P546.pdf

Embed Size (px)

Citation preview

  • 8/14/2019 P546.pdf

    1/3

    British Columbia Service Entrance Requirements

    for Single Family Residential Buildings

    TELUS Communications Inc. is responsible for providing and installing the network

    wiring to the property, and the owner/developer is responsible for providing

    a suitable pathway (trench, conduit, aerial support etc.) as stipulated by

    TELUS Communicat ions Inc. from the proper ty l ine to the bui lding Service

    Provider Demarcation Point (SPDP).

    Aerial Service If the drop wire crosses a street or lane to reach the house,the minimum placing clearance is 5.3 m above the crown of the road. If the minimum

    road clearance cannot be maintained, a clearance pole will be requested by TELUS

    to be installed. This will provide the minimum required CSA clearance in all weather

    conditions. So, if your house is a low ranch style, to ensure adequate road clearance

    it may be necessary to place a mast. Telephone drop wire may attach to the same

    mast as electrical utility. If this is done, a minimum of a 300 mm separation must

    be kept between electrical utility and TELUS wires.

    For aerial service, the following materials, available at electrical suppliers, are

    required: Weatherhead, EMT (metal) or PVC (plastic) with UV inhibitor conduit,

    pull string and a plastic Network Interface Box (NIB) (in-wall or surface mounted).

    A condui t size of 32 mm minimum allows for placing of TELUS and CATV

    service wire to the building. Please contact your local CATV representative for

    their requirements.

    If the conduit is to support the drop wire from the pole then a minimum of 50 mm

    HDG iron pipe must be used.

    Grounding TELUS recommends that a No. 6 insulated ground wire beprovided from (and connected to) the power service ground to the NIB.

    This is the maximum size conductor requi red by the Canadian Electrical

    Code (CEC) and therefore ensures that grounding will be adequate to

    accommodate future growth of the communication installation. Please note

    that the minimum size of ground wire that TELUS will accept is a No.10

    insulated ground wire. See Canadian Electrical Code Section 60-704.

    The grounding conductor placed in the NIB should then be directly

    connected to the grounding conductor of the buildings consumer service.

    As the next (least recommended) alternative, the NIB grounding conductor

    may be attached to the power service electrical equipment enclosures

    (if allowed by the electrical inspector). Where the power grounding

    conductor is run within a metal conduit, the NIB grounding conductor

    should be bonded to that conduit.

    This ground wire should be as short as possible (as a guideline it should

    be less than 6 m) with as few bends as practical (sweep bends only).

    It must be permanent and, where needed, guarded from mechanical

    injury. An approved connector should be used for all connections.

    Notes:

    1. A minimum 300 mm clearance must be maintained in all directions between

    TELUS wires and electrica l utility wires.2. TELUS wires may be attached to the electrical utility mast for support below the

    electrical utility wires (300 mm clearance). The maximum height of the TELUS

    service attachment point shall be 6.5 m maximum.

    3. The maximum height of the TELUS service attachment point shall be 6.5 m

    maximum. Electrical utility wires cannot be attached to the TELUS mast for

    support in order to meet CEC clearance requirements.

    4. TELUS policy is to place the protector/demarcation blocks on the first buildingon which the drop or entrance cable attaches, except, when no service is

    required at the first building and the entrance cable conduit is continuous

    to the second building.5. On single family homes all wires placed beyond the demarcation point

    (termination point of the entrance cable or drop) is classifed as inside wire

    and is the responsibility of the owner.6. Flexible or Rigid conduit (complete with string) to be placed in the stud wall or

    concrete slab from the NIB to the inside wire Star Configuration inside the home

    supplied and installed by the owner/builder.

    25 mmconduit for TELUS only or 32 mmfor shared TELUS and CATV.

    7. The inside wiring should be done in a Star Configuration where the individual

    set runs from each telephone jack and TV location collect at a common location

    within the home.

    .

    Jack (Note 5)

    Telephone

    drop to building

    32 mmConduit

    TELUS only box

    See underground service below

    32 mm Conduit

    Preferred installationmethod

    Alternate aerial routes

    Telephone Weatherhead (Note 3) Electrical utility mast andWeatherhead (Note 2)

    Electrical utility service

    Communicationdrops (wires)

    1200 mm

    300 mm Separation(in all directions)(Note 1)

    Telephoneattachments

    .

    FIGURE 1A - Typical Single Family Residence

    CATV only distribution box

    FIGURE 2 - Exterior Flush Mounted Network Interface Box (NIB)

    and Demarcation Boxes

    6.5 m max.height

    to service

    attachment point

    TELUS demarcation

    point and protector(Note 4)

    Underground conduit

    Inside wire (customer owned)

    Distribution boxWeatherhead

    Propertyline Garage

    SingleFamily Home

    Wiring and

    cross-connect box

    1-50 mm Commonentrance duct

    supplied/installed

    by developer

    Aerial OptionRemove cap and placeconduit access pathSee instructionprovided with box

    CATV Enclosure

    TELUS NIB

    Pipe adapter access:

    Telephone to CATV

    FIGURE 3 - Exterior Surface Mounted

    Network Interface Box (NIB)

    Aerial Option32 mm PVC or

    51 mm rigidsteel mast

    Underground Option25 mm or 50 mm PVC

    76mm 12.7mm

    76 mm 12.7 mm

    TELUSinstalled

    protectors(NID)

    Ground barfor No.6 green

    ground wire

    Flexible or Rigid conduit inthe stud wall or concrete slabfrom the NIB to the inside wireStar Configuration insidethe home

    25 mm for No.6 insulated ground,TELUS cable

    Page 1 of 3

  • 8/14/2019 P546.pdf

    2/3

    Mobile Home on Private Property

    Mobile home owners are required to provide:

    Notes:

    1. For aerial service, a Class 6 treated pole shall be provided adjacent to the

    mobile home at the point of service entry. The treated pole shall set 1.22 m (4')

    into the ground no more than 610 mm (2') from the mobile unit.

    For minimum clearance over public and private property, see telus.com/bics

    2. For underground service, a 2 m treated post measuring 100 mm X 100 mm

    (4" X 4") shall be set 0.7 m into the ground with 1300 200 mm above thefinal grade is required.

    A Network Interface Box (NIB) provided by the owner/builder is required for aerial or

    underground service. TELUS will install protection and demarcation devices inside the

    NIB. At least one inside wire run must extend into the NIB where it can be attached to

    the demarcation device.

    The building owner is required to supply a No.6 AWG green insulated ground wire

    to the NIB.

    Underground ServiceFigure 4A 1 The owner/builder is responsible for supplying all material and

    civil work (to TELUS specifications) on private property.

    Figure 4B 2 All duct material will be orange in colour. (50 mm PVC-DB2 conduit;

    50 mm PVC-DB2 coupler)

    Figure 4B 2A 50 mm PVC-DB2 300 mm radius bend or 90 50mm PVC J-bend(may be either DB2 duct or schedule 40).

    Figure 4B 3 The owner/builder is to make the physical connection at the TELUS

    specified point-of-connection.

    Figure 4A 4 TELUS conduit must be on the property line side of the trench with

    300 mm separation from electrical utility conduit. No crossover of

    TELUS conduit and electrical utility is permitted.

    Figure 4A 5 The minimum cover above conduit to 0.45 m (1.5') or the same

    depth as electrical utility.

    Figure 4A 6 All material used for back-filling must be select fill, clear of all rocks

    and sharp stones unless otherwise specified.

    Figure 4A 6A Native fill free of rock larger than 150 mm.

    Figure 4B 7 Extend conduit 1.3 m above the final grade into NIB. Pull string to

    be 3 mm braided nylon cord.Figure 4B 7A Owner/builder to provide drain in 90 bend into drain rock, by

    perforating the bend on the bottom side.

    Figure 4B 8 No installation can have more than two 90 or equivalent bends

    (2 X 45 = 1 X 90) without the use of a pull box. Pull boxes or

    L-bends must not be used in place of a bend.

    Figure 4B 9 Maximum pulling length 60 m (200') through two 90 (300 mm

    radius) bends or 90 m (300') on a straight pull.

    Figure 4B 10 Owner/builder to provide and install the plastic in-wall or surface

    Network Interface Box (NIB).

    Figure 4B 11 Owner/builder to ensure that TELUS and electrical utility conduit

    exit the concrete at minimum 300 mm separation.

    Figure 4B 12 Depending upon foundation type and local bylaws, conduit can

    be attached to exterior (All exposed PVC conduit must have

    UV inhibitors).The exposed 50 mm (2") orange conduit may be reduced to

    25 mm (1") grey conduit above the finished grade level. Do not glue

    the coupler reducer to the 50 mm conduit, as access to the larger

    conduit may be required in the future.

    Figure 4B 13 All above requirements are subject to local building inspectors

    approval.

    Figure 4B 14 The owner/builder to provide and install a non-metallic Flexible or

    Rigid conduit (complete with string) in the stud wall or concrete slab

    from the NIB to the inside wire Star Configuration inside the home.

    25 mmconduit for TELUS only or 32 mmfor shared TELUS and CATV.

    NOTE:All materials supplied by owner/developer are available at electrical supply outlets.

    Drop wireFor single mobile hon private property

    Demarcationpoint (NIB)

    25 mm schedule40 PVC ductrecommended

    FIGURE 1B - Mobile Home on Private Property (BC)

    Post

    NIB

    Undergroundoption

    (Note 1)

    (Note 2)

    FIGURE 4A -Typical Section Thru Trench

    5

    4

    1

    4

    0.45 m Minimum

    or same depth as

    electrical utility

    6A

    6

    Electrical

    utility conduit

    300 mm Minimum

    100 mm

    200 mm

    Property line

    FIGURE 4B - Typical Section Thru Trench (In-Wall)

    Stud

    Knockoutfor aerial

    connection

    Base plate

    Finished floor Finished grade

    1.3 m abovefinished grade

    Exterior finish

    Sheathing

    Caulk

    CATV

    TELUS NIB

    1-50 mm PVCDB2 duct 7A

    TELUSservice box

    Property line

    Coupling 3

    Placed by developeor TELUS

    Placed by builder/owner 8

    2

    10

    12

    2A

    13

    11

    7

    450 mm

    Minimum

    750mm

    Minimum

    14

    Page 2 of 3

  • 8/14/2019 P546.pdf

    3/3

    CSA Canadian Standards Association

    CEC Canadian Electrical Code

    CATV Community Antenna Television

    PVC Polyvinyl Compound

    EMT Electrical Metal Tubing

    HDG High Density Gauge

    UV Ultra Violet

    DB2 Direct Buried Type 2 Conduit

    NIB Network Interface Box

    Reference

    3 mm

    32 mm

    50 mm

    400 mm

    750 mm

    1.3 m

    0.12"

    1.25"

    2"

    16"

    30"

    4.3'

    Conversions

    Metric to Imperial (approximate)

    Wiring to Inside Star Configuration

    Outdoor Network Interface Box (NIB) to InsideStar Configuration

    The owner/bui lder to provide and install a non-metall ic Flex ible or Rigidconduit (complete with string) in the stud wall or concrete slab from the NIB

    to the inside wire Star Configuration inside the home.

    25 mmconduit for TELUS only or 32 mmfor shared TELUS and CATV.

    When using rigid conduit a maximum of four sweeping 90 degree bendsor a total of 360 degrees is allowable.

    When NOT placing the conduit, pre-wire a single CAT5e cable along with a

    single Bend Insensitive Fibre (BIF) (ITU-T-G657 compliant, indoor or

    outdoor rated) from the Network Interface Box (NIB) on the outside

    of the house to the inside wire Star Configuration or Multi-media

    Enclosure inside the home.

    Pre-wire Outlets to Inside Star Configuration(Multimedia Enclosure on Backboard Area)

    The inside wiring should be done in a star configuration where theindividual set runs from each telephone jack and TV location collect at a

    common location within the home (See Figure 5A and 5B).

    The centre o f the star is to be in a heated environment where there is no riskof the ambient air temperature falling below 0 (zero) Celsius.

    A garage is NOT a suitable location. Owner/builder will provide one (1) duplex 15A non-switched power

    receptacle dedicated to home networking communication and entertainment

    equipment, installed inside the multimedia enclosure. (The use of a

    Multimedia enclosure or Smart panel is not mandatory although it is strongly

    recommended.)

    If a multimedia enclosure is not used, a duplex

    receptacle is to be located within 450 mm (18 ") of the

    star location for the home networking, communication

    and entertainment equipment installed at this

    location.

    Total space required for the mounting of the Fibre

    Equipment and Multimedia enclosure will be a

    minimum of 600 mm (24") X 900 mm (36").

    Owner/builder will provide patch panels for

    Voice/Data/Coax.

    All individual set runs are to be terminated

    at both ends (wall outlets and patch

    panels).

    FIGURE 5A - Star Configuration Attached Garage

    Central Wiring Location to be located in heatedenvironment and NOT opening into the garage

    CATV

    TELUS NIB

    Flexible or Rigid conduit in the stud wall or concrete slab

    TT

    DV

    DV

    DV

    V

    CAT5e Voice

    CAT5e Data

    CoaxCAT5e TV

    DV

    T

    T

    Service conduit

    - Owner/builder to provide a Flexible or Rigid conduit from Service Entry

    conduit to a common Central Wiring Location.- The centre of the star is to be in a heated environment where there is

    no risk of the ambient air temperature falling below 0 (zero) Celsius.

    - Coax (CATV) and Cat5e will home run back to a common location.

    (See Figure 4B)

    (See Figure 5B)

    Page 3 of 3P546 (Rev. 06-2011)

    11_00310

    Please call 310-2255for more information about

    products and services offered by TELUS or visit

    telus.com/bics

    TELUS and the TELUS logo are trademarks of TELUS Corporation, used under licence

    2011 TELUS.

    FIGURE 5B - Star Configuration

    To WallOutlets

    (Backside

    of Box)

    Entrance conduit fromProperty Line

    CATV

    TELUS NIB

    Central Wiring Location to be located

    a heated environment and NOT openininto the garage.

    - All CAT5e Voice- All CAT5e Data- All CAT5e TV- All Coax

    25 mm Flexible or Rigid conduit for TELUS only32 mm Flexible or Rigid conduit for TELUS and CATV

    http://www.telus.com/bicshttp://www.telus.com/bics