Operating InstructionsVEGACAL 644 … 20 mA/HART
Contents1 About this document
1.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . 41.3 Symbolism used . . . . . . . . . . . . . . . . . . . . . . . 4
2 For your safety2.1 Authorised personnel . . . . . . . . . . . . . . . . . . . . 52.2 Appropriate use. . . . . . . . . . . . . . . . . . . . . . . . 52.3 Warning about misuse . . . . . . . . . . . . . . . . . . . 52.4 General safety instructions . . . . . . . . . . . . . . . . 52.5 CE conformity . . . . . . . . . . . . . . . . . . . . . . . . . 52.6 Compatibility acc. to NAMUR NE 53. . . . . . . . . 52.7 Safety information for Ex areas. . . . . . . . . . . . . 62.8 Environmental instructions . . . . . . . . . . . . . . . . 6
3 Product description3.1 Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . 73.2 Principle of operation . . . . . . . . . . . . . . . . . . . . 73.3 Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.4 Storage and transport . . . . . . . . . . . . . . . . . . . 9
4 Mounting4.1 General instructions. . . . . . . . . . . . . . . . . . . . . 104.2 Mounting information . . . . . . . . . . . . . . . . . . . . 11
5 Connecting to power supply5.1 Preparing the connection . . . . . . . . . . . . . . . . . 145.2 Connection procedure . . . . . . . . . . . . . . . . . . . 155.3 Wiring plans, single chamber housing . . . . . . . . 165.4 Wiring plans, double chamber housing . . . . . . . 185.5 Wiring plans, double chamber housing Exd . . . . 205.6 Wiring plans, version IP 66/IP 68 (1 bar) . . . . . . 22
6 Setup with the indicating and adjustment modulePLICSCOM6.1 Short description . . . . . . . . . . . . . . . . . . . . . . . 236.2 Installing the indicating and adjustment module
PLICSCOM . . . . . . . . . . . . . . . . . . . . . . . . . . . 236.3 Adjustment system . . . . . . . . . . . . . . . . . . . . . 256.4 Setup procedure . . . . . . . . . . . . . . . . . . . . . . . 266.5 Menu schematic . . . . . . . . . . . . . . . . . . . . . . . 30
2 VEGACAL 64 - 4 … 20 mA/HART
Contents
30030-EN-050923
7 Setup with PACTware™7.1 Connecting the PC . . . . . . . . . . . . . . . . . . . . . 337.2 Parameter adjustment with PACTware™ . . . . . . 34
8 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 368.2 Fault rectification . . . . . . . . . . . . . . . . . . . . . . . 368.3 Exchanging the electronics. . . . . . . . . . . . . . . . 398.4 Instrument repair . . . . . . . . . . . . . . . . . . . . . . . 39
9 Dismounting9.1 Dismounting procedure . . . . . . . . . . . . . . . . . . 419.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
10 Supplement10.1 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . 4210.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 4810.3 Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . 5010.4 Industrial property rights. . . . . . . . . . . . . . . . . . 52
VEGACAL 64 - 4 … 20 mA/HART 3
Contents
3003
0-EN-
0509
23
1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation of VEGACAL 64.Please read this manual before you start setup.
1.2 Target groupThis operating instructions manual is directed to trainedpersonnel. The contents of this manual should be madeavailable to these personnel and put into practice by them.
1.3 Symbolism usedInformation, tip, noteThis symbol indicates helpful additional information.
Caution, warning, dangerThis symbol informs you of a dangerous situation that couldoccur. Ignoring this cautionary note can impair the person and/or the instrument.
Ex applicationsThis symbol indicates special instructions for Ex applications.
l ListThe dot set in front indicates a list with no implied sequence.
à ActionThis arrow indicates a single action.
1 SequenceNumbers set in front indicate successive steps in a procedure.
4 VEGACAL 64 - 4 … 20 mA/HART
About this document
30030-EN-050923
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained, specialised personnelauthorised by the operator. For safety and warranty reasons,any internal work on the instruments must be carried out onlyby personnel authorised by the manufacturer.
2.2 Appropriate useVEGACAL 64 is a sensor for continuous level measurement.
2.3 Warning about misuseInappropriate or incorrect use of the instrument can give rise toapplication-specific hazards, e.g. vessel overfill or damage tosystem components through incorrect mounting or adjustment.
2.4 General safety instructionsVEGACAL 64 is a high-tech instrument requiring the strictobservance of standard regulations and guidelines. The usermust take note of the safety instructions in this operatinginstructions manual, the country-specific installation standards(e.g. the VDE regulations in Germany) as well as all prevailingsafety regulations and accident prevention rules.
2.5 CE conformityVEGACAL 64 is in CE conformity with EMC (89/336/EWG) andNSR (73/23/EWG).Conformity has been judged acc. to the following standards:l EMC:
- Emission EN 61326: 2004 (class B)- Susceptibility EN 61326: 2004 incl. supplement A
l LVD: EN 61010-1: 2001
2.6 Compatibility acc. to NAMUR NE 53VEGACAL 64 meets NAMUR recommendation NE 53. VEGAinstruments are generally upward and downward compatible:l sensor software for DTM-VEGACAL 64 HART, PA or FFl DTM VEGACAL 64 for adjustment software PACTware™
VEGACAL 64 - 4 … 20 mA/HART 5
For your safety
3003
0-EN-
0509
23
l adjustment module PLICSCOM for sensor softwareThe parameter adjustment of the basic sensor functions isindependent of the software version. The range of availablefunctions depends on the respective software version of theindividual components.The software version of VEGACAL 64 can be determined asfollows:l via PACTware™l on the type label of the electronicsl via the adjustment module PLICSCOMOn our website www.vega.com you will find all softwarehistories. Make use of this convenience and get registered forupdate information via e-mail.
2.7 Safety information for Ex areasPlease note the Ex-specific safety information for installationand operation in Ex areas. These safety instructions are part ofthe operating instructions manual and come with the Ex-approved instruments.
2.8 Environmental instructionsProtection of the environment is one of our most importantduties. That is why we have introduced an environmentmanagement system with the goal of continuously improvingcompany environmental protection. The environment man-agement system is certified acc. to DIN EN ISO 14001.Please help us fulfil this obligation by observing the environ-mental instructions in this manual:l Chapter "Storage and transport"l Chapter "Disposal"
6 VEGACAL 64 - 4 … 20 mA/HART
For your safety
30030-EN-050923
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGACAL 64 level sensorl Documentation
- this operating instructions manual- Ex-specific safety instructions (with Ex versions) and, if
necessary, further certificates
VEGACAL 64 consists of the following components:l Process fitting with probel Housing with electronicsl Housing cover, optionally available with indicating and
adjustment module PLICSCOM
1
2
3
Fig. 1: VEGACAL 64 – rod version with plastic housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3 Process fitting
3.2 Principle of operationVEGACAL 64 is a level sensor with fully insulated probe forcontinuous level measurement.The electronics functions acc. to the admittance principle(phase-selective admittance processing).
Scope of delivery
Components
Area of application
VEGACAL 64 - 4 … 20 mA/HART 7
Product description
3003
0-EN-
0509
23
It is designed for industrial use in all areas of processtechnology and can be applied in all areas of industrial processmeasurement.Fully insulated probes such as VEGACAL 64 are preferablyused in conductive liquids.VEGACAL 64 is particularly suitable for adhesive, conductiveproducts.The probe, the measured product and the vessel wall form anelectrical capacitor. The capacitance is influenced by threemain factors:
1
2
3
Fig. 2: Functional principle - Plate capacitor1 Distance between the electrode surfaces2 Size of the electrode surfaces3 Type of dielectric between the electrodes
The probe and the vessel wall are the capacitor plates. Themeasured product and the insulation are the dielectric. Due tothe higher dielectric constant (DK value) of the insulation andthe conductive product compared to air, the capacitanceincreases as the product gradually covers the probe.The capacitance as well as the resistance change areconverted in the oscillator into a level-proportional signal.Two-wire electronics 4 … 20 mA/HART for power supply andmeasured value transmission on the same cable.The power supply range can differ depending on the instru-ment version. The exact range is stated in the "Technical data"in the "Supplement".
Physical principle
Power supply
8 VEGACAL 64 - 4 … 20 mA/HART
Product description
30030-EN-050923
3.3 AdjustmentVEGACAL 64 can be adjusted with four different adjustmentmedia:l the indicating and adjustment module PLICSCOMl with the suitable VEGA DTM in conjunction with an
adjustment software acc. to FDT/DTM standard, e.g.PACTware™ and PC
l with manufacturer-specific adjustment programs AMS™ orPDM
l a HART handheldThe entered parameters are generally saved in VEGACAL 64,optionally also in PLICSCOM or in PACTware™.
3.4 Storage and transportYour instrument was protected by packaging during transport.Its capacity to handle normal loads during transport is assuredby a test acc. to DIN EN 24180.The packaging of standard instruments consists of environ-ment-friendly, recyclable cardboard. For special versions, PEfoam or PE foil is also used. Dispose of the packaging materialvia specialised recycling companies.
l Storage and transport temperature see "Supplement –Technical data – Ambient conditions"
l Relative humidity 20 … 85 %
Packaging
Storage and transport tem-perature
VEGACAL 64 - 4 … 20 mA/HART 9
Product description
3003
0-EN-
0509
23
4 Mounting4.1 General instructionsSelect an installation position you can easily reach formounting and connecting as well as later retrofitting of anindicating and adjustment module. The housing can be rotatedby 330° without the use of any tools. You can also install theindicating and adjustment module in four different positions(each displaced by 90°).With screwed versions, the housing must not be used forscrewing in! Tightening can cause damages on the lockingpiston of the housing.To screw in, use the hexagon above the thread.Use the recommended cable (see chapter "Connecting topower supply") and tighten the cable gland.You can give your VEGACAL 64 additional protection againstmoisture penetration by leading the connection cable down-ward in front of the cable entry. Rain and condensation watercan thus drain off. This applies mainly to mounting outdoors, inareas where moisture is expected (e.g. by cleaning processes)or on cooled or heated vessels.
Fig. 3: Measures against moisture penetration
The process fitting must be sealed if there is gauge or lowpressure in the vessel. Before use, check if the seal material isresistant against the measured product.
Installation location
Handling
Moisture
Pressure/Vacuum
10 VEGACAL 64 - 4 … 20 mA/HART
Mounting
30030-EN-050923
Insulating measures, such as e.g. covering the thread withteflon tape, can interrupt the necessary electrical connectionwith metal vessels. For this reason, ground the probe on thevessel or use a conductive seal material.Metal vesselMake sure that the mechanical connection of the probe to thevessel is electrically conductive to ensure sufficient grounding.Use conductive seals such as e.g. copper or lead etc.Insulating measures, such as covering the thread with Teflontape, can interrupt the necessary electrical connection withmetal vessels. For this reason, ground the probe on the vesselor use a conductive seal material.Non-conductive vesselIn non-conductive vessels, e.g. plastic tanks, the second poleof the capacitor must be provided separately, e.g. in the formof a concentric tube.If possible, the capacitive probe should be mounted verticallyor parallel to the counter electrode. This applies particularly tonon-conductive products.In cylindrical tanks, spherical tanks or other asymmetrical tankforms, nonlinear level values are generated due to the varyingdistance to the vessel wall.Use a concentric tube in non-conductive products or linearizethe meas. signal.
4.2 Mounting informationDuring operation, the probe must not touch any installations orthe vessel wall. The measured value can also change if thedistance to the vessel wall changes considerably. If necessary,secure the end of the probe (insulated).
Vessel material
Vessel forms
Installation location
VEGACAL 64 - 4 … 20 mA/HART 11
Mounting
3003
0-EN-
0509
23
1
2
3
4
Fig. 4: Fasten the probe1 Probe2 Plastic sleeve
In vessels with conical bottom it can be advantageous tomount the sensor in the center of the vessel, as measurementis then possible down to the lowest point of the vessel bottom.If VEGACAL 64 is mounted in the filling stream, unwantedfaulty measurements may be generated. Mount VEGACAL 64at a location in the vessel where no disturbing influence from e.g. filling openings, agitators, etc. can occur.This applies to all instrument types with long probe.
Inflowing material
12 VEGACAL 64 - 4 … 20 mA/HART
Mounting
30030-EN-050923
Fig. 5: Inflowing material
VEGACAL 64 - 4 … 20 mA/HART 13
Mounting
3003
0-EN-
0509
23
5 Connecting to power supply5.1 Preparing the connectionAlways observe the following safety instructions:l Connect only in the complete absence of line voltagel If overvoltages are expected, overvoltage arresters should
be installed.Tip:We recommend VEGA overvoltage arresters ÜS-F-LB-I andÜSB 62-36G.X.
In hazardous areas you should take note of the appropriateregulations, conformity and type approval certificates of thesensors and power supply units.
Power supply and current signal are transmitted via the sametwo-wire connection cable. The power supply range can differdepending on the instrument version. The exact range isstated in the "Technical data" in the "Supplement".Provide a reliable separation between the supply circuit andthe mains circuits acc. to DIN VDE 0106 part 101. The VEGApower supply units VEGATRENN 149AEx, VEGASTAB 690,VEGADIS 371 as well as all VEGAMETs meet this require-ment.Bear in mind the following factors regarding supply voltage:l the reduction of the output voltage of the power supply unit
under nominal load (with a sensor current of 20.5 mA or22 mA in case of fault signal)
l the influence of additional instruments in the circuit (seeload values in "Technical data").
VEGACAL 64 is connected with standard two-wire cablewithout screen. An outer cable diameter of 5 … 9 mm ensuresthe seal effect of the cable entry. If strong electromagneticinterference is expected, we recommend the use of screenedcable.When using VEGACAL 64 with cable entry 1/2" NPT andplastic housing, a metal 1/2" threaded insert is moulded intothe plastic housing.
Caution:
Note safety instructions
Take note of safetyinstructions for Exapplications
Select power supply
Selecting the connection ca-ble
Cable entry 1/2" NPT
14 VEGACAL 64 - 4 … 20 mA/HART
Connecting to power supply
30030-EN-050923
No grease should be used when screwing the NPT cablegland or steel tube into the threaded insert. Standard greasecan contain additives affecting the connection betweenthreaded insert and housing. This will influence the stability ofthe connection and the tightness of the housing.
If screened cable is necessary, connect the cable screen onboth ends to ground potential. In the sensor, the screen mustbe connected directly to the internal ground terminal. Theground terminal outside on the housing must be connected tothe potential equalisation (low impedance).If potential equalisation currents are expected, the connectionon the evaluation side must be made via a ceramic capacitor(e.g. 1 nF, 1500 V). The low frequency potential equalisationcurrents are thus suppressed, but the protective effect againsthigh frequency interference signals remains.Take note of the corresponding installation regulations for Exapplications. In particular, make sure that no potential equal-isation currents flow over the cable screen. In case ofgrounding on both sides this can be achieved by the use of acapacitor or a separate potential equalisation.
5.2 Connection procedureProceed as follows:1 Unscrew the housing cover2 If an indicating and adjustment module is installed, remove
it by turning it slightly to the left.3 Loosen compression nut of the cable entry4 Remove approx. 10 cm (4 in) of the cable mantle, strip
approx. 1 cm (0.4 in) insulation from the ends of theindividual wires
5 Insert the cable into the sensor through the cable entry6 Lift the opening levers of the terminals with a screwdriver
(see following illustration)7 Insert the wire ends into the open terminals according to
the wiring plan
Cable screening and ground-ing
Select connectioncable for Ex applica-tions
VEGACAL 64 - 4 … 20 mA/HART 15
Connecting to power supply
3003
0-EN-
0509
23
Fig. 6: Connection steps 6 and 7
8 Press down the opening levers of the terminals, you willhear the terminal spring closing
9 Check the hold of the wires in the terminals by lightlypulling on them
10 Connect the screen to the internal ground terminal and theexternal ground terminal to potential equalisation
11 Tighten the compression nut of the cable entry, the sealring must completely encircle the cable
12 Screw the housing cover back onThe electrical connection is finished.
5.3 Wiring plans, single chamber housingThe following illustrations apply to the non-Ex as well as to theEEx ia version.
16 VEGACAL 64 - 4 … 20 mA/HART
Connecting to power supply
30030-EN-050923
1
444
2 3
Fig. 7: Material versions, single chamber housing1 Plastic2 Aluminium3 Stainless steel4 Filter element for pressure compensation or blind stopper with version IP 66/
IP 68, 1 bar
I2C
Display
1 2 5 6 7 8
3
4
1
2
Fig. 8: Electronics and connection compartment, single chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Spring-loaded terminals for connection of the external indication VEGADIS
613 Ground terminal for connection of the cable screen4 Spring-loaded terminals for power supply
Housing overview
Electronics and connectioncompartment
VEGACAL 64 - 4 … 20 mA/HART 17
Connecting to power supply
3003
0-EN-
0509
23
I2C
Display
1
1 2 5 6 7 8
Fig. 9: Wiring plan, single chamber housing1 Power supply/Signal output
5.4 Wiring plans, double chamber housingThe following illustrations apply to the non-Ex as well as to theEx ia version. The Exd version is described in the nextsubchapter.
1 2 3
4 5
Fig. 10: Double chamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12x1 for VEGADIS 61 (option)3 Housing cover, electronics compartment4 Filter element for pressure compensation or blind stopper with version IP 66/
IP 68, 1 bar1)5 Cable entry or plug
1) Version IP 66/IP 68, 1 bar not with four-wire instruments
Wiring plan
Housing overview
18 VEGACAL 64 - 4 … 20 mA/HART
Connecting to power supply
30030-EN-050923
1
3 2
Display
1 2 5 6 7 8
I2C
Fig. 11: Electronics compartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection cable to the connection compartment3 Terminals for VEGADIS 61
3
1
2
Display
1 2 I2C
Fig. 12: Connection compartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection of the cable screen3 Spring-loaded terminals for power supply
Electronics compartment
Connection compartment
VEGACAL 64 - 4 … 20 mA/HART 19
Connecting to power supply
3003
0-EN-
0509
23
I2C
1
1 2
Fig. 13: Wiring plan, double chamber housing1 Power supply/Signal output
5.5 Wiring plans, double chamber housing Exd
1 2 3
4 5
Fig. 14: Double chamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12x1 for VEGADIS 61 (option)3 Housing cover, electronics compartment4 Filter element for pressure compensation or blind stopper with version IP 66/
IP 68, 1 bar2)5 Cable entry or plug
2) Version IP 66/IP 68, 1 bar not with four-wire instruments
Wiring plan
Housing overview
20 VEGACAL 64 - 4 … 20 mA/HART
Connecting to power supply
30030-EN-050923
1
3 2
Display
1 2 5 6 7 8
I2C
Fig. 15: Electronics compartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection cable to the connection compartment3 Terminals for VEGADIS 61
1
2
1 2
Fig. 16: Connection compartment, double chamber housing Exd1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connection of the cable screen
Electronics compartment
Connection compartment
VEGACAL 64 - 4 … 20 mA/HART 21
Connecting to power supply
3003
0-EN-
0509
23
1
1 2
Fig. 17: Wiring plan, double chamber housing Exd1 Power supply/Signal output
5.6 Wiring plans, version IP 66/IP 68 (1 bar)
+
-1
2
Fig. 18: Wire assignment, connection cable1 br (+) and bl (–) for power supply or to the processing system2 Screen
Wiring plan
Wire assignment, connectioncable
22 VEGACAL 64 - 4 … 20 mA/HART
Connecting to power supply
30030-EN-050923
6 Setup with the indicating andadjustment module PLICSCOM
6.1 Short descriptionThe indicating and adjustment module PLICSCOM is used formeasured value display, adjustment and diagnosis. It can bemounted in the following housing versions and instruments:l All sensors of the plics® instrument family, in the single as
well as in the double chamber housing (optionally in theelectronics or connection compartment)
l External indicating and adjustment unit VEGADIS 61.Note:You will find detailed information on the adjustment in theoperating instructions manual of the indicating and adjustmentmodule PLICSCOM.
6.2 Installing the indicating and adjustmentmodule PLICSCOM
PLICSCOM can be inserted or removed at any time. It is notnecessary to interrupt the power supply.To mount, proceed as follows:1 Unscrew the housing cover2 Place PLICSCOM in the desired position on the electronics
(you can choose any one of four different positions - eachdisplaced by 90°)
3 Press PLICSCOM lightly onto the electronics and turn it tothe right until it snaps in.
4 Screw housing cover with inspection window tightly backon
Removal is carried out in reverse order.PLICSCOM is powered by the sensor, an additional con-nection is not necessary.
Function/Configuration
Insert/remove PLICSCOM
VEGACAL 64 - 4 … 20 mA/HART 23
Setup with the indicating and adjustment module PLICSCOM
3003
0-EN-
0509
23
Fig. 19: Installation of PLICSCOMNote:If you intend to retrofit VEGACAL 64 with a PLICSCOM forcontinuous measured value indication, a higher cover with aninspection glass is required.
24 VEGACAL 64 - 4 … 20 mA/HART
Setup with the indicating and adjustment module PLICSCOM
30030-EN-050923
6.3 Adjustment system
1.1
2
3
1
Fig. 20: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keys
l [OK] key:- move to the menu overview- confirm selected menu- edit parameter- save value
l [–>] key to select:- menu change- list entry- editing position
l [+] key:- modify value of a parameter
l [ESC] key:- interrupt input- jump to the next higher menu
The sensor is adjusted via the four keys of the indicating andadjustment module. The LC display indicates the individualmenu items. The functions of the individual keys are shown inthe above illustration. Approx. 10 minutes after the lastpressing of a key, an automatic reset to measured valueindication is triggered. Any values not confirmed with [OK] willnot be saved.
Key functions
Adjustment system
VEGACAL 64 - 4 … 20 mA/HART 25
Setup with the indicating and adjustment module PLICSCOM
3003
0-EN-
0509
23
6.4 Setup procedureAfter VEGACAL 64 is connected to power supply, theinstrument carries out a self-test for approx. 30 seconds. Thefollowing steps are carried out:l Internal check of the electronicsl Indication of the instrument type, the firmware version as
well as the sensor TAGs (sensor name)l Output signal jumps briefly (approx. 10 seconds) to the set
fault currentThen the actual measured value is displayed and thecorresponding current is transmitted to the cable.3)
In HART-Multidrop mode (several sensors on one input) theaddress must be set before continuing with the parameteradjustment. You will find a detailed description in the operatinginstructions manual of PLICSCOM or in the online help ofPACTware™ or DTM.
HART mode
StandardAddress 0
VEGACAL 64 measures the capacitance of the respectiveproduct. To display the actual level of the product, anallocation of the measured capacitance to the percentageheight must be carried out. For this adjustment, the capaci-tance is entered with emptied and filled vessel.If the vessel cannot be emptied or filled completely, you cancarry out the adjustment also with two known levels - forexample with 10 % and 90 %. The difference between theempty and full adjustment values should be as large aspossible.The actual level can then be calculated on the basis of thesesettings.VEGACAL 64 must be installed. A change of level isnecessary for this adjustment.In the main menu item "Basic adjustment", the individualsubmenu items should be selected one after the other andprovided with the correct parameter values.
3) The values correspond to the actual level as well as to the settings alreadycarried out, e.g. default setting.
Switch on phase
Address setting HART-Multi-drop
Parameter adjustment
26 VEGACAL 64 - 4 … 20 mA/HART
Setup with the indicating and adjustment module PLICSCOM
30030-EN-050923
Tip:If the indicating and adjustment module PLICSCOM remainson the probe as a display, we recommend saving the sensordata in PLICSCOM.Use the function "Copy sensor data".
Start your parameter adjustment with the following menu itemsof the basic adjustment:To be on the safe side, note the adjustment values for full andempty. If an adjustment procedure fails, it is not necessary toagain carry out a level change.These values can be helpful if the electronics has to beexchanged.
% ValueEmpty adjustmentFull adjustment
Tab. 2: Adjustment protocolTip:For min. adjustment the vessel should be as empty aspossible, and for max. adjustment, as full as possible. If thevessel is already full, start with max. adjustment.
Note:If possible, the vessel should be as empty as possible for min.adjustment.
Proceed as follows:1 Move from the measured value display to the main menu
by pushing [OK].▶ Basic adjustment
DisplayDiagnosticsServiceInfo
2 Select the menu item "Basic adjustment" with [–>] andconfirm with [OK]. Now the menu item "Min. adjustment" isdisplayed.
Carrying out min. adjustment
VEGACAL 64 - 4 … 20 mA/HART 27
Setup with the indicating and adjustment module PLICSCOM
3003
0-EN-
0509
23
Min. adjustment0.00 %=0.0 pF
54.5 pF
3 Prepare the adjustment value for editing with [OK].Move tothe selection window with [OK].
Min. adjustmentAccept current meas-
ured value?
accept?Edit?
4 Accept the current measured value or move to the editingwindow with "Edit". To edit, set the cursor to the requestedposition with [–>]. Set the requested % value with [+] andsave with [OK]. The cursor jumps to the capacitance value.
5 Enter the current capacitance value in pF (displayedbelow) for the empty vessel corresponding to the per-centage value.
6 Save the settings with [OK] and move to "Max. adjustment"with [–>].
Fill the vessel to the highest possible level.
Note:For max. adjustment, the vessel should be as full as possible.This will make the calibration more accurate.
Proceed as follows:Max. adjustment100.00 %=1000.0 pF
327.4 pF
1 Prepare the adjustment value for editing with [OK].Move tothe selection window with [OK].
Min. adjustmentAccept current meas-
ured value?
accept?Edit?
Carrying out max. adjustment
28 VEGACAL 64 - 4 … 20 mA/HART
Setup with the indicating and adjustment module PLICSCOM
30030-EN-050923
2 Accept the current measured value or move to the editingwindow with "Edit". To edit, set the cursor to the requestedposition with [–>]. Set the requested % value with [+] andsave with [OK]. The cursor jumps to the capacitance value.
3 Enter the current capacitance value in pF (displayedbelow) for the full vessel corresponding to the percentagevalue.
4 Save the settings with [OK].To suppress fluctuation in the measured value display, e.g.caused by a turbulent product surface, an integration time canbe set. This time can be between 0 and 999 seconds. Pleasenote that the reaction time of the entire measurement will belonger and the sensor will react to quick changes of themeasured value with a corresponding delay. In general, a timeof a few seconds is sufficient to smooth the measured valuedisplay.
Damping
0 s
Enter the requested parameter via the appropriate keys, saveyour settings and jump to the next menu item with the [–>] key.A linearization is necessary for all vessels in which the vesselvolume does not increase linearly with the level – e.g. in acylindrical or spherical tank -–and the indication or output ofthe volume is requested. Corresponding linearization curvesare preprogrammed for these vessels. They represent thecorrelation between the level percentage and vessel volume.By activating the appropriate curve, the volume percentage ofthe vessel is displayed correctly. If the volume should not bedisplayed in percent but e.g. in l or kg, a scaling can be alsoset in the menu item "Display".
Linearization curve
Linear
Enter the requested parameter via the appropriate keys, saveyour settings and jump to the next menu item with the [–>] key.
Damping
Linearization curve
VEGACAL 64 - 4 … 20 mA/HART 29
Setup with the indicating and adjustment module PLICSCOM
3003
0-EN-
0509
23
In this menu item you can enter an unambiguous designationfor the sensor, e.g. the measurement loop name or the tank orproduct designation. In digital systems and in the documen-tation of larger plants, a singular designation should be enteredfor exact identification of individual measuring sites.
Sensor-TAG
Sensor
With this menu item, the Basic adjustment is finished and youcan now jump to the main menu with the [ESC] key.Additional adjustment and diagnosis options such as e.g.scaling, simulation or trend curve presentation are shown inthe following menu schematic. You will find a detaileddescription of these menu items in the operating instructionsmanual of the indicating and adjustment module.
Sensor-TAG
Optional settings
30 VEGACAL 64 - 4 … 20 mA/HART
Setup with the indicating and adjustment module PLICSCOM
30030-EN-050923
6.5 Menu schematicBasic adjustment
1▶ Basic adjustmentDisplayDiagnosticsServiceInfo
1.1Min. adjustment0.00 %=0.0 pF82.5 pF
1.2Max. adjustment100.00 %=1000.0 pF327.4 pF
1.3Damping
0 s
1.4Linearization curve
Linear
1.5Sensor-TAG
Sensor
Display2Basic adjustment
▶ DisplayDiagnosticsServiceInfo
2.1Displayed value scaled 2.2UnitVolume
hl
2.3Scaling
0 % = 000.5 hl100 % = 005.0 hl
Diagnostics3Basic adjustment
Display▶ Diagnostics
ServiceInfo
3.1Peak values
Capacit. min: 65.7 pFCapacit. max: 782.4 pF
3.2Sensor status
OK
3.3Trend recording
Presentation of the out-put trend
VEGACAL 64 - 4 … 20 mA/HART 31
Setup with the indicating and adjustment module PLICSCOM
3003
0-EN-
0509
23
Service4Basic adjustment
DisplayDiagnostics
▶ ServiceInfo
4.1Current outputOutput mode: 4-20mAFailure mode: <3.6mAMin. current: 4mA
4.2Simulation
Start simulation?
4.3Reset
Reset?
4.4Language
Deutsch
4.5HART modeStandardAddress 0
4.6Copy sensor data
Copy from sensorCopy to sensor
4.7PIN
Enable?
Info5Basic adjustment
DisplayDiagnosticsService
▶ Info
5.1Sensor typeVEGACAL 6xSerial number12345678
5.2Date of manufacture04. February 2005Software version4.10/00
5.3Date of last change using PC
04. March 2005
5.4Sensor details
Display now?
32 VEGACAL 64 - 4 … 20 mA/HART
Setup with the indicating and adjustment module PLICSCOM
30030-EN-050923
7 Setup with PACTware™7.1 Connecting the PC
~
=
Power supply
VEGACONNECT 3
PACTware /TM
>PA<
2
3 1
Fig. 21: PC connected directly to the sensor1 RS232 connection2 VEGACAL 643 I²C adapter cable for VEGACONNECT 3
Necessary components:l VEGACAL 64l PC with PACTware™ and suitable VEGA-DTMl VEGACONNECT 3 with I²C adapter cable (article no.
2.27323)l Power supply unit
Connecting the PC directly tothe sensor
VEGACAL 64 - 4 … 20 mA/HART 33
Setup with PACTware™
3003
0-EN-
0509
23
2
3
1
4~
=
Power supply
VEGACONNECT 3
PACTware /TM
Fig. 22: Connecting the PC to the signal cable1 RS232 connection2 VEGACAL 643 HART adapter cable for VEGACONNECT 34 HART resistance 250 Ohm
Necessary components:l VEGACAL 64l PC with PACTware™ and suitable VEGA-DTMl VEGACONNECT 3 with HART adapter cable (art. no.
2.25397)l HART resistance approx. 250 Ohml Power supply unitNote:With power supply units with integrated HART resistor (innerresistor approx. 250 Ohm) there is no additional externalresistor necessary. This applies e.g. for VEGA instrumentsVEGATRENN 149A, VEGADIS 371, VEGAMET 381. Alsostandard Ex separators are normally equipped with a sufficientcurrent limitation resistor. In these cases, VEGACONNECT 3can connected in parallel to the 4 … 20 mA cable.
7.2 Parameter adjustment with PACTware™Further setup steps are described in the operating instructionsmanual "DTM Collection/PACTware™" attached to each CDand which can also be downloaded from our homepage. Adetailed description is available in the online help ofPACTware™ and the VEGA-DTMs.
Connecting the PC to thesignal cable
34 VEGACAL 64 - 4 … 20 mA/HART
Setup with PACTware™
30030-EN-050923
Note:Keep in mind that for setup of VEGACAL 64, DTM-Collection04/2005 or a newer version should be applied.All currently available VEGA-DTMs are provided in the DTMCollection on CD and can be obtained from the responsibleVEGA agency for a token fee. This CD includes also the up-to-date PACTware™ version. The basic version of this DTMCollection incl. PACTware™ is also available as a free-of-charge download from the Internet.
Move via www.vega.com and "Downloads" to the item"Software".
VEGACAL 64 - 4 … 20 mA/HART 35
Setup with PACTware™
3003
0-EN-
0509
23
8 Maintenance and fault rectification8.1 MaintenanceWhen used as directed in normal operation, VEGACAL 64 iscompletely maintenance-free.
8.2 Fault rectificationVEGACAL 64 offers maximum reliability. Nevertheless faultscan occur during operation. These may be caused by thefollowing, e.g.:l Sensorl Processl Power supplyl Signal processing.The first measures to be taken are to check the output signalas well as evaluate failure messages via the indicating andadjustmentmodule PLICSCOM. The procedure is described inthe following. Further comprehensive diagnostics options canbe carried out with a laptop with the software PACTware™ andthe suitable DTM. In many cases, the causes can bedetermined in this way and faults can be rectified.Should these measures not be successful, please call inurgent cases the VEGA service hotline under the phonenumber +49 1805 858550.The hotline is available to you 7 days a week round-the-clock.Since we offer this service world-wide, the support is onlyavailable in the English language. The service is free ofcharge, only the standard telephone costs will be charged.Connect a hand-held multimeter with a suitable measuringrange. For this, you have to disconnect the signal cable.? Current signal not stable
l level fluctuationsà set integration time via PLICSCOM or PACTware™
? Current signal missingl incorrect connection to power supplyà Check connection acc. to chapter "Connection proce-
Causes of malfunction
Fault rectification
24 hour service hotline
Checking the current signal
36 VEGACAL 64 - 4 … 20 mA/HART
Maintenance and fault rectification
30030-EN-050923
dure" and correct, if necessary, acc. to chapter "Wiringplans"
l no power supplyà check cables for line break, repair, if necessaryl supply voltage too low or load resistance too highà check and adapt, if necessary
? Current signal greater than 22 mA or less than 3.6 mAl Electronics module defectiveà Exchange instrument or return it for repair
In Ex applications, the regulations for the wiring of intrinsicallysafe circuits must be observed.
? E013l no measured value availableà Probe insulation damaged, short-circuit through pene-
trating, conductive mediumà Exchange instrument or return it for repairl shortcircuit in the probe, e.g. because of moisture in the
housingà remove the oscillator and check the resistance
between the marked plug connections acc. to thefollowing illustration
Error messages viaPLICSCOM
VEGACAL 64 - 4 … 20 mA/HART 37
Maintenance and fault rectification
3003
0-EN-
0509
23
1 2 3
Fig. 23: Check the resistance in the probe1 Screening2 Probe3 Ground potential
à there should be no contact between any of theterminals (high resistance)
à however, if there is somehow contact, exchangeinstrument or return it for repair
? E017l adjustment span too smallà Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
? E036l no operable sensor softwareà carry out a software update or return instrument for
repair
? E041/E042/E043l hardware error, electronics defectiveà Exchange instrument or return it for repair
38 VEGACAL 64 - 4 … 20 mA/HART
Maintenance and fault rectification
30030-EN-050923
8.3 Exchanging the electronicsIf the electronics module is defective, it can be replaced by theuser.In Ex applications, only instruments and electronics moduleswith appropriate Ex approval may be used.
If there is no electronics module available on site, it can beordered from the responsible VEGA agency.The order data of the sensor must be loaded into the newoscillator. This can be done either:l at the factory by VEGA personnell or on site by the user.In both cases, the sensor serial number is necessary. Theserial numbers are stated on the type label of the instrument oron the delivery note.
Information:When loading on site, the order data must be downloaded fromthe Internet (see Operating Instructions manual of theoscillator).
The oscillators are adapted to the respective sensor and differin their signal output or in their power supply. You can find asuitable oscillator in the following overview.The oscillators differ only in their signal output and are suitablefor all series 60 sensors.The following types are available:l CL-E60H (4 … 20 mA/HART)l CL-E60P (Profibus PA)l CL-E60F (Foundation Fieldbus)In Ex applications, only electronics with appropriate Exapproval must be used.
8.4 Instrument repairIf it is necessary to repair VEGACAL 64 please proceed asfollows:You can download a return form (23 KB) from our homepagewww.vega.com under: "Services – Downloads – Forms and
Sensor serial number
Assignment
VEGACAL 64 - 4 … 20 mA/HART 39
Maintenance and fault rectification
3003
0-EN-
0509
23
Certificates – Repair form".By doing this you help us carry out the repair quickly andwithout having to call back for needed information.l Print and fill out one form per instrumentl Clean the instrument and pack it damage-proofl Attach the completed form and possibly also a safety data
sheet to the instrument.l Send the instrument to the respective address of your
agency. In Germany to the VEGA headquarters inSchiltach.
40 VEGACAL 64 - 4 … 20 mA/HART
Maintenance and fault rectification
30030-EN-050923
9 Dismounting9.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high temperatures,corrosive or toxic products etc.
Take note of chapters "Mounting" and "Connecting to powersupply" and carry out the listed steps in reverse order.
9.2 DisposalVEGACAL 64 consists of materials which can be recycled byspecialised recycling companies. We have purposely de-signed the electronic modules to be easily separable.Mark theinstrument as scrap and dispose of it according to nationalgovernment regulations (e.g. in Germany acc. to electronicscrap ordinance).Materials: see "Technical data"If you cannot dispose of the instrument properly, pleasecontact us about disposal methods or return.
VEGACAL 64 - 4 … 20 mA/HART 41
Dismounting
3003
0-EN-
0509
23
10 Supplement10.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting – Thread 316L- Process fitting - Flange 316L- Process seal Klingersil C-4400- insulation (fully insulated) FEP- Probe (rod FEP fully insulated
ø16 mm/ø0.63 in)316L
Materials, non-wetted parts- Housing plastic PBT (Polyester), Alu-die casting pow-
der-coated, 316L- Seal ring between housing and
housing coverNBR (stainless steel housing), silicone (Alu/plastic housing)
- Ground terminal 316LWeights- with plastic housing 1150 g (40 oz)- with Aluminium housing 1600 g (56 oz)- with stainless steel housing 1950 g (69 oz)- Rod weight ø16 mm (ø0.63 in) 1100 g/m (12 oz/ft)Sensor length (L) 0.2 … 6 m (0.7 … 20 ft)Max. lateral load 10 Nm (7.4 lbf ft)Max. torque (process fitting thread) 100 Nm (73 lbf ft)
Output variableOutput signal 4 … 20 mA/HARTResolution 1.6 µAFault signal current output unchanged; 20.5 mA; 22 mA;
<3.6 mA (adjustable)Current limitation 22 mALoad see load diagram in Power supplyIntegration time (63 % of the inputvariable)
0 … 999 s, adjustable
Rise time 500 ms (ti: 0 s, 0 … 100 %)Fulfilled NAMUR recommendation NE 43
42 VEGACAL 64 - 4 … 20 mA/HART
Supplement
30030-EN-050923
Input variableParameter level of conductive, adhesive liquidsMeasuring principle phase-selective admittance processing (PSA)Measuring range 0 … 3000 pFFrequency 270 kHz
Accuracy (similar to DIN EN 60770-1)Reference conditions acc. to DIN EN 61298-1- Temperature 18 … +30°C (64 … +86°F)- Relative humidity 45 … 75 %- Atmospheric pressure 860 … 1060 mbar (86 … 106 kPa/
12.5 … 15.4 psi)Temperature error- <120 pF <1 pF- >120 pF 1 pF, +0.25 % of the current measured valueLinearity error <0.25 % of the complete measuring rangeAccuracy 0.025 % of the current measured value
Characteristic curve deviation and measurement characteristicsTemperature drift 0.06 %/10 K relating to the max. measuring
range
Ambient conditionsAmbient, storage and transport temperature- without PLICSCOM -40 … +80°C (-40 … +176°F)- with PLICSCOM -20 … +70°C (-4 … +158°F)
Process conditionsProcess pressure -1… 64 bar (-100… 6400 kPa/-14.5… 928 psi)Process temperature VEGACAL 64 of316L
-50 … +150°C (-58 … +302°F)
VEGACAL 64 - 4 … 20 mA/HART 43
Supplement
3003
0-EN-
0509
23
1
2
-50˚C(-58˚F)
50˚C(122˚F)
40˚C(104˚F)
-40˚C(-40˚F)
80˚C(176˚F)
0˚C(32˚F)
100˚C(212˚F)
150˚C(302˚F)
Fig. 24: Ambient temperature – Product temperature1 Product temperature2 Ambient temperature
Dielectric figure (DK value) >1.5
Electromechanical data – version IP 66/IP 67 and IP 66/IP 68, 0.2 barCable entry/plug 4)
- Single chamber housing l 1x cable entryM20x1.5 (cable-ø 5… 9mm),1x blind stopper M20x1.5
or:l 1x closing cap ½ NPT, 1x blind stopper
½ NPTor:l 1x plug depending on the version, 1x blind
stopper M20x1.5- Double chamber housing l 1x cable entryM20x1.5 (cable-ø 5… 9mm),
1x blind stopper M20x1.5, plug M12x1 forVEGADIS 61 (option)
or:l 1x closing cap ½ NPT, 1x blind stopper
½ NPT, plug M12x1 for VEGADIS 61(option)
or:l 1x plug (depending on the version), 1x blind
stopperM20x1.5, plugM12x1 for VEGADIS61 (option)
Spring-loaded terminals for wire cross sections up to 2.5 mm²
4) Depending on the version M12x1, acc. to DIN 43650, Harting, Amphenol-Tuchel, 7/8" FF
44 VEGACAL 64 - 4 … 20 mA/HART
Supplement
30030-EN-050923
Electromechanical data – version IP 66/IP 68, 1 barCable entry- Single chamber housing l 1x IP 68 cable entry M20x1.5; 1x blind
stopper M20x1.5or:l 1x closing cap ½ NPT, 1x blind stopper
½ NPT- Double chamber housing l 1x IP 68 cable entry M20x1.5; 1x blind
stopperM20x1.5; plugM12x1 for VEGADIS61 (option)
or:l 1x closing cap ½ NPT, 1x blind stopper
½ NPT, plug M12x1 for VEGADIS 61(option)
Connection cable- Configuration four cores, one suspension cable, one breather
capillary, screen braiding, foil, mantle- wire cross section 0.5 mm²- wire resistance <0.036 Ohm/m- tensile load >1.200 N (270 pounds force)- Standard length 5 m (16.4 ft)- max. length 1000 m (3280 ft)- Min. bending radius 25 mm (with 25°C/77°F)- Diameter approx. 8 mm- Colour – standard PE Black- Colour – standard PUR Blue- Colour – Ex version Blue
Indicating and adjustment modulePower supply and data transmission through sensor via gold-plated sliding contacts
(I²C bus)Indication LC display in full dot matrixAdjustment elements 4 keysProtection- unassembled IP 20- mounted into the sensor without
coverIP 40
VEGACAL 64 - 4 … 20 mA/HART 45
Supplement
3003
0-EN-
0509
23
Materials- Housing ABS- Inspection window Polyester foil
Supply voltageSupply voltage- non-Ex instrument 12 … 36 V DC- EEx ia instrument 12 … 30 V DC- EExd ia-Gerät 18 … 36 V DCPermissible residual ripple- <100 Hz Uss<1 V- 100 Hz … 10 kHz Uss <10 mVLoad see diagram
1000
750
500
250
12 181614 20 22 24 26 28 30 32 34 36
Ω
V
4
12
3
Fig. 25: Voltage diagram1 HART load2 Voltage limit EEx ia instrument3 Voltage limit non-Ex/Exd instrument4 Supply voltage
Electrical protective measuresProtection- Plastic housing IP 66/IP 67- Alu and stainless steel standard IP 66/IP 68 (0.2 bar)5)- Alu and stainless housing, optionally
availableIP 66/IP 68 (1 bar)
5) Requirement to maintain the protection is the suitable cable.
46 VEGACAL 64 - 4 … 20 mA/HART
Supplement
30030-EN-050923
Overvoltage category IIIProtection class II
Approvals6)
ATEX II 1G, 1/2G, 2G EEx ia IIC T6;ATEX II 1/2G, 2G EEx d ia IIC T67)
ATEX II 1/2D 2D IP6X T8)
WHGShip approvals
6) Deviating data with Ex applications: see separate safety instructions.7) Only in conjunction with Aluminium double chamber housing.8) Not in conjunction with plastic housing.
VEGACAL 64 - 4 … 20 mA/HART 47
Supplement
3003
0-EN-
0509
23
10.2 Dimensions
Housing in protection IP 66/IP 67 and IP 66/IP 68, 0.2 bar11
2mm
(4
13/ 3
2")
117m
m (
4 39
/ 64"
)
116m
m (
4 9 /
16")
120m
m (
4 23
/ 32"
)
~ 69mm(2 23/32") ø 77mm
(3 1/32")
~ 69mm(2 23/32") ~ 116mm (4 9/16")
~ 87mm (3 27/64")
ø 77mm(3 1/32") ø 84mm (3 5/16")
ø 84mm(3 5/16")
M20x1,5M20x1,5/½ NPT
M20x1,5/½ NPT
M20x1,5/½ NPT
M20x1,5/½ NPT
M16x1,5
1 2 3 4
Fig. 26: Housing versions in protection IP 66/IP 67 and IP 66/IP 68, 0.2 bar (with integrated PLICSCOM the housing heightincreases by 9 mm/0.35 in)1 Plastic housing2 Stainless steel housing3 Aluminium double chamber housing4 Aluminium housing
Housing in protection IP 66/IP 68, 1 bar
117m
m (
4 39
/ 64"
)
116m
m (
4 9 /
16")
120m
m (
4 23
/ 32"
)
~ 103mm(4 1/16") ~ 150mm (5 29/32")
~ 105mm (4 9/64")
ø 77mm(3 1/32") ø 84mm (3 5/16")
ø 84mm(3 5/16")
M20x1,5M20x1,5 M20x1,5
M20x1,5/½ NPT
M16x1,5
1 2 3
Fig. 27: Housing versions in protection IP 66/IP 68, 1 bar (with integrated PLICSCOM the housing height increases by9 mm/0.35 in)1 Stainless steel housing2 Aluminium double chamber housing3 Aluminium housing
48 VEGACAL 64 - 4 … 20 mA/HART
Supplement
30030-EN-050923
ø16mm (5/8")
L
G 3/4 A, G 1 A, G 11/2 A
56 m
m(2
1/ 4
")22
mm
(2 1
/ 4")
Fig. 28: VEGACAL 64 - Threaded version G1L = Sensor length, see Technical data
VEGACAL 64 - 4 … 20 mA/HART 49
Supplement
3003
0-EN-
0509
23
10.3 CertificatesCE declaration of conformity
Fig. 29: CE declaration of conformity
50 VEGACAL 64 - 4 … 20 mA/HART
Supplement
30030-EN-050923
Manufacturer declaration
Fig. 30: Manufacturer declaration
VEGACAL 64 - 4 … 20 mA/HART 51
Supplement
3003
0-EN-
0509
23
10.4 Industrial property rights
52 VEGACAL 64 - 4 … 20 mA/HART
Supplement
30030-EN-050923
VEGACAL 64 - 4 … 20 mA/HART 53
Supplement
3003
0-EN-
0509
23
54 VEGACAL 64 - 4 … 20 mA/HART
Supplement
30030-EN-050923
VEGACAL 64 - 4 … 20 mA/HART 55
Supplement
3003
0-EN-
0509
23
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected]
ISO 9001
All statements concerning scope of delivery, application,practical use and operating conditions of the sensors andprocessing systems correspond to the information avail-
able at the time of printing.© VEGA Grieshaber KG, Schiltach/Germany 2005
Technical data subject to alterations 30030-EN-050923