Inspection Report: Nucor-Yamato Steel Co., AFIN: 47-00202, Permit #: AR0043117
Inspection Report Page 1 of 6
WATER DIVISION INSPECTION REPORT AFIN: 47-00202 PERMIT #: AR0043117 DATE: 9/21/2015
COUNTY: 47 Mississippi PDS #: 087212 MEDIA: WN
GPS LAT: 35.908677 LONG: -89.775796 LOCATION: Entrance
FACILITY INFORMATION INSPECTION INFORMATION NAME:
Nucor-Yamato Steel Co. LOCATION:
5929 Hwy. 18 East CITY:
Armorel
FACILITY TYPE:
2 - Industrial
INSPECTOR ID#:
52138 S - State
FACILITY EVALUATION RATING:
N
INSPECTION TYPE:
Reconnaissance
DATE(S): ENTRY TIME: EXIT TIME:
9/21/2015 10:55 12:30
PERMIT EFFECTIVE DATE:
12/1/2014
PERMIT EXPIRATION DATE:
11/30/2019
RESPONSIBLE OFFICIAL
NAME: / TITLE
Leon Topalian / GM/VP Nucor Corp COMPANY: Nucor-Yamato Steel Company MAILING ADDRESS:
P.O. Box 1228 CITY, STATE, ZIP: Blytheville AR 72315 PHONE & EXT: / FAX:
870-762-5500 / EMAIL:
FAYETTEVILLE SHALE RELATED: N
FAYETTEVILLE SHALE VIOLATIONS: N INSPECTION PARTICIPANTS
NAME/TITLE/PHONE/FAX/EMAIL/ETC.:
Gary McQuillis/Manager-Steelmaking Technology Kylee Clanton/Environmental Supervisor Tony Hodge/Environmental Engineer Ryan Stringer/Environmental Engineer
CONTACTED DURING INSPECTION: No
AREA EVALUATIONS (S=Satisfactory, M=Marginal, U=Unsatisfactory, N=Not Applicable/Evaluated)
S PERMIT N FLOW MEASUREMENT M STORMWATER N RECORDS/REPORTS N LABORATORY N FACILITY SITE REVIEW M OPERATION & MAINTENANCE N EFFLUENT/RECEIVING WATER N SELF-MONITORING PROGRAM N SAMPLING N SLUDGE HANDLING/DISPOSAL N PRETREATMENT N OTHER:
SUMMARY OF FINDINGS This reconnaissance inspection was performed in response to an accidental release of approximately 700 gallons of sulfuric acid to the facility’s stormwater water pond on 9/19/2015 resulting in a pH of less than 2 SU. Due to a small leak under the effluent weir (Outfall 002) the pH of the receiving stream (Ditch 14A) was impacted extending approximately 3/8ths of a mile downstream. The facility reported the incident immediately after it was discovered and took corrective action as needed to minimize the impact to the receiving stream. A detailed 5-day Follow-up and Non-Compliance report was received by the Department as required by the permit. At the time of the inspection, the facility was pumping water from the stormwater pond to the self-contained slag water system. A temporary berm had been constructed and there was no discharge from Outfall 002. The pH of the stormwater pond was ~2.75 SU at the time of the inspection. The majority of the impacted water in the receiving stream had been pumped to the slag water system. No dead fish were noted in the dewatered portion of the stream, the release was very slow and facility personnel believe fish in the receiving stream were able to move downstream to avoid the low pH water. Live fish were noted in the receiving stream downstream of the impacted area. A recommendation was made that the small areas of pooled water be removed from the impacted portion receiving stream to eliminate the possibility of downstream impacts when discharges resume. The facility agreed and immediately obtained a contractor to deploy vacuum trucks to collect the pooled water.
SeeBra
INS
SUP
e the 5-day Fanch data file
SPECTOR’S S
PERVISOR’S
ollow-up Rees for additio
SIGNATURE:
S SIGNATURE
port and Nononal informat
E:
GENER
n-Complianction.
RAL COMMEN
ce Report su
Bren
-
NTS
bmitted by th
nt L. Walker
-Supervisor N
he permittee
Name
e in the Enfor
DATE: 1
DATE:
rcement
0/16/2015
Inspection Report: Nucor-Yamato Steel Co., AFIN: 47-00202, Permit #: AR0043117
Inspection Report Page 3 of 6
Inspection Report: Nucor-Yamato Steel Co., AFIN: 47-00202, Permit #: AR0043117
Inspection Report Page 4 of 6
Water Division Photographic Evidence Sheet
Location: Nucor-Yamato Steel Photographer: Brent Walker Date: 9/21/2015 Time: 1136 Witness: None Photo #: 1 Description: Sulfuric acid tank and associated dosing equipment.
Photographer: Brent Walker Date: 9/21/2015 Time: 1136 Witness: None Photo #: 2 Description: Overview of stormwater pond.
Inspection Report: Nucor-Yamato Steel Co., AFIN: 47-00202, Permit #: AR0043117
Inspection Report Page 5 of 6
Water Division Photographic Evidence Sheet
Location: Nucor-Yamato Steel Photographer: Brent Walker Date: 9/21/2015 Time: 1136 Witness: None Photo #: 3 Description: Overview of stormwater pond.
Photographer: Brent Walker Date: 9/21/2015 Time: 1136 Witness: None Photo #: 4 Description: Sluice gate at stormwater pond.
Inspection Report: Nucor-Yamato Steel Co., AFIN: 47-00202, Permit #: AR0043117
Inspection Report Page 6 of 6
Water Division Photographic Evidence Sheet
Location: Nucor-Yamato Steel Photographer: Brent Walker Date: 9/21/2015 Time: 1143 Witness: None Photo #: 5 Description: Outfall 002