1 GIB NOISE CONTROL ® SYSTEMS SUPPLEMENT MAY 2020 GIB ® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO Noise Control Systems Supplement Issue Date May 2020 GIB Noise Control ® Design Notes SUPPLEMENT ISSUE DATE Environmental Noise March 2006 Polyester Sound Control Infill Sept 2017 Additional Two way FRR Noise Control Systems June 2018 Additional GIB Barrierline ® junction details incorporating a rigid air barrier May 2020

Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

1GIB NOISE CONTROL® SYSTEMS SUPPLEMENTMAY 2020 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

Noise Control Systems SupplementIssue Date May 2020

GIB Noise Control® Design Notes

SUPPLEMENT ISSUE DATE

Environmental Noise March 2006

Polyester Sound Control Infill Sept 2017

Additional Two way FRR Noise Control Systems June 2018

Additional GIB Barrierline® junction details incorporating a rigid air barrier May 2020

Page 2: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

2GIB NOISE CONTROL® SYSTEMS SUPPLEMENTMARCH 2006 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION

Environmental NoiseIssue Date March 2006

This Environmental Noise information is an extract from the GIB Noise Control® Systems literature March 2006.

SPECIFIC DESIGN

The design information set out in this literature is

necessarily generalised and only applicable to normal

situations. Specific acoustic design advice should

be sought from an experienced acoustical engineer

in less common situations. For instance, inner city

apartment developments of more than 5 storeys

would usually benefit from specific design since

even minor optimisation in construction can result in

appreciable cost reductions.

Specific design is also required where a residential

development is located in a business or industrial zone

and a specified internal noise level must be achieved

for compliance with a building consent. The information

given in this publication is based on normal free flowing

traffic as the noise source and different types of noise

could change the noise reduction values given. In

particular this information should not be used where

the noise source is loud or amplified music. Specific

design is required in this case.

VARIATION IN SOUND RATINGS

The ability of building materials to resist the

transmission of sound is dependent on their density,

thickness and stiffness. Generally speaking light and

stiff materials have poor sound insulation properties

because they allow sound at certain frequencies (near

the so-called critical frequency) to transmit easily.

Materials of similar thickness and weight can have

different sound reduction performance if they have

different critical frequencies. For example, laminated

glass has a better sound reduction because it reduces

the effect of the critical frequency by damping vibration

and reducing the stiffness of the window.

MULTI-STOREY BUILDINGS

In multi-storey buildings typical of apartment

developments there are fewer transmission paths

than traditional, single occupant, single level houses.

For instance in the case of a bedroom on a mid level

there will be no significant external noise transmission

through the roof or the floor since these are shielded by

the apartments above and below.

Because there are fewer transmission paths the

overall noise reduction is greater than a house with

roof and floor paths. This factor can be included in

the design by using the partial system performances

detailed for types A, B and C construction. Thus for

the apartment with only a wall and window path the

performance is about 3 dBA higher than the overall

system performance.

Multi-storey buildings do not often use weatherboards

as an external cladding. However, 6mm fibre cement

board can be used as an equivalent to 20mm

weatherboards. It should be noted that the noise level

does not reduce significantly with height in multi-storey

buildings even up to 30 storeys and so the same

construction must be used on all levels.

WINDOW TO WALL RATIO

There is no optimum window to wall ratio. Generally

speaking, from an acoustic point of view, the smaller

the window the better as it is often the weakest

Page 3: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

3MARCH 2006 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION GIB NOISE CONTROL® SYSTEMS SUPPLEMENT

ENVIRONMENTAL NOISE

path and thicker glazing or double glazing is more

expensive in comparison to other building systems.

The newer types of laminated glazing using a PMM

interlayer (e.g. Pilkington HUSH Glass) provide about

a 3 dBA improvement over similar thickness float

glass. A 3 dBA reduction would otherwise require an

increase from 6mm to 10mm float glass.

ASSUMPTIONS IN DESIGN

The major assumption in design is that the noise

spectrum is a traffic noise spectrum. The noise

reduction may be a little more for industrial noise, which

generally has more mid to high frequency, and less for

low frequency dominated noises such as pubs or night-

clubs etc.

Another significant assumption is that windows are

perfectly sealed. This is a reasonable assumption for

aluminium joinery but a poor assumption for timber

joinery. We would not recommend standard timber

joinery for any noise reduction application above

standard construction. Also all design assumes closed

windows. Open windows will generally lower the noise

reduction to between 10 and 15 dBA.

Fibre cement board (6mm) can be used as an

equivalent to 20mm weatherboards. However, if a brick

veneer is specified a slightly higher dBA loss can be

expected.

Noise levels quoted are average levels. These are

Leq for traffic noise, Ldn for aircraft noise and L10 for

industrial noise.

Page 4: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

4MARCH 2006 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION GIB NOISE CONTROL® SYSTEMS SUPPLEMENT

ENVIRONMENTAL NOISE

Knowing the environmental noise levels for the area will determine which construction type is most suitable to achieve the indoor noise level required.

TRAFFIC NOISE

The average Leq traffic noise levels quoted in the table

below will assist in determining the likely noise levels

faced when building within a certain distance of a

particular type of road.

AIRCRAFT NOISE

Ldn noise levels quoted are the average levels for aircraft

noise. Each airport prepares a set of noise boundaries

called the Inner Control Boundary and the Outer

Control Boundary. These are based on the 65 dBA

Ldn contour and the 55 dBA Ldn contour respectively.

Outside the Outer Control Boundary no noise control

is deemed necessary. Between the Outer and Inner

Control Boundaries housing is a permitted activity but

the walls and roof of the house must provide sufficient

sound insulation to achieve a reasonable indoor noise

level. Inside the Inner Control Boundary housing is

generally a controlled or discretionary activity subject

to meeting the internal noise levels. The relevant Local

Authority sets the indoor level. The most common level

is 45 dBA Ldn. These noise levels are subject to change

from time to time. The building designer must consult

the local authority to ascertain the required indoor level

and consult the relevant planning maps to determine

the aircraft noise exposure at the proposed

building location.

INDUSTRIAL NOISE

L10 noise levels quoted are the average levels for

industrial noise. Generally when dwellings are built in

an industrial or business zoned area the building must

be built with sufficient sound insulation to reduce the

noise level inside to a reasonable level, assuming that

the industry next door is making the maximum noise

level permitted by the District Plan rules for that zone.

Often this ‘reasonable’ level will be left to the acoustic

consultant to determine. The usual indoor level used

is a level of 35 dBA for bedrooms at night and 45

dBA for other habitable spaces during the day. The

maximum noise level will vary from zone to zone and

also from Local Authority to Local Authority. Generally

the noise levels will be between 60 dBA and 75 dBA.

Zonings are subject to plan changes and the building

designer must consult the local authority to determine

the current zoning and noise rules.

Average Daily Traffic Flows v/d = vehicles per day

6 Lane Motorway 60,000 v/d 100 km/hr

4 Lane Motorway 25,000 v/d 100 km/hr

4 Lane Busy Urban Arterial Rd 20,000 v/d 60 km/hr

2 Lane Urban Rd 6,000 v/d 50 km/hr

Dis

tanc

e fro

m

road

edg

e to

ho

use

faca

de

12m 72 dBA 68 dBA 66 dBA 60 dBA

25m 67 dBA 63 dBA 61 dBA 55 dBA

80m 62 dBA 58 dBA 56 dBA 50 dBA

150m 57 dBA 53 dBA 51 dBA <50 dBA

Exa

mpl

e

Auckland Southern Motorway S.H.20 to Airport Mt Eden Rd, Ellerslie Panmure Highway

Wellington Hutt Road Cable St, Wakefield St, Vivian St, Taranaki St

Christchurch Northern Motorway Blenheim Rd, Riccarton Rd

ROAD TRAFFIC NOISE LEVELS (Leq dBA)

Page 5: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

5MARCH 2006 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION GIB NOISE CONTROL® SYSTEMS SUPPLEMENT

ENVIRONMENTAL NOISE (18-20 dBA REDUCTION) – TYPE A

For external walls requiring a performance of 18-20

dBA reduction the following construction can be used.

In the example below the system initially has a higher

performance of 24 dBA but as windows, roof and floor

are added, the performance decreases to give an

overall system loss of 18-20 dBA.

STANDARD CONSTRUCTION (18-20 dBA) REDUCTION SYSTEM PERFORMANCE (dBA) LOSS As windows, roof and flooring are included

Wall only 24 dBA reduction

Wall and Window 20-22 dBA reduction

Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies to concrete floors)

10mm GIB® Standard Plasterboard

90mm timber wall framing

18-20mm weatherboard or min. 6mm

Cavity construction as required

fibre cement or brick veneer

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(18-20 dBA reduction) - Type A GIB-004-01-17014 JUN 2017

AGIB-004-01-170 (18-20 dBA reduction) - Type A

18-20mm weatherboard or min. 6mmfibre cement or brick veneer 10mm GIB® Standard Plasterboard

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Up to 20% of wall area 4mm floatglass or up to 50% of wall area7mm Pilkington HUSH Glass

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(18-20 dBA reduction) - Type A GIB-004-01-17114 JUN 2017

AGIB-004-01-171 (18-20 dBA reduction) - Type A

10mm GIB® Standard plasterboard

18-20mm weatherboard or min. 6mmfibre cement or brick veneer

GIB® Rondo® metal batten

13mm GIB® Standard Plasterboard

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Concrete or 0.55mm profiled steelsheet or tile

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(18-20 dBA reduction) - Type A GIB-004-01-17218 JUN 2017

AGIB-004-01-172 (18-20 dBA reduction) - Type A

Page 6: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

6MARCH 2006 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION GIB NOISE CONTROL® SYSTEMS SUPPLEMENT

ENVIRONMENTAL NOISE (18-20 dBA REDUCTION) – TYPE A

STANDARD CONSTRUCTION (18-20 dBA) REDUCTION SYSTEM PERFORMANCE (dBA) LOSS As windows, roof and flooring are included

Wall, Window and Truss Roof 19-21 dBA reduction (This performance level applies to concrete floors)

Wall, Window, Roof and Timber Floor 18-20 dBA reduction

10mm GIB® Standard Plasterboard

18-20mm weatherboard or min. 6mmfibre cement or brick veneer

13mm GIB® Standard Plasterboard

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Concrete or 0.55mm profiled steelsheet or tile

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(18-20 dBA reduction) - Type A GIB-004-01-17314 JUN 2017

AGIB-004-01-173 (18-20 dBA reduction) - Type A

20mm particle board or orientedstrand board

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(18-20 dBA reduction) - Type A GIB-004-01-17414 JUN 2017

AGIB-004-01-174 (18-20 dBA reduction) - Type A

Page 7: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

7MARCH 2006 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION GIB NOISE CONTROL® SYSTEMS SUPPLEMENT

ENVIRONMENTAL NOISE (25 dBA REDUCTION) – TYPE B

For external walls requiring a performance of 25

dBA loss the following construction can be used. In

the example below the system initially has a higher

performance of 33 dBA but as windows, roof and

floor are added, the performance decreases to give an

overall system loss of 25 dBA.

CONSTRUCTION FOR (25 dBA) REDUCTION SYSTEM PERFORMANCE (dBA) LOSS As windows, roof and flooring are included

Wall only 33 dBA reduction

Wall and Window 29 dBA reduction

Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies to concrete floors)

2 x 10mmGIB Braceline® GIB Noiseline®

90mm timber wall framing

18-20mm weatherboard or min. 6mmfibre cement or brick veneer

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Sheathing material suitable for useunder external cladding minimum9.5 kg/m² (not required with brickveneer)

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(25 dBA reduction) - Type B GIB-004-01-18018 JUN 2017

AGIB-004-01-180 (25 dBA reduction) - Type B

Cavity construction as required

18-20mm weatherboard or min. 6mmfibre cement or brick veneer

2 x 10mmGIB Braceline® GIB Noiseline®

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Up to 20% of wall area 7mm floatglass or up to 50% of wall area11mm Pilkington HUSH Glass

Sheathing material suitable for useunder external cladding minimum9.5 kg/m² (not required with brickveneer)

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(25 dBA reduction) - Type B GIB-004-01-18118 JUN 2017

AGIB-004-01-181 (25 dBA reduction) - Type B

2 x 10mmGIB Braceline® GIB Noiseline®

18-20mm weatherboard or min. 6mmfibre cement or brick veneer

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Concrete or 0.55mm profiled steelsheet or tile

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

12mm particle board or similar sarking

Sheathing material suitable for useunder external cladding minimum9.5 kg/m² (not required with brickveneer)

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(25 dBA reduction) - Type B GIB-004-01-18218 JUN 2017

AGIB-004-01-182 (25 dBA reduction) - Type B

GIB® Rondo® metal batten

13mm GIB® Standard Plasterboard

Page 8: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

8MARCH 2006 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION GIB NOISE CONTROL® SYSTEMS SUPPLEMENT

ENVIRONMENTAL NOISE (25 dBA REDUCTION) – TYPE B

CONSTRUCTION FOR (25 dBA) REDUCTION SYSTEM PERFORMANCE (dBA) LOSS As windows, roof and flooring are included

Wall, Window and Truss Roof 26 dBA reduction(This performance level applies to concrete floors)

Wall, Window, Roof and Timber Floor 25 dBA reduction

2 x 10mmGIB Braceline® GIB Noiseline®

18-20mm weatherboard or min. 6mmfibre cement or brick veneer

13mmGIB Braceline® GIB Noiseline®

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Concrete or 0.55mm profiled steelsheet or tile

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Sheathing material suitable for useunder external cladding minimum9.5 kg/m² (not required with brickveneer)

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(25 dBA reduction) - Type B GIB-004-01-18318 JUN 2017

AGIB-004-01-183 (25 dBA reduction) - Type B

2 x 20mm particle board or orientedstrand board

6mm fibre cement or similar

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(25 dBA reduction) - Type B GIB-004-01-18418 JUN 2017

AGIB-004-01-184 (25 dBA reduction) - Type B

Page 9: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

9MARCH 2006 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION GIB NOISE CONTROL® SYSTEMS SUPPLEMENT

ENVIRONMENTAL NOISE (30 dBA REDUCTION) – TYPE C

For external walls requiring a performance of 30

dBA loss the following construction can be used. In

the example below the system initially has a higher

performance of 35 dBA but as windows, roof and

floor are added, the performance decreases to give an

overall system loss of 30 dBA.

CONSTRUCTION FOR (30 dBA) REDUCTION SYSTEM PERFORMANCE (dBA) LOSS As windows, roof and flooring are included

Wall only 35 dBA reduction

Wall and Window 32 dBA reduction

Wall, Window and Skillion Roof 31 dBA reduction(This performance level applies to concrete floors)

2 x 10mmGIB Braceline® GIB Noiseline®

90mm timber wall framing

18-20mm weatherboard or min. 6mm

Cavity construction as required

fibre cement or brick veneer

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

GIB Rail®

Sheathing material suitable for useunder external cladding minimum9.5 kg/m² (not required with brickveneer)

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(30 dBA reduction) - Type C GIB-004-01-19018 JUN 2017

AGIB-004-01-190 (30 dBA reduction) - Type C

18-20mm weatherboard or min. 6mmfibre cement or brick veneer

2 x 10mmGIB Braceline® GIB Noiseline®

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Up to 20% of wall area 11mmPilkington HUSH Glass

Sheathing material suitable for useunder external cladding minimum9.5 kg/m² (not required with brickveneer)

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(30 dBA reduction) - Type C GIB-004-01-19118 JUN 2017

AGIB-004-01-191 (30 dBA reduction) - Type C

2 x 10mmGIB Braceline® GIB Noiseline®

18-20mm weatherboard or min. 6mmfibre cement or brick veneer

GIB Braceline® GIB Noiseline®

GIB® Rondo® metal batten

2 x 13mm

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Concrete or 0.55mm profiled steelsheet or tile

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

12mm particle board or similar sarking

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(30 dBA reduction) - Type C GIB-004-01-19218 JUN 2017

AGIB-004-01-192 (30 dBA reduction) - Type C

Page 10: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

10MARCH 2006 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION GIB NOISE CONTROL® SYSTEMS SUPPLEMENT

ENVIRONMENTAL NOISE (30 dBA REDUCTION) – TYPE C

STANDARD CONSTRUCTION (18-20 dBA) REDUCTION SYSTEM PERFORMANCE (dBA) LOSS As windows, roof and flooring are included

Wall, Window and Pitched Roof 31 dBA reduction

(This performance level applies to concrete floors)

Wall, Window, Roof and Timber Floor 30 dBA reduction

2 x 10mmGIB Braceline® GIB Noiseline®

18-20mm weatherboard or min. 6mmfibre cement or brick veneer

2 x 13mmGIB Braceline® GIB Noiseline®

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Concrete or 0.55mm profiled steelsheet

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

Sheathing material suitable for useunder external cladding minimum9.5 kg/m² (not required with brickveneer)

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(30 dBA reduction) - Type C GIB-004-01-19318 JUN 2017

AGIB-004-01-193 (30 dBA reduction) - Type C

2 x 20mm particle board or orientedstrand board

6mm fibre cement or similar

Pink® Batts® R2.2 (90mm) glasswool insulation (min)

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:Scale:

Date:

Reference

File:

1 : 10

GIB® Noise Control SystemEnvironmental Noise(30 dBA reduction) - Type C GIB-004-01-19418 JUN 2017

AGIB-004-01-194 (30 dBA reduction) - Type C

Page 11: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

11MARCH 2006 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION GIB NOISE CONTROL® SYSTEMS SUPPLEMENT

EXAMPLE – INSULATING FOR ENVIRONMENTAL NOISE

CONSTRUCTION TYPE C 30 dBA REDUCTION

When using Type C construction to control

environmental noise, only the section facing the noise

source needs to be specified Type C. The further

away from the noise source the lower the dBA loss

system required.

30 dBA reduction (construction Type C). The front wall and down the side walls of front rooms only facingthe noise source

5 dBA less than the construction for the wall facing the noise source. 25 dBA reduction (construction Type B)

5 dBA less than the construction for the wall facing the noise source. 25 dBA reduction (construction Type B)

10 dBA less than the construction for the wall facing the noise source. Construction Type A 18-20 dBA reduction.

Noise source

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

1 : 180

GIB® Noise Control SystemInsulating for Environmental Noise(30 dBA reduction) - Type C GIB-004-01-19518 JUN 2017

AGIB-004-01-195 Insulating for Environmental Noise

Note: When using construction methods Type B or Type C, all of the roof and ground floor (timber floors only) must be fully constructed to that specification. i.e. no reduction relating to distance from noise source.

Page 12: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

12GIB NOISE CONTROL® SYSTEMS SUPPLEMENTSEPTEMBER 2017 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION

Polyester Sound Control Infill Issue Date September 2017

It is acceptable to replace the specified Pink® Batts® glass wool infill in GIB Noise Control® Systems with polyester fibre infill of the same or greater thickness (if not compressed) provided the polyester manufacturer can prove it meets the minimum properties shown in the table below.

Based on testing carried out by Winstone Wallboards

in April 2017, subject to the conditions below, the

noise attenuation ratings specified in ‘GIB Noise

Control® Systems, 2017’ will be retained when

polyester fibre infill with the minimum properties listed

in the table above are substituted for either R1.2

(50mm), R1.8 (75mm) or R2.2 (90mm) Pink® Batts®

glass wool insulation of the same or greater thickness

(refer to the thickness of the Pink® Batts® specified in

the applicable GIB Noise Control® System).

In most cases GIB Noise Control® Systems also

provide Fire Resistance Ratings (FRRs). Subject to

the conditions below, substituting 100% polyester

fibre infill with the minimum properties listed in the

table above for either R1.2 (50mm), R1.8 (75mm) or

R2.2 (90mm) Pink® Batts® glass wool of the same or

greater thickness will retain the published FRRs for

these systems.

To maintain the specified STC and IIC ratings, it is

allowable to use the same thickness of polyester fibre

infill as the originally specified Pink® Batts® glass wool

infill. A greater thickness of polyester fibre infill may be

used, provided it is not compressed when installed

into the framing cavity.

The performance of any other infill product type must be

independently verified.

Conditions

— Except to the extent expressly stated in this

Testing Statement, where any substitution of

cavity infill takes place, independent verification

must be obtained to confirm that the noise control

performance of the system will be maintained.

Polyester fibre infill, and other insulation products’,

properties and characteristics may vary by

product type and manufacturer.

— It remains the responsibility of the specifier,

supplier and user to ensure compliance with the

performance and requirements in this document,

all other requirements and conditions of ‘GIB

Noise Control® Systems, 2017’, all applicable

manufacturer’s requirements, all required quality

and durability standards, and all Building Code

requirements.

Product Material Measured Density Kg/m3 Air Flow Resistivity rayls/m

Polyester Infill 100% Polyester 14.7 1900

Page 13: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

13SEPTEMBER 2017 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION GIB NOISE CONTROL® SYSTEMS SUPPLEMENT

— The testing referred to in this Testing Statement

related solely to noise attenuation and fire ratings,

and no assurance or representation is made in

relation to any other property or performance

characteristic of any infill except as expressly

stated in this document, and subject in all cases

to product-specific information issued by the

manufacturer.

POLYESTER SOUND CONTROL INFILL

Page 14: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

14GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

Additional Two way FRR Noise Control SystemsIssue Date June 2018

Complementing the full range of systems within the GIB Noise Control Systems® literature, Winstone Wallboards has recently completed testing on an additional range of systems for both intertenancy and sub-intertenancy situations.

In addition to releasing a range of systems that utilise

a single layer of GIB® plasterboard on either side, this

release includes specific systems codes that correlate

to systems utilising GIB Toughline® and GIB Toughline®

Aqua (formerly GIB Superline®). While GIB® alternative

tables can still be used to substitute different GIB®

plasterboards within a GIB® system to gain additional

performance characteristics, we are responding to

an industry desire to have specific codes for systems

utilising specific boards.

For any further information, please contact the

GIB® Helpline on 0800 100 442.

Page 15: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

15GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – INTERTENANCY

Two way FRR – double timber frame wall

Specification number Performance Specifications

GBTLA 60a STC

Rw

FRR

56

55

60/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Toughline® each side

Load bearing

1 x layer Pink® Batts® BIB R1.8 (75mm)

GBTLA 60b STC

Rw

FRR

56

57

60/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Braceline® / GIB Noiseline® each side

Load bearing

1 x layer Pink® Batts® BIB R1.8 (75mm)

GBTLA 60c STC

Rw

FRR

56

55

60/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Fyreline® each side

Load bearing

1 x layer Pink® Batts® BIB R1.8 (75mm)

GBTLA 60a2 STC

Rw

FRR

62

60

60/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Toughline® each side

Load bearing

2 x layers Pink® Batts® BIB R1.8 (75mm)

GBTLA 60b2 STC

Rw

FRR

63

62

60/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Braceline® / GIB Noiseline® each side

Load bearing

2 x layers Pink® Batts® BIB R1.8 (75mm)

GBTLA 60c2 STC

Rw

FRR

62

60

60/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Fyreline® each side

Load bearing

2 x layers Pink® Batts® BIB R1.8 (75mm)

Wet area option

GBTLA 60d STC

Rw

FRR

56

55

60/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Toughline® Aqua each side

Load bearing

1 x layer Pink® Batts® BIB R1.8 (75mm)

GBTLA 60d2 STC

Rw

FRR

62

60

60/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Toughline® Aqua each side

Load bearing

2 x layers Pink® Batts® BIB R1.8 (75mm)

FRAMING

Stud size Space between frames

90mm 25mm min

Framing to comply with:

— NZBC B1 — Structure: AS1 Clause 3 — Timber (NZS 3604) or VM1 Clause 6 — Timber (NZS 3603).

— NZBC B2 — Durability: AS1 Clause 3.2 — Timber (NZS 3602).— Studs at 600mm centres maximum.— Nogs at 1200mm centres for horizontal fixing.

Non-loading — Framing dimensions and heights as determined by NZS 3604 stud tables for non-loadbearing partitions.

Loadbearing — Framing Dimensions and height as determined by NZS 3604 stud and top plate tables for loadbearing walls.

Warning: The STC performance figures listed in the table above are based on studs spaced at 600mm centres. Reducing stud centres to less than 600mm will significantly lower the STC performance of these systems.

SOUND CONTROL INFILL

Pink® Batts® BIB R1.8 (75mm) minimum glass wool insulation installed between the studs and nogs.

WALL LINING

GIB® plasterboard linings as prescribed in the table above.

Vertical or horizontal fixing permitted.

Sheets shall be touch fitted.

When fixing vertically, use full height sheets where possible.

To achieve the fire rated performance figures listed in the table above all sheet joints must be formed over solid timber framing.

ACOUSTIC SEALANT

A bead of GIB Soundseal® acoustic sealant is required around the perimeter of the framing. The linings are then bedded onto the bead.

Page 16: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

16GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – INTERTENANCY

Layer of GIB® plasterboard as prescribed in table above

Pink® Batts® BIB R1.8 (75mm)

Double timber studs

FASTENING THE LINING

Fasteners 41mm x 6g GIB® Grabber® High Thread Drywall Screws.

Fastener centres Single screw at 300mm centres around the sheet perimeter.

Single screw at 300mm centres to intermediate studs.

Place fasteners 12mm from bound sheet edges and 18mm from sheet ends.

For tiled walls (tile weight up to 32kg/m2) Single screw at 100mm centres to perimeter of tiled wall and to all intermediate studs. No Adhesive.

Refer to GIB Aqualine® Wet Area System literature for complete wet area system details.

JOINTING

All fastener heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled “GIB® Site Guide”. Wall to ceiling junctions are to be reinforced with GIB® Paper Tape or GIB® RocTape and square stopped or finished with GIB-Cove®.

Screws at 300mm centres to intermediate studs

Screws at 300mm centres to sheet perimeter

Page 17: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

17GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – INTERTENANCY

Two way FRR – double timber frame wall

Specification number Performance Specifications

GBTLA 90e STC

Rw

FRR

60

59

-/90/90

Lining

LB/NLB

Insulation

1 x 16mm GIB Fyreline® each side

Load bearing

1 x layer Pink® Batts® R1.8 (75mm)

GBTLA 90e2 STC

Rw

FRR

65

63

-/90/90

Lining

LB/NLB

Insulation

1 x 16mm GIB Fyreline® each side

Load bearing

2 x layers Pink® Batts® R1.8 (75mm)

FRAMING

Stud size Space between frames

90mm 25mm min

Framing to comply with:

— NZBC B1 — Structure: AS1 Clause 3 — Timber (NZS 3604) or VM1 Clause 6 — Timber (NZS 3603).

— NZBC B2 — Durability: AS1 Clause 3.2 — Timber (NZS 3602).— Studs at 600mm centres maximum.— Nogs at 1200mm centres for horizontal fixing.

Non-loading — Framing dimensions and heights as determined by NZS 3604 stud tables for non-loadbearing partitions.

Loadbearing — Framing Dimensions and height as determined by NZS 3604 stud and top plate tables for loadbearing walls.

Warning: The STC performance figures listed in the table above are based on studs spaced at 600mm centres. Reducing stud centres to less than 600mm will significantly lower the STC performance of these systems.

SOUND CONTROL INFILL

Pink® Batts® BIB R1.8 (75mm) minimum glass wool insulation installed between the studs and nogs.

WALL LINING

1 layer of 16mm GIB Fyreline® each side of the frame.

Vertical or horizontal fixing permitted.

Sheets shall be touch fitted.

When fixing vertically, use full height sheets where possible.

To achieve the fire rated performance figures listed in the table above all sheet joints must be formed over solid timber framing.

ACOUSTIC SEALANT

A bead of GIB Soundseal® acoustic sealant is required around the perimeter of the framing. The linings are then bedded onto the bead.

FASTENING THE LINING

Fasteners 51mm x 7g GIB® Grabber® High Thread Drywall Screws.

Fastener centres Single screw at 300mm centres around the sheet perimeter.

Single screw at 300mm centres to intermediate studs.

Place fasteners 12mm from bound sheet edges and 18mm from sheet ends.

JOINTING

All fastener heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled “GIB® Site Guide”. Wall to ceiling junctions are to be reinforced with GIB® Paper Tape or GIB® RocTape and square stopped or finished with GIB-Cove®.

Page 18: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

18GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – INTERTENANCY

1 x layer of 16mm GIB Fyreline® plasterboard

Pink® Batts® BIB R1.8 (75mm)

Double timber studs

Screws at 300mm centres to intermediate studs

Screws at 300mm centres to sheet perimeter

Page 19: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

19GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – INTERTENANCY

Two way FRR – double steel frame wall

Specification number Performance Specifications

GBSA 60d STC

Rw

FRR

57

55

-/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Toughline® each side

Non load bearing

1 x layer Pink® Batts® R1.8 (75mm)

GBSA 60e STC

Rw

FRR

58

57

-/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Braceline® / GIB Noiseline® each side

Non load bearing

1 x layer Pink® Batts® R1.8 (75mm)

GBSA 60d2 STC

Rw

FRR

62

60

-/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Toughline® each side

Non load bearing

2 x layers Pink® Batts® R1.8 (75mm)

GBSA 60e2 STC

Rw

FRR

62

62

-/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Braceline® / GIB Noiseline® each side

Non load bearing

2 x layers Pink® Batts® R1.8 (75mm)

Wet area option

GBSA 60f STC

Rw

FRR

57

55

-/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Toughline® Aqua each side

Non load bearing

1 x layer Pink® Batts® R1.8 (75mm)

GBSA 60f2 STC

Rw

FRR

62

60

-/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Toughline® Aqua each side

Non load bearing

2 x layers Pink® Batts® R1.8 (75mm)

FRAMING AND WALL HEIGHT

Stud size Space between frames

64 x 34 x 0.50mm 25mm min

Minimum steel stud dimensions to be 64 x 34 x 0.50mm nominal with a 6mm return.

Minimum steel track dimensions to be 64 x 30 x 0.50mm nominal.

Top and bottom tracks are fixed to the floor and ceiling in true alignment.

Stud spacing at 600mm centres maximum.

Place studs to allow an expansion gap at the top of the frame as per the table below.

The studs are held in place by the “grip” of the channel runners. Light locating fasteners that fail at high temperatures, such as single aluminium rivets may be used. Otherwise positive fixing must be avoided.

Recommended maximum wall height Note that maximum wall heights for fire-rated systems can be lower than what can be achieved with non-fire-rated construction.

Nominal stud dimension (mm)

BMT (mm)

Stud centres (mm)

Max. wall height (mm)

Expansion at top of studs (mm)

64 x 340.50 or 0.55

600 2700 15

400 3000 15

76 x 34

0.55600 3200 15

400 3600 20*

0.75600 3600 20*

400 4200 20*

92 x 34

0.55600 3600 20*

400 4200 20*

0.75600 4200 20*

400 4800 25*

*Use a minimum 50mm deep head channel.

Contact the GIB® Helpline for different framing configurations.

Page 20: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

20GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – INTERTENANCY

SOUND CONTROL INFILL

Pink® Batts® BIB R1.8 (75mm) minimum glass wool insulation installed between the studs.

ACOUSTIC SEALANT

A bead of GIB Soundseal® acoustic sealant is required around the perimeter of the framing. The linings are then bedded onto the bead.

LINING

GIB® plasterboard as prescribed in the tables above.

Vertical fixing only permitted.

Sheets shall be touch fitted.

Offset joints between sheets on opposite sides of the frame.

Full height sheets shall be used where possible.

When sheet end butt joints are unavoidable, they shall fixed at 200mm centres and be formed over nogs.

All sheet joints must be formed over framing. Linings are fixed hard to floor.

FASTENING THE LINING

Fasteners 25mm x 6g GIB® Grabber® Drywall Self Tapping Screws.

Fastener centres 300mm centres up each stud.

Place stud fasteners 12mm from sheet edges generally and 50mm from sheet ends.

Fastening the linings at 18mm from sheet ends to top and bottom tracks is permitted as long as the fasteners do not connect the studs and tracks.

For tiled walls (tile weight up to 32kg/m2)Single screw at 100mm centres to perimeter of tiled wall and to all intermediate studs. No Adhesive.

Refer to GIB Aqualine Wet Area System literature for complete wet area system details.

SERVICES

Holes may be drilled or pre-punched in the metal studs to allow installation of electrical service lines and plumbing supply pipes.

JOINTING

All screw heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled “GIB® Site Guide”.

Layer of GIB® plasterboard as prescribed in the table above

Pink® Batts® BIB R1.8 (75mm)

Screws to 300mm centres up each stud

Page 21: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

21GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – INTERTENANCY

Two way FRR – double steel frame wall

Specification number Performance Specifications

GBSA 90e STC

Rw

FRR

60

59

-/90/90

Lining

LB/NLB

Insulation

1 x 16mm GIB Fyreline® each side

Non load bearing

1 x layer Pink® Batts® R1.8 (75mm)

GBSA 90e2 STC

Rw

FRR

64

63

Lining

LB/NLB

Insulation

1 x 16mm GIB Fyreline® each side

Non load bearing

2 x layers Pink® Batts® R1.8 (75mm)

FRAMING AND WALL HEIGHT

Stud size Space between frames

64 x 34 x 0.50mm 25mm min

Minimum steel stud dimensions to be 64 x 34 x 0.50mm nominal with a 6mm return.

Minimum steel track dimensions to be 64 x 30 x 0.50mm nominal.

Top and bottom tracks are fixed to the floor and ceiling in true alignment.

Stud spacing at 600mm centres maximum.

Place studs to allow an expansion gap at the top of the frame.

The studs are held in place by the “grip” of the channel runners. Light locating fasteners that fail at high temperatures, such as single aluminium rivets may be used. Otherwise positive fixing must be avoided.

Recommended maximum wall height Note that maximum wall heights for fire-rated systems can be lower than what can be achieved with non-fire-rated construction.

Nominal stud dimension (mm)

BMT (mm)

Stud centres (mm)

Max. wall height (mm)

Expansion at top of studs (mm)

64 x 340.50 or 0.55

600 2700 15

400 3000 15

76 x 34

0.55600 3200 15

400 3600 20*

0.75600 3600 20*

400 4200 20*

92 x 34

0.55600 3600 20*

400 4200 20*

0.75600 4200 20*

400 4800 25*

*Use a minimum 50mm deep head channel.

Contact the GIB® Helpline for different framing configurations.

Page 22: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

22GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – INTERTENANCY

SOUND CONTROL INFILL

Pink® Batts® BIB R1.8 (75mm) minimum glass wool insulation installed between the studs.

ACOUSTIC SEALANT

A bead of GIB Soundseal® acoustic sealant is required around the perimeter of the framing. The linings are then bedded onto the bead.

LINING

1 layer of 16mm GIB Fyreline® each side of the frame.

Vertical fixing only permitted.

Sheets shall be touch fitted.

Offset joints between sheets on opposite sides of the frame.

Full height sheets shall be used where possible.

When sheet end butt joints are unavoidable, they shall be formed over nogs.

All sheet joints must be formed over framing. Linings are fixed hard to floor.

FASTENING THE LINING

Fasteners 32mm x 6g GIB® Grabber® Drywall Self Tapping Screws.

Fastener centres 300mm centres up each stud.

Place stud fasteners 12mm from sheet edges generally and 50mm from sheet ends.

Fastening the linings at 18mm from sheet ends to top and bottom tracks is permitted as long as the fasteners do not connect the studs and tracks.

SERVICES

Holes may be drilled or pre-punched in the metal studs to allow installation of electrical service lines and plumbing supply pipes.

JOINTING

All screw heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled “GIB® Site Guide”.

1 layer of 16mm GIB Fyreline® plasterboard

Pink® Batts® BIB R1.8 (75mm)

Double Steel stud

Screws to 300mm centres up each stud

Page 23: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

23GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – INTERTENANCY

Page 24: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

24GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – INTERTENANCY

Two way FRR – steel frame wall – GIB Rondo® Quiet Stud®

Specification number Performance Specifications

GBQSA 90a STC

Rw

FRR

61

60

-/90/90

Lining

LB/NLB

Insulation

1 x 13mm GIB Toughline® (outer layer) and 1 x 10mm GIB Braceline® / GIB Noiseline® (inner layer) each side

Non load bearing

1 x layer Pink® Batts® R1.8 (75mm)

Wet area option

GBQSA 90b STC

Rw

FRR

61

60

-/90/90

Lining

LB/NLB

Insulation

1 x 13mm Toughline® Aqua (outer layer) and 1 x 10mm GIB Braceline® / GIB Noiseline® (inner layer) each side

Non load bearing

1 x layer Pink® Batts® R1.8 (75mm)

FRAMING

Stud size Space between frames

92 x 45 x 0.75mm N/A

GIB Rondo® Quiet Stud® resilient steel stud 92 x 45 x 0.75mm BMT and placed in 92 x 30 x 0.55mm BMT steel channel. Channel is fixed to floor and ceiling. Studs are friction fitted at 600mm centres maximum with a 15mm expansion gap at the top of the frame. No fixings to the top channel.

WALL HEIGHTS

Recommended maximum wall height is 3000mm. For wall heights up to 3400mm place studs at 400mm centres. For greater heights please contact the GIB® Helpline.

SOUND CONTROL INFILL

Pink® Batts® BIB R1.8 (75mm) minimum glass wool insulation installed between the studs.

ACOUSTIC SEALANT

A bead of GIB Soundseal® acoustic sealant is required around the perimeter of the inner lining. The outer lining is then bedded onto the bead.

LINING

1 layer of 13mm GIB Toughline® or GIB Toughline® Aqua plasterboard (outer layer) and 1 layer 10mm GIB Braceline® / GIB Noiseline® (inner layer) each side of the frame.

Inner layer joints on opposite sides of the frame are offset. Vertical joints of the outer layer are offset 600mm from those of the inner layer.

The inner layers must be fitted hard to floor. Use full height sheets where possible.

Sheet joints are touch fitted and must occur over framing. Where sheet end joints are unavoidable they must be over nogs and the outer layer joints offset from those on the inner layer.

FASTENING THE LINING

Fasteners Inner Layer: 25mm x 6g GIB® Grabber® Drywall Self Tapping Screws.

Outer Layer: 41mm x 6g GIB® Grabber® Self Tapping Screws.

Fastener centres Inner and Outer layer: 300mm centres up each stud.

Place stud fasteners 12mm from sheet edges generally and 50mm from sheet ends.

Fastening the linings at 18mm from sheet ends to top and bottom tracks is permitted as long as the fasteners do not connect the studs and tracks.

For tiled walls (tile weight up to 32kg/m2)Outer Layers: Single screw at 100mm centres to perimeter of tiled wall and to all intermediate studs. No Adhesive.

Refer to GIB Aqualine® Wet Area system literature for complete wet area system details.

JOINTING

All screw heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled “GIB® Site Guide”.

Page 25: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

25GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – INTERTENANCY

Outer layer: 1 layer of 13mm GIB Toughline® or 13mm GIB Toughline® Aqua

Inner Layer: 1 layer of 10mm GIB Braceline® / GIB Noiseline®

Pink® Batts® BIB R1.8 (75mm)

GIB Rondo® Quiet Stud®

Screws to 300mm centres up each stud for both inner and outer layers

Page 26: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

26GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – SUB-INTERTENANCY

Two way FRR – timber frame wall

Specification number Performance Specifications

GST 132a STC

Rw

FRR

40

39

30/30/30

Lining

LB/NLB

Insulation

1 x 13mm GIB® Standard each side

Load bearing

1 x layer Pink® Batts® R1.8 (75mm)

FRAMING

Stud size Space between frames

90mm N/A

Framing to comply with:

— NZBC B1 — Structure: AS1 Clause 3 — Timber (NZS 3604) or VM1 Clause 6 — Timber (NZS 3603).

— NZBC B2 — Durability: AS1 Clause 3.2 — Timber (NZS 3602).— Studs at 600mm centres maximum.— Nogs at 1200mm centres for horizontal fixing.

Non-loading — Framing dimensions and heights as determined by NZS 3604 stud tables for non-loadbearing partitions.

Loadbearing — Framing Dimensions and height as determined by NZS 3604 stud and top plate tables for loadbearing walls.

Warning: The STC performance figures listed in the table above are based on studs spaced at 600mm centres. Reducing stud centres to less than 600mm will significantly lower the STC performance of these systems.

SOUND CONTROL INFILL

A layer of Pink® Batts® BIB R1.8 (75mm) minimum glass wool insulation installed between the studs and nogs.

WALL LINING

1 layer of 13mm GIB® Standard each side of the frame.

Vertical or horizontal fixing permitted.

Sheets shall be touch fitted.

When fixing vertically, use full height sheets where possible.

All sheet joints must be formed over solid timber framing.

ACOUSTIC SEALANT

A bead of GIB Soundseal® acoustic sealant is required around the perimeter of the framing. The linings are then bedded onto the bead.

FASTENING THE LINING

Fasteners 41mm x 6g GIB® Grabber® High Thread Drywall Screws.

Fastener centres Single screw at 300mm centres around the sheet perimeter.

Single screw at 300mm centres to intermediate studs.

Place fasteners 12mm from bound sheet edges and 18mm from sheet ends.

JOINTING

All fastener heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled “GIB® Site Guide”. Wall to ceiling junctions are to be reinforced with GIB® Paper Tape or GIB® RocTape and square stopped or finished with GIB-Cove®.

Page 27: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

27GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – SUB-INTERTENANCY

1 layer of 13mm GIB® Standard plasterboard

Pink® Batts® BIB R1.8 (75mm)

Timber stud

Screws at 300mm centres to intermediate studs

Screws at 300mm centres to sheet perimeter

Page 28: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

28GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – SUB-INTERTENANCY

Two way FRR – steel frame wall

Specification number Performance Specifications

GSS 132a STC

Rw

FRR

45

44

-/30/30

Lining

LB/NLB

Insulation

1 x 13mm GIB® Standard each side

Non load bearing

1 x layer Pink® Batts® R1.8 (75mm)

FRAMING AND WALL HEIGHT

Minimum steel stud dimensions to be 64 x 34 x 0.50mm nominal with a 6mm return.

Minimum steel track dimensions to be 64 x 30 x 0.50mm nominal.

Top and bottom tracks are fixed to the floor and ceiling in true alignment.

Stud spacing at 600mm centres maximum.

Place studs to allow an expansion gap at the top of the frame as per the table below.

The studs are held in place by the “grip” of the channel runners. Light locating fasteners that fail at high temperatures, such as single aluminium rivets may be used. Otherwise positive fixing must be avoided.

Recommended maximum wall heightNote that maximum wall heights for fire-rated systems can be lower than what can be achieved with non-fire-rated construction.

Nominal stud dimension (mm)

BMT (mm)

Stud centres (mm)

Max. wall height (mm)

Expansion at top of studs (mm)

64 x 340.50 or 0.55

600 2700 15

400 3000 15

76 x 34

0.55600 3200 15

400 3600 20*

0.75600 3600 20*

400 4200 20*

92 x 34

0.55600 3600 20*

400 4200 20*

0.75600 4200 20*

400 4800 25*

*Use a minimum 50mm deep head channel.

Contact the GIB® Helpline for different framing configurations.

SOUND CONTROL INFILL

Pink® Batts® BIB R1.8 (75mm) minimum glass wool insulation installed between the studs and nogs.

ACOUSTIC SEALANT

A bead of GIB Soundseal® acoustic sealant is required around the perimeter of the framing. The linings are then bedded onto the bead.

LINING

1 layer of 13mm GIB® Standard plasterboard each side of the frame.

Vertical fixing only permitted.

Sheets shall be touch fitted.

Offset joints between sheets on opposite sides of the frame.

Full height sheets shall be used where possible.

When sheet end butt joints are unavoidable, they shall be fixed at 200mm centres and formed over nogs.

All sheet joints must be formed over framing. Linings are fixed hard to floor.

FASTENING THE LINING

Fasteners 25mm x 6g GIB® Grabber® Drywall Self Tapping Screws.

Fastener centres 300mm centres up each stud.

Place stud fasteners 12mm from sheet edges generally and 50mm from sheet ends.

Fastening the linings at 18mm from sheet ends to top and bottom tracks is permitted as long as the fasteners do not connect the studs and tracks.

SERVICES

Holes may be drilled or pre-punched in the metal studs to allow installation of electrical service lines and plumbing supply pipes.

JOINTING

All screw heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled “GIB® Site Guide”.

Page 29: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

29GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – SUB-INTERTENANCY

1 layer of 13mm GIB® Standard plasterboard

Pink® Batts® BIB R1.8 (75mm)

Steel stud

Screws to 300mm centres up each stud

Page 30: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

30GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – SUB-INTERTENANCY

Two way FRR – steel frame wall

Specification number Performance Specifications

GSS134a STC

Rw

FRR

50

49

-/45/45

Lining

LB/NLB

Insulation

2 x 13mm GIB® Standard each side

Non load bearing

1 x layer Pink® Batts® R1.8 (75mm)

FRAMING AND WALL HEIGHT

Minimum steel stud dimensions to be 64 x 34 x 0.50mm nominal with a 6mm return.

Minimum steel track dimensions to be 64 x 30 x 0.50mm nominal.

Top and bottom tracks are fixed to the floor and ceiling in true alignment.

Stud spacing at 600mm centres maximum.

Place studs to allow an expansion gap at the top of the frame as per the table below.

The studs are held in place by the “grip” of the channel runners. Light locating fasteners that fail at high temperatures, such as single aluminium rivets may be used. Otherwise positive fixing must be avoided.

Recommended maximum wall heightNote that maximum wall heights for fire-rated systems can be lower than what can be achieved with non-fire-rated construction.

Nominal stud dimension (mm)

BMT (mm)

Stud centres (mm)

Max. wall height (mm)

Expansion at top of studs (mm)

64 x 340.50 or 0.55

600 2700 15

400 3000 15

76 x 34

0.55600 3200 15

400 3600 20*

0.75600 3600 20*

400 4200 20*

92 x 34

0.55600 3600 20*

400 4200 20*

0.75600 4200 20*

400 4800 25*

*Use a minimum 50mm deep head channel.

Contact the GIB® Helpline for different framing configurations.

SOUND CONTROL INFILL

Pink® Batts® BIB R1.8 (75mm) minimum glass wool insulation installed between the studs.

ACOUSTIC SEALANT®

A bead of GIB Soundseal® acoustic sealant is required around the perimeter of the inner lining. The outer lining is then bedded onto the bead.

LINING

2 layers of 13mm GIB® Standard plasterboard fixed vertically each side of the frame.

Inner layer joints on opposite sides of the frame are offset. Vertical joints of the outer layer are offset 600mm from those of the inner layer.

The inner layers must be fitted hard to floor. Use full height sheets where possible.

Sheet joints are touch fitted and must occur over framing. Where sheet end joints are unavoidable they must be over nogs and the outer layer joints offset from those on the inner layer.

FASTENING THE LINING

Fasteners Inner Layer: 25mm x 6g GIB® Grabber® Drywall Self Tapping Screws.

Outer Layer: 41mm x 6g GIB Grabber Self Tapping Drywall Screws.

Fastener centres Inner and outer layer: 300mm centres up each stud.

Place stud fasteners 12mm from sheet edges generally and 50mm from sheet ends.

Fastening the linings at 18mm from sheet ends to top and bottom tracks is permitted as long as the fasteners do not connect the studs and tracks.

SERVICES

Holes may be drilled or pre-punched in the metal studs to allow installation of electrical service lines and plumbing supply pipes.

JOINTING

All screw heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled “GIB® Site Guide”.

Page 31: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

31GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – SUB-INTERTENANCY

2 layers of 13mm GIB® Standard plasterboard

Pink® Batts® BIB R1.8 (75mm)

Steel stud

Screws to 300mm centres up each stud for both inner and outer layers

Page 32: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

32GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – SUB-INTERTENANCY

Two way FRR – steel frame wall

Specification number Performance Specifications

GTS 132 STC

Rw

FRR

48

48

-/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Toughline® each side

Non load bearing

1 x layer Pink® Batts® R1.8 (75mm)

Wet area option

GTWS 132 STC

Rw

FRR

48

48

-/60/60

Lining

LB/NLB

Insulation

1 x 13mm GIB Toughline® Aqua each side

Non load bearing

1 x layer Pink® Batts® R1.8 (75mm)

FRAMING AND WALL HEIGHT

Minimum steel stud dimensions to be 64 x 34 x 0.50mm nominal with a 6mm return.

Minimum steel track dimensions to be 64 x 30 x 0.50mm nominal.

Top and bottom tracks are fixed to the floor and ceiling in true alignment.

Stud spacing at 600mm centres maximum.

Place studs to allow an expansion gap at the top of the frame as per the table below.

The studs are held in place by the “grip” of the channel runners. Light locating fasteners that fail at high temperatures, such as single aluminium rivets may be used. Otherwise positive fixing must be avoided.

Recommended maximum wall height Note that maximum wall heights for fire-rated systems can be lower than what can be achieved with non-fire-rated construction.

Nominal stud dimension (mm)

BMT (mm)

Stud centres (mm)

Max. wall height (mm)

Expansion at top of studs (mm)

64 x 340.50 or 0.55

600 2700 15

400 3000 15

76 x 34

0.55600 3200 15

400 3600 20*

0.75600 3600 20*

400 4200 20*

92 x 34

0.55600 3600 20*

400 4200 20*

0.75600 4200 20*

400 4800 25*

*Use a minimum 50mm deep head channel.

Contact the GIB® Helpline for different framing configurations.

SOUND CONTROL INFILL

Pink® Batts® BIB R1.8 (75mm) minimum glass wool insulation installed between the studs.

ACOUSTIC SEALANT

A bead of GIB Soundseal® acoustic sealant is required around the perimeter of the framing. The linings are then bedded onto the bead.

LINING

1 layer of 13mm GIB® Toughline or 13mm GIB Toughline® Aqua plasterboard each side of the frame.

Vertical fixing only permitted.

Sheets shall be touch fitted.

Offset joints between sheets on opposite sides of the frame.

Full height sheets shall be used where possible.

When sheet end butt joints are unavoidable, they shall be formed over nogs.

All sheet joints must be formed over framing. Linings are fixed hard to floor.

FASTENING THE LINING

Fasteners25mm x 6g GIB® Grabber® Drywall Self Tapping Screws.

Fastener centres300mm centres up each stud.

Place stud fasteners 12mm from sheet edges generally and 50mm from sheet ends.

Fastening the linings at 18mm from sheet ends to top and bottom tracks is permitted as long as the fasteners do not connect the studs and tracks.

For tiled walls (tile weight up to 32kg/m2)Single screw at 100mm centres to perimeter of tiled wall and to all intermediate studs. No Adhesive.

Refer to GIB Aqualine® Wet Area System literature for complete wet area system details.

Page 33: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

33GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – SUB-INTERTENANCY

SERVICES

Holes may be drilled or pre-punched in the metal studs to allow installation of electrical service lines and plumbing supply pipes.

JOINTING

All screw heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled “GIB® Site Guide”.

1 layer of 13mm GIB Toughline® or 13mm GIB Toughline® Aqua plasterboard

Pink® Batts® BIB R1.8 (75mm)

Steel stud

Screws to 300mm centres up each stud

Page 34: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

34GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – SUB-INTERTENANCY

Two way FRR – steel frame wall – GIB Rondo® Quiet Stud®

Specification number Performance Specifications

GBQSA 90c STC

Rw

FRR

47

49

-/90/90

Lining

LB/NLB

Insulation

1 x 16mm GIB Fyreline® each side

Non load bearing

1 x layer Pink® Batts® R1.8 (75mm)

FRAMING

GIB Rondo® Quiet Stud® resilient steel stud 92 x 45 x 0.75mm BMT and placed in 92 x 30 x 0.55mm BMT steel channel. Channel is fixed to floor and ceiling. Studs are friction fitted at 600mm centres maximum with a 15mm expansion gap at the top of the frame. No fixings to the top channel.

WALL HEIGHTS

Recommended maximum wall height is 3000mm. For wall heights up to 3400mm place studs at 400mm centres. For greater heights please contact the GIB® Helpline.

SOUND CONTROL INFILL

Pink® Batts® BIB R1.8 (75mm) minimum glass wool insulation installed between the studs.

ACOUSTIC SEALANT

A bead of GIB Soundseal® acoustic sealant is required around the perimeter of the framing. The linings are then bedded onto the bead.

LINING

1 layer of 16mm GIB® Fyreline each side of the frame.

Vertical fixing only permitted.

Sheets shall be touch-fitted

Offset joints between sheets on opposite sides of the frame.

Full height sheets shall be used where possible.

When sheet end butt joints are unavoidable, they shall be formed over nogs.

All sheet joints must be formed over framing. Linings are fixed hard to floor.

FASTENING THE LINING

Fasteners 32mm x 6g GIB® Grabber® Drywall Self Tapping Screws.

Fastener centres 300mm centres up each stud.

Place stud fasteners 12mm from sheet edges generally and 50mm from sheet ends.

Fastening the linings at 18mm from sheet ends to top and bottom tracks is permitted as long as the fasteners do not connect the studs and tracks.

JOINTING

All screw heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled “GIB® Site Guide”.

Page 35: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

35GIB NOISE CONTROL® SYSTEMS SUPPLEMENTJUNE 2018 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

NOISE CONTROL SYSTEMS – SUB-INTERTENANCY

Pink® Batts® BIB R1.8 (75mm)

Screws to 300mm centres up each stud

1 layer of GIB Fyreline®

GIB Rondo® Quiet Stud®

Page 36: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

36GIB NOISE CONTROL® SYSTEMS SUPPLEMENTMAY 2020 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFORMATION

Additional GIB Barrierline® junction details incorporating a rigid air barrier

Issue Date May 2020

It is becoming more common for terrace home designs to include a rigid air barrier. Careful consideration is required where terrace home intertenancy walls intersect with the external walls that incorporate a rigid air barrier.

Figures 1 to 8 show a number of junction details

where a GIB Barrierline® intertenancy system meets

an external wall or roof. All details incorporate GIB

Weatherline® as the rigid air barrier, solid timber or

mineral wool insulation fire stopping and include

both light and heavy wall cladding types.

For any further information, please contact the

GIB® Helpline on 0800 100 442.

GIB Barrierline®

Timber wall framing

GIB® Wall Clips at each GIB®H-Stud, both sides

Control joint opposite GIBBarrierline®. Detail by claddingsupplier

Fix solid H3.1 treated timber battento GIB® Rondo® 140 PerimeterChannel only. Timber batten forfire stopping, not for claddingfixing. Do not connect timberbatten to timber frames on eachside

GIB® Rondo® 140 PerimeterChannel vertically at outer ends ofwall. Fill any gaps between back ofGIB Weatherline® and GIB®Rondo® 140 Perimeter Channelwith GIB Fire Soundseal®

GIB® Wall Clips or GIB® WallStraps at wall ends both sides

External wall cladding to complywith NZBC E2

GIB® plasterboard

GIB Weatherline®

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

1 : 5

GIB® Intertenancy Barrier SystemsDetail at External Timber Frame Wall

GNS12319 Nov 2019

1601GNS123 Detail at External Timber Frame Wall

Figure 1: Detail at External Timber Frame Wall

GNS123

Page 37: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

37GIB NOISE CONTROL® SYSTEMS SUPPLEMENTMAY 2020 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

ADDITIONAL GIB BARRIERLINE® JUNCTION DETAILS INCORPORATING A RIGID AIR BARRIER

GIB Barrierline®

Timber wall framing

Fix solid H3.1 treated timber battento GIB® Rondo® 140 PerimeterChannel only. Timber batten forfire stopping, not for claddingfixing. Do not connect timberbatten to timber frames on eachside

GIB® Rondo® 140 PerimeterChannel vertically at outer ends ofwall. Fill any gaps between back ofGIB Weatherline® and GIB®Rondo® 140 Perimeter Channelwith GIB Fire Soundseal®

GIB® Wall Clips or GIB® WallStraps at wall ends both sides

External wall cladding to complywith NZBC E2

GIB® plasterboard

GIB Weatherline®

GIB® Wall Clips at each GIB®H-Stud, both sides

Note: Maximum allowable length of intertenancy wall projection will depend on building height and supporting structure. This will need to be determined by Specific Engineering Design (SED).

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

1 : 5

GIB® Intertenancy Barrier SystemsIntertenancy Wall Projection at External Timber FrameWall GNS12413 May 2020

1601GNS124 Intertenancy Wall Projection at External Timber Frame Wall

Figure 2: Intertenancy Wall Projection at External Timber Frame Wall

GNS124

Page 38: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

38GIB NOISE CONTROL® SYSTEMS SUPPLEMENTMAY 2020 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

ADDITIONAL GIB BARRIERLINE® JUNCTION DETAILS INCORPORATING A RIGID AIR BARRIER

GIB Barrierline®Timber wall framing

GIB® Wall Clips at each GIB®H-Stud, both sides

GIB® Rondo® 140 PerimeterChannel vertically at outer ends ofwall. Fill any gaps between back ofGIB Weatherline® and GIB®Rondo® 140 Perimeter Channelwith GIB Fire Soundseal®

GIB® Wall Clips or GIB® WallStraps at wall ends both sides

GIB® plasterboard

GIB Weatherline®

Fit solid H3.2 treated timber battento gap. Fix batten to GIB® Rondo®140 Perimeter Channel only. Donot connect timber batten to timberframes on each side

DPC

Note: Maximum allowable length of intertenancy wall projection will depend on building height and supporting structure. This will need to be determined by Specific Engineering Design (SED).

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

1 : 5

GIB® Intertenancy Barrier SystemsDetail at External Brick Veneer Wall

GNS12513 May 2020

1601GNS125 Detail at External Brick Veneer Wall

Figure 3: Detail at External Brick Veneer Wall

GNS125

Page 39: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

39GIB NOISE CONTROL® SYSTEMS SUPPLEMENTMAY 2020 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

ADDITIONAL GIB BARRIERLINE® JUNCTION DETAILS INCORPORATING A RIGID AIR BARRIER

GIB Barrierline®

Timber wall framingGIB® Wall Clips at each GIB®H-Stud, both sides

Brick veneer

Fit solid H3.2 treated timber battento gap. Fix batten to GIB® Rondo®140 Perimeter Channel only. Donot connect timber batten to timberframes on each side

GIB® Wall Clips or GIB® WallStraps at wall ends both sides

DPC

GIB® plasterboard

GIB Weatherline®

GIB® Rondo® 140 PerimeterChannel vertically at outer ends ofwall. Fill any gaps between back ofGIB Weatherline® and GIB®Rondo® 140 Perimeter Channelwith GIB Fire Soundseal®

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

1 : 5

GIB® Intertenancy Barrier SystemsDetail at External Brick Veneer Wall

GNS12622 AUG 2017

1601GNS126 Detail at Return in External Brick Veneer Wall

Figure 4: Detail at External Brick Veneer Wall

GNS126

Page 40: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

40GIB NOISE CONTROL® SYSTEMS SUPPLEMENTMAY 2020 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

ADDITIONAL GIB BARRIERLINE® JUNCTION DETAILS INCORPORATING A RIGID AIR BARRIER

GIB Barrierline®

Timber wall framingGIB® Wall Clips at each GIB®H-Stud, both sides

GIB® Wall Clips or GIB® WallStraps at wall ends both sides

GIB® plasterboard

GIB Weatherline®

External wall cladding to complywith NZBC E2

Fix solid H3.1 treated timber battento GIB® Rondo® 140 PerimeterChannel only. Timber batten forfire stopping, not for claddingfixing. Do not connect timberbatten to timber frames on eachside

GIB® Rondo® 140 PerimeterChannel vertically at outer ends ofwall. Fill any gaps between back ofGIB Weatherline® and GIB®Rondo® 140 Perimeter Channelwith GIB Fire Soundseal®

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

1 : 5

GIB® Intertenancy Barrier SystemsDetail at Return in External Lightweight Cladding

GNS12729 Nov 2019

1601GNS127 Detail at Return in External Lightweight Cladding

Figure 5: Detail at Return in External Lightweight Cladding

GNS127

GIB Barrierline®

Brick veneer

Fit solid H3.2 treated timber battento gap. Fix batten to GIB® Rondo®140 Perimeter Channel only. Donot connect timber batten to timberframes on each side

Control joint opposite GIBBarrierline®. Detail by claddingsupplier

GIB® Wall Clips at each GIB®H-Stud, both sides

GIB® Rondo® 140 PerimeterChannel vertically at outer ends ofwall. Fill any gaps between back ofGIB Weatherline® and GIB®Rondo® 140 Perimeter Channelwith GIB Fire Soundseal®

GIB® Wall Clips or GIB® WallStraps at wall ends both sides

DPC

GIB® plasterboard

GIB Weatherline®

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

1 : 5

GIB® Intertenancy Barrier SystemsDetail at External Brick Veneer Wall

GNS12819 Nov 2019

1601GNS128 Detail at External Brick Veneer Wall

Figure 6: Detail at External Brick Veneer Wall

GNS128

Page 41: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

41GIB NOISE CONTROL® SYSTEMS SUPPLEMENTMAY 2020 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

ADDITIONAL GIB BARRIERLINE® JUNCTION DETAILS INCORPORATING A RIGID AIR BARRIER

Continous GIB® Rondo® 140Perimeter Channel fixed back toback at 600mm centres

Roof truss

Fill void between battens withmineral wool or ceramic fibre cavityinsulation, 300mm min. width,40kg/m³ min. density

GIB® Rondo® 140 PerimeterChannel

600m

m m

ax. f

rom

GIB

® W

all

clip

to jo

int i

n G

IB B

arrie

rline

®

UNIT 2UNIT 1

GIB® Wall Clips at each GIB®H-Stud both sides of wall

GIB Barrierline®

16mm GIB Fyreline® fixed to GIBBarrierline® with chipboard screwsat 400mm max. centres

Wall cladding to comply with NZBCClauses E2 and C3

GIB Fyreline®

200

min

.

GIB® plasterboard

GIB® plasterboard

Flexible fire retardant underlay

GIB Weatherline®

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

1 : 10

GIB® Intertenancy Barrier SystemsStepped Roof Option A with Rigid Air Barrier

GNS34219 Mar 2020

1601GNS342 Stepped Roof Option A with Rigid Air Barrier

Figure 7: Stepped Roof Option A with Rigid Air Barrier

GNS342

Page 42: Noise Control Systems Supplement · Wall only 24 dBA reduction Wall and Window 20-22 dBA reduction Wall, Window and Skillion Roof 19-21 dBA reduction (This performance level applies

42GIB NOISE CONTROL® SYSTEMS SUPPLEMENTMAY 2020 GIB® HELPLINE 0800 100 442 OR GIB.CO.NZ FOR MORE INFO

ADDITIONAL GIB BARRIERLINE® JUNCTION DETAILS INCORPORATING A RIGID AIR BARRIER

UNIT 2UNIT 1

Roof truss

Fill void between battens withmineral wool or ceramic fibre cavityinsulation, 300mm min. width,40kg/m³ min. density

GIB® Rondo® 140 PerimeterChannel

200m

mm

in.

16mm GIB Fyreline® fixed to GIBBarrierline® with chipboard screwsat 400mm max. centres

Wall cladding to comply withNZBC E2

GIB® Wall Clips at each GIB®H-Stud both sides of wall

GIB Barrierline®

GIB® plasterboard

GIB® plasterboard

Continous GIB® Rondo® 140Perimeter Channel fixed back toback at 600mm centres

GIB Weatherline®

Unit 2 roof battens to extendacross and connect to top plate ofUnit 1 external wall

Note: The maximum allowable difference in the two roof heights will depend on the roof structure and external wall of Unit 1. This will need to be determined by Specific Engineering Design (SED).

© Winstone Wallboards Limited 2016. TERMS OF USE: The USER of these CAD drawings and related information is authorised to reproduce and distribute exact copies or exact extracts of these CAD drawings for the sole purpose of detailing, specifying, using, and promoting the use of Winstone Wallboards Ltd products and systems. It is the USER's responsibility to ensure full building performance specifications and to ensure specification and installation of GIB® products and

systems are in accordance with Winstone Wallboards Ltd GIB® publications. Appropriate expert advice should always be obtained to ensure suitability of these drawings for your specific application. See www.gib.co.nz for full terms of use. The USER is deemed to accept the terms of use.

© Copyright 2016 Winstone Wallboards Ltd All Dimensions are to be site checked before construction and installation

Issue:

Scale:

Date:

Reference

File:

As indicated

GIB® Intertenancy Barrier SystemsStepped Roof Option B with Rigid Air Barrier

GNS34313 May 2020

1601GNS343 Stepped Roof Option B with Rigid Air Barrier

Figure 8: Stepped Roof Option B with Rigid Air Barrier

GNS343