Technical Data 1630
Service chilled, hot water, up to 60% glycolFlow Characteristic equal percentageSize [mm] 0.5” [15]End Fitting NPT female endsBody forged brass, nickel platedBall chrome plated brassStem nickel plated brassSeat Teflon® PTFESeat O-ring EPDM (lubricated)Characterized Disc BrassPacking EPDMDiaphragm Polyester reinforced SiliconeRegulator Components stainless steel / brass / NitrileBody Pressure Rating [psi] 600Media Temperature Range (Water)
0°F to 212°F [-18°C to 100°C]
Differential Pressure Range 5 to 50 psiClose-Off Pressure 200 psiRangeability 100:1Valve Accuracy ± 5%*Weight 2 lb [0.9 kg]GPM 2.5GPM Range 0...(1.6-3.0)Leakage ANSI Class IV (0.01% of rated valve capacity at
50 psi differential)*See page 3 of the PICCV technical documentation for details.
ApplicationThe Pressure Independent Characterized Control Valve is typically used in air handling units on heating and cooling coils, and fan coil unit heating or cooling coils. Some other common applications include unit ventilators and VAV reheat coils. This valve is suitable for use in a hydronic system with constant or variable flow. This valve is designed with MFT functionality which facilitates the use of various control input.
Suitable Actuators Non-Spring SpringP2050B025 LR, LRC, KR TFR, LF
Dimensions (Inches [mm])
2.47” [62.8]
1.35
” [3
4.2]
6.30” [160]
C
A
B
D
E F
KRB24-3
A B C D E F6.56” [167] 4.47” [114] 5.09” [129] 2.34” [59.4] 1.33” [34] 1.25” [32]
P2050B025, 1/2”, Pressure Independent ValveChrome Plated Brass Ball and Brass Stem, NPT Female Ends
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Date
cre
ated
, 12/
04/2
017
- Sub
ject
to c
hang
e. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
Dimensions (Inches [mm])
C
AB
D
E F
2.6"[66]
6.5" [165]
1.69"[42]
3.22"[82]
2.34"[59.4]
LRB24-SA
A B C D E F7.68” [195] 4.47” [114] 7.13” [181] 2.34” [59.4] 1.48” [38]
Dimensions (Inches [mm])
C
A
B
D
7.64"[194]
4.49"[114]
2.28"[58]
3.78"[96]
E F
LF24-MFT
A B C D E F8.1” [206] 4.47” [114] 8.54” [217] 2.34” [59.4] 1.89” [48]
Dimensions (Inches [mm])
C
A
B
D
E F
7.5" [191]
1.69"[42]
3.22"[82]
2.34"[59.4]
2.6"[66]
LRX24-MFT
A B C D E F8.68” [220] 4.47” [114] 7.13” [181] 2.34” [59.4] 1.48” [38]
Dimensions (Inches [mm])
6.28"[159.55]
3.0"[76.2]
2.93"[74.5]
2.40"[61]
C
A
B
D
E F
TFRX24-MFT
A B C D E F7.1” [180] 4.47” [114] 6.98” [177] 2.34” [59.4] 1.5” [38]
P2050B025, 1/2”, Pressure Independent ValveChrome Plated Brass Ball and Brass Stem, NPT Female Ends
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Date
cre
ated
, 12/
04/2
017
- Sub
ject
to c
hang
e. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
Dimensions (Inches [mm])
C
A
B
D
E F
2.6"[66]
6.5" [165]
1.69"[42]
0.78" [20]
3.22"[82]
2.34"[59.4]
FlowSetR™ Dimensions
LRB24-3, LRX24-3, LRCB24-3
A B C D E F7.68” [195] 4.47” [114] 7.91” [201] 2.34” [59.4] 1.48” [38]
P2050B025, 1/2”, Pressure Independent ValveChrome Plated Brass Ball and Brass Stem, NPT Female Ends
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Date
cre
ated
, 12/
04/2
017
- Sub
ject
to c
hang
e. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
Technical Data 2258
Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%Power Consumption Running 1.5 WPower Consumption Holding 0.2 WTransformer Sizing 2 VA (class 2 power source)Electrical Connection 18 GA plenum rated cable with 1/2” conduit
connector protected NEMA 2 (IP54) 3ft [1m] 10ft [3m] and 16ft [5m]
Overload Protection electronic thoughout 0° to 90° rotationInput Impedance 600 ΩAngle of Rotation 90°Direction of Rotation (Motor) reversible with built-in switchPosition Indication integrated into handleManual Override external push buttonRunning Time (Motor) 90 secAmbient Temperature Range -22°F to 122°F [-30°C to 50°C]Storage Temperature Range -40°F to 176°F [-40°C to 80°C]Housing NEMA 2, IP42, UL Enclosure Type 2Agency Listings† cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/ECNoise Level (Motor) <35 dB (A) Servicing maintenance freeQuality Standard ISO 9001
†Rated Impulse Voltage 800V, Type action 1.B , Control Pollution Degree 3.
LRX24-3On/Off, Floating Point, Non-Spring Return, 24 V
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Date
cre
ated
, 11/
29/2
017
- Sub
ject
to c
hang
e. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
Wiring Diagrams
INSTALLATION NOTES
Provide overload protection and disconnect as required.
Actuators may be connected in parallel. Power consumption and input impedance must be observed.
Actuators may also be powered by 24 VDC.
Actuators Hot wire must be connected to the control board common. Only connect common to neg. (-) leg of control circuits. Terminal models (-T) have no-feedback.
Actuators with plenum cable do not have numbers; use color codes instead.
Meets cULus requirements without the need of an electrical ground connection.
! WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
2 3 1824 VAC Transformer
Blk (1) Common
Red (2) + Hot
Wht (3) Y Input
LineVolts
1
On/Off
2 3 1824 VAC Transformer
Blk (1) Common
Red (2) + Hot
Wht (3) Y Input
LineVolts
1
Floating Point
ComHot2 3 18
Blk (1) Common
Red (2) + Hot
Wht (3) Y Input
LineVolts
24 VAC Transformer
1
Floating Point - Triac Source
2 18Blk (1) Common
Red (2) + Hot
Wht (3) Y Input
LineVolts
24 VAC Transformer
ComHot6 1
Floating Point - Triac Sink
LRX24-3On/Off, Floating Point, Non-Spring Return, 24 V
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Date
cre
ated
, 11/
29/2
017
- Sub
ject
to c
hang
e. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.