43
NZ3200 INSTALLATION, COMMISSIONING & OPERATION NZ3200 Fire Alarm Control Panel (NZS4512:2003) Installation, Commissioning & Operation MAN2338-3

NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

NZ3200

Fire Alarm Control Panel (NZS4512:2003)

Installation, Commissioning &

Operation

MAN2338-3

Page 2: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

1

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

CONTENTS Page No

1 SYSTEM DESCRIPTION ...................................................................................................................... 3 1.1 General Description ......................................................................................... 3 1.2 System Layout ................................................................................................. 3 1.3 Main System Board 302-7080 .......................................................................... 5

1.3.1 Main Board Terminal and Connector Summary ....................................... 6 1.3.2 Detector Circuits TB5 & TB6 ..................................................................... 7 1.3.3 Bell Circuits TB4 ........................................................................................ 7 1.3.4 Bell Isolate (Internal) ................................................................................. 7 1.3.5 Self Test ..................................................................................................... 7 1.3.6 Walk Test ................................................................................................... 7 1.3.7 Door Interlock ............................................................................................ 7 1.3.8 Fault Indicators .......................................................................................... 8 1.3.9 DBA Input TB2 ........................................................................................... 8 1.3.10 Power Supply ............................................................................................. 8 1.3.11 Mains On Indicator .................................................................................... 8 1.3.12 Ancillary Power Output TB1 ...................................................................... 8 1.3.13 Fusing ........................................................................................................ 8

1.4 Zone Board 302-5880 ....................................................................................... 9 1.4.1 Detector Circuits ........................................................................................ 9

1.5 Batteries ........................................................................................................... 9

2 CONNECTING DEVICES ..................................................................................................................... 10 2.1 Detectors ........................................................................................................ 10

2.1.1 Detector Limitations ................................................................................ 10 2.1.2 Manual Call Points ................................................................................... 10

2.2 Bells and Sounders ....................................................................................... 12

3 CONNECTING THE EVACUATION AMPLIFIER ................................................................................. 13 3.1 Overview:........................................................................................................ 13 3.2 Specifications: ............................................................................................... 13 3.3 Operation:....................................................................................................... 13 3.4 Installation Criteria ........................................................................................ 14

4 CONNECTING BRIGADE INTERFACES ............................................................................................. 17 4.1 Connecting a Signal Generating Device....................................................... 17

5 SETTINGS .......................................................................................................................................... 18 5.1 Main System Board (302-7080) Settings....................................................... 18

5.1.1 Setting the Number of Zone Cards ......................................................... 18 5.1.2 Miscellaneous Settings ........................................................................... 18 5.1.3 Setting Zone Bell Output ......................................................................... 18 5.1.4 Setting Zone Brigade Call Output ........................................................... 18 5.1.5 Allocating AVF to a Zone......................................................................... 19

5.2 Zone Card (302-5880) Settings. ..................................................................... 19 5.2.1 Setting the Address of the Zone Cards. ................................................. 19 5.2.2 Setting Zone Bell Output ......................................................................... 19 5.2.3 Setting Zone Brigade Call Output ........................................................... 19 5.2.4 Setting Zone Configuration ..................................................................... 20

6 SPECIFICATIONS............................................................................................................................... 20

Page 3: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

2

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

7 INSTALLATION AND INITIAL OPERATION ...................................................................................... 21 7.1 Unpacking And Inspection ............................................................................ 21 7.2 Anti Static Precautions .................................................................................. 21 7.3 Installing the NZ3200 ..................................................................................... 21 7.4 Removing and Reinstalling the Index Panel ................................................ 21 7.5 Initial Operation.............................................................................................. 21

8 SYSTEM OPERATION ........................................................................................................................ 22 8.1 Resetting the System..................................................................................... 22 8.2 Isolating the Bells/Sounders ......................................................................... 22 8.3 Using the Walk Test Facility .......................................................................... 22 8.4 Self Test Facility............................................................................................. 22 8.5 Evacuation ...................................................................................................... 22

9 OPTIONS ............................................................................................................................................ 23 9.1 ASPI Relay Board ........................................................................................... 23

9.1.1 Description............................................................................................... 23 9.1.2 Settings .................................................................................................... 23 9.1.3 Installing the ASPI Relay Board .............................................................. 23

9.2 8 Way Relay Board ......................................................................................... 24 9.2.1 Description............................................................................................... 24 9.2.2 Connections ............................................................................................. 24 9.2.3 Technical Specifications ......................................................................... 24 9.2.4 Communications ..................................................................................... 24 9.2.5 Interface Relays ....................................................................................... 24 9.2.6 Link Settings ............................................................................................ 25 9.2.7 Programmable Relays ............................................................................. 26

9.3 LED Mimic Driver Board ................................................................................ 27 9.3.1 Description............................................................................................... 27 9.3.2 Specifications .......................................................................................... 28 9.3.3 Installation ............................................................................................... 28 9.3.4 Component Layout .................................................................................. 30

9.4 24 Volt Bell Driver Board ............................................................................... 32 9.4.1 Description............................................................................................... 32 9.4.2 Features ................................................................................................... 32 9.4.3 Specifications .......................................................................................... 32 9.4.4 Connections ............................................................................................. 32

10 TROUBLESHOOTING ......................................................................................................................... 34

11 INDEX PANEL ENGRAVING ............................................................................................................... 35 11.1 NZ3200/16 without DBA. For rear service FACP .......................................... 35 11.2 NZ3200/16 with DBA . For rear service FACP .............................................. 36 11.3 NZ3200/16 For front service FACP................................................................ 37 11.4 NZ3200/32 For Rear service FACP ................................................................ 38 11.5 NZ3200/32 For Rear service FACP ................................................................ 39

12 Appendix A. BATTERY CALCULATION. ........................................................................................... 40

13 Appendix B. EXAMPLE BATTERY CALCULATION .......................................................................... 41

14 Appendix C: DEVICES ........................................................................................................................ 42

Page 4: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

3

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

1 SYSTEM DESCRIPTION

1.1 General Description

The NZ3200 is available in two standard formats - the NZ3200/16 and the NZ3200/32. The NZ3200/16 accommodates the 302-7080 Main System Board, and one, eight-zone circuit board (302-5880) giving a total of 16 circuits. These circuits can operate with smoke detectors, heat detectors and manual call points. The NZ3200/32 panel accommodates the 302-7080 Main System Board, and up to three eight-zone circuit boards (302-5880) giving a maximum capacity of 32 circuits. Various options are available for both formats. These are listed in the Appendix Compatible Devices.

1.2 System Layout

Figure 1: NZ3200/16 System Layout

CN6TB1 ZD1

G1

Z1

Z8

Z7

Z6

Z5

Z4

Z3

Z2

Z1

-

+

+

+

+

+

+

+

+

-

-

-

-

-

-

-

API 588 8 ZONE AZF

Z2

Z3

Z4

Z5

Z6

Z7

Z8

MAINS

SWITCH

TRANSFORMER

8 ZONECIRCUITBOARD302-5880

SGDAREA

RELAY AREA

RELAY AREA

RELAY AREA

SW

9

SW1

SW

8S

W7

D2

8

TB2

D3

3D

38

D4

1D

47

D5

0D

53

D5

6D

59

D3

1D

37

D4

0D

44

D5

2

D5

5D

58

D3

6D

39

D4

3D

48

D5

1

D5

4D

57

CN10

LM

P1

BZ1

+

R10

RV1

CN3

U1

F5

F4D

23

D2

4D

26

D1

8

D5

D8

D11

D15

D9

D16

D10

D6

D21D20 D22

TB5

R2

SW5

SW4

CN4

TB3

SW3

TB4

D1

CN5

CN1

D49

R21

RV2

SW2

S W6

TB1

TB

6

R9

M1

MIM

IC L

ED

Z8

Z7

Z6

Z5

Z4

Z3

Z2

Z1

-

-

-

-

-

-

-

-

+

+

+

+

+

+

+

+

POWER

LAMP

2A

2A

3A1A

VOLTAGE

CHARGER

SET

TRIMV.SENSE

NORMAL

DEFECT

DBA

FIRE

Z5

Z6

Z7

Z8

Z4

Z3

Z2

Z1

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

-+

BE

LL

-+

BE

LL

Defects

Ext.

Bell

System

Battery

RESET

RESETTEST

BELL

ISOLATEMUTE

BUZZER WALKSELF

Mains On

NORMAL

AUXILARY

ISOLATE

3A

AC

LOCKINTER-

DEFECTEXT.

DBA

C O M

SWITCHES

N/C

N/O

AU

X

MAIN SYSTEMBOARD 302-7080

NZ3200 Main System Board

0 V 0 VBAT+27V

OUTPUT

SG

D T

yp

e I

I

MAINS CORD

CHASSISEARTHTERMINAL

BATTERY

F1

F2 F3

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

Page 5: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

4

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

CN1

CN9

CN2

CN5

API-708

API-588

CN1

CN2

CN3

API 708 CN4 PIN ALLOCATIONPin Function Cable Colour

1

2

3

4

5

6

Trial Evac

Trial Evac common

Ext. Brigade Isolate

Ext. Brigade Isolate common

Door switch

Door switch common

OrangeOrange

Green

Green

Blue

Blue

CN4 To keyswitches on door. Insulate connections.See Table below for correct wiring details

API-648 mounted to inside of bracket

6 Way PANDUIT ribbon fromCN2, API-708 to CN1, API-648

Lamp holders fitted to inside of bracketand wire back to CN5 pin1+3Note: remove lamps from API-708 andAPI-588 when using front mount panels

16 Way IDC ribbon from CN6, API-708to CN2, API-648(WA0059-5)

16 Way IDC ribbon from CN5,API-588 to CN2, API-648(WA0059-6)

Silence Alarm Brigade Use OnlyKeyswitch

Trial Evacuation keyswitch (trapped)

Door Switch (B56R) insulate connectors(See table below for allocation)

10 Way IDC cable(RIBBAB800LINK)

CN2

CN4

CN6

CN5

240AC TransformerMains Switch

AC AC

TB1

Cables run down the side of the cabinet. Use MNTRIBBCFCC4 clips to securethese cables. Note: run cables past hinge so as not to have them rub against sharp edges

Front loading Index panel

Earth strap to be connected from stud onthe side of panel to top hinge stud on door.

Hide keyswitch wiring behind lip of door

CN1

CN9

CN2

CN5

API-708

API-588Number 1

CN1

CN2

CN3

API 708 CN4 PIN ALLOCATIONPin Function Cable Colour

1

2

3

4

5

6

Trial Evac

Trial Evac common

Ext. Brigade Isolate

Ext. Brigade Isolate common

Door switch

Door switch common

OrangeOrange

Green

Green

Blue

Blue

CN4 To keyswitches on door. Insulate connections.See Table below for correct wiring details

API-648 mounted to inside of bracket

6 Way PANDUIT ribbon from CN2, API-708 to CN1, API-648 (WA0059-4)

Lamp holders fitted to inside of bracketand wire back to CN5 pin1+3Note: remove lamps from API-708 andAPI-588 when using front mount panels

16 Way IDC ribbon from CN6, API-708to CN2, API-648(WA0059-5)

16 Way IDC ribbon from CN5, API-588number 1 to CN2, API-648(WA0059-6)

Silence Alarm Brigade Use OnlyKeyswitch

Trial Evacuation keyswitch (trapped)

Door Switch (B56R) insulate connectors(See table below for allocation)

10 Way IDC cable(RIBBAB800LINK)

CN2

CN4

CN6

CN5

240AC TransformerMains Switch

AC AC

TB1

Cables run down the side of the cabinet. Use MNTRIBBCFCC4 clips to secure these cables. Note: run cables past hinge so as not to have them rub against sharp edges

Front loading Index panel

Earth strap to be connected from stud onthe side of panel to top hinge stud on door.

Hide keyswitch wiring behind lip of door

CN1

CN2

API-588Number 2

CN5

CN1CN2

API-588Number 3

CN5

CN3

16 Way IDC ribbon from CN5, API-588number 2 to CN2, API-648(WA0059-6)

16 Way IDC ribbon from CN5, API-588number 3 to CN2, API-648(WA0059-6)

NZ3200/16( 16 Zone )Front Access

NZ3200/32( 32 Zone )Front Access

CN2

Figure 2: Examples of 16 and 32 Zone Front Access FACP’s

Page 6: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

5

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

1.3 Main System Board 302-7080

The Main System Board provides most of the functions and common connections required by the NZ3200 system and the first eight zones.

The 302-7080 provides the following:

Bell circuits. SGD connections. Controls - Reset, Bell Isolate, Test, Buzzer Mute Aux Relay Isolate, Trial Evacuation and

Brigade Silence Alarm. System status indication. Power supply. Eight zone circuits.

Figure 3: 302-7080 Main System Board

R67

SW

9

BR1

-

+

RN13

ZD13

ZD12

ZD11

ZD10

ZD9

ZD8

ZD7

ZD6

CN7CN9

R63

C9+

C26

R22

R26

R29

CN8

C20

C38

C32

C25

C33

RN

7

RN

10

C16

+

SW1

SW

8

U9

R24

X1

U7

U17

U14

U16

U18

SW

7

M12

M18

M9

M13

M17

M16

M14

M7

M5

M11

M15

M19

C19

C23

C24

C29

C30

C34

C36

C39

RN11

C40

D28

C7

+

U10

U13

RN12

U11

U15CN6

C21RN4

R64

D45

TB2

D33

D38

D41

D47

D50

D53

D56

D59

D31

D37

D40

D44

D52

D55

D58

D36

D39

D43

D48

D51

D54

D57

CN10

LMP1

R33

R35

R37

R38

R41

R43

R45

R47

R49

R51

R55

R56

R58

R59

R62

R65

R36

R39

R44

R48

R52

R57

R60

R66

M4

M6

M8

M10

D13

+

C11

R14

R10

R4

R1

Q4

D4

RV1

CN3

U1

L1

C13

D19

ZD

4ZD3ZD2

R8R7

R6

R20

RL2

///

N/C

C

N/O

D23

D24

D26

D18

D5

D8

D11

D15

D9

D16

D10

D6

TH

1

C1

+

RL1

C8

+

U4

D21D20 D22

TB5

R12

R11

R13

R2

ZD1

SW5

SW4

CN4

C3

TB3

D14

ZD5

RN3

SW3

TB4

C5C6

R5

D3R3

C4

D7

D2

D25

D1

D12

C2

C12

C17

C18

+

C10

+

C15

C14

+

C41

C35

C27

C28

C37

C22

+

C31

CN2

CN5

CN1

D29

D27

D34D35

D42

D46

D17

D30

D49

D32

L4

L3

L2

Q3

Q2Q1

Q5

R27

R30

R31

R19

R16

R17

R18

R40

R15

R28

R23

R54

R25

R46

R53

R42

R50

R21

R61

R34

R32

RN1 RN

2

RN9

RN5

RN6

RN

8

RV2

SW2

SW6

TB1

TB6

U5

U3

U6

U8

U12

U2

R9

M1

D60

R68

R69

MIM

IC L

ED

Z8

Z7

Z6

Z5

Z4

Z3

Z2

Z1

-

-

-

-

-

-

-

-

+

+

+

+

+

+

+

+

POWER

LAMP

2A

2A

3A1A

VOLTAGE

CHARGER

SET

TRIMV.SENSE

EXT LED

NORMAL

DEFECT

DBA

FIRE

Z5

Z6

Z7

Z8

Z4

Z3

Z2

Z1

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

-+

BE

LL

-+

BE

LL

Defects

Ext.

Bell

System

Battery

RESET

RESETTEST

BELL

ISOLATEMUTE

BUZZER WALKSELF

AS

PI

Mim

ic

Mains On

NORMAL

AUXILARY

ISOLATE

3A

ACACLOCK

INTER-

DEFECT

EXT.DBA

COM

SWITCHES

N/C

N/O

AU

X

Z8Z1

302 7080NZ3200 Main system board

0V0VBAT

+27V

0V 0VBAT+27V

AC AC

OUTPUT

SG

D T

yp

e I

I

DC Out

Interlock connection

External defect connection

Direct Brigade Alarm input

SGD Type II connection

Auxrelayoutput

AC input fuse

ExtendedLEDConnection

SwitchConnection

Zoned bell selection switch

Zoned fire brigade call selection switch

Fire zone configuration switch

BellOutputs

DetectorZones

Remote mimic connection

ASPI relay connection

Connection to zone cards

Auxillary relay isolate switch

DisplayLamp

Systemconfigu-ration

ExtendedLED connnectionzones 1 - 8

Resetswitch

Defectindicators

Zone defectindicators1 - 8

Zone fireindicators1 - 8

Bell circuitfuses

DEFECT

F1

F4

F5

F2 F3

BZ1

ON

1 2 3 4 5 6 7 8

ON

1 2 3 4 5 6 7 8

ON

1 2 3 4 5 6 7 8

ON

1 2 3 4 5 6 7 8

AC in

Battery

Page 7: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

6

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

1.3.1 Main Board Terminal and Connector Summary

Screw Terminal Blocks TB1 Power TB2 External Other

1 27VAC In 1 DBA +ve 2 27VAC In 2 DBA 0volts 3 +27 volts Out 3 External Defect +ve 4 0 volts Out 4 External Defect 0 volts 5 Battery +ve 5 External Switch Interlock +ve 6 Battery -ve 6 External Switch Interlock 0 volts

TB3 Auxiliary Relay Output TB4 Bell Outputs

1 Auxiliary Normally Open RL1 Relay Contact 1 Bell 1 Output +ve 2 Auxiliary Common Relay RL1 Contact 2 Bell 1 Output -ve 3 Auxiliary Normally Closed RL1 Relay Contact 3 Bell 2 Output +ve 4 Bell 2 Output -ve

Plug In Connectors

CN1 SDG Connection CN2 Extended LED’s

1 +5 volts 1 +27 volts 2 Fire 2 Fire LED 3 +5 volts 3 DBA LED 4 Defect 4 Defect LED 5 Interlock 5 Normal LED 6 0 volts 6 0 volts

CN3 Auxiliary +27 Volts CN4 Door Controls 1, 5 0 volts 1 Trial Evacuation

3 + 27volts 2, 4, 6 0 volts 2, 4 No Connection 3 Ext Switch

5 Door Switch

CN5 Lamp CN6 Extended LED’s Zone 1 – 8 1 Lamp +ve 2 Zone 1 2 No Connection 4 Zone 2 3 Lamp -ve 6 Zone 3

8 Zone 4 CN8 Remote Mimic 10 Zone 5 1, 2 Line A, Line B 12 Zone 6 3, 4 Control 14 Zone 7 5 0 volts 16 Zone 8

CN7 ASPI Relay Connection CN9, CN10 Internal Comms

1 Data Out 1 Reset System 2 No Connection 2,4,6,8,10 0 volts 3 Clock 3 Line A 4 +27 volts 5 Line B

5,6,7 Address 7, 9 + 27 volts 8 0 volts

Page 8: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

7

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

1.3.2 Detector Circuits TB5 & TB6

The 302-7080 provides connection to eight zone circuits. All of the detector circuits can be configured to accept smoke detectors, heat detectors, manual call points or a combination of these devices. Detectors or manual call point types used are subject to the compatibility limitations.

Devices such as smoke detectors, which signal by increasing line current, can, when signaling, go through an optional Alarm Verification Facility (AVF). As such, when a detector goes into alarm, it is reset and not monitored for six to seven seconds, if an alarm is still present after this time, the system will latch into alarm. This function may be de-selected if desired in groups of two.

1.3.3 Bell Circuits TB4

The NZ3200 provides a monitored bell circuit split to drive two x 2Amp circuits. These circuits each require a 10K EOL resistor to give a system normal indication. If circuit is open or shorted, a defect signal is generated and the “Bells Fault” LED is illuminated.

See section 4 for connection details.

1.3.4 Bell Isolate (Internal)

This facility is set or reset by alternate pushes of the bell isolate switch. The yellow LED above the internal bell isolate switch indicates when the bell is isolated. When the bell is isolated, the bell relay will not respond to fire conditions thus enabling the system to be tested without disturbing the building occupants. This switch is monitored, see section 4.3.6.

1.3.5 Self Test

Pressing the “Test” button twice activates this function. This causes the unit to test each zone sequentially by placing it into alarm and defect conditions. When it has completed this test, it will automatically return to its normal mode of operation. This self-test may be terminated at any time by another press of the switch.

During the self test the Fire, Defect and Bell outputs are inhibited.

1.3.6 Walk Test

This function is initiated by pressing the “Test” button once on the Main System Board. When this button is pressed a LED directly above the switch indicates. While the panel is in the walk test mode the detectors can be operated in the field and the panel will automatically reset them after a period of four seconds. During the test the bell output and brigade output will operate as normal. To prevent an unnecessary fire call it is recommended to isolate the brigade. To restore the panel to normal operation simply repress the switch and the walk test indicator will turn off. This switch is monitored, see section 4.3.6.

1.3.7 Door Interlock

If any of the monitored switches as listed below within the NZ3200 are not in their normal state when the door is closed the buzzer will sound to alert the operator to this condition. If the condition is not rectified within two (2) minutes then a defect is signaled.

The following switches are monitored: Isolate, Test, AUX Relay Isolate, Walk Test and Internal Bell Isolate. If the Walk Test or Internal Bell Isolate are active when the door is closed, they automatically return to their normal state after forty seconds.

Provision is also made for auxiliary switches to be wired into the door interlock warning system via the interlock input on the Main System Board.

Page 9: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

8

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

1.3.8 Fault Indicators

Fault indicators are provided on the Main System Board for the following.

(a) Battery Fault. This indicates if the battery voltage is below 24.3 volts. (b) Bell Fault. This indicates an open or short circuit on bell line/s. (c) System Fault. This indicates one of the following:

Communications fault. A module is disconnected. The door was closed with a switch not in its normal position. See section 4.3.6.

(d) External defect (e) Zone defects (eight of)

1.3.9 DBA Input TB2

An input is provided for connection to any external device providing a Direct Brigade Alarm (DBA) output, eg sprinkler systems. A short circuit on this line will cause the DBA LED to light and the system bells to be energised. This input is monitored for normal condition with a 10K resistor. An open circuit will cause the DEFECT and SYSTEM LED to illuminate and the defect output to be energised.

1.3.10 Power Supply

The Main System Board has an on board switch mode power supply providing 27VDC at 1A for system power and charging the system batteries. The system incorporates a test function, controlled by the CPU on the 302-708, which decreases the power supply output voltage for forty-five minutes, every forty eight hours to check the condition of the system batteries. If the battery voltage falls below 24.3V during the test period a defect signal is generated and the battery fault LED is illuminated.

The system checks that the battery is connected four times a minute using the same test as above except the reduced voltage lasts for half a second.

1.3.11 Mains On Indicator

This LED is illuminated when the main power supply is connected and operational.

1.3.12 Ancillary Power Output TB1

A fused power supply output is provided to power ancillary devices. The output is marked +27V and 0V on TB1.

1.3.13 Fusing

The Main System Board has five fuses:

F1 AC Power supply fuse 3 Amp M205 F2 Power supply output fuse 1 Amp M205 F3 Battery fuse 3 Amp M205 F4 Bell circuit fuse 2 Amp M205 F5 Bell circuit fuse 2 Amp M205

Page 10: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

9

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

1.4 Zone Board 302-5880

The 302-5880 Zone board provides all the necessary functions to control and monitor eight (8) detector circuits. Up to three 302-5880 zone boards may be fitted to an NZ3200 system (NZ3200/32).

Figure 4: 302-5880 Zone Card

1.4.1 Detector Circuits

The 302-5880 zone board provides eight zone circuits, which operate identically to those provided on the 302-7080 board.

1.5 Batteries

The NZ3200/16 system is designed to accept two x 12V, 7 AH sealed lead acid batteries. These are fitted into the shelf on the inside of the door.

The NZ3200/32 system will accommodate two x 12V, up to 12 AH sealed lead acid batteries. These sit in the base of the cabinet.

See also Appendix A for battery calculations.

CPU

Address setting Mimic LED outputs

Connection from previous zone board

Connection to next zone board

Connection to auxiliary relay boards (ASPI) Configuration DIP switch

Fire selection DIP switch

Bell selection DIP switch

Lamp (fitted to rear of PCB)

Detector zone connection

CN6

LM

P1

CN2

CN11AUX.POWER

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

TB1

D9R31

RN4

CN5

ULN

2804

74HC573

74HC573

U13LM7805

DEFECT

+

U12

ec

b

RN1

SW3

UDN2983

74H

C574

74HC573

74HC574

U2

+

SW2

SW1

CN3

MIMIC DATA

K1

C36

R25

CN12

CN1

CN4

AUX DATA

OUTPUT

ON TO

MIM

IC L

ED

Z8Z1

ENABLE

SWITCH

CO

NF

IGFIRE

BELL

Z1

Z8

Z7

Z6

Z5

Z4

Z3

Z2

Z1-

+

+

+

+

+

+

+

+

-

-

-

-

-

-

-

302 5880 8 ZONE AZF

Z2

Z4

Z5

Z6

Z7

Z8

ZONE

Z3

FIRE

ON

1 2 3 4 5 6 7 8

ON

1 2 3 4 5 6 7 8

ON

1 2 3 4 5 6 7 8

Page 11: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

10

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

2 CONNECTING DEVICES

2.1 Detectors

A sample of the detectors approved for use with the NZ3200 are listed below. ( See Appendix A )

Detector Type Iq Order Code

Apollo Series 65 Ionisation Smoke Detector 45A 55000-217

Apollo Series 65 Photoelectric Smoke Detector 45A 55000-317

Orbis Photoelectric Smoke Detector with Flashing LED 120A 201-0501

Ampac Thermal Detector Blue Indicating 40A 4255-0300

Ampac Thermal Detector Yellow Indicating 40A 4255-0400

Ampac Fireray Beam 2000 8mA 220-0004

Ampac Fireray Beam 50R 4mA 220-0005

Ampac Fireray Beam 100R 4mA 220-0006

Note:

1. Iq = Quiescent Current Draw 2. The maximum current available for any one Detector Circuit is 4.8mA @ a line voltage

of 24VDC. As a guide to approximately determining the maximum number of detectors allowable on any one circuit, keeping in mind any losses, multiply the Iq of the type/s involved by the number required and if applicable (more than one type involved) add the resultants

3. Rate of Rise Heat Detectors are also available

FACP

+

-

3K3EOL1

2 SCREWCAPS

MOUNTINGHOLES

WIRE IN WIRE OUT

WIRE IN

HEAT DETECTORTERMINATING METHOD

AMPACVolts

LED

MEASURING LINE VOLTAGE

WIRE OUT

TB5

AMPAC MANUAL CALL POINT

IN +

+ OUT

IN - - OUT

SERIES65 DETECTOR

L1 In -R

L2

EarthL1 Out

AMPAC HEATDETECTOR

Figure 5: Example of Detector & MCP Wiring

The zone circuit must be terminated with an end of line resistor with a value of 3.3KΩ (2% tolerance or better, power rating 1/4W)

2.1.1 Detector Limitations

1. All indicating heat detectors draw a small monitoring current and this limits the number detectors that can be connected to a given zone circuit.

2. Detectors are not intended for use in areas subject to higher than normal corrosive environments or where corrosive gasses may be present.

2.1.2 Manual Call Points

Type !q Order Code

Ampac Manual Call Point 40µA 4255-700

Page 12: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

11

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

Connect as shown above.

Page 13: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

12

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

2.2 Bells and Sounders

Two bell/sounder circuits are provided, each capable of driving a 2 Amp load. These lines are monitored using a small current in reverse polarity to normal. For this reason it is necessary to connect bells via diodes, 1N4004 diodes are recommended, as shown below. Also observe bell/sounder polarity. If required these lines can be split to provide three or four bell parallel circuits total, however if this is done the end of line resistor must be changed. See table below for further detail.

+

-

Bell O/P1 or 2TB 1/2TB 3/4

EOL10K RESISTOR

BELLS

1N4004DIODES

Figure 6: Bell Sounder Connections

Bell Output 1 Bell Output 2

First Circuit Second Circuit First Circuit Second Circuit

No of Circuits

EOL Current

Available EOL

Current Available

EOL Current

Available EOL

Current Available

1 10K 2A - - *10K - - -

2 10K 2A - - 10K 2A - -

3 22K 1A 22K 1 10K 2A - -

4 22K 1A 22K 1 22K 1A 22K 1A

Note: For one bell circuit a 10K EOL is required on the panel on bell output 2.

Compatible Devices

Order Code Description

206-0002 Bell 24VDC Red 150 mm. 209-0018 Sounder with LED and mute facility.

205-0006 Horn Siren 24VDC 200mA Red.

205-0002 AS2W Flush sounder White 12/24V 15mA . 205-0001 AS2R Flush sounder Red 12/24V 15mA. 205-0009 Vara white 205-0010 Vara red 205-0011 Vector white 205-0013 Viper white 205-0014 Viper red 205-0062 Vantage Sounder AS2220 Evac Tones ( Red ) 205-0063 Vantage Sounder AS2220 Evac Tones ( White

205-0066 Vantage Combi Sounder AS2220 Evac Tones ( Red )

205-0067 Vantage Combi Sounder AS2220 Evac Tones ( White )

* Note: These devices do not comply with NZS4512 2003

Page 14: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

13

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

3 CONNECTING THE EVACUATION AMPLIFIER

3.1 Overview: The EVAC50W24V is one of a range of 100V-Line Amplifiers. Features include Generation of the ‘Alert’ and ‘Evacuation’ tones with verbal messages as specified by

NZS4512:2003. capable of driving up to 50W (with a 27.4VDC supply) into 100V PA loud speakers, the 100Vrms output line is overload and short-circuit protected and is monitored by the

amplifier circuit with the status transmitted to the panel. controlled through a set of signal (BELL) inputs. may be powered directly from the panel battery or from a separate DC source. when not active (100V line monitoring only) the amplifier draws less than 35mA. an optional microphone input board is available which can be used for public address

(PA) or ‘Fire Microphone’ operation.

3.2 Specifications:

Targeted Panel: NZ3200.

Board Dimensions: 97mm x 150mm. Height 50mm from bottom of PCB

Mounting Dimensions: 89mm x 130mm.

Operating Voltage: 20 - 29Vdc, nominal 27.4Vdc

Quiescent Current: 30mA RS485: <30mA @ 27.4Vdc

Operating Current: 2.5A @ 27.4Vdc nominal with 50W load.

Power Output: 50W @ 100V line: 27.4Vdc supply – overload and short-circuit protected

Tone: Evacuation tone and verbal message, compliant to NZS4512:2003 Programmed by using the LED base address dials and program mini-jumpers.

Monitoring: Fully monitored for open, short circuit or overload (10kΩ, 1W EOL resistor)

1200Hz

500Hz

VoiceMessage

3sec.

VoiceMessage

3sec.

0.0

sec.

3.7

5sec.

4.0

sec.

7.7

5sec.

8.0

sec.

11.7

5sec.

12.0

sec.

15.7

5sec.

16

.5sec.

19

.5sec.

20

.5sec.

23

.5sec.

24

.0sec.

3.75

sec0.25sec

Figure 7: NZS4512 Evacuation Signal with Voice Messaging

3.3 Operation: The Amplifier is connected to the FACP Bell circuit output as shown in the connection diagrams. Bell terminals ‘+’ and ‘-’ are connected to the corresponding ‘+’ and ‘-’ terminals on the amplifier. In the ‘Normal’ state, the FACP monitors the 100V line 10K 1W EOL resistor by applying an inverted voltage to the amplifier input terminals. In this state the amplifier connects the 10K 1W EOL line resistor to the Bell input. A 10K 1W EOL resistor must be used across the 100Vrms line for correct operation of the amplifier monitoring circuit.

Page 15: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

14

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

In the ‘Alarm’ state, the FACP reverses the bell voltage causing the amplifier to activate and output a repeating ‘Evacuation Tone followed by a voiced Evacuation Message’ onto the 100Vrms loudspeaker circuit. The amplifier is NOT monitored during the ‘Alarm’ state. If the amplifier output is overloaded, or the supply voltage becomes ‘Off-Normal’, the amplifier will signal a defect by turning on the Defect/Fault LED (refer Table 1).

Fault LED ON LED Defect Description

Off Off Amplifier inactive

Off Steady Amplifier active

Steady Flashing Supply Voltage below 10V or above 15V

Flashing Steady Amplifier output is overloaded

Table 1

The 100Vrms Line may have a maximum of three spurs. For these configurations an EOL resistor of the appropriate value must be installed at the end of each spur. (See Table 2).

Number Of Spurs Number Of Spurs

1 1 x 10K 1W

2 1 x 22K 1W on each spur

3 1 x 33K 1W on each spur

Table 2

3.4 Installation Criteria

Capacitively-coupled 100Vrms PA Speakers must be used with the 20W Amplifier. The capacitor must be bipolar and able to withstand 250V peak line voltage. The value should be around 1uF per watt of power for each speaker.

100Vrms speaker wiring must be separated from ELV (Extra Low Voltage) wiring.

Loading of the 100Vrms line must not exceed 20W.

An excessive load will cause the Amplifier to current limit and shutdown. The symptoms for this may be interruptions in the audio output and two or more amplifiers broadcasting out of synchronization.

Loading of the bell output must not exceed the maximum fuse (FACP Bell Circuit Fuse 4 = 2A) or relay (20W Amplifier Line Relay maximum contact current = 3A) rating.

100VRMS SPEAKERS

DECOUPLING CAPACITORS

10K OHM2W EOLRESISTOR

BELL IN

+

-

+-

Screen

+-

Figure 8: Basic Connection Diagram

Page 16: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

15

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

SPURRED 100VRMS SPEAKERS

DECOUPLING CAPACITORS

22K OHM1W EOLRESISTOR

BELL IN

+

-

+-

Screen

22K OHM1W EOLRESISTOR

+-

Figure 9: Spurred Speaker Wiring Diagram

302-7080

TB1

TB2

TB4BELLS

TB5ZONES

Z1

Z2

Z3

Z4

Z5

Z6

Z7

Z8

6K8

6K8

6K8

6K8

6K8

6K8

6K8

6K8

10K

10K

0R

DBA

EXT DEFECT

INTERLOCK

AC

AC

27V

0V

BATT

0V

CN4SWITCHES

CN6 IDC16MIMIC LED

CN10 IDC10ZONE EXPANSION

CN9 IDC10ZONE EXPANSION

CN2 6 WAY PANDUITEXT LED

GREY

GREY

330-0028 NZ3200 2A PSU

261-0002

261-0003

BATTERY

PINK

GREY

BLUE

PINK

GREY

BLUE

123456

320-0005- FRONT SERVICE KEYSWITCH

SW2287 DOOR SWITCHCAB1915

CAB1915

PINK

GREY

PINK

GREYCN5 3WAY PANDUIT

LAMP

CN8 5 WAY PANDUIT MIMIC

CN9 8 WAY PANDUITASPI

CN1 6WAY PANDUIT SGD TYPE II

CN3 5 WAY PANDUIT POWER

+

-

+

-

1C LOOP

ACTIVE

L(AC) PSU

N(AC) PSU NEUTRAL

NEUTRAL LOOP

BROWN(ACTIVE) TO C AND BLUE(NEUTRAL) TO NEUTRAL LOOP OF THE295-0001 (580M16) SWITCH SEE DIAGRAM BELLOW:

CLI574 PDL MAINS BLOCK295-0001 (CLI580M16) SWITCH

OEM2989 - 50W 24V AMP

DC SUPPLY IN+27.4V

-

+27.4V

-

+

-LINE (100V AUDIO)

10k 2WRESISTOR

DC SUPPLY OUT

OEM2989 - 50W 24V AMP

DC SUPPLY IN+27.4V

-

+27.4V

-

+

-LINE (100V AUDIO)

10k 2WRESISTOR

DC SUPPLY OUT

+

-

+

-

+

-

+

-

257-0003

CAB1923

123

CN6

CN1

302-5881 8 AZF ZONE CONNECTION

10k 0.6WRESISTOR

BELL IN

BELL OUT

BELL IN

BELL OUT

CAB1900

CAB1901

CAB1917

CAB1918

CAB1917

CAB1918

CAB1900

CAB1901

CAB1923

123

CAB1923

CAB1923 320-0007

240VAC FLEXABLE POWER CORD WITH PLUG

NZ3200 MAIN BOARD

(BELL O/Ps AREFUSED @ 2A)

10k 0.6WRESISTOR

FOE A SINGLE AMP INSTALLATION TERMINATETHE BELL OUT WITH A 10k 0.6W RESISTOR

Page 17: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

16

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

Figure 10: 16 Zone Front Service Cabling

Page 18: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

17

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

4 CONNECTING BRIGADE INTERFACES

The NZ3200 system allows for connection to the brigade signaling network using a Signal Generating Device (SGD Type II) software version 3.

4.1 Connecting a Signal Generating Device

To install the SGD firstly mount the unit on standoffs within the cabinet as shown below.

Figure 11: Connecting a SGD II

Connect SGD to the 302-7080 as shown above. All signals required for the SGD brigade signaling are found on connector CN1. The AMPAC Signal Generating Device is supplied with a connection cable. Simply connect one end of the cable to CN2 of the SGD and the other to CN1 of the 302-7080. Test the monitoring in accordance with the LTX SDG Input Interface Specifications.

MOUNT SGD ONSTAND OFFSPROVIDED INTHIS POSITION.

CONNECT CABLETO CONNECTORCN1.

CONNECT TO CN2

K2

M4

R10

U7

C11

C10

BZ

1

+

M3

M1

C2

+

U1

C1

+

CN

1

CN2

R1

X1

R6

C5

C4

R2

RN2

K1

C6

U3

C7

RN

1

R8

R9

R7

Q1

C8

C3

U4

R3

L1

ZD

1

L2

ZD

2

TB

1

M2

F1 D1

R5

U2

RN

3

R12

R11

R13

R14

U6 U5

R4

SW2

SW1 C9

302 678

250mA

7/8/97DO

OR

SW

ITC

H

FIR

E

SY

ST

EM

All links off = 16

SG

D

AD

DR

ES

S

PO

LL

ISO

LATE

DE

FE

CT

FIR

E

NO

RM

AL24 18

TE

ST

ISO

LATE

NO

RM

AL

NO

RM

AL

B-+ A

BAT

CH

TE

ST

ED

IIT

ypeS

GD A

MP

AC

CN6TB1 ZD1

G1

Z1

Z8

Z7

Z6

Z5

Z4

Z3

Z2

Z1

-

+

+

+

+

+

+

+

+

-

-

-

-

-

-

-

302 588 8 ZONE AZF

Z2

Z3

Z4

Z5

Z6

Z7

Z8

MAINS

SWITCH

TRANSFORMER

8 ZONECIRCUITBOARD302-5880

RELAY AREA

RELAY AREA

SW9

SW1

SW8

SW7

D2

8

TB2

D3

3D

38

D4

1D

47

D5

0D

53

D5

6D

59

D3

1D

37

D4

0D

44

D5

2

D5

5D

58

D3

6D

39

D4

3D

48

D5

1

D5

4D

57

CN10

LM

P1

BZ1

+

R10

RV1

CN3

U1

F5

F4

D2

3D

24

D2

6D

18

D5

D8

D11

D15

D9

D16

D10

D6

D21D20 D22

TB5

R2

SW5

SW4

CN4

TB3

SW3

TB4

D1

CN5

CN1

D49

R21

RV2

SW2

SW6

TB1

TB

6

M1

MIM

IC L

ED

Z8

Z7

Z6

Z5

Z4

Z3

Z2

Z1

-

-

-

-

-

-

-

-

+

+

+

+

+

+

+

+

POWER

LAMP

2A

2A

3A1A

VOLTAGE

CHARGER

SET

TRIMV.SENSE

NORMAL

DEFECT

DBA

FIRE

Z5

Z6

Z7

Z8

Z4

Z3

Z2

Z1

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

-+

BE

LL

-+

BE

LL

Defects

Ext.

Bell

System

Battery

RESET

RESETTEST

BELL

ISOLATEMUTE

BUZZER WALKSELF

Mains On

NORMAL

AUXILARY

ISOLATE

3A

AC

LOCKINTER-

DEFECTEXT.

DBA

C O M

SWITCHES

N/C

N/O

AU

X

MAIN SYSTEMBOARD 302-7080

NZ3200 Main System Board

0 V 0 VBAT+27V

OUTPUT

SG

D T

ype

II

MAINS CORD

CHASSISEARTHTERMINAL

BATTERY

F1

F2 F3

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

SW1

SW2

SW3

Page 19: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

18

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

5 SETTINGS

5.1 Main System Board (302-7080) Settings

The main system board has four (4) banks of DIP switches which are used to set the following:

SW6 - Zone cards fitted, monitoring etc. SW7 - Zone bell setting. SW8 - Zone fire output setting. SW9 - Zone configuration.

Note: each switch bank has eight switches. In the following discussion the bank is nominated first and the switch within that bank last. Thus SW6-2 would be the second switch on bank SW6.

5.1.1 Setting the Number of Zone Cards

Switches 1 and 2 of switch bank SW6 set the number of zone cards fitted to the system as shown in the table below.

Number of zone cards SW6 - 1 SW6 - 2

0 Off Off

1 On Off

2 Off On

3 On On

5.1.2 Miscellaneous Settings

The remaining six switches in switch bank SW6 set the functions as listed in the table below. Set the switch to the on position to enable the function.

Switch Function

SW6-3 Direct Brigade Alarm

SW6-4 Bell monitoring

SW6-5 Sound buzzer for defects

SW6-6 Factory use only – Must be set to OFF.

SW6-7 Switch on auxiliary output during trial evacuation

SW6-8 Unused

5.1.3 Setting Zone Bell Output

Each zone on the 302-7080 may be selected to either sound or not sound the bells when in alarm. To set a zone to sound the bells set the DIP switch on bank SW7 to on. For example to set zone two (2) to sound the bells when in alarm set SW7- 2 to on.

5.1.4 Setting Zone Brigade Call Output

Each zone on the 302-7080 may be selected to either call or not call the brigade when in alarm. To set a zone to call the brigade set the DIP switch on bank SW8 to on. For example to set zone two (2) to sound the bells and call the Brigade when in alarm set SW8- 2 to on.

Page 20: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

19

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

5.1.5 Allocating AVF to a Zone

AVF on each zone on the 302-7080 may be set to be either ON or OFF. To set a zone to have AVF set the DIP switch on bank SW9 to ON. For example to set zone two (2), four (4), six (6) and eight (8) to have AVF when in alarm set SW9- 2, 4, 6, & 8 to ON.

5.2 Zone Card (302-5880) Settings.

The zone card has three (3) banks of DIP switches which are used to set the following:

SW1 - Zone bell setting. SW2 - Zone fire output setting. SW3 - Zone configuration.

Also a set of four jumper pins is used to set the address

5.2.1 Setting the Address of the Zone Cards.

For the zone card to function correctly the address must be set using the address jumpers which are found immediately above the micro-controller. Each card in the system must have a unique address.

1

2

3

Address Setting

5.2.2 Setting Zone Bell Output

Each zone on the 302-5880 may be selected to either sound or not sound the bells when in alarm. To set a zone to sound the bells set the DIP switch on bank SW1 to ‘ON’. For example to set zone two (2) to sound the bells when in alarm set SW1-2 to ‘ON’

5.2.3 Setting Zone Brigade Call Output

Each zone on the 302-5880 may be selected to either call or not call the brigade when in alarm. To set a zone to call the brigade set the DIP switch on bank SW2 to ‘ON’. For example to set zone two (2) to call the brigade when in alarm set SW2- 2 to ‘ON’.

Zone AVF SW9 Setting

Zone 1 1 Off

Zone 2 2 On

Zone 3 3 Off

Zone 4 4 On

Zone 5 5 Off

Zone 6 6 On

Zone 7 7 Off

Zone 8 8 On

ON

1 2 3 4 5 6 7 8 Switch 9 set to above example

Page 21: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

20

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

5.2.4 Setting Zone Configuration

AVF on each zone on the 302-5880 may set to be either ON or OFF. To set a zone to have AVF set the DIP switch on bank SW3 to ON. For example to set zone 10, 12, 14, &16 to have AVF when in alarm set SW3- 2, 4, 6, & 8 to ON.

6 SPECIFICATIONS

Size 450mmH x 400mmW x 130mmD (NZ 3200/16) 753mmH x 400mmW x 130mmD (NZ 3200/32) Mains Supply 230V AC ± 10% @ 0.5A Power Supply Battery Charger Output Voltage 27V Output Current (continuous) 1A Output Current (peak) 1.8A Quiescent Current Main Board 0.045A Quiescent Current 8 Zone Board 0.053A Bell Circuits 2 X 2A Circuits Auxiliary Relay Change Over Contacts 5A @ 30V Detector Circuits

Maximum Cable Loop Impedance 50

Zone AVF SW3 Setting

Zone 9 1 Off

Zone 10 2 On

Zone 11 3 Off

Zone 12 4 On

Zone 13 5 Off

Zone 14 6 On

Zone 15 7 Off

Zone 16 8 On

ON

1 2 3 4 5 6 7 8 Switch 3 set to above example

Page 22: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

21

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

7 INSTALLATION AND INITIAL OPERATION

7.1 Unpacking And Inspection

Carefully check packing before unpacking goods for any transit damage. Unpack the goods and check both externally and internally for any loose or damaged components that may affect the appearance, installation or operation of the goods. An index of packaged goods is supplied loose.

7.2 Anti Static Precautions

To prevent damage to panel components please ensure that you are correctly earthed before touching or handling any of the wiring or printed circuit boards within the panel.

7.3 Installing the NZ3200

Do not apply power or connect batteries during this procedure.

1. Unpack the NZ3200 system. 2. Check for transit damage. 3. Unplug CN1 from the Main System Board and battery leads from TB1. 4. Unplug CN4 ( and CN2 on F.S. panels ) 5. Using a screwdriver undo four (4) slotted nuts holding the internal panel into the cabinet. 6. Withdraw the internal panel. 7. Drill all cable access and mounting holes. 8. Mount the unit into position. 9. Feed cables into the unit. 10. Install the engraved index with mounting provided. 11. Install the internal panel and secure with slotted nuts. Reconnect CN4 ( and CN2 for

Front Service panels. 12. Install any option cards and/or SGD. 13. Connect mains cabling to the mains switch. Ensure incoming Mains is properly earthed

using stud provided. 14. Connect detector cabling. 15. Connect ancillary cabling. 16. Set DIP switches on the 302-7080 and 302-5880 as necessary.

7.4 Removing and Reinstalling the Index Panel

To remove the index panel with the panel installed and wired requires the following before the above procedure can be performed.

1. Turn off mains power to the unit at the distribution board. 2. Disconnect the batteries. 3. Disconnect mains cabling from the switch block. 4. Remove all cables on the 302-7080, and 302-5880 if fitted, noting the position of each

cable before removal. 5. Reverse procedure once the index has been fitted.

7.5 Initial Operation

1. Switch on mains power to the unit. 2. The internal buzzer will sound for approx one second. Battery defect LED should be

illuminated. 3. Connect batteries. Press ‘RESET’, Battery defect LED should extinguish. 4. The unit is ready for operation.

Page 23: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

22

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

8 SYSTEM OPERATION

8.1 Resetting the System

To reset the system after a fire, press the ‘RESET’ button on the Main System Board. This will return the system back to its normal state if the cause of the alarm has been removed. The buzzer will sound for confirmation.

8.2 Isolating the Bells/Sounders

Bells may be isolated by either pressing the Bell Isolate switch on the Main System Board, or by operating the ‘Silence Alarms’ key switch on the outside of the cabinet.

Pressing Bell isolate on the Main System Board will cause the buzzer to beep and the LED above the switch to illuminate. To return Bells to normal press the switch again.

Note: Operating the key switch will cause a Defect signal to be sent.

8.3 Using the Walk Test Facility

To start the walk test facility, press the ‘Test’ switch on the Main System Board. The buzzer will beep once and the LED above the switch will illuminate. To avoid signalling the brigade isolate the Signal Generating Device (SGD). If it is not desirable to operate the sounders then isolate the bell as detailed above. Do not close the door at this stage.

The detectors can now be tested. As a detector is set into alarm the system will operate as normal, except that after approximately four seconds the detectors on the circuit in alarm will be reset. After testing is complete, press the ‘Walk Test’ switch to return to normal. Return any other switches to normal before closing the door of the NZ3200.

8.4 Self Test Facility

To start the test, press the ‘Test’ button twice. The system will now place each zone into fire and defect conditions sequentially. After each zone is tested, the system will flash the Defect and Fire LED of each zone that operated correctly.

The test will terminate when finished. It may also be terminated at any time by a another press of the ‘Test’ switch.

8.5 Evacuation

On the door of the NZ3200 a key switch is provided for Evacuation, operating this key switch will cause the system to operate the bells. This will override any other bell isolate or silence condition.

Page 24: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

23

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

9 OPTIONS

9.1 ASPI Relay Board

9.1.1 Description The ASPI (AMPAC Serial Peripheral Interface) Relay Board ( 302 5930 ) will provide the NZ3200 system with a 5 Amp relay contact for use by ancillary devices.

A fire zone or certain system functions can activate the relay. Refer to the table below.

TO CN7 OF THE MAIN SYSTEM BOARD 302 7080OR CN4 OF THE ZONE BOARD

N/O

COM

N/C

N/C=NORMALLY CLOSEDCOM=COMMONN/O=NORMALLY OPEN

C5

+

C4

+

RN1C3

R7

R1

R6

R5

K3SELECT

R4

U3

LM

78

L0

5

K1ADDRESS

CN2CN1

TB1

C2

C1

K2RTN

RL1JS1-12V

Q1

BD139

U2

74

HC

59

5

U1

74

HC

13

8

D11

D10

D9

D8

D7

D6

D5

D4

D3

D2

D1

R3

R2

D12

OF SELECT JUMPERS 1 to 3FIT ANY COMBINATION

ADDRESS JUMPER 1

K1 FIT ONLY ONE

78

654321

7654321

N/O

C OM

N/C

302 5930

AS

PI K1

K3

1

2

3

4

5

6

7

8

NOT USED

Example: Relay setto operate on Alarmin Zones 1 &2

1

2

3

4

Figure 12: ASPI Relay Board Layout

9.1.2 Settings

Select K3 Address 4 K1 Address 2 * K1 Address 1 K1

1 Zone 1 alarm Buzzer Zone 1 defect 2 Zone 2 alarm Bell # Zone 2 defect 3 Zone 3 alarm Defect Zone 3 defect 4 Zone 4 alarm Fire ! (selected zones) Zone 4 defect 5 Zone 5 alarm Fire (any zone) Zone 5 defect 6 Zone 6 alarm Normal Zone 6 defect 7 Zone 7 alarm Zone 7 defect 8 Zone 8 alarm PSU shutdown Zone 8 defect

# Will not operate on Trial Evacuation ! Normally energized. Operates from zones with “FIRE” output selected * 302-7080 only

9.1.3 Installing the ASPI Relay Board

1. Power system down and mount the board on standoffs at the bottom left side of the

panel. Holes are already drilled to accept these.

2. To connect a single ASPI board to an 302-7080, plug one end of the eight-way cable provided into CN1 of the ASPI board and the other end into CN7 of the 302-7080. To add more than one ASPI board onto an 302-7080 connect CN1 of the second ASPI board to CN2 of the first, etc. A maximum of four ASPI boards is permitted per 302-7080. ASPI relay boards may also be connected to the 302-5880. Only four ASPI relay boards may be fitted to a single 302-5880.

3. On the ASPI board there are a number of options available. Link K1 sets the address

of the board, only one address may be selected, only the 302-7080 board uses address 2. Link K3 sets the conditions that will activate the relay. Any combination is allowable. For example if the relay needs to activate from a fire on zone 1 or 2 then K1 would be set to 4 as Address 4 contains the zone alarm conditions and jumpers inserted in Select 1 and 2 as they are the link to the actual zones. See above. Link K2 must be left open.

4. Turn system on and test relay functions.

Page 25: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

24

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

9.2 8 Way Relay Board

9.2.1 Description 302-6623 provides 8 zoned outputs in the NZ3200 fire alarm system, using the AMPAC Serial Peripheral Interface (ASPI). Only one 302-6623 may be connected directly to each 302-5880 zone board. Voltage-free changeover contacts are provided, with a 2A rating. Fast Fit Product Code is 155-0003.

9.2.2 Connections

CN2 on the relay board connects to either CN4 (AUX DATA) on the zone board, or to the previous ASPI device, by means of an 8-way cable. To add more than one ASPI boards onto an 302-5880 connect ASPI IN of the second ASPI board to ASPI OUT of the first , etc. Fit the G0098 ASPI Line Termination Plug to ASPI OUT on the last board on the ASPI bus. A maximum of four ASPI boards is permitted per 302 5880 or 8 per 302-7080. No connection should be made to CN1 or CN3, though CN3 may be used to monitor the 24V supply to the relay board.

9.2.3 Technical Specifications

SIZE 175mm x 98mm

FUNCTION SWITCHES 4 x selectable zone output selection

POWER SUPPLY Provided via 8 way ribbon , nominal 27VDC ( 20-28V @ 170ma ) Local 5V provided by IC3

OUTPUTS Alarm, Isolate, Battery fault, valve monitor relays change- over contacts rated at 2A

Relay 1-4 ( RL5,6,7 and 8 ) selectable change-over contacts rated at 2A

Contacts normally voltage-free, nominal 27V supply available to be wired to relays to provide switched 27V.

COMMUNICATIONS Type Synchronous serial CMOS level

Speed- Up to 100Kbps

9.2.4 Communications

The 302-6620 connects to the main FACP via HCMOS level synchronous serial transmission. IC5 decodes the chip selects, and allows clock and data into shift register IC4 via tristate buffer IC2. IC3 drives the relay coils.

9.2.5 Interface Relays

ALARM RELAY (CN5)

The alarm relay provides volt-free changeover contacts, which operate when any zone goes into alarm, except for indicate-only or valve monitor zones.

Note: this relay also operates if alarm test is carried out on any zone (except for indicate-only or valve monitor zones).

ISOLATE RELAY (CN6)

The isolate relay provides volt-free changeover contacts, which operate when any zone, or the fault output, is isolated.

BATTERY FAULT RELAY (CN7)

The battery relay provides volt-free changeover contacts, which operate when the panel detects a battery fault.

Page 26: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

25

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

VALVE MONITOR RELAY (CN8)

The valve monitor relay provides volt-free changeover contacts, which operate when any valve monitor zone goes into alarm.

Note: this relay also operates if alarm test is carried out on any valve monitor zone.

9.2.6 Link Settings

For correct operation with the NZ3200 the jumper on LK1 must be set to position 7

Figure 13: Link Settings

RELAY CONNECTIONS

Alarm Output

Isolate Output

Normally open Terminal block CN5 pin 1 Normally open Terminal block CN6 pin 1 Common Terminal block CN5 pin 2 Common Terminal block CN6 pin 2 Normally closed Terminal block CN5 pin 3 Normally closed Terminal block CN6 pin 3 Battery Fault Output

Valve Monitor Output

Normally open Terminal block CN7 pin 1 Normally open Terminal block CN8 pin 1 Common Terminal block CN7 pin 2 Common Terminal block CN8 pin 2 Normally closed Terminal block CN7 pin 3 Normally closed Terminal block CN8 pin 3 Relay 1 Output

Relay 2 Output

Normally open Terminal block CN9 pin 1 Normally open Terminal block CN10 pin 1 Common Terminal block CN9 pin 2 Common Terminal block CN10 pin 2 Normally closed Terminal block CN9 pin 3 Normally closed Terminal block CN10 pin 3 Relay 3 Output

Relay 4 Output

Normally open Terminal block CN11 pin 1 Normally open Terminal block CN12 pin 1 Common Terminal block CN11 pin 2 Common Terminal block CN12 pin 2 Normally closed Terminal block CN11 pin 3 Normally closed Terminal block CN12 pin 3 Note: 27V supply (may be wired to relay common connections to convert the outputs to switched positive outputs)

+27V Terminal block CN3 pin 1 +0V Terminal block CN3 pin 2

IC3

R1

IC2

RN

1

LK1IC1

CN1 C1

C2

C3CN2 CN4

1

765432

11

1

Page 27: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

26

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

9.2.7 Programmable Relays

Each of the four programmable relays provides volt-free changeover contacts, which operate when one or more of the selected zones go into alarm.

Corresponding to each relay is a 4-pole DIP switch.

SW1 controls Relay 1 (CN9) SW2 controls Relay 2 (CN10) SW3 controls Relay 3 (CN11) SW4 controls Relay 4 (CN12)

The 4 poles correspond to the 4 zones.

Pole 1 selects zone 1 Pole 2 selects zone 2 Pole 3 selects zone 3 Pole 4 selects zone 4

To select one or more zones to operate a particular relay, the required poles on the appropriate DIP switch are set to the ON position. For example: If poles 1 and 3 of SW2 are set to the ON position, relay 2 will operate when zone 1 OR zone 3 go into alarm.

Figure 14: 8 Way Relay Board Layout

M10

CN12CN11CN10CN9CN8CN7CN6

M2

M1

RL8

D7

SW1

SW2

IC5

D9

D10

D11

D12

D13

D14

D15

D16

D17

D18

D19

D20

D21

D22

D23

D24

IC3

IC4

R1

R3

R2

IC2

RN

1

M5M4M3 M9M8M7

LK1IC1

M6

CN1

D1

D2 D3 D4 D5 D6 D8

RL1 RL2 RL3 RL4 RL5 RL6 RL7SW3

SW4

C1

C2

C4

C3

CN2 CN4

CN3CN5

1

765432

11

RELAY 4RELAY 3RELAY 2RELAY 1VALVEBATTERYISOLATEALARM

302 6623

RELAY2 RELAY4

1

RELAY1 RELAY3

+ -

Brigade powerconnect 24V

FAULT MONITOR

C N C N CCN O N CCNO N O N CCN O N CCC N CN ON O N CCN O N CC24V N O

ASPI In

ASPIOut

O N

1 2 3 4

O N

1 2 3 4

O N

1 2 3 4

O N

1 2 3 4

No

t U

se

d

N/O = Normally Open

C = Common

N/C = Normally Closed

Page 28: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

27

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

9.3 LED Mimic Driver Board

9.3.1 Description

The LED Mimic Driver Board (302-7150) in-conjunction with LED Mimic Display Board (302-7330) is designed to provide remote indication of the current status of an NZ3200 fire detection system. The mimic will indicate any zones in alarm as well as providing common fire, defect, DBA and system normal indications.

The LED Mimic Driver Board receives power and RS485 communications from the main panel. In small systems with 1, or 2 LED Mimic Driver Boards cabling can be achieved by using 2 Pair

Twisted 100 Shielded Data Cable (0.2mm2 cores minimum) eg OLEX JECP87F5002, BELDEN

9804, see Table 1 (on runs of less than 400 meters). In larger systems with more than two LED

Mimic Driver Boards or long cable distances using 1 Pair Twisted 100 Shielded Data Cable eg OLEX JECP87F5001, BELDEN 9841 for communications it will be necessary to supply power to LED Mimic Driver Boards via separate cables. The size of the power cables will depend on the number of mimics used and the total distance. Operation of the LED Mimic Driver Board is not monitored by the fire panel. If communications to the LED Mimic Board fail, the LED Mimic Board will flash the 'Defect' LED rapidly to indicate a communication defect. Correct operation of the LED Mimic Driver Board and fire panel is confirmed by the 'Normal' LED flashing on the LED Mimic Driver Board. The use of a LED Mimic Driver Board requires the installation of a Mimic Interface Board (302-6360) within the NZ3200 main panel.

SCR TX- TX++27 OV+27

TB

3

TB

1

OUT

OV GND

IN

SCR TX- TX+

To TB1 on nextLED Mimic Board

302-7150LED MIMIC DRIVER BOARD

TB

1

MIM

ICS

- + B ASH

302-6360MIMIC INTERFACE BOARD

NOTE:INSERT 'LK1' ON LASTLED REPEATER BOARD

Figure 15: Cabling Using 2 Pair Data Cable

Recommended Maximum Cabling Distances using 2 Pair Data Cable.

Number of LED Mimic Boards Maximum Distance

1 400m

2 200m

SCR TX- TX++27 OV+27

TB

3

TB

1

OUT

OV GND

IN

SCR TX- TX+

To TB1 on nextLED Mimic Board

302-7150Product Code 155-7150

LED MIMIC DRIVER BOARD

TB

1

MIM

ICS

- + B ASH

302-6360Product Code 155-0016

MIMIC INTERFACE BOARD

NOTE:INSERT 'LK1' ON LASTLED MIMIC DRIVER BOARD

Figure 16: Cabling Using 1 Pair Shielded Cable and Separate Power Cable

Page 29: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

28

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

Recommended Power Cable Size for Larger Systems.

Number of LED Repeater boards

Distance = <500m

Distance = 500m< >100m

Distance = 1000m< >1500m

Distance = 1500m< >2000m

1 0.3mm2 0.5 mm

2 1 mm

2 1.5 mm

2

2 0.5 mm2 1 mm

2 1.5 mm

2 2.5 mm

2

3 0.75 mm2 1.5 mm

2 2.5 mm

2 4 mm

2

9.3.2 Specifications

DIMENSIONS: 197 mm (L) x 108 mm (W) x 25 mm (D)

POWER REQUIREMENTS: Voltage 27VDC Current 100 mA (max)

FUNCTION KEYS - Lamp test - Lamp reset - Buzzer mute - CPU reset - Address switches - System switches

INDICATORS (LED) ON 302-7150 - Power on Green LED - Normal Green LED - Defect Yellow LED

POWER SUPPLY - Provided via TB1, 20 to 28VDC @ 100 mA maximum - 5volt output (aux power)

OUTPUTS - 32 outputs for Zone indication CN1, CN2, CN3, CN4

- 4 outputs for Alarm, DBA, Defect and Normal indication CN5 - 1 buzzer output

9.3.3 Installation

To install the Mimic Interface Board & LED Mimic Driver Board.

1. Power system down.

2. Mount the Mimic Interface Board on standoffs at the bottom or left side of the panel. Holes are already drilled to accept these (same mounting hole size as Single ASPI Relay Board).

3. To connect a Mimic Interface Board to an 302-7080, plug one end of the first five-way cable provided into CN1 (Comms) of the Mimic Interface Board and the other end into CN8 (Mimic) of the 302 708, plug one end of the second five-way cable provided into CN2 (Power) of the Mimic Interface Board and the other end into CN3 of the 302-7080.

4. Mount the LED Repeater Board in target enclosure on stand-offs. Connect 302-7330 LED Mimic Board to 302-7150 LED Mimic Driver Board via cables provided. Connect communication, and power cables from 302-6360 Mimic Interface Board (In NZ3200 panel) to 302-7150 LED Mimic Driver Board.

5. Set Switches as follows SW2-1 OFF, SW2-2 OFF, SW2-3 ON, SW2-4 OFF, SW2-5 OFF, SW2-6 ON , SW2-7 OFF, and SW2-8 ON (All LED Repeater Boards are set to address No. 4).

6. Turn system on.

Page 30: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

29

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

OUTPUT

ON TO

MIM

IC L

ED

ENABLE

SWITCH

CO

NF

IG

FIRE

BELL

Z1

Z8

Z7

Z6

Z5

Z4

Z3

Z2

Z1

-

+

+

+

+

+

+

+

+

-

-

-

-

-

-

-

68HC705C8

302 588 8 ZONE AZF

Z2

Z3

Z4

Z5

Z6

Z7

Z8

ZONE

CN6

LM

P1

CN2

AUX.POWER

CN11

DEFECT

D33

DEFECT

D32

DEFECT

D31

DEFECT

D30

DEFECT

D29

DEFECT

D28

DEFECT

D27

FIRE

D25

FIRE

D24

FIRE

D23

FIRE

D22

FIRE

D21

FIRE

D20

FIRE

D19

FIRED18

D1

7D

16

D1

5D

14

D1

3D

12

D11

D1

0

TB1

CN5

LM7805U13

DEFECTD26

SW3

SW2

SW1

MIMIC DATA

CN3

CN12

CN1

AUX DATACN4

TRANSFORMER

D11

TB

6

TB

1

SW6

SW2

RV2

Q1

F3F2

D49

CN1

CN5

CN2

D1

TB4

SW3

TB3

CN4

SW4

SW5

TB5

D22D20 D21

D6

D10

D16

D9

D15

D8

D5

D1

8D

26

D2

4D

23

F4

F1

F5

U1

RV1 +

LM

P1

CN10

D5

7D

54

D5

1

D4

8D

43

D3

9D

36

D5

8D

55

D5

2

D4

4D

40

D3

7D

31

D5

9D

56

D5

3D

50

D4

7D

41

D3

8D

33

TB2

CN6

D2

8

SW

7S

W8

SW1

CN8

CN9 CN7

BR1

SW

9

SG

D T

ype I

I

OUTPUT

ACAC

+27V BAT 0V0V

+27V BAT 0V0V

NZ3200 Main System Board302 708

AU

X

N/O

N/C

SWITCHES

COM

DBA EXT.

DEFECT

INTER-

LOCK

AC AC

3A

ISOLATE

AUXILARY

NORMAL

Mains On

Mimic AS

PI

SELF WALKBUZZER

MUTE ISOLATE

BELL

TEST RESET

RESET

Battery

System

Bell

Ext.

Defects

BE

LL

+-

BE

LL

+-

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

FIRE

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

DEFECT

Z1

Z2

Z3

Z4

Z8

Z7

Z6

Z5

FIRE

DBA

DEFECT

NORMAL

EXT LED

V.SENSE

TRIM

SET

CHARGER

VOLTAGE

1A 3A

2A

2A

LAMP

POWER

+

+

+

+

+

+

+

+

-

-

-

-

-

-

-

-

Z1

Z2

Z3

Z4

Z5

Z6

Z7

Z8

MIM

IC L

ED

U7

R5

M2

M1

R6

C1+ +

C4

C3

D2

R4

R3Q1

BC548

R7

F1

500mA

R1

ZD2

ZD1

D1

R2C2

L2

L1

U4

LM78L05

C5+

CN1

CO

MM

S

CN2

PO

WE

R

U374HC02

U2MAX485

U1MAX485

TB1

TOLED

MIMICDRIVER

M3

302 636

-

+

B

A

SH

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

O N

1 2 3 4 5 6 7 8

PDL POWER SWITCH

-

+

B

A

SH

Main System Board302 708Interface Board

302 636

MimicDriverBoard

302 715

Remote LEDBoard 302 733

CN5

CN1

CN2

CN3

CN4

CN1

CN2

CN3

CN4

CN5

TB1 TB1 CN1

CN2

CN8

CN3

5 Way Cable

Comms

PowerRS485+/- 27VDC

Figure 17: Main and Mimic Interface Board Cabling & Overall Block Diagram

Page 31: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

30

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

9.3.4 Component Layout

+

Aux 5V 500mA O/Pfor LED Expansion

BUZZER MUTE

LAMPRESET

LAMPTEST

FAULTNORMALPOWER ONLED DISPLAY

N/O

N/C

C0V

GP

I

302-7150 MAR 1999

OUT TB3

-

+-

+

GN

D

CPU RESET

OFF ON

ADDRESS

SYSTEM

LEDS FLASH

FA

CT

OR

YU

SE

ON

LY

SH

BA

SH

BA

K1

K2

ALM

PRE

DBA

DFT

NOM

RST

LT

BM

BI

EVC

BZ

1

2

3

4

5

LED

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

D4D3D2

SW3

CN7

SW7

SW2

SW5

SW4

SW6

BZ

1

U10

RL1

TB4

TB5

IN TB1

U7

U9

U8

U6

CN4

U4

CN6

U2

U5

Q1

HY1

CN3

CN2

CN1

U3

CN5

Q2

Mimic LEDBoard CN1Fire, DBA,Defect,Normal

Mimic LEDBoard CN2Zones 1-8

Relay O/P

Programable I/P

RS485 O/P

RS485 I/PFrom TB1 MimicInterface Board

27V IN

Fit Link K1 toLast Mimic Only

Voltage Free Changeover Contacts max 1A

Must be Voltage Free Contact

INPUTS

+ -

To Next LED Mimic if Required

27V O/P

SW2 Settings1-5, Address ( Max 31 )6, Configuration set to OFF for FACP set to ON for EVAC7, Not used8, LED Setting ON = Flash OFF = Steady

Iq = 8mA

Fit Link K2for Buzzerto Sound

ON1 2 3 4 5 6 7 8

ON1 2 3 4

SW1

NOT FITTEDFOR FACP

Mimic LEDBoard CN3Zones 9-16

Mimic LEDBoard CN2

Zones 17-24

Mimic LEDBoard CN3

Zones 25-32

Figure 18: 302-7150 LED Mimic Driver Board

Communications& Power To First:LED Mimic Driver

Board 302-6360

To NZ3200302-7080 CN8

To NZ3200302-7080 CN3

R5

M2

M1

R6

C1+ +

C4

C3

D2

R4

R3Q1

BC548

R7

500mA

R1

ZD2

ZD1

D1

R2C2

L2

L1

U4

LM78L05

C5+

CN1

CO

MM

S

CN2

PO

WE

R

U374HC02

U2MAX485

U1MAX485

TB1

MIMICS

M3

302 636

-

+

B

A

SH F1

Figure 19: 302-6360 NZ3200 Mimic Interface Board

Page 32: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

31

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

ON

1

2

3

4

5

6

7

8

302-715 REMOTE LED INDICATOR BOARD

REMOTE BUZZER

EVACUATION SW

BELL ISOLATE SW

BUZZER MUTE SW

LAMP TEST SW

RESET SW

302-733 REMOTE EXPANSION LED BOARD

26 WAY RIBBON

16 WAY RIBBON

16 WAY RIBBON

RS485In

1.2K Max

27VDC

-+

MUTE

TEST

N/F

SC

RT

X-

TX

++

27

OV

+27

K1

K2

Q2

CN5

X1

U3

CN1

CN2

CN3

HY1

Q1

U5

CN6

CN4

U8

U9

U7

TB3

TB1

TB5

TB4

RL1

U10

SW6

SW4

SW5

SW2

SW7

CN7 SW3

D2 D3

D4

POWER OUT

BUZZER

RESET

LAMP

FAULTNORMALPOWER ONLED DISPLAY

N/O

N/C

C0

VG

PI

302-715

OU

T

OV

GN

D

IN

CPU RESET

OFF O N

ADDRESS

SYSTEM

LEDS FLASH

FA

CT

OR

YU

SE

ON

LY

SC

RT

X-

TX

+

FIT K1 ONLAST MIMIC

ONLY

FIT K2

FOR BUZZER

ALM

PRE

DBA

FLT

NOM

RST

LT

BM

BI

EVC

BZ

1

2

3

4

5

LED

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

LAMP

LED AUX 5V

U2

BZ

1 +

U4

U6

TB2

TB1

D2

CN1

D10

D4

D3

D20

D19

D18

D17

D15

D14

D13

D12

D11

D9

D8

D7

D6

D5

D1

CN3

CN2

D21

RE

SE

TL

AM

P T

ST

BZ

MU

TE

BE

LL IS

OL

EV

AC

BZ

+B

Z-

ALARM

PRE-ALM

DBA

DFCT

NORM

D16

IF APPLICABLE ONLYLOWER SECTION OFBOARD IS USED FORZONES 17 - 32

IF APPLICABLE CN3, CN4 CONNECT TO CN2, CN3RESPECTIVELY OF 2nd REMOTE EXPANSION LEDBOARD FOR ZONES 17- 32

Figure 20: Cabling From the Remote LED Mimic Driver Board to the Remote Expansion LED Board

Page 33: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

32

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

9.4 24 Volt Bell Driver Board

9.4.1 Description

The API-731(24V Bell Driver) allows a larger number of bells and sounders to be connected to the NZ3200 system than is normally possible.

This bell driver allows the NZ3200 system to monitor the bell lines as usual. This means a total of four bell drivers may be connected to an NZ3200 system whilst maintaining full monitoring. Larger numbers may be used if monitoring is not required. Many variations are possible when connecting the bell drivers. The design of the bell driver retains the monitoring from the NZ3200 system, lines should be terminated as specified in the NZ3200 operators manual. 9.4.2 Features

The board provides a switched 27volt monitored output with a Defect output being returned to the NZ3200 for brigade indication. 9.4.3 Specifications

Size : 84mm x 48mm Power Requirements : 27V DC @ 10mA

9.4.4 Connections To install the bell driver board:

1. Disconnect mains power and batteries from the NZ3200 system. 2. Mount the bell driver using one of the option board locations. 3. Connect TB3 of the bell driver board to the Bell output of the NZ3200 302 708), +CTRL

connects to Bell+, -CTRL connects to Bell-. 4. Connect TB3:+VE of the bell driver to the positive of the batteries (may be connected at the

API-708, or from a previous bell driver), connect TB3: -VE to the negative of the batteries. 5. Terminate the bell line into the BELL (TB1:Bell+ and Bell-) output of the bell driver. 6. Terminate TB2:+VE,-VE of the BELL the bell line into the External Defect TB2:3,4 302 708)

as shown. 7. Turn on the NZ3200 system. Check that the Defect LED on the bell driver board isn’t

illuminated.

In the example below the system is able to drive a 24V 2Amp bell line and three 24V 2 Amp bell lines. Because the current required by the bell driver from the 320 708 board is very low, it is permissible to supply the full two amps from each bell output of the 320 708. In this instance each bell line would be terminated with a 5K resistor.

Page 34: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

33

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

IF MULTIPLE BOARDS ARE USED CONNECT DEFECT AS SHOWN BELOW

R1

0

R1

2

R3

C2

R8

U1

TB3D3

U2TB2

R5

C1

R7

R6

///

NO

NC

C

RL1

R2

R9

D4

+

C3D7

F1

M1 C4

D5

TB1

R11

D1

R4

R1

D2

D6 ZD

1

PO

WE

R

BELL O/P

2A

DEFECT

-VE

+V

E

DEFECT

302 731

+V

E-V

E

BELL O/P+

VE

-VE

FROM NZ3200

+ C

NT

RL

-

5K E.O.L.

TO TB2/3 EXT DEFECT 302 708

TO TB2/4 EXT DEFECT 302 708TO BELL O/P

TO BATTERIES O/P

R1

2

D3

U2

-VE

+V

E

DEFECT

TO TB2/3 EXT DEFECT 302 708

TO TB2/4 EXT DEFECT 302 708

R1

2

D3

U2

-VE

+V

E

DEFECT

R1

2

D3

U2

-VE

+V

E

DEFECT

DEFECT

DEFECT

DEFECT

TB2

TB2

TB2

+

-

+

-

+

-TB4 302 708

+

-

TB1 302 708

Figure 21: 24Volt Driver Board Layout and Wiring

Page 35: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

34

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

10 TROUBLESHOOTING

Problem Possible Cause/s Suggested Remedy / Action

Mains LED is off Mains supply is not operational. AC Fuse on MAF blown.

Check mains supply. Check and replace if necessary F1 on MAF.

Bell circuits in defect. Diodes not fitted in series with bell. End of line not fitted. Fuses blown.

Fit diodes to bells as shown in section 4.2. Fit end of line resistor as stated in table 4.2 Check fuses F4 and F5 on MAF. Replace if necessary.

Zone always in defect. Line is shorted. Line is open circuit.

Check and remove short. Locate and repair open circuit.

System defect LED flashes every 4 seconds.

Cable to CN4 of 302-7080 is disconnected.

Reconnect cable.

External defect operated but is not connected.

Wire link not fitted to external defect input.

Fit wire link.

Page 36: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

35

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

11 INDEX PANEL ENGRAVING

The NZ3200 is supplied with a front index panel, which has been pre-drilled to accept all the LED's for the system. The NZ3200 can also be supplied as a rear service panel. The panel should be engraved as shown in the following illustrations. When the DBA facility is not required, the top two LED's indicate fire (see section 6 for DIP switch settings), where the DBA is used the top LED indicates fire and the second LED indicates DBA.

11.1 NZ3200/16 without DBA. For rear service FACP

In the example below the zone information, defect and normal have been engraved in 3mm high lettering and fire in 6mm high. Note that ‘FIRE’ should be situated between the two LED's for clarity.

DEFECT

NORMAL

FIRE

GROUND FLOOR

FIRST FLOOR

SECOND FLOOR

STAIRWELL

PLANT ROOM

GROUND FLOOR

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

PLANT ROOM

STAIRWELL

THIRD FLOOR

RE

F

20.0

mm

47.0

mm

360.0

mm

380.0

mm

REF

15.1 mm

27.8 mm33.0 mm40.5 mm

53.2 mm

65.9 mm

78.6 mm

91.3 mm

104.0 mm

116.7 mm

129.4 mm

142.1 mm154.8 mm

167.5 mm

180.2 mm

192.9 mm

254.7 mm

267.4 mm

281.0 mm

292.8 mm

314.0 mm

280.1 mm

205.6 mm

Page 37: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

36

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

11.2 NZ3200/16 with DBA . For rear service FACP

In the example below all information is engraved in 3mm high lettering.

FIRE

DBA

DEFECT

NORMAL

GROUND FLOOR

FIRST FLOOR

SECOND FLOOR

STAIRWELL

PLANT ROOM

GROUND FLOOR

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

PLANT ROOM

STAIRWELL

THIRD FLOOR

RE

F

20.

0 m

m

47.

0 m

m

360

.0 m

m

380

.0 m

m

REF

15.1 mm

27.8 mm33.0 mm40.5 mm

53.2 mm

65.9 mm

78.6 mm

91.3 mm

104.0 mm

116.7 mm

129.4 mm

142.1 mm154.8 mm

167.5 mm

180.2 mm

205.6 mm

254.7 mm

267.4 mm

281.0 mm

292.8 mm

314.0 mm

280.1 mm

192.9 mm

Page 38: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

37

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

11.3 NZ3200/16 For front service FACP

30.8 mm

43.5 mm

56.2 mm

68.9 mm

94.3 mm

107.0 mm

119.7 mm

132.4 mm

145.1 mm

170.5 mm

183.2 mm

195.9 mm

208.6 mm

221.3 mm

269.8 mm

282.5 mm

295.2 mm

5.5

mm

22

.0 m

m

29

6.0

mm

RE

F

257.1 mm

29

0.5

mm

81.6 mm

157.8 mm

325.0 mm

314.5 mm

7.5 mm

55

.5 m

m

15

5.5

mm

162.5 mm

Page 39: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

38

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

11.4 NZ3200/32 For Rear service FACP

7.5

0 m

m

43

.50

mm

36

7.5

0 m

m

RE

F

37

5.0

0 m

m

-0.00 mm

27.40 mm

40.10 mm

52.80 mm

65.50 mm

78.20 mm

90.90 mm

103.60 mm

116.30 mm

129.00 mm

141.70 mm

154.40 mm

167.10 mm

179.80 mm

192.50 mm

205.20 mm

217.90 mm

230.60 mm

243.30 mm

256.00 mm

268.70 mm

281.40 mm

294.10 mm

306.80 mm

319.50 mm

332.20 mm

344.90 mm

357.60 mm

370.30 mm

383.00 mm

395.70 mm

408.40 mm

456.30 mm

469.00 mm

481.70 mm

494.40 mm

540.00 mm

68.50 mm

202.50 mm

470.50 mm

336.50 mm

A B

A B

A B

A B

A B

A B

A B

A B

A B

A B

A B

A B

A B

A B

A B

A B

A B

A B

A B

A B

A

A

A

A

A

A

A

A

14.70 mm

Page 40: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

39

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

11.5 NZ3200/32 For Rear service FACP

561.50 mm

529.46 mm

542.16 mm

572.00 mm

516.76 mm

504.06 mm

468.30 mm

455.60 mm

442.90 mm

430.20 mm

417.50 mm

404.80 mm

392.10 mm

379.40 mm374.00 mm366.70 mm

354.00 mm

341.30 mm

328.60 mm

315.90 mm

303.20 mm

290.50 mm

277.80 mm

265.10 mm

252.40 mm

239.70 mm

227.00 mm

214.30 mm

201.60 mm197.00 mm

188.90 mm

176.20 mm

163.50 mm

150.80 mm

138.10 mm

125.40 mm

112.70 mm

100.00 mm

87.30 mm

74.60 mm

8.00 mmREF

5.5

0 m

m

22

.00

mm

55

.50

mm

15

5.5

0 m

m

28

9.5

0 m

m2

95

.00

mm

RE

F

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

Page 41: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

40

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

12 Appendix A. BATTERY CALCULATION. Firstly calculate system quiescent current

Item Quantity Current each Current mA

Control and Indicating Equipment

Main system board 302-7080

45mA

Zone Cards 302-5880 53mA

ASPI relays & or 8 Way Relay Board etc

6mA

Detector circuits

Ampac Heat Detector blue Indicating 57°C

40µA

Ampac Heat Detector yellow Indicating 77°C

40µA

Apollo Series 65 Ionisation (LPC) 45µA

Apollo Series 65 Optical (LPC) 45µA

Apollo Series 65 Integrating Ionisation (LPC)

45µA

Apollo Orbis Optical 120µA

Apollo Orbis MultiSensor 120µA

Fireray 2000 Beam Detector Tx/Rx/controller

8mA

Ampac Manual Call Point 40µA

Evac / Alert EVAC50W24V 30mA

Signalling SGD Type II ( 302-6780 ) 2mA

Ancillary load

Total system quiescent current IQ (mA)

Secondly calculate maximum system alarm current

Item Quantity Current each Current

Control and Indicating Equipment

Quiescent current -

Total zones used 26mA

MAF additional load 34mA

ASPI relays & or 8 Way Relay Board etc

20 mA

Alarm Circuits Bells 15mA

Evac / Alert 2.5A

Sounders 100mA

Ancillary load

Total alarm current IA mA

Minimum battery requirement is given by.

See appendix B for an example.

BATTERY SIZE =(24 x IQ) + (0.5 X IA)

1000=

(24 x ___) + (0.5 X ___)

1000= AH

Page 42: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

41

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

13 Appendix B. EXAMPLE BATTERY CALCULATION Firstly calculate system quiescent current

Item Quantity Current each Current mA

Control and Indicating Equipment

Main system board 302-7080

1 45mA 45

Zone Cards 302-5880 1 53mA 53

ASPI relays & or 8 Way Relay Board etc

1 6mA 6

Detector circuits

Ampac Heat Detector blue Indicating 57°C

40 40µA 0.16

Ampac Heat Detector yellow Indicating 77°C

0 40µA 0

Apollo Series 65 Ionisation (LPC) 53 45µA 2.385

Apollo Series 65 Optical (LPC) 0 45µA 0

Apollo Series 65 Integrating Ionisation (LPC)

11 45µA 0.495

Apollo Orbis Optical 0 120µA 0

Apollo Orbis MultiSensor 0 120µA 0

Fireray 2000 Beam Detector Tx/Rx/controller

0 8mA 0

Ampac Manual Call Point 3 40µA 0.12

Evac / Alert EVAC50W24V 0 30mA 0

Signalling SGD Type II ( 302-6780 ) 1 2mA 2

Ancillary load 0 0

Total system quiescent current IQ (mA) 109.16

Secondly calculate maximum system alarm current

Item Quantity Current each Current

Control and Indicating Equipment

Quiescent current - - 109.16

Total zones used 16 26mA 416

MAF additional load 0 34mA 34

ASPI relays & or 8 Way Relay Board etc

1 20 mA 20

Alarm Circuits Bells 40 30mA 1200

Evac / Alert 0 2.5A 0

Sounders 5 15mA 75

Ancillary load 0 0

Total alarm current IA mA 1854.16

Rounded = 3.6AH

BATTERY SIZE =(24 x 110) + (0.5 X 1854)

1000= 3.567 AH

Page 43: NZ3200 INSTALLATION, COMMISSIONING & OPERATION · relay area relay area relay area 9 sw1 8 7 8 tb2 3 8 1 7 0 3 6 9 1 7 0 4 2 5 8 6 9 3 8 1 4 cn10 7 1 bz1 + 0 rv1 cn3 u1 f5 f4 3 4

42

NZ3200 INSTALLATION, COMMISSIONING & OPERATION

14 Appendix C: DEVICES

Q I = Quiescent Current Draw Heat Detectors

Order Code Description Iq

4255-0300 Ampac Heat Detector blue Indicating 57°C 40µA

4255-0400 Ampac Heat Detector yellow Indicating 77°C 40µA Note: Rate of Rise Heat Detectors are also available.

Smoke Detectors

Order Code Description Iq

55000-217 Apollo Series 65 Ionisation (LPC) 45µA

55000-317 Apollo Series 65 Optical (LPC) 45µA

55000-220 Apollo Series 65 Integrating Ionisation (LPC) 45µA

45681-200 Apollo Series 60/65 universal base N/A

201-0501 Apollo Orbis Optical 120µA

201-0505 Apollo Orbis MultiSensor 120µA

201-0528 Apollo Orbis universal base N/A

Beam Detectors

Order Code Description Iq

220 0004 Fireray 2000 Beam Detector Tx/Rx/controller 8mA

220 0005 Fireray 50R Beam Detector 4mA

220 0006 Fireray 100R Beam Detector 4mA

Manual Call Points

Order Code Description Iq

213 0042 Ampac Manual Call Point 40µA

UNCONTROLLED DOCUMENT

NOTE: Due to Ampac’s commitment to continuous improvement specifications may change without notice.