Building Science Air Flow Control John Straube, Ph.D., P.Eng presented by www.buildingscience.com Overview of Presentation Why control airflow? Vapor flow? Review of Driving Forces Air Barrier Systems – Functions + Requirements Airflow Within Enclosures – convective loops, windwashing, pumping Air Leakage Condensation – Control Strategies Tall Buildings Airflow Control No. 2/79 Building Science Airflow Control: Why 1. Comfort and Health Drafts Odors, particles, gases 2. Moisture control air leakage condensation 3. Energy Heat transferred with air 4. Sound 5. Required by some codes If you can’t enclose air, you can’t condition it Airflow Control No. 3/79 Building Science Airflow Control: What? Air flow through enclosure – Code requirement? Air flow within enclosure – Air loops inside enclosure – Air loop from interior and back – Air loop from exterior and back Therefore, CONTROL – = Limit or eliminate air flow through and within Building Science Airflow Control No. 4/79

Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Building Science Air Flow Control

John Straube, Ph.D., P.Eng

presented by www.buildingscience.com

Overview of Presentation

•  Why control airflow? Vapor flow? •  Review of Driving Forces •  Air Barrier Systems

– Functions + Requirements •  Airflow Within Enclosures

– convective loops, windwashing, pumping •  Air Leakage Condensation

– Control Strategies •  Tall Buildings

Airflow Control No. 2/79

Building Science

Airflow Control: Why

1.  Comfort and Health –  Drafts –  Odors, particles, gases

2.  Moisture control –  air leakage condensation

3.  Energy –  Heat transferred with air

4.  Sound 5.  Required by some codes

If you can’t enclose air, you can’t condition it

Airflow Control No. 3/79

Building Science

Airflow Control: What?

•  Air flow through enclosure – Code requirement?

•  Air flow within enclosure – Air loops inside enclosure – Air loop from interior and back – Air loop from exterior and back

•  Therefore, CONTROL – = Limit or eliminate air flow through and within

Building Science Airflow Control No. 4/79

betsypettit
Typewritten Text
Straube © buildingscience.com 1 of 19
betsypettit
Typewritten Text
betsypettit
Typewritten Text
betsypettit
Typewritten Text
betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
betsypettit
Typewritten Text
Page 2: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Driving Forces

•  1. Wind Pressures •  2. Buoyancy (or stack effect) •  3. HVAC

Building Science Airflow Control No. 5/79

Driving Forces

Wind Effect Stack Effect Combustion and Ventilation

Airflow Control No. 6/79

Building Science

1. Wind

•  Peak loads are high (>1000 Pa/20 psf) •  Average pressures much lower (<50 Pa) •  Wind Pressure Increases with Height

–  low-rise average pressure about 5 Pa –  twenty story building about 40 Pa on normal

day

Airflow Control No. 7/79

Building Science

•  Pressure on windward side •  Suction on lee and sidewalls

Wind Pressures / Flow Patterns

Common roof uplift failure

Air leaks

out

Airflow Control No. 8/79

Building Science

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 2 of 19
Page 3: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Wind Flow Patterns

Wind speed increases

with height

Airflow Control No. 9/79

Building Science

Pressure Distribution on Face

Peak Suctions at Sides +

Airflow Control No. 10/79

Building Science

Wind Pressure Distribution

Plan View

ΔP

Wind Direction

Airflow Control No. 11/79 Building Science

2. Stack Effect: Cold Weather

•  Hot air rises •  Tall Building in Winter

= Heavy Balloon

+

Airflow Control No. 12/79

Building Science

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 3 of 19
Page 4: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Stack Effect: Cold Weather

•  “Perfect” Building equally leaky everywhere

•  Neutral Pressure Plane at mid-height

+

NPP Air flows in at bottom

Air flows out at top

Airflow Control No. 13/79

Building Science

Stack Effect: Warm Weather

•  “Perfect” Building equally leaky everywhere

•  Neutral Pressure Plane at mid-height

+

NPP Air flows out at bottom

Air flows in at top

Airflow Control No. 14/79

Building Science

Stack Effect

•  When cold (20 F) outside – About 4 Pa per storey (10’) of height

•  When hot (95 F) outside – About 1.5 Pa per storey (10’) of height

•  Result – Revolving doors – We suck air from below in cold weather

Airflow Control No. 15/79

Building Science

3. HVAC Pressurization

•  More airflow forced into building than sucked out of building = Pressurization

+

Fan

Depends on size of fans, leakiness of

enclosure, etc.

Airflow Control No. 16/79

Building Science

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 4 of 19
Page 5: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

De-Pressurization

•  More airflow forced out of building than forced into building = De-Pressurization

Fan, Furnace, etc

Airflow Control No. 17/79

Building Science

Driving Forces Summary

•  Wind – Taller buildings see high pressures! – 2-10 Pa low bldgs, 30-200+ Pa tall buildings

•  Stack Effect – Pressure increases directly with temperature

difference and height •  HVAC

– Depends on design and operation

Airflow Control No. 18/79

Building Science

Controlling Air Leakage

• Strategy – “Find the holes and plug them”

•  This requires finicky attention to 3-D details.

Airflow Control No. 19/79

Building Science 2008 Typical Air Leakage Points Airflow Control No. 20/79

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 5 of 19
Page 6: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Building Science Airflow Control No. 21/79

Building Science Airflow Control No. 22/79

Rimjoist leakage

Building Science Airflow Control No. 23/79

Rimjoist condensation

Building Science Airflow Control No. 24/79

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 6 of 19
Page 7: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Bigholes

Airflow Control No. 25/79

Building Science

Leakage above ceilings

Airflow Control No. 26/79

Building Science

Bigholes

Problem: Filter

Airflow Control No. 27/79

Building Science Building Science Airflow Control No. 28/79

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 7 of 19
Page 8: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Seal

Partial solution

Solution: Seal

Airflow Control No. 29/79

Building Science 2008

If you can see daylight it is not sealed

Airflow Control No. 30/79

Building Science 2008

Partition-Ceiling

Partition-Wall

Bathtub

Airflow Control No. 31/79

Building Science

Big Air Leakage Points

AHUSheet metal and high-temperature

caulk

Caulk electrical

fixtures to

drywall

Seal HVAC

penetrations

Seal

bottom plate

Seal electricalpenetrations

Seal plumbing

penetrations

Seal and

insulate dropped

soffit

Seal chases

• Ductwork • Partitions • Dropped soffits • Cabinetry

• Ceiling lights • Rimjoists • Plumbing stacks • Attic hatch

Airflow Control No. 32/79

Building Science

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 8 of 19
Page 9: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Building Science Airflow Control No. 33/79

Service distribution causes air leak Fibrous insulation is airfilter

Air Barrier Systems

•  Function: to stop airflow through enclosure

•  ABS can be placed anywhere in the enclosure

•  Must be strong enough to take wind gusts (code requirement)

•  Many materials are air impermeable, but most systems are not airtight

Airflow Control No. 34/79

Building Science

Air Barrier Systems: Requirements •  Continuous

–  primary need, common failure

•  Strong –  designed for full wind load

•  Durable –  critical component - repair, replacement

•  Stiff –  control billowing, pumping

•  Air Impermeable –  (may be vapour permeable)

Building Science .com Airflow Control No. 35/79

Air Barrier Requirements

•  Air impermeability – Material: 0.02 lps/m2 @ 75 Pa – Component: 0.2 lps/m2 @ 75 Pa – Building: 2.0 lps/m2 @ 75 Pa

•  Building requirement most important for energy, interior RH, IAQ

•  Component requirement may matter for air leakage condensation control

Airflow Control No. 36/79

Building Science 2008

0.004 cfm / ft2 at 0.3” wg

0.04 cfm / ft2 at 0.3” wg

0.4 cfm / ft2 at 0.3” wg

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 9 of 19
Page 10: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Building Science Airflow Control No. 37/79

•  Cellulose in not an air barrier

•  DensePack (>3.5 pcf) can slow airflow

•  Improves horrible buildings, does not achieve good or great

Airflow Control No. 38/79

Building Science

Building Science Airflow Control No. 39/79

Exterior Air Barrier

Poly can be (?) an air and vapour barrier But BEWARE Air Conditioning Definitely not in South

Airflow Control No. 40/79

Building Science 2008

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 10 of 19
Page 11: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Use drywall, framing members •  Seal with sealant, gaskets, etc. • Is stiff, strong • Often easier to ensure quality • Widely applicable to all forms of commercial, residential • Allows choice of vapor permeance

The Airtight Drywall Approach

Airflow Control No. 41/79

Building Science

Airflow Within Enclosures

More than just air barriers!

1. Convective Loops

2. Wind washing

3.  Pumping

These can cause comfort, condensation, and energy problems

Airflow Control No. 42/79

Building Science

Convective Loops

Hot air = light

Cold air = heavy

•  Gaps in batt insulation on both sides

Batt

Outside

Inside A common performance problem

Air gaps

Airflow Control No. 43/79

Building Science

Steel studs are even “better”

Hot air = light

Cold air = heavy

•  Gaps in batt insulation on both sides

• hard to fill steel studs Batt Air gaps

Hot

Cold

Airflow Control No. 44/79

Building Science

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 11 of 19
Page 12: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Internal Stack Effect Cold Weather

Hot air = light

Cold air = heavy

Result: Air Flow

•  Gaps in batt insulation on both sides

•  closed circuit

•  energy cost

•  cold surfaces

Airflow Control No. 45/79

Building Science Airflow Control No. 46/79

Building Science

Air movement (Stack Effect)

More Vapor

Cold Weather

Air Flow

Warm Weather

More Vapor

Condensation if more vapour

Cold Surface

Airflow Control No. 47/79 Building Science 2008

Air Barrier

Windwashing

•  Need some airtightness outside air permeable insulation

•  Sealed housewrap, attached building paper •  Sheathing sealed with tape

– both OSB and insulated sheathing – high density MFI?

•  High density cavity insulation – some foams, maybe dense cellulose

Airflow Control No. 48/79

Building Science 2008

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 12 of 19
Page 13: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Pressure Distribution

Plan View

ΔP

Airflow Control No. 49/79

Building Science 2008

Pressure Distribution

Plan View

ΔP

Airflow Control No. 50/79

Building Science 2008

Lateral Airflows

Punched Steel Studs This costs

energy, promotes condensation, causes comfort problems

Cold: moldy interior corner or Hot: Condensation on back

Airflow Control No. 51/79

Building Science 2008

Using Exterior Sheathing to Control Wind washing

Airflow Control No. 52/79

Building Science 2008

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 13 of 19
Page 14: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Windwashing Drainage plane not an air barrier as installed

Airflow Control No. 53/79

Building Science 2008

Pumping Airflow and Adhered Membranes

•  Membrane is continuous and airtight but … –  It may not control airflow if not fully adhered or

supported –  E.g. roofing, housewraps, poly

Airflow Control No. 54/79

Building Science 2008

Pumping

Airflow Control No. 55/79

Building Science Building Science .com

56

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 14 of 19
Page 15: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Building Science .com

57

Building Science.com

58

Roof air barrier Deck level vapor control membrane rarely required if closed cell foam used

Fully adhered roof membrane

Building Science .com

59

Non-adhered, vapor permeable =modest performance

www.BuildingScience.com

Supported flexible membrane is better

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 15 of 19
Page 16: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Building Science Airflow Control No. 61/79

Air & Vapor Barrier, Water Barrier

Building Science Airflow Control No. 62/79

Air & Vapor Barrier, Water Barrier

www.BuildingScience.com

Fluid-applied products avoids laps Fully-adhered air-water barrier

www.BuildingScience.com

Vapor Permeable!

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 16 of 19
Page 17: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

www.BuildingScience.com

Closed-cell spray polyurethane foam: ccSPF - Rain control - Air Control - Thermal Control -  Vapor Control

Air sealing around components: e.g., windows and walls other Openings and penetrations

Airflow Control No. 66/79

Building Science .com

Building Science Airflow Control No. 67/79

Complex Air-sealing is often required, especially in retrofit

Building Science.com

Commercial Buildings: Often exterior air barrier is only practical solution

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 17 of 19
Page 18: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Review Air Barrier : Requirements

•  Continuous – primary need, common failure

•  Strong – designed for full wind load

•  Durable – critical component - repair, replacement

•  Stiff – control billowing, pumping

•  Air Impermeable –  (may be vapour permeable)

Airflow Control No. 70/79

Building Science 2008

Air Leakage Testing Air Leakage Testing

betsypettit
Typewritten Text
Building Science Fundamentals Airflow Control June 13-14, 2012
betsypettit
Typewritten Text
Straube © buildingscience.com 18 of 19
Page 19: Overview of Presentation Building ScienceCommon roof uplift failure Air leaks out . ... Cold air = heavy • Gaps in batt . insulation on both sides . Batt Outside Inside A common

Air Leakage Testing Conclusions •  Design, draw and spec a continuous air

barrier! •  Some airtightness on both sides of air

permeable insulation! •  Control driving forces

– pressurization –  temperature (insulated sheathing)

•  Beware flow within enclosures/buildings – compartments, stiff air barriers

Airflow Control No. 74/79