Outreach Energy and Water Efficiency Program

Case study report

JUNE 2013

Page 2: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study
Page 3: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 1

Contents

Further information 2

Summary 3

1 Background 51.1 TheOutreachEnergyandWaterEfficiencyProgram 51.2 Projectaims 5

2 Methodology 72.1 Recruitmentofcasestudyparticipants 72.2 Tools 72.3 Datacollectiontimeline 7

3 Results 113.1 Characteristicsofcasestudyparticipants 113.2 Thermalperformancesimulation 123.3 Airleakagerateandlocation 143.4 Thermographicinspectionofinsulation 163.5 Temperatureandenergymonitoring 173.6 Appliancereplacement 193.7 Householdenergybills 203.8 Costandgreenhousegassavings 233.9 Householdcompositionandbehaviour 243.10 Typeofheatingsystem 253.11 Clientresponsestoenergymonitors 25

4 Findings and recommendations 274.1 Thermalperformancesimulation 274.2 Airleakagerateandlocation 274.3 Insulation 284.4 Temperature 284.5 Appliancereplacement 284.6 Householdenergyuse 284.7 Costandgreenhousegassavings 294.8 Householdcompositionandbehaviour 294.9 Clientresponsestoenergymonitors 29

Appendix A 31Casestudy1 31Casestudy2 37Casestudy3 41Casestudy4 44Casestudy5 49Casestudy6 54Casestudy7 58Casestudy8 62Casestudy9 65Casestudy10 68Casestudy11 70

Page 4: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

2 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Further informationForfurtherinformationonthisreport,pleasecontact:

EnvironmentandSustainableDevelopmentDirectorate

Telephone:132281

Facsimile:62072316

Website:www.environment.act.gov.au/water

©AustralianCapitalTerritory,Canberra2013

Thisworkiscopyright.ApartfromanyuseaspermittedundertheCopyright Act 1968,nopartmaybereproducedwithoutthewrittenpermissionfromCustomerServicesandInformation,EnvironmentandSustainableDevelopmentDirectorate(ESDD),ACTGovernment,GPOBox158,CanberraCityACT2601

Disclaimer:ESDDdoesnotguaranteethatthedataisfreefromerrors.

PublishedbytheACTGovernmentEnvironmentandSustainableDevelopmentDirectorate

AcknowledgementsTheOutreachEnergyandWaterEfficiencyProgramforthesecasestudieswasdeliveredbyenergyefficiencyofficersonbehalfofthefollowingcommunitywelfareorganisations:

BelconnenCommunityService

Communities@Work

NorthsideCommunityService

SocietyofStVincentdePaul

YWCAofCanberra.

AssessorsandretrofittersfromC&JGroupandCoolPlanetprovidedenergyandwaterefficiencyassessments,educationandretrofittingfortheOutreachProgram.StafffromHousingACTcoordinatedtheenergyefficiencyimprovementsonHousingACTproperties.

Prepared byScinergy:theScienceofEnergyEfficiency

EditedbyBiotextPtyLtd,Canberra

The ACT Government is committed to making information, services, events and venues accessible to as many people as possible. If you have difficulty reading a standard printed document and would like to receive this publication on an alternative format – such as large print or audio – please telephone 02 6207 7307.

If English is not your first language and you require the translating and interpreting service please telephone 131 450. If you are deaf or hearing impaired and require the TTY typewriter service please telephone 02 6207 2622.

Page 5: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 3

Summary

BetweenMarchandSeptember2012,Scinergyconducteddiagnosticassessmentsandanalysisonasampleof11low-incomehouseholdsparticipatingintheACTGovernment’sOutreachEnergyandWaterEfficiencyProgram.

TheaimsoftheprojectweretocollectandanalysedatatodeterminewhethertheOutreachProgramisimprovinghouseholdenergyefficiency,andtoinformandimprovepolicyandprogramimplementation.Theprojectincluded:

• analysingthethermalperformanceofthebuildingenvelopeforeachcasestudyhouse

• predictingtheeffectivenessofproposedretrofitsforspecifichousesusingthermalperformancesimulations(theoreticalmodelling)

• measuringtheactualtemperature,airleakageandenergyuseineachhousebeforeandafterreplacingappliances,retrofittingandeducatingthehousehold

• determiningtheeffectivenessofbuildingenveloperetrofitsandhouseholdappliancereplacement

• comparingthepredictedresultswiththeactualresults.

Overall,thecasestudiesshowthattheOutreachEnergyandWaterEfficiencyProgramisassistinglow-incomehouseholdstoimprovetheenergyefficiencyoftheirhomes,reducetheirenergyconsumption,reducetheirenergybillsandcontributetoreducinggreenhousegasemissions.

Comparisonofwinterenergybillsfrom2011and2012showsthat9outof11casestudyhomesreducedtheirenergyconsumptionandsavedmoneyontheirbillsasaresultofparticipatingintheOutreachProgram.

Keyresultsrecordedacrossallcasestudyhomeswere:

• anaverage22%reductioninenergyuseinthewinterquartercomparedwiththepreviousyear,madeupof

– 33%reductioninelectricityconsumptioninthewinterquartercomparedwiththepreviousyear

– 5.9%reductioningasconsumptioninthewinterquartercomparedwiththepreviousyear

• anaverage$270.60netdollarsavingperhouseholdinthewinterquarter

• atotalreductionof18.44tonnesofcarbondioxideequivalent(CO2-e)inthewinterquarter.

Oftheeightcasestudyhomesthatunderwentthermalmodelling,allincreasedtheirenergystarratingafterretrofitting.

Whenconsideringcost-effectiveness,draughtsealingwasconsistentlythemosteffectiveretrofitmeasure.Insulationandheavydrapeswithpelmetsalsosignificantlyreducedenergyuseandincreasedcomfortincasestudyhomes.

Datafromfourcasestudyhomesshowedthatreplacingold,inefficientrefrigeratorswithnewmodelscanhalvetheenergyusedforrefrigeration.

Theprojectalsohighlightstheimportanceofbehaviourinthecontextofenergyreductions.

RefertoSection4‘Findingsandrecommendations’formoreinformation.

Page 6: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

4 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Page 7: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 5

1 Background

1.1 The Outreach Energy and Water Efficiency ProgramTheOutreachEnergyandWaterEfficiencyProgramassistslow-incomehouseholdsintheACTtoimprovetheenergyandwaterefficiencyoftheirhomes,reducetheirenergyandwaterconsumption,reducetheirenergyandwaterbills,andcontributetoreducinggreenhousegasemissions.TheprogramhasbeendevelopedbytheACTEnvironmentandSustainableDevelopmentDirectoratewithabudgetof$7.8millionoverfouryearstoJuly2015.

Theprogramprovideseligiblelow-incomehouseholdswithsomeorallofthefollowingassistance:

• ahomeenergyefficiencyassessmentandeducation

• newenergy-efficientandwater-efficientappliancestoreplaceold,inefficientappliances

• aretrofittoimprovetheenergyefficiencyandwaterefficiencyofhouseholds.

TheOutreachProgramisdeliveredbythefollowingcommunitywelfareorganisations:

• BelconnenCommunityService

• Communities@Work

• NorthsideCommunityService

• SocietyofStVincentdePaul

• YWCAofCanberra.

TheseorganisationsimplementtheprogramthroughtheirexistingclientsandobtainclientreferralsfromnetworkswithinthecommunityservicessectoroftheACT.Eachorganisationhasbeenprovidedwithfundingtodelivertheprogram,includingfundingforanEnergyEfficiencyOfficerineachorganisation.TheroleoftheEnergyEfficiencyOfficeristoidentifyeligiblehouseholdsthatwouldbenefitfromenergy-efficientandwater-efficientappliances,andreferthemforahomeenergyefficiencyassessment,retrofitandeducationsessiondeliveredbyapanelofserviceprovidersfundeddirectlybytheACTGovernment.EnergyEfficiencyOfficerscanalsoreferclientstoHousingACTfordraughtsealingandceilinginsulationtop-ups.

1.2 Project aimsTheaimoftheprojectwastocollectandanalysedatatodeterminewhethertheOutreachProgramisimprovinghouseholdenergyefficiency,andtoinformandimprovepolicyandprogramimplementation.Theprojectincluded:

• analysingthethermalperformanceofthebuildingenvelopeforeachcasestudyhouse

• predictingtheeffectivenessofproposedretrofitsforspecifichousesusingthermalperformancesimulations(theoreticalmodelling)

• measuringtheactualtemperature,airleakageandenergyuseineachhousebeforeandafterreplacingappliances,retrofittingandeducatingtheclient

• determiningtheeffectivenessofbuildingenveloperetrofitsandhouseholdappliancereplacement

• comparingthepredictedresultswiththeactualresults.

Page 8: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

6 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Page 9: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 7

2 Methodology

BetweenMarchandSeptember2012,Scinergyconducteddiagnosticassessmentsandcasestudyanalysison11low-incomehouseholdsparticipatingintheOutreachEnergyandWaterEfficiencyProgramusingan‘assessment–education–retrofit’process.

2.1 Recruitment of case study participantsTobeeligibleforinclusionintheOutreachProgramandthecasestudies,participantshadtobe:

• ACTresidents

• experiencingfinancialhardship

• earninglessthanthemaximumincomelimitasdefinedintheOutreachProgramspecifications.

Participationmayassistinreducingfinancialhardshipassociatedwithhighenergyorwaterconsumptioncosts.

Outreachparticipantswereaskedbythecommunityorganisationsiftheywouldliketotakepartinthecasestudies.Participationinthecasestudieswasentirelyoptional.

ThehousesandclientsselectedwerenewparticipantsintheOutreachProgram,hadenergyusagedataavailableforatleasttheprevious12months,andhadpotentialforavarietyofdifferentretrofitandeducationmeasures.

2.2 ToolsThemethodologywasbasedonthewell-establishedtheorythataninsulatedandairtightenvelopeisthekeytoanenergy-efficientandcomfortablebuilding.Usingvarioustechnologies,datawerecollectedtoassesshowwelleachbuildingwasperforming,prioritiseimprovements,andmeasuretheeffectofchangesonenergyuseandcomfort.Toolsincluded:

• householdelectricity-usemonitors

• applianceelectricity-usemonitors

• temperaturedataloggers

• fandepressurisationtoquantifyandlocateairleakage(seeBox1)

• thermographicinspectionofthebuildingenvelopetolocateinsulationgapsandairleaks

• thermalperformancesimulationofthebuildingtopredictheatingandcoolingloads.ThermalperformancewasmodelledusingBERSPro4.2software(whichisaccreditedundertheAustralianGovernment’sNationwideHouseEnergyRatingScheme[NatHERS])toshowthedifferencebetweenthethermalstartingpoint(initialstarrating)andendpoint(starratingafterretrofitting)ofthecasestudyhouses(seeTable2).

Anecdotalinformationwasalsocollectedatsitevisits.

2.3 Data collection timelineDatawerecollectedoverapproximatelyeightweekstomeasure:

• improvedefficiencyofreplacedappliances

• baselineelectricityconsumptionandtemperatureprofile

• energyconsumptionandtemperaturechangeduetoeducation

• energyconsumptionandtemperaturechangeduetoretrofitting

• qualitativefeedbackandinsightsintobehaviouralchangefromclients.

Page 10: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

8 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Box 1 Measuring air leakageAirleakageistheuncontrolledmovementofairintoandoutofabuilding(infiltration)thatisnotfortheplannedpurposeofexhaustingstaleairorbringinginfreshair(ventilation).Itisdrivenbythreemainforces:

• wind,whichexertsconstantlychangingpressuresonbuildings(highonthewindwardsideandlowontheleewardside,roughly150–1500pascals[Pa]differences)

• thestackeffect,whererisingwarmaircausespressuredifferenceswithinbuildings(lowerpressuresatthetop,higherpressuresnearthefloor,around5–10Padifferences)

• mechanicalheatingandventilationsystems,whichcreatepressuredifferenceswithinbuildingsastheyheat,coolandmoveair(5–10Padifferences).

Airleakagecanaccountfor30%ormoreofabuilding’sheatingandcoolingcosts,asocontrollingairleakageisthemosteffectivewaytoachievedirectenergysavings.InCanberra,typicalairleakageratesareequaltotwocompleteairchangesperhour,whichrepresentsasubstantialamountofenergyandmoney,especiallyinwinter.Uncontrolledairleakagealsocompromisestheeffectivenessofother,moreexpensive,energyefficiencymeasuressuchasnewheatingsystems,windowdressinganddoubleglazing.

Thebestwaytomeasureairleakageistouseablowerdoorandthermalcamera.Theblowerdoorincludesfourcomponents:acalibratedfan,anexpandabledoor-panelsystem,asensitivegaugetomeasurefanflowandbuildingpressure,andtailoredcomputersoftware.Thefanissealedintoanexteriordoorwaywiththedoor-panelsystemandthenusedtodrawairoutofthebuilding,creatingapressuredifferencebetweeninsideandoutside.Thispressuredifferencecausesairfromoutside,athigherpressure,tomoveintothebuildingthroughallthegapsinthebuildingenvelope.Thetighterthebuildingenvelope(fewergapsandcracks),thelessfanspeedisneededtocreateachangeinbuildingpressure.Thepressuregaugeandcomputerareusedtoregulateandrecordtheairflowandpressuredifferences.

Thethermalcameraisusedtolocatetheairleaks:aslongastheairbeingdrawninthroughtheleaksiswarmerorcoolerthantheinsideofthehouse,theareasurroundingtheleakwillchangetemperatureandshowuponthethermalimage.Evenifthereislittletemperaturedifferencebetweeninsideandoutside,aninfra-redscancanstillbeeffective,becausesubfloorspacesaregenerallycooler,androofspacesgenerallywarmer,thantheexternalairtemperature.Thistechniqueallowsyoutofindsignificant,andotherwiseundetectable,leakswithouthavingtoentertherooforfloorspace.Athermalcameracanalsoshowwhereinsulationismissingorhasbeenimproperlyinstalled.

aUSDepartmentofEnergy,OfficeofBuildingTechnology,http://apps1.eere.energy.gov/buildings/publications/pdfs/building_america/26446.pdf

DatawerecollectedfromthehouseholdsaccordingtothefollowingtimelineprovidedbytheOutreachProgramtoEnergyEfficiencyOfficersandserviceproviders:

Week 1: Client referral and baseline appliance data

• EnergyEfficiencyOfficeridentifiesclientwhowouldliketoparticipateinthestudy.

• EnergyEfficiencyOfficerconductsahomeenergyassessmentandinstallsapplianceenergymonitoronappliance(s)tobereplaced.

Week 2: Appliance replacement and installation of energy and temperature monitors

• EnergyEfficiencyOfficerrecordspreviousweek’senergyuseofoldapplianceandfitsenergymonitortonewappliance.

• Scinergyinstallstemperaturedataloggers(twointernal,oneexternal).

• Scinergy/electricianinstallshouseholdelectricity-usemonitor.

• Serviceproviderconductsacomprehensivehomeenergyassessmentandeducationsession,andprioritisesenergyefficiencyimprovementstodetermineretrofitmeasures.

Page 11: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 9

After the Week 2 visit: Thermal performance simulation

• Scinergyassessesthepotentialthermalperformance(predictedheatingandcoolingloadsandstarrating)usingsimulationsoftware.

Week 4: Building envelope testing #1 and education

• Scinergyretrievesapplianceenergymonitorfromnewapplianceandcollectsdata.

• Scinergyconductsairleakagetestingviafandepressurisationandthermographicinspectionofbuildingenvelope.

• Serviceprovidercarriesouteducationalcomponentofprogram,introducesclienttohouseholdenergymonitorandidentifiespotentialenergy-savingbehaviouralchanges.

Week 6: Retrofit

• Serviceprovideroverseesretrofitandinstallationofcurtains(ifrequired).

• Serviceprovidercarriesoutdraught-proofing.

Week 8: Building envelope testing #2 and data collection

• Scinergyretrievestemperaturedataloggersandcollectsresults.

• Scinergydownloadsdatafromhouseholdenergymonitor(monitorleftwithclient).

• Scinergyconductsairleakagetesttomeasureimprovementsachievedthroughretrofit.

After Week 8: Education and quality assurance

• Serviceproviderconductsfinaleducationsession,andchecksthequalityofretrofitandcustomersatisfaction.

Page 12: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

10 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Page 13: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 11

3 Results

Thissectionsummarisestheresultsoftheproject.FulldetailsforindividualcasestudiesarepresentedinAppendixA.

3.1 Characteristics of case study participantsThecharacteristicsoftheparticipatinghouseholdsvariedgreatlyin:

• thesize,age,typeofconstruction,designandorientationofbuildings

• thenumber,ageandeducationlevelofresidents,andtheirinterestinandbehaviourrelatingtoenergyandwaterefficiency.

Sixofthe11householdswereHousingACTresidents,andfivewerehome-owner–occupiers.IntheOutreachProgramasawhole,approximately75%ofparticipantsliveinHousingACTproperties.

Allcasestudyhouseholdshadbetweenoneandthreeresidents,althoughthenumberofpeopleinthehousecouldvaryconsiderablyatanypointintime.Thesevariationsincludednewresidentsmovinginduringthecasestudy,supportstaffpresent(inonehousehold)andhouseholdmembersbeingawayonholidays.

Manyofthecasestudyparticipantsspentconsiderabletimeathomebecauseoftheirfinancialcircumstances.Manywereretired,unemployedorondisabilitysupportpensions.Atleasttwoofthehouseholdshadmemberswithrespiratoryconditionsrelatedtocoldtemperatures,althoughhealthconcernswereself-reported,andmonitoringimprovementsinhealthwasoutsidethescopeofthisproject.

AsummaryofthehouseholdcharacteristicsisprovidedinTable1.

Table 1 Characteristics of case study participants

Case study number

Number of occupants

Type of residence

Financial circumstances

Description

1 3 Owner–occupier

Unemployedfull-timestudent

Motherwithteenagechildren.Twolargelivingareaswithreverse-cycleair-conditioning;centralgasheating.Electricityandgas.

2 1 HousingACT

Disabilitysupportpension

Chroniccardiacandrespiratoryhealthconditions.Gapsarounddoorsandwindows.Participantusesportableelectricresistanceheaterinsteadoftheelectricresistancewallheaterbecauseofitslocation.Electricityonly.

3 1 Owner–occupier

Retired,old-agepension

Participanthaslargewinterheatingbills.In2011,participanthadhealthconcerns,andasecondpersonwaslivinginthehome.Househaselectricheatinginslab.Electricityonly.

4 3 HousingACT

Single-parentpension

Motherofyoungchildrenwithrespiratoryhealthconcerns.Asecondadultmovedinduringthecasestudymonitoring.Extremelycoldhouse,withlimitedsolarheatgainbecauseofhouseorientation,andverydraughty.Electricresistanceheating.Electricityonly.

5 3 Owner–occupier

Disabilitysupportpension

Insulationwasthinandpatchy,andthehousehadpermanentventsineveryroom.Gasheatinginlivingareas.Electricreverse-cyclesystemsinbedrooms.Electricityandgas.

Page 14: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

12 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Case study number

Number of occupants

Type of residence

Financial circumstances

Description

6 2 HousingACT

Singlemotherwithpart-timework

Houseverycoldinwinterandveryhotinsummer.Electricresistancewall-mountedheater.Electricityonly.

7 3 Owner–occupier

Notlisted Housecoldinwinter,hotinsummer.Househadanumberofsignificantairleakagepoints,includingaskylight.Northerlyaspect.Wall-mountedelectricpanelheater.Electricityandgas.

8 3 HousingACT

Notlisted Housecoldinwinterandhotinsummer.Electricheating.Electricityonly.

9 1 HousingACT

Centrelinkpension

Three-storeyapartmentbuiltapproximately50yearsago.Inefficientelectricresistanceheating.Electricityonly.

10 3 HousingACT

Disabilitysupportpension

Threetenantswithdisabilities;1-2staffonsite24hoursperdaywithupto7peoplepresentatanyonetime.Tenantsdonothavedirectcontrolofenergyuseandrelyonstaffmembersforassistance.Gasheating.Electricityandgas.

11 2 Owner–occupier

Disabilitysupportpension

Householdersgetverycoldinwinter.Draughtyhousewithmanypointsofairleakage.Gasheating.Electricityandgas.

3.2 Thermal performance simulationThermalperformanceofthebuildingswasmodelledtoshowthedifferencebetweenthethermalstartingpoint(initialstarrating)andendpoint(starratingafterretrofitting)ofthecasestudyhouses(Table2).Oftheeightcasestudiesthatunderwentthermalmodelling,everyhouseincreaseditsenergystarratingafterretrofitting.

InCanberra’sclimate,a3-starhomeispredictedtorequire387megajoulespersquaremetre(MJ/m2)forheatingandcooling,whichis2.3timesmoreenergypersquaremetrethana6-starhome(165MJ/m2).1

Thedifferencesinmodelledthermalperformanceamonghousesaremainlyduetodifferencesinwindows(orientation,windowdressingsandsizerelativetoroomfloorarea),insulationlevelsandairtightness.Casestudy3,forexample,waswellsealed(withfewceilingpenetrationsorotherairleaks),andhadnorth-facingwindowstothemainlivingareas(allowingpassivesolarheatgainoverwinter),heavydrapestomostwindows,andbothceilingandwallinsulation.Incontrast,casestudies4and5wereextremelyleaky(withpermanentceilingventsineveryroom),andhadlittleopportunityforpassivesolarheatgaintolivingareas,poor-qualitywindowdressings,thinceilinginsulationandnowallinsulation.

TheimportanceofdraughtsealingisoftenunderestimatedinCanberra’sclimate.Thermalperformancemodellingsuggeststhatenergysavingsofapproximately10–20%canbeachievedinsomeofthecasestudyhousesbysealingpermanentceilingpenetrations—arelativelysimpleandinexpensiveretrofitmeasure.Physicalperformancetestingofcasestudyhouses,andstatisticalanalysisofthecorrelationbetweenreductioninairleakageandreductioninenergyuse,suggeststhat,forsomehouses,savingsfromdraughtsealingalonemaybehigherthan20%.

1 SeetheNatHERSat(www.nathers.gov.au)andtheBERSProat(www.solarlogic.com.au/bers-pro)formoreinformationonstarratings.

Page 15: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 13

Table 2 Star ratings of case study houses 1–8 before and after retrofitting

Case study number Star rating pre-retrofit

Star rating post-retrofit

Retrofit measures

1 3.9 4.5 •Draughtsealing•Pelmetstolivingareas

2 2.8 4.2 •Draughtsealing•Curtainsandpelmetstolivingareas

3 5.9 6.5 •Pelmetstolivingareas•Minordraughtsealing•Fillinggapsinceilinginsulation

4 2.9 4.7 •Draughtsealing•Ceilinginsulationtop-up•Wallinsulation

5 2.8 3.4 •Draughtsealing•Ceilinginsulationtop-up•Curtainsandpelmetstolivingareas

6 4.2 5.2 •Majordraughtsealing•Pelmetstolivingareasandbedrooms

7 3.3 4.9 •Draughtsealing•Curtainsandpelmetstolivingareas

8 2.8 3.4 •Draughtsealing•Curtainsandpelmetstolivingareas

Notes: Casestudies9,10and11werenotincludedinthemodellingbecauseofschedulingconstraints.ThermalperformancewasmodelledusingBERSPro4.2software(whichisaccreditedundertheAustralianGovernment’sNationwideHouseEnergyRatingScheme[NatHERS]).Inregulatorymode,energyefficiencyratingsoftwaredoesnotmodelwindowdressings,andstarratingsareexpressedin0.5increments.Forthepurposeofthisproject,thesimulationsoftwarewasruninnon-regulatorymodetomodeltheimpactofchangestowindowdressings,andratingsareexpressedin0.1incrementstogiveabetterindicationofchanges.FurtherdetailsofactualandpredictedheatingandcoolingloadscanbefoundinAppendixA.

Onlyonecasestudyhousehadwallinsulationinstalledduringthestudy.Thisoccurredverylateintheprocessandappearstohavecoincidedwithasignificantchangeinhouseholdcompositionandenergy-usebehaviour,soitisnotpossibletodrawfirmconclusionsabouttheeffectofwallinsulationfromthisstudy.However,wallinsulationiswellrecognisedasbeingextremelyeffectiveinacool,temperateclimate.TheBuildingCodeofAustraliasetsaminimumstandardofR2.8forexternalwallinsulationsystemsinCanberra’sclimatezone.

ThesoftwareprovidesanestimateofcurrentthermalperformanceusingtheNatHERSstarratingschemeandwasalsousedtopredictwhichbuildingenvelopeimprovementswouldbemosteffectiveforeightofthecasestudyhouseholds.Predictedimprovementsvaried:

• Forcasestudy4,withuninsulatedexternalwalls,installinginsulationwaspredictedtoreduceenergyrequirementsforheatingandcoolingby26%.(Althoughwallinsulationwasnotretrofittedtocasestudies5and8,thermalmodellingsuggesteditwouldresultinreductionsinenergyuseofnearly30%forthesehouses.)

• Forhouseswithlarge,inadequatelyfurnishedwindowstolivingareasthatdonotbenefitfrompassivesolarheatgain(casestudies2and7),installingcurtainsandpelmetswaspredictedtoreduceenergyrequirementsby16–19%.

• Forhouseswithmanyceilingpenetrationsandsubstantialairleakage(casestudies2,4,5,6,7and8),draughtsealingwaspredictedtoreduceenergyrequirementsby9–18%.

• Forhouseswiththinorpatchyceilinginsulation,estimatedtobeequivalenttoR2(casestudies4and5),toppinguptheceilinginsulationtoR4waspredictedtoreduceenergyrequirementsby30–40%.

Page 16: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

14 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

3.3 Air leakage rate and locationWhenahouseisdepressurised,airflowsinthroughanycracksorgapsintheinternalbuildingenvelope.Thisaircanoftenbecooler(e.g.airinflowfromsubfloorspacesorshadedwalls)orwarmer(e.g.airfromroofspaces—evenoncoldCanberradays,itdoesnottakemuchsunshinetoheattheairintheroofspacetotemperatureshigherthaninsidethehome).Thisairinflowcancreatetemperaturedifferencesinsidethehomeastheairmovesacrossinternalsurfaces,andcreatedraughts.

Thepresenceofdraughtscanaffectaperson’sperceivedtemperatureofaroom.Draughtscanmakeapersonfeelcoldbyremovingheatfromthebody—whenthedraughtisremoved,theroomcanfeelwarmereventhoughtheactualtemperaturemaybethesame.

Rates of air leakage

Thenumberofairchangesperhouratapressuredifferentialof50pascals(n50)isaninternationallyacceptedstandardforexpressingtherateofairleakageinhomes.Followingtheleadofthe2006UKbuildingstandards,2itissuggestedthathousesintheCanberraclimateshouldaimforann50oflessthan10.Onlytwoofthecasestudyhomesachievedanairleakageratebelow10beforeretrofitting(Image1).Themajorityhadmuchhigherratesofairleakagethatwereseriouslycompromisingtheirenergyefficiencyandcomfort.

Simpledraught-sealingmeasuresreducedtherateofairleakageinninecasestudyhomesbyanaverageof34%.Statisticalmodellingofactualairleakageandenergyconsumptiondatasuggeststhatdraughtsealingaccountsforalmost40%ofenergysavings.TherelationshipbetweenairleakageandenergyuseisdescribedinBox2.

Location of air leaks

Manyoutdatedmeasuresintendedtoimproveventilationandminimisemoisturelevelsandcondensationweremakingthesehousesextremelyleaky,difficulttoheatanduncomfortabletolivein.Airleakageviaceilingpenetrations,suchasunsealedexhaustfans,recessedlights,roofaccessholes,skylightsandpermanentvents,wascommonamongthecasestudyhouses(seeImage2forexamples).Permanentwallvents,openingsinbathroomandlaundrywindows,andgapsbetweenwindowarchitravesandwallswerealsoresponsibleforsignificantleakage.Mostofthesetypesofleakscanbesealedeasilyandcheaply.

PermanentpassiveventilationshouldnotbereliedontocontrolmoisturelevelsormaintainfreshairinCanberrahomes.Instead,activeventilation—mechanicalexhaustfansandthesimpleopeningofwindows—shouldbeusedtoreducemoisturebuild-upintheareaswhereitisgenerated.

Temperaturedifferencescausedbyairleakscanbevisualisedusinganinfra-red,orthermal,camera.Thermalimagescanshowthefingersofblue(createdbycoolerair)ororange(createdbywarmerair)thatoccurnexttoairleaks(Image2).Thesetypesofimagesareusedtohelplocateanddemonstrateairleaks,buttheydonotmeasuretherateofairleakageinparticularlocations

Image 1 Air leakage rates in case study homes before and after draught-sealing Note: Casestudies3and9werenotretestedforairleakageafterdraughtsealingbecausetheywerealreadybelowthetargetlevelof10airchangesperhourat50Pa,andfundswerebetterspentonhomesthatwerefurtherfromthistarget.

2 AirTightnessTestingandMeasurementAssociation,Technical standard L1: measuring air permeability of building envelopes (dwellings),AirTightnessTestingandMeasurementAssociation,Northampton,UK,2010.

Page 17: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 15

Box 2 The relationship between air leakage and energy useScinergy’sexperienceisthatthemostsubstantialreductionsinenergyuseinCanberrahomesoftenoccurafterairleakageisreduced.Oftheninecasestudyhomesthatweretestedforairleakagebeforeandafterretrofitting,eightshowedapositiverelationshipbetweenreductionsinairleakageandreductioninenergyuse,asshowninImageA.

Image A Relationship between reductions in air leakage and reductions in energy use for nine case study homes

Image 2 Thermal images showing common sources of air leakage in case study houses

Page 18: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

16 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

3.4 Thermographic inspection of insulationThermalimagingshowedthatthewallsofmostcasestudyhouseswereuninsulated.Ceilinginsulation,althoughpresent,appearedtobethinorpatchyinsomeofthehouses.Images3and4showexamplesfromtwocasestudyhouses;seeAppendixAformorethermalimages.

Onamild,sunnymorninginMarch(temperature10°Cminimumto20°Cmaximum),theuninsulatedsouth-eastandsouth-westfacingwallsofthemainbedroomincasestudy4wereatapproximately13°C;thethinly,butevenly,insulatedceilingwasat14.5°C.Thebedroomhadbeenheatedovernightbutwasnotheatedatthetimeoftesting.Thishouseisuncomfortablycoldwithoutactiveheatingbecauseofitsinadequateinsulationandlackofpassivesolarheatgain.(seeimage3)

Nowallinsulationwaspresentincasestudy5(asexpectedinahouseofthisage;image4a).Therockwoolinsulationintheceilingwasthinandunevenlyinstalled,causingsignificantfluctuationinceilingtemperaturethroughoutthehouse.Image5bshowsthethinorabsentinsulationattheedgeoftheroofspace(darkorangeareasindicatetheceilingheatingupasaresultofthesunstrikingthenorth-facingroofarea).Image5balsoshowstheupperpartsoftheuninsulatedwallsheatingupasaresultofthesolarheatgainintheroofspace—thiscancontributetosignificantheatbuild-upinsummer.Image5cindicatesthedifferenceintemperaturebetweentheuninsulatedroofaccessholeandtheadjoiningthinlyinsulatedceiling,illustratingthatevenathinlayerofceilinginsulationmakesasignificantdifferencetotherateofheattransfer.

Gapsinceilinginsulationofonly5%equatetoa50%reductionineffectiveness.3Fillinggapsinexistinginsulationcansignificantlyimprovetheenergyefficiencyofahome.

Image 3 Presence and effectiveness of insulation in case study 4

Image 4. Presence and effectiveness of insulation in case study 5

3 USBuildingPerformanceInstitute,Effective R-values for batt insulation,BuildingPerformanceInstitute,Malta,NewYork,2007, www.bpi.org/documents/Yellow_Sheet.pdf.

Page 19: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 17

3.5 Temperature and energy monitoringTemperatureandhouseholdenergyusevariedwiththedesign,age,construction,orientation,numberofwindowsandtypesofwindowdressingsofthecasestudyhouses;thesize,ageandbehaviourofthehouseholds;andtheheatingneedsandmethodsforeachhouse.Therewerealsodifferencesbetweenthecasestudyhousesinthetimingoftheproject(startdatesrangedfromMarchtoJune),therelativetimingofretrofitmeasuresandstepsinthemethod,andtheavailabilityofdatafrommonitoringdevices.Althoughthesevariationswereexpected,theymadeitdifficulttoassesstheimpactofindividualmeasuressuchaseducationsessionsorinstallationofcurtainsandpelmets.

Possibleexplanationsforapparenttrendsorchangesinindividualcasestudiesarebasedoninformalobservationsmadewhilevisitingthehouses.Thesedataprovideinterestinginsightsintodifferenthouseholds,buttheycannotbereliedontosupportorrejecttheretrofitoreducationalmeasures.Fordataloggingoftemperatureandenergyusedatatoprovidemeaningfulresults,the‘assessment–education–retrofit’processneedstobemuchmorecontrolled,andthedatacollectedneedtobemorecomprehensiveanddetailed.

ThetemperaturesexperiencedinsomehousesarewellbelowthelevelssuggestedbytheWorldHealthOrganizationasnecessarytomaintainhumanhealth.4Retrofitmeasurestoimprovethethermalperformanceofsuchhouseshavethepotentialtoresultinsignificantpositivehealthoutcomes.5

Manyofthecasestudyhouseholdswereexperiencingextremelyuncomfortabletemperatures,butthebetterdesignedandinsulatedhomeshadmorestableinternaltemperatures.Althoughnodefinitiveconclusioncanbemadeontherelativeeffectsofretrofitandeducationmeasureswithoutmorecontrolledtestingofthe‘assessment–education–retrofit’process,thefollowingobservationsontemperaturecanbemade:

• Casestudy2showedareductioninenergyuseafterthedraughtsealingandaslightincreaseininternaltemperatures.Thishouseholdmaybeexperiencingmorecomfortableinternaltemperaturesthanwerepossibleinpreviousyears.

• Casestudy4showedadecreaseinelectricityuseafterdraughtsealing,curtainsandceilinginsulation,andtheinternaltemperaturewasmaintained.Electricityuseincreasedafterafourthpersonmovedintothehome.

• Casestudy5showedareductioninelectricityuseandwarmerinternaltemperaturesaftertheretrofit.However,theenergybillsindicatedthattherewasanincreaseinelectricityforthe2012autumnandwinterperiodscomparedwith2011,andadecreaseingasuse.Thisindicatesthatshort-termobservationsmaynotalwayscorrelatewiththelong-termtrendinenergyuse.

• Casestudy6showednochangeinelectricityuse,butinternaltemperaturesincreasedaftertheretrofit.

• Casestudy9showedareductioninelectricityuse,andinternaltemperaturesweremaintained.Billingdataindicatethatthishouseholdmadethemostsignificantsavingsinelectricityfromthewinterof2011towinter2012.

Casestudy2(Image5onnextpage)wasaone-bedroomunitwithneighbourstothenorth,southandabove.Althoughtheunitwaspoorlyorientedandoverglazed,itbenefitedgreatlyfromtheinsulatingeffectsofneighbouringunits.Energyusedecreasedfollowingdraughtsealing,eventhoughinternaltemperaturesweremaintainedorslightlyincreased.InternaltemperaturesinJunewererelativelystableat14–17°Cinthebedroomand17–20°Cinthelivingarea.

Casestudy4(Image6onnextpage)wasasmallhousewithinadequateinsulationandlackofpassivesolarheatgain.Itwashometotwoinfantswithrespiratoryillnessesandhadtemperaturefluctuationsof5–16°Cinthemainlivingareaand8–18°CinthemainbedroomduringJune.Adramaticreductioninenergyuseoccurredbetweenmid-Mayandmid-Julyaftereducation,draughtsealing,curtaininstallationandceilinginsulationtop-up,buthousetemperaturesweremaintainedatverysimilarlevels.Thiswastheonlycasestudyhousetohavewallinsulationretrofitted.Unfortunately,thiswasnotinstalleduntilAugust,coincidingwithCanberra’scoldestweatherandanotheradultmovingintothehouse.Ratherthantheexpectedreductioninenergyuseorincreaseininternaltemperatures,therewasadramaticincreaseinenergyuse.Theincreaseinenergyusedoesnotappeartohavebeenrelatedtoheatingofthemainlivingareaandsuggestssignificantbehaviouralchangesinenergyuseduetothenewresident.

Casestudy6(Image7)wasa15-year-old,two-bedroomunitwithneighbourstothewest,andnorth-facinglivingareas.Thisunitexperiencedatemperaturerangeof15–20°Cinthelivingareaand12–22°CinthebedroominJune.Roomtemperaturesincreasedandelectricityusedecreasedslightlyafterdraughtsealingandeducation.

4 WorldHealthOrganization,Health impact of low indoor temperatures,reportofaWHOmeeting,Copenhagen,11–14November1985,WorldHealthOrganizationRegionalOfficeforEurope,Copenhagen,1987.

5 GGreenandJGilbertson,Warm front, better health: health impact evaluation of the Warm Front Scheme,CentreforRegionalEconomicandSocialResearch,SheffieldHallamUniversity,UK,2008.

Page 20: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

18 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Images5–7showhourlytemperatures(internalandexternal)inrelationtodailyelectricityuseinthreeofthecasestudyhomes,annotatedwiththetimeofsignificantevents.

• The red lineplotstheelectricityusage,whiletheotherlinesshowtheinternalandexternaltemperatures.

• The horizontal axisisthetimelineofeventsanddailymonitoring.

• The vertical axis plotsbothtemperatureandkilowatthours.

ImagesforotherhouseholdscanbefoundinAppendixA.

Image 5. Electricity use and temperature data in case study 2

Tem

pera

ture

(0 C)

1 M

AY

1 JU

NE

5 5

10 10

15 15

20 20

25 25

30 30

0 0

Bedroom temperature External temperature Electricity use

Electricity use

Leakagetest and

education

Post-

test

Tem

pera

ture

(0 C)

5 5

10 10

15 15

20 20

25 25

30 30

35 35

0 0

Electricity use

Draught sealing 2

Draught sealing 1

Living room temperature

Curtainsand

pelmets

Image 6. Electricity use and temperature data in case study 4

Tem

pera

ture

(0 C)

Electricity use (kWh)

50 50

40 40

30 30

20 20

10 10

0 0

Bedroom temperature External temperature Kitchen temperature Lounge temperature Main bedroom temperature Electricity use

1 M

AY

1 JU

NE

1 AU

GUST

1 JU

LYLeakage test andeducation

Draught sealing 1

Wallinsulation

Curtainsand ceilinginsulation

Post retrofit

test

Draught sealing 2

Electricity use

Page 21: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 19

Image 7 Electricity use and temperature data in case study 6Te

mpe

ratu

re (0 C)

Electricity use (kWh)

50 50

40 40

30 30

20 20

10 10

0 0

Bedroom temperature External temperature Living room temperature

Electricity use

1 M

AY

1 JU

NELeakage

testingCeiling

insulationinstalled

Draught sealing 2

Postretrofit test

Educationdraught sealing 1

Electricity use

3.6 Appliance replacement

RefrigeratorsAllfourrefrigeratorsthatwerereplacedweretwo-doorappliances(fridge–freezercombination).Theoldrefrigeratorsincasestudies2and3weresmall–mediumsizedandmadebefore1996.Casestudy7hadasmall–mediumsizedrefrigeratormadein2006,andcasestudy8hadalarge(520litre)refrigeratorofunknownage.Allofthesewerereplacedwithnewrefrigerators.

Electricity-usemonitorsshowedthatnewrefrigeratorsusedanaverageof54%lesselectricitythanoldrefrigerators(Image8).Dataareonlyavailablefromfourhouseholdsbecausesomeofthecasestudyclientshadtheirrefrigeratorsreplacedbeforetheprojectstarted.Interestingly,thereplacementrefrigeratorwasthesamemodelincasestudies3and7.Thedifferenceinconsumptionbetweenthetwonewapplianceshighlightsthechallengeofcollectingdataatdifferenttimesofyear,andtheeffectofotherfactorsonenergyconsumption,suchashouseholdcomposition,behaviour,andpositioningandmaintenanceoftheappliance.

Image 8. Average daily energy use of old refrigerators and new replacement refrigerators

Page 22: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

20 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Washing machinesTheamountandqualityofthedataavailableregardingwashingmachinereplacementwerelow.Onlyafewcasestudyclientshadtheirwashingmachinesreplaced,anddatacouldonlybecollectedfromthreehouseholds.Twohouseholdsusedverylittleenergyforwashingbecausetheclientsonlyoperatedthemachines2–3timeseachweek.Inonecase,thenewwashingmachineusedmoreenergyperweekthantheoldoneduringtheperiodofmonitoring,butthiscouldhavebeenbecausetheclientwashedthreeloadsratherthantwothatweek.Inanotherunusualhouseholdwithveryhighwashinganddryingrequirements,energyuseinthelaundrycomprisedamuchhigherproportionofoverallenergyuse.

3.7 Household energy billsComparisonofenergybillsfrom2011and2012showsthatenergyconsumptionacrossthecasestudyhomesdecreasedbyanaverageof13%intheautumnquarterand22%inthewinterquarter(Table3).

Mostcasestudyhousessavedenergycomparedwiththepreviousyear,eventhoughthewinterof2012wasthecoolestwinterfornight-timetemperaturessince1997,withtheminimumovernighttemperatureaveraging–0.3°C.6 BecausethecasestudieswereconductedwithoutacontrolgroupthatcouldhelpassesstheaverageenergyuseofCanberrahouseholds,itisdifficulttodeterminetherelativeenergysavingsmadeinthecasestudiescomparedwithacontrol,orwhetherthiswasaffectedbythedifferenttemperatures.

Thequarterlybillingperiodvariedbyuptotwomonthsbetweencasestudyhouses,soforsomehousesthebillencompassedcoldermonths.Forexample,someclientsreceivedautumnbillsinJunefortheMarch–Maybillingperiod,andothersinAugustfortheMay–Julybillingperiod.Billingperiodsbeginninginautumnaredescribedastheautumnquarter;billingperiodsbeginninginwinteraredescribedasthewinterquarter.

Table 3. Energy, greenhouse gas and cost savings for all case studies

Total energy saving (kWh)

Total CO2-e saving (kg)a

Total cost savingb

Average energy saving (%)

Average cost saving

Autumn 8017 7701.32 1055.04 13 $95.91

Winter 19054 18444.56 2976.63 22 $270.60

Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–Augusta Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChange

andEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).b Costsavingsforgasusagecalculatedusing2.113centspermegajoule

ElectricityElectricitybillsshowedanaverage25%reductioninelectricityconsumptionduringtheautumnquarterandanaverage33%reductioninthewinterquarter,comparedwiththepreviousyear’sbills(Table4).Inmostcases,retrofittingandeducationsessionswereconductedduringtheautumnquarter,sotheimpactoftheprogramonenergyusewassmallerduringtheautumnperiodformosthomes.

Intheautumnperiod,9ofthe11householdsreducedtheirelectricityusecomparedwiththepreviousyear(Image9).

Inthewinterperiod,8ofthe11householdsreducedtheirelectricityusecomparedwiththepreviousyear(Image10).

Table 4 Electricity and greenhouse gas savings for all case studies

Total electricity saving (kWh) Total CO2-e saving (kg)a Average energy saving (%)

Autumn 7107 7533.34 25

Winter 17052 18074.99 33

Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–Augusta Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChange

andEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

6 BureauofMeteorology,Canberra in winter 2012: mild days and cold nights for Canberra,BureauofMeteorology,Melbourne,2012.Availableatwww.bom.gov.au/climate/current/season/act/archive/201208.summary.shtml(accessed21March2012).

Page 23: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 21

Image 9 Electricity use during the 2012 autumn quarter compared with the same billing period in 2011

Image 10. Electricity use during the 2012 winter quarter compared with the same billing period in 2011

Page 24: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

22 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

GasFiveofthecasestudyhouseshadgasconnected.Gasconsumptiondatashowedanaverage2.6%reductionintheautumnquarter(Image11)andanaverage5.9%reductioninthewinterquarter(Image12).Foreaseofcomparisonwithelectricitydata,gasconsumptionwasconvertedfromMJperdaytokWhperday(Table5).

Table 5. Gas and greenhouse gas savings for all case studies

Total gas saving (kWh) Total CO2-e saving (kg)a Average energy saving (%)Autumn 910 168.16 2.6Winter 2002 369.95 5.9Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–Augusta Costsavingsforgasusagecalculatedusing2.113centspermegajoule

Image 11. Gas use during the 2012 autumn quarter compared with the same billing period in 2011

Image 12. Gas use during the 2012 winter quarter compared with the same billing period in 2011

Page 25: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 23

3.8 Cost and greenhouse gas savingsComparisonofenergybillsfrom2011and2012showsthattheaveragenetdollarsavingperhouseholdwas$95.91intheautumnquarterof2012and$270.44inthewinterquarterof2012.Tenof11casestudiesshowedcostsavingsintheirbillforwinter2012,and9of11casestudiesshowedcostsavingsintheirbillforautumn2012,comparedwiththeirenergyusageatthesametimethepreviousyear(Image13).Duringthisperiod,theelectricitytariffincreasedbyanaverageof3centsperkWh.

Atotalreductionof7.7tonnesofcarbondioxideequivalent(CO2-e)wasachievedintheautumnquarterand18.44tonnesofCO2-einthewinterquarterof2012.Nineof11casestudiesreducedgreenhousegasemissionsforwinterandautumn2012comparedwiththesametimethepreviousyear(Image14).

Image 13 Cost savings per quarter in 2012, compared with 2011

Image 14. Carbon dioxide equivalent (CO2-e) savings per quarter in 2012, compared with 2011

Page 26: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

24 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

3.9 Household composition and behaviourHouseholdcompositionandbehaviourcanplayasignificantroleinhowenergyisusedwithinahome.Thisishighlightedbythevarietyofcasestudyhouseholds,thenumberofresidentsandtheenergyrequirementoftheresidents.Theamountofenergyusedisalsoaffectedbyresidents’health,suchasrespiratoryconditionsorhealthmanagementappliances.

Thecasestudyhouseholdsrangefromsingle-occupanthouseholdstogroupsofthreeormore.Severalhouseholdshavepeoplewhospendlargeamountsoftimeathomeduringtheday,includingretirees,familieswithsmallchildrenandpeoplewithdisabilities.Thesehouseholdsarelikelytohavehigherheatingloadsthanhouseholdsthatspendmostofthedayawayfromthehome.

Casestudy10isanatypicalhouseholdwiththreeresidentswhohavemoderatetoseveredisabilitiesandatleastonestaffmemberpresentinthehousehold24hoursperday.Thishouseholdcantypicallyhave4–7peoplepresentatanyonetime,andtheenergyuseisnotentirelycontrolledbytheresidents.

Table6showsthedifferencesbetweenthereductioninenergyusedforheatingandcoolingpredictedbythemodellingandtheactualchangeinenergyuseinthehouseholds.Theactualchangeinenergyusealsoincludesenergyusedforappliances,lighting,hotwaterheating,andsoon.

Table 6. Predicted vs actual change in energy use in case studies 1–8 using thermal modelling

Case study number

Predicted reduction in energy for heating and cooling by energy efficiency rating modelling (%)

Actual reduction in overall household energy use between winter 2011 and

winter 2012 (%)1 17 222 36 223 18 734 41 425 21 236 23 357 28 28 16 13

Note: Casestudies9,10and11werenotincludedinthemodellingbecauseofschedulingconstraints.

Differencesbetweenpredictedenergyreductionfromthermalmodellingandactualenergyreduction(Table6)couldbeexplainedbyresidents’behaviour.Caseswheretheactualenergyreductionwaslessthanthepredictedreduction(casestudies2,7and8)couldbeexplainedbyresidentsenjoyingmorecomfortableinternaltemperaturesthantheyhadpreviouslyexperienced,ratherthanmaintaininglowertemperaturesandreducingtheirbills.

Casestudies1,3,4,5and6savedmoreenergythanthesoftwarepredicted.Thiscouldbeduetochangesinbehaviourandtheuseoflighting,hotwaterandotherappliances.Casestudy3hadthemostsignificantreduction,mostlyduetotheresidentrestrictingtheiruseofthein-slabheating,whichhadbeenusedfortheentirehousein2011,toasmallerareain2012.Thishouseholdalsohadfewerpeopleinthehomebetweenwinter2011andwinter2012.

Casestudy4initiallyhadalargereductioninenergyuse,butduringthecasestudyperiodasecondadultmovedintothehome,andtheenergyusechangeddramatically(seeImage6).Thechangeinenergyusedidnotappeartobeassociatedwithheatingofthemainlivingareasbecausetheinternaltemperaturesremainedconstant.Thishighlightstheimportanceofbehaviourinthecontextofenergyreductions.

RefertoAppendixAformoredetailsabouthouseholdcomposition,healthandbehaviourthatmightaffectenergyuse.

Page 27: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 25

3.10 Type of heating systemThetypeofheatingsystemcansignificantlyaffectenergyuse.Forexample,inefficientelectricheatingsystemsareoftenfoundinhouseholdsparticipatingintheOutreachProgram.Thesesystemscanbeexpensivetooperateandhaveminimalbenefits,especiallyiftheheatersarefixedelectricsystemsthathavebeeninappropriatelypositioned.Thisisparticularlyevidentincasestudy9,whichisasingle-occupant,three-storeyhomewithinefficientelectricresistanceheating.Thishouseholdhadthehighestenergyconsumptioninthewinterperiodofalltheparticipatingcasestudies,andelectricityuseincreasedmorethanfourfoldfromautumntowinter.Theeffectofdifferencesinthetypeofheatingsystemisalsoevidentincasestudy3,whichhasinefficientin-slabheating.

3.11 Client responses to energy monitorsScinergywasnotcontractedtoformallycollectoranalysequalitativedata.However,repeatedenthusiasticanecdotalfeedbackwasreceivedfromclientsabouttheenergymonitors.Itseemedthatenergymonitorswerenotonlyusefulasameanstocollectdailyenergy-usedata,butwerealsovaluableeducationaltoolsandmotivatorsofbehaviouralchange.Severalclientsusedthemtomeasuretheenergyuseoftheirappliancesandunderstandhowtheiractionsaffectedenergyuseindetail(sometimesevenbeforetheserviceproviderhadshownthemhowtousethedevice).Thepresenceoftheenergymonitorsseemedtomotivateclientstoreducetheirenergyconsumptionbyobservingandlimitingtheuseofcertainhigh-energyappliancesandbehaviours.Perhapsnotsurprisingly,clientspreferredtousethemonitorsonthe‘cost’setting,whichdisplayedenergyuseindollarsandcentsratherthanwatts.

Page 28: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

26 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Page 29: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 27

4 Findings and recommendations

TheOutreachProgramhadasignificantandmeasurableeffectontheenergyuseofallofthehouseholdsparticipatinginthecasestudies.Importantly,householdenergybillsshowedasubstantialreductioninenergyuseafterretrofittingcomparedwiththepreviousyear,andallhousesincreasedtheirenergyefficiencyrating.Thisalsocorrelatedwithcostsavingsonenergybillsandreducedgreenhousegasemissionsasaresultoftheprogram.

4.1 Thermal performance simulation

Finding

Alleightcasestudyhousesthatunderwentthermalmodellingincreasedtheirenergystarratingafterretrofitting.

Casestudyhomesvariedintheirthermalpotentialasaresultofdifferencesinglazing(orientation,dressingsandsizerelativetoroomfloorarea),insulationlevelsandairtightness.Themosteffectivewaytoreduceenergyuseandincreasecomfortthereforealsovariedamongcasestudyhouses:forsome,simpledraughtsealingwasthemosteffectiveoption,whilewallinsulationwasthebestoptionforothers.Heavydrapesandpelmetsalsosignificantlyreducedenergyuseinsomehouses.Whenconsideringcost-effectiveness,draughtsealingwasconsistentlythebestoption,sometimesbyasmuchas5–10times.

Recommendations

• Eachhouseholdshouldcontinuetobeassessedindividuallytoaccuratelydetermineandprioritisetheretrofitandeducationmeasures.Retrofitmeasuresandeducationsessionsmustcontinuetobetailoredtotheindividualhome,andissuesprioritisedtomaximiseenergy-savingpotentialforthelowestcost.

• Windowdrapereplacementshouldberestrictedtomainlivingareaswherecurrentdrapesareinadequate(unlessotherwisejustified).

• Theuseofcheapandeffectivepelmetoptions(suchascorflutetosealthegapbetweenthetopofthecurtaintrackandwall)shouldbeencouraged.

4.2 Air leakage rate and location

Finding

Mostcasestudyhouseshadhighratesofairleakage,andthemajorityofleakswereviaceilingpenetrations.Simpledraught-sealingmeasuresreducedtherateofairleakageinninecasestudyhomes,byanaverageof34%.Statisticalmodellingofactualairleakageandenergyconsumptiondatasuggeststhatdraughtsealingaccountsforalmost40%ofenergysavings.

Draughtsealinghasprovedtobethemosteffectiveretrofitmeasureforthesecasestudyhomes.Notonlydoesheatedairremaininthehomeforlonger,theclientalsofeelsmuchwarmer.

PermanentpassiveventilationshouldnotbereliedontocontrolmoisturelevelsormaintainfreshairinCanberrahomes.Instead,activeventilation—mechanicalexhaustfansandthesimpleopeningofwindows—shouldbeusedtoreducemoisturebuild-upintheareaswhereitisgenerated.

Recommendations

Draughtsealingshouldcontinuetobeakeyelementofretrofits.Tooptimisethebenefitofdraughtsealing,thefollowingproceduresareabest-practiceguide:

• Draughtsealfromthetopdown.Focusonextractorfansinheatedareas,passivevents,wallventsandventedskylights.

• Remindclientsoftheimportanceofusingextractorfansinthekitchenandbathroomfollowingdraught-sealingmeasurestopreventmoistureaccumulationandcondensation.Extractorfanscanalsobeusedtoventhotairfromahomeinsummer.

• Considerhouseholdbehaviourandpetswhenprioritisingtheretrofit.Thereislittlepointindraught-proofingahomeifexternalandinternaldoorsandwindowsareleftopentoallowventilationandmovementofpets. Discussoptionswiththeclientthatallowpetmovementwhilekeepingdoorsshut.

Page 30: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

28 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

4.3 Insulation

Finding

CeilinginsulationiscriticalintheCanberraclimate,andthemajorityofcasestudyhomeshadatleastR2.5insulationinstalled.Afterthislevelofinsulation,thesimulationsoftwareindicatedthatthenextmostcost-effectivemeasuresforCanberrahousesaredraughtsealingandwallinsulation.Mostcasestudyhouseshaduninsulatedwalls,andgapsintheirceilinginsulation.

Recommendations

• Ceilinginsulationshouldbetoppedupwherenecessary.

• Wallinsulationshouldbeconsidered,wherepossible,andparticularlyforhomeswithverypoorthermalperformance.Althoughtherearepotentialelectricalissuesandextracostsinvolved,insomecasesthepredictedbenefitstilloutweighstheup-frontcost.

4.4 Temperature

Finding

Beforeretrofitting,manycasestudyhousesexperiencedextremelyuncomfortabletemperaturesthatmaycompromisethehealthofresidents.

Temperaturemonitoringindicatedanimprovementinthetemperatureinseveralofthecasestudiesafterretrofits;however,temperatureandenergymonitoringwerecomplicatedbyexternalfactors.

Recommendations

• Althoughusefulforshowingtrends,temperaturemonitoringshouldbemoretightlycontrolledtomeasuretheeffectsofindividualmeasuressuchasretrofitsoreducation.

• Asurveyofcomfortlevelsexperiencedbyparticipantsshouldbeincludedinfuturestudies.

4.5 Appliance replacement

Finding

Datafromfourcasestudyhomesshowedthatreplacingold,inefficientrefrigeratorswithnewmodelscanhalvetheenergyusedforrefrigeration.Dataforreplacingwashingmachineswerenotsufficienttoallowanyconclusionstobedrawn.

Recommendations

• Oldrefrigeratorsandfreezersshouldcontinuetobereplaced.

• Furtherresearchshouldbeconductedtodeterminetheenergyandwatersavingsachievedbywashing-machinereplacement.

4.6 Household energy use

Finding

Comparisonofenergybillsfrom2011and2012showsthatenergyconsumptionacrossthecasestudyhomesdecreasedbyanaverageof13%intheautumnquarterand22%inthewinterquarter.Thisdecreaseincludeselectricityandgas.

Comparisonofenergybillsfrom2011and2012showsthatelectricityconsumptionacrossthecasestudyhomesdecreasedbyanaverageof25%intheautumnquarterand33%inthewinterquarter.

Inthefivecasestudyhouseswithgasconnected,gasconsumptiondecreasedbyanaverageof2.6%intheautumnquarterand5.9%inthewinterquarter.However,variationsinbillingperiodsamonghouseholdsmadedirectcomparisonsdifficult.

Page 31: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 29

Recommendation

• Furthercasestudiesofhouseswithgasconnectionswouldhelptounderstandwhyreductionsinthisformofenergyweremuchlessthanforelectricity.

4.7 Cost and greenhouse gas savings

Finding

Comparisonofenergybillsfrom2011and2012showsthattheaveragenetdollarsavingperhouseholdwas$95.91intheautumnquarterof2012and$270.60inthewinterquarterof2012.

Atotalreductionof7.7tonnesofCO2-ewasachievedintheautumnquarterand18.44tonnesofCO2-einthewinterquarterof2012.

Recommendation

• Greenhousegasemissionsandenergycostsshouldcontinuetobemonitored.

4.8 Household composition and behaviourDifferencesbetweenenergyreductionpredictedbythermalmodellingandactualenergyreductioncouldbeexplainedbyresidents’behaviour.Severalofthecasestudiesvariedsignificantlyfromthepredictedenergyreduction,whichindicatestheinfluenceofbehaviouronenergyreduction.Thisismostnotablydemonstratedbycasestudy3,whichsaved73%comparedwithapredictionof18%.

Recommendations

• Educationshouldcontinuetobeprovidedtoprogramparticipantstomaximiseopportunitiesforenergyreduction.

4.9 Client responses to energy monitors

Finding

Repeatedanecdotalevidencefrommultiplecasestudyhomessuggeststhatenergymonitorsmaybeusedasatooltosupportandmotivatebehaviouralchange.

Recommendation

• Formaltrialsofhouseholdenergymonitorsshouldbeconductedtoassesstheirimpactonclientbehaviour.

Page 32: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

30 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Page 33: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 31

Appendix A Case studies

Case study 1Communitywelfareorganisation:SocietyofStVincentdePaul

Serviceprovider:C&JGroup

Background information from Energy Efficiency Officer

Category Clientwouldbenefitfromanassessment,educationandbasicretrofit,suchascurtains,blindsanddraughtsealing

Household occupants 3

Financial circumstance Unemployed,full-timestudent,financialhardship

Type of residence Owner–occupier

Products to be replaced Washingmachine

Client concerns Overglazedbrick-veneerhousewithacape-codextension/masterbedroomupstairs.Approx.16m2oflivingareaandagrannyflatthatisrentedout.Thehousehasasmall2kWphotovoltaicsystemandflat-panel(twopanels)solarhotwatersystem,boostedbyinstantaneousgas.Ithastwolargeandsegregatedlivingrooms,bothofwhichareheatedandcooledbyanundersizedreverse-cycleair-conditionerinoneoftherooms,inadditiontothecentralgasheating.Thehousehasverylargesouth-facingwindowsandneedsall-rounddraught-proofingandsomeadditionalpropercurtains.Theclientisasinglemotherwithtwochildren,andtwograndchildrenwholivetherepart-time.Sheisveryinterestedinthesubjectmatterandcouldgreatlybenefitfromfurthereducationandretrofit.

Date of referral 12February2012

The house, its timeline of retrofitting activities and thermal performanceExtended,four-bedroom,two-bathroom,brickveneer,concreteslab,150m2.Originalhouseapproximately35yearsold,extensionapproximately20yearsold.

Thepotentialforpassivesolarheatgainishighasaresultofextensiveglazingtothenorthinthelivingroom,loungeroomandbedrooms,allowingthesuntostriketheconcreteslab.However,therearealsosignificantareasofglazingtothesouthinthemainopen-plankitchen/livingarea,whichcompromisethethermalperformanceofthehome.

Theclientalsohassolarpanelsforelectricitygeneration,andasolarhotwatersystemwithaninstantaneousgasboost.

Thethermalperformancesimulationindicatesthatdraughtsealingcouldbeasmuchas10timesmorecost-effectivethancurtainreplacementandpelmetinstallationinreducingtheheatingrequirementsforthishome.

Aerial view ↑North Modelled in BERS4.2 thermal simulation software Orange: kitchen/dining/living; red: living; blue/purple: bedrooms; green: laundry/bathroom; yellow: corridor

Page 34: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

32 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Timeline of testing and retrofitting activities

Date Action

22March Temperatureandenergy-usedataloggersinstalled

12April Airleakageassessmentandthermographicinspectionandeducation

4May Draughtsealing

10May Curtainsandpelmetsinstalled

17May Post-retrofittestandcollectionoftemperatureandenergy-usedata

28May DraftStoppa®overkitchenexhaustfanandinternaldraught-proofing

1June Recessedhalogenlampsinkitchenreplacedwithcompactfluorescentlamps

7June Finalblowerdoortestanddatacollection

Thermal performance simulation (energy efficiency rating) of proposed retrofit measures

Simulation and specifications Star rating

Heating (MJ/m2)

Cooling (MJ/m2)

Total (MJ/m2)

Predicted reduction

(%)

Actual cost ($)

Cost per MJ reduction

($)

Startingconditions:•CeilingsR3;wallsR1.5toextension,R0tooriginal;floorsR0

•Openexhaustfanandthreeventeddown-lightsinkitchen

•Leakyoldwall-mountedair-conditioningunitinlounge

•Curtainsbutnopelmetstowindowsthroughout

3.9 258 32 290

Startingconditionsplus:•Draughtsealing

4.2 233 32 265 9 450 18

Startingconditionsplus:•Curtainsandpelmetstoloungeanddining

4.2 238 32 270 7 4193 209

Completeretrofit:•Sealedexhaustfans•Sealedvents•Draughtsealed•Curtainsandpelmetstoloungeanddining

4.5 210 31 242 17 4643 96

Air leakage resultsVisualinspectionsuggestedthatthehousewouldbeveryleaky,andthiswasconfirmedbyfandepressurisationtesting.Thebuildingenvelopehadmanyobviousleakagepoints,including:

• unsealedexhaustfaninkitchen

• permanentventsinvariouspartsofthehome

• viaplumbingandelectricalpenetrationsbehindkitchenjoinery

• recessedlightinginceiling

Page 35: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 33

• unsealed‘Tastic’inbathroom

• unnecessarypermanentventinbedroomandlivingareas

• arounddoorsandsurroundingarchitrave

• aroundoldwall-mountedheater

• aroundexposedbeamsandsuspendedflooring

• betweenwindowsandgyprock,walljunctionsandroofbeams.

Therateofairleakagewasreducedby18%afterthefollowingdraught-sealingmeasures:

• installingaDraftStoppa®inthekitchen

• sealingunnecessaryceilingvents

• sealingaroundsomearchitravesandwindows

• installingaperspexpanelonthefrontoftheoldwall-mountedheater

• replacinghalogendown-lightswithsealedcompactfluorescentdown-lights.

Result from air leakage testing

Pre-retrofit Post-retrofit Difference

Airchangesperhourat50Pa 21.8 17.82 –18.3%

Effectiveleakageareaat4Pa(equivalentopensquarewindow)

45cmx45cm 40cmx40cm 21cmx21cm

Note: Apressuredifferenceof4Pabetweeninsideandoutsideisclosetothenormalpressuredifferentialexperiencedinthehomeoncold,windyCanberradays.

Air Leakage points

Ceiling vent in bedroom Unsealed exhaust fan in kitchen Leakage between architrave and gyprock

Leakage around air-conditioner Leakage through heating vent

Page 36: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

34 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

InsulationCeilinginsulationwaspresentandmostlyeven;thereweresomeinconsistentareas,mostlyaroundtheextremitiesofthehouse.

Thehousehasexcellentpotentialtousewintersolarheatgainthroughthelargeglazedareasfacingnorth.However,thehousealsohaslargeareasofglazingfacingsouth,whichcompromiseitsabilitytoretainheat.Italsohasadraughtyloftareaatoneendofthehousethatactstoremovemuchoftheaccumulatedheatandnegatesthepassivesolarheatgain.

Inadequate insulation

Inadequate insulation in living area

Solar heat gain through northern windows

Temperature and electricity useThehouseexperiencesseverelycoldtemperaturesinJune,withlivingareasrangingfrom10–22°Candbedrooms 6–15°C.

Datafromthermochronshighlightsthefollowing:

• Littleadditionalheatingisusedinthehomeduringtheevening.Thefamilyareaisoccasionallyheatedbutnotexcessively.

• Atsomepointinthemiddleoftheday,theinternaltemperaturereaches25°Casaresultofthepassivesolarheatgain.However,becauseofglazingonthesouthsideofthehouse,theseroomsalsodropaslowas10°Catnight.

• Theoveralltemperatureremainedconstant,despiteadecreaseinenergyusebytheclient.

• Theunheatednorth-facingbedroom,inwhichcurtainswererarelyopenedbutthewindowwasleftajar,followsexternaltemperaturesveryclosely.

Clientbehaviourplaysalargepartinkeepingthishousewarmandcold.Freshairisflushedthroughthehousethroughouttheday,whichkeepsthehousecool,despiteitshavingexcellentsolaraccessinthelivingandloungeroomsandsomeofthebedrooms.

Theclientreallylikesfreshairand,whilethehouseisnotaswarmasitcouldbeifitwasclosedandallowedtobenefitfromsolarpassiveheatgain,sheisusingnoadditionalheatingduringthedayandthereforenotwastingenergyintheprocess.

Page 37: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 35

Electricity use and temperature data in case study 1

1 A

PRIL

Tem

pera

ture

(0 C)

1 M

AY

1 JU

NE

5 5

10 10

15 15

20 20

25 25

30 30

35 35

0 0

bedroom temperatureexternal temperatureDinner room temperatureElectricity use

Electricity use

Lounge temperature

Leakage test and

education

Draught sealing 1

Draught sealing 2

Replacehalogen lamps

Curtainsand

pelmets

Post retrofit

test

Post retrofit test

Energy billsWhileelectricitydecreased,gasconsumptionincreased.Thiswasforavarietyofreasons:

• Thebrokeninstantaneous-boosthotwatersystemwasdisconnectedforseveralmonthsin2011andthenreconnectedin2012.

• Theclientwasadvisedintheeducationsessiontoboilwaterinakettleonthegasstoveratherthanusinganelectrickettle.Theclientfoundthispracticeunsustainableandtimeconsuming(waitingforthekettletoboil)andhasswitchedbacktotheelectrickettle.

• Themothersaidteenagersweretakinglongerhotshowersthantheyearbefore.

Electricity usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 30 17 –43%

Winter* 40 22 –45%

Gas usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 7 13 +85%

Winter* 5 13 +160%

Electricity + gas usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 37 30 –19%

Winter* 45 35 –22%

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 38: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

36 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Predicted versus actual reductions in energy useThermalsimulationsuggestedthatreductionsinenergyuseof17%forheatingandcoolingcouldbeachievedviathedraught-sealingandwindow-dressingmeasuresimplemented.

Actualenergyconsumptiondatafromquarterlybillsdemonstratea22%reductioninoverallhouseholdenergyuse(i.e.notjustheatingandcoolingbutalsoappliances,lighting,hotwaterheating,etc.)betweenwinter2011andwinter2012.Thissuggeststhateducationandassociatedbehaviouralchangecouldaccountfortheremaining5%reductioninenergyconsumption.

Total energy, greenhouse gas and cost savings

Energy saving (kWh) CO2-e saving (kg)a Cost saving ($)b

Autumn* 625 1140.19 112.86

Winter* 903 1594.51 204.95

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh.Emissionfactorfornaturalgasis51.33kgCO2-e/GJ(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

b Costsavingsforgasusagecalculatedusing2.113centspermegajoule

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 39: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 37

Case study 2Communitywelfareorganisation:BelconnenCommunityService

Serviceprovider:CoolPlanet

Background information from Energy Efficiency Officer

Category Clientwouldbenefitfromanassessment,educationandbasicretrofit,suchascurtains,blindsanddraughtsealing

Household occupants 1

Financial circumstance Disabilitysupportpension

Type of residence ACTHousing,bottomstorey,one-bedroombrickveneer

Products to be replaced Washingmachineandrefrigerator

Client concerns Theclientlivesaloneinthistownhouse.Hehaschroniccardiacandrespiratoryhealthconditionsandisvisionimpaired.Heisverymindfulofhisenergyuseandusesaveryoldfanheaterratherthanthewall-mountedelectricheater,andhas‘doorsnakes’atsomeofhisdoors.Hehascurtainsthatarenotblock-out,andnopelmets.Therearegapsarounddoorsandwindows.Hisold,inefficientrefrigeratorandwashingmachinewillbereplaced.Theclientiskeentoreducehisbills,hasagreedtotakepartinacasestudyandwillgreatlybenefitfromthisexercise.

Date of referral 23February2012

The house, its timeline of retrofitting activities and thermal performanceThisisasmallone-bedroomunit.

Thethermalperformancesimulationindicatesthatthedraught-sealingmeasuresimplementedmaybealmosttwiceascost-effectiveasthewindowdressingupgradesinreducingoverallenergyrequirementsforheatingandcoolinginthishouse.

Aerial view ↑North Modelled in BERS4.2 thermal simulation software Pink: kitchen/dining; blue: bedroom; green: laundry/ bathroom; yellow: corridor

Timeline of testing and retrofitting activities

Date Action

2April Temperatureandenergy-usedataloggersinstalled

16April Airleakageassessmentandthermographicinspection

20April Education

1May Draught-proofingexternalandinternaldoors

18May Curtainsandpelmetsinstalled

18May Post-retrofittestandcollectionoftemperatureandenergy-usedata

20June Furtherdraught-proofingcavitydoorsliderandwall–ceilingjoins

22June Finalblowerdoortestanddatacollection

Page 40: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

38 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Thermal performance simulation (energy efficiency rating) of proposed retrofit measures

Simulation and specifications

Star rating

Heating (MJ/m2)

Cooling (MJ/m2)

Total (MJ/m2)

Predicted reduction (%)

Actual cost ($)

Cost per MJ reduction ($)

Startingconditions:•Insulatedbyneighboursabove,tonorthandsouth

•Verydraughty•Curtains,nopelmets

2.8 344 70 414

Startingconditionsplus:•Curtainsandpelmetstoloungeandbedroom

3.4 285 48 334 19 1509 19

Startingconditionsplus:•Draughtsealing

3.3 274 75 349 16 747 11

Completeretrofit:•Draughtsealing•Curtainsandpelmets

4.2 215 52 267 36 2256 15

Air leakage resultsInitialtestingofthebuildingshowedthatitwascomparativelywellsealed.Thebuildingwasconstructedfrombrickandrenderedcement,withfewdoorsandwindows,andhadhighthermalmass.

Thebuildingenvelopehadmanyobviousleakagepoints,including:

• aroundplumbingpenetrationsinbathroom

• betweeninternalbrickandcement-renderedwalls

• betweenbricksandwindowframes,aswellassliding-doorframe

• throughinternal-wallsliding-doorframe

• throughgapswherebrickworkmeetsceiling

• throughunsealedexhaustfaninlaundry

• permanentopeninginbathroomwindow.

Silicon-basedsealantwasusedtofillgapsbetweenrenderedconcreteandbrickwallsinthelivingareasandbathroom,andaroundwindowanddoorframes.Thiswasalsousedaroundplumbingpenetrations.Doorsweresealedwithbrushandtapesealinginthebathroom(whichhadapermanentwindowvent)andthelaundry(whichhadanunsealedexhaustfanasaventfortheclothesdryer),toincreasetheairtightnessoftheconditionedspaceofthebuilding.However,duringtesting,boththesedoorswereleftopen,whichmeansthatthefinalairleakagetestdoesnotcapturethefullpictureoftheretrofittingmeasuresputinplace.

Result from air leakage testing

Pre-retrofit Post-retrofit Difference

Airchangesperhourat50Pa 13.3 11.8 –11%

Effectiveleakageareaat4Pa(equivalentopensquarewindow)

25cmx25cm 23cmx23cm 11cmx11cm

Note: Apressuredifferenceof4Pabetweeninsideandoutsideisclosetothenormalpressuredifferentialexperiencedinthehomeoncold,windyCanberradays.

Page 41: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 39

Air Leakage points

Leakage between window frame and internal brickwork

Leakage at junction of wall and ceiling in bathroom

Leakage between internal timber cladding, brickwork and ceiling

InsulationAsaground-floorunitinatwo-storeyapartmentcomplex,thisresidencebenefitedfrominsulationbyneighbourstothenorthandsouthandabove.Theexternal,uninsulatedandhighlyglazedeasternandwesternwallswerebyfarthecoolestpartsofthehouse.

Refrigerator replacement

Energy usage results for old and new refrigerators

Energy use (kWh/day) Energy use (kWh/year) CO2-e (kg/year)a Difference

Old 1.47 537 569

New 0.81 295 313 –45%

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

Temperature and electricity use

Electricity use and temperature data in case study 2

Tem

pera

ture

(0 C)

1 M

AY

1 JU

NE

5 5

10 10

15 15

20 20

25 25

30 30

0 0

Bedroom temperature External temperature Electricity use

Electricity use

Leakagetest and

education

Post-

test

Tem

pera

ture

(0 C)

5 5

10 10

15 15

20 20

25 25

30 30

35 35

0 0

Electricity use

Draught sealing 2

Draught sealing 1

Living room temperature

Curtainsand

pelmets

Page 42: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

40 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Energy bills

Electricity usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 15 11 –22.1%

Winter* 27 21 –22.1%

Predicted versus actual reductions in energy useThermalsimulationsuggestedthatreductionsinenergyuseof36%forheatingandcoolingcouldbeachievedusingthedraught-sealingandwindow-dressingmeasuresimplemented.

Actualenergyconsumptiondatafromquarterlybillsdemonstrateasmaller,butstillverysignificant,22%reductioninoverallhouseholdenergyuse(i.e.notjustheatingandcoolingbutalsoappliances,lighting,hotwaterheating,etc.)betweenwinter2011andwinter2012.

Theclientmaybeusingtheremainingpotentialreductionsinenergyuse(suggestedbythethermalmodelling)tomaintainmuchmorecomfortabletemperaturesthanpossibleinpreviousyears.Ratherthantakingallthebenefitintheformofreducedbills,thisclientisprobablyenjoyingthebenefitofincreasedcomfort.

Total energy, greenhouse gas and cost savings

Energy saving (kWh) CO2-e saving (kg)a Cost saving ($)b

Autumn* 294 312.08 44.60

Winter* 550 583.53 94.71

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

b Costsavingsforelectricitycalculatedusing15.15(autumn)and17.21(winter)centsperkilowatthour

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 43: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 41

Case study 3Communitywelfareorganisation:BelconnenCommunityService

Serviceprovider:CoolPlanet

Background information from Energy Efficiency Officer

Category Clientwouldbenefitfromanassessment,educationandbasicretrofit,suchascurtains,blindsanddraughtsealing

Household occupants 1

Financial circumstance Retired65+man,onagedpension.Hasoldinefficientwhitegoodsandlargeheatingbills.Difficultypayingbills,unabletoaffordtoreplacewhitegoods.

Type of residence Homeowner,singlestorey,brickveneer,southfacing,kitchenanddiningareanorthfacing

Products to be replaced Refrigerator,freezerandwashingmachine

Draught sealing required?

Feelshishomeisprettytightlysealed

Client concerns Theclienthaslivedinthisfour-bedroomhomeforabout15years.Hetriestoavoidusingunderfloorheatingasmuchaspossible,becauseelectricitybillspikesinwinter.Theclienthasnetandlightblock-outcurtainsinmostoftherooms,butnopelmets.Theclientisconsciousofenergyefficiencyandiskeentoseehowmuchhecansavemoneyandimprovethecomfortofhishome,particularlyinwinter.Heisveryopentobeingpartofthecasestudy.

Date of referral 4April2012

The house, its timeline of retrofitting activities and thermal performanceThethermalperformancesimulationindicatesthatthishousewasalreadyperformingverywellthermallyandthatfundswouldhavebeenbetterdirectedtootherhomesthatperformedlesswell.Althoughthehousewasnotveryleakycomparedwithothercasestudyhomes,draughtsealingwasstillthemostcost-effectiveretrofitmeasure.

Aerial view ↑North Modelled in BERS4.2 thermal simulation software Pink: kitchen/dining/living area; brown: secondary living area; blue/purple: bedrooms; green: laundry/bathroom

Timeline of testing and retrofitting activities

Date Action18April Temperatureandenergy-usedataloggersinstalled20May Airleakageassessmentandthermographicinspection19May Education10June Draught-proofingexternalandinternaldoors22June Curtainsandpelmetsinstalled

Page 44: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

42 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Thermal performance simulation (energy efficiency rating) of proposed retrofit measures

Simulation and specifications Star rating

Heating (MJ/m2)

Cooling (MJ/m2)

Total (MJ/m2)

Predicted reduction

(%)

Actual cost ($)

Cost per MJ reduction

($)

Startingconditions:•CeilingsR3—somegaps•WallsR1.5•Openexhaustfansinbathrooms,otherwisewellsealed

Goodcurtains,nopelmets

5.9 160 9 170

Startingconditionsplus:•Draughtsealing

6.2 146 9 155 9 423 28

Startingconditionsplus:•Ceilinginsulationgapsfilled

6.0 157 8 165 3 220 44

Startingconditionsplus:•Pelmetstolivingareas

6.2 149 9 157 8 1100 85

Completeretrofit:•Pelmetstolivingareas•Blindtokitchen•Ceilinginsulationgapsfilled•Sealedexhaustfan•Sealedexternaldoors

6.5 132 8 140 18 1743 58

Air leakage results

Result from air leakage testing

Pre-retrofit Post-retrofit Difference

Airchangesperhourat50Pa 7.72 – –

Notes: Casestudy3wasnotretestedforairleakageafterdraughtsealingbecauseitwasalreadybelowthetargetlevelof10airchangesperhourat50Pa,andfundswerebetterspentonhomesthatwerefurtherfromthistarget.

Refrigerator replacement

Energy usage results for old and new refrigerators

Energy use (kWh/day) Energy use (kWh/year) CO2-e (kg/year)a Difference

Old 2.1 766 812

New 0.92 329 349 –57%

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

Page 45: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 43

Temperature and electricity useEnergyconsumptionclearlydroppedfollowingtheeducationsessionandexplanationoftheenergy-usemonitor.

Electricity use and temperature data in case study 3

Educationre in-slabheating

Leakagetest

Tem

pera

ture

(0 C)

Electricity use (kWh)

50 50

40 40

30 30

20 20

10 10

0 0

1 M

AY

1 JU

NE

External temperatureElectricity use

Electricity use

Draught sealing 1

Post retrofit

test

Curtainsand

pelmets

Energy bills

Electricity usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 44 18 –60%

Winter* 65 18 –73%

Predicted versus actual reductions in energy useThermalsimulationsuggestedthatreductionsinenergyuseof18%forheatingandcoolingcouldbeachievedviathedraught-sealingandwindow-dressingmeasuresimplemented.

Actualenergyconsumptiondatafromquarterlybillsdemonstratea73%reductioninoverallhouseholdenergyuse(i.e.notjustheatingandcoolingbutalsoappliances,lighting,hotwaterheating,etc.)betweenwinter2011andwinter2012.Thissuggeststhateducationandassociatedbehaviourchangecouldaccountformostofthereductioninenergyconsumption.In2011,theclienthadbeenunwellandhadanotherfamilymemberstayinginthehouse.Asaresult,theinefficientelectricslabheatingsystemhadbeenusedthroughoutthewholehouseratherthanbeingzonedforuseintheendofthehouseoccupiedbytheresidentonhisown.

Total energy, greenhouse gas and cost savings

Energy saving (kWh) CO2-e saving (kg)a Cost saving ($)b

Autumn* 2395 2538.76 326.87

Winter* 4269 4525.82 685.84

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

b Peak/off-peakrateisusedtocalculatecostsavingsforelectricityusage.

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 46: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

44 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Case study 4Communitywelfareorganisation:SocietyofStVincentdePaul

Serviceprovider:C&JGroup

Background information from Energy Efficiency Officer

Category Homeisdraughty,withnocurtainsorblinds,andtheclienteitherhashighbillsorislivinginimpoverishedconditions.Clientwouldbenefitgreatlyfromanassessment,educationandbasicretrofit.

Household occupants 3

Financial circumstance Centrelink—singleparent

Type of residence ACTHousing

Products to be replaced Refrigeratorandwashingmachinealreadyreplaced

Draught sealing required?

Notsure

Client concerns Verycoldhouse;theclientisconcernedaboutwinterbillaffordability.Thehousehaspelmetsbutnocurtains.Theopen-planliving/diningareaisapriority.

Date of referral 27March2012

The house, its timeline of retrofitting activities and thermal performanceThree-bedroombrickveneer,98m2,approximately35yearsold.

Thepotentialforpassivesolarheatgaintothishouseislimited.Thelargeareaofglazinginthemainlivingareaandthewindowsofbedrooms2and3facesouth-west.Thesmallamountofsolarheatgainpossibleviathediningwindowisquicklylostthroughtheleakybuildingenvelopetothesurroundinguninsulatedwalls.Themainbedroomonthesouthernmostcornerofthehouseisextremelycold,withtwolargeuninsulatedexternalwallsandnoopportunityforsolarheatgain.

Thethermalperformancesimulationshowedthat:

• retrofittingwallinsulationisthesinglemosteffectiveretrofitmeasureforthishome,withapredicted27.9%reductioninenergyrequirementsforheatingandcooling

• draughtsealingceilingventsandfittingdamperstoexhaustfansisthemostcost-effectiveoptionatonly$14perMJ/m2reductioninpredictedenergyrequirements.

Thebestallocationoftheretrofitbudgetwas$500—draughtseal;$3100—draughtsealandinsulatewalls;$5100—draughtseal,insulatewallsandtop-upceilinginsulation.

Aerial view ↑North Modelled in BERS4.2 thermal simulation software Pink: kitchen/dining; purple: living; blue: bedrooms; green: laundry/bathroom; yellow: corridor

Page 47: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 45

Timeline of testing and retrofitting activities

Date Action

18April Temperatureandenergy-usedataloggersinstalled

3May Airleakageassessmentandthermographicinspection

7–11May Education

29May–1June Draught-proofing

6June Ceilinginsulationinstalled

7June Hollandblindsinstalled

22June Post-retrofittestandcollectionoftemperatureandenergy-usedata

22Juneonwards Temperaturedataloggerslostinclient’shome

2August Wallinsulationinstalled

28August Draught-proofinginternalbathroomandtoiletdoors

Thermal performance simulation (energy efficiency rating) of proposed retrofit measures

Simulation and specifications

Star rating

Heating (MJ/m2)

Cooling (MJ/m2)

Total (MJ/m2)

Predicted reduction (%)

Actual cost ($)

Cost per MJ reduction ($)

Startingconditions:•CeilingsR2,walls/floorsR0•Multipleceilingvents•Openexhaustfaninkitchen•Lightcurtains(2layers)

2.9 354 35 390

Startingconditionsplus:•Draughtsealing•DraftStoppa®tokitchenexhaust

3.3 321 34 355 9 311 9

Startingconditionsplus:•Newblindstoloungeanddining

2.9 354 35 390 0 1292 Novalue

Startingconditionsplus:•WallR2insulation•Associatedelectricalupgrade

3.9 259 29 288 26 4127 40

Startingconditionsplus:•CeilingR4insulation•Removalofoldinsulation

4.2 244 23 267 32 2045 16

Completeretrofit:•Sealedexhaustfans•Sealedvents•Draughtsealed•DraftStoppa®tokitchenexhaust

•Newblindstoloungeanddining

•R2inwallsandR4inceiling

4.7 211 21 232 41 7775 49

Page 48: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

46 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Air leakage resultsVisualinspectionsuggestedthatthehousewouldbeveryleaky,andthiswasconfirmedbyfandepressurisationtesting.Thebuildingenvelopehadmanyobviousleakagepoints,including:• unsealedexhaustfaninkitchenandbathroom

• permanentceilingventsineveryroom

• permanentopeningintoiletwindow

• arounddoorsandsurroundingarchitraves

• betweenwindowarchitravesandgyprock

• viaplumbingandelectricalpenetrationsbehindkitchenjoinery.

Therateofairleakagewasnearlyhalvedafterthefollowingdraught-sealingmeasureswereimplemented:

• installingDraftStoppa®onkitchenandbathroomfans

• caulkingaroundsomedoorwaysandwindowsframes

• sealingofthepermanentceilingvents.

Althoughunwantedairleakagewassignificantlyreduced,thereisscopeforfurtherretrofittingworkonthebuildingenvelope.Moretimeandbudgetgiventosealingthebuildingenvelopewouldyieldfurthergainsinairtightness,improvementsincomfortandreductionsinenergyuse.

Althoughthethermachrondata(see‘Temperatureandelectricityuse’)donotshowanincreaseininternaltemperatures,theclientissurethatthehousefeelsmuchmorecomfortable.

Result from air leakage testing

Pre-retrofit Post-retrofit Difference

Airchangesperhourat50Pa 25.01 13.89 –45%

Effectiveleakageareaat4Pa(equivalentopensquarewindow)

51cmx51cm 37cmx37cm 35cmx35cm

Note: Apressuredifferenceof4Pabetweeninsideandoutsideisclosetothenormalpressuredifferentialexperiencedinthehomeoncold,windyCanberradays.

Air Leakage points

Unsealed exhaust fan in kitchen Ceiling vent in bedroom Between architrave and gyprock

Page 49: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 47

InsulationThermalimagingshowedthatthewallswereuninsulated.Ceilinginsulation,althoughpresent,appearedtobethinandpatchyinsomeareas.Onamild,sunnydayinMarch,thewallsofthemasterbedroomwereatapproximately13°C;theceilingwasat14.5°C.

Inadequate insulation

Main bedroom, south corner, ceiling 5 March 2012, 10:28:37 am

Main bedroom, south corner, walls 5 March 2012, 10:28:46 am

Main bedroom, south-west wall 5 March 2012, 10:51:47 am

Temperature and electricity useResultsfromthetemperaturedataloggershighlightthefollowing:

• Thisisaverycoldhouse.Theinternaltemperatureisonly5°Chigherthantheexternaltemperature.Atsomepointinthemiddleoftheday,theexternaltemperaturealmostmatchestheinternaltemperature.

• Post-retrofitting,internaltemperaturesremainedconstantdespiteadecreaseinenergyusebytheclient.Thisindicatesthatthehousemaintainstemperatureasaresultofimprovedinsulationanddraught-proofing.

• Unfortunately,aroundthesametimethatwallinsulationwasinstalled,anotherpersonmovedintothehouse,andtheenergy-useprofileofthehousechangeddramatically.Theincreasedenergyusewasnotassociatedwithheating.

Electricity use and temperature data in case study 4

Tem

pera

ture

(0 C)

Electricity use (kWh)

50 50

40 40

30 30

20 20

10 10

0 0

Bedroom temperature External temperature Kitchen temperature Lounge temperature Main bedroom temperature Electricity use

1 M

AY

1 JU

NE

1 AU

GUST

1 JU

LYLeakage test andeducation

Draught sealing 1

Wallinsulation

Curtainsand ceilinginsulation

Post retrofit

test

Draught sealing 2

Electricity use

Page 50: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

48 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Energy bills

Electricity usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 33 21 –35%

Winter* 74 42 –42%

Other observationsAsaresultofherinvolvementwiththeprogram,theclienthasmadeagreatefforttoreduceherenergybills.Shesayssheismuchmoreconsciousofenergyuseandhowtoreduceit.Followinghereducationsession—andlearningthedifferencebetweenpeakandoff-peakpower—shehaschangedsomewell-wornroutinesandnowdoesherwashingatnight.

Otherchangestheclienthasmadeinclude:

• turningheatingononlyinthemorningandevening

• turningheatingoffinthebedroomovernight

• turningappliancesoffatthewall

• closingcurtainstokeeptheheatinside

• dressingfortheclimate

• talkingwithSpotlessaboutpossibleupgradingofheatingtoanefficientsplit-systemforthelounge/diningarea.

Total energy, greenhouse gas and cost savings

Energy saving (kWh) CO2-e saving (kg)a Cost saving ($)b

Autumn* 1056 1119.80 133.41

Winter* 2780 2947.20 418.30

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

b Peak/off-peakrateisusedtocalculatecostsavingsforelectricityusage.

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 51: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 49

Case study 5Communitywelfareorganisation:NorthsideCommunityService

Serviceprovider:C&JGroup

Background information from Energy Efficiency Officer

Category Clientwouldbenefitfromanassessment,educationandbasicretrofit,suchascurtains,blindsanddraughtsealing

Household occupants 3

Financial circumstance Disabilitysupportpension

Type of residence Owner–occupier

Products to be replaced Washingmachine,refrigeratorandfreezer

Draught sealing required?

Couldbenefitfrompelmets.Sensorlightstaysonallthetime.Gasheatingsettingsarefaulty.Insulationinceilingisalmostnon-existent,andthereisnoinsulationinwalls.

Date of referral 11April2012

The house, its timeline of retrofitting activities and thermal performanceThreebedrooms,onebathroom,brickveneer,suspendedtimberfloor,100m2,35yearsold.

Themainlivingroomhasglazingtothenorth-east,withgoodpotentialforpassivesolarheatgaintotheareaofgreatestenergyuse.However,thelivingareaisopentotheadjoiningdiningarea,whichisglazedtothesouthandwest.Thisadditionalspaceandtheorientationofthewindowsreducetheabilityofthejointliving/diningareastoretainheat.Thelargestbedroomhasarelativelyhighglazing-to-floor-arearatio,andthewindowsareorientedtothewestandsouth—thesefeaturesmakeitathermalweakpoint.Uninsulatedwalls,alargenumberofceilingpenetrationsandpatchyceilinginsulationsignificantlyaffecttheamountofenergyrequiredtomaintaincomfortabletemperatures.

Thisclienthasrecentlyconnectedsolarpanels,andthesolarfeed-intariffisoffsettinganybills.

Thethermalperformancesimulationindicatedthatdraughtsealingwouldprovidea16%reductioninenergyuseforalowcost.

Aerial view ↑North Modelled in BERS4.2 thermal simulation software Pink: kitchen/dining; red: living; blue/purple: bedrooms; green: laundry/bathroom; yellow: corridor

Page 52: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

50 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Timeline of testing and retrofitting activities

Date Action

9May Temperatureandenergy-usedataloggersinstalled

21May Education

23May Airleakageassessmentandthermographicinspection

29May Draught-proofing

31May Top-upinsulation,curtainsandpelmetsinstalled

17June Post-retrofittestandcollectionoftemperatureandenergy-usedata

22June Finalblowerdoortestanddatacollection

Thermal performance simulation (energy efficiency rating) of proposed retrofit measures

Simulation and specifications

Star rating

Heating (MJ/m2)

Cooling (MJ/m2)

Total (MJ/m2)

Predicted reduction (%)

Actual cost ($)

Cost per MJ reduction ($)

Startingconditions:•CeilingsR2,walls/floorsR0•Multipleceilingvents(eachroom)

•Openexhaustfaninkitchen•Lightcurtains/blinds

2.8 396 34 430

Startingconditionsplus:•Draughtsealing

3.2 329 34 363 16 675 10

Startingconditionsplus:•InsulationR2inceiling

2.7 385 27 412 4 1920 106

Startingconditionsplus:•Curtainsandpelmetstolounge,diningandkitchen

2.8 386 34 420 2 2720 272

Completeretrofit:•Sealedexhaustfans•Sealedvents•Draughtsealed•R4inceiling•Curtainsandpelmetstolounge,diningandkitchen

3.4 313 26 339 21 5315 58

Air leakage results

Sourcesofairleakageincluded:

• permanentceilingventsineveryroom,includinglargeceilingventdirectlyabovefluedgasheaterinlivingroom

• openexhaustfaninkitchen

• unsealed‘Tastic’inbathroom

• arounddoorsandwindowframes

• aroundceilingandwallpenetrations,suchasroofaccessholeandwall-mountedair-conditioningsystems.

Page 53: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 51

Therateofairleakagewasreducedby41%byinstallingaDraftStoppa®inthekitchen,sealingoffunnecessaryceilingventsandsealingaroundexternaldoors.

Thepermanentventsandotherpenetrationsintheceilingseriouslycompromisedthepotentialofthehousetostaywarm.Heatedairfromwithinthehomewasrisingandrapidlyescapingintotheroofspaceviatheholesintheceiling.

Thereductioninairleakageachievedinthishome,byfocusingmainlyontheholesintheceiling,isequivalenttoclosinga31cmx31cmwindowinthebuildingenvelope.

Result from air leakage testing

Pre-retrofit Post-retrofit Difference

Airchangesperhourat50Pa 21.02 12.46 –41%

Effectiveleakageareaat4Pa(equivalentopensquarewindow)

49cmx49cm 38cmx38cm 31cmx31cm

Note: Apressuredifferenceof4Pabetweeninsideandoutsideisclosetothenormalpressuredifferentialexperiencedinthehomeoncold,windyCanberradays.

Air Leakage points

Gap through architrave and around door

One of many ceiling vents Leakage around roof access hole

InsulationTheroofhadrockwoolinsulationthatwasthinandunevenlyinstalled.Thiscausedsignificantfluctuationsinceilingtemperaturethroughoutthehouse.Thermalimagingindicatedthatnowallinsulationwaspresent(asexpectedinahouseofthisage).

Inadequate insulation

Living area, no wall insulation Lounge area, patchy ceiling insulation

Page 54: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

52 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Temperature and electricity usePassiveventilationthroughoutthishomeviamultipleceilingventsandotherunsealedpenetrationsisresponsibleforthelargefluctuationsininternaltemperature.Datafromthethermochronshighlightthefollowing:

• Beforetheretrofit,internaltemperatureswereregularlyonly8°Cwarmerthantheexternaltemperature.Aftertheretrofit,theywereregularly10°Cwarmerthantheexternaltemperature.

• Thekitchen/diningareaiswarmerafterretrofittingandreachesamaximumtemperatureabove20°Cmoreoften.

• Followingtheretrofit,thehomemaintainshighertemperaturesandexperienceslessfluctuationintemperature,butenergyusehasdecreased.

Electricity use and temperature data in case study 5

Tem

pera

ture

(0 C)

Electricity use (kWh)

50 50

40 40

30 30

20 20

10 10

0 0

Bedroom temperatureExternal temperatureKitchen temperatureElectricity use

1 JU

NE

1 JU

LYEducation and leakage test

Draught sealing and curtains/pelmets

and top-up insulation

Electricity use

Post retrofit

test

Energy billsAgasheaterisusedtomaintainthelivingareasatcomfortabletemperatures.Electricreverse-cyclesystemsareusedinthebedrooms.Gasconsumptiondecreased,butelectricityconsumptionwasstable.

Electricity usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn 19 22 +14%

Winter 18 19 +5%

Gas usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn 112 98 –12.5%

Winter 120 87 –27.5%

Electricity + gas usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn 131 120 –8%

Winter 138 106 –23%

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 55: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 53

Predicted versus actual reductions in energy useThermalsimulationsuggestedthatreductionsinenergyuseof21%forheatingandcoolingcouldbeachievedviathedraught-sealingandwindow-dressingmeasuresimplemented.

Actualenergyconsumptiondatafromquarterlybillsdemonstratea23%reductioninoverallhouseholdenergyuse(i.e.notjustheatingandcoolingbutalsoappliances,lighting,hotwaterheating,etc.)betweenwinter2011andwinter2012.Thissuggeststhateducationandassociatedbehaviouralchangecouldaccountfortheextrareductioninenergyconsumption.

Total energy, greenhouse gas and cost savings

Energy saving (kWh) CO2-e saving (kg)a Cost saving ($)b

Autumn* 1038 –14.84 61.18

Winter* 2921 467.85 213.82

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh.Emissionfactorfornaturalgasis51.33kgCO2-e/GJ(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

b Costsavingsforgasusagecalculatedusing2.113centspermegajoule

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 56: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

54 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Case study 6Communitywelfareorganisation:BelconnenCommunityService

Serviceprovider:CoolPlanet

Background information from Energy Efficiency Officer

Category Clientwouldbenefitfromanassessment,educationandbasicretrofit,suchascurtains,blindsanddraughtsealing

Household occupants 2

Financial circumstance Youngsinglemotheronpartpensionandpart-timework;largeenergybills

Type of residence HousingACTsinglestorey,2bedrooms,brickveneer,northfacing

Products to be replaced Refrigeratorandwashingmachinealreadyreplaced

Draught sealing required? Contractorengaged

Client concerns Theclienthaslivedinthishomeforoneyear.Shereportsthatthehomeisverycoldinwinterandveryhotinsummer.Thereisawall-mountedelectricheater,whichshetriesnottousebecauseofcosts.Therearelightblock-outcurtainsinallrooms,butnopelmets.Therearethreelargeventsthroughoutthehome:twoareforventilationandtheotherisaskylight.Theclientreportsmassivedraughtsfromthese.Therearealsogapsaroundandunderdoors,whichsheblockswith‘doorsnakes’.Shehasenergy-efficientlightinginherhomeandisawareofenergyefficiency,butwouldlikefurthereducationandinformationtomakechoicesaboutherheating.EnergyEfficiencyOfficertalkedabouttheuseofpassiveheatingthroughnorth-facingwindows,aheatedthrowrugandcolumn-heateruse,aswellashighlightingthepotentialfortheretrofittoincreasethecomfortofherhome.

Date of referral 6April2012

The house, its timeline of retrofitting activities and thermal performanceTwo-bedroom,brick-veneertownhouse.

Thepotentialforpassivesolarheatgaintothishouseisgoodasaresultofthelargeareaofnorth-facingglazinginthelounge/living/kitchenarea.Thetwobedroomshavesouth-facingwindows.Themainissuewiththishouseistheventedskylightsusedinthekitchenandbathroomsforventilationandlight.

Thethermalperformancesimulationindicatesthatdraughtsealingceilingventsandfittingdamperstoexhaustfansisthesinglemosteffectiveretrofitmeasureforthishome,withapredicted21%reductioninenergyrequirementsforheatingandcooling.

Thebestallocationoftheretrofitbudgetwas$700—draughtseal;$1700—draughtsealandtop-upinsulationinceiling.

Aerial view ↑North Modelled in BERS4.2 thermal simulation software Pink: kitchen/dining/living; brown: garage; blue: bedrooms; green: laundry/bathroom; yellow: corridor

Page 57: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 55

Timeline of testing and retrofitting activities

Date Action

18April Temperatureandenergy-usedataloggersinstalled

10May Airleakageassessmentandthermographicinspection

6June Ceilinginsulationinstalled

11June Draught-proofing

12June Education

20June Draught-proofingbathroom,newextractorfaninstalled,andinvestigationofdampinchild’sbedroom

22June Post-retrofittest,andcollectionoftemperatureandenergy-usedata

Thermal performance simulation (energy efficiency rating) of proposed retrofit measures

Simulation and specifications

Star rating

Heating (MJ/m2)

Cooling (MJ/m2)

Total (MJ/m2)

Predicted reduction (%)

Actual cost ($)

Cost per MJ reduction ($)

Startingconditions:•CeilingsR3.5,wallsR1.5•Openexhaustfan•Draughtsealed•Nopelmets,lightdressing•Open-shaftskylightsx3

4.2 252 16 268

Startingconditionsplus:•Pelmetsx6

4.4 237 16 253 6 720 48

Startingconditionsplus:•Sealedexhaustfan•Sealedskylights

4.9 204 17 221 18 1578 34

Completeretrofit:•Sealedexhaustfans•Sealedskylights•Pelmetsx6

5.2 189 17 206 23 2298 37

Air leakage resultsTheoverallconditionandbuildofthehousewasreasonablygood,asexpectedforahouselessthan10yearsold.TheinitialairleakagedatashowedhigherthanaverageairexchangeratesforCanberrahomes.Thiswasmainlyduetothreevented-shaftskylightsinthebathroomsandtheopen-plankitchen/livingarea.Thesewereventedtotheroofcavityandallowedlargevolumesofairtoriseandescape.

Thissimplebuildingoversightanddesignflawwaseasilyrectifiedbyaddingsealedexhaustfansineachbathroomandsealingtheshaftswithremovableperspex.

Theimagesbelowshowtheairexchangeoccurringthroughtheskylights.Itisinterestingtonotethedifferenceintemperaturebetweentheairintheskylightshaftandthesurrounds—theairintheshaftiswarmer,partlyasaresultofthestackeffect,aswellasthesolarheatgainthroughtheshaftfromthemorningsun.

Airinfiltrationcanalsobeseenaroundtheroofaccessholeanddoors.Thesegapsaccountforthebulkoftheremainingunwantedairexchange.

Page 58: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

56 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Therateofairleakagewasreducedby75%afterdraughtsealingtheventedskylightsandaroundtheexternaldoors.Thereductioninairleakageachievedinthishome,byfocusingmainlyontheholesintheceiling,isequivalenttoclosinga25cmx25cmwindowinthebuildingenvelope.

Result from air leakage testing

Pre-retrofit Post-retrofit Difference

Airchangesperhourat50Pa 28.2 7.1 –75%

Effectiveleakageareaat4Pa(equivalentopensquarewindow)

48cmx48cm 23cmx23cm 42cmx42cm

Note: Apressuredifferenceof4Pabetweeninsideandoutsideisclosetothenormalpressuredifferentialexperiencedinthehomeoncold,windyCanberradays.

Air Leakage points

Vented skylight in kitchen Vented skylight and fan in bathroom

Leakage around roof access hole in laundry

InsulationTheroofwasreasonablyinsulated,butthewallshadnoinsulation.Theimagesbelowindicatethetemperaturedifferencesbetween:

• thewallsandtheceiling(showingtheeffectofinsulation)

• insulatedanduninsulatedsectionsoftheceiling

• internalandexternalwalls(wheretheinternalwallsareprotectedfromlargetemperaturefluctuationsbythesemi-conditionedspaceofthegarage).

Inadequate insulation

Insulated ceiling and uninsulated wall

Patchy ceiling insulation 5 October 2012, 10:36:38am

Internal and external walls 5 October 2012, 10:45:31am

Temperature and electricity useThedatagatheredshowthatenergyusestayedthesame(around40kWh/day)followingretrofitting.

Passiveventilationthroughoutthishomeviamultipleventedskylightsandotherunsealedpenetrationsisresponsibleforthelargefluctuationsininternaltemperature.Theenergyuseisthesamefollowingretrofit,buttheinternaltemperatureofthehomehasdramaticallyincreased.Thismaybeduetotheclientenjoyingthe

Page 59: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 57

feelingofwarmthinherhomeornotbeingfullyawarethatheatingisstillbeingusedandtheneedtolowerthethermostat.Thishighlightstheneedforfollow-upeducationsessionsfollowingretrofittingmeasuressothatclientsareawareofhowtheycanreducetheirenergyuse.

Electricity use and temperature data in case study 6

Tem

pera

ture

(0 C)

Electricity use (kWh)

50 50

40 40

30 30

20 20

10 10

0 0

Bedroom temperature External temperature Living room temperature

Electricity use1

MAY

1 JU

NELeakage

testingCeiling

insulationinstalled

Draught sealing 2

Postretrofit test

Educationdraught sealing 1

Electricity use

Energy bills

Electricity usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 23 14 –40%

Winter* 67 44 –35%

Predicted versus actual reductions in energy useThermalsimulationsuggestedthatreductionsinenergyuseof23%forheatingandcoolingcouldbeachievedviathedraught-sealingandwindow-dressingmeasuresimplemented.

Actualenergyconsumptiondatafromquarterlybillsdemonstratea35%reductioninoverallhouseholdenergyuse(i.e.notjustheatingandcoolingbutalsoappliances,lighting,hotwaterheating,etc.)betweenwinter2011andwinter2012.Thissuggeststhateducationandassociatedbehaviouralchangecouldaccountfortheextrareductioninenergyconsumption.

Total energy, greenhouse gas and cost savings

Energy saving (kWh) CO2-e saving (kg)a Cost saving ($)b

Autumn* 845 895.79 128.03

Winter* 2103 2229.09 345.65

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

b Actualratesforautumnandwinter2012wereusedtocalculatethecostsavingsforelectricityusage.

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 60: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

58 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Case study 7Communitywelfareorganisation:Communities@Work

Serviceprovider:CoolPlanet

Background information from Energy Efficiency Officer

Category Homeisdraughty,withnocurtainsorblinds,andtheclienteitherhashighbillsorislivinginimpoverishedconditions.Clientwouldbenefitgreatlyfromanassessment,educationandbasicretrofit.

Household occupants 3

Financial circumstance Low-incomehousehold

Type of residence Owner–occupier

Products to be replaced Refrigeratorandwashingmachine

Draught sealing required? Requiresdraught-proofingtoaddressairleakage.Requireswindowfurnishing,includingpelmets,toreducecurrenthighlossthroughaluminium-framedsingle-glazedwindows.Insulationtoceilingandwallsrequiressurveyandsubsequentrectification—minimumR5toceilings,R3towalls.

Client concerns Coldinwinter,hotinsummer

Date of referral 5May2012

The house, its timeline of retrofitting activities and thermal performanceTwo-bedroom,brick-veneertownhouse.

Thethermalperformancesimulationindicatesthatdraughtsealingshouldbetwiceascost-effectiveaswindow-dressingupgradesinthishouse.

Aerial view ↑North Case study 7 is the unit in the centre

Modelled in BERS4.2 thermal simulation software Pink: kitchen/dining/living; blue/purple: bedrooms; green: laundry/bathroom; yellow: corridor

Timeline of testing and retrofitting activities

Date Action

18May Temperatureandenergy-usedataloggersinstalled

7June Airleakageassessmentandthermographicinspection

12July Draught-proofing

24July Education

27July Post-retrofittestandcollectionoftemperatureandenergy-usedata

July–September Furtherdraught-proofingcavitydoorsliderandwall–ceilingjoins(exactdateunclear)

19September Curtainsandpelmetsinstalled

Page 61: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 59

Thermal performance simulation (energy efficiency rating) of proposed retrofit measures

Simulation and specifications

Star rating

Heating (MJ/m2)

Cooling (MJ/m2)

Total (MJ/m2)

Predicted reduction (%)

Actual cost ($)

Cost per MJ reduction ($)

Startingconditions:•CeilingsR3.5•Down-lightsx4•Openexhaustfaninkitchen,open-shaftskylightinbathroom

•Verydraughty

3.3 290 18 309

Startingconditionsplus:•Curtainstolivingareas•Blindtokitchen

4.3 244 19 260 16 1720 35

Startingconditionsplus:•Exhaustfancover•Down-lightcoversx4•Sealedskylight•Draughtsealing2xdoors/windows

4.2 256 19 274 11 561 16

Completeretrofit•Curtainstolivingareas•Blindtokitchen•Exhaustfancover•Down-lightcoversx4•Sealedskylight•Draughtsealing2xdoors/windows

4.9 207 15 222 28 2282 26

Air leakage resultsThehousewasbuiltinthelast10–20yearsandisinreasonablecondition.Ithasagoodnortherlyaspecttothelivingroomandtwobedrooms.Thehouseperformedreasonablywellduringinitialtestingwithrespecttoairleakage.However,giventhesmallsizeofthehouseandtheorientation,therewasplentyofscopeforimprovement.

Initialtestingofthebuildingshowedareasonablytightbuildingenvelope,withsomemajorpitfalls.Themainleakagewasaresultofanopen-shaftskylight,wall-mountedpanelheaterandventedrefrigeratorspace.Otherareasofleakageinclude:

• betweeninternalbrickandplasterboardinternalwalls

• betweenbricksandwindowframes,aswellassliding-doorframe

• throughinternal-wallsliding-doorframe

• gapswherebrickworkmeetsceiling

• unsealedexhaustfaninkitchen

• permanentopeningabovefridge

• unsealedopen-shaftskylight

• cavityslidingdoor

• wall-mountedpanelheater

• roofaccesshole.

Page 62: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

60 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Airleakagewasreducedby:

• sealingbetweentheinternalbrickwallandadjoiningwallsandcornicing

• installationofaDraftStoppa®abovethetoiletfan

• sealingarounddoorframesandcatches

• sealingaroundarchitravesanddoorframes

• sealingtheskylightinthebathroom.

Result from air leakage testing

Pre-retrofit Post-retrofit Difference

Airchangesperhourat50Pa 16.8 10.19 –40%

Effectiveleakageareaat4Pa(equivalentopensquarewindow)

34cmx34cm 23cmx23cm 25cmx25cm

Note: Apressuredifferenceof4Pabetweeninsideandoutsideisclosetothenormalpressuredifferentialexperiencedinthehomeoncold,windyCanberradays.

Air Leakage points

Leakage between architrave and gyprock

Leakage around roof access hole Leakage through sliding cavity door

Temperature and electricity useTheresultssuggestthatenergyusedecreased,andinternaltemperaturesincreasedinmid-Julyfollowingdraughtsealing.Theresultsareveryerratic,however,andthisisthoughttoberelatedtothehomeownerfrequentlygoingawayforextendedperiods.

Page 63: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 61

Electricity use and temperature data in case study 7

Draught sealing 1

Draught sealing 1

Education Curtains and pelmets

Postretrofit

test

Tem

pera

ture

(0 C)

1 AU

G

1 SE

PT

5 5

10 10

15 15

20 20

25 25

30 30

35 35

0 0

1 JU

NE

1 JU

LY

Hallway temperatureExternal temperatureKitchen temperatureElectricity use Electricity use

Leakage test

Energy bills

Electricity usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 7 8 14%

Winter* 9 15 62%

Gas usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 19 16 –16%

Winter* 43 36 –16%

Electricity + gas usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 28 24 –14%

Winter* 52 51 –2%

Total energy, greenhouse gas and cost savings

Energy saving (kWh) CO2-e saving (kg)a Cost savings ($)b

Autumn* 176 –52.25 6.1

Winter* 117 –434.05 –38.47

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh.Emissionfactorfornaturalgasis51.33kgCO2-e/GJ(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

b Costsavingsforgasusagecalculatedusing2.113centspermegajoule*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 64: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

62 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Case study 8Communitywelfareorganisation:Communities@work

Serviceprovider:CoolPlanet

Background information from Energy Efficiency Officer

Category Homeisdraughty,withnocurtainsorblinds,andtheclienteitherhashighbillsorislivinginimpoverishedconditions.Clientwouldbenefitgreatlyfromanassessment,educationandbasicretrofit.

Household occupants 3

Financial circumstance Low-incomehousehold

Type of residence HousingACTtenant

Products to be replaced Nil—awaitingcasestudy

Draught sealing required? Draughty,highairleakagehome,requiresdoor-baseanddoor-framesealing

Client concerns Coldinwinter,hotinsummer,highenergybills

Date of referral 17May2012

The house, its timeline of retrofitting activities and thermal performanceFour-bedroom,brickveneertownhouse,approximately40yearsold.

Thethermalperformancesimulationindicatesthatdraughtsealingwouldbefivetimesmorecost-effectivethanwindow-dressingupgradesinthishouse.

Aerial view ↑North Modelled in BERS4.2 thermal simulation software Pink: kitchen/dining; red: living; blue/purple: bedrooms; green: laundry/bathroom; yellow: corridor

Timeline of testing and retrofitting activities

Date Action

24May Temperatureandenergy-usedataloggersinstalled

7June Airleakageassessment

7July Draught-proofing

12July Draught-proofingofbathroomexhaustfan/skylight

27July Post-retrofittestandcollectionoftemperatureandenergy-usedata

5December Curtainsandpelmetsinstalled

Page 65: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 63

Thermal performance simulation (energy efficiency rating) of proposed retrofit measures

Simulation and specifications

Star rating

Heating (MJ/m2)

Cooling (MJ/m2)

Total (MJ/m2)

Predicted reduction (%)

Actual cost ($)

Cost per MJ reduction ($)

Startingconditions:•CeilingsR3•Unsealedexhaustfaninkitchenandbathroom

•Verydraughty

2.8 318 28 346

Startingconditionsplus:•Curtainstolivingareas

2.9 303 25 328 5 1570 87

Startingconditionsplus:•Exhaustfancovers•Draughtsealing

3.1 282 28 310 10 575 16

Completeretrofit:•Curtainstolivingareas•Exhaustfancovers•Draughtsealing

3.4 267 25 291 16 2145 39

Air leakage resultsThishousehadasurprisinglytightbuildingenvelopeforitsage,mainlyasaresultofitslackofceilingandwallvents,whichcanbecommoninthesehouses,anditsarchitravesandcornicing,whichwereinreasonablecondition.

Measurestoreduceairleakageincluded:

• sealingtwoexhaustfansusingDraftStoppas®

• resealingsomearchitravesusingsealant

• sealingexternaldoorwaysaroundthesidesandatthebottom.

Withthesefairlyminormodifications,thehousereachedcloseto10airchangesperhourat50Pa.Tofurtherreduceairleakage,thehousewouldrequirenewwindowsthatsealmoreeffectively.

Result from air leakage testing

Pre-retrofit Post-retrofit Difference

Airchangesperhourat50Pa 16.03 10.42 –36%

Effectiveleakageareaat4Pa(equivalentopensquarewindow)

40cmx40cm 33cmx33cm 23cmx23cm

Note: Apressuredifferenceof4Pabetweeninsideandoutsideisclosetothenormalpressuredifferentialexperiencedinthehomeoncold,windyCanberradays.

Refrigerator replacement

Energy usage results for old and new refrigerators

Energy use (kWh/day) Energy use (kWh/year) CO2-e (kg/year)a Difference

Old 2.3 839 889

New 0.91 334 354 –61%

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

Page 66: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

64 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Energy bills

Electricity usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 54 51 –6%

Winter* 67 58 –13%

Predicted versus actual reductions in energy useThermalsimulationsuggestedthatreductionsinannualenergyforheatingandcoolingof16%couldbeachievedviathedraught-sealingandwindow-dressingmeasuresimplemented.

Actualenergyconsumptiondatafromquarterlybillsdemonstratea13%reductioninoverallhouseholdenergyuse(i.e.notjustheatingandcoolingbutalsoappliances,lighting,hotwaterheating,etc.)betweenwinter2011andwinter2012.Thedifferencebetweenactualandpredictedenergysavingsislikelytobeduetoclientbehaviour.

Total energy, greenhouse gas and cost savings

Energy saving (kWh) CO2-e saving (kg)a Cost saving ($)b

Autumn* 291 308.19 44.05

Winter* 804 852.23 138.62

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

b Autumnandwinter2012rateisusedtocalculatecostsavingsforelectricityusage.

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 67: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 65

Case study 9Communitywelfareorganisation:YWCAofCanberra

Serviceprovider:C&JGroup

Background information from Energy Efficiency Officer

Category Clientwouldbenefitfromanassessment,educationandbasicretrofit,suchascurtains,blindsanddraughtsealing

Household occupants 1

Financial circumstance Centrelink

Type of residence ACTHousing

Products to be replaced Refrigerator

Draught sealing required?

RecommendedtoclienttocontactSpotless.Draughtsealingrequiredandinsulationcheck.Houselooksdraughty.

Client concerns Draughtyhouse,whichgetshotandcold.Curtainsexistbutaredirty;theclientisconcernedaboutprivacy,becauselivingroomwindowsfaceontoamajorroad.Possiblycouldalsoimprovethecurtaincurrentlyusedtozonethelivingarea.

Date of referral 10April2012

The house, its timeline of retrofitting activities and thermal performanceTwo-bedroom,three-storey,brick-veneerapartment,withneighbourstothenorthandsouth,approximately50yearsold.Casestudy9wasnotmodelledinBERS4.2thermalsimulationsoftwarebecauseitwasrecruitedlatetotheprogramandwasalreadya6-starhouse.

Thermal performance simulation (energy efficiency rating) of proposed retrofit measuresThermalperformancesimulationwasnotperformedbecauseofthecomplexity,anddifficultyinaccessingallareas,oftheoldthree-storeyunit.

Aerial view ↑North

Timeline of testing and retrofitting activities

Date Action

18April Temperatureandenergy-usedataloggersinstalled

11May Education

11May Airleakageassessment

25June Curtains,pelmets,lightinganddraughtsealingcompleted

13July Finalcollectionofdata

Page 68: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

66 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Air leakage resultsApressuredifferenceof4Pabetweeninsideandoutsideisclosetothenormalpressuredifferentialexperiencedinthehomeoncold,windyCanberradays.

Theoverallleakagerateofthisbuildingwaslowcomparedwithothercasestudyhousesbecausetheexternalwallandroofareawasrelativelysmallasaresultofitsthree-storey,multi-unitconstruction.Becausetheairleakageratewasalreadybelowourtargetof10airchangesperhourat50Pa,anditwasdifficulttotestinaconfinedentrancewayinthethree-storeyapartment,apost-retrofittestwasnotconducted.However,thereweresignificantleaksthatcouldbesealed,including:

• unsealedexhaustfaninkitchen

• permanentopeningsinwallsabovewindowsinkitchen,bathroomandlivingareas

• plumbingandelectricalpenetrationsbehindkitchenjoinery

• arounddoorsandsurroundingarchitrave,particularlyinthestaircase

• aroundoldwall-mountedheater

• betweenwindowsandgyprock,walljunctionsandroofbeams.

Measurestoaddresssomeoftheseleaksincluded:

• usingperspextosealaroundplumbingpenetrationsunderthekitchensink(althoughtherewerestillnoticeableleaksaroundthesepenetrations)

• addingsomesealantaroundarchitraves

• sealingvariousdoors.

Themainlivingareasdownstairshadapermanentopendoorframe,allowinganywarmairtoriseupthestairsandventouttheupstairspermanentopenings.

Therooflackedinsulation,andhenceanywarmaircontainedwasquicklycooledbythesurroundingcoldwalls.

Result from air leakage testing

Pre-retrofit Post-retrofit Difference

Airchangesperhourat50Pa 9.4 – –

Effectiveleakageareaat4Pa(equivalentopensquarewindow)

25cm×25cm – –

Notes: Casestudy9wasnotretestedforairleakageafterretrofittingbecauseitwasalreadybelowthetargetlevelof10airchangesperhourat50Pa,andfundswerebetterspentonhomesthatwerefurtherfromthistarget.

Page 69: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 67

Temperature and electricity useThisapartmentusesaveryinefficientheatingsystemtokeepinternaltemperatures10°Chigherthanexternaltemperatures.

Electricity use and temperature data in case study 9

Tem

pera

ture

(0 C)

1 JU

NE

20 20

40 40

60 60

80 80

100 100

120 120

140 140

160 160

0 01

JULY

Electricity use

Hallway temperatureExternal temperatureElectricity use

Leakagetest and education

Draught sealingand curtains

Energy bills

Electricity

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 27.3 23 –16%

Winter* 146 89 –39%

Total energy, greenhouse gas and cost savings

Energy saving (kWh) CO2-e saving (kg)a Cost saving ($)b

Autumn* 399 422.84 60.43

Winter* 5185 5496.05 928.10

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

b Variableratesareusedtocalculatecostsavingsforelectricityusage.

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 70: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

68 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Case study 10Communitywelfareorganisation:BelconnenCommunityService

Serviceprovider:CoolPlanet

Background information from Energy Efficiency Officer

Category Clientwouldbenefitfromanassessment,educationandbasicretrofit,suchascurtains,blindsanddraughtsealing

Household occupants Threetenantswithmoderatetoprofounddisabilities;1–2staffon24/7,andothercasualstaffthroughouttheday

Financial circumstance AlltenantsondisabilitysupportpensionType of residence ACTHousing,single-storeybrick-veneerfour-bedroomnewhome;sideofhouseis

northfacing,butthereisalargehomenextdoor,andaverandablocksmostofsun.Products to be replaced Monitorsplacedonsecondrefrigeratorandwashingmachine.(Appliancesmay

bereplacedbutarerelativelynew.)EarthSmartpowerboard,electricthrowandoutdoorclotheslinetobeprovided.ClotheslinependingapprovalfromEnvironmentandSustainableDevelopmentDirectorate.

Draught sealing required? Inadequateinsulation;contractorhascheckedandwillupgradeinsulation.Client concerns Concernsraisedaboutthehighcostofenergybills.Thefamilyoftheclientsissure

thatenergyusecanbedecreased.Thereisgasductedheatingthroughoutthehome.Itisdifficulttochangetheheatingsituationbecausethetenantshavevaryingdegreesofphysicaldisability.Block-outcurtainsareonmostofthewindows,buttherearenopelmets.Thewashingmachineisusedseveraltimesperday.Staffandfamilyareveryopentofurthereducationandretrofitting,andhaveagreedtobepartofacasestudy.

Date of referral 4May2012

The house, its timeline of retrofitting activities and thermal performanceFour-bedroom,brick-veneerhousebuiltin2009.Excellentsolaraccesstomainlivingareas.

Thermal performance simulation (energy efficiency rating) of proposed retrofit measures Thermalperformancesimulationwasnotconductedforcasestudy10because,whenthehousewasbuiltin2009,thedesignwasrequiredtomeetminimum6-starstandards.Thecertifiedenergyratedplanswereprovidedandshowedthatthetotalpredictedheatingandcoolingloadforthehousewasjust146MJ/m2.

Aerial view ↑North (at 45-degree angle)

Timeline of testing and retrofitting activities

Date Action

15May Temperatureandenergy-usedataloggersinstalled

21May Education

31May Airleakageassessment

18June Draught-proofingandcurtaininstallation

13July Follow-upairleakage,anddatacollection

Page 71: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 69

Air leakage resultsTheinternalbuildingenvelopeofthisrecentlybuilthousewasrelativelywellsealedtobeginwith.

Theareaswhereleakagewasoccurringincluded:

• aroundslidingdoorframes

• exhaustventsinthebathroomandlaundry

• openventilationbehindrefrigeratorandoven

• smallgapsinandaroundwindowsanddoorframes

• ceiling-mountedair-conditioningvents.

Thelaundrydoorwassealedusingbrushstripping,andfoamwasusedtosealaroundthesidesoftherefrigeratortolimitaircirculationtotheareabehindtherefrigeratorwhereitismosteffective.

Significanteffortandbudgetwouldberequiredtofurthersealahouseofthissize.Itisalsounlikelytoreturnsignificantbenefits.Theenergyusageofthehousecouldbebetterreducedwithfurtherattentiontoinsulation,heatingmanagementandenergy-efficientwhitegoods.

Result from air leakage testing

Pre-retrofit Post-retrofit Difference

Airchangesperhourat50Pa 9.99 9.60 –4%

Effectiveleakageareaat4Pa(equivalentopensquarewindow)

48cmx48cm 47cmx47cm 10cmx10cm

Note: Apressuredifferenceof4Pabetweeninsideandoutsideisclosetothenormalpressuredifferentialexperiencedinthehomeoncold,windyCanberradays.

Energy billsThisisnotatypicalhouseintermsofenergyusebecausetheresidentsrequireconstantassistance.Thereareusually4–7peopleinthehouseatanyonetime.

Electricity usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 36 32 –10%

Winter* 25 26 +4%

Gas usage

Energy use 2011 (kWh/day) Energy use (kWh/day) Difference

Autumn* 128 114 –11%

Winter* 65 84 +30%

Total energy, greenhouse gas and cost savings

Energy saving (kWh) CO2-e saving (kg)a Cost saving ($)b

Autumn* 1602 582.57 149.59

Winter* –1817 –412.76 –145.71

a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh(source:AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).

b 2012rateisusedtocalculatecostsavingsforgasusage.

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August

Page 72: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

70 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Case study 11Communitywelfareorganisation:NorthsideCommunityService

Serviceprovider:C&JGroup

Background information from Energy Efficiency Officer

Category Clientwouldbenefitfromanassessment,educationandbasicretrofit,suchascurtains,blindsanddraughtsealing

Household occupants 2

Financial circumstance Disabilitysupportpension

Type of residence Homeowner

Products to be replaced –

Draught sealing required? Yes.Gapsindoorsandwindows,vents,down-lights.

Client concerns Clientgetsverycoldinwinter.Possibleupgradeofinsulation.Windowcoveringsareinadequateinpartsofthepropertywhereheatislost.

Date of referral 27April2012

The house, its thermal performance and timeline of retrofitting activitiesFour-bedroom,brick-veneerhouse.

Thermalperformancesimulation(energy efficiencyrating)ofproposedretrofitmeasures Thermalperformancesimulationwasnotconductedforcasestudy11becauseoftimeconstraints.

Aerial view ↑North

Timeline of testing and retrofitting activities

Date Action

9May Temperatureandenergy-usedataloggersinstalled

25May Airleakageassessment

6June Education

8June Draught-proofing

19July Follow-upairleakage,anddatacollection

23August Curtainandpelmetinstalled

Page 73: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

environment.act.gov.au 71

Air leakage resultsThethermalperformanceofthehousewassignificantlycompromisedbyarangeofpenetrationsandopeningsinthebuildingenvelope,including:

• severalunsealedexhaustfansinkitchen,toiletandbathroom

• permanentventsinthewallsinmostrooms

• recessedlightinginceiling

• unsealed‘Tastic’inbathroom

• leakagearounddoorsandsurroundingarchitraveinfrontextensionroom,aswellasbetweenthebrickwallandceilinggyprock

• leakagearoundandthroughwindowframes

• leakagebetweenwindowarchitravesandgyprock

• permanentopeningsintoiletdoor

• leakagethroughslidingdooropeningsinbathroom

• gapsaroundceilingvents

• gapsthroughandarounddoorways

• gapsaroundslidingdoorinbathroom.

Measurestoreduceairleakageincluded:

• placingDraftStoppas®overthebathroomandkitchenfans

• sealingthepermanentwallvents(therecessedlightingwasunabletobesealedasthelightfittingsweretoolarge)

• siliconingceilingvents,wherepossible

• sealingdoorwayswithsealingtapeanddoorstops.

Theretrofitmadeasmalldifferencebut,giventhesizeofthehouseandthenumberofproblems,itwouldgreatlybenefitfromfurthertimeandbudgetbeingallocatedtoreducefurtherairleakage,particularlythroughthebathroomviatheunsealedTastic.Therecessedlightsshouldberemoved,andtheevaporativecoolingsystemshouldhaveventsplacedoverthesystembecauseitisparticularlyleaky.

Result from air leakage testing

Pre-retrofit Post-retrofit Difference

Airchangesperhourat50Pa 20.24 17.14 –15%

Effectiveleakageareaat4Pa(equivalentopensquarewindow)

48cmx48cm 46cmx46cm 14cmx14cm

Note: Apressuredifferenceof4Pabetweeninsideandoutsideisclosetothenormalpressuredifferentialexperiencedinthehomeoncold,windyCanberradays.

Page 74: Outreach Energy and Water Efficiency Program · to Housing ACT for draught sealing and ceiling insulation top-ups. ... 8 Outreach Energy and Water Efficiency Program - Case study

72 OutreachEnergyandWaterEfficiencyProgram-Casestudyreport

Temperature and electricity useThehouseusescentralgasheatingtomaintainverycomfortabletemperaturesrelativetoexternaltemperatures.Thepoorhealthoftheresidentsandthefactthattheyarehomealldayincreasestheirenergyrequirements.

Electricity use and temperature data in case study 11

Tem

pera

ture

(0 C)

Electricity use (kWh)

40 45

30 30

35 35

25 25

20 20

15 15

10 10

5 5

0 0

Kitchen temperatureExternal temperatureLounge temperatureElectricity use

1 JU

NE

1 JU

LY

Electricity use

Leakagetest

Draughtsealing

Education Postretrofit

test

Energy bills

Electricity usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 29 22 –25%

Winter* 28 24 –16%

Gas usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 121 136 +12%

Winter* 142 133 –6%

Electricity + gas usage

Energy use 2011 (kWh/day) Energy use 2012 (kWh/day) Difference

Autumn* 150 158 +5%

Winter* 170 157 –8%

Total energy, greenhouse gas and cost savings

Energy saving (kWh) CO2-e saving (kg)a Cost saving ($)b

Autumn* –704 448.19 –12.08

Winter* 1237 595.07 130.81a Scope2+Scope3emissionfactorforelectricityis1.06kgCO2-e/kWh.Emissionfactorfornaturalgasis51.33kgCO2-e/GJ(source:

AustralianGovernmentDepartmentofClimateChangeandEnergyEfficiency,National Greenhouse Gas Accounts factors,July2012).b Costsavingsforgasusagecalculatedusing2.113centspermegajoule

*Autumn=billingperiodsbeginninginMarch–May;winter=billingperiodsbeginninginJune–August