MICOM P821 Breaker Failure Protection Version V1.C Technical Data Sheet P821/EN TDS/C13 This Document Should be Read Alongside the Technical Manual

P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

Embed Size (px)

Citation preview

Page 1: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

MICOM P821

Breaker Failure Protection

Version V1.C

Technical Data Sheet P821/EN TDS/C13

This Document Should be Read Alongside the Technical Manual

Page 2: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation
Page 3: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

ENHANCED PROTECTION WITHADVANCED NUMERICAL TECHNOLOGY

The MiCOM P821 is an Advanced Breaker Failurerelay based on the latest numerical technology. It offers a range of protection functions, combinedwith extensive monitoring capacities to give youoptimised efficiency and maximum control for yourelectrical schemes.

GREATER SECURITY

MiCOM P821's enhanced breaker failure protectionfunction provides you with back up protectionwhen the primary circuit fails to isolate the fault. This numerical relay is more than just a phasesegregated detection device for 1/3 pole trippingrelay for EHV/HV/MV levels, it is also suitable for allvoltage ranges.

ANY APPLICATIONANY TIMEANYWHERE

The P821 can use either single stage breakerfailure protection (tBF1), for back up protection tothe local circuit breaker; or it can use a 2 stagebreaker failure protection (tBF1 & tBF2). In 2 stageconfiguration, the first stage will be used to re-tripthe same circuit breaker, while the other stage willbe used to provide general tripping to the upstreamcircuit breaker.

Customer benefits

• Reliable phase segregated detection for 1/3 pole breaker tripping, suitable for all voltage levels

• Sensitive residual current detection

• Fast RESET time

• 1 or 2 stage CB failure

• Simple and easy to programme, standard MiCOM Px20 settingprocedure

T&D

MiCOM P821Breaker FailureProtection

PROTECTION

Page 4: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

RECORDING

> Tripping statistic menu> Up to 75 events> Last 5 faults > 5 disturbance records :

32 samples/cycle, 3s duration.

PROTECTION FUNCTIONS

> Two stage CB Failure function (50BF)> Residual current detection (50BF (N))> Dead Zone Protection function (DBI)> Pole discrepancy function> Output relay latching features (86, Lockout)

BREAKER FAIL CHARACTERISTICS

> One independent timer per phase for stage one (3 times tBF1), single phase tripping orders

> One timer for second stage (tBF2),three phase tripping orders

> Measurement is insensitive to DC transient (avoiding undesired operation)

> Fast RESET time (12ms)> Configurable RESET Logic via digital Inputs

USER INTERFACE

> Display: 2 x 16 Alphanumeric characters, back-lit> LEDs: 8 including 4 programmable> Keyboard: 7 button tactile keypad

COMMUNICATION

> Front port: RS232 > Rear port: RS 485 , 2 wires, half duplex, isolated> Data rate: from 300 to 38400 bauds> Protocols:

Modbus RTU, Courier, IEC 60870-5-103, DNP3

CONTROL & SUPERVISION

> Monitoring the number of CB operation> Recording the sum of broken current quantity> Supervision of the local breaker

Closing & Opening times > Statistic Menu

MEASUREMENT

> Display of all measured quantities> All records time tagged to a 1ms resolution

Our policy is one of continuous development. Accordinglythe design of our products may change at any time. Whilstevery effort is made to produce up to date literature, thisbrochure should only be regarded as a guide and isintended for information purposes only. Its contents do notconstitute an offer for sale or advise on the application ofany product referred to in it. We cannot be held responsiblefor any reliance on any decisions taken on its contentswithout specific advice.

AU

TOM

AT

ION

-L3-

P82

1-D

S-0

9.04

-062

9-G

B -

© -

AR

EV

A -

200

4.A

RE

VA

, th

e A

RE

VA

logo

and

any

alte

rnat

ive

vers

ion

ther

eof

are

trad

emar

ks a

nd s

ervi

ce m

arks

of

AR

EV

A.

MiC

OM

is a

reg

iste

red

trad

emar

k of

AR

EV

A.A

ll tr

ade

nam

es o

r tr

adem

arks

men

tione

d he

rein

whe

ther

reg

iste

red

or n

ot,

are

the

prop

erty

of

thei

r ow

ners

.-

3891

9198

2 R

CS

PA

RIS

- P

rinte

d in

Fra

nce

- S

ON

OV

ISIO

N-I

TE

P

AREVA T&D Worldwide Contact Centre:http://www.areva-td.com/contactcentre/Tel.: +44 (0) 1785 250 070

www.areva-td.com

Busbar

LogicInputs(5)

LogicOutputs(8)

SCADASystem

FrontpanelPC

Vaux

52

3PhaseCTs

EarthCT

Functions

CB FAIL 50BF (Ph), I <

50BF (N), IN <tBF1

tBF2DBI

Poles Not Together

tAUX86, Lockout

Metering

SOE

Oscillography

Comms

Comms

X

XX

XX

X

X

2

24

75

5 x 3 sec5

X

X

X

CB FAIL Earth

Stage 1 Timer

Stage 2 Timer

Dead Zone (End Zone)Pole discrepancyCircuit Breaker monitoring,control and statistics

Auxiliary timers

Latching output contacts

Setting groups

Measurement (True RMS)

Event records

Disturbance recordsFault records

RS 232 front communication

RS 485 rear communication

Common Names MiCOMP821

Page 5: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

P821 Technical Data Sheet 1 P821/EN TDS/C13

Technical Data

Mechanical Specifications Design Modular MiCOM P821 relay in 20TE case. Mounting is front of panel flush mounting, or 19“ rack mounted (ordering options).

Enclosure Protection Per IEC 60529: 2001: IP 52 Protection (front panel) against dust and dripping water. IP 10 Protection for the rear.

Weight P821 (20TE): 1.7 Kg

Terminals

Rear Double fast on + M4 screw per connection. Full draw-out with automatic CT shorting in the case of the relay.

Front Port Serial PC Interface EIA(RS)232 DTE, 9 pin D-type female connector. MODBUS protocol for interface to MiCOM S1 software. Isolation to ELV level. Maximum cable length 15m.

Ratings

AC Measuring Inputs Nominal frequency: 50 and 60 Hz (settable) Operating range: 45 to 65Hz

AC Current Nominal current (In): 1 and 5 A dual rated. (1A and 5A inputs use different transformer tap connections, check correct terminals are wired). Nominal burden Phase < 0.025VA (1A) < 0.3VA (5A) Earth < 0.008VA at 0.1 Ιe (1A) < 0.01VA at 0.1 Ιe (5A) Thermal withstand: continuous 4 In for 2s: 40 In with 400A maximum for 1s; 100 In

Power Supply Auxiliary Voltage (Vx) Five ordering options: (i) Vx: 24 to 60 Vdc (ii) Vx: 48 to 150 Vdc (iii) Vx: 130 to 250 Vdc/100-250Vac, 50/60Hz (iv) Vx: 48 to 150 Vdc (ac immune) (v) Vx: 130 to 250 Vdc (ac immune)

Operating Range DC ±20% of Vx AC -20%, +10% of Vx Ripple Up to 12%

Nominal Burden 3W standby + 0.4W per energized relay +10mA per logic input 6VA standby + 0.4VA per energized relay + 10mA per logic input

Power Supply Interruption Per IEC 60255-11: 1979 The relay will withstand a 50ms interruption in the DC auxiliary supply, without de-energizing.

Logical Inputs Type: Optically insulated Burden: 10 mA per input Recognition time (DC): < 5ms

Logic Input Electrical Functionality

Ordering Code

Relay Auxiliary

Power Supply Range Vx

Auxiliary Voltage

Range For The Logic Inputs (*)

Max 0 level – min 1 level (Vdc)

Min Polaris. Current Level (mA)

A 24 - 60 Vdc 19 - 60 Vdc 9 - 15 3.35 mA

F 48 - 150 Vdc 32 - 150 Vdc 15 - 25 3.35 mA

H 125.-.250 Vdc 100 – 250 Vdc 105 – 145 Vdc 95 - 96 1.8 mA

M 130 - 250 Vdc 100 - 250 Vdc

48 - 250 Vdc 48 - 250 Vdc

15 - 38 15 - 38

2.20 mA 1.90 mA

T 48 - 150 Vdc Special ENA(**) 32 - 150 Vdc 15 - 25 3.35 mA

U 130 - 250 Vdc Special ENA(**) 48 - 250 Vdc 15 - 38 2.20 mA

V 48 – 150 Vdc 110 Vdc -30% / +20% 64 - 65 5 mA

W 130- 250 Vdc 110 – 250 Vac

220 Vdc -30% / +20% 132-133 2,5 mA

(*) The tolerance on the auxiliary voltage variations for the logic inputs is ±20% for DC voltage and -20%, +10% for AC voltage.

(**) Logic input recognition time for ENA assessment. Dedicated filtering on 24 samples (15ms at 50Hz).

Page 6: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

P821 Technical Data Sheet 2 P821/EN TDS/C12

Output Contacts

Standard Contacts Contact relay: Dry contact Ag Cd O Make current: Max. 30A and carry for 3s Carry capacity: 5A continuous Rated voltage: 250VAC Breaking characteristic: Breaking capacity AC: 1250 VA resistive 1250 VA inductive (P.F = 0.5) 220 VAC, 5A (cos ϕ = 0.6) Breaking capacity DC: 135 VDC, 0.3A (L/R = 30 ms) 250 VDC, 50W resistive or 25W inductive (L/R=40ms) Operation time: <7ms Durability: Loaded contact: 10000 operation minimum Unloaded contact: 100000 operation minimum

Environmental Conditions

Recommended Ambient Temperature Range Per IEC 60255-6: 1988 Operating temperature range: -25°C to 55°C (or 13°F to 131°F). -25°C to 70°C (*) (or 13°F to 158°F (*)). Storage and transit: -25°C to 70°C (or 13°F to 158°F) (*) The upper limit is permissible for a single 6 hour duration within any 24 hour period.

Ambient Humidity Range Per IEC 60068-2-3: 1969: 56 days at 93% relative humidity and +40°C Per IEC 60068-2-30: 1980: Damp heat cyclic, six (12 + 12) hour cycles, 93% RH, +25 to +55°C

Solar Radiation Avoid exposure of the front panel to direct solar radiation.

Type Tests

Insulation Per IEC 60255-5: 2000, Insulation resistance > 100MΩ at 500Vdc (Using only electronic/brushless insulation tester).

High Voltage (Dielectric) Withstand EIA(RS)232 ports excepted. Per IEC 60255-5: 2000, 2 kV rms AC, 1 minute: Between all independent circuits.

Between independent circuits and case earth. 1kV rms AC for 1 minute, across open watchdog contacts. 1kV rms AC for 1 minute, across open contacts of changeover output relays.

Impulse Voltage Withstand Test Per IEC 60255-5: 2000 Front time: 1.2 µs, Time to half-value: 50 µs, Peak value: 5 kV, 0.5J Between all independent circuits. Between all independent circuits and case earth. Between the terminals of independent circuits. EIA(RS)232 & EIA(RS)485 ports and normally open contacts of output relays excepted.

Electromagnetic Compatibility (EMC)

1 MHz Burst High Frequency Disturbance Test Per IEC 60255-22-1: 1988, Class III, Common-mode test voltage: 2.5 kV, Differential test voltage: 1.0 kV, EIA(RS)232 ports excepted.

Immunity to Electrostatic Discharge Per IEC 60255-22-2: 1996, Class 4, 15kV discharge in air to user interface, display, and exposed metalwork. Per IEC 60255-22-2: 1996, Class 3, 8kV discharge in air to all communication ports. 6kV point contact discharge to any part of the front of the product.

Electrical Fast Transient or Burst Requirements Per IEC 60255-22-4: 2002. Test severity Class III and IV: Amplitude: 2 kV, burst frequency 5kHz (Class III), Amplitude: 4 kV, burst frequency 2.5kHz (Class IV). Applied directly to auxiliary supply, and applied to all other inputs. EIA(RS)232 ports excepted.

Surge Withstand Capability IEEE/ANSI C37.90.1: 2002: 4kV fast transient and 2.5kV oscillatory applied directly across each output contact, optically isolated input, and power supply circuit.

Page 7: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

P821 Technical Data Sheet 3 P821/EN TDS/C13

Surge Immunity Test EIA(RS)232 ports excepted. Per IEC 61000-4-5: 1995 Levels 3 and 4 Level 4 - AC/DC PSU, CTs, input, output contacts. Level 3 - DC PSU, EIA(RS)485 rear protection communications channel.

Immunity to Radiated Electromagnetic Energy Per IEC 60255-22-3: 2000, Class III: Test field strength, frequency band 80 to 1000 MHz: 10 V/m, Test using AM: 1 kHz/80%, Spot tests at 80, 160, 450, 900 MHz

Radiated Immunity from Digital Communications Per EN61000-4-3: 2002, Level 4: Test field strength, frequency band 800 to 960 MHz, and 1.4 to 2.0 GHz: 30 V/m, Test using AM: 1 kHz/80%.

Radiated Immunity from Digital Radio Telephones PER IEC61000-4-3: 2002: 10 V/m, 900MHz and 1.89GHz.

Immunity to Conducted Disturbances Induced by Radio Frequency Fields Per IEC 61000-4-6: 2002, Level 3, Disturbing test voltage: 10 V

Power Frequency Magnetic Field Immunity Per IEC 61000-4-8: 1993, Level 5, 100A/m applied continuously, 1000A/m applied for 3s. Per IEC 61000-4-9: 1993, Level 5, 1000A/m applied in all planes. Per IEC 61000-4-10: 1993, Level 5, 100A/m applied in all planes at 100kHz/1MHz with a burst duration of 2s.

Conducted Emissions Per EN 55022: 1995, Class A: 0.15 - 0.5MHz, 79dBµV (quasi peak) 66dBµV (average) 0.5 - 30MHz, 73dBµV (quasi peak) 60dBµV (average).

Radiated Emissions Per EN 55022: 1995, Class A: 30 - 230MHz, 40dBµV/m at 10m measurement distance 230 - 1GHz, 47dBµV/m at 10m measurement distance.

EU Directives

EMC Compliance Per 89/336/EEC: Compliance to the European Commission Directive on EMC is claimed via the Standards route. Product Specific Standards were used to establish conformity: EN50263: 2000

Product Safety Per 73/23/EEC: Compliance with European Commission Low Voltage Directive. Compliance is demonstrated by reference to generic safety standards: EN61010-1: 2001 EN60950-1: 2001

73/23/EEC

Mechanical Robustness

Vibration Test Per IEC 60255-21-1: 1998 Response Class 2 Endurance Class 2

Shock and Bump Per IEC 60255-21-2: 1988 Shock response Class 2 Shock withstand Class 1 Bump Class 1

Seismic Test Per IEC 60255-21-3: 1993 Class 2

Page 8: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

P821 Technical Data Sheet 4 P821/EN TDS/C12

Protection Functions Circuit breaker failure (Phase and Earth) by current residual detection Current threshold

I> 5% … 400% x rated current, Standard

Ie> 5% … 400% x rated current, Sensitive

Ie> 1% … 400% x rated current, Very sensitive

Ie> 0,2% … 80.0% x rated current, Threshold hysteresis

max. 0.008 In or 0.95 Is Hysteresis

90% with a minimum of 0.0125 In CB failure timer 1 (retrip)

tBF1 0 ms … 40 s; step of 5 ms CB failure timer 2 (backtrip)

tBF2 0 ms … 40 s; step of 5 ms Current reset time

15 ms at 50 Hz 12 ms at 60 Hz

Dead zone protection Current threshold

5% to 400% x rated current Dead Zone time

t_DZ 0 ms … 40 s; step of 5 ms Hysteresis

95% with a minimum of 0.005 In

Pole Discrepancy FONCTION Current threshold

5% … 400% x rated current Pole Discrepancy time

t_PD 0 ms to 40 s; step of 5 ms Hysteresis

95% with a minimum of 0.005 In

Automation Functions

Auxiliary timers Auxiliary timer numbers 2 independent

associated to the logic Inputs Aux 1and Aux 2

tAux1 and tAux2 Range 0 ms to 200 s ; step of 10 ms

Circuit breaker control and monitoring Setting Ranges Circuit breaker opening time (t Open Pulse)

50 ms to 1 s; step of 10 ms Circuit breaker closing time (t Close Pulse)

50 ms to 1 s; step of 10 ms Circuit breaker opening alarm threshold

0 to 50000 operations Amps or square amps alarm threshold

0 to 4 109; step of 106 Circuit breaker tripping time alarm threshold

100 ms to 5 s; step of 100 ms Circuit breaker closing time alarm threshold

100 ms to 5 s; step of 100 ms

Page 9: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

P821 Technical Data Sheet 5 P821/EN TDS/C13

Recording Functions

Event recorder Capacity 75 events Time-tag to 1 millisecond Triggers

Any selected protection alarm and threshold Logic input change of state Self test events Setting changes

Fault recorder Capacity 5 faults Time-tag to 1 millisecond Triggers

Any selected protection alarm and threshold

Data Fault date Protection thresholds Setting Group AC inputs measurements (RMS) Fault magnitudes

Disturbance recorder Capacity

5 records of 3 s each Sampling rate

32 samples per frequency cycle Settings

Pre-time 100 ms to 3 s, step of 100 ms Post-time 100 ms to 3 s, step of 100 ms

Triggers Any selected protection alarm and threshold Logic input Remote command

Data AC input channels Digital input and output states Frequency value

Communications

Front port (RS232) Front port Communication Parameters

(Fixed)

Protocol Modbus RTU

Address To be specified in the « COMMUNICATIONS » menu of the relay

Messages format

IEC60870FT1.2

Baud rate 19200 bits/s

Parity Without

Stop bits 1

Data bits 8

Rear port (RS485)

Rear port settings

Setting options Setting available for:

Remote address

0 – 255 (step = 1) IEC / Kbus-Courier / Modbus RTU

Baud rate 9 600 or 19 200 bits/s

IEC

Baud rate 300, 600, 1200, 2400, 4800, 9600, 19 200 or 38 400 bits/s

Modbus

Baud rate 64000 bits/s Kbus

Parity “Even”, “Odd” or “Without”

Modbus RTU

Stop bits 0 or 1 or 2 Modbus RTU

Accuracy Breaker Fail Elements Deviation ± 2% Trigger DT: Is ± 2% Reset 0.95 Is ± 2% Time deviation ± 2% +20ms

Auxiliary Timers Time deviation ± 2% +10…20ms

Timers of Logic Functions Time deviation ± 2% +10…20ms

Autoreclosing Timers Time deviation ± 2% +10…20ms

Page 10: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

P821 Technical Data Sheet 6 P821/EN TDS/C12

Guide Form Specification The breaker fail protection has to be of entirely numerical technology and in a 4U draw out metal case.

The following functions have to be available: > Dual rated phase current inputs

> Circuit Breaker Failure phase protection:

> Current reset time less than 15 ms

> 2 independent timers with thresholds hysteresis

> Circuit Breaker Failure earth protection:

> Current reset time less than 15 ms

> 2 independent timers with thresholds hysteresis

> Dead Zone protection:

> 1 threshold with hysteresis

> Pole Discrepancy function:

> 1 threshold with hysteresis

> Circuit Breaker Monitoring

> Programmable I/O

> Relay latching (ANSI 86 code)

> Display of true RMS values

> 2 setting groups

> An RS485 rear port compatible with the following protocols: MODBUS™, Courier, IEC 60870-5-103, DNP3.0

> Records of the last 75 events, time-stamped to 1ms

> Data records relating to the last 5 faults

> Disturbance recorder with storage of 5 records, each lasting 2.5 seconds, 32 samples per cycle

The user interface must include the following elements: > A 32-character alphanumeric back-lit LCD

display

> An RS232 front port compatible with application software and PC setting software

> Programmable LEDs with customised labelling

Page 11: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

P821 Technical Data Sheet 7 P821/EN TDS/C13

CASE DIMENSIONS

9739

158168

49.5

Panel cut-out Flush mounting fixing details

Dimensionsin mm.

4 holes Ø 4.4 (M4 screw)

25.1 226

151.2 max.

Flush mountingP0395ENb

MiCOM

103

177

VA = 214.50 A

26

4 holes Ø 3.4

3926

Ala rme

Trip

Auxiliary supply

Equip. fail

AUX. 1

AUX. 3

AUX. 2

AUX. 4

P921

49.5

MiCOM P821 relay case dimensions (20TE case)

Page 12: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

P821 Technical Data Sheet 8 P821/EN TDS/C12

CONNECTION DIAGRAMS 36

Auxi

liary

volta

ge

Progra

mm

able

input

Phase

rota

tion

CB

29

L3

CT

shortin

glin

ksm

ake

bef

ore

(b)and

(c)dis

connec

t

(3)Earth

term

inals

are

typic

alonly

(2)C

Tco

nnec

tion

are

typic

alonly

Nota

:(1

)

(c)

(a)

(b)

23

27

25

21

19

L5L4

Short

term

inals

bre

ak

bef

ore

(c)

Long

term

inals

last

rela

yto

be

connec

ted

(:

term

inatin

gre

sist

or

for

the

*

30

32

*31

Progra

mm

able

outp

ut

Progra

mm

able

trip

pin

g

Watc

hdog

(4)

outp

ut

34

P821

MiC

OM

26

17

28

24

22

L2L1

RL7

RL8

13

15

11

RL6

RL5RL4

RL2 RL3

RL1

5 971320

1810 8 16

141224

33

+ _W

D

6

35

Module

term

inalblo

cks

(with

inte

gra

lca

seea

rth

link)

view

edfrom

rear

Pins

term

inals

(pcb

type)

(d)

Alte

rnativ

e:

The

earth

curr

entin

putis

connec

ted

toth

eso

mm

atio

nofth

eth

ree

phase

CTs

.

Alte

rnativ

e:

Connec

tion

to2

phase

sC

Ts+

aco

rebala

nce

dC

T.

input

Progra

mm

able

input

Progra

mm

able

input

Progra

mm

able

input

Progra

mm

able

Progra

mm

able

outp

ut

Progra

mm

able

outp

ut

Progra

mm

able

outp

ut

Progra

mm

able

outp

ut

Progra

mm

able

outp

ut

Progra

mm

able

outp

ut

The

curr

entin

puts

are

connec

ted

to3

phase

CTs

+a

core

bala

nce

dC

T.

bet

wee

n30-3

2)

+ - + - + - + - + -

47

55

53

49

51

37 45

43

41

39

35

33

29

31

48

56

54

52

50

37

38

46

44

4240

36

34

32

30

24

23

27

25

28

262

1 21

19

15

17

13

22

20

16

18

14

7 9 1153

8 12

1064

A

CA B

S1S2

S2

P2P1

P2

S1

P1

5A

5A

5A

5A

1A

1A

48

47

46

45

44

43

42

41

56

55

54

52

53

1A

1A

50

51

49

CA B

P2

S2S1

P1

5A

48

5A

47

46

45

44

5A

5A

43

42

41

56

1A

1A

55

54

53

52

1A

51

1A

50

49

B CS2

AP2

P1P2

S1

S2S1

P1

41

5A

5A

43

42

1A

1A

56

55

54

1A

1A

53

52

51

50

49 45

48

5A

5A

47

46

44

EIA

RS4

85

Port

com

munic

atio

n

Com

munic

atio

nca

ble

shie

ld

_ +

Case

earth

connec

tion

Case

earth

External connections

Page 13: P821 EN TDS C13 - Schneider Electric Belgiquemt.schneider-electric.be/OP_MAIN/Micom/P821_EN_TDS_C13.pdfSolar Radiation Avoid exposure of the front panel to direct solar radiation

P821 Technical Data Sheet 9 P821/EN TDS/C13

ORDERING INFORMATION

P 8 2 1 0 1

MiCOM Range Protection

P

Device Type MiCOM Breaker Fail Relay

8

Platform Px20 Platform

2

Model Standard (2 Ended)

1

E/F Current 0.1 – 40 ΙON A 0.01 – 8 ΙON B 0.002 – 1 ΙON C

Auxiliary Power Supply & Digital Input Voltage 24 – 60 Vdc & 24 – 60 Vdc A 48 – 150 Vdc & 48 – 150 Vdc F 130 – 250 Vdc / 110 – 250 Vac & 105 – 145 Vdc (Special application) H 130 – 250 Vdc/ 100 – 250 Vac & 130 – 250 Vdc / 100 – 250 Vac M 48 – 150 Vdc & 48 – 150 Vdc (AC Immune) T 130 – 250 Vdc / 110 – 250 Vac & 130 – 250 Vdc (AC Immune) U 48 – 150 Vdc & 110 Vdc – 30% / +20% (Special application) V 130 – 250 Vdc / 110 – 250 Vac & 220 Vdc – 30% / +20% (Special application) W

Communication Protocol MODBUS 1 K-BUS / COURIER 2 IEC60870-5-103 3 DNP3.0 4

Language French 0 English 1 Spanish 2 German 3 Italian 4 Russian 5 Polish 6 Portuguese – on request 7 Dutch – on request 8 Czech – on request 9 Hungarian – on request A Greek – on request B

Note : Please consult us for language availability