48
Content Page Liquid-coupled heat exchanger ECONET ® Premium Safety rules, warning 2 Introduction 3 Scope of delivery 3 Assembly and installation 9 Control and electrical installation 14 Maintenance instructions 18 Functional description 19 Controller operation 21 Menu structure overview 22 ECONET ® parameters 23 ECONET ® communication 25 Accessible network variable list 31 BACnet 33 Control panel 38 Parameters 39 Spare part list 42 Product code 46 AIR TREATMENT 9603 GB 2015.05.20 ECONET ® PREMIUM EQ STAZ-74, EQRZ-05, EQL STYZ-74, LQRZ-05 » INSTALLATION AND MAINTENANCE MANUAL AIR COMFORT Integrated pump and energy exchange package. Separated pump and energy exchange package.

NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Content page

liquid-coupled heat exchanger ECONET® premium

Safety rules, warning 2

Introduction 3

Scope of delivery 3

Assembly and installation 9

Control and electrical installation 14

Maintenance instructions 18

Functional description 19

Controller operation 21

Menu structure overview 22

ECONET® parameters 23

ECONET® communication 25

Accessible network variable list 31

BACnet 33

Control panel 38

Parameters 39

Spare part list 42

Product code 46

AIR COMFORT

AIR TREATMENT

9603 GB 2015.05.20

ECONET® prEMiuMEQ STAZ-74, EQRZ-05, EQL STYZ-74, LQRZ-05

» INSTALLATION AND MAINTENANCE MANUAL

AIR COMFORT

Integrated pump and energy exchange package.

Separated pump and energy exchange package.

Page 2: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 2

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

liQuid-COuplEd HEAT EXCHANGEr ECONET® prEMiuM (MulTiplE COils)

sAfETy rulEs, wArNiNGs

important: read this information before installing the equipment!

personnelQualified personnel should carry out installation, operation and maintenance of the equipment. A qualifiedperson is someone who is technically competent and familiar with all safety information and establishedsafety procedures, with the installation process, and with all the hazards involved.

warningsThis equipment can endanger life through rotating machinery and electrical shocks. Failure to observe thefollowing will constitute an ELECTRICAL SHOCK HAZARD. This is a product of the restricted sales distributionclass according to IEC 61800-3. In a domestic environment, this product may cause radio interference,in which case the user may be required to take adequate measures.

– The equipment contains high-value capacitors, which take time to discharge after removal of the mains supply.

– Before working on the equipment, ensure isolation of the mains supply. Wait for at least 3 minutes for the inverter to discharge to safe voltage levels.

– Never perform high-voltage resistance checks on the wiring without first disconnecting the inverter from the circuit being tested.

possible risksUnder fault conditions, power loss or other, unintentional operating conditions, the equipment may notoperate as specified. In particular:

– The motor speed may not be controlled

– The direction of rotation of the motor may not be controlled

– The motor may be energised

– Heat recovery liquid is poisonous and harmful and may cause risk of injury if leaking

Environmental requirements for storage, transportation and useIf the ECONET® unit is not being installed immediately, store the unit in a well-ventilated place away fromhigh temperatures, humidity, dust or metal particles.

Environment installed, and in use storage and transportation

Temperature Ambient temperature: 0 °C - +40 °C -25 °C - + 50 °C Intake air: -40 °C - + 40 °C, intake air temperature also subject to AHU dimensioning.

Humidity Possible condensation on pipework and on the supply and exhaust air coils.

Water ECONET® equipment achieves min IP21.

Pressure Atmospheric pressure, max altitude 1000 m.

Page 3: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 3

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® sCOpE Of dElivEry

pump unit: sTAZ-74, sTyZ-74system overwiewSingle pump units or double pump units (1, 2, 3) illustrated in the figure are delivered separately from the AHU. The pump unit is equipped with a stand for mounting ona flat floor.The pipework within the pump units (1, 2, 3) is protectedagainst rusting and insulated with Armaflex. The sensors and components within the pump units(1, 2, 3) are mounted and wired to the ECONET® control box.

The ECONET® control box is mounted on the pump unitand pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted onthe pump unit and wired to the pump/pumps and theECONET® control box. The exhaust air coil and supply air coil (21, 22) aremounted in the air handling unit.

iNTrOduCTiON

ECONET® system consists of a pump and equipped with single or double pump and a energy exchanger package. For eQ range air handling units, there are 2 options, either integrated pump unit and exchanger package or separated.

ECONET® system for eQ ECONET® system for eQl

Pump unit with integrated energy exchanger package (standard)

Separated Pump unit and energy exchanger package (option)

Separated Pump unit and energy exchanger package (standard)

GT4

MT

MT

GT42

MP

GP40

MT

GP41

SV41

+– +–

+– +–

GT2

SV40

6

2

7

8

9

3

1

10

11

22

17 18

44

5a

5b

5a

12

13

15 16

2019

21

24

14

23

1. Pump unit2. Single-pump solution3. Double-pump solution4. Controller5. a) Frequency inverter 1 b) Frequency inverter 26. Pressure gauge

with contact function7. Sensor, frost protection8. Control valve9. Sensor, ice protection10. Differential pressure

transmitter11. Sensor, temperature12. Shut-off valve13. Shut-off valve 14. Frost control valve15. Non-return valve16. Non-return valve17. Shut-off valve18. Shut-off valve19. Shut-off valve20. Shut-off valve21. Exhaust air main coil22. Exhaust air sub coil23. Supply air main coil24. Supply air sub coilMP. Pressure gauge MT. Thermometer

Page 4: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 4

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® sCOpE Of dElivEry

Air coils: EQrT and lQrTThe ECONET® coils consist of a set of finned coil in the supply air unit and in the exhaust air unit with functions for heat/cooling recovery, heating as well as cooling of the supply air.The coils are equipped with drip trays and connections for air purging and drainage. A droplet eliminator should be chosen if the air velocity through the coil is high. The coils are manufactured from copper tube, which is expanded against aluminium fins.The header consists of either copper or rust-protected steel.The maximum operating pressure of the coils is 1.5 MPa,and the test pressure is 2 MPa. Other material for the tubes, fins and the framework can be specified in the Acon selec-tion program. Coils with hygiene fins should be specified if cleanabilityof the coils according to standards VDI 3803 and VDI 6022 is required. The supply and exhaust air coils are connected together by a liquid circuit with the possibility to connect externally supplied energy or heating/cooling.

The pump unit consists of a pump/pumps, pipes , valves, sensors, frequency inverter/inverters and a controller for ECONET® energy recovery. The pipes in the pump unit are anti rust painted and insu-lated with Armaflex. The pump/pumps consists of a base and a pump head, between which the chamber stack and the outer sleeve are secured by means of staybolts.The base and pump head are made of cast iron, and all other wetted parts are made of stainless steel, DIN 1.4301. All pumps are equipped with a maintenance-free mechanical shaft seal of the cartridge type. Max. operating pressure for the pump is 16 bar/160 mWC/1.6 MPa. The pump unit is designed to be mounted separately witha stand for mounting on the floor. The pump unit is delivered separately on a pallet. Additional sensors with advanced freezing protection.A combined temperature and humidity sensor (GT20-GH20) and a temperature sensor (GT21) to be placed resp. in extract and exhaust air flow. They are delivered loose in the pump unit control box.

single pump unit with integrated exchanger package

2a2b 4a

A

B

CD

3

5

D1D2

H1

H3

H2H4

H5

H6

H7*

)

L

F

E

Picture shows eQ sizes 032-045 (DN:32)

2a = supply air coil:in, 2b = supply air coil:in (ECONET® Premium), 3 = supply air coil:out, 4a = exhaust air coil:in, 5 = exhaust air coil:outA = primary heating:in, B = primary heating:out, C = primary cooling:in, D = primary cooling:out, E = drain valve, filling valve, F = air purge

eQ siZE l d1 d2 H1 H2 H3 H4 H5 H6 H7*) pipE siZE 005-027 625 900 972 100 1655 1402 1427 1432 1482 1657 DN-25

032-045 625 900 972 100 1655 1402 1427 1432 1482 1657 DN-32

050-090 930 1150 1222 100 1980 1694 1777 1777 1937 2114 DN-50

Page 5: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 5

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® sCOpE Of dElivEry

double pump unit with integrated energy exchanger package

L

2a2b 4a

A

B

CD

3

5

D1D2

H1

H3

H2

H4

H5

H6

H7*

)

E

F

L

2a2b 4a

A

B

CD

3

5

D1D2

H1

H3

H2

H4

H5

H6

H7*

)

E

F

Picture shows eQ sizes 032-045 (DN:32)

2a = supply air coil:in, 2b = supply air coil:in (ECONET® Premium), 3 = supply air coil:out, 4a = exhaust air coil:in, 5 = exhaust air coil:outA = primary heating:in, B = primary heating:out, C = primary cooling:in, D = primary cooling:out, E = drain valve, filling valve, F = air purge

eQ siZE l d1 d2 H1 H2 H3 H4 H5 H6 H7*) pipE siZE 005-027 625 1210 1282 100 1655 1402 1432 1482 1552 1782 DN-25

032-045 625 1210 1282 100 1655 1402 1432 1482 1552 1782 DN-32

050-090 930 1490 1562 100 1980 1802 1584/1634 1719 1937 2114 DN-50

Page 6: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 6

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® sCOpE Of dElivEry

1 = heating/cooling:in, 2a, 2b = supply air coil:in, 3 = supply air coil:out, 4a = exhaust air coil:in, 5 = exhaust air coil:out, 6 = heating/cooling:out

The picture shows eQ sizes: 050-090

61 5

4a

3

2

L

H5

H4

H3

H2

H1

eQ siZE l d1 d2 H1 H2 H3 H4 H5 pipE siZE005-027 625 660 770 200 1600 630 680 730 DN 25

032-045 625 660 770 200 1600 630 680 730 DN 32

050-090 930 910 1020 200 1600 850 900 950 DN 50

eQ siZE l d1 d2 H1 H2 H3 H4 H5 pipE siZE60 930 910 1020 200 1600 850 900 950 DN 50

62-73 1075 960 1070 200 1600 1040 1090 1140 DN 65

82-84 1075 960 1070 200 1600 1040 1090 1140 DN 84

single pump unit

double pump unit

1= heating/cooling:in, 2a, 2b = supply air coil:in, 3 = supply air coil:out, 4a = exhaust air coil:in, 5 = exhaust air coil:out, 6 = heating/cooling:out

eQ siZE l1 l2 d1 d2 H1 H2 H3 H4 H5 A1 A2 A3 pipE siZE005-027 625 850 970 1085 200 1600 940 990 1040 250 175 325 DN 25

032-045 625 850 970 1085 200 1600 940 990 1040 250 175 325 DN 32

050-090 930 1250 1365 200 1600 1250 1300 1350 350 350 500 DN 50

eQ siZE l1 l2 d1 d2 H1 H2 H3 H4 H5 A1 A2 A3 pipE siZE60 930 1250 1365 200 1600 1250 1300 1350 350 350 500 DN 50

62-73 1075 1660 1775 200 1600 1240 1290 1340 600 250 725 DN 65

82-84 1075 1660 1775 200 1600 1240 1290 1340 600 250 725 DN 84

3

6

1

5

4a

2

L

2a

3

61 5

4a

2b

2b

2a

3

6

1

5

4a

L

2a

3

61 5

4a

2b

Page 7: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 7

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® sCOpE Of dElivEry

Exchanger package: EQrZ-05, lQrZ-05The ECONET® Exchanger Package contsists of one or two plateheat exchangers for connection to an external heating and/orcooling system. The Exchanger Package is delivered separatelyfrom the AHU and the ECONET® pump unit or integrated as standard for eQ range, see page 4 and 5. The exchangers are made of AISI 316 stainless steel, brazedwith pure copper. The tubes are made of high-pressure steel, painted with anti-corrosion paint. These are then insulated with Armaflex. The typical pressure rating is 31 bar (450 psi), and the typical temperature rating is 225 °C (437 °F). The heat exchanger package, the ECONET® pump unit and the external pipework must not exceed a total pressure drop of 40 kPa for maximum liquid flow. If the pressure drop is higher (a long distance between the components), it should

be taken into account when dimensioning the system.The pipe connections are male pipe threads from DN25 to DN50. The connections on the primary side against the plate exchangers are female pipe threads from DN25 to DN50.For dimensions DN65 and DN80, all connections are assem-bled flanges. The opening pressure for the delivered safety valve is 4.0 bar.All sizes of ECONET® Exchanger Package come with a speciallydesigned stand for mounting on a flat floor. The unit is delivered on a separate pallet.

packagingDuring transportation the ECONET® Exchanger protects in a appropriate package. This is totaly environmentally friendly and will discarded as secondary raw material.

B

H

D

The picture shows size eQL 82, 84

eQ or eQl EXp. vEssEl diM. fOr MAX sysTEM MAX B MAX H MAX d siZE bb CONNECTiON dN vOluME litre mm mm mm eQ 005 - 027 25 120 650 950 400

eQ 030 - 045 32 200 550 1100 550

eQ 054 - 068 50 400 710 1150 800

eQ 072 - 090 50 400 710 1150 875

eQL 60 50 400 710 1150 875

eQL 62,71 65 1000 750 1250 900

eQL 64, 73, 80 65 1000 750 1250 1050

eQL 82, 84 80 1000 850 1400 1200

1 1

622

3 3

4

5

B

H

D

1. Plate heat exchangers for supplementary heating/cooling2. Pipes for ECONET® pump unit3. Shut-off valves4. Drain valve, Filling valve5. Specially designed stand6. Expansion vessel with a safety valve

Every pipe is marked with the necessaryconnection information.

integrated pump unit and exchanger package: sTAZ-74 + EQrZ-05 and sTyZ-74 + lQrZ-05The pump unit and the exchanger package are also availableas one unit for the eQ range.

Page 8: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 8

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® sCOpE Of dElivEry

Controller for heat recovery, frequency inverter and sensorsThe liquid flow in the ECONET® circuit is controlled by the frequency inverter/inverters for the pump/pumps and by an ECONET® controller. The controller is equipped with software that optimizes the circulation flow in the circuit for each operating condition. The software in the controller includes protection and alarm functions. The controller is Modbus, Backnet or LonWorks compatible.Modbus communication is intrinsic to the controller, and the Backnet and LonWorks module for the controller can be chosen as an accessory. The controller is mounted on the pump unit and is programmed with input data for the specific project. The frequency inverter for the pump is mounted on the pump unit, and cables are routed to the ECONET® controller and the pump. Necessary components such as pressure and temperaturesensors for the pump unit are included.

Components within the scope of the delivery are installed, and cables are routed to the ECONET® controller and the frequency inverter. The additional components/sensors needed for the calculation of energy recovery efficiency are included in the delivery, if specified, but mounting and cabling has to be done on site (not included in Fläkt Woods delivery).

packagingSuitable packaging protects the ECONET® unit during trans-port. This is fully environmentally compatible, and should be taken for central disposal as a secondary raw material.

CommissioningIn order to guarantee safe and optional functionality for ECONET® heat recovery, commissioning of each ECONET® system shall be carried out by accredited and trained personnel. Commissioning of ECONET® can be ordered and carried out via the Fläkt Woods sales organisation, seeorder code.

Page 9: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 9

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® AssEMBly ANd iNsTAllATiON

unpackinginspection of delivered equipment– Check for signs of transit damage.

– Check that the product codes on the rating labels conform to your requirement.

– Check the delivered components against the bill of material.

– The code for the pump unit (STAZ-74, STYZ-74) can be found on the ECONET® control box.

– The code for the ECONET® Exchanger Package (EQRZ-05, LQRZ-05) can be found on one of the heat exchangers.

installation instructionThe following must be carried out on site by the plumbing/automation and electrical contractors.– Assembly of pump unit, installation of pipes from the pump unit to the exhaust air and supply air coils.

– Installation of necessary components for connecting an external energy source, as set out in the documentation.

– Filling and air purging of system.

– Power supply to the switch in the ECONET® controller.

– Connection between the ECONET® controller and the controller for the AHU.

– Wiring between the air flow sensor (supply air) and the ECONET® controller.

– Installation of the piping from the external energy source.

– Equipment and controls for supplementary heating and cooling (SV30, SV50).

Optionif ECONET® pump unit and exhanger package deliveredseparately, then piping between the units is to be completed (see below connections 6 and 1).With the advanced freezing protection:

– Mounting and wiring of the frost prevention sensors, combined humidity and temperature (GH20 - GT20) in the extract air and temperature (GT21) in the exhaust air.

– With energy calculation: Mounting and wiring of the delive- red sensors needed for energy recovery calculation, GT00, GT10, GT20, GT30, GT21, air flow sensor (exhaust air).

– Other: Commissioning of the ECONET® system.

– Controls for AHU, SV 30, SV 50, etz.

Page 10: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 10

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

liQuid-COuplEd HEAT EXCHANGEr ECONET® prEMiuM (MulTiplE COils)

ECONET® AssEMBly ANd iNsTAllATiON

EQrT or lQrT

= Pipe connection: ECONET®

= Pipe connection: Exchanger package

EQRZ-05 and LQRZ-05

STAZ-74 and STYZ-74

EQRT and LQRT

Page 11: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 11

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

liQuid-COuplEd HEAT EXCHANGEr ECONET® prEMiuM (MulTiplE COils)

Coil installationThe coils are installed in the air handling units at the factory. The coils must be connected as a counter flow connection.Warm against warm and cold against cold. The two coils in the flow and the two coils in the exhaust air flow coils must be connected in serial connection. A “T”con-nection must be inserted between the two coils in the supply air.

Connection to the pump unitConnections between the pump unit and the coils in the exhaust and supply air flows are depending on the flow direction. Pipes connections are described in the below drawings.

supply Air Handling unit

Exhaust Air Handling unit

pipe installationConnection to the pipe system should be carried out bythe plumbing contractorInstallation normally includes:

– Installation of necessary components for connecting an external energy source, as set out in the documentation.

The necessary components vary depending on the design of the object. Examples of external components are: External shut off valves Connection for filling Automatic air purging valve combined with a manual air purging valve Air purging valves for micro bubbles Filter Charging equipment Water trap Anti-freeze liquid

if exchanger package not included– Expansion vessel– Heat exchanger and valves for supplementary heating/ cooling.– Installation of pipes between the pump unit and the two exhaust air and supply air coils– Installation of pipes between the two supply and exhaust air coils including a “T”connection between the two supply air coils.– Filling of liquid and air purging of the pump before commis- sioning– Air purging the system– Shut of valves for each coil

If the exchanger package is delivered separately from pump unit:Mounting and installation of the exchanger package to the ECONET® pump unit, and connection of the external energy sources, including necessary valves, etc.

The Econet® must be connected to the pipe system so that ex-pansion forces or the pipe system’s own weight do not impose a load on the liquid connections. The liquid connections are provided with signs for the inlet and outlet.

ECONET® AssEMBly ANd iNsTAllATiON

Pump unit

4a 5

3

3

2a

2a2b

2b

2b+– +– Pump unit

4a

4a

5

5

3 2a2b

Pump unit4a

4a4b

4b

4b

4b

5

5

32a 2b

Pump unit

4a5

3

3

2a

2a 2b

2b

2b+– +–

+–

+– +–

+–

IndoorOutside

Indoor

Outside

Indoor

Outside

Indoor

Outside

Pump unit

4a 5

3

3

2a

2a2b

2b

2b+– +– Pump unit

4a

4a

5

5

3 2a2b

Pump unit4a

4a4b

4b

4b

4b

5

5

32a 2b

Pump unit

4a5

3

3

2a

2a 2b

2b

2b+– +–

+–

+– +–

+–

IndoorOutside

Indoor

Outside

Indoor

Outside

Indoor

Outside

important!– Hold the pipe connections steady with a pipe wrench when tightening external pipes.– Use fl ax (hemp) and paste for sealing the connections.– Use sealings suited for anti-freeze liquids, such as ethylene glycol mixtures.

Page 12: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 12

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

liQuid-COuplEd HEAT EXCHANGEr ECONET® prEMiuM (MulTiplE COils)

These plates indicate:

– Which of the plate heat exchangers are intended for heating and cooling.

– Inlet and outlet of the exchangers for primary heating and cooling.

– Pipes for connection to the ECONET® pump unit.

With the pipes installed correctly, the ECONET® Exchangerneeds to be protected from condensation with insulation onthe pipes to/from the primary systems. The shut-off valves on ECONET® Exchanger Package mustbe open when the system is running as normal.

The ECONET® must be connected to the pipe system sothat expansion forces or the pipe system’s own weight donot impose a load on the liquid connections. The liquid connections are provided with signs for the inlet and outlet.

General adviceFailure to observe general advice and installation require-ments can lead to the risk of damage.

flushing the pipe system– ECONET® pump units are cleaned and flushed at the factory. When flushing the remainder of the system, we recom- mend that the pump unit is disconnected and that the P40 pump is not used during flushing. It is extremely important to remove all the flushing/cleaning fluid from the system before filling with anti freeze as a chemical reaction can occur between the cleaning and anti- freeze liquids. As the coils cannot be emptied completely, they must not be exposed to the cold without anti-freeze.

filling– For optimal heat recovery, we recommend an approximate 25-35 % ethylene glycol mixture. Max mixture for the pump is a 40 % ethylene glycol mixture. The P40 pump should not be used when filling the system. Use a separate filling system, e.g. a separate pump with a non-return valve for filling the system, e.g. a hand pump.

– Fill until a static pressure of 1-1.5 bar is obtained on the suc- tion side of the pump to avoid the risk of pump cavitation.

ECONET® AssEMBly ANd iNsTAllATiON

NB!If the ECONET® Energy Exchanger Packageis not integrated in the ECONET®-unit,the system need an additional safety valve.

NB!A purging valve must be fi tted at thehighest point in the system.

important!– Hold the pipe connections steady with a pipe wrench when tightening external pipes.– Use fl ax (hemp) and paste for sealing the connections.– Use sealings suited for anti-freeze liquids, such as ethylene glycol mixtures.

The purging, safety valve and drain connections are routed to the connection vessel next to the unit.

Page 13: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 13

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® AssEMBly ANd iNsTAllATiON

– Uses premixed anti-freeze liquid, type ethylene glycol/ water mixture. Prevent exposure to oxygen. When using concentrated ethylene glycol, it must be mixed with distilled water. The liquid must be mixed 24 hours in advance, so that the mixture will be free of micro bubbles. When filling with premixed liquid from a tanker lorry, ask for a flushing certificate.

– Mark the system with a label showing the actual flow, type of anti-freeze liquid, and concentration.

– Check for, and seal any leaks.

– Check that the anti-freeze liquid used has sufficient protection against corrosion, anti fouling and biological growth. Follow the instructions of the anti-freeze liquid manufacturer.

Air purging To get rid of all air in the system takes time, but is vital forthe performance. Use automatic air purge valves combined with manual air purge valves. Prevent the risk of contami-nation blocking the sealing and jeopardizing the shut-off function of the automatic air purge valve. Install a filter if there is a continuous problem with contamination. When the system is free of all air, make sure that all automatic aireliminators are OK and all manual valves are closed. Open and close all valves a couple of times. Close the by-pass valve and start the ECONET® pump. The pump should be run manually via the frequency inverter at maximum 30 Hz.

Under no circumstances must the pump be allowed to run dry, due to the risk of damage to the seals. Purge the air from the pump with its own purging valve. Make sure that the system pressure is maintained at 1–1.5 bar. Refillthe system continuously as the pressure decreases.If the pressure drops below 0.5 bar, there will be an A-typealarm from the controller.

Miscellaneous– Under no circumstances may the P40 pump be run dry. This is because the pump will be damaged by the air, resulting in leakage.

– The coils for supplementary heating/cooling have to be installed with separate shut-off valves. The total pressure drop for the heat exchangers on the secondary side must not exceed 40 kPa at the maximum liquid flow for a closed heat recovery circuit. A higher value should be taken into account when dimensioning the system. The purging, safety valve and drain connections must be routed to the connection vessel next to the unit.

– Use air purge valves that can handle micro bubbles (type Spirovent or Flamcovent).

– The vessel must be installed on the suction side of the pump (between the pump and the plate heat exchangers for supplementary energy) with a volume of at least 5 % of the total system volume and with 1.0 bar pre-pressure, 4.5 bar opening pressure.

– If the risk of cavitation is present on the suction side of the pump, it is advisible to install underpressure air eliminators.

Page 14: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 14

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

liQuid-COuplEd HEAT EXCHANGEr ECONET® prEMiuM (MulTiplE COils)

Electrical connection and recommended fusesOnly the cabinet must be connected at disconnecting switch. Main power shall be 3x400 VAC. An electrician shall dimension the fuses for the pump according to the table below, and according to the site circumstances. Recommended minimum fuse for the cabinet is 10 A.

ECONET® CONTrOl ANd ElECTriCAl iNsTAllATiON

warning!Ensure that all wiring is electrically insulated and cannot be made “live” unintentionally by other personnel.

PEU

VW

N

T1 T2 T2

AHu siZE puMp OuTpuT MAX. CurrENT

EQ 005 0.37 kW 0.96 A

EQ 008, 009EU 20 0.55 kW 1.44 A

EQ 011, 014EU 21 0.75 kW 1.9 A

EQ 018, 20EU 22, 30 1.1 kW 2.55 A

EQ 023, 027, 032, 036EU 31, 32, 40 1.5 kW 3.15 A

EQ 041, 045, 050,054, 056EU 33, 41, 42, 50

2.2 kW 4.45 A

EQ 063, 068, 072EU 51 3 kW 6.35 A

EQ 079, 090EQL 60, 62EU 52, 53

4 kW 8 A

EQL 64, 71, 80 5.5 kW 11.2 A

EQL 73, 82 7.5 kW 15.2 A

EQL 84 11 kW 22.18 A

Table 1. Single pump max. currents. Pump data due to the size of the Air Handling Unit. The fuse size depends on site-specifi c circumstances and must be dimensioned by an electrician.

Table 2. Twin pump max. currents. Pump data due to the size of the Air Handling Unit. The fuse size depends on site-specifi c circumstances and must be dimensioned by an electrician.

AHu siZE puMp OuTpuT MAX. CurrENT

005 2 x 0.37 kW 2 x 0.96 A

008,009,011,014 2 x 0.55 kW 2 x1.44 A

018,020,023,027 2 x 0.7 kW 2 x 1.9 A

032,041 2 x 1.1 kW 2 x 2.55 A

045,050,054,056 2 x 1.5 kW 2 x 3.15 A

063,068,072079,090,60,62 2 x 2.2 kW 2 x 4.45 A

84 2 x 5.5 kW 2 x 11.2 A

Page 15: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 15

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® CONTrOl ANd ElECTriCAl iNsTAllATiON

sensor cable connectionssupply Airflow sensor signalThe supply airflow signal (GF10) must be connected in allproduct versions before commissioning the unit. The signal transducer is part of the air handling unit delivery.Connect the airflow sensor according to the illustrationsbelow.

frost prevention sensors (advanced frost protection)The extract air combined humidity and temperature sensor(GH20 - GT20) and the exhaust air temperature sensor (GT21) must be connected in all product versions before commis-sioning the unit. The signal transducer is part of the air hand-ling unit delivery. Connect the airflow sensor according tothe illustrations below.

Exhaust airflow sensor signal (option)The exhaust airflow signal (GF20) must be connected in the product version with heat recovery efficiency measurement.Connect the airflow sensor according to the illustrations below.

Temperature sensor content of delivery and installationThe temperature sensors are included, and their locationis apparent from the list of components and the flow diagramin the documentation.Temperature sensors GT40, GT41, GF42 are connectedin the electrical cabinet via terminals. All the air temperaturesensors are without cables. All the sensors should befitted in the air duct, approximately 1.5 m from any ductheaters, to give stable measurement values. GT00, GT10,GT20, GT21, GT30 are included when heat recoverymeasurement is chosen (option).

Main supply 3 x 400 v

L1L2L3NPE

U/T1V/T2W/T3

NPE

Main supply

Heat recovery signal

A-alarm

Cooling

pump 1 indication

ECONET® start signal

B-alarm

Cooling recovery

pump 2 indication

Modbus AHu or BMs

Control signals

RefBA

110111112

0-10 V DCCOM/M

9192

StartCOM

6970

StartCOM

7172

StartCOM

7374

CNO

12

CNO

34

CNO

8182

CNO

8384

Page 16: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 16

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® CONTrOl ANd ElECTriCAl iNsTAllATiON

Mandatory sensors ECONET® standard

supply air flow sensor Gf10GG0

OUT

939495

BM

103104

GG0U1BSM

979899

101102

sensors ECONET®

Temperature out to BMs

Outdoor temperature GT00

suply air temperature GT10

Extract air temperature GT20

Add. energy temperature GT30

GT40 out

GT41 out

GT42 out

GG0

OUT

515253

BM

107108

BM

105106

BM

101102

BM

4344

0-10 VM

0-10 VM

0-10 VM

858687888980

Humidity sensor GH20Temperature sensor GT20Extract

Exhaust temperature sensor GT21

GG0

OUT

939495

BM

103104

GG0U1BSM

979899

101102

Power

Humidity 0-10V

Temperature

When communication is used between the air handling unit controller and the pump unit (Modbus) or between the air handling unit and the BMScontroller (Modbus, Bacnet or Lon) some or all the sensors data can be transmitted via communication. In that case wiring the sensors to the pump unit is not required.

Combined humidity and temperature sensor (GH20 - GT20).Siemens QFM 2120.

Page 17: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 17

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® CONTrOl ANd ElECTriCAl iNsTAllATiON

sensor GT40 for liquid temperature at the pump p40The sensor is installed at the factory.

frost protection temperature sensor GT41 and ice protection temperature sensor GT42The sensors have been installed at the factory.

frost protection sensors GH20, GT20 (advanced frostprotection), (option)Extract air combined Humidity (GH20) and Temperature (GT20)sensor. A humidity and temperature sensor are required to optimize the frost protection. The combined sensor is a part of ECONET® delivery but it must be installed and connected according to the illustration on previous pages.

Exhaust air temperature sensor GT21 (advanced frostprotection or energy calculation), (option)A temperature sensor is required to optimize the frost preven-tion. It is a part of ECONET® delivery but must be installed and connected according to the illustration on previous pages.

Note! GT21 should be mounted as close as possible the coldest part of the exhaust air stream.

Following sensors included when heat recovery measurement is chosen (option).

Outdoor temperature sensor GT00An outdoor temperature sensor is needed in the product version with efficiency calculation. The temperature sensor is a part of the ECONET® delivery, but it must be installed and connected before commissioning. Connect the temperature sensor according to the illustration on the previous page.

supply air temperature sensor GT10A supply air temperature sensor is required in product ver-sion with efficiency calculation. The temperature sensor isa part of the ECONET® delivery, but it must be installed and connected before commissioning. Connect the temperature sensor according to the illustration on the previous page.

Extract air temperature sensor GT20An extract air temperature sensor is required in the product version with efficiency calculation. The temperature sensor is a part of the frost prevention optimisation package.

Exhaust air temperature sensor GT21An exhaust air temperature sensor is required in the productversion with efficiency calculation. The temperature sensor is a part of the frost prevention optimisation package.

supply liquid temperature sensor GT30 or GT50The temperature sensor for the liquid arriving at the ECONET®

pump group shall be installed either on the primary side of the heat exchanger or in the incoming pipe to the circuit.The sensor is required in the product version with efficiency calculation for monitoring reasons.The temperature sensor is a part of the ECONET® delivery, but it must be installed and connected before commissioning.Connect the temperature sensor according to the illustration on the previous page.

Page 18: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 18

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

liQuid-COuplEd HEAT EXCHANGEr ECONET® prEMiuM (MulTiplE COils)

MAiNTENANCE iNTruCTiONs

General maintenance instructionsThe ECONET® unit does not require regular maintenance, other than observing the maintenance instructions providedby the anti-freeze liquid manufacturer. On the other hand, we recommend that regular performance checks are carried out to ensure that the unit operates as it should.

Check and pay special attention to the following:

- abnormal noise and vibrations, if any - corrosion on piping and brazed pipe joints, if any - loose pipe clamps, if any

warning! Avoid fl ushing with water near the electrical connections of the inverter and cabinet, since water could then seep into them and may cause a short circuit.

Cleaning the standard ECONET® coilsEven an effective air filter cannot remove all the dust from the air. The coating of dust on heating surfaces obstructs the air flow and gives poorer heat transfer. The coils must be kept clean, which is best performed with one of the following alter-natives or combinations of these.

1. Blowing clean with compressed air2. Blowing clean with steam3. Washing or rinsing with water. In the case of heating surfaces that are coated with grease, an appro- priate detergent should be added.4. Vacuum cleaning After cleaning, all the fallen dust should be removed before starting the fan.The drip trays for the coils should be cleaned as appropriate.Also ensure that the water trap is cleaned and filled with water.

Cleanable coils for hygiene applicationsAll ECONET® coils with hygiene fins are fully cleanable accor-ding to the standards VDI3803 and VDI6022. This means that the coil can be cleaned with a high-pressure water system right through the core. The cleaning nozzle used for coilswith a fin pitch of 2.0-2.5 mm and deeper than six tubes is THD Power Clean manufactured by TECHNISCHER HYGIENE DIENST GMBH (E-mail: [email protected], web: www.thd.info).If the coil is six tubes deep or less, an ordinary nozzle can be used.

1. Make sure that no sensitive equip- ment, either inside or outside the unit, can be harmed by the water. Be extra careful not to damage the filter. If the unit has an empty section (EQTC), use the special drip plate to protect the rest of the unit.2. Clean the coil with a high-pressure cleaner. If the coil is deeper than six tubes, a THD Power Clean is needed to ensure a full cleanability.3. Point the nozzle at a 45-degree angle to have a free passage for the water jet through the coil. Make sure that the water penetrates the coil.4. Remove all dirt.5. Dry all surrounding parts in the unit. heaters, to give stable measurement values. GT00, GT10, GT20, GT21, GT30 are included when heat recovery measurement is chosen (option).

Anti-freeze liquidFollow the instructions from the anti-freeze liquid manufacturerregarding controls, maintenance, flushing and intervals for filling with fresh liquid, etc.

TAsk iNTErvAl, EACH yEAr

Liquid status Check the freezing point of the frost protection fl uid and follow the instructions from the anti-freeze liquidmanufacturer, controls of frost protection/quality, purity, colour, etc.Check the system pressure and top up with ethylene glycol mixture if necessary.Check the liquid fl ow against the balancing report.

Coils Check that the fi nned surface of the coils are not dirty and clean if necessary.

Water trap Check that water is present in the water trap for the exhaust air and supply air coils.

Air purging Check frequently initially. An annual check is suffi cient after the fi rst year.Shut off the pump and wait a couple of hours to make sure that the air bubbles have risen to the highest points in thesystem, where the air-valves should be present. Open/close all valves in the system so that all trapped air can be removed.

Valve checking Shut down the system and open/close every valve to make sure it has a smooth operation.

Pump seals Check the seals, and replace them if leakage is excessive.

Page 19: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 19

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® fuNCTiONAl dEsCripTiON

functionThe heat recovery function is controlled by the ECONET®

control box. The specific functions for the AHU must be con-trolled by a separate controller (not included in the ECONET® delivery). The functions below describe the internal heat recovery function for ECONET®. The process and instru-mentation diagram for ECONET® is shown below.

ECONET®, extended delivery:Standard/normal: GT40, GT41, GT42, SV40, SV41, GP41, GF10, FO40.1, P40.1Advanced frost prevention: GT20, GH20, GT21Option: Double pump: FO40.2, P40.2Efficiency calculation: GT 00, GT10, GT20, GT21, GT30, GF20

Air handling unit not runningWhen the temperature GT41 is below +16 °C, the pump will start to operate at a constant low speed. When the liquid tempera-ture GT41 is higher than +17 °C, the pump P40 will stop.

start of the air handling unitWhen ECONET® receives a start-up signal, the pump P40starts to operate at a constant high speed after 3 minutes.After that the pump goes to optimal sequence.

Main functionECONET® is a part of the sequence to control the supplyair temperature to its set point.

Main functions of ECONET® control box (control sequence):• Cooling recovery, On/Off signal The pump P40 and frequency converter FO40 regulate the liquid flow to an optimal value for cooling recovery, and valve SV40 by-pass will then close. NOTE. The heat recovery signal must be 0 %.

• Supplementary cooling, On/Off signal The pump P40 and frequency converter FO40 regulate the liquid flow to the optimal value for supplementary cooling. SV40 will open. NOTE. The heat recovery signal must be 0 %.

• Heat recovery, 0...100 %, 0...10 V signal The pump P40 starts at minimum speed, the valve SV40 moves from open to closed, pump P40 goes from minimum speed to optimal speed (optimal heat recovery liquid flow).

• See below for twin-pump function and other support functions, further down.

frost and ice protection• Frost protection The liquid temperature at GT41 is prevented from dropping below the temperaure (approx -3 °C) for frost protection by regulating the liquid flow with the pump P40 and FO40 from optimal liquid flow to an increased liquid flow.

• Prevention against frost formation on the exhaust air coils (air side) When conditions are such that increasing the liquid flow is not sufficient, the valve, SV40, is controlled by the controller.

• Risk of frost formation When the liquid temperature GT41 falls below the A alarm value (approx. -10 °C), the A-type alarm is given.

GT21

SV41

GT42

GP41

GT41

GT40

GT00

GT10 GF

10

P40.1FO40.1

GT30

GT20

GF20

Exhaust coils

Exhaust air

Supply coils

Supply air

Supplementaryenergy

*GT30 and GT50 alternatively on the supply pipe to the heat/cooling exchanger

*

GH20

SV40

Page 20: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 20

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® fuNCTiONAl dEsCripTiON

• Ice protection: Protection against ice formation in the heat exchangers for supplementary heating/cooling (waterside) The liquid temperature at GT42 is prevented from dropping below the temperature (approx. 6 °C) for ice protection by regulating the liquid flow with the pump P40 and FO40 from optimal liquid flow to an increased liquid flow.

• Risk of ice formation When the liquid temperature GT42 falls below the A alarm value (approx. 2 °C), the A-type alarm is given.

Alarms• A-type alarms – Risk of frost formation, GT41 ( - 10 °C) – Risk of ice formation, GT42 (+ 2 °C) – Pump indication not the same as set value (conflict alarm, should run but does not, or should not run but does) – Low pressure in ECONET® liquid circuit – Internal hardware fault (heat recovery, GF10, GT41, GT42).

• Risk of frost formation When the liquid temperature GT41 falls below the A alarm value (approx. -10 °C), the A-type alarm is given.

• B-type alarms – One of the twin pumps has stopped when it should run.

Additional functions/options• Redundant pumps The ECONET® product version with redundant pumps has two pumps (P40.1 and P40.2) and frequency converters (FO40.1 and FO40.2) running in parallel. They are started and controlled in parallel. In the event of one of the pumps failing to run, the other pump continues to run automati- cally. Failure of one pump is indicated with the B-type alarm. The ECONET® unit continues running according to control signals with one pump only.

• Energy and Power calculation If energy calculation is specified, the ECONET® controller calculates an estimate of momentary power for – Recovered power – Additional power and – Power to the supply air The same momentary powers are accumulated to energy, and the following energy consumption values are calcu- lated: – Recovered heating energy – Recovered cooling energy – Additional heating energy – Additional cooling energy – Heating energy to supply air – Cooling energy to supply air Calculated power and energy values are shown locally or via the communication interface. The calculated values are estimates only and are not calibrated. They can be used for general monitoring, but not as the basis for func- tions such as invoicing, for example.

• Efficiency calculation If necessary, additional measurement sensors (GT00, GT10, GT20, GT21) are installed and connected. The ECONET® controller then calculates the heat recovery efficiencies. The following efficiencies are calculated: – Supply air temperature heat recovery efficiency – Exhaust air temperature heat recovery efficiency – Momentary power heat recovery efficiency Due to measurement inaccuracies and small temperature differences the calculated efficiency values may exceed 100 %.

• Monitoring Two additional sensors (GF20, GT30) are used for dia- gnosing the operation of the ECONET® unit. – Exhaust airflow sensor: In order to evaluate heat recovery efficiency, the supply and exhaust flows must be equal. – Additional heating/cooling liquid temperature: The temperature level must be high enough to provide necessary additional heating/cooling.

Page 21: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 21

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

CONTrOllEr OpErATiON

1. lCd displayDisplay of the values and settings.

2. Home buttonReturn to the start page irrespectiveof which menu you are in.

3. Alarm buttonDisplay of the alarm list andacknowledged alarms.

4. return buttonMove one menu upwards inthe menu tree.

5. up buttonMove cursor upwards orincrease value.

6. down buttonMove cursor downwards ordecrease value.

7. Enter buttonConfirm changes to values andmenu selection.

1

2

3

4

5

6

7

OperationThe unit is operated by external automation equipment such as the building automation system or the AHU main controller. The current status can be read from the “home” display that is always accessible by pressing home button.

Operating informationThe full status of the unit is presented in the Main overviewmenu. Here you can read the set points, actual values, control signals, output signals to valves and frequency converters etc.Use the row selector buttons (5) and (6) to scroll between values.

AlarmsAlarms are indicated by the red flashing LED on the alarm button (3). Press the alarm button once to access the alarm list detail. Latest alarm is presented in clear text.

Alarm acknowledgementPress alarm button once to access the alarm list. Active alarms are marked with plus code. Press the enter and then execute to acknowledge alarms. The alarm lamp is then lit. The alarm lamp should then go out. Active alarms cannot be acknowledged. If the alarm remains, the alarm lamp is con-tinuously lit.

Page 22: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 22

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

MENu sTruCTurE OvErviEw

The table below shows the overview of the menu structure.There is no detailed description for each separate display oritem in a display. The structure and displays and the namesshould be self-explanatory. The user interface consists of groups of parameters to be shown to the user. The tree below shows the tree structure.

All the texts are language-dependent. To be able to see allthe values on a display page that is limited to 6 rows, usethe row selector buttons to scroll to the lines that are below the lowest line shown in the display.

MENu sTruCTurE OvErviEw dEsCripTiON

Start page First menu when switching on the power

Password enter User password: 1000, Service password: 2000

ECONET® Unit Information

Main overview All actual values and setpoints along with the control signals

Operating mode An overwiev of current operation modes

Energy Energy readouts

Setpoints/settings Setpoints and settings for air flow and pressures

Auxiliary Various auxillary functions

IO´s Status of inouts and outputs

Inputs Analog and digital inputs

Outputs Analog and digital outputs

Manual operation Overwiev of functions overrided in manual operation

Loop controllers Measured operating period and reset of runtime meter

Operating hours Status and settings of relevant controllers

System settings System settings in the controller

Global functions Settings for summer/winter changeover

Alarm handling Alarm handling and alarm status

System overview System settings. Such as time, communication etc.

Overview IO/raw values Raw value on the inputs and outputs

Configuration Reconfiguration of the system

Actual operationg mode Displaying the current operating mode

Heat recovery signal Actual heat recovery signal, 0 - 100 %

ECONET® Climatix

Page 23: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 23

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® pArAMETErs

The configuration parameters for ECONET® are listed in the table below. They are checked during the commissioningphase, and they can be changed during the operation phase.

Most of the parameters are automatically downloaded and preset during manufacturing.

Commissioning short description permissible range Config.airflow Configure airflow

Pressure range Pressure range 0...8000 Pa

K-factor supply K-factor supply 0...50

K-factor exhaust K-factor exhaust 0...50

Config.liquidflow Configure liquid flow measurement

Pressure range Pressure range 0...1000 kPa

Pressure lower Liquid pressure lower 0...1000 kPa

Flow lower Liquid flow lower 0...20 ltr/s

Pressure upper Liquid pressure upper 0...1000 kPa

Flow upper Liquid flow upper 0...20 ltr/s

Optimal heating rec. Optimal heating curve

Air lower Optimal heating air flow lower 0...50 m3/s

Liquid lower Optimal heating liquid flow lower 0...20 ltr/s

Air upper Optimal heating air flow upper 0...50 m3/s

Liquid upper Optimal heating liquid flow upper 0...20 ltr/s

Optimal cooling rec. Optimal cooling with heat recovery curve

Air lower Optimal cooling air flow lower 0...50 m3/s

Liquid lower Optimal cooling liquid flow lower 0...20 ltr/s

Air upper Optimal cooling air flow upper 0...50 m3/s

Liquid upper Optimal cooling liquid flow upper 0...20 ltr/s

Optimal cooling Optimal cooling with heat recovery curve

Air lower Optimal cooling air flow lower 0...50 m3/s

Liquid lower Optimal cooling liquid flow lower 0...20 ltr/s

Air upper Optimal cooling air flow upper 0...50 m3/s

Liquid upper Optimal cooling liquid flow upper 0...20 ltr/s

laminar flow / limits fluid flow setpoints

Nominal setpoint Nominal laminar flow 0...20 ltr/s

Comp setback / Comp.factor Laminar flow compensation 0...20 ltr/s

idle idle state setpoints Starttemp. Liquid temperature idle set point 40...100 °C

Flow setpoint Liquid flow idle set point 0...15 ltr/s

startup start state setpoint Flow setpoint Start flow set point 0...15 ltr/s

Startuptime Start state duration 0...10 Min.

frost protection frost protection Frost protection Frost protection setpoint

Frost alarmlimit Frost protection alarm set point

ice protection ice building protection Ice protection Ice protection setpoint

Ice alarmlimit Ice protection alarm set point

Page 24: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 24

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

Commissioning short description permissible range fC controller

Propor.Fact Liquid flow controller P-term

Integr.Fact Liquid flow controller, I-term

Diffen.Fact Liquid flow controller, D-term must be 0

frost controller Control settings, frost protection controller Propor.Fact Frost protection controller P-term

Integr.Fact Frost protection controller I-term

Diffen.Fact Frost protection controller D-term must be 0

ice controller Control settings, ice protection controller Propor.Fact Ice building protection controller P-term

Integr.Fact Ice building protection controller I-term

Diffen.Fact Ice building protection controller D-term must be 0

frequency converter fC settings Min. speed Frequency converter minimum speed 20 %

Other settings Other settings Alarmlimit low eff. Heat recovery efficiency low alarm limit 0...100 %

Min nominator Minimum permissible nominator when calculating efficiencies

Concentration Heat recovery liquid concentration max 40 %

Coil frost protection ice building on coil protection Exh hum.Dew. + Dz Exhaust humidity dewpoint dead zone –64...64 °C

Exh hum.Dew. + Dz Exhaust dewpoint max limit of setpoint –64...64 °C

dew point controller ice building on coil protection Gain Dew point controller P-term

Int action time Dew point controller I-term

Derivate time Dew point D-term

ECONET® pArAMETErs

Page 25: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 25

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® COMMuNiCATiON

In ECONET® there are currently three communication protocol options available: Modbus, LonTalk and BACnet. The following profiles define the communication interface when integrating ECONET® into a larger automation system.

Modbus rTuThe purpose of this section is to provide users with a means of familiarizing themselves with the configuration and use of Modbus within Climatix. More information can be found from the following documents:

• Climatix Modbus communication, slave mode Integration guide Fläkt Woods 8947GB 201006.• For the full specification of Modbus, refer to “modbus.org”.

Modbus RTU uses the RS485 bus as its communication medi-um. RS485 is a balanced line, half-duplex transmissionsystem that meets the requirements for a truly multi-point communication network, and the standard specifies up to 32 drivers and 32 receivers on a single (2-wire) bus. Half-duplex data transmission means that data can be transmitted in both directions on a signal carrier, but not at the same time.

Connection and configurationinternal interfaceRS485 (one of two Modbus interfaces always available on the basic controller) can be defined as either master or slave. The MODBUS-IP interface is always a slave and the internal RS485 Modbus interface is automatically set to master ifthe energy meter function is enabled.

External communication moduleA slave interface is always provided with the external Mod-bus communication module POL 902.Reference the above listed documentation for instructionsregarding commissioning.

ECONET® communicationFollow the instructions below to configure RS485 and Mod-bus. Settings in Climatix controller:1. Commissioning the unit with all settings before starting to configure Modbus.2. Log in with password 2000.

Navigate to menu “System overview – Communication – Modbus” to set slave address, baudrate and parity.

MENU SYSTEM OVERVIEW

COMMUNICATION MODBUS

3. Set the slave address for the device. (1-247, Must be unique within the system).4. Set Baudrate for RS485 (2400-38400).5. Set Parity for RS485 (None, Even, Odd).6. Set number of Stopbit for RS485 (1 or 2).7. Reset is required in order for the configured settings to take effect.

Note!Note that the temperature values are given in tenths of a degree Celsius. For example, 21 degrees Celsius is given as a numeric value 210. The numeric value must therefore be divided by 10 to arrive at the correct value.

Modbus addresses0 x read and write on/off information1 x read on/off3 x read numeric values4 x read and write numeric valuesRegister address list.

Page 26: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 26

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

THE AddrEssEs fOr ACCEssiBlE rEGisTErs ArE As iNdiCATEd iN THE fOllOwiNG TABlE

input states Address parameter description value/unit factor0x0001 Reset alarms Acknowledge all alarms in the ECONET®. Write 1 for Alarms that are not corrected will remain. reset puls

0x0002 Communication Test Enable Configuration parameter. Not active och *Active

0x0003 Communication Test Configuration parameter. Not active och *Active

0x0007 Energy Meter Reset Reset puls to reset the energy meter . Write 1 for reset puls

0x0011 Unit stop Digital input for stopping the unit. Not active och *Active

0x0012 Digital control input 1 Control input. Not active och *Active

0x0014 Summer-Winter switch Input for change of summe/winter mode. Not active och *Active

input coils Address parameter description value/unit factor1x0001 Alarm class A Danger active Indication of one ore more alarms of alarm class A is active. Not active och *Active danger class. 1x0002 Alarm class A Critical active indication of one ore more alarms of alarm class A is active. Not active och *Active Critical class. 1x0003 Alarm class B active Indication of one ore more alarms of alarm class B is active. Not active och *Active

1x0004 Alarm class C active Indication of one ore more alarms of alarm class C is active. Not active och *Active

1x0005 Frost protection alarm Temperature after supply air coil has reach a critical low temp. Ok*Alarm

1x0006 Ice protection alarm Temperature after exhaust air coil has reach a critical low temp. Ok*Alarm

1x0007 Pressure low liquid alarm The pressure switch, PS40, indicating low pressure in the liquid. Ok*Alarm

1x0008 Pump1 alarm Alarm from frecuency inverter to pump 1. Ok*Alarm

1x0009 Pump2 alarm Alarm from frecuency inverter to pump 2. Ok*Alarm

1x0010 Both pumps alarm Alarm from both the pumps. Ok*Alarm

1x0011 Additional heating temperature alarm The sensor mounted on the additional heating is in alarm. Ok*Alarm

1x0012 Supply flow alarm Alarm on the supply air flow sensor. Ok*Alarm

1x0013 Exhaust flow alarm Alarm on the exhaust air flow sensor. Ok*Alarm

1x0014 Efficiency alarm Heat efficiency alarm. Default alarm limit 0%. Ok*Alarm

1x0020 Out temp sensor alarm Outdoor temperature sensor is in alarm. GT00. Ok*Alarm

1x0021 Supply temp sensor alarm Supply air temperature sensor in alarm. GT10. Ok*Alarm

1x0022 Exhaust temp sensor alarm Exhaust air temperature sensor in alarm. GT20. Ok*Alarm

1x0023 Extract temp sensor alarm Extract air temperature sensor in alarm. GT21. Ok*Alarm

1x0024 Alarm liquid pump temp Themperature sensor after pump in alarm. GT40. Ok*Alarm

1x0025 Aux temp sensor alarm Auxiliary temperature sensor in alarm. Ok*Alarm

1x0026 Added cooling temp sensor alarm The sensor mounted on the additional cooling is in alarm. Ok*Alarm

1x0027 Exhaust humidity sensor alarm Humidity sensor in exhaust in alarm, GH20. Ok*Alarm

1x0028 Heat recovery air pressure sensor alarm Pressure sensor, pressure drop over exhaust air coil, in alarm. Ok*Alarm

1x0033 Pump1 Start signal to pump1 from controller. Off*On

1x0034 Pump1 indication Pump1 run indication. Off*On

1x0035 Pump2 Start signal to pump2 from controller. Off*On

1x0036 Pump2 indication Pump2 run indication. Off*On

1x0039 Bypass valve open Indication of that the Bypass valve SV40 is open. Off*On

1x0040 Bypass valve closed Indication of that the Bypass valve SV40 is closed. Off*On

1x0047 Alarm A output Status for the alarm relay for A alarm. Off*On

1x0048 Alarm B output Status for the alarm relay for B alarm. Off*On

1x0050 Actual status ECONET® start Status of the start signal to the ECONET®. Off*On

1x0051 Actual status cooling start Status of the cooling start signal to the ECONET®. Off*On

Page 27: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 27

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

Address parameter description value/unit factor

1x0052 Actual status cooling reovery start Status of the cooling recovery start signal to the ECONET®. Off*On

1x0053 Actual status pump1 feedback Status of the pump 1 feedback signal. Off*On

1x0054 Actual status pump2 feedback Status of the pump 2 feedback signal. Off*On

input registerAddress parameter description value/unit factor

3x0001 ECONET® start Status of the start signal to the ECONET®. Off*On 1

3x0002 Cooling start Status of the cooling start signal to the ECONET®. Off*On 1

3x0003 Cooling recovery start Status of the cooling recovery start signal to the ECONET®. Off*On 1

3x0004 Heating recovery input Startus of the heating recovery input to the ECONET®. 0–100 % 1

3x0005 Supply air flow Supply air flow value in l/s. xx.y l/s 1

3x0006 Exhaust air flow Exhaust air flow value in l/s. xx.y l/s 1

3x0009 Actual operation mode 0=Stop, 1=Alarm, 2=Idle, 3=Startup, 4=Heating recovery, 0-7 1 5=Cooling, 6=Cooling recovery, 7=Hand mode.

3x0010 Liquid flow The actual liquid flow in the pipe work. xx.y l/s 0.1

3x0011 Actual setpoint liquid flow The setpoint of the liquid flow. Depending of the mode and air flow. xx.y l/s 0.1

3x0012 Supply air flow The actual supply air flow in m3/s. xx.y m3/s 0.1

3x0013 Exhaust air flow The actual exhaust air flow in m3/s. xx.y m3/s 0.1

3x0020 Liquid temperature at pump, GT40 Temperature of the liquid after the pump. xx.y °C 0.1

3x0021 Frost temperature, GT41 Temperature of the liquid between the supply coil xx.y °C 0.1 and the exhaust coil.

3x0022 Ice temperature, GT42 Temperature of the liquid before the plate heat exhanger xx.y °C 0.1 or before the pump.

3x0023 Out door temperature Temperature of the air in the outdoor duct. xx.y °C 0.1

3x0024 Supply air temperature Temperature of the air in the supply duct. xx.y °C 0.1

3x0025 Exhaust air temperature Temperature of the air in the exhaust air duct. xx.y °C 0.1

3x0026 Extract air temperature Temperature of the air in the extract air duct. xx.y °C 0.1

3x0027 Additional heat temperature Temperature oft the liquid in the inlet to the plate xx.y °C 0.1 heat exhanger of the additional heating.

3x0030 Analog output bypass valve The output value to the bypas valve, SV40. 0–100 % 1

3x0031 Analog output frequency inverter pump1 The output value to the frequency inverter for the first pump, Pump 1. 0–100 % 1

3x0032 Analog output frequency inverter pump2 The output value to the frequency inverter for the secound pump, Pump 2. 0–100 % 1

3x0033 Aux temperature Temperature of the auxiliary tempeterature sensor. -x.y-+x.y °C 0.1

3x0034 Additional cooling temperature Temperature of the liquid in the inlet to the plate -x.y-+x.y °C 0.1 heat exhanger of the additional cooling.

3x0040 Efficency extract The efficiency of the ECONET®. 0–xxx % 0.1 Temperature sensors in the air streams needed.

3x0041 Efficiency ECONET® The efficiency of the ECONET®. 0–xxx % 0.1 Temperature sensors in the air streams needed.

3x0043 Power supply Power to the supply air from the supply coil. xx.y kW 0.1

3x0044 Power recovered Power to the exhaust coil from the exhaust air. xx.y kW 0.1

3x0045 Power additional Power from the additional cooling/heating. xx.y kW 0.1

3x0046 Recovery energy effect Recovery energy effect by the ECONET®. xx.y % 0.1

3x0047 Check Check value of the summation of the power calculation. xx.y kW 0.1

3x0060 Scale liquid pressure sensor Set by the factory. xxx kPa 0.1

3x0061 Liquid pressure lower Uniqe for the project. Set by the factory. xx.y kPa 0.1

3x0062 Liquid flow lower Uniqe for the project. Set by the factory. xx.y l/s 0.1

3x0063 Liquid pressure upper Uniqe for the project. Set by the factory. xx.y kPa 0.1

3x0064 Liquid flow upper Uniqe for the project. Set by the factory. xx.y l/s 0.1

3x0065 Supply scale air pressure sensor The supply air pressure sensor scale. Same value as in the sensor. xxx Pa 0.1 Set in factory.

3x0066 K-factor supply air The K-factor for the supply air fan inlet. Set in factory. xx.yy 0.1

3x0067 K-factor exhaust air The K-factor for the exhaust air fan inlet. Set in factory. xx.yy 0.1

Page 28: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 28

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

Address parameter description value/unit factor

3x0068 Laminar nominal flow Laminar nominal flow. xx.y l/s 0.1

3x0069 Laminar compensation factor Laminar compensation factor. xx.y l/s 0.1

3x0070 Optimal heating air flow lower Configuration of optimal flow curve in heat recovery mode. xx.y m3/s 0.1

3x0071 Optimal heating liquid flow lower Configuration of optimal flow curve in heat recovery mode. xx.y l/s 0.1

3x0072 Optimal heating air flow upper Configuration of optimal flow curve in heat recovery mode. xx.y m3/s 0.1

3x0073 Optimal heating liquid flow upper Configuration of optimal flow curve in heat recovery mode. xx.y l/s 0.1

3x0074 Optimal cooling recovery air flow lower Configuration of optimal flow curve in cooling recovery mode. xx.y m3/s 0.1

3x0075 Optimal cooling recovery liquid flow lower Configuration of optimal flow curve in cooling recovery mode. xx.y l/s 0.1

3x0076 Optimal cooling recovery air flow upper Configuration of optimal flow curve in cooling recovery mode. xx.y m3/s 0.1

3x0077 Optimal cooling recovery liquid flow upper Configuration of optimal flow curve in cooling recovery mode. xx.y l/s 0.1

3x0078 Optimal cooling air flow lower Configuration of optimal flow curve in cooling mode. xx.y m3/s 0.1

3x0079 Optimal cooling liquid flow lower Configuration of optimal flow curve in cooling mode. xx.y l/s 0.1

3x0080 Optimal cooling air flow upper Configuration of optimal flow curve in cooling mode. xx.y mv/s 0.1

3x0081 Optimal cooling liquid flow upper Configuration of optimal flow curve in cooling mode. xx.y l/s 0.1

3x0082 Idle flow setpoint Setpoint for the ECONET® water flow in idle state. xx.y l/s 0.1

3x0083 Idle temperature setpoint Setpoint for the ECONET® water temperature in idle state. xx.y °C 0.1

3x0084 Startup flow setpoint Setpoint for the water flow during startup time. xx.y l/s 0.1

3x0085 Startup time ECONET® startup time. (Delay of AHU start). xx min 1

3x0086 Frost protection setpoint Water frost protection setpoint after the supply air coil. xx.y °C 0.1

3x0087 Frost protection alarm limit Water frost protection alarm limit after the supply air coil. xx.y °C 0.1

3x0088 Frost protection controller P Gain for the frost controller. xx.yy 0.01

3x0089 Frost protection controller I Integration time for the frost controller. xx.yy 0.01

3x0090 Ice protection setpoint Water ice protection setpoint after the exhaust air coil. xx.y °C 0.1

3x0091 Ice protection alarm limit Water ice protection alarm limit after the exhaust air coil. xx.y °C 0.1

3x0092 Ice protection controller P Gain for the ice protection controller. xx.yy 0.01

3x0093 Ice protection controller I Integration time for the ice protection controller. xx.yy 0.1

3x0094 Dew.Point controlller P Gain for the dewpoint controller. xx.yy 0.01

3x0095 Dew.Point controlller I Integration time for the dewpoint controller. xx.yy 0.1

3x0096 Heat recovery frost pressure The pressure value for the pressure drop over the exhaust air coil. xxx Pa 0.1

3x0150 Exhaust air relative humidity Messured value of the relative humidity in exhaust air. 0-100 % rH 0.1

3x0151 Coil frost protection controller output Coil frost protection controller output. 0–100 % 0

3x0152 Coil frost protection bypass valve output Coil frost protection bypass valve output. 0–100 % 0

3x0153 Coil frost protection flow controller output Coil frost protection flow controller output. 0–100 % 0

3x0154 Coil frost protection coil bypass valve output Coil frost protection coil bypass valve output. 0–100 % 0

3x0155 Coil frost protection flowcurve X1 Flow curve for coil frost protection. 0–100 % 0.1

3x0156 Coil frost protection flowcurve X2 Flow curve for coil frost protection. 0–100 % 0.1

3x0157 Coil frost protection flowcurve Y1 Flow curve for coil frost protection. 0–100 % 0.1

3x0158 Coil frost protection flowcurve Y2 Flow curve for coil frost protection. 0–100 % 0.1

3x0160 Coil frost protection bypass valve curve X1 Bypass valve curve for coil frost protection. 0–100 % 0.1

3x0161 Coil frost protection bypass valve curve X2 Bypass valve curve for coil frost protection. 0–100 % 0.1

3x0162 Coil frost protection bypass valve curve Y1 Bypass valve curve for coil frost protection. 0–100 % 0.1

3x0163 Coil frost protection bypass valve curve Y2 Bypass valve curve for coil frost protection. 0–100 % 0.1

3x0165 Coil frost protection coil bypass valve X1 Coil bypass valve curve for coil frost protection. 0–100 % 0.1

3x0166 Coil frost protection coil bypass valve X2 Coil bypass valve curve for coil frost protection. 0–100 % 0.1

3x0167 Coil frost protection coil bypass valve Y1 Coil bypass valve curve for coil frost protection. 0–100 % 0.1

3x0168 Coil frost protection coil bypass valve Y2 Coil bypass valve curve for coil frost protection. 0–100 % 0.1

3x0173 Coil frost protection exhaust dewpoint dead zone Coil frost protection exhaust dewpoint dead zone. xx.y °C 0.1

3x0174 Coil frost protection exhaust max dewpoint setpoint Coil frost protection exhaust max dewpoint setpoint. xx.y °C 0.1

Page 29: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 29

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

Holding registerAddress parameter description value/unit factor4x0001 ECONET® start 0=Off, 1=On. Off*On 1

4x0002 Cooling start 0=Off, 1=On. Off*On 1

4x0003 Cooling recovery start 0=Off, 1=On. Off*On 1

4x0004 Heating recovery signal Control signal to ECONET® from BMS. Heating recovery demand 0-100%. 0–100 % 1

4x0005 Supply air flow Supply air flow from external system, BMS. xx.y l/s 1

4x0006 Exhaust air flow Exhaust air flow from external system, BMS. xx.y l/s 1

4x0007 Out door temperature Use if out door temperature will be sent from BMS to ECONET®. -x.y-+x.y °C 0.1

4x0008 Supply temperature Use if supply air temperature will be sent from BMS to ECONET®. -x.y-+x.y °C 0.1

4x0009 Exhaust temperature Use if exhaust air temperature will be sent from BMS to ECONET®. -x.y-+x.y °C 0.1

4x0010 Extract temperature Use if extract air temperature will be sent from BMS to ECONET®. -x.y-+x.y °C 0.1

4x0150 Exhaust air relative humidty The realativ humidity in exhaust air. Used by the coil frost protection controller. 0-100% rH 0.1

4x0155 Coil frost protection flowcurve X1 Set by factory. xxx 0.1

4x0156 Coil frost protection flowcurve X2 Set by factory. 0–100 % 0.1

4x0157 Coil frost protection flowcurve Y1 Set by factory. 0–100 % 0.1

4x0158 Coil frost protection flowcurve Y2 Set by factory. 0–100 % 0.1

4x0160 Coil frost protection bypass valve curve X1 Set by factory. 0–100 % 0.1

4x0161 Coil frost protection bypass valve curve X2 Set by factory. 0–100 % 0.1

4x0162 Coil frost protection bypass valve curve Y1 Set by factory. 0–100 % 0.1

4x0163 Coil frost protection bypass valve curve Y2 Set by factory. 0–100 % 0.1

4x0165 Coil frost protection coil bypass valve X1 Set by factory. 0–100 % 0.1

4x0166 Coil frost protection coil bypass valve X2 Set by factory. 0–100 % 0.1

4x0167 Coil frost protection coil bypass valve Y1 Set by factory. 0–100 % 0.1

4x0168 Coil frost protection coil bypass valve Y2 Set by factory. 0–100 % 0.1

4x0173 Defrost coil humidity setpoint Deadzone Dead zone of the dewpoint temperature for xx.y °C 0.1 the coil frost protection controller.

4x0174 Defrost coil humidity abs limit Max dewpoint temp for the coil frost protection controller. xx.y °C 0.1

4x0200 Idle flow setpoint Liquid flow setpoint in idle mode. xx.y l/s 0.01

4x0201 Idle temperature setpoint Liquid tempereature setpoint in idle mode. xx.y °C 0.01

4x0202 Startup flow setpoint Liquid flow setpoint in startup mode. xx.y l/s 0.01

4x0203 Startup time Liquid tempereature setpoint in startup mode. xx.y °C 0.01

4x0204 Frost protection setpoint Controller setpoint for frost protection controller. xx.y °C 0.01

4x0205 Frost protection alarm limit Alarm limit for frost protection controller. xx.y °C 0.01

4x0206 Frost protection controller P Gain for the frost protection controller. xx.yy 1

4x0207 Frost protection controller I Integration time for the frost protection controller. xx.yy 1

4x0208 Liquid frost temperature Liquid temperature,GT41, after the supply coil. xx.y °C 0.1

4x0209 Ice protection setpoint Controller setpoint for ice protection controller. xx.y °C 0.1

4x0210 Ice protection alarm limit Alarm limit for ice protection controller. xx.y °C 0.01

4x0211 Ice protection controller P Gain for the ice protection controller. xx.yy 1

4x0212 Ice protection controller I Integration time for the ice protection controller. xx.yy 1

4x0213 Liquid ice temperature Liquid temperature,GT42, after the exhaust coil. xx.y °C 0.1

4x0214 Coil frost protection controller P Gain for the coil frost protection controller. xx.yy 0.01

4x0215 Coil frost protection controller I Integration time for the coil frost protection controller. xx.yy 1

4x0216 Coil frost protection controller D Derivition time for the coil frost protection controller. xx.yy 1

4x0220 Additional heating temperature Additional heating water temperature. xx.y °C 0.1

4x0221 Additional cooling temperature Additional cooling water temperature. xx.y °C 0.1

4x0222 Aux temperature Auxiliary temperature sensor. xx.y °C 0.1

Page 30: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 30

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ECONET® COMMuNiCATiON

lonTalkThe purpose of this document is to provide users with a quick and simple means to familiarize themselves withthe configuration and use of the Lon module on Climatix.More information can be found in the following documents:

• Climatix LON communication with POL906.00 Integration guide Fläkt Woods 8971 GB 2011.11.• For the full specification on LonTalk, please refer to the relevant standards.• You will also find more information about LonTalk at www.echelon.com and www.lonmark.org.

Lon communication is mostly used to integrate our ECONET® controller into a building management system. The goal of integration is to have the necessary dataavailable on the management PC, and to permit changes to the dedicated set points and stages. Use the commis-sioning workbook for ECONET® parameter settings. A special LON tool (for example NLStart Maker or NL 220 from Newron-Systems, or LonMaker from Echelon) must be used to configure the network, bind the variables and

to observe the snvt’s. The tool is also used to download the XIF and NXE files (LON image) for ECONET®. The image for ECONET® does not follow the image defined in Clima-tix LON communication with POL906.00 Integration guide Fläkt Woods 897GB 2011.11 (ClimatixAHU V1.x. loaded per default). The ECONET® image including two files (*.NXE and *.XIF) can be received from FWG. To communicate with the LON device, the PC must have a LON interface (card) installed as well. The ECONET® controller uses FTT-10A (Free Topology Technology) transceivers on a 78 kbs network. When deciding on the topology, relevant factors are themaximum cable length and the distance between the twofurthest bus subscribers. For details of the design, pleaseconsult the manuals mentioned above.

ConnectionConnect the LON module to the Climatix controller via the internal communication extension bus (plug connection on the left side of the controller) and follow the commissioning instructions as described in the manuals mentioned above.

settingsPush the “service pin” (alternatively execute software trigger for the service pin via the HMI if available in installed version) to send the neuron ID onto the bus as well as to identify the unit on the bus. The neuron ID can now be read with Climatix Scope from Climatix – LONInitEx or with Lon integration tools.

The elements and connections in the figure are:

position Element / Connection1 LON interface.

Plug connection: Screw/terminal connection.

2 ”Service” pin3 Status display ”BSP” (Board Support Package).4 Status display ”BUS” (bus connections

o.k./bus traffic).5 Plug connection ”Communication extension bus”.6 Climatix controller POL6XX.

Page 31: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 31

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ACCEssiBlE NETwOrk vAriABlE lisT

The following table contains the communication interface definition for Econoet 3.0 LON.Liquid-coupled heat exchanger ECONET®.

The interface description file that must be downloaded into the LON bus communication card is available fromyour ECONET® supplier.

signal type sNvT Type variable name description symbolinput SNVT_object_request nviRequest Object Request

output SNVT_object_status nvoStatus Object Status

Control inputs

input SNVT_lev_percent nviHeatRecCtrl ECONET® heat recovery signal HRC

input SNVT_switch nviEconetStart ECONET® start signal Start

input SNVT_switch nviCoolingStart ECONET® cooling start Cooling

input SNVT_switch nviCoolingRec ECONET® cooling recovery CoolRec

input SNVT_flow nviSupAirFlow Supply air flow from external system GF10.E

input SNVT_flow nviExhAirFlow Exhaust air flow from external system GF10.E

input SNVT_temp_p nviTemp_1 Universal temp 1

input SNVT_temp_p nviTemp_2 Universal temp 2

input SNVT_lev_percent nviPerc_1 Universal percent 1

input SNVT_switch nviSwitch_1 Universal switch 1

input SNVT_flow nviFlow_1 Universal flow 1

Energy

output SNVT_lev_percent nvoHREffEconet ECONET® heat recovery efficiency Meco

output SNVT_lev_percent nvoHREffExtract Extract temp heat recovery efficiency Mext

output SNVT_count_f nvoRecPower Recovered heating/cooling power Erec

output SNVT_count_f nvoAddPower Additional heating/cooling power Eadd

output SNVT_count_f nvoSupPower Supply heating/cooling power Esup

output SNVT_lev_percent nvoRecEff Rec.energy efficiency RecEff

output SNVT_count_f nvoSupHEnergy Cumulative supply heating energy

output SNVT_count_f nvoSupCEnergy Cumulative Supply cooling energy

output SNVT_count_f nvoRecHEnergy Cumulative recovered heating energy

output SNVT_count_f nvoRecCEnergy Cumulative recovered cooling energy

output SNVT_count_f nvoAddHEnergy Cumulative additional heating energy

output SNVT_count_f nvoAddCEnergy Cumulative additional cooling energy

flows

output SNVT_count_f nvoLiqFlowMeas Liquid flow measurement GF41.M

output SNVT_count_f nvoLiqFlowSetp Liquid flow setpoint GF41.SP

output SNVT_flow nvoSupAirFlow Supply airflow measurement GF10.M

output SNVT_flow nvoExhAirFlow Exhaust airflow measurement GF20.M

Temperatures

output SNVT_temp_p nvoAddLiqTemp Liquid temperature to ECONET® GT30

output SNVT_temp_p nvoSupLiqTemp Liquid temperature before supply coil GT40

output SNVT_temp_p nvoFrostLiqTemp Liquid temperature after supply coil GT41

output SNVT_temp_p nvoIceLiqTemp Liquid temperature after exhaust coil GT42

output SNVT_temp_p nvoOutdoorTemp Outdoor air temperature GT00

output SNVT_temp_p nvoSupAirTemp Supply air temperature GT10

output SNVT_temp_p nvoExhAirTemp Exhaust air temperature GT20

output SNVT_temp_p nvoExtAirTemp Extract air temperature Gt21

Page 32: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 32

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

ACCEssiBlE NETwOrk vAriABlE lisT

signal type sNvT Type variable name description symbol Control signals

output SNVT_lev_percent nvoByPassValve By-pass valve control signal SV40.O

output SNVT_lev_percent nvoPump1Ctrl Pump 1 speed control signal FO40.1

output SNVT_switch nvoPump1Start Pump 1 start P40.1.O

output SNVT_switch nvoPump1Ind Pump 1 feedback P40.1.FB

output SNVT_lev_percent nvoPump2Ctrl Pump 2 speed control signal FO40.2

output SNVT_switch nvoPump2Start Pump 2 start P40.2.O

output SNVT_switch nvoPump2Ind Pump 2 feedback P40.2.FB

Alarms

output SNVT_switch nvoPressureAlarm Liquid circuit pressure low PS40

output SNVT_switch nvoFrostAlarm Defrosting alarm GT41LL

output SNVT_switch nvoIceAlarm Ice protection alarm GT42LL

output SNVT_switch nvoPump1Alarm Pump 1 alarm P40.1.AL

output SNVT_switch nvoPump2Alarm Pump 2 alarm P40.2.AL

output SNVT_switch nvoSensorAlarm Temperature sensors Talm

output SNVT_switch nvoAlarmA A-type alarm active AlarmA

standard snvt

output SNVT_state_64 NvoAlarm LON Init Alarms

output SNVT_state nvoUniState1 LON Init Status outputs

output SNVT_state nvoUniState2 LON Init Status inputs

input SNVT_state nviUniState2 LON Init Control inputs

input SNVT_switch nviResetAlarm Reset alarms

input SNVT_time_stamp NviActTime Set realtime clock

output SNVT_switch nvoOpMode Actual operation mode Networkconfig

nciMaxSndTime ”Standardtext”

nciMaxRcvTime ”Standardtext”

nciMinSndTime ”Standardtext”

nciStartupDelay ”Standardtext”

Page 33: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 33

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

BACNET

The purpose of this document is to provide the userswith a quick and simple means of familiarizing them selves with the configuration and use of the BACnet module on Climatix. More information can be found in the following documents:

• Climatix BACnet/IP communication with POL908.00 Integration guide Fläkt Woods 8963GB 2010.07.• For the full specification of BACnet, refer to “ANSI/ ASHRAE Standard 135-2010”.

The BACnet/IP module supports BACnet standard B-AAC (BACnet Advanced Application Controller) and in the future may support other objects such as “Loop Controller” and “Trend”.

Connection and configurationConnect the LON module to the Climatix controller via the internal communication extension bus (plug connection on the left side of the controller) and follow the commissioning instructions as described in the manuals mentioned above.

The elements and connections in the figure are:

position Element / Connection1 Ethernet interface10/100 Mbit (IEEE 802.3U),

RJ45 plug, 8-pin.

2 Status display ”BSP” (Board Support Package).3 Status display ”BUS” (bus connections/bus traffic o.k.).4 Plug connection ”Communication extension bus”.5 Climatix controller POL6XX.

Page 34: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 34

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

BACNET OBjECTs This section describes the BACnet objects available in the specific application. Either the object-name or the object-instance can be used as a BACnet reference.

Object name Object Object type description High limit low limit state text unitSupplyTmp 45150 Analog Input Supply air temp 99 -64 °CExtAirTmp 31214 Analog Input Extract air temp 99 -64 °COutTmp 53218 Analog Input Out door air temp 64 -64 °CExhAirTmp 7422 Analog Input Exhaust air temp 99 -64 °CLiqPumpTmp 34366 Analog Input Liquid pump temp 100 0 °CLiqFrostTmp 26917 Analog Input Liquid frost protection temp 100 -10 °CLiqIceTemp 235 Analog Input Liquid ice protection temp 100 2 °CLiqTemp 33288 Analog Input Liquid temp 100 0 °CAddClgTmp 53543 Analog Input Added Cooling temp 100 0 °CSplyAirFlow 35295 Analog Input Supply air flow in l/s 60000 0 l/sSplyAirFlow_m3 43371 Analog Value Supply air flow in m3/s 6000 -100 m3/sExhAirFlow 61823 Analog Input Exh air flow in l/s 60000 0 l/sExhAirFlow_m3 50620 Analog Value Exh air flow in m3/s 6000 -100 m3/sHrecSignl 53776 Analog Input Hrecovery signal 105 0 %ECONET® 20174 Binary Input ECONET® start Off*On Cooling 42300 Binary Input Cooling Off*On CoolRec 3094 Binary Input Cooling recovery Off*On Pmp1Alm 1236 Binary Input Pump1 alarm OK*Fault Pmp2Alm 40712 Binary Input Pump2 alarm OK*Fault Pmp12Alm 1920 Binary Input Pump 1 and 2 alarm OK*Fault GPAlm 62388 Binary Input Pressure alarm OK*Fault ExhaustHum 37799 Analog Input Room humidity 100 0 %r.H.StartTime 15880 Analog Value Start time minIdleTempSetP 7882 Analog Value Idle temp setpoint °CActOpMode 6080 Multi-StateValue Actual operaton mode Stop* Alarm* Idle* Start* Hrec* Cooling* ClgRec* Hand RunLamNominal 26323 Analog Value Laminar nominal l/sLamCompFac 47745 Analog Value Laminar compensation factor l/sOptCrecLoAir 34352 Analog Value Optimal cooling recovery air flow lower m3/sOptCrecLoLiq 62466 Analog Value Optimal cooling recovery liquid flow lower l/sOptCrecUpAir 58719 Analog Value Optimal cooling recovery air flow upper m3/sOptCrecUpLiq 38765 Analog Value Optimal cooling recovery liquid flow upper l/sOptCoolLoAir 56237 Analog Value Optimal cooling air flow lower mv/sOptCoolLoLiq 43423 Analog Value Optimal cooling liquid flow lower l/sOptCoolUpAir 47298 Analog Value Optimal cooling air flow upper m3/sOptCoolUpLiq 51952 Analog Value Optimal cooling liquid flow upper l/sOptHrecLoAir 33419 Analog Value Optimal heat recovery air flow lower m3/sOptHrecLoLiq 61625 Analog Value Optimal heat recovery liquid flow lower l/sOptHrecUpAir 57828 Analog Value Optimal heat recovery air flow upper m3/sOptHrecUpLiq 37846 Analog Value Optimal heat recovery liquid flow upper l/sIdleFlowSetPoint 57959 Analog Value Idle flow setpoint l/sStartFlowSetPoint 47508 Analog Value Start flow setpoint l/sScaleLiqFlow 3384 Analog Value Scale liquid flow kPaLiqPressLower 49124 Analog Value Liquid pressure lower kPaLiqFlowLower 26447 Analog Value Liquid flow lower l/sLiqPressUpper 22811 Analog Value Liquid pressure upper kPaLiqFlowUpper 33200 Analog Value Liquid flow upper l/sLiquidFlow 22917 Analog Value Liquid flow 20 -50 l/sFrostSpv 977 Analog Value Protect frost controller setpoint °CActualFlowSetp 62390 Analog Value ActualFlowSetp 20 -64 l/sPmp1CmdFB 19948 Binary Input Pump1 CmdFB.FbVal OK*Fault Pump1Cmd 37036 Binary Output Pump1 Cmd.OnOff Off*On

Page 35: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 35

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

BACNET OBjECTs

Object name Object Object type description High limit low limit state text unit Pmp2CmdFB 33353 Binary Input Pump2 CmdFB.FbVal OK*Fault Pump2Cmd 59478 Binary Output Pump2 Cmd.OnOff Off*On Pump1Ind 2123 Binary Output Pump 1 Ind Off*On Pump2Ind 59033 Binary Output Pump 2 Ind Off*On Pmp1Pos 42873 Analog Output Pmp1Pos 100 0 %Pmp2Pos 15525 Analog Output Pmp2Pos 100 0 %IceSpv 16873 Analog Value Protection Ice controller setpoint °CBPValvPos 4598 Analog Output Bypass Valve Pos 100 0 %BPValveO 14788 Binary Output Bypass Valve CmdO Off*On BPValveC 63560 Binary Output Bypass Valve CmdC Off*On EffSupply 34320 Analog Value Efficiency Supply %EffExtract 52679 Analog Value Efficiency Extract %EffEconet 9396 Analog Value Efficiency ECONET® %Efficiency 47690 Analog Output Efficiency 1000 -1000 %SupPower 47696 Analog Value Supply Power 15000 -50 kWTotSupEnHeat 35511 Analog Value Total Supply Energy Heating 15000 -50 kWhRecPower 7836 Analog Value Recvered Power 15000 -50 kWTotSupEnCool 58207 Analog Value Total Supply Energy Cooling 15000 -50 kWhAddPower 39805 Analog Value Added Power 15000 -50 kWTotRecEnHeat 46041 Analog Value Total Recoverd Energy Heating 15000 -50 kWhRecEnergyEff 40871 Analog Value Recoverde Energy Effiency 15000 -50 %TotRecEnCool 55857 Analog Value Tot Recoverd Energy Cooling 15000 -50 kWhCheck 63846 Analog Value Power Check value 15000 -50 kWTotAddEnHeat 37876 Analog Value Total Added Energy Heating 15000 -50 kWhTotAddEnCool 64028 Analog Value Total Added Energy Cooling 15000 -50 kWhAuxTemp 115 Analog Input Aux temp 64 -64 °CExhMaxDewPSp 391 Analog Value Coil Frost Protion Exh Max Dewpoint Setpoint °CExhDEwSpDz 59342 Analog Value Coil Frost Protion Exh Dewpoint Dead zone °CExhDewP 36364 Analog Value Coil Frost Protion Exh DewPoint 64 -64 °CExhAbsH 59428 Analog Value Coil Frost Protion Exh Absolute Humidity 1000 -64 g/kgActDewPSetpoint 52868 Analog Value Coil Frost Protion Actual DewPoint Setpoint 64 -64 °CDewPDmd 16806 Analog Output Coil Frost Protion Controller output 100 0 %FlwContrX1 34860 Analog Value Coil Frost Protion Flow ControllerX1 %FlwContrY1 47901 Analog Value Coil Frost Protion Flow Controller Y1 %FlwContrX2 47183 Analog Value Coil Frost Protion Flow Controller X2 %FlwContrY2 41169 Analog Value Coil Frost Protion Flow Controller Y2 %CoilByPassX1 61522 Analog Value Coil Frost Protion Coil ByPass X1 %CoilByPassX2 49201 Analog Value Coil Frost Protion Coil ByPass X2 %CoilByPassY1 50019 Analog Value Coil Frost Protion Coil ByPass Y1 %CoilByPassY2 62208 Analog Value Coil Frost Protion Coil ByPass Y2 %ExhByPassX1 19899 Analog Value Coil Frost Protion Exh ByPass X1 %ExhByPassX2 32216 Analog Value Coil Frost Protion Exh ByPass X2 %ExhByPassY1 32394 Analog Value Coil Frost Protion Exh ByPass Y1 %ExhByPassY2 20201 Analog Value Coil Frost Protion Exh ByPass Y2 %CoilByPass 49936 Analog Output Coil Frost Protion Coil ByPass 100 0 %FlowDmd 43608 Analog Value Coil Frost Protion Flow Controller 64 -64 %ExhByPassVlvDmd 32606 Analog Value Coil Frost Protion Exh ByPass Valve 64 -64 %AckAlmPls 39130 Multi-State Value Acknowledge Alarm Pulse Off*On CommTest 60516 Binary Value Communication Test Off*On AlmCl0 46769 Multi-State Value AlmCl0 Normal*Alarm AlmCl1 42640 Multi-State Value AlmCl1 Normal*Alarm AlmCl2 38643 Multi-State Value AlmCl2 Normal*Alarm AlmCl3 34514 Multi-State Value AlmCl3 Normal*Alarm

Page 36: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 36

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

BACNET OBjECTs

Object name Object Object type description High limit low limit state text unit AlmOutHigh 5714 Binary Output Alarm High Normal*Alarm AlmOutLow 8035 Binary Output Alarm Low Normal*Alarm Scale 65081 Analog Value Exh Air Flow Scale PaKFact 24939 Analog Value Exh Air Flow K-FactorSuplAirFlowScale 1595 Analog Value Supl Air Flow Scale PaSuplAirFlowKFact 39273 Analog Value Supl Air Flow K-FactorNC11 11 Notification Class NotificationClass11NC21 21 Notification Class NotificationClass21NC31 31 Notification Class NotificationClass31NC41 41 Notification Class NotificationClass41NC12 12 Notification Class NotificationClass12NC22 22 Notification Class NotificationClass22NC32 32 Notification Class NotificationClass32NC42 42 Notification Class NotificationClass42NC13 13 Notification Class NotificationClass13NC23 23 Notification Class NotificationClass23NC33 33 Notification Class NotificationClass33NC43 43 Notification Class NotificationClass43NC14 14 Notification Class NotificationClass14NC24 24 Notification Class NotificationClass24NC34 34 Notification Class NotificationClass34BACnetClientConfig 1 FileBACnetCovConfig 2 FileErrorLog 3 FileHistroyLog 4 FileBACnetEvent 5 FileEnrollmentConfigEDE-File 6 File EDE-File_StateText 7 File BACnetNotification 8 FileClassConfig BACnetDynamic 9 FileTrendlogConfig FrostProtCtlrKp 907 Analog Value Protection Frost Controller Proportional Factor FrostProtCtlrTI 908 Analog Value Protection Frost Controller Integral Factor sFrostProtCtlrTD 909 Analog Value Protection Frost Controller Differential Factor sFcCtlrKp 904 Analog Value FcControl Proportional Factor FcCtlrTI 905 Analog Value FcControl Integral Factor sFcCtlrTD 906 Analog Value FcControl Differential Factor sIceProtCtlrKp 910 Analog Value Protection Ice Controller Proportional Factor IceProtCtlrTI 911 Analog Value Protection Ice Controller Integral Factor sIceProtCtlrTD 912 Analog Value Protection Ice Controller Differential Factor sCoilFrostProtCtlrKp 901 Analog Value Coil Frost Protection Controller Proportional Factor CoilFrostProtTI 902 Analog Value Coil Frost Protection Controller Integral Factor s

CoilFrostCtlrTD 903 Analog Value Coil Frost Protection Controller Differential Factor s

Page 37: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 37

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

BACNET OBjECTs

Object name Object Object type description High limit low limit state text unitTrendObj1 1 Trend Log Trend01

TrendObj2 2 Trend Log Trend02

TrendObj3 3 Trend Log Trend03

TrendObj4 4 Trend Log Trend04

TrendObj5 5 Trend Log Trend05

TrendObj6 6 Trend Log Trend06

TrendObj7 7 Trend Log Trend07

TrendObj8 8 Trend Log Trend08

TrendObj9 9 Trend Log Trend09

TrendObj10 10 Trend Log Trend10

TrendObj11 11 Trend Log Trend11

TrendObj12 12 Trend Log Trend12

TrendObj13 13 Trend Log Trend13

TrendObj14 14 Trend Log Trend14

TrendObj15 15 Trend Log Trend15

TrendObj16 16 Trend Log Trend16

TrendObj17 17 Trend Log Trend17

TrendObj18 18 Trend Log Trend18

TrendObj19 19 Trend Log Trend19

TrendObj20 20 Trend Log Trend20

TrendObj21 21 Trend Log Trend21

TrendObj22 22 Trend Log Trend22

TrendObj23 23 Trend Log Trend23

TrendObj24 24 Trend Log Trend24

TrendObj25 25 Trend Log Trend25

TrendObj26 26 Trend Log Trend26

TrendObj27 27 Trend Log Trend27

TrendObj28 28 Trend Log Trend28

TrendObj29 29 Trend Log Trend29

TrendObj30 30 Trend Log Trend30

Page 38: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 38

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

CONTrOl pANEl

Application macroBasic HvAC This macro is used for direct control of the heat re covery pump speed. Set parameter 9902 to 1 to activate this macro.

lCd display divided into five sections:• Upper left — Identifies the control site, local (LOC) or remote (REM).• Upper right — Identifies the parameter units.• Centre section — varies, but normally shows parameter value, menus or lists Also shows a code for control panel fault.• Lower left — OUTPUT in control mode, or MENU when other operating modes are selected.• Lower right — The motor’s Direction of rotation of the motor, and an indication whether a value can be modified (SET).

EXIT/RESET key — Exit and move tothe closest higher menu level. Do not save changed values.

Up • Scroll up through a menu or list.• Increase the value when a para- meter is selected.• Lower the reference value in the

reference operating mode.

LOC/REM — Switches between local control and remote control off.

MENU/ENTER key — One step down into the menu structure, at the lowest menu level the displayed value is saved as the new setting.

Down -• Scroll down through a menu or list.• Increase the value when a parameter

is selected.• Lower the reference value in the

reference operating mode.

ROTDIRC key — Switches the direction of rotation of the motor.

STOP Stops the unit. START Starts the unit.

Page 39: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 39

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

pArAMETErs

Once function testing is complete, the fault log should be deleted (see page 36).The following parameters must be set:

Group 99: start parameters

COdE NAME sETTiNG sET puMp 1 sET puMp 2

9901 LANGUAGE Swedish English Swedish English

9902 APPLIC MACRO 1 1 1

9905 MOTOR NOM VOLT Acc. to motor rating plate 3 x _______V 3 x _______V

9906 MOTOR NOM CURRENT Acc. to motor rating plate __________A __________A

9907 MOTOR NOM FREQ Acc. to motor rating plate __________Hz __________Hz

9908 MOTOR NOM SPEED Acc. to motor rating plate __________rpm __________rpm

9909 MOTOR NOM POWER Acc. to motor rating plate __________kW __________kW

9910 MOTOR IDENTIFIER 0=OFF 0=OFF 0=OFF

COdE NAME sETTiNG sET puMp 1 sET puMp 2

1105 EXT REF1 MAX Acc. to Max frequencies _______Hz 50Hz _______Hz 50Hz

COdE NAME sETTiNG sET puMp 1 sET puMp 2

2003 MAX CURRENT 1.1xnom.current ____________A ____________A

2007 MIN FREQUENCY 0 Hz 0 Hz 0 Hz

2008 MAX FREQUENCY 50 Hz 50 Hz 50 Hz

Group 11: selection of the reference

Group 20: limits

Page 40: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 40

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

dEsCripTiON Of pArAMETErs sET AT THE fACTOry

pArAMETEr NO. dEsCripTiON

9901 LANGUAGE

Select the display language.

0 = ENGLISH 1= ENGLISH (AM) 2 = DEUTSCH 3 = ITALIANO 4 = ESPA—OL 5 = PORTUGISISKA

6 = NEDERLANDS 7 = FRANCAIS 8 = DANSK 9 = SUOMI 10 = SVENSKA

9902 APPLIC MACRO

Selection of the application macro.

The application macro is combinations of parameter values that configure ACS550 for a

specific purpose.

1= ABB STANDARD 2 = PULSE CONTROL 3 = VARIABLE 4 = MOTORPOT 5 = HAND/AUTO

6 = PID-REGL 7 = PFC-CONTROL 8 = TORQUE-CTRL 12 = PID - CONST. SPEED.

0 = OWN 1 LOAD -1 = OWN 1 SAVE -2 = OWN 2 LOAD -3 = OWN 2 SAVE

9905 MOTOR NOM VOLT

Defines the nominal motor voltage.

Must be equal to the value on the motor rating plate.

ACS550 cannot supply the motor with a voltage higher than the mains voltage.

9906 MOTOR NOM VOLT

Defines the motor’s rated current.

Must be equal to the value on the motor rating plate.

Permitted range: (0.2.2.0) · I2hd (where I2hd is the heavy-duty current of the converter).

9907 MOTOR NOM FREQ

Defines the rated current of the motor.

Range: 10.500 Hz (typically 50 or 60 Hz)

Defines the frequency when the output voltage is equal to MOTOR NOM VOLT.

Field weakening point = Nom freq * supply voltage / Motor Nom volt.

9908 MOTOR NOM SPEED

Defines the rated speed of the motor.

Must be equal to the value on the motor rating plate.

9909 MOTOR NOM POWER

Defines the rated power of the motor.

Must be equal to the value on the motor rating plate.

1105 EXT REF1 MAX

Defines the maximum for external reference 1.

Maximum analogue input signal (as a percentage of the maximum signal in V or A) corresponds to REF1

MAX in _______Hz/rpm.

Parameter 1302 MAXIMUM AI1 or 1305 MAXIMUM AI2 defines the maximum analogue input signal.

Page 41: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 41

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

dEsCripTiON Of pArAMETErs sET AT THE fACTOry

pArAMETEr NO dEsCripTiON

2007 MINIMUM FREQUENCY

Defines the lowest permitted frequency of the motor.

2008 MAXIMUM FREQUENCY

Defines the highest permitted frequency of the motor.

resetting the fault log1. Select parameter 0401.2. Hold down [arrow up] and [arrow down] at the same time.3. Press [SAVE]

The error log is now reset.

Page 42: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 42

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

spArE pArTs lisT

pOs pArT MAkEr TypE NOTE1 Bypass-valve Siemens 005, 008, 009 =>BG

011, 014 =>BL

018, 020 =>BN

023–036 =>CP

041=>DR

054–090,60 =>ES

62–84 =>FT

2 Single pump P40 Grundfos bbb=005 => CR1s-11 Shaft seal: HQQE

bbb=008,009 => CR1-10 Motor:220-240V D / 380-415V Y

bbb=011,014 => CR3-10

bbb=018=> CR3-11

bbb=020 => CR3-12

bbb=023,027 => CR5-9

bbb=032,036 => CR5-10

bbb=041,045 => CR5-12

bbb=050,054,056 => CR10-6

bbb=063,068 => CR10-7

bbb=072 => CR10-8

bb/bbb=079,090,60,62 => CR15-5

bb=64,71,80 => CR20-5

bb=73 => CR20-6

bb=82 => CR34-2

bb=84 => CR35-2

3 Double pumps P40.1 and P40.2 Grundfos bbb=005 => 2 x CR1s-10 Shaft seal: HQQE

bbb=008,009,011,014 => CR1-8 Motors:220-240V D / 380-415V Y

bbb=018,020 => 2 x CR3-8

bbb= 023,027 => 2 x CR3-9

bbb=032,036,041 => 2 x CR5-8

bbb=045,050,054,056 => 2 x CR5-9

bbb/bb=063,068,072,079,090,60 => 2 x CR10-5

bb=62 => 2 x CR10-6

bb=64,71,73,80,82 => 2 x CR15-4

bb=84 => 2 x CR20-4

4 One frequency inverter ABB IP54 bbb=005,008,009 Used for single-pump solutions

bbb=011,014,018,020 => ACH550-02A4-4+B055

bbb=023,027,032,036 => ACH550-03A3-4+B055

bbb=041,045,050,054,056,063,068 => ACH550-05A4-4+B055

bbb=072 => ACH550-06A9-4+B055

bb/bbb=079,090,60,62 => ACH550-08A8-4+B055

bb=64,71,73,80,82 => ACH550-12A-4+B055

bb=84 => ACH550-15A-4+B055

5 Two frquency inverters ABB IP54 bbb=005-027 => 2xACH550-02A4-4+B055 Used for double-pump solutions

bbb=032-056 => 2xACH550-03A3-4+B055

bbb/bb=063-090,60,62 => 2xACH550-05A4-4+B055

bb=64,71,73,80,82 => 2xACH550-08A8-4+B055

bb=84 => 2xACH550-12A-4-+B055

Ordering code: STAZ-74-bbb-c-d-e-f-g-h-i-j-k-l.STYZ-74-bb-c-d-e-f-g-h-i-j-k-l.bbb = eQ-size, bb = eQL-size, k = 7 (Multiple coils)List of items that can be provided as spare parts.

Page 43: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 43

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

spArE pArTs lisT

List of items that can be provided as spare parts.

pOs pArT MAkEr TypE NOTE6 Temperature sensor, GT40 Produal or similar TEV and AT80

7 Temperature sensor, GT41 Produal or similar TEV and AT80

8 Temperature sensor, GT42 Produal or similar TEV and AT80

9 Temperature sensor, GT30 Siemens or similar QAD 26.220 Surface sensor

10 Temperature sensor, GT00 Siemens Ni1000 Duct sensor

11 Temperature sensor, GT10 Siemens Ni1000 Duct sensor

13 Temperature sensor, GT21 Siemens Ni1000 Duct sensor

14 Pressure switch, PS40 Distributor Ahlsell Pressure gauge

NO 100.1+9

15 Pressure sensor, GP41 Huba Control Huba part.nr.

DistributorWexon 692.918001141

Wexon DTP 4-010

16 Valve actuator Johnson 24VAC/5A4GGA

17 Controller Siemens Climatix POL 871.71 + 955.00/STD ECONET® 6.0 application software

only through FWG

18 Controller HMI Siemens Climatix POL 871.71

19 LonTalk communication Modul Siemens Climatix POL 906.00/STD ECONET® 6.0 communicator

image only through FWG

20 Backnet communication module Siemens Climatix POL 908.00/STD

21 Bypass valve SV41 Siemens GQD 161-3A22

22 Actuator

23 Combined Humidity and Siemens QFM2120 Duct sensor

Temperature sensor

List of items that can be provided as spare parts.

Page 44: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 44

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

spArE pArTs lisT

pos 1 plate heat exchanger Maker: swEp fwG ordering code EQrZ-05 and lQrZ-05 Code spare partdd=ff=5 eee=ggg=10 B5TH x 10

dd=ff=5 eee=ggg=14 B5TH x 14

dd=ff=5 eee=ggg=20 B5TH x 20

dd=ff=5 eee=ggg=30 B5TH x 30

dd=ff=8 eee=ggg=10 B8TH x 10

dd=ff=8 eee=ggg=20 B8TH x 20

dd=ff=8 eee=ggg=24 B8TH x 24

dd=ff=8 eee=ggg=30 B8TH x 30

dd=ff=8 eee=ggg=40 B8TH x 40

dd=ff=10 eee=ggg=10 B10TH x 10

dd=ff=10 eee=ggg=20 B10TH x 20

dd=ff=10 eee=ggg=30 B10TH x 30

dd=ff=10 eee=ggg=40 B10TH x 40

dd=ff=10 eee=ggg=50 B10TH x 50

dd=ff=10 eee=ggg=60 B10TH x 60

dd=ff=10 eee=ggg=70 B10TH x 70

dd=ff=15H eee=ggg=16 B15H x 16

dd=ff=15H eee=ggg=20 B15H x 20

dd=ff=15H eee=ggg=30 B15H x 30

dd=ff=15H eee=ggg=40 B15H x 40

dd=ff=16H eee=ggg=20 B16H x 20

dd=ff=16H eee=ggg=30 B16H x 30

dd=ff=16H eee=ggg=40 B16H x 40

dd=ff=16H eee=ggg=50 B16H x 50

dd=ff=16H eee=ggg=60 B16H x 60

dd=ff=16H eee=ggg=70 B16H x 70

dd=ff=16H eee=ggg=80 B16H x 80

dd=ff=16H eee=ggg=90 B16H x 90

dd=ff=16H eee=ggg=100 B16H x 100

dd=ff=16H eee=ggg=120 B16H x 120

dd=ff=25 eee=ggg=10 B25H x 10

dd=ff=25 eee=ggg=20 B25H x 20

dd=ff=25 eee=ggg=30 B25H x 30

dd=ff=25 eee=ggg=40 B25H x 40

dd=ff=25 eee=ggg=50 B25H x 50

dd=ff=25 eee=ggg=60 B25H x 60

dd=ff=25 eee=ggg=70 B25H x 70

dd=ff=25 eee=ggg=80 B25H x 80

dd=ff=28 eee=ggg=36 B28H x 36

dd=ff=28 eee=ggg=46 B28H x 46

dd=ff=28 eee=ggg=56 B28H x 56

dd=ff=28 eee=ggg=66 B28H x 66

dd=ff=28 eee=ggg=76 B28H x 76

dd=ff=28 eee=ggg=86 B28H x 86

dd=ff=28 eee=ggg=96 B28H x 96

dd=ff=28 eee=ggg=106 B28H x 106

dd=ff=28 eee=ggg=116 B28H x 116

dd=ff=28 eee=ggg=126 B28H x 126

dd=ff=28 eee=ggg=136 B28H x 136

dd=ff=35 eee=ggg=40 B35H x 40

dd=ff=35 eee=ggg=50 B35H x 50

dd=ff=35 eee=ggg=60 B35H x 60

dd=ff=35 eee=ggg=70 B35H x 70

dd=ff=35 eee=ggg=80 B35H x 80

dd=ff=35 eee=ggg=90 B35H x 90

dd=ff=35 eee=ggg=100 B35H x 100

dd=ff=46 eee=ggg=30 B120H x 30

dd=ff=46 eee=ggg=40 B120H x 40

dd=ff=46 eee=ggg=50 B120H x 50

dd=ff=46 eee=ggg=60 B120H x 60

dd=ff=46 eee=ggg=70 B120H x 70

dd=ff=46 eee=ggg=80 B120H x 80

dd=ff=46 eee=ggg=90 B120H x 90

dd=ff=46 eee=ggg=100 B120H x 100

dd=ff=46 eee=ggg=110 B120H x 110

dd=ff=46 eee=ggg=120 B120H x 120

dd=ff=46 eee=ggg=130 B120H x 130

dd=ff=46 eee=ggg=140 B120H x 140

dd=ff=56 eee=ggg=60 B56H x 60

dd=ff=56 eee=ggg=80 B56H x 80

dd=ff=56 eee=ggg=100 B56H x 100

dd=ff=56 eee=ggg=120 B56H x 120

dd=ff=56 eee=ggg=140 B56H x 140

dd=ff=56 eee=ggg=160 B56H x 160

dd=ff=56 eee=ggg=180 B56H x 180

dd=ff=70 eee=ggg=120 B427L x 120

dd=ff=70 eee=ggg=140 B427L x 140

dd=ff=70 eee=ggg=160 B427L x 160

dd=ff=70 eee=ggg=200 B427L x 200

dd=ff=72 eee=ggg=120 B427M1 x 120

dd=ff=72 eee=ggg=140 B427M1 x 140

dd=ff=72 eee=ggg=160 B427M1 x 160

dd=ff=72 eee=ggg=180 B427M1 x 180

dd=ff=72 eee=ggg=200 B427M1 x 200

dd=ff=72 eee=ggg=240 B427M1 x 240

Page 45: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 45

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

spArE pArTs lisT

pos 2 Expansion vessel Maker: TA-flex fwG ordering code EQrZ-05 and lQrZ-05

Code Spare part Note

bbb=005-045 TA-FLEX 12L TA-no: 6-00029-012

bbb=050-090, bb=eQL 60 TA-FLEX 25L TA-no: 6-00029-025

bb=eQL 62-84 TA-FLEX 50L TA-no: 6-00029-040 pos 3 shut-off valves Code Spare part bbb=005-090, bb=eQL 60 Ventim VM 4322

bb=eQL 62-84 Ventim VM 3002 pos 4 drain valve, filling valve Code Spare part TA-SAV DN15 pos 5 safety valve Code Spare partTA TA no: 6-00028-240

Page 46: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 46

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

prOduCT COdE(EQrZ-05-BBB-C-dd-EEE-ff-GGG-H, lQrZ-05-BB-C-dd-EEE-ff-GGG-H-i)

size (bbb/bb)eQ 005, 008, 009, 011, 014, 018, 020, 023, 027, 032, 036, 041, 045, 047, 050, 054, 056, 063, 068, 072, 079, 081, 090eQL 60, 62, 64, 71, 73, 80, 82, 84

Heat exchangers for (c)1 = Heating2 = Cooling3 = Heating and cooling4 = Heating, integrated into the pump unit (STAZ-74)5 = Cooling, integrated into the pump unit (STAZ-74)6 = Heating and cooling, integrated into the pump unit (STAZ-74)

size, Heat exchanger (dd) 0 = Without 5 = B5 8 = B810 = B10T15 = B1516 = B1625 = B25T28 = B2835 = B3545 = B4556 = B5670 = B427L72 = B427M

Number of plates, Heat exchanger (eee)size, Cooling exchanger (ff) 0 = Without 5 = B5 8 = B810 = B10T15 = B1516 = B1625 = B25T28 = B2835 = B3545 = B4556 = B5670 = B427L72 = B427M

Number of plates, Cooling exchanger (ggg)Type of pipes (h)1 = High pressure steel, Anti-corrision painted (Normal)2 = Stainless steel

version (i)only for eQl1 = Standard2 = Integrated into the pump unit (STYZ-74)

Page 47: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 47

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

prOduCT COdE(sTAZ-74-BBB-C-d-E-f-G-H-i-j-k)

size AHu (b)005, 008, 009, 011, 014, 018, 020, 023, 027, 032, 036, 041, 045, 047, 050, 054, 056, 063, 068, 072, 079, 081, 090 pump choise (c)1 = Single pump2 = Double pump

functions (d)0 = Standard freezing protection 1 = Advanced freezing protection 2 = ECONET® efficiency and energy calculation

Communication (e)0 = Without3 = LonWorks 7 = Modbus RTU8 = BACnet Electrical connection (f)6 = Plug & play 7 = Standard

power supply and protection class (g)1 = 3x400 VAC, IP21 2 = 3x400 VAC, IP54

Bracket/stand (h)1 = Standard2 = Integrated energy exchanger package (bbb=005-090)

language (i)1 = Swedish2 = German3 = English4 = Finnish

Material (j)1 = Standard2 = Stainless steel

Construction variant (k)5 = ECONET Compact/ver 57 = ECONET Premium/ver 78 = ECONET Standard/ver 8

Page 48: NY 9603 GB 2015 05 20 - VacomAIR · and pre-programmed with specific data for the project. The frequency inverter/inverters is/are mounted on the pump unit and wired to the pump/pumps

Installation and maintenance 48

Fläkt Woods 9603 GB 2015.05.20 Specifications are subject to change without further notice

Liquid-coupLed heat exchanger econet® premium (muLtipLe coiLs)

prOduCT COdE(sTyZ-74-BB-C-d-E-f-G-H-i-j-k-l)

unit size (b)60,62,64,71,73,80,82,84

pump choice (c)1 = Single pump2 = Double pump

functions (d)0 = Standard freezing protection1 = Advanced freezing protection2 = ECONET® efficiency and energy calculation

Communication (e)0 = Without3 = LON7 = Modbus RTU 8 = BACnet 9 = Web pages

Electricity connection (f)6 = Plug and play7 = Standard

protection class (g)1 = IP21 2 = IP54

Output variant EurT (h)1…5Bracket/Stand (i)1 = With2 = Integrated EURZ-05

language (j)1 = Swedish2 = German3 = English4 = Finnish

Construction version (k)5 = ECONET Compact/ver 57 = ECONET Premium/ver 78 = ECONET Standard/ver 8

Connection side of coil (l)1 = Right, standard 2 = Left, standard 3 = Right, stainless steel 4 = Left, stainless steel 5 = None 6 = None, stainless steel