Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
PUBLIC WORKS DEPARTMENTBUILDINGS
OFFICE OF THE ENGINEER-IN-CHIEF (BUILDINGS), CHIEF ENGINEER (BUILDINGS) CHENNAI REGION AND
CHIEF ENGINEER (GENERAL), PWD., CHEPAUK, CHENNAI – 5
GUIDELINES FOR PLANNING, DESIGN AND CONSTRUCTION OF BUILDINGS
WITH RESPECT TOFIRE, EARTHQUAKE, CYCLONE, FLOOD, TSUNAMI AND OTHER HAZARDS
MAP OF EARTHQUAKE ZONES IN TAMIL NADU
Tamilaga Arasu Building Research Station, PWD, Taramani, Chennai-600 113
Zone - III Moderate Intensity Zone
Zone - II Low Intensity Zone
PUBLIC WORKS DEPARTMENT
BUILDINGS
OFFICE OF THE ENGINEER-IN-CHIEF (BUILDINGS) &
CHIEF ENGINEER (BUILDINGS) CHENNAI REGION AND
CHIEF ENGINEER (GENERAL), PWD.,
CHEPAUK, CHENNAI – 600 005
Technical Circular No. AEE/T10/24475/2017, dated 27.10.2017
Sub : Disaster Management - Guidelines for Planning,
Design and Construction of buildings with respect
to Fire, Earthquake, Cyclone, Flood, Tsunami and
other hazards-Regarding.
This circular is issued to all the Superintending Engineers and Executive Engineers
of Tamilnadu Public Works Department with Guidelines for Planning, Design and
Construction with respect to Fire, Earthquake, Tsunami, Cyclone, Flood and other
hazards.
Disaster prevention involves engineering intervention in buildings and structures
to make them strong enough to withstand natural hazard so that the exposure of the
society to hazard situation could be avoided or minimized.
Public Works department buildings organization is committed to Plan, design,
construct and maintain the Public Buildings and monitor the stability of the public
buildings.
Various types of Public Buildings constructed and maintained by PWD include
Hospitals, Medical colleges, Schools, Hostel buildings, Court Buildings, District
Collectorates, Taluk Offices, Sub Registrar Offices, Veterinary Buildings and office
buildings for various other departments of the Government.
Every building shall be so Planned, Designed, Constructed, equipped, maintained
and operated so as to provide not only adequate comfort to the occupants but also to
take meticulous care to avoid undue danger to the life and safety of the occupants from
Fire, Earthquake, Tsunami, Cyclone, Flood and other hazards.
The public buildings are constructed based on the Codes published by the Bureauof Indian standards including the National Building code 201G. In Tamilnadu publicworks Department, the stability of the buildings and structures are ensured in Designand Construction with respect to Fire, Earthquake, Tsunami, cyclone, Flood and otherhazards.
Although the Architect wing and the Planning and Designs wing functioning underthe administrative control of the Engineer-in-Chief (Buildings) at Chennai are invotved inArchitectural planning and Structural Designing of the buildings respectively, it isinstructed that the superintending Engineers and Executive Engineers should also ensurethe provisions to be made during execution of building works with respect to Fire,Eafthquake, Tsunami, cyclone, Flood and other hazards, constructed based on the codespublished by the Bureau of Indian standards including the National Building code 2016.
Hence the enclosed general guidelines (as per various IS Codes and Guidelinesissued by Ministries of Government of India) are issued through this circularmemorandum for Architects and all Engineers of Public Works Department with respectto engineering intervention in buildings.
Hence, through this circular memorandum, it is instructed that all the officials ofPublic works Department are requested to adhere to general guidelines enclosed forDisaster preparedness to withstand hazards effectively.
Enc!.: Booklet-1No.
r1-..'*"{ril1,,
IO
The Chief Engineer (Buildings), pWTrichy Region, Trichy
The Chief Engineer (Buildings), pWD.,Madurai Region, Madurai
AII the Superintending Engineers of pWD, BO.
All the Executive Engineers of pWD, BO.
D:\DISASTERMANAGEMENT\Final CIRCUtARANDIETTER3l.08.20lT\FinatOflnat\Di*stermanaSementcircularfinal3l0820lT.docx
PUBLIC WORKS DEPARTMENT BUILDINGS
OFFICE OF THE ENGINEER-IN-CHIEF (BUILDINGS),
CHIEF ENGINEER (BUILDINGS) CHENNAI REGION AND CHIEF ENGINEER (GENERAL), PWD., CHEPAUK, CHENNAI – 5
GUIDELINES FOR
PLANNING, DESIGN AND CONSTRUCTION OF BUILDINGS
WITH RESPECT TO
FIRE, EARTHQUAKE, CYCLONE, FLOOD, TSUNAMI AND OTHER HAZARDS
2017
Tamilaga Arasu Building Research Station, Taramani, Chennai.113
Guidelines for Planning, Design and Construction of buildings with
respect to Fire, Earthquake, Cyclone, Flood, Tsunami and other hazards
CONTENTS
Sl.
No. Topics Page No
1
Guidelines for Fire and Life safety Measures
1
2
Guidelines for Planning Earthquake resistant Structures
5
3
Guidelines for Planning Earthquake resistant Structural
Designs
8
4
Guidelines for planning and design of Tsunami resistant
buildings
14
5
Guidelines for Planning and Design of Cyclone resistant
buildings
18
6
Guidelines for Planning and Design of Flood resistant
buildings
25
7
Fire preparedness : extract of “ 15 maintenance of fire
fighting systems ” as in NBC VOL 2 Chapter 12
27
8
Case Study on Fire Safety Arrangements in Tamil Nadu
Government Multi Specialty Hospital, Chennai and RGGH
Chennai
30
9
Case Study on Pre Tsunamy Cyclone Shelters and Post
Tsunami Multi Purpose Evacuation Centres
43
10
Multipurpose Evacuation Shelters – 121 Nos. in 12 Coastal
Districts of Tamilnadu
49
11
District Level PWD contact person during the period of
Disaster
52
12
Disaster Hazard Specific Response Actions in Buildings
54
1. Guidelines for Fire and Life Safety Measures in Buildings
1
1. Guidelines for Fire and Life Safety Measures in Buildings
The guidelines to be followed in Fire and Life safety in the buildings as per
Part IV of NBC 2016 are furnished below.
1.0. General Exit Requirement:
1.0.1. Every building meant for human occupancy shall be provided with exits
sufficient to permit safe egress of occupants, in case of fire or other
emergency.
1.0.2. Provision of internal staircase, external staircase and corridor or
passageway which have direct access to these staircases shall be
maintained by occupants in case of emergencies and shall lead to the
exterior of a building or to a street. Lifts and escalators shall not be
considered as exits.
1.0.3. All buildings shall have a minimum of two staircases. The actual
number of exits shall conform to the accepted standards on the basis
of occupant load of building (Floor area in m2 required for a
person), for different occupancies, width required per person and the
maximum travel distance to be maintained in a building.
1.0.4. In general indicative terms, the occupant load will be 12.5 for
residential occupancies, 15 for institutional, 4 for educational, 10 for
office buildings, 0.65 to 1.80 for assembly, 3 for basement shopping
area and 6 for upper floor shopping area in mercantile buildings. The
travel distances to the nearest exits for all multistoried, special
commercial, institutional and public buildings shall be of 30 m and for
fully sprinklered building, the travel distances may be increased up to
45m
1.0.5. All the exits and exit passageways to exit discharge shall have a clear
ceiling height of at least 2.40m . The height of exit door shall be at
least 2.00m
2
1.0.6. Exit doorways shall not be less than 1 m in width but for assembly
buildings it shall not be less than 2 m in width.
Fig.1
1.0.7. The minimum width of tread without nosing shall be 250 mm for internal
staircase of residential buildings. This shall be 300 mm for assembly,
hotels, educational, institutional, business and other buildings. The
treads shall be constructed and maintained in a manner to prevent
slipping. The maximum height of riser shall be 190 mm for residential
buildings and 150 mm for other buildings and the number shall be
limited to 15 per flight.
1.0.8. Internal staircase shall not be arranged round a lift shaft.
1.0.9. The internal staircases shall be constructed with non combustible
materials and shall have a minimum fire resistant rating of
120minutes ; The external stairs shall be directly connecting all floors
to the ground; it shall be continuous, free of obstructions and the
entrance to the external stairs shall be separate and remote from the
internal staircase.
1.0.10. The ramps shall comply requirements for staircases regarding enclosure
dimension and capacity. The slope of the ramp shall not exceed 1 in
12 (8 percent)
3
1.0.11. Smoke Control: In building design compartmentation plays a vital role
in limiting spread of fire. The building plan should ensure avoidance of
spread of smoke to adjacent spaces. through leakage openings. All floors
shall be compartmented with area of ach compartment being not more
than 750 m2.
1.0.12. Pressurization is a method adopted for protecting the exits from
ingress of smoke, especially in high-rise buildings. In pressurization,
air is injected into the staircases, lobbies, etc, as applicable, to raise
their pressures lightly above the pressure in adjacent parts of the
building. As a result, ingress of smoke or toxic gases into the exits will
be prevented. The pressurization of staircases and lift lobbies shall be
adopted as per standards.
The following are the other safety arrangements to be provided in
buildings.
1.1. The fire detection and alarm systems include electro mechanical
systems, such as air handling units, pressurisation systems, smoke
management systems, creation of compartmentation through the release of
fire barriers, hold up fire doors etc and monitoring of fire water storage
tanks and pumps, pressures in hydrant and sprinkler systems etc. These
systems should be provided as per standards.
1.2. The voice evacuation systems shall employ Tamil and English using
pre recorded messages and integrate with fire alarm panels for alerting the
zone of fire and surrounding zones / floors.
1.3. Fire Extinguishers/Fixed Fire Fighting Installations: All buildings
depending upon the occupancy use and height shall be protected by fire
extinguishers, wet riser, down-comer, automatic sprinkler installation,
high/medium velocity water spray, foam, gaseous or dry powder system in
accordance with the provisions of the NBC 2016
1.4. A satisfactory supply of water for the purpose of fire fighting shall
always be available in the form of underground/ terrace level static storage
4
tanks with capacities specified. The minimum water supply requirement is
specified in Table.7 of NBC2016
1.5. Automatic sprinklers shall be installed in the false ceiling voids exceeding
800mm in height. The pressure in sprinkler system shall not exceed 12
bars.
1.6. Refuge area measuring to an extent of 15 sq. m shall be provided as a
staging area and secured place for effecting rescue of occupants for all
Multi-storey Building expecting residential occupancy where balcony is
provided. To ensue life safety more stringent, refuge area shall also be –
provided in the Commercial Special Building where is no sufficient near and
side setback even though it is less than 24 m in height.
1.7. Fire preparedness : extract of “ 15 maintenance of fire fighting systems ”
as in NBC VOL 2 Chapter 12 is enclosed in Chapter 7. Case Studies on Fire
and Life Safety measure are enclosed in Chapter 8.
5
2. Guidelines for Earthquake Resistant Structures
2.0. The following are the Guidelines to be considered in planning Earthquake Resistant Structures.
2.1. Earthquake causes shaking of the ground. Therefore a building resting on it
will experience motion at its base. Even though the base of the building
moves with the ground, the roof has a tendency to stay in its original
position. But since the walls and columns are connected to it, they drag the
roof along with them. The inertia force experienced by the roof is
transferred to the ground via the columns, causing forces in columns and in
other members.
2.2. The behaviour of a building during earthquakes depends critically on its
overall shape, size and geometry, in addition to how the earthquake forces
are carried to the ground. Hence, at the planning stage itself, the
unfavourable features should be avoided
2.3. In general, buildings with simple geometry in plan have performed well
during strong earthquakes. Buildings with re-entrant corners, like those U,
V, H and + shaped in plan have sustained significant damage. Many times,
the bad effects of these interior corners in the plan of buildings are avoided
by making the buildings in two parts. For example, an L-shaped plan can be
broken up into two rectangular plan shapes using a separation joint at the
junction A building is said to be earthquake-resistant, if it possesses four
main attributes, namely,
1) Simple and regular structural configuration,
2) At least a minimum initial lateral stiffness,
3) At least a minimum lateral strength, and
4) Adequate ductility.
2.4. Buildings with simple regular geometry and uniformly distributed mass and
stiffness in plan and in elevation, suffer much less damage, than buildings
with irregular configurations.
2.5. The following simple illustrations show how to plan for earthquake resistant
structures
6
The following simple illustrations show how to plan for earthquake resistant
Fig.2
The following simple illustrations show how to plan for earthquake resistant
7
Fig.3
Tamil Nadu falls under Zone II and Zone III Seismic zones as per IS
1893 part 1 :2016
8
3. Guidelines for Earthquake resistant Structural Designs.
3.1. IS 1893: (Part 1) 2016 code of practice for Earthquake Resistant Design of Structures deals with the earthquake hazard assessment for
earthquake - resistant design of buildings. Bureau of Indian Standards, based on the past seismic history, grouped the country into four seismic zones, viz. Zone-II, -III, -IV and –V.
Zone II Low intensity zone
Zone III Moderate intensity zone
Zone IV Severe intensity zone
Zone V Very severe intensity zone
The state of Tamil Nadu lies in Zone II & III as illustrated in the following map.
SEISMIC ZONES OF TAMIL NADU (AS PER IS 1893, PART 1:2016)
Zone - III Chennai, Coimbatore, Kalpakkam, Kancheepuram,
Tiruvannamalai, Vellore & Salem etc.
Zone - II
Cuddalore, Thanjavur, Tiruchirappali & Madurai etc.
Fig.4
9
3.2. As stated in IS 1893: (Part 1) 2016 Chennai, Coimbatore, Kalpakkam,
Kancheepuram, Tiruvannamalai, Vellore, Salem etc are some of the places
under Zone III of moderate intensity of earthquake. The places including
Madurai, Cuddalore, Thanjavur, Tiruchirapalli, etc are under Zone II of Low
intensity of Earthquake.
3.3. Importance Factor: If the building is required to function for life-safety
purposes after an earthquake or its failure could impair the continued
operation of the facility, a factor called Importance Factor is assigned in
the structural design calculations. Importance factor is used in estimating
lateral design force in seismic structural design and this provision shall
enhance the structural stability at the time of earthquake.
3.4. As per seismic code IS 1893: (Part 1) 2016 importance factor for residences
is changed to 1.2 from 1.0. Further in this code it is recommended to adopt
appropriate importance factors for a maximum value of 1.5 for various
types of buildings. However a higher value of 1.8 is adopted as per the
instructions given in the Guidelines for design and construction of Cyclone/
Tsunami Shelters issued by Government of India – UNDP Disaster risk
management programme, Ministry of home affairs -2006.
3.5. Due to this higher important factor of 1.8, the buildings constructed for
Tsunami shelter sizes of beams and columns were increased. The area of
steel provided is arrived for the worst load combinations of seismic and
wind loads.
3.6. IS 13920 :2016, code of practice for Ductile Design and Detail
covers the requirements for designing and detailing of members of
reinforced concrete (RC) structures designed to resist lateral effects of
earthquake shaking, so as to give them adequate stiffness, strength and
ductility to resist severe earthquake shaking without collapse.
3.7. The criteria adopted by codes for fixing the level of design, seismic loading
are generally as below
� Structures should be able to resist minor earthquake without damage.
� Structures should be able to resist moderate earthquake without structures damage, but with some non-structural damage.
� Structures should be able to resist major earthquake without collapse
but with some structural & non-structural damage.
10
The following illustrations show ductile detailing for reinforcement bars in RCC Constructions.
Fig.5
Fig.6
Fig.7
11
Fig.8
Fig.9
Fig.10
12
Fig.11
Fig.12
Fig.13
>20 db
13
Fig.14
Fig.15
14
4. Guidelines for Planning and Design of Tsunami resistant buildings
4.0. The general guidelines for planning of Tsunami Resistant Buildings are given
below.
4.1. The tsunami waves always approach from the direction of sea towards the
coast. It is known that the tsunami forces can even be ten times larger than
the maximum earthquake or cyclonic wind pressures. It will therefore
require a very heavy wall structure in the lower stories of the building to
make it safe against tsunami impacts. The kinds of actions created on the
building are shown in Figure below.
Fig.16
ACTION ON STRUCTURE DUE TO TSUNAMIS
Minimize Tsunami Wave Pressures
4.2. Buildings constructed on reinforced stilt columns should have sufficient
clearance under the building superstructure, such that the tsunami wave
will be able to pass though, exerting only the minimum pressures on the
columns
4.3. For further reduction in such hydrodynamic pressures, the columns may be
made circular, octagonal or square with chamfered/rounded corners. The
15
risers in stairs should be left open for water to pass through. The exterior
walls of the structure may be shaped in a manner to deflect the wave
energy sideways. Suitable gaps between a cluster of buildings, will allow the
wave to pass through, thus decreasing the pressure on the structures.
Fig.17
STRUCTURE ON STILTS
Provide Collapsible Structural Obstructions
4.4. Buildings may be built with infill/cladding wall panels which would break
easily and give way to the tsunami wave to pass through.
Provide Coastal Protection Wall 4.5. Coastal protection walls may be constructed by which the wave water will
be deflected back towards the sea. (Fig 17). The walls may be curved
concavely towards the sea in vertical or the horizontal plane. Needless to
say that the walls will have to be designed for the resulting very large
reactive forces.
4.6. The presence of vegetation (mangroves) is also a coastal protection
measure and acts to some extent as a buffer to the tsunami wave action.
Fig.17
BLOCKING WALLS FOR DEFLECTION OF TSUNAMI
16
Provide Break Waters
4.7. On the coastal side of the building, appropriate energy dissipation blocks of
concrete or stone may be arranged as is done under the canal falls or the
spill way dams which will dissipate the energy of the fast moving waters of
the tsunami so that the impact on the building elements will be minimized
to safe level.
Fig.18
WAVE BREAKERS FOR SLOWING SPEED OF WAVES
Evacuation of Population
4.8. Evacuation of people could be effected by vertical evacuation through raised
platforms with proper staircase approach, or into upper floors of multistorey
buildings, or to platforms constructed at high enough elevation as part of
elevated water towers, or by creating safe areas at higher elevations
provided with easy and direct approach to the nearby communities. The
design approach for structures to be used for evacuation purpose should be
chosen suitably for the sites under consideration.
Fig.19
VERTICAL EVACUATION
17
Fig.20
Table I
18
5. Guidelines for Planning and Design of Cyclone resistant buildings
5.0. The following are the guidelines for Planning Cyclone Resistant Buildings
5.1. The buildings are pulled apart by winds moving swiftly around and over the
building. This lowers the pressure on the outside and creates suction on the
walls and roof. Therefore the buildings are to be planned and designed
considering these aspects of wind force and pressure.
The following illustrations show actions of wind forces
Fig.21
Fig.22
19
Fig.23
Fig.24
5.2. Guidelines for improving the cyclonic resistance of Low rise houses
and other buildings/ structures are furnished in IS 15498:2004
a) As far as possible, the building shall be founded on good ground. Part of the
building on good ground and partly on made up ground shall be avoided
[see. Fig 25.a ].
b) Regular plan shapes are preferred. Reentrant corners are to be avoided
c) For individual buildings, a circular or polygonal plan is preferred over
rectangular or square plans but from the view point of functional efficiency,
often a rectangular plan is commonly used. Where most prevalent wind
direction is known, a building should be so oriented, where feasible, that its
smallest facade faces the wind.
d) A symmetrical building with a compact plan-form is more stable than an
asymmetrical building with a zig-zag plan, having empty pockets as the
latter is more prone to wind/cyclone related damage [see Fig. 25 c]
20
Fig.25
e) In case of construction of group of buildings with a row type or cluster
arrangement, cluster arrangement can be followed in preference to row
type. However, in certain cases, both may give rise to adverse wind
pressure due to tunnel action and studies need to be conducted to look into
this aspect
f) Long walls having length in excess of 3.5 m shall be provided with cross
walls or integrated pilasters
21
g) Buildings are not to be located in low-lying areas as cyclones are invariably
associated with floods.
h) In hilly regions, construction along ridges should be avoided since they
experience an accentuation of wind velocity whereas valleys experience
lower speeds in general
i) Except in case of buildings with large span with sloped roofs, roof pitches
having a slope less than I in 3 shall be avoided.
j) The percent of the total opening in the cross section of the frontal wall shall
be less than 50 percent of the width of the wall. Opening in load bearing
walls should not be within a distance of h/6 from the inner corner for the
purpose o providing lateral support to cross walls, where h is the storey
height up to eave level.(Fig 26)
Fig.26
5.3. Further regarding the door, window openings and glazing the following are
to be considered
a) If doors & shutters cannot be shut, make sure there are opposing
openings to reduce pressure build up. Trees can be planted around the
buildings
22
b) Since failure of any door or window on windward side may lead to
adverse upward pressure. The doors and windows should have adequate
anchorage with holdfasts.
c) Large size Glass paneling result in more damages. Panel sizes may be
well designed with smaller sizes. Thin plastic films can be pasted to glass
panels for holding debris in case of breaking due to wind forces. A
metallic fabric mesh outside large panels can prevent damages. (Fig 27)
Fig.27
5.4. Guidelines for Designing Cyclone Resistant Buildings considering
wind forces
5.4.1. The design criteria for wind loads can be considered along with design
criteria for Earth quake so that the design is economical considering all
the forces.
5.4.2. The cyclone shelters now constructed in PWD are renamed as
Emergency shelters to be used during all the natural disasters such as
Tsunami, Cyclone, Flood etc and also continue to be used throughout the
year as a school or community hall..
23
Design for Wind loads:
5.4.3. The calculations for wind pressure and design forces on various
structural members can be done as per IS 875 part 3 :2015. The
Basic wind speed differ for different regions as per Wind speed map
published in the code. (Refer the map enclosed). The Wind velocity
can be adopted as 65 miles/second (250km/ hour) with normal load
factors for areas on east coast as per the Design Criteria for the
Construction of Cyclone Shelters issued by the Ministry of Home Affairs,
Government of India
5.4.4. As per the above code the following parameters are considered for
different types of structural members of various types of buildings for
calculating wind pressures and design forces. Data: Wind Zone, Terrain
category
5.4.5. Design Factors: Risk coefficient factor, Terrain and Height factor,
Topography factor, importance factor for cyclone region, Wind
directionality factor, Area averaging factor, Tributary area of short wall,
Tributary area of long walls, Tributary area of roof, Permeability of the
buildings, internal pressure, External pressure etc
24
BASIC WIND SPEED MAP OF INDIA
Fig.28
AS PER IS 875 PART 3 2015
25
6. Guidelines for Planning and Design of Flood resistant buildings
6.0. The following are the guidelines to be followed for Planning and Designing of Flood Resistant Buildings.
6.1. The estimation of flood, maximaum flood level etc are done by the Water
Resources department. The Local GovernmentS impose development
control rules so that the premises of the buildings are located in a proper
orientation to face the flood situation. The following are to be considered
during the planning and design f the individual buildings which come under
the purview of the PWD Engineers.
6.2. Rising the elevation: The elevation of living area should be above the
base flood elevation (B. F. E.). There should be enough space for the
passage of flow in case of flood. For an area with a low probability of flood
the space below the living area can be utilized for parking the vehicle,
laundry or bathroom etc. The B. F. E. is the water surface level for a flood
of 100 years return period.
6.3. Building the lower levels water tight: The walls and openings of the
lower levels are sealed to stop the water from penetrating the house. The
sealing should be sufficiently strong to bear the forces in the flood
conditions acting in the form of lateral forces and uplift thrust of the flood
water. The building for such purpose should be designed by taking all these
forces in consideration. Enclosures, sealants, membranes and coatings can
be used to make the lower levels watertight.
6.4. Wet flood proofing: Wet flood proofing involves the controlled and safe
passage of flood water through the lower levels of the building.
6.5. The rain water harvesting arrangements for the building and the
premises should be well designed and well maintained.
6.6. The sewers and water supply system should be above the water level
or should be sealed when the water rises above them to avoid any health
hazards.
6.7. Electrical appliances and outlets should also be at higher levels. The
inlets points should be opened well before any pileup of water to avoid
pressure at the structure.
26
Fig.29
Fig.30
Illustrations showing the elevation of living area above the base flood elevation (B. F. E.). and the suggested rain water percolation in car parking area
and the lawn
27
7. FIRE PREPAREDNESS : EXTRACT OF “ 15 MAINTENANCE OF FIRE
FIGHTING SYSTEMS ” AS IN NBC VOL 2 CHAPTER 12
7.1. Maintenance of fire detection and suppression systems in any facility is a
very important task for the facility manager. All owners shall arrange to
deploy adequate number of trained people to man the systems and also
ensure adequate budgetary support to enable proper maintenance and
upkeep of the systems.
7.2. Besides properly maintaining all systems, such as fire detectors, sprinklers,
first aid fire equipment, yard hydrants, fire tanks, fire pumps, etc, it is
imperative that all fire exits and staircases are kept free from any form of
obstruction to allow easy egress of occupants in case of any fire incident.
7.3. At the time of commissioning of any facility proper testing of all fire
detection and suppression systems shall be done in accordance with
relevant Indian Standards and proper record of same shal be maintained.
Wherever lift lobbies, staircases, lift wells or any other such location has
been designed to remain under pressure from firefighting point of view it is
imperative that necessary pressure fans, etc, are kept properly maintained
so that there is no failure in this regard. Security guards/lift operators shall
be guided to ensure that, wherever doors have been provided to maintain
differential pressures are closed to ensure proper functioning.
7.4. Similarly smoke extraction fans, fire dampers in HVAC systems shall be
periodically (at least a fortnightly check is desirable) run and tested to
ensure that they function properly in case of any emergency.
7.5. The facility manager shall hold regular mock firefighting drills so that
people are made aware of thesystems installed, the location of nearest
exits, etc.
7.6. Maintenance of fire extinguishers shall be carried out in accordance with
the good practice [12(6)]. Periodic inspection, testing and refilling shall be
got done from competent and trained persons as per provisions given
in the above mentioned good practice and as per recommendations of the
manufacturers.
28
7.7. Proper records of this activity shall be maintained. All fire detection
systems shall be strictly maintained in accordance with the good practice
[12(7)]. Facility manager shall ensure that during any fit out or
refurbishment, no detector is subjected to any interior decoration
treatment such as painting, alteration of exterior cover to conform to the
environment.
7.8. A log book should be maintained for recording details, including causes of
all the alarms (genuine, test or false), faults service tests and routine
inspections, servicing/repairs, etc, as and when done. Period of
disconnection/non-operation should also be shown.
7.9. Checks shall be made every day to ascertain that the fire panel indicates
normal operation and if not, then any fault indicated should be recorded in
a log book and corrective action taken and record of that should also be
maintained. It shall be ensured that any fault warning recorded the
previous day has received attention. The control panel shall be manned
regularly so that in case of any incident, immediate action can be initiated.
7.10. Success of any firefighting system will depend upon timely and proper
functioning of the fire pumps. Regular maintenance of these pumps shall
be done in accordance with the good practice [12(8)]. Checking of jockey
pumps shall be a daily exercise. Adequate stock of diesel shall be
maintained in a safe location to ensure that pumps can be operated for
design duration.
7.11. Other fire installations such as external fire hydrants, hose reels, etc, shall
be checked periodically and shall be maintained. External fire hydrants
shall be inspected, checked and maintained in accordance with the good
practice [12(9)]. Internal fire hydrants and hose reels on premises shall be
maintained in accordance with the good practice [12(10)]. Automatic
sprinkler system shall be maintained in accordance with the good practice
[12(11)].
29
Fire Water Reservoirs/Tank
7.12. It shall be ensured that fire water tank reservoirs are always full and free
from any foreign materials. The water level shall be recorded weekly.
Reservoirs shall be cleaned at least once in a year or more frequently
depending upon quality of water and sludge formation shall be prevented.
Records of inspection, testing and maintenance operations and reports
of hydraulic pressure tests of extinguishers and other equipment shall be
maintained as per history sheet.
7.13. All maintenance operations shall be carried out as a well-planned exercise
to ensure that the facility is not subjected to unnecessary risk.
a) In case of planned shut down:
a. Authorities shall be kept informed before shutting of the installation
for any reason, whatsoever.
b. A thorough assessment of the risk shall be undertaken before a part
or total shut down to ensure that there is no incident of fire during
shut down.
c. The heads of all the departments, tenants, RWAs shall be notified in
writing that the installation shall remain inoperative and they shall
exercise abundant caution during the period.
b) In case of unplanned shut down . When the installation is rendered
inoperative as a matter of urgency or by accident, the measures stated
above for planned shutdown shall be implemented with least possible delay.
Fire Drills
7.14. Carrying out regular and periodic fire drills, at intervals as may be
prescribed, is essential to ensure reparedness of personnel and testing
of equipment to ensure that all systems function smoothly in case of any
exigency.
7.15. All assets used for firefighting and fire prevention can be equipped with
sensors. These sensors shall be capable of monitoring the health of the
equipment. Sensors should log the status and send to the central database
at monitoring station or BMS, where provided.
7.16. Staircases, fire exits, refuge areas, passages, open surroundings inside or
outside the premises should be kept clear of goods.
30
8.1. CASE STUDY
ON
FIRE SAFETY ARRANGEMENTS IN
TAMILNADU GOVERNMENT MULTI SUPER SPECIALTY
HOSPITAL,
OMANDURAR GOVERNMENT ESTATE,
CHENNAI - 600 002
31
TamilNadu Government Multi Super Specialty Hospital,
Omandurar Government Estate,
Chennai - 600 002 GENERAL DETAILS
1 Name of the Building and Address
TamilNadu Government Multi Super
Specialty Hospital,
Omandurar Government Estate,
Chennai - 600 002
a. Plot area 83,000 Sq.mtrs
b. Total No. of floors with floor area
Total Floor area Ground + 6 floors
i. Basement Nil
ii. Ground floor 17455 Sq.mtrs
iii. Mezzanine, I Nil
iv. Floors ( 1st - 6th floor ) 68964 Sq.mtrs
c. Height of Building ( in meters) 30.60 mtrs
d. Entrance ( width ) Drive way entry - 5.10 mtrs
Building Entry - 4.20 mtrs
e. Approach road (width) 7.20 mtrs
2 Occupancy / Use Hospital
3 Parking areas 5500 Sq.mtrs
4 Fire resistance of construction materials
Stair case and Electrical rooms are provided
with Fire rated doors a. Self closing fire / smoke check doors
b. Partitions Aluminium, Brick wall, Gypsum Board
Partitions
c. False ceiling Gypsum board false ceiling and Metal False
ceiling
d. lining for air-conditioning ducts Available
e. Insulation for air-conditioning ducts Available
f. Panelling Wooden wall paneling in Conference hall in
Ground floor & Third floor
g. Surface finishes Floor finish - Granite & Marble
Walls - Plastic Emulsion Paint
32
5 Compartmentation Considered in the original plan of the
building
6 Ventilation Natural lighting through OTS covered with
Skylight Glazing Units
7 Means of Entry Staircases, Lift
8 Means of Escape Through staircases, Emergency exit points
at 10 locations
9 Electrical Insulations FRLS & PVC Insulated wires
10 Alternate lighting arrangements UPS &Generators available
11 Rooms air-conditioners Proper rated voltage stabilizers provided
12 Drainage Underground Drains through sewer pipe
lines
33
Details of the building to be shown to the inspection team from Tamil Nadu Fire and Rescue Services
1 Description of the Building and Address
TamilNadu Government Multi Super
Specialty Hospital,
Omandurar Government Estate,
Chennai - 600 002
a. No. of floors with each floor in
Sq.mts
Ground + 6 floors
Ground floor - 17455
First floor - 11274
Second floor - 11061
Third floor - 10137
Fourth floor - 11061
fifth floor - 12595
Sixth floor - 12836
b(i) No. of staircase with width of each
staircase 17 Nos of staircase of width 4.00 mtrs
b(ii)
No. of lifts and capacity of each,
availability of service staircase,
service lift etc. Should be
mentioned
17 Numbers of lift and 1 number of service
lift
c.
No. of rooms and halls at each
floor along with the nature of
occupancy
Varies from 85 rooms to 110 rooms at each
floor
d. Canteen details if any 2 nos of canteen (1 each at Ground floor &
Third floor )
2 Total occupancy As per bed strength
3 No. of HP machinery installed 10 Numbers
4 Details of Generators, if any provided
a. H.P / K.V of generator 200 KVA LT Generators 2 nos
250 KVA LT Generators 2 nos
b. Quantity of diesel, furnace oil
stored 990 Litrs
c. Whether proper licence obtained
for such storage Not required
5 Nature of Air-Conditioner system in the
premises Chilled water air conditioning system
6
Extent of site and set back around the
building on all for directions ( to be
specified separately
1. North side - 80 mtrs
2. South side - 12 mtrs
3. East side - 12 mtrs
4. West side - 7.50 mtrs
7
Whether Automatic fire detectors / fire
alarms installed
Provided to be modified according to
converted plan
34
8 Lightining protections Provided to be modified according to
converted plan
9 Fire protection and Alarm system Provided to be modified according to
converted plan
10 Water supply ( Well / Bore pumps, wate
mains etc.,) Metro water
11 Fire pumps (Total Nos) 3 Nos + 1 No. (Alternate diesel pump)
12 Wet riser down corner & Hydrant
systems & automatic sprinkler system.
Wet riser - 13 Nos
Hydrant - 109 Nos @ 30m interval
Automatic sprinkler system in all floors
13 Hose reel & Hose box Hose reel - 96 Nos & Hose box - 96 Nos
each @ every 1000 m2
14 Portable fire extinguishers ABC type - 6kg - 93 Nos
Co2 Type - 4.5 kg - 14 Nos
Co2 type - 22.50 kg - 7 Nos
15 Fire lift with separate generator To be provided
16 Storage or Diesel / Oil / LPG To be provided
17 Communication system
a. Public Address System available
b. Inter Communication System available
c. Illuminated Signs available
18
Maintenance of fire protection installation
equipments ( by whom )
Public works department
19 Fire fighting training to staff -
20 Details of licences issued No
21
No. of fire lifts available and their
location
As in item 1(b)
22
Whether any alternative power supply is
available for fire lifts, emergency lights
and pumps of wet riser ( their rated
capacity)
Alternate diesel pump is available for wet
riser
23
Whether safety officer available round
the clock and if so, whether his
subordinates are trained by local fire
services
Yes
24
Whether fire drill has been conducted
and joint evacuation drill has been
conducted by the security officer and the
local fire officer
Joint evacuation drill has been conducted
during October 2016 along with fire
department officials
26
Details of present inspections to comply
table 3 in part IV of NBC of India 1983
As below
35
a. Wet riser 13 Nos
b. Hose reel 96 Nos
c. Details of hoses 182 Nos
d. extinguishers - their nos and
capacity
ABC type - 6kg - 93 Nos
Co2 Type - 4.5 kg - 14 Nos
Co2 type - 22.50 kg - 7 Nos
e. Hydrants 109 Nos
f. Sprinklers
Available in all floor ( Temporarily suspended
)
g.
water supply details such as
Underground Tank / or terrace
tank
Fire Sump - 5.00 lakh litres capacity
h. Fire buckets with stand Nil
27
Whether copy of approved plan of the
building is enclosed
No
FIRE FIGHTING SYSTEM ARRANGEMENTS IN TAMILNADU GOVERNMENT
MULTI SUPER SPECIALTY HOSPITAL AT OMANDURAR GOVERNMENT ESTATE, CHENNAI – 600 002
Sl.No. DESCRIPTION AS PER TAMILNADU
FIRE & RESCUE SERVICE NORMS
AVAILABLE
1 WET RISER FOR EVERY 1000 M2 - 1
No. 91 Nos @
1000m2/each
2 FIRE FIGHTING UG SUMP 150000 Litres 500000 Litres
3 TERRACE OHT 20000 Litres 55000 Litres
4 FIRE FIGHTING UG SUMP -
MOTOR 2280 LPM 4550 LPM
5 ALTERNATE DIESEL PUMP 2280 LPM 4550 LPM
6 JOCKEY PUMP 180 LPM 10.80 m3/s
7 FIRE SERVICE INLET To be provided
provided with NRV (4 ways) near
Omandurar Estate
Metro Station
8 HOSE ASSEMBLY Every 1000 m2 30m length of 20mm dia hose provided at
every 1000m2
9 YARD HYDRANT Every 30m interval 13 Nos Yard Hydrant
provided at 30m
interval
36
10 FIRE ALARMS To be Provided at all
floors
Existing in all floors
(Usage Temporarily suspended)
11 AUTOMATIC DETECTION SYSTEM
To be Provided at all floors
Existing in all floors (Usage Temporarily
suspended)
12 AUTOMATIC SPRINKLER
SYSTEM
To be Provided at all
floors
Existing in all floors (Usage Temporarily
suspended)
13 PUBLIC ADDRESS SYSTEM To be Provided at all
floors Provided in all floors
14 ALTERNATE INDEPENDENT
POWER SYSTEM To be Provided
Generator system with Diesel is
provided
15 RAMP FOR EXIT Ramp in 1:10 at Exit
point
2 Ramps in 1:10 slope provided at exit
points
16 RAMP WIDTH 2.10 2.10
17
EXIT STAIRCASE WITH
AUTOMATIC SELF CLOSING FIRE CHECK DOORS
To be provided
Provided at all
staircases and Electrical rooms
18 MINIMUM WIDTH OF
CORRIDOR 2.40 3.00
19 MANIFOLD Isolated Isolated from
Hospital
20 CAR PARKING Covered car parking with
automatic sprinkler system to be provided
Open car parking
system
21 OPEn SPACE AROUND THE BUILDING
7.00 m minimum - 7.50 m
22 WIDTH OF MAIN GATE 4.50 m 7.00 m
23 EXIT STAIRCASE WIDTH 2.00 m 4.00 m
24 LOUVERED WINDOWS 2 2
25 PERIODICAL MAINTENACE Should be done
maintained by well
experienced fire fighting contractors
26 REGULAR MOCK DRILL Every 6 months Every 6 months
27 FIRE SERVICE LIFT Separate 1 No. Outside
the building Not available
37
CO2
22.50 Kg
CO2
4.50 Kg
ABC
6Kg
1 GROUND FLOOR 1 11 13 13 13 13
2 FIRST FLOOR 1 - 10 13 13 13
3 SECOND FLOOR 1 - 14 13 13 13
4 THIRD FLOOR 1 - 14 13 13 13
5 FOURTH FLOOR 1 - 14 13 13 13
6 FIFTH FLOOR 1 - 14 13 13 13
7 SIXTH FLOOR 1 - 14 13 13 13
8 LAWN - - - 13 1 4
9 DRIVE WAY - - - 5 5 5
TOTAL 7 11 93 96 96 13 96 1 4
HOSE
REEL
DRUM
FOURWAY
FIRE
BRIGADE
UNIT
WATER
MONITOR
FIRE FIGHTING SYSTEM ARRANGEMENTS IN TAMILNADU GOVERNMENT MULTI SUPER SPECIALTY
HOSPITAL AT OMANDURAR GOVERNMENT ESTATE, CHENNAI - 02
AVAILABLE FIRE FIGHTING SYSTEM ARRANGEMENTS
FIRE EXTINGUISHER
Sl.No. LOCATION
WET RISER
WITH
HYDRANT
VALVE
HOSE
REEL BOX
YARD
HYDRANT
38
8.2. CASE STUDY
ON
FIRE SAFETY ARRANGEMENTS IN
RAJIV GANDHI GOVERNMENT GENERAL HOSPITAL,
CHENNAI-3
39
FIRE FIGHTING SYSTEM ARRANGEMENTS IN RAJIV GANDHI GOVERNMENT GENERAL
HOSPITAL, CHENNAI - 03
AVAILABLE FIRE FIGHTING SYSTEM ARRANGEMENTS –Tower Block 1
Sl.
No. LOCATION
Fire
Extinguisher WET
RISER
WITH
HYDRANT
VALVE
HOSE
REEL
BOX
YARD
HYDRANT
HOSE
REEL
DRUM
FOURWAY
FIRE
BRIGADE
UNIT
CO2
4.50
Kg
DCP
10KG
1 GROUND FLOOR 1 8 4 4 4
2 FIRST FLOOR 1 8 4 4 4
3 SECOND FLOOR 1 8 4 4 4
4 THIRD FLOOR 1 8 4 4 4
5 FOURTH FLOOR 1 8 4 4 4
6 FIFTH FLOOR 1 8 4 4 4
7 SIXTH FLOOR 1 8 4 4 4
8 BASEMENT 1 8 4 4 1 4 1
Total 8 64 32 32 1 32 1
FIRE FIGHTING SYSTEM ARRANGEMENTS IN RAJIV GANDHI GOVERNMENT
GENERAL HOSPITAL, CHENNAI – 03
AVAILABLE FIRE FIGHTING SYSTEM ARRANGEMENTS in Tower Block II
Sl.
No. LOCATION
Fire
Extinguisher
WET
RISE
R
WITH
HYDR
ANT
VALV
E
HOSE
REEL
BOX
YARD
HYDRA
NT
HOSE
REEL
DRUM
FOURWA
Y FIRE
BRIGAD
E UNIT
CO2
4.50 Kg
DCP
10KG 1 GROUND FLOOR 1 8 4 4 4
2 FIRST FLOOR 1 8 4 4 4
3 SECOND FLOOR 1 8 4 4 4
4 THIRD FLOOR 1 8 4 4 4
5 FOURTH FLOOR 1 8 4 4 4
6 FIFTH FLOOR 1 8 4 4 4
7 SIXTH FLOOR 1 8 4 4 4
8 BASEMENT 1 8 4 4 1 4 1
Total 8 64 32 32 1 32 1
40
FIRE FIGHTING SYSTEM ARRANGEMENTS IN RAJIV GANDHI GOVERNMENT
GENERAL HOSPITAL, CHENNAI - 03
AVAILABLE FIRE EXTINGUISHERS
Sl. No. LOCATION
DCP
5KG
I SPECIALITY BLOCK
1 GROUND FLOOR 2
2 FIRST FLOOR 2
3 SECOND FLOOR 2
4 THIRD FLOOR 2
5 FOURTH FLOOR 2
6 FIFTH FLOOR 2
7 SIXTH FLOOR 2
II BIR BLOCK
1 GROUND FLOOR 1
2 FIRST FLOOR 1
III PSYCHIATRY BLOCK
1 GROUND FLOOR 1
2 FIRST FLOOR 1
IV STD BLOCK
1 GROUND FLOOR 1
2 FIRST FLOOR 1
3 SECOND FLOOR 1
V CARDIO THORACIC
1 GROUND FLOOR 1
2 FIRST FLOOR 1
3 SECOND FLOOR 1
4 THIRD FLOOR 1
5 FOURTH FLOOR 1
6 FIFTH FLOOR 1
7 SIXTH FLOOR 1
8 SEVENTH FLOOR 1
VI CARDIOLOGY BLOCK
1 GROUND FLOOR 1
2 FIRST FLOOR 1
3 SECOND FLOOR 1
4 THIRD FLOOR 1
5 FOURTH FLOOR 1
41
6 FIFTH FLOOR 1
7 SIXTH FLOOR 1
8 SEVENTH FLOOR 1
VII NEUROLOGY BLOCK
1 GROUND FLOOR 1
2 FIRST FLOOR 1
3 SECOND FLOOR 1
4 THIRD FLOOR 1
5 FOURTH FLOOR 1
6 FIFTH FLOOR 1
7 SIXTH FLOOR 1
VIII SURGICAL BLOCK
1 GROUND FLOOR 1
2 FIRST FLOOR 1
3 SECOND FLOOR 1
IX ORTHO BLOCK
1 GROUND FLOOR 1
2 FIRST FLOOR 1
3 SECOND FLOOR 1
4 THIRD FLOOR 1
TOTAL 51
FIRE FIGHTING SYSTEM ARRANGEMENTS IN RAJIV GANDHI GOVERNMENT
GENERAL HOSPITAL, CHENNAI - 03
Sl.
No. DESCRIPTION
AS PER
TAMILNADU FIRE
& RESCUE
SERVICE NORMS
AVAILABLE
Tower block I Tower block
II
1 WET RISER
FOR EVERY 1000 M2
-
1 No.
32 Nos @ 1000
/m2/each
32 Nos @ 1000
/m2/each
2 FIRE FIGHTING UG
SUMP 150000 Litres
279000
lites
279000
lites
3 TERRACE OHT 20000 Litres 60000
litres
60000
litres
4 FIRE FIGHTING UG
SUMP - MOTOR 2280 LPM YES YES
5 ALTERNATE DIESEL
PUMP 2280 LPM YES
6 JOCKEY PUMP 180 LPM
42
7 FIRE SERVICE INLET To be provided 1 To be
provided
8 YARD HYDRANT Every 30m
interval 1 1
9 FIRE ALARMS To be Provided
at all floors
available
available
10 AUTOMATIC
DETECTION SYSTEM
To be Provided at
all floors
available
available
11 AUTOMATIC
SPRINKLER SYSTEM
To be Provided at all
floors Not avaiable Not avaiable
12 PUBLIC ADDRESS
SYSTEM
To be Provided at
all floors
available
available
13
ALTERNATE
INDEPENDENT
POWER SYSTEM
To be Provided Gen set
available
Gen set
available
14 RAMP FOR EXIT Ramp in 1:10
at Exit point
Ramp in 1:10
at Exit point
Ramp in 1:10
at Exit point
15 RAMP WIDTH 2.10 2.10 2.10
16
EXIT STAIRCASE
WITH AUTOMATIC
SELF CLOSING FIRE
CHECK DOORS
To be provided Not avaiable Not avaiable
17 MINIMUM WIDTH OF
CORRIDOR 2.40 3.00 3.00
18 MANIFOLD Isolated Isolated from
Hospital NIL
19 OPEn SPACE AROUND
THE BUILDING 7.00 m 7.40 7.40
20 WIDTH OF MAIN
GATE 4.50 m 5 5
21 EXIT STAIRCASE
WIDTH 2.00 m 4 4
22 LOUVERED WINDOWS 2 6 6
23 REGULAR MOCK
DRILL Every 6 months
Every
6 months
Every
6 months
24 FIRE SERVICE LIFT Separate 1 No.
Outside the building To be Provided To be Provided
43
9. A CASE STUDY OF PRE TSUNAMY CYCLONE SHELTERS AND POST
TSUNAMI CONSTRUCTION OF NEW MULT PURPOSE EVACUATION
SHELTERS
PRE DISASTER ARRANGEMENTS IN EMERGENCY CYCLONE SHELTERS
9.1. During the Tsunami in 2004 there were existing 123 cyclone shelters. Those
buildings were constructed during the period 1979 to 1991 along the
coastal Districts of Tamil Nadu to provide safe shelter for the large number
of people in the coastal area. The available Cyclone shelters were in
circular shape and could be used only during emergency periods like
Cyclone, Tsunami etc.
9.2. For 114 cyclone shelters repair and renovation works for an amount of
Rs.251 Lakhs were carried out under Emergency Tsunami Reconstruction
Project
PICTURE OF OLD TYPE CYCLONE SHELTERS AFTER REHABILITATION
9.3. These shelters could not be utilized during normal periods for any
community functions as the shape of the building is not suitable for such
purposes and are in remote places Those existing Cyclone Shelters were not
used due to following reasons
1. There was limited capacity in Cyclone Shelters and these facilities could
not provide shelter to everyone in a community.
44
2. Cyclone Shelters could not permit pets due to limited ability to cater for
pets and people in the same space pet owners will need to identify, early
in their cyclone planning, other arrangements for sheltering their pets.
3. Cyclone shelters could not have enough space for bedding and personal
goods – as it takes up valuable floor space.
4. Cyclone Shelters would be used to accommodate as many people as is
possible in the available space and most people had to be seated in a
chair and would not be able to lie or sit on a mattress or stretcher. Older
adults and children were unlikely to be able to fall asleep in a shelter.
5. Cyclone Shelters were not intended to be evacuation centres or recovery
centres that were established only to provide relief services and housing
over an extended period for people whose houses were damaged or
destroyed during the event. When the Cyclone had passed persons
sheltering in the building would be directed elsewhere.
6. Cyclone Shelters would become cramped, crowded, noisy, smelly with
no privacy.
7. Cyclone Shelters were established as a safe place away from the
habitation in an elevated area.
POST DISASTER APPROACH IN CONSTRUCTING NEW MULT PURPOSE EVACUATION SHELTER
9.4. From the lessons learnt from the relief operations during the 2004 Tsunami
a new approach was evolved with the following aspects.
• Assessment of need:
People living very close to the sea and are vulnerable to the damages
caused by frequent natural disaster flood , storm , Tsunami etc.
Community consultations were made.
• Identification of site:
1. The Government of Tamil Nadu had under taken field visit to study
and find out villages / settlements where people do not have access to
safe shelters within a radius of 1.5 km free from natural barriers.
45
2. Based on the findings 145 villages have been identified tentatively,
these location have brrn conformed or changes suggested by the
consultants as applicable.
3. Government or Poromboke land is prepared for Shelter construction to
avoid social issues such as land acquisition and resettlement.
Construction of 121 Multipurpose evacuation shelters in 12 coastal districts of Tamil Nadu under CDRRP with world bank assistance
9.5. Instead of Constructing shelters solely as a refugee camp during Tsunami,
Construction of Permanent Multipurpose Evacuation Shelters shall serve the
people at all times. Considering this it was proposed to construct the
following buildings in 12 coastal districts to a cost of Rs.294.24 crores
9.6. Some of such Permanent Multipurpose Evacuation Shelters are constructed
as 500 People Capacity School Building, 1000 People Capacity School
Building, 1000 People Capacity Community Hall Building, 2000 People
Capacity Community Hall Building, 3000 People Capacity Community Hall
Building, PHC Waiting Hall, Fisheries Staff Training Institute.
9.7. Generally the following features can be seen in a typical
Multipurpose Evacuation Shelter
Plinth area: Ground floor - 724.00 Sq.m
First floor - 724.00 Sq.m
Total Area - 1448.00Sq.m
Ground floor Stilt floor for cattle accommodation.
First floor-Carpet area – 409.69 Sq.m
Area required for one person - 1.00 Sq.m
No. of persons can be accommodated - 410 Nos.
Terrace floor- Helipad arrangement
(with free access area of 564 Sq.m)
SPECIAL FEATURES:-
� Easy approach. Accommodation - 410 persons (409.69 Sq.m.)
� Kitchen, Store pantry. - 76.19 Sq.m.
46
� Dispensary - 23.00 Sq.m.
� Separate Internal and external water supply Arrangements.
� Separate Internal and external Sanitary Arrangements.
� Separate Internal and external Electrification Arrangements.
� One Generator Set.
� Ramp for disabled and Children.
� With standing Severe Cyclones, earthquakes, inundation, floods,
Tsunami etc.,
� Easy approach
DESIGN CRITERIA:-
� Strom surge level at the site is 3.00m above ground level.
� The proposed basement level is 1.50m above the ground level.
� It is proposed to provide STILT FLOOR.
� STILT FLOOR on the ground floor can be used by providing
temporary partitions of concrete benches.
� Rain water harvesting is done for providing water supply during
cyclone storm surge period.
� RCC frames with non load bearing wall laterally supported by filler
walls and deeper foundation on elevated ground to avoid submerge
of main building during Cyclone.
9.8. Setting up Maintenance arrangements:
Formation of Shelter Management Committee is under process by SIRD.
9.9. Construction, certification and hand over
The completed MEPS as School building has building has been handed over
to the Education Department and the Community Hall building has been
handed over to the Town Panchayat .
The School building key will be with the Head Master and the Community
Hall building key will be with the Panchayat President or the convenient
person with the knowledge of the president it could be kept with the care
taking team. No others will be allowed to keep the key with them
47
A SCHOOL BUILDING IN THOOTHUKUDI DISTRICT
A COMMUNITY HALL BUILDING IN CUDDALORE DISTRICT
48
9.10. . Action plan for the future management of Multipurpose Evacuation
Shelters
After formation of Shelter Management Committee , the completed
Multipurpose Evacuation Shelters may be used as follows.
During any calamities or any disaster the information will be passed
through the Public Administration System will be operated from here.
Monthly Village Restoration Committee meeting will be held.
Emergency meetings in the village like Panchayat meetings will be
conducted.
By considering the development of the children’s education evening
tuition centre will be conducted with the concern of Shelter
Management Committee.
Weekly Self Help Group meeting will be conducted.
Seed could be stored if needed during unavoidable situation with the
concern of Shelter Management Committee.
Community function like marriage function, marriage reception, Birth
day celebration, Ear ring celebration, could be performed.
Government meetings could be conducted . No political, religion and
caste related meetings or gatherings could be conducted.
A separate Register will be maintained for recording the visitors , the
chief guest and the programs performed.
49
10. MULTI PURPOSE EVACUATION SHELTERS - 121 NOS. IN 12 COASTAL
DISTRICTS OF TAMILNADU
Sl.
No. Name of Place Type of Building
Thiruvallur District
1 Thirupalaivanam II (Pulicat [Jameelabath] ) Community Hall (1000)
2 Andarmadam(Pulicat [Kottaikuppam]) Community Hall (2000)
3 Pallipalayam(Annamalaichery) School Building (500)
4 Elavoor - 1 (Sunnambukulam) School Building (500)
5 Elavoor - 2 (Methipalayam ) Community Hall (1000)
Kancheepuram District
6 Uthandi School Building(500)
7 Nemmeli School Building(1000)
8 Pattipulam School Building(500)
9 Sholinganallur School Building(1000)
10 Kanathur Community Hall(1000)
Villupuram District
11 Bommaiyarpalayam School Building(500)
12 Marakkanam North [Alagankuppam] School Building(500)
13 Kottakuppam School Building(1000)
14 Kottaikuppam Madura/
PeriyamudaliyarchavadiBommaiyarpalayam [Pillai
Chavady)
School Building(500)
15 Mandavaipudukuppam School Building(500)
16 Marakkanam South [Ekkairkuppam] Community Hall(1000)
17 Panichamedu Community Hall(1000)
18 Anumandaikuppam School Building(500)
19 Chettinagar School Building(500)
20 Nochikuppam Community Hall(2000)
21 Keelputhupattu School Building(500)
22 Pudupattinam Community Hall(1000)
Koonimedukuppam Community Hall(1000)
Cuddalore District
23 Pachayankuppam H/O Sothikuppam School Building(1000)
24 Kudikadu H/O Eachankadu Community Hall(1000)
25 Thiyagavalli Community Hall(1000)
26 Thiyagavalli [Madurai Naickenpettai] Community Hall(1000)
27 Thirunaraiyur Community Hall(2000)
28 Keezhakundalavadi Community Hall(1000)
29 Ambikapuram Community Hall(1000)
30 Veerankoilthittu Community Hall(1000)
31 Killai [North] Kozhaiayru Community Hall(1000)
32 Pinnathur [East] Community Hall(2000)
33 Thillaividangan [South] Community Hall(1000)
34 Killai [North] MGR Thittu Community Hall(1000)
35 Parangipettai Community Hall(2000)
36 PunjaiMagathuvaizhaikai Community Hall(2000)
Nagapattinam District
37 Pachayankuppam H/O Sothikuppam School Building(1000)
38 Kudikadu H/O Eachankadu Community Hall(1000)
39 Thiyagavalli Community Hall(1000)
50
40 Thiyagavalli [Madurai Naickenpettai] Community Hall(1000)
41 Thirunaraiyur Community Hall(2000)
42 Keezhakundalavadi Community Hall(1000)
43 Ambikapuram Community Hall(1000)
44 Veerankoilthittu Community Hall(1000)
45 Killai [North] Kozhaiayru Community Hall(1000)
Thiruvarur District
46 Jambuvanodai Community Hall(1000)
47 Idumbavanam School Building(1000)
48 ThillaiVizhagam Community Hall(1000)
49 Karpaganatherkulam Community Hall(2000)
50 Thondiayakadu Community Hall(2000)
51 Vilangadu Community Hall(1000)
Thanjavur District
52 Kuppathevan [SembianmadeviPattinam]/
Manthiripattinam
School Building(500)
53 Thiruvathevan [Annanagarpudutheru] School Building(500)
54 Senthalaivayal School Building(500)
55 Thiruvathevan [Somanathapattinam] Community Hall(1000)
56 Vilangulam School Building(500)
57 Nadium / Pilliarthidal School Building(500)
58 Marakkavalasai School Building(500)
59 Karisavayal School Building(500)
60 Pudupattinam Community Hall(1000)
61 Kallivayal School Building(1000)
62 Rajamadam [Keezhathottam] School Building(500)
63 Kollakadu School Building(500)
64 Palanjur School Building(500)
65 Adirampattinam School Building(1000)
Pudukottai District
66 Pilliarthidal Community Hall(1000)
67 Manmelkudi Community Hall(1000)
68 Pariyamadaipaichal School Building(500)
69 Nattanipursakudi / R.Pudupattinam Community Hall(1000)
70 Kattumavadi [Alaganvayal] School Building(500)
71 Mumbalai School Building(500)
72 Mimisal Community Hall(1000)
73 Nattanipurasakidi / Muthukuda Community Hall(1000)
74 Avudaiyarpattinam Community Hall(1000)
75 Kottaipattinam School Building(500)
Ramanathapuram District
76 Muthuraghunathapuram [Pethanandal] School Building(500)
77 Iranian Valasai Community Hall(1000)
78 Therbogi Community Hall(1000)
79 AlagankulamPudikudiyiruppu School Building(500)
80 Mandapam School Building(1000)
81 Santhakonvalasai School Building(500)
82 Vedalai School Building(500)
83 Sundaramudaiyan School Building(500)
84 Pirappanvalasai School Building(1000)
85 Rameswaram [Natarajapuram] Community Hall(1000)
86 Rameswaram town -1 School Building(500)
87 Rameswaram south /Karaiyur School Building(1000)
88 Rameswaram / Sambai School Building(1000)
89 Pamban School Building(1000)
51
90 T. Mariyur School Building(500)
91 Keelamunthal Community Hall(1000)
92 Thiruppalaikudi/ Adanchari Community Hall(1000)
93 Kannirajapuram School Building(1000)
94 Kannigapuri Community Hall(1000)
95 Kalpar Community Hall(1000)
96 Earwadi School Building(1000)
97 Nambuthalai / Vadi Community Hall(2000)
98 Mullimunai Community Hall(1000)
Thoothukudi District
99 Vembar School Building(1000)
100 Siluvaipatti H/o Mappilaiyurani Community Hall(2000)
101 Kayalpattinam School Building(1000)
102 KeelaThiruchendur [Amali Nagar] School Building(1000)
103 Tharuvaikulam School Building(1000)
Tirunelveli District
104 Chettikulam School Building(500)
105 Karaisithuoveri Community Hall(2000)
106 Kuttam [Annanagar, Kuttapanai] Community Hall(1000)
107 Kuttam [Kuduthalai] School Building(500)
108 Vijayapathi @ Uvari Community Hall(2000)
109 Thiruvembalapuram @ Kootupuli Community Hall(3000)
Kanyakumari District
110 Kanniyakumari School Building(500)
111 Thengamputhur (Melamanakudi) PHC
112 Kadiapattinam-Muttom PHC
113 Periyavilai School Building(500)
114 Colachel School Building(1000)
115 Midalam School Building(500)
116 Pozhikarai / Rajakkamangalam PHC
117 Enayaputhanthurai / Kiliyur School Building(1000)
118 Ezhudesam/ Erayumanthurai School Building(500)
119 Poothurai School Building(500)
120 Kollencode / Vallavilai School Building(500)
121 Neerodi / Marthandanthurai PHC
52
11. District Level PWD contact person during the period of Disaster
Name of Division Office No
Executive Engineer, PWD., South Presidency Division, Chennai-5
044-28517520
Executive Engineer, PWD., North Presidency Division,
Chennai-5
044-28516568
Executive Engineer, PWD.,
Construction Division- I, Chennai-5
28410402 Ext-293
Executive Engineer, PWD., Buildings (C&M) Division, Tiruvellore
27661174
Executive Engineer, PWD., Buildings (C&M) Division,
Kancheepuram
27238672
Executive Engineer, PWD.,
Buildings (C&M) Division, Villupuram
04146-226793
Executive Engineer, PWD., Buildings (C&M) Division,
Cuddalore
04142-230274
Executive Engineer, PWD.,
Buildings (C&M) Division, Vellore
0416-2220113
Executive Engineer, PWD., Buildings (C&M) Division, Thiruvannamalai
04175-236068
Executive Engineer, PWD., Buildings (C&M) Division, Namakkal
04286-230966
Executive Engineer, PWD., Buildings (C&M) Division,
Salem
0427-2413116
Executive Engineer, PWD.,
Buildings (C&M) Division, Ariyalur
04329-224550
Executive Engineer, PWD., Buildings (C&M) Division,
Dharmapuri
04342-230161
Executive Engineer, PWD., Buildings (C&M) Division,
Erode
0424-2265650
Executive Engineer, PWD.,
Buildings (C&M) Division, Coimbatore
0422-2395521
Executive Engineer, PWD., Buildings (C&M) Division,
Karur
04324-231630
53
Name of Division Office No
Executive Engineer, PWD., Buildings (C&M) Division,
Ooty
0423-2450123
Executive Engineer, PWD.,
Buildings (C&M) Division, Trichy
0431-2771632
Executive Engineer, PWD., Buildings (C&M) Division,
Pudukottai
04322-221596
Executive Engineer, PWD.,
Buildings (C&M) Division, Thanjavur
04362-230323
Executive Engineer, PWD., Buildings (C&M) Division, Madurai
0452-2530718
Executive Engineer, PWD., Buildings (C&M) Division,
Ramnad
04567-230728
Executive Engineer, PWD.,
Buildings (C&M) Division, Dindigul
0451-2427432
Executive Engineer, PWD., Buildings (C&M) Division,
Theni
04546-260429
Executive Engineer, PWD.,
Buildings (C&M) Division, Tutucurin
0461-2325039
Executive Engineer, PWD., Buildings (C&M) Division, Tirunelveli
0462-2585555
Executive Engineer, PWD., Buildings (C&M) Division,
Virudhunagar
04562-244711
Executive Engineer, PWD.,
Buildings (C&M) Division, Nagercoil
04652-278330
54
12. DISASTER HAZARD SPECIFIC RESPONSE ACTIONS IN BUILDINGS
12.1. Introduction
Tamil Nadu Public Works Department Buildings wing provides the
framework for responding disasters such as Fire, Trapping inside elevator , Flood
inside building ,Cyclone/hurricane , evacuation disaster preparedness etc., that
may affect the in the building campus. It describe response actions that must be
taken during disaster It also provides life safety and emergency response actions
within the building. This is applicable during or immediately following disaster
within the building.
12.2. Fire
Fire safety and emergency action, BEFORE the fire:
i. Plan and practice escape routes inside building and campus
ii. Post emergency numbers near telephones.
iii. Review the printed "Guide to Using Portable Fire Extinguishers"
iv. Do not store combustible materials near a heat source, in hallways,
stairwells or exit paths.
v. Extension cords are for temporary needs only. Never run them under
carpets or anywhere they can be pinched or crushed.
vi. Do not overload electrical outlets by using plug extenders or multiple
power strips.
vii. Keep all electrical appliances away from anything that can catch fire.
Remember always to turn them off at the end of the day.
viii. Pay attention to housekeeping issues.
ix. Keep your work area neat and tidy and keep combustible such as paper
and trash to a minimum.
Fire safety and emergency action, DURING the fire:
i. Immediately notify the fire department and your co-workers by pulling
the fire alarm
ii. Use a fire extinguisher to extinguish the fire.
iii. Evacuate as quickly and as safely as possible.
iv. On your way out, warn others.
55
v. Close doors and windows if time permits, to delay the spread of the
smoke and fire.
vi. Feel closed doors for heat before opening.
vii. Do not open them if they are hot.
viii. Use the stairs to evacuate. Do not use elevators.
ix. If you encounter smoke, stay low to the ground. If possible, cover
mouth with a cloth to avoid inhaling smoke and gases.
x. Once outside, go to your building’s tell those in charge there that you
are out of the building,
xi. Report injured or trapped persons and any signs of building damage you
observed.
xii. Wait for instructions from emergency responders.
xiii. Do not re-enter the building until the all clear is given by emergency
responders.
xiv. If unable to leave the building, find a location away from the smoke and
heat where you can signal for firefighter assistance.
xv. Seal the room. Use wet cloth to stuff around cracks in doors and seal up
vents to protect against smoke.
xvi. Do not break windows. Flames and smoke can come back in from the
outside.
12.3. Flooding inside the building
i. Stop using electrical equipment.
ii. Never attempt to walk or drive through flood waters.
iii. Avoid areas where electricity is exposed or near water.
iv. Evacuate the building if necessary and proceed to your building’s
evacuation shelter
v. Call authorities concern for help
56
12.4. Earthquake
i. Stay indoors. Crawl under a table or desk or brace yourself by standing
in an interior doorway.
ii. Do not use elevators, electrical equipment or telephone.
iii. Do not use open flame.
iv. Be prepared for aftershocks.
12.5. High winds / hurricane attacks the building
i. Stay indoors.
ii. Move away from windows and open doors (preferably into an interior
hallway). If possible, move to the lowest level of the building.
iii. Do not use elevators, electrical equipment or telephone.
iv. Sit on the floor and cover your head with your arms to protect from
flying debris
12.6. Trapped in an elevator:
i. Use the emergency telephone inside the elevator to call for assistance.
ii. Press the elevator alarm inside the elevator to signal for help.
iii. Use your cell phone to inform others
12.7. Building Evacuation [Incidents occurring inside this building]
i. In the event of a sudden emergency, such as a fire, natural gas leak, or
hazardous materials spill within the building, all occupants may have to
evacuate.
ii. Building evacuation plans with evacuation routes highlighted are to be
posted throughout the building.
If an evacuation of the building is necessary:
• Pull the fire alarm inside the building for incidents
57
• Dial to official in charge of building and give details about the hazard
• Evacuate immediately.
• Close doors behind you and do not stop for belongings.
• Use stairways, not elevators.
• Evacuate to at least 50 feet from building and remain there until
accounted for.
• Attempt to account for everyone in the department.
• Do not re-enter the building until fire department officials, or other
designated safety personnel communicate that it is safe to return.
• User department officials should determine whether employees should
seek shelter in another facility or leave campus.
12.8. Shelter in place
1. A situation may occur at the safest action will be to shelter in place.
2. Situations such as cyclones/hurricanes, floods falls on building may
cause departmental officials to give a shelter.
3. When a shelter given, the following steps should be taken:
4. Do not leave the building. Find a safe place within the building to stay
and wait for further information. 5. For which the Government of Tamil Nadu constructed evacuation
shelters on the sea shore areas throughout state.
6. Wait for the "all clear" to be given before leaving safe shelter
12.9. Communications
1. When an emergency or disaster is announced, or if building occupants
are alerted to an emergency, all building occupants should notify others in the area. Emergency personnel should be notified.
2. In coordination with the building coordinator, all occupants should
ensure that the appropriate protective action (evacuation, shelter in place, etc.) is communicated as much as possible.
3. User departments should maintain a call roster of all people so that
they may contact them later.
58
4. The building coordinator, in coordination with emergency officials and department heads, will make the determination to take proactive action.
5. The majority of communications during an emergency or disaster incident in the building will be face-to-face.
12.10. Emergency Preparedness of occupants of the buildings
1. Emergency preparedness is the responsibility of every department, member, staff member and every one inside the building.
2. Actively participate in fire safety training including fire extinguisher training and fire evacuation drills
3. Become familiar with your work areas and building.
4. Pay attention to the location of fire evacuation maps, fire extinguishers, fire alarm pull stations, and other fire and life safety equipment in the building.
5. Recognize potential fire hazards and report them immediately.
6. Keep your work areas clean and free of debris and other combustible materials.
7. Make building security.
8. Use caution when approaching suspicious situations, people, packages, etc. Maintain accountability of your personal belongings.
9. Register your cell phone for emergency alerts
10.Remain aware of your surroundings.
12.11. The building coordinator
The user department shall appoint building coordinator, the building coordinator should be:
1. A Responsible employee that can make decisions in a high stress
environment. 2. Knowledgeable about the departments occupying the building
3. Someone who maintains a regular work schedule within the building.
4. Someone who is able to build relationships and effectively communicate with other departments staff within the building.
5. They serve as the communication liaison between emergency service agencies and building occupants.
6. In respect of Pubtic Works Department, the Executive Engineer of BuildingConstruction and Maintenance Division PWD of respective districts ofTamilnadu will be the contact person by the building coordinator of userdepartment. The list of addresses and Phone numbers are enclosed inChapter 11.
1,2.12. For disaster -temporary maintenance of the building :
For disaster preparedness, the temporary maintenance for all GovernmentBuildings maintained by PWD are carried out based on the priority listfurnished by the various user department from the budget provision underMaintenance and Head of respective departments
L2.L3. For disaster - permanent maintenance of the building :
If case of permanent requirements towards attending disaster works in thebuildings, necessary funds , If it is not prioritized under routineMaintenance and Repair by the user department a separate specificsanction will be demanded.
f1*,. "*$[1,r.Enqineer'in-Chief (Buildings) &
Chief Engl;eer (Buildings)' Chcryl.l!Region &
Ctiief Engineer (Genef-l) lH D '
f mPa-uX, ehennai4O0 *$5'
.1onr')
t1- ev{
59