Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Opti-Climate YAM SeriesAir Handling Units
3
Tailor Made Design
Energy Saving
Quiet Operation Precise Control
of Temperature & Humidity
Indoor Air Quality
Indoor Air Clean
Intelligent Control
54
YAM Features
The patented design of YAM series meets the EN 1886 Class(D1, L1, T2, TB2). The unit casing consists of foam injected, cold bridge free, AL frame profiles and high density polymerized polyurethane foam injected panel with edges, which are joined together with strong AL-plastic composite tri-axial angle lug.
China utility model patent No. ZL201220187540.1
The casing boasts a strong frame that is a complete metal complex of AL-plastic composite tri-axial angle lug and foam injected AL profile.
Coupling with high-quality closed cell foam synthetic rubber, the unique knife-shaped at the foam panel edge gives perfect ring seal.
The air leakage at joint is eliminated by the anti-flaming and high/low temperature resistant gasket and professional mechanical assemble.
The air leakage at the double-layer sealed access door is eliminated by reliable vehicle-using sponge sealing strip and high-strength lockers.
Double skin construction is provided by "sandwich" type with high density strip.
The foam panel and profile skins are injected with PU foam of 45kg/m3, providing a thermal conductivity coefficient lower than 0.02W/m·k.
Al profile employs nylon insulation strips design and the skin is filled with PU foam.
The damper and drain pan are fixed with strips to isolate the cold bridge.
The drain pan uses 20mm thickness synthetic rubber insulation for heat resistance and anti-condensation.
The flush-joint from the panel to frame has a smooth surface and arcs at corners to prevent dirt retention and water standing.
Drain pan is dual V-shaped structure with longitudinal slope, and allows quick and easy drainage of condensate water.
The high quality direct-driven fan (plug fan) is optional, to avoid pollution caused by wheel belt.
Airflow Range: 1,200~200,000m3/h
High Intensity
Superior Performance
Low Air Leakage
Better Heat Insulation
Cold Bridge Free Design
Special design for clean-room industry application
76
Nomenclature Selection Software Overview
Model Description
Note
Unit Hand: Left Hand (L) or Right Hand (R)
Unit Configuration: S-Single-tier, D-Double-tier
Opti-Climate YAM Series AHU
Insulation Thickness: 50mm
Dimension: Height Module × Width Module, 15M×18M
YAM 50 - 1518 - S - R
Distinguishing the unit hand
Single-tier units
Double-tier units
Calculating the Overall Dimension
1. Module Design: 1M=95mm2. Unit Height a) Height of single-tier unit
= (Height module × 95 + 96) + Height of base (mm)Example: Height of 15M high single-tier unit with 100mm base= (15 × 95 + 96) + 100 = 1621 (mm)
b) Height of double-tier unit =2× (Height module × 95 + 96) + Height of base (mm)Example: Height of 15M high double-tier unit with 100mm base=2× (15 × 95 + 96) + 100 = 3142 (mm)
3. Unit Width = Width module × 95 + 96(mm) Example: Width of 18M-wide unit = 18×95 + 96 = 1806 (mm)4. Length of the unit = Sum of lengths of all delivery sections. Length of delivery section = length module ×95 + 96 (mm) Example: Length of 28M - long delivery section = 28 × 95 + 96 = 2756 (mm)
AECworks YAM Selection Software Features
Custom Made The user-friendly selection software UI makes easy selection. The perfect project management system quickly responds to customer's increasing design requirements.
The flexible parametric design improves the design efficiency and effectively shortens supply period.
Powerful Function Diverse configurations include simple and practical single-tier unit, slim unit and double-tier unit with smaller occupied area, to meet various customer requirements.
Over 400 models including 81 preferred standard models are available to satisfy for both ordinary application and special applications with high requirement for dimension.
Providing more than 20 segments for your option.
Professional software for coil selection Providing diverse rows of coils, circuit designs and fin options, the software is suitable for different operating conditions and environments, and can optimize configuration and improve efficiency of heat exchange.
Comprehensive Output Reports Comprehensive performance report is provided. Scaled assembly drawing with automatic output is provided
for professional's direct use Psychrometric I-D chart is provided to help to determine air state parameters in each functional Segment and visually reflect the changes of air parameter.
9M
C
6M 6M 5M
2566
475
390
100
1241
25661201
9013401521
The left hand is shown in the figure.
The left hand is shown in the figure.
98
0 5000 10000 15000 20000 25000 30000 35000 40000
0507070705110709090913070713110909110715111109151311091715111115131317111117131511201515131820131320151817171520221513241719241515241722202015272022241926181726
推荐风量(2.0~2.5m/s) 高速风量(2.5~3.0m/s)
Airflow: m3/h
Note: Preferred standard models are listed.
Quick Selection
Model
20000 30000 40000 50000 60000 70000 80000 90000 100000 110000 120000 130000 140000 150000 160000 170000 180000 190000 200000 210000
22221728262022241730282020283019242422282624282424292628322428282433302726332436283432323036323630462654324628542658344628583254305834543258345830663266346632723472
推荐风量(2.0~2.5m/s) 高速风量(2.5~3.0m/s)
Airflow: m3/h
Note: Preferred standard models are listed.
Model
Airflow under recommended face velocity (2.0-2.5m/s)
Airflow under high face velocity (2.5-3.0m/s)
Airflow under recommended face velocity (2.0-2.5m/s)
Airflow under high face velocity (2.5-3.0m/s)
1110
Segment Specifications
Segment SpecificationsSegment Name Notation Sketch
( Airflow direction)Length (Module)
(for reference only) Optional
Humidifier Segment HM
L=6M Electrode humidifier(EL) L=6M Steam humidifier(SH) L=6M High pressure atomizing humidifier(SP) L=6M Electric heat humidifier(EH)
Manual/ Motorized switch On-Off/Proportional control mode Humidifier Brand
Supply Fan – DIDW Fan Segment
SF-D L=8M~37MFan brand, Motor brand, Fan discharge, Motor location, Access door, Moisture-proof light, Viewport
Return Fan – DIDW Fan Segment
RF-D L=8M~37MFan brand, Motor brand, Fan discharge, Motor location, Access door, Moisture-proof light, Viewport
Supply Fan-Plug Fan Segment
SF-P L=11M~39MFan brand, Motor brand, Fan discharge, Motor location, Access door, Moisture-proof light, Viewport
Return Fan-Plug Fan Segment
RF-P L=11M~39MFan brand, Motor brand, Fan discharge, Motor location, Access door, Moisture-proof light, Viewport
Empty Segment ES L=2M~21MTop and side damper, Access door, Moisture-proof light, Viewport
Sound Attenuator Segment
AT L=9M, 11M, 13M, 15M, 17M
Diffuser Segment DF L=5M~10M Access door, Moisture-proof light, Viewport
Air Outlet Segment AO L=5M~36M
Damper arrangement, Flange, Manual damper, Motorized damper without actuator, Motorized damper with On-Off or analog signal actuator, Access door, Moisture-proof light, Viewport
TiO2 Sterilizer Segment TA L=3M
UV Segment UV L=2M
Vertical Economizer Segment
VE L=5M~34M
Damper arrangement, Exhaust air ratio, Flange, Manual damper, Motorized damper without actuator, Motorized damper with On-Off or analog signal actuator, Access door, Moisture-proof light, Viewport
Segment Specifications
L
L
L
L
L
L
L
L
L
L
L
Segment Name Notation Sketch ( Airflow direction)
Length (Module) (for reference only) Optional
Air Inlet Segment AI L=5M~36M
Damper arrangement, Flange, Manual damper, Motorized damper without actuator, Motorized damper with On-Off or analog signal actuator, Access door, Moisture-proof light, Viewport
Mixing Box Segment MB L=5M~36M
Damper arrangement, Fresh air ratio, Flange, Manual damper, Motorized damper without actuator, Motorized damper with On-Off or analog signal actuator, Access door, Moisture-proof light, Viewport
Economizer Segment EE L=12M~36M
Damper arrangement, Exhaust air ratio, Flange, Manual damper, Motorized damper without actuator, Motorized damper with On-Off or analog signal actuator, Access door, Moisture-proof light, Viewport
Open Return Filter Segment
OF No occupy a separate segmentG3/G4 Plate filter, TiO2 Sterilizer, Without filter media (only offer plate filter frame), Spare filter
Plate Filter Segment PFL=2M 46mm Plate L=3M 96mm Plate
G3/G4 Plate filter, Without filter media (Plate filter frame only), Spare filter, Pressure difference gauge, Pressure difference transmitter
Bag Filter Segment BF
L=6M 380mm Bag, Plate+380mm Bag,L=8M 600mm Bag, Plate+600mm Bag.
G3/G4 Plate filter, G3/G4/F5/F6/F7/F8 Bag filter, 380/600mm Bag filter, Single-bag filter, Plate and bag Combination filter (with Single-bag or Plate and bag combination filter frame), Spare filter, Pressure difference gauge, Pressure difference transmitter
High-efficiency Filter Segment
HF L=5MF9/H11/H13 High-efficiency filter, Without filter media (Filter frame only), Spare filter, Pressure difference gauge, Pressure difference transmitter
Heating Coil Segment HCL=3M 1R、2R L=4M 3R、4R
1~4R Heating coil, Steel/Copper header, Piping direction, 1~2&4R Steam coil
Cooling Coil Segment CC L=5M~11M
1-6&8&10R Cooling coil+1-4R Heating coil, 1-6&8&10R Cooling coil+1-2&4R Steam Coil, Dual cooling coil, Steel/Copper header, Piping direction, Eliminator, 50/100/150/200mm Evaporative humidifier(EV), Humidifier brand
Turn Segment TN L=5M~15M Access door, Moisture-proof light, Viewport
Electric Heater Segment EH L=3M Heater Power
L
L
L
L
L
L
HC
L
EL CC
L
L
L
L
1312
Segments Specifications & Application
Air Inlet / Mixing Box / Air Outlet / Economizer Segment
Air Inlet Segment - It's connected to the duct to supply air into AHU of air conditioning system. Air Outlet Segment - It's connected to the air supply duct to supply air to the air conditioning system.
Mixing Box Segment - It can adjust the ratio of return air and fresh air to satisfy the need of air conditioning environment.
Economizer Segment - It can adjust the ratio of return air to fresh air and exhaust air to satisfy the need of air conditioning environment.
Note:1. If a damper located at the side of AHU, the width (Mdl_Y) will determine the length of AHU segment (Damper required to
be installed in the casing which length module not less than width module of damper). To minimize the length size and cost of AHU, it is recommended to maximize the length of damper, rather than the width.
2. Because of high volume of return air, it is recommended to position the return air damper at the front of unit. If no damper is needed, you can only choose flange opening.
3. Please contact our local office for detailed damper dimension.
Unit Width Module W 7M 9M ≥11M
Mdl_X/Y 7 9,5 W,W-4-2n
Damper and Others
Damper
Damper material options: Galvanized steel, Aluminum alloy and stainless steel. Providing flange, manual damper, motorized damper without actuator or with actuator. Damper Location- Air inlet, Air outlet, Mixing box segment: Front/Top/Side/Bottom- Economizer segment: Top/Side
Optional damper dimension module (Mdl_X, Mdl_Y) is matched with AHU module. Example: 7Mx9M damper can be positioned at the front of YAM0709 or above models., Mdl_X/Y is same as height module H or less than height module H-4 at height. Mdl_X/Y logic at width is as follow (n is number such as 0,1,2)
Actuator
Use On-off or analog signal actuator - On-Off type actuator: Open or cut off air flow through AHU. - 0-10V type actuator: Adjust the ratio of fresh or exhaust air.
Filter Segment
Plate filter: Polyester synthetic fiber filter media (thickness of 46mm or 96mm available; filtering efficiency: G3/G4)
Bag filter: Polyester synthetic fiber and glass fiber is optional (bag length of 380mm or 600mm; filtering efficiency: G3/G4/F5-F8)
High efficiency filter: The V-shape pleated filter and box filter are available, using ultra fine glass fiber filter paper. (Filter efficiency of V-shape pleated filter is F9/H11/ H13 and of box filter is H11/ H13).
Installation Framework- The filter framework is made of galvanized steel or stainless steel.- The primary filter and secondary pre-filter and medium filter
segments are fixed with clamps and bolts and the high-efficiency filter segment is pulled tightly with bolts to minimize the leakage rate even under high air pressure drop, resulting in a bypass leakage rate meeting EN1886 class F9.
Service Instructions- Remove the open return filter from side.- Replace the plate and bag filters from the dirty side (upstream side)
and clean side (downstream side).- Replace the high-efficiency filter from the dirty side (upstream
side).
Options - Pressure difference gauge: Provide the visual reading of differential
pressure through the filter, avoiding the filter efficiency reduction due to dust over-accumulation
- Pressure difference transmitter: Translate the differential pressure through the filter into signals to the control system to monitor pressure variation.
TiO2 Sterilizer The nano-level air sterilization and cleaning technology is decomposed
all organic substance, bacteria and virus to CO2 and water, and eliminate odor, hazardous microorganism and other hazardous substances.
Options
Auxiliary Drain Pan, bottom damper, safety grid
1514
Unit Size 0507 0511 0707 0709 0713 0715 0909 0911 0915 0917 1109 1111 1115 1117 1120 1307 1311 1313 1315 1318 1320 1324 1511 1515 1518 1520 1524
H×W (Height x Width)
12"x12" - 1 - - - - 1 1 1 1 1 1 1 1 - - - - - - - - 1 1 - - 1
12"x20" - - - - - - 1 - 2 - 1 - 2 - - - - - - - - - - 2 2 - -
12"x24" 1 1 - - - - - 1 - 2 - 1 - 2 3 - - - - - - - 1 - 1 3 3
20"x12" - - - - - - 1 1 1 1 - - - - - - 1 - 1 - - 1 2 2 - - 2
20"x20" - - - - - - 1 - 2 - - - - - - - - 1 2 2 - - - 4 4 - -
20"x24" - - - - - - - 1 - 2 - - - - - 1 1 1 - 1 3 3 2 - 2 6 6
24"x12" - - - 1 - 1 - - - - 1 1 1 1 - - 1 - 1 - - 1 - - - - -
24"x20" - - - 1 1 2 - - - - 1 - 2 - - - - 1 2 2 - - - - - - -
24"x24" - - 1 - 1 - - - - - - 1 - 2 3 1 1 1 - 1 3 3 - - - - -
Unit Size 1527 1711 1717 1719 1722 1726 1728 1730 2013 2020 2022 2028 2215 2222 2224 2228 2415 2419 2424 2429 2433 2436 2618 2620 2624 2628 2633
H×W (Height x Width)
12"x12" - 1 1 - 1 - 1 1 - - - - 1 1 1 1 1 - 1 1 - 1 - - - - -
12"x20" - - - 1 2 1 2 - - - - - 2 2 - 2 2 1 - 1 - 1 - - - - -
12"x24" 4 1 2 2 1 3 2 4 - - - - - 1 3 2 - 2 3 3 5 4 - - - - -
20"x12" - - - - - - - - - - - - 2 2 2 2 - - - - - - - - 1 1 -
20"x20" - - - - - - - - - - - - 4 4 - 4 - - - - - - 2 - - 2 -
20"x24" 8 - - - - - - - - - - - - 2 6 4 - - - - - - 1 3 3 2 5
24"x12" - 2 2 - 2 - 2 2 - - 3 3 1 1 1 1 3 - 3 3 - 3 - - 3 3 -
24"x20" - - - 2 4 2 4 - 3 - 6 6 2 2 - 2 6 3 - 3 - 3 6 - - 6 -
24"x24" - 2 4 4 2 6 4 8 3 9 3 6 - 1 3 2 - 6 9 9 15 12 3 9 9 6 15
Unit Size 2654 2658 2820 2824 2828 2834 2854 2858 3019 3027 3036 3046 3058 3066 3224 3232 3236 3246 3254 3258 3266 3272 3446 3454 3458 3466 3472
H×W (Height x Width)
12"x12" - - - 1 1 - 1 - - - 1 - - - - - - - - - - - - - - - -
12"x20" - - - - 2 - 2 1 1 - 1 - 1 - - - - - - - - - - - - - -
12"x24" - - 3 3 2 5 6 8 2 4 4 7 8 10 - - - - - - - - - - - - -
20"x12" 1 - - 2 2 - 2 - - - - - - - 1 - 1 - 1 - - - - - - - -
20"x20" 2 1 - - 4 - 4 2 - - - - - - - 1 1 - 2 1 - - - - - - -
20"x24" 6 8 6 6 4 10 12 16 - - - - - - 3 4 4 7 6 8 10 11 - - - - -
24"x12" 3 - - 2 2 - 2 - - - 4 - - - 4 - 4 - 4 - - - - 5 - - -
24"x20" 6 3 - - 4 - 4 2 4 - 4 - 4 - - 4 4 - 8 4 - - - 10 5 - -
24"x24" 18 24 6 6 4 10 12 16 8 16 16 28 32 40 12 16 16 28 24 32 40 44 35 30 40 50 55
Note: Sizes of the plate filters and high-efficiency filters in the table are stated non-directionally, meaning that 12"x20" is identical to 20"x12", and so is 12"x24" to 24"x12", 20"x24" to 24"x20". The delivery sizes are stated in 12"x20"/12"x24"/20"x24". Sizes of bag filters are stated directionally, of which the front one stands for the height.
Segments Specifications & Application
Quantity of Filters Cooling Coil Segment/Heating Coil Segment
Steam Coil Segment
Optional coils: Steel tube & aluminum fins coil, steel tube & stainless steel fins coil, stainless steel tube & aluminum fins coil, and stainless steel tube & stainless steel fins coil.
Max design working pressure of steam coil: 0.4MPa
Electric Heater Segment
Sound Attenuator Segment
Unit SizeLength of sound
attenuator segmentInsertion loss of center frequency dB
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz
YAM 1520 9M 0.5 4.4 7.8 19.4 18.9 13.8 8.8 0.3
For detailed insertion losses of sound attenuator segments, see the selection report.
Comparison of Efficiency and Specifications in China, USA and EU
ChinaGB/T14295
Premium efficiency≥5μm80%>Efficiency≥20%
Medium efficiency≥1μm70%>Efficiency≥20%
High-medium efficiency≥1μm99%>Efficiency≥70%
Sub-HEPA efficiency≥0.5μm99.9%>Efficiency≥25%
HEPA efficiency≥0.5μmEfficiency≥99.9%
U.S.ASHRAE
C1 C2-C4 L5 L6 L7 L8 M9 M10 M11 M12 M13 M17 H12~H16 VH17 VH18 VH19 VH20
EuropeNew specification
G165%
G280%
G380%~90%
G4>90%
F540%
F660%
F790%
F890%
F985%
H1095%
H1199%
H1299.90%
H1399.95%
H1499.995%
V15V1799.9995%
EuropeOld specification
EU1 EU2 EU3 EU4 EU5 EU6 EU7 EU8 EU9 EU10 EU11 EU12 EU13 EU14
Cooling and heating coil are made of mechanically expanded copper tubes with aluminium fins, providing reliable performance and satisfying AHRI 410, and being certified by AHRI 410.
All coils are pre-tested for leakage according to the national standard before delivery. The coil has a framework made of galvanized steel or stainless steel for protection. The drain pan is made of galvanized steel or stainless steel. Drain pan is dual V-shaped structure with longitudinal slope, and allows quick and easy drainage of condensed water.
An eliminator can be installed if required by customer to prevent condensed water from being blown out of coil. (As specified by the manufacturer, eliminator can be installed for coil face velocity in the range 2.5~3m/s).
Aluminum fin and hydrophilic aluminum fin is available.
The electric heater employs stainless steel tube with helical fins and temperature protection switch, etc.
PTC electric heaters are optional for small AHUs for the low surface temperature.(PTC heater performance will be varied by air velocity)
The electric heater element is fixed on the frame. Electric control box is supplied and installed by the user. And its control must be interlocked with the fan.
Features- 1-4 steps control, to satisfy various needs of heating power;- Overheating protection: Built-in temperature protection switch shall automatically
shut off when the temperature is too high.
Sound attenuator uses galvanized steel as frame, non-hygroscopic and anticorrosive superfine fiber glass as inner lining acoustic absorbent, with perforated plate as protective cover of lining material.
The allowable max wind speed is 20m/s. The sound attenuator unit is on the guide rail in the box.
The standard sound attenuator segment is delivered at the length of 9M/11M/13M/15M/17M.
Example:
1716
Segments Specifications & Application
Evaporative Humidifier
The humidifier humidifies air through natural water evaporation. The evaporative humidifier eliminates "white powder" during cooling. Humidification efficiency: up to 80% Safe, Reliable and Durable The stuffing process is employed to achieve direct evaporative cooling for the maller size and lower temperature.
Steam Humidifier
The humidifier dries steam by means of steam-water separation and dual-dewatering, and then spurts the steam through orifice with metal muffling & filtering net.
It uses the unique heat-insulating sleeve to supply the steam, making the system free from the heat interference by out-of-service nozzle jet.
The single-boom, dual-boom or tri-boom dry steam humidifier can be selected according to the steam quantity and height module for clean isenthalpic humidification.
Regulating Signal:ON-OFF、0-10V/4-20mA Regulation Mode: switch type, proportion type Diverse regulating valves: manual valve, solenoid valve, motorized valve
Electrode Humidifier
Humidifier converts electric energy to heat with electrode and heats water to steam, which is delivered to AHU through pipe.
Humidifier is integrated to electric control box and controlled by microcomputer, easy for installation and use.
Stainless steel or aluminum alloy steam distribution pipe Regulating Signal:ON-OFF、0-10V/4-20mA Regulation Mode: switch type, proportion type
Electric heat humidifier
Humidifier converts electric energy to heat with electric heating tube and heats water to steam, which is delivered to AHU through pipe.
Humidifier is integrated to electric control box and controlled by microcomputer, easy for installation and use.
Stainless steel or aluminum alloy steam distribution pipe Regulating Signal:ON-OFF、0-10V/4-20mA
Regulation Mode: switch type, proportion type
High-pressure atomizing humidifier
After pressurized with high-pressure pump, spray water is delivered to AHU and spurted through nozzle therein.
The humidifier consists of nozzle, internal pipeline, circulating water pump and control box, with circuits for alarm and protection built in.
Small-pore wet film (100mm thick) acts as eliminator. It is free of water floating, and has higher humidification efficiency
On outlet of fan there's flexible connection of canvas up to requirements for fire prevention, which prevents transfer of vibration.
Belt is product from well known brand, with high driving power and good wear resistance.
European-style taper sleeve belt pulley is used, reliable in running and easy for disassembly.
Each bearing is product from known brand, with high assembly accuracy. This guarantees long-time continuous running of unit.
For plug fan application, depending on flexible air-out modes, it is unnecessary to consider driving direction of fan. This avoids use of unnecessary air duct and makes installation easier.
Plug fan with open structure, easier for cleaning and maintenance High efficiency, low noise Direct-driven plug fan is directly driven with motor. This avoids secondary pollution from debris of belt produced during belt driving. Such fan is widely used in clean-room industries e.g. electronics, pharmacy etc.
High-quality motor with high energy efficiency from famous brand is used, high in efficiency and reliable in running. It is IP55 protection class and Class F insulation.
Constant-speed motors and VSD motors are available. Power supply: 380V/3P/50Hz, 380-415V/3/50Hz, 460V/3P/60Hz, 380 V/3P/60Hz, /230V/3P/60Hz
Humidifier Segment
Double-inlet forward-curve/backward-curve centrifugal fan or plug fan from well known brand is adopted, safer and more reliable.
Both impeller and frame are made from high-strength alloy steel plate with robust design. Impeller has been statically and dynamically balanced.
The optional VSD converter can regulate the running speed of fan, reducing energy consumption of system.
High-quality damper spring is used for damping, which effectively lowers vibration and noise produced by fan.
Base of motor is equipped with sliding rail adjustment device to facilitate adjusting motor belt by user.
Fan Segment
1918
Segments Specifications & Application Notes for installation and maintenance
Air Washer Segment
It uses closed double-layer casing, diffuser and eliminator to prevent common water leakage and floating.
The precise and tested combination of pump, hydraulic pipeline and special nozzle gives spray or water film to perform specific heat and moisture exchanges, and meets clean spray and static electricity.
UV Lamp Segment
It uses high-grade and durable UV lamp to persistently kill bacteria and germs retained by or attached on specific functional segments e.g. filter segment and cooling coil segment. The interlocked limit switch of access door is used to avoid radial harm against unintended incomer.
Special Filter Segment
The special filter, e.g. electrostatic cleaning filter and roll filter, can be provided according to functional requirements. An external electrostatic precipitation filter is used to remove fibers and large-particle dust and then the built-in high-pressure dust collector, through positive and negative corona, to filter suspending fine dust particles with and kill bacteria and germs attached on dust particles.
The roll filter is ideal for large volume applications for its longer maintenance period and lower maintenance cost that rely on its automatic filter replacement.
Direct Gas Burner Segment
For brand-new fresh air unit fan with large air quantity and high-heat application in winter or throughout the year, the Segment can effectively save initial investment and running cost.
Rapid Absorption Steam Humidifier Segment
The spray tube and orifice have reasonable arrangement, applicable for vertical and horizontal flow.
It optimizes the humidification effect by evening the steam diffusion and shortening the absorption distance.
Professional design of steam collecting tube and water collecting tube delivers the perfect steam-water separation.
It is free from steam preheating and retains no residual water in steam pipe, delivering clean humidification.
It is ideal for industries of tobacco, coating, electronics, textile, etc.
Special Segments Schematics of installation and maintenance
L
Wall
Notes for Installation
1. The AHU must have a horizontal foundation and proper vibration-isolating measure during the installation. After installation, fix the AHU with foundation bolts.
2. Important: all delivery sections must stay at the same level and no inclination shall be acceptable during the field installation. Before tightening bolts, ensure all contact surface retain the same level.
3. The foundation height must be enough to install the water trap as required and no lower than 150mm.
4. The tube near equipment must be fixed to eliminate any torque-caused damages against equipment when tubing (inlet, outlet, steam).
5. It is recommended to use flexible connectors for inlet and outlet pipes and self-closing valves (provided by customers) for steam and hot water inlets to ensure that the internal temperature is not higher than 60°C.
6. When using the crane or forklift to load/unload or position equipment, please ensure the stress points shall be lifting holes or forklift holes and no shoveling or lifting on the base or any other casing part shall be allowable.7. The electric heater must interlock with the fan when an electric heater segment exists.8. The installation of AHU water trap must follow the right figure. 9. All electrical components and shell of the AHU must be grounded.
Notes for Maintenance
1. The AHU shall be under the maintenance by specially-appointed staff.2. All electrical components and safety devices shall be regularly inspected.3. Periodically inspect and adjust the belt tension to optimize the AHU state. 4. Periodically inspect the filter DP and cleanliness and clean or replace those with over DP.5. Periodically lubricate components that need lubricating.6. Vent air in the coil before starting the unit.7. During shutdown in winter, cut off all water and steam supplies and drain off the coil or take other anti-freezing measures to
prevent coil cracking.8. Periodically clean the AHU internal and coil. The coil is cleaned by compressed air or high-pressure steam.
Schematic of Service SpaceFoundation Schematic
L standing for the distance from the service side to wall must be longer than width of casing.
W=U
nit w
idth
+200
A
A
H
150 150
A-A Enlargement
Floor drain
drainage ditchfoundation floor
The shadow stands for foundation, the surface of which must be flat.
Floor drain and drain pipe shall be located at the same side.
L=Unit length+200
The founda-tion bolt hole.
Coil at the negative pressure sideP=Absolute value of positive pressure(Pa) in the SegmentH≥P/10+50(mm)
Coil at the positive pressure sideP=Absolute value of negative pressure(Pa) in the SegmentH≥P/10+100(mm)
AB
Coil at the negative pressure sideP=Absolute value of positive pressure(Pa) in the SegmentA=P/10(mm)B≥50(mm)
Coil at the positive pressure sideP=Absolute value of negative pressure(Pa) in the SegmentA≥50(mm)B≥P/10+60(mm)
2120
Network Diagram of Control System
Flexible Control System
With incomparable professional knowledge and capability in fields of intelligence, air conditioning, energy management and green building, Johnson Controls provides tailor-made solutions for comprehensive commercial buildings.
Monitoring Server Building Control Client
WebInterface
BACnet IPWeb Service
BA
Cne
tM
S/T
P
BA
Cne
tM
S/T
P
Network Control Engine
FCU ControllerTUC03 Series
VAV ControllerVMA1600 Series
AHU ControllerFEC Series
Typical applications: Cooling / Heating with Humidifier, 2 pipes
Description1. Monitor and Alarm: DDC monitoring the status of fan, manual/auto mode, fault alarm2. System start/stop interlock: interlocks between the fresh air damper, return air damper, cooling/hot water valve, humidifying valve and supply fan.3. Temperature Control: DDC provides modulating (PI) control for the motorized cooling/heating valve based on the sensed return temperature and set
point, so as to maintain the desired return air temperature.4. Humidity Control: Compare the sensor (HE-1) value and setpoint of air supply humidity to control the humidifier start/stop and filter dust accumulation
alarm.5. The differential pressure switch (DPS) monitors the status of filter, when the set point is exceeded, a signal will be driven to DDC.
BI AI AI AICO
BIAO BI BI BI BI
COBI
CO
Typical applications: Cooling & Heating with Humidity Control, 4 pipes
For details of more control system solutions, please contact our local office.
CO
CO CO COAO AOAOBOAI AI AI AIBI BI BI BI BI BI
Network Control Engine
Description1. Monitor and Alarm: DDC monitoring the status of fan, manual/auto mode, fault alarm2. System start/stop interlock: Interlocks between the fresh air damper, return air damper, cooling/hot water valve, humidifier, VSD converter and supply fan.3. Temperature Control: DDC provides modulating (PI) control for the motorized cooling/heating valve based on the sensed return temperature and set point, so as to maintain the desired return air temperature.4. Humidity Control: Compare the sensor (HE-1) value and setpoint of air supply humidity to control the humidifier start/stop and filter dust accumulation
alarm.5. Supply Air Static Pressure Control: A differential pressure transmitter (DPT-1) measures the supply air duct static pressure. DDC modulate the fan speed via VSD converter (VSD) to maintain the supply static pressure set point.6. The differential pressure switch (DPS) monitors the status of filter, when the set point is exceeded, a signal will be driven to DDC.
PUBL-7224 (1114)