alpha connect
Operating ManualBACnet / ModBus
UK
83055700cUK – Translation into English of the original German operating manual
2 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Contents
1 Configuringthebuildingservicesmanagementsystem(GLT) ..................................31.1 Requirements:..............................................................31.2 Followingtheconfiguration ..................................4
1.3 Enablingwithadongle ...........................................4
1.4 Completionoftheconfiguration ........................4
2 alphaconnecttool ..........................................................52.1 Languageselection...................................................5
2.2 Networkcardselection ...........................................5
2.3 Menubar .........................................................................52.4 Executiontypes ...........................................................5
2.5 Additionalalphaconnectfunctions..................9
2.6 SaveIBNlog–Part1 ..............................................9
2.7 SaveIBNlog–Part2 ..............................................9
2.8 SaveIBNlog–Part3 ..............................................9
2.9 Theversioninformationwindow(autoupdate) ...........................................................................10
2.10 Whatyoushouldnote: ..........................................10
3 BACnet.....................................................................................11
3.1 Term .................................................................................11
3.2 Functions .....................................................................11
3.3 Objects ...........................................................................11
3.4 Objectsprovided ......................................................11
3.5 Services .........................................................................13
3.6 Supportedfunctions ...............................................13
3.7 Transportsystems/transmissionroutes ...14
3.8 Datapoints ...................................................................14
3.9 DatarequiredforBACnetintegration(checklist): ....................................................................14
3.10 BACnetprotocolinformation .............................15
3.11 Productdescription: ................................................15
3.12 StandardObjectTypesSupported: ...............15
3.13 DataLinkLayerOptions: .....................................16
3.14 NetworkingOptions: ...............................................16
3.15 CharacterSetsSupported: ................................16
3.16 Descriptionofthedatapoints ...........................17
3.17 BACnetObjectlist ...................................................22
4 ModBus ...................................................................................23
4.1 Term .................................................................................23
4.2 Functions.......................................................................23
4.3 Register ..........................................................................24
4.4 Connection ...................................................................24
4.5 Datapoints ...................................................................24
4.6 Discreteinputs(readonly) .................................24
4.7 Inputregister(readonly) .....................................24
4.8 Coils .................................................................................25
4.9 Holdingregister .........................................................26
4.10 Configuration ..............................................................27
3Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
1 Configuringthebuildingservicesmanagementsystem(GLT)
BACnet is availablewith software versionV1.60andhigher, ModBus with V1.74/V2.74/V3.76/V4.76 andhigher.
ThefollowingdisplaycanbeseenundertheService->Information->BACnetmenuitemofanunconfiguredsystem:
Thedisplaymeansthatalphaconnectisnotconfiguredandnotactivated.
If the point BACnet is missing under "Service" ->"Information", thesoftwareversionof thecontroller isolderthanV1.60.
NOTE.As soon as ModBus is available, the menuitem is no longer called BACnet but GLT(buildingservicesmanagementsystem).
1.1 Requirements:Fortheconfigurationthecomputermustbeconnectedtoafunctioningnetworkordirectlytotheheatpumptobeconfigured.
The computer must have an IP address, which it iseitherassignedbythecontrollerwithactivatedDHCPserver (->VariantA),byanotherDHCPserver in the
network (->VariantB),orwhich isassignedmanually(->VariantC).
VariantA: HeatpumpcontrollerasDHCPserverTheDHCPserver isactivatedat thecontrollerunderService->SystemControl->WebServer.
ThePCmustthenbeconfiguredastheDHCPclient.
VariantB: HeatpumpcontrollerasDHCPclientThe DHCP client is activated at the controller underService->SystemControl->WebServer.
The PCmust then also be configured as theDHCPclient. The PC and heat pump controller are thenassignedtheIPaddressesbyanexistingDHCPserverinthenetwork(e.g.arouter).
VariantC:ManualconfigurationoftheIPsettingsThe IP settings are set up at the controller underService->SystemControl->IPaddress.
An IP address, different to that of the controller IP,mustthenbesetinthesamenetworkatthePC.
4 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Example:
HeatpumpcontrollerhastheIPaddress192.168.1.5->PChastheIPaddress192.168.1.10.
NOTE.IfthebroadcastaddressissetincorrectlytheheatpumpcontrollerisnotfoundviaBACnet!
IfthenetworkissetupcorrectlytheGLTconfigurationcanbecarriedoutwiththehelpofalphaconnect.
1.2 FollowingtheconfigurationIftheconfigurationwascarriedoutusingthetool,thedisplay (for BACnet) looks like this and the GLT isactivatedfor4hoursfortesting:
Theremainingtesttimeisdisplayedinthetitlerowandthesetvaluesbelowit.
If thefourhourshaveexpiredtheGLT isdeactivatedagainandcanberestartedusingthetoolifnecessary.
1.3 EnablingwithadongleUSBdonglewithalicenceisrequired.
If this is inserted into the heat pump controller a GLT_Iconappearsonthemainscreen.
If this is selected a confirmation prompt appears,whether theGLTshouldbeactivatedpermanentlyornot:
Thestill-availablelicencesaredisplayed,forexample:
Onconfirmationa licence isenabledfromthedongleandthefollowingdisplayappears:
The following display can now be seen under theService->Information->GLTmenuitem:
ForBACnet:
ForModBus:
NOTE.ItispossibletoswitchbetweenModBusandBACnetatanytime.
1.4 CompletionoftheconfigurationIf the configurationwas carried outwithVariantA orB (controller as DHCP client or DHCP server), theIP data should now be entered manually accordingto Variant C. You are usually given this data by thebuildingservicesmanagementsystemengineer.
THE CONFIGURATION IS COMPLETED
5Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
2 alphaconnecttoolThe alpha connect tool is located on the USB stick,withwhichtheseinstructionswereenclosed.
2.1 LanguageselectionWhentheprogramisrunforthefirsttimethelanguageselection window is displayed automatically. If thelanguageistobechangedatalaterdatethelanguageselectionwindowcanbeopenedagainviatheOptionmenu.
Laterversionsof theprogrammaycontainadditionallanguages.
1
2
1 Selectlanguage 2 Confirm
2.2 NetworkcardselectionThe program detects the correct network cardautomaticallyanddoesnothavetobeconfiguredanyfurther.
Ifdetectionisnotpossible(severalnetworkcardsandIPaddresses),amessageopensandthenetworkcardselectionwindow(inEnglish)opens.
1
2
3
1 Currentlyselectednetworkcard 2 IPdataofthecurrentnetworkcard 3 Statusdisplay.Onlynetworkcardswith
greenstatusaresuitable.
2.3 Menubar
File: ExittheprogramandcreatetheEDEfiles.
Options: Changing the language,switchingbetweendefault and expert mode and selecting the networkcard.
Tools: Creating GLT files and the broadcastcomputer
2.4 ExecutiontypesTherearetwotypesofexecutionforthisprogram:
-Defaultmode(guidedinstallation),whichisactivatedbydefault
-Expertmode,inwhichalloptionsaredisplayedinawindow.
Executiontype:DefaultmodeBydefault, intheStartwindowabroadcast isstartedto all heat pumps in the same network (immediateenvironment) and they are listed in a list with theirserialnumber,IPandstatus.
512
3
4
1 IP information 2 Search function 3 Heat pumps found 4 Open manual input 5 Selection information
6 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
IPinformation
The IP information is solely to provide informationto the user. It shows the current IP of the selectednetworkcard.
Searchfunction
The search bar shows the search progress. Click"Search"torestartthesearch.
If the search ends without having found a heatpump to display, thewindow formanual input opensautomatically.
Heatpumpsfound
This list enables oneof theheat pumps found to beselected. The extended data is displayed followingselectioninthe"Selectioninformation"windowandtheconfigurationandtestbuttonsbecomeavailable.
Thestatusisalwaysoneofthesestates:Not possible:GLTisnotpossiblewiththiscontrollerfirmware.Pleaseperformanupdate.Possible:GLTispossiblebutnotyetactivated.Test run:GLThasbeenconfiguredandisrunningintestmode.Activated:GLThasalreadybeenactivatedonthiscontroller.
SelectioninformationwindowThewindowshowsfurtherinformationontheselectedheatpumpandallowstheGLTtobeconfiguredaswellasdirecttestingoftheheatpump.
The device name is the alias of the heat pump onthe BACnet level; accordingly, unconfigured BACnetsystems do not return any names. Irrelevant forModBus.
ConfiguringisonlypossibleforsystemsinwhichGLTispossible inprinciple;direct testing isonlyavailableforsystemswithalreadyconfiguredGLT.
ConfigurationwindowAllotherwindowshaveacounterpart inExpertmodeandarethereforeexplainedthereingreaterdetail.
However, in default mode there is always a buttonlabelled "Back",whichenables return to thepreviouswindow.
SwitchingtoExpertmodeTo switch to Expert mode, you can either use the"Options" -> "Expert mod" menu or the keyboardshortcut"CTRL+E".
ProceedasfollowstoswitchfromExportmodebacktoDefaultmode.
7Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Executiontype:ExpertExpertmodeconsistsoffourdifferentblocks,eachofwhich is explained individually in the following. Theblocks correspond to the individual steps of defaultmode.
ManualinputManual inputenablesdirectselectionofaheatpumpinthenetwork.Subnetmask,broadcastandgatewayareallacceptedbythecurrentlyselectednetworkcardandcanalsonotbechanged. In the"IP"field,enterthe same numbers as you can see under Service/SystemControl/IPaddress.
If the DHCP server is activated on the controller,alternatively you can set the checkmark at "DHCP Server active"toenteradefaultconfiguration.
Check also whether the port is correct. By default,youcanremovethecheckmarkfromthedefaultport;otherwise,pleaseentertheportofthecontrollerinthe"Port"field(bydefault"47808"forBACnet).
Then click "Test connection". If everything has beenenteredandconnectedcorrectly, the text turnsgreenand changes to "Connection test successful". Fromnowtheotherstepsareavailable.
ConfigurationIn the configuration block you can make varioussettings. After clicking "Save & Test" the GLT isactivatedandatestrunisstartedonthisheatpump.
InsystemsinwhichModBus/TCPisnotyetavailable,BACnetispreselectedandcanbeconfigureddirectly.
forBACnet: forModBus:
Overviewoftheconfigurationoptions:• Off: GLT is possibly licensed but not activated.
Control listensneither toBACnetnor toModBusqueries.
• BACnet/IP: GLT is configured on BACnet andlistens to theportgivenunder"BACnetPort",bydefault47808
• ModBus/TCP:GLTisconfiguredonModBusandlistenstoTCPPort502forincomingconnections.Thedevicename isusedsolely for identificationpurposesbyAlphaConnectandhasnoeffectontheGLT.
• TheNAD is an additional network address. TheGLT only responds to commands sent to thisaddress. Exception: The value 0 is accepted as"Broadcast"(ModBus).
• Theindividualoptionsunder"Writable Settings" correspond to the data points of the heat pumpwhich are writable in principle; a checkmarkmeans"writable".
• The"BACnet Port"fieldgivestheportviawhichthecontrollercanbereachedbyBACnet.(Default:47808)
• The other text fields are used to identify thesysteminthenetwork.
8 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Testrun–Part1Duringthetestrun,thestatuswindowshownbelowisdisplayed forBACnet, and illustrates the current teststatus.Itmustbeclosedmanuallywhenthetestrunisfinished.
ItdoesnotappearwithModBus.
Testrun–Part2Duringthetest,theprogramsearchesforthecurrentlyset system.With BACnet this is done via aWho Is (broadcast), with ModBus the system is addresseddirectly. If thesetheatpump is included in the listofresults,thesettingwassuccessful.
Thistestcanberepeatedbyclicking"Update".
NOTE.With ModBus the current system only isalways displayed; with BACnet all thosefoundinthenetworkaredisplayed.
Testrun–Part3If a device is selected from the list, the programautomatically queries the list of data points from thisdevice,aswellasthecurrentvalues.
ExampleofaBACnetdevice:
NOTE.Ifadevicehas toomanydatapoints,errorscanoccur.
ExampleofaModBusdevice:
NOTE.The displayed values correspond to allavailable data points; however, it is notpossible to query the names, resolution orunitsofthedatapointsviaModBus.
9Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
2.5 Additionalalphaconnectfunctions
Click "Save IBN record" to open a file selectionwizard,which savesall relevant dataof the selecteddeviceinCSVformat.
2.6 SaveIBNlog–Part1This block is only used if you want to save the IBNrecord. In thiswindow you canenter peripheral dataonthecurrentprojectandsaveit/printitout.
Indefaultmodethisblock isonlyopened ifyouwanttosavetheIBNrecordattheendofthetestroutine.Italsoincludesthe"Save"button.
The project data is saved over the runtime of theprogram and is automatically available when theprogramisre-opened.
2.7 SaveIBNlog–Part2
Installer
Thiswindowappearsifyouclickoneofthe"Change"buttons in the project informationwindow. It enablesvariousinformationtobeentered,whichcanbesaved;howeveronlythenameandfirstnamearedisplayedinthemainwindow.
2.8 SaveIBNlog–Part3
Project
Fortheprojectsettingthe"Firstname"fieldisblockedand the "Name" field becomes "Project name". Thisis done for clarity reasons only and has no practicalbackground.
Additionalfunctions(ModBus)The ModBus configuration can be saved using theTools→"SaveModBusConfiguration"menu item. InthefileinCSVformat(MSExcel-compatible)youcanthenviewwhichdatahasbeenreadoutandwhetheritiswritableornot.
10 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Additionalfunctions(BACnet)TheTools -> "SaveEDEFiles" item can be used tooutputtheEDEfilesrelevantforthebuildingservicesmanagement system engineer according to theBACnetstandardforthecurrentlyconfiguredsystem.
2.9 Theversioninformationwindow(autoupdate)
The program information provides a quick overviewofthecurrentversionof theprogram,thedate itwascreated and two options for updating the programautomatically.
1
2
3
4
1Givesthecurrentversionnumberoftheprogram.
2Givesthedateonwhichtheprogramwascreated.
3 Updatestheprogram,providedanupdateisavailable.
4Ifactivated,theprogramtriestoupdateitselfautomaticallywhenitisstarted.
Confirmationdialog.Performtheupdate?
2.10 Whatyoushouldnote:• With V1.xx & V2.xx the licence is saved on the
masterboard,withV3.xx&V4.xxitissavedonthecontrol unit, i.e. if the corresponding componenthas to be replaced a new licence is required(contactcustomerservice!).
• Configurationissavedoncontrolunit;intheeventofadefecttheGLTmustbereconfigured.
• If the outside temperature is preset the outsidetemperature sensor in the device must bedisconnected.
• If theconnectionbetweenWPandGLT fails thedevice carries on running with the most recententries.
• IfpumpswhicharenormallycontrolledbytheWPcontroller are controlled by an external controlsystem:
->contactthefactorytodiscusstheinterface
• Ifthedeviceisnotfoundviaalphaconnect
->checktheIPandportsetting
-> check the broadcast address with the broad-cast calculator in alpha connect under Tools ->BroadcastCalculator
11Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
3 BACnet
3.1 TermThe abbreviation "BACnet" stands for "BuildingAutomation and Control network". BACnet isan independent data transmission protocol for"open communication in data networks of buildingautomationandbuildingcontrol"with theobjectiveof"interoperability", i.e. theabilityofdevices insystemsto work with those of other manufacturers, acrosssystems.BACnet is basedonstandardisedservices,objectsand functionsand is continuouslyadapted tonew requirements and added to in various interestgroupsworldwide.
NOTE.TheBACnetdeviceIDmustbeuniqueinthecompleteBACnetnetwork!
3.2 Functions• Integration in a higher-level building services
controlsystemwithBACnet/IP
• Alltemperaturescanbereadout.
• Outdoortemperature,returnsetpointtemperatureandthethreemixingcircuitsetpointtemperaturescanbepreset.
• Faults can be read out with error number anddescription.
• FaultscanbeacknowledgedviaBACnet.
• Current operating state and the number ofcompressorscurrentlyrunningcanbereadout.
• Alloperatingmodescanbepreset:
Heatingmode
Domestichotwatermode
Coolingmode
Ventilationmode
Swimmingpoolmode
Mixingcircuit2mode
Mixingcircuit3mode
• Number of released compressors can bepredefined(Block,1VD,2VD)
• Thecurrentheatquantitiescanbereadout.
Heatingheatquantity
Hotwaterheatquantity
• DateandtimeoftheheatpumpcontrollercanbesynchronisedviaBACnet.
• DevicecanberestartedviaBACnet.
3.3 ObjectsThedata in aBACnet device is divided into objects.Eachobjecthasspecificproperties.
Example:
There is an outdoor temperature object with theproperties:
B A C n e tname
Germanname Example:
Objecttype Objecttype AnaloginputO b j e c tname
Objectname Outdoor tempera-ture
Present val-ue
Currentvalue 25.4
Unit Unit °CDescription Description Current outdoor
temperature... ... ...
Other objects would include, for example, flowtemperature,numberofcompressorsrunning,heatingmode…
3.4 ObjectsprovidedThevalueswhichare tobeprovidedvia theBACnetprotocolareassignedBACnetobjecttypes.Atpresentthere are 37 different object types in the BACnetstandard.Themostimportantare:
Analoginput -AnalogOutput -Analogvalue -Multi-StateInput -Multi-StateValue -BinaryInput -BinaryOutput -Accumulator (Count/metervalueinput)
Analog inputs, for example, represent a specificmeasuredvaluewithcorrespondingpropertiessuchasname,unit,statusordescriptionoftheobject.
12 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Allvalues fromtheconceptwhichare tobereadoutorchangedareassignedoneobject typeeach inthefollowingdescription.
TheBinary Inputobjectspecifiesanobjecttype,whoseproperties represent external visible characteristicsof thedatapoint forabinary input. It isaphysicalorhardwaredatapoint,whichcanonlyassumeoneoftwouniquestatesasaswitchingoractuatingcommand.IntheBACnetstandardthestatesarecalled"active"and"inactive".
Thebinaryinputshereare:• Self-resettingfault
• Non-self-resettingfault
The Binary Output object specifies an objecttype, whose properties represent external visiblecharacteristicsofthedatapointforabinaryoutput. Itis a physical or hardwaredatapoint,which canonlyassume one of two unique states as a switching oractuatingcommand.IntheBACnetstandardthestatesarecalled"active"and"inactive".
Thebinaryoutputshereare:• Errorreset
The Analog Input object is an object type whichrepresentsthepropertiesofananaloghardwareinput.For example, a sensor for measuring temperaturecan be connected to this input. If there are severalanalog inputs in a device, several other instancesofthesameobjecttypearecreatedwithdifferentObject_Identifiers. The pickup device (sensor) can assumeanyvaluewithinitsmeasuringrange.
Theanaloginputsinclude:• Flowtemperature
• Returntemperature
• Hotgastemperature
• Heatsourcesinputtemperature
• Heatsourcesoutputtemperature
• Mixingcircuit1temperature
• Return,externaltemperature
• Roomremoteadjustertemperature
• Mixingcircuit2temperature
• Roomremoteadjuster2temperature
• Mixingcircuit3temperature
• Roomremoteadjuster3temperature
• Solarcollectortemperature
• Solarstoragetanktemperature
• Externalenergysourcetemperature
• Supplyairtemperature
The Analog Value object is used to output analogvalues (voltages, currents, temperatures) on ahardware connection of a BACnet device. It is aphysicalorhardwaredatapoint.Thecontrollingdevice(actuator) can assume any value between 0 and100%within its range of control, which is convertedfromthephysicaloutputasacontrolcommandintoacorrespondingcurrentorvoltagevalue.Forexample,itcanbeusedtosendtheoutdoortemperaturefromacentralweatherstationtoallBACnetdevices.
Theanalogvaluesoftheheatpumpcontrollerare:• Outdoortemperature
• Returnsetpointtemperature
• Mixingcircuit1setpointtemperature
• Mixingcircuit2setpointtemperature
• Mixingcircuit3setpointtemperature
TheMulti-State Inputobjectspecifiesanobjecttype,whose object properties represent externally visiblecharacteristicsofadatapointforseveralbinaryinputs,connected by an arbitrary binary logic within theBACnet device. The object is derived from physicalor virtual data points, e.g. the limit value messagesof several analog inputs or from a mathematicalcalculation. The "Present Value" is an integer whichrepresentsastate.
Multi-stateinputsare:
• Operatingstate
• Off / with 1 VD / with 2 VDs (currently runningcompressors)
The Multi-State Value object specifies an objecttype, whose object properties represent externallyvisiblecharacteristicsofadatapointforseveralbinaryoutputs,connectedbyanarbitrarybinary logicwithintheBACnetdevice.Theobjectisderivedfromphysicalorvirtualdatapoints,e.g.for"active/inactivestatesofseveralbinaryoutputsorthevalueofananalogoutput.The"PresentValue"isanintegerwhichrepresentsthestate.
13Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Multi-statevalueshereare:• Block/Release1VD/Release2VDs
• Heatingmode
• Domestichotwatermode
• Coolingmode
• Ventilationmode
• Swimmingpoolmode
• Mixingcircuit2mode
• Mixingcircuit3mode
The Accumulator object specifies an object typewhose properties represent externally visiblecharacteristics of a measurement pulse counter forpulsegeneratingmeasuringdevices, e.g. for kilowatthoursorheatquantitymeasurement.ItisaphysicalorhardwaredatapointfortheGA"Count"function.
Count(meter)valueinputshereare:• Heatingheatquantity
• Domestichotwaterheatquantity
• Swimmingpoolheatquantity
• Totalheatquantity
3.5 ServicesWithBACnet,dataisexchangedviadefinedservices.
Examples:• Readingproperties(readproperty)
• Writingproperties(writeproperty)
• Readseveralproperties(readpropertymultiple)
• Searchingfordevices(who-is,i-am)
• Timesynchronisation
• Restarttheunit(reinitializedevice)
• ...
3.6 SupportedfunctionsThe BACnet profile: "BACnet Application SpecificController"(B-ASC)issupported.
AB-ASC is a configurable automation device. It canbe intended for special applications and supportsprogramsproducedbythemanufacturer.
A more precise list of which BACnet InteroperabilityBuildingBlocks(BIBBs)wereimplementedforthiscanbeseeninthefollowingtable.
DS-RP-B D M -DDB-B
DS-WP-B D M -DOB-BD M -DCC-B
Meaningoftheindividualabbreviationsinthetable:
DS-RP-B – Data Sharing-ReadProperty-B Aclientcanreadoutavaluefromthecontroller.
DS-WP-B – Data Sharing-WriteProperty-BAclientcanwriteavalueonthecontroller.
DM-DDB-B – Device Management-Dynamic Device Binding-B
Aclientsearches for informationaboutotherdevicesin the GA network and interprets correspondingannouncements(Who-Is/I-Am).
DM-DOB-B – Device Management-Dynamic Object Binding-B
A client searches the GA network for addressinformationaboutBACnetobjects(Who-Has,I-Have).
DM-DCC-B – Device Management-DeviceCommunicationControl-B
The client exerts control over the communicationbehaviourofthecontroller.In addition to the required BIBBs others are alsocurrentlysupported:
DS-RPM-B – Data Sharing-ReadPropertyMultiple-B
Aclientcanreadoutseveralvaluesfromthecontrolleratthesametime.
DS-COV-B – Data Sharing COV-BThe client subscribes for information about value
changesfromtheheatpumpcontroller.
DM-TS-B or DM-UTC-B – Device Management-TimeSynchronization or Device Management-UTCTimeSynchronization-B
Theclientprovidestimesynchronisationwiththelocal/UTCworldtime.
DM-RD-B – Device Management-ReinitializeDevice-B
Theclientinstigatesthecontrollertoperformawarmorcoldstartofthesoftware.
14 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
3.7 Transportsystems/transmissionroutes
In the BACnet standard there are various datatransmissionroutes,suchasEthernetorserialinterface/port(RS232)ordifferenttwo-wireorradio(wireless)solutions.
WeuseBACnet / IPovertheEthernetinterfaceoftheheatpumpcontroller.
BACnet / IP is supported
3.8 DatapointsThe following tables show the data points providedwiththecorrespondingobjecttype.
Default:BACnetobjecttype
Flow OBJECT_ANALOG_INPUT
Return OBJECT_ANALOG_INPUT
Hotgas OBJECT_ANALOG_INPUT
Heatsourceon OBJECT_ANALOG_INPUT
Heatsourceoff OBJECT_ANALOG_INPUT
Mixingcircuit1 OBJECT_ANALOG_INPUT
Externalreturn OBJECT_ANALOG_INPUT
Roomremoteadjuster OBJECT_ANALOG_INPUT
Operatingstate OBJECT_MULTI_STATE_INPUT
Off/with1VD/with2VD OBJECT_MULTI_STATE_INPUT
Outdoortemp. OBJECT_ANALOG_VALUE/INPUT
Mixingcircuit1setpoint OBJECT_ANALOG_VALUE/INPUT
Returnsetpoint OBJECT_ANALOG_VALUE/INPUT
Block/release1VD/Release2VD
OBJECT_MULTI_STATE_VALUE
Heatingmode OBJECT_MULTI_STATE_VALUE/INPUT
Domestichotwatermode OBJECT_MULTI_STATE_VALUE/INPUT
Self-resettingfault OBJECT_BINARY_INPUT
Fault OBJECT_BINARY_INPUT
Errorreset OBJECT_BINARY_OUTPUT
with Comfort board:BACnetobjecttype
Mixingcircuit2 OBJECT_ANALOG_INPUT
Roomremoteadjuster2 OBJECT_ANALOG_INPUT
Mixingcircuit3 OBJECT_ANALOG_INPUT
Roomremoteadjuster3 OBJECT_ANALOG_INPUT
Solarcollector OBJECT_ANALOG_INPUT
Solarstoragetank OBJECT_ANALOG_INPUT
Externalenergysource OBJECT_ANALOG_INPUT
Mixingcircuit2setpoint OBJECT_ANALOG_VALUE/INPUT
Mixingcircuit3setpoint OBJECT_ANALOG_VALUE/INPUT
MK2mode OBJECT_MULTI_STATE_VALUE/INPUT
MK3mode OBJECT_MULTI_STATE_VALUE/INPUT
Coolingmode OBJECT_MULTI_STATE_VALUE/INPUT
Swimmingpoolmode OBJECT_MULTI_STATE_VALUE/INPUT
with ventilation board:BACnetobjecttype
Supplyairtemperature OBJECT_ANALOG_INPUT
Ventilationmode OBJECT_MULTI_STATE_VALUE/INPUT
with heat metering:BACnetobjecttype
Heatingheatquantity OBJECT_ACCUMULATOR
Domestichotwaterheatquantity OBJECT_ACCUMULATOR
Swimmingpoolheatquantity OBJECT_ACCUMULATOR
Totalheatquantity OBJECT_ACCUMULATOR
3.9 DatarequiredforBACnetintegration(checklist):
The following data is required to configure a controlunit:
Example Data
IPaddress 192.168.1.2
Subnetmask 255.255.255.0
Broadcastaddress 192.168.1.255
Gateway 192.168.1.1
UDPport 47808
BACnetDevicename WP1
BACnetDeviceID 1234
Modelname LW...
Location Kasendorf
Devicedescription Heatpump
Accesstodatapoints Readonly Read/write
Outdoortemperature
Returnsetpointtemperature
15Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Mixingcircuit1set-pointtemperature
Mixingcircuit2set-pointtemperature
Mixingcircuit3set-pointtemperature
Heatingmode
Domesticwatermode
MK2mode
MK3mode
Coolingmode
Swimmingpoolmode
Ventilationmode
3.10 BACnetprotocolinformationBACnetprotocolrevision:1Rev.10
3.11 Productdescription:The BACnet provides the heat pump controller withaccesstotheheatpump
BACnet Standardized Device Profile (Annex L):
BACnetOperatorWorkstation(B-OWS)
BACnetBuildingController(B-BC)
BACnet Advanced Application Controller (B-AAC)
x BACnetApplicationSpecificController(B-ASC)
BACnetSmartSensor(B-SS)
BACnetSmartActuator(B-SA)
List of all BACnet Interoperability Building BlocksSupported(AnnexK):
DataSharingReadProperty-B DS-RP-BData Sharing Read Property Multi-ple-B
DS-RPM-B
DataSharingWriteProperty-B DS-WP-BDataSharingCOV-B DS-COV-BDevice Management Dynamic De-viceBinding-B
DM-DDB-B
Device Management Dynamic Ob-jectBinding-B
DM-DOB-B
Device Management Device Com-municationControl-B
DM-DCC-B
DeviceManagementTimeSynchro-nization-B
DM-TS-B
DeviceManagementReinitializeDe-vice-B
DM-RD-B
Segmentation Capability:X Segmentedrequestssupported WindowSize:16
X Segmentedresponsessupported WindowSize:16
3.12 StandardObjectTypesSupported:
Analog InputDynamicallyCreatable: No
DynamicallyDeletable: No
ProprietaryProperties: None
OptionalProper-tiesSupported
WriteableProperties
PropertyRangeRestrictions
Description upto48characters
Analog ValueDynamicallyCreatable: No
DynamicallyDeletable: No
ProprietaryProperties: None
OptionalProper-tiesSupported
WriteableProperties
PropertyRangeRestrictions
Description upto48charactersPresent_Value
Binary InputDynamicallyCreatable: No
DynamicallyDeletable: No
ProprietaryProperties: None
OptionalProper-tiesSupported
WriteableProperties
PropertyRangeRestrictions
Description upto48characters
Binary OutputDynamicallyCreatable: No
DynamicallyDeletable: No
ProprietaryProperties: None
16 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
OptionalProper-tiesSupported
WriteableProperties
PropertyRangeRestrictions
Description upto48charactersPresent_Value
DeviceDynamicallyCreatable: No
DynamicallyDeletable: No
ProprietaryProperties: None
OptionalProper-tiesSupported
WriteableProperties
PropertyRangeRestrictions
Description upto48characters
Multistate InputDynamicallyCreatable: No
DynamicallyDeletable: No
ProprietaryProperties: None
OptionalProper-tiesSupported
WriteableProperties
PropertyRangeRestrictions
Description upto48characters
Multistate ValueDynamicallyCreatable: No
DynamicallyDeletable: No
ProprietaryProperties: None
OptionalProper-tiesSupported
WriteableProperties
PropertyRangeRestrictions
Description upto48characters
AccumulatorDynamicallyCreatable: No
DynamicallyDeletable: No
ProprietaryProperties: None
OptionalProper-tiesSupported
WriteableProperties
PropertyRangeRestrictions
Description upto48characters
3.13 DataLinkLayerOptions:x BACnetIP,(AnnexJ)
BACnetIP,(AnnexJ),ForeignDevice
ISO8802-3,Ethernet(Clause7)
ANSI/ATA878.1,2.5Mb.ARCNET(Clause8)
ANSI/ATA878.1,RS-485ARCNET (Clause8), baudrate(s)____________
MS/TPmaster(Clause9),baudrate(s):
MS/TPslave(Clause9),baudrate(s):
Point-To-Point, EIA 232 (Clause 10), baudrate(s):
Point-To-Point, modem, (Clause 10), baud rate(s):
LonTalk,(Clause11),medium:__________
Other:
3.14 NetworkingOptions: Router,Clause6-Listallroutingconfigurations,
e.g.,ARCNET-Ethernet,Ethernet-MS/TP,etc.
AnnexH,BACnetTunnelingRouteroverIP
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by ForeignDevices?
Yes No
3.15 CharacterSetsSupported:Indicatingsupportformultiplecharactersetsdoesnotimplythattheycanallbesupportedsimultaneously.
x ANSIX3.4
IBM/MicrosoftDBCS
ISO8859-1
ISO10646(UCS-2)
ISO10646(UCS-4)
JISC6226
17Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
3.16 DescriptionofthedatapointsFlow temperature
BACnetObjectType AnaloginputBACnetObjectID 1Unit °CResolution 0.1 °C
Return temperature
BACnetObjectType AnaloginputBACnetObjectID 2Unit °CResolution 0.1 °C
Hot gas temperature
BACnetObjectType AnaloginputBACnetObjectID 3Unit °CResolution 0.1 °C
Heat source on
BACnetObjectType AnaloginputBACnetObjectID 4Unit °CResolution 0.1 °C
Heat source off
BACnetObjectType AnaloginputBACnetObjectID 5Unit °CResolution 0.1 °C
Mixing circuit 1
BACnetObjectType AnaloginputBACnetObjectID 6Unit °CResolution 0.1 °C
External return
BACnetObjectType AnaloginputBACnetObjectID 7Unit °CResolution 0.1 °C
Room remote adjuster
BACnetObjectType AnaloginputBACnetObjectID 8Unit °CResolution 0.1 °C
Mixing circuit 2
BACnetObjectType AnaloginputBACnetObjectID 9Unit °CResolution 0.1 °C
Room remote adjuster 2
BACnetObjectType AnaloginputBACnetObjectID 10Unit °CResolution 0.1 °C
Mixing circuit 3
BACnetObjectType AnaloginputBACnetObjectID 11Unit °CResolution 0.1 °C
Room remote adjuster 3
BACnetObjectType AnaloginputBACnetObjectID 12Unit °CResolution 0.1 °C
Solar collector
BACnetObjectType AnaloginputBACnetObjectID 13Unit °CResolution 0.1 °C
Solar storage tank
BACnetObjectType AnaloginputBACnetObjectID 14Unit °CResolution 0.1 °C
18 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
External energy source
BACnetObjectType AnaloginputBACnetObjectID 15Unit °CResolution 0.1 °C
Outdoor temperature
BACnet Object-Type
Analoginput Analogvalue
BACnet ObjectID
16 1
Unit °CResolution 0.1 °C
If the outdoor temperature is preset via BACnet ->disconnectsensorinthedevice.
Return setpoint temperature
BACnetObjectType Analoginput AnalogvalueBACnetObjectID 17 2Unit °CResolution 0.1 °C
Mixing circuit 1 setpoint temperature
BACnetObjectType Analoginput AnalogvalueBACnetObjectID 18 3Unit °CResolution 0.1 °C
Mixing circuit 2 setpoint temperature
BACnetObjectType Analoginput Analog val-ue
BACnetObjectID 19 4Unit °CResolution 0.1 °C
Mixing circuit 3 setpoint temperature
BACnetObjectType Analoginput AnalogvalueBACnetObjectID 20 5Unit °CResolution 0.1 °C
Supply air temperature
BACnetObjectType AnaloginputBACnetObjectID 21Unit °CResolution 0.1 °C
Hot water actual temperature
BACnetObjectType AnaloginputBACnetObjectID 22Unit °CResolution 0.1 °C
Hot water setpoint temperature
BACnetObjectType Analoginput AnalogvalueBACnetObjectID 23 6Unit °CResolution 0.1 °C
Temperature, compressor intake
BACnetObjectType AnaloginputBACnetObjectID 24Unit °CResolution 0.1 °C
Temperature, evaporator intake
BACnetObjectType AnaloginputBACnetObjectID 25Unit °CResolution 0.1 °C
Temperature, compressor heater
BACnetObjectType AnaloginputBACnetObjectID 26Unit °CResolution 0.1 °C
Overheating
BACnetObjectType AnaloginputBACnetObjectID 27Unit KResolution 0.1bar
19Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Overheating setpoint
BACnetObjectType AnaloginputBACnetObjectID 28Unit KResolution 0.1 K
Pressure HD
BACnetObjectType AnaloginputBACnetObjectID 29Unit °CResolution 0.1 °C
Pressure ND
BACnetObjectType AnaloginputBACnetObjectID 30Unit BarResolution 0.01bar
RBE room temperature, actual
BACnetObjectType AnalogInputBACnetObject-ID 31Unit °CResolution 0,1°C
RBE room temperature, setpoint
BACnetObjectType AnalogInputBACnetObject-ID 32Einheit °CResolution 0,1°C
Current flow
BACnetObjectType AnalogInputBACnetObject-ID 33Unit l/hResolution 1l/h
Heating curve, heating, end pointBACnetObjectType AnalogInput AnalogValueBACnetObject-ID 34 7Unit °CResolution 0,1°C
Heating curve, heating, parallel shift
BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 35 8Unit °CResolution 0,1°C
Heating curve, heating, end point MK 1
BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 36 9Unit °CResolution 0,1°C
Heating curve, heating, parallel shift MK 1
BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 37 10Unit °CResolution 0,1°C
Heating curve, heating, end point MK 2
BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 38 11Unit °CResolution 0,1°C
Heating curve, heating, parallel shift MK 2
BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 39 12Unit °CResolution 0,1°C
Heating curve, heating, end point MK 3
BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 40 13Unit °CResolution 0,1°C
Heating curve, heating, parallel shift MK 3
BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 41 14Unit °CResolution 0,1°C
20 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Temperature, plus/minus
BACnetObjectType AnalogInput AnalogValueBACnetObject-ID 42 15Unit °CResolution 0,1°C
Operating state
BACnetObjectType MultistateinputBACnetObjectID 1States 1=Heatingmode
2=Domestichotwater3=Swimmingpool4=EVUoff5=Defrost6=Off7=Externalenergysource
Off / with 1 compressor / with 2 compressors (currently running)
BACnetObjectType MultistateinputBACnetObjectID 2States 1=Off
2=1compressorisrunning3=2compressorsarerunning
Block / Release 1 compressor / Release 2 compressors
BACnetObjectType MultistatevalueBACnetObjectID 1States 1=Blockheatpump
2=Release1compressor3 = Release 2 compres-sors
Heating mode
B A C n e t ObjectType
Multistateinput Multistatevalue
BACnetObjectID 3 2States 1=Automatic
2=Secondheatgenerator3=Party4=Holidays5=Off
Domestic hot water mode
BACnet Object-Type
Multistateinput Multistatevalue
BACnet ObjectID
4 3
States 1=Automatic2=Secondheatgenerator3=Party4=Holidays5=Off6=Charge
Mixing circuit 2 mode
BACnetObjectType Multistateinput Multistatevalue
BACnetObjectID 6 5States 1=Automatic
2=Secondheatgenerator3=Party4=Holidays5=Off
Mixing circuit 3 mode
BACnetObjectType Multistateinput Multistatevalue
BACnetObjectID 7 6States 1=Automatic
2=Secondheatgenerator3=Party4=Holidays5=Off
Cooling mode
BACnetObjectType Multistateinput Multistatevalue
BACnetObjectID 8 7States 1=Off
2=Automatic
21Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Heating heat quantity
BACnetObjectType AccumulatorBACnetObjectID 1Unit kWhResolution 1kWh
Domestic hot water heat quantity
BACnetObjectType AccumulatorBACnetObjectID 2Unit kWhResolution 1kWh
Swimming pool heat quantity
BACnetObjectType AccumulatorBACnetObjectID 3Unit kWhResolution 1kWh
Total heat quantity
BACnetObjectType AccumulatorBACnetObjectID 4Unit kWhResolution 1kWh
Ventilation mode
BACnetObjectType Multistateinput Multistatevalue
BACnetObjectID 9 8States 1=Automatic
2=Party3=Holidays4=Off
Swimming pool mode
BACnetObjectType Multistateinput Multistatevalue
BACnetObjectID 10 9States 1=Automatic
2=Notused3=Party4=Holidays5=Off
Self-resetting fault
BACnetObjectType BinaryinputBACnetObjectID 1States INACTIVE->nofaultACTIVE->fault
In the event of a fault, the error number with acorresponding description is displayed in theDescriptionandintheActiveText
Non-self-resetting fault
BACnetObjectType BinaryinputBACnetObjectID 2States INACTIVE->nofault
ACTIVE->faultIn the event of a fault the error number with acorresponding description is displayed in theDescriptionandintheActiveText
Error reset
BACnetObjectType BinaryoutputBACnetObjectID 1States INACTIVE->normal
ACTIVE->Errorreset
Set1tothisdatapointtoacknowledgeerrors.
22 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
3.17 BACnetObjectlistThefollowingtableshowstheobjectIDsofthedatapoints:whetheravalueisreadonly(INPUT)orwhetheritisalsowritable(VALUE).
Default:ANALOG
INPUTANALOG VALUE
MULTISTATE INPUT
MULTISTATE VALUE
BINARY INPUT
BINARY OUTPUT
ACCUMU-LATOR
Flow 1
Return 2
Hot gas 3
Heat source on 4
Heat source off 5
Mixing circuit 1 6
External return 7
Room remote adjuster 8
Operating state 1
Off / with 1VD / with 2VD 2
Outdoor temp. 16 1
Return setpoint 17 2
Mixing circuit 1 setpoint 18 3
Block/Release 1VD/Release 2VD 1
Heating mode 3 2
Domestic hot water mode 4 3
Self-resetting fault 1
Fault 2
Error reset 1
Domestic water actual temperature 22
Domestic water setpoint temperature 23 6
RBE room temperature, actual 31
RBE room temperature, setpoint 32
Current flow 33
Heating curve, heating, end point 34 7
Heating curve, heating, parallel shift 35 8
Heating curve, heating, end point MK 1 36 9
Heating curve, heating, parallel shift MK 1 37 10
Heating curve, heating, end point MK 2 38 11
Heating curve, heating, parallel shift MK 2 39 12
Heating curve, heating, end point MK 3 40 13
Heating curve, heating, parallel shift MK 3 41 14
Temperature, plus/minus 42 15
with Comfort board:ANALOG
INPUTANALOG VALUE
MULTISTATE INPUT
MULTISTATE VALUE
BINARY INPUT
BINARY OUTPUT
ACCUMU-LATOR
Mixing circuit 2 9
Room remote adjuster 2 10
Mixing circuit 3 11
Room remote adjuster 3 12
Solar collector 13
Solar storage tank 14
External energy source 15
Mixing circuit 2 setpoint 19 4
Mixing circuit 3 setpoint 20 5
MK2 mode 6 5
MK3 mode 7 6
Cooling mode 8 7
Swimming pool mode 10 9
23Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
with ventilation board:ANALOG
INPUTANALOG VALUE
MULTISTATE INPUT
MULTISTATE VALUE
BINARY INPUT
BINARY OUTPUT
ACCUMU-LATOR
Supply air temperature 21
Ventilation mode 9 8
with heat metering:ANALOG
INPUTANALOG VALUE
MULTISTATE INPUT
MULTISTATE VALUE
BINARY INPUT
BINARY OUTPUT
ACCUMU-LATOR
Heating heat quantity 1
Domestic hot water heat quantity
2
Swimming pool heat quantity 3
Total heat quantity 4
for heatpumps with LIN- and / or MODBus:ANALOG
INPUTANALOG VALUE
MULTISTATE INPUT
MULTISTATE VALUE
BINARY INPUT
BINARY OUTPUT
ACCUMU-LATOR
Compressor intake 24
Evaporator intake 25
Compressor heater 26
Overheating 27
Overheating setpoint 28
Pressure HD 29
Pressure ND 30
4 ModBus
4.1 TermModBusisanindependentprotocolforcommunicationbetweencomponentsofdifferentmanufacturersandsystems.In industry it isused in its "RTU" formasade factostandardand isusedwidely.TheModBus/TCPstandard isrelativelynewandwasstandardisedin2007.
ModBusisbasedonregisteraccesses,sothateachfunctionisassignedaspecificaddressandcanbechanged/readoutbythe"master".
Theait-DeutschlandGmbHcontrolsupportstheModBus/TCPstandardastheslave.
4.2 Functions• IntegrationinaproprietaryhomenetworkwithModBus/TCP.
• Diversedatapointscanbereadout.
◦ Temperatures
◦ Inputs
◦ Outputs
◦ Operatinghours
◦ Heatquantity
• Diversesetpointsandoperatingmodesaswellastheoutdoortemperaturecanbepredefinedviaahigher-levelGLT.
• Faultscanbeacknowledged.
24 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
4.3 RegisterThe ModBus/TCP data is provided in the form ofregisters.Fourtypesaresupported:
1. Discrete inputs: Truth values (Boolean values),e.g.inputs.Readonly
2. Coils:Truthvalues(Booleanvalues),e.g.outputs.Writable.
3. Inputregisters: Integervaluesof thecontrol,e.g.temperatures.Readonly.
4. Holding registers: Integer values of the control,e.g.setpointvalues.Writable.
Here the following must be noted: If a value is nolonger to be predefined, a value outside the definedlimits must be transferred. For coils, this means thevalue"0";forholdingregistersitmeansavalueoutsidethelimitsfortherelevantdatapointintheappendix.
4.4 ConnectionModBus/TCP shares the IP address of the controlsystemandcanbereachedviatheTCPport502.
WerecommendthatyouusethefreewareqModMasterforthetest,availableathttp://sourceforge.net/projects/qmodmaster/.
Whenprogrammingnote that someModBusstationsor nodes begin with address "1" but send 0. Ourregistersare0-based.
4.5 DatapointsAll data points are availablewith each configuration;however, they do not always have valid values oreffects. In general the following applies: If the datapointisnotvisibleinthecontroller,thevaluesaretobedeemedinvalid.
4.6 Discreteinputs(readonly)
Name IDEVU 0EVU2 1SWT 2VD1 3VD2 4ZWE1 5ZWE2 6ZWE3 7
4.7 Inputregister(readonly)Name ID Resolution Unit
Meantemperature 0 10 °CFlow 1 10 °CReturn 2 10 °CExternalreturn 3 10 °CHotwatertemperature 4 10 °CMK1flow 5 10 °CFlowMK2 6 10 °CFlowMK3 7 10 °CHotgastemperature 8 10 °CHeatsourceinlettemper-
ature9 10 °C
Heat source outlet tem-perature
10 10 °C
Room remote adjuster 1temperature
11 10 °C
Room remote adjuster 2temperature
12 10 °C
Room remote adjuster 3temperature
13 10 °C
Solar collector tempera-ture
14 10 °C
Solar storage tank tem-perature
15 10 °C
External energy sourcetemperature
16 10 °C
Supplyairtemperature 17 10 °CExtractairtemperature 18 10 °C
25Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Name ID Resolu-tion
Unit
Compressorintaketem-perature
19 10 °C
Evaporator intake tem-perature
20 10 °C
Temperature, compres-sorheater
21 10 °C
Overheating 22 10 KelvinOverheatingsetpoint 23 10 KelvinRBEroomtemperature,
actual24 10 °C
RBEroomtemperature,setpoint
25 10 °C
Highpressure 26 100 barLowpressure 27 100 barVD1operatinghours 28 1 Hours(h)VD2operatinghours 29 1 Hours(h)ZWE1operatinghours 30 1 Hours(h)ZWE2operatinghours 31 1 Hours(h)ZWE3operatinghours 32 1 Hours(h)Heat pump operating
hours33 1 Hours(h)
Heatingoperatinghours 34 1 Hours(h)Hot water operating
hours35 1 Hours(h)
Swimming pool operat-inghours
36 1 Hours(h)
Systemstatus 37 0=Heatingmode
1=Domestichotwa-ter
2=Swimmingpool
3=EVUoff
4=Defrost
5=Off
6 = External energysource
Heating heat quantity(High)
38 10 kWh
Heating heat quantity(High)
39 10 kWh
Hot water heat quantity(High)
40 10 kWh
Hot water heat quantity(High)
41 10 kWh
Swimming pool heatquantity(High)
42 10 kWh
Swimming pool heatquantity(High)
43 10 kWh
Total heat quantity(High)
44 10 kWh
Total heat quantity(High)
45 10 kWh
Errormemory 46
4.8 CoilsPleasenote:Allcoilsonlyhaveaneffectif"1"issenttothem.
If"0","Automatic"isassumed.
Name ID DescriptionErrorreset 0 Acknowledges the currently
queuederrorWatchdog 1 Reserved,isnotusedHUP 2 ForcedswitchingonoftheHUP.VEN 3 Forcedswitchingonofthefan.ZUP 4 ForcedswitchingonoftheZUP.BUP 5 ForcedswitchingonoftheBUP.BOSUP 6 ForcedswitchingonoftheBOSUP.ZIP 7 ForcedswitchingonoftheZIP.FUP2 8 Forced switching on of the 2nd
FUP.FUP3 9 Forced switching on of the 3rd
FUP.SLP 10 ForcedswitchingonoftheSLP.SUP 11 ForcedswitchingonoftheSUP.VSK 12 ForcedswitchingonoftheVSK.FRH 13 ForcedswitchingonoftheFRH.
26 Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
4.9 HoldingregisterName ID Resolution Unit Min. Max.
Outdoortemperature 0 10 °C -200 800Returnsetpoint 1 10 °C 150 800MK1flowsetpoint 2 10 °C 150 800MK2flowsetpoint 3 10 °C 150 800MK3flowsetpoint 4 10 °C 150 800Hotwater,setpoint 5 10 °C 150 800Release/block 6 1 0 2Heatingmode 7 1 0 4Hotwatermode 8 1 0 5MK2mode 9 1 0 4MK3mode 10 1 0 4Coolingmode 11 1 0 1Ventilationmode 12 1 0 3Swimmingpoolmode 13 1 0 4SmartGridcontrol 14 1 0 3Heatingcurve,heating,endpoint 15 10 °C 200 700Heatingcurve,heating,parallelshift 16 10 °C 50 350Heatingcurve,heating,endpointMK1 17 10 °C 200 700Heatingcurve,heating,parallelshiftMK1 18 10 °C 50 350Heatingcurve,heating,endpointMK2 19 10 °C 200 700Heatingcurve,heating,parallelshiftMK2 20 10 °C 50 350Heatingcurve,heating,endpointMK3 21 10 °C 200 700Heatingcurve,heating,parallelshiftMK3 22 10 °C 50 350Temperature,plus/minus 23 10 °C -50 50
27Subject to change without notice | 83055700cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
4.10 ConfigurationFor systems with software versions older than thestatesgivenforModBus/TCP,theconfigurationscreenisasfollows.TheGLTselectionisgreyedout,BACnetispreselectedandcanbeconfigured.
For a ModBus/TCP-compatible device the screenlookssomewhatdifferent:
NOTE.For ModBus TCP only the currently editedclient is displayed under "Devices found"as it isasingleconnection.Thedatapointsdisplayedon the right-handside correspondto all available registers via ModBus/TCP;however, it is not possible to query thenames,resolutionorunitviaModBus
ait-deutschland GmbHIndustriestraße 395359 Kasendorf, Germany
E [email protected] www.alpha-innotec.de
alpha innotec – an ait-deutschland GmbH brand