1 Off Grid Inverter Charger User and Installation Manual PICOGLF50KW384V240VS PICOGLF50KW384V2083P PICOGLF30KW300V240VS PICOGLF30KW300V2083P PICOGLF30KW300V4803P

Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

1

Off Grid Inverter Charger

User and Installation Manual

PICOGLF50KW384V240VS

PICOGLF50KW384V2083P

PICOGLF30KW300V240VS

PICOGLF30KW300V2083P

PICOGLF30KW300V4803P

Page 2: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

2

Read the manual carefully. Follow all warning and operating instructions contained in the manual before operating the inverter. Keep the manual for future reference. The information included in this manual is based on the product at the time of publication. However, this manual is subject to change without prior notice. AIMS Power™ reserves the right to continuously improve the product. In addition, the illustrations in this manual are only meant to help explain system configuration concepts and installation instructions. Your system or application may be different than the examples used in this manual. Exclusion of Liability AIMS Power cannot monitor the compliance to this manual, nor the conditions and methods of installation, operation, usage and maintenance of the solar controller. Improper installation may result in damage to property and, as a result, to bodily injury. We assume no responsibility or liability for loss, damage or costs which result from, or are in any way related to, incorrect installation, improper operation, or incorrect use and maintenance. AIMS Power reserves the right to make changes to the product, technical data or assembly and operating instructions without prior notice.

Page 3: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

3

Contents _Toc25567765

Safety Instructions ................................................................................................................................ 5

1. Product Introduction ......................................................................................................................... 6

2. Technical Information ........................................................................................................................ 8

3. Unpacking the Inverter ..................................................................................................................... 8

4. Installation ........................................................................................................................................ 9

5. Electrical Connection ...................................................................................................................... 10

6. LCD Display Layout ........................................................................................................................ 12

7.LCD Panel Operating Instructions ................................................................................................... 14

9. Malfunction and Troubleshooting .................................................................................................... 19

10. Maintenance ................................................................................................................................. 20

11. Warranty Conditions ..................................................................................................................... 21

12. Specifications ............................................................................................................................... 22

Page 4: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

4

SYMBOLS

SYMBOL DESCRIPTION

Grounding point

Refer to instructions

Properly dispose

Beware of dangerous electrical voltage. The inverter operates at high voltages!

CE mark The inverter complies with the requirements of the applicable CE

guidelines.

SAA mark

The inverter complies with the requirements of the applicable

Australia guidelines.

UL mark The inverter complies with the standard of UL1741.

CSA mark The inverter complies with the standard of CSA22.2.

Page 5: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

Off Grid Inverter

5

Safety Instructions Warning: The warnings, cautions, and instructions discussed in this instruction manual cannot cover all possible conditions and situations that may occur. It must be understood by the operator that common sense and caution are factors which cannot be built into this product and must be supplied by operator.to prevent electric shock.

1. To avoid risk of fire and electronic shock, make sure existing wiring is in good electrical condition and the wire is not undersized.

2. This equipment contains components which may produce arcs and/or sparks. To prevent fire and/or explosion, do not install in compartments containing batteries or flammable materials including any space containing gasoline-powered machinery, fuel tanks, joints, fittings, or areas that contain fuel.

3. To reduce the risk of electrical shock, disconnect both AC and DC power from the inverter before attempting any maintenance or cleaning. Simply turning off the controls will not reduce this risk.

4. Never smoke or allow sparks or flames close to the inverter or solar system. 5. Remove personal metal items such as rings, bracelets, necklaces, and watches when working with this product. 6. Do not operate if under the influence of alcohol or drugs. Read warning labels on prescriptions to determine if your

judgement or reflexes are impaired while taking drugs. If there is any doubt, do not operate the box. 7. People with pacemakers should consult their physician(s) before using this product. Electromagnetic fields near a

pacemaker could cause interference to or failure of the pacemaker. 8. Keep inverter away from children. Don't install the inverter where it is accessible to children. 9. Properly maintain all equipment. Check all wiring, batteries, inverters and charge controllers. 10. Ensure someone is within close range when working with any type of electrical equipment. 11. Do not expose the inverter to rain, snow, spray, damp area, bilge or dust. 12. Do not cover or obstruct the ventilation openings. Install in a well-ventilated area. Do not install the inverter in a

zero-clearance compartment. Overheating may result. Allow at least 12” of clearance around the inverter for air flow. Make sure that the air can circulate freely around the unit. A minimum air flow of 145CFM is required.

13. See Warranty Instructions for servicing the inverter. Only a professional electrician should service the inverter.

NOTE CAREFULLY INSPECT ALL PARTS AND MAKE SURE THERE IS NO DAMAGE. NOTIFY MANUFACTURER OF ANY DAMAGES BEFORE ACCEPTING DELIVERY AND INSTALLING THE INVERTER.

NOTE Do not close any breakers until all equipment is completely connected and inspected.

Warning Use proper grounding, using appropriate cable and fuse size.

Danger Before performing checks or maintenance, open (off) AC breaker, turn off start switch, then open (off) DC breaker. Wait 5 minutes for energy to dissipate. Measure DC and AC voltages with a multimeter and ensure there is no voltage between DC side and AC side. The display will slowly dim and disappear as the voltage drops.

Danger Don’t make any connections or open door when the inverter is powered on. Shock may occur.

WARNING INSTALLATION & MAINTENANCE SHOULD BE PERFORMED BY A PROFESSIONAL ELECTRICIAN/TECHNICIAN. ALL ELECTRICAL INSTALLATION SHOULD FOLLOW LOCAL CODES.

Page 6: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

Off Grid Inverter

6

1. Product Introduction Summary

Our PICOGLF series off grid inverter is one of the largest DC to AC inverters in the world. The Global LF Series Pure Sine Wave Inverter is a combination of an inverter, trickle battery charger and an AC auto-transfer switch into one complete system, with a peak conversion efficiency of 94%. It is packed with unique features and it is one of the most advanced inverters on the market today. It features power factor correction, customizable AC and DC operation and a pure sine wave output with unprecedentedly high surge capability to meet demanding power needs of inductive loads without damaging the equipment. When utility AC power cuts off (or falls out of acceptable range), the transfer relay is de-energized, and the load is automatically transferred to Inverter mode. Once the qualified AC power is restored the relay is re-energized and the load is automatically reconnected to AC bypass mode. The priority is programmable.

Features

Advanced short circuit, over load, over temperature protections ensure a service life up to 15 years or more.

Two types of startup modes: Soft Start and Variable Frequency Start. User can select mode according to the type of load.

Adjustable output frequency. Adjustable AC output voltage. Output voltage can be set between -40 % to +20 % of rated voltage. Adjustable DC voltage range. Over-voltage point, under-voltage point,

over-voltage recovery point and under-voltage recovery point can be set via the LCD panel. Powerful data display and fault instruction function. The LCD can display DC input voltage, output

frequency, phase voltage, phase current, AC bypass input voltage, power generated, time and date, temperature, fault code display.

Pure sine wave output with quick transfer less than 50ms, minimal waveform distortion and stable output voltage.

Low frequency transformer with isolated DC and AC busbars to eliminate interference. Wide input voltage range, customizable to customer’s requirement. Input voltage range of 100-

300V or 200-600V or 400-800V, suitable for solar/wind system without using backup batteries and charge controller. it can save many cost and maximization use the solar/wind energy.

Using SVPWM space vector algorithms, high conversion efficiency, high instantaneous power and low losses conversion efficiency up to 94%.

Output AC power compatible for all types of home electric equipment, sensitive electronics, and electric motors, etc.

European CE (EMC & LVD) certified and UL1741 & CSA22.2 listed.

Page 7: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

Off Grid Inverter

7

Physical Layout

Model number nomenclature

Example: PICOGLF50KW384V240

VS

No. Name Description LCD

Display Screen

Displays inverter’s operating status. Some functions are settable using the LCD display. Battery voltage, AC output voltage, AC current, frequency, work mode and faults.

Lock & Handle Inverter lock and handle for main door. Cable Gland The input and output wire throughputs.

4 Start Switch Start switch to charge capacitors for starting the inverter. Breakers DC input and AC output breaker.

Connection Terminals DC input terminal & AC output terminal. Name Plate Basic inverter specifications listed on the nameplate

including serial number.

1.LCD

2. Lock & Handle

3. Cable Gland

4. Start Switch

5. Breakers

7. Name Plate

6. Connection Terminals

Page 8: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

Off Grid Inverter

8

2. Technical Information Derating

Reducing the output power is a way to prevent inverter overload or damage. When the operating environment temperature and altitude are too high, both can cause a decrease in the inverter’s output power.

Inverter temperature derating curve

η=(Pout/Pnom)x100 T = environment temperature Pout is the off grid inverter’s actual maximum output power Pnom is the off grid inverter’s allowed max. output power

3. Unpacking the Inverter

The product has been tested, thoroughly inspected and packaged to withstand transportation. It is important to check the package and inverter before installing.

Be sure to inspect for any damage or incorrect quantities BEFORE signing for the product. If you accept the product, make sure to have the carrier NOTE the damage before signing.

Page 9: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

Off Grid Inverter

9

The nameplate shows the inverter’s model and other important information. Confirm you ordered and that you received the correct inverter.

NO. Description 1 AIMS Power Logo and product name. 2 Inverter model and parameter information. 3 Serial number. 4 Certifications and safety symbols. 5 Company info.

4. Installation

Location The inverter must be installed in a cool dry area. Water, dirt and dust will damage the inverter.

A 1ft clearance around the inverter is recommended. Installation must comply with local standards and codes. Do not install the inverter in a flammable or explosive area or a place where flammable or explosive

materials are stored. Do not install the inverter in areas where the inverter is vulnerable to lightning strikes. Do not install the inverter in a high salt, humid environment. Inverter has a rating of IP20. Install indoors and out of direct sunlight. Place inverter on a solid, sturdy, flat surface that can handle the inverter’s weight. The ideal temperature should be maintained within -13 to 122°F and

humidity not exceeding 95%. The inverter should be installed vertically. Do not allow the inverter to tilt forwards.

Note!

Photos are for reference only, check nameplate on the inverter.

Page 10: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

Off Grid Inverter

10

Never install the inverter horizontally. Install the inverter so the LCD is easy to access and read. The inverter should have plenty of air flow all around the inverter for

proper cooling fan operation. Don't install the inverter where passersby or children can tamper or

access the unit.

5. Electrical Connection As mentioned several times in this manual, installation should be done by a licensed professional. The electrical connections should be tested immediately after the installation is completed.

Prechecks

All electrical connections must meet local electrical codes. Incorrect wiring and/or installation may damage the inverter and may cause bodily harm. Before making any connections or performing maintenance to the inverter, make sure all power is off and no voltage present on the AC and DC sides.

Test for correct grounding, using proper cable and fuse sizes. Use a fuse or breaker 12 inches off the battery bank. Confirm the front panel breakers are in the "OFF" position and confirm all connections are properly wired. Check that the DC input breakers are in the “OFF” position. The cable between the battery and inverter should be as short as possible to avoid voltage drop. Never turn off DC input breaker with the inverter on or under a load, damage to the breaker or the inverter will occur.

Ensure all air vents are free from obstructions and clear of dust and debris. Don’t connect ground wire (PE) of cabinet and neutral wire (N) together.

NOTE: Do not over shut DC breaker off during operation. To shut AC off, use AC breaker first, then disengage AC start switch. To shut down inverter completely, follow above steps first then turn off DC breaker. Shutting off DC breaker during operation and under a load will damage the breaker and cause arcing.

Terminals Description

DC positive input terminals

DC negative input terminals

L1, L2 AC input terminals, connect with AC grid or generator

L1, L2, N AC output terminals, connect with AC load panel

PE Earth ground

Page 11: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

Off Grid Inverter

11

Terminal Block

Warning!

Do not reverse the polarity when connecting to DC input terminals. Confirm your wires are connected properly. Use the proper size cable and use bigger cable to handle voltage drop for long distance runs. REVERSE POLARITY IS NOT COVERED UNDER WARRANTY.

Source ground to case ground must be isolated and wire length should be as short as possible. After all wire connections have been made, check all voltages to ensure the voltages are within inverter’s

specification. Never operate any inductive motor larger than 30% of the inverters output due to high startup surge. When turning on the DC input breakers, the breaker may trip or pop the first time. This is normal as

the large capacitors are rapidly charging. If this happens, simply reset the DC breakers. When powering on the inverter, we recommend turning on the output circuit breaker first, then turn

on start switch allowing a soft start of AC loads to avoid any damage by large inrush current to inverter.

Before performing checks or maintenance, open (off) AC breaker, turn off start switch, then open (off) DC breaker. Wait 5 minutes for energy to dissipate. Measure DC and AC voltages with a multimeter and ensure there is no voltage between DC side and AC side. The display will slowly dim and disappear as the voltage drops. Inverter may still be live and have voltage present in the off position due to the large capacitors. Never touch any connection prior to testing with a multimeter.

When the inverter is operating normally, it is typical to see a rise in temperature. The cooling fans will start when the temperature reaches @ 113°F.

Do not open inverter’s door or touch any wire while in operation.

NOTE

After all connections are made and voltages are verified with a multimeter, proceed to the startup procedure

in section 6.

When the inverter is running, it is normal for the inverter to get warm. To avoid injury, only touch the LCD display and start/stop switch. DO NOT TOUCH ANY BREAKERS WHILE INVERTER IS OPERATING. THIS M AY CAUSE BODILY HARM AND RUIN THE INVERTER.

Page 12: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

Off Grid Inverter

12

6. LCD Display Layout

LED Indicators

There are 5 LED lights on the panel: Grid, Run, Fault, Auto, Manual. Table7-1 LED Indicator Direction

LED Indicator Color Instructions Grid

Amber AC bypass priority mode indicates the AC grid input condition.

Run

Green

Battery priority mode indicates the battery supply condition. Inverter mode.

Fault Red System fault. Auto Blue Inverter running, indicates the inverter is work

normally. Manual

Illuminated Variable frequency mode, the inverter is working in variable frequency mode.

*When in inverter mode, the LED will be blue/green or blue/amber. This is normal. Fault Code

DCU OVER DC over-voltage DCU UNDER DC under-voltage OVER LOAD Current over-load MOD Module error OUTErr Output voltage unbalance (This error is only for 3 phase

output, single phase output without this error display).

Page 13: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

Off Grid Inverter

13

If any inverter parameters need to be made, follow instructions on page 15 LCD Panel Operating Instructions. All parameters must be set prior to engaging start switch DW.

Page 14: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

Off Grid Inverter

14

LCD Display Interface Overview

7. LCD Panel Operating Instructions Inverter power on, the first interface display parameter, press “down” key to display the following parameters:

DC IN DC input voltage display

AC OUT AC output voltage display

AC OUT Output current display

Freq Output frequency display

AC INPUT: AC bypass input

U: V Bypass phase voltage

OUT:

W:

KWH

Total generated amounts Generated amounts

Page 15: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

Off Grid Inverter

15

Inv State: Inverter working state:

DCU OVER DC over-voltage

DCU UNDER DC under-voltage

OVER LOAD Over-load

MOD Module error

Fault display:”N” indicates no error, ”Y” indicates error

OUTErr Output voltage unbalanced

**This error is only for 3 phase output. (NA for 240V)

Fault alarm can be divided into automatic recovery and non-automatic recovery: When the LCD

screen display MOD error and overload you need to manually restart, turn off the DC circuit breaker

until the LCD screen is completely off and then turn on the DC circuit breaker; over-voltage, under-

voltage will automatically recover (the under-voltage recovery default setting is 10 minutes), and can

be set according to the customer application.

Keypad function

1. Running Info Running state display

2. Inv Start Mode Inverter Start mode

3. Work Modes Working Mode

4. Parameter Set System parameter setting

Page 16: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

16

Press “ 2. Inv Start Mode ” displays the following

1. Voltage Constant frequency step-down voltage

Starting mode

2. Frequency Variable frequency starting mode

Y : YES N: NO

Press “ 3. Work Modes ” displays the following

1. Inv Battery priority mode 2. Bypass AC bypass priority mode

Y : YES N: NO

Time: Display current time and date

Tem: Environmental temperature display

Press “ 4. Parameter Set ” you will need to enter password each time. Note! If you want to adjust the parameter setting, please contact the

manufacturer and ask for password

Note! When inverter is working, please don't adjust parameters setting. If you want to adjust parameter setting, please turn off start button and operation of inverter.

The following settings are to be set by a qualified professional. If you are not qualified to make these changes, damage will occur and not covered under warranty.

Page 17: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

17

1. Freq Set Frequency setting

2. VIout Set Output voltage setting

3. CT&Temp Set Current ratio setting and temperature

Protection setting

4. Alarm Set DC over-voltage and under-voltage setting

5. UdcR Set Recovery setting of DC over-voltage and under-voltage

6. Udc Under Delay Default recovery time of under-voltage is 10 minutes 7. Time Set Date and time setting

8. Overload Set Overload times and overload time setting

Press “ 1. Freq Set ” output frequency setting display as following

Max Fre: HZ Recommend maximum output

frequency setting between 30-100Hz

Min Fre: HZ The minimum frequency of output Starting

can’t less than 5Hz

Press “ 2. Vout Set ” output voltage and current setting display as following

Vout Set Output voltage setting

Iout –Max Set: Output current setting Note: Output Max Current default is the overload protection current value and can be lowered, Output voltage should be set to no more than 20% of the rated power. If the inverter is damaged by incorrect settings it will not be covered under warranty.

Press “ 3. CT&Temp Set ” Current and mutual inductance ratio and Protection temperature setting display as following

CT Set: Current and mutual inductance ratio setting

Temp Set: Protection temperature setting

Page 18: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

18

Press “ 4. Alarm Set ” over-voltage and under-voltage setting display as following

Udc-over Set: DC over-voltage protection setting Udc-under Set DC under-voltage protection setting

Press “ 5. UdcR Set ” DC over-voltage and under-voltage recovery setting display as following

Udc-over Set: DC over-voltage recovery setting

Udc-under Set: DC under-voltage recovery setting

Press “ 6. Udc Under Delay ” Under-voltage recovery time setting display as following

Udc Under Delay: Under-voltage recovery time setting

Min Minute

Press “ 7. Time Set ” to display as following

Time:

Display date and time setting

Press “ 8. Over Load Set ”

Recovery over Load Set: Overload times

setting Overload surge time

Page 19: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

19

8. Malfunction and Troubleshooting If a malfunction or alarm sounds, the malfunction LED will light up, LCD will display current malfunction or stop condition, please refer to chart below for commons malfunction and troubleshooting steps.

Condition code

Name Phenomena Cause value Troubleshooting

State 01

DC input voltage low

Inverter stopped working, No AC output, inverter restarts automatically

Battery voltage out of inverter’s DC range. DC input voltage lower than min input voltage of inverter

Check battery output voltage on the inverter, ensure the output voltage is within spec of inverter.

State 02

DC input Over voltage

Inverter stopped working, No AC output, inverter

restarts automatically

DC input voltage higher than maximum input voltage of inverter

Check battery output. voltage or PV array voltage and ensure the output voltage is within spec of inverter.

State 03

Output overload

Inverter shut down, AC loads turn on and off

Load higher than rated output power of inverter.

Battery bank too small

Insure correct system design. This fault is usually caused by high surge devices that the inverter or battery bank can’t support.

State 04

IPM fault

Inverter shut down, will no longer output AC power

Check for short circuit on AC output. If this fault appears frequently, please contact AIMS Power

Under fault of MOD, overload, output error and fault alarm, turn off the DC input breaker for 1

hour to restart the machine.

Page 20: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

20

9. Maintenance

CAUTION Before performing checks or maintenance, open (off) AC breaker, turn off start switch, then open (off) DC breaker. Wait 5 minutes for energy to dissipate. Measure DC and AC voltages with a multimeter and ensure there is no voltage between DC side and AC side. The display will slowly dim and disappear as the voltage drops. Inverter may still be live and have voltage present in the off position due to the large capacitors. Never touch any connection prior to testing with a multimeter.

Every 6 months

● Check all ventilation and fan airways. Blow air and clear all dust in the inverter

and in the surrounding area. If high level of dust is accumulating, relocate inverter or find a way to keep dust at a minimum.

● Check the inverter cable connections. If loose, tighten according to the proper connection guidelines in this manual.

● Ensure the cables are not damaged, inspect for cracking, fraying, cut or over heated wiring.

Parts Check the contents Solutions

Input and output terminals

Loose Tighten

Input and output cable

Condition of cable Replace poor quality cable

Control board Accumulation of dust

and dirt Using 392kPa-588kPa pressure dry

compressed air to clean inverter Bus capacitor Discoloration or smell Replace capacitor Radiator Fan Not working Replace fan

Inside of cabinet Accumulation of dust

and dirt Using 392kPa-588kPa pressure dry

compressed air to blow off

Button cell LCD doesn't display

Time Replace the CR1220 Button Cell on the

motherboard

Page 21: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

21

10. Warranty Conditions

All AIMS Power® products come with warranty coverage against defects as follows, from the date of purchase, unless otherwise indicated:

• 2-Year with optional extended warranties

Within the warranty coverage period, AIMS Power® will either repair or replace, at its sole discretion, the defective product. A refund may be issued if a defective product is not repairable or a comparable replacement is available. – We will never issue a refund. We will always have a replacement if the unit is not repairable. Our distributors offer their own return policy. AIMS only covers warranty issues.

Any shipping charges that occur as a result of a warranty return or exchange are NOT covered by the warranty and are the responsibility of the customer.

The warranty does not cover the following:

• Products that AIMS Power® determine, in its sole discretion, to be free of any material or workmanship defects or flaws

• Products evidencing excessive wear, misuse or alteration • Products with missing or defaced labels, stickers, or other identifying information • Improper care or storage (e.g. water damage, exposure to extreme heat or cold temperatures) • Alterations or customization • Items that were purchased second hand, or from an unauthorized seller • Items outside of the covered warranty period

AIMS Power 9550 Gateway Drive Reno, NV 89521 775-359-6703 www.aimscorp.net

Page 22: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

22

Off Grid Inverter

11. Specifications

Model 30KW Isolation mode Low Frequency Transformer

DC Input Rated voltage (Vdc) 300V Operating: 270-430V DC Programming: 250-500V DC

Rated current(A) 100A DC operating range 270-430V DC Programmable range 250-500V DC

AC Output

Rated power (KW) 30KW

Rated voltage 120/240V split

120/208V 3 phase 480 3 phase

Output phases Split phase | 3 phase – depends on model

Rated current (A) 125A | 83.3A (phase current)

Output frequency 60Hz Output waveform Pure Sine Wave

Voltage accuracy Load balance≤1%, Unbalance load≤5% Waveform distortion

rate (THD) Linear load≤2%, Nonlinear load≤3%

Dynamic Response 5%, ≤50ms( load 0 ~ 100%)

Power Factor (PF) 0.95 Inverter Efficiency >94%

Electrical insulation properties 2000Vac, 1 Minute

Running mode Working continuously, can work 24h*7@50% load Output voltage (Vac) 110/120/220/230/240/380/400/415/440VAC can be customized

Phases Single / Split/ Three phase optional – per order

Protection Function

Overload Ability 120% - 35 seconds, 150% - 5 seconds

Protection Input reverse polarity, under voltage, over voltage, output over-current, short circuit, overheating etc.

Display LCD Communication port RS485(Optional)

Cooling method Fan-cooled Short-circuit protection No automatic recovery, need to restart the machine

Working environment

& Mechanical dimension

Degree of protection IP20(indoor) Working Altitude (m) ≤2500m Working temperature -15~+50℃

Relative humidity 0~90%,non-condensing Noise (1 meter) ≤50dB

Depth* Width * Height 650x750x1100mm | 24” x 24.75” x 42.50” Weight (Kg) 260Kg | 568lb – 650lb

Certifications European CE (EMC & LVD) UL, CSA

Page 23: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

23

Off Grid Inverter

Model 50KW Isolation mode Low Frequency Transformer

DC Input Rated voltage (Vdc) 360V

Rated current(A) 139A DC operating range 346-550V DC Programmable range 320-600V DC

AC Output

Rated power (KW) 50KW

Rated voltage 120/240V | 120/208V Output phases Split phase | 3 phase

Rated current (A) 208.3A |138.8A (phase current)

Output frequency 50Hz or 60Hz Output waveform Pure Sine Wave

Voltage accuracy Load balance≤1%, Unbalance load≤5% Waveform distortion

rate (THD) Linear load≤2%, Nonlinear load≤3%

Dynamic Response 5%, ≤50ms (load 0 ~ 100%)

Power Factor (PF) 0.95 Inverter Efficiency >94%

Electrical insulation properties 2000Vac, 1 Minute

Running mode Working continuously, can work 24h*7 Output voltage (Vac) 110/120/220/230/240/380/400/415/440VAC can be customized

Phases Single / Split/ Three phase optional – per order

Protection Function

Overload Ability 120% - 35 seconds, 150% - 5 seconds

Protection Input reverse polarity, under voltage, over voltage, output over-current, short circuit, overheating etc.

Display LCD Communication port RS485(Optional)

Cooling method Fan-cooled Short-circuit protection No automatic recovery, need to restart the machine

Working environment

& Mechanical dimension

Degree of protection IP20(indoor) Working Altitude (m) ≤2500m Working temperature -15~+50℃

Relative humidity 0~90%,non-condensing Noise (1 meter) ≤50dB

Depth* Width * Height 710x750x1300mm| 31.5” x 31.5” x 49.5” Weight (Kg) 400Kg | 900lb -960lb

Certification European CE (EMC & LVD) UL, CSA

Page 24: Off Grid Inverter Charger - AIMS Power DC_41201.pdf · 2020-04-01 · Off Grid Inverter 9 The nameplate shows the inverter’s model and other important information. Confirm you ordered

24

Electrical Diagram