Operating InstructionsIndicating and adjustment module PLICSCOM

Contents1 About this document

1.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . 41.3 Symbolism used . . . . . . . . . . . . . . . . . . . . . . . 4

2 For your safety2.1 Authorised personnel . . . . . . . . . . . . . . . . . . . . 52.2 Appropriate use. . . . . . . . . . . . . . . . . . . . . . . . 52.3 Warning about misuse . . . . . . . . . . . . . . . . . . . 52.4 CE conformity . . . . . . . . . . . . . . . . . . . . . . . . . 52.5 Compatibility according to NAMUR NE 53. . . . . 52.6 Safety instructions for Ex areas . . . . . . . . . . . . 62.7 Functional range of approved instruments . . . . . 62.8 Environmental instructions . . . . . . . . . . . . . . . . 6

3 Product description3.1 Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . 73.2 Principle of operation . . . . . . . . . . . . . . . . . . . . 83.3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.4 Storage and transport . . . . . . . . . . . . . . . . . . . 9

4 Mounting4.1 Mounting steps . . . . . . . . . . . . . . . . . . . . . . . . 10

5 Setup5.1 Adjustment system . . . . . . . . . . . . . . . . . . . . . 115.2 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125.3 General functions . . . . . . . . . . . . . . . . . . . . . . 125.4 Functions - 4 … 20 mA/HART . . . . . . . . . . . . . 215.5 Functions - Profibus PA . . . . . . . . . . . . . . . . . . 235.6 Saving the parameter adjustment data . . . . . . . 265.7 Menu schematic for a 4 … 20 mA/HART sensor

(example: VEGAPULS 61) . . . . . . . . . . . . . . . . 275.8 Menu schematic for a Profibus PA sensor

(example: VEGAFLEX 61) . . . . . . . . . . . . . . . . 295.9 Menu schematic for a Foundation Fieldbus

sensor (example: VEGABAR 52) . . . . . . . . . . . 316 Maintenance and fault rectification

6.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 336.2 Instrument repair . . . . . . . . . . . . . . . . . . . . . . . 33

2 Indicating and adjustment module PLICSCOM

Contents

27835-EN-070123

7 Dismounting7.1 Dismounting steps . . . . . . . . . . . . . . . . . . . . . . 347.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

8 Supplement8.1 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . 358.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 368.3 Industrial property rights. . . . . . . . . . . . . . . . . . 378.4 Trademark . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Supplementary operating instructions manualsInformation:Depending on the selected version, supplementary instruc-tions manuals come with the shipment. You can find thesupplementary instructions manuals in chapter "Productdescription".

Indicating and adjustment module PLICSCOM 3

Contents

2783

5-EN-

0701

23

1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read thismanual before you start setup.

1.2 Target groupThis operating instructions manual is directed to trained,qualified personnel. The contents of this manual should bemade available to these personnel and put into practice bythem.

1.3 Symbolism usedInformation, tip, noteThis symbol indicates helpful additional information.

Caution: If this warning is ignored, faults ormalfunctions can result.Warning: If this warning is ignored, injury to persons and/orserious damage to the instrument can result.Danger: If this warning is ignored, serious injury to personsand/or destruction of the instrument can result.

Ex applicationsThis symbol indicates special instructions for Ex applications.

l ListThe dot set in front indicates a list with no implied sequence.

à ActionThis arrow indicates a single action.

1 SequenceNumbers set in front indicate successive steps in a procedure.

4 Indicating and adjustment module PLICSCOM

About this document

27835-EN-070123

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist personnelauthorised by the operator. For safety and warranty reasons,any internal work on the instruments must be carried out onlyby personnel authorised by the manufacturer.

2.2 Appropriate usePLICSCOM is a pluggable indicating and adjustment modulefor VEGA level and pressure sensors.

2.3 Warning about misuseInappropriate or incorrect use of the instrument can give rise toapplication-specific hazards, e.g. vessel overfill or damage tosystem components through incorrect mounting or adjustment.

2.4 General safety instructionsPLICSCOM is a high-tech instrument requiring the strictobservance of standard regulations and guidelines. The usermust take note of the safety instructions in this operatinginstructions manual, the country-specific installation standards(e.g. the VDE regulations in Germany) as well as all prevailingsafety regulations and accident prevention rules.

2.5 CE conformityThe indicating and adjustment module is in CE conformity toEMC (89/336/EWG) and NSR (73/23/EWG).Conformity has been judged according to the followingstandards:l EMC:

- Emission EN 61326: 1997- Susceptibility EN 61326: 1997 + A1:1998

l LVD: EN 61010-1: 2001

2.6 Compatibility according to NAMUR NE 53PLICSCOM meets NAMUR recommendation NE 53.

Indicating and adjustment module PLICSCOM 5

For your safety

2783

5-EN-

0701

23

The parameter adjustment of the basic sensor functions isindependent of the software version. The range of availablefunctions depends on the respective software version of theindividual components.You can view all software histories on our website www.vega.com.Make use of this advantage and get registered for updateinformation via e-mail.

2.7 Safety instructions for Ex areasPlease note the Ex-specific safety information for installationand operation in Ex areas. These safety instructions are part ofthe operating instructions manual and come with the Ex-approved instruments.

2.8 Functional range of approved instrumentsInstruments with national approvals such as according to FMor CSA are partly supplied with a previous hardware orsoftware version. For approval-technical reasons, somefunctions for these instruments will be only available at a laterdate.You will find corresponding instructions in the description ofthe individual functions in this operating instructions manual.

2.9 Environmental instructionsProtection of the environment is one of our most importantduties. That is why we have introduced an environmentmanagement system with the goal of continuously improvingcompany environmental protection. The environment man-agement system is certified according to DIN EN ISO 14001.Please help us fulfil this obligation by observing the environ-mental instructions in this manual:l Chapter "Storage and transport"l Chapter "Disposal"

6 Indicating and adjustment module PLICSCOM

For your safety

27835-EN-070123

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l Indicating and adjustment modulel Documentation

- this operating instructions manual- Supplementary instructions manual "Heating for indi-

cating and adjustment module" (optional)

The indicating and adjustment module is equipped with adisplay with full dot matrix as well as four keys for adjustment.Depending on the respective version of the indicating andadjustment module as well as the sensor electronics, anintegrated background lighting can be switched on via theadjustment menu.The display can be optionally equipped with heating to ensuregood readability at low temperatures down to -40°C (-40°F).

1

2

Fig. 1: Indicating and adjustment module1 Indication2 Keys

Scope of delivery

Equipment

Indicating and adjustment module PLICSCOM 7

Product description

2783

5-EN-

0701

23

1

2

Fig. 2: Rear of the indicating/adjustment module1 Integrated seal ring2 Gold plated contact paths

3.2 Principle of operationThe indicating and adjustment module is used for measuredvalue indication, adjustment, and diagnostics for the followingVEGA plics® sensors:l VEGAPULS series 60l VEGAFLEX series 60l VEGASON series 60l VEGABAR series 50 and 60l VEGACAL series 60The indicating and adjustment module is integrated in therespective sensor housing or in the external indicating andadjustment unit VEGADIS 61. After mounting, the sensor andthe indicating and adjustment module are splash-proof alsowithout housing cover.The operation of two indicating and adjustment modules inparallel in the sensor and in VEGADIS 61 is not supported.Power is supplied directly by the respective sensor or byVEGADIS 61. An additional connection is not necessary.The backlight is also powered by the sensor or via VEGADIS61. Prerequisite for this is a supply voltage at a certain level.The exact voltage specifications can be found in the operatinginstructions manual of the respective sensor.

Area of application

Supply

8 Indicating and adjustment module PLICSCOM

Product description

27835-EN-070123

For instruments with national approvals such as e.g. accordingto FM and CSA, this function only available at a later date.The optional heating requires its own power supply. You canfind further details in the supplementary instructions manual"Heating for indicating and adjustment module".

3.3 OperationThe adjustment is carried out via the integrated keys. Theentered parameters are generally saved in the respectivesensor. A copy function enables loading of the parameters intothe indicating and adjustment module.

3.4 Storage and transportYour instrument was protected by packaging during transport.Its capacity to handle normal loads during transport is assuredby a test according to DIN EN 24180.The packaging of standard instruments consists of environ-ment-friendly, recyclable cardboard. For special versions, PEfoam or PE foil is also used. Dispose of the packaging materialvia specialised recycling companies.

l Storage and transport temperature see "Supplement -Technical data - Ambient conditions"

l Relative humidity 20 … 85 %

Packaging

Storage and transport tem-perature

Indicating and adjustment module PLICSCOM 9

Product description

2783

5-EN-

0701

23

4 Mounting4.1 Mounting stepsPLICSCOM can be mounted or dismounted at any time. It isnot necessary to interrupt the power supply.To mount, proceed as follows:1 Unscrew the housing cover2 Place PLICSCOM in the required position to the electronicsInformation:Four different positions are possible, each displaced by 90°.

Fig. 3: Installation of PLICSCOM

3 Press PLICSCOM lightly onto the electronics and turn it tothe right until it snaps in

4 Screw housing cover with inspection window tightly backon

Note:If you intend to retrofit the sensor with an indicating andadjustment module for continuous measured value indication,a higher cover with an inspection glass is required.

Dismounting is carried out in reverse order.

Insert/remove PLICSCOM

10 Indicating and adjustment module PLICSCOM

Mounting

27835-EN-070123

5 Setup5.1 Adjustment system

1.1

2

3

1

Fig. 4: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keys

l [OK] key:- move to the menu overview- confirm selected menu- edit parameter- save value

l [->] key to select:- menu change- list entry- Select editing position

l [+] key:- Change value of a parameter

l [ESC] key:- interrupt input- jump to the next higher menu

The sensor is adjusted via the four keys of the indicating andadjustment module. The LC display indicates the individualmenu items. The functions of the individual keys are shown inthe above illustration. Approx. 10 minutes after the lastpressing of a key, an automatic reset to measured value

Key functions

Adjustment system

Indicating and adjustment module PLICSCOM 11

Setup

2783

5-EN-

0701

23

indication is triggered. Any values not confirmed with [OK] willnot be saved.

5.2 OverviewContinuously measuring sensors for level and pressure havevarious functions. Hence they can be adapted in an optimumway to the respective application. The functions are structuredin a clear menu form (see section "Menu schematics").The following functions are described in this operatinginstructions manual:l General functionsl Functions for 4 … 20 mA/HARTl Functions for Profibus PAl Functions for Foundation FieldbusFurther, sensor-specific functions are described in theoperating instructions manual of the respective sensor.

5.3 General functionsThe general functions are described in this paragraph. Thefunctions of the indicating/adjustment module are determinedby the sensor and correspond to the respective softwareversion of the sensor.

Information:The respective menu item number differs depending on thesensor type and signal output.

The following presentations are available in the measuredvalue display:l Level as digital value, sensor TAGl Level as digital value and bar graph, sensor TAGl Only with pressure transmitters: Level or pressure as

digital value, temperature valueWith [->] you select the different presentations of themeasured value. You can reach the menu overview from anypresentation with [OK]. With [ESC] you return from the menuoverview to the measured value display.In the menu overview you select the appropriate menu with [->]and open it with [OK]. Then the individual menu items areavailable.

Measured value indication

Menu overview

12 Indicating and adjustment module PLICSCOM

Setup

27835-EN-070123

▶ Basic adjustment 1IndicationDiagnosticsServiceInfo

Menu section, basic adjustmentTo damp process-dependent measured value fluctuations, youhave to set an integration time of 0 … 999 s in this menu item.Depending on the sensor type, the factory setting is 0 s or 1 s.

Damping

0 s

In this menu item you select the linearization curve:l linearl Cylindrical tankl Spherical tankl User programmableUser programmable means: Switching on a linearization curveprogrammed via PC and PACTware™A linearization is necessary for all vessels in which the vesselvolume does not increase linearly with the level - e.g. with acylindrical or spherical tank - and the indication or output of thevolume is required. Corresponding linearization curves arepreprogrammed for these vessels. They represent thecorrelation between the level percentage and vessel volume.The linearization applies to the measured value indication andthe current output.By activating the appropriate curve, thevolume percentage of the vessel is displayed correctly. If thevolume should not be displayed in percent but e.g. in l or kg, ascaling can be also set in the menu item "Display".Factory setting is linear.

Linearisation curve

linear

Caution:Note the following, if the respective sensor is used as part ofan overfill protection system according to WHG:

Damping

Linearisation curve

Indicating and adjustment module PLICSCOM 13

Setup

2783

5-EN-

0701

23

If a linearisation curve is selected, the measuring signal is nolonger compulsorily linear proportional to the level. This mustbe taken into consideration by the user, particularly whenadjusting the switching point on the level switch.

In the menu item "Sensor-TAG" you can edit a twelve-digitmeasurement loop name. An unambiguous designation can bethus assigned to the sensor, e.g. the measurement loop nameor the tank or product designation. In digital systems and in thedocumentation of larger plants, a singular designation shouldbe entered for exact identification of individual measuringsites.The characters comprise:l Letters from A … Zl Numbers from 0 … 9l Special characters +, -, /, -Factory setting is "Sensor".

Sensor-TAG

Sensor

Menu section, displayAn integrated background lighting can be switched via theadjustment menu. The following version is necessary:l Indicating and adjustment module …- 01 or higherl Sensor electronics 4 … 20 mA …- 01 or higherl Sensor electronics pressure transmitter 4 … 20 mA …- 02

or higherl Sensor electronics Profibus PA or Foundation Fieldbus …-

03 or higherThe version is stated on the type label of the indicating andadjustment module or the sensor electronics. The functiondepends also on the height of the supply voltage, seeoperating instructions manual of the respective sensor.

Information:For instruments with national approvals such as e.g. accordingto FM and CSA, this function only available at a later date.

In the default setting, the lightning is deactivated.

Edit sensor TAG

Lighting

14 Indicating and adjustment module PLICSCOM

Setup

27835-EN-070123

Menu section, diagnosticsMin. and max. measured values are saved in the sensor. Thevalues are displayed in the menu item "Peak values".l Min. and max. distance in m(d): Radar, guided microwave,

ultrasonic sensorsl Min. and max. pressure: pressure transmitter1)l Min. and max. temperature: ultrasonic sensors, pressure

transmittersPointer

When non-contact level sensors are used, the measurementcan be influenced by the respective process conditions. In thismenu item, the measurement reliability of the level echo isdisplayed as dB value. The measurement reliability equalssignal strength minus noise. The higher the value, the morereliable the measurement.In this menu item, the device status is displayed. If the sensordetects a fault, "OK" will be displayed. If a fault is detected, aflashing failure message is outputted sensor-specifically, e.g."E013". The fault is also displayed in clear text, e.g. "Nomeasurement value".

Information:The fault message as well as the clear text indication are alsocarried out in the measured value display.

Meas. reliability

Sensor status

With ultrasonic and radar sensors as well as sensors withguided microwave, the "Echo curve" represents the signalstrength of the echoes over the measuring range. The units ofthe signal strength are "dB" (ultrasonic and radar) and "Volt"(guided microwave). The signal strength enables the assess-ment of the quality of the measurement.

1) Pressure: -50 … +150 % of the nominal pressure range; temperature:-50 … +150 °C.

Pointer

Meas. reliability

Sensor status

Curve selection

Indicating and adjustment module PLICSCOM 15

Setup

2783

5-EN-

0701

23

With ultrasonic and radar sensors, the "False echo curve"represents the saved false echoes (see menu "Service") of theempty vessel with signal strength in "dB" over the measuringrange.With all plics® sensors, up to 3000 measured values(depending on the sensor) are recorded when starting a"Trend curve". Then the values can be displayed over atimeline. The oldest measured values are always deleted.In the menu item "Choose curve", the respective curve isselected.

Curve selection

Echo curve ▼

Information:The trend recording is not activated when being shipped. Itmust be started by the user via the menu item "Start trendcurve".

A comparison of echo and false echo curve allows a moredetailled specification on the measurement reliability. Theselected curve is updated permanently. With the [OK] key, asubmenu with zoom functions is opened.The following functions are available with "Echo and falseecho curve":l "X-Zoom": Zoom function for the meas. distancel "Y-Zoom": 1, 2, 5 and 10-times signal magnification in "dB"l "Unzoom": Reset the presentation to the nominal measur-

ing range with single magnificationIn the menu item "Trend curve" the following are available:l "X-Zoom": Resolution

- 1 minute- 1 hour- 1 day

l "Stop/Start": Interrupt a recording or start a new recordingl "Unzoom": Reset the resolution to minutesAs default setting, the recording pattern has 1 minute. With theadjustment software PACTware™, this pattern can be also setto 1 hour or 1 day.

Curve presentation

16 Indicating and adjustment module PLICSCOM

Setup

27835-EN-070123

Echo curve

Menu section, serviceIn this menu item you simulate a user-defined level or pressurevalue via the current output. This allows you to test the signalpath, e.g. through connected indicating instruments or theinput card of the control system.The following simulation variables are available:l Percentl Currentl Pressure (with pressure transmitters)l Distance (with radar and guided microwave)With Profibus PA sensors, the selection of the simulated valueis made via the "Channel" in the menu "Basic adjustments".How to start the simulation:1 Push [OK]2 Select the requested simulation variable with [->] and

confirm with [OK]3 Set the requested value with [+] and [->].4 Push [OK]The simulation is now running, with 4 … 20 mA/HART acurrent is outputted and with Profibus PA or FoundationFieldbus a digital value.How to interrupt the simulation:à Push [ESC]Information:The simulation is terminated automatically 10 minutes after thelast key has been pushed.

Simulation

Start simulation?

With the reset function, modified values are reset. Threesubfunctions are available:l Basic adjustment

Simulation of meas-ured values

Reset

Indicating and adjustment module PLICSCOM 17

Setup

2783

5-EN-

0701

23

- Reset the values modified with the indicating andadjustment module to the sensor-specific basic setting

l Factory setting- As basic adjustment, but also reset of special

parameters to the default values2)l Peak values measured value and temperature3)

- Reset of the min./max. values of pressure, level andtemperature to the current values

Information:Because the reset values are nearly sensor-specifc, they arelisted in the operating instructions manual of the respectivesensor.

Reset

Reset?

In this menu item you select the internal arithmetic unit of thesensor.With radar, guided microwave and ultrasonic sensors this ism(d) or ft(d).For pressure transmitters more comprehensive units areavailable. They are described in the operating instructionsmanual of the respective sensor in the menu "Basic adjust-ments".

Unit of measurement

m(d)

The sensor is already set to the ordered national language. Inthis menu item you can change the language. The followinglanguages are available:l Deutschl Englishl Françaisl Espanõl

2) Special parameters are parameters which are set customer-specifically onthe service level with the adjustment software PACTware™.

3) Temperature only with pressure transmitters and ultrasonic sensors.

Unit of measurement

Language

18 Indicating and adjustment module PLICSCOM

Setup

27835-EN-070123

l Pycckuul Japanesel Chinese

Language

Deutsch

With this functionl Load parameter adjustment data from the sensor into the

indicating and adjustment modulel Write parameter adjustment data from the indicating and

adjustment module into the sensorThe data are permanently saved in an EEPROM memory inthe indicating and adjustment module and remain there even incase of power failure. From there, they can be written in one orseveral sensors or kept as backup for a probable sensorexchange.Kind and volume of the copied data depend on the respectivesensor.

Information:Before writing the data into the sensor, it is checked if the datafit the sensor. If data do not fit, a fault signal is triggered or thefunction is blocked. When writing data into the sensor, you willsee from which instrument type the data originate and whichTAG-no. this sensor had.

The following items are checked:l Software versionl WHG approvall SIL activatedl Measuring principlel Radar C-band/K-bandl Radar measuring range <30 m or >30 ml Signal outputl Pressure measuring range

Copy sensor data

Copy sensor data?

Copy sensor data

Indicating and adjustment module PLICSCOM 19

Setup

2783

5-EN-

0701

23

In this menu item, the PIN is activated/deactivated perma-nently. Entering a 4-digit PIN protects the sensor data againstunauthorized access and unintentional modifications. If the PINis activated permanently, it can be deactivated temporarily (i.e.for approx. 60 min.) in any menu item. The instrument isdelivered with the PIN set to 0000.

PIN

Disable permanently?

Only the following functions are permitted with activated PIN:l Select menu items and show datal Read data from the sensor into the indicating/adjustment

module.Menu section, infoIn this menu item the most important sensor information can bedisplayed:l Sensor typel Serial number: 8-digit number, e.g. 12345678

Sensor typeMaihakPULS 400

Serial number12345678

l Date of manufacture: Date of the factory calibration, e.g.16. March 2006

l Software version: Edition of the sensor software, e.g. 3.32Date of manufacture14. December 2005Software version3.30

l Date of last change using PC: Date of the last change ofsensor parameters via PC, e.g. 16. March 2006

Last change using PC

14. December 2005

l Sensor details, e.g. approval, process fitting, seal, meas-uring cell, measuring range, electronics, housing, cableentry, plug, cable length etc.

PIN

Info

20 Indicating and adjustment module PLICSCOM

Setup

27835-EN-070123

Sensor characteristics

Display now?

5.4 Functions - 4 … 20 mA/HARTThe 4 … 20 mA/HART special functions are briefly describedin this paragraph. The respective range of functions of theindicating and adjustment module is determined by the sensorand the sensor software revision.In the menu item "Display" you can define how the measuredvalue should be presented on the display.The following indication values are available:l Heightl Pressure (only with pressure transmitters)l Distance (only with radar, guided microwave, ultrasonics)l Currentl Scaledl Percentl Lin. percentl Temperature (only with pressure transmitters).The selection "scaled" opens the menu items "Display unit"and "Scaling". In "Display unit" there are the following options:l Heightl Massl Flowl Volumel Without unitDepending on selection, the different units are in turnavailable.In the menu item "Scaling", the requested numerical value withdecimal point is entered for 0 % and 100 % of the measuredvalue.There is the following relation between the indication value inthe menu "Display" and the adjustment unit in the menu "Basicadjustment":l With radar, guided microwave and ultrasonics, displayed

value "Distance" means: presentation of the measuredvalue in the selected adjustment unit, e.g. m(d)

Introduction

Indication

Indicating and adjustment module PLICSCOM 21

Setup

2783

5-EN-

0701

23

l With pressure, displayed value "Pressure" or "Height"means: presentation of the measured value in the selectedadjustment unit, e.g. bar or m.

Displayed value

Scaled ▼

Anzeigeeinheit

Volumen▼l ▼

Scaling

0 % = 0.0 l100 % = 100.0 l

Menu section, serviceIn the menu item "Current output" you determine the behaviourof the current output during operation and in case of failure.The following options are available:Current outputOutput mode 4 … 20 mA

20 … 4 mAFailure mode4) Hold value

20.5 mA22 mA<3.6 mA

Min. current5) 3.8 mA4 mA

Max. current6) 20 mA20.5 mA

The values in bold font represent the data of the factory setting.In HART multidrop mode, the current is constantly 4 mA. Thisvalue does not change even in case of failure.

4) Value of the current output in case of failure, e.g. if no valid measured valueis delivered.

5) This value is not underrun during operation.6) This value is not exceeded during operation.

Current output

22 Indicating and adjustment module PLICSCOM

Setup

27835-EN-070123

Current output

Output mode: 4-20 mA ▼Failure mode: 22 mA ▼Min. current 3.8 mA ▼

Certain sensors are suitable for use according to IEC 61508.For this use, you have to activate the menu item "SIL". Thisinfluences the following menu items:l Menu items "Current output" in "Failure mode", "Hold

value" and "20.5 mA" blockedl "HART mode", "Multidrop" blockedThe default setting for "SIL" is "deactivated".

Note:For such applications, take note of "Safety Manual".

HART offers standard and multidrop modeThe mode standard with the fixed address 0 means output ofthe measured value as 4 … 20 mA signal.In Multidrop mode, up to 15 sensors can be operated on onetwo-wire cable. An address between 1 and 126 must beassigned to each sensor.7)In this menu item you determine the HARTmode and enter theaddress for multidrop.

HART mode

StandardAddress 0

The default setting is standard with address 0.

5.5 Functions - Profibus PAThe Profibus PA special functions are briefly described in thisparagraph. The respective range of functions of the indicatingand adjustment module is determined by the sensor and thesensor software revision.

7) The 4 … 20 mA signal of the HART sensor is switched off. The sensorconsumes a constant current of 4 mA. The measuring signal is transmittedexclusively as digital HART signal.

Functional safety (SIL)

HART mode

Introduction

Indicating and adjustment module PLICSCOM 23

Setup

2783

5-EN-

0701

23

Menu section, basic adjustmentLevel and pressure sensors operate as slaves on the ProfibusPA. To be identified as a bus participant, each sensor musthave a unique address. Each instrument is delivered withaddress 126. With this address, it can at first be connected toan existing bus. However, the address must be changed. Thiscan be done in this menu item.

Sensor address

126

The channel is the input selector switch for function block (FB)of the sensor. Within the function block, additional scalings(Out-Scale) are carried out. In this menu item, the value fir thefunction block is selected:l SV1 (Secondary Value 1):

- Percent with radar, guided microwave and ultrasonicsensors

- Pressure or height with pressure transmittersl SV2 (Secondary Value 2):

- Distance with radar, guided microwave and ultrasonicsensors

- Percent with pressure transmittersl PV (Primary Value):

- Linearised percentage valueChannel

PV lin. value

Menu section, displayRadar, guided microwave and ultrasonic sensors deliver thefollowing measured values:l SV1 (Secondary Value 1): Percentage value after the

adjustmentl SV2 (Secondary Value 2): Distance value before the

adjustmentl PV (Primary Value): Linearised percentage valuel PA-Out (value after passing the function block): PA outputA pressure transmitter delivers the following measured values:

Sensor address

Channel

Indication

24 Indicating and adjustment module PLICSCOM

Setup

27835-EN-070123

l SV1 (Secondary Value 1): Pressure or height value beforeadjustment

l SV2 (Secondary Value 2): Percentage value after theadjustment

l PV (Primary Value): Linearised percentage valuel PA-Out (value after passing the function block): PA outputl TemperatureIn the menu item "Display" you can define which measuredvalue should be presented on the display.

Displayed value

PA-Out

Menu section, serviceProfibus transmits two values cyclically. The first value isdetermined in the menu item "Channel". The selection of theadditional cyclical value is made in the menu item "AdditionalPA value".Radar, guided microwave and ultrasonic sensors deliver thefollowing measured values:l SV1 (Secondary Value 1): Percentage value after the

adjustmentl SV2 (Secondary Value 2): Distance value before the

adjustmentl PV (Primary Value): Linearised percentage valueWith pressure transmitters the following values are available:l SV1 (Secondary Value 1): Pressure or height value before

adjustmentl SV2 (Secondary Value 2): Percentage value after the

adjustmentl PV (Primary Value): Linearised percentage value

Additional PA value

Here, you determine the unit and scaling for PA-Out. Thesesettings also apply to the values displayed on the indicatingand adjustment module if in the menu item "Displayed value"PA-Out was selected.

Additional PA value

Determine Out-Scale

Indicating and adjustment module PLICSCOM 25

Setup

2783

5-EN-

0701

23

The following displayed values are available in "Out-Scaleunit":l Pressure (only with pressure transmitters)l Heightl Massl Flowl Volumel Others (no unit, %, mA)In the menu item "PV-Out-Scale", the requested numericalvalue with decimal point is entered for 0 % and 100 % of themeasured value.

Out-Scale-Unit

PV-Out-Scale

5.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in thisoperating instructions manual and archive them afterwards.They are hence available for multiple use or service purposes.Alternatively the data can be loaded from the sensor into theindicating and adjustment module. The procedure is describedin the menu item "Copy sensor data". The data remain thereeven the power supply fails.If it is necessary to exchange the sensor, the indicating andadjustment module is inserted into the replacement instrumentand the data are written into the sensor under the menu item"Copy sensor data".

26 Indicating and adjustment module PLICSCOM

Setup

27835-EN-070123

5.7 Menu schematic for a 4 … 20 mA/HART sensor(example: VEGAPULS 61)

Information:Depending on the version and application, the highlightedmenu windows are not always available.

Basic adjustment1▶ Basic adjustment

IndicationDiagnosticsServiceInfo

1.1Min. adjustment0.00 %=10,000 m(d)

8,000 m(d)

1.2Min. adjustment100.00 %=1,000 m(d)

2,000 m(d)

1.3MediumLiquidWater based(DK>10)

1.4Vessel form

Storage tank

1.5Damping

0 s

1.6Linearisation curve

linear

1.7Sensor-TAG

Sensor

Indication2Basic adjustment

▶ IndicationDiagnosticsServiceInfo

2.1Displayed value

Scaled

2.2Display unit

Volumem³

2.3Scaling

0 % = 0,0 m³100 % = 100 m³

2.4Lighting

Switched off▼

Diagnostics3Basic adjustment

Indication▶ Diagnostics

ServiceInfo

Indicating and adjustment module PLICSCOM 27

Setup

2783

5-EN-

0701

23

3.1Pointer

Distance min.: 0.234 m(d)Distance max.: 5.385 m(d)

3.2Meas. reliability8 db

Sensor statusOK

3.3Curve selection

Echo curve

3.4Echo curve

Presentation of the echocurve

Service4Basic adjustment

IndicationDiagnostics

▶ ServiceInfo

4.1Gating out of false signals

Jetzt ändern?

4.2Extended setting

None

4.3Current outputOutput mode: 4-20 mAFail.mode: <3.6 mAmin. current: 4 mAmin. current: 4 mA

4.4Simulation

Start simulation? ▼

4.6Reset

Reset?

4.7Unit of measurement

m(d)▼select?

4.8Language

Deutsch ▼4.9SIL

Not activated▼

4.10HART mode

StandardAddress 0

4.11Copy sensor data

Copy sensor data?

4.12PIN

Enable?

Info5Basic adjustment

IndicationDiagnosticsService

▶ Info

5.1Sensor typeVEGAPULS 6x

Serial number12345678

5.2Date of manufacture15. December 2006Software version3.32

5.3Last change using PC

15. December 2006

5.4Sensor characteristics

Display now?

Setup

28 Indicating and adjustment module PLICSCOM

27835-EN-070123

5.8 Menu schematic for a Profibus PA sensor(example: VEGAFLEX 61)

Information:Depending on the version and application, the highlightedmenu windows are not always available.

Basic adjustment1▶ Basic adjustment

IndicationDiagnosticsServiceInfo

1.1Sensor address

000

1.2Min. adjustment0.00 %=10,000 m(d)8,000 m(d)

1.3Min. adjustment100.00 %=1,000 m(d)2,000 m(d)

1.4Linearisation curve

linear

1.5Channel

PV lin. value

1.6Damping

0 s

1.7Sensor-TAG

Sensor

Indication2Basic adjustment

▶ IndicationDiagnosticsServiceInfo

2.1Displayed value

Primary Value

Diagnostics3Basic adjustment

Indication▶ Diagnostics

ServiceInfo

Setup

Indicating and adjustment module PLICSCOM 29

2783

5-EN-

0701

23

3.1Pointer

Distance min: 0.580 m(d)Dist. max: 16.785 m(d)

3.2Sensor status

OK

3.3Curve selection

Echo curve

3.4Echo curve

Presentation of the echocurve

Service4Basic adjustment

IndicationDiagnostics

▶ ServiceInfo

4.1Sensor

5.00 mRod

4.2ApplicationLiquid

Standard(DK ≥2)

4.3Gating out of false signals

Change now?

4.4Additional PA value

Secondary Value 1

4.5Out-Scale-Unit

Volumehl

4.6PV-Out-Scale

0 % = 0,0 m³100 % = 100 m³

4.7Simulation

Start simulation?

4.8Reset

Reset?

4.9Unit of measurement

m(d)select?

4.10Language

Deutsch

4.11Copy sensor data

Copy sensor data?

4.12PIN

Enable?

Info5Basic adjustment

IndicationDiagnosticsService

▶ Info

5.2Sensor typeVEGAFLEX 6x

Serial number12345678

5.2Date of manufacture15. Dec. 2006Software version3.22

5.3Last change using PC

15. Dec. 2006

5.5Sensor characteristics

Display now?

Setup

30 Indicating and adjustment module PLICSCOM

27835-EN-070123

5.9 Menu schematic for a Foundation Fieldbussensor (example: VEGABAR 52)

Information:Menu schematic for a Foundation Fieldbus sensor (example:VEGABAR 52)Depending on the version and application, the highlightedmenu windows are not always available.

Basic adjustment1▶ Basic adjustment

IndicationDiagnosticsServiceInfo

1.1Unit of measurement

bar

1.2Position correctionOffset

P=+0000 mbar53 mbar

1.3Zero000.0 %

P=000 mbar

53 mbar

1.4Span100.00 %

P=1000 mbar

53 mbar

1.5Damping

1 s

1.6Linearisation curve

linear

Indication2Basic adjustment

▶ IndicationDiagnosticsServiceInfo

2.1Displayed value

AI-Out

2.4Lighting

Switched off▼

Setup

Indicating and adjustment module PLICSCOM 31

2783

5-EN-

0701

23

Diagnostics3Basic adjustment

Indication▶ Diagnostics

ServiceInfo

3.1PointerTmin.: -12.5 °CTmax.: +85.5 °Cp-min.: -0.58 barp-max.: 16.765 bar

3.2Sensor status

OK

3.3Trend recording

Service4Basic adjustment

IndicationDiagnostics

▶ ServiceInfo

4.1Simulation

Start simulation?

4.2Reset

Reset?

4.3Language

Deutsch

4.4Copy sensor data

Copy sensor data?

4.5PIN

Enable?

4.6Application

Process pressure

Info5Basic adjustment

IndicationDiagnosticsService

▶ Info

5.1Device-ID

Sensor-TAG

5.2Sensor typeVEGABAR 5x

Serial number12345678

5.2Date of manufacture15. December 2006Software version3.32

5.3Last change using PC

16. March 2006

5.5Sensor characteristics

Display now?

Setup

32 Indicating and adjustment module PLICSCOM

27835-EN-070123

6 Maintenance and fault rectification6.1 MaintenanceWhen used as directed in normal condition, the indicating andadjustment module is maintenance-free.

6.2 Instrument repairIf a repair is necessary, please proceed as follows:You can download a return form (23 KB) in the Internet fromour homepage www.vega.com under: "Downloads - Formsand Certificates - Repair form".By doing this you help us carry out the repair quickly andwithout having to call for additional information.l Print and fill out one form per instrumentl Clean the instrument and pack it damage-proofl Attach the filled in form and if necessary, a safety data

sheet to the instrumentl Please ask the agency serving you for the address of your

return shipment. You find the respective agency on ourwebsite www.vega.com under: "Company - VEGA world-wide"

Maintenance and fault rectification

Indicating and adjustment module PLICSCOM 33

2783

5-EN-

0701

23

7 Dismounting7.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high temperatures,corrosive or toxic products etc.

Take note of chapters "Mounting" and "Connecting to powersupply" and carry out the listed steps in reverse order.

7.2 DisposalThe indicating and adjustment module consists of materialswhich can recycled by specialised recycling companies. Wehave purposely designed the components to be easilyseparable.WEEE directive 2002/96/EGThis indicating and adjustment module is not subject to theWEEE directive 2002/96/EG and the respective national laws(in Germany, e.g. ElektroG). Pass the indicating and adjust-ment module directly on to a specialised recycling companyand do not use the municipal collecting points. They may onlybe used for privately used products according to the WEEEdirective.Correct disposal avoids negative effects to persons andenvironment and ensures recycling of useful raw materials.Materials: see "Technical data"If you cannot dispose of the instrument properly, pleasecontact us about disposal methods or return.

Dismounting

34 Indicating and adjustment module PLICSCOM

27835-EN-070123

8 Supplement8.1 Technical dataGeneral dataWeight approx. 150 g

Ambient conditionsAmbient temperature -15 … +70 °C (+5 … +158 °F)Storage and transport temperature -40 … +80 °C (-40 … +176 °F)

Indicating and adjustment modulePower supply and data transmission through sensor via gold-plated sliding contacts

(I²C bus)Indication LC display in Dot matrixAdjustment elements 4 keysProtection- unassembled IP 20- mounted into the sensor without

coverIP 40

Materials- Housing ABS- Inspection window Polyester foil

Display lightSupply through the sensor, voltage range see sensor

operating instructions manual

Supplement

Indicating and adjustment module PLICSCOM 35

2783

5-EN-

0701

23

8.2 Dimensions

PLICSCOM27

,6m

m(1

3/ 3

2")

ø66,

3mm

(2 3

9 /64

")

45,1mm (1 25/32")

9,7mm (3/8")

Fig. 5: PLICSCOM

Supplement

36 Indicating and adjustment module PLICSCOM

27835-EN-070123

8.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only in U.S.A.: Further information see patent label at the sensor housing.VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte.Nähere Informationen unter http://www.vega.com.Les lignes de produits VEGA sont globalement protégées par des droits depropriété intellectuelle.Pour plus d'informations, on pourra se référer au site http://www.vega.com.VEGA lineas de productos están protegidas por los derechos en el campo de lapropiedad industrial.Para mayor información revise la pagina web http://www.vega.com.Линии продукции фирмы ВЕГА защищаются по всему миру правами наинтеллектуальную собственность.Дальнейшую информацию смотрите на сайте http://www.vega.com.德�VEGA公司列�品在全球享有知���保�。�一步信息���网站<http://www.vega.com>。

8.4 TrademarkAll brands used as well as trade and company names areproperty of their lawful proprietor/originator.

Supplement

Indicating and adjustment module PLICSCOM 37

2783

5-EN-

0701

23

Supplement

38 Indicating and adjustment module PLICSCOM

27835-EN-070123

Supplement

Indicating and adjustment module PLICSCOM 39

2783

5-EN-

0701

23