Operating Instructionsfor the Fire Alarm System
Release 05.00.00
Copyright 25.10.2006
All rights reserved. Without express approval of the publisher this manual may not completely or in part be reproduced or forwarded electronically or mechanically, copied, recorded or stored in any form.
Securiton AG Alpenstrasse 20 CH–3052 Zollikofen Switzerland
Contents Table
Chapter 1 Prerequisites for Operation..........................................................................5Hierarchical Design of the SecuriPro® Fire Alarm System.................................................5
Chapter 2 Operation and Display Devices...................................................................7The operating devices MIC 732 and MIC 734...................................................................7The operating device MIC 742........................................................................................14The fire brigade operating part of the MIC742................................................................20The fire brigade operating device FBM 732....................................................................21
Chapter 3 Operation and Information.........................................................................23Switching the system to present / absent........................................................................23Operation on detection areas..........................................................................................25Operation on detection zones.........................................................................................27Operation on detectors...................................................................................................30Local alarm.....................................................................................................................33Alarm transmission.........................................................................................................35Outputs...........................................................................................................................37Inputs..............................................................................................................................39Time................................................................................................................................41Changing, reprogramming the operator code.................................................................42Context operation............................................................................................................45Remote Access...............................................................................................................46
Chapter 4 Extended Information.................................................................................47Polling the system status................................................................................................47Polling the event memory................................................................................................48Polling the maintenance memory....................................................................................49Polling the alarm counter................................................................................................49
Chapter 5 Procedure for Alarms and Faults...............................................................51Procedure for alarm signal..............................................................................................51Procedure for fault indication..........................................................................................53
Chapter 6 Procedure for Different System States.....................................................55Resetting the alarms.......................................................................................................55Resetting the setting deviations......................................................................................56
Chapter 7 Assistance for Troubleshooting................................................................57Procedure in case of faults..............................................................................................57
Chapter 1 Prerequisites for Operation
Subjects in this chapter
Hierarchical Design of the SecuriPro® Fire Alarm System
Hierarchical Design of the SecuriPro® Fire Alarm System
Presentation of the design
A SecuriPro fire alarm system is subdivided in descending order into the lo-gical units System
Detection area
Detection zone
Detector.
Note:A fire alarm system may contain up to 96 detection areas.If several main control units (MCU 211) are networked in a system, each one starts with a new fire detection area.
Configuration of the fire alarm system
The display of commands and information in these operating instructions is based on a standard configuration. Therefore it does not necessarily conform to the displays and functions available at your device. The larger and the more complex the fire alarm system, the more pages can be called with the softkey [MORE] and assigned to corresponding functions.
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
5
Chapter 2 Operation and Display Devices
Subjects in this chapter The operating devices MIC 732 and MIC 734The operating device MIC
742
The fire brigade operating part of the MIC742
The operating devices MIC 732 and MIC 734
Purpose With the MIC 732 and MIC 734, you can operate the fire alarm system and call information concerning its status.
Figure The figure shows the operation device MIC 734.
Note:The inscription strip is customer-specific and therefore not binding in these Operating Instructions.
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
7
The operating devices MIC 732 and MIC 734, continued
Function descrip-tion
Components and their functions
Legend Function descriptionA Key-operated switch
For enabling display and operationB Function keys <F1> to <F5>
For entering the functions and softkeys displayedC Function key "back" and "clear" respectively
Undoes a non-acknowledged entry
Moves back stepwise in the menu structure (>2sec to root)D Display
MIC 731: Display with 4 lines at 40 characters each
MIC 734: Display with 8 lines at 40 characters eachE LED
Light-emitting diodeF Individual inscription strip
Inscription of the LEDG Numerical keyboard
[ * ] = Terminate numerical input
[ # ] = Discard operator code
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
8
A B C E F GD
The operating devices MIC 732 and MIC 734, continued
Softkeys Keys and their functions:
Function Description Display[MORE] Displays additional menu
itemsSecuriton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTION ZONEF4: DETECTOR
[MORE]
[ZOOM] Displays detailed informa-tion in lists
Securiton AG 13.02.02 14:54
F1: DZ-0023 <OFF> Cafeteria
[ALL] [ UP ] [DOWN] [ZOOM]
[DOWN] Displays the next element in lists
[UP] Displays the previous ele-ment in lists
[ALL] Executes the function dis-played for all elements in listsNote:Appears only at the end of a list
[ENTER] Executes the function dis-played
Securiton AG 13.02.02 14:54
01/23 DZ-0023 <OFF>Building F Cafeteria
[ENTER] [ UP ] [DOWN]
[TO] For processing several ob-jects from - to within the same higher-order unit (e.g. detector zone)
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: SWITCH OFF SMOKE PARTF4: SWITCH ON SMOKE PARTDETECTION ZONE NO. 0001 [TO ] [MORE]
Note:The Softkey [TO] is superimposed on the function key <F4>.
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
9
The operating devices MIC 732 and MIC 734, continued
Meaning of the display
1st line: First event or system name with date and time2nd line: For several event of the same priority, the last one
3rd to 6th lines: Assignment of the function keys <F1> to <F4>7th line: Temporary check-back signals, waiting instructions (busy)
etc.8th line: Inscription of the softkeys
Below you find an example with the operator code set in the main menu, with 4 specified deviations
1st line2nd line3rd line4th line5th line6th line7th line7th line
001.SETTING DEVIATION: DZ0002 office 102004.SETTING DEVIATION: DZ0005 office 105F1: SETTING DEVIATIONSF2: OPERATION AND INFOF3: EXTENDED INFORMATION
[XXXX] [XXXX] [XXXX] [XXXX] [MORE]
Display of events The priorities for displaying events are set in descending order as follows: Alarm
Pre-alarm
Fault
Set deviation
Disconnections
Info
The display is composed as follows:
001 Fire DZ0001 1st Floor Corridor
001 Fire DZ0001 1st Floor Corridor
Event number
Each additional event is incremen-ted by 1
Designation of the event
(e.g. criterion)
System-related des-ignation of the event
(e.g. detector zone 0001)
Object-related des-ignation of the event
(e.g. detector zone "1st Floor Corridor"
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
10
The operating devices MIC 732 and MIC 734, continued
Display of com-mands and in-formation
The display is divided into the following 3 operational levels: Display without key
Display with key
Display with operator code (key required)
Possible display without key Securiton AG 13.02.02 14:54
Possible display with the key turned to the right (with entering a code)
Securiton AG 13.02.02 14:54
F1: LAMP TEST
CODE:
Possible display with the key turned to the right and after entering a code
Securiton AG 13.02.02 14:55
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
[MORE]
Input of com-mands
Commands can be entered via the function keys <F1> to <F4>.
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
11
The operating devices MIC 732 and MIC 734, continued
Operator code The operator code regulates the authorisation for operating the MIC 732 and MIC 734 and is used to identify persons. It consists of a two-digit operator code ID number plus a freely selectable combination of three to six digits. The two-digit ID number is defined in the operator code profile and cannot be changed.
Securiton AG 13.02.02 14:54
F1: LAMP TEST
CODE:
Note:The operator code ID numbers are defined during project planning.
Entering the op-erator code
To enter your operator code, proceed stepwise as follows:
Step Procedure Process/reading on display
1. Turn the key to the right Securiton AG 13.02.02 14:54
F1: LAMP TEST
CODE:
2. Enter the ID number and your personal operator code (3 to max. 6 digits) via the numer-ical keyboard
Securiton AG 13.02.02 14:54
F1: LAMP TEST
CODE: ********
Attention:If you have made a typing error, you can discard the entry with the key [ # ] before acknowledgement.
3. Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:55
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
Discard operator code
A set operator code can be discarded with the key [ # ] of the numerical key-board
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
12
The operating devices MIC 732 and MIC 734, continued
Procedure To carry out the lamp test, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right Securiton AG 13.02.02 14:54
F1: LAMP TEST
CODE:
2. Press the function key for Lamp test
For 5s all points of the display are actu-ated, all LED's flash, and the buzzer sounds intermittently
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
13
The operating device MIC 742
Purpose With the MIC 742, you can operate the fire alarm system and call information concerning its status.Included is the Swedish fire brigade operating panel according to SS3654 and SS3654 T1
Figure The figure shows the operation device MIC 742.
Note:The inscription strip in the right part of the operation panel is customer-specific and therefore not binding in these Operating Instructions.
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
14
The operating device MIC 742
, continued
Function descrip-tion
Components and their functions
Legend Function descriptionA Operating part for the fire brigade
Elements within the rectangular white frame are according to the to Swedish standard SS3654 and SS3654 T1 for fire brigade panel.Refer to chapter “The fire brigade operating part of the MIC742” on page 21 in this document.
B Key-operated switch
For enabling display and operationC Function keys <F1> to <F5>
For entering the functions and softkeys displayedD Function key "back" and "clear" respectively
Undoes a non-acknowledged entry
Moves back stepwise in the menu structure (>2sec to root)E Display
Display with 4 lines at 40 characters eachF LED
Light-emitting diodeG Individual inscription strip
Inscription of the LEDH Numerical keyboard
[ * ] = Terminate numerical input
[ # ] = Discard operator code
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
15
B D E FC G HA
Softkeys Keys and their functions:
Function Description Display[MORE] Displays additional menu
itemsSecuriton AG 13.02.02 14:54F1: SYSTEMF2: DETECTION AREAF3: DETECTION ZONE [MORE]
[ZOOM] Displays detailed informa-tion in lists
Securiton AG 13.02.02 14:54F1: DZ-0023 <OFF> Cafeteria
[ALL] [ UP ] [DOWN] [ZOOM][DOWN] Displays the next element in lists
[UP] Displays the previous ele-ment in lists
[ALL] Executes the function dis-played for all elements in listsNote:Appears only at the end of a list
[ENTER] Executes the function dis-played
Securiton AG 13.02.02 14:5401/23 DZ-0023 <OFF>Building F Cafeteria[ENTER] [ UP ] [DOWN]
[TO] For processing several ob-jects from - to within the same higher-order unit (e.g. detector zone)
Securiton AG 13.02.02 14:54F1: SWITCH OFFF2: SWITCH ONDETECTION ZONE NO. 0001 [TO ] [MORE]
Note:The Softkey [TO] is superimposed on the function key <F4>.
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
16
The operating device MIC 742
, continued
Meaning of the display
1st line: First event or system name with date and time2nd line: For several event of the same priority, the last one3rd line: Temporary check-back signals, waiting instructions (busy)
etc.4th line: Assignment of the function keys <F1> to <F4>
Below you find an example with the operator code set in the main menu, with 4 specified deviations
1st line2nd line3rd line4th line
001.SETTING DEVIATION: DZ0002 office 102004.SETTING DEVIATION: DZ0005 office 105F1: SETTING DEVIATIONS[XXXX] [XXXX] [XXXX] [XXXX] [MORE]
Display of events The priorities for displaying events are set in descending order as follows: Alarm
Pre-alarm
Fault
Set deviation
Disconnections
Info
The display is composed as follows:
001 Fire DZ0001 1st Floor Corridor
001 Fire DZ0001 1st Floor Corridor
Event number
Each additional event is incremen-ted by 1
Designation of the event
(e.g. criterion)
System-related des-ignation of the event
(e.g. detector zone 0001)
Object-related des-ignation of the event
(e.g. detector zone "1st Floor Corridor"
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
17
The operating device MIC 742
, continued
Display of com-mands and in-formation
The display is divided into the following 3 operational levels: Display without key
Display with key
Display with operator code (key required)
Possible display without key Securiton AG 13.02.02 14:54
Possible display with the key turned to the right (with entering a code)
Securiton AG 13.02.02 14:54F1: LAMP TEST
CODE:
Possible display with the key turned to the right and after entering a code
Securiton AG 13.02.02 14:55F1: OPERATION AND INFOF2: EXTENDED INFORMATION [MORE]
Input of com-mands
Commands can be entered via the function keys <F1> to <F4>.
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
18
The operating device MIC 742
, continued
Operator code The operator code regulates the authorisation for operating the MIC 742 and is used to identify persons. It consists of a two-digit operator code ID number plus a freely selectable combination of three to six digits. The two-digit ID number is defined in the operator code profile and cannot be changed.
Securiton AG 13.02.02 14:54F1: LAMP TEST
CODE:
Note:The operator code ID numbers are defined during project planning.
Entering the op-erator code
To enter your operator code, proceed stepwise as follows:
Step Procedure Process/reading on display
1. Turn the key to the right Securiton AG 13.02.02 14:54F1: LAMP TEST
CODE:
2. Enter the ID number and your personal operator code (3 to max. 6 digits) via the numer-ical keyboard
Securiton AG 13.02.02 14:54F1: LAMP TEST
CODE: ********
Attention:If you have made a typing error, you can discard the entry with the key [ # ] before acknowledgement.
3. Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:55F1: OPERATION AND INFOF2: EXTENDED INFORMATION
Discard operator code
A set operator code can be discarded with the key [ # ] of the numerical key-board
Procedure To carry out the lamp test, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right Securiton AG 13.02.02 14:54F1: LAMP TEST
CODE:
2. Press the function key for LAMP TEST
For 5s all points of the display are actu-ated, all LED's flash, and the buzzer sounds intermittently
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
19
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
20
The fire brigade operating part of the MIC742
Purpose The fire brigade operating device is an integrated part of the MIC742 and is used for the standardised alarm handling by the fire brigade in Sweden, ac-cording to the standards SS3654 and SS3654 T1
FigureFire brigade part of the MIC742
LED Displays A BrandIndicates that at least one fire detector is in alarm
B Släckanlägging aktiveradIndicates the activation of extinguishing systems
C Brandventilation aktiveradIndicates the activation of smoke ventilation systems
D Styrutgång aktiveradIndicates the activation of fire incident controls
E Larmsändare aktiveradIndicates the activation of alarm transmission units
F Ingen functionThis LED is disabled and has no function
G FLERA LARMThis indicator activates as soon that more than one fire detector is in alarm
Buttons: H FLERA LARMScrolls down the alarm list in the LCD starting from the most recent alarm
I LARMDOM TYSTResets the alarm acoustic devices of the fire alarm system *)
J ATERSTALLNINGResets the fire alarm system *)
Note:*) Functions can be carried out only with the fire brigade key in “on” position
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
21
A
BCDEF
G H I J
The fire brigade operating device FBM 732
Purpose The fire brigade operating device is used for the standardised alarm handling by the fire brigade. Depending on customer requirements, the FBM can how-ever also be operated by the operator and/or caretaker.
Displays on the FBM 732:K Alarm
L Fault
M Alarm transmission activated
Functions on the FBM 732:N Switch off alarm devices
O Reset fire alarm system.
Note:Functions can be carried out only with the standardised key-operated switch SAE 12600.
FigureFBM 732
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
22
A
B
C
D
E
The fire brigade operating device FBM 732, continued
Displays and their meaning
Display and function description:
Display Meaning
Fire alarm without transmission Automatic detector alarm before expiration of a delay or inspection time.
Fire alarm with transmission Fire alarm with
immediate transmission with a pushbut-ton alarm (hand-operated fire alarm)
or
after a delay or inspection period with automatic detector alarm.
Fault The fire alarm system recognizes a fault in-dication (collective display).
Switching off the siren
Display and procedure:
Display Procedure
Turn the key-operated switch and
simultaneously press the siren pushbutton.
In this way all buzzers and acoustical alarm devices are switched off.
Resetting the alarm
Display and procedure:
Display Procedure
Turn the key-operated switch and
simultaneously press the Reset pushbutton.
With this procedure the entire fire alarm system is switched back to the normal operating state.
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
23
und gleichzeitig
und gleichzeitig
Chapter 3 Operation and Information
Subjects in this chapter Switching the system to present / absentOperation on detection areas
Operation on detection zonesOperation on detectorsLocal alarm
Alarm transmission
Outputs
Inputs
TimeContext operation
Remote Access
Switching the system to present / absent
Procedure To switch the system to present / absent, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for System
Securiton AG 13.02.02 14:54
F1: PRESENT
4. Press the function key for the desired function
Securiton AG 13.02.02 14:54
F1: PRESENT
DA-00 SWITCHED OFF
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
25
Operation on detection areas
Standard func-tions
The following functions are present: Switch on and off respectively
Poll status
Reset
Procedure with list selection
To edit detection areas, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for De-tection area
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: RESETDETECTION AREA NO.: __ [MORE]
4. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: DA-00 <ON> Building AF2: DA-01 <ON> Building BF3: DA-02 <ON> Building C
[DOWN] [ZOOM]
5. Press the function key for the desired detection area, or first press the softkey [DOWN] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: DA-01 <ON> Building BF2: DA-02 <ON> Building CF3: DA-03 <ON> Building D
[DOWN] [ZOOM]
Note:
Only those detection areas are shown for which the desired function can be executed.
Continued on next page
, continued
Procedure with numerical entries
To edit detection areas, proceed stepwise as follows.
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
26
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for De-tection area
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: RESETDETECTION AREA NO.: __ [MORE]
4. Enter the detection area via the numerical keyboard
Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: RESETDETECTION AREA NO.: 00 [TO] [MORE]
5. Press the softkey [TO] if you want to edit detection areas from - to, and enter the "to" detection area as described above
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: RESETDETECTION AREA NO.: 00 ok [MORE]
Note:
The Softkey [TO] is superimposed on the function key <F4>.
6. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: RESETDETECTION AREA NO.: __ [MORE]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
27
Operation on detection zones
Standard func-tions
The following functions are present: Switch on and off respectively
Switch the smoke part on and off respectively
Switch the heat part on and off respectively
Poll status
Reset
Procedure with list selection
To edit detection zones, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for De-tection zone
Securiton AG 13.02.02 14:54
F1: DETECTION AREAF2: DETECTOR ZONE
4. Press the function key for De-tection area
Securiton AG 13.02.02 14:54
F1: DETECTOR ZONE
DETECTION AREA NO.: __00.00
5. Press the function key for De-tector zone
Securiton AG 13.02.02 14:54
F1: DA-00 Building AF2: DA-01 Building BF3: DA-02 Building C
[DOWN] [ZOOM]Continued on next page
Operation on detection zones, continued
Step Procedure Process/reading on display
6. Press the function key for the desired detection area, or first press the softkey [DOWN] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: SWITCH OFF SMOKE PARTF4: SWITCH ON SMOKE PARTDETECTOR ZONE NO.: 00__.00 [MORE]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
28
7. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: DZ-0001 <OFF> Entrance hallF2: DZ-0002 <OFF> Staircase northF3: DZ-0003 <OFF> Staircase south
[DOWN] [ZOOM]
8. Press the function key for the desired detector zone, or first press the softkey [DOWN] if the desired detector zone is not displayed
Securiton AG 13.02.02 14:54
F1: DZ-0002 <OFF> Staircase northF2: DZ-0003 <OFF> Staircase southF3: DZ-0004 <OFF> Archive
[DOWN] [ZOOM]
Continued on next page
Operation on detection zones, continued
Procedure with numerical entries
To edit detection zones, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for De-tector zone
Securiton AG 13.02.02 14:54
F1: DETECTION AREAF2: DETECTOR ZONE
4. Press the function key for De-tector zone
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: SWITCH OFF SMOKE PARTF4: SWITCH ON SMOKE PARTDETECTOR ZONE NO.: ____ [MORE]
5. Enter the detection zones via the numerical keyboard
Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: SWITCH OFF SMOKE PARTF4: SWITCH ON SMOKE PARTDETECTOR ZONE NO.: 0001 [TO] [MORE]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
29
6. Press the softkey [TO] if you want to edit detection zones within a detection area from - to, and enter the "to" detector zone as described above
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: SWITCH OFF SMOKE PARTF4: SWITCH ON SMOKE PARTDETECTOR ZONE NO.: 0001 ok [MORE]
Note:
The Softkey [TO] is superimposed on the function key <F4>.
7. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: SWITCH OFF SMOKE PARTF4: SWITCH ON SMOKE PARTDETECTOR ZONE NO.: ____ [MORE]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
30
Operation on detectors
Standard func-tions
The following functions are present: Switch off/on
Exchange
Switch off/on smoke part
Switch off/on heat part
Poll status
Reset
Disconnect/Connect
Procedure with list selection
To edit detectors, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for De-tector
Securiton AG 13.02.02 14:54
F1: DETECTION AREAF2: DETECTOR
4. Press the function key for De-tection area
Securiton AG 13.02.02 14:54
F1: DETECTOR ZONE
DETECTION AREA NO.: __00.00
5. Press the function key for De-tector zone
Securiton AG 13.02.02 14:54
F1: DA-00 Building AF2: DA-01 Building BF3: DA-02 Building C
[DOWN] [ZOOM]
6. Press the function key for the desired detection area, or first press the softkey [DOWN] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: DETECTOR
DETECTOR ZONE NO.: 00__.00 [MORE]
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
31
Operation on detectors, continued
Step Procedure Process/reading on display
7. Press the function key for De-tector
Securiton AG 13.02.02 14:54
F1: DZ-0001 Entrance hallF2: DZ-0002 Staircase northF3: DZ-0003 Staircase south
[DOWN] [ZOOM]
8. Press the function key for the desired detector zone, or first press the softkey [DOWN] if the desired detector zone is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: EXCHANGEF4: SWITCH OFF SMOKE PARTDETECTOR NO.: 0001.__
9. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: DET-0001.01 <DISCONNECT> frontF2: DET-0001.02 <DISCONNECT> middleF3: DET-0001.03 <DISCONNECT> rear
[DOWN] [ZOOM]
10. Press the function key for the desired detector, or first press the softkey [DOWN] if the de-sired detector is not displayed
Securiton AG 13.02.02 14:54
F1: DET-0001.02 <DISCONNECT> middleF2: DET-0001.02 <DISCONNECT> rear
[DOWN] [ZOOM]
Continued on next page
Operation on detectors, continued
Procedure with numerical entries
To edit detectors, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for De-tector
Securiton AG 13.02.02 14:54
F1: DETECTION AREAF2: DETECTOR
[MORE]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
32
4. Press the function key for De-tector
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: EXCHANGEF4: SWITCH OFF SMOKE PARTDETECTOR NO.: ____.__ [MORE]
5. Enter the detector number via the numerical keyboard
Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: EXCHANGEF4: SWITCH OFF SMOKE PARTDETECTOR NO.: 0001.01 [TO] [MORE]
6. Press the softkey [TO] if you want to edit detectors within a detector zone from - to, and enter the "to" detector as de-scribed above
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: EXCHANGEF4: SWITCH OFF SMOKE PARTDETECTOR NO.: 0001.01 ok [MORE]
Note:
The Softkey [TO] is superimposed on the function key <F4>.
7. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: EXCHANGEF4: SWITCH OFF SMOKE PARTDETECTOR NO.: ____.__ [MORE]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
33
Local alarm
Standard func-tions
The following functions are present: Switch on and off respectively
Poll status
Reset
Switch maintenance on and off
Procedure with list selection
To edit the local alarm, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for Local alarm, or first press the softkey [MORE] if the desired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONLOCAL ALARM NO.: __ [MORE]
4. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: AE-01 BUZZER [OFF] BUZZER ALARMF2: AE-02 BUZZER [OFF] BUZZER FAULTF3: AU-03 BUZZER [OFF] BUZZER PREALARMF4: AU-04 AU [OFF] SIREN [DOWN]
5. Press the function key for the desired local alarm, or first press the softkey [DOWN] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONLOCAL ALARM NO.: __ [MORE]
Continued on next page
Local alarm, continued
Procedure with numerical entries
To edit the local alarm, proceed stepwise as follows.
Step Procedure Process/reading on display
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
34
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for Local alarm, or first press the softkey [MORE] if the desired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONLOCAL ALARM NO.: __ [MORE]
4. Enter the local alarm number via the numerical keyboard
Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONLOCAL ALARM NO.: 01 [TO] [MORE]
5. Press the softkey [TO] if you want to edit local alarms from - to, and enter the "to" local alarm as described above
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONLOCAL ALARM NO.: 01 ok [MORE]
Note:
The Softkey [TO] is superimposed on the function key <F4>.
6. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONLOCAL ALARM NO.: __ [MORE]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
35
Alarm transmission
Standard func-tions
The following functions are present: Switch on and off respectively
Poll status
Reset
Switch maintenance on and off
Procedure with list selection
To edit the local alarm, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for Alarm transmission, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONALARM TRANSMISSION NO.: __ [MORE]
4. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: TU-01 TU <OFF> FIREF2: TU-02 TU <OFF> FIRE MCPF3: TU-03 TU <OFF> FAULTF4: TU-04 TU <OFF> SC SYSTEM [DOWN] [ZOOM]
5. Press the function key for the desired alarm transmission, or first press the softkey [DOWN] if the desired func-tion is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONALARM TRANSMISSION NO.: __ [MORE]
Continued on next page
Alarm transmission, continued
Procedure with numerical entries
To edit the local alarm, proceed stepwise as follows.
Step Procedure Process/reading on display
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
36
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for Alarm transmission, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONALARM TRANSMISSION NO.: __ [MORE]
4. Enter the local alarm trans-mission number via the nu-merical keyboard
Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONALARM TRANSMISSION NO.: 01 [TO] [MORE]
5. Press the softkey [TO] if you want to edit alarm transmis-sions from - to, and enter the "to" alarm transmission as de-scribed above
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLL STATUSF4: MAINT. SWITCH ONALARM TRANSMISSION NO.: 01 ok [MORE]
6. Note:
The Softkey [TO] is superimposed on the function key <F4>.
7. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLL STATUSF4: MAINT. SWITCH ONALARM TRANSMISSION NO.: __ [MORE]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
37
Outputs
Standard func-tions
The following functions are present: Switch on and off respectively
Poll status
Switch maintenance on and off
Procedure with list selection
To edit the local alarm, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for Outputs, or first press the softkey [MORE] if the desired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONOUTPUT NO.: ___ [MORE]
4. Press the function key for the desired function, or first press the softkey [ZOOM] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: OUT-001 [OFF] IOM LB1 ACTIVATEDF2: OUT-002 [OFF] IOM LB1 ACTIVATEDF3: OUT-003 [OFF] IOM LHT ACTIVATED [DOWN] [ZOOM]
5. Press the function key for the desired output, or first press the softkey [ZOOM] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONOUTPUT NO.: ___ [DOWN] [ZOOM]
Continued on next page
Outputs, continued
Procedure with numerical entries
To edit the local alarm, proceed stepwise as follows.
Step Procedure Process/reading on display
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
38
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for Outputs, or first press the softkey [MORE] if the desired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONOUTPUT NO.: ___ [MORE]
4. Enter the output number via the numerical keyboard
Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONOUTPUT NO.: 001 [TO] [MORE]
5. Press the softkey [TO] if you want to edit outputs from - to, and enter the "to" output as described above
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONOUTPUT NO.: 001 ok [MORE]
6. Note:
The Softkey [TO] is superimposed on the function key <F4>.
7. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUSF4: MAINT. SWITCH ONOUTPUT NO.: ___ [MORE]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
39
Inputs
Standard func-tions
The following functions are present: Switch on and off respectively
Poll status
Procedure with list selection
To edit the local alarm, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for In-puts, or first press the softkey [MORE] if the desired func-tion is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUS
INPUT NO.: ___ [MORE]
4. Press the function key for the desired function, or first press the softkey [ZOOM] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: IN-001 [OFF] Extinguisher releasedF2: IN-002 [OFF] Extinguisher fault [DOWN] [ZOOM]
5. Press the function key for the desired input, or first press the softkey [DOWN] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUS
INPUT NO.: ___ [MORE]
Continued on next page
Inputs, continued
Procedure with numerical entries
To edit the local alarm, proceed stepwise as follows.
Step Procedure Process/reading on display
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
40
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for In-puts, or first press the softkey [MORE] if the desired func-tion is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUS
INPUT NO.: ___ [MORE]
4. Enter the input number via the numerical keyboard
Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUS
INPUT NO.: 001 [TO] [MORE]
5. Press the softkey [TO] if you want to edit inputs from - to, and enter the "to" input as de-scribed above
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUS
INPUT NO.: 001 ok [TO] [MORE]
6. Note:
The Softkey [TO] is superimposed on the function key <F4>.
7. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: SWITCH OFFF2: SWITCH ONF3: POLLING STATUS
INPUT NO.: ___ [MORE]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
41
Time
Standard func-tions
The following functions are present: Input time
Input date
Procedure To edit the time, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for Time, or first press the softkey [MORE] if the desired function is not displayed
Securiton AG 13.02.02 14:54
F1: TIME INPUTF2: DATE INPUT
4. Press the function key for Time input
Securiton AG 13.02.02 14:54
F1: TIME INPUTF2: DATE INPUT
TIME INPUT: 14:54:49
5. Enter the correct time via the numerical keyboard
Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:54
F1: TIME INPUTF2: DATE INPUT
6. Press the function key for Date input
Securiton AG 13.02.02 14:54
F1: TIME INPUTF2: DATE INPUT
DATE INPUT: 13.02.02
7. Enter the correct date via the numerical keyboard
Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:54
F1: TIME INPUTF2: DATE INPUT
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
42
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
43
Changing, reprogramming the operator code
Changing the op-erator code
To change your operator code, proceed stepwise as follows:
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:55
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTION ZONEF4: DETECTOR
[MORE]
3. Press the function key for Code, or first press the softkey [MORE] if the desired function is not displayed
Securiton AG 13.02.02 14:55
F1: CHANGE
4. Press the function key for Change
Securiton AG 13.02.02 14:55
F1: CHANGE
PCODE NEW ______
5. Enter the new operator code without operator code ID (3 to max. 6 digits) via the numer-ical keyboard
Securiton AG 13.02.02 14:55
F1: CHANGE
PCODE NEW ******
Attention:If you have made a typing error, you can discard the entry with the key <CLEAR> before acknowledgment.
6. Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:55
F1: CHANGE
CONFIRM PCODE ------
7. Confirm the new operator code once more as described above
Securiton AG 13.02.02 14:55
F1: CHANGE
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
44
, continued
Reprogramming the operator code
To reprogram an operator code, proceed stepwise as follows:
Note:You need the appropriate authorisation to reprogram an operator code.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:55
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTION ZONEF4: DETECTOR
[MORE]
3. Press the function key for Code, or first press the softkey [MORE] if the desired function is not displayed
Securiton AG 13.02.02 14:55
F1: CHANGEF2: NEW PROGRAMMING
4. Press the function key for New programming
Securiton AG 13.02.02 14:55
F1: CHANGEF2: NEW PROGRAMMING
ID/PCCODE NEW ______
5. Enter the existing operator code ID and the new operator code (3 to max. 6 digits) via the numerical keyboard
Securiton AG 13.02.02 14:55
F1: CHANGEF2: NEW PROGRAMMING
ID/PCCODE NEW ******
6. Acknowledge the entry with the key [ * ] of the numerical keyboard
Securiton AG 13.02.02 14:55
F1: CHANGEF2: NEW PROGRAMMING
CONFIRM ID/PCCODE ------
7. Confirm the new operator code once more as described above
Securiton AG 13.02.02 14:55
F1: CHANGEF2: NEW PROGRAMMING
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
45
Context operation
Procedure Context operation, also called alternative operation, is a form of operation meant to facilitate switch on, switch off, disconnect and connect operations. This means: If one tries to again switch off an already switched off detector zone, the
system proposes to switch on this detector zone. If one tries to again switch on a detector zone with bad AR (e.g.
smashed pushbutton glass), the system proposes partial switching off of this detector zone.
Note:You need the appropriate authorisation to reprogram an operator code.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:55
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info
Securiton AG 13.02.02 14:55
F1: SYSTEMF2: DETECTION AREAF3: DETECTION ZONEF4: DETECTOR
[MORE]
3. Try to switch on a zone (or a detector) which is already switched on.
Press <F1> [COMMAND]
Securiton AG 13.02.02 14:55
01/01 DZ-0001 ALREADY ONBUILDING A STAIRCASE NORD
DETECTION ZONE-NO: 0001[COMMAND]
4. Press <F1> [ENTER] in order to carry out the context oper-ation
Securiton AG 13.02.02 14:55
01/01 DZ-0001 ALREADY ONBUILDING A STAIRCASE NORD
DETECTION ZONE-NO: 0001[ENTER]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
46
Remote Access
Standard func-tions
The following functions are present: Release remote access
Delete Installer Password
Procedure To operate remote acces functions, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Op-eration and info, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEMF2: DETECTION AREAF3: DETECTOR ZONEF4: DETECTOR
[MORE]
3. Press the function key for Re-mote Access, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: RELEASE REMOTE ACCESSF2: DELETE INSTALLER PASSWORD
4. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
F1: RELEASE REMOTE ACCESSF2: DELETE INSTALLER PASSWORD
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
47
Chapter 4 Extended Information
Subjects in this chapter Polling the system statusPolling the event memoryPolling the maintenance
memoryPolling the alarm counter
Polling the system status
Standard func-tions
The following functions are present: Polling the pre-alarm, alarm and fault lists
Polling the setting deviations
Polling the disconnections
Polling In maintenance
Polling bad switch-on check
Polling bad arming readiness
Procedure To query the system status, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Ex-tended information, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEM STATUSF2: EVENT MEMORYF3: ALARM COUNTER
3. Press the function key for System status
Securiton AG 13.02.02 14:54
F1: ALARM LISTF2: PREALARM LISTF3: FAULT LISTF4: INFO LIST [MORE]
4. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
01/02 DZ-0001 SETTING DEVIATION entranc02/02 DZ-0003 SETTING DEVIATION stairca
[ZOOM]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
49
Polling the event memory
Standard func-tions
The following functions are present: Polling
Print all
Print alarms
Print faults
Print on/off switchings
Print last 100 events
Procedure To query or print the event memory, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Ex-tended information, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEM STATUSF2: EVENT MEMORYF3: ALARM MEMORYF4: MAINTENANCE MEMORY
3. Press the function key for Event memory
Securiton AG 13.02.02 14:54
F1: POLLINGF3: PRINTS ALLF3: PRINTS ALARMSF4: PRINTS FAULTS
[MORE]
4. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
Securiton AG 13.02.02 14:54
01: DZ-0006 SWITCHED ON 02: DZ-0005 SWITCHED ON 03: DZ-0004 SWITCHED ON 04 DZ-0003 SWITCHED ON
[P-DOWN][ UP ] [DOWN] [ZOOM]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
50
Polling the maintenance memory
Procedure To query the maintenance memory, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Ex-tended information, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEM STATUSF2: EVENT MEMORYF3: ALARM MEMORYF4: MAINTENANCE MEMORY
3. Press the function key for Maintenance memory
Securiton AG 13.02.02 14:54
01:DZ-0001 IN MAINT. entrance hall
Polling the alarm counter
Procedure To query the alarm counter, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
2. Press the function key for Ex-tended information, or first press the softkey [MORE] if the desired function is not dis-played
Securiton AG 13.02.02 14:54
F1: SYSTEM STATUSF2: EVENT MEMORYF3: ALARM COUNTER
3. Press the function key for Alarm counter
Securiton AG 13.02.02 14:54
01:MEMORY ALARM COUNTER VALUE: 092
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
51
Chapter 5 Procedure for Alarms and Faults
Subjects in this chapter Procedure for alarm signalProcedure for fault indication
Procedure for alarm signal
Alarms for differ-ent system states
Transmission of alarms for different system states
System state „Present“ System state „Absent“The alarm message from automatic de-tectors is transmitted to the fire brigade with a three-minute delay.
During this lag phase, it is possible to ef-fect another delay of 5 minutes by press-ing the corresponding function key IN-SPECTION.
All alarm messages are immediately transmitted to the fire brigade.
Alarm messages from hand-operated fire alarms are always transmitted to the fire brigade directly and without delay.
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
53
Procedure for alarm signal, continued
Procedure for fire alarm/status "Present"
If an alarm is signaled in the "Present" state, i.e. without immediate transmis-sion to the fire brigade, proceed stepwise as described below. Display on the FBM 732:
Attention:Also mind the indications on the PIM 731 and the group alarm indication on the PIM 734.Possible reading on the MIC 732 or MIC 734 display
001 FIRE DZ0002 1ST FLOOR CORRIDOR
F1: SWITCH OFF BUZZERF2: ALARM LIST
Step Procedure Process/reading on display
1. Press the function key for Switch off buzzer
001 FIRE DZ0002 1ST FLOOR CORRIDOR
F1: INSPECTF2: ALARM LISTF3: ABSENTF4: LAMP TEST
[MORE]
Note: The delay period of 3 minutes counts from the triggering of the alarm until its transmission to the fire brigade
2. Press the function key for In-spect
Go to the source of the fire
Note: The inspection time lasts 5 minutes
3. If the alarm is genuine:
Press the nearest pushbutton
The alarm is transmitted immediately.
If the alarm is false:
Turn the key to the right
Enter your personal operator code
001 FIRE DZ0002 1ST FLOOR CORRIDOR
F1: INSPECTF2: RESET SYSTEMF3: ALARM LISTF4: OPERATION AND INFO
[MORE]
Press the function key for RE-SET SYSTEM
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
54
Procedure for fault indication
Procedure for fault indication
If a fault is indicated, proceed stepwise as follows.
Display on the FBM 732:
Attention:Also pay attention to the group fault indication on the PIM 731On the FBM, faults cannot be acknowledged!
Possible reading on the MIC 732 or MIC 734 display
001 FIRE DZ0002 1ST FLOOR CORRIDOR
F1: SWITCH OFF BUZZERF2: FAULT LIST
Step Procedure Process/reading on display
4. Press the function key for Switch off buzzer
001 FAULT DZ0099 SYSTEM FAULT
F1: SWITCH OFF REMOTE ALARMF2: RESET SYSTEMF3: FAULT LISTF4: OPERATION AND INFO
[MORE]
Note:
Further procedure see chapter 7
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
55
Extended Information
Chapter 6 Procedure for Different System States
Subjects in this chapter Resetting the alarmsResetting the setting deviations
Resetting the alarms
Standard func-tions
The following functions are possible: Switch off buzzer (without operator code)
Inspect (without operator code)
Switch off local alarm
Switch off alarm transmission
Reset system
Poll pre-alarm
Poll alarm
Poll fault list
Info list
Maintenance list
Procedure In case of an alarm, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
001. Brand: DZ0001 Entrance hall
F1: SWITCH OFF LOCAL ALARMF2: SWITCH OFF REMOTE ALARMF3: RESET SYSTEMF4: ALARM LIST
[MORE]
2. Press the function key for the desired function, or first press the softkey [MORE] if the de-sired function is not displayed
001. Fire: DZ0001 Entrance hall
F1: RESET SYSTEMF2: ALARM LISTF3: OPERATION AND INFOF4: EXTENDED INFORMATIONDA-00 ACKNOWLEDGED
The system is reset Securiton AG 13.02.02 14:54
F1: OPERATION AND INFOF2: EXTENDED INFORMATION
Copyright by Securiton AG Release 01.05.00
Bedienungsanleitung für das FAS R0X00meldesystem SecuriPro®
57
Resetting the setting deviations
Procedure To reset setting deviations, proceed stepwise as follows.
Step Procedure Process/reading on display
1. Turn the key to the right
Enter your personal operator code
001. SETTING DEVIATION: DZ0001 Entrance 004. SETTING DEVIATION: DZ0004 ArchiveF1: SETTING DEVIATIONSF2: OPERATION AND INFOF3: EXTENDED INFORMATION
2. Press the function key for Setting deviations, or first press the softkey [MORE] if the desired function is not dis-played
001. SETTING DEVIATION: DZ0001 Entrance 004. SETTING DEVIATION: DZ0004 ArchiveF1: DZ0001 <ON> Entrance hallF2: DZ0002 <ON> Staircase northF3: DZ0003 <ON> Staircase south
[DOWN] [ZOOM]
Press the function key for the desired set deviation, or first press the softkey [DOWN] if the desired set deviation is not displayed
001. SETTING DEVIATION:: DZ0001 Entrance hall004. SETTING DEVIATION:: DZ0004 ArchiveF1: DZ0002 <ON> Staircase northF2: DZ0003 <ON> Staircase southF3: DZ0004 <ON> Archive
[ZOOM]
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
58
Chapter 7 Assistance for Troubleshooting
Subjects in this chapter Procedure in case of faults
Procedure in case of faults
Procedure The table below shows a list of frequently occurring faults and offers help for their correction:
Note:If the fault cannot be corrected by these means, call your service company.
Kind of fault Possible cause Correction
Fault of a specific detector Detector optics defective
Defective electronics
Replace detector
Wait 5 minutes
Reset fault
Accu failure Battery defective or not charged
Call Service
Power failure Power failure > 1 hour Wait until power is switched on again
Reset fault
Circuit breaker activated Switch circuit breaker on
Reset fault
Power supply unit defective Call Service
Short to earth Short-circuit to earth, e.g.
Water in a detector
Leakage currents by soil-ing
Call Service
Communication fault Electromagnetic disturb-ances
System overload
Defective LAN device
Call Service
Fault SI300 (FA) SI302 (DIVERS) SI302 (OA1) SI303 (OA1) SI303 (OA2) SI304 (LAN1) SI305 (LAN2)
Fuse faults in MCU Call Service
Continued on next page
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
59
Procedure in case of faults, continued
Fault Possible cause Correction
Fault L1 xxxxxxxxx
Fault L2 xxxxxxxxx
Technical problem (tempor-ary or permanent) in the detector line.Usually caused by the re-moval of a detector
Reset fault
If the fault cannot be ac-knowledged:Call Service
LAN channel A fault
LAN channel B fault
Communication fault in the LAN
Call Service
System cannot be reset fol-lowing an alarm
Common alarm LED alarm is not reset
Poll alarm list
Bring faulty detector into normal position
or
Switch off pertinent de-tector zone
Reset system
Copyright by Securiton AG Release 05.00
Operating Instructions for the Fire Alarm System SecuriPro ®
60