH-35JUNE 2002
(SIZE & TYPE AS INDICATED)CONDUIT RISER
SKETCH DATE STYLE
TYPE A
CONCRETE ENCASEDCONDUIT
TYPE B
18" MIN.
37
35
36
35
36
38
6
3334
2"MIN.
NOTES ON CONDUIT RISER FOR PRIMARY CIRCUITS, ELIMINATE SERVICE CAPAND PROVIDE GROUNDING TYPE INSULATING BUSHING.BOND CONDUIT TO POLE GROUND AND SYSTEM NEUTRAL (IF EXISTING).SEE GROUNDING NOTES ON SKETCH OH-41.SPACE STRAPS AT MAXIMUM OF 4' INTERVALS.
1'-6" O.C.
3" MINIMUM
FINISHED GRADE
DUCTBANK MARKING TAPE
3000 P.S.I. CONCRETEP.V.C. CONDUIT SIZEAS INDICATED
LEVELING BLOCKSAT BASE SPACERS
24" M
IN.EQUAL
EQUAL
3" MINIMUMSEPARATION(TYP.)
BASE SPACERS
(TYP.)
NOTE: # OF DUCTS SHALL BE AS INDICATED ON PLANS.
3"
SECONDARY
TRANSFORMER BOXGRADE
TERMINATIONSLOW VOLTAGE CABLE
CURRENT TRANSFORMERS (800/5)3-POLE FUSE BLOCK
SECONDARY CIRCUIT
WHD
#4/0 BARE
MIN2'-0"
GRADE.PAD. MIN 18" BELOW FINISHEDENCIRCLING ENTIRE CONCRETE #4/0 BARE COPPER GROUND LOOP
600V INSULATION
CORNER OF PAD.OF 4, 1 AT EACHGROUND ROD, TYP
GROUND PAD (TYP OF 2)
#4/0, 600VINSULATIONPRIMARY CIRCUIT
CONNECTORLOAD BREAK PRIMARY NEUTRALBUSHING INSERT
BREAK OIL SWITCH2 POSITION LOAD
CURRENT-LIMITINGOIL-IMMERSED
PRIMARY COMPARTMENT
ARRESTERSSURGE
TRANSFORMERBUSHING WELL
X0
BAYONET OIL-IMMERSEDEXPULSION FUSES
FUSES
CABLE WELL
TRANSFORMER BOX, SEE DETAIL THIS SHEET.
G
G
G
G GROUND ROD - 3/4" x 10' CONNECTTO CONDUCTORS BY EXOTHERMICWELD (TYP)
PAD MOUNTED COMPARTMENTAL TYPETRANSFORMER (SECURE TO TRANSFORMERBOX PER MANUFACTURER'SRECOMMENDATION).
SECONDARY NEUTRAL GROUND NO.4/0 AWG CU MINIMUM
TRANSFORMERSECTION
EXOTHERMIC WELD (TYP)
EQUIPMENT GROUND
OUTGOING SECONDARY CONDUIT(S)(NUMBER AS NOTED ON PLANS)
PRIMARY CONDUITNUMBER AS NOTED ONPLANS
EXTEND GRAVEL FILL AMINIMUM OF ONE FOOTBEYOND PAD ON ALL SIDES.WELL COMPACTED GRAVELSUBSURFACE SHALL BE 6INCHES THICK
EXTEND PAD A MINIMUM OF 8INCHES BEYOND UNIT ON ALLSIDES
PAD MOUNTED TRANSFORMER DETAILNOT TO SCALE
TYPICAL PAD MOUNTED COMPARTMENTAL TRANSFORMER DETAILNOT TO SCALE
COMPARTMENT
X10" 10"
6"
9" 18"2-1/2"18"
29"
29"
5"
18"
TRANSFORMER BOX DETAIL
(DETAIL BASED ON PARKING BUMPER COMAPNY STANDARD DETAILS)
CONCRETE ENCASED DUCTBANK - DETAIL 'A'NOT TO SCALE
CONNECTORLOOP FEED
WATTHOUR DEMAND METER: TOCONFORM TO BASESTANDARDS. ITRON V&I CS3SERIES METER.
PRIMARYJUNCTIONENCLOSURE
CONCRETE
14"
14"
PLAN
SIDE ELEVATION
FRONT ELEVATION
DEAD FRONT MODULE
'U' STRAPS SUPPLIED WITHMODULE.
MOUNT 'U' STRAPS CLAMPS (6)SUPPLIED WITH ENCLOSURE) OVER 'U'STRAPS TO SECURE TO MODULE.
DEAD FRONT BUSHING WELLINSERT CONNECTOR.
UNDERGROUNDPRIMARY CONDUIT
UNDERGROUNDPRIMARY CONDUIT
PRIMARY CABLES
FINISHED GRADE
CONCRETE
18"
23"
62"
DEAD FRONT PARKINGSTAND
DEAD FRONT MODULE
GROUND LUG (TYPICAL OF3)
CONCRETE
GRADE
TOP IN OPENEDPOSITION.
LIFTING LUGS(TYPICAL FOR 4)GROUND LINE, DO NOT FILL
INTERIOR OF ENCLOSURE.
46-1/4"3"
32"
41"
THREE PHASE, FULLY DEAD FRONT, 2-WAY SECTIONALIZING PEDESTAL WITH15KV, 600 AMP RATINGS. PROVIDE INDUSTRY STANDARD DEAD FRONTJUNCTION MODULES AND ELBOWS CONFORMING TO ANSI/IEEE 386. UNIT SHALLBE DESIGNED FOR DIRECT BURIAL WITH THE JUNCTION MODULES MOUNTEDABOVE GROUND LINE. PEDESTAL SHALL BE IN CONFORMANCE WITH ANSIC57.12.28 ENCLOSURE IS A ONE PIECE METAL UNIT WITH SWING UP TOP.
CABLES/CONDUIT SHALL ENTER/EXIT SO THAT LOAD BREAK ELBOWS ANDCABLES MAY BE OPERATED FROM FEED THRUS ON PARKING STANDS ORJUNCTIONS.
DO NOT INSTALL CONDUIT BENDS TO TRAIN ELBOWS. THIS SHALL ALLOW MORECABLE MOVEMENT AND FREEDOM FOR FUTURE SWITCHING.
INCOMING CABLES SHALL BE PROPERLY PHASED AND LABELED BEFORE THEYARE POSITIONED AS SHOWN.
ENCLOSURE WILL ACCEPT THREE PRIMARY JUNCTION MODULES. DO NOTINSTALL PRIMARY JUNCTION MODULES WITH WALL MOUNTING BRACKETS.
ENCLOSURE SHALL BE CORROSION RESISTANT AND SHALL BE FABRICATED OFSTAINLESS STEEL CONFORMING TO ASTM A 167, TYPE 304 OR 304L. PAINTENCLOSURE MUNSELL 7GY3.29/1.5 GREEN. PAINT COATING SYSTEM SHALLCOMPLY WITH NEMA C57.12.28. THE MUNSELL COLOR NOTATION IS SPECIFIED INASTM D 1535.
PROVIDE 15 KV 600 AMP ELBOW CONNECTOR FOR EACH TERMINATION.PROVIDE FAULT INDICATORS ON EACH OUTPUT.
1.
2.
3.
4.
5.
6.
7.
NOTES:
PAD MOUNT PRIMARY TAP BOX DETAILNOT TO SCALE
1
2
3
4
5
6
7
8
E
E
E E
1
1
1 1
11
2
2
2
HEAT PUMP208V, 1PH
HEAT PUMP208V, 1PH
HEAT PUMP208V, 3PH
HEAT PUMP208V, 3PH
33
E4
1 (TYP)
57
6
8
The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)
WALKERGROUP
i n c o r p o r a t e d
the
ARCHITECTURE
DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
NDEMOLITION FLOOR PLANSCALE: 1/8" = 1'-0"
NDEMOLITION MEZZANINE FLOOR PLANSCALE: 1/8" = 1'-0"
1
2
3
4
5
6
7
REMOVE EXISTING LIGHT FIXTURE, EXISTING CIRCUITING TO REMAIN ANDBE REUSED.
EXISTING BUILDING TO BE DEMOLISHED COMPLETELY, SEE ARCHITECTURALPLANS.
REMOVE EXISTING AHU CONNECTION IN ATTIC SPACE.
REMOVE EXISTING WATER HEATER CONNECTION.
REMOVE EXISTING PANEL, EXISTING BRANCH CIRCUIT TO REMAIN AND BERECONNECTED TO NEW PANEL.
EXISTING LIGHTING CONTROL PANEL TO REMAIN.
EXISTING TELEPHONE SERVICE TO REMAIN.
NOTES THIS SHEET
1
2
3
4
5
6
7
8
20 CF
E F G H
0.5
B.1 B.7BA C D
I J K L M N O P
OC
D
V
VD
VV
D
DO
O
D
V
V
OS
OS
OSV V
O
VA
A
A
A
A
A
A
C
C
C
E E E
C
C
D D
E E
B BF F
A A
CC
EE
A
A
A
A
E
K
F
F
ALA-3
ALA-1 ALA-33
C 2
E 2C 2
G 2 H 2
J4 C
C C
1 TYP.
1 TYP.
1 TYP.
311BABYSITTING
309MECH./ ELEC.
310TELECOM
308OFFICE
307OFFICE
301VESTIBULE
305MEN'S
306WOMEN'S
304
FELLOWSHIPHALL
314KITCHEN
313PANTRY
302CORRIDOR
303JAN.
312UNISEX O
5
F F
F
F
J 2 TYP
TORECEPTACLECIRCUIT
110MECH.
106VESTIBULE
107UNISEX
105ALTAR
108STORAGE
109CORRIDOR
104CHAPEL
102STORAGE
103CONFESSIONAL
101VESTIBULE 1
8
1
The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)
WALKERGROUP
i n c o r p o r a t e d
the
ARCHITECTURE
DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
NNEW WORK FIRST FLOOR PLANSCALE: 1/8" = 1'-0"
NNEW WORK MEZZANINE FLOOR PLANSCALE: 1/8" = 1'-0"
1
2
3
4
5
RELAMP EXISTING INCANDESCENT LAMPS WITH LED LAMPS (SIX LAMPS PERFIXTURE)
CONNECT TO EXISTING CIRCUIT RETAINED DURING DEMOLITION.
ROUTE CIRCUIT THROUGH TIME CLOCK AND PHOTOCELL, FOR CONTROL.
INTERCEPT EXISTING LIGHTING CIRCUIT AND EXTEND AS INDICATED.
INVERTER FOR "ETERNAL FLAME" LIGHT. 1000W, 120V, 1PH. INTERCEPTEXISTING CIRCUIT AND EXTEND TO INVERTER AND EXISTING CIRCUITBREAKER.
NOTES THIS SHEET
STYLE NO. VOLTAGE MOUNTING NOTESFIXTURESYMBOL
NUMBER ANDTYPE OF LAMPS
LIGHTING FIXTURE SCHEDULE
NL-2, 2x4 LED UNIVERSAL RECESSED
SURFACE, WALL 8'-0" AFFLEDNL-67
NL-63 LED SURFACE; UNIVERSAL
UNIVERSAL
UNIVERSAL
FIXTURE LUMENS MUST BE 4800, 38 WATTS, FULLY DIMMABLE DRIVER TO 1%, USING 0-10 VCD CONTROLS. PROVIDEEMERGENCY BATTERY WHERE INDICATED
FIXTURE LUMENS MUST BE 3300, 26 WATTS, NON-DIMMABLE DRIVER. PROVIDE EMERGENCY BATTERY WHERE INDICATED.
FIXTURE LUMENS MUST BE 4800, 32 WATTS. NON-DIMMABLE DRIVER.
FIXTURE LUMENS MUST BE 4000, 38 WATTS, NON-DIMMABLE DRIVER.
FIXTURE LUMENS MUST BE 3000. 35 WATTS, NON-DIMMABLE DRIVER, PROVIDE EMERGENCY BATTERY WHERE INDICATED.
FIXTURE LUMENS MUST BE 2000, 26 WATTS, NON-DIMMABLE DRIVER.
FIXTURE LUMENS MUST BE 3300, 26 WATTS, NON-DIMMABLE DRIVER.
FIXTURE LUMENS MUST BE 4800, 38 WATTS, NON-DIMMABLE DRIVER.
PROVIDE FIXTURE WITH TWO TYPE E HEADS, POLYCARBONATE WHITE HOUSING
PROVIDE FIXTURE WITH WHITE HOUSING AND VOLTMETER.
PROVIDE FIXTURE WITH WHITE HOUSING AND VOLTMETER. PROVIDE SINGLE FACE, RED LETTERING. UNIVERSALMOUNTING.
MOUNT FIXTURE TO SIDE OF BEAM. CONNECT TO EXISTING CIRCUIT. PROVIDE WITH LED LAMP 3,000 LUMENS, 6" DIAMETERFIXTURE. PROVIDE DIMMABLE LED DRIVER TO 10%, DRIVER SHALL BE COMPATIBLE WITH THE EXISTING LINE VOLTAGEDIMMING SYSTEM.
FIXTURE LUMENS MUST BE 1320, 17 WATTS. NON-DIMMABLE DRIVER.
1
2
3
4
1
10
11
2
5
NL-2, 2X2 LED UNIVERSAL RECESSED
3NL-5, 1X4 LED UNIVERSAL SURFACE
NL-10, 1x4 LED UNIVERSAL SURFACE, 6" ABOVE MIRROR 4
6
NL-19 LED UNIVERSAL RECESSED 5
6SHEET E-501 LED UNIVERSAL SURFACE, CEILING
7NL-7 LED UNIVERSAL SURFACE, 6" ABOVE MIRROR
NL-5, 2x4 LED UNIVERSAL SURFACE 8
7
8
9
10
11
NL-54 LED SURFACE; WALL 8'-0"UNIVERSAL 9
SEE DETAIL
12
NL-20, MODIFIEDLED UNIVERSAL SURFACE 12
NL-5, 1X2 LED UNIVERSAL SURFACE 13
13
A
B
C
D
E
F
G
H
J
K
& TYPE
1
2
3
4
5
6
7
8
20 CF
E F G H
0.5
B.1 B.7BA C D
I J K L M N O P
AC-1
388MCA, 208V, 3PH
600A-3P, NF, 4X
MDP-38; 3 #750 KCMIL,
1 #2 GND - 4"C.
E
GFI GFI GFI
GFI
GFI
MDP
MDA
VFD
E
E
EE
E
E
VAV-2
120V, 1PH
VAV-3
120V, 1PH
VAV-1
120V, 1PH
VAV-5
120V, 1PH
VAV-4
120V, 1PH
GFI
GFI GFI
GFI
GFI
GFI GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
EWC
ALA
MDA-4
ALA-14
MDA-6
ALA-12
MDA-37; 3 #8, 1
#10 GND - 1"C.
ALA-4
MDA-2
ALA-2
E
E
MDA-1
30A-2P, FU @ 15, 4X
DSS-1B
9A, 208V, 1PH
CONTROL AND
POWER CABLE
ALA-6
ALA-8
ALA-10
ALA-24
ALA-19
VAV-6
120V, 1PH
MDA-12
ALA-23
ALA-25; 3 #6, 1 #6 GND
- 3/4"C.
ALA-21
WP
M
TO LIGHT
CIRCUIT
EF-2
120V, 1PH
ALA-16
E
VAV-7
120V, 1PH
MDA-14
EF-3
120V, 1PH
MDA-26
MDA-10 MDA-8
ALA-22
ALA-20
ALA-18
E
WH-1
9KW, 208V, 3PH
MDA-32; 3 #10, 1 #10
GND - 3/4"C.
60A-3P, NF
M
HWRP-1
120V, 1PH
MDA-30
MDP-4
MDP-2
MDP-10
MDP-8
MDP-6
WP
WP WP
WP
VAV-8
120V, 1PH
E
MDA-16
MDA-5
MDA-7
MDA-9
GFI
CLA
FACP
CLA-22
EF-1
120V, 1PH
TO LIGHT
CLA-20
E
LIFT STATION
TWO 2HP, 208V, 3PH
MDA-31, 3 #10,
1#10GND IN 3/4"C
CLA-26
A
E-201
MDA-24
EF-5
120V, 1PH
DSS-1A
E
UH-2
3KW,208V, 1PH
MDA-20
110
MECH.
106
VESTIBULE
107
UNISEX
105
ALTAR
108
STORAGE
109
CORRIDOR
104
CHAPEL
102
STORAGE
103
CONFESSIONAL
101
VESTIBULE
M
M
M M
M
M
M
M
M/WP
311
BABYSITTING
309
MECH./ ELEC.
310
TELECOM
308OFFICE
307
OFFICE
301
VESTIBULE
305
MEN'S
306
WOMEN'S
304
FELLOWSHIP
HALL
314
KITCHEN
313
PANTRY
302
CORRIDOR
E E
E
M M
M
MDA-30
1
2
2
3
E
M
E
M
MDA-18
VAV-9
120V, 1PH
4
RECIR PUMP
120V, 1PH
B-1
120V, 1PH
E
M
E
M
VFD
VFD
B-2
120V, 1PH
SHWP-1
3/4HP, 208V, 3PH
SHWP-2
3/4HP, 208V, 3PH
VFD
MDP
MDP-12
MDP-3
MDP-5
MDP-13
MDP-19
MDP-1
MDP-31, 3 #6,
1 #10 GND-3/4"C
AHU-1
10 HP, 208V, 3PH
E
E
E
E
M
MM
UH-1
120V, 1PH
M
MDP-7
EF-4
120V, 1PH
WP
E
WH-2
1.6KW, 120V, 1PH
MDP-9
MDP-14
DDC PANEL, 120V
M
M
M
MDP-16
DAMPER
120V, 1PH
DAMPER
120V, 1PH
TO LIGHTS
E
MDP-11
5
The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)
WALKERGROUP
i n c o r p o r a t e d
the
ARCHITECTURE
DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
1/8" = 1'-0"
0 4' 16'8'
NNEW WORK FIRST FLOOR PLANSCALE: 1/8" = 1'-0"
NENLARGED PLAN - MECHANICAL ROOMSCALE: 1/4" = 1'-0"
1/4" = 1'-0"
0 2' 8'4'
A
E-201
1
2
3
4
5
AHU-2: 7.5HP, 208V, 3PH
DAMPER: 120V, 1PH.
HOOD: 120V, 1PH.
PROVIDE PANEL IN SAME LOCATION AS REMOVED PANEL. RECONNECT
EXISTING CIRCUITS TO PANEL.
GAS SHUT OFF VALVE CONNECTION, 120V, 1PH.
NOTES THIS SHEET
The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)
WALKERGROUP
i n c o r p o r a t e d
the
ARCHITECTURE
DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
REVISED: AUGUST 2004 NL-67LIGHTING PLATE:
DECORATIVE EMERGENCY LIGHTING UNIT
MR16 HALOGEN LAMPS MUST BE 5 WATTS, HIGH-OUTPUT OR AS INDICATED IN
HOUSING - UV STABLE, FLAME-RATED, HIGH-IMPACT THERMOPLASTIC IN WHITE ORBLACK TEXTURED FINISH.
INTERNAL COMPONENTS - FULLY AUTOMATIC, SOLID STATE, CONSTANT VOLTAGE,CURRENT-LIMITED BATTERY CHARGER; MAINTENANCE-FREE LEAD-ACID BATTERY;
EXTERIOR HOUSING INDICATORS - LED AC-ON INDICATOR AND INTEGRAL TEST SWITCH.
LAMP HEADS - UV STABLE, FLAME RATED POLYCARBONATE THERMOPLASTIC.
MOUNTING - DIRECTLY TO 4" OCTAGONAL OR SQUARE OUTLET BOX.
CERTIFICATION - UL LISTED AND LABELED. COMPLIES WITH UL 924 AND NFPA 101
OPTIONS - VOLTMETER, VANDAL-RESISTANT SHIELD, SELF-DIAGNOSTIC/TESTING7.
6. REQUIREMENTS. LISTED FOR DAMP LOCATIONS.
LUMINAIRE REQUIREMENTS:
1.
3.
5.
4.
2.
AND BUILT-IN OVERLOAD AND LOW-VOLTAGE BATTERY PROTECTION.
13"NOMINAL
NOMINAL5"
MAX. DEPTH4" NOMINAL
ELECTRONICS AND WIRE GUARD.
LIGHTING FIXTURE SCHEDULE.
HOUSING - DIE-CAST ALUMINUM OR HIGH-IMPACT, UV-STABILIZED, INJECTION-MOLDED
LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. RED OR GREEN LETTERS
FINISH (ON CAST ALUMINUM HOUSING ONLY) - TEXTURED POWDER COAT FINISHOPTIONS INCLUDE WHITE, WHITE WITH BRUSHED ALUMINUM FACE, BLACK, OR BLACK
EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT TYPE BATTERY CHARGER WITH
MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR END-OF-FIXTURE
ILLUMINATION - PROVIDED BY RED, GREEN OR WHITE HIGH-OUTPUT LEDS INSIDE
1.
2.
3.
4.
5.
6.
LUMINAIRE REQUIREMENTS:
REVISED: AUGUST 2004 NL-63
MOUNTING.
THERMOPLASTIC. SINGLE OR DOUBLE-FACED AS INDICATED.
AS INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT, RIGHT OR BOTH
MAINTENANCE-FREE, NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND
LIGHTING PLATE:
LED EXIT SIGN
13"NOMINAL
NOMINAL9"
WITH BRUSHED ALUMINUM FACE.
DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING AS REQUIRED.
TEST SWITCH.
OF FIXTURE HOUSING. PROVIDE POLYSTYRENE DIFFUSER IN COLOR INDICATED WITH FREQUENCY-MATCHED SILKSCREEN COATING FOR MAXIMUM LED LIGHT OUTPUT.
CERTIFICATION - UL LISTED AND CERTIFIED FOR DAMP LOCATIONS.7.
REMOTE EMERGENCY LIGHTING UNITS
LAMPS AND FINISHES MUST BE COMPATIBLEWITH PRIMARY UNIT WITH WHICH USED.
FOR USE WITH BATTERY UNIT
1.
NOTES:
TYPE - C
REMOTE FIXTURES
TYPE - E
TYPE - D
TYPE - A TYPE - B
SKETCH DATE JUNE 2002 STYLE NL-54
SURFACE LED WRAPAROUNDREVISED: APRIL 2016 NL-5LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FORRIGIDITY; ENDCAPS SAME MATERIAL AS HOUSING, SECURED WITH TABS, SCREWS ORRIVETS. OPTIONAL LENGTHS OF 2FT OR 4FT.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITHHIGH-REFLECTANCE, WHITE POLYESTER POWDER COAT, PAINTED AFTER FABRICATION.
3. LENS - 100% VIRGIN ACRYLIC, CLEAR PRISMATIC DIFFUSER WITH MINIMUM 0.1 INCHTHICKNESS, CONTINUOUSLY SUPPORTED ALONG SIDES OF LUMINAIRE.
4. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500KCCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FORCOLOR CONSISTENCY, AND MINIMUM EFFICACY OF 95 LUMENS/WATT. INITIAL LUMENOUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.
5. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONICDISTORTION. OPTIONAL STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.
6. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPEDWITH EMERGENCY BATTERY BACK-UP.
7. MOUNTING - SURFACE ON CEILING OR SUSPENDED.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THATMAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE ACERTAIN MANUFACTURER OR PREFERENCE.
DIRECT/INDIRECT FLUORESCENT TROFFERREVISED: APRIL 2016 NL-2LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FORRIGIDITY; ENDCAPS SECURED WITH TABS, SCREWS OR RIVETS. OPTIONAL SIZES OF 2FTx 2FT AND 2FT x 4FT AVAILABLE.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITHHIGH-REFLECTANCE, BAKED WHITE ENAMEL OR POLYESTER POWDER COAT.
3. REFLECTORS - TWO-PIECE CURVED ALUMINUM WITH MATTE WHITE FINISH.
4. DIFFUSE BASKET - WHITE PERFORATED OR ACRYLIC.
5. LIGHT SOURCE - LINEAR T8, T5 OR TT5 WITH QUANTITY AND WATTAGE AS INDICATED INLUMINAIRE SCHEDULE. 3500K CCT UON; MINIMUM CRI OF 80.
6. BALLAST - PROGRAMMED-START, CLASS P, THERMALLY-PROTECTED, < 20% TOTALHARMONIC DISTORTION, HIGH POWER FACTOR (> 0.9), ELECTRONIC TYPE WITH 'A' SOUNDRATING. DIMMING OPTION AVAILABLE.
7. CERTIFICATIONS - UL 1598, DAMP LOCATION, UL 924 WHEN EQUIPPED WITH EMERGENCYBATTERY BACK-UP.
8. MOUNTING - RECESSED IN SOLID OR ACOUSTICAL TILE CEILING.
9. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THATMAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE ACERTAIN MANUFACTURER OR PREFERENCE.
WALL MOUNTED FLUORESCENTREVISED: APRIL 2016 NL-10LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FORRIGIDITY; END CAPS SAME MATERIAL AS HOUSING, SECURED WITH TABS, SCREWS ORRIVETS. WHITE ENAMEL FINISH APPLIED AFTER FABRICATION. OPTIONAL LENGTHS OF 2FT, 3 FT OR 4 FT.
2. LENS - ACRYLIC PRISMATIC (CLEAR PRISMATIC PATTERN A12) OR WHITE OPAL, WITHMINIMUM THICKNESS OF 0.125 IN.
3. LIGHT SOURCE - LINEAR T8, T5 OR T5HO FLUORESCENT TUBES WITH QUANTITY ANDCHARACTERISTICS AS INDICATED IN LUMINAIRE SCHEDULE.
4. BALLAST - PROGRAMMED-START, CLASS P, THERMALLY-PROTECTED, HIGH POWERFACTOR (>0.9), ELECTRONIC TYPE WITH <20% THD AND 'A' SOUND RATING.
5. CERTIFICATION - UL 1598, DAMP LOCATION, UL 924 WHEN EQUIPPED WITH EMERGENCYBATTERY BACK-UP.
6. MOUNTING - SURFACE ON WALL.
7. OPTIONS - EMERGENCY BACK-UP, <10% THD BALLAST, DOWNLIGHT COMPONENT ONLY.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THATMAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE ACERTAIN MANUFACTURER OR PREFERENCE.
LED RECESSED DOWNLIGHTREVISED: APRIL 2016 NL-19LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, OR FORGED ALUMINUM WITH HEAT SINK.DRIVER MUST BE ACCESSIBLE FROM BOTTOM OF LUMINAIRE. PROVIDE T-BAR HANGERSFOR INSTALLATION IN ACOUSTICAL TILE CEILINGS OR TABS WHEN MOUNTING IN HARDCEILINGS.
2. REFLECTOR AND TRIM - SPECIFICATION GRADE, LOW IRRIDESCENT, SPECULARALUMINUM REFLECTOR WITH METALLIC OR PAINTED TRIM RING..
3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500KCCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FORCOLOR CONSISTENCY, AND MINIMUM EFFICACY OF 90 LUMENS/WATT. INITIAL LUMENOUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONICDISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.
5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPEDWITH EMERGENCY BATTERY BACK-UP.
6. MOUNTING - RECESSED IN HARD OR ACOUSTICAL TILE CEILING.
7. OPTIONS - EMERGENCY BATTERY BACK-UP, WALL-WASH TRIM, IC RATED FOR DIRECTCONTACT WITH INSULATION, VARIOUS APERTURE DIAMETERS, AND VARIOUS GLASSLENSES.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THATMAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE ACERTAIN MANUFACTURER OR PREFERENCE.
LED INDUSTRIAL STRIPREVISED: APRIL 2016 NL-7LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR RIGIDITYAND SPECULAR ALUMINUM OR HIGHLY-REFLECTIVE PAINTED STEEL REFLECTORS.OPTIONAL LENGTHS OF 4FT OR 8FT.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITHHIGH-REFLECTANCE, WHITE POLYESTER POWDER COAT, PAINTED AFTER FABRICATION.
3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70, 3500KCCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING TOLERANCE FORCOLOR CONSISTENCY, AND MINIMUM EFFICACY OF 100 LUMENS/WATT. INITIAL LUMENOUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONICDISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.
5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPEDWITH EMERGENCY BATTERY BACK-UP.
6. MOUNTING - SURFACE ON CEILING OR SUSPENDED.
7. OPTIONS - WIRE GUARD, CHAIN, STEM OR SWIVEL STEM HANGERS.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THATMAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE ACERTAIN MANUFACTURER OR PREFERENCE.
INDICATELENGTH
SURFACE MOUNTTYPE A
PENDANT MOUNTTYPE B
WALL MOUNTTYPE C
LAMP OPTIONS
2 F13/T4 DOUBLE TWIN TUBE COMPACT FLUORESCENT LAMPS.
2 F26/T4 DOUBLE TWIN TUBE COMPACT FLUORESCENT LAMPS.
LUMINAIRE REQUIREMENTS
HOUSING - ALUMINUM .050"± THICK WITH WHITE ACRYLIC ENAMELEDFINISH. PROVIDE INTERNAL GREEN GROUNDING SCREW.
REFLECTOR - SPECULAR ALUMINUM.
BALLAST - HIGH POWER FACTOR ( > .9) ELECTROMAGNETIC BALLAST.
LENS TRIM RING - ALUMINUM WITH WHITE ACRYLIC ENAMELEDFINISH.
REGRESS - 1" MATTE BLACK FROM TRIM RING UP TO LENS.
LENS - FLAT PRISMATIC GLASS.
1.
2.
1.
2.
3.
4.
5.
6.
7.
8.
9.
SKETCH DATE JUNE 2002 STYLE NL-20
ROUND-SURFACE, PENDANT OR WALL MOUNTCOMPACT FLUORESCENT - INTERIOR/EXTERIOR
MINIMUM FIXTURE EFFICIENCY - 60%.
MINIMUM SPACING CRITERIA: 1.2
HOUSING DIMENSIONS - 12" DIA. ±1" X 6" HIGH ±1".
FIXTURE SHALL HAVE UL LABEL FOR WET OR DAMP LOCATIONSAS INDICATED.
10.
DETAIL BASED ON LITHONIA LIGHTING, "VR4" SERIES
LUMINAIRE DESCRIPTION:
1. HOUSING MUST BE 0.054" THICK (MINIMUM) MARINE GRADE ALUMINUMBACK PLATE.
2. HOUSING MUST BE FULLY GASKETED AROUND LENS, AND BETWEENLUMINAIRE AND CEILING, WITH DOUBLE BAKED NEOPRENE GASKETS.PROVIDE INTERNAL GREEN GROUNDING SCREW.
3. LENS MUST BE PRISMATIC POLYCARBONATE HELD IN PLACE WITH 4STAINLESS STEEL SCREWS.
4. MOUNT BACK PLATE TO CEILING WITH (4) 1/4"Ø SCREWS OR ANCHORS.
5. PROVIDE WIRING COMPARTMENT SUITABLE FOR USE WITH 60°C WIREINSULATION.
6. FIXTURE MUST BE UL LISTED FOR WET LOCATIONS.
TYPE LAMP # LAMP TYPE INPUT WATTS VOLTAGE MOUNTING
SURFACE, CEILING120/27726LEDNA
CEILING-MOUNTED VANDAL-RESISTANT LUMINAIRE
12"
8"
LIGHTING DETAIL F - LED
The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)
WALKERGROUP
i n c o r p o r a t e d
the
ARCHITECTURE
DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:
(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL
SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
02/24/2020
PANELMDP
800A MCB208/120V3P, 4W
22 KAIC
PANELCLA
200A MLO208/120V3P, 4W
22 KAIC
PANELMDA
225A MCB208/120V3P, 4W
22 KAIC
PANELALA
150A MLO208/120V3P, 4W
22 KAIC
ELECTRICAL LOAD SUMMARYLOAD CONNECTED DEMAND DEMAND
DESCRIPTION LOAD FACTOR LOAD LIGHTING 17.1 KVA 100% 17.1 KVA EXTERIOR LIGHTING 3.0 KVA 100% 3.0 KVA RECEPTACLES 21.9 KVA NOTE - 116.0 KVA AIR CONDITIONING 168.3 KVA 100% 168.3 KVA HEATING 13.9 KVA 100% 13.9 KVA VENTILATION 2.0 KVA 100% 2.0 KVA MISCELLANEOUS 6.9 KVA 100% 6.9 KVA KITCHEN EQUIP. 10.6 KVA 100% 10.6 KVA WATER HEATER 15.7 KVA 100% 15.7 KVA
TOTAL 259.3 KVA 253.4 KVANOTES:1. 1st 10 KVA @ 100%, REMAINDER @ 50%
PANELBOARD MDP SCHEDULESEE POWER RISER DIAGRAM FOR RATINGS
LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED
BOILER #1 4.5 20/1P 1 2 20/1P 10.0 HEAT TRACEBOILER #2 4.5 20/1P 3 4 20/1P 10.0 HEAT TRACERECIRC PUMPS 7.0 20/1P 5 6 20/1P 10.0 HEAT TRACEEF/UH 3.0 20/1P 7 8 20/1P 10.0 HEAT TRACEWH-2 13.8 20/1P 9 10 20/1P 10.0 HEAT TRACEGAS VALVE 1.5 20/1P 11 12 20/1P 3.0 RECEPTACLESSHWP-1 3.5 20/3P 13 14 20/1P 3.0 DDC
3.5 16 20/1P 5.0 DAMPERS3.5 18 20/1P SPARE
SHWP-2 3.5 20/3P 19 20 20/1P SPARE3.5 22 20/1P SPARE
3.5 24 20/1P SPAREPANEL CLA 92.5 200/3P 25 26 20/1P SPARE
70.0 28 20/1P SPARE90.0 30 20/1P SPARE
AHU-1 30.8 60/3P 31 32 225/3P 197.2 PANEL MDA30.8 201.6
30.8 138.6SPD 60/3P 37 38 450/3P 388.0 CHILLER
388.0388.0
TOTAL 137.8 126.1 136.3 608.2 614.6 539.6 TOTALTOTAL CONNECTED AMPS A: 746.0 B: 740.7 C: 675.9
PANELBOARD CLA SCHEDULESEE POWER RISER DIAGRAM FOR RATINGS
LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED
LTG/RECEPT LEFT 5.0 20/1P 1 2 20/1P 10.0 STEEPLE LIGHTSLTG/RECEPT CONFESS 5.0 20/1P 3 4 20/1P 5.0 LTG/RECEPT STORAGERECEPT - LOFT 5.0 20/1P 5 6 20/1P 5.0 LTG/RECEPT ATTICWATER HTR STORAGE 12.0 20/1P 7 8 20/1P 5.0 LTG/RECEPT FOYERLTG/RECEPT STORAGE 5.0 20/1P 9 10 20/1P SPARELTG/RECEPT RIGHT 5.0 20/1P 11 12 20/1P 5.0 LTG ELEC & TOILETRECEPT - STORAGE 5.0 20/1P 13 14 20/1P 5.0 LTG - BACK HALLTRACK - BACK STAGE 5.0 20/1P 15 16 20/1P 5.0 TRACK LIGHTINGTRACK - CNR STAGE 5.0 20/1P 17 18 20/1P SPARERECEPT - BACK STAGE 5.0 20/1P 19 20 20/1P 1.5 RECEPT - TOILETRECEPT - BACK STAGE 5.0 20/1P 21 22 20/1P 5.0 FIRE ALARMDIMMER PANEL 35.0 60/3P 23 24 40/1P 30.0 WATER HEATER
35.0 26 20/1P 9.0 RECEPT -ALTER35.0 28 20/1P SPARE
SPARE 20/1P 29 30 20/1P SPARESPARE 20/1P 31 32 20/1P SPARESPARE 20/1P 33 34 20/1P SPARESPARE 20/1P 35 36 20/1P SPARESPARE 20/1P 37 38 20/1P SPARESPARE 20/1P 39 40 20/1P SPARESPARE 20/1P 41 42 20/1P SPARE
TOTAL 62.0 55.0 50.0 30.5 15.0 40.0 TOTALTOTAL CONNECTED AMPS A: 92.5 B: 70.0 C: 90.0
PANELBOARD MDA SCHEDULESEE POWER RISER DIAGRAM FOR RATINGS
LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED
TELE RM AC 9.0 15/2P 1 2 20/1P 5.8 VAV-1DSS-A & B 9.0 4 20/1P 5.8 VAV-2RECEPT - TEL ROOM 3.0 20/1P 5 6 20/1P 5.8 VAV-3RECEPT - TEL ROOM 3.0 20/1P 7 8 20/1P 5.8 VAV-4RECEPT - TEL ROOM 4.5 20/1P 9 10 20/1P 5.8 VAV-5SPARE 20/1P 11 12 20/1P 5.8 VAV-6SPARE 20/1P 13 14 20/1P 5.8 VAV-7SPARE 20/1P 15 16 20/1P 5.8 VAV-8SPARE 20/1P 17 18 20/1P 5.8 VAV-9SPARE 20/1P 19 20 20/2P 14.4 UH-2SPARE 20/1P 21 14.4SPARE 20/1P 23 24 20/1P 3.0 EF-4SPARE 20/1P 25 26 20/1P 2.4 EF-3SPARE 20/1P 27 28 20/1P 3.0 DAMPERSSPARE 20/1P 29 30 20/1P 2.7 HW RECIRC PUMPLIFT STATION 18.7 30/3P 31 32 40/3P 25.0 WH-1
18.7 25.018.7 25.0
AHU-2 24.2 50/3P 37 38 150/3P 83.1 PANEL ALA24.2 85.4
24.2 44.6TOTAL 54.9 56.4 45.9 142.3 145.2 92.7 TOTAL
TOTAL CONNECTED AMPS A: 197.2 B: 201.6 C: 138.6
PANELBOARD ALA SCHEDULESEE POWER RISER DIAGRAM FOR RATINGS
LOAD (AMPS) BKR CKT PHASE CKT BKR LOAD (AMPS)LOAD SERVED A B C TRIP NO. A B C NO. TRIP A B C LOAD SERVED
LIGHTING 7.5 20/1P 1 2 20/1P 7.5 RECEPT - 311LIGHTING 4.9 20/1P 3 4 20/1P 6.0 RECEPT - 311EXTERIOR LIGHTING 4.0 20/1P 5 6 20/1P 3.0 RECEPT - 311EXTERIOR LIGHTING 4.1 20/1P 7 8 20/1P 3.0 RECEPT - 311EXTERIOR LIGHTING 12.5 20/1P 9 10 20/1P 4.5 RECEPT - 311EXTERIOR LIGHTING 4.1 20/1P 11 12 20/1P 10.5 RECEPT - 307SPARE 20/1P 13 14 20/1P 7.5 RECEPT - 308SPARE 20/1P 15 16 20/1P 10.5 RECEPT - TOILETSSPARE 20/1P 17 18 20/1P G 12.5 REECPT - EWCRECEPT - KIT 314 12.5 20/1P 19 20 20/1P 6.0 RECETP - 304RECEPT - KIT 314 3.0 20/1P 21 22 20/1P 9.0 RECETP - 304RECEPT - KIT 314 3.0 20/1P 23 24 20/1P 7.5 RECETP - 304OVEN 35.0 50/2P 25 26 20/1P SPARE
35.0 28 20/1P SPARESPARE 20/1P 29 30 20/1P SPARESPARE 20/1P 31 32 20/1P SPARESPARE 20/1P 33 34 20/1P SPARESPARE 20/1P 35 36 20/1P SPARESPARE 20/1P 37 38 20/1P SPARESPARE 20/1P 39 40 20/1P SPARESPARE 20/1P 41 42 20/1P SPARE
TOTAL 59.1 55.4 11.1 24.0 30.0 33.5 TOTALTOTAL CONNECTED AMPS A: 83.1 B: 85.4 C: 44.6
G - INDICATED GFI CIRCUIT BREAKER
POWER RISER DIAGRAMNOT TO SCALE
SERVICE GROUND:1 #6 - 1/2"C TO GROUND ROD1 #3/0 - 1/2"C TO WATER SERVICE1 #3/0 - 1/2"C TO BUILDING STEEL1 #3/0 - 1/2"C TO REBAR IN SLAB
SERVICE GROUND:1 #6 - 1/2"C TO GROUND ROD1 #2 - 1/2"C TO WATER SERVICE1 #2 - 1/2"C TO BUILDING STEEL1 #2 - 1/2"C TO REBAR IN SLAB
4 #1/0, 1 #6 GND - 2"C
4 - #4/0, 1 #4 GND - 2-1/2"C
4 #3/0, 1 #6 GND - 2-1/2"C
TWO 4" CONDUITS WITH4- 600 KCMIL IN EACH CONDUIT AND ONESPARE 4"C TO TRANSFORMER
SPD
4 #6, 1 #8 GND - 3/4"C
CC
TC
PSITE LIGHTING CONTACTOR:6 POLE, 120V, 20A.CONTROL MUST BEPHOTOCELL ON,TIME CLOCK OFF
TO SITE LIGHTINGCIRCUITS
SEE PRIMARY ONE-LINEDIAGRAM SHEET ES102FOR CONTINUATION
Name: Service Transformer "X" * Type: 120/208, 3p, 150kVASource N/A Impedance (%Z) 2Voltage 208 KVA 150Phase 3 Full Load Amps 417Voltage Fluctuation: 1.05Multiplier 50.00 Fault Current 21885
Name: Panel MDP * Conductor Size: 600KCMILSource: Service Transformer "X" Material: CopperVoltage 208 Conduit Type: Non-MagneticPhase 3 5 Voltage Rating: Up To 5KVAvailable Fault Current 21885 Constant 25000Multiplier 0.846 Conductors/Phase: 2Fault Current 18515 Length (ft): 50Load (Amps): 630 1.1 Voltage Drop (%) 1.1 (0.5%)
Name: Panel "CLA" * Conductor Size: #3/0Source: Panel MDP Material: CopperVoltage 208 Conduit Type: MagneticPhase 3 7 Voltage Rating: Up To 5KVAvailable Fault Current 18515 Constant 10638Multiplier 0.580 Conductors/Phase: 1Fault Current 10741 Length (ft): 50Load (Amps): 160 1.3 Voltage Drop (%) 1.3 (0.6%)Name: Panel "MDA" * Conductor Size: #4/0Source: Panel MDP Material: CopperVoltage 208 Conduit Type: Non-MagneticPhase 3 5 Voltage Rating: Up To 5KVAvailable Fault Current 18515 Constant 13514Multiplier 0.467 Conductors/Phase: 1Fault Current 8654 Length (ft): 100Load (Amps): 180 2.3 Voltage Drop (%) 2.3 (1.1%)Name: Panel "ALA" * Conductor Size: #1/0Source: Panel "MDA" Material: CopperVoltage 208 Conduit Type: MagneticPhase 3 7 Voltage Rating: Up To 5KVAvailable Fault Current 8654 Constant 7692Multiplier 0.914 Conductors/Phase: 1Fault Current 7913 Length (ft): 10Load (Amps): 120 0.3 Voltage Drop (%) 0.3 (0.1%)