    NEURON II

    User Manual

    Version 1.1 13 July 2009

  • 8/22/2019 NII Manual 1 1

    2/35

    INDEX

    # Chapter Page1.0 Salient Features 1

    2.0 Technical Features 3

    3.0 Input Output Description 44.0 Main Screen 6

    5.0 Menu Structure 8

    5.1 View 8

    5.1.1Operator 9

    5.1.2 Fault Report 10

    5.1.3 Day Report 10

    5.1.4 Service Time 10

    5.1.5 Cumulative Time 11

    5.1.6 VFD 11

    5.2 Operator 11

    5.2.1 Machine 12

    5.2.2 Schedule 13

    5.2.3 Maintenance 135.2.4 Language 13

    5.2.5 Change Password 14

    5.3 Service 14

    5.3.1 Calibration 15

    5.3.2 Relay 15

    5.3.3 Change Password 16

    5.3.4 Maintenance 16

    5.3.5 Clock 16

    5.3.6 Self Test 17

    5.4 Factory menu 17

    5.4.1 Machine 18

    5.4.2 Change Password 19

    5.4.3 Integrator Dryer 195.5 Customer care 19

    6.0 Controls 20

    6.1 Start Sequence 20

    6.2 Stop Sequence 22

    6.3 Fan Control 23

    6.4 ADV control 24

    6.5 Dryer Control 24

    7.0 Data Interface 25

    7.1 Analog output 25

    7.2 DCS Port 25

    8.0 Construction & Dimension Drawing 26

    9.0 Revision Details 27

    10.0 Appendix 28

    APPENDIX A: MODBUS Table 28

    APPENDIX B: Mimic LED Table 32

    APPENDIX C: Short Cut Key Functions 33

  • 8/22/2019 NII Manual 1 1

    3/35

    1.0 Salient features

    Saves Money

    The Smart Logic of NEURON II automatically decides the start delay required to ensure minimum wait time

    between successive starts of the compressor and dryer thereby increasing their l ifetime.

    Start Inhibit till sump pressure is within safe limits to enhance the life of the compressor

    Low Voltage & Short time Power Interrupts detection to enhance the life of the contactors

    Automatic Display Back-light Control to increase the Display Lifetime

    Data validation of critical parameters for protecting the compressor from improper usage.

    Saves Energy

    Automatic Dryer ON/OFF Control to reduce power wastage

    Automatic Fan ON/OFF Control based on temperature to reduce power wastage

    Pressure Scheduling to allow user to plan for air requirements and avoid power wastage

    Dedicated VFD interface port for synchronized operation of integrated compressor with VFD

  • 8/22/2019 NII Manual 1 1

    4/35

    Saves Time

    Easy User Interface thro 8 line Graphical Display and intuitive menu navigation keys

    Multi Language menu & message display: English, Hindi, Selective European Languages

    Mimic LED indication for fault diagnosis

    Easy to read Fault and Warning message display

    Cumulative Hours Display for Load, Unload, Run, Stop, Fault, Standby

    Total No of Start/Stop and Load/Unload Cycle Display

    Compressor Utilisation Display

    Service Remain Hours Display

    Dryer or Ambient Temperature (Pt100 sensor) Display

    Different Control Modes: Local, Remote & DCS

    Unload Mode for Service

    Pressure & Temperature Units Selectable PSI or Bar, Centigrade or Fahrenheit

    30 Day Report includes Date, Load, Unload, Run, Stop, Standby, Fault hours

    99 Fault Report includes Fault Code along with the Date, Time, Pressure, Temperature and Run Status

    MODBUS RTU protocol for monitoring the compressor through DCS interface (BAUD 9600 / 19200)

    Analog Output for Pressure (Channel1), Temperature/Sump Pressure, Pt100 (Programmable on Channel2)

    Programmable Relay for Load, Warn, Trip, Standby, Service, Ready, Remote

    Easy Firmware update using a handheld programming device or a laptop

    Optional Features

    Optional add-on Fault Predictive Device

    o Eliminate the need for the customer to call for service or repair

    o Compressor life could be increased by regular monitoring for problems

    o Production can be maximized due to the minimal downtime

    Optional Add-on IO card further extends Input and Output

    o 4 nos of Isolated Digital Input

    o 4 nos of Relay Output

    o 2 nos of Analog Input, 4-20ma

    o 2 nos of Analog Input, RTD

  • 8/22/2019 NII Manual 1 1

    5/35

    2.0 Technical Features

    8 nos of Optically Isolated Digital Inputs of 24VDC01 = Emergency Stop02 = Differential Pressure Oil Filter - DPOF03 = Reverse Rotation

    04 = Differential Pressure Air Filter - DPAF05 = Remote Start/Stop06 = High Sump Pressure07 = Cooler08 = Main Motor Overload

    8 nos of Output Relay (SPDT 250V AC 10A, 1, 00,000 cycle electric life)01 = Main contactor02 = Star contactor03 = Delta contactor04 = Load Valve05 = Fan06 = Auto Drain Valve07 = Dryer (if Dryer is Connected) else Programmable

    08 = Programmable [Load, Service, Standby, Warn, Trip, Remote, Ready]4 nos of Analog Input Channels

    1 no of 4-20mA Channel, 0 to 16 bar for Discharge Pressure1 no of RTD (KTY10) channel, 0 to 150 degree C for Discharge Temperature1 no of 4-20mA channel, 0 to 16 bar for Sump Pressure1 no of RTD (Pt-100) channel, -50 to +85 degree C for Drier or Ambient Temperature

    2 nos of Analog Output Channels0 to 5 VDC, One for Discharge Pressure and One Programmable

    9 nos of Function keysUp, Down, Left, Right, Enter, Escape, Start, Stop and Reset.

    1 no of Display128X64 White Backlight Graphical LCD

    11 nos of LEDs for visualization alarm & machine status

    AutoAir FilterMain Motor OverloadReverse RotationCoolerPressureTemperatureDifferential Pressure Oil FilterDifferential Pressure Separator ElementStart & Stop

    1 no. of Dual led for start/stop indicationGreen for start and Red for stop

    1 no. of Non Volatile MemoryFor storage of 30 Day & 99 Fault Reports

    1 no. of Real Time ClockWith Battery life of about 10 years

    4 nos of Communication Port (RS485, 2 wire)Serial Port 1: MODBUS-RTU or SCADA PortSerial Port 2: Dedicated FPD Port (For future use)Serial Port 3: Add-On I/O Interface Port (For future use)Serial Port 4: VFD Interface Port (For future use)

    1 no. of In System Programming (ISP) portPower Supply Input: 24VAC +/- 25%, 50Hz, 1A (In built Protection present for Surge, Over Current)

  • 8/22/2019 NII Manual 1 1

    6/35

    3.0 Input Output Description

    X01: Power supplyConnector type: 3 pole combicon

    Pin Function Id Active state1 24V AC Phase 24 VAC P -

    2 Earth Earth -

    3 24V AC Neutral 24 VAC N -

    X02: RelaysConnector type: 10 pole combicon

    Pin Function Id Active state

    1 Common - Load Relay Common

    2 Load Relay L / UL Load when Energised

    3 Common - Fan Relay Common

    4 Fan Relay Fan Energised

    5 Common - Auto Drain Valve Relay Common

    6 Auto Drain Valve Relay ADV Energised

    7 Common Dryer Relay Common

    8 Dryer Relay Dryer / Pr2 Energised

    9 Common - Programmable Relay Common

    10 Programmable Relay Pr1 Energised

    X03: Main Motor RelaysConnector type: 4 pole combicon

    Pin Function Id Active state

    1 Common for Main, Star and Delta

    contactors

    Common -

    2 Main Contactor Main Energised

    3 Star Contactor Star Energised

    4 Delta Contactor Delta Energised

  • 8/22/2019 NII Manual 1 1

    7/35

    X04: Digital inputsConnector type: 11 pole combicon

    X05: Analog InputsConnector type: 8 pole combicon

    Pin Function Id Type Range

    1 Discharge pressure Dis. Pr 4-20 ma

    2 15 to 24VDC 18V

    0 to 16 bar

    3 Discharge temperature Dis. Tr + KTY10

    4 Discharge temperature Dis. Tr -

    0 to 150 C

    5 Sump Pressure Sump Pr 4-20 ma

    6 15 to 24VDC 18V

    0 to 16 bar

    7 Dryer or Amb temperature Pt100 + Pt100

    8 Dryer or Amb temperature Pt100 -

    -50 to +85 C

    X06: Analog outputs and VFDConnector type: 5 pole combicon

    Pin Function Id Type Protocol /Range

    1 VFD Interface VFD A RS485 A

    2 VFD Interface VFD B RS485 B

    FC Protocol

    3 Supply Ground For 5V 0VDC - -

    4 Dis. Pressure Output AO1 Voltage 0 to 16 bar

    5 Programmable Analog

    Output

    AO2 Voltage Programmable

    Pin Function Id Active state

    1 Digital Inputs Common 24VDC 24VDC -

    2 Emergency Stop Emergency Fault if open3 Differential Pressure Oil Filter DPOF Fault if open

    4 Reverse Rotation Rev. Rot Fault if closed

    5 Differential Pressure Air Filter DPAF Fault if open

    6 Remote Start Stop Control Remote Stop if open/ start on

    Closure

    7 High Sump Pressure HSP Fault if open

    8 Cooler Fault Input Cooler Fault if open

    9 Main Motor Overload MMOL Fault if open

    10 24V supply ground GND24 -

    11 No Connection - -

  • 8/22/2019 NII Manual 1 1

    8/35

    X07: CommunicationConnector type: 6 pole combicon

    Pin Function Id Type Protocol

    1 DCS Interface DCS A RS485 A

    2 DCS Interface DCS B RS485 B

    Modbus

    3 FPD Interface FPD A RS485 A

    4 FPD Interface FPD B RS485 B

    ASCII

    5 Add On Interface Add-On A RS485 A

    6 Add On Interface Add-On B RS485 B

    Modbus

    4.0 Main Screen

    Dis. Pr : 6.0 bar

    Dis. Tr : 32 C

    Message1Message2

    Warning

    HH:MM:SS DD/MM

    Message1: Based on the short cut key pressed (refer APPENDIX C)

    Message2: Compressor Status or Fault message- Pressure schedule

    - If Blank Pressure Schedule is Disabled

    - If PS Pressure Schedule is Enabled

    - If PS blinkingWaiting for Pressure Schedule Acknowledgement

    - Control Mode

    - L Local, ON/OFF Control from Local Keypad

    - R Remote, ON/OFF Control from Remote Input

    - D DCS, Control is from DCS System

    - MManual, Start need to given after Power failure

    - A Auto, Compressor will Automatically Restart after power failure

    1 2

    1

    2

  • 8/22/2019 NII Manual 1 1

    9/35

    Message 2 - Compressor Status or Fault message

    Status Description

    Ready Ready for Start

    Star Motor Running in Star

    Run Motor Running in Delta

    Run Load Compressor in LoadRun Unload Compressor in Unload

    Stop Busy Stop Sequence in Progress

    Idle Controller in Idle condition, User interface will not work for this period

    (5 Seconds)

    Emergency Stop Emergency Stop Push Switch is ON

    Start Inhibit xx.x During the Start, if the Sump Pressure is higher than the set start sump

    pressure value, you will see this message. XX.X denotes the live sump

    pressure value. The Compressor Starts only if the Sump Pressure valuegoes below the set value.

    Start Inhibit

    seconds

    If Sump Pressure is Not used (Disabled) then the controller will ensure

    minimum 60 seconds delay between the stop and the start. Count stops ifSTOP key is pressed

    Auto Restart

    seconds

    If Compressor is in Auto Mode,

    The controller will ensure minimum delay (user set, e.g. 90 sec) between

    stop and start. Count stops if STOP key is pressed

    Start ack wait This message is displayed after a fault is cleared and waiting for user

    acknowledgement. By pressing RESET key user can acknowledge.

    Fault Description

    Pr. Probe Failure Discharge Pressure Sensor Probe Failure

    Tp. Probe Failure Temperature Sensor Probe Failure

    Sump Pr. Probe

    Failure

    Sump Pressure Sensor Probe Failure

    HSP (A) Case 1: Sump Pressure is enabled

    If Sump Pressure exceeds the set high sump pressure value.

    Case 2: Sump Pressure is disabled

    If Discharge Pressure exceeds the set high sump pressure value.

    HSP (D) If the HSP Digital Input Opens due to High Sump Pressure

    Cooler If the Cooler Digital Input Opens due to Cooler fault

    Main Motor Overload IF the MMOL Digital Input Opens due to Main Motor Over Load.

    Rev Rot / Ph Fail If the Rev Rot Input Closes when Motor Running due to motorreverse rotation or Phase failure.

    Trip Temperature If the Discharge Temperature exceeds the set trip temperature value.

    Sump Pressure Not

    Developing

    After the Start, The Sump Pressure should be at least 1.0 bar in 10

    seconds. If this is NOT achieved this Fault occurs

    Power failure If the Mains Supply is Interrupted for more than 50 msec

    Low Voltage If the Mains Supply Voltage is less than the 67% of rated Voltage.

    Compressor is tripped & All Controller Operation is Halted until the

    Mains Supply Comes back to normal (at least 75% of the rated)

  • 8/22/2019 NII Manual 1 1

    10/35

    5.0 Menu Structure

    Press any one of the following keys,,and to enter main menu

    Main Menu

    Dis. Pr : 6.0 bar

    Dis. Tr : 32 C

    Status

    View

    Operator

    ServiceFactory

    Customer Care

    5.1 View

    View

    Operator Fault

    Report

    DayReport

    Service

    Time

    Cumulative

    TimeVFD

  • 8/22/2019 NII Manual 1 1

    11/35

    5.1.1 Operator

    LEVEL 1 LEVEL 2 LEVEL 3 LEVEL 4

    View Operator Mode Control mode Local / Remote / DCS

    Unload Mode Enable / Disable

    Auto Restart ON/ OFF

    Pressure Unit PSI / Bar

    Temperature Unit Fahren / Centi

    Pressure Unload pressure X X . X b or p (bar or psi)

    Load pressure X X . X b or p

    Pr. Schedule ON/ OFF

    Start Sump Press X X . X b or p

    Max .Diff Pressure X X . X b or p

    Delay Warn RST delay X X X s (second)

    Star delay X X sDTR delay X X s

    RTS delay X X s

    Stanby TimeSby X X m(minute)

    St/Sp PH X X

    DCS port Type Modbus / SCADA

    ID X X

    Baud 9600/19200

    Parity None / Even

    Length 8 / 7

    Stop Bit 2 / 1

    Temperature Trip Temperature X X X C or F

    Warn Temp X X X C or F

    Fan Temp X X X C or F

    Low Dew Pt X X C or F

    High Dew Pt X X C or F

  • 8/22/2019 NII Manual 1 1

    12/35

    5.1.2 Fault Report

    Use, to select the Fault Record number (1 to 99).

    LEVEL 1 LEVEL 2 LEVEL 3

    View Fault report Fault code: XX, Message

    Time: HH:MM:SS

    Date: DD/MM/YY

    Dis.Pr: X X .X

    Dis.Tr: X X X

    Status: Load/ UnLoad /OFF

    Fault Code:

    01 & 09 Reserved

    02-Main Motor Overload, 03-Cooler, 04-HSP(Analog), 05Trip Temperature, 06-Reverse Rotation, 07-Pressure Probe Failure, 08-Temperature Probe Failure, 0A-

    HSP(Digital), 0B-Power Failure( Short Power Interrupt), 0C-Sump Pressure Not

    Developing , 0D-Sump Pressure probe Failure.

    5.1.3 Day Report

    Use, to select the Record number (1 to 30).

    LEVEL 1 LEVEL 2 LEVEL 3

    View Day report Date: DD/MM/YY

    L: X X Hours St: X X Hours

    UL: X X Hours F: X X Hours

    R: X X Hours Sby: X X Hours

    STC: X X X LDC: X X X X X

    L- Load, St Stop, UL Unload, F- Fault, R- Run, Sby- Standby, STC Start Count,LDC Load Count

    5.1.4 Service Time

    LEVEL 1 LEVEL 2 LEVEL 3

    View Service time Remaining AFCT: X X X X X X hours

    Remaining OFCT: X X X X X X hours

    Remaining OSCT: X X X X X X hours

    Remaining OCT: X X X X X X hours

    Remaining RGT: X X X X X X hours

  • 8/22/2019 NII Manual 1 1

    13/35

    5.1.5 Cumulative Time

    LEVEL 1 LEVEL 2 LEVEL 3

    View Cumulative time Load X X X X X X hrs: X X Min

    Unload X X X X X X hrs: X X Min

    Run X X X X X X hrs: X X MinStop X X X X X X hrs: X X Min

    Fault X X X X X X hrs: X X Min

    Standby X X X X X X hrs: X X Min

    Start Count X X X X X X

    Load Count X X X X X X X X X

    Utilisation X X %

    5.1.6 VFDIf VFD is connected to the compressor and VFD port is connected, user can view the

    following parameters of VFD in Neuron II.

    1. Voltage in V2. Current in A3. Frequency in Hz4. Power in KW5. Run Hours6. Kilowatt Hour (Multiply the value shown by 100 to get the real KWH)7. Status of the VFD

    5.2 OperatorPassword required.

    Operator

    Machine Schedule Maintenance Language Change

    Password

    Mode Pressure Set

    Delay

    DCS

    PortAuto Drain

    Valve

    Set Dew

    Point

  • 8/22/2019 NII Manual 1 1

    14/35

    5.2.1 Machine

    # Item Min Max Option Default Unit

    Mode

    1 Auto Restart - - on / off off -

    2 Pr Unit - - bar / psi bar -3 Tr Unit - - cen / fah cen -

    4 Control

    mode

    - - loc/rem/dcs loc -

    5 Unload

    mode

    - - en/dis dis -

    6 Analog

    output

    - - Tmp / Sp /

    Pt

    Tmp -

    Pressure

    7 Unload

    Pressure

    > load

    pressure+0.5

    (bar)

    < max unload

    pressure (bar)

    - 7.0 bar bar/psi

    8 Load

    Pressure

    4.0 (bar) < unload

    pressure-0.5(bar)

    - 5.5 bar bar/psi

    Set Delay

    9 Warn RST 90 300 - 90 second

    10 Star 6 10 - 6 second

    11 DTR 10 60 - 10 second

    12 RTS 5 30 - 10 second

    13 Standby 1 99 - 5 minute

    14 St/Sp per hr 3 10 - 5 -

    DCS Port

    15 Type - - Modbus

    /SCADA

    modbus -

    16 ID 01 99 - 01 -

    17 Baud - - 9600/19200 9600 bps

    18 Parity - - None /Even None -

    19 Length - - 8 / 7 8 -

    20 Stop Bit - - 2 / 1 2 -

    Auto Drain Valve

    21 Off time 1 150 - 4 minute

    22 On time 1 15 - 5 SecondSet Dew Point

    23 Low Dew

    point

    -6 C +2 C - -2 C C/F

    24 High Dew

    point

    6 C 12 C - 8 C C/F

  • 8/22/2019 NII Manual 1 1

    15/35

    5.2.2 Schedule

    Enable Pressure Schedule, and then use, to select the schedule number (1 to 32).

    Then Press Enter to set the following

    # Item Min Max Option Default Unit

    1 Day - - Sun to Sat /

    --- (means noschedule)

    --- -

    2 Action - - on / off off -

    3 Time HH 00 23 - 00 Hour

    4 Time MM 00 59 - 00 Minute

    5 Unload

    Pressure

    > Load

    Pressure

    + 0.5(bar)

    < Max

    Unload

    Pressure(bar)

    - 6.5 bar bar/psi

    6 Load Pressure 4.0 bar < UnloadPressure

    0.5 (bar)

    - 4.5 bar bar/psi

    5.2.3 Maintenance

    # Item Min Max Option Default Unit

    1 AF changed - - no/yes no -2 OF changed - - no/yes no -

    3 OS changed - - no/yes no -

    4 Oil changed - - no/yes no -

    5 Re Grease - - no/yes no -

    5.2.4 Language

    # Item

    1 English2 Hindi

    3 Portuguese

    Default is English.

  • 8/22/2019 NII Manual 1 1

    16/35

    5.2.5 Change Password

    Procedure for changing the password

    1. Enter the old Password

    2. If old password is correct, next screen is displayed. If wrong the control comes

    out of the change password screen.

    3. Enter the New password

    4. Enter the New password again

    5. If the new password matches both the times then new password is updated. If

    mismatch the control goes back to step 3.

    Pressing Esc will bring the control to the main menu screen

    5.3 ServicePassword required.

    Service

    Calibration Relay ChangePassword

    Maintenance Clock SelfTest

  • 8/22/2019 NII Manual 1 1

    17/35

    5.3.1 Calibration

    Select the parameter need to calibrated using the,keys. Then Press Enter to

    calibrate.

    Dis Pressure/ Dis Temperature/ Sump Pressure Calibration

    Run the Compressor. When the value is stable at some point, measure the actual value

    using a standard & recently calibrated meter and enter the meter reading in to the set

    value field displayed in Neuron II. Set Value should not exceed +/- 1 bar, +/- 10 C.

    Pt 100 Calibration

    When the Dew point/ Ambient Temperature is stable at some point, measure the actual

    value using a standard & recently calibrated meter and enter the meter reading in to the

    set value field displayed in Neuron II. Set Value should not exceed +/- 3 C.

    Analog Output 1 & 2Calibration for analog output should be done for two values one at zero and one at 8.0 bar

    / 80 degree C. These values are set by connecting a Variable Resistor (TRIM POT) in the

    analog input channel. Measure the Analog output value (can be viewed in the DCS/VFD /

    or any master unit where this output is connected). Enter this value in set pr:

    Note: Calibration need to be done only when the compressor is in off condition and the

    digital outputs (relay terminals) are disconnected from the controller.

    Note: Calibration for Pressure will be only in bar and for temperature only in Centigrade.

    5.3.2 Relay

    Select the Programmable Relay 1 or 2 using the,keys. Then Press Enter to assign

    the any one of the following functionality for the relay.

    # Item

    1 Warn

    2 Load

    3 Service

    4 Standby

    5 Trip

    6 Remote

    7 Ready

    Default:Relay 1 = Warn

    Relay 2 = Trip

    Note: If Dryer is enabled then Programmable

    Relay 2 is not user programmable.

    It is used for automatic dryer control.

  • 8/22/2019 NII Manual 1 1

    18/35

    5.3.3 Change Password

    Procedure for changing the password

    1. Enter the old Password

    2. If old password is correct, next screen is displayed. If wrong the control comes

    out of the change password screen.

    3. Enter the New password

    4. Enter the New password again

    5. If the new password matches both the times then new password is updated. If

    mismatch the control goes back to step 3.

    Pressing Esc will bring the control to the main menu screen

    5.3.4 Maintenance

    # Item Min Max Option Default Unit

    1 Set AFCT 000000 999999 - 002000H Hour

    2 Set OFCT 000000 999999 - 002000H Hour

    3 Set OSCT 000000 999999 - 004000H Hour

    4 Set OCT 000000 999999 - 002000H Hour

    5 Set RGT 000000 999999 - 002000H Hour

    5.3.5 Clock

    # Item Min Max

    1 Hour 00 23

    2 Minute 00 59

    3 Second 00 59

    4 Date 01 31

    5 Month 01 12

    6 Year 00 99

    7 Day Sun/Mon/Tue/Wed/Thu/Fri/Sat

  • 8/22/2019 NII Manual 1 1

    19/35

    5.3.6 Self Test

    Self Test for testing the Controller Display, Mimic Leds, Keys, Input/Output, Memory &

    Communication Ports working.

    Follow the instructions displayed in the screen

    Warning!!!

    Self Test should be conducted only when the compressor wiring is totally disconnected

    from the controller. Do NOT perform self test when the controller is connected to the

    compressor. Doing so will cause severe damage to the compressor.

    5.4 Factory menuPassword required.

    Factory

    Machine ChangePassword

    Dryer

    Compressor

    Info

    DPSE DPOF Max.

    PressureSettings

    Temperature

    Settings

  • 8/22/2019 NII Manual 1 1

    20/35

    5.4.1 Machine

    # Item Min Max Option Default Unit

    Compressor Info

    1 Rating - - 11 to 315 22 KW

    2 Pressure - - LP/ 7.0 to 12.5 LP bar3 Fab no A-Z 00000 A-Z

    999999

    - A00000 -

    4 DPSE - - on/off off -

    5 DPOF - - on/off off -

    Max. Pressure Settings

    6 Max UL

    Pressure

    > Unload

    Pressure

    < 13.5 bar - 7.5 bar bar

    /psi

    7 High Sump

    Pressure

    > Max

    Unloadpressure +1

    < Max

    Unloadpressure

    +3

    - 10.5 bar bar

    /psi

    8 Sump

    Pressure

    - - enable/disable disable -

    9 Start Sump

    Pressure

    0.0 bar 16.0 bar - 2.2 bar bar

    /psi

    10 Max.

    Differential

    Pressure

    0.0 bar 2.0 bar - 1.5 bar bar

    /psi

    Temperature Settings

    11 Trip

    temperature

    110 C 120 C - 110 C C / F

    12 Warn

    temperature

    90 C 110 C - 105 C C / F

    13 Fan

    temperature

    60 80 C - 70 C C / F

  • 8/22/2019 NII Manual 1 1

    21/35

    5.4.2 Change Password

    Procedure for changing the password

    1. Enter the old Password

    2. If old password is correct, next screen is displayed. If wrong the control comes

    out of the change password screen.

    3. Enter the New password

    4. Enter the New password again

    5. If the new password matches both the times then new password is updated. If

    mismatch the control goes back to step 3.

    Pressing Esc will bring the control to the main menu screen

    5.4.3 Dryer

    # Item Min Max Option Default Unit

    1 Dryer Mode - - on/off off -

    2 Dryer Delay 2 10 - 3 Minute

    5.5 Customer care

    Dis. Pr : 6.0 barDis. Tr : 32 C

    Status

    Toll Free No

    1800-425-3544

    e-mail

    [email protected]

  • 8/22/2019 NII Manual 1 1

    22/35

    6.0 Controls

    6.1 Start SequenceExit loop

    FAULT?

    ON

    Command

    No

    Yes

    AUTO

    mode

    ON?

    Dis. Pr.

  • 8/22/2019 NII Manual 1 1

    23/35

    STAR

    ON

    MAIN ON

    NO. OF. START

    INCREMENT

    DELTA ON

    STAR OFF

    Exit loop

    Delay for 100msecs

    (Fixed)

    STAR TO DELTA delay x sec

    (Star delay)

    Delta to run delay x sec

    (DTR delay)

    Start Sequence

  • 8/22/2019 NII Manual 1 1

    24/35

    6.2 Stop Sequence

    Is

    STAR ON

    LOAD OFF

    DELTA & MAIN

    OFF

    (RTS delay)

    Run to stop x sec

    IDLE delay for 5 secsFixed delay

    READY

    Yes

    No

    Stop

  • 8/22/2019 NII Manual 1 1

    25/35

    6.3 Fan Control

    Dis. Temp

    > Set FANTemp

    FAN ON

    No

    Yes

    FAN

    = ON?

    Dis. Temp< (Set FAN

    Temp 5 C)

    FAN OFF

    Exit Loop

    No

    Yes

    No

    Yes

    Exit Loop

    State = Run?

    No

  • 8/22/2019 NII Manual 1 1

    26/35

    6.4 ADV control

    As per the User set On & Off time the Drain Valve is automatically controlled.

    6.5 Dryer Control

    Calculate elapsed time from

    last stop

    IsElapsed time>set

    dryer delay ?

    Dryer ON

    No

    Yes

    Dryer ON command generates

    internally when Compressormotor starts runnin

    Dryer OFF when Compressor is stopped

    On time

    Off time

  • 8/22/2019 NII Manual 1 1

    27/35

    7.0 Data Interface

    Neuron II has two types of Data Interface

    Analog output

    DCS Port

    7.1 Analog output

    Two Channels are available as analog output. The First Channel will output the current

    Discharge Pressure value 0.0 to16.0 bar, converted into 1 to 4.75V.

    The Second channel is programmable. User can select any one of the following in menu

    Operator/ Machine/ Mode/ Analog output

    a. Dis. Temperature 0 to 150 C, converted into 1 to 4.75V

    b. Sump Pressure 0 to 16.0 bar, converted into 1 to 4.75V

    c. Pt100 Temperature -50 to 90 C, converted into 1.25 to 4.75V

    Note: Analog output will be 0V in case of probe failure.

    7.2 DCS Port

    DCS port can be of Modbus RTU type to interface to Generic DCS system or SCADA

    type to interface to ELGI SCADA software.

    User can select the Port type in menu Operator/ Machine/ DCS Port. Also the ID,

    Baud Rate, Parity, data Length, Stop Bit are user settable. The Modbus data table is

    provided in the Appendix.

  • 8/22/2019 NII Manual 1 1

    28/35

    8.0 Construction

    Corrosion & Dust protected Back Cover

    IP65 polyethylene front keypad

    Inputs and Outputs through terminal block, board to wires, disconnect able, screw terminals

    Front Plate Dimensions 260 x 145mm

    Enclosure Dimensions 235 X 120 X 70 mm

    Operating Temperature - 0C to +75C

    Relative Humidity

  • 8/22/2019 NII Manual 1 1

    29/35

    9.0 Revision Details

    Version Date Changes

    1.0 2 April 2009 Initial Draft1.1 8 July 2009 Pilot Batch S/W

    Version 1.1

  • 8/22/2019 NII Manual 1 1

    30/35

    10.0 Appendix

    APPENDIX A: MODBUS TABLE [Function Code: 0x03(Read) & 0x10(Write)]

    # DataDescription

    Address Type Bytes Example / Format Access

    Cumulative Time & Count Registers

    1 Load Hours 1010 BCD 4 HHHHHH:MM R

    2 UnloadHours

    1012 BCD 4 HHHHHH:MM R

    3 Run Hours 1014 BCD 4 HHHHHH:MM R

    4 Stop Hours 1016 BCD 4 HHHHHH:MM R

    5 Fault Hours 1018 BCD 4 HHHHHH:MM R

    6 Standby

    Hours

    101A BCD 4 HHHHHH:MM R

    7 No of Start 101C BCD 4 NNNNNNNN R8 Load Count 101E BCD 6 NNNNNNNNNNNN R

    9 Utilization % 1022 BCD 2 XXXX R

    Service Remaining Time Registers

    10 Rem AFCT

    Hours

    1028 Int 2 H8063 = -99

    (X10000)

    Minutes 1029 ULong 4 H000927BF =

    599999

    R

    11 Rem OFCT

    Hours

    102B Int 2 H8063 = -99

    (X10000)

    Minutes 102C ULong 4 H000927BF =599999

    R

    12 Rem OSCTHours

    102E Int 2 H8063 = -99(X10000)

    Minutes 102F ULong 4 H000927BF =599999

    R

    13 Rem OCTHours

    1031 Int 2 H8063 = -99(X10000)

    Minutes 1032 ULong 4 H000927BF =599999

    R

    14 Rem RGT

    Hours

    1034 Int 2 H8063 = -99

    (X10000)

    Minutes 1035 ULong 4 H000927BF =

    599999

    R

  • 8/22/2019 NII Manual 1 1

    31/35

    Mode Registers

    15 Control

    Mode

    1040 BCD 2 0001-DCS

    0002-Local

    0003-Remote

    R/W

    16 Unload Mode 1041 BCD 2 0001-Disabled0002-Enabled

    R/W

    17 Auto Restart

    1042 BCD 2 0001-OFF

    0002-ON

    R/W

    18 Pr Unit 1043 BCD 2 0001-BAR0002-PSI

    R/W

    19 Tr unit 1044 BCD 2 0001-Centi0002-Farhen

    R/W

    20 Pr.Schdl(on/off)

    1045 BCD 2 0001-OFF0002-ON

    R

    Analog Registers

    27 Dis. Pressure

    104A BCD 2 1200 (/100) =12.0 bar

    R

    28 Dis.Temperature

    104B BCD 2 1100 (/10) =110 C

    R

    29 Dew Point /Ambient

    Temperature

    104C BCD 2 MSB 01 = +MSB 02 = -

    LSB = 30

    R

    30 Sump

    Pressure

    104D BCD 2 1200 (/100) =

    12.0 bar

    R

    31 Diff Pressure 104E BCD 2 0100 (/100)

    =1.0 bar

    R

    32 Set UnloadPressure

    104F BCD 2 0120 (/10) =12.0 bar

    R/W

    33 Set Load

    Pressure

    1050 BCD 2 0080 (/10) =

    8.0 bar

    R/W

    34 Set DiffPressure

    1051 BCD 2 0010 (/10) =1.0 bar

    R/W

    35 Trip Temp 1052 BCD 2 0110 = 110 C R

    36 Warn Temp 1053 BCD 2 0105 = 105 C R/W

    37 Low Dew

    Point

    1054 BCD 2 MSB 01 = +

    MSB 02 = -LSB = 30

    R/W

    38 High DewPoint

    1055 BCD 2 MSB 01 = +MSB 02 = -

    LSB = 30

    R/W

    39 Fan Temp 1056 BCD 2 0070 = 70 C R/W

  • 8/22/2019 NII Manual 1 1

    32/35

    Delay Registers

    21 Auto Restart

    Delay (Sec)

    1060 BCD 2 0100 R/W

    22 Star Delay

    (Sec)

    1061 BCD 2 0005 R/W

    23 DTR Delay

    (Sec)

    1062 BCD 2 0010 R/W

    24 RTS Delay

    (Sec)

    1063 BCD 2 0010 R/W

    25 Standby

    Time (Min)

    1064 BCD 2 0005 R/W

    26 Max. No of

    Start per hour

    1065 BCD 2 0005 R/W

    RTC Registers

    40 Hour 106A BCD 2 0023 R

    41 Minutes 106B BCD 2 0059 R42 Seconds 106C BCD 2 0059 R

    43 Date 106D BCD 2 0031 R

    44 Month 106E BCD 2 0012 R

    45 Year 106F BCD 2 0009 R

    46 Day 1070 BCD 2 0001

    Sunday -1

    R

    Status Registers

    47 General

    Status

    1071 UInt 2 Refer table R

    48 Warning

    Status

    1072 UInt 2 Refer table R

    49 Fault Status 1073 UInt 2 Refer table R

    Start / StopFunction Code: 05Address : 1074

    Value : 0xFF00 Start

    0x0000 Stop

  • 8/22/2019 NII Manual 1 1

    33/35

    Status Register Bit Definition:

    Bit Position General Warning Fault

    0 Ready DPSE HSP

    1 Star DPOF Cooler

    2 Run Dryer Probe Failure Main Motor Overload3 Run Load Low Dew Point Reverse Rotation

    4 Run Unload High Dew Point Pressure Probe Failure

    5 Stop Busy High Differentialpressure

    Temperature ProbeFailure

    6 Idle Warn Temperature Trip Temperature

    7 Emergency Stop Change Air Filter Sump Pressure Not

    Developing

    8 Start Inhibit Change Oil Filter Sump Pressure probeFailure

    9 Start ack wait Change Oil Separator Power failure

    10 Standby Change Oil Reserved11 Reserved Change Grease Reserved

    12 Reserved Reserved Reserved

    13 Reserved Reserved Reserved

    14 Reserved Reserved Reserved

    15 Reserved Reserved Reserved

  • 8/22/2019 NII Manual 1 1

    34/35

    APPENDIX B: MIMIC LED TABLE

    # LED Description

    1 Auto To indicate the machine is in automatic on/off mode. This Led

    glows in Amber Colour on these conditions

    1. When Pressure Schedule is enabled (or)2. When Auto Restart is enabled2 Air Filter Glows in Amber colour when

    1. Air Filter Service is due based on service hours2. Air Filter Digital Input (DPAF) is Open

    3 Main Motor

    Overload

    Glows in Red when the main motor overload Digital Input is

    Open.

    4 Reverse Rotation Glows in Red when the Reverse Rotation Digital Input isClosed and the machine is in Run state

    5 Cooler Glows in Red when the cooler Digital Input is Open

    6 Pressure Glows in Red when the

    1. HSP Digital Input is Open2. Analog Pressure Input is Open (Probe Failure)3. Dis. Pressure is higher than set HSP

    7 Temperature Glows in Red when the

    1. Analog Temperature Input is Open (Probe Failure)2. Dis. Temperature is higher than set Trip temp.

    8 Differential

    Pressure Oil Filter(DPOF)

    Glows in Amber when the

    1. DPOF Digital Input is Open & DPOF is enabled2. Oil Filter Service is due

    9 Differential

    Pressure Separator

    Element (DPSE)

    Glows in Amber when the

    1. DPSE Digital Input is Open & DPSE is enabled

    2. Oil Separator Filter Service is due10 Start & Stop 1. Glows in Red when machine is stopped / idle

    2. Glows in Green when machine is running

  • 8/22/2019 NII Manual 1 1

    35/35

    APPENDIX C: Short Cut Key Functions

    Note1: All shortcut key functions only when the display is in Main Screen.

    Note2: On every press of the key NEXT message is displayed.

    LEFT Warning messages

    Warning Description

    DPSE Differential Pressure Separator Element Due For

    Service

    DPOF Differential Pressure Oil Filter Due For Service

    Dryer Probe Failure Pt100 Sensor Probe Failure

    Low Dew Point Live Dew Point less than the Set Low Dew Point

    High Dew Point Live Dew Point greater than the Set High Dew Point

    High Differential pressure Difference Between the Sump & Discharge Pressure is

    greater than the set max Differential Pressure value.

    Warn Temperature Discharge Temperature exceeds the set Warn valueChange Air Filter Air Filter Due For Service

    Change Oil Filter Oil Filter Due For Service

    Change Oil Separator Oil Separator Due For Service

    Change Oil Oil Change Due For Service

    Change Grease Re Grease Due For Service

    Start Stop Exceeded No. of Start stop per hour exceeded

    RIGHT - Live Analog Values

    1. Live Differential Pressure2. Live Sump Pressure

    3. Live Pt100 Temperature

    UP Set Analog Values

    1. Set Load Pressure

    2. Set Unload Pressure

    3. Set Start Sump Pressure4. Max Differential Pressure

    DOWN Today Report

    1. Date

    2. Load and Stop Hours

    3. Unload and Fault Hours4. Run and Standby Hours

    5. Start Count and Load Count