O-Calc® Pro Capacity Summary InfoPole Identification: 09080
Report Created: 8/1/2012File: pole 09080.pplx
File Name: pole 09080.pplx Pole Length / Class: 40 / 4 Code: NESC Structure Type: Junction
Pole Num: 09080 Pole Species: PONDEROSA PINE NESC Rule: Rule 250B Status: N/A
Latitude: 38.88655 Setting Depth (ft): 6.00 Construction Grade: C Pole Strength Factor: 0.85
Longitude: -92.26195 G/L Circumference (in): 36.50 Loading District: Heavy Transverse Wind LF: 1.75
Aux Data 4:
Unset G/L Fiber Stress (psi): 6,600 Ice Thickness (in): 0.50 Wire Tension LF: 1.30
Aux Data 4:
Unset Allowable Stress (psi): 5,610 Wind Speed (mph): 39.53 Vertical LF: 1.90
Aux Data 5:
Unset Fiber Stress Ht. Reduction: No Wind Pressure (psf):
4.00
Guy Summary Guy Tensions Maximum Guy Tensions
Attach Height (ft)
% Allowable Tension
Wind Angle % Allowable Tension
Wind Angle
Guy 1 23.9 0.0% 12.7° 173.2% 188.6°
Anchor SummaryLead Length
(ft)Max. % Allow.
Capacity
Anchor 1 9.0 25.9%
Pole Capacity Utilization Height Wind Angle
Maximum: 80.0% 0.0 ft 12.7°
Groundline: 80.0% 0.0 ft 12.7°
Vertical: 7.1% 26.8 ft 158.0°
Pole Moments Load Angle Wind Angle
Max Capac. Util: 56,576 ft-lb 30.2° 12.7°
Groundline: 56,576 ft-lb 30.2° 12.7°
Version: 4 / 4.06 Page 1 of 4* includes Load Factor(s) ² Worst Wind per Guy Wire ³ Wind at 12.7°
BOONE ELECTRIC COOP Pole Analysis Report
Detailed Load ComponentsPower: Owner Height
(ft)Horiz. Offset
(in)
Cable Dia. (in)
Rotate Angle (deg)
Cable Weight (lbs/ft)
Lead/Span
Length (ft)
Span Angle (deg)
Wire Length
(ft)
Tension (lbs)
Tension Moment
(ft-lb)*
Offset Moment
(ft-lb)*
Wind Moment
(ft-lb)*
Moment at GL(ft-lb)*
Primary ACSR 477.0 KCM 18/1 PELICAN 34.62 3.34 0.8140 - 0.517 315.0 98.0 315.2 1,533 26,112 42 5,330 31,484
Primary ACSR 477.0 KCM 18/1 PELICAN 34.62 3.34 0.8140 - 0.517 225.0 278.0 225.1 1,533 -26,112 30 3,807 -22,274
Primary ACSR 477.0 KCM 18/1 PELICAN 32.78 30.45 0.8140 - 0.517 315.0 98.0 315.2 1,533 24,724 858 5,047 30,629
Primary ACSR 477.0 KCM 18/1 PELICAN 32.78 30.45 0.8140 - 0.517 225.0 278.0 225.1 1,533 -24,724 613 3,605 -20,506
Primary ACSR 477.0 KCM 18/1 PELICAN 32.78 30.45 0.8140 - 0.517 315.0 98.0 315.2 1,533 24,724 -990 5,047 28,781
Primary ACSR 477.0 KCM 18/1 PELICAN 32.78 30.45 0.8140 - 0.517 225.0 278.0 225.1 1,533 -24,724 -707 3,605 -21,827
Neutral ACSR 477.0 KCM 18/1 PELICAN 28.75 5.97 0.8140 - 0.517 315.0 98.0 315.1 1,533 21,659 -184 4,421 25,896
Neutral ACSR 477.0 KCM 18/1 PELICAN 28.75 5.97 0.8140 - 0.517 225.0 278.0 225.3 1,533 -21,659 -131 3,158 -18,632
Totals: 0 -470 34,019 33,550
LOAD SUMMARY BY OWNER<Undefined>: 1,810 53,866 4,198 4,749 45 4,243 75.6Pole: 173 2,677 209 1,511 14 223 4.0Charter: 2 32 2 29 0 3 0.0Totals 1,985 56,576 4,409 6,289 59 4,469 79.7
GROUNDLINE LOAD SUMMARY:*Wind at 12.7°, Applied Moment 56,576 ft-lb at 30.2°, Allowable Moment 71,980 ft-lbShear Load (lbs)*
Percent Applied
Load
Bending Moment
(ft-lb)
Percent of Applied
Moment**
Percent of Pole
Capacity
Bending Stress (+/-psi)
Vertical Load (lbs)
Vertical Stress
(psi)
Total Stress
(psi)
Percent of Pole
Capacity
Powers: 1,055 53.1 33,550 55.6 43.7 2,615 2,738 26 2,641 47.1Comms: 745 37.5 20,038 28.2 22.2 1,562 1,841 17 1,579 28.1Guys/Braces: 4 0.2 100 0.2 0.1 8 10 0 8 0.1Pole: 173 8.7 2,677 4.7 3.7 209 1,511 14 223 4.0Crossarms: 2 0.1 48 0.1 0.1 4 76 1 4 0.1Risers: 2 0.1 32 0.1 0.0 2 29 0 3 0.0Insulators: 4 0.2 131 0.1 0.1 10 84 1 11 0.2Pole Load: 1,985 100.0 56,576 100.0 78.6 4,409 6,289 59 4,469 79.7Pole Reserve Capacity: 15,404 21.4 1,201 1,141 20.3
Version: 4 / 4.06 Page 2 of 4* includes Load Factor(s) ² Worst Wind per Guy Wire ³ Wind at 12.7°
BOONE ELECTRIC COOP Pole Analysis Report
Comm: Owner Height (ft)
Horiz. Offset
(in)
Cable Dia. (in)
Rotate Angle (deg)
Cable Weight (lbs/ft)
Lead/Span
Length (ft)
Span Angle (deg)
Wire Length
(ft)
Tension (lbs)
Tension Moment
(ft-lb)*
Offset Moment
(ft-lb)*
Wind Moment
(ft-lb)*
Moment at GL(ft-lb)*
Overlashed Span Bundle 26.53 6.38 0.2500 - 0.121 315.0 98.0 315.0 1,000 13,040 66 2,862 15,968
Telco BELOPTIX DT096 - 72 FIBERS - DIELECTRIC (0.516)
26.53 6.38 0.5160 - 0.097 315.0 98.0 315.0 0 62 2,862 2,924
Overlashed Span Bundle 26.53 6.38 0.2500 - 0.121 225.0 278.0 225.0 1,000 -13,040 47 2,044 -10,949
Telco BELOPTIX DT096 - 72 FIBERS - DIELECTRIC (0.516)
26.53 6.38 0.5160 - 0.097 225.0 278.0 225.0 0 44 2,044 2,089
Overlashed Span Bundle 25.59 6.45 0.2500 - 0.121 315.0 98.0 315.0 1,000 12,575 66 2,760 15,401
Telco BELOPTIX DT096 - 72 FIBERS - DIELECTRIC (0.516)
25.59 6.45 0.5160 - 0.097 315.0 98.0 315.0 0 63 2,760 2,823
Overlashed Span Bundle 25.59 6.45 0.2500 - 0.121 225.0 278.0 225.0 1,000 -12,575 47 1,971 -10,556
Telco BELOPTIX DT096 - 72 FIBERS - DIELECTRIC (0.516)
25.59 6.45 0.5160 - 0.097 225.0 278.0 225.0 0 45 1,971 2,016
Overlashed Span Bundle 25.11 6.49 0.2500 - 0.121 96.0 152.0 96.0 1,000 -17,194 -13 553 -16,654
CATV CATV .50 Jacket 25.08 6.47 0.5600 - 0.072 96.0 152.0 96.0 0 -12 552 540
CATV CATV .625 Jacket 25.08 6.53 0.6850 - 0.116 96.0 152.0 96.0 0 -12 552 541
Overlashed Span Bundle 25.09 6.49 0.2500 - 0.121 315.0 98.0 315.0 1,000 12,332 68 2,901 15,301
CATV BELOPTIX 2-60 CT FIBER - ARMORED
25.07 6.63 0.5300 - 0.120 315.0 98.0 315.0 0 70 2,898 2,968
CATV CATV .50 Jacket 25.07 6.36 0.5600 - 0.072 315.0 98.0 315.0 0 58 2,898 2,956
Overlashed Span Bundle 25.09 6.49 0.2500 - 0.121 225.0 278.0 225.0 1,000 -12,332 48 2,072 -10,212
CATV BELOPTIX 2-60 CT FIBER - ARMORED
25.07 6.63 0.5300 - 0.120 225.0 278.0 225.0 0 50 2,070 2,120
CATV CATV .50 Jacket 25.07 6.36 0.5600 - 0.072 225.0 278.0 225.0 0 41 2,070 2,111
Overlashed Span Bundle 24.08 6.56 0.3750 - 0.273 96.0 152.0 96.0 800 -13,190 -26 472 -12,744
Telco TELE 1.0 24.08 6.56 0.5000 - 0.200 96.0 152.0 96.0 0 -22 472 449
Overlashed Span Bundle 24.08 6.56 0.3750 - 0.273 51.0 330.0 51.0 800 12,439 -14 266 12,692
Telco TELE 1.0 24.08 6.56 0.5000 - 0.200 51.0 330.0 51.0 0 -12 266 254
Totals: -17,945 666 37,317 20,038
Crossarm: Owner Height (ft)
Horiz. Offset
(in)
Offset Angle (deg)
Rotate Angle (deg)
Unit Weight
(lbs)
Unit Height
(in)
Unit Depth
(in)
Unit Diameter
(in)
Unit Length
(in)
Tension Moment
(ft-lb)*
Offset Moment
(ft-lb)*
Wind Moment
(ft-lb)*
Moment at GL(ft-lb)*
Normal CROSSARM 3-1/2 X 4-1/2 X 6 31.97 5.24 278.0 278.0 40.00 4.50 3.50 - 72.00 - -13 61 48
Totals: 0 -13 61 48
Riser: Owner Height (ft)
Horiz. Offset
(in)
Offset Angle (deg)
Rotate Angle (deg)
Unit Weight
(lbs)
Unit Height
(in)
Unit Depth
(in)
Unit Diameter
(in)
Unit Length
(in)
Tension Moment
(ft-lb)*
Offset Moment
(ft-lb)*
Wind Moment
(ft-lb)*
Moment at GL(ft-lb)*
catv riser 8.0° catv riser Charter 15.43 5.95 8.0 8.0 1.29 185.22 - 0.00 - - 7 25 32
Totals: 0 7 25 32
Version: 4 / 4.06 Page 3 of 4* includes Load Factor(s) ² Worst Wind per Guy Wire ³ Wind at 12.7°
BOONE ELECTRIC COOP Pole Analysis Report
Insulator: Owner Height (ft)
Horiz. Offset
(in)
Offset Angle (deg)
Rotate Angle (deg)
Unit Weight
(lbs)
Unit Height
(in)
Unit Depth
(in)
Unit Diameter
(in)
Unit Length
(in)
Tension Moment
(ft-lb)*
Offset Moment
(ft-lb)*
Wind Moment
(ft-lb)*
Moment at GL(ft-lb)*
Pin Pin Insulator - 5 kV 34.00 3.34 98.0 180.0 6.00 7.50 - 3.50 - - 1 42 43
Pin Pin Insulator - 5 kV 32.16 30.00 358.1 0.0 6.00 7.50 - 3.50 - - 25 39 64
Pin Pin Insulator - 5 kV 32.16 -30.00 197.9 0.0 6.00 7.50 - 3.50 - - -28 39 11
Spool Spool Insulator - 20 kV 28.75 3.72 188.0 0.0 1.00 2.12 - 2.50 - - -1 7 6
Bolt Three Bolt 26.53 3.88 8.0 180.0 5.00 0.00 - 3.00 - - 5 0 5
Bolt Three Bolt 25.59 3.95 8.0 180.0 5.00 0.00 - 3.00 - - 5 0 5
Bolt Three Bolt 25.11 3.99 152.0 234.0 5.00 0.00 - 3.00 - - -3 0 -3
Bolt Three Bolt 25.09 3.99 8.0 180.0 5.00 0.00 - 3.00 - - 5 0 5
J-Hook J-Hook 24.08 4.06 240.0 232.0 5.00 0.00 - 3.00 - - -5 0 -5
Totals: 0 4 127 131
Guy Wire and Brace: Owner Attach Height (ft)
End Height (ft)
Lead/Span Length (ft)
Wire Dia. (in)
Percent Solid (%)
Lead Angle (deg)
Incline Angle (deg)
Wire Weight (lbs/ft)
Rest Length (ft)
Stretch Length (in)
Guy 1: EHS 1/4 Down 23.94 0.00 9.00 0.250 75.0 338.0 69.4 0.121 25.57 0.00
Guy Wire and Brace (Loads and Reactions)
Elastic Modulus (psi) Rated Tensile
Strength (lbs)
Guy Strength
Factor
Allowable Tension
(lbs)
Initial Tension
(lbs)
Required Tension²
(lbs)
Required Tension³
(lbs)
Applied Tension³
(lbs)
Vertical Load³ (lbs)
Shear Load in Guy Dir³
(lbs)
Shear Load at Report
Angle³ (lbs)
Moment at GL³ (ft-lb)*
Guy 1: EHS 1/4 Down 23,000,000 6,650 0.90 5,985 700 10,368 0 0 0 0 0 100
Totals: 0 0 0 100
Anchor/Rod Load Summary: Owner Rod Length AGL (in)
Lead Length (ft)
Lead Angle (deg)
Strength of Assembly (lbs)
Anchor/Rod Strength
Factor
Allowable Load (lbs)
Max Load² (lbs)
Load at Pole MCU³ (lbs)
Max Required Capacity² (%)
Proposed CATV - 12" - Soil Class 3 0.00 9.00 60.0 40,000 1.00 40,000 10,368 0 25.9
Pole BucklingBuckling Constant
Buckling Column Hgt
Buckling Section Height
Buckling Section Diam.
Min. Buckling
Diam. at GL
Diameter at Tip
Diameter at GL
Modulus of Elasticity
Pole Density
Ice Density
Pole Tip Height
Buckling Load Capacity at Hgt.
Buckling Load Applied at Hgt.
Buckling Load Factor of Safety
(ft) (% Buckling Col. Hgt.) (in) (in) (in) (in) (psi) (pcf) (pcf) (ft) (lbs) (lbs)
0.71 26.78 35.02 10.26 13.72 6.69 11.62 1,000,000 50.00 57.00 34.00 88,295 6,289 14.04
Version: 4 / 4.06 Page 4 of 4* includes Load Factor(s) ² Worst Wind per Guy Wire ³ Wind at 12.7°
BOONE ELECTRIC COOP Pole Analysis Report