Asset: ELMHURST EDUCATIONAL CAMPUS - Q, 45-10 94TH STREET, New York, 11373
Inspection Id Inspection Type Time In Last Edited
SA : Q744 Architectural - Senior 2019-02-22 7:42 AM 2019-03-06 2:47 PM
AA : Q744 Architectural - Associate 2019-02-22 8:53 AM 2019-05-21 9:10 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment Room 343 (Science Prep Room) - No key
Principal(s) Information
Principal Name Phuong Nguyen
Organization Civic Leadership Academy - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? Yes
Summary of Principal's Feedback A Principal questionnaire form was returned with the followingcomments: 1. The heating and cooling systems have not workedeffectively since the opening of the building in 2008. Some classroomsare consistently cold or hot, while others fluctuate. 2. The Roof leakshave caused one classroom on the 4th Floor not to be usable and thisclassroom is need due to the number of students in the building.
Principal Name George Badia
Organization Pan American International High School - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? No
Principal Name Nicholas Bleiberg
Organization Voyages Preparatory School - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? No
Principal Name Fritzy Brown
Organization Queens Transitional Center - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? No
Custodian Was not present
Fireman Jared Relling
Building Square Footage 205000
Comments on the Area Entire Building Leased
Comments on the Stories (Floors) plus Basements 4+B
Comments on the Number of Classrooms 70
Comments on the Year Built 2008
Student Population 1298
Staff Population 194
Weather Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 1 of 41
Facade Photo
Corner of 94th Street and 46th Avenue -Northwest View
Main Entrance Photo
Facade A - Corona Avenue
Roof Photo
Roof 1 - Northwest View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 2 of 41
Have any Systems/Major Building Components been upgraded? Yes
Systems: New Health Clinic Room 134
Year: 2016
Systems: New Computer Room 374: Partial Roofing repairs
Year: 2015
Systems: Partial Handrail repairs
Year: 2014
Systems: Partial Canopies repairs
Year: 2011
Systems: Interior Renovation
Year: 2008
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? Yes
Year Leased 2008
Inspection Full Inspection
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
Yes Broken Glass Broken windowpanes arepotential safetyhazards.
EXTERIOR |WINDOWS |WINDOWS
Room 274, 412 Jared Relling Fireman
Yes Potential FallingDebris
Leaning Fenceis a potentialsafety hazard
SITE | FENCES NortheastCorner
Jared Relling Fireman
Yes Tripping Hazard Damaged/Missing stair nosingis a potentialtripping hazard.
EXTERIOR |STAIRS/RAMPS: EXTERIOR |STAIRS/RAMPS
Exterior stairs atthe South andEast entrances.
Jared Relling Fireman
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 3 of 41
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators Yes Yes
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms Rooms 274 and 474 Yes Yes
Auditorium No
Cafeteria 1st Floor - Room 103, 1st Floor - Room135
Yes Yes Yes Yes
Classrooms Basement, 1st - 4th Floors Yes Yes
Computer Rooms Rooms 374, 451 Yes Yes
Gymnasium No
Library Room B74A Yes Yes
Main Office Room 165 (Queens Transitional Center);Room 225 (Voyages Preparatory School);Room 325 (Pan American InternationalHigh School); Room 425 (CivicLeadership Academy)
Yes Yes
Multi-purpose Room 2nd, 3rd and 4th Floors Yes Yes Yes Yes
Nurse's Room Rooms 122 and 134 Yes Yes
Pool No
Science Lab Rooms 231, 239, 245, 331, 339, 345,431A, 439, 445
Yes Yes
Toilet Rooms (Boys) Basement, 1st - 4th Floors Yes Yes
Toilet Rooms (Girls) Basement , 1st - 4th Floors Yes Yes
Toilet Rooms (Staff) Basement, 1st - 4th Floors Yes Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 4 of 41
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Does not Exist
AWNINGS AND CANOPIES Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CHIMNEY Inspected
Material Type(s) Metal
Condition 5 - Poor
Deficiency METAL: LOOSE OR MISSING SUPPORTS
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 5 of 41
Question Response
EXTERIOR
CHIMNEY
Deficiency Photo1
CH
Violations No violations recorded.
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Does not Exist
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 24,200
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 24,200
Instance Quantity Uom S.F.
Deficiency STUCCO CEMENT SURFACE: CRACKS, SPALLING
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 6 of 41
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C
Violations No violations recorded.
EXTERIOR SOFFITS Does not Exist
LOADING DOCK Inspected
Condition 3 - Fair
Deficiency CHEEK WALL/CRACKS, SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 7 of 41
Question Response
EXTERIOR
LOADING DOCK
Deficiency Photo1
Loading Dock Ramp Cheek Wall
Violations No violations recorded.
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry, Concrete
Replacement Quantity 6,000
Replacement Uom C.F.
InspectedInstance on All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 6,000
Instance Quantity Uom C.F.
Deficiency No deficiencies recorded
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 41,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on IRMA: Roof 1
Instance Condition 4 - Between Fair and Poor
Instance Quantity 41,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2008
Source of Installation Custodial Staff
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 8 of 41
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Deficiency IRMA: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE
Roof Plan reference
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - Room 401A, 417, 439, 441, 445, 449, 4th Floor LobbyCorridor near Rooms 411, 437
Violations No violations recorded.
Deficiency IRMA: ROOFING: DAMAGED INSULATION
Roof Plan reference
Deficiency Quantity 430
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 9 of 41
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Deficiency Photo1
Roof 1
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
RAILINGS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS Inspected
Condition 5 - Poor
Deficiency CONCRETE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 45
Quantity Uom S.F.
Potential Action REPAIR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 10 of 41
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Loading Dock 1
Violations No violations recorded.
Deficiency CONCRETE: WORN-OUT TREAD/RISER/NOSING
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Main Entrance
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 29,000
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 11 of 41
Question Response
EXTERIOR
WINDOWS
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Other: All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 29,000
Instance Quantity Uom S.F.
Installation Year 2008
Source of Installation Custodial Staff
Deficiency ALUMINUM - OTHER: BROKEN PANE
Roof Plan reference
Elevation
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1 No photo recorded
Violations No violations recorded.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Corridor near Room B01, B05, B20
Deficiency Quantity 30
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 12 of 41
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Corridor near Room B01
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 3 - Fair
Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE
Deficiency Location/Instance Boiler Room North Room
Deficiency Quantity 90
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Does not Exist
AUDITORIUM Does not Exist
CAFETERIA Inspected
InspectedInstance on 1st Floor - Room 103
InspectedInstance on 1st Floor - Room 135
Ceiling
InspectedInstance on 1st Floor - Room 135
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 13 of 41
Question Response
INTERIOR
CAFETERIA
Ceiling
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Near Rear Entrance
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Rear Entrance
Violations No violations recorded.
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED
Deficiency Location/Instance Near Vending Machines, near Kitchen
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Kitchen
Violations No violations recorded.
InspectedInstance on 1st Floor - Room 103
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED
Deficiency Location/Instance Near Windows, Near Servery, Rear Section
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 14 of 41
Question Response
INTERIOR
CAFETERIA
Ceiling
Deficiency Photo1
Near Windows
Violations No violations recorded.
Door(s)
InspectedInstance on 1st Floor - Room 103
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - Room 135
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on 1st Floor - Room 135
Does not ExistInstance on 1st Floor - Room 103
Floor Finish
InspectedInstance on 1st Floor - Room 135
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near Vending Machines, near Kitchen
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Kitchen
Violations No violations recorded.
InspectedInstance on 1st Floor - Room 103
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Center
Deficiency Quantity 10
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 15 of 41
Question Response
INTERIOR
CAFETERIA
Floor Finish
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 1st Floor - Room 103
Does not ExistInstance on 1st Floor - Room 135
Stage
Does not ExistInstance on 1st Floor - Room 103
Does not ExistInstance on 1st Floor - Room 135
Walls
InspectedInstance on 1st Floor - Room 135
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Near Windows at Center
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Windows at Center
Violations No violations recorded.
InspectedInstance on 1st Floor - Room 103
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Near Windows in Rear Section
Deficiency Quantity 10
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 16 of 41
Question Response
INTERIOR
CAFETERIA
Walls
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Windows in Rear Section
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor - Room 103
Does not ExistInstance on 1st Floor - Room 135
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Rooms B46,231,243,245,374, and others
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room B46
Violations No violations recorded.
Deficiency TECTUM: DAMAGED/MISSING
Deficiency Location/Instance Corridor near Rooms B17,426
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 17 of 41
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo1
Corridor near Room B17
Violations No violations recorded.
Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK
Deficiency Location/Instance Rooms 401A,417,439,445,449, Corridor near Rooms 411,437
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 401A
Violations No violations recorded.
Deficiency TECTUM: DAMAGED/MISSING - ACTIVE LEAK
Deficiency Location/Instance 4th Floor Lobby
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
4th Floor Lobby
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 18 of 41
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s) Inspected
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 208,370,445,474
Deficiency Quantity 4
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 208
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Main Entrance Lobby
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Lobby
Violations No violations recorded.
Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET
Deficiency Location/Instance Room 374
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 19 of 41
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Room 374
Violations No violations recorded.
Deficiency EPOXY FLOORING: CRACKS/SPALLING
Deficiency Location/Instance Rooms 243,345,445
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 445
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Room 231, Corridor near Rooms B44,146,148,339, and others
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room B44
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 20 of 41
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Corridor near Room 154
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 154
Violations No violations recorded.
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Corridor near Rooms B68,142,164,205,403, and others
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 205
Violations No violations recorded.
Specialties Inspected
Classroom Locker(s) Inspected
Condition 2 - Between Good and Fair
Deficiency DAMAGED UNITS
Deficiency Location/Instance Lockers 2-197,2-138,2-251,4-514
Deficiency Quantity 4
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 21 of 41
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Specialties
Classroom Locker(s)
Deficiency Photo1
Locker 4-514
Violations No violations recorded.
Fixed Seating Does not Exist
GYMNASIUM Does not Exist
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency METAL PAN: DAMAGED/MISSING
Deficiency Location/Instance Near Exit 5
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Exit 5
Violations No violations recorded.
Door(s)
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 22 of 41
Question Response
INTERIOR
KITCHEN
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room B74A (3600 SF)
Built-in Furnishing
Does not ExistInstance on Room B74A (3600 SF)
Ceiling
InspectedInstance on Room B74A (3600 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room B74A (3600 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room B74A (3600 SF)
Condition 4 - Between Fair and Poor
Deficiency CARPET: WORN/DETERIORATED
Deficiency Location/Instance Near Bookshelves
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Bookshelves
Violations No violations recorded.
Walls
InspectedInstance on Room B74A (3600 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InspectedInstance on 2nd Floor - Boys (319 Lockers)
Alternative use No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 23 of 41
Question Response
INTERIOR
LOCKER ROOM
InspectedInstance on 2nd Floor - Girls (320 Lockers)
Alternative use No
InspectedInstance on 3rd Floor - Boys (319 Lockers)
Alternative use No
InspectedInstance on 3rd Floor - Girls (320 Lockers)
Alternative use No
InspectedInstance on 4th Floor - Boys (319 Lockers)
Alternative use No
InspectedInstance on 4th Floor - Girls (320 Lockers)
Alternative use No
Ceiling
InspectedInstance on 3rd Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 4th Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 2nd Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 2nd Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 4th Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 3rd Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 3rd Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 3rd Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 2nd Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 4th Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 4th Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 2nd Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 24 of 41
Question Response
INTERIOR
LOCKER ROOM
Floor Finish
InspectedInstance on 3rd Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 3rd Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 2nd Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 4th Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 4th Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 2nd Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Locker Room Lockers
InspectedInstance on 2nd Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency DAMAGED UNITS
Deficiency Location/Instance Locker 31
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Locker 31
Violations No violations recorded.
InspectedInstance on 3rd Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency DAMAGED UNITS
Deficiency Location/Instance Lockers 3,45,74,116,157, and others
Deficiency Quantity 7
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 25 of 41
Question Response
INTERIOR
LOCKER ROOM
Locker Room Lockers
Purpose of Action LEVEL 2
Deficiency Photo1
Locker 3
Violations No violations recorded.
InspectedInstance on 4th Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency DAMAGED UNITS
Deficiency Location/Instance Lockers 128,141,142,227,228, and others
Deficiency Quantity 9
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Locker 128
Violations No violations recorded.
Walls
InspectedInstance on 3rd Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 3rd Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 2nd Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 4th Floor - Boys (319 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 4th Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 26 of 41
Question Response
INTERIOR
LOCKER ROOM Inspected
Walls
Deficiency No deficiencies recorded
InspectedInstance on 2nd Floor - Girls (320 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
MULTI-PURPOSE ROOM Inspected
InspectedInstance on 2nd Floor
InspectedInstance on 3rd Floor
InspectedInstance on 4th Floor
Ceiling
InspectedInstance on 4th Floor
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Office
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED
Deficiency Location/Instance Near Windows, Center
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 27 of 41
Question Response
INTERIOR
MULTI-PURPOSE ROOM Inspected
Ceiling
Near Windows
Violations No violations recorded.
InspectedInstance on 4th Floor
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED
Deficiency Location/Instance Center
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Door(s)
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 4th Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on 3rd Floor
Does not ExistInstance on 4th Floor
Does not ExistInstance on 2nd Floor
Floor Finish
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 4th Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 28 of 41
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Sliding-folding Partition
InspectedInstance on 4th Floor
Condition 3 - Fair
Deficiency MOVABLE PANELS: DAMAGED
Deficiency Location/Instance Center
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Stage
Does not ExistInstance on 3rd Floor
Does not ExistInstance on 4th Floor
Does not ExistInstance on 2nd Floor
Walls
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance Near Windows, near Entrance
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Entrance
Violations No violations recorded.
InspectedInstance on 3rd Floor
Condition 3 - Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 29 of 41
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Walls
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance Near Windows, near Entrance
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Near Windows, near Locker Room Boys
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Locker Room Boys
Violations No violations recorded.
InspectedInstance on 4th Floor
Condition 3 - Fair
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance Perimeter Walls
Deficiency Quantity 140
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 30 of 41
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Walls
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 4th Floor
Does not ExistInstance on 2nd Floor
Does not ExistInstance on 3rd Floor
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Inspected
InspectedInstance on Room 331
Alternative use Yes
InspectedInstance on Rooms 231,239,245,339,431A,439,445
Alternative use No
InspectedInstance on Room 345
Alternative use No
Fixed Equipment
InspectedInstance on Room 345
Condition 2 - Between Good and Fair
Deficiency CABINETRY: MISSING/DAMAGED
Deficiency Location/Instance Room 345
Deficiency Quantity 4
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 345
Violations No violations recorded.
SCIENCE PREP ROOM Inspected
InaccessibleInstance on Room 343
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 31 of 41
Question Response
INTERIOR
SCIENCE PREP ROOM
InspectedInstance on Rooms 243,443
Alternative use No
Fixed Equipment
InspectedInstance on Rooms 243,443
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Partition Does not Exist
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Stairs AB/Bulkhead, CD/1,2,3, EF/1,3
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair AB/Bulkhead
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency MASONRY: CRACKS/SPALLING
Deficiency Location/Instance Stairs G/4, H/3
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 32 of 41
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo1
Stair G/4
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED - ACTIVELEAK
Deficiency Location/Instance Room 441
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 441
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Does not Exist
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 33 of 41
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Ceiling
Deficiency Location/Instance Room 438
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 438
Violations No violations recorded.
Door(s) Inspected
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 242
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 242
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency BROKEN/MISSING
Deficiency Location/Instance 3rd Floor Locker Room Boys
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 34 of 41
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Stalls
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
3rd Floor Locker Room Boys
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance 3rd Floor Locker Room Boys
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
3rd Floor Locker Room Boys
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 35 of 41
Question Response
SITE
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 3 - Fair
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance Along 94th Street
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Along 94th Street
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance 94th Street
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
94th Street
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 36 of 41
Question Response
SITE
FENCES
Deficiency Location/Instance 94th Street
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
94th Street
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance Northeast Corner
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Northeast Corner
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Parking Lot
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 37 of 41
Question Response
SITE
PAVING
Student Non-Use
Asphalt
Deficiency Photo1
Parking Lot
Violations No violations recorded.
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance North Side
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North Side
Violations No violations recorded.
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 38 of 41
Question Response
SITE
PAVING
Student Use
Asphalt
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Concrete Does not Exist
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Near Exit 3
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Exit 3
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency HEAVING
Deficiency Location/Instance 94th Street
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 39 of 41
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
94th Street
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 94th Street
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
94th Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Does not Exist
PLAYING SURFACE Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SEATING Inspected
Benches Does not Exist
Bleachers Inspected
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Metal/Wood/Plastic Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 40 of 41
Question Response
SITE
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS: EXTERIOR Inspected
Railings Does not Exist
Site Cheek/flank Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs/ramps Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q744
PB/A&W Print Date: 6/20/2019Page 41 of 41