Upload
vinod-kumar-nehta
View
1.608
Download
57
Tags:
Embed Size (px)
DESCRIPTION
Citation preview
Submitted by: 113007
113013
113022
NOVEC 1230 Fire suppression system
Fire is the rapid oxidation of a material in the chemical process of combustion, releasing heat, light, and various reaction products.
What is Fire?
According to ISI - 2190/1979: Class A, Class B, Class C, Class D fires
• Water
Disadvantages- Conducts electricity, May spread Class B fires, Freezes in cold climates, May carry pollutants as run-off water
• Multi-Purpose dry chemical
Disadvantages-Obscures vision, More irritating than ordinary dry chemical, Nozzle pressure may cause burning liquids to splash
• Regular dry chemical
Disadvantages-Leaves a residue, Obscures vision, Not good on deep-seated Class A fires, Absorbs moisture and may "cake" within container, May be irritating, Nozzle pressure may cause burning liquids to splash
Fire Extinguishing agents
• Carbon di oxide
Disadvantages-Generally >35% concentration by volume required for total flooding system, Toxic to humans at >4% by volume, Dissipates rapidly - allows reflash, Has a cooling/chilling effect on some electronic components
• Halon 1211
Disadvantages-Acutely toxic at >4% by volume (dizziness, impaired coordination and cardiac effects), Must be used at >5% by volume, Toxic decomposition products are generated by fire, Vapor density = 5.7 (collects in pits and low areas), Production restricted per Montreal Protocol due to depletion of ozone layer.
Properties Novec
1230
Halon13
01
HFC-
227ea
HFC-
125
Ozone Depletion
Potential (ODP)1
0.0 12 0.0 0
Global Warming
Potential (GWP)-
IPCC2
1 6900 3500 3400
Atmospheric
Lifetime (years)
0.014 65 33 29.0
Why Novec 1230?
1World Meteorological Organization (WMO) 1998, Model-Derived Method.2Intergovernmental Panel on Climate Change (IPCC) 2007 Method.
Environmentally-sustainable technology
Agent Novec 1230
HFC-125
HFC-227ea
Inert Gas
CO2
Use Concentration1
4.2-5.9% 8.7-12.1%
6.25-8.7%
34.2-40.6%
30-75
NOAEL2 10% 7.5% 9% 43% <5
Safety Margin
69-138% nil% 3-44% 6-26% Lethal at Design Concentration
Margin of human safety surpassing all chemical agents, CO2 and inert gas mixture
1 2008 NFPA 2001 and NFPA 12.2 NOAEL for cardiac sensitization (halocarbons) and effects specific to CO2
• Novec 1230 fluid extinguishes principally via the second
mechanism – removing heat from the fire.
• Upon discharge, Novec 1230 fluid creates a gaseous mixture with
air. This agent/air mixture has a heat capacity much larger than
that of air alone. A higher heat capacity means that this gas
mixture will absorb more energy (heat) for each degree of
temperature change it experiences.
• At a proper system design concentration, the agent/air mixture
absorbs sufficient heat to upset the balance of the fire triangle.
The amount of heat the fire loses to the surroundings is increased
by the presence of the agent. This causes the combustion zone to
cool to the point that the fire extinguishes.
Extinguishing mechanism of Novec 1230 Fluid
Applications• Data Processing Centers
- Computer Rooms
- Data Storage Facilities
• Oil & Gas Petrochemical
Facilities
- Pumping Facilities
- Gas Compressor Rooms
- Offshore Oil Exploration
Rigs
• Telecommunications
- Cellular Sites
- Switching Centers
• Transportation
- Merchant Marine Vessels
- Mass Transit Vehicles
• Commercial and Military
Aviation
- Engine protection
• Recreation
- Pleasure Craft
- Race Cars
• Commercial Marine
- Control and Paint Rooms
- Engine Rooms
- Storage Rooms
• Cultural Facilities
- Museums
- Libraries
- Archives
• Military Systems
- Combat Vehicles
- Marine Engine Rooms
• Medical Facilities
Manufacturing Facilities • Storage Areas
1. Agent Storage Components - Storage components consist of the
cylinder assembly(s), which contains the Novec 1230 fluid, and the
cylinder bracket(s), which holds the cylinder assembly securely in place.
2. Agent Fluid Distribution Components - Distribution components
consist of the discharge nozzles used to introduce the Novec 1230 fluid
into a protected hazard along with the associ ated piping system used to
connect the nozzles to the cylinder assembly.
3. Trim Components - Trim components complete the installation of
the suppression system and consist of connection fittings, pressure
gauge, low-pressure supervisory switch, electric valve actuator, and
manual valve actuator.
System Components
4. Slave Arrangement Components - Slave arrangement components consist of the pneumatic valve actuator(s), actuation check valve, vent check, actuation hose, and fittings required for a multiple cylinder (slave) arrangement.
5. Supplemental Components - Supplemental components include the discharge pressure switch and manifold check valve. They supplement the core equipment or complete a specific multi-cylinder configuration.
6. Control Panel - This device monitors the condition of the electric actuator, detectors, warning devices, cylinder pressure, and any manual release and abort stations. All electric or electronic devices must connect to the control panel in order to function.
7. Detection and Alarm Devices - Detection devices coupled with manual release and abort stations maximize system efficiency while audible and visual alarm devices alert staff of alarm conditions.
System Components(contd.)
Typical Clean agent System Layout
• the library serves as an important resource for history scholars as well as a point of reference for educators, students and interested visitors
• The singular collection consists of rare books, art and photographs and primary source documents etc
• In December 1999, the library suffered an accidental discharge of its fire suppression system, which was originally installed two decades earlier. Fortunately, no loss or significant damage was incurred by the discharge, but the cleanup process was substantial and costly
Case Study
Daughters of the Republic of Texas Library, in San Antonio, Texas
• Upon completion of the feasibility study, the board retained the services of, a premium brand of Tyco Fire Suppression & Building Products. The system chosen as the best option to meet all their specific needs was the Novec 1230 clean agent fire suppression system.
• The Novec 1230 system—installed throughout the Daughters of the Republic of Texas Library, support offices, and library vault—provides continued fire protection of the irreplaceable art, photographs, books, documents, and maps representing the cultural heritage of Texas.
• The Novec 1230 system is ideally suited for the protection of libraries, archives, and document repositories as it can be discharged on books, precious artifacts and other delicate items without causing harm.
• The Novec 1230 system—installed throughout the Daughters of the Republic of Texas Library, support offices, and library vault—provides continued fire protection of the irreplaceable art, photographs, books, documents, and maps representing the cultural heritage of Texas.
Ceiling-mounted agent discharge nozzle and notification device.
Manual release stations
Novec 1230 Fire protection fluid cylinders provide manual back up
Clean agent fire extinguisher
The Novec 1230 system is installed in Library and Store &
Pharmacy of a hospital. It provides continued fire protection of
the costly medicines and irreplaceable photographs, books,
documents. The contents of the library are protected by this
fire suppression system that does not cause damage while still
being environment friendly.
GAS SUPPRESSION SYSTEM CALCULATIONS
Design calculations for Library area
Step 01: Determine hazard volume
Library- 46’ (l) x 32’5” (b) x 10’ (h) = 14950 ft3
Step 02: Determine Volume of solid, permanent structures, or
equipment.
Area of each column = 2.42ft2
Volume = 2.42 x 10 = 24.2ft3
No. of pillars occupying room area = 7
Total Volume = 24.2 x 7 = 169.4 say 170 ft3
Step 03: Calculate reduced volume
Reduced volume = Step 1 ans. – step 2 ans.
= 14950-170 = 14780 ft3~418.52m3
Step 04: Determination of NOVEC 1230 Quantity
Q = V* CF *C Alt
Where, Q- Agent quantity required [kg]
V = Hazard volume [m³]
CF = Flooding factor [kg/m³]
C Alt = Altitude correction factor
Therefore, Q = 418.52x 0.5875x 0.90
= 221.29
Hence required agent quantity = say 225Kg
To check the concentration C reached in the hazard the following formula can be used:
Where,• Q = agent quantity supplied from the system [kg] (at sea level)
• V = hazard volume [m³]
• s = specific vapour volume [m³/kg] = 0.0664 + 0.000274 * T (at sea level)
• T = max. Hazard temperature [°C]
Altitude = 542m
A quantity of 225 kg Novec 1230 has been calculated at an altitude of 542 m.
At sea level this would result in 225 kg / 0.943 = 250 kg Novec
Specific vapour volume(s) for Novec 1230:
Formula: S = 0.0664 + 0.000274 * 40 =0.077
C= (250 x 0.0773 x 100) / 418.52+ (250 x 0.0773)
= 1932.5 / 437.84
= 4.41% (Concentration is less than NOAEL* (10%) – okay for occupied space)
*No Observed Adverse Effect Level
Step 06: Determination of number and size of tanks required
* 75% of max. filling
Tank fill level = actual filling(kg)/max. filling(kg)
1 x 412.7 kg tanks required - filled with 250kg Novec 1230
Nominal
Cylinder
Size
P/N Fill Capacity Empty Weight
Minimum Maximum
Lb kg Lb Kg lb Kg
600 lb 20508 304 137.9 609 276.2 346 157.0
900 lb 20509 455 206.4 910 412.7 471 213.6
1000 lb 20510 561 254.5 1000 453.6 766 346.5
Step 07: Determination of number
Number of nozzles:
Total Volume of hazard area / coverage area of each nozzle
360° Pattern: 418.52/ 292 = 1.43 say 2
180o Pattern: 418.52/ 146 = 2.86 say 3
Step 08: Pipe Size Estimation
Total quantity = 250 kg Novec 1230 (in 10 s) from 2 nozzles
• 12.5 kg/s
• Find the next higher value in "Max. Flow" column
Estimated Pipe size = 50 mm (2”)
Pipe
Type
Pipe
Diame
ter
Intern
al
Diame
ter
Min
Flow
(kg/sec)
Max
Flow
(kg/sec
)
40T 15 mm 15.8 0.454 1.361
40T 20 mm 20.93 0.907 2.495
40T 25 mm 26.64 1.59 3.855
40T 32 mm 35.05 2.72 5.67
40T 40 mm 40.89 4.08 9.072
40T 50
mm
52.5 6.35 13.61
40T 65 mm 62.71 9.072 24.95
40T 80 mm 77.93 13.61 40.82
40T 100
mm
102.25 24.95 56.7
40T 125
mm
128.2 40.82 90.72
40T 150
mm
154.05 54.43 136.1
Step 09: Pressure Venting
Where, A = required free venting area (m²)
Q = Novec 1230 flow (kg/s)
V = specific volume of agent (m³/kg)*
Δp = max. allowable pressure increase (Pa)**
VHOM = specific volume of the homogeneous air / Novec 1230 mixture***
c2 = resistance coefficient for the opening****
* Use 0.072 m³/kg for Novec 1230.
** A value between 100 and 300 Pascal’s should be used if there is no other value offered by the client or clients’ representative.
*** 0.42 is a good average value for 4.2% Novec 1230 concentration.
**** 0.5<c2<1; to simplify the formula, use c2=1
• 250 kg Novec 1230 to be discharged (within 10 seconds).
• Maximum overpressure allowed = 300 Pa.
• A = [(25 x 0.072)/ (√300 x 4.2)] x 1
= 1.8 / 35.5
= 0.05 m2
Therefore, 0.05 m² free venting area is required.
Design Layout of Novec1230 gas suppression system for Library
Design Layout of Novec1230 gas suppression system for Store & Pharmacy
The designing of Novec 1230 gas fire suppression system is achieved based on design criteria provided by one of the leading supplier of the product ‘Tyco’. We are positive that we have fulfilled the design requirements for the selected two areas of the building i.e., library and store & pharmacy of a hospital. Even though the initial cost of the installing Novec 1230 clean agent is high, it has its own advantages over the conventional fire extinguishing systems of protecting the environment and irreplaceable valuable things.
Conclusion
Thank you..!!