OXYMAT

Citation preview

  • Oxymat presents the next generation of control systems with more functionalities, higher flexibility and easy integration with

    other systems - all included in the intellicontrol that comes with the generator.

    INTELLICONTROL

    Built-in functionality

    Worldwide Manufacturer of PSA Generator Systems

    Main features

    Operation

    Automatic Runs the system with all alarms active and pressure monitoring of product tank for stand-by function

    Service mode Runs the system with all alarms active, but no impact on the system. Do not switch into stand-by

    Remote auto mode Runs as automatic but will be stopped if local modes are activated (Automatic or Service mode)

    Start/Stop via SMS Starts as remote auto mode-option

    Analogue Pressure in product tank

    Pressures in both columns-option

    Purity monitoring-option

    Password As default 4 levels are implemented: guest, operator, superuser and administrator ; advanced user control can be acti-vated for strict access control and allows the system to work with individual users and levels

    Alarm system All alarms are described on the controllers display for easy and fast recovery. Alarms on air dryer and air pack can be monitored by the controller (requires digital signals from air pack and dryer).

    Drain Control Automatic drain with double time settings-one for operation and one for system stop

    Automatic start Automatic start in auto mode after power failure; intelligent startup procedure ensures correct pressures before PSA starts.

    Smart delivery Optimized version of our standard smart delivery function (Oxygen)

    Delayed delivery Option for delayed delivery from PSA to product tank after stand-by and system start; this ensures that purity stays correct

    Service system A service system with pre-warnings informs the operator when it is time for the next service

    7 touch color screen-wide screen format Easy to use advanced control system Quick overview through screen with all relevant information displayed Advanced user access system with audit trail Easily updated via USB or SD card Multilanguage user interface Multiple settings storage for varying operating conditions Full logging of all measured values with selectable graph for playback Remote view and control via Ethernet available (option) Remote operation and control via SMS available (option) Quality logic controller multi expandable Intellicontrol can interface to any monitoring or control system available (option)

  • Worldwide Manufacturer of PSA Generator Systems

    Add-on features

    Product name Name Description

    26210 Alarm pack Column pressure monitoringAudio and visual alarm in one unit. Can be placed anywhere. Visual alarm is active whenever an alarm is present in the system. Audio will turn on when an alarm appears but can be turned off from for control panel.Voltage free contacts for following alarms: Purity alarmPurity stopLow pressure productQuick stopLow pressure columnsAlarm on air packAlarm on air dryer

    26011 Purity control Purges product outside valid purity range. Placed after product tank.

    26012 Utility monitoring Monitoring and alarm levels for 4 important parametersAirpressureAirtemperatureDewpoint AirDewpoint product

    26510 Flow monitoring External flow meter connected. Reading is shown on the screenincluding totalizer

    26511 Flow control External flow controller is connected. Actual flow is shown on the screen and flow can be controlled from the screen. Including totalizer

    26430 Datalogging and remote control Logging of all measured values to SD card (USB) remote access for view and control. Ether-net link, ModBUS, TCP/IP

    26211 SMS alarm and control Sends a text message containing alarm information to any cell phone. And start, stop reset can be done via SMS

    OM1 26101 Oxygen monitor for Oxygen genera-tors

    Range 0,1-100%. Includes alarm function (through control)

    OM1E 26121 Oxygen monitor + output As OM1 plus 2 x analogue output 4-20mA representing pressure and purity

    OM2 26102 Oxygen monitor forNitrogen generators

    Range 0,1-25%Includes alarm function (through control)

    OM2E 26122 Oxygen monitor + output As OM2 plus 2 x analogue output 4-20mA representing pressure and purity

    OM3 26103 Oxygen monitor Range 5-1000ppm, includes alarm function (through control)

    OM3E 26123 Oxygen monitor+output As OM3, plus 2xanalogue output 4-20mA representing pressure and purity

    XCON 26600 X-controller for standard control panels

    X-CON can control up to 6 lines via remote start based on flow or pressure. X-CON starts and stops lines according to actual product demand.

    UPS 26601 UPS module Battery backup for standard controls. 30min.

    RCON 26602 Redundancy controller for 2 standard control panels

    RCON can start/stop 2 standard PSAs for redundancy purposes. The PSAs are load balanced based on hour counter and automatically started if alarms.

    FCON Standalone flow controller FCON can regulate the flow using a motor valve. The control needs just an analogue signal representing the flow.

    RM1 27000 Room monitoring Oxygen detection inside container. Includes audio/visual alarm.

    RM2 27001 Room monitor with battery backup. Oxygen detection inside container. Runs independently and includes relay outputs for alarms.

    FILM 27100 Manual filling station Filling of high pressure bottles. Operator controls when filling is in progress.

    BACM 27200 Manual backup Filling of high pressure backup bottles. Operator controls when filling is in progress. Includes alarm for low pressure and change-over system.