(07) Category Page 1 NC State Construction Office Facility Condition Assessment Program Deficiency Information Deficiency No.: 08-M001 Inspector: RWT Agency No.: 6000 Agency Name: UNIV Institution & Building Name: WCU - ALBRIGHT BENTON DORMITORY Complex: 150005 Asset: 00000001-0 Compass: 15000500000001-0 Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3) Correction Priority: 2 Years Deficiency Title: UPGRADE MECHANICAL ROOM EQUIPMENT Component: 1.082 Description of Deficiency: THE STEAM AND HOT WATER EQUIPMENT FOR THE BUILDING, LOCATED IN THE GROUND FLOOR MECHANICAL ROOM, IS DETERIORATED WITH AGE. THE CONTROLS HAVE BECOME OUTDATED AND DO NOT OPERATE RELIABLY OR EFFICIENTLY. THE THERMOSTATIC VALVES HAVE A HIGH FAILURE RATE. THE AIR COMPRESSOR IS OLD AND REQUIRES EXTENSIVE REPAIRS. . Correction Required: UPGRADE THE STEAM AND HOT WATER EQUIPMENT AND CONTROLS. REPLACE THERMOSTATIC VALVES. REPLACE AIR COMPRESSOR. Estimated cost of correction: 155000 Cost estimate status: 1 (plus design fees and contingencies) Preliminary = 1 Final = 2 BLDG. FUNDED BY: 2 General Fund = 1 Revenue Receipts = 2

North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 1NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M001 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ALBRIGHT BENTON DORMITORY

Complex: 150005 Asset: 00000001-0 Compass: 15000500000001-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: UPGRADE MECHANICAL ROOM EQUIPMENT

Component: 1.082

Description of Deficiency: THE STEAM AND HOT WATER EQUIPMENT FOR THE BUILDING, LOCATED IN THE GROUND FLOOR MECHANICAL ROOM, IS DETERIORATED WITH AGE. THE CONTROLS HAVE BECOME OUTDATED AND DO NOT OPERATE RELIABLY OR EFFICIENTLY. THE THERMOSTATIC VALVES HAVE A HIGH FAILURE RATE. THE AIR COMPRESSOR IS OLD AND REQUIRES EXTENSIVE REPAIRS. .

Correction Required: UPGRADE THE STEAM AND HOT WATER EQUIPMENT AND CONTROLS. REPLACE THERMOSTATIC VALVES. REPLACE AIR COMPRESSOR.

Estimated cost of correction: 155000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 2: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 2NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M002 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ALBRIGHT BENTON DORMITORY

Complex: 150005 Asset: 00000001-0 Compass: 15000500000001-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE AIR HANDLING UNIT

Component: 1.082

Description of Deficiency: THE EXISTING AIR HANDLING UNIT SERVING THE DAY ROOM AND CORRIDOR IS ORIGINAL EQUIPMENT, IS DETERIORATED WITH AGE, HAS BECOME CORRODED, AND HAS VIBRATION PROBLEMS.

Correction Required: REPLACE AIR HANDLING UNIT SERVING THE DAY ROOM AND CORRIDOR.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 3: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(14) Category Page 3NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G001 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ALBRIGHT BENTON DORMITORY

Complex: 150005 Asset: 00000001-0 Compass: 15000500000001-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE INTERIOR DOOR HARDWARE IN BENTON HALL

Component: 1.064

Description of Deficiency: SOME INTERIOR DOOR HARDWARE WILL BE NEAR END OF USEFUL LIFE. ONE HALF WERE REPLACED.

Correction Required: REPLACE OR REPAIR DOORS AND HARDWARE AS NEEDED.

Estimated cost of correction: 68000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 4: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 4NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G002 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ALBRIGHT BENTON DORMITORY

Complex: 150005 Asset: 00000001-0 Compass: 15000500000001-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE ROOF (BUILT-UP)

Component: 1.05

Description of Deficiency: BUILT-UP ROOF SYSTEM IS NEAR END OF FUNCTIONAL LIFE AND SHOWS EVIDENCE OF DETERIORATION AT FLASHING.

Correction Required: REMOVE ALL ROOF MATERIALS TO EXPOSE STRUCTURAL DECK AND REPAIR AS REQUIRED. INSTALL NEW FLASHING, EXPANSION JOINTS AND DRAINS AS NEEDED. INSTALL MEMBRANE OVER NEW INSULATION (MINIMUM R-20) AT MINIMUM SLOPE OF ONE QUARTER INCH PER FOOT. COST ESTIMATE ASSUMES HIGH QUALITY BUILT-UP, SINGLE PLY OR OTHER SYSTEM WITH A LIGHT, REFLECTIVE SURFACE.

Estimated cost of correction: 260000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 5: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 5NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G003 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ALBRIGHT BENTON DORMITORY

Complex: 150005 Asset: 00000001-0 Compass: 15000500000001-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: ON SOUTHWEST WALLS, WATER IS PENETRATING WALL BELOW GRADE AND CONTRIBUTING TO DAMAGE OF INTERIOR SURFACES AND FUNGAL GROWTH. SOME LINTELS, CAULK AND MORTAR JOINTS ARE DETERIORATED. CORRIDOR FLOOR HAS SETTLED ABOUT ONE INCH.

Correction Required: EXCAVATE EARTH IN AFFECTED AREAS, INSTALL NEW WATERPROOFING SYSTEM AND DRAINS AND REPLACE ALL DAMAGED MATERIALS. REPAIR LINTELS, CAULK AND REPAINT MORTAR JOINTS AS NEEDED. TO REDUCE MOISTURE THROUGH EXTERIOR WALL, SEAL EXTERIOR WITH SILICON WATERPROOFING AND CONSIDER PAINTING INTERIOR WALLS WITH A LOW PERM RATED PAINT. GROUT INJECTION UNDER FLOOR SLAB MAY CORRECT SETTLEMENT.

Estimated cost of correction: 50000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 6: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 6NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G004 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ALBRIGHT BENTON DORMITORY

Complex: 150005 Asset: 00000001-0 Compass: 15000500000001-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BATHROOMS

Component: 1.062

Description of Deficiency: SOME PANS IN SHOWER FLOORS ARE BEGINNING TO LEAK INTO CEILINGS AND ARE NEAR END OF USEFUL LIFE. SOME WERE REPLACED. BATHROOMS HAVE OLD WORN FINISHES AND FIXTURES.

Correction Required: RENOVATE BATHROOMS TO INCLUDE NEW FINISHES, FIXTURES AND APPURTENANCES. REPLACE / REPAIR SHOWER PANS AND PLUMBING AS NEEDED.

Estimated cost of correction: 320000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 7: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(08) Category Page 7NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M003 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BUCHANAN DORMITORY

Complex: 150005 Asset: 00000002-0 Compass: 15000500000002-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: UPGRADE MECHANICAL ROOM EQUIPMENT

Component: 1.082

Description of Deficiency: THE STEAM AND HOT WATER EQUIPMENT FOR THE BUILDING, LOCATED IN THE GROUND FLOOR MECHANICAL ROOM, IS DETERIORATED WITH AGE. THE CONTROLS HAVE BECOME OUTDATED AND DO NOT OPERATE RELIABLY OR EFFICIENTLY. THE MECHANICAL ROOM DOES NOT HAVE ADEQUATE VENTILATION. CONTROLS ARE NOT CONNECTED TO THE ENERGY MANAGEMENT SYSTEM FOR MONITORING.

Correction Required: UPGRADE THE STEAM AND HOT WATER EQUIPMENT AND CONTROLS. UPDATE CONTROLS TO ADD BUILDING SYSTEMS MONITORING TO THE ENERGY MANAGEMENT SYSTEM.

Estimated cost of correction: 95000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 8: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 8NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E001 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BUCHANAN DORMITORY

Complex: 150005 Asset: 00000002-0 Compass: 15000500000002-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: UPGRADE FIRE ALARM SYSTEM

Component: 1.102

Description of Deficiency: THE EXISTING EDWARDS FIRE ALARM SYSTEM IS ZONED AND PAST ITS LIFE EXPECTANCY. ALSO THERE ARE NO SMOKE DETECTORS IN THE SLEEPING AREAS.

Correction Required: RECOMMEND INSTALLING A BUILDING WIDE ADDRESSABLE FIRE ALARM SYSTEM TO INCLUDE SMOKE DETECTORS IN ALL SLEEPING AREAS.

Estimated cost of correction: 85000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 9: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 9NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E002 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BUCHANAN DORMITORY

Complex: 150005 Asset: 00000002-0 Compass: 15000500000002-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXIT FIXTURES

Component: 1.101

Description of Deficiency: SOME OF THE EXISTING EXIT FIXTURES HAVE NOT BEEN UPGRADED. THEY WASTE ENERGY AND MAINTENANCE LABOR COST.

Correction Required: RECOMMEND UPGRADING THE REMAINING EXIT FIXTURES TO LED TYPE.

Estimated cost of correction: 4000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 10: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 10NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E003 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BUCHANAN DORMITORY

Complex: 150005 Asset: 00000002-0 Compass: 15000500000002-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REWIRE COMPLETELY

Component: 1.091

Description of Deficiency: THE EXISTING WIRE, PANELS, AND SWITCHES ARE REACHING THE END OF THERE SERVICE LIVES.

Correction Required: COMPLETELY REWIRE AND REPLACE EXISTING PANELS AND SWITCHES.

Estimated cost of correction: 45000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 11: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 11NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G005 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BUCHANAN DORMITORY

Complex: 150005 Asset: 00000002-0 Compass: 15000500000002-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: SOME SHELF ANGLES ARE RUSTED AND CAULKING AT SLATE FASCIA IS DETERIORATED.

Correction Required: REPAINT STEEL SHELF ANGLES AND RE-CAULK JOINTS.

Estimated cost of correction: 16000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 12: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(14) Category Page 12NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G006 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BUCHANAN DORMITORY

Complex: 150005 Asset: 00000002-0 Compass: 15000500000002-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE DOORS AND HARDWARE

Component: 1.064

Description of Deficiency: SOME DOORS AND HARDWARE WILL BE NEAR END OF USEFUL LIFE.

Correction Required: REPLACE OR REPAIR DOORS AND HARDWARE AS NEEDED.

Estimated cost of correction: 46000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 13: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 13NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G007 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BUCHANAN DORMITORY

Complex: 150005 Asset: 00000002-0 Compass: 15000500000002-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BATHROOMS

Component: 9.500

Description of Deficiency: BATHROOMS ARE VERY WORN DUE TO AGE AND HEAVY USE.

Correction Required: RENOVATE BATHROOMS TO INCLUDE WALL, CEILING AND FLOOR FINISHES; NEW VANITIES, SINKS, AND LAVATORIES; TOILETS; SHOWERS; NEW FIXTURES AND HARDWARE. REPAIR / REPLACE PLUMBING AS NEEDED.

Estimated cost of correction: 160000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 14: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 14NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G008 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BUCHANAN DORMITORY

Complex: 150005 Asset: 00000002-0 Compass: 15000500000002-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: INSTALL ELEVATOR

Component: 1.070

Description of Deficiency: 4 STORY BUILDING DOES NOT HAVE ELEVATOR

Correction Required: INSTALL ELEVATOR AND TOWER

Estimated cost of correction: 300000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 15: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 15NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G009 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BUCHANAN DORMITORY

Complex: 150005 Asset: 00000002-0 Compass: 15000500000002-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: LIFE SAFETY CODE STUDY - EXITS

Component: 1.061

Description of Deficiency: DOI REPORT INDICATES THAT WALL ADDED BETWEEN ACTIVITY ROOM AND ENTRY CORRIDOR IS NOT FIRE RATED, AND STEPS FROM ACTIVITY ROOM TO THE UPPER AND LOWER CORRIDORS DO NOT MEET CODE. STEPS OPEN DIRECTLY OFF CORRIDORS WITHOUT A PROPER LANDING, AND HAVE NO FIRE DOORS. ALSO, STAIRS DO NOT DISCHARGE DIRECTLY TO OUTSIDE AND DO NOT COMPLY WITH CODE. HANDRAILS ARE TOO SHORT AND OPENINGS TOO LARGE AND ORIGINAL TREADS ARE SLIPPERY AND SOME ARE LOOSE.

Correction Required: PROVIDE A RATED WALL AS REQUIRED. REBUILD THE STEPS TO PROVIDE PROPER LANDINGS AT THE CORRIDORS ALONG WITH FIRE DOORS AS REQUIRED. INSTALL NEW RAILINGS THAT MEET CODE REQUIREMENTS. BECAUSE OF THE COMPLEXITY OF THIS DEFICIENCY, A STUDY TO DETERMINE A DESIGN AND ESTIMATED COST IS RECOMMENDED.

Estimated cost of correction: 98000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 16: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 16NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G010 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MADISON RESIDENCE

Complex: 150005 Asset: 00000003-0 Compass: 15000500000003-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE SLATE ROOF

Component: 1.05

Description of Deficiency: THE SYNTHETIC SLATE SHINGLE ROOF ON/AT CARPORT IS SHOWING SIGNS OF DETERIORATION AND IS AT END OF EXPECTED LIFE. IN ADDITION, BUILT-IN GUTTERS AND DOWNSPOUTS ARE ALSO IN POOR CONDITION. TERRA-COTTA SUB-SURFACE DRAINS ARE LIKELY TO BE IN POOR CONDITION.

Correction Required: REMOVE ALL ROOF MATERIALS TO EXPOSE STRUCTURAL DECK AND REPAIR AS REQUIRED. INSTALL NEW FLASHING, EXPANSION JOINTS AND DRAINS AS NEEDED. INSTALL NEW SLATE SHINGLES TO MATCH MAIN BUILDING. REMOVE AND REPLACE DAMAGED, DETERIORATED AND END OF LIFE GUTTERS SYSTEM AND DOWNSPOUTS. CLEAN (ROD-OUT) SUB-SURFACE DRAINAGE SYSTEM AND REPAIR AND REPLACE AS REQUIRED.

Estimated cost of correction: 85000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 17: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 17NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G011 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MADISON RESIDENCE

Complex: 150005 Asset: 00000003-0 Compass: 15000500000003-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: MORTAR AND CAULK JOINTS ARE SHOWING SIGNS OF DETERIORATION. DECORATIVE ENTRYWAYS AND EAVES ARE ALSO IN POOR CONDITION.

Correction Required: CLEAN WALLS AND RE-CAULK AND RE-POINT MORTAR JOINTS AS NEEDED (BUILDING-WIDE AND AT DECORATIVE ELEMENTS). TO REDUCE MOISTURE THROUGH EXTERIOR WALL, APPLY A SILICON COATING TO MASONRY.

Estimated cost of correction: 175000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 18: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 18NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M004 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MADISON RESIDENCE

Complex: 150005 Asset: 00000003-0 Compass: 15000500000003-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 4 Years

Deficiency Title: REPAIR CONDENSATE DRAINS

Component: 1.082

Description of Deficiency: CONDENSATE DRAINS AT THE FAN COIL UNITS ARE NOT ADEQUATE. MANY DRAINS DO NOT HAVE ENOUGH SLOPE TO PROVIDE GOOD DRAINAGE. WATER BACKS UP FREQUENTLY.

Correction Required: REPAIR CONDENSATE DRAINS.

Estimated cost of correction: 20000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 19: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 19NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M005 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MADISON RESIDENCE

Complex: 150005 Asset: 00000003-0 Compass: 15000500000003-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: PROVIDE EXHAUST FOR MECHANICAL ROOM

Component: 1.082

Description of Deficiency: THE MECHANICAL SPACE USED FOR STEAM SERVICE TO THE BUILDING DOES NOT HAVE ADEQUATE VENTILATION.

Correction Required: PROVIDE PROPER VENTILATION FOR MECHANICAL SPACE.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 20: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 20NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M006 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MOORE CLASSROOM BUILDING

Complex: 150005 Asset: 00000004-0 Compass: 15000500000004-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: UPGRADE MECHANICAL

Component: 1.082

Description of Deficiency: ONE SPECIAL USE AREA IN THE BUILDING REQUIRES 100% OUTDOOR AIR VENTILATION FOR USE AS A CADAVER LAB. THE CHILLER FOR THE BUILDING IS REQUIRED TO RUN TO CONDITION THIS SPACE, RESULTING IN SUBOPTIMAL ENERGY PERFORMANCE. THIS SPECIAL USE AREA COULD BE BETTER SERVED BY A SEPARATE, DEDICATED UNIT FOR COOLING. THE MECHANICAL ROOM HAS INADEQUATE VENTILATION AND EXHAUST. THE PLUMBING FIXTURES ARE OLD AND DAMAGED.

Correction Required: PROVIDE A SEPARATE, DEDICATED SYSTEM TO PROVIDE COOLING FOR THE CADAVER LAB. PROVIDE ADEQUATE VENTILATION FOR THE MECHANICAL ROOM. REPLACE DETERIORATED PLUMBING FIXTURES.

Estimated cost of correction: 125000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 21: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 21NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E004 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MOORE CLASSROOM BUILDING

Complex: 150005 Asset: 00000004-0 Compass: 15000500000004-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE OBSOLETE WIRING

Component: 1.091

Description of Deficiency: THE CIRCUITS CONSIST OF CLOTH COVERED RUBBER INSULATED (TYPE RH) SINGLE CONDUCTOR CABLES. THE RUBBER INSULATION TYPICALLY DRIES OUT TO THE EXTENT THAT IT MAY CRACK AND FALL AWAY. GROUNDING IS THROUGH THE CIRCUIT CONDUIT. THE OBSOLETE WIRING MAY HAVE BEEN INSTALLED 83 YEARS AGO DURING ORIGINAL CONSTRUCTION AND IS POTENTIALLY DANGEROUS.

Correction Required: REPLACE OBSOLETE WIRING AND PROVIDE SUPPLEMENTAL EQUIPMENT GROUNDING CONDUCTORS. A CONDUIT MAY BE REUSED IF IT HAD NOT BEEN DAMAGED.

Estimated cost of correction: 150000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 22: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(21) Category Page 22NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E005 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MOORE CLASSROOM BUILDING

Complex: 150005 Asset: 00000004-0 Compass: 15000500000004-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE OBSOLETE ELECTRICAL PANELS

Component: 1.091

Description of Deficiency: THE SERVICE ENTRANCE AND DISTRIBUTION EQUIPMENT WAS RECENTLY REPLACED; HOWEVER, THE BRANCH CIRCUIT PANELS ARE OBSOLETE. THE WESTINGHOUSE PANELS APPEAR TO HAVE BEEN INSTALLED HAVING BEEN INSTALLED SOME 54 YEARS AGO. THE SQUARE-D BRANCH PANELS APPEAR TO BE ORIGINAL TO THE BUILDING AND MAY BE AS OLD AS 83 YEARS. REPLACEMENT PARTS FOR THESE PANELS ARE ONLY AVAILABLE FROM ELECTRICAL SALVAGE COMPANIES AND ONLY IF THE COMPANIES COINCIDENTLY HAVE THE PARTS IN STOCK. FAILURES OF A BUS OR BREAKER WILL RESULT IN AN EXTENDED ELECTRICAL OUTAGE OF ONE OR MORE CIRCUITS WHILE REPLACEMENT PARTS ARE LOCATED, OR WHILE A REPLACEMENT PANEL IS INSTALLED.

Correction Required: RECOMMEND REPLACING ALL OBSOLETE ELECTRICAL PANELS. ENSURE THAT THE REPLACEMENT PANELS HAVE AT LEAST 20% SPARE BREAKER POSITIONS FOR FUTURE CIRCUITS.

Estimated cost of correction: 40000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 23: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 23NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G012 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MOORE CLASSROOM BUILDING

Complex: 150005 Asset: 00000004-0 Compass: 15000500000004-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR FLOORS

Component: 1.062

Description of Deficiency: MOST FLOORING AND CARPET IS IN POOR CONDITION DUE TO AGE AND HEAVY USE. SOME TILE IS ASBESTOS.

Correction Required: REPLACE / RESTORE FLOORS AND CARPET. ABATE ASBESTOS TILE AND REPLACE WITH VCT. REPLACE WORN CARPET. SOME WORN VCT IS ON TOP OF PLYWOOD WHICH IS ON TOP OF ORIGINAL HARWOOD FLOORS. WHERE POSSIBLE - REMOVE OLD VCT AND PLYWOOD AND RESTORE HARDWOOD FLOORS.

Estimated cost of correction: 130000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 24: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 24NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G013 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MOORE CLASSROOM BUILDING

Complex: 150005 Asset: 00000004-0 Compass: 15000500000004-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: LIFE SAFETY CODE CORRECTIONS

Component: 8.1

Description of Deficiency: DOI REPORT INDICATES THAT ALL WINDOWS WITHIN 10 FEET OF THE EXTERIOR STAIRS ARE REQUIRED TO BE 1/4 INCH WIRE GLASS IN STEEL FRAMES. THE HEIGHT OF HANDRAILS ON EXIT STAIRS DOES NOT COMPLY WITH THE STATE BUILDING CODE. CEILING IN GROUND FLOOR STORAGE INCLUDING ROOM 10 IS NOT FIRE RATED.

Correction Required: REPLACE ALL WINDOWS WITHIN 10 FEET OF EXTERIOR STAIRS WITH 1/4 INCH WIRE GLASS IN STEEL FRAMES. RENOVATE HANDRAIL ON EXIT STAIRS AND INSTALL A FIRE RATED CEILING IN GROUND FLOOR AREAS.

Estimated cost of correction: 9000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 25: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 25NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G014 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MOORE CLASSROOM BUILDING

Complex: 150005 Asset: 00000004-0 Compass: 15000500000004-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: ADA CORRECTIONS

Component: 9.4

Description of Deficiency: BUILDING DOES NOT COMPLY WITH ADA GUIDELINES AND APPLICABLE SECTIONS OF THE STATE BUILDING CODE.

Correction Required: RENOVATE COMPONENTS OF THE BUILDING AS SPECIFIED IN THE CURRENT ADA STUDY. COST ESTIMATE IS BASED ON ESTIMATES IN THE STUDY.

Estimated cost of correction: 85000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 26: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 26NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G015 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MOORE CLASSROOM BUILDING

Complex: 150005 Asset: 00000004-0 Compass: 15000500000004-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR & PAINT EXTERIOR FIRE STAIR

Component: 1.035

Description of Deficiency: EXTERIOR STEEL FIRE STAIR IS RUSTED. HANDRAIL IS ADEQUATE HEIGHT TO COMPLY WITH BUILDING CODE.

Correction Required: CLEAN AND REPAINT EXTERIOR STEEL FIRE STAIR AND RENOVATE HANDRAIL TO MEET BUILDING CODE.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 27: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 27NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G016 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MOORE CLASSROOM BUILDING

Complex: 150005 Asset: 00000004-0 Compass: 15000500000004-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: MORTAR AND CAULKED JOINTS IN THE LIMESTONE CORNICE AND BASE OF WALL, EXTERIOR MASONRY AND RETAINING WALLS HAVE SOME DETERIORATION. LIMESTONE IS DISCOLORED.

Correction Required: REPAIR CAULK AND RE-POINT MORTAR JOINTS OF THE LIMESTONE SECTIONS AND MASONRY WALLS AS NEEDED. TO REDUCE MOISTURE THROUGH EXTERIOR WALL, SEAL EXTERIOR WITH SILANE/SILOXANE WATERPROOFING AND CONSIDER PAINTING INTERIOR WALLS WITH A LOW PERM RATED PAINT.

Estimated cost of correction: 72000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 28: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 28NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G017 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MOORE CLASSROOM BUILDING

Complex: 150005 Asset: 00000004-0 Compass: 15000500000004-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BATHROOMS

Component: 9.500

Description of Deficiency: BATHROOMS ARE IN POOR CONDITION DUE TO AGE AND HEAVY USE. MANY ARE NOT ADA COMPLIANT.

Correction Required: RENOVATE BATHROOMS TO INCLUDE WALL, CEILING AND FLOOR FINISHES; NEW VANITIES, SINKS, AND LAVATORIES; TOILETS; NEW FIXTURES AND HARDWARE. REPAIR / REPLACE PLUMBING AS NEEDED.

Estimated cost of correction: 40000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 29: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 29NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G018 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REYNOLDS DORMITORY

Complex: 150005 Asset: 00000005-0 Compass: 15000500000005-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: COMPLETE BUILDING RENOVATION

Component: 9.1

Description of Deficiency: ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL SYSTEMS IN THIS 55 YEAR OLD RESIDENCE HALL ARE AT THE END OF THEIR EXPECTED USEFUL LIFE. ORIGINAL, METAL, SINGLE GLAZED WINDOWS AND MOST EXTERIOR DOORS AND STOREFRONT SYSTEMS ARE IN POOR OPERATING CONDITION. BUILDING DOES NOT FULLY COMPLY WITH CURRENT LIFE SAFETY AND ADA CODES (BUILDING DOES HAVE AN EXISTING ELEVATOR) HEATING AND VENTILATION SYSTEMS DO NOT COMPLY WITH CURRENT STANDARDS FOR COMFORT AND HEALTH. ROOF IS SCHEDULED TO BE REPLACED SOON.

Correction Required: REMOVE ALL EXISTING INTERIOR SYSTEMS, AND REVISE INTERIOR PLANS AS REQUIRED BY FUNCTIONS AND CODES. REMOVE (ABATE) ALL HAZARDOUS MATERIALS ASSOCIATED WITH RENOVATION. CONSTRUCT NEW INTERIOR SPACES INCLUDING ALL ARCHITECTURAL SYSTEMS AND FINISHES. INSTALL NEW OPERABLE WINDOWS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. REPLACE DAMAGED AND DETERIORATED EXTERIOR DOORS, DOOR FRAMES AND HARDWARE. INSTALL NEW LIGHTING, FIRE ALARMS, ELECTRICAL AND MECHANICAL SERVICE SYSTEMS AS REQUIRED BY CURRENT STANDARDS AND BUILDING CODES. RENOVATE EXTERIOR BUILDING ENTRY WAYS (INCLUDING, DOOR FRAMES, DOORS, HARDWARE AND SURROUNDS). RENOVATE/RECONFIGURE FREIGHT ELEVATOR TO ACCOMMODATE PASSENGERS.

Estimated cost of correction: 12150000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1

Page 30: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

Revenue Receipts = 2

Page 31: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(14) Category Page 30NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G019 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ROBERTSON DORMITORY

Complex: 150005 Asset: 00000006-0 Compass: 15000500000006-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE WOOD WINDOWS

Component: 1.042

Description of Deficiency: ORIGINAL, SINGLE GLAZED, WOOD WINDOWS ARE BEYOND END OF EXPECTED LIFE, IN POOR OPERATING CONDITION, AND DUE TO LEAKAGE OF OUTDOOR AIR, CONTRIBUTE TO HIGH ENERGY COSTS AND DISCOMFORT OF OCCUPANTS. PAINT ON WINDOW SILLS IS PEELING.

Correction Required: INSTALL NEW WINDOWS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. A LOWER COST OPTION IS INTERIOR STORM TYPE WINDOWS. COST ESTIMATE IS FOR NEW WINDOWS. REPAINT WINDOW SILLS.

Estimated cost of correction: 170000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 32: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 31NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G020 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ROBERTSON DORMITORY

Complex: 150005 Asset: 00000006-0 Compass: 15000500000006-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: LIFE SAFETY CODE - DOORS AND STAIR TREADS

Component: 8.1

Description of Deficiency: THE EXISTING, WOOD CORRIDOR DOOR FRAMES AND DOORS, AND HANDRAILS IN STAIRS DO NOT COMPLY WITH STATE BUILDING CODE. ALSO, SOME STAIR TREADS ARE NEAR END OF LIFE. EXIT DOOR THRESHOLDS ARE A TRIP HAZARD.

Correction Required: INSTALL NEW STEEL FRAMES AND WOOD DOORS WITH HARDWARE. REPLACE STAIR TREADS, THRESHOLDS AND HANDRAILS IN STAIRS.

Estimated cost of correction: 115000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 33: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 32NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G021 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ROBERTSON DORMITORY

Complex: 150005 Asset: 00000006-0 Compass: 15000500000006-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: ADA CORRECTIONS

Component: 9.4

Description of Deficiency: BUILDING DOES NOT COMPLY WITH ADA GUIDELINES AND APPLICABLE SECTIONS OF THE STATE BUILDING CODE.

Correction Required: RENOVATE COMPONENTS OF THE BUILDING AS SPECIFIED IN THE CURRENT ADA STUDY. COST ESTIMATE IS BASED ON ESTIMATES IN THE STUDY.

Estimated cost of correction: 183000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 34: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 33NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G022 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ROBERTSON DORMITORY

Complex: 150005 Asset: 00000006-0 Compass: 15000500000006-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: MORTAR AND CAULKED JOINTS IN EXTERIOR MASONRY HAVE SOME DETERIORATION. MOISTURE PENETRATES WALLS.

Correction Required: REPAIR CAULK AND RE-POINT MORTAR JOINTS OF MASONRY WALLS AS NEEDED. TO REDUCE MOISTURE THROUGH EXTERIOR WALL, SEAL EXTERIOR WITH SILANE/SILOXANE WATERPROOFING AND CONSIDER PAINTING INTERIOR WALLS WITH A LOW PERM RATED PAINT.

Estimated cost of correction: 48000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 35: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 34NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E006 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ROBERTSON DORMITORY

Complex: 150005 Asset: 00000006-0 Compass: 15000500000006-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXIT LIGHTS

Component: 1.101

Description of Deficiency: THE EXIT LIGHTING IN THIS BUILDING DOES NOT MEET CODE AND DOI STANDARDS.

Correction Required: INSTALL EXIT LIGHTING IN THIS BUILDING. ENSURE THAT THE NEW EXIT LIGHTS ARE LED AND THAT ALL LIGHTING CODE REQUIREMENTS ARE MET.

Estimated cost of correction: 6000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 36: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 35NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G023 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ROBERTSON DORMITORY

Complex: 150005 Asset: 00000006-0 Compass: 15000500000006-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: RENOVATE INTERIOR

Component: 9.100

Description of Deficiency: ROOM, FINISHES, CABINETS AND BATHROOMS ARE ALL VERY WORN DUE TO AGE AND HEAVY USE.

Correction Required: RENOVATE BUILDING INTERIOR AND REPLACE WINDOWS. REPLACE WINDOWS WITH DBL PANE CLAD LOW MAINTENANCE UNITS. REPLACE ALL INTERIOR HALL CARPET. IF ORIGINAL FLOORS ARE TERRAZZO, REMOVE CARPET AND RESTORE TERRAZZO. RENOVATE APARTMENTS TO INCLUDE NEW KITCHEN CABINETS, SINKS, PLUMBING, APPLIANCES AND FIXTURES. RENOVATE BATHROOMS TO INCLUDE NEW LAVATORIES, SINKS, CABINETRY, FIXTURES, SHOWERS AND APPURTENANCES. REPAIR PLUMBING AS NEEDED. REPLACE APARTMENT CARPET AND VCT. INVESTIGATE RESTORATION OF ORIGINAL FLOORING IF TERRAZZO OR HARDWOOD.

Estimated cost of correction: 1300000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 37: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 36NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M007 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ROBERTSON DORMITORY

Complex: 150005 Asset: 00000006-0 Compass: 15000500000006-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 4 Years

Deficiency Title: REPLACE HVAC CONTROLS

Component: 1.082

Description of Deficiency: THE HVAC CONTROLS SYSTEM IS OLD AND OBSOLETE. REPLACEMENT PARTS ARE NOT AVAILABLE. ENERGY CONSERVATION FEATURES ARE LIMITED.

Correction Required: UPGRADE THE HVAC CONTROLS SYSTEM TO PROVIDE A RELIABLE, ENERGY EFFICIENT SYSTEM.

Estimated cost of correction: 60000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 38: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(21) Category Page 37NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E007 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HUNTER #9 & ADDITION

Complex: 150005 Asset: 00000009-0 Compass: 15000500000009-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE OBSOLETE ELECTRICAL PANELS

Component: 1.091

Description of Deficiency: AN ITE BRAND PANEL LABELED "W", AND THE WESTINGHOUSE TYPE B10B PANELS, ARE OBSOLETE; THE WESTINGHOUSE PANELS HAD BEEN INSTALLED SOME 54 YEARS AGO. REPLACEMENT PARTS ARE ONLY AVAILABLE FROM ELECTRICAL SALVAGE COMPANIES AND ONLY IF THE COMPANIES COINCIDENTLY HAVE THE PARTS IN STOCK. FAILURES OF A BUS OR BREAKER WILL RESULT IN AN EXTENDED ELECTRICAL OUTAGE OF ONE OR MORE CIRCUITS WHILE REPLACEMENT PARTS ARE LOCATED, OR WHILE A REPLACEMENT PANEL IS INSTALLED. THE BREAKER SPACE IN ITE PANEL "W" HAD LONG BEEN DEPLETED. CIRCUITS IN THE PANEL ARE DOUBLED AND TRIPLED ON INDIVIDUAL BREAKERS IN VIOLATION OF NATIONAL ELECTRICAL CODE.

Correction Required: RECOMMEND REPLACING ALL OBSOLETE ELECTRICAL PANELS. ENSURE THAT THE REPLACEMENT PANELS HAVE AT LEAST 20% SPARE BREAKER POSITIONS FOR FUTURE CIRCUITS.

Estimated cost of correction: 24000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 39: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(22) Category Page 38NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E008 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HUNTER #9 & ADDITION

Complex: 150005 Asset: 00000009-0 Compass: 15000500000009-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE OBSOLETE LIGHT FIXTURES

Component: 1.092

Description of Deficiency: LIGHTING IN THE ORIGINAL BUILDING IS OBSOLETE IN THAT REPLACEMENT PARTS ARE DIFFICULT TO OBTAIN, THE QUALITY OF LIGHT IS INADEQUATE FOR THE USE OF A SPACE, AND THE LIGHTING SYSTEM AND DOES NOT MEET ENERGY CODE. BALLASTS OF FIXTURES THAT ARE ORIGINAL TO THE BUILDING ARE LIKELY TO CONTAIN PCBS.

Correction Required: RECOMMEND A DESIGNED RENOVATION OF LIGHTING TO COMPLY WITH NC BUILDING CODE AND NC ENERGY CODE, AND TO FOLLOW RECOMMENDATIONS OF THE ILLUMINATING ENGINEERING SOCIETY (IES) FOR THE SPECIFIC APPLICATIONS OF THE SPACES.

Estimated cost of correction: 100000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 40: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 39NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E009 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HUNTER #9 & ADDITION

Complex: 150005 Asset: 00000009-0 Compass: 15000500000009-0

Deficiency Type: 2 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPAIR FLOOR RECEPTACLE OUTLETS

Component: 1.091

Description of Deficiency: A MAJORITY OF THE SOME EIGHTY (80) COVERS TO FLOOR RECEPTACLE OUTLETS IN THE STACKS ARE DAMAGED AND REQUIRE REPLACEMENT. THE CONDITION IS LIKELY THE RESULT OF RESIDENTIAL GRADE ASSEMBLIES HAVING BEEN PROVIDED DURING CONSTRUCTION.

Correction Required: REPLACE ALL FLOOR RECEPTACLE COVERS AND, AS NECESSARY, ASSOCIATED RECEPTACLES. ENSURE THAT RECEPTACLE OUTLET COVERS ARE COMMERCIAL GRADE.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 41: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 40NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E010 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HUNTER #9 & ADDITION

Complex: 150005 Asset: 00000009-0 Compass: 15000500000009-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE OBSOLETE WIRING

Component: 1.091

Description of Deficiency: THE BRANCH CIRCUITS IN THE ORIGINAL BUILDING OF CLOTH COVERED RUBBER INSULATED (TYPE RH) SINGLE CONDUCTOR CABLES. THE RUBBER INSULATION TYPICALLY DRIES OUT TO THE EXTENT THAT IT MAY CRACK AND FALL AWAY. GROUNDING IS THROUGH THE CIRCUIT CONDUIT. THE OBSOLETE WIRING METHOD WAS INSTALLED 54 YEARS AGO AND IS POTENTIALLY DANGEROUS.

Correction Required: REPLACE OBSOLETE WIRING AND PROVIDE SUPPLEMENTAL EQUIPMENT GROUNDING CONDUCTORS. A CONDUIT MAY BE REUSED IF IT HAD NOT BEEN DAMAGED.

Estimated cost of correction: 55000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 42: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 41NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G024 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HUNTER #9 & ADDITION

Complex: 150005 Asset: 00000009-0 Compass: 15000500000009-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: MOISTURE IS PENETRATING THE BASEMENT WALL (SOUTHEAST CORNER AT M.E. ROOM) AND THEN INTRODUCED INTO OCCUPIED SPACES. PLASTER WALL AND TILE FLOOR APPEARS TO HAVE BEEN DAMAGED.

Correction Required: FOUNDATION WALLS SHOULD BE EXCAVATED (AT SOUTHEAST CORNER), REPAIRED AND WATERPROOFED. FOUNDATION DRAINAGE SHOULD BE IMPROVED. REPAIR DAMAGED INTERIOR FINISHES.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 43: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 42NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G025 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HUNTER #9 & ADDITION

Complex: 150005 Asset: 00000009-0 Compass: 15000500000009-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: COMPLETE BUILDING RENOVATION (PARTS OF BUILDING)

Component: 6.1

Description of Deficiency: PORTIONS OF LIBRARY ARE ORIGINAL CONSTRUCTION AND DO NOT COMPLY WITH CURRENT BUILDING CODES AND ADA GUIDELINES. SOME AREAS HAVE BEEN NOTED IN ANNUAL DOI REPORT. WINDOWS AND STOREFRONT SYSTEMS AS WELL AS MASONRY BRIDGE WAY ARE AT END OF LIFE.

Correction Required: REMOVE ALL EXISTING DETERIORATED INTERIOR SYSTEMS AND REVISE INTERIOR PLANS AS REQUIRED BY FUNCTIONS AND CODES. REMOVE (ABATE) ANY HAZARDOUS MATERIALS ASSOCIATED WITH RENOVATION. CONSTRUCT NEW INTERIOR SPACES INCLUDING ALL ARCHITECTURAL SYSTEMS AND FINISHES. INSTALL NEW OPERABLE WINDOWS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. INSTALL NEW LIGHTING, FIRE ALARMS, ELECTRICAL AND MECHANICAL SERVICE SYSTEMS AS REQUIRED BY CURRENT STANDARDS AND BUILDING CODES. RENOVATE EXTERIOR BUILDING ENVELOPE AND MASONRY BRIDGE WAY.

Estimated cost of correction: 13115000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 44: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 43NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E011 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HUNTER #9 & ADDITION

Complex: 150005 Asset: 00000009-0 Compass: 15000500000009-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE EMERGENCY GENERATOR

Component: 1.101

Description of Deficiency: THE ONAN BRAND EMERGENCY GENERATOR SYSTEM IS OBSOLETE AND PAST ITS USEFUL LIFE. THE FUEL STORAGE TANK IS BURIED WITHOUT SPILL PREVENTION OR LEAK DETECTION/CONTAINMENT.

Correction Required: REPLACE THE EMERGENCY GENERATOR SYSTEM TO INCLUDE A GENERATOR, AN AUTOMATIC TRANSFER SWITCH, AND A CODE COMPLIANT FUEL STORAGE SYSTEM. IF THE REPLACEMENT GENERATOR IS TO BE INSTALLED OUTSIDE THE BUILDING IT SHOULD BE PROVIDED WITH A SOUND ATTENUATED STORM WEATHER RESISTANT ENCLOSURE.

Estimated cost of correction: 20000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 45: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 44NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M008 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HUNTER #9 & ADDITION

Complex: 150005 Asset: 00000009-0 Compass: 15000500000009-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: HVAC UPGRADE

Component: 1.082

Description of Deficiency: THE HVAC CONTROLS SYSTEM IS AGED AND OBSOLETE, AND ENERGY CONSERVATION FEATURES ARE LIMITED. ONLY THE CHILLER CONTROLS HAVE BEEN UPGRADED IN RECENT YEARS TO DDC. BOTH CONDENSER WATER PUMPS ARE 27 YEARS OLD. STEAM PIPING AND VALVES ARE DIFFICULT TO REACH BECAUSE OF THEIR LOCATION NEAR THE CEILINGS IN THE STEAM ROOMS. THE AIR HANDLERS IN THE NEW AND OLD SECTIONS OF HUNTER LIBRARY ARE IN GOOD CONDITION, BUT ONLY 5 OF THE 18 AIR HANDLERS HAVE HUMIDIFICATION CAPABILITY.

Correction Required: UPGRADE THE HVAC CONTROLS SYSTEM TO PROVIDE A RELIABLE, ENERGY EFFICIENT SYSTEM. THE NEW CONTROL SYSTEM SHOULD BE CONNECTED TO THE CAMPUS ENERGY MANAGEMENT SYSTEM. PROVIDE PROPER HVAC ZONING. PROVIDE CATWALKS IN THE STEAM ROOMS OR LOWER THE STEAM PIPING AND VALVES TO PROVIDE MAINTENANCE ACCESS.

Estimated cost of correction: 800000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 46: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 45NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M009 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HUNTER #9 & ADDITION

Complex: 150005 Asset: 00000009-0 Compass: 15000500000009-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: PLUMBING FIXTURE UPGRADE

Component: 1.081

Description of Deficiency: PLUMBING FIXTURES IN SOME PORTIONS OF HUNTER LIBRARY ARE AGING AND CORRODED.

Correction Required: REPLACE ALL CORRODED FIXTURES IN HUNTER LIBRARY.

Estimated cost of correction: 50000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 47: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 46NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M010 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HUNTER #9 & ADDITION

Complex: 150005 Asset: 00000009-0 Compass: 15000500000009-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: PROVIDE FIRE SPRINKLER SYSTEM

Component: 1.083

Description of Deficiency: HUNTER LIBRARY AND ADDITION HAVE NO SPRINKLER SYSTEM FOR FIRE PROTECTION.

Correction Required: PROVIDE A FIRE PROTECTION SPRINKLER SYSTEM FOR HUNTER LIBRARY AND ADDITION.

Estimated cost of correction: 1000000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 48: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 47NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M011 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STILLWELL SCIENCE BUILDING

Complex: 150005 Asset: 00000010-0 Compass: 15000500000010-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: UPGRADE VENTILATION CONTROL SYSTEM

Component: 1.082

Description of Deficiency: THE STILLWELL GREENHOUSE VENTS ARE CONTROLLED BY AN ANTIQUATED VACUUM TUBE CONTROLLER WITH MECHANICAL OPEN/CLOSE DEVICES.

Correction Required: PROVIDE A MODERN CONTROL SYSTEM FOR THE STILLWELL GREENHOUSE VENTS.

Estimated cost of correction: 15000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 49: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(14) Category Page 48NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G026 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STILLWELL SCIENCE BUILDING

Complex: 150005 Asset: 00000010-0 Compass: 15000500000010-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE EXTERIOR DOORS

Component: 1.043

Description of Deficiency: SOME EXTERIOR DOORS AND HARDWARE (HOLLOW METAL FRAMES) ARE AT/NEAR END OF USEFUL LIFE.

Correction Required: REMOVE AND REPLACE DAMAGED OR DETERIORATED EXTERIOR DOORS AND FRAMES.

Estimated cost of correction: 105000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 50: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 49NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M012 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STILLWELL SCIENCE BUILDING

Complex: 150005 Asset: 00000010-0 Compass: 15000500000010-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: FAN NOISE CORRECTION

Component: 1.082

Description of Deficiency: THE NOISE FROM THE FUME HOODS AND LAB EXHAUST DUCTWORK IS VERY HIGH IN LAB ROOM 419. THIS NOISE INTERFERES WITH EFFECTIVE TEACHING IN THIS ROOM.

Correction Required: INVESTIGATE AND ELIMINATE THE SOURCE OF THE EXCESSIVE NOISE IN LAB ROOM 419. EXHAUST FAN EF-2A IN THE PENTHOUSE MECHANICAL ROOM MAY NEED REPLACEMENT. ALIGNMENT OF THE EXHAUST DUCTWORK AND CANVAS JOINTS MAY BE AN ISSUE.

Estimated cost of correction: 30000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 51: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 50NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G027 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STILLWELL SCIENCE BUILDING

Complex: 150005 Asset: 00000010-0 Compass: 15000500000010-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: SOME CAULK/MORTAR JOINTS AT MASONRY WINDOW SILLS ARE DETERIORATED. IN GENERAL, MASONRY BUILDING ENVELOPE IS SHOWING SIGNS OF DETERIORATION. BRICK IS BROKEN AT/ABOVE WINDOW AT NORTHEAST CORNER AND GROUT AT GLASS BLOCK IS ALSO IN POOR CONDITION.

Correction Required: REPLACE DETERIORATED CAULK/MORTAR AT MASONRY WINDOW SILL JOINTS. REPAIR AND WATERPROOF EXTERIOR BUILDING ENVELOPE.

Estimated cost of correction: 500000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 52: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 51NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E012 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STILLWELL SCIENCE BUILDING

Complex: 150005 Asset: 00000010-0 Compass: 15000500000010-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE ELECTRICAL PANEL

Component: 1.091

Description of Deficiency: THE EXISTING PANEL IS OLD AND REACHING THE END OF IT'S SERVICE LIFE.

Correction Required: RECOMMEND REPLACING THE OBSOLETE PANEL, WITH A PANEL THAT MEETS NEC REQUIREMENTS.

Estimated cost of correction: 5000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 53: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 52NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E013 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STILLWELL SCIENCE BUILDING

Complex: 150005 Asset: 00000010-0 Compass: 15000500000010-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE THEATER LIGHTING

Component: 1.092

Description of Deficiency: THE EXISTING LIGHTS ARE OLD AND ARE NOT ENERGY FRIENDLY

Correction Required: INSTALL ENERGY SAVING LIGHTS

Estimated cost of correction: 45000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 54: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 53NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M013 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HOEY

Complex: 150005 Asset: 00000012-0 Compass: 15000500000012-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: PROVIDE COMPLETE SPRINKLER SYSTEM

Component: 1.083

Description of Deficiency: ONLY TWO STORAGE ROOMS AT HOEY AUDITORIUM ARE PROTECTED BY FIRE SPRINKLERS.

Correction Required: PROVIDE A COMPLETE FIRE SPRINKLER SYSTEM FOR THE ENTIRE HOEY AUDITORIUM BUILDING.

Estimated cost of correction: 600000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 55: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 54NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G028 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HOEY

Complex: 150005 Asset: 00000012-0 Compass: 15000500000012-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: MISCELLANEOUS RENOVATION

Component: 9.5

Description of Deficiency: AT AUDITORIUM AND LOBBY OF BUILDING, INTERIOR FINISHES, FLOOR COVERING (CARPET, RUNNERS) AND FLOOR FINISHES (9 X 9 FLOOR TILE) AT LOWER LEVEL ARE SHOWING SIGNS OF DETERIORATION AND ARE NEARING END OF EXPECTED LIFE. ASBESTOS MAY BE PRESENT AT FLOOR TILE.

Correction Required: REPLACE DAMAGED AND DETERIORATED INTERIOR AND FLOOR FINISHES THROUGHOUT BUILDING. PRESENCE OF ASBESTOS CONTAINING FLOORING MATERIALS MAY INCREASE COST OF PROJECT ACCORDINGLY.

Estimated cost of correction: 275000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 56: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 55NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G029 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HOEY

Complex: 150005 Asset: 00000012-0 Compass: 15000500000012-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: PORTIONS OF EXTERIOR MASONRY APPEAR TO BE IN POOR CONDITION. SOME MORTAR AND CAULK JOINTS ARE DETERIORATED.

Correction Required: CLEAN WALLS (ABOVE GRADE), RE-CAULK AND RE-POINT MORTAR JOINTS AS NEEDED. TO REDUCE MOISTURE MOVING THROUGH EXTERIOR WALL, APPLY A SILICON COATING TO EXTERIOR.

Estimated cost of correction: 225000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 57: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 56NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G030 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HOEY

Complex: 150005 Asset: 00000012-0 Compass: 15000500000012-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE BUILT-UP AND SINGLE PLY ROOFS

Component: 1.05

Description of Deficiency: FACILITIES MAINTENANCE PERSONNEL STATES (AND OBSERVED FROM ADJACENT ELEVATION) THAT THE EXISTING BUILT-UP ROOF AND SINGLE PLY ROOF AT CANOPY IS SHOWING SIGNS OF DETERIORATION AND IS NEAR END OF USEFUL LIFE.

Correction Required: REMOVE EQUIPMENT NOT ON CURBS, AND ALL ROOFING MATERIALS, TO EXPOSE STRUCTURAL DECK. REPAIR DECK AS REQUIRED. INSTALL NEW, CORRECTLY DETAILED FLASHING, EXPANSION JOINTS, DRAINS OR GUTTERS AND OTHER RELATED COMPONENTS. INSTALL MEMBRANE OVER NEW INSULATION HAVING A MINIMUM R-20 VALUE AND MINIMUM SLOPE OF ONE QUARTER INCH PER FOOT. COST ESTIMATE ASSUMES A HIGH QUALITY SYSTEM OF BUILT-UP, SINGLE PLY OR EQUIVALENT TYPE WITH A LIGHT COLORED OR REFLECTIVE SURFACE.

Estimated cost of correction: 125000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 58: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 57NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G031 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HOEY

Complex: 150005 Asset: 00000012-0 Compass: 15000500000012-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: ADA CORRECTIONS

Component: 9.4

Description of Deficiency: BUILDING DOES NOT COMPLY WITH ADA GUIDELINES AND APPLICABLE SECTIONS OF THE STATE BUILDING CODE.

Correction Required: RENOVATE COMPONENTS OF THE BUILDING AS REQUIRED TO COMPLY WITH ADA CODES AND GUIDELINES.

Estimated cost of correction: 225000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 59: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(08) Category Page 58NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M014 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HOEY

Complex: 150005 Asset: 00000012-0 Compass: 15000500000012-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: COMPLETE HVAC RENOVATION

Component: 1.082

Description of Deficiency: HOEY AUDITORIUM HAS AN ASSORTMENT OF PNEUMATICALLY CONTROLLED AIR HANDLERS, FAN COIL UNITS AND CABINET UNITS. THE SMALL AIR HANDLING UNIT OVER THE BACKSTAGE AREA IS VERY DIFFICULT TO SERVICE IN ITS CURRENT SUSPENDED LOCATION. THE INSUFFICIENTLY SIZED HVAC SYSTEM REQUIRES 24 HOURS TO COOL THE BUILDING FOR A PERFORMANCE. OUTSIDE AIR TO HOEY AUDITORIUM IS CONTROLLED BY A MANUAL DAMPER.

Correction Required: PROVIDE A CENTRAL HVAC SYSTEM WITH DDC CONTROL. REDESIGN THE DUCTWORK LAYOUT FOR PROPER HVAC ZONING.

Estimated cost of correction: 400000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 60: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 59NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M015 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MCKEE HALL

Complex: 150005 Asset: 00000013-0 Compass: 15000500000013-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: HVAC UPGRADE

Component: 1.082

Description of Deficiency: IN MECHANICAL ROOM G23, THE ROTATION OF THE MAKEUP AIR HANDLER FAN DOES NOT MATCH THE GEOMETRY OF THE AHU DISCHARGE PORT. THIS RESULTS IN UNNECESSARY AIR PRESSURE DROP IMMEDIATELY DOWNSTREAM OF THE FAN.

Correction Required: REPLACE THE FAN WHEEL WITH A WHEEL DESIGNED TO SMOOTHLY DIRECT THE AIR FLOW THROUGH THE DISCHARGE PORT. REPLACE MOTOR AS NECESSARY.

Estimated cost of correction: 15000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 61: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 60NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G032 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MCKEE HALL

Complex: 150005 Asset: 00000013-0 Compass: 15000500000013-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: MASONRY BUILDING ENVELOPE (BRICK) IS SHOWING SIGNS OF DETERIORATION. WINDOW LINTELS ARE EXTREMELY RUSTY. LIMESTONE DECORATIVE ENTRY WAY IS ALSO IN POOR CONDITION.

Correction Required: POINT-UP DETERIORATED MORTAR JOINTS (BUILDING-WIDE) AND REPAIR WINDOW LINTELS. RE-CAULK AND RESTORE DECORATIVE LIMESTONE ENTRYWAY.

Estimated cost of correction: 100000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 62: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 61NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G033 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MCKEE HALL

Complex: 150005 Asset: 00000013-0 Compass: 15000500000013-0

Deficiency Type: 2 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: MISCELLANEOUS RENOVATION - INTERIOR FINISHES

Component: 9.5

Description of Deficiency: RECENTLY INSTALLED VINYL FLOOR TILE (BUILDING-WIDE) HAS, AND IS, EXHIBITING ADHESION CONCERNS. GROUND FLOOR APPEARS TO BE IN SOMEWHAT WORST CONDITION.

Correction Required: REMOVE DAMAGED AND POORLY ADHERED FLOOR TILE. PREPARE SURFACE, AND INSTALL NEW FLOOR TILE.

Estimated cost of correction: 276000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 63: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 62NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M016 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MCKEE HALL

Complex: 150005 Asset: 00000013-0 Compass: 15000500000013-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: SPRINKLER REPIPING

Component: 1.083

Description of Deficiency: THE INCOMING FIRE SPRINKLER LINE TO MECHANICAL ROOM G16A IS PIPED IN SUCH A WAY THAT THE SUPPLY AIR DUCT TO THE SECOND FLOOR IS RESTRICTED IN SIZE. THIS RESULTS IN REDUCED STATIC PRESSURE TO THE SECOND FLOOR OF MCKEE HALL.

Correction Required: REPIPE THE INCOMING FIRE SPRINKLER LINE TO ALLOW A LARGER SUPPLY AIR DUCT TO THE SECOND FLOOR. INSTALL A LARGER SUPPLY AIR DUCT AFTER THE LINE IS REPIPED.

Estimated cost of correction: 20000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 64: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 63NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M017 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MCKEE HALL

Complex: 150005 Asset: 00000013-0 Compass: 15000500000013-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: PLUMBING FIXTURE UPGRADE

Component: 1.081

Description of Deficiency: PLUMBING FIXTURES, ESPECIALLY LAVATORIES, ARE BADLY CORRODED AND UNSIGHTLY IN SOME MCKEE HALL RESTROOMS.

Correction Required: REPLACE ALL CORRODED FIXTURES IN MCKEE HALL.

Estimated cost of correction: 20000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 65: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(08) Category Page 64NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M018 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REID GYM

Complex: 150005 Asset: 00000014-0 Compass: 15000500000014-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: COMPLETE MECHANICAL RENOVATION

Component: 1.082

Description of Deficiency: ALL STEAM PIPING IN THE MECHANICAL ROOM IS CORRODED AND NEEDS REPLACEMENT. PRESSURE RELIEF VALVES IN 5 AND 15 PSIG STEAM LINES DISCHARGE DIRECTLY INTO THE MECHANICAL ROOM INSTEAD OF BEING VENTED OUTSIDE. A REGULATOR FAILURE COULD DELIVER 125 PSIG STEAM TO THESE RELIEF VALVES, PRESENTING A SERIOUS PERSONNEL HAZARD IN THE MECHANICAL ROOM. ALL STEAM AND CONDENSATE LINES THROUGHOUT REID GYM ARE AGING AND IN NEED OF REPLACEMENT. THE FOUR PIPE FAN COIL UNITS IN THREE CLASSROOMS ARE OUTMODED AND A MAINTENANCE PROBLEM. THERE IS NO DDC INTERFACE WITH THE CAMPUS ENERGY MANAGEMENT SYSTEM. ONE THERMOSTAT CONTROLS THE STEAM HEAT TO BOTH LOCKER ROOMS AND THE ADJOINING REC ROOM. MAKEUP AIR UNIT #2 IN MECHANICAL ROOM B100 IS LEAKING. ANTIQUATED, POORLY SEALED, CHAIN OPERATED OVERHEAD WINDOWS ADD TO ENERGY MANAGEMENT PROBLEMS.

Correction Required: REPLACE ALL STEAM AND CONDENSATE PIPING IN THE MECHANICAL ROOM AND THROUGHOUT REID GYM. IN THE MECHANICAL ROOM, ADD LINES TO CARRY BLOWOFF STEAM FROM THE PRESSURE RELIEF VALVES TO OUTSIDE THE BUILDING FOR PERSONNEL SAFETY. CONSIDER CONVERSION TO HOT WATER HEATING, WITH THE ADDITION OF STEAM TO HEATING HOT WATER HEAT EXCHANGERS IN THE MECHANICAL ROOM. PROVIDE DDC CONTROLLED HOT WATER/CHILLED WATER FAN COIL UNITS IN THE CLASSROOMS. PROVIDE A DDC CONTROL SYSTEM FOR REID GYM. PROVIDE ZONE TEMPERATURE CONTROL FOR EACH LOCKER ROOM. REPLACE OBSOLETE WINDOWS WITH PROPERLY SEALED DOUBLE PANE WINDOWS.

Estimated cost of correction: 500000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

Page 66: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 67: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(04) Category Page 65NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E014 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REID GYM

Complex: 150005 Asset: 00000014-0 Compass: 15000500000014-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: ELECTRICAL REPAIR

Component: 1.091

Description of Deficiency: THE ELECTRICAL PANEL NEXT TO JANITOR ROOM 203 IN REID GYM FEELS ABNORMALLY WARM.

Correction Required: CHECK THIS ELECTRICAL PANEL FOR OVERLOAD.

Estimated cost of correction: 0 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 68: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 66NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G034 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REID GYM

Complex: 150005 Asset: 00000014-0 Compass: 15000500000014-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE ROOF

Component: 1.05

Description of Deficiency: THE ASPHALT SHINGLE ROOF "LAND LOCKED" AT FRONT OF MAIN GYM IS SHOWING SIGNS OF DETERIORATION AND IS NEAR/AT END OF LIFE.

Correction Required: REMOVE EXISTING ASPHALT SHINGLES DOWN TO STRUCTURAL DECK. REPAIR DECK AS REQUIRED. INSTALL NEW FLASHING AND ASPHALT SHINGLES AT FRONT OF MAIN GYM.

Estimated cost of correction: 15000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 69: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 67NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M019 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REID GYM

Complex: 150005 Asset: 00000014-0 Compass: 15000500000014-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: POOL RENOVATION

Component: 5.120

Description of Deficiency: STEAM AND CONDENSATE PIPING, ESPECIALLY THE VENT PIPE ABOVE THE CONDENSATE RECEIVER TANK, IS BADLY CORRODED IN THE REID GYM POOL MACHINERY ROOM. ALL IRON PIPE AROUND THE REID GYM POOL IS BADLY CORRODED, AND FLOODING OF THE MACHINERY ROOM WILL RESULT IF ONE OF THESE PIPES RUPTURES. THIS ROOM NEEDS ADDITIONAL VENTILATION FOR PERSONNEL SAFETY. MANY OF THE PLASTIC PIPE FITTINGS ARE LEAKING IN THIS ROOM.

Correction Required: REPLACE ALL STEAM, CONDENSATE, AND POOL WATER PIPING IN AND AROUND THE REID GYM POOL. PROVIDE ADEQUATE VENTILATION IN THE POOL MACHINERY ROOM. REPAIR ALL LEAKING FITTINGS.

Estimated cost of correction: 250000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 70: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 68NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M020 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REID GYM

Complex: 150005 Asset: 00000014-0 Compass: 15000500000014-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: DOMESTIC HOT WATER HEATER REPLACEMENT

Component: 1.081

Description of Deficiency: ONE OF THE TWO DOMESTIC STEAM TO HOT WATER HEATERS IN THE REID GYM MECHANICAL ROOM LEAKS IN THE TUBE BUNDLE.

Correction Required: REPLACE BOTH STEAM TO HOT WATER DOMESTIC HOT WATER HEATERS.

Estimated cost of correction: 80000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 71: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 69NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M021 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REID GYM

Complex: 150005 Asset: 00000014-0 Compass: 15000500000014-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: PLUMBING UPGRADES

Component: 1.081

Description of Deficiency: THE LOCKER ROOMS IN REID GYM NEED COMPLETE PLUMBING RENOVATION. FIXTURES ARE AGING AND ARE HARD TO MAINTAIN. THE FLOOR DRAINS ARE CORRODED AND CLOG PERIODICALLY.

Correction Required: REPLACE ALL LOCKER ROOM FIXTURES. REPAIR FLOOR DRAINS.

Estimated cost of correction: 200000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 72: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 70NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E015 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REID GYM

Complex: 150005 Asset: 00000014-0 Compass: 15000500000014-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE OBSOLETE ELECTRICAL PANELS

Component: 1.091

Description of Deficiency: THE ORIGINAL 800 AMP TAPPED SERVICE ENTRANCE PANEL AND ASSOCIATED BRANCH CIRCUIT PANELS ARE OBSOLETE THESE WERE MANUFACTURED SOME 52 YEARS AGO BY NOW DEFUNCT TRUMBELL ELECTRIC. REPLACEMENT PARTS ARE ONLY AVAILABLE FROM ELECTRICAL SALVAGE COMPANIES AND ONLY IF THE COMPANIES COINCIDENTLY HAVE THE PARTS IN STOCK. A FAILURE OF A BUS OR A CIRCUIT BREAKER WILL RESULT IN AN EXTENDED ELECTRICAL OUTAGE OF ONE OR MORE CIRCUITS WHILE REPLACEMENT DEVICES ARE LOCATED AND INSTALLED. THE FEEDER AND BRANCH WIRING OF THESE PANELS IS LIKELY OBSOLETE CLOTH COVERED RUBBER TYPE RH CABLE. THE RUBBER INSULATION OF RH CABLE TYPICALLY DRIES OUT TO THE EXTENT THAT IT MAY CRACK AND FALL AWAY.

Correction Required: REPLACE THE OBSOLETE ELECTRICAL PANELS. ENSURE THAT THE REPLACEMENT PANELS HAVE AT LEAST 20% SPARE BREAKER POSITIONS FOR FUTURE CIRCUITS. REPLACE OBSOLETE TYPE RH INSULATED CABLE AND PROVIDE SUPPLEMENTAL EQUIPMENT GROUNDING CONDUCTORS. EXISTING RACEWAY MAY BE REUSED IF UNDAMAGED.

Estimated cost of correction: 35000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 73: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 71NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E016 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REID GYM

Complex: 150005 Asset: 00000014-0 Compass: 15000500000014-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE FIRE ALARM SYSTEM

Component: 1.091

Description of Deficiency: THE EDWARDS LSS4/12 IS A CONVENTIONAL ZONED FIRE ALARM CONTROL PANEL THAT IS NO LONGER MANUFACTURED. REPLACEMENT PARTS WILL BECOME DIFFICULT TO OBTAIN AS THE MANUFACTURER DEPLETES ITS STOCK. THE FIRE ALARM SYSTEM HAS INSUFFICIENT NOTIFICATION APPLIANCES AND INITIATION DEVICES TO SATISFY THE PRESENT REQUIREMENTS OF NFPA 72® .

Correction Required: RECOMMEND REPLACING THE OBSOLETE CONVENTIONAL FIRE ALARM SYSTEM WITH ONE THAT IS ADDRESSABLE. AN ASSESSMENT OF THE BUILDING SHOULD BE MADE TO DETERMINE THE EXTENT THAT ADDITIONAL NOTIFICATION APPLIANCES AND MANUAL PULL STATIONS MUST BE INSTALLED TO SATISFY THE PRESENT REQUIREMENTS OF NATIONAL FIRE ALARM CODE® .

Estimated cost of correction: 200000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 74: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(22) Category Page 72NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E017 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REID GYM

Complex: 150005 Asset: 00000014-0 Compass: 15000500000014-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE LIGHTING

Component: 1.092

Description of Deficiency: SIXTY SIX (66) 250 WATT HIGH INTENSITY DISCHARGE LAMPS ILLUMINATE THE GYMNASIUM. THESE CONSUME 16,500 WATTS, ARE NOT SECTIONALIZED SWITCHED, AND NOT AS EFFECTIVE OR EFFICIENT AS RECENTLY DEVELOPED LUMINARIES FOR GYMNASIUMS.

Correction Required: RECOMMEND A DESIGNED RENOVATION OF THE GYMNASIUM LIGHTING TO COMPLY WITH NC BUILDING CODE AND NC ENERGY CODE, AND TO FOLLOW RECOMMENDATIONS OF THE ILLUMINATING ENGINEERING SOCIETY (IES) FOR ILLUMINATING GYMNASIUMS.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 75: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 73NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G035 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REID GYM

Complex: 150005 Asset: 00000014-0 Compass: 15000500000014-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: COMPLETE BUILDING RENOVATION (PARTS OF BUILDING)

Component: 6.1

Description of Deficiency: MOST PORTIONS OF GYMNASIUM ARE ORIGINAL CONSTRUCTION AND DO NOT COMPLY WITH CURRENT BUILDING CODES AND ADA GUIDELINES. WINDOWS, EXTERIOR DOORS, STOREFRONT SYSTEMS AS WELL AS POOL, LOCKER ROOMS AND BLEACHERS ARE AT END OF LIFE.

Correction Required: REMOVE ALL EXISTING DETERIORATED INTERIOR SYSTEMS AND REVISE INTERIOR PLANS AS REQUIRED BY FUNCTIONS AND CODES. REMOVE (ABATE) ANY HAZARDOUS MATERIALS ASSOCIATED WITH RENOVATION. CONSTRUCT NEW INTERIOR SPACES INCLUDING ALL ARCHITECTURAL SYSTEMS AND FINISHES. INSTALL NEW OPERABLE WINDOWS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. INSTALL NEW LIGHTING, FIRE ALARMS, ELECTRICAL AND MECHANICAL SERVICE SYSTEMS AS REQUIRED BY CURRENT STANDARDS AND BUILDING CODES. RENOVATE EXTERIOR BUILDING ENVELOPE AND MASONRY BRIDGE WAY.

Estimated cost of correction: 9025575 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 76: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 74NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G036 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BREESE GYMNASIUM

Complex: 150005 Asset: 00000015-0 Compass: 15000500000015-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: COMPLETE BUILDING RENOVATION (FIRST FLOOR)

Component: 6.1

Description of Deficiency: FIRST FLOOR LEVEL, POOL AND SURROUNDING DECK AREA AND LOCKER ROOMS ARE AT END OF USEFUL LIFE AND POOL USE LIKELY IN NO LONGER VIABLE. SECOND FLOOR LEVEL HAS HAD A RECENT RENOVATION. SOME WINDOWS AND STOREFRONT SYSTEMS AS WELL AS STONE EXTERIOR IS SHOWING SIGNS OF DETERIORATION.

Correction Required: REMOVE ALL EXISTING INTERIOR SYSTEMS AT FIRST FLOOR LEVEL AND REVISE INTERIOR PLANS AS REQUIRED BY FUNCTIONS AND CODES. REMOVE (ABATE) ANY HAZARDOUS MATERIALS ASSOCIATED WITH RENOVATION. CONSTRUCT NEW INTERIOR SPACES INCLUDING ALL ARCHITECTURAL SYSTEMS AND FINISHES. INSTALL NEW OPERABLE WINDOWS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. INSTALL NEW LIGHTING, FIRE ALARMS, ELECTRICAL AND MECHANICAL SERVICE SYSTEMS AS REQUIRED BY CURRENT STANDARDS AND BUILDING CODES. RENOVATE EXTERIOR BUILDING ENVELOPE.

Estimated cost of correction: 2600000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 77: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 75NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M022 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BREESE GYMNASIUM

Complex: 150005 Asset: 00000015-0 Compass: 15000500000015-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: POOL UPGRADES

Component: 5.120

Description of Deficiency: THE POOL EQUIPMENT ROOM IN BREESE GYMNASIUM IS VERY HOT AND REQUIRES MORE VENTILATION FOR PERSONNEL SAFETY. THE FOUR SAND FILTRATION TANKS, INSTALLED IN 1974, ARE BADLY CORRODED AND IN DANGER OF BLOWOUT. THESE FILTRATION TANKS CANNOT BE ISOLATED FROM EACH OTHER FOR MAINTENANCE. THE POOL MAIN DRAIN IS LEAKING APPROXIMATELY 1,000 GALLONS PER DAY, WASTING ENORMOUS AMOUNTS OF WATER AND POOL CHEMICALS. STEAM LINES AND THE STEAM HEAT EXCHANGER FOR THE POOL ARE AGING AND SHOULD BE REPLACED. SOME STEAM LINES IN THE POOL MECHANICAL ROOM ARE LINED WITH ASBESTOS. ADDITIONAL VENTILATION IS NEEDED IN THE POOL AREA.

Correction Required: PROVIDE ADDITIONAL VENTILATION FOR THE POOL EQUIPMENT ROOM. PROVIDE NEW SAND FILTRATION TANKS WITH INDIVIDUAL ISOLATION VALVES. REPLACE THE POOL DRAIN. PROVIDE A COMPLETE UPGRADE OF BREESE GYMNASIUM POOL CIRCULATION AND FILTRATION EQUIPMENT AND CIRCULATING WATER LINES. REPLACE AGING STEAM LINES AND ABATE ALL ASBESTOS. PROVIDE ADDITIONAL VENTILATION TO THE POOL AREA.

Estimated cost of correction: 600000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 78: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 76NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M023 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BREESE GYMNASIUM

Complex: 150005 Asset: 00000015-0 Compass: 15000500000015-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: PROVIDE FIRE SPRINKLER SYSTEM

Component: 1.083

Description of Deficiency: BREESE GYMNASIUM HAS NO SPRINKLER SYSTEM FOR FIRE PROTECTION.

Correction Required: PROVIDE A FIRE PROTECTION SPRINKLER SYSTEM FOR BREESE GYMNASIUM.

Estimated cost of correction: 400000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 79: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 77NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M024 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BREESE GYMNASIUM

Complex: 150005 Asset: 00000015-0 Compass: 15000500000015-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: PLUMBING UPGRADES

Component: 1.081

Description of Deficiency: BREESE GYMNASIUM PLUMBING AND FIXTURES DATE TO 1939. FIXTURES AND LINES ARE CORRODED AND OUTMODED.

Correction Required: PROVIDE A COMPLETE PLUMBING UPGRADE FOR BREESE GYMNASIUM.

Estimated cost of correction: 300000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 80: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 78NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M025 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BIRD BUILDING

Complex: 150005 Asset: 00000016-0 Compass: 15000500000016-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: HVAC UPGRADE

Component: 1.082

Description of Deficiency: IN MECHANICAL ROOM 113, THE SUCTION LINE TO CHILLED WATER PUMP 1 IS 1 INCH. THE SUCTION LINE TO CHILLED WATER PUMP 2 IS 2 INCH. THIS RESULTS IN A PRESSURE IMBALANCE ACROSS THESE PUMPS. CHILLED WATER PUMP 1 WAS INCORRECTLY PIPED 1 INCH DURING THE BIRD/MCKEE RENOVATION PROJECT.

Correction Required: PROVIDE A 2 INCH SUCTION LINE TO CHILLED WATER PUMP 1.

Estimated cost of correction: 5000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 81: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(14) Category Page 79NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G037 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BIRD BUILDING

Complex: 150005 Asset: 00000016-0 Compass: 15000500000016-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE EXTERIOR DOORS

Component: 1.043

Description of Deficiency: ALTHOUGH BUILDING WAS RECENTLY RENOVATED, SOME EXTERIOR DOORS (ALUMINUM STOREFRONT SYSTEMS) AND HARDWARE ARE NEAR/AT END OF USEFUL LIFE. IN ADDITION, DECORATIVE LIMESTONE AND MASONRY WINDOW SILLS ARE SHOWING SIGNS OF DETERIORATION. STONEWORK AT PLANTERS AT BACK OF BUILDING ARE ALSO IN A STATE OF DISREPAIR.

Correction Required: REMOVE AND REPLACE DAMAGED OR DETERIORATED EXTERIOR DOORS AND FRAMES (ALUMINUM STOREFRONT SYSTEMS). REPAIR DAMAGED AND DETERIORATED DECORATIVE LIMESTONE AND WINDOW SILLS. PREPARE AND REPAINT RUSTY WINDOW LINTELS. REBUILD STONEWORK AT PLANTERS.

Estimated cost of correction: 165000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 82: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 80NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G038 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BIRD BUILDING

Complex: 150005 Asset: 00000016-0 Compass: 15000500000016-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE SINGLE PLY ROOF

Component: 1.05

Description of Deficiency: THE SINGLE PLY ROOF IS IN FAIR TO POOR CONDITION AND AT/NEAR END OF EXPECTED LIFE.

Correction Required: REMOVE ALL ROOF MATERIALS TO EXPOSE STRUCTURAL DECK AND REPAIR AS REQUIRED. REMOVE OBSOLETE EQUIPMENT STANDS AT ROOF. INSTALL NEW FLASHING, EXPANSION JOINTS AND DRAINS AS NEEDED. INSTALL MEMBRANE OVER NEW INSULATION (MINIMUM R-20) AT MINIMUM SLOPE OF ONE QUARTER INCH PER FOOT. COST ESTIMATE ASSUMES HIGH QUALITY BUILT-UP, SINGLE PLY OR OTHER SYSTEM WITH A LIGHT, REFLECTIVE SURFACE.

Estimated cost of correction: 102000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 83: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(14) Category Page 81NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G039 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - GROUNDS MAINTENANCE

Complex: 150005 Asset: 00000017-0 Compass: 15000500000017-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR WINDOWS

Component: 1.042

Description of Deficiency: STEEL WINDOW FRAMES ARE RUSTED.

Correction Required: CLEAN AND REPAINT STEEL WINDOW FRAMES. CONSIDER ADDING STORM WINDOWS.

Estimated cost of correction: 5000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 84: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 82NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E018 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - GROUNDS MAINTENANCE

Complex: 150005 Asset: 00000017-0 Compass: 15000500000017-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: INSTALL FIRE ALARM

Component: 1.102

Description of Deficiency: THIS BUILDING HAS NO FIRE ALARM SYSTEM.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 85: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 83NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G040 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - GROUNDS MAINTENANCE

Complex: 150005 Asset: 00000017-0 Compass: 15000500000017-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: MORTAR AND CAULKED JOINTS IN EXTERIOR MASONRY HAVE SOME DETERIORATION. MOISTURE PENETRATES WALLS.

Correction Required: REPAIR CAULK AND REPOINT MORTAR JOINTS OF MASONRY WALLS AS NEEDED. TO REDUCE MOISTURE THROUGH EXTERIOR WALL, SEAL EXTERIOR WITH SILANE/SILOXANE WATERPROOFING AND CONSIDER PAINTING INTERIOR WALLS WITH A LOW PERM RATED PAINT.

Estimated cost of correction: 12000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 86: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 84NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E019 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - GROUNDS MAINTENANCE

Complex: 150005 Asset: 00000017-0 Compass: 15000500000017-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: PROVIDE FIRE ALARM SYSTEM

Component: 1.102

Description of Deficiency: THIS ASSET DOES NOT HAVE A FIRE/SMOKE DETECTION SYSTEM. A FIRE ALARM SYSTEM IS CRITICAL TO THE PROTECTION OF LIVES AND THE PROTECTION OF STATE-OWNED PROPERTY, FOR WHICH THE STATE IS SELF INSURED.

Correction Required: RECOMMEND INSTALLATION OF A FIRE ALARM SYSTEM THAT IS COMPLIANT WITH NATIONAL FIRE ALARM CODE® AND DEPARTMENT OF INSURANCE FIRE DETECTION AND ALARM SYSTEM GUIDELINES.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 87: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 85NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M026 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - GROUNDS MAINTENANCE

Complex: 150005 Asset: 00000017-0 Compass: 15000500000017-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE PLUMBING DRAIN

Component: 1.082

Description of Deficiency: THE DRAIN AT THE PAINT SEPARATOR IS DAMAGED AND BACKS UP FREQUENTLY AND REQUIRES EXTENSIVE MAINTENANCE.

Correction Required: REPLACE DRAIN AT PAINT SEPARATOR.

Estimated cost of correction: 5000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 88: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 86NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E020 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STEAM PLANT

Complex: 150005 Asset: 00000019-0 Compass: 15000500000019-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REWIRE COMPLETELY

Component: 1.091

Description of Deficiency: THE EXISTING WIRE, PANELS, AND SWITCHES ARE REACHING THE END OF THERE SERVICE LIVES.

Correction Required: COMPLETELY REWIRE AND REPLACE EXISTING PANELS AND SWITCHES.

Estimated cost of correction: 20000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 89: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(06) Category Page 87NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M027 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STEAM PLANT

Complex: 150005 Asset: 00000019-0 Compass: 15000500000019-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: UPGRADE STEAM PLANT INFRASTRUCTURE

Component: 4.100

Description of Deficiency: THE STEAM PLANT HAS FOUR BOILERS, WITH MANUFACTURER DATES LISTED AS 1951, 1966, 1968, AND 1973. THE BOILERS APPEAR TO BE IN RELATIVELY GOOD CONDITION FOR THE AGE OF THE EQUIPMENT. THE PLANT HAS DETERIORATED WITH AGE, INCLUDING MECHANICAL PIPING AND CONNECTIONS TO THE STEAM DISTRIBUTION PIPING. ALTHOUGH SIGNIFICANT EFFORTS HAVE BEEN MADE TO UPDATE BOILER CONTROLS, MUCH OF THE PLANT INFRASTRUCTURE IS IN NEED OF EXTENSIVE REPAIRS OR RENOVATION. .

Correction Required: PROVIDE EXTENSIVE RENOVATION TO THE STEAM PLANT MECHANICAL INFRASTRUCTURE. IT MAY BE DIFFICULT OR IMPRACTICAL TO MAKE THE APPROPRIATE SYSTEM UPGRADES WITHIN THE EXISTING FACILITY.

Estimated cost of correction: 2100000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 90: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 88NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G041 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STEAM PLANT

Complex: 150005 Asset: 00000019-0 Compass: 15000500000019-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BUILDING

Component: 9.500

Description of Deficiency: VARIOUS BUILDING SYSTEMS ARE IN VERY POOR CONDITION DUE TO AGE AND HEAVY USE. OTHER DEFICIENCY REPORTS OUTLINE ITEMS THAT MAY NEED ATTENTION BEFORE FUNDS ARE AVAILABLE FOR A COMPLETE RENOVATION.

Correction Required: FULL BUILDING RENOVATION TO INCLUDE: REPLACE ROOFS WITH HIGH QUALITY MEMBRANE OR BUILT UP ROOF. INCLUDE DECK REPAIRS AND NEW INSULATION. REMOVE ALL EXISTING ROOF MATERIALS AND REPLACE. REPAIR DETERIORATED WALLS (BRICK) AND MORTAR. REPLACE WINDOWS. REPLACE INTERIOR AND EXTERIOR DOORS. RENOVATE ALL BATHROOMS. RENOVATE ALL INTERIOR FINISHES INCLUDING CEILINGS, FLOORS AND PARTITIONS. REPAIR CONCRETE FLOORS AS NEEDED. ESTIMATE IS FOR ARCHITECTURAL RENOVATION AND DOES NOT INCLUDE MEHANICAL OR ELECTRICAL SYSTEMS.

Estimated cost of correction: 1800000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 91: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 89NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E021 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STEAM PLANT

Complex: 150005 Asset: 00000019-0 Compass: 15000500000019-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE ELECTRICAL SYSTEM

Component: 1.091

Description of Deficiency: THE TAPPED SERVICE ENTRANCE FUSED PANEL, DISTRIBUTION SWITCHBOARD, AND BRANCH CIRCUIT PANELS ARE OBSOLETE, HAVING BEEN INSTALLED SOME 70 YEARS AGO. REPLACEMENT PARTS ARE ONLY AVAILABLE FROM ELECTRICAL SALVAGE COMPANIES AND ONLY IF THE COMPANIES COINCIDENTLY HAVE THE PARTS IN STOCK. A FAILURE OF A BUS OR A CIRCUIT BREAKER WILL RESULT IN AN EXTENDED ELECTRICAL OUTAGE OF ONE OR MORE CIRCUITS OF THE AFFECTED EQUIPMENT WHILE REPLACEMENT DEVICES ARE LOCATED AND INSTALLED. WIRING CONSISTS OF CLOTH COVERED RUBBER INSULATED (TYPE RH) SINGLE CONDUCTOR CABLES. THE RUBBER INSULATION TYPICALLY DRIES OUT TO THE EXTENT THAT IT MAY CRACK AND FALL AWAY. GROUNDING IS THROUGH THE CIRCUIT CONDUIT. THE 70 YEAR OLD OBSOLETE WIRING IS POTENTIALLY DANGEROUS.

Correction Required: RECOMMEND COMPLETE ELECTRICAL UPGRADE OF THIS FACILITY TO INCLUDE ALL OBSOLETE ELECTRICAL EQUIPMENT AND POTENTIALLY DANGEROUS WIRING.

Estimated cost of correction: 200000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 92: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(14) Category Page 90NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G042 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STEAM PLANT

Complex: 150005 Asset: 00000019-0 Compass: 15000500000019-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR EXTERIOR WALLS AND WINDOWS

Component: 1.041

Description of Deficiency: EAST, SOUTH AND WEST WALLS HAVE LEAKS BELOW GRADE THAT ALLOWS WATER TO PENETRATE. SOME WATERPROOFING HAS BEEN DONE. SOME MORTAR JOINTS AND HANDMADE BRICK ARE NOT STRUCTURALLY SOLID. OPERATORS ON WINDOWS ARE IN POOR CONDITION.

Correction Required: EXCAVATE FOUNDATION WALL AND INSTALL WATERPROOFING WHERE REQUIRED. STRUCTURAL CONDITION OF WALL IS APPARENTLY ADEQUATE FOR THE PROJECTED FUTURE USE OF TEN YEARS. REPAIR OR REPLACE STORM DRAIN PIPE AS NEEDED. REPOINT MORTAR JOINTS WHERE NEEDED. REPLACE OPERATORS ON WINDOWS TO PROVIDE BETTER VENTILATION.

Estimated cost of correction: 65000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 93: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 91NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G043 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STEAM PLANT

Complex: 150005 Asset: 00000019-0 Compass: 15000500000019-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE BUILT-UP ROOF

Component: 1.05

Description of Deficiency: THE UPPER ROOF WILL BE NEAR END OF EXPECTED LIFE. SOME REPAIR MAY BE REQUIRED BEFORE FUNDS ARE AVAILABLE FOR REPLACEMENT.

Correction Required: REMOVE ALL ROOF MATERIALS TO EXPOSE STRUCTURAL DECK AND REPAIR AS REQUIRED. INSTALL NEW FLASHING, EXPANSION JOINTS AND DRAINS AS NEEDED. INSTALL MEMBRANE OVER NEW INSULATION (MINIMUM R-20) AT MINIMUM SLOPE OF ONE QUARTER INCH PER FOOT. COST ESTIMATE ASSUMES HIGH QUALITY BUILT-UP, SINGLE PLY OR OTHER SYSTEM WITH A LIGHT, REFLECTIVE SURFACE.

Estimated cost of correction: 215000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 94: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(08) Category Page 92NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G044 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STEAM PLANT

Complex: 150005 Asset: 00000019-0 Compass: 15000500000019-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: STRUCTURAL STUDY - CONCRETE STEAM TUNNEL

Component: 6.1

Description of Deficiency: CONCRETE STEAM TUNNEL LEAKS PRIMARILY AT CONNECTION OF WALLS TO ROOF SLAB DURING HEAVY RAINS. TUNNEL IS ABOUT 900 FEET IN LENGTH AND HAS AN AVERAGE OF 5 FEET OF EARTH OVER ROOF SLAB.

Correction Required: EXCAVATE AND REPAIR AS NEEDED. A STRUCTURAL STUDY TO DETERMINE METHOD AND ESTIMATED COST OF REPAIR IS RECOMMENDED.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 95: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 93NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E022 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STEAM PLANT

Complex: 150005 Asset: 00000019-0 Compass: 15000500000019-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: UPGRADE FIRE ALARM SYSTEM

Component: 1.102

Description of Deficiency: THE EDWARDS EST-2 FIRE ALARM CONTROL PANEL WAS RECENTLY INSTALLED; HOWEVER, THE SYSTEM WAS NOT UPGRADED TO HAVE SUFFICIENT NOTIFICATION APPLIANCES AND INITIATION DEVICES TO SATISFY THE PRESENT REQUIREMENTS OF NFPA 72® .

Correction Required: PROVIDE ADDITIONAL FIRE ALARM SYSTEM DEVICES TO SATISFY THE PRESENT REQUIREMENTS OF NFPA 72® AND NC FIRE CODE.

Estimated cost of correction: 50000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 96: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 94NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E023 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STEAM PLANT

Complex: 150005 Asset: 00000019-0 Compass: 15000500000019-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EMERGENCY GENERATOR

Component: 1.101

Description of Deficiency: THE EMERGENCY GENERATOR SYSTEM IS OBSOLETE AND PAST ITS USEFUL LIFE. THE FUEL TANK DOES NOT HAVE SPILL PREVENTION OR LEAK DETECTION/CONTAINMENT. THE FUEL LINE IS LAID ON THE GROUND SURFACE WITHOUT SUPPORT OR PROPER PROTECTION, AND IS DIRECTLY BURIED IN CONCRETE WITHOUT A SLEEVE TO PROTECT IT AGAINST CORROSION AS IT PENETRATES THE GENERATOR ENCLOSURE. POWER TRANSFERS ARE MADE MANUALLY, WITHOUT SAFETY INTERLOCKS, IN A WORKING SPACE THAT IS NON-COMPLIANT TO NEC.

Correction Required: REPLACE THE EMERGENCY GENERATOR SYSTEM TO INCLUDE A GENERATOR, AN AUTOMATIC TRANSFER SWITCH, AND A CODE COMPLIANT FUEL STORAGE SYSTEM. THE REPLACEMENT GENERATOR SHOULD BE PROVIDED WITH A SOUND ATTENUATED STORM WEATHER RESISTANT ENCLOSURE.

Estimated cost of correction: 27000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 97: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 95NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G045 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - INFIRMARY (GRAHAM BLDG.)

Complex: 150005 Asset: 00000020-0 Compass: 15000500000020-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: COMPLETE BUILDING RENOVATION

Component: 9.1

Description of Deficiency: ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL SYSTEMS IN THIS 68 YEAR OLD INFIRMARY BUILDING ARE AT THE END OF THEIR EXPECTED USEFUL LIFE. BUILDING IS PRESENTLY VACANT. ORIGINAL, METAL, SINGLE GLAZED WINDOWS AND MOST EXTERIOR DOORS AND STOREFRONT SYSTEMS ARE IN POOR OPERATING CONDITION. BUILDING DOES NOT COMPLY WITH CURRENT LIFE SAFETY AND ADA CODES (AND DOES NOT HAVE AN EXISTING ELEVATOR). HEATING AND VENTILATION SYSTEMS DO NOT COMPLY WITH CURRENT STANDARDS FOR COMFORT AND HEALTH. ROOFS (BOTH TERRA COTTA TILE SINGLE AND SINGLE PLY ARE ALSO IN POOR CONDITION.

Correction Required: REMOVE ALL EXISTING INTERIOR SYSTEMS, AND REVISE INTERIOR PLANS AS REQUIRED BY FUNCTIONS AND CODES. REMOVE (ABATE) ALL HAZARDOUS MATERIALS ASSOCIATED WITH RENOVATION. CONSTRUCT NEW INTERIOR SPACES INCLUDING ALL ARCHITECTURAL SYSTEMS AND FINISHES. INSTALL NEW OPERABLE WINDOWS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. REPLACE DAMAGED AND DETERIORATED EXTERIOR DOORS, DOOR FRAMES AND HARDWARE. INSTALL NEW LIGHTING, FIRE ALARMS, ELECTRICAL AND MECHANICAL SERVICE SYSTEMS AS REQUIRED BY CURRENT STANDARDS AND BUILDING CODES. RENOVATE EXTERIOR BUILDING ENTRY WAYS (INCLUDING, DOOR FRAMES, DOORS, HARDWARE, SURROUNDS AND STEPS). INSTALL NEW ELEVATOR SHAFT WAY AND ELEVATOR. REMOVE ALL ROOF MATERIALS (SINGLE PLY ROOF AND TERRA COTTA ROOFS) TO EXPOSE STRUCTURAL DECK AND REPAIR AS REQUIRED. INSTALL NEW FLASHING, EXPANSION JOINTS, AND DRAINS AS NEEDED. INSTALL MEMBRANE OVER NEW INSULATION (MINIMUM R-20) AT MINIMUM SLOPE OF 1/4 INCH PER FOOT (SINGLE PLY ROOF). COST ESTIMATE ASSUMES HIGH QUALITY BUILT-UP, SINGLE PLY OR OTHER SYSTEM, WITH A LIGHT REFLECTIVE SURFACE. INSTALL NEW

Page 98: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

TERRA COTTA TILE (OR APPROPRIATE SUBSTITUTE) AT OLDER ROOF PORTION OF BUILDING.

Estimated cost of correction: 2800000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 99: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 96NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E024 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CHANCELLOR'S HOME

Complex: 150005 Asset: 00000022-0 Compass: 15000500000022-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REWIRE COMPLETELY

Component: 1.091

Description of Deficiency: THE EXISTING WIRE, PANELS, AND SWITCHES ARE REACHING THE END OF THERE SERVICE LIVES.

Correction Required: COMPLETELY REWIRE AND REPLACE EXISTING PANELS AND SWITCHES.

Estimated cost of correction: 40000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 100: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 97NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G046 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CHANCELLOR'S HOME

Complex: 150005 Asset: 00000022-0 Compass: 15000500000022-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: MISCELLANEOUS RENOVATION

Component: 9.5

Description of Deficiency: BATT TYPE INSULATION AT ATTIC SPACE IS EXTREMELY COMPRESSED AND THERE IS NO INSULATION AT CRAWL SPACE (CEILING AREA).

Correction Required: INSTALL AN ADDITIONAL LAYER OF INSULATION AT ATTIC SPACE (TO COMPLY WITH CURRENT CODE), AND INSTALL NEW INSULATION AT CRAWL SPACE (CEILING).

Estimated cost of correction: 6000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 101: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 98NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M028 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CHANCELLOR'S HOME

Complex: 150005 Asset: 00000022-0 Compass: 15000500000022-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE FURNACE

Component: 1.082

Description of Deficiency: ONE OF TWO EXISTING FURNACES IS OVER 35 YEARS OLD, OIL FIRED, APPROX 80% EFFICIENCY. ONE OF THE EXISTING OIL-FIRED FURNACES IS EXPERIENCING HEAVY VIBRATION AND IS IN POOR CONDITION. DUCT LOCATED IN THE CRAWL SPACE, APPEARS TO BE COVERED WITH ASBESTOS.

Correction Required: REPLACE THE FURNACE. CONSIDER NATURAL GAS. CONDUCT ASBESTOS ABATEMENT AND REPLACE DUCTWORK.

Estimated cost of correction: 12000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 102: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 99NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E025 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BROWN CAFETERIA

Complex: 150005 Asset: 00000023-0 Compass: 15000500000023-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: INSTALL AN EMERGENCY GENERATOR

Component: 1.100

Description of Deficiency: THERE IS NO EMERGENCY POWER SOURCE TO RUN PUMPS , FANS, MOTORS, AND ANY OTHER REQUIRED EQUIPMENT UNDER ADVERSE SITUATIONS.

Correction Required: INSTALL A DIESEL GENERATOR TO SUPPLY EMERGENCY POWER

Estimated cost of correction: 50000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 103: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 100NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G047 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BROWN CAFETERIA

Complex: 150005 Asset: 00000023-0 Compass: 15000500000023-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BUILDING

Component: 9.100

Description of Deficiency: 50 YO BUILDING HAS MANY SYSTEMS WHICH ARE WORN OUT DUE TO AGE AND HEAVY USE. BUILDING USES HAVE CHANGED SINCE ORIGINAL CONSTRUCTION.

Correction Required: RENOVATE BUILDING TO INCLUDE: REMOVE AND REPLACE ROOF. ROOF IS 10 YO BUT PONDS WATER AND DOES NOT DRAIN PROPERLY - SOME LEAKS. REPLACE WINDOWS WITH LOW MAINTENANCE DBL PANE CLAD UNITS. REPLACE EXTERIOR DOORS. RENOVATE ALL FLOOR FINISHES INCLUDING VCT AND CARPET. ABATE ASBESTOS CEILING FINISH (SPRAY ON). RECONFIGURE INTERIOR SPACES AS NEEDED FOR PRESENT AND FUTURE USE. FULL BATHROOM AND KITCHEN RENOVATION. FULL HVAC AND ELECTRICAL RENOVATION INCLUDING ALL SYSTEMS AND FIRE ALARM AND SUPPRESSION SYSTEMS. REPLACE ALL INTERIOR DOORS AND HARDWARE. RENOVATE ALL INTERIOR FINISHES.

Estimated cost of correction: 8100000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 104: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 101NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E026 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BROWN CAFETERIA

Complex: 150005 Asset: 00000023-0 Compass: 15000500000023-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REWIRE COMPLETELY

Component: 1.091

Description of Deficiency: THE EXISTING WIRE, PANELS, AND SWITCHES ARE REACHING THE END OF THERE SERVICE LIVES.

Correction Required: COMPLETELY REWIRE AND REPLACE EXISTING PANELS AND SWITCHES.

Estimated cost of correction: 50000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 105: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 102NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E027 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BROWN CAFETERIA

Complex: 150005 Asset: 00000023-0 Compass: 15000500000023-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: INSTALL FIRE ALARM

Component: 1.102

Description of Deficiency: THIS BUILDING HAS NO FIRE ALARM SYSTEM.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 95000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 106: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 103NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G048 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - DODSON CAFETERIA

Complex: 150005 Asset: 00000024-0 Compass: 15000500000024-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: LIFE SAFETY CODE CORRECTIONS

Component: 8.1

Description of Deficiency: ALTHOUGH IT APPEARS THAT SOME WORK HAS BEEN COMPLETED, AS PER DOI INSPECTION, THE FIRE-RATED PLASTER CEILINGS IN THE DOWNSTAIRS MECHANICAL ROOMS SHOULD BE REPAIRED. IN ADDITION THE FRENCH DOORS FROM THE SIDE DINING ROOM TO THE MAIN DINING ROOM NEED TO BE RE-HINGED TO SWING IN THE DIRECTION OF EXIT TRAVEL FROM THE SIDE DINING ROOM.

Correction Required: PATCH/SEAL OPENINGS AT MECHANICAL ROOM WALLS AND CEILINGS. RE-SWING FRENCH DOORS AT SIDE DINING ROOM TO THE DIRECTION OF EXIT TRAVEL. ADD SELF-LATCHING PANIC HARDWARE AT FIRST FLOOR (SOUTH STAIRS). ALL MODIFICATIONS SHOULD CONFORM TO STATE BUILDING CODE.

Estimated cost of correction: 15000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 107: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 104NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G049 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - KILLIAN ED & PSY

Complex: 150005 Asset: 00000025-0 Compass: 15000500000025-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: COMPLETE BUILDING RENOVATION

Component: 9.1

Description of Deficiency: ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL SYSTEMS IN THIS 41 YEAR OLD BUILDING ARE AT THE END OF THEIR EXPECTED USEFUL LIFE. EXTERIOR MASONRY WALLS EXHIBIT STRUCTURAL CONCERNS. ORIGINAL, METAL, SINGLE GLAZED WINDOWS AND MOST EXTERIOR DOORS AND STOREFRONT SYSTEMS ARE IN POOR OPERATING CONDITION. BUILDING DOES NOT FULLY COMPLY WITH CURRENT LIFE SAFETY CODES OR ADA GUIDELINES, AND ELEVATOR IS ALSO AT END OF LIFE. HEATING AND VENTILATION SYSTEMS DO NOT COMPLY WITH CURRENT STANDARDS FOR COMFORT AND HEALTH. SINGLE PLY ROOF IS ALSO IN POOR CONDITION.

Correction Required: REMOVE ALL EXISTING INTERIOR SYSTEMS, AND REVISE INTERIOR PLANS AS REQUIRED BY FUNCTIONS AND CODES. REMOVE (ABATE) ALL HAZARDOUS MATERIALS ASSOCIATED WITH RENOVATION. CONSTRUCT NEW INTERIOR SPACES INCLUDING ALL ARCHITECTURAL SYSTEMS AND FINISHES. INSTALL NEW OPERABLE WINDOWS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. REPLACE DAMAGED AND DETERIORATED EXTERIOR DOORS, DOOR FRAMES AND HARDWARE. INSTALL NEW LIGHTING, FIRE ALARMS, ELECTRICAL AND MECHANICAL SERVICE SYSTEMS AS REQUIRED BY CURRENT STANDARDS AND BUILDING CODES. RENOVATE EXTERIOR BUILDING ENTRY WAYS (INCLUDING, DOOR FRAMES, DOORS, HARDWARE, SURROUNDS AND STEPS). RENOVATE ELEVATOR TO MEET CURRENT BUILDING NEEDS TO CONFORM TO CURRENT CODE. REMOVE ALL ROOF MATERIALS (BUILT-UP ROOF WITH BALLAST) TO EXPOSE STRUCTURAL DECK AND REPAIR AS REQUIRED. INSTALL NEW FLASHING, EXPANSION JOINTS, AND DRAINS AS NEEDED. INSTALL MEMBRANE OVER NEW INSULATION (MINIMUM R-20) AT MINIMUM SLOPE OF 1/4 INCH PER FOOT. COST ESTIMATE ASSUMES HIGH QUALITY BUILT-UP, SINGLE PLY OR OTHER SYSTEM, WITH A LIGHT REFLECTIVE SURFACE.

Estimated cost of correction: 11700000 Cost estimate status: 1

Page 108: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(plus design fees and contingencies) Preliminary = 1Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 109: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(22) Category Page 105NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E028 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - KILLIAN ED & PSY

Complex: 150005 Asset: 00000025-0 Compass: 15000500000025-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE LIGHTING SYSTEM

Component: 1.092

Description of Deficiency: LIGHTING IN THE ORIGINAL BUILDING IS OBSOLETE, REPLACEMENT PARTS ARE DIFFICULT TO OBTAIN, THE QUALITY OF LIGHT IS INADEQUATE FOR THE USE OF A SPACE, AND THE LIGHTING SYSTEM AND DOES NOT MEET ENERGY CODE. BALLASTS OF FIXTURES THAT ARE ORIGINAL TO THE BUILDING ARE LIKELY TO CONTAIN PCBS.

Correction Required: RECOMMEND A DESIGNED RENOVATION OF LIGHTING TO COMPLY WITH NC BUILDING CODE AND NC ENERGY CODE, AND TO FOLLOW RECOMMENDATIONS OF THE ILLUMINATING ENGINEERING SOCIETY (IES) FOR THE SPECIFIC APPLICATIONS OF THE SPACES.

Estimated cost of correction: 100000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 110: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 106NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G050 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CAMP LAB SCHOOL

Complex: 150005 Asset: 00000026-0 Compass: 15000500000026-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR EXTERIOR WALLS AND SOFFITS

Component: 1.041

Description of Deficiency: MORTAR JOINTS IN EXTERIOR MASONRY HAVE SOME CRACKS DUE TO MINOR SETTLEMENT. SOFFIT HAS SOME DETERIORATION.

Correction Required: REPAIR AND REPOINT MORTAR JOINTS IN MASONRY WALLS AS NEEDED. REPAIR OR REPLACE SOFFIT MATERIAL.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 111: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 107NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E029 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CAMP LAB SCHOOL

Complex: 150005 Asset: 00000026-0 Compass: 15000500000026-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE EXISTING LIGHTING

Component: 1.092

Description of Deficiency: THE EXISTING LIGHTS ARE OLD AND ARE NOT ENERGY FRIENDLY

Correction Required: INSTALL ENERGY SAVING LIGHTS

Estimated cost of correction: 75000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: General Fund = 1Revenue Receipts = 2

Page 112: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 108NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 04-E030 Inspector: FM

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CAMP LAB SCHOOL

Complex: 150005 Asset: 00000026-0 Compass: 15000500000026-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 4 Years

Deficiency Title: REPLACE SEVERAL ELECTRICAL PANELS

Component: 1.091

Description of Deficiency: THERE ARE SEVERAL ELECTRICAL PANELS THAT ARE THE ORIGINAL ONES AND PAST THEIR LIFE EXPECTANCY.

Correction Required: RECOMMEND REPLACING THE ORIGINAL PANELS AND THEIR FEEDERS AS NEEDED.

Estimated cost of correction: 16000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 113: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 109NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E031 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CAMP LAB SCHOOL

Complex: 150005 Asset: 00000026-0 Compass: 15000500000026-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE ELECTRICAL PANEL

Component: 1.091

Description of Deficiency: THE EXISTING PANEL IS OLD AND REACHING THE END OF IT'S SERVICE LIFE.

Correction Required: RECOMMEND REPLACING THE OBSOLETE PANEL, WITH A PANEL THAT MEETS NEC REQUIREMENTS.

Estimated cost of correction: 20000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 114: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 110NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G051 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CAMP LAB SHOP

Complex: 150005 Asset: 00000027-0 Compass: 15000500000027-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR EXTERIOR SOFFITS

Component: 1.041

Description of Deficiency: SOFFIT HAS SOME DETERIORATION.

Correction Required: REPAIR OR REPLACE SOFFIT MATERIAL.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 115: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 111NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G052 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CAMP GYMNASIUM

Complex: 150005 Asset: 00000028-0 Compass: 15000500000028-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR EXTERIOR WALLS AND SOFFITS

Component: 1.041

Description of Deficiency: MORTAR JOINTS IN EXTERIOR MASONRY HAVE SOME CRACKS DUE TO MINOR SETTLEMENT. SOFFIT HAS SOME DETERIORATION.

Correction Required: REPAIR AND REPOINT MORTAR JOINTS IN MASONRY WALLS AS NEEDED. REPAIR OR REPLACE SOFFIT MATERIAL.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 116: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(14) Category Page 112NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G053 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CAMP GYMNASIUM

Complex: 150005 Asset: 00000028-0 Compass: 15000500000028-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE WINDOWS

Component: 1.042

Description of Deficiency: ORIGINAL, SINGLE GLAZED, STEEL WINDOWS AND DOORS ARE BEYOND END OF EXPECTED LIFE, IN POOR OPERATING CONDITION AND DUE TO LEAKAGE OF OUTDOOR AIR, CONTRIBUTE TO HIGH ENERGY COST AND DISCOMFORT OF OCCUPANTS.

Correction Required: INSTALL NEW WINDOWS AND DOORS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. A LOWER COST OPTION IS INTERIOR STORM TYPE WINDOWS. COST ESTIMATE IS FOR NEW WINDOWS AND EXTERIOR DOORS.

Estimated cost of correction: 40000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 117: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(22) Category Page 113NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E032 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CAMP GYMNASIUM

Complex: 150005 Asset: 00000028-0 Compass: 15000500000028-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE LIGHTING

Component: 1.092

Description of Deficiency: THIRTY (30) 1000 WATT INCANDESCENT LAMPS ILLUMINATE THE GYMNASIUM. THESE CONSUME 30,000 WATTS AND HAVE A LIFE EXPECTANCY OF ONLY 1000 HOURS. THIS CONDITION WASTES ENERGY AND COSTS $3000 LABOR FOR EACH INSTANCE OF GROUP RE-LAMPING, THE MOST EFFICIENT PROCEDURE FOR MAINTENANCE.

Correction Required: RECOMMEND A DESIGNED RENOVATION OF THE GYMNASIUM LIGHTING TO COMPLY WITH NC BUILDING CODE AND NC ENERGY CODE, AND TO FOLLOW RECOMMENDATIONS OF THE ILLUMINATING ENGINEERING SOCIETY (IES) FOR ILLUMINATING GYMNASIUMS.

Estimated cost of correction: 20000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 118: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 114NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G054 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - OLD STUDENT UNION

Complex: 150005 Asset: 00000029-0 Compass: 15000500000029-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: ALTHOUGH RECENT REPAIR WORK HAS BEEN DONE IT APPEARS THAT MOISTURE IS STILL PENETRATING THE LOWER LEVEL WALL (EAST SIDE OF BUILDING), AND THEN BEING INTRODUCED INTO OCCUPIED SPACES. INTERIOR FINISHES APPEAR TO HAVE BEEN DAMAGED. IN ADDITION, STEPS, RAMP AND ASSOCIATED HANDRAILS AND STONE WALL AT DRIVEWAY ARE IN POOR CONDITION.

Correction Required: FOUNDATION WALLS SHOULD BE EXCAVATED (EAST SIDE OF BUILDING), REPAIRED AND WATERPROOFED. FOUNDATION DRAINAGE SHOULD BE IMPROVED. REPAIR DAMAGED INTERIOR FINISHES. REBUILD, REPAIR AND RECONSTRUCT STEPS, RAMP, STONEWALL AND HANDRAILS.

Estimated cost of correction: 235000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 119: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 115NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G055 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - OLD STUDENT UNION

Complex: 150005 Asset: 00000029-0 Compass: 15000500000029-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE FLOOR FINISHES

Component: 1.062

Description of Deficiency: AT THE LOWER LEVEL OF THE BUILDING, FLOOR FINISHES (9 X 9 FLOOR TILE) ARE SHOWING SIGNS OF DETERIORATION AND ARE NEARING END OF EXPECTED LIFE. MOISTURE INFILTRATION AND DAMPNESS APPEARS TO HAVE CAUSED FLOOR TILE TO LOSE ADHESION. ASBESTOS MAY BE PRESENT.

Correction Required: REPLACE DAMAGED AND DETERIORATED FLOOR FINISHES AT LOWER LEVEL OF BUILDING. PRESENCE OF ASBESTOS CONTAINING FLOORING MATERIALS MAY INCREASE COST OF PROJECT ACCORDINGLY.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 120: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 116NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G056 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - OLD STUDENT UNION

Complex: 150005 Asset: 00000029-0 Compass: 15000500000029-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: MISCELLANEOUS RENOVATION

Component: 9.5

Description of Deficiency: BAY/BOW AND REPLACEMENT WINDOWS APPEAR TO BE IN POOR CONDITION AND WOOD JAMBS REQUIRE CONSTANT MAINTENANCE.

Correction Required: REMOVE AND REPLACE DAMAGED AND DETERIORATED BAY/BOW WINDOWS TO MATCH WINDOWS AT THE REMAINDER OF THE BUILDING.

Estimated cost of correction: 35000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 121: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 117NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M029 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - OLD STUDENT UNION

Complex: 150005 Asset: 00000029-0 Compass: 15000500000029-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: PROVIDE EXHAUST FOR MECHANICAL ROOM

Component: 1.082

Description of Deficiency: THE MECHANICAL SPACE USED FOR STEAM SERVICE TO THE BUILDING DOES NOT HAVE ADEQUATE VENTILATION.

Correction Required: PROVIDE PROPER VENTILATION FOR MECHANICAL SPACE.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 122: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 118NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E033 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - WATER TREATMENT PLANT

Complex: 150005 Asset: 00000030-0 Compass: 15000500000030-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REWIRE COMPLETELY

Component: 1.091

Description of Deficiency: THE EXISTING WIRE, PANELS, AND SWITCHES ARE REACHING THE END OF THERE SERVICE LIVES.

Correction Required: COMPLETELY REWIRE AND REPLACE EXISTING PANELS AND SWITCHES.

Estimated cost of correction: 15000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 123: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 119NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G057 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - WATER TREATMENT PLANT

Complex: 150005 Asset: 00000030-0 Compass: 15000500000030-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPAIR SETTLING BASIN WALL LEAKS AND STORAGE TANKS

Component: 9.5

Description of Deficiency: MOST OF THE WATER TREATMENT PLANT STRUCTURES, TANKS, SYSTEMS AND EQUIPMENT ARE NEAR END OF USEFUL MAINTAINABLE LIFE.

Correction Required: REWORK, REBUILD AND RENOVATE WATER TREATMENT STRUCTURES, TANKS, SYSTEMS AND VARIOUS EQUIPMENT AS OUTLINED IN STEAM AND WATER UTILITY MASTER PLAN BY WILEY & WILSON, COMM. NO. 205204.00.

Estimated cost of correction: 1235000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 124: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 120NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M030 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - WATER TREATMENT PLANT

Complex: 150005 Asset: 00000030-0 Compass: 15000500000030-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: UPGRADE WATER TREATMENT PLANT

Component: 1.082

Description of Deficiency: THE WATER PLANT IS IN AN AGED CONDITION OVERALL, WITH SOME DETERIORATED OR OUTDATED EQUIPMENT NEEDING PROMPT ATTENTION. EQUIPMENT AND SYSTEMS IN NEED OF UPGRADES INCLUDE: RAW WATER PUMPS; FINISHING WATER PUMP; PLANT SLUDGE HANDLING SYSTEM; SODA ASH FEED SYSTEM; RAW WATER MIXER; AND, FLOCCULATION BASIN BAFFLES. SOME OF THE PARTS NEEDED FOR MAINTENANCE AND REPAIR ARE NO LONGER AVAILABLE FOR SOME OF THESE SYSTEMS.

Correction Required: UPGRADE THE DETERIORATED AND OUTDATED SYSTEMS IN THE WATER TREATMENT PLANT.

Estimated cost of correction: 1400000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 125: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 121NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G058 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BIRD ALUMNI HOUSE

Complex: 150005 Asset: 00000032-0 Compass: 15000500000032-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: MISCELLANEOUS RENOVATION

Component: 9.5

Description of Deficiency: BACK PORCH AREA (WOOD FRAMED) IS SITTING DIRECTLY ON GRADE. DETERIORATION WAS NOTED AT BASE OF WOOD EXIT DOOR. SOME WOOD TRIM IS ALSO SHOWING SIGNS OF DETERIORATION.

Correction Required: DEMOLISH DETERIORATED BACK PORCH AREA (WOOD FRAMED) AND REBUILD. REPAIR, REPLACE AND REPAINT DAMAGED/DETERIORATED WOOD TRIM.

Estimated cost of correction: 55000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 126: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(14) Category Page 122NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G059 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BIRD ALUMNI HOUSE

Complex: 150005 Asset: 00000032-0 Compass: 15000500000032-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE WINDOWS

Component: 1.042

Description of Deficiency: THE EXISTING OLD, WOOD WINDOWS WITH ALUMINUM STORM WINDOWS HAVE BECOME DIFFICULT TO OPERATE AND MAINTAIN. IN ADDITION, THE WINDOWS ARE SINGLE PANE GLASS AND ENERGY INEFFICIENT. THE HOLLOW METAL FRAME AND METAL DOORS (AT BACK OF BUILDING) ARE NEAR END OF USEFUL LIFE.

Correction Required: REPLACE THE EXISTING, OLD, WOOD WINDOWS (AND STORM WINDOWS) WITH NEW, OPERABLE WINDOWS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING.

Estimated cost of correction: 30000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 127: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 123NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E034 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - APARTMENT 6 - 7 - 8

Complex: 150005 Asset: 00000034-0 Compass: 15000500000034-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXISTING FIRE ALARM

Component: 1.102

Description of Deficiency: THE EXISTING FIRE ALARM DOES NOT MEET THE FIRE CODE.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 10000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 128: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 124NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G060 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - APARTMENT 6 - 7 - 8

Complex: 150005 Asset: 00000034-0 Compass: 15000500000034-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: RENOVATE BUILDING

Component: 9.500

Description of Deficiency: BUILDING IS IN POOR OVERALL CONDITION DUE TO AGE AND HEAVY USE. MAJOR CRACKS IN WALLS DUE TO SETTLEMENT.

Correction Required: RENOVATE BUILDING TO INCLUDE REPAIR OF EXTERIOR WALLS (ALSO SHOWN AS A SEPARATE DEFICIENCY); REPLACE SGL PANE WINDOWS WITH DBL PANE LOW MAINTENANCE UNITS; REPLACE EXTERIOR DOORS AND HARDWARE; REPAIR ALL INTERIOR WALL CRACKS; REPLACE CARPET AND TILE; PAINT INTERIOR FINISHES; RENOVATE BATHROOMS TO INCLUDE LAVATORIES, CABINETRY, SHOWERS / TUBS; FIXTURES, HARDWARE AND APPURTENANCES; REPLACE KITCHEN CABINETS, FIXTURES, APPLIANCES.

Estimated cost of correction: 600000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 129: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 125NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G061 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - APARTMENT 6 - 7 - 8

Complex: 150005 Asset: 00000034-0 Compass: 15000500000034-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR EXTERIOR WALL SETTLEMENT

Component: 1.041

Description of Deficiency: NORTH SIDE WALL FOUNDATION AND STEPS HAVE MAJOR SETTLEMENT AND CRACKS.

Correction Required: STABILIZE FOUNDATION BY INJECTION OF GROUT UNDER FOOTING. CAULK CRACKS AS NEEDED. REBUILD STEPS.

Estimated cost of correction: 4000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 130: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 126NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M031 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HINDS UNIVERSITY CENTER

Complex: 150005 Asset: 00000038-0 Compass: 15000500000038-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: MISCELLANEOUS MECHANICAL

Component: 1.082

Description of Deficiency: THE MECHANICAL ROOM DOES NOT HAVE ADEQUATE VENTILATION AND EXHAUST. VAV VALVES THROUGHOUT THE BUILDING EXHIBIT A SYSTEMIC FLAW AND ARE PRONE TO LEAKING.

Correction Required: PROVIDE PROPER VENTILATION FOR MECHANICAL SPACE. REPAIR OR REPLACE VAV VALVES.

Estimated cost of correction: 90000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 131: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 127NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G062 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HINDS UNIVERSITY CENTER

Complex: 150005 Asset: 00000038-0 Compass: 15000500000038-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: EXTERIOR WALL SURFACES (SYNTHETIC STUCCO) APPEARS TO BE IN FAIR CONDITION, EXCEPT FOR MINOR CRACKING. SOME CAULK JOINTS ARE SHOWING SIGNS OF DETERIORATION.

Correction Required: REPAIR AND RE-CAULK EXTERIOR WALL SURFACES (SYNTHETIC STUCCO) AND JOINTS PER MANUFACTURER'S DIRECTION AND RECOMMENDATIONS.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 132: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 128NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G063 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HINDS UNIVERSITY CENTER

Complex: 150005 Asset: 00000038-0 Compass: 15000500000038-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE DAMAGED METAL ROOF

Component: 1.05

Description of Deficiency: METAL PANEL ROOF (AT LOWER ROOF OVER STOREROOM) APPEARS TO HAVE BEEN SEVERELY DAMAGED.

Correction Required: REMOVE AND REPLACE DAMAGED METAL PANEL ROOF.

Estimated cost of correction: 15000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 133: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 129NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G064 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - KILLIAN ANNEX

Complex: 150005 Asset: 00000039-0 Compass: 15000500000039-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE BUILT-UP ROOF

Component: 1.05

Description of Deficiency: THE EXISTING BUILT-UP ROOF ON THIS BUILDING HAS SOFT SPOTS, BUBBLES AND MULTIPLE PATCHES. ROOF APPEARS TO BE AT END OF USEFUL LIFE.

Correction Required: REMOVE EQUIPMENT NOT ON CURBS, AND ALL ROOFING MATERIALS, TO EXPOSE STRUCTURAL DECK. REPAIR DECK AS REQUIRED. INSTALL NEW, CORRECTLY DETAILED FLASHING, EXPANSION JOINTS, DRAINS OR GUTTERS AND OTHER RELATED COMPONENTS. INSTALL MEMBRANE OVER NEW INSULATION HAVING A MINIMUM R-20 VALUE AND MINIMUM SLOPE OF ONE QUARTER INCH PER FOOT. COST ESTIMATE ASSUMES A HIGH QUALITY SYSTEM OF BUILT-UP, SINGLE PLY OR EQUIVALENT TYPE WITH A LIGHT COLORED OR REFLECTIVE SURFACE.

Estimated cost of correction: 210000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 134: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 130NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G065 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - KILLIAN ANNEX

Complex: 150005 Asset: 00000039-0 Compass: 15000500000039-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: DECORATIVE MASONRY AT/ABOVE WINDOWS ARE STAINED AND SHOWING SIGNS OF DETERIORATION

Correction Required: CLEAN DECORATIVE MASONRY AT/ABOVE WINDOWS. REMOVE DETERIORATED CAULKING AND REPLACE. SEAL MASONRY SURFACES TO PREVENT FURTHER DETERIORATION.

Estimated cost of correction: 208000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 135: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 131NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M032 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - KILLIAN ANNEX

Complex: 150005 Asset: 00000039-0 Compass: 15000500000039-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 6 Years

Deficiency Title: REPLACE AIR HANDLING UNIT AND CONTROLS

Component: 1.082

Description of Deficiency: THE AIR HANDLING UNIT SERVING THE FIRST FLOOR IS DETERIORATING AND REQUIRING INCREASED MAINTENANCE. MULTIZONE AHU SERVING FIRST FLOOR. THE HVAC CONTROLS IN DIFFERENT PARTS OF THE BUILDING ARE NOT COMPATIBLE WITH EACH OTHER. THE CHILLER SERVING THIS BUILDING OPERATES ON A DIFFERENT CONTROL SYSTEM, AND THE SYSTEMS DO NOT OPERATE OPTIMALLY.

Correction Required: BUDGET FOR REBUILDING OR REPLACING THE AIR HANDLING UNIT SERVING THE FIRST FLOOR WITHIN 6 YEARS. UPGRADE HVAC CONTROLS TO PROVIDE PROPER COORDINATION AND OPERATION OF EQUIPMENT.

Estimated cost of correction: 125000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 136: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(09) Category Page 132NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M033 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - KILLIAN ANNEX

Complex: 150005 Asset: 00000039-0 Compass: 15000500000039-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE COOLING TOWER

Component: 1.082

Description of Deficiency: COOLING TOWER IS DETERIORATED WITH AGE, HAS BECOME CORRODED, AND LEAKS.

Correction Required: REPLACE THE COOLING TOWER.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 137: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 133NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G066 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - SCOTT DORMITORY

Complex: 150005 Asset: 00000040-0 Compass: 15000500000040-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: COMPLETE BUILDING RENOVATION

Component: 9.1

Description of Deficiency: ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL SYSTEMS IN THIS 39 YEAR OLD RESIDENCE HALL ARE AT THE END OF USEFUL LIFE. ORIGINAL, METAL, SINGLE GLAZED WINDOWS (AT LOBBY STOREFRONTS) AND MOST EXTERIOR DOORS ARE IN POOR OPERATING CONDITION. BUILDING DOES NOT COMPLY WITH CURRENT LIFE SAFETY AND ADA CODES (BUT DOES HAVE RECENTLY REWORKED EXISTING ELEVATORS). HEATING AND VENTILATION SYSTEMS DO NOT COMPLY WITH CURRENT STANDARDS FOR COMFORT AND HEALTH. ROOFS (BOTH BUILT-UP MAIN AND LOBBY ROOFS) ARE ALSO IN POOR CONDITION.

Correction Required: REMOVE ALL EXISTING INTERIOR SYSTEMS, AND REVISE INTERIOR PLANS AS REQUIRED BY FUNCTIONS AND CODES. REMOVE (ABATE) ALL HAZARDOUS MATERIALS ASSOCIATED WITH RENOVATION. CONSTRUCT NEW INTERIOR SPACES INCLUDING ALL ARCHITECTURAL SYSTEMS AND FINISHES. INSTALL NEW STOREFRONT SYSTEMS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. REPLACE DAMAGED AND DETERIORATED EXTERIOR DOORS, DOOR FRAMES AND HARDWARE. INSTALL NEW LIGHTING, FIRE ALARMS, ELECTRICAL AND MECHANICAL SERVICE SYSTEMS AS REQUIRED BY CURRENT STANDARDS AND BUILDING CODES. RENOVATE EXTERIOR BUILDING ENTRY WAYS (INCLUDING, DOOR FRAMES, DOORS, HARDWARE, SURROUNDS AND STEPS). REMOVE ALL ROOF MATERIALS (BUILT-UP ROOFS AT BOTH MAIN AND LOBBY) TO EXPOSE STRUCTURAL DECK AND REPAIR AS REQUIRED. INSTALL NEW FLASHING, EXPANSION JOINTS, AND DRAINS AS NEEDED. INSTALL MEMBRANE OVER NEW INSULATION (MINIMUM R-20) AT MINIMUM SLOPE OF 1/4 INCH PER FOOT. COST ESTIMATE ASSUMES HIGH QUALITY BUILT-UP, SINGLE PLY OR OTHER SYSTEM, WITH A LIGHT REFLECTIVE SURFACE.

Estimated cost of correction: 27650000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Page 138: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 139: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 134NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G067 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - UNIVERSITY PRINT SHOP

Complex: 150005 Asset: 00000042-0 Compass: 15000500000042-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: MISCELLANEOUS RENOVATION

Component: 9.5

Description of Deficiency: SUSPENDED CEILING TILE (BUILDING-WIDE) IS IN POOR CONDITION. IN ADDITION, RESTROOMS ARE NOT ADA ACCESSIBLE AND ARE NEAR/AT END OF LIFE.

Correction Required: REMOVE AND REPLACE DAMAGED AND DETERIORATED SUSPENDED CEILING TILE (BUILDING-WIDE). RENOVATE EXISTING RESTROOMS TO COMPLY WITH ADA.

Estimated cost of correction: 95000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 140: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 135NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G068 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - UNIVERSITY PRINT SHOP

Complex: 150005 Asset: 00000042-0 Compass: 15000500000042-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE SINGLE PLY AND CORRUGATED METAL ROOFS

Component: 1.05

Description of Deficiency: APPROX. 15 YEAR OLD SINGLE-PLY ROOF IS LIKELY NEARING END OF USEFUL LIFE. ACCESS TO ROOF WAS NOT AVAILABLE AT TIME OF SURVEY. IN ADDITION, CORRUGATED METAL PANEL COVERED SHED ROOF AT BACK OF BUILDING IS ALSO IN A STATE OF DISREPAIR.

Correction Required: REMOVE ALL ROOF MEMBRANE TO EXPOSE STRUCTURAL DECK AND REPAIR AS REQUIRED. INSTALL NEW FLASHING, EXPANSION JOINTS AND DRAINS AS NEEDED. INSTALL MEMBRANE OVER NEW INSULATION (MINIMUM R-20) AT MINIMUM SLOPE OF ONE QUARTER INCH PER FOOT. COST ESTIMATE ASSUMES HIGH QUALITY BUILT-UP, SINGLE PLY OR OTHER SYSTEM WITH A LIGHT, REFLECTIVE SURFACE. DISMANTLE AND REBUILD CORRUGATED METAL SHED ROOF AND STRUCTURAL SUPPORTS AT BACK OF BUILDING.

Estimated cost of correction: 88000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 141: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 136NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M034 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - UNIVERSITY PRINT SHOP

Complex: 150005 Asset: 00000042-0 Compass: 15000500000042-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: HVAC UPGRADE

Component: 1.082

Description of Deficiency: THE PRINT SHOP HVAC SYSTEM IS INADEQUATE TO CONTROL TEMPERATURE AND HUMIDITY. IN THE BANNER AREA, THE WINTERTIME HUMIDITY IS TOO LOW, NECESSITATING A PORTABLE HUMIDIFIER. THE AIR HANDLERS ARE SUPPLY AND RETURN ONLY, WITH NO OUTSIDE AIR THROUGH THE AIR HANDLERS. THIS LEAVES HEAVY CONCENTRATIONS OF CHEMICAL VAPORS IN THE PRINT SHOP.

Correction Required: PROVIDE A COMPLETE HVAC UPGRADE AT THE PRINT SHOP, ALLOWING ADEQUATE VENTILATION AND SEPARATE ZONE CONTROL OF TEMPERATURE AND HUMIDITY.

Estimated cost of correction: 200000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 142: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 137NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M035 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - UNIVERSITY PRINT SHOP

Complex: 150005 Asset: 00000042-0 Compass: 15000500000042-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: PROVIDE FIRE SPRINKLER SYSTEM

Component: 1.083

Description of Deficiency: THE PRINT SHOP HAS NO SPRINKLER SYSTEM, DESPITE THE PRESENCE OF FLAMMABLE CHEMICALS AND PAPERS USED IN PRINTING PROCESSES.

Correction Required: PROVIDE A FIRE PROTECTION SPRINKLER SYSTEM.

Estimated cost of correction: 150000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 143: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 138NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G069 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FORSYTH BUILDING

Complex: 150005 Asset: 00000043-0 Compass: 15000500000043-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: THE CAULK JOINTS AT THE LIMESTONE PANELS HAVE DETERIORATED WHICH COULD LEAD TO WATER INFILTRATION INTO THE BUILDING.

Correction Required: REMOVE THE OLD DETERIORATED CAULKING AND INSTALL NEW CAULK MATERIAL AS REQUIRED AT LIMESTONE PANELS.

Estimated cost of correction: 65000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 144: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 139NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M036 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FORSYTH BUILDING

Complex: 150005 Asset: 00000043-0 Compass: 15000500000043-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: HVAC UPGRADE

Component: 1.082

Description of Deficiency: ALL NINE AIR HANDLING UNITS IN FORSYTH BUILDING ARE OVER FORTY YEARS OLD. DUCTWORK SERVING THESE AIR HANDLERS IS DIRTY AND NEEDS CLEANING. CHILLED WATER AND HOT WATER PIPING SERVING THE AIR HANDLERS IS AGING AND CORRODED.

Correction Required: REPLACE ALL AIR HANDLERS WITH MODERN UNITS. CLEAN, REZONE AND TAB ALL HVAC DUCTWORK. REPLACE CHILLED WATER AND HOT WATER PIPING.

Estimated cost of correction: 700000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 145: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 140NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E035 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FORSYTH BUILDING

Complex: 150005 Asset: 00000043-0 Compass: 15000500000043-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE EXISTING LIGHTING

Component: 1.092

Description of Deficiency: THE EXISTING LIGHTS ARE OLD AND ARE NOT ENERGY FRIENDLY

Correction Required: INSTALL ENERGY SAVING LIGHTS

Estimated cost of correction: 10000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 146: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 141NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E036 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FORSYTH BUILDING

Complex: 150005 Asset: 00000043-0 Compass: 15000500000043-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXIT LIGHTS

Component: 1.101

Description of Deficiency: THE EXIT LIGHTING IN THIS BUILDING DOES NOT MEET CODE AND DOI STANDARDS.

Correction Required: INSTALL EXIT LIGHTING IN THIS BUILDING. ENSURE THAT THE NEW EXIT LIGHTS ARE LED AND THAT ALL LIGHTING CODE REQUIREMENTS ARE MET.

Estimated cost of correction: 10000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 147: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 142NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G070 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: ADA CORRECTIONS

Component: 9.4

Description of Deficiency: BUILDING DOES NOT COMPLY WITH ADA GUIDELINES AND APPLICABLE SECTIONS OF THE STATE BUILDING CODE.

Correction Required: RENOVATE COMPONENTS OF THE BUILDING AS SPECIFIED IN THE CURRENT ADA STUDY. COST ESTIMATE IS BASED ON ESTIMATES IN THE STUDY.

Estimated cost of correction: 463000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 148: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 143NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M037 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 4 Years

Deficiency Title: UPGRADE PLUMBING

Component: 1.081

Description of Deficiency: PLUMBING FIXTURES ARE AGING AND USE EXCESSIVE AMOUNTS OF WATER COMPARED TO CURRENT STANDARDS.

Correction Required: REPLACE PLUMBING FIXTURES WITH LOW FLOW FIXTURES.

Estimated cost of correction: 100000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 149: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 144NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E037 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE EMERGENCY GENERATOR

Component: 1.100

Description of Deficiency: THE EMERGENCY GENERATOR IS REACHING THE END OF IT'S SERVICE LIFE AND NEEDS TO BE REPLACED.

Correction Required: INSTALL A DIESEL GENERATOR TO SUPPLY EMERGENCY POWER

Estimated cost of correction: 50000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 150: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 145NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G071 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPAIR ENTRANCE BRIDGE

Component: 5.1

Description of Deficiency: WATER PENETRATES CONCRETE WALK AND DAMAGES CONCRETE AND STEEL BEAM BELOW. BRICK WALL BELOW BRIDGE HAS SETTLED.

Correction Required: REPAIR DAMAGE AND ADD WATERPROOF COATING TO CONCRETE WALKWAY.

Estimated cost of correction: 18000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 151: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(08) Category Page 146NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M038 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 5 Years

Deficiency Title: RENOVATE HVAC SYSTEM

Component: 1.082

Description of Deficiency: THE EXISTING AIR HANDLING UNITS ARE APPROXIMATELY 30 YEARS OLD, DETERIORATED WITH AGE, AND CORRODED. THE HVAC CONTROLS SYSTEM HAS LIMITED ENERGY CONSERVATION FEATURES. THE COOLING TOWER IS NATURAL DRAFT AND CANNOT CARRY THE FULL LOAD WHEN HUMIDITY IS HIGH.

Correction Required: PROVIDE A NEW CENTRAL HVAC SYSTEM TO REPLACE THE DETERIORATED EQUIPMENT. CONNECT HVAC CONTROLS TO THE ENERGY MANAGEMENT SYSTEM. STUDY THE COOLING TOWER TO DETERMINE IF NATURAL DRAFT IS THE APPROPRIATE APPLICATION. BUDGET FOR FUTURE REPLACEMENT AND ENSURE IT IS SIZED APPROPRIATELY.

Estimated cost of correction: 2900000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 152: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 147NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E038 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE ELECTRICAL PANEL

Component: 1.091

Description of Deficiency: THE EXISTING PANEL IS OLD AND REACHING THE END OF IT'S SERVICE LIFE.

Correction Required: RECOMMEND REPLACING THE OBSOLETE PANEL, WITH A PANEL THAT MEETS NEC REQUIREMENTS.

Estimated cost of correction: 4500 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 153: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 148NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G072 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: UPGRADE ELEVATOR

Component: 1.07

Description of Deficiency: PASSENGER ELEVATOR DOES NOT COMPLY WITH CURRENT CODES AND STANDARDS.

Correction Required: UPGRADE ELEVATOR TO LARGER CAB.

Estimated cost of correction: 120000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 154: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 149NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M039 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: ADD MAKE-UP WATER AT COOLING TOWER

Component: 1.081

Description of Deficiency: THERE IS NO MAKE UP WATER AVAILABLE AT THE COOLING TOWER, MAKING CONTROL AND MAINTENANCE DIFFICULT.

Correction Required: PROVIDE SUPPLY WATER CONNECTION AT THE COOLING TOWER.

Estimated cost of correction: 8000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 155: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 150NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G073 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: LIFE SAFETY CODE CORRECTIONS

Component: 8.1

Description of Deficiency: DOI REPORT INDICATES THAT EXIT AT GLASS STAIR AND AT ROOM 186 DOES NOT COMPLY WITH THE STATE BUILDING CODE. ALSO, WOOD FRAME PARTITIONS IN ROOM 380 ARE NOT FIRE RATED. RAILINGS ON EAST SIDE EXTERIOR STAIR HAS INADEQUATE HANDRAILS.

Correction Required: RENOVATE EXITS, HANDRAILS AND PARTITIONS AS REQUIRED TO COMPLY WITH STATE BUILDING CODE.

Estimated cost of correction: 10000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 156: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 151NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M040 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: INSTALL AN AUTOMATIC FIRE SPRINKLER SYSTEM

Component: 1.083

Description of Deficiency: AS REPORTED BY THE DEPARTMENT OF INSURANCE AND IRI, THIS BUILDING DOES NOT HAVE FIRE PROTECTION IN THE EVENT OF A FIRE.

Correction Required: INSTALL AN AUTOMATIC SPRINKLER SYSTEM IN THIS BUILDING.

Estimated cost of correction: 575000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 157: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 152NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E039 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE EMERGENCY GENERATOR

Component: 1.101

Description of Deficiency: THE ONAN BRAND 15 KW EMERGENCY GENERATOR SYSTEM IS OBSOLETE AND PAST ITS USEFUL LIFE. REPLACEMENT PARTS ARE NO LONGER AVAILABLE.

Correction Required: REPLACE THE EMERGENCY GENERATOR SYSTEM TO INCLUDE THE GENERATOR AND THE AUTOMATIC TRANSFER SWITCH. THE GENERATOR SHOULD BE PROVIDED WITH A SOUND ATTENUATED STORM WEATHER RESISTANT ENCLOSURE.

Estimated cost of correction: 20000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 158: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 153NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E040 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE EXISTING LIGHTING

Component: 1.092

Description of Deficiency: THE EXISTING LIGHTS ARE OLD AND ARE NOT ENERGY FRIENDLY

Correction Required: INSTALL ENERGY SAVING LIGHTS

Estimated cost of correction: 100000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: General Fund = 1Revenue Receipts = 2

Page 159: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(21) Category Page 154NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E041 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - BELK ARTS COMPLEX

Complex: 150005 Asset: 00000044-0 Compass: 15000500000044-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE OBSOLETE ELECTRICAL SWITCHBOARD

Component: 1.091

Description of Deficiency: THE 480Y/277 VOLT MAIN SWITCH BOARD AND ASSOCIATED DISTRIBUTION SECTION WERE MANUFACTURED OVER 37 YEARS AGO BY NOW DEFUNCT FEDERAL PACIFIC COMPANY (FPE). REPLACEMENT PARTS FOR THIS EQUIPMENT ARE ONLY AVAILABLE FROM ELECTRICAL SALVAGE COMPANIES AND ONLY IF THE COMPANIES COINCIDENTLY HAVE THE PARTS IN STOCK. FAILURES OF A BUS OR BREAKER WILL RESULT IN AN EXTENDED ELECTRICAL OUTAGE OF ONE OR MORE CIRCUITS WHILE REPLACEMENT PARTS ARE LOCATED, OR WHILE A REPLACEMENT PANEL IS INSTALLED.

Correction Required: REPLACE THE OBSOLETE ELECTRICAL SWITCHBOARD AND ITS DISTRIBUTION SECTION.

Estimated cost of correction: 40000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 160: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 155NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G074 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HARRILL RESIDENCE

Complex: 150005 Asset: 00000045-0 Compass: 15000500000045-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE FLOOR TILE

Component: 1.062

Description of Deficiency: SOME FLOOR TILE IS IN POOR CONDITION DUE TO AGE AND HEAVY USE.

Correction Required: REPLACE VCT WHERE NEEDED.

Estimated cost of correction: 26000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 161: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 156NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G075 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HARRILL RESIDENCE

Complex: 150005 Asset: 00000045-0 Compass: 15000500000045-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE CEILINGS

Component: 1.063

Description of Deficiency: 2X4 SUSPENDED CEILINGS ARE IN POOR CONDITION, SAGGING, DISCOLORED.

Correction Required: REPLACE 2X4 SYSTEM WITH 2X2 SYSTEM.

Estimated cost of correction: 18000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 162: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 157NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G076 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HARRILL RESIDENCE

Complex: 150005 Asset: 00000045-0 Compass: 15000500000045-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: ADA CORRECTIONS

Component: 9.4

Description of Deficiency: BUILDING DOES NOT COMPLY WITH ADA GUIDELINES AND APPLICABLE SECTIONS OF THE STATE BUILDING CODE.

Correction Required: RENOVATE COMPONENTS OF THE BUILDING AS SPECIFIED IN THE CURRENT ADA STUDY. COST ESTIMATE IS BASED ON ESTIMATES IN THE STUDY.

Estimated cost of correction: 616000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 163: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 158NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G077 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HARRILL RESIDENCE

Complex: 150005 Asset: 00000045-0 Compass: 15000500000045-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: LIFE SAFETY CODE CORRECTIONS

Component: 8.1

Description of Deficiency: TRANSOMS ABOVE CORRIDOR DOORS, EXTERIOR EXIT DOORS, AND SUITE AND STUDY ROOM DOORS DO NOT COMPLY WITH THE STATE BUILDING CODE.

Correction Required: REPLACE THE WOOD TRANSOMS WITH RATED MATERIALS APPROPRIATE FOR AN EXIT CORRIDOR. RENOVATE EXTERIOR EXIT DOORS, SUITE AND STUDY ROOM DOORS TO COMPLY WITH STATE BUILDING CODE. A STUDY TO DETERMINE SCOPE OF WORK AND A COST ESTIMATE IS RECOMMENDED.

Estimated cost of correction: 30000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 164: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 159NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G078 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HARRILL RESIDENCE

Complex: 150005 Asset: 00000045-0 Compass: 15000500000045-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR EXTERIOR WALLS

Component: 1.041

Description of Deficiency: MORTAR JOINTS HAVE CRACKS AT CORNERS AND HORIZONTALLY AT FLOOR LEVEL. SHELF ANGLES AND LINTELS HAVE RUSTED.

Correction Required: REPAIR MORTAR JOINTS AND REPAINT STEEL SHELF ANGLES AND LINTELS.

Estimated cost of correction: 32000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 165: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 160NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E042 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HARRILL RESIDENCE

Complex: 150005 Asset: 00000045-0 Compass: 15000500000045-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXISTING FIRE ALARM

Component: 1.102

Description of Deficiency: THE EXISTING FIRE ALARM DOES NOT MEET THE FIRE CODE.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 125000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 166: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 161NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E043 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HARRILL RESIDENCE

Complex: 150005 Asset: 00000045-0 Compass: 15000500000045-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REWIRE COMPLETELY

Component: 1.091

Description of Deficiency: THE EXISTING WIRE, PANELS, AND SWITCHES ARE REACHING THE END OF THERE SERVICE LIVES.

Correction Required: COMPLETELY REWIRE AND REPLACE EXISTING PANELS AND SWITCHES.

Estimated cost of correction: 100000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 167: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 162NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G079 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HARRILL RESIDENCE

Complex: 150005 Asset: 00000045-0 Compass: 15000500000045-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE DOORS AND HARDWARE

Component: 1.064

Description of Deficiency: SOME DOORS AND HARDWARE ARE IN POOR CONDITION DUE TO AGE AND HEAVY USE.

Correction Required: REPLACE DOORS AND HARDWARE AS NEEDED.

Estimated cost of correction: 36000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 168: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 163NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G080 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HARRILL RESIDENCE

Complex: 150005 Asset: 00000045-0 Compass: 15000500000045-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BATHROOMS

Component: 9.500

Description of Deficiency: BATHROOMS ARE IN POOR CONDITION DUE TO AGE AND HEAVY USE.

Correction Required: RENOVATE BATHROOMS TO INCLUDE WALL, CEILING AND FLOOR FINISHES; NEW VANITIES, SINKS, AND LAVATORIES; TOILETS; SHOWERS; NEW FIXTURES AND HARDWARE. REPAIR / REPLACE PLUMBING AS NEEDED.

Estimated cost of correction: 680000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 169: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 164NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G081 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HARRILL RESIDENCE

Complex: 150005 Asset: 00000045-0 Compass: 15000500000045-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE LOBBY STOREFRONT SYSTEMS

Component: 1.041

Description of Deficiency: ORIGINAL STOREFRONT SYSTEMS ARE DETERIORATED, DIFFICULT TO OPERATE AND MAINTAIN AND ENERGY INEFFICIENT.

Correction Required: REPLACE STOREFRONT SYSTEMS.

Estimated cost of correction: 22000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 170: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 165NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M041 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - HARRILL RESIDENCE

Complex: 150005 Asset: 00000045-0 Compass: 15000500000045-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 4 Years

Deficiency Title: REPLACE AIR COMPRESSOR

Component: 1.082

Description of Deficiency: THE EXISTING AIR COMPRESSOR IS OVER 35 YEARS OLD, BUT IS STILL IN OPERABLE CONDITION.

Correction Required: BUDGET FOR REPLACING AIR COMPRESSOR WITHIN 4 YEARS.

Estimated cost of correction: 4000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 171: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 166NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G082 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - WALKER RESIDENCE

Complex: 150005 Asset: 00000046-0 Compass: 15000500000046-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: COMPLETE BUILDING RENOVATION

Component: 9.1

Description of Deficiency: ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL SYSTEMS IN THIS 36 YEAR OLD RESIDENCE HALL ARE AT THE END OF USEFUL LIFE. ORIGINAL, METAL, SINGLE GLAZED WINDOWS (AT LOBBY STOREFRONTS) AND MOST EXTERIOR DOORS ARE IN POOR OPERATING CONDITION. CAULK JOINTS AT DECORATIVE MASONRY WINDOW SILLS ARE OPEN. BUILDING DOES NOT COMPLY WITH CURRENT LIFE SAFETY AND ADA CODES (BUT DOES HAVE RECENTLY REWORKED, EXISTING ELEVATORS). HEATING AND VENTILATION SYSTEMS DO NOT COMPLY WITH CURRENT STANDARDS FOR COMFORT AND HEALTH.

Correction Required: REMOVE ALL EXISTING INTERIOR SYSTEMS, AND REVISE INTERIOR PLANS AS REQUIRED BY FUNCTIONS AND CODES. REMOVE (ABATE) ALL HAZARDOUS MATERIALS ASSOCIATED WITH RENOVATION. CONSTRUCT NEW INTERIOR SPACES INCLUDING ALL ARCHITECTURAL SYSTEMS AND FINISHES. INSTALL NEW STOREFRONT SYSTEMS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. REPLACE DAMAGED AND DETERIORATED EXTERIOR DOORS, DOOR FRAMES AND HARDWARE. INSTALL NEW LIGHTING, FIRE ALARMS, ELECTRICAL AND MECHANICAL SERVICE SYSTEMS AS REQUIRED BY CURRENT STANDARDS AND BUILDING CODES. RENOVATE EXTERIOR BUILDING ENTRY WAYS (INCLUDING, DOOR FRAMES, DOORS, HARDWARE, SURROUNDS AND STEPS) AND BUILDING ENVELOPE.

Estimated cost of correction: 12600000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 172: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 167NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G083 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - PHYSICAL PLANT

Complex: 150005 Asset: 00000047-0 Compass: 15000500000047-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE BUILT-UP ROOF

Component: 1.05

Description of Deficiency: THE LARGER ROOF SECTION WILL BE NEAR END OF EXPECTED LIFE. SOME REPAIR MAY BE REQUIRED BEFORE FUNDS ARE AVAILABLE FOR REPLACEMENT.

Correction Required: REMOVE ALL ROOF MATERIALS TO EXPOSE STRUCTURAL DECK AND REPAIR AS REQUIRED. INSTALL NEW FLASHING, EXPANSION JOINTS AND DRAINS AS NEEDED. INSTALL MEMBRANE OVER NEW INSULATION (MINIMUM R-20) AT MINIMUM SLOPE OF ONE QUARTER INCH PER FOOT. COST ESTIMATE ASSUMES HIGH QUALITY BUILT-UP, SINGLE PLY OR OTHER SYSTEM WITH A LIGHT, REFLECTIVE SURFACE.

Estimated cost of correction: 90000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 173: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(06) Category Page 168NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M042 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - PHYSICAL PLANT

Complex: 150005 Asset: 00000047-0 Compass: 15000500000047-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE BOILER

Component: 1.082

Description of Deficiency: THE EXISTING BOILER IS APPROXIMATELY 35 YEARS OLD AND IS OVERSIZED FOR THE APPLICATION RESULTING IN INEFFICIENT ENERGY PERFORMANCE.

Correction Required: REPLACE THE BOILER ENSURING IT IS APPROPRIATELY SIZED FOR THE APPLICATION.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 174: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(14) Category Page 169NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G084 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - PHYSICAL PLANT

Complex: 150005 Asset: 00000047-0 Compass: 15000500000047-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 6 Years

Deficiency Title: REPLACE WINDOWS

Component: 1.042

Description of Deficiency: ORIGINAL, SINGLE GLAZED, STEEL WINDOWS ARE IN GOOD CONDITION, HOWEVER, DUE TO LEAKAGE OF OUTDOOR AIR, CONTRIBUTE TO HIGH ENERGY COST.

Correction Required: INSTALL NEW WINDOWS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. A LOWER COST OPTION IS INTERIOR STORM TYPE WINDOWS. COST ESTIMATE IS FOR NEW WINDOWS.

Estimated cost of correction: 30000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 175: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 170NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G085 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENTS

Complex: 150005 Asset: 00000048-0 Compass: 15000500000048-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: LIFE SAFETY CODE CORRECTIONS

Component: 8.1

Description of Deficiency: DOI REPORT INDICATES THAT DRAFT-STOPPING PARTITIONS IN ATTIC MAY NOT ALIGN WITH APARTMENT PARTY WALLS.

Correction Required: VERIFY CONSTRUCTION IN ATTIC AND CORRECT AS REQUIRED TO COMPLY WITH CODE.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 176: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 171NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E044 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENTS

Complex: 150005 Asset: 00000048-0 Compass: 15000500000048-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXISTING FIRE ALARM

Component: 1.102

Description of Deficiency: THE EXISTING FIRE ALARM DOES NOT MEET THE FIRE CODE.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 177: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 172NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G086 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENTS

Complex: 150005 Asset: 00000048-0 Compass: 15000500000048-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: ARCHITECTURAL RENOVATION

Component: 9.500

Description of Deficiency: WOOD WINDOWS ARE IN POOR CONDITION; BATHROOMS AND KITCHENS ARE DETERIORATED DUE TO AGE AND WEAR; ASPHALT SHINGLE ROOF IS BEYOND END OF USEFUL LIFE; EXTERIOR CONCRETE BALCONY AND DECKS ARE SPALLING, CRACKING AND NEED EXTENSIVE REPAIR

Correction Required: RENOVATE BUILDING TO INCLUDE REPAIR OF EXTERIOR CONCRETE BALCONY AND DECKS; REPLACE KITCHEN CABINETS, APPLIANCES, FIXTURES; RENOVATE BATHROOMS TO INCLUDE VANITIES AND LAVATORIES, TOILETS, SHOWERS AND BATHS, FIXTURES AND APPURTENANCES; REPLACE VCT; ABATE VAT AND REPLACE WITH VCT; PAINT WALLS AND CEILINGS; REPAIR PELLA WOOD WINDOWS; CLEAN AND PAINT EXTERIOR TRIM.

Estimated cost of correction: 980000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 178: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(14) Category Page 173NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G087 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - JORDAN-PHILIPS FIELD HOUSE

Complex: 150005 Asset: 00000049-0 Compass: 15000500000049-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 5 Years

Deficiency Title: REPLACE WINDOWS

Component: 1.042

Description of Deficiency: ORIGINAL, SINGLE GLAZED, ALUMINUM WINDOWS ARE NEAR END OF EXPECTED LIFE, IN POOR OPERATING CONDITION AND DUE TO LEAKAGE OF OUTDOOR AIR, CONTRIBUTE TO HIGH ENERGY COST AND DISCOMFORT OF OCCUPANTS.

Correction Required: INSTALL NEW WINDOWS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. A LOWER COST OPTION IS INTERIOR STORM TYPE WINDOWS. COST ESTIMATE IS FOR NEW WINDOWS.

Estimated cost of correction: 36000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 179: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(06) Category Page 174NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M043 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - JORDAN-PHILIPS FIELD HOUSE

Complex: 150005 Asset: 00000049-0 Compass: 15000500000049-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: PROVIDE WATER HEATER

Component: 1.082

Description of Deficiency: THE EXISTING BOILER PROVIDES HEATING HOT WATER FOR SPACE HEATING, AS WELL AS DOMESTIC HOT WATER. THE BOILER RUNS IN SUMMER TO PROVIDE DOMESTIC HOT WATER WHEN THERE IS NO OTHER HEATING LOAD. THE BOILER IS OVERSIZED FOR THIS APPLICATION.

Correction Required: INSTALL A NEW WATER HEATER TO PROVIDE HOT WATER FOR SHOWERS AND LAVATORIES DURING THE NON-HEATING SEASON.

Estimated cost of correction: 6000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 180: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 175NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E045 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - NATURAL SCIENCE BUILDING

Complex: 150005 Asset: 00000050-0 Compass: 15000500000050-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE EMERGENCY GENERATORS

Component: 1.101

Description of Deficiency: TWO GENERATORS, ONE AT 480Y/277 VOLTS AND ANOTHER AT 208Y/120 VOLTS, SERVE THIS ASSET. BOTH GENERATOR SYSTEMS ARE OBSOLETE, AND BOTH HAVE ABOVE GROUND FUEL STORAGE TANKS WITHOUT SPILL PREVENTION OR LEAK DETECTION/CONTAINMENT AND UNPROTECTED FUEL LINES.

Correction Required: RECOMMEND REPLACING BOTH EMERGENCY GENERATOR SYSTEMS WITH ONE 480Y/277 VOLT SYSTEM AND A STEP DOWN TRANSFORMER FOR THE 208Y/120 VOLTS LOADS. THE SYSTEM SHOULD INCLUDE A GENERATOR AND AUTOMATIC TRANSFER SWITCH, AND A CODE COMPLIANT FUEL STORAGE SYSTEM. IF THE REPLACEMENT GENERATOR IS TO BE INSTALLED OUTSIDE THE BUILDING IT SHOULD BE PROVIDED WITH A SOUND ATTENUATED STORM WEATHER RESISTANT ENCLOSURE.

Estimated cost of correction: 40000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 181: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 176NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G088 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - NATURAL SCIENCE BUILDING

Complex: 150005 Asset: 00000050-0 Compass: 15000500000050-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: COMPLETE BUILDING RENOVATION

Component: 9.1

Description of Deficiency: ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL SYSTEMS IN THIS 31 YEAR OLD SCIENCE BUILDING ARE AT THE END OF THEIR EXPECTED USEFUL LIFE. EXTERIOR, PRECAST CONCRETE PANELS ARE SHOWING MAJ0R SIGNS OF DETERIORATION. ORIGINAL, METAL, SINGLE GLAZED WINDOWS AND MOST EXTERIOR DOORS ARE IN FAIR TO POOR OPERATING CONDITION. BUILDING DOES NOT FULLY COMPLY WITH CURRENT LIFE SAFETY AND ADA CODES (BUILDING DOES HAVE AN EXISTING ELEVATOR BUT IT REQUIRES CONSTANT MAINTENANCE). HEATING AND VENTILATION SYSTEMS DO NOT COMPLY WITH CURRENT STANDARDS FOR COMFORT AND HEALTH. ROOFS (SINGLE PLY ROOF AT MAIN PORTION AND BUILT-UP ROOF AT CONNECTOR) ARE ALSO NEARING END OF USEFUL LIFE.

Correction Required: REMOVE ALL EXISTING INTERIOR SYSTEMS, AND REVISE INTERIOR PLANS AS REQUIRED BY FUNCTIONS AND CODES. REMOVE (ABATE) ALL HAZARDOUS MATERIALS ASSOCIATED WITH RENOVATION. CONSTRUCT NEW INTERIOR SPACES INCLUDING ALL ARCHITECTURAL SYSTEMS AND FINISHES. INSTALL NEW OPERABLE WINDOWS WITH THERMAL BREAK FRAMES AND INSULATED GLASS WITH LOW E COATING. REPLACE DAMAGED AND DETERIORATED EXTERIOR DOORS, DOOR FRAMES AND HARDWARE. INSTALL NEW LIGHTING, FIRE ALARMS, ELECTRICAL AND MECHANICAL SERVICE SYSTEMS AS REQUIRED BY CURRENT STANDARDS AND BUILDING CODES. REPLACE DAMAGED AND DETERIORATED EXTERIOR, PRECAST CONCRETE PANELS. RENOVATE EXTERIOR BUILDING ENTRY WAYS (INCLUDING, DOOR FRAMES, DOORS, HARDWARE, SURROUNDS AND STEPS). UPGRADE AND MODERNIZE ELEVATOR. REMOVE ALL ROOF MATERIALS (SINGLE PLY AND BUILT-UP ROOFS) TO EXPOSE STRUCTURAL DECK AND REPAIR AS REQUIRED. INSTALL NEW FLASHING, EXPANSION JOINTS, AND DRAINS AS NEEDED. INSTALL MEMBRANE OVER NEW INSULATION (MINIMUM R-20) AT MINIMUM SLOPE OF 1/4 INCH PER FOOT (SINGLE

Page 182: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

PLY ROOF). COST ESTIMATE ASSUMES HIGH QUALITY BUILT-UP, SINGLE PLY OR OTHER SYSTEM, WITH A LIGHT REFLECTIVE SURFACE.

Estimated cost of correction: 13515000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 183: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 177NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G089 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - E.J. WHITMIRE STADIUM

Complex: 150005 Asset: 00000051-0 Compass: 15000500000051-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: ADA CORRECTIONS

Component: 9.4

Description of Deficiency: BUILDING DOES NOT COMPLY WITH ADA GUIDELINES AND APPLICABLE SECTIONS OF THE STATE BUILDING CODE.

Correction Required: RENOVATE COMPONENTS OF THE BUILDING AS SPECIFIED IN THE CURRENT ADA STUDY. COST ESTIMATE IS BASED ON ESTIMATES IN THE STUDY.

Estimated cost of correction: 30000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 184: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 178NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G090 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - E.J. WHITMIRE STADIUM

Complex: 150005 Asset: 00000051-0 Compass: 15000500000051-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE CANVAS AWNING ROOF

Component: 1.05

Description of Deficiency: CANVAS AWNING ROOF, THAT SHADES WEST GLASS, IS DIFFICULT TO MOUNT AND TAKE DOWN FOR STORAGE. THIS REQUIRES 8 MECHANICS WITH SAFETY HARNESS ABOUT 2 DAYS TO INSTALL.

Correction Required: WHEN CANVAS AWNING IS NEAR END OF USEFUL LIFE, REPLACE IT WITH A PERMANENT FIXED TEFLON COATED FABRIC AWNING.

Estimated cost of correction: 35000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 185: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 179NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E046 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - E.J. WHITMIRE STADIUM

Complex: 150005 Asset: 00000051-0 Compass: 15000500000051-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REWIRE COMPLETELY

Component: 1.091

Description of Deficiency: THE EXISTING WIRE, PANELS, AND SWITCHES ARE REACHING THE END OF THERE SERVICE LIVES.

Correction Required: COMPLETELY REWIRE AND REPLACE EXISTING PANELS AND SWITCHES.

Estimated cost of correction: 15000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 186: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 180NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G091 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - E.J. WHITMIRE STADIUM

Complex: 150005 Asset: 00000051-0 Compass: 15000500000051-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR ROOF

Component: 1.050

Description of Deficiency: DUE TO CAMERA TRIPODS, CIGARETTE BUTTS AND HEAVY USE - THE ROOF OVER THE PRESS BOX HAS LEAKS AND REQUIRES CONSTANT MAINTENANCE.

Correction Required: REMOVE ALL ROOF MATERIAL TO EXPOSE STRUCTURAL DECK. REPAIR DECK AND DRAINS AS NEEDED. INSTALL NEW FLASHING, EXPANSION JOINTS AND NEW INSULATION (MINIMUM R-20). INSTALL INSULATION TO INSURE POSITIVE DRAINAGE. INSTALL NEW BUILT UP ROOF OR MEMBRANE ROOF. COST ESTIMATE ASSUMES HIGH QUALITY ROOF. REPAIR OR REPLACE DRAINAGE SYSTEMS AS NEEDED. INSTALL CLOSE FITTING PAVERS TO PROTECT THE ROOF.

Estimated cost of correction: 60000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 187: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 181NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G092 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - E.J. WHITMIRE STADIUM

Complex: 150005 Asset: 00000051-0 Compass: 15000500000051-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPAIR & WATERPROOF STRUCTURE AND SEATS

Component: 9.5

Description of Deficiency: WATER PENETRATION HAS DAMAGED THE CONCRETE STRUCTURE AND STEEL COMPONENTS ARE RUSTED. SOME ALUMINUM SEATS ON STEEL BRACKETS ARE LOOSE AND BOLTS ARE WEAK. ALSO, SOME AREAS OF STEEL HANDRAILS ARE RUSTED AND CAULKING IS DETERIORATED.

Correction Required: REMOVE SEATS AND TIGHTEN AS REQUIRED. REMOVE ANY DAMAGED COMPONENTS THAT ARE NOT REPAIRABLE. REPLACE CAULKING WHERE NEEDED. REMOVE RUST AND REPAINT ALL EXPOSED STEEL. CLEAN CONCRETE SURFACES AND APPLY A WATERPROOFING COATING.

Estimated cost of correction: 600000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 188: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 182NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G093 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - E.J. WHITMIRE STADIUM

Complex: 150005 Asset: 00000051-0 Compass: 15000500000051-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE INTERIOR FINISHES

Component: 9.5

Description of Deficiency: CONCRETE FLOORS IN TOILETS AND CONCESSIONS SALES HAVE CRACKS. TOILET IN PRESS BOX NEEDS RENOVATION. TOILET ENTRANCE HAS LOW HEAD CLEARANCE AND ELECTRICAL ROOM HAS COMBUSTIBLE STORAGE NEXT TO AMPLIFIER.

Correction Required: PATCH CRACKS IN FLOOR, CLEAN AND APPLY WATERPROOF SEALER. RENOVATE TOILET IN PRESS BOX AND CORRECT OTHER ITEMS.

Estimated cost of correction: 12000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 189: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 183NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E047 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - H.F. ROBINSON ADMIN. BLDG.

Complex: 150005 Asset: 00000081-0 Compass: 15000500000081-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE EMERGENCY GENERATOR

Component: 1.100

Description of Deficiency: THE EMERGENCY GENERATOR IS REACHING THE END OF IT'S SERVICE LIFE AND NEEDS TO BE REPLACED.

Correction Required: INSTALL A DIESEL GENERATOR TO SUPPLY EMERGENCY POWER

Estimated cost of correction: 50000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 190: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(08) Category Page 184NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M044 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - H.F. ROBINSON ADMIN. BLDG.

Complex: 150005 Asset: 00000081-0 Compass: 15000500000081-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: HVAC UPGRADE

Component: 1.082

Description of Deficiency: THE FIFTH FLOOR OF H.F. ROBINSON BUILDING HAS INADEQUATE COOLING IN THE SUMMER, AFFECTING THE CHANCELLOR'S AND OTHER OFFICES. IN THE WINTER, THE FIRST FLOOR OF THIS BUILDING IS COLD, ESPECIALLY IN THE LOBBY AREA. THE BUILDING IS UNDER NEGATIVE PRESSURE DUE PARTIALLY TO A LARGE, IMPROPERLY CONTROLLED EXHAUST FAN ON THE ROOF. ADDITIONALLY, THE OUTSIDE AIR INTAKES ARE VERY SMALL FOR BOTH AIR HANDLERS. LIGHT MACHINERY NOISE CAN BE HEARD ON THE CHANCELLOR'S RECEPTION AREA. THIS IS PROBABLY DUCT NOISE UNRELATED TO THE ROOFTOP EXHAUST FAN.

Correction Required: PERFORM A COMPLETE HVAC ANALYSIS OF H.F. ROBINSON BUILDING. INVESTIGATE THIS BUILDING FOR TEST AND BALANCE PROBLEMS. PROVIDE ADDITIONAL COOLING FOR THE FIFTH FLOOR OFFICES, POSSIBLY WITH A ROOF MOUNTED DX UNIT. A PREHEATED MAKEUP AIR UNIT IS ALSO RECOMMENDED.

Estimated cost of correction: 400000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 191: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 185NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G094 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - H.F. ROBINSON ADMIN. BLDG.

Complex: 150005 Asset: 00000081-0 Compass: 15000500000081-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: ADA CORRECTIONS

Component: 9.4

Description of Deficiency: BUILDING DOES NOT COMPLY WITH ADA GUIDELINES AND APPLICABLE SECTIONS OF THE STATE BUILDING CODE.

Correction Required: RENOVATE COMPONENTS OF THE BUILDING AS SPECIFIED IN THE CURRENT ADA STUDY. COST ESTIMATE IS BASED ON ESTIMATES IN THE STUDY.

Estimated cost of correction: 158000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 192: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 186NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E048 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - H.F. ROBINSON ADMIN. BLDG.

Complex: 150005 Asset: 00000081-0 Compass: 15000500000081-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: PROVIDE EGRESS LIGHTING

Component: 1.092

Description of Deficiency: THE AUDITORIUM VESTIBULE DOES NOT HAVE EMERGENCY EGRESS LIGHTING. VESTIBULE LIGHTING IS NOT SUPPORTED BY THE EMERGENCY GENERATOR.

Correction Required: PROVIDE EMERGENCY EGRESS LIGHTING FOR THE AUDITORIUM VESTIBULE. IF BATTERY POWERED EGRESS LUMINARIES ARE PROVIDED, ENSURE THAT THEY ARE ENERGIZED FROM THE UNSWITCHED PORTION OF THE VESTIBULE LIGHTING CIRCUIT. IF THE EXISTING LUMINARIES ARE RECIRCUITED TO A GENERATOR CIRCUIT, ENSURE THAT THE BALLAST(S) ARE REPLACED TO A TYPE THAT WILL ENERGIZE THE LAMPS FROM A GENERATOR CIRCUIT UPON SENSING DE-ENERIZATION OF THE NORMAL CIRCUIT.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 193: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 187NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E049 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - H.F. ROBINSON ADMIN. BLDG.

Complex: 150005 Asset: 00000081-0 Compass: 15000500000081-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE LIGHTING

Component: 1.092

Description of Deficiency: THE SECOND FLOOR LOBBY IS ILLUMINATED BY 100 WATT HIGH INTENSITY DISCHARGE (HID) FIXTURES. UPON THE RESTORATION OF POWER AFTER AN ELECTRICAL OUTAGE EVENT, EITHER UPON CONNECTION TO THE EMERGENCY GENERATOR OR UPON RESTORATION OF THE UTILITY, THE SECOND FLOOR LOBBY WILL BE DARK FOR THE TIME REQUIRED FOR THE HID LIGHTING TO RECOVER. AGED HID LAMPS CAN REQUIRE AS LONG AS 30 MINUTES TO RECOVER. THESE 29 YEAR OLD LUMINARIES ARE NOT AS EFFECTIVE OR EFFICIENT AS RECENTLY DEVELOPED FLORESCENT LUMINARIES FOR A SIMILAR APPLICATION.

Correction Required: RECOMMEND A DESIGNED RENOVATION OF THE SECOND FLOOR LOBBY LIGHTING TO COMPLY WITH NC BUILDING CODE AND NC ENERGY CODE, AND TO FOLLOW RECOMMENDATIONS OF THE ILLUMINATING ENGINEERING SOCIETY (IES) FOR ILLUMINATING SIMILAR SPACES. SPECIAL CONSIDERATION SHOULD BE MADE FOR EGRESS LIGHTING OF THE SPACE BEING ENERGIZED BY A GENERATOR.

Estimated cost of correction: 8000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 194: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 188NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G095 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - H.F. ROBINSON ADMIN. BLDG.

Complex: 150005 Asset: 00000081-0 Compass: 15000500000081-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: ENGINEERING STUDY

Component: 1.041

Description of Deficiency: FRONT GALLERY SERVES AS MUSEUM AND RECEIVES DIRECT AFTERNOON SUNLIGHT THROUGH LARGE WINDOWS. SUNLIGHT CAUSES HEAT GAIN AND DAMAGES MUSEUM ARTIFACTS.

Correction Required: HIRE CONSULTANT TO STUDY DESIGN OF BUILDING, MUSEUM AREA AND WINDOWS TO DETERMINE SOLUTIONS TO REDUCE HEAT GAIN AND DAMAGE TO ARTIFACTS. PREFERABLY AT LEAST 2 OR 3 SOLUTIONS SHOULD BE PRESENTED WITH COST ESTIMATES.

Estimated cost of correction: 5000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 195: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 189NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E050 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MUSIC ENGLISH (COULTER)

Complex: 150005 Asset: 00000086-0 Compass: 15000500000086-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXIT LIGHTS

Component: 1.101

Description of Deficiency: THE EXIT LIGHTING IN THIS BUILDING DOES NOT MEET CODE AND DOI STANDARDS.

Correction Required: INSTALL EXIT LIGHTING IN THIS BUILDING. ENSURE THAT THE NEW EXIT LIGHTS ARE LED AND THAT ALL LIGHTING CODE REQUIREMENTS ARE MET.

Estimated cost of correction: 10000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 196: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(22) Category Page 190NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E051 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MUSIC ENGLISH (COULTER)

Complex: 150005 Asset: 00000086-0 Compass: 15000500000086-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE LIGHTING

Component: 1.092

Description of Deficiency: EIGHTEEN (18) 1500 WATT HIGH INTENSITY DISCHARGE LAMPS ILLUMINATE THE BAND REHEARSAL HALL. THESE CONSUME 27,000 WATTS, ARE NOT SECTIONALIZED SWITCHED, AND NOT AS EFFECTIVE OR EFFICIENT AS RECENTLY DEVELOPED LUMINARIES FOR A SIMILAR APPLICATION. FIFTY ONE (51) DIMMABLE QUARTZ LAMPS ARE USED IN THE AUDITORIUM. THESE HAVE A SHORT LIFE AND SIX (6) MEN REQUIRE TEN (10) HOURS TO PERFORM GROUP RELAMPING.

Correction Required: RECOMMEND A DESIGNED RENOVATION OF THE BAND REHEARSAL HALL AND AUDITORIUM LIGHTING TO COMPLY WITH NC BUILDING CODE AND NC ENERGY CODE, AND TO FOLLOW RECOMMENDATIONS OF THE ILLUMINATING ENGINEERING SOCIETY (IES) FOR ILLUMINATING SIMILAR SPACES. SPECIAL CONSIDERATION SHOULD BE MADE FOR MAINTAINABILITY.

Estimated cost of correction: 50000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 197: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 191NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E052 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MUSIC ENGLISH (COULTER)

Complex: 150005 Asset: 00000086-0 Compass: 15000500000086-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE OLDER EXIT FIXTURES

Component: 1.101

Description of Deficiency: THE EXIT LIGHTS IN THIS BUILDING ARE OLD. THESE TYPE OF EXIT LAMPS ARE SUBJECT TO FREQUENT BURN-OUT, REQUIRING MAINTENANCE STAFF TO SPEND A LARGE PORTION OF THEIR TIME RELAMPING. THE NEW LED TYPE HAVE A LIFE EXPECTANCY OF 20 YEARS AND REDUCE ENERGY USE.

Correction Required: RECOMMEND REPLACING ALL OLDER EXIT LIGHT FIXTURES WITH LED TYPE.

Estimated cost of correction: 4500 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 198: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 192NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G096 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MUSIC ENGLISH (COULTER)

Complex: 150005 Asset: 00000086-0 Compass: 15000500000086-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: MISCELLANEOUS RENOVATION

Component: 9.5

Description of Deficiency: SOUND BOOTHS AT SECOND AND THIRD FLOOR ARE AT THE END OF USEFUL LIFE. IN ADDITION, SUSPENDED CEILING TILE THROUGH-OUR BUILDING IS IN POOR CONDITION. GROUT AT MOST RESTROOM CERAMIC TILE FLOORS IS ALSO DETERIORATED.

Correction Required: REMOVE AND REPLACE END OF LIFE SOUND BOOTHS AT SECOND AND THIRD FLOOR. IN ADDITION, REPLACE SUSPENDED CEILING TILE THROUGH-OUR BUILDING. RE-GROUT RESTROOM CERAMIC TILE FLOORS.

Estimated cost of correction: 450000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 199: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 193NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E053 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MUSIC ENGLISH (COULTER)

Complex: 150005 Asset: 00000086-0 Compass: 15000500000086-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE EMERGENCY GENERATOR

Component: 1.100

Description of Deficiency: THE EMERGENCY GENERATOR IS REACHING THE END OF IT'S SERVICE LIFE AND NEEDS TO BE REPLACED.

Correction Required: INSTALL A DIESEL GENERATOR TO SUPPLY EMERGENCY POWER

Estimated cost of correction: 50000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 200: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(08) Category Page 194NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M045 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MUSIC ENGLISH (COULTER)

Complex: 150005 Asset: 00000086-0 Compass: 15000500000086-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: PROVIDE COMPLETE MECHANICAL RENOVATION

Component: 1.082

Description of Deficiency: THE EXISTING HVAC SYSTEM IS OVER 30 YEARS OLD, HAS DETERIORATED WITH AGE, AND IS CORRODED. THE HVAC CONTROLS SYSTEM IS AGED AND OBSOLETE. THE PLUMBING FIXTURES ARE OLD AND DAMAGED. THE PLUMBING PIPES ARE DETERIORATED DUE TO AGE. THE BUILDING HAS NO SPRINKLER SYSTEM FOR FIRE PROTECTION. HUMIDIFIERS AND HUMIDITY CONTROL ARE REQUIRED FOR THE MUSICAL INSTRUMENTS IN THE BUILDING.

Correction Required: PROVIDE A NEW CENTRAL HVAC SYSTEM TO REPLACE THE DETERIORATED EQUIPMENT. REPLACE THE PLUMBING FIXTURES AND PIPING. PROVIDE A NEW FIRE SPRINKLER SYSTEM. ENSURE PROPER HUMIDIFICATION AND HUMIDITY CONTROL.

Estimated cost of correction: 3600000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 201: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 195NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G097 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MUSIC ENGLISH (COULTER)

Complex: 150005 Asset: 00000086-0 Compass: 15000500000086-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: SIDEWALK REPAIR

Component: 2.4

Description of Deficiency: BRICK PAVERS (PROBABLY LAID ON UNSTABLE SOIL) AT NORTHWEST CORNER ENTRANCE HAS SETTLED/DROPPED DOWN, AND MAY POSE A TRIPPING HAZARD. IN ADDITION, OTHER SIDEWALKS AT BUILDING PERIMETER ARE SHOWING SIGNS OF HEAVY USE AND DETERIORATION.

Correction Required: BREAK UP AND REMOVE NON-LEVEL BRICK PAVERS. BRING IN FILL, RE-GRADE AND COMPACT SOIL. LAY NEW BRICK SIDEWALK. REPAIR AND/OR REPLACE DAMAGED AND DETERIORATED SIDEWALKS AT PERIMETER OF BUILDING.

Estimated cost of correction: 85000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 202: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 196NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G098 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - MUSIC ENGLISH (COULTER)

Complex: 150005 Asset: 00000086-0 Compass: 15000500000086-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: UPGRADE ELEVATOR

Component: 1.07

Description of Deficiency: ELEVATOR DOES NOT COMPLY WITH CURRENT CODES AND STANDARDS. FUNCTION IS NOT RELIABLE AND ELEVATOR REQUIRES CONSTANT MAINTENANCE AND REPAIR.

Correction Required: UPGRADE ELEVATOR AS REQUIRED. COST ESTIMATE IS BASED ON QUOTE FURNISHED BY ELEVATOR MAINTENANCE GROUP PLUS ESCALATION.

Estimated cost of correction: 95000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 203: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 197NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M046 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000087-0 Compass: 15000500000087-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPAIR SANITARY SEWER PIPING

Component: 1.081

Description of Deficiency: THE SANITARY SEWER PIPING IS IN POOR CONDITION AND REQUIRES INCREASING REPAIRS.

Correction Required: REPLACE THE SECTIONS OF DAMAGED SANITARY SEWER PIPING FOR ALL THE APARTMENTS.

Estimated cost of correction: 8000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 204: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 198NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E054 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000087-0 Compass: 15000500000087-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXISTING FIRE ALARM

Component: 1.102

Description of Deficiency: THE EXISTING FIRE ALARM DOES NOT MEET THE FIRE CODE.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 12000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 205: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 199NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G099 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000087-0 Compass: 15000500000087-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BUILDING

Component: 9.500

Description of Deficiency: BUILDING FINISHES ARE DETERIORATED DUE TO AGE AND HEAVY USE.

Correction Required: ARCHITECTURAL RENOVATION TO INCLUDE: REPLACE INT AND EXT DOORS AND ADA HARDWARE; REPAIR WOOD DBL PANE WINDOWS AS NEEDED; RENOVATE KITCHENS WITH NEW CABINETS, APPLIANCES, FIXTURES AND HARDWARE; RENOVATE BATHROOMS INCLUDING VANITIES, SINKS, TOILETS, BATHS / SHOWERS, FIXTURES AND HARDWARE, REPAIR PLUMBING AS NEEDED, FLOOR, WALL AND CEILING FINISHES; ABATE ASB TILE; REPLACE FLOOR TILE WITH NEW VCT OR CARPET TILES; REMOVE MULTIPLE COATS OF PAINT ON INTERIOR TRIM; PAINT INTERIOR WALLS, CEILINGS AND TRIM; REPAIR AND PAINT EXTERIOR TRIM; APPLY WATERPROOFING TO CONCRETE SLABS PRIOR TO INSTALLING NEW VCT OR CARPET; REPAIR EXTERIOR WALLS AND WOOD TRIM DAMAGED DUE TO WATER.

Estimated cost of correction: 315000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 206: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 200NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G100 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000087-0 Compass: 15000500000087-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE ROOF

Component: 1.050

Description of Deficiency: ROOF IS BEYOND END OF EXPECTED LIFE

Correction Required: REMOVE ALL SHINGLE ROOF MATERIAL TO EXPOSE STRUCTURAL DECK. REPAIR DECK AS NEEDED. INSTALL NEW FLASHING AND PENETRATION BOOTS. INSTALL NEW SHINGLES. INSTALL RIDGE VENTS. REPAIR OR INSTALL NEW GUTTERS AND DOWNLEADERS AS NEEDED. COST ESTIMATE ASSUMES HIGH QUALITY LONG LIFE ROOF. CONSIDER INSTALLING STANDING SEAM METAL ROOF.

Estimated cost of correction: 62000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 207: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 201NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G101 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000088-0 Compass: 15000500000088-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE ROOF

Component: 1.050

Description of Deficiency: ROOF IS BEYOND END OF EXPECTED LIFE

Correction Required: REMOVE ALL SHINGLE ROOF MATERIAL TO EXPOSE STRUCTURAL DECK. REPAIR DECK AS NEEDED. INSTALL NEW FLASHING AND PENETRATION BOOTS. INSTALL NEW SHINGLES. INSTALL RIDGE VENTS. REPAIR OR INSTALL NEW GUTTERS AND DOWNLEADERS AS NEEDED. COST ESTIMATE ASSUMES HIGH QUALITY LONG LIFE ROOF. CONSIDER INSTALLING STANDING SEAM METAL ROOF.

Estimated cost of correction: 62000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 208: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 202NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E055 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000088-0 Compass: 15000551000088-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXISTING FIRE ALARM

Component: 1.102

Description of Deficiency: THE EXISTING FIRE ALARM DOES NOT MEET THE FIRE CODE.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 12000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 209: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 203NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G102 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000088-0 Compass: 15000500000088-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BUILDING

Component: 9.500

Description of Deficiency: BUILDING FINISHES ARE DETERIORATED DUE TO AGE AND HEAVY USE.

Correction Required: ARCHITECTURAL RENOVATION TO INCLUDE: REPLACE INT AND EXT DOORS AND ADA HARDWARE; REPAIR WOOD DBL PANE WINDOWS AS NEEDED; RENOVATE KITCHENS WITH NEW CABINETS, APPLIANCES, FIXTURES AND HARDWARE; RENOVATE BATHROOMS INCLUDING VANITIES, SINKS, TOILETS, BATHS / SHOWERS, FIXTURES AND HARDWARE, REPAIR PLUMBING AS NEEDED, FLOOR, WALL AND CEILING FINISHES; ABATE ASB TILE; REPLACE FLOOR TILE WITH NEW VCT OR CARPET TILES; REMOVE MULTIPLE COATS OF PAINT ON INTERIOR TRIM; PAINT INTERIOR WALLS, CEILINGS AND TRIM; REPAIR AND PAINT EXTERIOR TRIM; APPLY WATERPROOFING TO CONCRETE SLABS PRIOR TO INSTALLING NEW VCT OR CARPET; REPAIR EXTERIOR WALLS AND WOOD TRIM DAMAGED DUE TO WATER.

Estimated cost of correction: 315000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 210: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 204NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E056 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000089-0 Compass: 15000500000089-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXISTING FIRE ALARM

Component: 1.102

Description of Deficiency: THE EXISTING FIRE ALARM DOES NOT MEET THE FIRE CODE.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 12000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 211: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 205NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G103 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000089-0 Compass: 15000500000089-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE ROOF

Component: 1.050

Description of Deficiency: ROOF IS BEYOND END OF EXPECTED LIFE

Correction Required: REMOVE ALL SHINGLE ROOF MATERIAL TO EXPOSE STRUCTURAL DECK. REPAIR DECK AS NEEDED. INSTALL NEW FLASHING AND PENETRATION BOOTS. INSTALL NEW SHINGLES. INSTALL RIDGE VENTS. REPAIR OR INSTALL NEW GUTTERS AND DOWNLEADERS AS NEEDED. COST ESTIMATE ASSUMES HIGH QUALITY LONG LIFE ROOF. CONSIDER INSTALLING STANDING SEAM METAL ROOF.

Estimated cost of correction: 62000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 212: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 206NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G104 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000089-0 Compass: 15000500000089-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BUILDING

Component: 9.500

Description of Deficiency: BUILDING FINISHES ARE DETERIORATED DUE TO AGE AND HEAVY USE.

Correction Required: ARCHITECTURAL RENOVATION TO INCLUDE: REPLACE INT AND EXT DOORS AND ADA HARDWARE; REPAIR WOOD DBL PANE WINDOWS AS NEEDED; RENOVATE KITCHENS WITH NEW CABINETS, APPLIANCES, FIXTURES AND HARDWARE; RENOVATE BATHROOMS INCLUDING VANITIES, SINKS, TOILETS, BATHS / SHOWERS, FIXTURES AND HARDWARE, REPAIR PLUMBING AS NEEDED, FLOOR, WALL AND CEILING FINISHES; ABATE ASB TILE; REPLACE FLOOR TILE WITH NEW VCT OR CARPET TILES; REMOVE MULTIPLE COATS OF PAINT ON INTERIOR TRIM; PAINT INTERIOR WALLS, CEILINGS AND TRIM; REPAIR AND PAINT EXTERIOR TRIM; APPLY WATERPROOFING TO CONCRETE SLABS PRIOR TO INSTALLING NEW VCT OR CARPET; REPAIR EXTERIOR WALLS AND WOOD TRIM DAMAGED DUE TO WATER.

Estimated cost of correction: 315000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 213: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 207NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G105 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000090-0 Compass: 15000500000090-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE ROOF

Component: 1.050

Description of Deficiency: ROOF IS BEYOND END OF EXPECTED LIFE

Correction Required: REMOVE ALL SHINGLE ROOF MATERIAL TO EXPOSE STRUCTURAL DECK. REPAIR DECK AS NEEDED. INSTALL NEW FLASHING AND PENETRATION BOOTS. INSTALL NEW SHINGLES. INSTALL RIDGE VENTS. REPAIR OR INSTALL NEW GUTTERS AND DOWNLEADERS AS NEEDED. COST ESTIMATE ASSUMES HIGH QUALITY LONG LIFE ROOF. CONSIDER INSTALLING STANDING SEAM METAL ROOF.

Estimated cost of correction: 62000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 214: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 208NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G106 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000090-0 Compass: 15000500000090-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BUILDING

Component: 9.500

Description of Deficiency: BUILDING FINISHES ARE DETERIORATED DUE TO AGE AND HEAVY USE.

Correction Required: ARCHITECTURAL RENOVATION TO INCLUDE: REPLACE INT AND EXT DOORS AND ADA HARDWARE; REPAIR WOOD DBL PANE WINDOWS AS NEEDED; RENOVATE KITCHENS WITH NEW CABINETS, APPLIANCES, FIXTURES AND HARDWARE; RENOVATE BATHROOMS INCLUDING VANITIES, SINKS, TOILETS, BATHS / SHOWERS, FIXTURES AND HARDWARE, REPAIR PLUMBING AS NEEDED, FLOOR, WALL AND CEILING FINISHES; ABATE ASB TILE; REPLACE FLOOR TILE WITH NEW VCT OR CARPET TILES; REMOVE MULTIPLE COATS OF PAINT ON INTERIOR TRIM; PAINT INTERIOR WALLS, CEILINGS AND TRIM; REPAIR AND PAINT EXTERIOR TRIM; APPLY WATERPROOFING TO CONCRETE SLABS PRIOR TO INSTALLING NEW VCT OR CARPET; REPAIR EXTERIOR WALLS AND WOOD TRIM DAMAGED DUE TO WATER.

Estimated cost of correction: 315000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 215: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 209NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E057 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000090-0 Compass: 15000500000090-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXISTING FIRE ALARM

Component: 1.102

Description of Deficiency: THE EXISTING FIRE ALARM DOES NOT MEET THE FIRE CODE.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 12000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 216: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 210NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E058 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000091-0 Compass: 15000500000091-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXISTING FIRE ALARM

Component: 1.102

Description of Deficiency: THE EXISTING FIRE ALARM DOES NOT MEET THE FIRE CODE.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 12000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 217: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 211NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G107 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000091-0 Compass: 15000500000091-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BUILDING

Component: 9.500

Description of Deficiency: BUILDING FINISHES ARE DETERIORATED DUE TO AGE AND HEAVY USE.

Correction Required: ARCHITECTURAL RENOVATION TO INCLUDE: REPLACE INT AND EXT DOORS AND ADA HARDWARE; REPAIR WOOD DBL PANE WINDOWS AS NEEDED; RENOVATE KITCHENS WITH NEW CABINETS, APPLIANCES, FIXTURES AND HARDWARE; RENOVATE BATHROOMS INCLUDING VANITIES, SINKS, TOILETS, BATHS / SHOWERS, FIXTURES AND HARDWARE, REPAIR PLUMBING AS NEEDED, FLOOR, WALL AND CEILING FINISHES; ABATE ASB TILE; REPLACE FLOOR TILE WITH NEW VCT OR CARPET TILES; REMOVE MULTIPLE COATS OF PAINT ON INTERIOR TRIM; PAINT INTERIOR WALLS, CEILINGS AND TRIM; REPAIR AND PAINT EXTERIOR TRIM; APPLY WATERPROOFING TO CONCRETE SLABS PRIOR TO INSTALLING NEW VCT OR CARPET; REPAIR EXTERIOR WALLS AND WOOD TRIM DAMAGED DUE TO WATER.

Estimated cost of correction: 315000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 218: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 212NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G108 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - FACULTY APARTMENT

Complex: 150005 Asset: 00000091-0 Compass: 15000500000091-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE ROOF

Component: 1.050

Description of Deficiency: ROOF IS BEYOND END OF EXPECTED LIFE

Correction Required: REMOVE ALL SHINGLE ROOF MATERIAL TO EXPOSE STRUCTURAL DECK. REPAIR DECK AS NEEDED. INSTALL NEW FLASHING AND PENETRATION BOOTS. INSTALL NEW SHINGLES. INSTALL RIDGE VENTS. REPAIR OR INSTALL NEW GUTTERS AND DOWNLEADERS AS NEEDED. COST ESTIMATE ASSUMES HIGH QUALITY LONG LIFE ROOF. CONSIDER INSTALLING STANDING SEAM METAL ROOF.

Estimated cost of correction: 62000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 219: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 213NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G109 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - JENKINS HOUSE

Complex: 150005 Asset: 00000092-0 Compass: 15000500000092-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: RENOVATE BUILDING

Component: 9.500

Description of Deficiency: BUILDING IS VERY RUN DOW AND DETERIORATED. ROOF LEAKS AND REQUIRES CONSTANT MAINTENANCE, FLOORS ARE DAMAGES, KITCHEN IS NOT USABLE. PORCHES ARE DETERIORATED. FOUNDATION NEEDS REPAIR.

Correction Required: ARCHITECTURAL RENOVATION TO INCLUDE: REPAIR AND RESTORE WOOD FLOOR; REPAIR AND RESTORE INTERIOR AND EXTERIOR WOOD DOORS; INSTALL DBL PANE LOW MAINT WINDOW UNITS; REPLACE ASPHALT SHINGLE ROOF; REPAIR AND RESTORE PORCH AND ENTRANCES; REPAIR FIREPLACE, LINE CHIMNEY AND RETURN TO WORKING CONDITION; RENOVATE KITCHEN INCLUDING NEW CABINETS, APPLIANCES, FIXTURES, COUNTERTOPS - RENOVATE TO HEAVY DUTY CATERING STANDARD, HARDWARE; RENOVATE BATHROOM WITH NEW FINISHES, FIXTURES - CONFIGURE TO BE ADA COMPLIANT. REPAIR FOUNDATION AND BASEMENT AS NEEDED.

Estimated cost of correction: 310000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 220: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 214NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E059 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STUDENT SUPPLY STORE

Complex: 150005 Asset: 00000094-0 Compass: 15000500000094-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXISTING FIRE ALARM

Component: 1.102

Description of Deficiency: THE EXISTING FIRE ALARM DOES NOT MEET THE FIRE CODE.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 40000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 221: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 215NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G110 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STUDENT SUPPLY STORE

Complex: 150005 Asset: 00000094-0 Compass: 15000500000094-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: ADA CORRECTIONS

Component: 9.4

Description of Deficiency: BUILDING DOES NOT COMPLY WITH ADA GUIDELINES AND APPLICABLE SECTIONS OF THE STATE BUILDING CODE.

Correction Required: RENOVATE COMPONENTS OF THE BUILDING TO COMPLY WITH ADA.

Estimated cost of correction: 15000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 222: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 216NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G111 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STUDENT SUPPLY STORE

Complex: 150005 Asset: 00000094-0 Compass: 15000500000094-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: STRUCTURAL STUDY

Component: 6.1

Description of Deficiency: EXTERIOR MASONRY WALL (BRICK) AT SOUTHWEST CORNER OF BOOKSTORE, AND BRICK COLUMN SUPPORTING OFFICES OVER LOADING DOCK SHOW SIGNS OF FRACTURE (CRACK FROM FOUNDATION TO WINDOW LINE). IN ADDITION, THERE ARE CRACKS AT FLOOR AND AT CONCRETE BLOCK WALL (HAIR-LINE CRACK) AT INTERIOR RAMP.

Correction Required: A STRUCTURAL STUDY OF EXTERIOR MASONRY WALL, SUPPORT COLUMN, INTERIOR RAMP FLOOR AND CONCRETE BLOCK WALL TO DETERMINE EXTENT OF CONCEALED DAMAGE AND ESTIMATED COST OF REPAIR IS RECOMMENDED.

Estimated cost of correction: 10000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 223: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 217NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M047 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STUDENT SUPPLY STORE

Complex: 150005 Asset: 00000094-0 Compass: 15000500000094-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: HVAC UPGRADE

Component: 1.082

Description of Deficiency: THE ENTIRE BOOKSTORE (STUDENT SUPPLY STORE) BUILDING IS ONE HVAC ZONE. THE UPSTAIRS OFFICE AREA IS SOMETIMES HOT, WHILE THE BOOK RENTAL AREA IS OFTEN COLD. A WALL SEPARATING THE BOOK RENTAL AREA FROM THE REST OF THE FIRST FLOOR WAS BUILT AFTER INITIAL CONSTRUCTION, RESULTING IN ADDITIONAL ZONING PROBLEMS. SEPARATE HVAC ZONES ARE NEEDED WITHIN THIS BUILDING. THE R22 DX AIR COOLED CONDENSING UNIT OUTSIDE THE BOOKSTORE OPERATES SATISFACTORILY BUT IS 25 YEARS OLD.

Correction Required: REPLACE THE AGING AIR COOLED CONDENSING UNIT WITH A NEW R134 UNIT. PROVIDE SEPARATELY CONTROLLED HVAC ZONES.

Estimated cost of correction: 250000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 224: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 218NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M048 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - STUDENT SUPPLY STORE

Complex: 150005 Asset: 00000094-0 Compass: 15000500000094-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: PROVIDE FIRE SPRINKLER SYSTEM

Component: 1.083

Description of Deficiency: AS NOTED PREVIOUSLY BY THE DEPARTMENT OF INSURANCE, THE BOOKSTORE HAS NO SPRINKLER SYSTEM.

Correction Required: PROVIDE A FIRE PROTECTION SPRINKLER SYSTEM.

Estimated cost of correction: 150000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 225: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 219NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E060 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: PROVIDE EGRESS LIGHTING

Component: 1.092

Description of Deficiency: THE AUXILIARY GYMNASIUM, ROOM 1801, AND THE RACQUET BALL COURTS DO NOT HAVE EMERGENCY EGRESS LIGHTING. LIGHTING IN THESE AREAS ARE NOT SUPPORTED BY THE EMERGENCY GENERATOR.

Correction Required: PROVIDE EMERGENCY EGRESS LIGHTING FOR THE AUXILIARY GYMNASIUM AND THE RACQUET BALL COURTS.

Estimated cost of correction: 12000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 226: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(01) Category Page 220NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E061 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REBUILD MEDIUM VOLTAGE SWITCHES

Component: 1.091

Description of Deficiency: THE FOUR (4) 12470Y/7200V SWITCHES LOCATED IN THIS ASSET WERE MANUFACTURED BY NOW DEFUNCT FEDERAL PACIFIC COMPANY (FPE). THE PHASE BARRIERS OF THIS 21 YEAR OLD EQUIPMENT ARE SEVERELY WARPED AND THE BUS INSULATORS ARE BREAKING DOWN. INSULATOR FAILURE CAN CAUSE CATASTROPHIC DAMAGE TO THE SWITCHGEAR.

Correction Required: RECOMMEND CONTRACTING AN ELECTRICAL EQUIPMENT SERVICE COMPANY TO REBUILD, IN-PLACE, EACH OF THE SWITCHES. THE PHASE BARRIERS AND BUS INSULATORS MAY BE FIELD REPLACEABLE, AND AT THE TIME THAT THOSE COMPONENTS ARE EXCHANGED, THE SWITCH MECHANISMS MAY BE CLEANED AND LUBRICATED.

Estimated cost of correction: 30000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 227: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(21) Category Page 221NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E062 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE OBSOLETE ELECTRICAL PANELS

Component: 1.091

Description of Deficiency: APPROXIMATELY 14 BRANCH CIRCUIT PANELS WERE MANUFACTURED BY NOW DEFUNCT FEDERAL PACIFIC COMPANY (FPE). THIS OBSOLETE EQUIPMENT WAS INSTALLED SOME 21 YEARS AGO. REPLACEMENT PARTS ARE ONLY AVAILABLE FROM ELECTRICAL SALVAGE COMPANIES AND ONLY IF THE COMPANIES COINCIDENTLY HAVE THE PARTS IN STOCK. FAILURES OF A BUS OR BREAKER WILL RESULT IN AN EXTENDED ELECTRICAL OUTAGE OF ONE OR MORE CIRCUITS WHILE REPLACEMENT PARTS ARE LOCATED, OR WHILE A REPLACEMENT PANEL IS INSTALLED. MORE SO, IT IS IMPORTANT TO KNOW THAT THE FPE STAB-LOK TYPE BRANCH BREAKERS ARE RECOGNIZED IN INDUSTRY REPORTS TO FAIL TO OPEN DURING OVERLOAD CURRENTS.

Correction Required: REPLACE ALL OBSOLETE AND POTENTIALLY UNSAFE BRANCH CIRCUIT PANELS.

Estimated cost of correction: 70000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 228: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 222NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E063 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE FIRE ALARM SYSTEM

Component: 1.102

Description of Deficiency: THE EDWARDS EST-3 REPLACEMENT FIRE ALARM CONTROL PANEL WAS RECENTLY INSTALLED; HOWEVER, THE SYSTEM WAS NOT UPGRADED TO HAVE SUFFICIENT NOTIFICATION APPLIANCES AND INITIATION DEVICES TO SATISFY THE PRESENT REQUIREMENTS OF NFPA 72® .

Correction Required: PROVIDE ADDITIONAL FIRE ALARM SYSTEM DEVICES TO SATISFY THE PRESENT REQUIREMENTS OF NFPA 72® AND NC FIRE CODE.

Estimated cost of correction: 70000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 229: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(15) Category Page 223NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G112 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPAIR CONCRETE FLOORS

Component: 1.062

Description of Deficiency: CONCRETE FLOORS AT BOTTOM AND UNDER SEATING HAVE DEVELOPED CRACKS.

Correction Required: REPAIR / SEAL CRACKS AND APPLY SEALANT TO CONCRETE FLOORS.

Estimated cost of correction: 160000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 230: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(12) Category Page 224NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G113 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: ADA CORRECTIONS

Component: 9.4

Description of Deficiency: BUILDING DOES NOT COMPLY WITH ADA GUIDELINES AND APPLICABLE SECTIONS OF THE STATE BUILDING CODE.

Correction Required: RENOVATE COMPONENTS OF THE BUILDING AS SPECIFIED IN THE CURRENT ADA STUDY. COST ESTIMATE IS BASED ON ESTIMATES IN THE STUDY.

Estimated cost of correction: 128000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 231: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 225NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M049 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 4 Years

Deficiency Title: UPGRADE HVAC CONTROLS

Component: 1.082

Description of Deficiency: THE EXISTING HVAC CONTROL SYSTEMS ARE PRIMARILY PNEUMATIC WITH A LIMITED PORTION COMPRISED OF DDC. THE HVAC CONTROLS SYSTEM IS AGED AND OBSOLETE, AND ENERGY FEATURES ARE LIMITED. ACTUATORS ARE DAMAGED. THE CONTROLS CANNOT PERFORM TO MEET THE ORIGINAL DESIGN INTENT. HUMIDIFIERS INSTALLED ON SOME AIR HANDLING UNITS ARE NO LONGER IN OPERATION.

Correction Required: UPGRADE THE HVAC CONTROLS SYSTEM TO PROVIDE A RELIABLE, ENERGY EFFICIENT SYSTEM. THE NEW CONTROLS SHOULD BE CONNECTED TO A CAMPUS ENERGY MANAGEMENT SYSTEM.

Estimated cost of correction: 250000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 232: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 226NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G114 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: MAINTAIN CURRENT USE OF ICE SKATING RINK

Component: 5.12

Description of Deficiency: OUTDOOR ICE SKATING RINK HAS LIMITED USE FOR SOME TYPES OF RECREATION. THIS RINK IS NOT BEING OPERATED DUE TO PROBLEMS WITH LEAKING REFRIGERANT PIPING IN THE CONCRETE SLAB. SOLAR HEAT GAIN THAT CAUSED INADEQUATE FREEZING OF THE SURFACE WAS ALSO A PROBLEM. SOME WEATHER CONDITIONS PREVENTED ITS USE.

Correction Required: BECAUSE OF HIGH REPAIR AND OPERATING COST, RENOVATION IS NOT RECOMMENDED. A NEW REFRIGERANT PIPING SYSTEM WOULD BE REQUIRED. A STRUCTURE OVER THE RINK TO PREVENT SOLAR HEAT GAIN AND PROVIDE FOR USE DURING INCLEMENT WEATHER WOULD BE REQUIRED. ESTIMATED RENOVATION COST IS OVER $500,000. ESTIMATED COST IS FOR MINOR REPAIR.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 233: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 227NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E064 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXIT LIGHTS

Component: 1.101

Description of Deficiency: THE EXIT LIGHTING IN THIS BUILDING DOES NOT MEET CODE AND DOI STANDARDS.

Correction Required: INSTALL EXIT LIGHTING IN THIS BUILDING. ENSURE THAT THE NEW EXIT LIGHTS ARE LED AND THAT ALL LIGHTING CODE REQUIREMENTS ARE MET.

Estimated cost of correction: 15000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 234: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 228NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G115 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE CENTER SPEAKERS AND RIGGING

Component: 9.500

Description of Deficiency: CENTER SPEAKERS AND RIGGING NO LONGER WORKS EFFECTIVELY. DIFFICULT TO OPERATE AND MAINTAIN.

Correction Required: REPAIR OR REPLACE CENTER CLUSTER SUFFICIENT FOR CURRENT AND FUTURE NEEDS.

Estimated cost of correction: 100000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 235: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(13) Category Page 229NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G116 Inspector: WDS

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPAIR GLASS CURTAIN WALL

Component: 1.041

Description of Deficiency: GLASS CURTAIN WALL LEAKS AND HAS DETERIORATED GASKETS. SIMILAR PARTS OF GLASS ROOF LEAKS. GASKETS HAVE BROKEN AND SHRUNK OVER TIME AND NO LONGER SEAL WINDOW UNITS IN THE FRAMES. LEAKS DAMAGE INTERIOR OF BUILDING.

Correction Required: REPAIR / REPLACE GASKETS IN CURTAIN WALL AND ROOF. ESSENTIALLY A REPAIR OF THE ENTIRE GLASS WALL SYSTEMS.

Estimated cost of correction: 600000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 236: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 230NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E065 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXISTING FIRE ALARM

Component: 1.102

Description of Deficiency: THE EXISTING FIRE ALARM DOES NOT MEET THE FIRE CODE.

Correction Required: INSTALL A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE NC FIRE CODE AND DOI REQUIREMENTS.

Estimated cost of correction: 150000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 237: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 231NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E066 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE ELECTRICAL PANEL

Component: 1.091

Description of Deficiency: THE EXISTING PANEL IS OLD AND REACHING THE END OF IT'S SERVICE LIFE.

Correction Required: RECOMMEND REPLACING THE OBSOLETE PANEL, WITH A PANEL THAT MEETS NEC REQUIREMENTS.

Estimated cost of correction: 13500 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 238: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 232NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M050 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - LISTON B. RAMSEY ACTIVITIES CENTER

Complex: 150005 Asset: 00000106-0 Compass: 15000500000106-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPAIR HEAT RECOVERY UNIT

Component: 1.082

Description of Deficiency: THE EXISTING HEAT RECOVERY UNIT ON EXHAUST FAN 5 IS DETERIORATED WITH AGE AND NO LONGER FUNCTIONAL. THE EXISTING COILS OBSTRUCT AIR FLOW. THE VENTILATION FOR THE LOCKERS ROOMS IS NOT ADEQUATE.

Correction Required: REPAIR OR REPLACE THE HEAT RECOVERY UNIT. RESTORE ADEQUATE VENTILATION AND EXHAUST.

Estimated cost of correction: 12000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 239: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 233NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E067 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - WAREHOUSE AND STORAGE

Complex: 150005 Asset: 00000109-0 Compass: 15000500000109-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EXIT LIGHTS

Component: 1.101

Description of Deficiency: THE EXIT LIGHTING IN THIS BUILDING DOES NOT MEET CODE AND DOI STANDARDS.

Correction Required: INSTALL EXIT LIGHTING IN THIS BUILDING. ENSURE THAT THE NEW EXIT LIGHTS ARE LED AND THAT ALL LIGHTING CODE REQUIREMENTS ARE MET.

Estimated cost of correction: 15000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 240: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(22) Category Page 234NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E068 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - WAREHOUSE AND STORAGE

Complex: 150005 Asset: 00000109-0 Compass: 15000500000109-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE LIGHTING

Component: 1.092

Description of Deficiency: EIGHTY NINE (89) 250 WATT HIGH INTENSITY DISCHARGE LAMPS ILLUMINATE THE WAREHOUSE. THESE CONSUME 22,250 WATTS AND ARE IMPROPERLY APPLIED TO THE SPACE. THE HOLOPHANE LUMINARIES ARE FOR A HIGH BAY APPLICATION FOR A LOW BAY REQUIREMENT. THE BRANCH CIRCUIT BREAKERS FROM WHICH THE LIGHTS ARE ENERGIZED ARE EXTREMELY WARM.

Correction Required: RECOMMEND A DESIGNED RENOVATION OF THE WAREHOUSE LIGHTING TO COMPLY WITH NC BUILDING CODE AND NC ENERGY CODE, AND TO FOLLOW RECOMMENDATIONS OF THE ILLUMINATING ENGINEERING SOCIETY (IES) FOR ILLUMINATING SIMILAR SPACES. AS A PART OF LUMINAIRE CHANGE, ENSURE THAT THE BRANCH CIRCUIT BREAKERS ARE SWD RATED.

Estimated cost of correction: 22000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 241: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(03) Category Page 235NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G117 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - WAREHOUSE AND STORAGE

Complex: 150005 Asset: 00000109-0 Compass: 15000500000109-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPAIR ROOF

Component: 1.05

Description of Deficiency: WAREHOUSE ROOF APPEARS TO HAVE LEAKED AT METAL ROOF TO FIREWALL/DIVIDER FLASHING AND HAS DAMAGED INTERIOR OF STRUCTURE.

Correction Required: REMOVE DAMAGED AND DEFECTIVE FLASHING. INSTALL MEMBRANE AT EXPOSED FIREWALL/DIVIDER TO OBTAIN A WEATHER TIGHT SEAL. REPAIR DAMAGED INTERIOR FINISHES.

Estimated cost of correction: 15000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 242: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 236NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E069 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - KATUSI (CORE BLDG)

Complex: 150005 Asset: 00000123-0 Compass: 15000500000123-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: PROVIDE EGRESS LIGHTING

Component: 1.101

Description of Deficiency: EMERGENCY EGRESS LIGHTING IN THE AMPHITHEATER IS PROVIDED BY A SINGLE LAMP INCANDESCENT BATTERY POWERED LUMINAIRE. A SINGLE LAMP FOR A SINGLE LUMINAIRE IN THE SPACE YIELDS A VIOLATION OF NEC ARTICLE 700.16. THE AMPHITHEATER LUMINARIES ARE NOT POWERED BY A GENERATOR SUPPLIED CIRCUIT. DURING A POWER OUTAGE THE AMPHITHEATER LIGHTS WILL GO OUT AND THE SINGLE EGRESS LAMP WILL ILLUMINATE. , SOME 10 SECONDS LATER, WHEN THE GENERATOR SUPPLIES POWER TO THE BUILDING, THE SINGLE EGRESS LAMP WILL GO OUT, AND THE AMPHITHEATER WILL BE DARK.

Correction Required: RECOMMEND THAT A SUFFICIENT QUANTITY OF EXISTING LUMINARIES ARE RETROFITTED OR AN EGRESS LIGHTING APPLICATION WITH BATTERY BALLASTS. ESTIMATED COST INCLUDES WIRING TO A GENERATOR SUPPLIED CIRCUIT.

Estimated cost of correction: 7500 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 243: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(22) Category Page 237NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E070 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - KATUSI (CORE BLDG)

Complex: 150005 Asset: 00000123-0 Compass: 15000500000123-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPLACE OBSOLETE LIGHTING SYSTEM

Component: 1.092

Description of Deficiency: DINING ROOM LIGHTING CONTROL IS THROUGH AN OBSOLETE LUTRON DA-2500-TSP. PARTS AND SERVICE ARE UNAVAILABLE FOR CONTINUED CONTROL OF NUMEROUS 60 WATT INCANDESCENT LUMINARIES.

Correction Required: RECOMMEND AN ENGINEERED REPLACEMENT DINING ROOM LIGHTING CONTROL SYSTEM TO INCLUDE LIGHT HARVESTING CAPABILITY AND DESIGN FEATURES TO COMPLY WITH OR SURPASS THE REQUIREMENTS OF ENERGY CONSERVATION CODE.

Estimated cost of correction: 16000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 244: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 238NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M051 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ATANTOI (RES. A)

Complex: 150005 Asset: 00000124-0 Compass: 15000500000124-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: HVAC UPGRADE

Component: 1.082

Description of Deficiency: CORRIDOR VENTILATION IS INSUFFICIENT ON THE FIRST AND SECOND FLOORS OF THE ATANTO AND AHYSTI RESIDENTIAL BUILDINGS. PORTABLE DEHUMIDIFIERS ARE CURRENTLY USED IN BOTH BUILDINGS TO PREVENT MOLD AND MAINTAIN COMFORTABLE HUMIDITY LEVELS. AIR CURRENTLY RECIRCULATES AT THE END OF EACH UPSTAIRS CORRIDOR, RATHER THAN FLOWING THE LENGTH OF EACH CORRIDOR.

Correction Required: PROVIDE OVERHEAD FAN COIL UNITS, SIMILAR TO THE SECOND FLOOR FAN COIL UNITS, FOR FIRST FLOOR CORRIDOR VENTILATION IN THE ATANTO AND AHYSTI BUILDINGS. PROVIDE APPROPRIATE FIRST FLOOR DUCTING TO VENTILATE THE ENTIRE CORRIDOR LENGTH. REDUCT THE UPSTAIRS CORRIDORS TO PROVIDE AIR FLOW THE ENTIRE LENGTH OF THE CORRIDORS.

Estimated cost of correction: 20000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 245: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 239NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E071 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ATANTOI (RES. A)

Complex: 150005 Asset: 00000124-0 Compass: 15000500000124-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EGRESS LIGHTING

Component: 1.101

Description of Deficiency: THE EXISTING EMERGENCY EGRESS LIGHTING IS PROVIDED BY MISAPPLIED SINGLE LAMP WALL MOUNTED BATTERY POWERED LUMINARIES. THESE UNITS ARE INTENDED BY THEIR MANUFACTURER TO HAVE BEEN CEILING MOUNTED FOR FLOOR ILLUMINATION. BY BEING WALL MOUNTED AND HAVING A SINGLE LAMP, IT IS QUESTIONABLE THAT COMPLIANCE TO NC BUILDING CODE, PARAGRAPH 1006.4, HAD BEEN MET REGARDING MEANS OF EGRESS ILLUMINATION QUALITIES.

Correction Required: RECOMMEND REPLACING THE EXISTING EGRESS LIGHTING LUMINARIES WITH ONES THAT ARE INTENDED FOR THE APPLICATION OF BEING WALL MOUNTED AND THAT COMPLY WITH THE REQUIREMENTS OF NC BUILDING CODE.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 246: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 240NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M052 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - AHYSTI (RES. B)

Complex: 150005 Asset: 00000125-0 Compass: 15000500000125-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: HVAC UPGRADE

Component: 1.082

Description of Deficiency: CORRIDOR VENTILATION IS INSUFFICIENT ON THE FIRST AND SECOND FLOORS OF THE AHYSTI AND ATANTO RESIDENTIAL BUILDINGS. PORTABLE DEHUMIDIFIERS ARE CURRENTLY USED IN BOTH BUILDINGS TO PREVENT MOLD AND MAINTAIN COMFORTABLE HUMIDITY LEVELS. AIR CURRENTLY RECIRCULATES AT THE END OF EACH UPSTAIRS CORRIDOR, RATHER THAN FLOWING THE LENGTH OF EACH CORRIDOR.

Correction Required: PROVIDE OVERHEAD FAN COIL UNITS, SIMILAR TO THE SECOND FLOOR FAN COIL UNITS, FOR FIRST FLOOR CORRIDOR VENTILATION IN THE AHYSTI AND ATANTO BUILDINGS. PROVIDE APPROPRIATE FIRST FLOOR DUCTING TO VENTILATE THE ENTIRE CORRIDOR LENGTH. REDUCT THE UPSTAIRS CORRIDORS TO PROVIDE AIR FLOW THE ENTIRE LENGTH OF THE CORRIDORS.

Estimated cost of correction: 20000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 247: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(02) Category Page 241NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E072 Inspector: CVC

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - AHYSTI (RES. B)

Complex: 150005 Asset: 00000125-0 Compass: 15000500000125-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPLACE EGRESS LIGHTING

Component: 1.101

Description of Deficiency: THE EXISTING EMERGENCY EGRESS LIGHTING IS PROVIDED BY MISAPPLIED SINGLE LAMP WALL MOUNTED BATTERY POWERED LUMINARIES. THESE UNITS ARE INTENDED BY THEIR MANUFACTURER TO HAVE BEEN CEILING MOUNTED FOR FLOOR ILLUMINATION. BY BEING WALL MOUNTED AND HAVING A SINGLE LAMP, IT IS QUESTIONABLE THAT COMPLIANCE TO NC BUILDING CODE, PARAGRAPH 1006.4, HAD BEEN MET REGARDING MEANS OF EGRESS ILLUMINATION QUALITIES.

Correction Required: RECOMMEND REPLACING THE EXISTING EGRESS LIGHTING LUMINARIES WITH ONES THAT ARE INTENDED FOR THE APPLICATION OF BEING WALL MOUNTED AND THAT COMPLY WITH THE REQUIREMENTS OF NC BUILDING CODE.

Estimated cost of correction: 3000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 248: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 242NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M053 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - PERFORMING ARTS

Complex: 150005 Asset: 00000135-0 Compass: 15000500000135-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: RETROCOMMISSION CONTROLS

Component: 1.082

Description of Deficiency: THIS IS A NEW BUILDING WITH EQUIPMENT IN GOOD CONDITION, BUT SOME CONTROLS AND COMPONENTS ARE NOT OPERATING PROPERLY. THE BUILDING SYSTEMS ARE NOT EXECUTING THE DESIRED SEQUENCE OF OPERATIONS. BUILDING OPERATION AND ENERGY EFFICIENCY IS NOT OPTIMUM. SOME AREAS OF THE BUILDING HAVE ISSUES WITH HUMIDIFICATION AND DEHUMIDIFICATION. THERE IS NO USER INTERFACE IN THE BUILDING CONTROLS FOR MAINTENANCE STAFF. VFD ISSUES. STEAM LEAKS NEAR VFD'S. STEAM PIT NEEDS SUMP PUMP. WATER AND AIR BALANCE ISSUES. SOME VAV'S MAY BE IMPROPERLY SIZED. CW PIPING QUESTIONABLE.

Correction Required: RETROCOMMISSION BUILDING WITH FOCUS ON HVAC CONTROLS.

Estimated cost of correction: 125000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 249: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 243NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G118 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CENTRAL DRIVE HALL

Complex: 150005 Asset: 00000136-0 Compass: 15000500000136-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: MISCELLANEOUS RENOVATION

Component: 9.5

Description of Deficiency: LACK OF GUTTERS AND POOR SURFACE DRAINAGE AT BUILDING PERIMETER WAS NOTED. NOTE: GUTTERS HAVE RECENTLY BEEN ADDED AT SOME LOCATIONS.

Correction Required: INSTALL GUTTER SYSTEM AND PROVIDE PROPER SURFACE AND SUB-SURFACE RUNOFF AT BUILDING PERIMETER

Estimated cost of correction: 250000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 250: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 244NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G119 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CENTRAL DRIVE HALL

Complex: 150005 Asset: 00000136-0 Compass: 15000553000000-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: RETAINING WALLS

Component: 5.3

Description of Deficiency: ELECTRICAL TRANSFORMERS AT NORTH SIDE OF CAMPUS BOOKSTORE AND NEAR FOOTBALL STADIUM DO NOT APPEAR TO HAVE NECESSARY CLEARANCE FOR MAINTENANCE.

Correction Required: ENLARGE CLEARANCE SPACE AROUND TRANSFORMERS TO PROVIDE SAFE ACCESS.

Estimated cost of correction: 30000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 251: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(10) Category Page 245NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M054 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CENTRAL DRIVE HALL

Complex: 150005 Asset: 00000136-0 Compass: 15000500000136-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: AHU RETROFIT

Component: 1.082

Description of Deficiency: THE COOLING COILS IN SOME AIR HANDLERS ARE PIPED BACKWARDS. IN THESE AIR HANDLERS, THE ENTERING CHILLED WATER FIRST CIRCULATES THROUGH THE LAST (DOWNWIND) ROW OF COILS IN THE TUBE BUNDLE. THE CHILLED WATER EXITS THE TUBE BUNDLE AFTER PASSING THROUGH THE FIRST (UPWIND) ROW OF COILS. THIS PIPING ARRANGEMENT RESULTS IN HIGHER AIR TEMPERATURES AND LESS EFFECTIVE DEHUMIDIFICATION.

Correction Required: REPIPE THE IMPROPERLY PIPED AIR HANDLERS SUCH THAT INCOMING CHILLED WATER FIRST CIRCULATES THROUGH THE UPWIND ROW OF COILS IN THE COOLING COILS.

Estimated cost of correction: 10000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 2 General Fund = 1Revenue Receipts = 2

Page 252: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(17) Category Page 246NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G120 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REGIONAL LABOR FORCE DEV.

Complex: 150005 Asset: 00000137-0 Compass: 15000500000137-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: MISCELLANEOUS RENOVATION

Component: 9.5

Description of Deficiency: COPING WALL FLASHING DOES NOT EXTEND TO BUILDING EDGE CREATING A LEAK PRONE CAULKED SEAL AND INDIVIDUAL SEALS AT PERIMETER.

Correction Required: REWORK COPING WALL FLASHING TO PREVENT FUTURE LEAKS AND DAMAGE TO STRUCTURE.

Estimated cost of correction: 95000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 253: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 247NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M055 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - REGIONAL LABOR FORCE DEV.

Complex: 150005 Asset: 00000137-0 Compass: 15000500000137-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: GLYCOL SYSTEM DOES NOT WORK

Component: 1.082

Description of Deficiency: THE GLYCOL SYSTEM DOES NOT OPERATE PROPERLY, EXPOSING EQUIPMENT TO THE DANGER OF DAMAGE DUE TO FREEZING.

Correction Required: REPAIR GLYCOL SYSTEM TO PROVIDE PROTECTION FROM FREEZING.

Estimated cost of correction: 5000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 254: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(04) Category Page 248NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E073 Inspector: JB

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - SOFTBALL COMPLEX

Complex: 150005 Asset: 00000141-0 Compass: 15000500000141-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: ATTIC LIGHTING UPGRADE

Component: 1.092

Description of Deficiency: THE ATTICS ABOVE THE CONCESSION BUILDING AND THE HOME TEAM LOCKER ROOM BUILDING AT THE SOFTBALL FIELD ARE NOT LIGHTED AND LACK ELECTRICAL RECEPTACLES NEEDED FOR HVAC EQUIPMENT MAINTENANCE.

Correction Required: INSTALL LIGHTING AND POWER RECEPTACLES IN BOTH ATTICS

Estimated cost of correction: 5000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 255: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 249NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G121 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - PARKING LOTS IN ALL AREAS

Complex: 150005 Asset: 21000000-0 Compass: 15000521000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPAIR / RESURFACE PARKING LOTS (ONE YR.)

Component: 2.1

Description of Deficiency: SOME ASPHALT PAVING HAS A WEATHERED SURFACE, EXPOSED AGGREGATE AND CRACKS. CONDITION OF SURFACE IN EACH LOT VARIES DEPENDING ON INITIAL QUALITY, AGE, TRAFFIC LOAD, AND MAINTENANCE HISTORY. SOME LOTS NEED REPAIRS OF CRACKS AND HOLES AND REPAVING WITHIN APPROX. 1 YEAR.

Correction Required: PATCH CRACKS AND BROKEN AREAS OR REMOVE PART OF SURFACE TO ACHIEVE A SOUND BASE. PAVE A NEW WEARING SURFACE SUITABLE FOR TYPE OF VEHICLE TRAFFIC. SOME LOTS NEED REPAIR AND ADDITION OF A REJUVENATION COATING TO EXTEND LIFE UNTIL REPAVING IS NEEDED. REPAINT ALL MARKINGS AND STRIPES.

Estimated cost of correction: 250000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 256: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 250NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G122 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - PARKING LOTS IN ALL AREAS

Complex: 150005 Asset: 21000000-0 Compass: 15000521000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 5 Years

Deficiency Title: REPAIR / RESURFACE PARKING LOTS (FIVE YRS.)

Component: 2.1

Description of Deficiency: SOME ASPHALT PAVING HAS A WEATHERED SURFACE, EXPOSED AGGREGATE AND CRACKS. CONDITION OF SURFACE IN EACH LOT VARIES DEPENDING ON INITIAL QUALITY, AGE, TRAFFIC LOAD, AND MAINTENANCE HISTORY. SOME LOTS NEED REPAIR OF CRACKS AND HOLES AND REPAVING WITHIN APPROX. 5 YEARS.

Correction Required: PATCH CRACKS AND BROKEN AREAS OR REMOVE PART OF SURFACE TO ACHIEVE A SOUND BASE. PAVE A NEW WEARING SURFACE SUITABLE FOR TYPE OF VEHICLE TRAFFIC. SOME LOTS NEED REPAIR AND ADDITION OF A REJUVENATION COATING TO EXTEND LIFE UNTIL REPAVING IS NEEDED. REPAINT ALL MARKINGS AND STRIPES.

Estimated cost of correction: 250000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 257: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 251NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G123 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - PARKING LOTS IN ALL AREAS

Complex: 150005 Asset: 21000000-0 Compass: 15000521000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPAIR / RESURFACE PARKING LOTS (THREE YRS.)

Component: 2.1

Description of Deficiency: SOME ASPHALT PAVING HAS A WEATHERED SURFACE, EXPOSED AGGREGATE AND CRACKS. CONDITION OF SURFACE IN EACH LOT VARIES DEPENDING ON INITIAL QUALITY, AGE, TRAFFIC LOAD, AND MAINTENANCE HISTORY. SOME LOTS NEED REPAIR OF CRACKS AND HOLES AND REPAVING WITHIN APPROX. 3 YEARS.

Correction Required: PATCH CRACKS AND BROKEN AREAS OR REMOVE PART OF SURFACE TO ACHIEVE A SOUND BASE. PAVE A NEW WEARING SURFACE SUITABLE FOR TYPE OF VEHICLE TRAFFIC. SOME LOTS NEED REPAIR AND ADDITION OF A REJUVENATION COATING TO EXTEND LIFE UNTIL REPAVING IS NEEDED. REPAINT ALL MARKINGS AND STRIPES.

Estimated cost of correction: 150000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 258: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 252NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G124 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ROADWAYS IN ALL AREAS

Complex: 150005 Asset: 22000000-0 Compass: 15000522000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: REPAIR / RESURFACE ROADWAYS (THREE YRS.)

Component: 2.2

Description of Deficiency: SOME ASPHALT PAVING HAS A WEATHERED SURFACE, EXPOSED AGGREGATE AND CRACKS. CONDITION OF SURFACE IN EACH ROAD VARIES DEPENDING ON INITIAL QUALITY, AGE, TRAFFIC LOAD, AND MAINTENANCE HISTORY. SOME ROADS NEED REPAIR OF CRACKS AND HOLES AND REPAVING WITHIN 3 YEARS.

Correction Required: PATCH CRACKS AND BROKEN AREAS OR REMOVE PART OF SURFACE TO ACHIEVE A SOUND BASE. PAVE A NEW WEARING SURFACE SUITABLE FOR TYPE OF VEHICLE TRAFFIC. SOME ROADS NEED REPAIR AND ADDITION OF A REJUVENATION COATING TO EXTEND LIFE UNTIL REPAVING IS NEEDED. REPAINT ALL MARKINGS AND STRIPES.

Estimated cost of correction: 35000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 259: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 253NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G125 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - ROADWAYS IN ALL AREAS

Complex: 150005 Asset: 22000000-0 Compass: 15000522000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPAIR / RESURFACE ROADWAYS (ONE YR.)

Component: 2.2

Description of Deficiency: SOME ASPHALT PAVING HAS A WEATHERED SURFACE, EXPOSED AGGREGATE AND CRACKS. CONDITION OF SURFACE IN EACH ROAD VARIES DEPENDING ON INITIAL QUALITY, AGE, TRAFFIC LOAD, AND MAINTENANCE HISTORY. SOME ROADS NEED REPAIR OF CRACKS AND HOLES AND REPAVING WITHIN 1 YEAR.

Correction Required: PATCH CRACKS AND BROKEN AREAS OR REMOVE PART OF SURFACE TO ACHIEVE A SOUND BASE. PAVE A NEW WEARING SURFACE SUITABLE FOR TYPE OF VEHICLE TRAFFIC. SOME ROADS NEED REPAIR AND ADDITION OF A REJUVENATION COATING TO EXTEND LIFE UNTIL REPAVING IS NEEDED. REPAINT ALL MARKINGS AND STRIPES.

Estimated cost of correction: 85000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 260: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 254NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E074 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - CAMPUS WIDE

Complex: 150005 Asset: 23000000-0 Compass: 15000523000000-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: ADDITIONAL CAMPUS LIGHTING

Component: 2.300

Description of Deficiency: AS THE CAMPUS CHANGES, ADDITIONAL LIGHTING IS REQUIRED TO PROVIDE SAFE WALKWAYS.

Correction Required: INSTALL LIGHTING AS NEEDED FOR SAFETY.

Estimated cost of correction: 30000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 261: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 255NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-G126 Inspector: RCW

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - SIDEWALKS IN ALL AREAS

Complex: 150005 Asset: 24000000-0 Compass: 15000524000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: REPAIR / REPLACE SIDEWALKS

Component: 2.4

Description of Deficiency: SOME CONCRETE AND MASONRY WALKS AND STEPS THROUGHOUT CAMPUS HAVE BEEN DAMAGED BY FREEZING WEATHER CONDITIONS. SOME SURFACES ARE WEATHERED AND ERODED IN NUMEROUS LOCATIONS. SOME SURFACES ARE ROUGH AND UNEVEN. CRACKS AND STRUCTURAL DAMAGE HAVE ALSO DEVELOPED IN SOME PLACES.

Correction Required: PATCH OR REPAIR DAMAGED AREAS IN WALKS AND STEPS. CONSTRUCT NEW WALKS AND STEPS WHERE NEEDED.

Estimated cost of correction: 300000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 262: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 256NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M056 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - INFRASTRUCTURE - SEWER LINES

Complex: 150005 Asset: 31000000-0 Compass: 15000531000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE ALL THE DAMAGED SEWER LINES

Component: 3.1

Description of Deficiency: SOME SECTIONS OF THE SANITARY SEWER PIPING SYSTEM ARE KNOWN TO BE DAMAGED BEYOND REPAIR. MOST OF THOSE PIPES ARE SIX AND EIGHT INCH DIAMETER.

Correction Required: REPLACE ALL THE DAMAGED SEWER PIPING SYSTEM.

Estimated cost of correction: 400000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 263: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 257NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M057 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - INFRASTRUCTURE - SEWER MANHOLES

Complex: 150005 Asset: 31000000-0 Compass: 15000531000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: INSTALL TWO NEW MANHOLES FOR SEWAGE DRAIN SYSTEM

Component: 3.1

Description of Deficiency: DUE TO THE HILLY TOPOGRAPHICAL NATURE OF THE CAMPUS SITE, SEWER DRAIN BLOCKAGE IS A COMMON FREQUENT PROBLEM. THIS PROBLEM IS A HEALTH HAZARD AND REQUIRES EXTENSIVE REPAIR AND MAINTENANCE.

Correction Required: INSTALL TWO NEW MANHOLES FOR THE SEWAGE DRAIN SYSTEM.

Estimated cost of correction: 80000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 264: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 258NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M058 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - INFRASTRUCTURE - WATER DISTR.

Complex: 150005 Asset: 32000000-0 Compass: 15000532000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: REPLACE UPGRADE WATER LINES

Component: 3.200

Description of Deficiency: WATER DISTRIBUTION LINES ARE AGING, DAMAGED AND IN NEED OF EXTENSIVE REPAIR OR REPLACEMENT THROUGHOUT CAMPUS.

Correction Required: REPLACE WATER DISTRIBUTION SUPPLY LINES ON CAMPUS.

Estimated cost of correction: 1800000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 265: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 259NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M059 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - INFRASTRUCTURE - PLUMBING

Complex: 150005 Asset: 32000000-0 Compass: 15000532000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 2 Years

Deficiency Title: GENERAL MAINTENANCE CAMPUS WIDE

Component: 3.200

Description of Deficiency: THROUGHOUT CAMPUS, PLUMBING FIXTURES ARE MISSING AERATORS. USE OF AERATORS CAN HELP REDUCE WATER USAGE.

Correction Required: INSTALL AERATORS THROUGHOUT CAMPUS

Estimated cost of correction: 8000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 266: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(05) Category Page 260NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M060 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - INFRASTRUCTURE - STORM DRAINS

Complex: 150005 Asset: 33000000-0 Compass: 15000533000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 4 Years

Deficiency Title: UPGRADE STORM DRAIN SYSTEM

Component: 3.300

Description of Deficiency: THE STORM DRAIN SYSTEM ON CAMPUS IS INADEQUATE, AS EVIDENCED BY EROSION IN SEVERAL LOCATIONS.

Correction Required: UPGRADE THE STORM DRAIN SYSTEM, INCLUDING REPLACEMENT OF DAMAGED PIPING AND THE ADDITION OF CATCH BASINS.

Estimated cost of correction: 375000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 267: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(06) Category Page 261NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M061 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - INFRASTRUCTURE - STEAM DISTR.

Complex: 150005 Asset: 41000000-0 Compass: 15000541000000-0

Deficiency Type: 3 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 1 Years

Deficiency Title: REPLACE STEAM AND CONDENSATE PIPING

Component: 4.100

Description of Deficiency: OVER 6000 FT OF STEAM LINES TO BE REPLACED, EVEN MORE CONDENSATE LINES, AND 15-20 MANHOLES, MINIMUM. ALTHOUGH STEAM PIPING IS HOLDING UP, CONDENSATE PIPING IS DETERIORATING.

Correction Required: REPLACE HIGHEST PRIORITY LINES FIRST, DISTRIBUTION CHOKE POINTS AND HIGHEST LOSS OF CONDENSATE RETURN.

Estimated cost of correction: 4200000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 268: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(07) Category Page 262NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-M062 Inspector: RWT

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - INFRASTRUCTURE - ENERGY MGT

Complex: 150005 Asset: 43600000-0 Compass: 15000543600000-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 3 Years

Deficiency Title: CAMPUS ENERGY MANAGEMENT

Component: 4.360

Description of Deficiency: HVAC CONTROLS AND ENERGY MANAGEMENT SYSTEMS LACK COMPONENTS AT SEVERAL LOCATION TO ALLOW REMOTE MONITORING AND CONTROL.

Correction Required: UPGRADE ENERGY MANAGEMENT SYSTEM ON CAMPUS TO CONNECT EXISTING CONTROL SYSTEMS BY ADDING OR UPGRADING NECESSARY COMPONENTS

Estimated cost of correction: 180000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 269: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 263NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E075 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - INFRASTRUCTURE - ELECTRICAL

Complex: 150005 Asset: 44000000-0 Compass: 15000544000000-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 4 Years

Deficiency Title: UPGRADE DISTRIBUTION LINES

Component: 1.091

Description of Deficiency: THE EXISTING DISTRIBUTION LINES NEED REPLACING. PART OF THIS REPLACEMENT IS REQUIRED FOR A SAFE VOLTAGE INCREASE CONVERSATION.

Correction Required: REPLACE THE EXISTING LINES, UPGRADED FOR THE VOLTAGE CONVERSATION.

Estimated cost of correction: 200000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 270: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 264NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E076 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - INFRASTRUCTURE - ELECTRICAL

Complex: 150005 Asset: 51000000-0 Compass: 15000551000000-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: ADDITIONAL CALL BOXES

Component: 1.100

Description of Deficiency: ADDITIONAL CALL BOXES ARE NEEDED AS THE CAMPUS GROWS FOR THE SAFETY OF THE STUDENTS.

Correction Required: INSTALL CALL BOXES IN LOCATIONS POINTED OUT BY THE SAFETY OFFICER.

Estimated cost of correction: 25000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2

Page 271: North Carolina State Facility Condition Assessment Program€¦  · Web viewNC State Construction Office. Facility Condition Assessment Program. Deficiency Information. Deficiency

(16) Category Page 265NC State Construction Office

Facility Condition Assessment ProgramDeficiency Information

Deficiency No.: 08-E077 Inspector: GAR

Agency No.: 6000 Agency Name: UNIV

Institution & Building Name: WCU - INFRASTRUCTURE - ELECTRICAL

Complex: 150005 Asset: 57000000-0 Compass: 15000557000000-0

Deficiency Type: 1 (Initial Deficiency = 1; Maintenance Deficiency = 2; Normal Degradation = 3)

Correction Priority: 0 Years

Deficiency Title: ADDITIONAL EXIT AND EGRESS LIGHTING

Component: 1.101

Description of Deficiency: CAMPUS BUILDINGS NEED ADDITIONAL EGRESS AND EXIT LIGHTS.

Correction Required: INSTALL ADDITIONAL LIGHTS, AS REQUESTED BY THE SAFETY OFFICER.

Estimated cost of correction: 10000 Cost estimate status: 1(plus design fees and contingencies) Preliminary = 1

Final = 2

BLDG. FUNDED BY: 1 General Fund = 1Revenue Receipts = 2