Upload
akmezim
View
39
Download
3
Embed Size (px)
DESCRIPTION
National Grid Technical Specification for CTs
Citation preview
This document is for internal and contract specific use only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any losses arising under or in connection with this information. This limit on liability applies to all and any claims in contract, tort (including negligence), misrepresentation (excluding fraudulent misrepresentation), breach of statutory duty or otherwise. This limit on liability does not exclude or restrict liability where prohibited by the law nor does it supersede the express terms of any related agreements." Copyright © National Grid plc 2011, all rights reserved All copyright and other intellectual property rights arising in any information contained within this document are, unless otherwise stated, owned by National Grid plc or other companies in the National Grid group of companies. No part of this publication may by reproduced in any material form (including photocopying and restoring in any medium or electronic means and whether or not transiently or incidentally) without the written permission of National Grid plc This information should not be forwarded to third parties.
National Grid Technical Specification TS 3.02.04 Technical Specification Addendum Addendum No 3
Uncontrolled When Printed Page 1 of 2
ADDENDUM
Date Effective From 24 November 201115 July 2011
Originated by Approved by
Name Tony Westmorland David Wright
Job Title Generator & Asset Compliance Engineer
ENI Manager
Department Policy ENI
Date 24 November 2011 16 March 2012 ORIGINAL DOCUMENT DETAILS
DOCUMENT TITLE Current Transformers for Protection and General Use
DOCUMENT NUMBER TS 3.2.4
ISSUE NUMBER 5 Rev. 2
ISSUE DATE December 2003
ADDENDUM DETAILS The above document shall be read in conjunction with the following amendments: Check appropriate boxes below
Addition Replacement X Deletion
AMENDMENTS
Delete Amendment 1
Replace Schedule of Particulars - Schedule 10 with new schedule as detailed below: -
National Grid Technical Specification TS 3.02.04 Technical Specification Addendum Addendum No 3
Uncontrolled When Printed Page 2 of 2
SCHEDULE 10 TABLE OF PARTICULARS FOR 420 kV, 300 kV AND 145 kV CURRENT TRANSFORMERS
Note: For tapped current transformers the knee-point voltage, magnetising current and secondary resistance
are specified for the full winding, shown underlined.
Reference Clauses
CT Designation
Ratio
Minimum Knee-Point Voltage (Vk) or Class
Maximum Magnetising Current (mA) at Vk/2
Maximum Sec Res (ohms) at 75C
4.2 to 4.4
420 kV, 4000 A (i) PX A (ii) PX B (iv) Measurement/ Protection
1/1000/2000 1/1200/2000 1/1000/2000
3570
780
30 VA Class 1 5P20
60
24
Not Specified
4.4
2.7
3.0
4.2 to 4.4
300 kV, 3150A (i) PX A (ii) PX B (iii) Measurement/ Protection
1/600/1200/2000 1/600/1200/2000 1/600/1200/2000
2750
2000
30 VA Class 1 5P20
60
30
4.7
3.1
4.2 to 4.4
145 kV, 2000A (i) PX A (ii) PX B (iii) Measurement/ Protection + PXB + Class 1
1/500/600/1000/1200
1/500/600/1000/1200
1/500/600/1000/1200
1000
1000
30VA Class 1 5P20
800
60
30
30
2
2 2
National Grid - Internal and Contract Specific Document Number TS 3.02.04 Addendum Addendum No 2
Uncontrolled When Printed Page 1 of 2
ADDENDUM
Date Effective From 17 August 2010
Originated by Approved by
Name Tony Westmorland David Wright
Job Title Applied Policy Engineer Electricity Network Investment Manager
Department Asset Policy ENI, Asset Management
Date 17/08/2010 18/10/2010 ORIGINAL DOCUMENT DETAILS
DOCUMENT TITLE Current Transformers for Protection and General Use
DOCUMENT NUMBER TS 3.2.4
ISSUE NUMBER 5
ISSUE DATE December 2003
National Grid - Internal and Contract Specific Document Number TS 3.02.04 Addendum Addendum No 2
Uncontrolled When Printed Page 2 of 2
ADDENDUM DETAILS The above document shall be read in conjunction with the following amendments: Check appropriate boxes below
Addition x Replacement Deletion
Schedule 10 – Add new Schedule of Particulars for 400kV, 5000A Current Transformers as detailed below: -
SCHEDULE 10 TABLE OF PARTICULARS FOR 420 KV CURRENT TRANSFORMERS
TS Reference Clauses
CT Designation Turns Ratio Knee-Point Voltage (Vk)
or IEC Rating and Class
Magnetising Current (mA)
Max Sec Res (ohms)
4.2 to 4.4 420 KV, 5000 A
PXA 1/1000/2000/3000 3000/1 450(Rct + 7.5) - -
PXB 1/1000/2000/3000 3000/1 90(Rct + 5) 40 at Vk/2 5.0 at 75°C
MEASUREMENT AND PROTECTION
1/1000/2000/3000 3000/1
2000/1
1000/1
30 VA Class 1
5P20
30 VA Class 1
5P20
30 VA Class 1
5P10
Notes: 1. This specification has been issued for current transformers with a 5000A continuous current
rating with 2xPXA, 1xDual Purpose and 2PXB cores. For current transformers with a maximum continuous current rating of 4000A, refer to separate schedule of particulars.
2. The accuracy class and knee points are to be maintained for the ratios which are underlined in the table above. 3. The Current Transformer shall be assigned a short time overload rating of 2 times rated current
for 3 minutes. (refer to Table 1 of TS 2.1) 4. The Current Transformer shall be assigned a post fault continuous current rating of 1.206 times
rated current. (refer to Table 1 of TS 2.1) 5. The Current Transformer characteristics (knee point, mag current etc.) are as defined in the table above. Requirements for Dual Purpose Measurement/Protection Current Transformers
1. Current transformers intended for the dual purpose of measurement and protection shall meet the performance requirements of IEC 60044-1, Clause 4.2.1 and the above table.
2. All measurement/protection CTs shall have an extended measuring range of 200% In except CTs for Transformers and Quad Boosters which shall have an extended measuring range of 300% In.
3. All measurement/protection CTs shall meet the short time overload ratings given in Table 1 of TS 2.1.
National Grid - - Internal and Contract Specific Technical Specification TS 3.2.4 Technical Specification Addendum Addendum No 1
Uncontrolled When Printed Page 1 of 1
TECHNICAL SPECIFICATION ADDENDUM
DOCUMENT TITLE Current Transformers for Protection and General Use DOCUMENT NUMBER TS 3.2.4 ISSUE NUMBER 5 ISSUE DATE December 2003 This Technical Specification shall be read in conjunction with the following amendments: Check appropriate boxes below
Addition Replacement X Deletion
AMENDMENTS
Schedule 10 – Replace Schedule of Particulars for 300kV Current Transformers with new schedule as detailed below: - SCHEDULE 10 TABLE OF PARTICULARS FOR 300 kV CURRENT TRANSFORMERS
TS Reference Clauses
CT Designation Turns Ratio Knee Point Voltage (Vk) or
IEC Rating Class
Magnetising Current
(mA)
Max Sec Res
(ohms)
4.2 to 4.4 300 kV, 3150A
PXA 1/600/1200/2000 2000/1
1200/1
267(Rct + 7.5)
160(Rct + 7.5)
-
-
-
-
PXB 1/600/1200/2000 2000/1
1200/1
137(Rct + 3.0)
82(Rct + 3.0)
60 at Vk/2
60 at Vk/2
2.4 at 75°C
2.4 at 75°C
MEASUREMENT AND PROTECTION
1/600/1200/2000 2000/1 30 VA Class 1
5P20
1200/1
600/1
30 VA Class 1
5P20
30VA Class 1
5P10
Date Effective From 01 January 2010
Originated by Authorised by Approved by
Name Tony Westmorland Ursula Bryan David Wright
Job Title Applied Policy Engineer Asset Policy Manager Electricity Network Investment Manager
Department Asset Policy Asset Policy ENI, Asset Management
Date 05/01/2010 05/02/2010 08/02/2010
National GridTechnical Specification
Current Transformers forProtection and GeneralUse
NGTS 3.2.4Issue 5December 2003
CONTENTS Page
Foreword ...................................................11 Scope ..............................................12 References ......................................13 General Requirements ....................24 Performance Requirements.............35 Testing Requirements .....................46 List Of Schedules ............................7Appendix A..............................................18Appendix B..............................................19
Authorised for Issue by:
Mike DeanAsset Strategy Manager
Uncontrolled when printed. This document will be valid on the day of printing only
© National Grid 2003
“No part of this publication may be reproduced, stored in a retrievalsystem, or transmitted in any form or by any means electronic,mechanical, photocopying, recording or otherwise, without thewritten permission of the National Grid obtained from the issuinglocation.
The contents of National Grid engineering documents are basedon the needs of National Grid and the conditions under which itoperates. It should not therefore be assumed that thespecifications and requirements stated therein necessarily meetthe particular circumstances and requirements of otherorganisations. The principles set out in this document are forinformation only and therefore National Grid is not liable tocustomers / suppliers for any loss or damage resulting fromreliance on the contents. It is the responsibility of such externalorganisations to check that the document is the latest version andis appropriate for their purposes.”
(National Grid Legal Services. November 1999)
Registered Office Registered in1-3 Strand England and WalesLondon No. 2366977WC2N 5EH
Published by:National GridNGT HouseWarwick Technology ParkGallows HillWarwickCV34 6DA
Uncontrolled when printed. This document will be valid on theday of printing only.
Administrative enquiries regarding this document should bedirected to:
Asset Support at Warwick, Telephone: 01926 655063
Technical enquiries regarding this document should be directed to:
Contact name: Tony WestmorlandAsset Policy
Telephone: 01926 655966
NGTS 3.2.4Issue 5
December 2003
Page 1
CURRENT TRANSFORMERS FOR PROTECTION AND GENERAL USE
FOREWORD
This Specification defines the functional and performance requirements for current transformers (CTs) forprotection and general use on The National Grid Transco (NGT) UK Transmission System (Electricity).It supports the more general requirements defined in the companion documents NGTS 1, NGTS 2.1 andNGTS 2.2.
1 SCOPE
This is a functional and performance specification for CTs used for protection and measurementapplication. For CTs used in Settlements Metering applications reference should be made toNGTS 3.2.6.
2 REFERENCES
2.1 International, European and British National Documentation
This document makes reference to, or should be read in conjunction with, the documents listedbelow. Where a standard has been harmonised into a Euronorm, only this latter reference isgiven. The issue and date of the documents detailed below shall be applicable at the time ofissue of this specification unless a specific issue date is given
IEC 60044-1 Instrument transformers- Part 1: Current Transformers
IEC 567 Guide for the sampling of gases and of oil from oil filled electrical equipmentand for the analysis of free and dissolved gases.
IEC 60044-6 Requirements for protective Current Transformers for transient performance
BS EN 60694 Common specifications for high voltage switchgear and controlgearstandards
BS 7626 Current Transformers
2.2 National Grid Technical Specifications
The following NGTS documentation is relevant to current transformers and should be read inconjunction with this document.
NGTS 1 Ratings and General Requirements for Plant, Equipment, Apparatus andServices for use on and Direct Connections to the National GridTransmission System
NGTS 2.1 Substations
NGTS 2.2 Switchgear for use on, and at Connection Points to, the National Grid System
NGTS 2.3 Transformers and Reactors for use on 132, 275 and 400 kV Systems
NGTS 2.6 Protection
NGTS 3.2.4Issue 5
December 2003
Page 2
2.3 Definitions and Abbreviations
The definitions used in NGTS1 and NGTS2.2 apply to this document.
3 GENERAL REQUIREMENTS
All CTs shall comply with NGTS 1, NGTS 2.1, NGTS 2.2 and IEC 60044-1. In addition, thefollowing clauses apply:
3.1 General Requirements for all Current Transformers
3.1.1 Additional specification and testing requirements for protection Class PX cores are given inAppendix E. For information, these requirements are identical to those given in the now obsoleteBS 3938 Class X sections.
3.1.2 Secondary ratings and transformation ratios shall be selected from the attached Schedules andshall be specified in the contract Enquiry Document or Supplementary Agreement as appropriate
3.1.3 A single secondary terminal box shall be mounted on the transformer to accommodate thenecessary secondary terminal connections.
3.1.4 Secondary terminals and connections shall be suitable for their required purpose regardingrating, reliability and the effects of environmental conditions and corrosion.
3.1.5 Secondary terminal boxes shall comply to at least IP54 environment of BSEN60529 as requiredby NGTS 1
3.1.6 Primary and secondary terminal markings, and rating plate markings shall be inaccordance with IEC 60044�1
3.1.7 The rated continuous primary current of the current transformer shall be chosen to exceed themaximum continuous rating of the associated circuit and shall be selected from the standardvalues detailed in IEC 60044-1
3.1.8 A thermal short-time current rating (Ith) shall be assigned to all current transformers inaccordance with IEC 60044-1. The value of Ith shall not be less than the corresponding valuefor the associated switchgear or transformer primary plant.
3.1.9 Current transformer secondary terminals should allow the application of shorting/earthing linksor wiring for maintenance purposes. Separately, a terminal for earthing purposes shall beprovided within the terminal box and shall be clearly marked.
3.1.10 For all oil filled CTs the supplier shall declare the type of insulating oil being used.
3.1.11 For oil-filled equipment fitted with an external oil expansion system, means shall be provided togive a permanent visual indication of the volume of the oil. The status of the indicator should bevisible from ground level.
3.1.12 For oil filled CTs where the oil expansion system is wholly internal ie gas cushion or flexiblediaphragm, the CT shall be fitted with a permanent internal pressure indicator. The status of theindicator shall be visible from ground level.
3.1.13 All oil filled CTs shall be fitted with an oil sample valve, situated at the base of the CT, suitablefor taking oil samples for Dissolved Gas Analysis (DGA) in accordance with IEC 567. Thesample valve shall be situated on the earthed base tank of the CT. Valves where the oil isextracted by using a hypodermic needle are not suitable.
NGTS 3.2.4Issue 5
December 2003
Page 3
3.1.14 Both ends of the CT secondary windings shall be earth free.
3.2 Additional Requirements for Post-Type Current Transformers
3.2.1 An insulation test terminal (test tap) shall be provided for the purpose of performing capacitanceand dielectric loss (tan �) measurements of the primary insulation during routine maintenance.The test terminals shall be suitably identified.
3.3 Additional Requirements for Current Transformers for GIS Application
3.3.1 Current transformers may be mounted internally or externally to the GIS enclosure.
3.3.2 Adequate protection against adverse environmental conditions shall be provided for externallymounted CTs as required in NGTS 2.2.
3.4 Additional Requirements for Ring-Type Current Transformers
3.4.1 Current transformers mounted internally to power transformers shall be capable of operating inan environment as detailed in NGTS 2.3.
3.4.2 Current transformers supplied as loose equipment for power transformer application shall beequipped with secondary terminals or shall be supplied with leads of suitable length for thisapplication. Such leads shall be capable of satisfying the test requirement of Clause 5.4.3.
3.4.3 Current transformers supplied with throughwall bushings can be mounted internally or externallyto the bushing. Current transformers mounted internally shall be capable of operating within thatenvironment. Current transformers mounted externally shall be suitably protected against theeffects of adverse environmental conditions as required by NGTS 2.2.
3.4.4 Current transformers supplied as loose equipment for other switchgear applications shall becapable of operating within that environment. Current transformers for other switchgearapplications, mounted externally, shall be suitably protected against the effects of adverseenvironmental conditions as required by NGTS 2.2.
3.5 Additional Requirements for Measurement/Protection and Class PX Protective CurrentTransformers
3.5.1 Measurement/Protection and class PX protective current transformers with a rated primarycurrent of 2500 A or below and with untapped secondary windings shall have a rated secondarycurrent of 1A (as selected from IEC 60044-1). The rated secondary current for currenttransformers of this primary rating with tapped secondary windings shall be 1 A correspondingto the highest transformation ratio.
3.5.2 Measurement/Protection and class PX protective current transformers with a rated primarycurrent in excess of 2500 A shall have a rated secondary current selected from the values statedin IEC 60044-1
4 PERFORMANCE REQUIREMENTS
4.1 General
All current transformers shall comply with the performance requirements of IEC 60044-1 for theprimary ratings detailed in NGTS 1, NGTS 2.1 and NGTS 2.2. The following requirements shallalso apply as appropriate:
NGTS 3.2.4Issue 5
December 2003
Page 4
4.2 Protection Type PX-A Current Transformers
4.2.1 Protection type PX-A current transformers shall meet the additional requirements given inAppendix E providing accurate transformation up to the maximum fault current rating of theassociated main plant. This performance shall be maintained under both fault and steady-stateconditions without saturation
4.2.2 Type PX-A current transformers shall also meet the performance requirements of Schedule 10of this Specification.
4.3 Protection Type PX-B Current Transformers
4.3.1 Protection type PX-B current transformers shall meet the additional requirements given inAppendix E providing accurate steady-state transformation up to the maximum fault currentrating of the associated main plant.
4.3.2 Type PX-B current transformers shall also meet the performance requirements of Schedule 9of this Specification.
4.4 Dual Purpose Measurement/Protection Current Transformers
4.4.1 Current transformers intended for the dual purpose of measurement and protection shall meetthe performance requirements of IEC 60044-1, Clause 4.2.1 and Schedule 10 of thisSpecification.
4.5 Interposing Current Transformers
4.5.1 Short duration overload capabilities are assigned to the main current transformers and theassociated interposing current transformers shall be capable of carrying the correspondingcurrent.
4.6 Line Drop Compensation Current Transformers (as used in tap change voltage controlschemes)
4.6.1 Line drop compensation current transformers shall comply with accuracy class 5 of BS 7626.
5 TESTING REQUIREMENTS
5.1 Type Tests
5.1.1 All current transformers shall be type tested in accordance with IEC 60044-1 (type tests) andIEC 60044-1 (special tests). The additional requirements for protection class PX cores given inAppendix B. Current transformers using a gas insulation system, a leakage test on the gassystem shall be performed by the supplier to demonstrate compliance with NGTS 2.2.
5.1.2 Radio interference voltage tests to IEC 60694 are to be performed on open-terminal currenttransformers.
5.1.3 A multi chopped impulse test shall be performed on all oil filled current transformers rated72.5 kV and above. The test method is given in Appendix D.
5.1.4 Temperature Rise - The thermal time constant of all equipment shall be determined on bothrising and falling temperature.
5.1.5 For oil filled equipment oil samples for DGA shall be taken before and after the dielectric typetests and shall comply with 5.5.3.
NGTS 3.2.4Issue 5
December 2003
Page 5
5.1.6 Accuracy at Short-Term Continuous Current Levels - Current transformers which have ameasurement specification shall have their errors determined at a current of 12000 A for 420 kVrating and 7500 A for 300 kV rating respectively. These currents shall be withstood for a periodof 3 minutes.
5.1.7 Routine tests shall be performed before and after all type tests.
5.2 Routine tests
5.2.1 All current transformers shall be routine tested in accordance with:
IEC 60044-1 (routine tests)
IEC 60044-1 (special tests)
The additional requirements for protection class PX transformers are given in Appendix B.
5.3 Additional Routine Tests
5.3.1 Accuracy Tests
a) These shall be performed in a laboratory having traceability to National/Internationalstandards.
b) The overall accuracy and uncertainty of the measurement shall be demonstrated prior totesting and shall be commensurate with the accuracy class of the transformer under test.
c) Full accuracy routine tests to IEC 60044-1.
5.3.2 Capacitance and dielectric loss angle (tan δ) measurements of the primary insulation over thevoltage range 10 kV to rated voltage shall be performed.
5.3.3 Leads for loose current transformers as detailed in Clause 3.4.2 of this Specification shallwithstand a power frequency test voltage of 5 kV (peak). For PXA application, the test levelsshall be determined by tests in Appendix B 14.2.2.
5.3.4 An oil sample for DGA shall be taken as described in 5.5 from all oil filled CTs. The sample shallbe taken at least 24 hours after the final routine electrical testing has been performed. Theresults shall be included in the routine test report as detailed in Clause 5.5.
5.4 Routine Test Reports
5.4.1 Routine test reports shall include details of all routine measurements made in accordance withthis specification. The information regarding the overall accuracy and uncertainty of theaccuracy measurements shall also be recorded.
5.4.2 During the partial discharge (PD) test, the value of measured PD at the specified test voltageshall be recorded together with the value of the PD extinction voltage. Extinction voltage isdefined as the voltage level at which measurable PD is completely extinguished upon decreasingtest voltage. The background PD level at the time of the test should also be recorded in thereport.
5.4.3 Where oil samples are taken for Dissolved Gas Analysis (DGA) the report shall contain thefollowing information:
a) Name and Address of the laboratory where the analysis was performed
b) The Accuracy, Precision and Detection Limits for the individual gas measurementexpressed in either parts per million (ppm) or percentage by volume.
NGTS 3.2.4Issue 5
December 2003
Page 6
c) The Sampling Procedure (stating the Standard Method IEC 567 if applicable).
d) The Gas Extraction Method used (stating the Standard Method IEC 567 if applicable).
e) Calibration Procedure adopted by the laboratory, including details of the number of pointsused over the range (f)and the gases used.
f) Accreditation Status of the laboratory for the purposes of DGA testing.
g) Date Sampled and Analysed.
h) Report the following:
Measurement Units No. Decimal Places
Oil Volume Tested mls 0
Total Gas Content % 2
Hydrogen ppm 0
Methane ppm 0
Ethane ppm 0
Ethylene ppm 0
Acetylene ppm 0*
Carbon monoxide ppm 0
Carbon dioxide ppm 0
Oxygen ppm 0
Nitrogen ppm 0
Moisture mg/l 0
*Note: For DGA samples associated with Type Tests, the acetylene value shall be quoted to onedecimal place
NGTS 3.2.4Issue 5
December 2003
Page 7
6 LIST OF SCHEDULES
Schedule 1 Overhead Line Feeder Circuits
Schedule 2 Synchronous Compensators Associated with Auto-Transformers
Schedule 3 Static Compensators (Reactors and Capacitors) Associated with Auto-Transformers
Schedule 4 Series Reactors
Schedule 5 Shunt Reactors
Schedule 6 Bus Sections and Couplers and other users Directly Connected via NGC busbar protection
Schedule 7 Auto-Transformer Circuits
Schedule 8 Transformer Neutral and Neutral End Current Transformer Units for use withSupergrid Auto-Transformers and Shunt Reactors
Schedule 9 Secondary ratings and rated transformation ratios for double woundtransformer current transformer circuit.
Schedule 10 Table of Particulars for 420 kV, 300 kV and 145 kV Current Transformers
NGTS 3.2.4Issue 5
December 2003
Page 8
SCHEDULE 1 OVERHEAD LINE FEEDER CIRCUITS
Class X Protection Current Transformers Measurement/Protection Current Transformers
SystemVoltage
Rated Currentof Switchgear
RatedContinuous
ThermalCurrent
Turns Ratio Extended PrimaryCurrent Rating %
kV A A Main Busbar Thermal Accuracy
RatedTransformation
Ratio
275
275
400
2000
2500
4000
2000
2500
4000
1/600/1200
1/600/1200
1/1000/2000
1/600/1200
1/600/1200
1/2000
170
210
200
420
420
500
1200/600/1
1200/600/1
2000/1000/1
NGTS 3.2.4Issue 5
December 2003
Page 9
SCHEDULE 2 SYNCHRONOUS COMPENSATORS ASSOCIATED WITH AUTO-TRANSFORMERS
Class X Protection Current Transformers Measurement/Protection Current TransformersCompensator
Rating Voltage CurrentRated
Current ofSwitchgear
RatedContinuous
ThermalCurrent
Turns Ratio Extended PrimaryCurrent Rating % Rated Transformer Ratio
MVA kV A A A Main REF* UEF** Connections Thermal Accuracy BackUp Reverse Power
60 13 2665 3000 3000 1/600 1/600 1/300 1/600 - - 3000/5 3000/5
* REF - restricted earth fault** UEF - unrestricted earth fault
NGTS 3.2.4Issue 5
December 2003
Page 10
SCHEDULE 3 STATIC COMPENSATORS (REACTORS AND CAPACITORS) ASSOCIATED WITH AUTO-TRANSFORMERS
Class X Protection Current Transformers Measurement/ProtectionCurrent Transformers
CompensatorRating Voltage Current
RatedCurrent ofSwitchgear
RatedContinuous
ThermalCurrent
Turns Ratio Extended PrimaryCurrent Rating %
MVA kV A A A HVConnections
CompensatorProtection REF*
UEF** andInstantaneous
Earth FaultThermal Accuracy
RatedTransfor-mationRatio
60
30+30
13
13
2665
1335+
1335
3000
2000
3000
2000
1/600
1/600
1/600
1/1500
1/600
1/1500
1/1500 #
1/300+
1/1500#
-
-
-
-
3000/5
3000/5
* REF - restricted earth fault** UEF - unrestricted earth fault# A relay may be required+ 300/1 ratio to be specified when earth fault current is restricted to 300 A by NER.
1500/1 ratio to be specified when earth fault current is restricted by impedance of earthing transformer only.
NGTS 3.2.4Issue 5
December 2003
Page 11
SCHEDULE 4 SERIES REACTORS
Class X Protection Current Transformers Measurement/Protection CurrentTransformers
Rating SystemVoltage Current
RatedCurrent ofSwitchgear
RatedContinuous
Thermal CurrentTurns Ratio Extended Primary
Current Rating %
MVA kV A A A Main Busbar Thermal Accuracy
RatedTransformation
Ratio
90
750
750
1320
2000
132
275
275
400
400
395
1575
1575
1905
2890
800
2000
2500
4000
4000
800
2000
2500
4000
4000
1/500/1000
1/600/1200
1/600/1200
1/1000/2000
1/1000/2000
1/500/1000
1/600/1200
1/600/1200
1/2000
1/2000
-
170
210
200
200
-
170
210
200
290
1200/600/1
1200/600/1
1200/600/1
2000/1000/1
2000/1000/1
NGTS 3.2.4Issue 5
December 2003
Page 12
SCHEDULE 5 SHUNT REACTORS
Class X Protection Current Transformers Measurement/Protection CurrentTransformers
Rated ContinuousThermal Current
ATurns Ratio
Extended PrimaryCurrent Rating Thermal
and Accuracy %Rating System
Voltage CurrentRated
Current ofSwitchgear
MVA kV A A
Locatednear
Switchgear
Locatedin
Bushing
MainProtection
FeederProtection orif Applicable
ConnectionsProtection
if Applicable
Locatednear
Switchgear
Locatedin Bushing
RatedTransformation
Ratio
100 275 210 2000 2000 500 1/600/1200 1/600/1200 1/600/1200 170 - 1200/600/1 *
100 275 210 2500 2500 500 1/600/1200 1/600/1200 1/600/1200 210 - 1200/600/1 *
200 400 290 4000 4000 500 1/1000 1/1000/2000 1/2000 200 - 2000/1000/1 *
* 0.5 A relay to be specified.
NGTS 3.2.4Issue 5
December 2003
Page 13
SCHEDULE 6 BUS SECTIONS AND BUS COUPLERS
ALSO OTHER USER CT’s AT CONNECTION POINTS AND ASSOCIATED WITH NGC BUSBAR PROTECTION
Class X Protection Current Transformers Measurement/Protection Current Transformers
Turns RatioSystem Voltage Rated Current ofSwitchgear Rated Continuous
Thermal Current Extended Primary Current Rating %
kV A ABusbar
Thermal Accuracy
RatedTransformation
Ratio
275
275
400
2000
2500
4000
2000
2500
4000
1/600/1200
1/600/1200
1/1000/2000
170
210
200
420
420
500
1200/600/1
1200/600/1
2000/1000/1
NGTS 3.2.4Issue 5
December 2003
Page 14
SCHEDULE 7 AUTO TRANSFORMER CIRCUITS
Class X Protection Current Transformers Measurement/Protection Current TransformerTurns Ratio Extended Primary Current Rating %Nominal
RatingSystemVoltage Current
RatedCurrent
ofSw/gear
Rated ContinuousThermal Current
A* Thermal * Accuracy **
MVA kV A ALocated
nearSw/gear
Locatedin
Bushing
Main HV and LVConnections Busbar Back Up LV Located
nearSw/gear
Locatedin
Bushing
Locatednear
Sw/gear
Locatedin
Bushing
RatedTransform-ation Ratio
120
180
240
240
500
750
1000
275
132
275
132
275
132
400
132
400
275
400
275
400
275
250
530
380
790
500
1050
350
1050
720
1050
1080
1580
1440
2100
2500
800
2500
1250
2500
2000
4000
2000
4000
2500
4000
2500
4000
2500
2500
800
2500
1250
2500
2000
4000
2000
4000
2500
4000
2500
4000
2500
450
800
660
1200
870
1600
610
1600
1100
1600
1700
2500
2200
3200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/600/1200
1/500/1000
1/600/1200
1/500/1000
1/600/1200
1/500/1000
1/1000/2000
1/500/1000
1/1000/2000
1/600/1200
1/1000/2000
1/600/1200
1/1000/2000
1/600/1200
1/600/1200
1/500/1000
1/600/1200
1/500/1000
1/600/1200
1/500/1000
1/2000
1/500/1000
1/2000
1/600/1200
1/2000
1/600/1200
1/2000
1/600/1200
1/500/1000#
1/500/1000#
1/500/1000#
1/500/1000#
1/600/1200
1/600/1200
1/600/1200
210
-
210
110
210
170
200
170
200
210
200
210
200
210
-
-
-
-
-
135
-
135
-
135
-
210
110
270
210
-
210
130
210
180
200
180
200
210
200
270
200
350
-
-
-
130
-
180
-
180
-
180
110
270
150
350
1200/600/1
1200/600/1
1200/600/1
1200/600/1
1200/600/1
1200/600/1
2000/1000/1
1200/600/1
2000/1000/1
1200/600/1
2000/1000/1
1200/600/1
2000/1000/1
1200/600/1
* Designed to cater for 150% overload** Designed to cater for 200% overload# At busbar stations where post-type CT housings are installed and LV connection protection is specified, the back-up protection is to be supplied from the
Type A 1/600/1200 CT.
NGTS 3.2.4Issue 5
December 2003
Page 15
SCHEDULE 8 TRANSFORMER NEUTRAL AND NEUTRAL END CURRENTTRANSFORMER UNITS FOR USE WITH SUPERGRID AUTOTRANSFORMERS AND SHUNT REACTORS
275/132 kV, 400/275 kV and 400/132 kV auto-transformers and 400 kV and 275 kV ShuntReactors (11 kV primary insulation)
Type Primary ConductorRating (A) (sec) Turns Ratio Function
Transformer275/132 kV(Up to 360 MVA)
82003 sec 1/600/1200
At Least 2Secondaries, NeutralEarth Fault Check,Fault recorder etc
Transformer400/275 kV(Up to 1000 MVA)
66001 sec 1/1000/2000 "
Transformer400/132 kV(Up to 360 MVA)
10 6003 sec 1/1000/2000 "
Shunt Reactor275 kV(Up to 100 MVA)
21001 sec 1/600/1200 Neutral Earth Fault
Check
Shunt Reactor400 kV(Up to 200 MVA)
29001 sec 1/1000/2000 "
Table A- Neutral Current Transformers
275/132 kV, 400/275 kV and 400/132 kV auto-transformers and 400 kV and 275 kV ShuntReactors (11 kV Primary Insulation)
Type Primary ConductorCMR (Ihv - Ilv) amp Turns ratio Function
Transformer275/132 kV(Up to 360 MVA)
820 1/600/1200
AutoTransformer
OverallProtection
Transformer400/275 kV(Up to 1000 MVA)
660 1/600/1200 "
Transformer400/132 kV(Up to 360 MVA)
1060 1/600/1200 "
Shunt Reactor275 kV(Up to 100 MVA)
210 1/600/1200Shunt Reactor
OverallProtection
Shunt Reactor400 kV(Up to 200 MVA)
290 1/1000 "
Table B - Neutral End Current Transformers (3 Single Phase Windings Starred)
NGTS 3.2.4Issue 5
December 2003
Page 16
SCHEDULE 9 SECONDARY RATINGS AND RATED TRANSFORMATION RATIOS FOR DOUBLE WOUND TRANSFORMER CURRENTTRANSFORMER CIRCUITS
Current Class X Protection Current Transformers Measurement/ProtectionCurrent Transformers
Turns RatioType Nominal
RatingSystemVoltage VT Ratio
AtNominal
RatioTap
Position
AtMeanTap
Position
RatedCurrent
ofSw/gear
RatedContinuous
ThermalCurrent
AMain Protection
Extended PrimaryCurrent Rating*
Thermal andAccuracy %
MVA kV A A A
LocatedN
earSw
/gear
LocatedN
earB
ushing
Main C
T
InterposingC
T
Back up LV
HV and LV
Connections
Busbar
LV unrestricted earthfault Located
nearSw
/gear
Located inB
ushing
Rated Transform
ationR
atio EG B
ack up HV
Star/Delta 75
27533
-33000/110
1571312
1661312
25002000
25002000
3002000
1/2001/800/1600
0.577/1.01.0/1.0/1.0
-1/1000/2000
1/600/12001/800
1/600/12001/800
-1/600/1200
210-
--
1200/600/12000/1
Star/Delta 100
27533
-33000/110
2101750
2211750
25002500
25002700
4002700
1/2001/800/1600
0.577/1.01.0/1.0/1.0
-1/1000/2000
1/600/12001/800
1/600/12001/800
-1/800/1600
210135
-135
1200/600/12000/1
Star/Delta 120
27533
-33000/110
2502100
2652100
25002500
25003200
4503200
1/4001/800/1600
0.577/0.70.7/1.0/1.0
-1/800/1600
1/600/12001/800
1/600/12001/800
-1/800/1600
210160
-160
1200/600/12000/1
Star/Star 120
27566
-66000/100
2501050
2501050
25002000
25002000
4501600
1/4001/800/1600
0.577/0.71.0/1.0/0.7
-1/800/1600
1/600/12001/800
1/600/12001/800
-1/600/1200
210170
-140
1200/600/11200/1
Star/Delta 120
27566
-66000/110
2501050
2501050
25002000
25002000
4501600
1/4001/800/1600
0.577/0.70.577/0.7
-1/800/1600
1/600/12001/800
1/600/12001/800
-1/600/1200
210170
-140
1200/600/11200/1
Star/Star 180
27566
-66000/110
3801580
3801580
25002000
25002400
7002400
1/4001/800/1600
0.577/11/1/1
-1/800/1600
1/600/12001/800
1/600/12001/800
-1/800/1600
210120
-120
1200/600/12000/1
Star/Delta 180
27566
-66000/110
3801580
3801580
25002000
25002400
7002400
1/4001/800/1600
0.577/1.00.577/1.0
-1/800/1600
1/600/12001/800
1/600/12001/800
-1/800/1600
210120
-120
1200/600/12000/1
Star/Delta 180
40066
-66000/110
2601580
2601580
40002000
40002400
5002400
1/4001/800/1600
0.577/0.71/1/1
-1/800/1600
1/1000/20001/800
1/20001/800
-1/800/1600
200120
-120
2000/1000/12000/1
Notes1 275/33 transformers’ mean tap position is -5%. 275/66 and 400/66 transformers mean tap position corresponds with the nominal ratio tap position.2 Double wound transformers, not covered by the schedule, should be referred to the General Manager, Engineering and Technology.3 For Settlement Metering CTs see NGTS 3.2.6.* Designed to cater for 150% overload.jxa/cw/may.01
NGTS 3.2.4Issue 5
December 2003
Page 17
SCHEDULE 10 TABLE OF PARTICULARS FOR 420 kV, 300 kV AND 145 kV CURRENTTRANSFORMERS
RatioReferenceClauses
CTDesignation
Turns Current
Knee-PointVoltage (Vk)
or IEC Ratingand Class
Magnetising
Current(mA)
Max SecRes (ohms)
4.2 to 4.4 420 kV, 4000 A
(i) Prot A 1/1000/2000 300 (Rct + 7.5)
(ii) Prot B 1/2000 60 (Rct + 5) 40 at Vk
2
5.0 at 75�C
(iii) Prot BSpecial Ratio
1/600/1200 82 (Rct +3) 60 at Vk
2
2.4 at 75�C
(iv) Measure-ment/Protection
1/1000/2000 2000/1 30 VA Class 1
5P20
1000/1 30 VA Class 1
5P10
4.2 to 4.4 300 kV, 2000 or2500 A
(i) Prot A 1/600/1200 160 (Rct + 7.5)
(ii) Prot B 1/600/1200 82 (Rct + 3) 60 at Vk
2
2.4 at 75�C
(iii) Prot BSpecial Ratio
1/600/1200 1200/1 30 VA Class 1
5P20
600/1 30 VA Class 1
5P10
4.2 to 4.4 145 kV, 2000A
(i) Prot A 1/600/1200
1/500/100050 (Rct + 17)
60 (Rct + 12)
(ii) Prot B 1/500/1000 95 (Rct + 2.5) 60 at Vk
2
2.4 at 75�C
(iii) Prot BSpecial Ratio
1/600/1200 1200/1 30VA Class 1
5P20
600/1 30VA Class 1
5P10
Note - For tapped current transformers the knee-point voltage, magnetising current and secondary resistance arespecified for the full winding, shown underlined.
NGTS 3.2.4Issue 5
December 2003
Page 18
APPENDIX A
MULTICHOPPED IMPULSE TYPE TEST SPECIFICATION
All oil filled CTs rated at 72.5 kV and above, shall be subjected to a 600 chopped negative polarity impulsetest at 60% of the rated BIL level for that equipment. The time to chop shall be between 2-5�s. A full setof routine electrical tests shall be performed, and oil samples for dissolved gas analysis shall be taken,both before and after this test.
The supplier shall submit to NGC details of how the test will be conducted.
The three criteria which must all be satisfied for the CT to pass the test are:
A1 The results of the routine electrical tests, performed before and after the chopped impulse test,are the same within the error specification for the test field.
A2 No evidence of degradation is found when the CT is dismantled and examined after the test.
A3 Any increases in the DGA levels are within the limits listed below.
Dissolved Gas Allowable increase after 3 days (ppm)
Hydrogen (H2) 5
Methane (CH4) 3
Ethane (C2H6) 3
Ethylene (C2H4) 2
Acetylene (C2H2) no detectable increase
The application of this test to CTs which have an ERIP or SRBP condenser core shall be subjectto agreement between NGC and the supplier.
NGTS 3.2.4Issue 5
December 2003
Page 19
APPENDIX B
ADDITIONAL REQUIREMENTS FOR PROTECTION CLASS PX TRANSFORMERS
Within the scope of IEC 60044-1 paragraph 5 additional requirements may be specified for certainprotective systems. The specification and tests for Class PX transformers was addressed in BS 3938.This document was withdrawn in June 1998. The following amendment has been tabled by theUnited Kingdom BSI PEL 38 Instrument Transformer Technical Committee for inclusion IEC 60044-1addressing these requirements.
The numbering of this section is identical to the submission made to IEC. When the amendment has beenincorporated into IEC 60044-1 this document will be revised.
B1.1 Scope
Modify 5th paragraph
For certain protective systems, ........resonant earthed networks), additional requirements aregiven in Clause 14 for class PX transformers.
After 5th paragraph add
Clause 14 covers the requirements and tests in addition to those in clauses 3 to 10 that arenecessary for current transformers for use with electrical protective relays, and in particular forforms of protection for which knowledge of the transformer secondary excitation characteristic,secondary winding resistance, secondary burden resistance and turns ratio is sufficient to assessits performance in relation to the protective relay system with which it is to be used.
B1.2 Normative references
Add
44-6 (1992) :instrument transformers, Part 6 : Requirements for protective current transformersfor transient performance
B2 Definitions
B2.1 General definitions
Add
B2.1.32 rated resistive burden (Rb) : For definition see IEC Publication 60044-6 Clause 3.11.
B2.1.33 secondary winding resistance (Rct) : For definition see IEC Publication 60044-6Clause 3.12.
B2.3 Additional definitions for protective current transformers.
B2.3.10 Excitation characteristic : A graphical or tabular presentation of the relationship between ther.m.s value of the exciting current and a sinusoidal r.m.s e.m.f applied to the secondaryterminals of a current transformer, the primary and other windings being open circuited, over arange of values sufficient to define the characteristics from low levels of excitation up to the ratedknee point e.m.f.
B2.3.12 Rated knee point e.m.f (Ek) : That minimum sinusoidal e.m.f. (r.m.s) at rated power frequencywhen applied to the secondary terminals of the transformer, all other terminals being open-circuited, which when increased by 10% causes the r.m.s exciting current to increase by no morethan 50%.
Note: - The actual knee point e.m.f will be � the rated knee point e.m.f.
NGTS 3.2.4Issue 5
December 2003
Page 20
B2.3.13 Rated turns ratio : The required ratio of the number of primary turns to the number of secondaryturns eg
Example 1: 1/ 600 (one primary turn with six hundred secondary turns)
Example 2: 2/1200 (a current transformer of similar ratio to example 1 but employing twoprimary turns).
B2.3.14 Turns ratio error: The difference between the rated and actual turns ratios. expressed as apercentage.
Turns ratio error (%) = (actual turns ratio - rated turns ratio) × 100rated turns ratio
B6 Classification of tests
B6.1 Type tests
Modify as follows :
(f) determination of errors (see 11.4 and/or 12.4, 11.6, 12.5, 14.3)
B6.2 Routine tests
Modify as follows :
(d) power-frequency withstand test on secondary winding ( see 8.3 or 14.4.4);
(e) power-frequency withstand tests, between sections ( see 8.3 or 14.4.4 );
(f) inter-turn over voltage test (see 8.4 or 14.4.5);
(g) determination of errors (see 11.5 and/or 12.4, 11.6, 12.6, 14.4)
B10.2 Rating plate markings
Modify as follows :
(e) The rated output and the corresponding accuracy class, together with additionalinformation specified in the later parts of these recommendations (see 11.7 and/or 12.7,13.8, 14.5).
B14 Additional requirements for Class PX protective current transformers
B14.1 Specification of performance for Class PX protective current transformers:
The performance of class PX current transformers shall be specified in terms of the following:
(a) rated primary current (Ipn)
(b) rated secondary current (Isn)
(c) rated turns ratio. The turns ratio error shall not exceed ± 0.25%
(d) rated knee point e.m.f. (Ek)
(e) maximum exciting current (Ie) at the rated knee point e.m.f. and / or at a statedpercentage thereof
(f) maximum resistance of the secondary winding at a temperature of 75°C (Rct)
NGTS 3.2.4Issue 5
December 2003
Page 21
(g) rated resistive burden (Rb)
(h) dimensioning factor (Kx)
Note - The rated knee point e.m.f. is generally determined as follows:
� � snbctxk IRRKE ����
B14.2 Insulation requirements for class PX protective current transformers.
B14.2.1 Insulation requirements for secondary winding
The secondary winding insulation of class PX current transformers having a rated knee pointvoltage Ek ≥ 2 kV shall be capable of withstanding a rated power frequency withstand voltageof 5 kV r.m.s for 60 s. For Ek < 2 kV the withstand voltage shall be 3 kV r.m.s for 60 s.
B14.2.2 Inter-turn insulation requirements
For Class PX transformers having a rated knee point e.m.f of 450 V or less the rated withstandvoltage for inter-turn insulation shall be 4.5 kV peak. For those with a rated knee point e.m.f ofgreater than 450V, the rated withstand voltage for the inter-turn insulation shall be a peakvoltage of 10 times the r.m.s value of the specified knee point e.m.f, or 10 kV peak, whicheveris the lower. Note: For some EHV transmission systems a higher limiting value of peak voltagemay be agreed between the manufacturer and the purchaser.
B14.3 Type tests for class PX protective current transformers
Class PX current transformers shall in addition to the requirements of clause 7 be tested asbelow.
B14.3.1 Proof of low reactance type
An inspection of drawings shall be made in accordance with the requirements of IECPublication 60044-6 Clause 7.3.1 a) in order to establish proof of low leakage reactance design.If compliance with the requirements of low leakage reactance design cannot be established tothe mutual satisfaction of the manufacturer and purchaser by reference to drawings then thecomposite error shall be determined for the complete secondary winding using either of thedirect methods of test given in Appendix A Clause A.5 or A.6 of this document, at a secondarycurrent of Kx. Isn and with a secondary burden Rb. Proof of low leakage reactance design shallbe considered to have been established if the value of composite error from the direct methodof test is less than 1.1times that deduced from the secondary excitation characteristic.
Note - The value of primary current required to perform direct composite error tests on certaintransformer types may be beyond the capability of facilities normally provided by manufacturers.Tests at lower levels of primary current may be agreed between the manufacturer and purchaser.
B14.4 Routine tests for class PX protective current transformers
Class PX current transformers shall in addition to the requirements of clause 8 be tested asbelow:
B14.4.1 Rated knee point e.m.f. (Ek) and maximum exciting current (Ie)
A sinusoidal e.m.f. of rated frequency equal to the rated knee-point e.m.f. shall be applied to thecomplete secondary winding, all other windings being open-circuited and the exciting currentmeasured.
NGTS 3.2.4Issue 5
December 2003
Page 22
The e.m.f. shall then be increased by 10% and the exciting current shall not increase by morethan 50%. All measurement shall be performed using r.m.s. measuring instruments. Due to thenon sinusoidal nature of the measured quantities the measurements should be performed usingr.m.s measuring instruments having a crest factor ≥3.
The excitation characteristic shall be plotted at least up to the rated knee point e.m.f. Theexciting current (I'e) at the rated knee-point e.m.f. and at any stated percentage, shall not exceedthe rated value. The number of measurement points shall be agreed between the manufacturerand the purchaser.
B14.4.2 Secondary winding resistance (Rct)
The resistance of the complete secondary winding shall be measured. The value obtained whencorrected to 75°C shall not exceed the specified value.
B14.4.3 Turns ratio error ( t)
The turns ratio shall be determined in accordance with IEC publication 60044-6 Annex E. Theturns ratio error shall not exceed the value given in Clause 14.1 (c).
Note - A simplified test involving measurement of the ratio error with zero connected burden maybe substituted by agreement between the manufacturer and purchaser.
B14.4.4 Insulation tests
Tests shall be performed to demonstrate compliance with Clause 14.2.1 . For test method referto Clause 8.3.
B14.4.5 Inter-turn insulation tests
Tests shall be performed to demonstrate compliance with Clause 14.2.2. For test methodrefer to Clause 8.4
B14.5 Marking of rating plate of Class PX current transformers
B14.5.1 Principal marking : See Clauses 10.2.
B14.5.2 Special marking
(a) rated turns ratio
(b) rated knee point e.m.f. (Ek)
(c) maximum exciting current (Ie) at the rated knee point e.m.f. and/or at the statedpercentage thereof.
(d) maximum resistance of the complete secondary winding at a temperature of 75°C (Rct)
The following may also be required by the purchaser:
(e) dimensioning factor (Kx)
(f) rated resistive burden (Rb)
RECORD OF REVISION
DOCUMENT NO: NGTS 3.2.4
ISSUE NO: 5
This issue has been revised and amended as follows:
DATE DETAILS OF REVISION AUTHORISATION
December 2003 Editorial changes