P341_EN_TDS_B11

Embed Size (px)

Citation preview

  • 7/29/2019 P341_EN_TDS_B11

    1/32

    MiCOM P341

    Generator Protection RelaySoftware Version 0320Hardw are Suffix J

    Technical Data SheetP341/EN TDS/B11

    This Document Should be Read Alongside the Technical Manual

  • 7/29/2019 P341_EN_TDS_B11

    2/32

    The MiCOM Interconnection Protection Relays

    offer the protection requirements necessary for

    operating machines in parallel with the main

    power supply network. They provide flexible and

    reliable integration of protection, control,

    monitoring and measurements. Extensive

    functionality is available to satisfy complete

    protection and control for a wide range of system

    applications, including protection for both

    connection and generator in simple applications

    or the more sophisticated interconnection

    protection necessary for larger units or those

    connected at higher voltages.

    The variable number of opto inputs and output

    contacts available allow complex protection

    schemes to be created using the relay's powerful

    but easy to use logic.

    A customer choice of industry standard protocols

    are available on the relay, facilitating an easier

    integration into both new and existing network

    control systems.

    Customer Benefits

    Extensive protectionfunctionality to meet therequirements for mostinterconnectionprotection applications

    Cost-effective solutionsto match applicationrequirements

    Flexiblecommunicationsoptions with a numberof protocols andcommunications portsavailable

    AREVA T&D

    MiCOM P341, P922GInterconnection ProtectionRelays

    PROTECTION

    MiCOM P922G

    Interconnection

    protection relay

    MiCOM P341

    Interconnection

    protection relay

  • 7/29/2019 P341_EN_TDS_B11

    3/32

    APPLICATION

    With embedded generators running in parallel with the

    normal public supply there is a risk that, due to fault

    clearances on the external system, the embedded

    generator may become disconnected from the main

    supply network. The machine may continue to supply

    external load and there is a significant risk of

    unsynchronised reconnection due to auto-reclosure of

    the remote circuit breaker. A range of protection

    functions are provided to detect this condition.

    Loss of mains techniques are provided as well as the

    more traditional functions encompassing voltage,

    frequency and power elements.

    The P341 provides overcurrent and ground fault, under

    and overvoltage, under and overfrequency, thermal

    overload, negative phase sequence overcurrent and

    overvoltage and power protection for the generator.

    In addition, rate of change of frequency and voltage

    vector shift protections are provided for loss of mains.

    The P922G provides , under and overvoltage, residual

    voltage and under and overfrequency protection.The P922G meets the specifications of EDF GTE 2666

    and is only available in the French language with

    MODBUS communications.

    GLOBAL FUNCTIONS

    The following global functions are generally available in

    both devices :

    > Under/over voltage protection

    > Under/overfrequency protection

    > Residual overvoltage protection

    > Metering

    > Event recording

    > Disturbance recording

    > Fault recording

    > Breaker condition monitoring

    MAIN PROTECTION FUNCTIONS

    The main protection functions are autonomous and can

    be individually enabled or disabled to suit a particular

    application. Each protection function is available in 4

    separate setting groups (P341) and 2 (P922G) which

    can be individually enabled or disabled.

    Three phase tripping with faulted phase indication is

    provided for all protection functions.

    2

    FUNCTIONS OVERVIEW P341 P922G

    81R Rate of change of frequency 1 -

    V Voltage vector shift 1 -

    50/51/67 Directional / non directional, instantaneous / time delayed 4 -

    phase overcurrent50N/51N/67N Directional / non directional, instantaneous / time delayed 4 -

    phase ground fault

    67N/67W Sensitive directional ground fault / wattmetric ground fault 4 -

    64 Restricted earth fault 1 -

    59N Neutral voltage displacement/residual overvoltage 2 3

    27/59 Under/Over voltage 2/2 2/2

    81U/81O Under/Over frequency 4/2 6

    32R/32L/32O Reverse/Low Forward/Over power 2 -

    49 Stator thermal overload 2 -

    46 Directional / non directional, negative phase sequence overcurrent 4

    47 Negative phase sequence overvoltage 1 -50BF CB Fail 2 -

    Current transformer supervision 1 -

    Voltage transformer supervision 1 -

    Number of setting groups 4 2

    CLIO (4 analogue inputs+4 analogue outputs) Option -

    IRIG-B Option -

    Front communications port (EIA(RS) 232 9-pin) Rear communications port (EIA (RS) 485 / K-Bus) (COMM1) Rear communications fibre optic port (COMM1) Option -

    2nd rear communications port (COMM2) Option -

    Opto Inputs 8-16 5

    Output Contacts 7-15 8

  • 7/29/2019 P341_EN_TDS_B11

    4/32

    .

    Remote

    Communication

    BinaryInput / Output

    Local

    Communication

    (RS232)

    to SCADA / subst ation control / RTU / modem ...

    via RS485 using Modbus

    Metering

    V

    81O81U

    2759 59N

    Disturbance

    Recording

    Fault Records

    LOGIC LEDS

    Interconnection Protection P922G

    COMM1

    FUNCTIONAL OVERVIEW

    MiCOM P341 :

    Comprehensive protection for all yourinterconnection protection requirements

    (Description of ANSI code nos. see Functions Overview)

    .

    Remote

    Communication

    Binary

    Input / Output

    Local

    Communication

    (RS232)to SCADA / substation control / RTU / modem ...via RS485 or Fiber optic using IEC60870-5-103,

    Modbus, DNP3.0, Courier on COMM1.COMM2 is RS485 / RS232 Courier only

    Metering

    I

    V

    I SENSITIVE

    CTS6767N

    67N

    67W

    32R / 32L

    32O46

    81R 47V81O81U2759

    64

    50

    5149

    VTS 59N

    50BF

    DisturbanceRecording

    Fault Records

    CLIO

    PSL LEDS

    Interconnection

    Protection P341Optional

    Alwaysavailable

    COMM1 COMM2

  • 7/29/2019 P341_EN_TDS_B11

    5/32

    4

    The IDMT stages have a programmable reset timer for

    grading with electromechanical relays, to reduce

    autoreclose dead times and to reduce clearance times

    where intermittent faults occur.

    The phase fault directional elements are internally

    polarised by quadrature phase-phase voltages, and

    will make a correct directional decision down to 0.5V

    (Vn = 110/120V) or 2.0V (Vn = 380/440V). A

    synchronous polarising signal is maintained for 3.2s

    after voltage collapse to ensure that the instantaneous

    and time delayed overcurrent elements operate

    correctly for close-up three phase faults.

    > Standard ground fault (P341)

    The standard ground fault element operates from a

    residual current that is derived internally from the

    summation of the three phase currents.

    The directionality of the ground fault elements is

    provided by either residual voltage or negative

    sequence voltage.Voltage transformer supervision

    (VTS) can be used to block the directional element or

    to revert it to non-directional.

    > Sensitive ground fault (P341)

    A core balance CT should be used to drive the

    sensitive ground fault function. The directionality of the

    sensitive ground fault elements is provided by the

    residual voltage.

    > Wattmetric (P341)

    The sensitive ground fault protection is also suitable for

    Petersen Coil grounded systems by enabling a

    wattmetric element.This form of protection uses the

    sensitive ground fault protection directional

    characteristic, but with a directional residual power

    threshold providing an additional constraint on

    operation.

    > Restricted ground fault (P341)

    The sensitive ground fault element may be configured

    as a high impedance differential restricted ground fault

    element. When high impedance resticted ground fault

    protection is used an additional stabilising resistance

    and a metrosil will be required.

    > Loss of mains (P341)

    In order to protect against unsynchronised

    reconnection due to autoreclosure of a remote circuit

    breaker onto a system which has become

    disconnected from the mains, specific protection is

    required. Loss of the grid connection can be protected

    against using voltage, frequency and power protection,

    but, when the machine rating closely matches the

    connected load this condition may be difficult to detect.Two methods of detection are therefore offered, rate of

    change of frequency and voltage vector shift.

    > Rate of change of frequency (P341)

    This element detects the fluctuation in frequency that

    will occur as the machine adjusts to the new load

    conditions following loss of the grid. It is inherently

    damped allowing sensitive settings to be used.

    To improve stability for external system events an

    adjustable definite time delay can be used.

    > Voltage vector shift (P341)

    This protection measures the instantaneous change in

    the three phase voltage angle that occurs when the

    connection to the main supply network is lost. To

    provide stability this element must be less sensitive

    than the rate of change of frequency element.

    However, it operates without any intentional time delay,

    providing fast tripping.

    > Phase overcurrent (P341)

    Four independent stages are available for each phase

    overcurrent, ground fault and sensitive ground fault

    element.Each stage may be selected as non-directional or

    directional (forward/reverse). All stages have definite

    time (DT) delayed characteristics, two of the stages

    may also be independently set to one of nine inverse

    definite minimum time (IDMT) curves (IEC and IEEE).

    MiCOM P341 :

    dual loss of mains protection -df/dt and voltage vector shift

    Figure 1Simple

    function selection

    by mouseclick

  • 7/29/2019 P341_EN_TDS_B11

    6/32

    > Blocked overcurrent logic (P341)

    Each stage of overcurrent, ground fault and sensitive

    ground fault protection can be blocked by an optically

    isolated input. This enables the overcurrent and ground

    fault protection to be integrated into a blocked

    overcurrent busbar protection scheme.

    > Neutral displacement/residual overvoltage

    (P341/P22G)

    Three stages of residual overvoltage (or neutral voltage

    displacement) protection are provided within the P922G

    and two stages in the P341. Depending on the VT

    configuration set on the relay, the protection will

    operate from either an internally calculated value from

    the 3 phase to neutral voltage measurements or a

    directly measured value of residual voltage from a

    broken delata VT or from the secondary winding of a

    distribution transformer ground at the generator neutral.

    The fist stage can be configured for either inverse time

    or definite time operation, with all subsequent stages

    definite time only.

    This function provides protection against ground faults

    irrespective of the system grounding connection used.

    > Under/overvoltage (P341/P22G)

    Under/overvoltage protection may be configured to

    operate from either phase-phase or phase-neutral

    voltage elements and from Any Phase variation

    (OR mode) or Three Phase variation (AND mode).

    Two independent stages with definite time elements are

    available for under and overvoltage protection.

    The first stage can also be configured to an inverse

    characteristic.

    > Under/overfrequency (P341/P922G)

    The P341 provides two independent stages of

    overfrequency and four of under frequency. The P922G

    provides 6 stages of frequency protection, each stage

    can be set for under or over frequency operation.

    Each stage functions as a definite time element.

    > Power protection (P341)

    The selectable power element can be used to provide

    loss of mains protection whether the normal power flow

    is into or out of the utility system, tripping when import

    power reverses, or export power exceeds normal limits.

    In addition to the standard 3 phase power protection

    (minimum setting 2% Pn) a sensitive single phase

    power protection element can be used (minimum

    setting 0.5% Pn) which uses the sensitive ground fault

    current input.

    > Thermal overload (P341)

    To monitor the thermal state of a generator or a feeder,

    a thermal replica protection is provided. The thermal

    element has a trip and an alarm stage. Positive and

    negative sequence currents are taken into account so

    that any unbalance condition can be detected and any

    abnormal heating of the rotor can be avoided. There

    are separate time constants for heating and cooling

    and in the event of loss of auxiliary supply the thermal

    state is stored in non volatile memory.

    > Negative phase sequence overcurrent (P341)

    Four definite time negative phase sequence overcurrent

    stages are available within the P341.

    Each stage may be selected as non-directional or

    directional (forward/reverse) and can operate for

    remote phase-phase and phase-ground faults even with

    delta-star transformers present.

    > Negative phase sequence overvoltage (P341)

    One definite time stage of negative phase sequence

    overvoltage protection is provided within the P341.

    Negative phase sequence overvoltage protection can

    be used for the detection of voltage unbalance which

    will quickly lead to overheating and damage of

    generators.

    > Analog (Current Loop) Inputs and Outputs

    (CLIO) (P341)

    Four analog (or current loop) inputs are provided for

    transducers with ranges of 0-1mA, 0-10mA, 0-20mA or

    4-20mA. The analog inputs can be used for various

    transducers such as vibration monitors, tachometers

    and pressure transducers. Associated with each input

    there are two time delayed protection stages, one for

    alarm and one for trip. Each stage can be set for 'Over'or 'Under' operation.

    Four analog (or current loop) outputs are provided with

    ranges of 0-1mA, 0-10mA, 0-20mA or 4-20mA which

    can alleviate the need for separate transducers.These

    may be used to feed standard moving coil ammeters

    for analog indication of certain measured quantities or

    into a SCADA using an existing analog RTU.

  • 7/29/2019 P341_EN_TDS_B11

    7/32

    6

    SUPERVISORY FUNCTIONS

    > Circuit breaker failure protection (P341)

    Two stage circuit breaker failure protection may be

    used for tripping upstream circuit breakers and/or the

    local secondary trip coil.The circuit breaker failure

    logic may also be initiated externally from other

    protection devices if required.

    > Voltage transformer supervision (P341)

    Voltage transformer supervision (VTS) is provided to

    detect loss of one, two or three VT signals, providing

    indication and inhibition of voltage dependent

    protection elements. An optically isolated input may

    also be configured to initiate the voltage transformer

    supervision alarm and blocking when used with

    miniature circuit breakers (MCBs) or other external

    forms of voltage transformer supervision.

    > Current transformer supervision (P341)

    Current transformer supervision (CTS) is provided todetect loss of phase CT signals and inhibit the

    operation of current dependent protection elements.

    PLANT SUPERVISION

    > Trip circuit monitoring (P341)

    Monitoring of the trip circuit in both breaker open and

    closed states can be realised using the programmable

    scheme logic.

    > Circuit breaker state monitoring

    In the P341 an alarm will be generated if there is a

    discrepancy between the open and closed contacts of

    the circuit breaker.

    > Circuit breaker condition monitoring

    The circuit breaker condition monitoring features

    include:

    monitoring the number of breaker trip operations

    recording the sum of the broken current quantity

    Ix, 1.0 x 2.0 (P341 only)

    monitoring the breaker operating time

    monitoring the fault frequency counter

    (P341 only)

    CONTROL

    > Circuit breaker control (P341)

    Circuit breaker control is available from the front panel

    user interface, optically isolated inputs and remotely via

    the substation communications.

    > Programmable scheme logic

    The P922G uses simple logic to program the digital

    inputs, output contacts and LED's.

    Programmable scheme logic in the P341 allows the

    user to customise the protection and control functions.

    It is also used to programme the functionality of the

    digital inputs, output contacts and LED indications. The

    programmable scheme logic comprises gate logic and

    general purpose timers.The gate logic includes OR,

    AND and majority gate functions, with the ability to

    invert the inputs and outputs, and provide feedback.

    The system is optimised to evaluate changes to the

    scheme logic signals and thus minimise any delays in

    logic execution. The programmable scheme logic may

    be configured using the graphical MiCOM S1 PC basedsupport software, as illustrated in Figure 2.

    The required logic is drawn as shown and is then

    downloaded directly into the relay. The logic may also

    be uploaded from the relay and then modified using

    MiCOM S1 support software.

    Comprehensive Post-fault analysisand communication options

    Figure 2 PSL Editor (MiCOM S1)

  • 7/29/2019 P341_EN_TDS_B11

    8/32

    > Control inputs (P341)

    The ON/OFF status of 32 control inputs can be

    changed manually or remotely via the communications

    to provide user defined control functions within the

    P341 PSL.

    > Latched output contacts

    Each P922G and P341 relay output contact can be

    individually programmed to be latched. Once in the

    latched state, the contact can be reset either locally or

    remotely (P341/P922G), or via the PSL in the P341

    relays.

    In addition to the ability to latch output contacts, on the

    P341 relays, each of the contacts can be individually

    conditioned by a timer to give pulse, dwell, delay on

    pick-up or delay on drop-off operation.

    MEASUREMENTS &POST FAULT ANALYSIS

    The P341 and P922G are capable of measuring andstoring a number of quantities. All events, faults and

    disturbance records are time tagged to a resolution of

    1ms using an internal real time clock. On the P341

    relays a pulsed opto input or an optional IRIG-B port is

    also available to maintain the accuracy of the real time

    clock. A supervised and easily accessed lithium

    battery ensures that the real time clock and records

    are maintained during auxiliary supply interruptions.

    > Power System Measurements

    The measurements provided will depend upon the

    application and model of the relay. Where appropriate

    the measurements may be viewed in primary or

    secondary terms and can be viewed locally or

    remotely.

    Measurements include:

    Phase / line voltages

    Sequence voltages

    Phase angles

    System frequency

    Phase / line currents (P341)

    Sequence currents (P341)

    W/Var/VA (P341)

    > Event Recording

    The P922G can store up to 75 event records for

    viewing via the local and remote communication

    ports using MiCOM S1. The P341 relay can store up to

    512 event records for viewing locally on the LCD, or

    extraction via the communication ports.

    > Fault Recording

    The relays store the last 5 faults records, typically

    containing:

    Date and time

    Protection operation

    Active setting group

    Fault voltages, frequency, etc..

    > Disturbance Recording

    The relays have an internal waveform capture facility

    with a user programmable trigger point. The P922G

    can record five disturbances, each with a duration of

    2.5 seconds at a sampling rate of 32 samples per

    cycle.The P341 can record 10 disturbances, each witha duration of 7.5 seconds (75s maximum) at a

    sampling rate of 24 samples per cycle. All disturbance

    records capture both analog and digital information

    and when extracted via the communication ports, are

    stored in Comtrade format.

    These records can be examined using MiCOM S1 or

    any other suitable software programme.

  • 7/29/2019 P341_EN_TDS_B11

    9/32

    AUTOMATION-L3-P341/922G-BR-03.05-0845b-GB

    -

    -AREVA-

    2006

    .AREVA

    ,the

    AREVAlogoan

    danya

    lterna

    tive

    vers

    ion

    thereo

    fare

    tra

    demarksan

    dserv

    icemarkso

    fAREVA

    .

    MiCOM

    isareg

    istere

    dtra

    demarko

    fAREVA

    .Alltrad

    enamesor

    tra

    demarksmen

    tione

    dhere

    inw

    he

    therreg

    istere

    dorno

    t,are

    thepropertyo

    fthe

    irowners.

    -389191982RCSPARIS-

    PDF

    ONLY-

    SONOVISION-I

    TEP

    AREVA T&D Worldwide Contact Centre:

    http://www.areva-td.com/contactcentre/

    Tel.: +44 (0) 1785 250 070

    www.areva-td.com

    www.areva-td.com/protectionrelays

    AREVA TRACK RECORD -

    INTERCONNECTION PROTECTION

    >> KVFG/MX3VI: First numerical relays combining voltage and

    frequency protection features.

    Over 3500 devices installed since 1996.

    >> MiCOM P92x: Combined numerical voltage and frequency relay.

    Over 4000 devices installed since 2000

    >> MiCOM P94x: Designed for all frequency based load applications.

    Over 600 units installed since 1999.

    >> MiCOM P342/3: Designed for all generator protection applications.

    Over 2,000 units installed since 1999.

    >> MiCOM P341: Designed for all Interconnection protection

    applications. Over 600 units installed since 1999.

    Our policy is one of continuous development. Accordingly thedesign of our products may change at any time. Whilst everyeffort is made to produce up to date literature, this brochureshould only be regarded as a guide and is intended forinformation purposes only. Its contents do not constitute an offerfor sale or advise on the application of any product referred to init. We cannot be held responsible for any reliance on anydecisions taken on its contents without specific advice.

    INFORMATION INTERFACES

    Information exchange is done via the local control

    panel, the front PC interface, the main rear

    communications interface (COMM1) or an optional

    second rear interface (COMM2 - P341).

    > Local communication

    The front EIA(RS)232 communication port has been

    designed for use with the MiCOM S1 software and is

    primarily for configuring the relay settings and

    programmable scheme logic. It is also used to locally

    extract event, fault and disturbance record information

    and can be used as a commissioning tool by viewing

    all relay measurements simultaneously.

    > Rear communication

    The P341 main rear communications interface

    supports the four protocols listed below (selected at

    time of order) and is intended for integration with

    substation control systems.

    Courier/K-Bus

    Modbus

    IEC 60870-5-103*

    DNP 3.0

    The P922G only supports the MODBUS protocol.

    An optional fiber optic interface is available for any of

    the above protocols with the P341.

    An optional 2nd rear communications port with the

    Courier protocol is available with the P341. This port is

    intended for central settings or remote access with

    MiCOM S1.

    Clock synchronization can be achieved using one of

    the protocols or using the IRIG-B input (P341) or using

    an opto input (P341).

    > Password protection

    To prevent unauthorised setting changes, all relays

    have password facilities. On the P922G one level of

    password control is available, whereas the P341

    provides two password levels.

    EMC COMPLIANCE

    89/336/EEC

    PRODUCT SAFETY

    73/23/EEC

    P34X THIRD PARTY COMPLIANCES

    File Number : E202519

    Original Issue Date :05-10-2002

    (Complies with Canadian and

    US requirements)

    Certificate Number : 104 Issue 2

    Assessment Date : 16-04-2004

    C USULfi

    Compliance with the

    European Commission

    Directive on EMC

    Compliance with the

    European Commission

    Low voltage directive

  • 7/29/2019 P341_EN_TDS_B11

    10/32

    P341 Technical Data Sheet 9 P341 Software Version 0320J

    Technical Data

    Mechanical SpecificationsDesignModular MiCOM Px40 platform relay, P341 in40TE case. Mounting is front of panel flushmounting, or 19 rack mounted (orderingoptions).

    Enclosure ProtectionPer IEC 60529: 1989:IP 52 Protection (front panel) against dust anddripping water,IP 50 Protection for sides of the case,IP 10 Protection for the rear.

    WeightP341(40TE):7kg

    Terminals

    AC Current and Voltage Measuring InputsLocated on heavy duty (black) terminal block:Threaded M4 terminals, for ring lugconnection.CT inputs have integral safety shorting, uponremoval of the terminal block.

    General Input/Output TerminalsFor power supply, opto inputs, output contactsand RP1 rear communications.Located on general purpose (grey) blocks:Threaded M4 terminals, for ring lugconnection.

    Case Protective Earth ConnectionTwo rear stud connections, threaded M4.Must be earthed (grounded) for safety,minimum earth wire size 2.5mm

    2.

    Front Port Serial PC Interface

    EIA(RS)232 DTE, 9 pin D-type femaleconnector Socket SK1.Courier protocol for interface to MiCOM S1software.Isolation to ELV (extra low voltage) level.Maximum cable length 15m.

    Front Download/Monitor PortEIA(RS)232, 25 pin D-type female connectorSocket SK2.For firmware and menu text downloads.Isolation to ELV level.

    Rear Communications Port (RP1)EIA(RS)485 signal levels, two wireconnections located on general purpose block,M4 screw.

    For screened twisted pair cable, multidrop,1000m max.For K-Bus, IEC-60870-5-103, MODBUS orDNP3.0 protocol (ordering options).Isolation to SELV (safety extra low low voltage)level .

    Optional Rear Fiber Connection forSCADA/DCSBFOC 2.5 -(ST)-interface for glass fiber, asper IEC 874-10.850nm short-haul fibers, one Tx and one Rx.For Courier, IEC-60870-5-103, MODBUS orDNP3.0 (Ordering options).

    Optional Second Rear CommunicationsPort (RP2)EIA(RS)232, 9 pin D-type female connector,

    socket SK4.Courier protocol: K-Bus, EIA(RS)232, orEIA(RS)485 connection.Isolation to SELV level.

    Optional Rear IRIG-B InterfaceBNC plugIsolation to SELV level.50 ohm coaxial cable.

    Ratings

    AC Measuring InputsNominal frequency: 50 and 60 Hz (settable)Operating range: 40 to 70 Hz

    AC CurrentNominal current (In): 1 and 5 A dual rated.(1A and 5A inputs use different transformer tapconnections, check correct terminals arewired).Nominal burden

    < 0.04 VA at In,

  • 7/29/2019 P341_EN_TDS_B11

    11/32

    P341 Technical Data Sheet 10 P341 Software Version 0320J

    Power supply

    Auxiliary Voltage (Vx)Three ordering options:(i) Vx: 24 to 48 Vdc

    (ii) Vx: 48 to 110 Vdc, and 30 to 100Vac (rms)(iii) Vx: 110 to 250 Vdc, and 100 to240Vac (rms)

    Operating Range(i) 19 to 65V (dc only for this variant)(ii) 37 to 150V (dc), 24 to 110V (ac)(iii) 87 to 300V (dc), 80 to 265V (ac).With a tolerable ac ripple of up to 12% for a dcsupply, per IEC 60255-11: 1979.

    Nominal Burden

    Quiescent burden: 11W or 24 VA. (Extra1.25W when fitted with second rearcommunications board).Additions for energized binary inputs/outputs:Per opto input:

    0.09W (24 to 54V),0.12W (110/125V),0.19W (220/250V).

    Per energized output relay: 0.13W

    Power-up TimeTime to power up < 11s.

    Power Supply InterruptionPer IEC 60255-11: 1979:

    The relay will withstand a 20ms interruptionin the DC auxiliary supply, withoutde-energizing.

    Per IEC 61000-4-11: 1994:The relay will withstand a 20ms interruptionin an AC auxiliary supply, withoutde-energizing.

    Battery BackupFront panel mounted

    Type AA, 3.6V Lithium Thionyl ChlorideBattery

    Field Voltage OutputRegulated 48VdcCurrent limited at 112mA maximum outputOperating range 40 to 60V

    Digital (Opto) InputsUniversal opto inputs with programmablevoltage thresholds (24/27, 30/34, 48/54,110/125, 220/220V). May be energized from

    the 48V field voltage, or the external batterysupply.Rated nominal voltage: 24 to 250VdcOperating range: 19 to 265VdcWithstand: 300Vdc, 300Vrms.Nominal pick-up and reset thresholds:

    Nominal battery 24/27: 60 - 80% DO/PU(logic 0) 19.2

    Nominal battery 24/27: 50 - 70% DO/PU(logic 0) 16.8

    Nominal battery 30/34: 60 - 80% DO/PU(logic 0) 24.0

    Nominal battery 30/34: 50 - 70% DO/PU(logic 0) 21.0

    Nominal battery 48/54: 60 - 80% DO/PU(logic 0) 38.4

    Nominal battery 48/54: 50 - 70% DO/PU(logic 0) 33.6

    Nominal battery 110/125: 60 - 80% DO/PU(logic 0) 88.0

    Nominal battery 110/125: 50 - 70% DO/PU(logic 0) 77.0

    Nominal battery 220/250: 60 - 80% DO/PU(logic 0) 176.0

    Nominal battery 220/250: 50 - 70% DO/PU

    (logic 0) 154Recognition time:

  • 7/29/2019 P341_EN_TDS_B11

    12/32

    P341 Technical Data Sheet 11 P341 Software Version 0320J

    Environmental Conditions

    Ambient Temperature RangePer IEC 60255-6: 1988:Operating temperature range:

    -25C to +55C (or -13F to +131F)Storage and transit:-25C to +70C (or -13F to +158F)

    Ambient Humidity RangePer IEC 60068-2-3: 1969:

    56 days at 93% relative humidity and +40 CPer IEC 60068-2-30: 1980

    Damp heat cyclic, six (12 + 12) hour cycles,93% RH, +25 to +55 C

    Type Tests

    InsulationPer IEC 60255-5: 2000:

    Insulation resistance > 100M at 500Vdc(Using only electronic/brushless insulationtester).

    Creepage Distances and ClearancesPer EN 61010-1: 2001Pollution degree 3,Overvoltage category III,Impulse test voltage 5 kV.

    High Voltage (Dielectric) Withstand(i) Per IEC 60255-5: 2000, 2 kV rms

    AC, 1 minute:Between all independent circuits.Between independent circuits and protective(earth) conductor terminal.

    1kV rms AC for 1 minute, across openwatchdog contacts.1kV rms AC for 1 minute, across opencontacts of changeover output relays.1kV rms AC for 1 minute for all D-typeEIA(RS)232/EIA(RS)485 ports between

    the communications port terminals andprotective (earth) conductor terminal

    (ii) Per ANSI/IEEE C37.90-1989 (reaffirmed1994):1.5 kV rms AC for 1 minute, across opencontacts of normally open output relays.1kV rms AC for 1 minute, across openwatchdog contacts.1kV rms AC for 1 minute, across opencontacts of changeover output relays.

    Impulse Voltage Withstand Test

    Per IEC 60255-5: 2000:Front time: 1.2 s, Time to half-value: 50 s,Peak value: 5 kV, 0.5JBetween all independent circuits.Between all independent circuits andprotective (earth) conductor terminal.

    Between the terminals of independent circuits.EIA(RS)232 & EIA(RS)485 ports and normallyopen contacts of output relays excepted.

    Electromagnetic Compatibility

    (EMC)

    1 MHz Burst High Frequency DisturbanceTestPer IEC 60255-22-1: 1988, Class III,Common-mode test voltage: 2.5 kV,Differential test voltage: 1.0 kV,

    Test duration: 2 s, Source impedance: 200 (EIA(RS)232 ports excepted).

    Immunity to Electrostatic DischargePer IEC 60255-22-2: 1996, Class 4,

    15kV discharge in air to user interface,display, and exposed metalwork.

    Per IEC 60255-22-2: 1996, Class 3,8kV discharge in air to all communicationports.

    6kV point contact discharge to any part of thefront of the product.

    Electrical Fast Transient or BurstRequirementsPer IEC 60255-22-4: 2002. Test severityClass III and IV:Amplitude: 2 kV, burst frequency 5kHz

    (Class III),Amplitude: 4 kV, burst frequency 2.5kHz(Class IV).Applied directly to auxiliary supply, andapplied to all other inputs. (EIA(RS)232 portsexcepted).

    Surge Withstand CapabilityPer IEEE/ANSI C37.90.1: 2002:4kV fast transient and 2.5kV oscillatory applieddirectly across each output contact, opticallyisolated input, and power supply circuit.

    Surge Immunity Test(EIA(RS)232 ports excepted).Per IEC 61000-4-5: 2002 Level 4,Time to half-value: 1.2/50 s,Amplitude: 4kV between all groups andprotective (earth) conductor terminal.Amplitude: 2kV between terminals of eachgroup.

    Immunity to Radiated ElectromagneticEnergy

    Per IEC 60255-22-3: 2000, Class III:Test field strength, frequency band 80 to 1000MHz:

    10 V/m,Test using AM: 1 kHz / 80%,Spot tests at 80, 160, 450, 900 MHz

  • 7/29/2019 P341_EN_TDS_B11

    13/32

    P341 Technical Data Sheet 12 P341 Software Version 0320J

    Per IEEE/ANSI C37.90.2: 2004:80MHz to 1000MHz, 1kHz 80% am and ampulsed modulated.Field strength of 35V/m.

    Radiated Immunity from DigitalCommunicationsPer EN61000-4-3: 2002, Level 4:Test field strength, frequency band 800 to 960MHz, and 1.4 to 2.0 GHz:

    30 V/m,Test using AM: 1 kHz/80%.

    Radiated Immunity from Digital RadioTelephonesPer IEC61000-4-3: 2002:10 V/m, 900MHz and 1.89GHz.

    Immunity to Conducted DisturbancesInduced by Radio Frequency FieldsPer IEC 61000-4-6: 1996, Level 3,Disturbing test voltage: 10 V.

    Power Frequency Magnetic Field ImmunityPer IEC 61000-4-8: 1994, Level 5,

    100A/m applied continuously,1000A/m applied for 3s.

    Per IEC 61000-4-9: 1993, Level 5,1000A/m applied in all planes.

    Per IEC 61000-4-10: 1993, Level 5,

    100A/m applied in all planes at100kHz/1MHz with a burst duration of 2s.

    Conducted EmissionsPer EN 55022: 1998:

    0.15 - 0.5MHz, 79dBV (quasi peak) 66dBV(average)

    0.5 - 30MHz, 73dBV (quasi peak) 60dBV(average).

    Radiated EmissionsPer EN 55022: 1998:

    30 - 230MHz, 40dBV/m at 10mmeasurement distance230 - 1GHz, 47dBV/m at 10m measurementdistance.

    EU Directives

    EMC CompliancePer 89/336/EEC:Compliance to the European CommissionDirective on EMC is claimed via the TechnicalConstruction File route. Product Specific

    Standards were used to establish conformity:EN50263: 2000

    Product SafetyPer 73/23/EEC:Compliance with European Commission LowVoltage Directive. Compliance isdemonstrated by reference to generic safetystandards:

    IEC60255-27: 2005EN60255-5: 2001

    73/23/EEC

    R&TTE ComplianceRadio and Telecommunications TerminalEquipment (R & TTE) directive 95/5/EC.Compliance demonstrated by compliance tothe Low Voltage Directive, 73/23/EECamended by 93/68/EEC, down to zero volts byreference to safety standards.

    Applicable to rear communications ports.

    ATEX ComplianceATEX Potentially Explosive Atmospheresdirective 94/9/EC, for equipment.The equipment is compliant with Article 1(2) ofEuropean directive 94/9/EC.It is approved for operation outside an ATEXhazardous area. It is however approved forconnection to Increased Safety, Ex e, motorswith rated ATEX protection, EquipmentCategory 2, to ensure their safe operation in

    gas Zones 1 and 2 hazardous areas.

    CAUTION - Equipment with this marking is notitself suitable for operation within a potentiallyexplosive atmosphere.

    Compliance demonstrated by Notified Bodycertificates of compliance.

    II (2) G

    Mechanical Robustness

    Vibration TestPer IEC 60255-21-1: 1996:

    Response Class 2Endurance Class 2

    Shock and BumpPer IEC 60255-21-2: 1996:

    Shock response Class 2

    Shock withstand Class 1Bump Class 1

    Seismic TestPer IEC 60255-21-3: 1995:

    Class 2

  • 7/29/2019 P341_EN_TDS_B11

    14/32

    P341 Technical Data Sheet 13 P341 Software Version 0320J

    P34x THIRD PARTY COMPLIANCES(UL/CUL, ENA)

    File Number: E202519Original Issue Date: 05-10-2002(Complies with Canadian and USrequirements).

    Certificate Number: 104 Issue 2Assessment Date: 16-04-2004

  • 7/29/2019 P341_EN_TDS_B11

    15/32

    P341 Technical Data Sheet 14 P341 Software Version 0320J

    Protection Functions

    Reverse/Low Forward/Over Power(3 Phase)

    Accuracy

    Pick-up: Setting 10%Reverse/Over Power Drop-off:

    0.95 of setting 10%Low forward power Drop-off:

    1.05 of setting 10%Angle variation Pick-up:

    Expected pick-up angle 2 degreeAngle variation Drop-off:

    Expected drop-off angle 2.5 degreeOperating time: 2% or 50ms whichever is

    greater

    Repeatability:

  • 7/29/2019 P341_EN_TDS_B11

    16/32

    P341 Technical Data Sheet 15 P341 Software Version 0320J

    Wattmetric SEF Accuracy

    P = 0W Pick-up: ISEF> 5%P > 0W Pick-up: P> 5%P = 0W Drop-off: (0.95 x ISEF>) 5%P > 0W Drop-off: 0.9 x P> 5%Boundary accuracy: 5% with 1 hysteresisRepeatability: 5%

    Zero Sequence Polarizing QuantitiesAccuracy

    Operating boundary Pick-up: 2 of RCA 90Hysteresis:

  • 7/29/2019 P341_EN_TDS_B11

    17/32

    P341 Technical Data Sheet 16 P341 Software Version 0320J

    Instantaneous operation:

  • 7/29/2019 P341_EN_TDS_B11

    18/32

    P341 Technical Data Sheet 17 P341 Software Version 0320J

    Current Loop Input and Outputs

    Accuracy

    Current loop input accuracy: 1% of full scaleCLI drop-off threshold Under: setting 1% of

    full scaleCLI drop-off threshold Over: setting 1% of full

    scaleCLI sampling interval: 50msCLI instantaneous operating time: < 250ms

    CLI DT operating time: 2% setting or 200mswhichever is the greater

    CLO conversion interval: 50msCLO latency: < 1.07s or

  • 7/29/2019 P341_EN_TDS_B11

    19/32

    P341 Technical Data Sheet 18 P341 Software Version 0320J

    Settings, Measurements andRecords List

    Settings List

    Global Settings (System Data)Language: English/French/German/SpanishFrequency: 50/60Hz

    Circuit Breaker Control(CB Control):

    CB Control by:DisabledLocalRemote

    Local+RemoteOptoOpto+localOpto+RemoteOpto+Rem+localClose Pulse Time: 0.10...10.00sTrip Pulse Time: 0.105.00sMan Close t max: 0.019999.00sMan Close Delay: 0.01600.00sCB Healthy Time: 0.019999.00sCheck Sync. Time: 0.01...9999.00sReset Lockout by: User Interface/CB CloseMan Close RstDly: 0.10...600.00s

    CB Status Input:None52A52B52A & 52B

    Date and TimeIRIG-B Sync: Disabled/EnabledBattery Alarm: Disabled/Enabled

    ConfigurationSetting Group:

    Select via MenuSelect via PSLActive Settings: Group 1/2/3/4Setting Group 1: Disabled/EnabledSetting Group 2: Disabled/EnabledSetting Group 3: Disabled/EnabledSetting Group 4: Disabled/EnabledSystem Config: Invisible/VisiblePower: Disabled/EnabledOvercurrent: Disabled/EnabledThermal Overload: Disabled/EnabledEarth Fault: Disabled/EnabledSEF/REF/Spower: Disabled or SEF/REF or

    Sensitive Power

    Residual O/V NVD: Disabled/Enableddf/dt: Disabled/EnabledV Vector Shift: Disabled/EnabledReconnect Delay: Disabled/EnabledVolt Protection: Disabled/EnabledFreq Protection: Disabled/Enabled

    CB Fail: Disabled/EnabledSupervision: Disabled/EnabledInput Labels: Invisible/VisibleOutput Labels: Invisible/VisibleCT & VT Ratios: Invisible/VisibleEvent Recorder: Invisible/VisibleDisturb Recorder: Invisible/VisibleMeasuret Setup: Invisible/VisibleComms Settings: Invisible/VisibleCommission Tests: Invisible/VisibleSetting Values: Primary/SecondaryControl Inputs: Invisible/VisibleCLIO Inputs: Disabled/Enabled

    CLIO Outputs: Disabled/EnabledCtrl I/P Config: Invisible/VisibleCtrl I/P Labels: Invisible/VisibleDirect Access: Disabled/EnabledLCD Contrast: 031

    CT and VT RatiosMain VT Primary: 100...1000000VMain VT Sec'y: 80...140

    (100/120V) 320560V (380/480V)VN VT Primary (P342/3): 1001000000VVN VT Secondary (P342/3): 80140V

    (100/120V) 320560V (380/480V)Phase CT Primary: 1A30kAPhase CT Sec'y: 1A/5ASEF CT Primary: 1A30KASEF CT Secy: 1A/5A

    Sequence of Event Recorder(Record Control)Alarm Event: Disabled/EnabledRelay O/P Event: Disabled/EnabledOpto Input Event: Disabled/EnabledGeneral Event: Disabled/Enabled

    Fault Rec Event: Disabled/EnabledMaint Rec Event: Disabled/EnabledProtection Event: Disabled/EnabledDDB 31 - 0: (up to):DDB 1022 - 992:

    Binary function link strings, selecting whichDDB signals will be stored as events, andwhich will be filtered out.

    Oscillography(Disturbance Recorder)Duration: 0.1010.50s

    Trigger Position: 0.0100.0%Trigger Mode: Single/ExtendedAnalog Channel 1: (up to):Analog Channel 15:

    Disturbance channels selected from:IA/IB/IC/VA/VB/VC/VN/ISensitive

  • 7/29/2019 P341_EN_TDS_B11

    20/32

    P341 Technical Data Sheet 19 P341 Software Version 0320J

    Digital Input 1: (up to):Digital Input 32:Selected binary channel assignment from anyDDB status point within the relay (opto input,output contact, alarms, starts, trips, controls,logic).

    Input 1 Trigger: No Trigger/Trigger/LH (Low toHigh)/Trigger H/L (High to Low)

    (up to):Input 32 Trigger: No Trigger/TriggerL/H/Trigger H/L

    Measured Operating Data(Measuret Setup)Default Display:

    Access Level3Ph + N Current3Ph Voltage

    PowerDate and TimeDescriptionPlant ReferenceFrequency

    Local Values: Primary/SecondaryRemote Values: Primary/SecondaryMeasurement Ref: VA/VB/VC/IA/IB/ICMeasurement Mode: 0/1/2/3Fix Dem Period: 199minsRoll Sub Period: 199minsNum Sub Periods: 115Remote2 Values: Primary/Secondary

    CommunicationsRP1 Address: (Courier or IEC870-5-103):

    0255RP1 Address: (DNP3.0):

    065534RP1 Address: (MODBUS):

    1247RP1 InactivTimer: 130minsRP1 Baud Rate: (IEC870-5-103):

    9600/19200 bits/sRP1 Baud Rate: (MODBUS, Courier):

    9600/19200/38400 bits/sRP1 Baud Rate: (DNP3.0):1200/2400/4800/9600/19200/ 38400 bits/s

    RP1 Parity: Odd/Even/None(MODBUS, DNP3.0)

    RP1 Meas Period: 160s(IEC870-5-103)

    RP1 PhysicalLink:Copper (EIA(RS)485/K bus) or Fiber Optic

    RP1 Time Sync: Disabled/EnabledMODBUS IEC Timer: Standard/ReverseRP1 CS103Blocking:

    Disabled

    Monitor BlockingCommand Blocking

    RP1 Port Config: (Courier):K BusEIA485 (RS485)

    RP1 Comms Mode: (Courier):

    IEC60870 FT1.2IEC60870 10-Bit No parity

    Note: If RP1 Port Config is K Bus the baudrate is fixed at 64 kbits/s

    Optional Additional Second RearCommunication(Rear Port2 (RP2))RP2 Port Config:

    EIA(RS)232EIA(RS)485K-Bus

    RP2 Comms Mode:IEC60870 FT1.2IEC60870 10-Bit No parity

    RP2 Address: 0255RP2 InactivTimer: 130minsRP2 Baud Rate:

    9600/19200/38400 bits/sNote: If RP2 Port Config is K Bus the baud

    rate is fixed at 64 kbits/s

    Commission TestsMonitor Bit 1:

    (up to):Monitor Bit 8:

    Binary function link strings, selecting whichDDB signals have their status visible in theCommissioning menu, for test purposes

    Test Mode:

    DisabledTest ModeBlocked Contacts

    Test Pattern:Configuration of which output contacts are tobe energized when the contact test isapplied

    Circuit Breaker ConditionMonitoring(CB Monitor Setup)Broken I^: 1.02.0

    I^ Maintenance: Alarm Disabled/EnabledI^ Maintenance: 125000I^ Lockout: Alarm Disabled/EnabledI^ Lockout: 125000No. CB Ops Maint: Alarm Disabled/EnabledNo. CB Ops Maint: 110000No. CB Ops Lock: Alarm Disabled/EnabledNo. CB Ops Lock: 110000CB Time Maint: Alarm Disabled/EnabledCB Time Maint: 0.0050.500sCB Time Lockout: Alarm Disabled/EnabledCB Time Lockout: 0.0050.500sFault Freq Lock: Alarm Disabled/Enabled

    Fault Freq Count: 19999Fault Freq Time: 09999s

  • 7/29/2019 P341_EN_TDS_B11

    21/32

    P341 Technical Data Sheet 20 P341 Software Version 0320J

    Opto Coupled Binary Inputs(Opto Config)Global Nominal V:

    24 - 27V30 - 34V48 - 54V110 - 125V220 - 250V

    CustomOpto Input 1:

    (up to):Opto Input #. (# = max. opto no. fitted):

    Custom options allow independentthresholds to be set per opto, from the samerange as above.

    Opto Filter Control:Binary function link string, selecting whichoptos will have an extra 1/2 cycle noise filter,

    and which will not.Characteristics:Standard 60% - 80%50% - 70%

    Control Inputs into PSL(Ctrl. I/P Config.)Hotkey Enabled:

    Binary function link string, selecting which ofthe control inputs will be driven fromHotkeys.

    Control Input 1: Latched/Pulsed(up to):

    Control Input 32: Latched/PulsedCtrl Command 1:

    (up to):Ctrl Command 32:

    ON/OFFSET/RESETIN/OUTENABLED/DISABLED

    Control Input User Labels(Ctrl. I/P Labels)Control Input 1:

    (up to):Control Input 32:

    User defined text string to describe thefunction of the particular control input

    Settings in Multiple GroupsNote: All settings here onwards apply for

    setting groups # = 1 to 4.

  • 7/29/2019 P341_EN_TDS_B11

    22/32

    P341 Technical Data Sheet 21 P341 Software Version 0320J

    Protection Functions

    System Config.Phase Sequence: Standard ABC/Reverse

    ACB

    VT Reversal: No Swap/A-B Swapped/B-CSwapped/C-A Swapped

    CT1 Reversal: No Swap/A-B Swapped/B-CSwapped/C-A Swapped

    Reverse/Low Forward/Over Power(3 Phase)Operating mode:

    GeneratingMotoring

    Power 1 Function:Reverse

    Low forwardOver

    -P>1 Setting (reverse power/P1Setting (Overpower):

    4300.0W (1A, 100V/120V)161200.0W (1A, 380V/480V)201500.0W (5A, 100V/120V)806000.0W (5A, 380V/480V)

    Equivalent Range in %Pn 0.5%157%Power 1 Time Delay: 0.00100.0sPower 1 DO Timer: 0.00100.0sP1 Poledead Inh: Disabled/Enabled

    Power 2 as Power 1

    Sensitive/Reverse/LowForward/Over Power (1 Phase)Operating mode:

    GeneratingMotoring

    Sen Power1 Func:ReverseLow forwardOver

    Sen -P>1 Setting (Reverse Power)/Sen P Setting(Over Power):

    0.3100.0W (1A, 100/120V)1.20400.0W (1A, 380/480V)1.50500.0W (5A, 100/120V)6.02000.0W (5A, 380/480V)

    Equivalent range in %Pn 0.5%157%Sen Power 1 Delay: 0.00100.0sPower 1 DO Timer: 0.00100.0sP1 Poledead Inh: Disabled/Enabled

    Comp angle C: -5+5.0Sen Power2 as Sen Power 1

    Phase Overcurrent (Overcurrent)Phase O/C: Sub HeadingI>1 Function:

    DisabledDTIEC S Inverse

    IEC V InverseIEC E InverseUK LT InverseUK RectifierRIIEEE M InverseIEEE V InverseIEEE E InverseUS InverseUS ST Inverse

    I>1 Direction:Non-DirectionalDirectional FwdDirectional Rev

    I>1 Current Set: 0.084.00 InI>1 Time Delay: 0.00100.00sI>1 TMS: 0.0251.200I>1 Time Dial: 0.01100.00I>1 K (RI): 0.1010.00I>1 Reset Char: DT/InverseI>1 tRESET: 0.00100.00sI>2 as I>1I>3 Status: Disabled/EnabledI>3 Direction:

    Non-DirectionalDirectional FwdDirectional Rev

    I>3 Current Set: 0.0810.00 InI>3 Time Delay: 0.00100.00sI>4 as I>3I> Char Angle: -95+95

    o

    I >Function Link:Bit 0 = VTS Blocks I>1Bit 1 = VTS Blocks I>2Bit 2 = VTS Blocks I>3Bit 3 = VTS Blocks I>4Bit 4, 5, 6 & 7 are not usedBinary function link string, selecting which

    overcurrent elements (stages 1 to 4) will beblocked if VTS detection of fuse failureoccurs.

    Inverse time (IDMT) characteristic

    IDMT characteristics are selectable from achoice of four IEC/UK and five IEEE/US curvesas shown in the table below.

    The IEC/UK IDMT curves conform to thefollowing formula:

    t = T x

    K

    (/s) - 1 + L

  • 7/29/2019 P341_EN_TDS_B11

    23/32

    P341 Technical Data Sheet 22 P341 Software Version 0320J

    The IEEE/US IDMT curves conform to thefollowing formula:

    t = TD x

    K

    (/s)

    - 1+ L

    Where:

    t = Operation timeK = Constant

    = Measured currentS = Current threshold setting = ConstantL = ANSI/IEEE constant (zero for IEC/UK

    curves)T = Time multiplier setting for IEC/UK curvesTD = Time dial setting for IEEE/US curves

    IDMT characteristics

    IDMT Curve Stand. K L

    Standard inverse IEC 0.14 0.02 0

    Very inverse IEC 13.5 1 0

    Extremely inverse IEC 80 2 0

    Long time inverse UK 120 1 0

    Rectifier UK 45900 5.6 0

    Moderately inverse IEEE 0.0515 0.02 0.114

    Very inverse IEEE 19.61 2 0.491

    Extremely inverse IEEE 28.2 2 0.1217

    Inverse US-C08 5.95 2 0.18

    Short time inverse US-C02 0.16758 0.02 0.11858

    The IEC extremely inverse curve becomesdefinite time at currents greater than 20 xsetting. The IEC standard, very and long timeinverse curves become definite time atcurrents greater than 30 x setting.

    For all IEC/UK curves, the reset characteristicis definite time only.

    For all IEEE/US curves, the reset characteristiccan be selected as either inverse curve ordefinite time.

    The inverse reset characteristics aredependent upon the selected IEEE/US IDMTcurve as shown in the table below.

    All inverse reset curves conform to thefollowing formula:

    tRESET =

    TD x S

    (1 - M2)in seconds

    Where:

    TD = Time dial setting for IEEE curvesS = Constant

    M = /s

    Curve Description Standard S

    Moderately inverse IEEE 4.85

    Very inverse IEEE 21.6

    Extremely inverse IEEE 29.1

    Inverse US 5.95

    Short time inverse US 2.261

    The RI curve (electromechanical) has beenincluded in the first stage characteristic settingoptions for Phase Overcurrent and Earth Faultprotections. The curve is represented by thefollowing equation:

    t = K x

    1

    0.339 - ( )0.236/M in seconds

    With K adjustable from 0.1 to 10 in steps of0.05

    M = /s

    Curve 4

    Curve 1

    Curve 2

    Curve 3

    1000

    100

    10

    1

    0.1

    100.010.01.0

    Current (Multiples of Is)

    OperatingTime(s)

    Curve 1 Standard inverse

    Curve 2 Very inverse

    Curve 3 Extremely inverse

    Curve 4 UK long time inverse

    IEC Curves

    P2136ENa

  • 7/29/2019 P341_EN_TDS_B11

    24/32

    P341 Technical Data Sheet 23 P341 Software Version 0320J

    Curve 5 IEEE moderately inverse

    Curve 6 IEEE very inverse

    Curve 7 IEEE extremely inverse

    Curve 8 US inverse

    Curve 9 US short time inverse

    Amercian Curves

    Curve 5

    100.010.01.0

    Current (Multiples of Is)

    0.1

    1

    10

    100

    OperatingTime(s)

    Curve 6

    Curve 9

    Curve 7

    Curve 8

    P2137ENa

    NPS Overcurrent2>1 Status: Disabled/Enabled2>1 Direction:

    Non-DirectionalDirectional FwdDirectional Rev

    2> Current Set: 0.084.00n2> Time Delay: 0.00100.00s2>2/3/4 as for2>12> VTS Block:

    Bit 0 = VTS Blocks 2>1Bit 1 = VTS Blocks 2>2Bit 2 = VTS Blocks 2>3Bit 3 = VTS Blocks 2>4Bits 4, 5, 6 & 7 are not usedBinary function link string, selecting whichNPS overcurrent elements (stages 1 to 4)will be blocked if VTS detection of fusefailure occurs.

    2> V2pol Set:0.525.0 (100V 120V)2100V (380/480V)

    2> Char Angle: -95+95

    Thermal OverloadThermal: Disabled/EnabledThermal I>: 0.502.50 InThermal Alarm: 20..100%T-heating: 1200 minutes

    T-cooling: 1200 minutesM Factor: 010

    The thermal time characteristic is given by:

    t = loge (eq2 - P2)/(eq2 - (Thermal >)2)

    t = . loge ((K2

    -A

    2

    )/(K

    2

    -1))Where:

    K = eq/Thermal >A = P/Thermal >t = Time to trip, following application of the

    overload current, = Heating time constant of the protected

    plant

    eq = Equivalent currentThermal > = Relay setting currentP = Steady state pre-load current

    before application of theoverload

    eq = (12

    + M22)

    1 = Positive sequence current2 = Negative sequence currentM = A user settable constant

    proportional to the thermalcapacity of the machine

    Earth Fault

    IN1>1 Function:

    DisabledDTIEC S InverseIEC V InverseIEC E InverseUK LT InverseRIIEEE M InverseIEEE V InverseIEEE E InverseUS InverseUS ST InverseIDG

    IN1>1 DirectionalNon-DirectionalDirectional FwdDirectional Rev

    IN1>1 Current Set: 0.084.00 InIN1>1 IDG Is: 1.04.0 InIN1>1 Time Delay: 0.00200.00sIN1>1 TMS: 0.0251.200IN1>1 Time Dial: 0.01100.00IN1>1 K(RI): 0.10.10.00IN1>1 IDG Time: 1.00...2.00IN1>1 Reset Char.: DT/InverseIN1>1 tRESET: 0.00100.00s

    IN1>2 as IN>1IN1>3 Status:

    DisabledEnabled

    IN1>3 Directional:Non-Directional

  • 7/29/2019 P341_EN_TDS_B11

    25/32

    P341 Technical Data Sheet 24 P341 Software Version 0320J

    Directional FwdDirectional Rev

    IN1>3 Current Set: 0.0832.00 InIN1>3 Time Delay: 0.00200.00sIN1>4 as IN>3IN1> Blocking:

    Binary function link string, selecting whichground overcurrent elements (stages 1 to 4)will be blocked if VTS detection of fusefailure occurs.IN1> Char Angle: -95 +95

    o

    IN1> Polarization:Zero SequenceNeg. Sequence

    IN1> VNpol Set:0.580.0V (100/110V)2320V (380/480V)

    IN1> V2pol Set:0.525.0V (100/110V)

    2100V (380/480V)IN1> I2pol Set: 0.081.00 In

    The IDG curve is commonly used for timedelayed earth fault protection in the Swedishmarket. This curve is available in stage 1 ofthe Earth Fault protection.

    The IDG curve is represented by the followingequation:

    t = 5.8 - 1.35 loge

    N > Setting in seconds

    Where:

    = Measured currentN>Setting = An adjustable setting which

    defines the start point of thecharacteristic

    Although the start point of the characteristic is

    defined by the N> setting, the actual relaycurrent threshold is a different setting called

    IDG s. The IDG s setting is set as amultiple of N>.

    An additional setting IDG Time is also usedto set the minimum operating time at highlevels of fault current.

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1 10 100

    I/IN>

    Operatingtime(seconds)

    IDG Is Setting Range

    IDG Time Setting Range

    P2242ENa

    IDG Characteristic

    SEF/REF ProtnSEF/REF Options:

    SEFSEF Cos (PHI)SEF Sin (PHI)Wattmetric

    Hi Z REFISEF>1 Function:

    DisabledDTIEC S InverseIEC V InverseIEC E InverseUK LT InverseRIIEEE M InverseIEEE V InverseIEEE E InverseUS InverseUS ST InverseIDG

    ISEF>1 Directional:Non-DirectionalDirectional FwdDirectional Rev.

    ISEF>1 Current Set: 0.005...0.10 InISEF>1 IDG Is: 1.0...4.0 InISEF>1 Time Delay: 0.00...200.00sISEF>1 TMS: 0.025...1.200ISEF>1 Time Dial: 0.01...100.0ISEF>1 IDG Time: 1.00...2.00ISEF>1 Reset Char: DT/InverseISEF>1 tRESET: 0.00...100.00sISEF>2 as ISEF>2ISEF>3 Status:

    DisabledEnabled

    ISEF>3 Directional:Non-DirectionalDirectional FwdDirectional Rev

    ISEF>3 Current Set: 0.005...0.80 InISEF>3 Time Delay: 0.00...200.00sISEF>4 as ISEF>3

    ISEF> Blocking:Binary function link string, selecting whichground overcurrent elements (stages 1 to 4)will be blocked if VTS detection of fusefailure occurs.ISEF> Char. Angle: -95...+95

    o

    ISEF> VNpol Set:0.5...80.0V (100/120V)2...320V (380/480V)WATTMETRIC SEF:

    PN> Setting: 0....20In W (100/120V)PN> Setting: 0 ....80In W (380/480V)

    Restricted Earth Fault (HighImpedance)IREF>Is: 0.05.1.00 In

  • 7/29/2019 P341_EN_TDS_B11

    26/32

    P341 Technical Data Sheet 25 P341 Software Version 0320J

    Residual O/V NVDVN>1 Status: Disabled/EnabledVN>1 Input: DerivedVN> 1 Function:

    DisabledDT

    IDMTVN> 1 Voltage Set:

    180V (100/120V)4320V (380/480V)

    VN> 1 Time Delay: 0.00100.00sVN>1 TMS: 0.5100.0VN> 1 tRESET: 0.00100.00VN>2 as VN>1VN>3/4 as VN>1 exceptVN>3/4 Input: VN1

    DF/DTdf/dt Status: Disabled/Enabled

    df/dt Setting: 0.110 Hz/sdf/dt Time Delay: 0.00100.0sdf/dt f low: 4565Hzdf/dt f high: 4565Hz

    V Vector ShiftV Shift Status: Disabled/EnabledV Shift Angle: 230

    o

    Reconnect DelayReconnect Status: Disabled/Enabled

    Reconnect Delay: 0300.0sReconnect tPULSE: 010.0s

    Voltage Protection

    Under VoltageV< Measurt Mode:

    Phase-PhasePhase-Neutral

    V< Operate Mode:Any PhaseThree Phase

    V< 1 Function:DisabledDTIDMT

    V2 Time Delay: 0.00100.00s

    The inverse characteristic is given by thefollowing formula:

    t =K

    (M - 1)

    Where:

    K = Time multiplier settingt = Operating time in secondsM = Applied input voltage/relay setting voltage

    NPS Over VoltageV2>1 status: Enabled/DisabledV2>1 Voltage Set:

    1150V (100/120V)4600V (380/480V)

    V2>1 Time Delay: 0.00100.00s

    Frequency Protection

    Under FrequencyF

  • 7/29/2019 P341_EN_TDS_B11

    27/32

    P341 Technical Data Sheet 26 P341 Software Version 0320J

    Bit 2 - Enable Block F1 Setting: 45.0068.00HzF>1 Time Delay: 0.1100.0sF>2 as F>1

    CB FailCB Fail 1 Status: Disabled/EnabledCB Fail 1 Timer: 0.0010.00sCB Fail 2 Status: Disabled/EnabledCB Fail 2 Timer: 0.0010.00sCBF Non I Reset: I< Only, CB Open & I Inhibit: 0.08 In32.0 InVTS I2> Inhibit: 0.05 In0.50 InNegative phase sequence voltage (V2):

    10V (100/120V)40V (380/480V)

    Phase overvoltage:Pick-up 30V,Drop-off 10V (100/120V)Pick-up 120V,Drop-off 40V (380/480v)

    Superimposed Current: 0.1 In

    Current Transformer SupervisionCTS 1 Status: Disabled/EnabledCTS 1 VN Input: Measured/DerivedCTS 1 VN< Inhibit:

    0.522V (100/120V)288V (380/480V)

    CTS 1 IN> Set: 0.084InCTS 2 as CTS1

    Plant Supervision

    CB State Monitoring Control andCondition MonitoringBroken I^: 12.0I^ Maintenance:

    Alarm disabled

    Alarm enabledI^ Maintenance: 1In^25000In^I^ Lockout:

    Alarm disabledAlarm enabled

    I^ Lockout: 125000

    No CB Ops. Maint:Alarm disabledAlarm enabled

    No CB Ops: Maint: 110000No CB Ops Lock:

    Alarm disabledAlarm enabled

    No CB Ops Lock: 110000CB Time Maint:

    Alarm disabledAlarm enabled

    CB Time Maint: 0.0050.500sCB Time Lockout:

    Alarm disabledAlarm enabled

    CB Time Lockout: 0.0050.500sFault Freq Lock:

    Alarm disabledAlarm enabled

    Fault Freq Count: 19999Fault Freq Time: 09999s

    Input LabelsOpto Input 132: Input L1Input L32

    Output LabelsRelay 132: Output R1Output R32

    Current Loop InputCLIO1 Input 1: Disabled/EnabledCLI1 Input Type:

    0 - 1mA0 - 10mA0 - 20mA4 - 20mA

    CLI1 Input Label: 16 characters (CLIO input 1)CLI1 Minimum: -9999+9999

    CLI1 Maximum: -9999+9999CLI1 Alarm: Disabled/EnabledCLI1 Alarm Fn: Over/UnderCLI1 Alarm Set: CLI1 minCLI1 maxCLI1 Alarm Delay: 0.0100.0sCLI1 Trip: Disabled/EnabledCLI1 Trip Fn: Over/UnderCLI1 Trip Set: CLI1 minCLI1 maxCLI1 Trip Delay: 0.0100.0sCLI1 I< Alarm (420 mA input only):

    Disabled/EnabledCLI1 I< Alm Set (420 mA input only):

    0.04.0mA

    CLI2/3/4 as CLI1

    Current Loop OutputCLO1 Output 1: Disabled/EnabledCLO1 Output Type:

  • 7/29/2019 P341_EN_TDS_B11

    28/32

    P341 Technical Data Sheet 27 P341 Software Version 0320J

    0 - 1mA0 - 10mA0 - 20mA4 - 20mA

    CLO1 Set Values: Primary/SecondaryCLO1 Parameter: As shown below*

    CLO1 Min: Range, step size and unitcorresponds to the selected parameter

    CLO1 Max: Same as CLO1 MinCLO2/3/4 as CLO1Current Loop Output ParametersCurrent Magnitude:

    IA MagnitudeIB MagnitudeIC MagnitudeIN Derived Mag: 0.0016.0

    I Sen Mag: 0.00 2.0APhase Sequence Components:

    I1 Magnitude

    I2 MagnitudeI0 Magnitude:0.0016.0A

    Phase Currents:IA RMS*IB RMS*IC RMS*0.0016.0A

    P-P Voltage Magnitude:VAB MagnitudeVBC MagnitudeVCA Magnitude0.0200.0V

    P-N Voltage Magnitude:VAN MagnitudeVBN MagnitudeVCN Magnitude0.0200.0V

    Neutral Voltage Magnitude:VN1 Measured MagVN Derived Mag0.0200.0V

    Phase Sequence Voltage Components:V1 Magnitude*V2 MagnitudeV0 Magnitude0.0200.0V

    RMS Phase Voltages:VAN RMS*VBN RMS*VCN RMS*0.0200.0V

    Frequency: 0.0070.0Hz3 Phase Watts*: -6000W6000W3 Phase Vars*: -6000Var6000Var3 Phase VA*: 06000VA3Ph Power Factor*: -11Single Phase Active Power:

    A Phase Watts*:B Phase Watts*:C Phase Watts*:-2000W2000W

    Single Phase Reactive Power:A Phase Vars*:

    B Phase Vars*:C Phase Vars*-2000Var2000Var

    Single Phase Apparent Power:A Phase VA*:B Phase VA*:

    C Phase VA*02000VA

    Single Phase Power Factor:Aph Power Factor*BPh Power Factor*CPh Power Factor*-11

    3 Phase Current Demands:IA Fixed/Roll/Peak Demand*IB Fixed/Roll/Peak Demand*IC Fixed/Roll/Peak Demand*0.0016.0A

    3ph Active Power Demands:

    3Ph W Fix/Roll/Peak Demand*-6000W6000W

    3ph Reactive Power Demands:3Ph Vars Fix/Roll/Peak Dem*-6000Var6000Var

    Thermal Overload: 0.00200.0%CL Input 1-4: -99999999.0

    Note 1: Measurements marked with anasterisk, the internal refresh rate isnominally 1s, others are 0.5 powersystem cycles or less.

    Note 2: The polarity of Watts, Var and powerfactor is affected by the measurementsMode setting.

    Note 3: These settings are for nominal 1A and100/120V versions only. For otherversions they need to be multipliedaccordingly.

  • 7/29/2019 P341_EN_TDS_B11

    29/32

    P341 Technical Data Sheet 28 P341 Software Version 0320J

    CASE DIMENSIONS

    A = Clearance holes

    B = Mounting holes

    A

    BA

    BA

    DIAG No.

    SER No.

    In

    Vx

    Vn

    A 50/60 HzV

    VV

    SK1 SK2

    E202519

    US LISTEDC

    IBD2IND. CONT. EQ.

    UL

    SK3

    TRIP

    ALARM

    HEALTHY

    OUT OFSERVICE

    = CLEAR

    = READ

    = ENTER

    C

    P1647ENb

    Flush mounting panelPanel cut-out detail

    Note: If mounting plate is required

    use flush mounting cut out

    dimensions

    23.30 8 off holes Dia. 3.4155.40

    159.00

    168.

    00

    B

    Front view240.00

    Incl. wiring

    157.5max.

    Side view30.00

    All dimensions in mm

    177.0(4U)

    483 (19 rack)

    Sealingstrip

    202.00181.3010.35

    A B

    177.00

    206.00

    200.00

    Secondary cover (when fitted)

    P341 case dimensions (40TE case)

  • 7/29/2019 P341_EN_TDS_B11

    30/32

    P341 Technical Data Sheet 29 P341 Software Version 0320J

    CONNECTION DIAGRAMS

    (For a full set of Connection Diagrams for all Hardware configurations, see technical manualP341/EN/CO

    Interconnection Protection Relay (40TE) for Embedded Generation (8 I/P & 70 IP + CLIO)

  • 7/29/2019 P341_EN_TDS_B11

    31/32

    P341 Technical Data Sheet 30 P341 Software Version 0320J

    ORDERING INFORMATION

    MiCOM P341 INTERCONNECTION RELAY NOMENCLATURE

    A N N N A X X X A X X N N X A

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

    Character Type (A=Alpha, N=Numeric,

    X=Alpha-numeric)

    Character Numbering (Maximum = 15)P 3 4 1 * * * * * A 0 * * 0 *

    Vx Aux Rating24-48 Vdc48-110 Vdc, 30-100 Vac110-250 Vdc, 100-240 Vac

    123

    In/Vn RatingIn=1A/5A, Vn=100/120VIn=1A/5A, Vn=380/480V

    12

    Hardware OptionsNothingIRIG-B onlyFibre Optic Converter Only

    IRIG-B & Fibre Optic Converter2

    ndrear Comms. Port*

    2nd

    rear Comms. + IRIG-B*

    123

    478

    Product SpecificSize 40TE Case, No Option (8 Optos + 7 Relays)Size 40TE Case, 8 Optos + 7 Relays + CLIO*Size 40TE Case, 16 Optos + 7 Relays*Size 40TE Case, 8 Optos + 15 Relays*Size 40TE Case, 12 Optos + 11 Relays*

    ABCDE

    Protocol OptionsK-BusModbusIEC60870-5-103DNP3.0

    1234

    Mounting

    Panel Mounting M

    Software **

    Setting FilesDefaultCustomer

    01

    Design SuffixOriginalPhase 2 HardwareOriginal Hardware

    ACJ

    Note Design Suffix

    A = Original hardware (48V opto inputs only, lower contact rating, no I/O expansion available)C = Universal optos, new relays, new power supplyJ = Phase 2 CPU and front panel with 2 hotkeys and dual characteristic optos

    * Not available in design suffix A

    Note Mounting

    For rack mounting in 40TE case, assembled single frames and blanking plates are available

  • 7/29/2019 P341_EN_TDS_B11

    32/32

    AREVA T&D Worldwide Contact Centre:

    http://www.areva-td.com/contactcentre/Tel.: +44 (0) 1785 250 070

    Our policy is one of continuous development. Accordingly

    the design of our products may change at any time. Whilst

    every effort is made to produce up to date literature, this

    brochure should only be regarded as a guide and is

    intended for information purposes only. Its contents do notconstitute an offer for sale or advise on the application of

    any product referred to in it. We cannot be held responsible

    for any reliance on any decisions taken on its contents

    A

    UTOMATION-L3-P341-TDS-GB

    -

    -AREVA-2004AREVA,theAREVAlogoandanyalternativeversionthereofaretrademarksandservicemarksofAREVA.

    M

    iCOMisaregisteredtrademarkofAREVA.Alltradenamesortrademarksmentionedhereinwhetherregisteredornot,arethepropertyoftheirowners-389191982RCSPARIS.

    ADDITIONAL INFORMATION RESOURCEFurther information on the MiCOM series of relays may beobtained from www.areva-td.com