Asset: LAFAYETTE AF - BROOKLYN, 2630 BENSON AVENUE, New York, 11214
Inspection Id Inspection Type Time In Last Edited
SA : K401 Architectural - Senior 2018-11-19 7:57 AM 2019-06-10 3:44 PM
AA : K401 Architectural - Associate 2018-11-19 8:56 AM 2018-11-21 7:46 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment The following spaces are inaccessible: Shower Rooms - 1st FloorNorth, 1st Floor South (Locked, Storage)
Principal(s) Information
Principal Name Jon Harriman
Organization International High School at Lafayette - Brooklyn
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal had no comments about the physical condition of theAthletic Field at this time.
Principal Name Tracy Murren
Organization Kingsborough Early College Secondary School - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? No
Principal Name Tom Mullen
Organization Expeditionary Learning School For Community Leaders - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? No
Principal Name Eugenia Kelch
Organization Life Academy High School for Film and Music - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? No
Principal Name Derek Cradle
Organization High School of Sports Management - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? No
Custodian Was not present
Fireman Theo Kanos (Fieldman)
Building Square Footage 3100
Comments on the Area 140,000SF Playing Surfaces (191,000 SF Total Site Area)
Comments on the Stories (Floors) plus Basements 1 (No Basement)
Comments on the Number of Classrooms 0
Comments on the Year Built 1938
Student Population 1940
Staff Population 1
Weather Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 1 of 21
Facade Photo
Corner of Facades A and B - North View
Main Entrance Photo
Facade A - South Locker Room Entrance
Roof Photo
Roof 1 - Southwest View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 2 of 21
Have any Systems/Major Building Components been upgraded? Yes
Systems: Football/Soccer Field, Running Track surfacesreplacement; Field House Roofing and Flashingreplacement; Exterior Walls repairs
Year: 2004
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
Yes ProtrudingElements
Protruding metallocker door withexposed sharpedges is apotential safetyhazard.
INTERIOR |LOCKERROOM | LockerRoom Lockers
Center Michael DeSimeone
Fireman
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings No Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms No
Auditorium No
Cafeteria No
Classrooms No
Computer Rooms No
Gymnasium No
Library No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 3 of 21
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Main Office No
Multi-purpose Room No
Nurse's Room No
Pool No
Science Lab No
Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Does not Exist
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Does not Exist
COPING Does not Exist
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 3 - Fair
Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 4 of 21
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 5
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Does not Exist
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 2,800
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 2,800
Instance Quantity Uom S.F.
Deficiency BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDINGCORNERS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 5 of 21
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
South corner of Fieldhouse
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Does not Exist
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 3,100
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Does not Exist
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Does not Exist
ROOFING Inspected
InspectedInstance on Modified Bitumen: Roof 1
Instance Condition 3 - Fair
Instance Quantity 3,100
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2004
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 6 of 21
Question Response
EXTERIOR
ROOF
Roofing
ROOFING Inspected
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
RAILINGS Does not Exist
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
WINDOWS Does not Exist
INTERIOR Inspected
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 7 of 21
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Deficiency Location/Instance Equipment Storage Room
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Equipment Storage Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Does not Exist
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Coach Office
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 8 of 21
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish Inspected
Coach Office
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Near South Shower Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near South Shower Room
Violations No violations recorded.
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InspectedInstance on 1st Floor - South (51 Lockers)
Alternative use No
InspectedInstance on 1st Floor - North (48 Lockers)
Alternative use No
Ceiling
Does not ExistInstance on 1st Floor - North (48 Lockers)
Does not ExistInstance on 1st Floor - South (51 Lockers)
Door(s)
InspectedInstance on 1st Floor - North (48 Lockers)
Condition 3 - Fair
Deficiency METAL: DETERIORATED DOOR
Deficiency Location/Instance Entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 9 of 21
Question Response
INTERIOR
LOCKER ROOM
Door(s)
Deficiency Photo1
Entrance
Violations No violations recorded.
InspectedInstance on 1st Floor - South (51 Lockers)
Condition 3 - Fair
Deficiency METAL: DAMAGED LOUVER
Deficiency Location/Instance Entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor - North (48 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - South (51 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Locker Room Lockers
InspectedInstance on 1st Floor - North (48 Lockers)
Condition 5 - Poor
Deficiency DAMAGED UNITS
Deficiency Location/Instance Lockers 2,6,9,10,23
Deficiency Quantity 5
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 10 of 21
Question Response
INTERIOR
LOCKER ROOM
Locker Room Lockers
Purpose of Action LEVEL 2
Deficiency Photo1
Locker 10
Violations No violations recorded.
InspectedInstance on 1st Floor - South (51 Lockers)
Condition 4 - Between Fair and Poor
Deficiency DAMAGED UNITS
Deficiency Location/Instance Perimeter Walls
Deficiency Quantity 3
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Perimeter Wall
Violations No violations recorded.
Deficiency DAMAGED UNITS
Deficiency Location/Instance Center
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 11 of 21
Question Response
INTERIOR
LOCKER ROOM
Locker Room Lockers
Deficiency Photo1
Center
Violations No violations recorded.
Walls
InspectedInstance on 1st Floor - South (51 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - North (48 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SHOWER ROOM Inspected
InaccessibleInstance on 1st Floor - North
InaccessibleInstance on 1st Floor - South
STAIRS/RAMPS: INTERIOR Does not Exist
TOILET ROOMS - STAFF Inspected
Ceiling Does not Exist
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 5 - Poor
Deficiency RUST - MAJOR
Deficiency Location/Instance South Side
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 12 of 21
Question Response
INTERIOR
TOILET ROOMS - STAFF
Stalls Inspected
Deficiency Photo1
South Side
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Near Entrance
Deficiency Quantity 5
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Deficiency MASONRY: CRACKS/SPALLING
Deficiency Location/Instance Near Entrance
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 13 of 21
Question Response
INTERIOR
TOILET ROOMS - STAFF Inspected
Walls Inspected
Near Entrance
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Does not Exist
Door(s) Inspected
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR
Deficiency Location/Instance South Locker Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South Locker Room
Violations No violations recorded.
Floor Finish Inspected
Condition 3 - Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance South Locker Room
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South Locker Room
Violations No violations recorded.
Stalls Inspected
Condition 5 - Poor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 14 of 21
Question Response
INTERIOR
TOILET ROOMS - STUDENTS Inspected
Stalls
Deficiency RUST - MAJOR
Deficiency Location/Instance North Locker Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North Locker Room
Violations No violations recorded.
Deficiency BROKEN/MISSING
Deficiency Location/Instance South Locker Room, North Locker Room
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South Locker Room
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ATHLETIC FIELDS Inspected
PLAYING SURFACE Inspected
Synthetic Turf Field exists? Year of Installation
Yes 2004
Replacement Quantity 140,000
Replacement Uom S.F.
InspectedInstance on Football/Soccer Field
Instance Condition 3 - Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 15 of 21
Question Response
ATHLETIC FIELDS
PLAYING SURFACE
Instance Quantity 75,000
Instance Quantity Uom S.F.
Deficiency ARTIFICIAL TURF: DAMAGED/WORN OUT
Deficiency Location/Instance Football Field
Roof Plan reference
Deficiency Quantity 500
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the Goal Post
Violations No violations recorded.
InspectedInstance on Running Track
Instance Condition 4 - Between Fair and Poor
Instance Quantity 40,000
Instance Quantity Uom S.F.
Deficiency ATHLETIC WEARING SURFACE: DAMAGED/DETERIORATED
Deficiency Location/Instance Running Track
Roof Plan reference
Deficiency Quantity 1,000
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 16 of 21
Question Response
ATHLETIC FIELDS
PLAYING SURFACE
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
North side of Running Track
Violations No violations recorded.
InspectedInstance on Tennis/Handball Corts
Instance Condition 4 - Between Fair and Poor
Instance Quantity 25,000
Instance Quantity Uom S.F.
Deficiency ASPHALT: DAMAGED/DETERIORATED
Deficiency Location/Instance Tennis/Handball Court
Roof Plan reference
Deficiency Quantity 700
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Tennis Court
Violations No violations recorded.
FIXED EQUIPMENT Inspected
Basketball Backboard Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 17 of 21
Question Response
ATHLETIC FIELDS
FIXED EQUIPMENT
Basketball Hoops Does not Exist
Basketball Posts Does not Exist
Football Goal Posts Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Tennis Net Posts Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SEATING Inspected
Benches Inspected
Concrete Does not Exist
Metal/Wood/Plastic Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Bleachers Inspected
Concrete Does not Exist
Metal/Wood/Plastic Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FENCES Inspected
Condition 3 - Fair
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance Bay 43rd Street
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 18 of 21
Question Response
SITE
FENCES
Deficiency Photo1
Bay 43rd Street
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance Bay 43rd Street, 27th Avenue
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Bay 43rd Street
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
Site Sidewalks & Walkways Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 19 of 21
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Location/Instance 27th Avenue
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
27th Avenue
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 2 - Between Good and Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance 27th Avenue, Bath Avenue
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Bath Avenue
Violations No violations recorded.
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR
Deficiency Location/Instance Handball Court
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 20 of 21
Question Response
SITE
SITE WALLS (NOT RETAINING WALLS)
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency CAST IN PLACE CONCRETE: DETERIORATED EXPANSIONJOINT
Deficiency Location/Instance Handball Court
Deficiency Quantity 30
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Handball Court
Violations No violations recorded.
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K401
PB/A&W Print Date: 6/21/2019Page 21 of 21