Upload
adip-chy
View
217
Download
0
Embed Size (px)
Citation preview
7/29/2019 P341_EN_TDS_B11
1/32
MiCOM P341
Generator Protection RelaySoftware Version 0320Hardw are Suffix J
Technical Data SheetP341/EN TDS/B11
This Document Should be Read Alongside the Technical Manual
7/29/2019 P341_EN_TDS_B11
2/32
The MiCOM Interconnection Protection Relays
offer the protection requirements necessary for
operating machines in parallel with the main
power supply network. They provide flexible and
reliable integration of protection, control,
monitoring and measurements. Extensive
functionality is available to satisfy complete
protection and control for a wide range of system
applications, including protection for both
connection and generator in simple applications
or the more sophisticated interconnection
protection necessary for larger units or those
connected at higher voltages.
The variable number of opto inputs and output
contacts available allow complex protection
schemes to be created using the relay's powerful
but easy to use logic.
A customer choice of industry standard protocols
are available on the relay, facilitating an easier
integration into both new and existing network
control systems.
Customer Benefits
Extensive protectionfunctionality to meet therequirements for mostinterconnectionprotection applications
Cost-effective solutionsto match applicationrequirements
Flexiblecommunicationsoptions with a numberof protocols andcommunications portsavailable
AREVA T&D
MiCOM P341, P922GInterconnection ProtectionRelays
PROTECTION
MiCOM P922G
Interconnection
protection relay
MiCOM P341
Interconnection
protection relay
7/29/2019 P341_EN_TDS_B11
3/32
APPLICATION
With embedded generators running in parallel with the
normal public supply there is a risk that, due to fault
clearances on the external system, the embedded
generator may become disconnected from the main
supply network. The machine may continue to supply
external load and there is a significant risk of
unsynchronised reconnection due to auto-reclosure of
the remote circuit breaker. A range of protection
functions are provided to detect this condition.
Loss of mains techniques are provided as well as the
more traditional functions encompassing voltage,
frequency and power elements.
The P341 provides overcurrent and ground fault, under
and overvoltage, under and overfrequency, thermal
overload, negative phase sequence overcurrent and
overvoltage and power protection for the generator.
In addition, rate of change of frequency and voltage
vector shift protections are provided for loss of mains.
The P922G provides , under and overvoltage, residual
voltage and under and overfrequency protection.The P922G meets the specifications of EDF GTE 2666
and is only available in the French language with
MODBUS communications.
GLOBAL FUNCTIONS
The following global functions are generally available in
both devices :
> Under/over voltage protection
> Under/overfrequency protection
> Residual overvoltage protection
> Metering
> Event recording
> Disturbance recording
> Fault recording
> Breaker condition monitoring
MAIN PROTECTION FUNCTIONS
The main protection functions are autonomous and can
be individually enabled or disabled to suit a particular
application. Each protection function is available in 4
separate setting groups (P341) and 2 (P922G) which
can be individually enabled or disabled.
Three phase tripping with faulted phase indication is
provided for all protection functions.
2
FUNCTIONS OVERVIEW P341 P922G
81R Rate of change of frequency 1 -
V Voltage vector shift 1 -
50/51/67 Directional / non directional, instantaneous / time delayed 4 -
phase overcurrent50N/51N/67N Directional / non directional, instantaneous / time delayed 4 -
phase ground fault
67N/67W Sensitive directional ground fault / wattmetric ground fault 4 -
64 Restricted earth fault 1 -
59N Neutral voltage displacement/residual overvoltage 2 3
27/59 Under/Over voltage 2/2 2/2
81U/81O Under/Over frequency 4/2 6
32R/32L/32O Reverse/Low Forward/Over power 2 -
49 Stator thermal overload 2 -
46 Directional / non directional, negative phase sequence overcurrent 4
47 Negative phase sequence overvoltage 1 -50BF CB Fail 2 -
Current transformer supervision 1 -
Voltage transformer supervision 1 -
Number of setting groups 4 2
CLIO (4 analogue inputs+4 analogue outputs) Option -
IRIG-B Option -
Front communications port (EIA(RS) 232 9-pin) Rear communications port (EIA (RS) 485 / K-Bus) (COMM1) Rear communications fibre optic port (COMM1) Option -
2nd rear communications port (COMM2) Option -
Opto Inputs 8-16 5
Output Contacts 7-15 8
7/29/2019 P341_EN_TDS_B11
4/32
.
Remote
Communication
BinaryInput / Output
Local
Communication
(RS232)
to SCADA / subst ation control / RTU / modem ...
via RS485 using Modbus
Metering
V
81O81U
2759 59N
Disturbance
Recording
Fault Records
LOGIC LEDS
Interconnection Protection P922G
COMM1
FUNCTIONAL OVERVIEW
MiCOM P341 :
Comprehensive protection for all yourinterconnection protection requirements
(Description of ANSI code nos. see Functions Overview)
.
Remote
Communication
Binary
Input / Output
Local
Communication
(RS232)to SCADA / substation control / RTU / modem ...via RS485 or Fiber optic using IEC60870-5-103,
Modbus, DNP3.0, Courier on COMM1.COMM2 is RS485 / RS232 Courier only
Metering
I
V
I SENSITIVE
CTS6767N
67N
67W
32R / 32L
32O46
81R 47V81O81U2759
64
50
5149
VTS 59N
50BF
DisturbanceRecording
Fault Records
CLIO
PSL LEDS
Interconnection
Protection P341Optional
Alwaysavailable
COMM1 COMM2
7/29/2019 P341_EN_TDS_B11
5/32
4
The IDMT stages have a programmable reset timer for
grading with electromechanical relays, to reduce
autoreclose dead times and to reduce clearance times
where intermittent faults occur.
The phase fault directional elements are internally
polarised by quadrature phase-phase voltages, and
will make a correct directional decision down to 0.5V
(Vn = 110/120V) or 2.0V (Vn = 380/440V). A
synchronous polarising signal is maintained for 3.2s
after voltage collapse to ensure that the instantaneous
and time delayed overcurrent elements operate
correctly for close-up three phase faults.
> Standard ground fault (P341)
The standard ground fault element operates from a
residual current that is derived internally from the
summation of the three phase currents.
The directionality of the ground fault elements is
provided by either residual voltage or negative
sequence voltage.Voltage transformer supervision
(VTS) can be used to block the directional element or
to revert it to non-directional.
> Sensitive ground fault (P341)
A core balance CT should be used to drive the
sensitive ground fault function. The directionality of the
sensitive ground fault elements is provided by the
residual voltage.
> Wattmetric (P341)
The sensitive ground fault protection is also suitable for
Petersen Coil grounded systems by enabling a
wattmetric element.This form of protection uses the
sensitive ground fault protection directional
characteristic, but with a directional residual power
threshold providing an additional constraint on
operation.
> Restricted ground fault (P341)
The sensitive ground fault element may be configured
as a high impedance differential restricted ground fault
element. When high impedance resticted ground fault
protection is used an additional stabilising resistance
and a metrosil will be required.
> Loss of mains (P341)
In order to protect against unsynchronised
reconnection due to autoreclosure of a remote circuit
breaker onto a system which has become
disconnected from the mains, specific protection is
required. Loss of the grid connection can be protected
against using voltage, frequency and power protection,
but, when the machine rating closely matches the
connected load this condition may be difficult to detect.Two methods of detection are therefore offered, rate of
change of frequency and voltage vector shift.
> Rate of change of frequency (P341)
This element detects the fluctuation in frequency that
will occur as the machine adjusts to the new load
conditions following loss of the grid. It is inherently
damped allowing sensitive settings to be used.
To improve stability for external system events an
adjustable definite time delay can be used.
> Voltage vector shift (P341)
This protection measures the instantaneous change in
the three phase voltage angle that occurs when the
connection to the main supply network is lost. To
provide stability this element must be less sensitive
than the rate of change of frequency element.
However, it operates without any intentional time delay,
providing fast tripping.
> Phase overcurrent (P341)
Four independent stages are available for each phase
overcurrent, ground fault and sensitive ground fault
element.Each stage may be selected as non-directional or
directional (forward/reverse). All stages have definite
time (DT) delayed characteristics, two of the stages
may also be independently set to one of nine inverse
definite minimum time (IDMT) curves (IEC and IEEE).
MiCOM P341 :
dual loss of mains protection -df/dt and voltage vector shift
Figure 1Simple
function selection
by mouseclick
7/29/2019 P341_EN_TDS_B11
6/32
> Blocked overcurrent logic (P341)
Each stage of overcurrent, ground fault and sensitive
ground fault protection can be blocked by an optically
isolated input. This enables the overcurrent and ground
fault protection to be integrated into a blocked
overcurrent busbar protection scheme.
> Neutral displacement/residual overvoltage
(P341/P22G)
Three stages of residual overvoltage (or neutral voltage
displacement) protection are provided within the P922G
and two stages in the P341. Depending on the VT
configuration set on the relay, the protection will
operate from either an internally calculated value from
the 3 phase to neutral voltage measurements or a
directly measured value of residual voltage from a
broken delata VT or from the secondary winding of a
distribution transformer ground at the generator neutral.
The fist stage can be configured for either inverse time
or definite time operation, with all subsequent stages
definite time only.
This function provides protection against ground faults
irrespective of the system grounding connection used.
> Under/overvoltage (P341/P22G)
Under/overvoltage protection may be configured to
operate from either phase-phase or phase-neutral
voltage elements and from Any Phase variation
(OR mode) or Three Phase variation (AND mode).
Two independent stages with definite time elements are
available for under and overvoltage protection.
The first stage can also be configured to an inverse
characteristic.
> Under/overfrequency (P341/P922G)
The P341 provides two independent stages of
overfrequency and four of under frequency. The P922G
provides 6 stages of frequency protection, each stage
can be set for under or over frequency operation.
Each stage functions as a definite time element.
> Power protection (P341)
The selectable power element can be used to provide
loss of mains protection whether the normal power flow
is into or out of the utility system, tripping when import
power reverses, or export power exceeds normal limits.
In addition to the standard 3 phase power protection
(minimum setting 2% Pn) a sensitive single phase
power protection element can be used (minimum
setting 0.5% Pn) which uses the sensitive ground fault
current input.
> Thermal overload (P341)
To monitor the thermal state of a generator or a feeder,
a thermal replica protection is provided. The thermal
element has a trip and an alarm stage. Positive and
negative sequence currents are taken into account so
that any unbalance condition can be detected and any
abnormal heating of the rotor can be avoided. There
are separate time constants for heating and cooling
and in the event of loss of auxiliary supply the thermal
state is stored in non volatile memory.
> Negative phase sequence overcurrent (P341)
Four definite time negative phase sequence overcurrent
stages are available within the P341.
Each stage may be selected as non-directional or
directional (forward/reverse) and can operate for
remote phase-phase and phase-ground faults even with
delta-star transformers present.
> Negative phase sequence overvoltage (P341)
One definite time stage of negative phase sequence
overvoltage protection is provided within the P341.
Negative phase sequence overvoltage protection can
be used for the detection of voltage unbalance which
will quickly lead to overheating and damage of
generators.
> Analog (Current Loop) Inputs and Outputs
(CLIO) (P341)
Four analog (or current loop) inputs are provided for
transducers with ranges of 0-1mA, 0-10mA, 0-20mA or
4-20mA. The analog inputs can be used for various
transducers such as vibration monitors, tachometers
and pressure transducers. Associated with each input
there are two time delayed protection stages, one for
alarm and one for trip. Each stage can be set for 'Over'or 'Under' operation.
Four analog (or current loop) outputs are provided with
ranges of 0-1mA, 0-10mA, 0-20mA or 4-20mA which
can alleviate the need for separate transducers.These
may be used to feed standard moving coil ammeters
for analog indication of certain measured quantities or
into a SCADA using an existing analog RTU.
7/29/2019 P341_EN_TDS_B11
7/32
6
SUPERVISORY FUNCTIONS
> Circuit breaker failure protection (P341)
Two stage circuit breaker failure protection may be
used for tripping upstream circuit breakers and/or the
local secondary trip coil.The circuit breaker failure
logic may also be initiated externally from other
protection devices if required.
> Voltage transformer supervision (P341)
Voltage transformer supervision (VTS) is provided to
detect loss of one, two or three VT signals, providing
indication and inhibition of voltage dependent
protection elements. An optically isolated input may
also be configured to initiate the voltage transformer
supervision alarm and blocking when used with
miniature circuit breakers (MCBs) or other external
forms of voltage transformer supervision.
> Current transformer supervision (P341)
Current transformer supervision (CTS) is provided todetect loss of phase CT signals and inhibit the
operation of current dependent protection elements.
PLANT SUPERVISION
> Trip circuit monitoring (P341)
Monitoring of the trip circuit in both breaker open and
closed states can be realised using the programmable
scheme logic.
> Circuit breaker state monitoring
In the P341 an alarm will be generated if there is a
discrepancy between the open and closed contacts of
the circuit breaker.
> Circuit breaker condition monitoring
The circuit breaker condition monitoring features
include:
monitoring the number of breaker trip operations
recording the sum of the broken current quantity
Ix, 1.0 x 2.0 (P341 only)
monitoring the breaker operating time
monitoring the fault frequency counter
(P341 only)
CONTROL
> Circuit breaker control (P341)
Circuit breaker control is available from the front panel
user interface, optically isolated inputs and remotely via
the substation communications.
> Programmable scheme logic
The P922G uses simple logic to program the digital
inputs, output contacts and LED's.
Programmable scheme logic in the P341 allows the
user to customise the protection and control functions.
It is also used to programme the functionality of the
digital inputs, output contacts and LED indications. The
programmable scheme logic comprises gate logic and
general purpose timers.The gate logic includes OR,
AND and majority gate functions, with the ability to
invert the inputs and outputs, and provide feedback.
The system is optimised to evaluate changes to the
scheme logic signals and thus minimise any delays in
logic execution. The programmable scheme logic may
be configured using the graphical MiCOM S1 PC basedsupport software, as illustrated in Figure 2.
The required logic is drawn as shown and is then
downloaded directly into the relay. The logic may also
be uploaded from the relay and then modified using
MiCOM S1 support software.
Comprehensive Post-fault analysisand communication options
Figure 2 PSL Editor (MiCOM S1)
7/29/2019 P341_EN_TDS_B11
8/32
> Control inputs (P341)
The ON/OFF status of 32 control inputs can be
changed manually or remotely via the communications
to provide user defined control functions within the
P341 PSL.
> Latched output contacts
Each P922G and P341 relay output contact can be
individually programmed to be latched. Once in the
latched state, the contact can be reset either locally or
remotely (P341/P922G), or via the PSL in the P341
relays.
In addition to the ability to latch output contacts, on the
P341 relays, each of the contacts can be individually
conditioned by a timer to give pulse, dwell, delay on
pick-up or delay on drop-off operation.
MEASUREMENTS &POST FAULT ANALYSIS
The P341 and P922G are capable of measuring andstoring a number of quantities. All events, faults and
disturbance records are time tagged to a resolution of
1ms using an internal real time clock. On the P341
relays a pulsed opto input or an optional IRIG-B port is
also available to maintain the accuracy of the real time
clock. A supervised and easily accessed lithium
battery ensures that the real time clock and records
are maintained during auxiliary supply interruptions.
> Power System Measurements
The measurements provided will depend upon the
application and model of the relay. Where appropriate
the measurements may be viewed in primary or
secondary terms and can be viewed locally or
remotely.
Measurements include:
Phase / line voltages
Sequence voltages
Phase angles
System frequency
Phase / line currents (P341)
Sequence currents (P341)
W/Var/VA (P341)
> Event Recording
The P922G can store up to 75 event records for
viewing via the local and remote communication
ports using MiCOM S1. The P341 relay can store up to
512 event records for viewing locally on the LCD, or
extraction via the communication ports.
> Fault Recording
The relays store the last 5 faults records, typically
containing:
Date and time
Protection operation
Active setting group
Fault voltages, frequency, etc..
> Disturbance Recording
The relays have an internal waveform capture facility
with a user programmable trigger point. The P922G
can record five disturbances, each with a duration of
2.5 seconds at a sampling rate of 32 samples per
cycle.The P341 can record 10 disturbances, each witha duration of 7.5 seconds (75s maximum) at a
sampling rate of 24 samples per cycle. All disturbance
records capture both analog and digital information
and when extracted via the communication ports, are
stored in Comtrade format.
These records can be examined using MiCOM S1 or
any other suitable software programme.
7/29/2019 P341_EN_TDS_B11
9/32
AUTOMATION-L3-P341/922G-BR-03.05-0845b-GB
-
-AREVA-
2006
.AREVA
,the
AREVAlogoan
danya
lterna
tive
vers
ion
thereo
fare
tra
demarksan
dserv
icemarkso
fAREVA
.
MiCOM
isareg
istere
dtra
demarko
fAREVA
.Alltrad
enamesor
tra
demarksmen
tione
dhere
inw
he
therreg
istere
dorno
t,are
thepropertyo
fthe
irowners.
-389191982RCSPARIS-
ONLY-
SONOVISION-I
TEP
AREVA T&D Worldwide Contact Centre:
http://www.areva-td.com/contactcentre/
Tel.: +44 (0) 1785 250 070
www.areva-td.com
www.areva-td.com/protectionrelays
AREVA TRACK RECORD -
INTERCONNECTION PROTECTION
>> KVFG/MX3VI: First numerical relays combining voltage and
frequency protection features.
Over 3500 devices installed since 1996.
>> MiCOM P92x: Combined numerical voltage and frequency relay.
Over 4000 devices installed since 2000
>> MiCOM P94x: Designed for all frequency based load applications.
Over 600 units installed since 1999.
>> MiCOM P342/3: Designed for all generator protection applications.
Over 2,000 units installed since 1999.
>> MiCOM P341: Designed for all Interconnection protection
applications. Over 600 units installed since 1999.
Our policy is one of continuous development. Accordingly thedesign of our products may change at any time. Whilst everyeffort is made to produce up to date literature, this brochureshould only be regarded as a guide and is intended forinformation purposes only. Its contents do not constitute an offerfor sale or advise on the application of any product referred to init. We cannot be held responsible for any reliance on anydecisions taken on its contents without specific advice.
INFORMATION INTERFACES
Information exchange is done via the local control
panel, the front PC interface, the main rear
communications interface (COMM1) or an optional
second rear interface (COMM2 - P341).
> Local communication
The front EIA(RS)232 communication port has been
designed for use with the MiCOM S1 software and is
primarily for configuring the relay settings and
programmable scheme logic. It is also used to locally
extract event, fault and disturbance record information
and can be used as a commissioning tool by viewing
all relay measurements simultaneously.
> Rear communication
The P341 main rear communications interface
supports the four protocols listed below (selected at
time of order) and is intended for integration with
substation control systems.
Courier/K-Bus
Modbus
IEC 60870-5-103*
DNP 3.0
The P922G only supports the MODBUS protocol.
An optional fiber optic interface is available for any of
the above protocols with the P341.
An optional 2nd rear communications port with the
Courier protocol is available with the P341. This port is
intended for central settings or remote access with
MiCOM S1.
Clock synchronization can be achieved using one of
the protocols or using the IRIG-B input (P341) or using
an opto input (P341).
> Password protection
To prevent unauthorised setting changes, all relays
have password facilities. On the P922G one level of
password control is available, whereas the P341
provides two password levels.
EMC COMPLIANCE
89/336/EEC
PRODUCT SAFETY
73/23/EEC
P34X THIRD PARTY COMPLIANCES
File Number : E202519
Original Issue Date :05-10-2002
(Complies with Canadian and
US requirements)
Certificate Number : 104 Issue 2
Assessment Date : 16-04-2004
C USULfi
Compliance with the
European Commission
Directive on EMC
Compliance with the
European Commission
Low voltage directive
7/29/2019 P341_EN_TDS_B11
10/32
P341 Technical Data Sheet 9 P341 Software Version 0320J
Technical Data
Mechanical SpecificationsDesignModular MiCOM Px40 platform relay, P341 in40TE case. Mounting is front of panel flushmounting, or 19 rack mounted (orderingoptions).
Enclosure ProtectionPer IEC 60529: 1989:IP 52 Protection (front panel) against dust anddripping water,IP 50 Protection for sides of the case,IP 10 Protection for the rear.
WeightP341(40TE):7kg
Terminals
AC Current and Voltage Measuring InputsLocated on heavy duty (black) terminal block:Threaded M4 terminals, for ring lugconnection.CT inputs have integral safety shorting, uponremoval of the terminal block.
General Input/Output TerminalsFor power supply, opto inputs, output contactsand RP1 rear communications.Located on general purpose (grey) blocks:Threaded M4 terminals, for ring lugconnection.
Case Protective Earth ConnectionTwo rear stud connections, threaded M4.Must be earthed (grounded) for safety,minimum earth wire size 2.5mm
2.
Front Port Serial PC Interface
EIA(RS)232 DTE, 9 pin D-type femaleconnector Socket SK1.Courier protocol for interface to MiCOM S1software.Isolation to ELV (extra low voltage) level.Maximum cable length 15m.
Front Download/Monitor PortEIA(RS)232, 25 pin D-type female connectorSocket SK2.For firmware and menu text downloads.Isolation to ELV level.
Rear Communications Port (RP1)EIA(RS)485 signal levels, two wireconnections located on general purpose block,M4 screw.
For screened twisted pair cable, multidrop,1000m max.For K-Bus, IEC-60870-5-103, MODBUS orDNP3.0 protocol (ordering options).Isolation to SELV (safety extra low low voltage)level .
Optional Rear Fiber Connection forSCADA/DCSBFOC 2.5 -(ST)-interface for glass fiber, asper IEC 874-10.850nm short-haul fibers, one Tx and one Rx.For Courier, IEC-60870-5-103, MODBUS orDNP3.0 (Ordering options).
Optional Second Rear CommunicationsPort (RP2)EIA(RS)232, 9 pin D-type female connector,
socket SK4.Courier protocol: K-Bus, EIA(RS)232, orEIA(RS)485 connection.Isolation to SELV level.
Optional Rear IRIG-B InterfaceBNC plugIsolation to SELV level.50 ohm coaxial cable.
Ratings
AC Measuring InputsNominal frequency: 50 and 60 Hz (settable)Operating range: 40 to 70 Hz
AC CurrentNominal current (In): 1 and 5 A dual rated.(1A and 5A inputs use different transformer tapconnections, check correct terminals arewired).Nominal burden
< 0.04 VA at In,
7/29/2019 P341_EN_TDS_B11
11/32
P341 Technical Data Sheet 10 P341 Software Version 0320J
Power supply
Auxiliary Voltage (Vx)Three ordering options:(i) Vx: 24 to 48 Vdc
(ii) Vx: 48 to 110 Vdc, and 30 to 100Vac (rms)(iii) Vx: 110 to 250 Vdc, and 100 to240Vac (rms)
Operating Range(i) 19 to 65V (dc only for this variant)(ii) 37 to 150V (dc), 24 to 110V (ac)(iii) 87 to 300V (dc), 80 to 265V (ac).With a tolerable ac ripple of up to 12% for a dcsupply, per IEC 60255-11: 1979.
Nominal Burden
Quiescent burden: 11W or 24 VA. (Extra1.25W when fitted with second rearcommunications board).Additions for energized binary inputs/outputs:Per opto input:
0.09W (24 to 54V),0.12W (110/125V),0.19W (220/250V).
Per energized output relay: 0.13W
Power-up TimeTime to power up < 11s.
Power Supply InterruptionPer IEC 60255-11: 1979:
The relay will withstand a 20ms interruptionin the DC auxiliary supply, withoutde-energizing.
Per IEC 61000-4-11: 1994:The relay will withstand a 20ms interruptionin an AC auxiliary supply, withoutde-energizing.
Battery BackupFront panel mounted
Type AA, 3.6V Lithium Thionyl ChlorideBattery
Field Voltage OutputRegulated 48VdcCurrent limited at 112mA maximum outputOperating range 40 to 60V
Digital (Opto) InputsUniversal opto inputs with programmablevoltage thresholds (24/27, 30/34, 48/54,110/125, 220/220V). May be energized from
the 48V field voltage, or the external batterysupply.Rated nominal voltage: 24 to 250VdcOperating range: 19 to 265VdcWithstand: 300Vdc, 300Vrms.Nominal pick-up and reset thresholds:
Nominal battery 24/27: 60 - 80% DO/PU(logic 0) 19.2
Nominal battery 24/27: 50 - 70% DO/PU(logic 0) 16.8
Nominal battery 30/34: 60 - 80% DO/PU(logic 0) 24.0
Nominal battery 30/34: 50 - 70% DO/PU(logic 0) 21.0
Nominal battery 48/54: 60 - 80% DO/PU(logic 0) 38.4
Nominal battery 48/54: 50 - 70% DO/PU(logic 0) 33.6
Nominal battery 110/125: 60 - 80% DO/PU(logic 0) 88.0
Nominal battery 110/125: 50 - 70% DO/PU(logic 0) 77.0
Nominal battery 220/250: 60 - 80% DO/PU(logic 0) 176.0
Nominal battery 220/250: 50 - 70% DO/PU
(logic 0) 154Recognition time:
7/29/2019 P341_EN_TDS_B11
12/32
P341 Technical Data Sheet 11 P341 Software Version 0320J
Environmental Conditions
Ambient Temperature RangePer IEC 60255-6: 1988:Operating temperature range:
-25C to +55C (or -13F to +131F)Storage and transit:-25C to +70C (or -13F to +158F)
Ambient Humidity RangePer IEC 60068-2-3: 1969:
56 days at 93% relative humidity and +40 CPer IEC 60068-2-30: 1980
Damp heat cyclic, six (12 + 12) hour cycles,93% RH, +25 to +55 C
Type Tests
InsulationPer IEC 60255-5: 2000:
Insulation resistance > 100M at 500Vdc(Using only electronic/brushless insulationtester).
Creepage Distances and ClearancesPer EN 61010-1: 2001Pollution degree 3,Overvoltage category III,Impulse test voltage 5 kV.
High Voltage (Dielectric) Withstand(i) Per IEC 60255-5: 2000, 2 kV rms
AC, 1 minute:Between all independent circuits.Between independent circuits and protective(earth) conductor terminal.
1kV rms AC for 1 minute, across openwatchdog contacts.1kV rms AC for 1 minute, across opencontacts of changeover output relays.1kV rms AC for 1 minute for all D-typeEIA(RS)232/EIA(RS)485 ports between
the communications port terminals andprotective (earth) conductor terminal
(ii) Per ANSI/IEEE C37.90-1989 (reaffirmed1994):1.5 kV rms AC for 1 minute, across opencontacts of normally open output relays.1kV rms AC for 1 minute, across openwatchdog contacts.1kV rms AC for 1 minute, across opencontacts of changeover output relays.
Impulse Voltage Withstand Test
Per IEC 60255-5: 2000:Front time: 1.2 s, Time to half-value: 50 s,Peak value: 5 kV, 0.5JBetween all independent circuits.Between all independent circuits andprotective (earth) conductor terminal.
Between the terminals of independent circuits.EIA(RS)232 & EIA(RS)485 ports and normallyopen contacts of output relays excepted.
Electromagnetic Compatibility
(EMC)
1 MHz Burst High Frequency DisturbanceTestPer IEC 60255-22-1: 1988, Class III,Common-mode test voltage: 2.5 kV,Differential test voltage: 1.0 kV,
Test duration: 2 s, Source impedance: 200 (EIA(RS)232 ports excepted).
Immunity to Electrostatic DischargePer IEC 60255-22-2: 1996, Class 4,
15kV discharge in air to user interface,display, and exposed metalwork.
Per IEC 60255-22-2: 1996, Class 3,8kV discharge in air to all communicationports.
6kV point contact discharge to any part of thefront of the product.
Electrical Fast Transient or BurstRequirementsPer IEC 60255-22-4: 2002. Test severityClass III and IV:Amplitude: 2 kV, burst frequency 5kHz
(Class III),Amplitude: 4 kV, burst frequency 2.5kHz(Class IV).Applied directly to auxiliary supply, andapplied to all other inputs. (EIA(RS)232 portsexcepted).
Surge Withstand CapabilityPer IEEE/ANSI C37.90.1: 2002:4kV fast transient and 2.5kV oscillatory applieddirectly across each output contact, opticallyisolated input, and power supply circuit.
Surge Immunity Test(EIA(RS)232 ports excepted).Per IEC 61000-4-5: 2002 Level 4,Time to half-value: 1.2/50 s,Amplitude: 4kV between all groups andprotective (earth) conductor terminal.Amplitude: 2kV between terminals of eachgroup.
Immunity to Radiated ElectromagneticEnergy
Per IEC 60255-22-3: 2000, Class III:Test field strength, frequency band 80 to 1000MHz:
10 V/m,Test using AM: 1 kHz / 80%,Spot tests at 80, 160, 450, 900 MHz
7/29/2019 P341_EN_TDS_B11
13/32
P341 Technical Data Sheet 12 P341 Software Version 0320J
Per IEEE/ANSI C37.90.2: 2004:80MHz to 1000MHz, 1kHz 80% am and ampulsed modulated.Field strength of 35V/m.
Radiated Immunity from DigitalCommunicationsPer EN61000-4-3: 2002, Level 4:Test field strength, frequency band 800 to 960MHz, and 1.4 to 2.0 GHz:
30 V/m,Test using AM: 1 kHz/80%.
Radiated Immunity from Digital RadioTelephonesPer IEC61000-4-3: 2002:10 V/m, 900MHz and 1.89GHz.
Immunity to Conducted DisturbancesInduced by Radio Frequency FieldsPer IEC 61000-4-6: 1996, Level 3,Disturbing test voltage: 10 V.
Power Frequency Magnetic Field ImmunityPer IEC 61000-4-8: 1994, Level 5,
100A/m applied continuously,1000A/m applied for 3s.
Per IEC 61000-4-9: 1993, Level 5,1000A/m applied in all planes.
Per IEC 61000-4-10: 1993, Level 5,
100A/m applied in all planes at100kHz/1MHz with a burst duration of 2s.
Conducted EmissionsPer EN 55022: 1998:
0.15 - 0.5MHz, 79dBV (quasi peak) 66dBV(average)
0.5 - 30MHz, 73dBV (quasi peak) 60dBV(average).
Radiated EmissionsPer EN 55022: 1998:
30 - 230MHz, 40dBV/m at 10mmeasurement distance230 - 1GHz, 47dBV/m at 10m measurementdistance.
EU Directives
EMC CompliancePer 89/336/EEC:Compliance to the European CommissionDirective on EMC is claimed via the TechnicalConstruction File route. Product Specific
Standards were used to establish conformity:EN50263: 2000
Product SafetyPer 73/23/EEC:Compliance with European Commission LowVoltage Directive. Compliance isdemonstrated by reference to generic safetystandards:
IEC60255-27: 2005EN60255-5: 2001
73/23/EEC
R&TTE ComplianceRadio and Telecommunications TerminalEquipment (R & TTE) directive 95/5/EC.Compliance demonstrated by compliance tothe Low Voltage Directive, 73/23/EECamended by 93/68/EEC, down to zero volts byreference to safety standards.
Applicable to rear communications ports.
ATEX ComplianceATEX Potentially Explosive Atmospheresdirective 94/9/EC, for equipment.The equipment is compliant with Article 1(2) ofEuropean directive 94/9/EC.It is approved for operation outside an ATEXhazardous area. It is however approved forconnection to Increased Safety, Ex e, motorswith rated ATEX protection, EquipmentCategory 2, to ensure their safe operation in
gas Zones 1 and 2 hazardous areas.
CAUTION - Equipment with this marking is notitself suitable for operation within a potentiallyexplosive atmosphere.
Compliance demonstrated by Notified Bodycertificates of compliance.
II (2) G
Mechanical Robustness
Vibration TestPer IEC 60255-21-1: 1996:
Response Class 2Endurance Class 2
Shock and BumpPer IEC 60255-21-2: 1996:
Shock response Class 2
Shock withstand Class 1Bump Class 1
Seismic TestPer IEC 60255-21-3: 1995:
Class 2
7/29/2019 P341_EN_TDS_B11
14/32
P341 Technical Data Sheet 13 P341 Software Version 0320J
P34x THIRD PARTY COMPLIANCES(UL/CUL, ENA)
File Number: E202519Original Issue Date: 05-10-2002(Complies with Canadian and USrequirements).
Certificate Number: 104 Issue 2Assessment Date: 16-04-2004
7/29/2019 P341_EN_TDS_B11
15/32
P341 Technical Data Sheet 14 P341 Software Version 0320J
Protection Functions
Reverse/Low Forward/Over Power(3 Phase)
Accuracy
Pick-up: Setting 10%Reverse/Over Power Drop-off:
0.95 of setting 10%Low forward power Drop-off:
1.05 of setting 10%Angle variation Pick-up:
Expected pick-up angle 2 degreeAngle variation Drop-off:
Expected drop-off angle 2.5 degreeOperating time: 2% or 50ms whichever is
greater
Repeatability:
7/29/2019 P341_EN_TDS_B11
16/32
P341 Technical Data Sheet 15 P341 Software Version 0320J
Wattmetric SEF Accuracy
P = 0W Pick-up: ISEF> 5%P > 0W Pick-up: P> 5%P = 0W Drop-off: (0.95 x ISEF>) 5%P > 0W Drop-off: 0.9 x P> 5%Boundary accuracy: 5% with 1 hysteresisRepeatability: 5%
Zero Sequence Polarizing QuantitiesAccuracy
Operating boundary Pick-up: 2 of RCA 90Hysteresis:
7/29/2019 P341_EN_TDS_B11
17/32
P341 Technical Data Sheet 16 P341 Software Version 0320J
Instantaneous operation:
7/29/2019 P341_EN_TDS_B11
18/32
P341 Technical Data Sheet 17 P341 Software Version 0320J
Current Loop Input and Outputs
Accuracy
Current loop input accuracy: 1% of full scaleCLI drop-off threshold Under: setting 1% of
full scaleCLI drop-off threshold Over: setting 1% of full
scaleCLI sampling interval: 50msCLI instantaneous operating time: < 250ms
CLI DT operating time: 2% setting or 200mswhichever is the greater
CLO conversion interval: 50msCLO latency: < 1.07s or
7/29/2019 P341_EN_TDS_B11
19/32
P341 Technical Data Sheet 18 P341 Software Version 0320J
Settings, Measurements andRecords List
Settings List
Global Settings (System Data)Language: English/French/German/SpanishFrequency: 50/60Hz
Circuit Breaker Control(CB Control):
CB Control by:DisabledLocalRemote
Local+RemoteOptoOpto+localOpto+RemoteOpto+Rem+localClose Pulse Time: 0.10...10.00sTrip Pulse Time: 0.105.00sMan Close t max: 0.019999.00sMan Close Delay: 0.01600.00sCB Healthy Time: 0.019999.00sCheck Sync. Time: 0.01...9999.00sReset Lockout by: User Interface/CB CloseMan Close RstDly: 0.10...600.00s
CB Status Input:None52A52B52A & 52B
Date and TimeIRIG-B Sync: Disabled/EnabledBattery Alarm: Disabled/Enabled
ConfigurationSetting Group:
Select via MenuSelect via PSLActive Settings: Group 1/2/3/4Setting Group 1: Disabled/EnabledSetting Group 2: Disabled/EnabledSetting Group 3: Disabled/EnabledSetting Group 4: Disabled/EnabledSystem Config: Invisible/VisiblePower: Disabled/EnabledOvercurrent: Disabled/EnabledThermal Overload: Disabled/EnabledEarth Fault: Disabled/EnabledSEF/REF/Spower: Disabled or SEF/REF or
Sensitive Power
Residual O/V NVD: Disabled/Enableddf/dt: Disabled/EnabledV Vector Shift: Disabled/EnabledReconnect Delay: Disabled/EnabledVolt Protection: Disabled/EnabledFreq Protection: Disabled/Enabled
CB Fail: Disabled/EnabledSupervision: Disabled/EnabledInput Labels: Invisible/VisibleOutput Labels: Invisible/VisibleCT & VT Ratios: Invisible/VisibleEvent Recorder: Invisible/VisibleDisturb Recorder: Invisible/VisibleMeasuret Setup: Invisible/VisibleComms Settings: Invisible/VisibleCommission Tests: Invisible/VisibleSetting Values: Primary/SecondaryControl Inputs: Invisible/VisibleCLIO Inputs: Disabled/Enabled
CLIO Outputs: Disabled/EnabledCtrl I/P Config: Invisible/VisibleCtrl I/P Labels: Invisible/VisibleDirect Access: Disabled/EnabledLCD Contrast: 031
CT and VT RatiosMain VT Primary: 100...1000000VMain VT Sec'y: 80...140
(100/120V) 320560V (380/480V)VN VT Primary (P342/3): 1001000000VVN VT Secondary (P342/3): 80140V
(100/120V) 320560V (380/480V)Phase CT Primary: 1A30kAPhase CT Sec'y: 1A/5ASEF CT Primary: 1A30KASEF CT Secy: 1A/5A
Sequence of Event Recorder(Record Control)Alarm Event: Disabled/EnabledRelay O/P Event: Disabled/EnabledOpto Input Event: Disabled/EnabledGeneral Event: Disabled/Enabled
Fault Rec Event: Disabled/EnabledMaint Rec Event: Disabled/EnabledProtection Event: Disabled/EnabledDDB 31 - 0: (up to):DDB 1022 - 992:
Binary function link strings, selecting whichDDB signals will be stored as events, andwhich will be filtered out.
Oscillography(Disturbance Recorder)Duration: 0.1010.50s
Trigger Position: 0.0100.0%Trigger Mode: Single/ExtendedAnalog Channel 1: (up to):Analog Channel 15:
Disturbance channels selected from:IA/IB/IC/VA/VB/VC/VN/ISensitive
7/29/2019 P341_EN_TDS_B11
20/32
P341 Technical Data Sheet 19 P341 Software Version 0320J
Digital Input 1: (up to):Digital Input 32:Selected binary channel assignment from anyDDB status point within the relay (opto input,output contact, alarms, starts, trips, controls,logic).
Input 1 Trigger: No Trigger/Trigger/LH (Low toHigh)/Trigger H/L (High to Low)
(up to):Input 32 Trigger: No Trigger/TriggerL/H/Trigger H/L
Measured Operating Data(Measuret Setup)Default Display:
Access Level3Ph + N Current3Ph Voltage
PowerDate and TimeDescriptionPlant ReferenceFrequency
Local Values: Primary/SecondaryRemote Values: Primary/SecondaryMeasurement Ref: VA/VB/VC/IA/IB/ICMeasurement Mode: 0/1/2/3Fix Dem Period: 199minsRoll Sub Period: 199minsNum Sub Periods: 115Remote2 Values: Primary/Secondary
CommunicationsRP1 Address: (Courier or IEC870-5-103):
0255RP1 Address: (DNP3.0):
065534RP1 Address: (MODBUS):
1247RP1 InactivTimer: 130minsRP1 Baud Rate: (IEC870-5-103):
9600/19200 bits/sRP1 Baud Rate: (MODBUS, Courier):
9600/19200/38400 bits/sRP1 Baud Rate: (DNP3.0):1200/2400/4800/9600/19200/ 38400 bits/s
RP1 Parity: Odd/Even/None(MODBUS, DNP3.0)
RP1 Meas Period: 160s(IEC870-5-103)
RP1 PhysicalLink:Copper (EIA(RS)485/K bus) or Fiber Optic
RP1 Time Sync: Disabled/EnabledMODBUS IEC Timer: Standard/ReverseRP1 CS103Blocking:
Disabled
Monitor BlockingCommand Blocking
RP1 Port Config: (Courier):K BusEIA485 (RS485)
RP1 Comms Mode: (Courier):
IEC60870 FT1.2IEC60870 10-Bit No parity
Note: If RP1 Port Config is K Bus the baudrate is fixed at 64 kbits/s
Optional Additional Second RearCommunication(Rear Port2 (RP2))RP2 Port Config:
EIA(RS)232EIA(RS)485K-Bus
RP2 Comms Mode:IEC60870 FT1.2IEC60870 10-Bit No parity
RP2 Address: 0255RP2 InactivTimer: 130minsRP2 Baud Rate:
9600/19200/38400 bits/sNote: If RP2 Port Config is K Bus the baud
rate is fixed at 64 kbits/s
Commission TestsMonitor Bit 1:
(up to):Monitor Bit 8:
Binary function link strings, selecting whichDDB signals have their status visible in theCommissioning menu, for test purposes
Test Mode:
DisabledTest ModeBlocked Contacts
Test Pattern:Configuration of which output contacts are tobe energized when the contact test isapplied
Circuit Breaker ConditionMonitoring(CB Monitor Setup)Broken I^: 1.02.0
I^ Maintenance: Alarm Disabled/EnabledI^ Maintenance: 125000I^ Lockout: Alarm Disabled/EnabledI^ Lockout: 125000No. CB Ops Maint: Alarm Disabled/EnabledNo. CB Ops Maint: 110000No. CB Ops Lock: Alarm Disabled/EnabledNo. CB Ops Lock: 110000CB Time Maint: Alarm Disabled/EnabledCB Time Maint: 0.0050.500sCB Time Lockout: Alarm Disabled/EnabledCB Time Lockout: 0.0050.500sFault Freq Lock: Alarm Disabled/Enabled
Fault Freq Count: 19999Fault Freq Time: 09999s
7/29/2019 P341_EN_TDS_B11
21/32
P341 Technical Data Sheet 20 P341 Software Version 0320J
Opto Coupled Binary Inputs(Opto Config)Global Nominal V:
24 - 27V30 - 34V48 - 54V110 - 125V220 - 250V
CustomOpto Input 1:
(up to):Opto Input #. (# = max. opto no. fitted):
Custom options allow independentthresholds to be set per opto, from the samerange as above.
Opto Filter Control:Binary function link string, selecting whichoptos will have an extra 1/2 cycle noise filter,
and which will not.Characteristics:Standard 60% - 80%50% - 70%
Control Inputs into PSL(Ctrl. I/P Config.)Hotkey Enabled:
Binary function link string, selecting which ofthe control inputs will be driven fromHotkeys.
Control Input 1: Latched/Pulsed(up to):
Control Input 32: Latched/PulsedCtrl Command 1:
(up to):Ctrl Command 32:
ON/OFFSET/RESETIN/OUTENABLED/DISABLED
Control Input User Labels(Ctrl. I/P Labels)Control Input 1:
(up to):Control Input 32:
User defined text string to describe thefunction of the particular control input
Settings in Multiple GroupsNote: All settings here onwards apply for
setting groups # = 1 to 4.
7/29/2019 P341_EN_TDS_B11
22/32
P341 Technical Data Sheet 21 P341 Software Version 0320J
Protection Functions
System Config.Phase Sequence: Standard ABC/Reverse
ACB
VT Reversal: No Swap/A-B Swapped/B-CSwapped/C-A Swapped
CT1 Reversal: No Swap/A-B Swapped/B-CSwapped/C-A Swapped
Reverse/Low Forward/Over Power(3 Phase)Operating mode:
GeneratingMotoring
Power 1 Function:Reverse
Low forwardOver
-P>1 Setting (reverse power/P1Setting (Overpower):
4300.0W (1A, 100V/120V)161200.0W (1A, 380V/480V)201500.0W (5A, 100V/120V)806000.0W (5A, 380V/480V)
Equivalent Range in %Pn 0.5%157%Power 1 Time Delay: 0.00100.0sPower 1 DO Timer: 0.00100.0sP1 Poledead Inh: Disabled/Enabled
Power 2 as Power 1
Sensitive/Reverse/LowForward/Over Power (1 Phase)Operating mode:
GeneratingMotoring
Sen Power1 Func:ReverseLow forwardOver
Sen -P>1 Setting (Reverse Power)/Sen P Setting(Over Power):
0.3100.0W (1A, 100/120V)1.20400.0W (1A, 380/480V)1.50500.0W (5A, 100/120V)6.02000.0W (5A, 380/480V)
Equivalent range in %Pn 0.5%157%Sen Power 1 Delay: 0.00100.0sPower 1 DO Timer: 0.00100.0sP1 Poledead Inh: Disabled/Enabled
Comp angle C: -5+5.0Sen Power2 as Sen Power 1
Phase Overcurrent (Overcurrent)Phase O/C: Sub HeadingI>1 Function:
DisabledDTIEC S Inverse
IEC V InverseIEC E InverseUK LT InverseUK RectifierRIIEEE M InverseIEEE V InverseIEEE E InverseUS InverseUS ST Inverse
I>1 Direction:Non-DirectionalDirectional FwdDirectional Rev
I>1 Current Set: 0.084.00 InI>1 Time Delay: 0.00100.00sI>1 TMS: 0.0251.200I>1 Time Dial: 0.01100.00I>1 K (RI): 0.1010.00I>1 Reset Char: DT/InverseI>1 tRESET: 0.00100.00sI>2 as I>1I>3 Status: Disabled/EnabledI>3 Direction:
Non-DirectionalDirectional FwdDirectional Rev
I>3 Current Set: 0.0810.00 InI>3 Time Delay: 0.00100.00sI>4 as I>3I> Char Angle: -95+95
o
I >Function Link:Bit 0 = VTS Blocks I>1Bit 1 = VTS Blocks I>2Bit 2 = VTS Blocks I>3Bit 3 = VTS Blocks I>4Bit 4, 5, 6 & 7 are not usedBinary function link string, selecting which
overcurrent elements (stages 1 to 4) will beblocked if VTS detection of fuse failureoccurs.
Inverse time (IDMT) characteristic
IDMT characteristics are selectable from achoice of four IEC/UK and five IEEE/US curvesas shown in the table below.
The IEC/UK IDMT curves conform to thefollowing formula:
t = T x
K
(/s) - 1 + L
7/29/2019 P341_EN_TDS_B11
23/32
P341 Technical Data Sheet 22 P341 Software Version 0320J
The IEEE/US IDMT curves conform to thefollowing formula:
t = TD x
K
(/s)
- 1+ L
Where:
t = Operation timeK = Constant
= Measured currentS = Current threshold setting = ConstantL = ANSI/IEEE constant (zero for IEC/UK
curves)T = Time multiplier setting for IEC/UK curvesTD = Time dial setting for IEEE/US curves
IDMT characteristics
IDMT Curve Stand. K L
Standard inverse IEC 0.14 0.02 0
Very inverse IEC 13.5 1 0
Extremely inverse IEC 80 2 0
Long time inverse UK 120 1 0
Rectifier UK 45900 5.6 0
Moderately inverse IEEE 0.0515 0.02 0.114
Very inverse IEEE 19.61 2 0.491
Extremely inverse IEEE 28.2 2 0.1217
Inverse US-C08 5.95 2 0.18
Short time inverse US-C02 0.16758 0.02 0.11858
The IEC extremely inverse curve becomesdefinite time at currents greater than 20 xsetting. The IEC standard, very and long timeinverse curves become definite time atcurrents greater than 30 x setting.
For all IEC/UK curves, the reset characteristicis definite time only.
For all IEEE/US curves, the reset characteristiccan be selected as either inverse curve ordefinite time.
The inverse reset characteristics aredependent upon the selected IEEE/US IDMTcurve as shown in the table below.
All inverse reset curves conform to thefollowing formula:
tRESET =
TD x S
(1 - M2)in seconds
Where:
TD = Time dial setting for IEEE curvesS = Constant
M = /s
Curve Description Standard S
Moderately inverse IEEE 4.85
Very inverse IEEE 21.6
Extremely inverse IEEE 29.1
Inverse US 5.95
Short time inverse US 2.261
The RI curve (electromechanical) has beenincluded in the first stage characteristic settingoptions for Phase Overcurrent and Earth Faultprotections. The curve is represented by thefollowing equation:
t = K x
1
0.339 - ( )0.236/M in seconds
With K adjustable from 0.1 to 10 in steps of0.05
M = /s
Curve 4
Curve 1
Curve 2
Curve 3
1000
100
10
1
0.1
100.010.01.0
Current (Multiples of Is)
OperatingTime(s)
Curve 1 Standard inverse
Curve 2 Very inverse
Curve 3 Extremely inverse
Curve 4 UK long time inverse
IEC Curves
P2136ENa
7/29/2019 P341_EN_TDS_B11
24/32
P341 Technical Data Sheet 23 P341 Software Version 0320J
Curve 5 IEEE moderately inverse
Curve 6 IEEE very inverse
Curve 7 IEEE extremely inverse
Curve 8 US inverse
Curve 9 US short time inverse
Amercian Curves
Curve 5
100.010.01.0
Current (Multiples of Is)
0.1
1
10
100
OperatingTime(s)
Curve 6
Curve 9
Curve 7
Curve 8
P2137ENa
NPS Overcurrent2>1 Status: Disabled/Enabled2>1 Direction:
Non-DirectionalDirectional FwdDirectional Rev
2> Current Set: 0.084.00n2> Time Delay: 0.00100.00s2>2/3/4 as for2>12> VTS Block:
Bit 0 = VTS Blocks 2>1Bit 1 = VTS Blocks 2>2Bit 2 = VTS Blocks 2>3Bit 3 = VTS Blocks 2>4Bits 4, 5, 6 & 7 are not usedBinary function link string, selecting whichNPS overcurrent elements (stages 1 to 4)will be blocked if VTS detection of fusefailure occurs.
2> V2pol Set:0.525.0 (100V 120V)2100V (380/480V)
2> Char Angle: -95+95
Thermal OverloadThermal: Disabled/EnabledThermal I>: 0.502.50 InThermal Alarm: 20..100%T-heating: 1200 minutes
T-cooling: 1200 minutesM Factor: 010
The thermal time characteristic is given by:
t = loge (eq2 - P2)/(eq2 - (Thermal >)2)
t = . loge ((K2
-A
2
)/(K
2
-1))Where:
K = eq/Thermal >A = P/Thermal >t = Time to trip, following application of the
overload current, = Heating time constant of the protected
plant
eq = Equivalent currentThermal > = Relay setting currentP = Steady state pre-load current
before application of theoverload
eq = (12
+ M22)
1 = Positive sequence current2 = Negative sequence currentM = A user settable constant
proportional to the thermalcapacity of the machine
Earth Fault
IN1>1 Function:
DisabledDTIEC S InverseIEC V InverseIEC E InverseUK LT InverseRIIEEE M InverseIEEE V InverseIEEE E InverseUS InverseUS ST InverseIDG
IN1>1 DirectionalNon-DirectionalDirectional FwdDirectional Rev
IN1>1 Current Set: 0.084.00 InIN1>1 IDG Is: 1.04.0 InIN1>1 Time Delay: 0.00200.00sIN1>1 TMS: 0.0251.200IN1>1 Time Dial: 0.01100.00IN1>1 K(RI): 0.10.10.00IN1>1 IDG Time: 1.00...2.00IN1>1 Reset Char.: DT/InverseIN1>1 tRESET: 0.00100.00s
IN1>2 as IN>1IN1>3 Status:
DisabledEnabled
IN1>3 Directional:Non-Directional
7/29/2019 P341_EN_TDS_B11
25/32
P341 Technical Data Sheet 24 P341 Software Version 0320J
Directional FwdDirectional Rev
IN1>3 Current Set: 0.0832.00 InIN1>3 Time Delay: 0.00200.00sIN1>4 as IN>3IN1> Blocking:
Binary function link string, selecting whichground overcurrent elements (stages 1 to 4)will be blocked if VTS detection of fusefailure occurs.IN1> Char Angle: -95 +95
o
IN1> Polarization:Zero SequenceNeg. Sequence
IN1> VNpol Set:0.580.0V (100/110V)2320V (380/480V)
IN1> V2pol Set:0.525.0V (100/110V)
2100V (380/480V)IN1> I2pol Set: 0.081.00 In
The IDG curve is commonly used for timedelayed earth fault protection in the Swedishmarket. This curve is available in stage 1 ofthe Earth Fault protection.
The IDG curve is represented by the followingequation:
t = 5.8 - 1.35 loge
N > Setting in seconds
Where:
= Measured currentN>Setting = An adjustable setting which
defines the start point of thecharacteristic
Although the start point of the characteristic is
defined by the N> setting, the actual relaycurrent threshold is a different setting called
IDG s. The IDG s setting is set as amultiple of N>.
An additional setting IDG Time is also usedto set the minimum operating time at highlevels of fault current.
0
1
2
3
4
5
6
7
8
9
10
1 10 100
I/IN>
Operatingtime(seconds)
IDG Is Setting Range
IDG Time Setting Range
P2242ENa
IDG Characteristic
SEF/REF ProtnSEF/REF Options:
SEFSEF Cos (PHI)SEF Sin (PHI)Wattmetric
Hi Z REFISEF>1 Function:
DisabledDTIEC S InverseIEC V InverseIEC E InverseUK LT InverseRIIEEE M InverseIEEE V InverseIEEE E InverseUS InverseUS ST InverseIDG
ISEF>1 Directional:Non-DirectionalDirectional FwdDirectional Rev.
ISEF>1 Current Set: 0.005...0.10 InISEF>1 IDG Is: 1.0...4.0 InISEF>1 Time Delay: 0.00...200.00sISEF>1 TMS: 0.025...1.200ISEF>1 Time Dial: 0.01...100.0ISEF>1 IDG Time: 1.00...2.00ISEF>1 Reset Char: DT/InverseISEF>1 tRESET: 0.00...100.00sISEF>2 as ISEF>2ISEF>3 Status:
DisabledEnabled
ISEF>3 Directional:Non-DirectionalDirectional FwdDirectional Rev
ISEF>3 Current Set: 0.005...0.80 InISEF>3 Time Delay: 0.00...200.00sISEF>4 as ISEF>3
ISEF> Blocking:Binary function link string, selecting whichground overcurrent elements (stages 1 to 4)will be blocked if VTS detection of fusefailure occurs.ISEF> Char. Angle: -95...+95
o
ISEF> VNpol Set:0.5...80.0V (100/120V)2...320V (380/480V)WATTMETRIC SEF:
PN> Setting: 0....20In W (100/120V)PN> Setting: 0 ....80In W (380/480V)
Restricted Earth Fault (HighImpedance)IREF>Is: 0.05.1.00 In
7/29/2019 P341_EN_TDS_B11
26/32
P341 Technical Data Sheet 25 P341 Software Version 0320J
Residual O/V NVDVN>1 Status: Disabled/EnabledVN>1 Input: DerivedVN> 1 Function:
DisabledDT
IDMTVN> 1 Voltage Set:
180V (100/120V)4320V (380/480V)
VN> 1 Time Delay: 0.00100.00sVN>1 TMS: 0.5100.0VN> 1 tRESET: 0.00100.00VN>2 as VN>1VN>3/4 as VN>1 exceptVN>3/4 Input: VN1
DF/DTdf/dt Status: Disabled/Enabled
df/dt Setting: 0.110 Hz/sdf/dt Time Delay: 0.00100.0sdf/dt f low: 4565Hzdf/dt f high: 4565Hz
V Vector ShiftV Shift Status: Disabled/EnabledV Shift Angle: 230
o
Reconnect DelayReconnect Status: Disabled/Enabled
Reconnect Delay: 0300.0sReconnect tPULSE: 010.0s
Voltage Protection
Under VoltageV< Measurt Mode:
Phase-PhasePhase-Neutral
V< Operate Mode:Any PhaseThree Phase
V< 1 Function:DisabledDTIDMT
V2 Time Delay: 0.00100.00s
The inverse characteristic is given by thefollowing formula:
t =K
(M - 1)
Where:
K = Time multiplier settingt = Operating time in secondsM = Applied input voltage/relay setting voltage
NPS Over VoltageV2>1 status: Enabled/DisabledV2>1 Voltage Set:
1150V (100/120V)4600V (380/480V)
V2>1 Time Delay: 0.00100.00s
Frequency Protection
Under FrequencyF
7/29/2019 P341_EN_TDS_B11
27/32
P341 Technical Data Sheet 26 P341 Software Version 0320J
Bit 2 - Enable Block F1 Setting: 45.0068.00HzF>1 Time Delay: 0.1100.0sF>2 as F>1
CB FailCB Fail 1 Status: Disabled/EnabledCB Fail 1 Timer: 0.0010.00sCB Fail 2 Status: Disabled/EnabledCB Fail 2 Timer: 0.0010.00sCBF Non I Reset: I< Only, CB Open & I Inhibit: 0.08 In32.0 InVTS I2> Inhibit: 0.05 In0.50 InNegative phase sequence voltage (V2):
10V (100/120V)40V (380/480V)
Phase overvoltage:Pick-up 30V,Drop-off 10V (100/120V)Pick-up 120V,Drop-off 40V (380/480v)
Superimposed Current: 0.1 In
Current Transformer SupervisionCTS 1 Status: Disabled/EnabledCTS 1 VN Input: Measured/DerivedCTS 1 VN< Inhibit:
0.522V (100/120V)288V (380/480V)
CTS 1 IN> Set: 0.084InCTS 2 as CTS1
Plant Supervision
CB State Monitoring Control andCondition MonitoringBroken I^: 12.0I^ Maintenance:
Alarm disabled
Alarm enabledI^ Maintenance: 1In^25000In^I^ Lockout:
Alarm disabledAlarm enabled
I^ Lockout: 125000
No CB Ops. Maint:Alarm disabledAlarm enabled
No CB Ops: Maint: 110000No CB Ops Lock:
Alarm disabledAlarm enabled
No CB Ops Lock: 110000CB Time Maint:
Alarm disabledAlarm enabled
CB Time Maint: 0.0050.500sCB Time Lockout:
Alarm disabledAlarm enabled
CB Time Lockout: 0.0050.500sFault Freq Lock:
Alarm disabledAlarm enabled
Fault Freq Count: 19999Fault Freq Time: 09999s
Input LabelsOpto Input 132: Input L1Input L32
Output LabelsRelay 132: Output R1Output R32
Current Loop InputCLIO1 Input 1: Disabled/EnabledCLI1 Input Type:
0 - 1mA0 - 10mA0 - 20mA4 - 20mA
CLI1 Input Label: 16 characters (CLIO input 1)CLI1 Minimum: -9999+9999
CLI1 Maximum: -9999+9999CLI1 Alarm: Disabled/EnabledCLI1 Alarm Fn: Over/UnderCLI1 Alarm Set: CLI1 minCLI1 maxCLI1 Alarm Delay: 0.0100.0sCLI1 Trip: Disabled/EnabledCLI1 Trip Fn: Over/UnderCLI1 Trip Set: CLI1 minCLI1 maxCLI1 Trip Delay: 0.0100.0sCLI1 I< Alarm (420 mA input only):
Disabled/EnabledCLI1 I< Alm Set (420 mA input only):
0.04.0mA
CLI2/3/4 as CLI1
Current Loop OutputCLO1 Output 1: Disabled/EnabledCLO1 Output Type:
7/29/2019 P341_EN_TDS_B11
28/32
P341 Technical Data Sheet 27 P341 Software Version 0320J
0 - 1mA0 - 10mA0 - 20mA4 - 20mA
CLO1 Set Values: Primary/SecondaryCLO1 Parameter: As shown below*
CLO1 Min: Range, step size and unitcorresponds to the selected parameter
CLO1 Max: Same as CLO1 MinCLO2/3/4 as CLO1Current Loop Output ParametersCurrent Magnitude:
IA MagnitudeIB MagnitudeIC MagnitudeIN Derived Mag: 0.0016.0
I Sen Mag: 0.00 2.0APhase Sequence Components:
I1 Magnitude
I2 MagnitudeI0 Magnitude:0.0016.0A
Phase Currents:IA RMS*IB RMS*IC RMS*0.0016.0A
P-P Voltage Magnitude:VAB MagnitudeVBC MagnitudeVCA Magnitude0.0200.0V
P-N Voltage Magnitude:VAN MagnitudeVBN MagnitudeVCN Magnitude0.0200.0V
Neutral Voltage Magnitude:VN1 Measured MagVN Derived Mag0.0200.0V
Phase Sequence Voltage Components:V1 Magnitude*V2 MagnitudeV0 Magnitude0.0200.0V
RMS Phase Voltages:VAN RMS*VBN RMS*VCN RMS*0.0200.0V
Frequency: 0.0070.0Hz3 Phase Watts*: -6000W6000W3 Phase Vars*: -6000Var6000Var3 Phase VA*: 06000VA3Ph Power Factor*: -11Single Phase Active Power:
A Phase Watts*:B Phase Watts*:C Phase Watts*:-2000W2000W
Single Phase Reactive Power:A Phase Vars*:
B Phase Vars*:C Phase Vars*-2000Var2000Var
Single Phase Apparent Power:A Phase VA*:B Phase VA*:
C Phase VA*02000VA
Single Phase Power Factor:Aph Power Factor*BPh Power Factor*CPh Power Factor*-11
3 Phase Current Demands:IA Fixed/Roll/Peak Demand*IB Fixed/Roll/Peak Demand*IC Fixed/Roll/Peak Demand*0.0016.0A
3ph Active Power Demands:
3Ph W Fix/Roll/Peak Demand*-6000W6000W
3ph Reactive Power Demands:3Ph Vars Fix/Roll/Peak Dem*-6000Var6000Var
Thermal Overload: 0.00200.0%CL Input 1-4: -99999999.0
Note 1: Measurements marked with anasterisk, the internal refresh rate isnominally 1s, others are 0.5 powersystem cycles or less.
Note 2: The polarity of Watts, Var and powerfactor is affected by the measurementsMode setting.
Note 3: These settings are for nominal 1A and100/120V versions only. For otherversions they need to be multipliedaccordingly.
7/29/2019 P341_EN_TDS_B11
29/32
P341 Technical Data Sheet 28 P341 Software Version 0320J
CASE DIMENSIONS
A = Clearance holes
B = Mounting holes
A
BA
BA
DIAG No.
SER No.
In
Vx
Vn
A 50/60 HzV
VV
SK1 SK2
E202519
US LISTEDC
IBD2IND. CONT. EQ.
UL
SK3
TRIP
ALARM
HEALTHY
OUT OFSERVICE
= CLEAR
= READ
= ENTER
C
P1647ENb
Flush mounting panelPanel cut-out detail
Note: If mounting plate is required
use flush mounting cut out
dimensions
23.30 8 off holes Dia. 3.4155.40
159.00
168.
00
B
Front view240.00
Incl. wiring
157.5max.
Side view30.00
All dimensions in mm
177.0(4U)
483 (19 rack)
Sealingstrip
202.00181.3010.35
A B
177.00
206.00
200.00
Secondary cover (when fitted)
P341 case dimensions (40TE case)
7/29/2019 P341_EN_TDS_B11
30/32
P341 Technical Data Sheet 29 P341 Software Version 0320J
CONNECTION DIAGRAMS
(For a full set of Connection Diagrams for all Hardware configurations, see technical manualP341/EN/CO
Interconnection Protection Relay (40TE) for Embedded Generation (8 I/P & 70 IP + CLIO)
7/29/2019 P341_EN_TDS_B11
31/32
P341 Technical Data Sheet 30 P341 Software Version 0320J
ORDERING INFORMATION
MiCOM P341 INTERCONNECTION RELAY NOMENCLATURE
A N N N A X X X A X X N N X A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Character Type (A=Alpha, N=Numeric,
X=Alpha-numeric)
Character Numbering (Maximum = 15)P 3 4 1 * * * * * A 0 * * 0 *
Vx Aux Rating24-48 Vdc48-110 Vdc, 30-100 Vac110-250 Vdc, 100-240 Vac
123
In/Vn RatingIn=1A/5A, Vn=100/120VIn=1A/5A, Vn=380/480V
12
Hardware OptionsNothingIRIG-B onlyFibre Optic Converter Only
IRIG-B & Fibre Optic Converter2
ndrear Comms. Port*
2nd
rear Comms. + IRIG-B*
123
478
Product SpecificSize 40TE Case, No Option (8 Optos + 7 Relays)Size 40TE Case, 8 Optos + 7 Relays + CLIO*Size 40TE Case, 16 Optos + 7 Relays*Size 40TE Case, 8 Optos + 15 Relays*Size 40TE Case, 12 Optos + 11 Relays*
ABCDE
Protocol OptionsK-BusModbusIEC60870-5-103DNP3.0
1234
Mounting
Panel Mounting M
Software **
Setting FilesDefaultCustomer
01
Design SuffixOriginalPhase 2 HardwareOriginal Hardware
ACJ
Note Design Suffix
A = Original hardware (48V opto inputs only, lower contact rating, no I/O expansion available)C = Universal optos, new relays, new power supplyJ = Phase 2 CPU and front panel with 2 hotkeys and dual characteristic optos
* Not available in design suffix A
Note Mounting
For rack mounting in 40TE case, assembled single frames and blanking plates are available
7/29/2019 P341_EN_TDS_B11
32/32
AREVA T&D Worldwide Contact Centre:
http://www.areva-td.com/contactcentre/Tel.: +44 (0) 1785 250 070
Our policy is one of continuous development. Accordingly
the design of our products may change at any time. Whilst
every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is
intended for information purposes only. Its contents do notconstitute an offer for sale or advise on the application of
any product referred to in it. We cannot be held responsible
for any reliance on any decisions taken on its contents
A
UTOMATION-L3-P341-TDS-GB
-
-AREVA-2004AREVA,theAREVAlogoandanyalternativeversionthereofaretrademarksandservicemarksofAREVA.
M
iCOMisaregisteredtrademarkofAREVA.Alltradenamesortrademarksmentionedhereinwhetherregisteredornot,arethepropertyoftheirowners-389191982RCSPARIS.
ADDITIONAL INFORMATION RESOURCEFurther information on the MiCOM series of relays may beobtained from www.areva-td.com