DETAIL
NUMBER DETAIL DESCRIPTION
SERIES 0300
0330-056 CONCRETE EQUIPMENT PADS - 2 OF 2
0330-106 SURFACE TREATMENT OF NEW OPENINGS IN EXISTING CONCRETE
SERIES 0500
0512-056 BEAM/WALL CONNECTION - STEEL
0559-077 PIPE SUPPORT - 2 OF 2
SERIES 2000
2605-005 EQUIPMENT MOUNTING PEDESTAL
2605-006 RAILING MOUNTED EQUIPMENT SUPPORT
2605-012 PEDESTAL MOUNTED DEVICE
2605-013 PEDESTAL MOUNTED DEVICE AT RAILING
2605-013A PEDESTAL MOUNTED DEVICE AT RAILING
2605-017 CONDUIT SUPPORT ON STRUCTURE
2605-100 TERMINATION OF SHIELDED INSTRUMENTATION CABLE - 1 OF 2
2605-100C UNACCEPTABLE METHOD OF GROUNDING INSTRUMENTATION CABLE SHIELD - SHEET 2 OF 2
2605-101A SUBMERSIBLE PUMP/MIXER CONTROL STATION
2605-203 CONDUIT GROUNDING
2605-302 CONDUIT RACKING SYSTEM
2605-308 WATERTIGHT WALL CONDUIT SEAL
SERIES 4000
4027-607 PASSING PIPE WALL PENETRATION WITH MODULAR MECHANICAL SEAL
4091-160 DISSOLVED OXYGEN SENSOR, ALUMINUM COVER INSTALLATION
4091-210 THERMAL MASS FLOW ELEMENT INSTALLATION FOR PROCESS AIR SERVICE
4091-305 PRESSURE CONNECTION INSTALLATION
4091-383 MULTIPLE CASE MOUNTED INSTRUMENTS - STANCHION
CITY OF WILSONVILLE DCN 012AERATION BASIN IMPROVEMENTS PROJECT
DCN 012
STANDARD DETAILS
DETAIL 2 OF 2
0330-056B.dgn 2019\03\25
NTS
0330-056
CONCRETE EQUIPMENT PADS
1.
2.
3.
4.
5.
6.
7.
8.
AB DIA (IN.)
MIN PAD HT (IN.)
1 2
7 10 11 15 18 21 24
1/2 5/8 3/4 7/8 1 1/4 1 3/8 1 1/2 1 3/4
8 1/2 12 1/2 16 1/2
EQUIPMENT BASES SHALL BE INSTALLED LEVEL UNLESS INDICATED OTHERWISE.
4"
1
1.5
6"
MIN
MIN
NOTE:
6"
1
1.5
6"
#5@12" EW T&B
MIN
1'-0"
MIN
NOTE:
2 - #4 @ TOP OF PAD
TYPE H
NOTES:
TYPE J
TYPE G
0330-105
0330-057
MAX
1 1/2" INDICATED BY THE MANUFACTURER AND APPROVED BY THE ENGINEER.
PAD SIZE SHALL BE MINIMUM INDICATED OR AS SHOWN ON THE PLANS OR AS
SHALL BE 8 TIMES THE BOLT DIAMETER.
MOVEMENT OF 1/2" IN ALL HORIZONTAL DIRECTIONS. THE MINIMUM SLEEVE LENGTH
ANCHOR BOLT SLEEVES SHALL BE USED TO PROVIDE MINIMUM ANCHOR BOLT
PAD IS BEING PLACED.
A TEMPLATE OR OTHER ACCEPTABLE MEANS, MATCHING THE BASE PLATE, WHILE
APPROVED BY THE ENGINEER. ANCHOR BOLTS SHALL BE HELD IN POSITION WITH
BOLTS SHALL BE DETERMINED BY THE EQUIPMENT MANUFACTURER AND AS
THE SIZE, NUMBER, TYPE, LOCATION, AND THREAD PROJECTION OF THE ANCHOR
SHALL NOT BE EXPOSED TO VIEW.
THE NON-SHRINK GROUT IS PLACED. WEDGES OR SHIMS THAT ARE LEFT IN PLACE
WEDGES, SHIMS, OR LEVELING NUTS SHALL BE USED TO SUPPORT THE BASE WHILE
4" MINIMUM EDGE DISTANCE IN EACH DIRECTION.
AND APPROVED BY THE ENGINEER. ANCHORS SHALL BE INSTALLED WITH
THAN 3/4" DIAMETER WHEN APPROVED BY THE EQUIPMENT MANUFACTURER
OF CAST-IN-PLACE ANCHOR BOLTS FOR EQUIPMENT ANCHOR BOLTS LESS
AT CONTRACTOR'S OPTION, CONCRETE ANCHORS MAY BE USED IN LIEU
MIN6"
ALL AROUND
EDGE OF SLAB
THICKENED
6"
#5 CONT
CLR FROM TOP SURFACE
#5@12" EW AT 2"
TYP
CHAMFER,
3/4"
GRADE
FINISH
SEE NOTE
ANCHORS,
CONCRETE
EQUIPMENT
ON PLANS
NOTED OTHERWISE
6" MIN, TYP UNLESS
ANCHORS SPECIFIED.
TO PAD IS REQUIRED, USE CONCRETE
WHEN ANCHORAGE OF EQUIPMENT
TYP
CHAMFER,
3/4"
ALL AROUND
EDGE OF SLAB
THICKENED 2 - #5 CONT
GRADE
FINISH
EQUIPMENT
SEE NOTE
ANCHORS,
CONCRETEON PLANS
NOTED OTHERWISE
6" MIN, TYP UNLESS
ANCHORS SPECIFIED.
TO PAD IS REQUIRED, USE CONCRETE
WHEN ANCHORAGE OF EQUIPMENT
W/ MECH
T.O. PAD, COORD
EQUIPMENT BASE
#4@12"
FOR THICKNESS SEE PLANS
SLAB OR SLAB ON GRADE,
EXST OR NEW SUSPENDED
PRIOR TO PLACING PAD
ROUGHEN AND CLEAN
CONSTRUCTION JOINT,
3/4" CHAMFER, TYP
4 1/2" MIN ALL AROUND
NON-SHRINK GROUT
1 1/2" FLUID
3" MIN ALL AROUND
CONCRETE ANCHOR
EMBED PER
@ 12" MAX, 4 MIN,
#5 ADHESIVE DOWEL
AFTER BOLTS ARE ALIGNED. SEE .
ANCHOR BOLT DIAMETER. SLEEVES SHALL BE FILLED WITH NON-SHRINK GROUT
THAN BOLT DIAMETER AND A MAXIMUM INTERNAL DIAMETER 3" GREATER THAN
ANCHOR BOLT SLEEVES SHALL HAVE A MINIMUM INTERNAL DIAMETER 1" GREATER
1'-0"
MIN
MINIMUM SHOWN, USE TYPE "B" EQUIPMENT PAD WITH BLOCKOUT.
EQUIPMENT OR PIPING ELEVATION REQUIRE A PAD HEIGHT LESS THAN THE
KEEP ANCHOR BOLT ABOVE SUPPORTING SLAB (SEE TABLE BELOW). WHERE
HEIGHT OF PADS SHALL BE MINIMUM REQUIRED FOR ANCHOR BOLT CLEARANCE TO
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
0330-106.dgn 2019\04\02
NTS
0330-106
OPENINGS IN EXISTING CONCRETE
NOTES:
WALL OR SLAB
EXST CONCRETE
SEE NOTE 2
SEE NOTE 3
NEW OPNG
3.
2.
1.
NEW OPENING IN EXISTING WALL OR SLAB
PLAN OR ELEVATION
SECTION
EXST REBAR
REMOVED, SEE PLANS
OR SLAB SECTION TO BE
EXST CONCRETE WALL
OR SLAB TO REMAIN
EXST CONCRETE WALL
AND REBAR, SEE NOTE 3
OF EXISTING CONCRETE
NEW SAW CUT SURFACE
SECTION 09 90 00. THE ENTIRE CUT SURFACE MAY BE COATED.
COAT MINIMUM 2" DIAMETER OVER AND AROUND CUT REBAR PER SPECIFICATION
REBAR AND CONCRETE BEYOND OPENING.
CORE DRILL CORNERS TO DIAMETER REQUIRED TO PREVENT OVER CUTTING OF
OPERATION IS COMPLETE.
SUPPORT ADJACENT ELEVATED SLABS AND CUT SLAB SECTION UNTIL CUTTING
SURFACE TREATMENT OF NEW
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
2 1/2"3"
4"
TYP
3"
7" MIN
EMBED
3"3"
4"
TYP
6"
TY
P
3 1/2"
1 1/4"
1 1/4"
TY
P
BE
AM D
EP
TH
S
7" MIN
EMBED
3"3"
6"
3 1/2"
1 1/4"
TY
PT
YP
1 1/4"
TYP
4"
6"
BE
AM D
EP
TH
3"
8"
OR 1
0"
2 1/2"
3"
12"
3"
3"
MIN
6"
3 1/2"
6"
MIN
6"
MIN
6"
MIN
3 1/2"
3 1/2"
6"
MIN
6"
MIN
EMBED
7" MIN
1.3" DIMENSION TYPICAL EXCEPT 2 1/2" FOR 5" BEAMS AND 2" FOR 4" BEAMS.
2.
STEEL BEAM
3.
NOTES:
6"
MA
X
DE
PT
H
BE
AM
TURN, AND LOCK WITH DOUBLE NUT.
SLOTTED HOLES IN BEAM WEB AT ONE END. TIGHTEN NUTS SNUG TIGHT, BACK OFF 1/2
WHERE BOTH ENDS OF BEAM ARE ATTACHED TO A WALL, PROVIDE LONG HORIZONTALLY
SPACING AND EDGE DISTANCE AS SHOWN.
AS REQUIRED TO LOWER ANCHORS TO CLEAR REINFORCING WHILE MAINTAINING
PENETRATING RADAR OR OTHER ACCEPTABLE MEANS. ADD LENGTH TO CLIP ANGLES
INSTALLATION. FIELD LOCATE BEAM REINFORCING PRIOR TO FABRICATION WITH GROUND
DO NOT CUT EXISTING CONCRETE BEAM TOP REINFORCING DURING DRILL-IN ANCHOR
BEAM
STEEL
BEAM
STEEL
NOTE 1
SEE
3",
NO
TE 2
MIN, S
EE
NO
TE 2
MIN, S
EE
NO
TE 2
MIN, S
EE
ANCHORS
STUD TYPE ADHESIVE
W/ 6 - 3/4" DIA SST
L4x3 1/2x3/8x1'-2 1/2"
INSTALLATION
FLANGE FOR BEAM
COPE BOTTOM
IN BEAM WEB)
SLOTTED HOLES
SHORT HORIZONTAL
BOLTS (PROVIDE
3 - 3/4" DIA A325N
WALL OR BEAM
EXISTING CONCRETE
WALL OR BEAM
EXISTING CONCRETE
ANGLE 3"@45°
CLIP BOTTOM OF
ANCHORS
STUD TYPE ADHESIVE
W/ 4 - 3/4" DIA SST
L4x3 1/2x3/8x0'-8 1/2"IN BEAM WEB)
SLOTTED HOLES
SHORT HORIZONTAL
BOLTS (PROVIDE
2 - 3/4" DIA A325N
INSTALLATION
FLANGE FOR BEAM
COPE BOTTOM
LENGTH FOR 4" BEAM)
ANCHORS (0'-2 3/4"
TYPE ADHESIVE
2 - 3/4" DIA SST STUD
L7x4x3/8x0'-3" W/
WALL OR BEAM
CONCRETE
EXISTING
SLOTTED HOLES IN BEAM WEB)
(PROVIDE SHORT HORIZONTAL
2 - 3/4" DIA A325N BOLTS
ANGLE 3"@45°
CLIP BOTTOM OF
2019\04\020512-056.dgn
NTS
0512-056
BEAM / WALL CONNECTION - STEEL
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP IMPROVEMENT DBO
45°
0559-077B.dgn 2019\03\25
NTS
0559-077
EXPANSION SUPPORT - TYPE 'B'
1'-2"
FOR 1/16" +/- GAP AT TOP
WASHER SPACER AT BOLTS
CLAMP, PROVIDE PLATE
BENT PL3/8x5 SST PIPE
TO PIPE CLAMP
TEFLON SHEET BONDED
ALP, TYP
SST TUBE
4x4x1/4
AT 6 1/2" GA, 4" MIN EMBED
DIA SST WEDGE ANCHORS
3/4x9x1'-0" SST PL W/ 4 - 5/8"
3/16
3/16
CONC WALL
DETAIL 2 OF 2
T&BTYP
PIPE SUPPORT
TYP
3'-3"
MA
X1. OMIT UPPER SUPPORT AT SINGLE LINE OF PIPING.
NOTE:
NO
TE 1
TYP OF 47/8" DIA BOLT,
SEE NOTE 1SST PIPE,3" DIA SCH 40S
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
1.
2.
3.
1/2" RADIUS, TYP
NOTE 2
FLOOR OR PLATFORM,
10"
10"
1 1/4", TYP
3'-0"
MA
X
PLANOVERSIZED DEVICES
ELEVATION
NTS
EQUIPMENT MOUNTING PEDESTAL
2605-005
USE WASHERS AND SPLIT-LOCK WASHERS UNDER ALL NUTS.
OR OTHER DEVICES
CONTROL STATION
GROUT
NON-SHRINK
WITH 3#4 REBAR EACH WAY, CENTERED.
FOR YARD LOCATIONS, PROVIDE 2'-0" SQUARE x 6" THICK CONCRETE PAD AT GRADE
INDICATED.
GREATER THAN 2'-0" SQ FT SHALL BE PEDESTAL MOUNTED UNLESS OTHERWISE
CONTROL STATIONS DEVICES AND EQUIPMENT HAVING A FRONTAL AREA NOT
NOTES:
4.
OVERSIZED DEVICES
REQUIRED FOR
1/4" PLATE, SIZE AS
MIN C4x2.16
AS SPECIFIED
COAT DISSIMILAR MATERIALS
MIN3/16
MIN3/16
2605-008
5.
SPECIFIED.
SUBMIT FINAL DESIGN AND CALCULATIONS FOR SUPPORT AND ANCHORAGE AS
DEVICES USE DETAIL .
WHERE EQUIPMENT REQUIRES A LARGE BACKPLATE TO SUPPORT MULTIPLE
1/2" RADIUS, TYP
(18" MAX, WIDTH), ROUND EDGES,
MIN 1/4" MOUNTING PLATE,
MIN 1/2" PLATE
LEVELING NUTS, (TYP OF 4)
OR ANCHOR BOLTS WITH
MIN 1/2" CONCRETE ANCHORS
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
RAILING
ROUND EDGES
DEVICE BOX
4"
5 1/2"
FRONT
NTS
RAILING MOUNTED EQUIPMENT SUPPORT
2605-006
REQUIRED
LENGTH AS
5/16" DIA U-BOLTS,
LOCKWASHERS
NUTS AND
3/16" PLATE
TYP
1/2" RADIUS,
NOTES:
SIDE
CONNECTIONS PER SPECIFICATIONS.
ALUMINUM IN CONTACT WITH STEEL MEMBERS AND
1. AT ALUMINUM RAILING, PROVIDE PROTECTION FOR
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
1.
2.
GRADE
8"
8"
3"
NTS
PEDESTAL MOUNTED DEVICE
2605-012
DEVICE
IF ALUMINUM IS USED
CONCRETE AS SPECIFIED,
CONTACT WITH
PAINT ALUMINUM IN
OR WIDER THAN 18 INCHES SHALL BE SUPPORTED BY 2 CHANNELS.
EQUIPMENT HAVING A FRONTAL AREA GREATER THAN 3 SQUARE FEET
USE WASHER AND SPLIT-LOCK WASHERS UNDER ALL NUTS AND BOLTS.
WALL
CONCRETE
NOTES:
TO CHANNEL
ROUND EDGES, WELD
SIZE AS REQUIRED,
PROVIDE MIN 1/4" PLATE,
MIN 6" CHANNEL
CONCRETE ANCHORS
MIN (2) 5/8" DIA
5'-0"
MA
X
3.
SPECIFIED.
SUBMIT FINAL DESIGN AND CALCULATIONS FOR SUPPORT AND ANCHORAGE AS
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
1/2" RADIUS, TYP
RAILING
CONDUIT CLAMP
8"
8"
3"
5'-0"
MA
X
NTS
PEDESTAL MOUNTED DEVICE AT RAILING
2605-013
DEVICE
EDGES, WELD TO CHANNEL.
AS REQUIRED, ROUND
PROVIDE 1/4" PLATE SIZE
FOR OVERSIZE DEVICE
IF ALUMINUM IS USED
WITH CONCRETE AS SPECIFIED,
PAINT ALUMINUM IN CONTACT
NOTES:
SPLIT LOCK WASHERS UNDER ALL NUTS AND BOLTS.
THAN 18 INCHES SHALL BE SUPPORTED BY TWO CHANNELS. INSTALL RING AND
1. EQUIPMENT HAVING A FRONTAL AREA GREATER THAN 3 SQUARE FEET OR WIDER
2.
SPECIFIED.
SUBMIT FINAL DESIGN AND CALCULATIONS FOR SUPPORT AND ANCHORAGE AS
CONCRETE WALL
MIN C6X10.5 CHANNEL
STEEL.
MOUNTING TO STRUCTURAL
USE MIN (2) 5/8" BOLTS FOR
MIN (2) 5/8" CONCRETE ANCHORS.
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
1/2" RADIUS, TYP
RAILING
CONDUIT CLAMP
8"
8"
3"
5'-0"
MA
X
NTS
PEDESTAL MOUNTED DEVICE AT RAILING
2605-013A
DEVICE
EDGES, WELD TO CHANNEL.
AS REQUIRED, ROUND
PROVIDE 1/4" PLATE SIZE
FOR OVERSIZE DEVICE
IF ALUMINUM IS USED
WITH CONCRETE AS SPECIFIED,
PAINT ALUMINUM IN CONTACT
NOTES:
SPLIT LOCK WASHERS UNDER ALL NUTS AND BOLTS.
THAN 18 INCHES SHALL BE SUPPORTED BY TWO CHANNELS. INSTALL RING AND
1. EQUIPMENT HAVING A FRONTAL AREA GREATER THAN 3 SQUARE FEET OR WIDER
2.
SPECIFIED.
SUBMIT FINAL DESIGN AND CALCULATIONS FOR SUPPORT AND ANCHORAGE AS
CONCRETE WALL
MIN C6X10.5 CHANNEL
STEEL.
MOUNTING TO STRUCTURAL
USE MIN (2) 5/8" BOLTS FOR
MIN (2) 5/8" CONCRETE ANCHORS.
DETAIL
CONNECTION
SUBMERSIBLE
2605-101A FOR
SEE DETAIL
TERMINAL JUNCTION BOX
JACJGDCN12 - NEW DRAWING04/20191
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
CONDUIT
NTS
CONDUIT SUPPORT ON STRUCTURE
2605-017
COLUMN
WALL OR
CLAMP
CONDUIT
NOTES:
MATERIAL REQUIREMENTS.
CLASSIFICATION TABLES FOR
AS SPECIFIED. REFERENCE AREA
MIN 3/8" DIA, CONCRETE ANCHOR,
FOR MATERIAL REQUIREMENTS.
AREA CLASSIFICATION TABLES
FORMED CHANNEL. REFERENCE
1. THIS DETAIL APPLIES ONLY WHEN THERE IS MORE THAN ONE CONDUIT TO SUPPORT.
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
COVER THIS
OUTER JACKET
OUTER JACKET
WRAPPED SHIELD
SHIELD
SHRINK TUBING
SIGNAL LEADS
LUG, TYP
GROUND LEAD
OUTER JACKET
SHRINK TUBING
COVER THIS
SHIELD
NTS
TERMINATION OF SHIELDED INSTRUMENTATION CABLE
2605-100
WIRE
INSULATED
GREEN
SHRINK TUBING
PORTION WITH
CONNECTOR
CRIMPED SPLICE
SHRINK TUBING
PORTION WITH
NOTES:
WITH THIS DETAIL WHERE GROUNDING IS REQUIRED.
1. ALL SHIELDED INSTRUMENTATION CABLE SHALL BE TERMINATED IN ACCORDANCE
SHEET 1 OF 2
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
GROUND LEAD
2605-100c.dgn 2019\03\25
NTS
2605-100C
INSTRUMENTATION CABLE SHIELD
UNACCEPTABLE METHOD OF GROUNDING
SHEET 2 OF 2
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
XXXXX
NTS
2605-101A
SUBMERSIBLE PUMP/MIXER CONTROL STATION
DECKTOP SLAB/
STRAIN RELIEF CORD GRIP
NOTES:
P & ID'S.
1. FOR CONTROL REQUIREMENTS, SEE MOTOR CONTROL DIAGRAMS AND
(2" MIN)
PVC CONDUIT SLEEVE
CORD FITTING
HOOK, MIN 5/8" DIA
FOR CONTINUATION
SEE DETAIL 2605-013A
JACJG DCN12 - NEW DRAWING 04/20191
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
NTS
CONDUIT GROUNDING
2605-203
ENCLOSURE
EQUIPMENT
GROUND WIRE
CONDUIT
METAL
BUSHING
GROUNDING
NOTES:
SHALL BE GROUNDED IN ACCORDANCE WITH THIS DETAIL.
1. THE ENDS OF ALL CONDUITS REQUIRED TO BE GROUNDED BY THE SPECIFICATIONS
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
NOTES:
1.
CONDUIT CLAMPS
NTS
CONDUIT RACKING SYSTEM
2605-302
FLOOR
CATWALK
CHANNEL
CATWALK
CONDUIT INSTALLATION.
CATWALK CHANNEL FOR
PROVIDED AS PART OF
CONDUIT SUPPORT CHANNEL
SPECIFIED IN SECTION 01 88 15.LOCATE AND SIZE SUPPORTS FOR VERTICAL AND LATERAL LOADS AS
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
NTS
WATERTIGHT WALL CONDUIT SEAL
2605-308
STRUCTURE
INSIDE OF
SLEEVE
OVERSIZE
WHERE ACCESSIBLE
GLAND LOCATED
ADJUSTABLE
NOTES:
EXTERIOR WALLS ARE BELOW GRADE.
1. USE WATERTIGHT CONDUIT SEAL WHERE CONDUIT PENETRATIONS OF BUILDING
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
4027-607.dgn 2019\04\02
NTS
4027-607
MODULAR MECHANICAL
SEAL ASSEMBLY WITH
PASSING PIPE
JOINT TO BE WATERTIGHT
CAULK TO PROTECT THREADS,
FILL WITH SILICONE
NOTES:
2.
1.
ASSEMBLY MANUFACTURER
BY MECHANICAL SEAL
DIAMETER RECOMMENDED
WALL CORE DRILL TO
CMU OR PRE-CAST CONCRETE
FOR EXISTING CONCRETE,
WALLDRY INTERIOR
GROUT
NON-SHRINK
FILL WITH
NOTE 2
EXTERIOR WALL
WATER SIDE OR
SST BOLTS AND NUTS
AS SPECIFIED
NEW STRUCTURES, NOTE 1
PIPE SLEEVE WITH SEEP RING,
WHERE PIPE PASSES THROUGH INTERIOR WALL, GROUT IS NOT REQUIRED.
IMMEDIATELY.
CORE DRILLING. IF EMBEDDED ITEMS ARE FOUND, NOTIFY THE ENGINEER
ULTRASONIC TEST OR X-RAY THE AREA FOR EMBEDDED ITEMS BEFORE
WHERE EXISTING CONCRETE STRUCTURE IS TO BE CORE DRILLED,
PASSING PIPE WALL PENETRATION WITH MODULAR
MECHANICAL SEAL
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
4091-160.dgn 2019\03\25
NTS
4091-160
DISSOLVED OXYGEN SENSOR,
ALUMINUM COVER INSTALLATION
NOTES:
1.
2.
INSTRUMENT MANUFACTURER.
BY * ARE SUPPLIED BY
COMPONENTS DESIGNATED
1 1/2" - 12 UNF MALE THREADS
WATER SURFACE
MINIMUM
STEEL PIPE
1 1/2" STAINLESS
1 1/2", SEE NOTE 2
TACK WELD BOLTS
FLOW
6"
PLATE
0.25" ALUMINUM
NUTS AND BOLTS
STAINLESS STEEL
FEMALE THREADS
1 1/2" SST BULKHEAD,
10
ADAPTER ASSEMBLY *
DO SENSOR *
CABLE *
ALUMINUM COVER
AERATION BASIN
(BY COVER SUPPLIER)
8" AL VENT NOZZLE
ELBOW
1 1/2" PVC 90 DEG
1 1/2" PVC PIPE
1 1/2" PVC UNION
OF SENSOR.
ALLOW REMOVAL
EXCESS CABLE TO
COIL AND CLAMP
TRANSMITTER (AIT),
CABLE TO
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
4091-210.dgn 2019\03\25
NTS
4091-210
FE
AS REQUIRED
LENGTH
INSERTION
FITTING
COMPRESSION
TYP
CONDUIT,
ENCLOSURE
TERMINAL
NEMA 4X
FOR PROCESS AIR SERVICE
THERMAL MASS FLOW ELEMENT INSTALLATION
VARIES, SEE SPECS
PROCESS PIPE, SIZE
90° FROM VERTICAL
BETWEEN VERTICAL AND
INSTALLATION SHOULD BE
INSTRUCTIONS
MANUFACTURER'S
INSTALL PER
FLOW DIRECTION ARROW,
AS PROCESS PIPE
SAME MATERIAL
1" THREADOLET
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP DBO
FEMALE NPT BUSHING
SOLVENT WELD BY
REDUCING TEE W/
SOLVENT WELD
PIPE ON PVC
3/4" SCHED 80 PVC
PIPE ON CPVC,
3/4" SCHED 80 CPVC
3/4" V306
CEMENT LINE STEEL PIPE, CAST IRON PIPE AND DUCTILE IRON PIPE
2019\04\024091-305.dgn
NTS
4091-305
PRESSURE CONNECTION INSTALLATION
3/4" SST PIPE
STRAP SADDLE
3/4" TAP, DOUBLE
3/16
MATERIAL AS PIPE
BUSHING SAME
SCREWED TEE WITH
STEEL & SST PIPE 3 1/2" & SMALLER
STEEL & SST PIPE 4" & LARGER
SAME MATERIAL AS PIPE
3/4" THREADOLET
3/4" V306 FOR SST PIPE3/4" V302 FOR STEEL PIPE
3/4" V306 FOR SST PIPE3/4" V302 FOR STEEL PIPE
PVC AND CPVC PIPE
3/4" V335 FOR CPVC PIPE3/4" V330 FOR PVC PIPE
3/4" SST PIPE
3/4" SST PIPE
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP IMPROVEMENT DBO
2019\04\024091-383.dgn
NTS
4091-383
4'-6"
ROUND OFF ALL EXPOSED EDGES AND CORNERS.
3/16
3/16
1.
2.
NOTES:
INS
TR
UM
EN
T
TO S
UIT
INSTRUMENT
APPLICATION
FOR OUTDOOR
REQUIRED
SUN SHIELD
2'-0"
MIN
6"
2'-0" MIN
6" 6" 6"
2"
1 1/2"
OR SMALL PANEL
INSTRUMENT
SIDES AS REQUIRED
TACK WELD TO TOP &
SHEET 10 GA ALUMINUM,
BACK FORMED OF SINGLE
MIN3"
CORNERS
EDGES &
ROUND
FOOT
MOUNTING
INSTRUMENT
ENCLOSURE
INSTRUMENT
MULTIPLE CASE MOUNTED INSTRUMENTS - STANCHION
AS APPLICABLE
UNISTRUT (SHOWN)
SUPPORT ANGLE OR
INSTRUMENT/HOOD
WASHERS, TYP OF 4
WITH SST NUTS AND
3/8" SST STUD BOLT
W/SST BOLTS, NUTS & WASHERS
SECURE INSTRUMENT TO STANCHION
MOUNTING HOLES TO SUIT INSTRUMENT
PAINT ALUMINUM IN CONTACT WITH CONCRETE ACCORDING TO SPECIFICATIONS FOR PAINTING.
3.REFER TO AREA CLASSIFICATION TABLES FOR ANCHOR MATERIAL REQUIREMENTS.
4.ORIENT INSTRUMENT MOUNTING STANCHION SO THE OPEN SIDE OF THE SUN SHIELD FACES NORTH.
BACK PLATESUN SHIELD
14 GA ALUMINUM
SINGLE SHEET
FORMED OF
TOP & SIDES
SUIT INSTRUMENT
AL LENGTH TO
L MIN 2-1/2"x2"x1/4"
2605-008B
ELECTRICAL DETAIL
2 AND HIGHER), SEE
6x3.00 IN SEISMIC ZONES
SEISMIC ZONES 0 AND 1,
CHANNEL (MIN 4x2.16 IN
ALPL MIN 1/2"x12"x12",
CONCRETE ANCHORS
WITH MIN (4) 1/2"
SECURE TO SLAB
GROUT
MIN 1" NONSHRINK
5.SUBMIT FINAL DESIGN AND CALCULATIONS FOR SUPPORT AND ANCHORAGE AS SPECIFIED.
© CH2M HILL
CITY OF WILSONVILLE
Wilsonville, OR 97070
WWTP IMPROVEMENT DBO