OWNER: SET NUMBER COVER SHEET INDEX OF DRAWINGS LB0 SITE-WIND ZONE PLAN / LB1 THE BOARD OF REGENTS THE UNIVERSITY OF TEXAS SYSTEM PARTIAL ROOF PLAN LB2 PARTIAL ROOF PLAN / ROOFING DETAILS LB3 ROOFING DETAILS LB4 ROOFING DETAILS LB5 ROOFING DETAILS LB6 FALL PROTECTION PLAN / DETAILS S1 AUSTIN, TEXAS OWNER'S REPRESENTATIVE: REUBEN PINKSON, ARCHITECT - FACILITIES MANAGEMENT U. T. HEALTH SCIENCE CENTER - SAN ANTONIO 7703 FLOYD CURL DRIVE SAN ANTONIO, TEXAS 78284-7957 ROOFING CONSULTANTS: HOLLON+CANNON GROUP, LLC 12885 RESEARCH BLVD, SUITE 210B AUSTIN, TEXAS 78750 (512) 300-0452 ROOFING SCHEDULES LIBRARY BUILDING

OWNER: THE BOARD OF REGENTS THE ... - UT Health San Antoniouthscsa.edu/facilities/bids/files/rfb745-14-9803/... · san antonio, texas 78284-7957 roofing consultants: hollon+cannon

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: OWNER: THE BOARD OF REGENTS THE ... - UT Health San Antoniouthscsa.edu/facilities/bids/files/rfb745-14-9803/... · san antonio, texas 78284-7957 roofing consultants: hollon+cannon

OWNER:

SET NUMBER

COVER SHEETINDEX OF DRAWINGS

LB0

SITE-WIND ZONE PLAN / LB1

THE BOARD OF REGENTSTHE UNIVERSITY OF TEXAS SYSTEM

PARTIAL ROOF PLANLB2

PARTIAL ROOF PLAN / ROOFING DETAILSLB3

ROOFING DETAILSLB4

ROOFING DETAILSLB5

ROOFING DETAILSLB6

FALL PROTECTION PLAN / DETAILSS1

AUSTIN, TEXAS

OWNER'S REPRESENTATIVE:

REUBEN PINKSON, ARCHITECT - FACILITIES MANAGEMENTU. T. HEALTH SCIENCE CENTER - SAN ANTONIO7703 FLOYD CURL DRIVESAN ANTONIO, TEXAS 78284-7957

ROOFING CONSULTANTS:

HOLLON+CANNON GROUP, LLC12885 RESEARCH BLVD, SUITE 210BAUSTIN, TEXAS 78750(512) 300-0452

ROOFING SCHEDULES

LIBRARYBUILDING

Page 2: OWNER: THE BOARD OF REGENTS THE ... - UT Health San Antoniouthscsa.edu/facilities/bids/files/rfb745-14-9803/... · san antonio, texas 78284-7957 roofing consultants: hollon+cannon

EXISTING ROOF ASSEMBLY SCHEDULE

SECTION:

2.0" EPS INSULATIONSTRUCTURAL CONCRETE DECK

L1aROOF

SINGLE-PLY MEMBRANE

METAL DECKING

L1b, L1c, L1d, L2 and L3SECTIONS:ROOF

STONE BALLAST

2.5" EPS INSULATION

L4 thru L13SECTIONS:ROOF

STRUCTURAL CONCRETE

SINGLE-PLY MEMBRANESTONE BALLAST

NEW ROOF ASSEMBLY SCHEDULE

SECTION: L1aROOF

REMOVE EXISTING ROOFING TO STRUCTURAL CONCRETE DECK

2-PLY MODIFIED BITUMEN ROOF MEMBRANE TORCH APPLIED1/2" GYPSUM COVER BOARD SET IN ADHESIVE

REMOVE EXISTING COATING TO CONCRETE DECK

L4 thru L13SECTION:ROOF

1-PLY MODIFIED BITUMEN MEMBRANE

PREPARE EXISTING CONCRETE PER MANUFACTURER'SRECOMMENDATIONS

1/8" / FT. TAPERED POLYISOCYANURATE INSULATION W/ 3.5" STARTING THICKNESS SET IN ADHESIVE

L1b, L1c, L1d, L2 and L3SECTIONS:ROOF

2-PLY MODIFIED BITUMEN ROOF MEMBRANE TORCH APPLIED1/2" GYPSUM COVER BOARD SET IN ADHESIVE

1/8" / FT. TAPERED POLYISOCYANURATE INSULATION W/ 3.5"STARTING THICKNESS SET IN ADHESIVE

REMOVE EXISTING ROOFING TO METAL DECKPOLYISOCYANURATE FILL INSULATION AS REQ'D TO MATCHTOP SURFACE OF ADJACENT CONCRETE DECK MECHANICALLYFASTENED

SYMBOLS LEGEND

SYMBOL LABEL DESCRIPTION DETAIL

PS PENETRATION FL'G 1/LB4

RD PRIMARY ROOF DRAIN 9/LB4

EF EXHAUST FAN 3/LB4

OSC OVERFLOW SCUPPER 6/LB3, 8/LB5

C CONDENSATE LINE 8/LB4

E ELECTRICAL LINE SECTIONG GAS LINE 07 7200 00

NOT IN CONTRACT

TRAFFIC PAD

slope DRAINAGE SLOPE

TAPERED CRICKET

VTR PLUMBING VENT 2/LB4

FP FALL PROTECTION 4/LB5

HS HOT STACK 6/LB4

WIND UP-LIFT PRESSURES AND PERIMETER DIAGRAM

MEAN ROOF HEIGHT< 60 ft.

ZONE 1 FIELD=ZONE 2 PERIMETER=ZONE 3 CORNER=

a = 10% OF LEAST HORIZONTAL DIMENSIONOF BUILDING, OR 0.4 h, WHICHEVER IS

OF LEAST HORIZONTAL DIMENSION OR 3 ft.SMALLER, BUT NOT LESS THAN EITHER 4%

ZONE 1

MEAN ROOF HEIGHT> 60 ft.

FIELD=ZONE 2ZONE 3

PERIMETER=CORNER=

a = 10% OF LEAST HORIZONTAL DIMENSIONOF BUILDING, BUT NOT LESS THAN 3 ft.

(CONTRACTOR SHALL VERIFY ASSUMPTIONS W/ MANUFACTURER)DESIGN ASSUMPTIONS

BEXPOSURE CATEGORY

3

90 MPHBASIC WIND SPEED =

PARTIALLY ENCLOSEDCLASSIFICATION OF ENCLOSURE =

=

1.15OCCUPANCY IMPORTANCE FACTOR =

1TOPOGRAPHIC FACTOR =

BLD'G HEIGHT

WIND UPLIFT PRESSURES (PSF)(CONTRACTOR SHALL VERIFY PRESSURES W/ MANUFACTURER)

FIELD PERIMETER CORNER

0 to 30'-0" 27 39 56

30'-0" to 40'-0'' 28 43 61

40'-0" to 50'-0'' 30 46 64

DESIGN UPLIFT PRESSURE (PSF)INSTALLED WIND UPLIFT RESISTANCE VALUES SHALL BE TWO (2.0) TIMES THE SPECIFIED

WIND UPLIFT PRESSURES

3

aa

2

3

3

2

2

1

SAMPLE PLAN VIEW OF ROOF

3

2a

2a2

2

3

2

3

1

2

SAMPLE PLAN VIEW OF ROOF

2

3

GENERAL NOTES TO CONTRACTOR

GENERAL NOTES:

1. CONTRACTOR SHALL VERIFY OPERATIONAL STATUS OF ROOF TOP EQUIPMENT W/ OWNER.ABANDONED EQUIPMENT AND CURBS SHALL BE REMOVED FROM THE BUILDING. AND DISPOSED OF. REPAIR DECKING AT ABANDONED PENETRATIONS (NOT SCHEDULED ON

2. EXISTING GAS, CONDENSATE, ELECTRICAL, HYDRONIC PIPING, ETC. SHALL BEDISCONNECTED, RAISED AND RECONNECTED AS REQ'D TO ACCOMMODATE NEW ROOFSYSTEM THICKNESS AND MEMBRANE FLASHING HEIGHT REQUIREMENTS.

1. PROVIDE PIPE SUPPORTS PER DETAIL 8/LB4 AT "SMALL" CONDUIT / PIPING, UNLESS OTHERWISE INDICATED ON ROOF PLAN. SEE SPECIFICATION SECTION 07 7200 00 FOR

3. EXISTING ROOF TOP EQUIPMENT SHALL BE DISCONNECTED RAISED AND RECONNECTEDAS REQ'D TO PROVIDE MEMBRANE BASE FLASHING HEIGHTS SPECIFIED.

EQUIPMENT / PIPING SUPPORTS:

1. PROVIDE TRAFFIC PROTECTION PADS AT ROOF ACCESS POINTS AND ON ALL SIDES OFROOF TOP UNITS.

TRAFFIC PROTECTION:

THE DRAWINGS FOR REMOVAL) PER UNIT PRICING, DETAILS AND SPECIFICATIONS.

DRAINAGE:

1. CRICKETS / SADDLES SHALL BE TWICE THE ADJACENT ROOF SLOPE

ROOF TOP EQUIPMENT / PENETRATIONS:

1. CONTRACTOR SHALL VERIFY FIELD DIMENSIONS.

2. PROVIDE TAPERED CRICKETS ON HIGH SIDE OF CURBED PENETRATIONS AS REQ'D TODIRECT DRAINAGE AROUND PENETRATION.

2. FIELD MEASUREMENTS ARE REQUIRED FOR BIDDING PURPOSES.

4. EXISTING DUCT WORK SHALL BE DISCONNECTED, RAISED AND RECONNECTED AS REQ'D TO ACCOMMODATE NEW ROOF SYSTEM THICKNESS AND MEMBRANE FLASHING HEIGHT REQUIREMENTS.

DEFINITION OF "SMALL" CONDUIT / PIPING.

3. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF EXISTING ROOFING SYSTEM.

L1a

L2

L3

L1b L1c

L1d

SITE PLAN / KEY PLAN / WIND ZONE PLAN - LIBRARY BUILDINGNOT TO SCALE

PLAN NORTH

CORNER(ZONE 3)

PERIMETER(ZONE 2)

FIELD(ZONE 1)

1/2" GYPSUM BOARD

KEYED NOTES TO CONTRACTOR

1 PROVIDE NEW BACKER ROD AND SEALANT AT INTERIOR / EXTERIOR CONTROL JOINTS PER DETAIL 3/LB5.

2 FIELD VERIFY SCUPPER LOCATIONS WITH ARCHITECT

3 LOWER FLASHING / EXPANSION JOINT CURB BELOW STEELSUPPORT ANCHOR PER DETAIL 2/LB6

4 REMOVE CABLE PENETRATION THROUGH BASE FLASHING.REMOVE CABLE RUN FROM ROOF SURFACE.OWNER TO RETAIN CABLING AND ACCESSORIES.

MONOLITHIC RESIN MEMBRANE

COATING

1. PROVIDE ISOLATION TAPE BETWEEN TREATED WOOD BLOCKING AND METALCOMPONENTS, WHETHER SHOWN IN DRAWINGS OR NOT.

TREATED WOOD BLOCKING

12/21/2012DATE:

SHEET:

LB1OF

6

PCCCHECKED BY:

CANNON J.DRAWN BY:

1.

REVISION SCHEDULE:

ISSUE FOR BID 12/21/122.3.4.5.6.7.

hollongroup, llc

+hg c

+cannon

KEY PLAN / SITE PLANROOFING SCHEDULES

UT

HE

ALT

H S

CIE

NC

E C

EN

TER

at S

AN

AN

TON

IOR

EP

LAC

EM

EN

T of

Roo

f at

DO

LPH

BR

ISC

OE

JR

. LIB

RA

RY

RO

OF

San

Ant

onio

, Tex

as 7

8229

Page 3: OWNER: THE BOARD OF REGENTS THE ... - UT Health San Antoniouthscsa.edu/facilities/bids/files/rfb745-14-9803/... · san antonio, texas 78284-7957 roofing consultants: hollon+cannon

HYD

HS HS HS

HYD

LIBRARY - SECTIONS L1, L2, L31/8" = 1'-0''SCALE:

PLAN NORTH

1

LB2

ROOF PLAN

L1a

L2

L3

L1b

L1c

L1d

RD RD

RD

RD RD RD RD

RDRDRDRD

1/8'

'/ft

. TA

PERE

DIN

SUL

ATI

ON

1/8'

'/ft

. TA

PERE

DIN

SUL

ATI

ON

1/8'

'/ft

. TA

PERE

DIN

SUL

ATI

ON

1/8'

'/ft

. TA

PERE

DIN

SUL

ATI

ON

1/8'

'/ft

. TA

PERE

DIN

SUL

ATI

ON

1/8'

'/ft

. TA

PERE

DIN

SUL

ATI

ON

slopeslope

ODOD

OD OD OD

1/8'

'/ft

. TA

PERE

DIN

SUL

ATI

ON

1/8'

'/ft

. TA

PERE

DIN

SUL

ATI

ON

1/8''/ft. TAPEREDINSULATION

slopeslope

DS

DS

PS

ABAND.

RH

EF

EF

VTR

VTR

EF

PSPSPS

FP

FP

PS

PS

PS

PS

FP

FP

FP

FP

FP

FP

FPEF

EF

VTR

VTR

VTR

VTR

VTR

VTR

FPFP

PS

PS

FP

FP

VTR

EF

VTR

LB410

ROOF HATCH PERDETAIL 5/LB4

LINE OF METALDECKING

LB57 SIM.

LB57SIM.LB5

7SIM.

LB57

SIM.

LB34

LB57

LB57

LB57

LB57

LB57

LB57

LB57

LB57

LB46TYP.

LB61TYP.

OD

LB54TYP.

EF

SPLASH PAN PERDETAIL 7/LB4

LB43TYP.

LB42TYP.

LB49TYP.

LB57

EXIST. HYDRANT TO BE EXTENDED BY OWNER.PROVIDE ROOF FLASHING PER DETAIL 1/LB4 - SIM.

LB410

LINE OF METALDECKING

(SHOWN DASHED)(SHOWN DASHED)LB57

LB54 TYP.

RD

LB49TYP.

LB42TYP.

LB41 TYP.

LB61TYP.

OD

ROOF LINE BELOWSEE ENLARGED PLAN SHEET LB3

ROOF LINE BELOWSEE ENLARGED PLAN SHEET LB3

ROOF LINE BELOWSEE ENLARGED PLAN SHEET LB3

ROOF LINE BELOWSEE ENLARGED PLAN SHEET LB3

LINE OF METALDECKING(SHOWN DASHED)

SPLASHPAN PERDETAIL 7/LB4

LB55

(HIGH ROOF)TYP. @ "L2"

LB56

(LOW ROOF)TYP. @ "L1"

LB56

(LOW ROOF)TYP. @ "L1"

LB55

(HIGH ROOF)TYP. @ "L3"

LB34

LB34

EXP.

JT.

EXP. JT.

LB34

EXP.

JT.

OSC

NEW OVERFLOW SCUPPERPER DETAIL 6/LB3

NEW OVERFLOW SCUPPERPER DETAIL 6/LB3

OSCNEWNEW

OSCNEW

OSCNEW

NEW OVERFLOW SCUPPERPER DETAIL 6/LB3

NEW OVERFLOW SCUPPERPER DETAIL 6/LB3

EXIST. HYDRANT TO BE EXTENDED BY OWNER. PROVIDE ROOF FLASHINGPER DETAIL 1/LB4 - SIM.

OSC

NEW OVERFLOW SCUPPERPER DETAIL 6/LB3NEW

NEW OVERFLOW SCUPPERPER DETAIL 6/LB3

OSCNEW

OSCNEW

SIM.

NEW OVERFLOW SCUPPERPER DETAIL 8/LB5

NEWFP

NEWFP

NEW FALL PROTECTION ANCHORSRE: STRUCTURAL. PROVIDE ROOF FLASHINGPER DETAIL 1/LB4

1

1

1

22

22

22

SKYLIGHTABAND.SKYLIGHT

3 TYP.

3TYP.

3TYP.

4

444

CRICKET SLOPE @ TWICE ROOF SLOPETYPICAL

12/21/2012DATE:

SHEET:

LB2OF

6

PCCCHECKED BY:

CANNON J.DRAWN BY:

1.

REVISION SCHEDULE:

ISSUE FOR BID 12/21/122.3.4.5.6.7.

hollongroup, llc

+hg c

+cannon

ROOF PLAN

UT

HE

ALT

H S

CIE

NC

E C

EN

TER

at S

AN

AN

TON

IOR

EP

LAC

EM

EN

T of

Roo

f at

DO

LPH

BR

ISC

OE

JR

. LIB

RA

RY

RO

OF

San

Ant

onio

, Tex

as 7

8229

Page 4: OWNER: THE BOARD OF REGENTS THE ... - UT Health San Antoniouthscsa.edu/facilities/bids/files/rfb745-14-9803/... · san antonio, texas 78284-7957 roofing consultants: hollon+cannon

LIBRARY - SECTIONS 1/8" = 1'-0''SCALE:

PLAN NORTH

1

LB3

PARTIAL ROOF PLAN (4TH FLOOR)

LIBRARY - SECTIONS 1/8" = 1'-0''SCALE:

PLAN NORTH

2

LB3

PARTIAL ROOF PLAN (3RD FLOOR)

(INTERIOR SPACE)

(INTERIOR SPACE)

LIBRARY - SECTIONS 1/8" = 1'-0''SCALE:

PLAN NORTH

3

LB3

PARTIAL ROOF PLAN (2ND FLOOR)

(INTERIOR SPACE)

L4 L5 L6 L7

L8 L9 L10

L11 L12 L13

FLASHING AT ROOF EDGEPER DETAIL 4/LB6 TYP.

SHELF ROOF BELOW PERPLAN 2/LB3

SHELF ROOF BELOW PERPLAN 2/LB3

DRAIN DRAIN DRAIN DRAIN

DRAIN DRAIN DRAIN

DRAIN DRAIN DRAIN

FLASHING AT WINDOWPER DETAIL 3/LB6 - TYP.

FLASHING AT WINDOWPER DETAIL 3/LB6 - TYP.

FLASHING AT ROOF EDGEPER DETAIL 4/LB6 TYP.

FLASHING AT ROOF EDGEPER DETAIL 4/LB6 TYP.

FLASHING AT WINDOWPER DETAIL 3/LB6 - TYP.

1/2'' COVER BOARD

ROOF SYSTEM

BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY1/4'' COVER BD.

CANT STRIP

3" = 1'-0"PARAPET4

LB3

TAPERED POLYISO. (THICKNESS VARIES)

POLYISOCYANURATE

3/4" PLYWOOD

EXIST. STRUC. CONC. DECK

SCREWS W/ NEOPRENE WASHERS@ 16'' O.C.

24 GA. PRE-FINISHED CONT. CLEAT

1" 2" 1"3"8"

-MIN

.

24 GA. PRE-FINISHED EXP. JT. COVERSELF-ADHERING UNDERLAYMENT24 GA. PRE-FINISHED COUNTERFLASHINGSCREWS @ 16'' O.C.24 GA. PRE-FINISHED RECEIVER

DRIVE-PINS W/ NEOPRENE WASHERS@ 16'' O.C.

CONT. SEALANTEXIST. PARAPET

1'' STANDING SEAM PER DETAIL 1/LB5

DRIVE-PINS W/ NEOPRENE WASHERS @ 16'' O.C.

22 GA. GALV. CONT. CLEATSELF-ADHERING UNDERLAYMENT

EXIST. TILE EXTERIOREXIST. CONC. PARAPET

24 GA. PRE-FINISHED COPING

3" = 1'-0"PARAPET COPING5

LB3

NOTE: SEE DETAIL 4/LB3 FOR PARAPET

3"

4"

FLASHING BELOW

NOTE: SEE DETAIL 5/LB3 FOR COPING ABOVE

3" = 1'-0"SCUPPER6

LB3

EXIST. STRUC. CONC. DECK

NOT TO SCALEELEVATION - CLOSUREA

2'' SEE SCHEDULE 2"

2"4"

2"

NOT TO SCALEISOMETRICB

24 GA. PRE-FINISHED CLOSURE PLATE SET

PROVIDE NEW SCUPPER OPENING THRU EXIST PARAPET AS REQ'D

4" 1/2''-MIN.

2''

4"-M

IN.

EXIST. CONCRETE PANEL

DRIVE-PINS W/ NEOPRENE WASHERS

DRIVE-PINS W/ NEOPRENE WASHERS@ EA CORNER

24 GA. GALV. SCUPPER SLEEVESOLDER ALL JOINTS WATERTIGHT

1/2'' COVER BOARDROOF SYSTEM

1/4'' COVER BOARD2X TRT'D WD. CANT (@ SCUPPER ONLY)

NOTE:1. PARAPET / WALL EXPANSION JOINT NOTES PER DETAIL 4/LB32. SCUPPER FLOW LINE SHALL BE 2" ABOVE

EDGE OF PRIMARY DRAINAGE DEVISE

2"

4"3"

1/4'' COVER BOARDMEMBRANE STRIP-IN PLYMEMBRANE BASE FLASHING

1" 2" 1"

EXIST. TILE

IN SEALANT

@ EA CORNER

TRT'D WD. BLK'G TO MATCH HT. OF INSULATION ANCHOR TO DECK

POLYISOCYANURATE

TAPERED POLYISO

@ 6'' O.C.

FLEXIBLE VAPOR RETARDER W/ COMPRESSIBLE INSULATION

4"X6" CONT. STL. ANGLE ANCHORED TOCURB AND DECK @ 24'' O.C. - STAGGERED

2X TRT'D WD. CURB AS REQ'D TO PROVIDE FLASHING HT.

1"1"

FIEL

DV

ERIF

Y

EXIST.

SCUPPER SIZES

SCUPPER DIMENSIONS

4" x 24"

12/21/2012DATE:

SHEET:

LB3OF

6

PCCCHECKED BY:

CANNON J.DRAWN BY:

1.

REVISION SCHEDULE:

ISSUE FOR BID 12/21/122.3.4.5.6.7.

hollongroup, llc

+hg c

+cannon

PARTIAL ROOF PLANSROOFING DETAILS

UT

HE

ALT

H S

CIE

NC

E C

EN

TER

at S

AN

AN

TON

IOR

EP

LAC

EM

EN

T of

Roo

f at

DO

LPH

BR

ISC

OE

JR

. LIB

RA

RY

RO

OF

San

Ant

onio

, Tex

as 7

8229

Page 5: OWNER: THE BOARD OF REGENTS THE ... - UT Health San Antoniouthscsa.edu/facilities/bids/files/rfb745-14-9803/... · san antonio, texas 78284-7957 roofing consultants: hollon+cannon

3" = 1'-0"PENETRATION FLASHING1

LB4 3" = 1'-0"VENT THRU ROOF2

LB4 3" = 1'-0"FLANGED VENT4

LB43" = 1'-0"MECHANICAL CURB3

LB4

EXISTING OR NEW RIGID PENETRATION

NOTE:1. CONDUIT PENETRATING ROOFING ASSEMBLY SHALL BE RIGID CONDUIT. CONTRACTOR

2. CONDUIT SHALL BE ONE CONTINUOUS PIECE FROM UNDERSIDE OF DECK EXTENDINGMIN. 6" ABOVE PENETRATION SEAL. ANCHOR TO DECK OR NEAREST STRUC. FRAMING ASREQ'D TO ELIMINATE MOVEMENT.

SHALL REPLACE ALL FLEXIBLE OR DAMAGED PENETRATIONS W/ RIGID CONDUIT

REMOVE ASPHALTIC CONTAMINATES FROM PENETRATION PRIOR TO INSTALLATION OF PENETRATION SEAL

1/2" COVER BOARD

EXISTING DECKING

POLYISOCYANURATE

OR SEALANT

3. MINIMUM 1'' SPACE IS REQUIRED BETWEEN PENETRATIONS AND INTERIOR WALL OFPENETRATION CURB AND BETWEEN MULTIPLE PENETRATIONS. REROUTE PENETRATIONSAS REQUIRED TO PROVIDE MINIMUM 1" SPACING REQUIRED

BIRD SCREEN

8"

4"1/2"MIN.

EXISTING FLUE EXTEND AS NECESSARY

24 GA. GALV. VENT FLASHINGFULLY SOLDER JOINTS WATERTIGHT

EXISTING DECKING

POLYISOCYANURATE

24 GA. GALV. VENT CAPPROVIDE CAP TO MATCH EXIST.

1/2'' COVER BOARDROOF SYSTEMSTRIP-IN PLY

COVER BD. ANCHOR TO DECK W/TRT'D WD. BLK'G TO MATCH HT. OF

2" MIN

.

APPROPRIATE FASTENERS @ 6'' O.C.

VENT STACK EXTENSION AS REQ'D

CONT. SEALANT

NOTE:1. PRIME VENT FLANGE, SET IN MASTIC AND NAIL AT 3" O.C. - STAGGERED

EXIST. CURB

24 GA. GALV. SLIP FLASHING

EXISTING MECHANICAL HOOD

PROVIDE MIN. 8'' FLASHING HEIGHTTRT'D 2X CURB EXTENSION

DO NOT MODIFY - DAMAGEDCOMPONENTS SHALL BE REPLACED

3"

8"-M

IN.

EXISTING DECKING

POLYISOCYANURATE

1/2'' COVER BOARDROOF SYSTEM

BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY

1/4'' COVER BD.

1/4'' COVER

CANT STRIP

@ 12'' O.C. (MIN. 2 PER SIDE)SCREWS W/ NEOPRENE WASHERS

NOTE:1. EXTEND EXISTING CURB W/ TRT'D 2X BLK'G AND SIMPSON "A24" ANGLES, OR APPROVED EQUAL,

SPACED AT 12" O.C.

BOARD

EXISTING STACKEXTEND AS NECESSARY TO PROVIDE 8" HEIGHT

1"

8''-M

IN.

4''-MIN.

2. REMOVE VENT EXTENSION / GOOSE NECK, WERE EXISTING, AS REQ'D TO INSTALL NEWLEAD FLASHING. REINSTALL IN CONT. BEAD OF SEALANT

4# LEAD FLASHING - FOLD INTOTOP OF STACK MIN. 1"

CONT. SEALANT

PVC VENT EXTENSION(IF NECESSARY)

CONT. SEALANT

ROOF SYSTEM

STRIP-IN PLY

1/2'' COVER BOARD

NOTE:1. PRIME LEAD FLANGE AND SET IN MASTIC

3"

24 GA. STAINLESSSTEELSLEEVE

EXISTING DECKING

POLYISOCYANURATE

MONOLITHIC RESIN FLASHINGAS PRODUCED BY THE MEMBRANEMANUFACTURERROOF SYSTEM

GRANULAR SURFACEDTRAFFIC PAD 2" LARGERTHAN SUPPORTSET PAD IN FULL BED OF FLASHING CEMENT

ADJUSTABLE HEIGHT PIPE SUPPORTADHERE TO TRAFFIC PAD W/ SEALANT

3" = 1'-0"PIPE SUPPORT8

LB4

NOTE:1. DISCONNECT, RAISE AND RECONNECT EXISTING GAS LINES, ELECTRICAL LINES, ETC.

2. SPACE PIPE SUPPORTS @ 8'-0" O.C.

AS REQ'D TO ACCOMMODATE HEIGHT OF PIPE SUPPORT.

3. PROVIDE PIPE SUPPORTS WITHIN 12"-18" OF CORNERS AND/OR TEE INTERSECTIONS

4. PROVIDE PIPE RETAINER BRACKETS (NOT SHOWN)

EXISTING STRUC. CONC. DECK

TRT'D WD. BETWEEN DRAINBOWL AND DECK

EXIST. UNDERDECK CLAMP

1/2'' COVER BOARD

MEMBRANE BASE PLYMEMBRANE CAP SHEET

MEMBRANE STRIP-IN PLY

1/2"/FT. TAPERED POLYISOCYANURATE SUMP W/ 2'' STARTING THICKNESS(SEE PLAN VIEW FOR OVERALL SIZE)

36"X 36" LEAD SHEET FLASHINGDRAIN CLAMPING RINGNEW DRAIN STRAINERPOLYISOCYANURATE1/2" COVER BOARD

3'-0"

3.5"

3" = 1'-0"PRIMARY ROOF DRAIN9

LB4

NOT TO SCALEROOF DRAIN - PLAN VIEWA

slsl

slsl

6'-0"TYP. ALL SIDES

1/2"/FT. TAPEREDSUMP

CRICKET

NOTE:1. REPLACE MISSING OR DAMAGED COMPONENTS W/ NEW CAST IRON COMPONENTS

2. REPLACE ALL PLASTIC / NONMETAL COMPONENTS W/ NEW CAST IRON COMPONENTS

3. RAISE OR LOWER DRAIN BOWL AS REQ'D TO MATCH HEIGHT SHOWN BELOW

4. LEAD SHEET FLASHING - PRIME ALL SURFACES AND SET IN FULL BED OF MASTIC

EXIST. DRAIN LINE - MODIFY AS REQ'D TO ACCOMMODATE CHANGE IN DRAIN BOWL ELEVATION

DOWNSPOUT

24 GA. GALV. SPLASH PANADHERE TO TRAFFIC PAD W/ SEALANT

GRANULAR SURFACEDTRAFFIC PAD 2" LARGERTHAN SPLASH PAN

24 GA. X 1" GALV.STRAP POP-RIVETTO DS AND SPLASH PAN

SET PAD IN FULL BED OF FLASHING CEMENT

3" = 1'-0"SPLASH PAN7

LB4

24 GA. GALV. 1'' TALLRIBS SOLDERED TOSPLASH PAN

NOT TO SCALEPLAN VIEWA

24 GA. GALV. SPLASH PANADHERE TO TRAFFIC PAD W/ SEALANT

30"

12"

18"

TRAFFIC PAD

NOT TO SCALEISOMETRICA NOT TO SCALE

PLAN VIEWC

24 GA. GALV. SPLASH PANADHERE TO TRAFFIC PAD W/ SEALANT

TRAFFIC PADGRANULAR SURFACED

ROOF LINE

PROVIDE 45° BREAK @ BACKOF SPLASH PAN AS REQ'D TOFIT TIGHT AGAINST CANT STRIP

LINE OF CANT / BASE FLASHING

3" = 1'-0"HOT STACK6

LB43" = 1'-0"ROOF HATCH5

LB4

EXISTING FLUE EXTEND AS

24 GA. GALV. VENT BASEFULLY SOLDER JOINTS WATERTIGHT

EXISTING

1/2'' COVER BOARDROOF SYSTEMSTRIP-IN PLYCONT. SEALANT

4"1/2"MIN.

24 GA. GALV. UMBRELLAFULLY SOLDER JOINTS WATERTIGHT

STAINLESS STEEL CLAMPINGDRAW BAND

CONT. SEALANT

NECESSARY

8''-M

IN.

2"-M

IN.

NOTE:1. PRIME VENT BASE

FIELD VERIFY 1" MIN. ALL SIDES

FLANGE, SET IN MASTIC AND NAIL AT 3" O.C. - STAGGERED

POLYISOCYANURATE

1/2'' COVER BOARDROOF SYSTEM

BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY1/4'' COVER BD.

CANT STRIP

POLYISOCYANURATE

POLYISOCYANURATE

ANCHOR TOP OF BASE FLASHING

EXIST. ROOF HATCHANCHOR TO BLK'G @ 12'' O.C.

8''-M

IN.

DECKING

EXISTING DECKING

COVER BD. ANCHOR TO DECK W/TRT'D WD. BLK'G TO MATCH HT. OF

APPROPRIATE FASTENERS @ 12'' O.C. COVER BD. ANCHOR TO DECK W/TRT'D WD. BLK'G TO MATCH HT. OF

APPROPRIATE FASTENERS @ 6'' O.C.

3" = 1'-0"SKYLIGHT10

LB4

EXTENSION PROVIDE TRT'D 2X CURB

1/2'' COVER BOARDROOF SYSTEM

BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY1/4'' COVER BD.

CANT STRIP

MIN. 8'' FLASHINGHEIGHT TAPERED POLYISO

(THICKNESS VARIES)

POLYISOCYANURATE

EXIST. METAL DECK

EXIST. CURB

EXIST. SHEATHING

8"-M

IN.

3'' POLYISOCYANURATE INSULATION ADHERED

2X4'S W/ JOIST HANGERS @ 24'' O.C.

SELF-ADHERING UNDERLAYMENT

3/4'' PLYWOOD NAILED @ 8'' O.C.

3"

SCREWS W/ NEOPRENE WASHERS@ 16'' O.C.

24 GA. GALV. CURB COVERPROVIDE POSITIVE DRAINAGE

TO BOTTOM OF PLYWOOD.

NOTE:1. EXTEND EXISTING CURB W/ TRT'D 2X BLK'G AND SIMPSON "A24" ANGLES, OR APPROVED EQUAL,

SPACED AT 12" O.C.

12/21/2012DATE:

SHEET:

LB4OF

6

PCCCHECKED BY:

CANNON J.DRAWN BY:

1.

REVISION SCHEDULE:

ISSUE FOR BID 12/21/122.3.4.5.6.7.

hollongroup, llc

+hg c

+cannon

ROOFING DETAILS

UT

HE

ALT

H S

CIE

NC

E C

EN

TER

at S

AN

AN

TON

IOR

EP

LAC

EM

EN

T of

Roo

f at

DO

LPH

BR

ISC

OE

JR

. LIB

RA

RY

RO

OF

San

Ant

onio

, Tex

as 7

8229

Page 6: OWNER: THE BOARD OF REGENTS THE ... - UT Health San Antoniouthscsa.edu/facilities/bids/files/rfb745-14-9803/... · san antonio, texas 78284-7957 roofing consultants: hollon+cannon

NOTE:1. SEE 1/LB5 FOR COPING JOINT INFORMATION2 SEE 2/LB5 FOR COPING CORNER JOINT INFORMATION

1/2'' COVER BOARD

ROOF SYSTEM

BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY1/4'' COVER BOARD

CANT STRIP

SCREWS W/ NEOPRENE WASHERS@ 16'' O.C.

TAPERED POLYISO.(THICKNESS VARIES)

CONTINUOUS

COPING

1'' STANDING SEAM

1'' SELF-ADHERING

COPING

NOT TO SCALECOPING JOINT1

LB5

(FILL SEAM W/ SEALANT)

NOT TO SCALECOPING CORNER JOINT2

LB5

CLEAT

COPING

CONTINUOUS CLEAT

1'' STANDING SEAM

NOT TO SCALEEXPLODED VIEWA NOT TO SCALE

SECTIONB

UNDERLAYMENT

1" STANDING SEAMPER DETAIL 1B/LB5

EQ.

EQ.

EQ.

4"

24 GA. PRE-FINISHED COPING

1'' STANDING SEAM PER DETAIL 1/LB5

POLYISOCYANURATE

EXIST. CONC. PARAPET

2X TRT'D WD. STUDS @ 16'' O.C.FILL BETWEEN STUDS W/ BATT INSUL.

22 GA. GALV. CONT. CLEAT

1/4" COVER BOARD OVER TOP OF PARAPET

24 GA. PRE-FINIHSED FASCIA

22 GA. GALV. CONT. CLEAT

24 GA. PRE-FINIHSED FASCIA

22 GA. GALV. CONT. CLEAT 2"

3/4"

3/4"

3/4" PLYWOOD

EXIST. STRUC. CONC. DECK

3/4" PLYWOOD

3" = 1'-0"PARAPET7

LB5

8"-M

IN.

3/4" PLYWOODPROVIDE 1/2"/FT. SLOPE

SELF-ADHERING UNDERLAYMENT

2x''a'' - TYP

SEALANT

TYP''a''

CLOSED CELLBACKER ROD

MASONRY

NOT TO SCALECONTROL JOINT3

LB5

3'' = 1'-0''SECTIONA 3'' = 1'-0''

ELEVATION @ COPINGB

4"

SECTION "A"

CONTROL JOINT

EXTEND CJ 4'' MIN.BELOW COPING

24 GA. PRE-FINISHEDCOPING

EXIST. PARAPETPANEL

3" = 1'-0"EXIST. FALL PROTECTION ANCHOR4

LB5

EXISTING STEEL ANCHORSCRAPE, PRIME AND PAINTEXPOSED PORTION OF STEEL

1/2" COVER BOARD

EXISTING DECKING

POLYISOCYANURATE

MONOLITHIC RESIN FLASHINGAS PRODUCED BY THE MEMBRANEMANUFACTURERROOF SYSTEM

NOTE:1. REMOVE ASPHALTIC CONTAMINATES FROM

PENETRATION PRIOR TO INSTALLATION OF RESIN FLASHING

3" = 1'-0"GUTTER5

LB5

6" 3/4"

4''1/2"MIN.

3"1/

2"

1/2'' COVER BOARDMEMBRANE BASE PLY

MEMBRANE CAP PLYMEMBRANE STRIP-IN PLY

POLYISOCYANURATE

1"5"

24 GA. PRE-FINISHED EDGE METAL

12 GA. x 1" GALV. GUTTER STRAP

24 GA. PRE-FINISHED GUTTER

5-1/2'' WIDE TRT'D WD. BLK'GANCHORED TO EXISTING BLK'G@ 12'' O.C. - STAGGERED TOP OF BLK'G SHALL MATCH TOPOF COVER BOARD1/

2"

5"x5" 24 GA. PRE-FINISHED DOWNSPOUT

@ 30'' O.C.

EXIST. METAL DECK

3" = 1'-0"WALL FLASHING6

LB5

8"-M

IN.

EXISTING STRUC. CONC. DECK

POLYISOCYANURATE

1/2'' COVER BOARD

ROOF SYSTEMCANT STRIP

24 GA. PRE-FINISHED COUNTERFLASHING

SCREWS @ 16'' O.C.24 GA. PRE-FINISHED RECEIVER

DRIVE-PINS W/ NEOPRENE WASHERS@ 16'' O.C.

CONT. SEALANTEXIST. CONC. WALL

BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY1/4'' COVER BD.

12 GA. x 1'' GALVANIZED TERM BARANCHOR @ 12'' O.C.

1"1"

3"

TAPERED POLYISO.

POLYISOCYANURATE

EXIST. CONC. PARAPET

3" = 1'-0"PARAPET8

LB5

4" 1/2''-MIN.

24 GA. GALV. SCUPPER SLEEVESOLDER ALL JOINTS WATERTIGHT

1/2'' COVER BOARDROOF SYSTEM

1/4'' COVER BOARD2X TRT'D WD. CANT (@ SCUPPER ONLY)

4"3"

IN CONT. BED OF SEALANT24 GA. PRE-FINISHED CLOSURE PLATE SET

MODIFY EXISTING PARAPET AS REQ'DTO ACCOMMODATE NEW SCUPPER ELEVATION

2''

4"-M

IN.

EXIST. CONC. PARAPET

FASTENER W/ NEOPRENE WASHERS@ EA CORNER

DRIVE-PINS W/ NEOPRENE WASHERS

AND DIMENSIONS(MATERIAL TO BE REMOVED SHOWN DASHED)

1-1/2"

2"

NOTE:1. PARAPET PER DETAIL 7/LB52. SCUPPER FLOW LINE SHALL BE 2" ABOVE

EDGE OF PRIMARY DRAINAGE DEVISE

NOT TO SCALEELEVATION - CLOSUREA

2'' SEE SCHEDULE 2"

2"4"

2"

NOT TO SCALEISOMETRICB

EXIST. STRUC. CONC. DECK

TRT'D WD. BLK'G TO MATCH HT. OF INSULATION ANCHOR TO DECK@ 6'' O.C.

FIEL

DV

ERIF

Y

NEW

SCUPPER SIZES

SCUPPER DIMENSIONS

4" x 18"

EXIST. CONC.PANEL

12/21/2012DATE:

SHEET:

LB5OF

6

PCCCHECKED BY:

CANNON J.DRAWN BY:

1.

REVISION SCHEDULE:

ISSUE FOR BID 12/21/122.3.4.5.6.7.

hollongroup, llc

+hg c

+cannon

ROOFING DETAILS

UT

HE

ALT

H S

CIE

NC

E C

EN

TER

at S

AN

AN

TON

IOR

EP

LAC

EM

EN

T of

Roo

f at

DO

LPH

BR

ISC

OE

JR

. LIB

RA

RY

RO

OF

San

Ant

onio

, Tex

as 7

8229

Page 7: OWNER: THE BOARD OF REGENTS THE ... - UT Health San Antoniouthscsa.edu/facilities/bids/files/rfb745-14-9803/... · san antonio, texas 78284-7957 roofing consultants: hollon+cannon

3" = 1'-0"SMALL DECK REPAIR1

LB6

EXIST. STRUC. CONC. DECK

POLYISOCYANURATE

10 GA. GALV. STEEL PLATEANCHOR TO DECK AT EA. CORNER

1/2'' COVER BOARDROOF SYSTEM

12''-MAX.

4" - TYP.

3" - TYP. DRIVE-PINS W/ NEOPRENE WASHERS @ EA. CORNERFILL VOID W/ BATT INSULATOIN24 GA. PRE-FINISHED CLOSURE

1/2'' COVER BOARD

ROOF SYSTEMMONOLITHIC RESIN FLASHING

3" = 1'-0"PARAPET2

LB6

TAPERED POLYISO. (THICKNESS VARIES)

POLYISOCYANURATE

EXIST. STRUC. CONC. DECK

SCREWS W/ NEOPRENE WASHERS@ 16'' O.C.

24 GA. PRE-FINISHED CONT. CLEAT

24 GA. PRE-FINISHED EXP. JT. COVER

SELF-ADHERING UNDERLAYMENT

SCREWS @ 16'' O.C.

24 GA. PRE-FINISHED RECEIVER

DRIVE-PINS W/ NEOPRENE WASHERS@ 16'' O.C.

CONT. SEALANT

EXIST. STEEL SUPPORT / ANCHORPLATE - SCRAPE, PRIME AND PAINT

EXIST. PARAPET

1" 2" 1"

3/4" PLYWOOD

FLEXIBLE VAPOR RETARDERW/ COMPRESSIBLE INSUL.

4"X6" CONT. STL. ANGLE ANCHORED TO CURB AND

2X TRT'D WD. CURB AS REQ'D TO PROVIDE

DECK @ 24'' O.C. STAGGERED

FLASHING HT.

4"

3"

3'' = 1'-0''ELEVATION @ SUPPORT ANCHOR TO WALLA

EXPANSION JOINT COVER / CLEAT

FIELDCONT. SEALANT BEADSURFACE MOUNTED RECEIVER

COUNTERFLASHING

MOD. BIT. BASE FLASHING

ROOF LINE

SURFACE MOUNTED RECEIVER

1/2"TYP.

EXPANSION JOINT COVER / CLEAT

STEEL PLATE / ANCHOREXIST. PARAPET

2/LB

6

4/LB

3

NOTE:1. LOWER FLASHING AT POST CONNECTION AS SHOWN.2. PROVIDE RESIN MEMBRANE FLASHING AT BASE FLASHING

LESS THAN 8" IN HEIGHT

RESIN MEMBRANE FLASHING

2"

1/2"TYP.

2" 44 3"

MONOLITHIC RESIN FLASHING

EXIST. CONC. DECK

MEMBRANE BASE PLYBACKER ROD AND SEALANT

1/4"-MAX

EXIST. WINDOW

3" = 1'-0"FLASHING @ WINDOW3

LB6

NOTE:1. FLASHING SHALL NOT BLOCK WINDOW WEEP SYSTEM

2"

3" = 1'-0"FLASHING @ ROOF EDGE4

LB6

MONOLITHIC RESIN FLASHINGMEMBRANE BASE PLY

EXIST. CONC. DECK

2. EXTEND MEMBRANE BASE PLY BELOW EDGE OF WINDOW

12/21/2012DATE:

SHEET:

LB6OF

6

PCCCHECKED BY:

CANNON J.DRAWN BY:

1.

REVISION SCHEDULE:

ISSUE FOR BID 12/21/122.3.4.5.6.7.

hollongroup, llc

+hg c

+cannon

ROOFING DETAILS

UT

HE

ALT

H S

CIE

NC

E C

EN

TER

at S

AN

AN

TON

IOR

EP

LAC

EM

EN

T of

Roo

f at

DO

LPH

BR

ISC

OE

JR

. LIB

RA

RY

RO

OF

San

Ant

onio

, Tex

as 7

8229

Page 8: OWNER: THE BOARD OF REGENTS THE ... - UT Health San Antoniouthscsa.edu/facilities/bids/files/rfb745-14-9803/... · san antonio, texas 78284-7957 roofing consultants: hollon+cannon

L3

12/21/2012DATE:

SHEET:

S11

DRWCHECKED BY:

MMDRAWN BY:

1.

REVISION SCHEDULE:

ISSUE FOR BID 12/21/122.3.4.5.6.7.

hollongroup, llc

+hg c

+cannon

STRUCTURAL PLAN

UT

HE

ALT

H S

CIE

NC

E C

EN

TER

at S

AN

AN

TON

IOR

EP

LAC

EM

EN

T of

Roo

f at

DO

LPH

BR

ISC

OE

JR

. LIB

RA

RY

RO

OF

San

Ant

onio

, Tex

as 7

8229

C:\Users\marc\Desktop\0Jobsnew\6852 UTHSC Library Fall Arrestors\6852 S-1.dwg, 12/21/2012 9:47:47 AM, marc,DWG To PDF.pc3

Page 9: OWNER: THE BOARD OF REGENTS THE ... - UT Health San Antoniouthscsa.edu/facilities/bids/files/rfb745-14-9803/... · san antonio, texas 78284-7957 roofing consultants: hollon+cannon

Project Manual  

for the 

 

UNIVERSITY OF TEXAS  

HEALTH SCIENCE CENTER AT SAN ANTONIO 

 

Replacement of the Dolph Briscoe Jr. Library Roof   

December 21, 2012 

 WORK REQUEST NO. 00275239‐002 

SERVICE ORDER NO. SO13‐022 

 

             

12885 Research Blvd., Suite 210B Austin, Texas  78750 Ph (512) 300‐0452  

Page 10: OWNER: THE BOARD OF REGENTS THE ... - UT Health San Antoniouthscsa.edu/facilities/bids/files/rfb745-14-9803/... · san antonio, texas 78284-7957 roofing consultants: hollon+cannon

Replacement of the Dolph Briscoe Jr. Library Roof The U.T. Health Science Center at San Antonio

TABLE OF CONTENTS - 1

TABLE OF CONTENTS - DIVISION 01 THRU 26 SECTION TITLE PAGE NO. DIVISION 01 - GENERAL REQUIREMENTS SECTION 01 1100 00 - SUMMARY OF THE WORK 01 1100 00-1 THRU 4 SECTION 01 2200 00 - UNIT PRICES 01 2200 00-1 THRU 2 SECTION 01 3100 00 - PROJECT MANAGEMENT AND COORDINATION 01 3100 00-1 THRU 6 SECTION 01 3300 00 - SUBMITTAL PROCEDURES 01 3300 00-1 THRU 5 SECTION 01 4000 00 - QUALITY REQUIREMENTS 01 4000 00-1 THRU 2 SECTION 01 4200 00 - REFERENCE STANDARDS 01 4200 00-1 THRU 3 SECTION 01 5000 00 - TEMPORARY FACILITIES AND CONTROLS 01 5000 00-1 THRU 4 SECTION 01 6100 00 - PRODUCT REQUIREMENTS 01 6100 00-1 THRU 2 SECTION 01 7329 00 - CUTTING AND PATCHING 01 7329 00-1 THRU 3 SECTION 01 7800 00 - CLOSEOUT PROCEDURES 01 7800 00-1 THRU 5 DIVISION 02 THRU 05 - NOT USED DIVISION 06 - WOODS AND PLASTICS SECTION 06 1050 00 - ROOF CARPENTRY 06 1050 00-1 THRU 5 DIVISION 07 - THERMAL AND MOISTURE PROTECTION SECTION 07 0151 00 - PREPARATION FOR RE-ROOFING 07 0151 00-1 THRU 6 SECTION 07 5216 00 - MODIFIED BITUMEN ROOF SYSTEM 07 5216 00-1 THRU 12 SECTION 07 5220 00 - ROOFING INSTALLER’S WARRANTY 07 5220 00-1 THRU 2 SECTION 07 5600 00 - FLUID APPLIED FLASHING AND MEMBRANE 07 5600 00-1 THRU 7 SECTION 07 6200 00 - FLASHING AND SHEET METAL 07 6200 00-1 THRU 9 SECTION 07 7200 00 - ROOF ACCESSORIES 07 7200 00-1 THRU 3 SECTION 07 7900 00 - JOINT SEALERS 07 7900 00-1 THRU 4 DIVISION 09 THRU 22 - NOT USED DIVISION 23 - MECHANICAL SECTION 23 0530 00 - MECHANICAL PROVISIONS 23 0530 00-1 THRU 9 DIVISION 24 THRU 25 - NOT USED DIVISION 26 - ELECTRICAL SECTION 26 0530 00 - ELECTRICAL PROVISIONS 26 0530 00-1 THRU 3 END OF TABLE OF CONTENTS