OMSI Façade Technical Catalogue Structural Glazing System Dear Our Valued Customer, When you search an innovative solution for your projects'….. Join OMSI Façade. OMSI
Customer Support: 0109497777
c
1- Definition and Description.
The system consists from four sides structural glazing curtain wall with mullion and
transom width of 52 mm with overall depth of (145,120 mm) which can
accommodate design loads with inner supporting frame work and outer pre-glazed
panels.
Also, it can be used with horizontal cover caps or with vertical cover caps.
2- System Components:
2.1. The overall frame Work:
Sections are made of aluminum alloy extruded profiles. The mullions profiles to be
either free standing supported to the floor and the upper slab or to be continues and
supported to the building slabs using a special deigned aluminum or steel brackets to
transfer the loads from the framework to the building structural elements. The
transoms' depth is to be the same mullion depth or smaller and to be assembled to
the mullions using aluminum connection and stainless steel fixation screws. All the
transoms should be of overlap type to enhance the system performance towards air
infiltration and water penetration.
2.1.1. Three different loads to be taken into considerations during structural
calculations preparation (dead loads, wind loads and thermal actions).
Technical Specifications
Structural Glazing Curtain Wall system SG 52
Dd
Customer Support: 0109497777
2.2 Glazing manufacturing.
Two ways of manufacturing insulated glaze are used:
1st: by using double glazing material "polysulphide".
2nd: by using outer panels sections.
2.2.1. 1st using double glazing material "polysulphide"
A18 mm air gap "spacer" is used between a two 6 mm panes. The glaze unit is then
sealed on the edge by using polysulphide to prevent humid outside air from entering
the unit. Polysulphide provides an adhesive with greater tightness and it has
excellent resistance to fuels, ozone, salt water and sunlight. Glaze unit fixation to the
frame work will be by inserting the aluminum profile "clip holder" into the
polysulphide while manufacturing to be hold by another aluminum profile
"restraining clip holder" into the inner frame work.
2.2.2. 2nd using outer panels' sections.
The pre-assembled, pre-glazed outer panels to be made of aluminum extruded
profiles and an insulating or single glass layer. The panels should be fixed to the inner
frame work using multi-point fixation supports with a calculated quantity according
to various design loads. The joints between outer panels were designed to be 18 mm
width a 12 mm air gap “spacer” is used to be inserted in.
For the two mentioned methods, the projects consultant can choose between 2
types of joints:
Dry glazing joint using EPDM rubber gasket.
Wet sealing joint using approved weather seal silicone.
The type of panels, either to be vision panels to see through or to be spandrel panels
in front of slabs and up-stands.
Customer Support: 0109497777
2.3.1. Glazing Properties:
The glazing shall be of top quality, float tinted or reflective type and without any
manufacturing defects according to Egyptian standard ES353 & ES354, according to
the following characteristics:
Glaze thickness: as shown in project specs.
Glaze color: as described in project specs.
U Value (ISO) of (varies per glass type) W/m2.K
Solar energy reflection: as required……..%
Solar energy transmission: as required……%
Daylight reflection: as required……. %
Daylight transmission: as required……..%
2.3.2 Insulated glass vision panel (IG units):
Consists of 2 panes of glaze determined by project's specifications with intermediate
air gap of 18 mm.
IG units need not to use the same type of glaze. Tempered and annealed glaze can
be used at the same units. If one of the panes is reflective or tinted glaze, it must
face the exterior.
If reflective glaze the mirror face to be towards interior. It may be necessary to
temper one of the panes to protect against thermal breaking.
The benefits of having GL units can be summarized as follows:
Heat loss for double glazing will be double in single glazing.
Draughts through vision panels caused by sinking cooled will be less.
Reduce the outside noise.
Reduce the condensation for the internal glaze pane.
Increases the re-sale value of the property.
Saving on energy bills.
Customer Support: 0109497777
2.3.3. Spandrel glaze panels (SG units):
Spandrel glaze is not specially a type of glaze, but it refers to the use of obscure glaze
in non-vision areas of a building.
One of these areas is the spandrel of a building. The spandrel is the part of a building
between the head of one window and the sill of the window above it. For aesthetic
reason, this area is often covered with glaze.
Several methods can be used to make spandrel glaze. One of them is using a colored
ceramic paint called a "Frit" to one surface of the glaze. In this case the glaze must
be either tempered or heat strengthened because the frit causes the glaze to absorb
heat. If reflective glaze is used s a spandrel application, the back surface must be
obscured visible under certain light conditions. Also, in this case we have to use an
insulating material between glaze and building face. Usually, we can use rock wool
insulation with certain thickness ad density can be specified by project specifications.
2.3.4. Operable panels:
In case of operable panels existence. The panels should be of the top hung projected
out type with a stainless steel balancing arms and a special handle mechanism with
transmission angles to allow multi-locking points.
2.4. Glass Bonding:
The glass pane must be fixed to the pre-assembled panel frame using 3M-VHB tape.
The innovative 3M-VHB tape is two-sided pressure sensitive adhesive acrylic foam
tape designed to bond glass to metal frames in glass curtain walling systems. Each
application will be reviewed on project specific bases. Application guidelines will be
based upon adhesion test results generated by 3M technical service. These project
specific application guidelines must be followed during the glass bonding process.
2.4.1. The distinctive advantages of using 3M-VHB tape are:
Reliability Granted:
20 Years warranty for qualifying applications.
Bonds with excellent dynamic strength to replace wet glazing.
Resistance for environmental conditions such as UV, moisture, heat and cold.
Customer Support: 0109497777
Viscoelasticity absorbs shock and allows movements for reliability against
wind, vibrations and thermal expansion or contraction.
Simplified application to save time and materials.
Speed assembly and delivery.
Bonds on contact with no drying, fixturing and liquid mess.
Saving the time, labor and material of spacer tape, gasketing, masking and
clean-up.
Eliminates the time and testing of 2-parts systems for glaze/butterfly, snap
time and mix ratio.
Eye appeal from a distance and even up close from both inside and outside.
Clean edge lines.
Tape bonds, seals and conforms to a variety of surfaces.
Color remains constant from one end to the other.
No color change as seen between structural silicone and spacer tape or
gasket.
2.4.2. 3M-VHB-Tape Design guidelines.
For tape area calculations the following guidelines can be used.
Dynamic Loads.
For dynamic tensile or sheer loads (such as wind-loads), a design strength of 12
psi (85kPa) is used for 3M-VHB Structural Glazing Tape. This design strength
provides a safety factor of at least 5 and was established based on material
property testing as well as ASTM dynamic load testing for curtain wall
applications.
Static Loads.
For static tensile or sheer loads (such as dead weight loads, snow loads and other
long-term loads), a design strength of 0.25 psi (1.7kPa) is used for 3M-VHB
Structural Glazing Tape. This means 4 square inches of 3M-VHB Structural Glazing
Customer Support: 0109497777
Tape per one pound of load should be used to support static loads. These
guidelines provide a safety factor of at least 5.
2.4.3. 3M-VHB Product Information.
Adhesive:
High performance acrylic.
Adhesive Carrier:
Conformable close cell acrylic foam.
Thickness:
2.3 mm
Density:
720 kg/m3
Liner:
0.125mm polyethylene film
Peel strength:
350 N/100mm Stainless steel, ASTM D3330
Tensile strength:
480kPa – Aluminum T-block, ASTM D1002
Dynamic overlap shear strength:
450kPa- Stainless steel ASTM D1002
Static shear strength:
1000 g/0.5 sq. in. for 10000 min. at 220C
500 g/0.5 sq. in. for 10000 min at 930C
3. Material, finishing and qualities:
3.1. Materials:
All extruded aluminum profiles shall be 6063-T6 alloy and temper (ASTM
B-221 alloy G.S IOA-T5).
All fasteners, where exposed, shall be aluminum, stainless steel or plated
steel in accordance with ASTM A-164.
Customer Support: 0109497777
Perimeter anchors shall be aluminum or steel, providing the steel is
properly
Isolated from the aluminum.
Glazing gaskets shall be EPDM (see rubber gaskets specs.)
3.2. Finishing:
Powder coating for all aluminum parts shall be made of pure polyester
powder with film thickness 60 to 90 microns. Appropriate 8 stages, chromate
pretreatment should be carried out before applying powder coat.
3.3. Qualities:
All Steel products shall be hot galvanized.
All screws and bolts shall be made of stainless steel or chromate steel.
All the weather stripping or finishing gaskets shall be made of EPDM.
All the coupling and contracts between the aluminum components and other
materials shall be protected.
4. Execution:
4.1. Installation
All Jambs, head and sill track shall be set in correct locations as shown in
the shop drawings details and shall be level, square, plumb and in
alignment with other wok in accordance with the manufacturer's
installation instructions and approved shop drawings.
All joints between framing and the building structure shall be sealed in
order to secure a watertight installation.
4.2. Protection & Cleaning:
After installation, the general contractor shall adequately protect exposed
portions of aluminum surfaces from damage by grinding and polishing
compounds, plaster, lime acid, cement or other contaminants.
The General Contractor shall be responsible for final cleaning.
Customer Support: 0109497777
OMSI Façade Technical Catalogue
for System CW 52
Conventional Curtain Wall system
Structural Glazing System
Customer Support: 0109497777
Basic Elements Mullion profiles
Customer Support: 0109497777
Basic Elements Mullion design
Customer Support: 0109497777
Basic Elements Transom Design
Customer Support: 0109497777
Basic Elements Starting & Ending Mullion Design
Customer Support: 0109497777
Basic Elements Mullion & Transom Relation
Customer Support: 0109497777
Basic Elements Special Screws
Customer Support: 0109497777
Basic Elements Special screws
Customer Support: 0109497777
Basic Elements Gaskets Design
Customer Support: 0109497777
Basic Elements Transom Joint
Customer Support: 0109497777
Basic Elements Structure Frame
Customer Support: 0109497777
SGR (52-001) "L" Shape & "U" Shape
Customer Support: 0109497777
SGR ( 52-001) "L" Shape & "U" Shape
Customer Support: 0109497777
SGR ( 52-001) Mullion & Transom & Clip holder fixation
Customer Support: 0109497777
SGR (52-001) SGR (52-001) Perspective
Customer Support: 0109497777
SGR (52-001) SGR (52-001) Plan
Customer Support: 0109497777
SGT (52-002) "L" Shape & "U" Shape
Customer Support: 0109497777
SGT (52-002) "L" Shape & "U" Shape
Customer Support: 0109497777
SGT (52-002) SGT (52-002) Plan
Customer Support: 0109497777
Curtain wall System Plan
Customer Support: 0109497777
Curtain Wall System Plan
Customer Support: 0109497777
Curtain Wall System Plan
Customer Support: 0109497777