NHS Borders, Borders Hospital
Lighting Proposal
Our Sales Engineer Ray Clarkson and Lighting Engineer Graham Lucas visited Borders
Hospital on Monday 31 January 2011 and conducted a brief survey of lighting located in
the following areas of the Hospital:-
Hospital Corridors
Fire Escape Stairs
Recovery Area
Snake
Hospital Management Offices and corridor
Physiotherapy suite and Gymnasium
Main Entrance Corridor
Ward and Ward Shower
Entrance Canopy
We have prepared various lighting plots for these areas and have proposed replacement luminaires that are more energy efficient than those existing. A summary of the types of
luminaires proposed and their catalogue numbers and a brief description are shown on the
next page. On the pages following the summary we have explained our designs in more
detail and have included plots and information on the suggested equipment.
Our summary shows a column for quantities. We have shown a quantity when we have
produced a specific design for an area. When no quantity is detailed it is because we have
produced a sample plot for an area and because we don’t have specific details of the quantity of luminaires in the area concerned. You will need to decide how many luminaires
you wish to use based on the information given in the following pages.
For those luminaires that are operated from the non-essential and essential supplies we
have assumed that the backup generators provide 240v 50Hz and that the change over
relay is at the generator.
Borders Hospital Lighting Proposal
Location Qty Luminaire Cat. No. Luminaire DescriptionHospital Corridor (41m
long) 10 XL11057J
Thorlux XL-Five 3x14w recessed 600x600mm module with HF gear and faceted crossblade
louvre. Spacing 3m.
3 SLA13698
Thorlux LED Non maintained emergency recessed luminaire with corridor optic and control
unit. 3 hour duration
Fire escape Stairs KB10859J Thorlux Kanby T5 controller luminaire 1500mm 2x35w with HF gear
EFB9303 Thorlux 1x8w T5 Eight-65 non maintained emergency bulkhead 3 hour duration
Recovery Area SD12893J
Thorlux Skydome 4x24w recessed 600x600mm module with HF gear and domed diffuser
fitted with 6500K lamps
NL14350 Thorlux recessed LED Night Light
Snake KB10834J Thorlux Kanby T5 reflector luminaire 1500mm 1x35w with HF gear
MS10834 Ex-Or presence detector. Detection pattern 6m at 2.5m mounting height.Hospital management
office 10 HI12305J
Thorlux Hi-Style Pro 1x40w TC-L recessed 600mmx600mm module with HF gear central
louvre and perforated steel side baffles.Hospital management
corridor 6 96107638 Thorn Cruz 160 1x34w LED recessed down light.
Physiotherapy AL14085D
Thorlux A-Line Smart 1500mm 2 x 49w T5 IP65 luminaire fitted with internal reflector and
sensor for PIR detection and daylight linking
Gym 6 SW13295D
Thorlux Solow T5 Smart 1500mm 4x80w T5 luminaire with wire guard ans sensor for PIR
detection and daylight linking. Narrow light distribution.
Main Entrance Corridor 7 HI12563J
Thorlux Hi-Style Com 2x55w TC-L recessed 600mmx600mm module with HF gear and
central perforated basket.
6 Bed Ward 2 JUB13066J Thorlux Jubilee 1500mm 2x35w T5 surface mounted shallow profile controller luminaire
3 NL14350 Thorlux recessed LED Night Light
1
Borders Hospital Lighting Proposal
Location Qty Luminaire Cat. No. Luminaire Description
Alternative recessed option for 6 Bed Ward
6 Bed Ward 2 SD12893J
Thorlux Skydome 4x24w recessed 600x600mm module with HF gear and domed diffuser
fitted with 6500K lamps
3 NL14350 Thorlux recessed LED Night Light
Ward shower area DQ25X1MV2PW
Designplan Quadrant LED 25 LED IP65 square luminaire with white body and prismatic
controller
MSB1000T
Ex-Or Battenfix Sensor for fitting into 20mm knock out on side of above luminaire sensor is
IP4X, (IP65 version available in September 2011).Entrance Canopy
Lighting 7 5480.102.T13 Ghidini Maximaestro 56 LED IP65 floodlight
7 SA1.13 Wall mounting bracket for the above
8 D277/1X32LEDV2C31
Designplan Pantheon LED 32 LED IP65 wall mounted IP65 luminaire with white body and
opal diffuser
2
Hospital Corridor
We chose a corridor that is 41m long and our plot determined that this corridor could be
illuminated using a 3x14w T5 recessed module with a faceted cross blade louvre and that
these luminaires can be mounted 3m apart and provide 150 lux at floor level.
This spacing of 3m can be used to determine the quantity of luminaires needed for any of
the hospital corridors
These luminaires can be operated from both essential and non-essential supplies. We
have also examined the use of recessed LED emergency lighting (surface versions are
also available) in the corridor and using LED luminaires with corridor specific optics we
can use 3 luminaires in this length of corridor and in some instances the spacing could be
up to 20m. We would however recommend that at least two emergency luminaires are
used in any short corridor to ensure an extra margin of safety.
These LED luminaires can be used in any of the corridor areas of the hospital as long as
the maximum spacing of 20m is not exceeded.
Borders Hospital
Corridor Lighting
Partner for Contact: Ian GentlemanOrder No.: Company: Borders NHSCustomer No.:
Date: 07.02.2011Operator: Graham Lucas
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Table of contents
Borders HospitalProject Cover 1Table of contents 2THORLUX XL11057 XL-Five Faceted - 3x14W
Luminaire Data Sheet 3Room 1
Summary 4Luminaires (layout plan) 5Room Surfaces
FloorIsolines (E) 6Greyscale (E) 7Value Chart (E) 8
Page 2
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
THORLUX XL11057 XL-Five Faceted - 3x14W / Luminaire Data Sheet
Luminous emittance 1:
160
240
320
cd/klm 79%C0 - C180 C90 - C270
0° 15° 30°
45°
60°
75°
90°
105°105°
90°
75°
60°
45°
30° 15° 0°
Luminaire classification according to CIE: 100CIE flux code: 54 91 99 100 79
Recessed luminaire with low brightness louvre
Luminous emittance 1:
Glare Evaluation According to UGR
Ceiling 70 70 50 50 30 70 70 50 50 30
Walls 50 30 50 30 30 50 30 50 30 30
Floor 20 20 20 20 20 20 20 20 20 20
Room SizeX Y
Viewing direction at right anglesto lamp axis
Viewing direction parallelto lamp axis
2H 2H 16.2 17.4 16.4 17.6 17.8 14.1 15.3 14.4 15.5 15.73H 16.3 17.3 16.6 17.6 17.8 14.6 15.7 14.9 15.9 16.24H 16.2 17.2 16.6 17.5 17.8 14.7 15.7 15.1 16.0 16.36H 16.2 17.1 16.5 17.4 17.7 14.8 15.7 15.1 16.0 16.38H 16.1 17.0 16.5 17.3 17.6 14.8 15.7 15.2 16.0 16.3
12H 16.1 16.9 16.5 17.3 17.6 14.8 15.6 15.2 15.9 16.3
4H 2H 16.3 17.3 16.6 17.6 17.8 14.5 15.5 14.8 15.7 16.03H 16.4 17.3 16.8 17.6 17.9 15.1 15.9 15.4 16.2 16.64H 16.4 17.2 16.8 17.5 17.9 15.3 16.0 15.6 16.3 16.76H 16.4 17.0 16.8 17.4 17.8 15.4 16.0 15.8 16.4 16.88H 16.4 17.0 16.8 17.3 17.8 15.4 16.0 15.8 16.4 16.8
12H 16.4 16.9 16.8 17.3 17.7 15.4 15.9 15.9 16.3 16.8
8H 4H 16.4 17.0 16.8 17.4 17.8 15.2 15.8 15.7 16.2 16.66H 16.4 16.9 16.8 17.3 17.7 15.4 15.9 15.8 16.3 16.78H 16.4 16.8 16.8 17.2 17.7 15.4 15.9 15.9 16.3 16.8
12H 16.3 16.7 16.8 17.2 17.7 15.5 15.8 16.0 16.3 16.8
12H 4H 16.4 16.9 16.8 17.3 17.7 15.2 15.7 15.7 16.1 16.66H 16.4 16.8 16.8 17.2 17.7 15.4 15.8 15.8 16.2 16.78H 16.3 16.7 16.8 17.2 17.7 15.4 15.8 15.9 16.3 16.8
Variation of the observer position for the luminaire distances S
S = 1.0H +0.2 / -0.3 +0.4 / -0.5S = 1.5H +1.1 / -2.1 +1.3 / -1.7S = 2.0H +2.6 / -5.4 +1.8 / -3.1
Standard table BK01 BK02
Correction Summand -6.2 -7.1
Corrected Glare Indices referring to 3600lm Total Luminous Flux
Page 3
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Summary
3.00 m
41.00 m
0.00
Height of Room: 2.800 m, Mounting Height: 2.865 m, Maintenance factor: 0.80
Values in Lux, Scale 1:527
Surface [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 211 165 269 0.782Floor 10 167 110 197 0.658Ceiling 70 34 28 290 0.822Walls (4) 50 98 31 187 /
Workplane:Height: 0.750 mGrid: 107 x 7 Points Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.448, Ceiling / Working Plane: 0.159.
Luminaire Parts List
Specific connected load: 5.92 W/m² = 2.80 W/m²/100 lx (Ground area: 123.00 m²)
No. Pieces Designation (Correction Factor) [lm] P [W]
1 14 THORLUX XL11057 XL-Five Faceted - 3x14W (1.000) 3600 52.0Total: 50400 728.0
Page 4
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Luminaires (layout plan)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3.00 m0.00
41.00 m
0.00
1.50
4.50
7.50
10.50
13.50
16.50
19.50
22.50
25.50
28.50
31.50
34.50
37.50
39.90
Scale 1 : 278
Luminaire Parts List
No. Pieces Designation
1 14 THORLUX XL11057 XL-Five Faceted - 3x14W
Page 5
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Isolines (E)
140
160
160
180
180
180
180
180
180
180
3.00 m0.00
41.00 m
0.00
Values in Lux, Scale 1 : 321Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 128 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax167 110 197 0.658 0.557
Page 6
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Greyscale (E)
120
140
160
180
lx
3.00 m0.00
41.00 m
0.00
Scale 1 : 321Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 128 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax167 110 197 0.658 0.557
Page 7
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Value Chart (E)
131152168159174159176159174160170162170164167167164170161173159175164191181
3.00 m0.00
41.00 m
0.00
Values in Lux, Scale 1 : 321Not all calculated values could be displayed.
Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 128 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax167 110 197 0.658 0.557
Page 8
Borders Hospital
Corridor (41mx3m) Emergency Lighting with recessed LED
Partner for Contact: Ian GentlemanOrder No.: Company: Borders NHSCustomer No.:
Date: 07.02.2011Operator: Graham Lucas
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor LED Emergency.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Table of contents
Borders HospitalProject Cover 1Table of contents 2THORLUX SLA13698 Recessed LED Downlighter Corridor Lens - 3W
Luminaire Data Sheet 3Room 1
Luminaires (layout plan) 4Light scenes
Light scene 1Room Surfaces
Escape Route 3Isolines (E) 5Greyscale (E) 6
Page 2
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor LED Emergency.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
THORLUX SLA13698 Recessed LED Downlighter Corridor Lens - 3W / Luminaire Data Sheet
Luminous emittance 1:
800
1200
1600
cd/klm 84%C0 - C180 C90 - C270
0° 15° 30° 45°
60°
75°
90°
105°
120°
135°150°165°180°165°150°135°
120°
105°
90°
75°
60°
45° 30° 15° 0°
Luminaire classification according to CIE: 94CIE flux code: 24 43 80 95 87
3W high performance LED emergency downlighter
Luminous emittance 1:
Glare Evaluation According to UGR
Ceiling 70 70 50 50 30 70 70 50 50 30
Walls 50 30 50 30 30 50 30 50 30 30
Floor 20 20 20 20 20 20 20 20 20 20
Room SizeX Y
Viewing direction at right anglesto lamp axis
Viewing direction parallelto lamp axis
2H 2H 21.8 23.5 22.2 23.8 24.2 13.6 15.2 14.0 15.6 15.93H 35.5 37.0 35.9 37.4 37.8 14.7 16.2 15.1 16.6 17.04H 39.4 40.8 39.8 41.3 41.7 15.2 16.7 15.7 17.1 17.56H 41.0 42.4 41.5 42.8 43.3 15.7 17.1 16.1 17.5 17.98H 41.4 42.7 41.8 43.1 43.6 15.9 17.2 16.3 17.7 18.1
12H 41.6 42.9 42.1 43.4 43.8 16.1 17.4 16.6 17.8 18.3
4H 2H 21.8 23.3 22.3 23.7 24.1 15.8 17.3 16.2 17.7 18.13H 35.2 36.5 35.7 36.9 37.4 16.9 18.2 17.3 18.6 19.14H 39.1 40.3 39.6 40.8 41.3 17.4 18.6 17.9 19.0 19.56H 40.8 41.9 41.3 42.4 42.9 17.9 18.9 18.4 19.4 20.08H 41.2 42.2 41.8 42.7 43.3 18.1 19.1 18.6 19.6 20.2
12H 41.6 42.5 42.2 43.1 43.6 18.4 19.3 18.9 19.8 20.3
8H 4H 39.0 40.0 39.5 40.5 41.0 20.4 21.3 20.9 21.8 22.46H 40.7 41.6 41.3 42.1 42.7 20.9 21.7 21.4 22.2 22.88H 41.2 41.9 41.8 42.5 43.1 21.2 21.9 21.7 22.4 23.0
12H 41.7 42.3 42.3 42.9 43.5 21.4 22.0 22.0 22.6 23.2
12H 4H 39.0 39.9 39.5 40.4 40.9 22.2 23.1 22.7 23.6 24.26H 40.7 41.5 41.3 42.0 42.6 23.4 24.1 23.9 24.6 25.28H 41.2 41.9 41.8 42.4 43.0 23.7 24.3 24.3 24.9 25.5
Variation of the observer position for the luminaire distances S
S = 1.0H +0.5 / -0.5 +0.2 / -0.2S = 1.5H +1.4 / -1.8 +0.2 / -0.3S = 2.0H +2.4 / -3.6 +0.5 / -1.0
Standard table --- ---
Correction Summand --- ---
Corrected Glare Indices referring to 209lm Total Luminous Flux
Page 3
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor LED Emergency.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Luminaires (layout plan)
1
1
1
3.00 m0.00
41.00 m
0.00
6.83
20.50
34.17
Scale 1 : 278
Luminaire Parts List
No. Pieces Designation
1 3 THORLUX SLA13698 Recessed LED Downlighter Corridor Lens - 3W
Page 4
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor LED Emergency.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Light scene 1 / Escape Route 3 / Isolines (E)
2.00 m
40.00 m
0.00
Values in Lux, Scale 1 : 314Position of surface in room:Marked point:(2.500 m, 40.500 m, 0.000 m)
Grid: 1 x 17 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax2.39 0.70 4.89 0.292 0.143
Centre line: Emin: 1.50 lx, Emin / Emax: 0.35 (1 : 2.86).
Page 5
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Corridor LED Emergency.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Light scene 1 / Escape Route 3 / Greyscale (E)
2.00 m
40.00 m
0.00
Scale 1 : 314Position of surface in room:Marked point:(2.500 m, 40.500 m, 0.000 m)
Grid: 1 x 17 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax2.39 0.70 4.89 0.292 0.143
Centre line: Emin: 1.50 lx, Emin / Emax: 0.35 (1 : 2.86).
Page 6
Downlighter completewith Control Unit -Area version
� Small size - unobtrusive
� Three hour, non-maintained emergencyoperation
� Stand-alone self-test and Scanlight ATcompatible
� May be positioned for maximum effect
� Reliable LED technology
� Status indicator shows operationalcondition
� Low power consumption (4W total)
� Superb photometric performance
� Die-cast heat sink for long LED life
200 CRS.
45
42
207
2 x fixing slots4mm clearance
LED DALI Emergency ControlUnit supplied with ScanlightLED Downlighters
APPROX.
CAT. No. DISTRIBUTION TYPE kg
SLA 13697 Area Non-maintained 0.9
SLA 13698 Corridor Non-maintained 0.9
Wiring accessories - see page 234
Range
DOWNLIGHTER, (BELOW CEILING)
CONTROL UNIT
DOWNLIGHTER, (ABOVE CEILING)
Corridor version
LED Downlighter - Area and Corridor VersionsLED emergency luminaires for recessed mounting
Accessories
DESCRIPTION CAT. No.
Mounting bracket for control module � SLA 13101
LED plasterboard bezel� SLA 13213
Mains supply plug (required when not usingmodular wiring cables)
SLA 12982
� Fits across ceiling T-bars� Required for use with plasterboard ceilings(masks larger 60mm dia. cut-out)
NOTE: When used with plasterboard ceilingsuse SLA 13213 bezel and
60mm dia. cut-out (approx.)
55 dia.
55 dia.
42
38
2.5
Ceiling cut-out -45mm dia. (approx.)
3.5
42
38
2.5
11.5
Area Version
Corridor Version
Jun. ‘09 21
20 Jun. ‘09
CANDELAS PER 1000 LUMENS
600
1200
1800
2400
TRANSVERSE AXIAL
Spacing Table
MOUNTING A B
HEIGHT (m) (m) (m)
2.0 3.8 8.5
2.5 4.2 9.8
3.0 4.6 11.0
3.5 4.9 12.0
4.0 5.0 12.8
Maintenance factor 0.90
Typical spacing for area lens
Typical spacing for corridor (escape route) lens
Photometric Guide
Photometric Guide
A
A A
A
B B
MountingHeight
MountingHeight
A
A
B
B
B
CANDELAS PER 1000 LUMENS
TRANSVERSE AXIAL
80
160
240
320
0.5 lux minimum
1 lux minimum(on centre line)
LED DownlighterEmergency lighting performance
Spacing Table
MOUNTING A B
HEIGHT (m) (m) (m)
2.0 7.5 17.9
2.5 8.7 20.8
3.0 9.2 23.3
3.5 4.8 21.9
4.0 4.9 21.5
Maintenance factor 0.90
Fire Escape Stairs
We have proposed the use of Thorlux Kanby T5 controller luminaires to replace existing
luminaires on a on-for-one basis. These luminaires operate on high frequency electronic
control gear and will save energy compared to older less efficient T8 luminaires.
For emergency lighting we have proposed Thorlux Eight-65 emergency bulkhead
luminaires to replace your existing bulkhead units.
Borders Hospital
Half Landing on Stairs
Partner for Contact: Ian GentlemanOrder No.: Company: Borders NHSCustomer No.:
Date: 07.02.2011Operator: Graham Lucas
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Escape Stairs.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Table of contents
Borders HospitalProject Cover 1Table of contents 2THORLUX KB10859 Kanby T5 Polycarbonate Diffuser - 2x35W
Luminaire Data Sheet 3Room 1
Luminaires (layout plan) 4Room Surfaces
FloorIsolines (E) 5Greyscale (E) 6Value Chart (E) 7
Page 2
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Escape Stairs.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
THORLUX KB10859 Kanby T5 Polycarbonate Diffuser - 2x35W / Luminaire Data Sheet
Luminous emittance 1:
80
120
160
200
cd/klm 82%C0 - C180 C90 - C270
0° 15° 30° 45°
60°
75°
90°
105°
120°
135°150°165°180°165°150°135°
120°
105°
90°
75°
60°
45° 30° 15° 0°
Luminaire classification according to CIE: 84CIE flux code: 38 69 88 84 82
Surface mounted diffuser luminaire
Luminous emittance 1:
Glare Evaluation According to UGR
Ceiling 70 70 50 50 30 70 70 50 50 30
Walls 50 30 50 30 30 50 30 50 30 30
Floor 20 20 20 20 20 20 20 20 20 20
Room SizeX Y
Viewing direction at right anglesto lamp axis
Viewing direction parallelto lamp axis
2H 2H 19.4 20.6 19.9 21.1 21.7 16.9 18.1 17.4 18.6 19.23H 21.5 22.6 22.0 23.1 23.7 17.9 19.0 18.5 19.6 20.24H 22.5 23.6 23.1 24.2 24.8 18.2 19.2 18.7 19.8 20.46H 23.6 24.6 24.2 25.2 25.8 18.3 19.3 18.9 19.8 20.58H 24.1 25.1 24.7 25.7 26.3 18.3 19.2 18.9 19.8 20.5
12H 24.7 25.6 25.3 26.2 26.8 18.3 19.2 18.9 19.8 20.5
4H 2H 19.7 20.7 20.2 21.3 21.9 17.8 18.8 18.3 19.4 20.03H 22.1 23.0 22.7 23.6 24.3 19.1 20.1 19.8 20.6 21.34H 23.4 24.2 24.0 24.8 25.5 19.6 20.4 20.2 21.0 21.76H 24.6 25.3 25.3 26.0 26.7 19.9 20.6 20.6 21.3 22.08H 25.3 25.9 25.9 26.6 27.3 20.0 20.7 20.7 21.3 22.1
12H 25.9 26.5 26.6 27.2 27.9 20.1 20.7 20.7 21.3 22.1
8H 4H 23.6 24.2 24.2 24.9 25.6 20.4 21.1 21.1 21.8 22.56H 25.1 25.6 25.7 26.3 27.1 21.0 21.6 21.7 22.3 23.18H 25.9 26.3 26.6 27.0 27.9 21.3 21.8 22.0 22.5 23.3
12H 26.7 27.1 27.4 27.8 28.7 21.4 21.9 22.2 22.6 23.4
12H 4H 23.5 24.2 24.2 24.8 25.6 20.7 21.3 21.3 21.9 22.76H 25.1 25.6 25.8 26.3 27.1 21.4 21.9 22.1 22.6 23.48H 26.0 26.4 26.7 27.1 28.0 21.8 22.2 22.5 22.9 23.7
Variation of the observer position for the luminaire distances S
S = 1.0H +0.1 / -0.1 +0.2 / -0.2S = 1.5H +0.2 / -0.2 +0.4 / -0.5S = 2.0H +0.3 / -0.4 +0.6 / -1.1
Standard table BK09 BK14
Correction Summand 2.9 -1.5
Corrected Glare Indices referring to 6600lm Total Luminous Flux
Page 3
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Escape Stairs.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Luminaires (layout plan)
1
1.50 m0.00
3.40 m
0.00
1.70
Scale 1 : 23
Luminaire Parts List
No. Pieces Designation
1 1 THORLUX KB10859 Kanby T5 Polycarbonate Diffuser - 2x35W
Page 4
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Escape Stairs.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Isolines (E)
120
120
150
150
150
150
180180
180180
180
180
180
210
210
1.50 m0.00
3.40 m
0.00
Values in Lux, Scale 1 : 27Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 13 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax163 109 213 0.670 0.513
Page 5
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Escape Stairs.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Greyscale (E)
120
150
180
210
lx
1.50 m0.00
3.40 m
0.00
Scale 1 : 27Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 13 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax163 109 213 0.670 0.513
Page 6
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Escape Stairs.dlx 07.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Value Chart (E)
121
130
156
175
184
197
204
197
185
171
156
130
121
121
134
159
178
194
201
206
201
194
178
159
133
121
129
137
165
186
201
210
213
211
200
187
165
136
128
123
132
159
179
195
206
209
206
195
180
159
130
125
121
128
156
176
192
203
206
203
192
176
156
127
121
111
119
145
163
178
188
192
188
178
164
145
117
111
109
115
141
158
171
182
184
182
172
158
141
115
109
1.50 m0.00
3.40 m
0.00
Values in Lux, Scale 1 : 27
Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 13 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax163 109 213 0.670 0.513
Page 7
Legend Kit
Self-adhesive legend kit (inc. A, B and C) �Cat. No. EFB 9137
�Order separately
102
160
400
Semi-recessed mounting cut-out149 x 389mmmaximum
� Off-white polycarbonate body
� Opal or clear prismatic polycarbonate covers
� May be semi-recessed
� Emergency and AutoTest versions
� Three hour, maintained or non-maintained operation
� Optional self-adhesive legend kit
� Complies with M.O.D. JSP482 Chapter 8 Documentfor ‘Category C’areas
� Fitted with 3500K lamp
RangeOPAL CLEAR APPROX.
LAMP VERSION VERSION kg TYPE
MAINS
2 x 8WT5 FB 9308E FB 9322E 1.3 -
1 x 11WTC-S FB 9305E FB 9319E 1.7 -
EMERGENCY
1 x 8WT5 EFB 9304E EFB 9318E 2.0 Maintained1 x 8WT5 EFB 9303 EFB 9317 1.8 Non-maintained
1 x 11WTC-S EFB 9307E EFB 9321E 2.7 Maintained1 x 11WTC-S EFB 9306 EFB 9320 2.4 Non-maintained
AUTOTEST
1 x 8WT5 TFB 9304E TFB 9318E 2.0 Maintained1 x 8WT5 TFB 9303 TFB 9317 1.8 Non-maintained
1 x 11WTC-S TFB 9307E TFB 9321E 2.7 Maintained1 x 11WTC-S TFB 9306 TFB 9320 2.4 Non-maintained
Eight - 65Fluorescent T5 and PL emergency bulkhead luminaires
24 Oct. ‘08
Snake
We have proposed the use of Thorlux Kanby T5 fluorescent reflector luminaires to replace
your existing on a one-for-one basis. We have also proposed the use of Ex-Or passive
infra red motion detectors to switch the luminaires on and off. Each sensor will have a
detection pattern of 6m at a mounting height of 2.5m and we suggest these are mounted above the access route around the snake. There are various ways that these can be
linked and wired to suit specific circumstances that we would need to discuss.
Recovery.
We have proposed Thorlux Skydome 4x24w T5 recessed module with domed
polycarbonate diffusers. Sky-Dome has been designed to exclude dust, dirt and flies. All
control gear is outside the lamp enclosure and the diffuser frame is gasketted.
We propose replacement of your existing luminaires on a one-for-one basis.
These luminaires can be operated from both essential and non-essential supplies. We
have also examined the use of recessed LED Night lighting and propose that these should
be used instead of any existing night lights again on a one-for-one replacement basis.
Sky-DomeRecessed luminaire with domed polycarbonate diffuser
� Steel body finished white
� Shallow body depth at 106mm
� Domed diffuser provides wall and ceiling illumination
� Suitable for most ceiling types. Lay-in or pull-up withoptional side arm suspensions
� Sky-Dome has been designed to exclude dust, dirtand flies. All control gear is outside the lampenclosure and the diffuser frame is gasketted
� Fitted with 6500K lamps
Range
NOMINAL APPROX.
SIZE (mm) LAMP CAT. No. kg CIRCUIT
STANDARDVERSIONS
600 x 6004 x 14WT5 SD 12892 5.8 D-J
4 x 24WT5 SD 12893 5.8 D-J
600 x 6002 x 40WTC-L SD 12894 5.8 D-J
2 x 55WTC-L SD 12895 5.8 D-J
SMARTVERSIONS
600 x 600 4 x 14WT5 SD 13787 5.8 D
600 x 600 2 x 55WTC-L SD 13790 5.8 D
Circuit: add suffix required:D - high frequency regulating J - high frequency e.g. SD 12892D etc.
EMERGENCYVERSION - prefix catalogue number with ‘ESD’.AUTOTEST VERSION - prefix catalogue number with ‘TSD’ .Emergency and AutoTest versions add 0.7kg to weights listed.
ACCESSORY - Optional side arm suspension kit, HI 12349 (4 arms per kit)(Not required for lay-in mounting)
LAMP COMPARTMENT
GEAR COMPARTMENT
IP42LAMP COMPARTMENT (SMART VERSION)
CANDELAS PER 1000 LUMENS
TRANSVERSE AXIAL
4 LAMP - 14WD.L.O.R. 69%
FACTOR: 4 x 24W = 0.91
2 x 40W = 0.91
2 x 55W = 0.87
SPACING LUX AVERAGE LUX AVERAGE
LAMP (Metres) 70/50/20 80/60/30
OPEN PLAN
3.0 x 3.0 320 3604 x 14WT5 3.0 x 2.4 380 440
2.4 x 2.4 450 510
3.0 x 3.0 430 4904 x 24WT5 3.0 x 2.4 520 600
2.4 x 2.4 620 700
3.0 x 3.0 440 5002 x 40WTC-L 3.0 x 2.4 530 600
2.4 x 2.4 620 710
3.0 x 3.0 570 6502 x 55WTC-L 3.0 x 2.4 690 780
2.4 x 2.4 810 920
CORRIDOR
4 x 14WT5 5.4 140 170
4 x 24WT5 5.4 190 230
2 x 40WTC-L 5.4 190 230
2 x 55WTC-L 5.4 250 300
Performance Guide
Typical task area illuminance assuming an open area with goodreflection factors, 0.85 maintenance factor and a 2.65 metreceiling height.
Oct. ‘08 23
Sky-Dome Design Registration Number 3021532
Smart Version
553
106112243
108
597 220
571597
6-way‘T’piece(Smart
and LCMversions
only)
118
89 21 dia. mains entry hole(Standard versions only)
ALL DIMENSIONS ARE IN MILLIMETRES
600 CRS.
Exposed T-bar
(15 or 24)
600 CRS.
Spring Tee
600 CRS.
Concealed
600 CRS.
Lay-in on Exposed T-bar
(15 or 24)
Plasterboard Ceiling
597 x 597
57715
25 x 25nogging
20
29
6
Side arm suspensionadjustment range
Mounting Arrangements
Sky-Dome
22 Oct. ‘08
Recessed version
LED Night LightRecessed or surface LED downlighter
Nov. ‘10
� Complies with the CIBSE 2008 HospitalLighting Guide (LG2)
� Attractive contemporary styling
� Surface or recessed versions available
� Injection moulded polycarbonatebody finished RAL 9010
� Highly efficient thermally managed1.5W LED
� Extremely low glare optics for maximumpatient visual comfort
� Powered at 500mA for long“maintenancefree” life
� Supplied complete with high qualityelectronic driver
Surface version
APPROX.CAT. No. VERSION kg
NL 14350 Recessed 0.13
NL 14387 Surface 0.30
Range
37
55 dia.38 45
40dia.42
3
Spot centre forconduit entry
RECESSED VERSION
SURFACE VERSION
155
245 82
StatusIndicator
Status Indicator
IP54
IP20
SURFACE VERSION
RECESSED VERSION
Hospital Management & Corridor
We have proposed Thorlux Histyle Pro 1x40w compact fluorescent recessed module
suitable for VDT environments.
We have produced a plot that shows that spacing these luminaires at 2.4m centres will
provide an illuminance of 400 lux. These areas need to be illuminated to between 300 –
500 lux.
This spacing can be used to determine the number of luminaires needed to illuminate any
office type area. These luminaires are 600mm x 600mm so some work will need to be done on the ceiling to allow them to fit as your existing ceiling in this area has 1200mm x
600mm tiles.
For the corridor we have looked at using Thorn Cruz 160 34 LED recessed downlight
luminaires and these can be used at 3m centres to illuminate the corridor.
Borders Hospital
Management Office
Partner for Contact: Ian GentlemanOrder No.: Company: Borders NHSCustomer No.:
Date: 08.02.2011Operator: Graham Lucas
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Office.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Table of contents
Borders HospitalProject Cover 1Table of contents 2THORLUX HI12303 Hi - Style Pro - 1x40W
Luminaire Data Sheet 3Room 1
Luminaires (layout plan) 4Room Surfaces
WorkplaneIsolines (E) 5Greyscale (E) 6Value Chart (E) 7
Page 2
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Office.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
THORLUX HI12303 Hi - Style Pro - 1x40W / Luminaire Data Sheet
Luminous emittance 1:
160
240
cd/klm 78%C0 - C180 C90 - C270
0° 15° 30°
45°
60°
75°
90°
105°105°
90°
75°
60°
45°
30° 15° 0°
Luminaire classification according to CIE: 100CIE flux code: 63 93 99 100 78
Recessed direct/indirect luminaire with LG7:2005 louvre
Luminous emittance 1:
Glare Evaluation According to UGR
Ceiling 70 70 50 50 30 70 70 50 50 30
Walls 50 30 50 30 30 50 30 50 30 30
Floor 20 20 20 20 20 20 20 20 20 20
Room SizeX Y
Viewing direction at right anglesto lamp axis
Viewing direction parallelto lamp axis
2H 2H 13.1 14.1 13.3 14.4 14.6 10.1 11.2 10.4 11.4 11.63H 13.9 14.8 14.2 15.1 15.3 10.8 11.8 11.1 12.1 12.34H 13.9 14.8 14.2 15.1 15.4 11.1 12.1 11.5 12.3 12.66H 13.9 14.7 14.2 15.0 15.3 11.4 12.2 11.8 12.5 12.88H 13.9 14.7 14.2 15.0 15.3 11.5 12.3 11.8 12.6 12.9
12H 13.8 14.6 14.2 14.9 15.3 11.5 12.3 11.9 12.6 12.9
4H 2H 13.1 14.0 13.5 14.3 14.6 10.6 11.5 10.9 11.7 12.03H 14.1 14.8 14.4 15.1 15.5 11.5 12.3 11.9 12.6 12.94H 14.1 14.8 14.5 15.2 15.5 12.0 12.6 12.4 13.0 13.36H 14.2 14.7 14.6 15.1 15.5 12.3 12.9 12.7 13.3 13.78H 14.2 14.7 14.6 15.1 15.5 12.4 13.0 12.9 13.3 13.8
12H 14.1 14.6 14.6 15.0 15.5 12.5 13.0 13.0 13.4 13.8
8H 4H 14.2 14.7 14.6 15.1 15.5 12.1 12.6 12.5 13.0 13.46H 14.2 14.6 14.7 15.1 15.5 12.5 12.9 13.0 13.4 13.88H 14.2 14.6 14.7 15.0 15.5 12.7 13.1 13.2 13.5 14.0
12H 14.2 14.5 14.7 15.0 15.5 12.8 13.1 13.3 13.6 14.1
12H 4H 14.1 14.6 14.6 15.0 15.4 12.1 12.5 12.5 13.0 13.46H 14.2 14.6 14.7 15.0 15.5 12.5 12.9 13.0 13.3 13.88H 14.2 14.5 14.7 15.0 15.5 12.7 13.0 13.2 13.5 14.0
Variation of the observer position for the luminaire distances S
S = 1.0H +0.6 / -1.1 +0.9 / -1.2S = 1.5H +1.4 / -3.1 +1.8 / -2.6S = 2.0H +2.9 / -3.7 +2.6 / -3.3
Standard table BK01 BK02
Correction Summand -7.7 -8.9
Corrected Glare Indices referring to 3500lm Total Luminous Flux
Page 3
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Office.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Luminaires (layout plan)
1
1
1
1
1
1
1
1
1
1
1
1
8.30 m0.00 0.60 3.00 5.40 7.80
6.60 m
0.00
0.60
3.00
5.40
Scale 1 : 60
Luminaire Parts List
No. Pieces Designation
1 12 THORLUX HI12303 Hi - Style Pro - 1x40W
Page 4
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Office.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Workplane / Isolines (E)
360360360
400400 400
400400400400
440440
440
440
440
440
440
440
440
440440
440
440
8.30 m0.00 0.50 7.80
6.60 m
0.00
0.50
6.10
Values in Lux, Scale 1 : 60Position of surface in room:Working plane with 0.500 m Boundary ZoneMarked point:(0.500 m, 0.500 m, 0.750 m)
Grid: 11 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax412 332 488 0.804 0.680
Page 5
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Office.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Workplane / Greyscale (E)
360 400 440 lx
8.30 m0.00 0.50 7.80
6.60 m
0.00
0.50
6.10
Scale 1 : 60Position of surface in room:Working plane with 0.500 m Boundary ZoneMarked point:(0.500 m, 0.500 m, 0.750 m)
Grid: 11 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax412 332 488 0.804 0.680
Page 6
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Office.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Workplane / Value Chart (E)
408 385 393 420 402 385 398 423 402 388 414
470 447 456 485 466 446 461 488 464 448 474
422 403 412 435 420 403 416 437 421 406 427
413 392 402 426 409 391 404 427 410 395 417
465 442 452 480 461 440 455 482 460 443 468
393 373 382 405 388 372 384 406 389 375 398
354 333 341 364 348 332 343 365 348 334 358
8.30 m0.00 0.50 7.80
6.60 m
0.00
0.50
6.10
Values in Lux, Scale 1 : 60
Position of surface in room:Working plane with 0.500 m Boundary ZoneMarked point:(0.500 m, 0.500 m, 0.750 m)
Grid: 11 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax412 332 488 0.804 0.680
Page 7
Borders Hospital
Management Offices Corridor Lighting
Partner for Contact: Ian GentlemanOrder No.: Company: Borders NHSCustomer No.:
Date: 11.02.2011Operator: Graham Lucas
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Offices Corridor.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Table of contents
Borders HospitalProject Cover 1Table of contents 2Thorn 96107638 CRUZ 160 1x34W LED L840 HFX [STD]
Luminaire Data Sheet 3Room 1
Luminaires (layout plan) 4Room Surfaces
FloorIsolines (E) 5Greyscale (E) 6Value Chart (E) 7
Page 2
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Offices Corridor.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Thorn 96107638 CRUZ 160 1x34W LED L840 HFX [STD] / Luminaire Data Sheet
Luminous emittance 1:
400
600
800
1000
cd/klm 94%C0 - C180 C90 - C270
0° 15° 30°
45°
60°
75°
90°
105°105°
90°
75°
60°
45°
30° 15° 0°
Luminaire classification according to CIE: 100CIE flux code: 100 100 100 92 93
A stylish, recessed High-Flux-LED downlight with integral 2000lm light engine with active cooling and remote DALI dimmable gear. IP20, Class I electrical. LOR 0.94, UGR<19. Body in die-cast, sand blasted aluminium with black polycarbonate gear cover and one-piece specular anodised high purity aluminium reflector. Luminaire secured by patented, tool-free "sec-lock" in Ø160mm cut-out. Suitable for ceiling thicknesses 1-35mm. Complete with 4000K LED
Dimensions: Ø178 x 137 mm Total power: 34 W Weight: 1.8 kg
Luminous emittance 1:
Glare Evaluation According to UGR
Ceiling 70 70 50 50 30 70 70 50 50 30
Walls 50 30 50 30 30 50 30 50 30 30
Floor 20 20 20 20 20 20 20 20 20 20
Room SizeX Y
Viewing direction at right anglesto lamp axis
Viewing direction parallelto lamp axis
2H 2H 1.3 2.0 1.6 2.2 2.4 1.3 2.0 1.6 2.2 2.43H 1.2 1.8 1.5 2.1 2.3 1.2 1.8 1.5 2.1 2.34H 1.1 1.7 1.4 2.0 2.2 1.1 1.7 1.4 2.0 2.26H 1.1 1.6 1.4 1.9 2.2 1.1 1.6 1.4 1.9 2.28H 1.0 1.5 1.3 1.8 2.1 1.0 1.5 1.3 1.8 2.1
12H 1.0 1.5 1.3 1.8 2.1 1.0 1.5 1.3 1.8 2.1
4H 2H 1.1 1.7 1.4 2.0 2.2 1.1 1.7 1.4 2.0 2.23H 1.0 1.5 1.3 1.8 2.1 1.0 1.5 1.3 1.8 2.14H 0.9 1.3 1.3 1.7 2.0 0.9 1.3 1.3 1.7 2.06H 0.8 1.2 1.2 1.6 1.9 0.8 1.2 1.2 1.6 1.98H 0.8 1.1 1.2 1.5 1.9 0.8 1.1 1.2 1.5 1.9
12H 0.8 1.0 1.2 1.4 1.8 0.8 1.0 1.2 1.4 1.8
8H 4H 0.8 1.1 1.2 1.5 1.9 0.8 1.1 1.2 1.5 1.96H 0.7 0.9 1.2 1.4 1.8 0.7 0.9 1.2 1.4 1.88H 0.7 0.9 1.1 1.3 1.8 0.7 0.9 1.1 1.3 1.8
12H 0.6 0.8 1.1 1.2 1.7 0.6 0.8 1.1 1.2 1.7
12H 4H 0.8 1.0 1.2 1.4 1.8 0.8 1.0 1.2 1.4 1.86H 0.7 0.9 1.1 1.3 1.8 0.7 0.9 1.1 1.3 1.88H 0.6 0.8 1.1 1.2 1.7 0.6 0.8 1.1 1.2 1.7
Variation of the observer position for the luminaire distances S
S = 1.0H +3.7 / -23.3 +3.7 / -23.3S = 1.5H +6.4 / -97.3 +6.4 / -97.3S = 2.0H +8.4 / -95.3 +8.4 / -95.3
Standard table BK00 BK00
Correction Summand -3.9 -3.9
Corrected Glare Indices referring to 2000lm Total Luminous Flux
Page 3
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Offices Corridor.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Luminaires (layout plan)
1
1
1
1
1
1
1.80 m0.00 0.90
16.90 m
0.00
1.50
4.50
7.50
10.50
13.50
15.90
Scale 1 : 115
Luminaire Parts List
No. Pieces Designation
1 6 Thorn 96107638 CRUZ 160 1x34W LED L840 HFX [STD]
Page 4
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Offices Corridor.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Isolines (E)
160200
200
200
200
200
240240
240
280
1.80 m0.00
16.90 m
0.00
Values in Lux, Scale 1 : 133Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 128 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax206 102 290 0.496 0.352
Page 5
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Offices Corridor.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Greyscale (E)
120
160
200
240
280
lx
1.80 m0.00
16.90 m
0.00
Scale 1 : 133Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 128 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax206 102 290 0.496 0.352
Page 6
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Management Offices Corridor.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Value Chart (E)
150194211196178196215211183183210216203179193214213191180213228237267234220
157201217204195204223216195192216225209198203221219200197219238249281241229
1.80 m0.00
16.90 m
0.00
Values in Lux, Scale 1 : 133Not all calculated values could be displayed.
Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 128 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax206 102 290 0.496 0.352
Page 7
Cruz 160 LED
96107638 CRUZ 160 1x34W LED L840 HFX
Thorn Lighting is constantly developing and improving its products. The right is reserved to change specifications without prior notification or public announcement. © Thorn Lighting
34W LED-DLM
Cruz 160 LED
A stylish, recessed High-Flux-LED downlight with integral 2000lm light engine with active cooling and remote DALI dimmable gear. IP20, Class I electrical. LOR 0.94, UGR<19. Body in die-cast, sand blasted aluminium with black polycarbonate gear cover and one-piece specular anodised high purity aluminium reflector. Luminaire secured by patented, tool-free "sec-lock" in Ø160mm cut-out. Suitable for ceiling thicknesses 1-35mm. Complete with 4000K LED
Dimensions: Ø178 x 137 mmTotal power: 34 WWeight: 1.8 kg
TLG_CRUZ_F_LEDP1.jpg
TLG_CRUZ_M_160LED.wmf
0°
30°30°
60°60°
90° 90°
120° 120°
150° 150°
180°
250500750
cd/klm
TLG_LE_1169.ldt
Lamp position: STD - standardLamp: LED-DLM 34WLOR: 0,94 ULOR: 0,00 DLOR: 0,94
Physiotherapy Suit
We have proposed Thorlux A-Line Smart 2x49w T5 IP65 sealed surface mounted
luminaires. These luminaires have individual or group PIR control and daylight linking.
The A-LineXL Smart version combines the latest “Digital Technology” to provide a simple,
effective method of lighting control which minimises energy consumption whilst retaining
high levels of user comfort. An integral sensor (Smart Micro-pod) monitors ambient light
and presence, controlling output to the correct level and ensuring that the area is only illuminated when occupied.
We suggest these are used to replace your existing lighting on a one-for-one basis.
Physiotherapy Gymnasium.
We have proposed Thorlux Solow Smart 4x80w T5 surface mounted luminaires. These
luminaires have individual or group PIR control and daylight linking.
The Thorlux Solow Smart combines the latest “Digital Technology” to provide a simple,
effective method of lighting control which minimises energy consumption whilst retaining
high levels of user comfort. An integral sensor (Smart Micro-pod) monitors ambient light
and presence, controlling output to the correct level and ensuring that the area is only illuminated when occupied.
These luminaires are suitable for use at up to 10m mounting height
We suggest these are used to replace your existing lighting on a one-for-one basis.
Borders Hospital
Gym
Partner for Contact: Ian GentlemanOrder No.: Company: Borders NHSCustomer No.:
Date: 10.02.2011Operator: Graham Lucas
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Gym.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Table of contents
Borders HospitalProject Cover 1Table of contents 2THORLUX SW13298 Solow T5 Narrow Wire Guard SMART - 4x80W
Luminaire Data Sheet 3Room 1
Luminaires (layout plan) 4Room Surfaces
FloorIsolines (E) 5Greyscale (E) 6Value Chart (E) 7
Page 2
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Gym.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
THORLUX SW13298 Solow T5 Narrow Wire Guard SMART - 4x80W / Luminaire Data Sheet
Luminous emittance 1:
200
300
400
cd/klm 70%C0 - C180 C90 - C270
0° 15° 30°
45°
60°
75°
90°
105°105°
90°
75°
60°
45°
30° 15° 0°
Luminaire classification according to CIE: 99CIE flux code: 61 89 98 99 70
Shallow depth T5 low bay luminaire c/w SMART pod
Luminous emittance 1:
Glare Evaluation According to UGR
Ceiling 70 70 50 50 30 70 70 50 50 30
Walls 50 30 50 30 30 50 30 50 30 30
Floor 20 20 20 20 20 20 20 20 20 20
Room SizeX Y
Viewing direction at right anglesto lamp axis
Viewing direction parallelto lamp axis
2H 2H 17.0 18.1 17.3 18.3 18.6 21.2 22.3 21.5 22.5 22.83H 17.9 18.9 18.2 19.1 19.4 22.4 23.5 22.8 23.7 24.04H 18.1 19.0 18.4 19.3 19.6 22.8 23.8 23.2 24.1 24.46H 18.3 19.2 18.6 19.5 19.8 23.1 23.9 23.4 24.2 24.58H 18.4 19.2 18.8 19.5 19.9 23.1 23.9 23.5 24.3 24.6
12H 18.5 19.3 18.9 19.6 19.9 23.1 23.9 23.5 24.2 24.6
4H 2H 17.5 18.4 17.8 18.7 19.0 21.2 22.1 21.5 22.4 22.73H 18.6 19.3 18.9 19.7 20.0 22.6 23.4 23.0 23.7 24.04H 18.9 19.5 19.3 19.9 20.3 23.1 23.8 23.5 24.1 24.56H 19.2 19.8 19.6 20.2 20.6 23.4 24.0 23.8 24.4 24.88H 19.3 19.9 19.8 20.3 20.7 23.4 24.0 23.9 24.4 24.8
12H 19.5 20.0 19.9 20.4 20.8 23.5 24.0 23.9 24.4 24.8
8H 4H 19.1 19.7 19.5 20.1 20.5 23.0 23.6 23.5 24.0 24.46H 19.5 20.0 20.0 20.4 20.9 23.4 23.9 23.9 24.3 24.88H 19.8 20.2 20.3 20.6 21.1 23.5 23.9 24.0 24.4 24.9
12H 20.0 20.3 20.5 20.8 21.3 23.6 23.9 24.1 24.4 24.9
12H 4H 19.1 19.6 19.6 20.0 20.5 23.0 23.5 23.5 23.9 24.46H 19.6 20.0 20.1 20.4 20.9 23.4 23.8 23.9 24.2 24.78H 19.9 20.2 20.4 20.7 21.2 23.5 23.9 24.0 24.3 24.9
Variation of the observer position for the luminaire distances S
S = 1.0H +0.3 / -0.5 +0.1 / -0.2S = 1.5H +0.6 / -1.2 +0.7 / -0.8S = 2.0H +1.1 / -1.9 +1.6 / -1.8
Standard table BK03 BK04
Correction Summand -9.9 -5.8
Corrected Glare Indices referring to 25800lm Total Luminous Flux
Page 3
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Gym.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Luminaires (layout plan)
1
1
1
1
1
1
19.20 m0.00 3.20 9.60 16.00
9.00 m
0.00
2.25
6.75
Scale 1 : 138
Luminaire Parts List
No. Pieces Designation
1 6 THORLUX SW13298 Solow T5 Narrow Wire Guard SMART - 4x80W
Page 4
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Gym.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Isolines (E)
240
240
240
280
280280
280
280
280
280320
320320 320
320
320
320
320320320
320
320360
360360 360
360360
360
360360360
360
360
19.20 m0.00
9.00 m
0.00
Values in Lux, Scale 1 : 138Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 21 x 11 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax315 210 400 0.665 0.524
Page 5
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Gym.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Greyscale (E)
240 280 320 360 lx
19.20 m0.00
9.00 m
0.00
Scale 1 : 138Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 21 x 11 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax315 210 400 0.665 0.524
Page 6
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Gym.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Value Chart (E)
211 233 250 263 275 281 288 296 298 298 299 298 298 296 288 281 275 263 250 233 210
222 244 265 280 293 304 310 314 318 323 325 323 318 314 310 304 293 280 265 244 225
239 262 285 302 317 328 335 340 344 350 352 349 344 340 335 328 317 302 285 262 241
259 278 303 324 338 348 355 362 366 371 373 370 366 362 355 348 338 324 303 278 259
272 294 321 341 357 368 375 382 387 392 394 392 387 382 375 368 357 341 320 294 272
273 299 326 346 362 374 382 389 394 398 400 398 394 389 382 374 362 346 325 298 276
272 294 321 341 357 368 375 382 387 392 394 392 387 382 375 368 357 341 320 294 272
259 278 303 324 338 348 355 362 366 371 373 370 366 362 355 348 338 324 303 278 259
239 262 285 302 317 328 335 340 344 350 352 349 344 340 335 328 317 302 285 262 241
222 244 265 280 293 304 310 314 318 323 325 323 318 314 310 304 293 280 265 244 225
211 233 250 263 275 281 288 296 298 298 299 298 298 296 288 281 275 263 250 233 210
19.20 m0.00
9.00 m
0.00
Values in Lux, Scale 1 : 138
Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 21 x 11 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax315 210 400 0.665 0.524
Page 7
Range
POLYCARBONATE WIRE GLARE REDUCTION
NOMINAL OPEN APPROX. COVER APPROX. GUARD APPROX. LOUVRE APPROX.
SIZE (mm) LAMP VERSION kg VERSION kg VERSION kg VERSION kg CIRCUIT
BROAD DISTRIBUTION
1200 4 x 54W T5 SW 12062 11.2 SW 12064 13.1 SW 12194 12.7 SW 12195 11.9 D-J-T
1500 4 x 80W T5 SW 12066 12.5 - - SW 12196 14.4 SW 12197 13.3 D-J-T
NARROWDISTRIBUTION
1200 4 x 54W T5 SW 12063 11.2 SW 12065 13.1 SW 12198 12.7 SW 12199 11.9 D-J-T
1500 4 x 80W T5 SW 12067 12.5 - - SW 12200 14.4 SW 12201 13.3 D-J-T
CIRCUIT - add suffix required:D - high frequency regulating J - high frequency (dual circuit) T - DSI (digital electronic for use with ECO-Sport controller) e.g. SW 12062D etc.
EMERGENCYVERSION - prefix catalogue number with ‘ESW’.AUTOTEST VERSION - prefix catalogue number with ‘TSW’.
Emergency and AutoTest versions add 0.7kg to weights listed.
LAMPSMUST BE ORDERED SEPARATELY
ECO-Sport - An impact resistant,simple, light level controller withthree programmable preset levels.See page 270 for further details.Cat No. ECO 13551
SolowT5Energy efficient high output T5 luminaires
Polycarbonate Cover Glare Reduction LouvreWire Guard
� Zinc coated steel body and backplate finished white
� Lockable quick-release latches detach body frombackplate for easy access
� Lamps may be switched in pairs (J - highfrequency only)
� Open and protected versions (covers, wire guardsand louvres supplied fitted)
� DSI (digital electronic) versions for use withECO-Sport Controller
� Solow T5 enables full compliance with‘Recommendations for Sports Hall Lighting’provided by U.K. Sports Council
Certified as ball impact resistant to
DIN 18032 Part 3 VDE 0710 Part 13
Oct. ‘08 15
AccessoriesAPPROX.
DESCRIPTION CAT. No. kg
Kit of 3 spacers for trunking fix SW 11792 0.22
Smart-Programmer (for use with Smart versions) LCM 10777 0.30
54W - 1250 / 80W - 1550
54W - 1080 CRS. / 80W - 1380 CRS
54W - 950 CRS. / 80W - 1250 CRS54W - 990 CRS. / 80W - 1290 CRS
6 slots7 x 20
3 holes21 dia.
3 holes9 dia.
10080
247 350
125
Photometric Guide
4 x 54W, SOLOWT5, OPEN
Broad DistributionD.L.O.R. 80 % U.L.O.R. 0%
4 x 54W, SOLOWT5, OPEN
Narrow DistributionD.L.O.R. 74 % U.L.O.R. 0%
FACTOR: 4 x 80W = 1.06 FACTOR: 4 x 80W = 1.04
14 Oct. ‘08
� Zinc coated steel body and backplate finished white
� Lockable quick-release latches detach body frombackplate for easy access
� Open and protected versions (covers, wire guardsand louvres supplied fitted)
� Individual or group PIR control and daylight linking
� Programmable for on/off switching or dim only
� Solow T5 Smart enables full compliance with‘Recommendations for Sports Hall Lighting’provided by U.K. Sports Council
� Suitable for use up to 10 metres mounting height
Range
POLYCARBONATE WIRE GLARE REDUCTION
NOMINAL OPEN APPROX. COVER APPROX. GUARD APPROX. LOUVRE APPROX.
SIZE (mm) LAMP VERSION kg VERSION kg VERSION kg VERSION kg
BROAD DISTRIBUTION
1200 4 x 54W T5 SW 13286D 11.2 SW 13287D 13.1 SW 13288D 12.7 SW 13289D 11.91500 4 x 80W T5 SW 13290D 12.5 - - SW 13291D 14.4 SW 13292D 13.3
NARROWDISTRIBUTION
1200 4 x 54W T5 SW 13293D 11.2 SW 13294D 13.1 SW 13295D 12.7 SW 13296D 11.91500 4 x 80W T5 SW 13297D 12.5 - - SW 13298D 14.4 SW 13299D 13.3
EMERGENCYVERSION - prefix catalogue number with ‘ESW’
AUTOTEST VERSION - prefix catalogue number with ‘TSW’.
Emergency and AutoTest versions add 0.7kg to weights listed.
LAMPSMUST BE ORDERED SEPARATELY
SolowT5 SmartT5 luminaires with intelligent lighting controls
Photometric Guide, Dimensions
and Accessories - see page 14
Certified as ball impact resistant to
DIN 18032 Part 3 VDE 0710 Part 13
Polycarbonate Cover Glare Reduction LouvreWire Guard
Oct. ‘08 17
Main Entrance Corridor.
At present this corridor looks a bit dark and needs uplifting. The reason for the dark
appearance is probably due to a dark ceiling that makes the corridor appear gloomy
especially when compared to the bright reception area at the hospital entrance. We have
proposed Thorlux Hi-Style Com recessed luminaires. These luminaires will brighten up the
ceiling and as we have also spaced the luminaires at 2.4m centres and this will illuminate the area to 240 lux. This is a higher than usual level for a corridor so will help to act as a
transition zone between the reception and the hospital corridor further within the building
and will allow the eye to adjust. This should greatly enhance the appearance of this
corridor.
Borders Hospital
Main Entrance Corridor Lighting
Partner for Contact: Ian GentlemanOrder No.: Company: Borders NHSCustomer No.:
Date: 08.02.2011Operator: Graham Lucas
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Main Corridor.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Table of contents
Borders HospitalProject Cover 1Table of contents 2THORLUX HI12563 Hi - Style Com - 2x55W
Luminaire Data Sheet 3Room 1
Luminaires (layout plan) 4Room Surfaces
FloorIsolines (E) 5Greyscale (E) 6Value Chart (E) 7
Page 2
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Main Corridor.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
THORLUX HI12563 Hi - Style Com - 2x55W / Luminaire Data Sheet
Luminous emittance 1:
80
120
160
cd/klm 44%C0 - C180 C90 - C270
0° 15° 30°
45°
60°
75°
90°
105°105°
90°
75°
60°
45°
30° 15° 0°
Luminaire classification according to CIE: 100CIE flux code: 42 77 96 100 44
Recessed direct/indirect luminaire with perforated metal basket
Luminous emittance 1:
Glare Evaluation According to UGR
Ceiling 70 70 50 50 30 70 70 50 50 30
Walls 50 30 50 30 30 50 30 50 30 30
Floor 20 20 20 20 20 20 20 20 20 20
Room SizeX Y
Viewing direction at right anglesto lamp axis
Viewing direction parallelto lamp axis
2H 2H 19.2 20.5 19.5 20.8 21.0 16.2 17.6 16.5 17.8 18.13H 20.8 22.0 21.1 22.3 22.6 17.7 19.0 18.1 19.3 19.64H 21.1 22.3 21.5 22.6 22.9 18.3 19.4 18.6 19.7 20.06H 21.3 22.4 21.7 22.8 23.1 18.6 19.7 18.9 20.0 20.38H 21.4 22.5 21.8 22.8 23.1 18.6 19.7 19.0 20.0 20.4
12H 21.5 22.5 21.9 22.8 23.2 18.7 19.7 19.1 20.0 20.4
4H 2H 19.6 20.8 20.0 21.1 21.4 17.5 18.7 17.8 19.0 19.33H 21.5 22.5 21.9 22.8 23.2 19.3 20.3 19.7 20.6 21.04H 21.9 22.8 22.3 23.2 23.5 19.9 20.8 20.3 21.2 21.66H 22.2 23.0 22.7 23.4 23.8 20.3 21.1 20.7 21.5 21.98H 22.4 23.1 22.8 23.5 23.9 20.4 21.1 20.8 21.5 21.9
12H 22.5 23.1 22.9 23.5 24.0 20.5 21.1 20.9 21.5 22.0
8H 4H 22.1 22.8 22.5 23.2 23.6 20.4 21.1 20.8 21.5 21.96H 22.5 23.1 23.0 23.6 24.0 20.8 21.4 21.3 21.8 22.38H 22.7 23.2 23.2 23.7 24.2 21.0 21.5 21.5 21.9 22.4
12H 22.9 23.3 23.4 23.8 24.3 21.1 21.5 21.6 22.0 22.5
12H 4H 22.1 22.7 22.5 23.1 23.6 20.4 21.0 20.8 21.4 21.96H 22.6 23.1 23.0 23.5 24.0 20.9 21.4 21.4 21.9 22.38H 22.8 23.2 23.3 23.7 24.2 21.1 21.5 21.6 22.0 22.5
Variation of the observer position for the luminaire distances S
S = 1.0H +0.1 / -0.1 +0.1 / -0.1S = 1.5H +0.2 / -0.2 +0.3 / -0.4S = 2.0H +0.6 / -0.8 +0.6 / -1.0
Standard table BK05 BK05
Correction Summand -5.2 -7.3
Corrected Glare Indices referring to 9600lm Total Luminous Flux
Page 3
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Main Corridor.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Luminaires (layout plan)
1
1
1
1
1
1
1
3.60 m0.00 1.80
17.00 m
0.00
1.20
3.60
6.00
8.40
10.80
13.20
15.60
Scale 1 : 115
Luminaire Parts List
No. Pieces Designation
1 7 THORLUX HI12563 Hi - Style Com - 2x55W
Page 4
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Main Corridor.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Isolines (E)
180
210
210210
240
240
240
240
240
240240
240
240
240
240270
270
270
270
270
270
270
270
270
270
3.60 m0.00
17.00 m
0.00
Values in Lux, Scale 1 : 133Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 31 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax241 160 283 0.663 0.566
Page 5
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Main Corridor.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Greyscale (E)
180
210
240
270
lx
3.60 m0.00
17.00 m
0.00
Scale 1 : 133Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 31 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax241 160 283 0.663 0.566
Page 6
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Main Corridor.dlx 08.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Value Chart (E)
178
219
237
252
252
257
255
257
256
256
255
251
248
231
210
169
198
244
261
276
275
282
278
279
278
279
279
274
272
254
235
184
177
219
237
251
252
256
254
256
256
255
254
251
248
231
210
168
3.60 m0.00
17.00 m
0.00
Values in Lux, Scale 1 : 133Not all calculated values could be displayed.
Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 31 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax241 160 283 0.663 0.566
Page 7
Ward Lighting.
We have proposed two alternatives using either recessed luminaires or surface
luminaires.
Your existing central ward lighting can be replaced by either 2 x Thorlux Jubilee surface
lighting luminaires or two recessed Thorlux Skydome luminaires. These luminaires will
provide general lighting of 100 lux average as recommended in Lighting Guide LG2 and
will comply with the glare requirements for recumbent patients.
Borders Hospital
6 Bed Ward Surface Luminaires
Partner for Contact: Ian GentlemanOrder No.: Company: Borders NHSCustomer No.:
Date: 10.02.2011Operator: Graham Lucas
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward Surface Luminaires.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Table of contents
Borders HospitalProject Cover 1Table of contents 2THORLUX JUB13066 Jubilee - 2x35W
Luminaire Data Sheet 3Room 1
Luminaires (layout plan) 4Room Surfaces
FloorIsolines (E) 5Greyscale (E) 6Value Chart (E) 7
Page 2
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward Surface Luminaires.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
THORLUX JUB13066 Jubilee - 2x35W / Luminaire Data Sheet
Luminous emittance 1:
80
120
160
200
240
cd/klm 82%C0 - C180 C90 - C270
0° 15° 30° 45°
60°
75°
90°
105°
120°
135°150°165°180°165°150°135°
120°
105°
90°
75°
60°
45° 30° 15° 0°
Luminaire classification according to CIE: 90CIE flux code: 42 72 90 90 82
Surface mounted diffuser luminaire
Luminous emittance 1:
Glare Evaluation According to UGR
Ceiling 70 70 50 50 30 70 70 50 50 30
Walls 50 30 50 30 30 50 30 50 30 30
Floor 20 20 20 20 20 20 20 20 20 20
Room SizeX Y
Viewing direction at right anglesto lamp axis
Viewing direction parallelto lamp axis
2H 2H 18.0 19.3 18.5 19.7 20.2 16.4 17.6 16.8 18.1 18.53H 20.5 21.7 21.0 22.1 22.6 18.1 19.2 18.5 19.7 20.14H 21.8 22.9 22.3 23.3 23.8 18.7 19.8 19.2 20.2 20.76H 23.1 24.2 23.6 24.6 25.2 19.1 20.1 19.6 20.6 21.18H 23.9 24.9 24.4 25.3 25.9 19.2 20.2 19.7 20.7 21.2
12H 24.7 25.7 25.2 26.2 26.7 19.3 20.2 19.8 20.7 21.3
4H 2H 18.5 19.6 19.0 20.1 20.6 17.3 18.4 17.7 18.8 19.33H 21.3 22.2 21.8 22.7 23.2 19.2 20.1 19.7 20.6 21.24H 22.7 23.6 23.3 24.1 24.7 20.0 20.8 20.5 21.3 21.96H 24.3 25.1 24.9 25.6 26.2 20.5 21.3 21.1 21.8 22.48H 25.2 25.9 25.8 26.5 27.1 20.7 21.4 21.3 22.0 22.6
12H 26.2 26.9 26.8 27.4 28.1 20.8 21.5 21.4 22.1 22.7
8H 4H 23.0 23.7 23.6 24.3 24.9 20.7 21.4 21.3 22.0 22.66H 24.9 25.5 25.5 26.1 26.7 21.6 22.1 22.2 22.7 23.48H 26.0 26.5 26.6 27.1 27.8 21.9 22.4 22.5 23.0 23.7
12H 27.3 27.7 27.9 28.3 29.0 22.1 22.6 22.8 23.2 23.9
12H 4H 23.0 23.7 23.6 24.2 24.9 21.0 21.6 21.6 22.2 22.86H 25.0 25.5 25.6 26.1 26.8 22.0 22.5 22.6 23.1 23.88H 26.2 26.6 26.8 27.2 27.9 22.4 22.9 23.1 23.5 24.2
Variation of the observer position for the luminaire distances S
S = 1.0H +0.1 / -0.1 +0.1 / -0.1S = 1.5H +0.3 / -0.3 +0.2 / -0.3S = 2.0H +0.4 / -0.5 +0.3 / -0.6
Standard table BK12 BK14
Correction Summand 3.7 -1.6
Corrected Glare Indices referring to 6600lm Total Luminous Flux
Page 3
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward Surface Luminaires.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Luminaires (layout plan)
1
1
6.50 m0.00 3.25
8.60 m
0.00
2.15
6.45
Scale 1 : 59
Luminaire Parts List
No. Pieces Designation
1 2 THORLUX JUB13066 Jubilee - 2x35W
Page 4
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward Surface Luminaires.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Isolines (E)
60
90
90
90
90
90
90
90
90
120
120120
120
120
120
120
120120
120
120
120
150
150150
150
150
150150
150
150
180 180
180 180
6.50 m0.00
8.60 m
0.00
Values in Lux, Scale 1 : 68Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 13 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax116 59 191 0.509 0.309
Page 5
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward Surface Luminaires.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Greyscale (E)
60
90
120
150
180
lx
6.50 m0.00
8.60 m
0.00
Scale 1 : 68Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 13 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax116 59 191 0.509 0.309
Page 6
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward Surface Luminaires.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Value Chart (E)
59 67 80 98 112 124 129 124 112 98 81 68 59
71 85 105 133 160 183 191 183 161 134 106 85 71
76 89 107 134 157 176 183 176 157 134 108 89 77
75 86 99 119 134 145 149 145 134 119 99 86 75
76 89 107 133 157 176 183 176 157 134 107 89 76
71 85 105 133 160 182 190 182 160 133 105 85 71
59 67 80 98 112 124 129 124 112 98 80 67 59
6.50 m0.00
8.60 m
0.00
Values in Lux, Scale 1 : 68
Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 13 x 7 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax116 59 191 0.509 0.309
Page 7
Borders Hospital
6 Bed Ward Recessed Option
Partner for Contact: Ian GentlemanOrder No.: Company: Borders NHSCustomer No.:
Date: 11.02.2011Operator: Graham Lucas
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Table of contents
Borders HospitalProject Cover 1Table of contents 2THORLUX SD12893 Skydome - 4x24W
Luminaire Data Sheet 3Room 1
Luminaires (layout plan) 4Room Surfaces
FloorIsolines (E) 5Greyscale (E) 6Value Chart (E) 7
Page 2
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
THORLUX SD12893 Skydome - 4x24W / Luminaire Data Sheet
Luminous emittance 1:
80
120
160
200
240
cd/klm 63%C0 - C180 C90 - C270
0° 15° 30°
45°
60°
75°
90°
105°105°
90°
75°
60°
45°
30° 15° 0°
Luminaire classification according to CIE: 98CIE flux code: 45 76 92 98 63
Recessed luminaire with domed polycarbonate cover
Luminous emittance 1:
Glare Evaluation According to UGR
Ceiling 70 70 50 50 30 70 70 50 50 30
Walls 50 30 50 30 30 50 30 50 30 30
Floor 20 20 20 20 20 20 20 20 20 20
Room SizeX Y
Viewing direction at right anglesto lamp axis
Viewing direction parallelto lamp axis
2H 2H 16.6 18.0 17.0 18.2 18.5 16.2 17.5 16.5 17.8 18.13H 18.6 19.8 18.9 20.1 20.4 18.1 19.3 18.5 19.6 19.94H 19.4 20.6 19.8 20.9 21.2 18.9 20.1 19.3 20.4 20.76H 20.3 21.3 20.7 21.7 22.0 19.7 20.8 20.1 21.1 21.58H 20.7 21.7 21.1 22.1 22.4 20.1 21.2 20.5 21.5 21.9
12H 21.1 22.1 21.5 22.5 22.8 20.5 21.5 20.9 21.9 22.3
4H 2H 17.2 18.3 17.5 18.6 19.0 16.8 18.0 17.2 18.3 18.63H 19.4 20.4 19.8 20.7 21.1 19.0 20.0 19.4 20.3 20.74H 20.4 21.3 20.9 21.7 22.1 20.0 20.9 20.4 21.3 21.76H 21.5 22.2 21.9 22.6 23.1 21.0 21.8 21.4 22.2 22.68H 22.0 22.7 22.4 23.1 23.6 21.5 22.2 21.9 22.6 23.1
12H 22.5 23.2 23.0 23.6 24.1 22.0 22.6 22.5 23.1 23.6
8H 4H 20.8 21.5 21.3 22.0 22.4 20.5 21.2 20.9 21.6 22.16H 22.1 22.7 22.6 23.2 23.7 21.7 22.3 22.2 22.8 23.38H 22.8 23.3 23.3 23.8 24.3 22.3 22.9 22.9 23.4 23.9
12H 23.5 24.0 24.0 24.5 25.0 23.0 23.5 23.6 24.0 24.6
12H 4H 20.9 21.5 21.4 22.0 22.5 20.6 21.2 21.0 21.7 22.16H 22.3 22.8 22.8 23.3 23.8 21.9 22.4 22.4 22.9 23.48H 23.0 23.5 23.5 24.0 24.5 22.6 23.1 23.1 23.6 24.1
Variation of the observer position for the luminaire distances S
S = 1.0H +0.1 / -0.1 +0.1 / -0.1S = 1.5H +0.2 / -0.3 +0.2 / -0.3S = 2.0H +0.3 / -0.5 +0.3 / -0.6
Standard table BK08 BK08
Correction Summand -2.3 -2.7
Corrected Glare Indices referring to 7000lm Total Luminous Flux
Page 3
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Luminaires (layout plan)
1
1
6.50 m0.00 3.25
8.60 m
0.00
2.15
6.45
Scale 1 : 59
Luminaire Parts List
No. Pieces Designation
1 2 THORLUX SD12893 Skydome - 4x24W
Page 4
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Isolines (E)
60
60
60
60
6060
60
60
90
90 90
90
90
90
90
90
90
90
90
120
120120
120
120
120
120
120120
120
120
120
150
150
150
150
150
150
150
150
150
150
6.50 m0.00
8.60 m
0.00
Values in Lux, Scale 1 : 68Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 9 x 11 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax100 45 189 0.452 0.239
Page 5
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Greyscale (E)
60
90
120
150
lx
6.50 m0.00
8.60 m
0.00
Scale 1 : 68Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 9 x 11 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax100 45 189 0.452 0.239
Page 6
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital 6 Bed Ward.dlx 11.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Room 1 / Floor / Value Chart (E)
45 58 77 93 102 93 77 58 45
54 72 102 132 148 132 102 73 54
60 84 123 166 189 166 123 84 60
62 85 122 161 182 161 122 85 62
60 80 107 133 147 134 107 80 60
59 76 100 122 132 122 100 76 59
60 80 107 133 147 133 107 80 60
62 85 122 161 182 161 122 85 62
60 84 122 166 188 166 122 84 60
54 72 102 133 149 133 102 72 54
45 57 77 93 101 93 77 57 45
6.50 m0.00
8.60 m
0.00
Values in Lux, Scale 1 : 68
Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 9 x 11 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax100 45 189 0.452 0.239
Page 7
Standard Range
NOMINAL LENGTH APPROX
SIZE (mm) LAMP CAT. No. (mm) kg CIRCUIT
600 2 x 14WT5 JUB 13612 595 3.0 D-J
12001 x 28WT5 JUB 13061 1195 4.0 D-J
2 x 28WT5 JUB 13062 4.1 D-J
15001 x 35WT5 JUB 13065 1495 5.0 D-J
2 x 35WT5 JUB 13066 5.1 D-J
15001 x 49WT5 JUB 13067 1495 5.0 D-J
2 x 49WT5 JUB 13068 5.1 D-J
Smart Range
600 2 x 14WT5 JUB 13616 645 3.0 D
12001 x 28WT5 JUB 13077 1245 4.0 D
2 x 28WT5 JUB 13078 4.1 D
15001 x 35WT5 JUB 13079 1545 5.0 D
2 x 35WT5 JUB 13080 5.1 D
15001 x 49WT5 JUB 13081 1545 5.0 D
2 x 49WT5 JUB 13082 5.1 D
CIRCUIT - add suffix required:D - high frequency regulating J - high frequency e.g. JUB 13061D etc.
EMERGENCYVERSION - prefix catalogue number with ‘EJB’.AUTOTEST VERSION - prefix catalogue number with ‘TJB’.Emergency and AutoTest versions add 0.7kg to weights listed.
LAMPSMUST BE ORDERED SEPARATELY
� Shallow profile with co-extruded ‘Satin-Glo’polycarbonate controller
� Steel body finished full polyester powdercoated white
� Smart versions with intelligent lighting control
Jubilee with Smart Micro-Pod
JubileeT5 surface mounted shallow profile controller luminaires
Dimensions and Photometric data - see page 7
Oct. ‘08 3
� ‘Satin-Glo’polycarbonate side controllers providehigh angle illuminance
� Vibrant appearance louvre made from highreflectivity Miro aluminium
� Finger print resistant coating on louvre
� Excellent optical LG7:2005 design
� High light output ratio - up to 94%
� Steel body finished full polyester powder coated white
� Smart versions with intelligent lighting control
Standard Range
NOMINAL LENGTH APPROX.
SIZE (mm) LAMP CAT. No. (mm) kg CIRCUIT
12001 x 28WT5 JUB 13069 1195 4.4 D-J
2 x 28WT5 JUB 13070 4.5 D-J
15001 x 35WT5 JUB 13073 1495 5.4 D-J
2 x 35WT5 JUB 13074 5.5 D-J
15001 x 49WT5 JUB 13075 1495 5.4 D-J
2 x 49WT5 JUB 13076 � 5.5 D-J
Smart Range
12001 x 28WT5 JUB 13083 1195 4.4 D
2 x 28WT5 JUB 13084 4.5 D
15001 x 35WT5 JUB 13085 1495 5.4 D
2 x 35WT5 JUB 13086 5.5 D
15001 x 49WT5 JUB 13087 1495 5.4 D
2 x 49WT5 JUB 13088 � 5.5 D
CIRCUIT - add suffix required:D - high frequency regulating J - high frequency e.g. JUB 13069D etc.
EMERGENCYVERSION - prefix catalogue number with ‘EJB’.AUTOTEST VERSION - prefix catalogue number with ‘TJB’.Emergency and AutoTest versions add 0.7kg to weights listed.
� 2 x 49W - Greater than 1500, less than 2000cd/m2 at 65°
LAMPSMUST BE ORDERED SEPARATELY
Smart Micro-pod in Jubilee-XL louvre
Jubilee-XLT5 surface mounted controller/louvre luminaires
Dimensions and Photometric data - see page 7
Oct. ‘08 5
Jubilee and Jubilee-XLPhotometric guide and dimensions
Nov. ‘08 7
Smart Micro-pod(Jubilee version only)
600 CRS.
2 x BESA box slots
28W - 982 CRS.
2 x slots 5.5 x 10.5
50
1200 VERSION(Jubilee and Jubilee-XL versions)
600 VERSION(Jubilee version only)
Smart Micro-pod
14W -382 CRS.
2 x slots 5.5 x 10.5
50
21 dia. hole
193
22
Smart Micro-pod(Jubilee version only)
1200 CRS.
2 x BESA box slots
35 & 49W - 1282 CRS.
2 x slots 5.5 x 10.5
50
1500 VERSION(Jubilee and Jubilee-XL versions)
21 dia. hole
300
Single or twin lamp
200
78
JUBILEE-XLJUBILEE
Knockoutseach end forM20 conduit
100
200
Single or twin lamp
CANDELAS PER 1000 LUMENS
TRANSVERSE AXIAL
FACTORS: 2 x 14W = 1.08
2 x 35W = 1.10
2 x 49W = 0.98
2 x 28WD.L.O.R. 66% U.L.O.R. 9%
CANDELAS PER 1000 LUMENS
TRANSVERSE AXIAL
Jubilee Photometric Guide
1 x 28WD.L.O.R. 77% U.L.O.R. 11%
FACTORS: 1 x 35W = 0.91
1 x 49W = 0.86
FACTORS: 1 x 35W = 0.91
1 x 49W = 0.87
CANDELAS PER 1000 LUMENS
TRANSVERSE AXIAL
Jubilee-XL Photometric Guide
XL 1 x 28WD.L.O.R. 91% U.L.O.R. 3%
FACTORS: 2 x 35W = 1.10
2 x 49W = 1.04
CANDELAS PER 1000 LUMENS
TRANSVERSE AXIAL
XL 2 x 28WD.L.O.R. 74% U.L.O.R. 3%
Dimensions and Fixings
Ward Washing Area.
We suggest the use of Designplan Quadrant LED luminaires with white body colour.
These luminaires can be fitted with an Ex-Or battenfix sensor which can be fitted via the
end knockout. The current version of battenfix is IP4X however an IP65 version will be available in September 2011 so the luminaires could be installed now with the sensors
installed at a later date if the IP4X versions are thought to be unsuitable.
Quadrant LEDIP65 / IK16
Quadrant LED is a vandal & weather resistant fitting for ceiling or wall mounting.Zinc coated steel body finished in chemical & abrasion resistant textured blackpolyester powder coat. Body has provision for entry in back & at ends, gasketsprovided.Injection moulded clear polycarbonate diffuser held against polythene gasket bysocket cap stainless steel screws.9, 16 or 25 x 1w LED arrays on removable gear tray, LED driver is integral.
DQ9X1MV2PB 9x1w Natural White 4000k 2.50kg
DQ16X1MV2PB 16x1w Natural White 4000k 2.50kg
DQ25X1MV2PB 25x1w Natural white 4000k 2.50kg
Options/NotesOpal diffuser delete P and add suffix XSelf-contained LED emergency facility add suffix EMLEDSemi-recessed version available add suffix SRFor white finish delete B and add suffix WBlank end to body add suffix 585For duel swithcing add suffix SC
Designplan Lighting Ltd - 6 Wealdstone Road - Kimpton Industrial Estate - Sutton - Surrey - United Kingdom - SM3 9RWTel: 020 8254 2000 - Fax: 020 8644 4253 - Sales Hotline: 020 8254 2020 - Email: [email protected] - Web: www.designplan.co.uk
W4466A
Installation and Commissioning
Instructions
Note: HP2000 or HP10 required for commissioning
BattenFit Sensor
MSB1000T - Switching
MSB1000PT - Switching with photocell
Ex-Or Novar ED&S Limited
Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: +44 (0)1942 719229
Fax: +44 (0)1942 272767
Email: [email protected]
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre.Do not dispose of with normal household waste.Do not burn.
Important Additional Notes
1. A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
2. Due to the fact that the photocell (MSB1000PT) is on the ceiling looking down, it is not possible for measurements made
with a lux meter on the working plane to remain constant when daylight illuminates the ceiling and the working plane to a
differing extent. Therefore, products of this type should be regarded as capable of maintaining an APPROXIMATE light
level only.
3. This equipment switches lights no more frequently than would a responsible human occupant. However, manufacturers of
some particular lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles in order to achieve
a predicted lamp life. Please check with the manufacturer of the luminaires to ensure that they are compatible with
automatic controls in this respect.
Dimensions
Technical Data
OPERATING VOLTAGE: 230V~ 50Hz (UK & Europe)
POWER CONSUMPTION: <0.5W
CAPACITY: 2A Switching
MAXIMUM NUMBER OF BALLASTS: 4 (Electronic or HF Ballasts)
WEIGHT: 100g
COLOUR: White
MATERIAL: Flame retardant PC/ABS
IP RATING: 4X - estimated
107
600mm
40Fig.11
Fig. 12
14
M2
0 x
1.5
14
29
20mm Female AdaptorRS 600-408 orFARNELL 4319047
If there is insufficient space for the locknut, the adaptor shown below (Fig. 3) can be used.
Fig. 3
Fig. 1
Fig. 2
BattenFit Sensor: MSB1000T - Switching
MSB1000PT - Switching with photocell
Only suitably qualified personnel should install this equipment.
This passive infrared presence detector is designed to be fitted to a batten-style luminaire.
Installation
1. Remove the M20 knockout from the end cap of the luminaire.
2. Pass the sensor wires through from the outside and insert the threaded end of the sensor into the hole.
3. A polarising plate can be made in order to prevent rotation of the sensor - an example design is given below (Fig. 4).
4. If a polarising plate is to be used, pass the wires through the slot and position it against the inside face of the end cap. Ensure that the tab is positioned correctly i.e. at the ceiling side, away from the lamp.
5. Fit and tighten the locknut.
6. Connect the wires in accordance with the wiring instructions.
Polarising Plate (not supplied)
The purpose of the polarising plate is to ensure that the sensor does not rotate from the correct position, i.e. pointing vertically downwards, during transport or installation.
The two overall dimensions marked ‘SEE TEXT’ need to be made such that when the plate is positioned against the inner face of the luminaire end cap, it cannot rotate.
The 3.5mm ‘tab’ should be located closest to the ceiling (away from the lamp). The 6.0mm slot is optional and is to allow the wires to pass through for ease of assembly.
Material can be plastic sheet, minimum thicknesss 1.0mm, recommended thickness 1.5-2.0mm, or mild/stainless steel sheet, minimum thickness 0.6mm, recommended thickness 1.0-1.6mm.
SE
E T
EX
T
SEE TEXT
7.3
6.0
203.5
HP10 Parameter Options (MSB1000PT only except Walk Test)
PHOTOCELLENABLED
MOVEMENT DETECTORAUTOMATICOPERATION
MOVEMENTDETECTOR
SEMI-AUTOMATICOPERATION
NOTUSED
POWER UPON
POWERUPOFF
PHOTOCELLDISABLED
5 min
ON
OFF
10 min
20 min
OFF DELAYAdd together to give required time.
All OFF = 10 secs (Walk Test)
PHOTOCELL MODE
= ACTIVE
NOT USED
24 Hr Cycle
No 24 Hr CyclePHOTOCELL
MODE = PASSIVE
NOTUSED
Off Delay
The Off Delay may be set between 5 and 35 minutes (MSB1000PT only). A 10-second Off Delay is available for walk-testing the product. In a typical office environment a 20-minute Off Delay is usually satisfactory.
Movement Detector Operation (Automatic/Semi-Automatic)
Where absence detection is required (ie the user manually turns lights ON if required but lights still turn off automatically once an area is vacated), semi-automatic operation can be set via the programmer.
Power Up Setting (On/Off)
Set to ON the detector will automatically switch its outputs on when Mains is applied. If set to OFF, the detector will power up without turning its outputs on, wait for 30 seconds and THEN look for movement. Only if the area is occupied will the output switch on at this time. The detector must be set to Power Up ON when used in conjunction with semi-automatic operation.
Photocell Operation (Passive/Active/Disabled)
The MSB1000PT has an in-built photocell. The photocell has three modes of operation - Passive, Active and Disabled. Its operational behaviour is governed by the setting chosen and by the values stored in the Upper and Lower thresholds (see diagram overleaf).
Passive - The photocell will inhibit turn-on of the controlled load if sufficient natural light is available. It will not turn the load off whilst an area is occupied
Active - The photocell will turn the controlled load on and off as required whilst natural light levels fluctuate during a period of occupancy. This mode of operation operates in conjunction with a passing cloud timer (PCT). The PCT is asymmetrical in operation - the load will be switched on immediately that the light level falls below the lower set point, however, the load switches off only if the light level exceeds the upper threshold continuously for a period equal to the Off Delay.
Disabled - The photocell has no effect.
24hr Cycle (Yes/No)
Not applicable.
Defaults (where applicable)
The units are supplied with factory default settings (Power-Up On, fully Automatic operation, a 20 minute Off Delay, no 24hr Cycle, Passive Photocell). Programme using the MLS Digital Programmer with LCD display (HP2000), or the LightSpot Programmer (HP10) incorporating 12 dil switches.
Please note that additional parameters are available
via the HP2000
21 3 4 5 6 7 8 9 10 11 12
Fig. 4
- 2 - - 7 -
W4466A
Electrical Connections
LOAD
BlueBrownBlack
BlueBrownBlack
Multiple Detectors may be connected in parallel, as is shown above, to control the same Maximum Load
L N E
SUPPLY
Maximum Total Load not to exceedthat specified for a Single Detector
LOAD LOAD
L N E
Fig. 6
W4466A
Photocell
The photocell (MSB1000PT only) can be programmed to operate in one of two ways: Active or Passive.
(Factory default setting is ‘Passive’.)
In all operating modes, the photocell can hold lights off as a vacant area becomes occupied, and if the light
level falls too low during the period of occupancy, the lights switch on. In ‘Passive Mode’ the lights do not
switch off whilst the area is occupied no matter how much light is measured. In ‘Active Mode’ the photocell is
able to switch the lights off whilst the area is occupied.
Setting the Photocell
1. If the lights are not already on, switch them on manually by pressing ‘Utilities/User Remote/Luminaire+/OK’
[HP2000], or ‘Up’ [HP10]. Fluorescent lights do not reach full output until up to 15 minutes after being
switched on, so ensure that the lights are fully warmed up before continuing. This stage may be omitted if
the intention is to operate the detector’s photocell in Passive Mode only [the detector must have already
been programmed to Passive Mode].
2. Wait until the time of day when the natural light level is at the point below which you would want the lights to
be on, and above which you would not want the lights to be on.
3. Start the internal self-programming mechanism by pressing ‘Utilities/Set Light Level/OK’ [HP2000], or
‘Store’ [HP10]. The detector takes a measurement, adds a small amount and stores the value in the Upper
Threshold. Then it turns the lights off, makes another measurement and stores the value in the Lower
Threshold. The lights now switch on again to acknowledge a successful programming operation.
The two switching thresholds have now been set, and the difference between them is equal to the contribution
made by the electric lighting; this is the perfect amount of hysteresis to ensure that the lights will not oscillate.
The thresholds may be read back and fine-tuned if necessary using the HP2000. Please note that the values
are non-specific units i.e. not lux.
Note: The light level perceived by the detector at the moment immediately prior to a Download operation
[HP2000 only] is shown momentarily on the HP2000 screen following the Download; this is a useful mechanism
for troubleshooting.
Lights ON = Lights OFF =
Upper Threshold
Lower Threshold
NaturalLight Level
Duration of Off Delay
Note that when the natural light level exceeds the ‘upper threshold’ value, the lights do not immediately turn off. They will turn off only when the upper threshold has been exceeded for the duration of the programmed Off Delay.
Active ModePassive Mode
Occupancy Area Occupied = Area Unoccupied =
L N E L N E
Always check product label before connecting.
Black
Blue
Brown - Live
- Neutral
- Switched live
Fig. 5
- 6 - - 3 -
Fig. 10
Walk Testing
In order to verify the installation, there is an inbuilt facility (Walk Test Mode) to temporarily reduce the time delay to 10 seconds. An HP2000 or HP10 Programmer is required to access this facility.
Using the HP10:
Use the DIL switches to enable walk test mode.
Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before moving and triggering the lights back on.
Re-programme the desired Off Delay once testing is complete (MSB1000PT only).
Using the HP2000:
Go to the Utilities menu, place the cursor over ‘Walk Test’, point the programmer at the detector and press OK.
Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before moving and triggering the lights back on.
After 5 minutes, the time-out will be restored to what it was before walk test was enabled.
Notes on Walk Testing:
l During walk test, after the lights have turned off, wait 5 seconds before moving again because the sensitivity is deliberately reduced for a few seconds following switch off.
l Sensitivity is greater when approaching the circular footprint at a tangent rather than heading towards the centre (see Fig. 7).
l Most luminaires take approximately 1 second to strike after presence has been detected.
l The detection pattern is cone-shaped which means that when standing at the very edge of the detection footprint only a person’s feet will be visible (see Fig. 8).
Detection Profile
Plan ViewoDetection pattern is a 360 cone shape.
Diameter is 2.25 x the mounting height.
Fig. 7
Direction of most commonly used entry into detection zone, i.e. start of corridor or doorway
Fig. 8
5m
5m
2.5
m
o97
2.5m
DETECTION ZONE
- 4 - - 5 -
W4466A
5.6m
BATTEN LUMINAIRE
DETECTION ZONE
59
MA
X
If the distance between the bottom of the sensor and the bottom of the end cap exceeds 59mm, there may be a blind spot in the detection zone. If this arises, there are extended sensors available.
Fig. 9
Main Entrance Canopy.
We suggest that the existing lighting could be replaced by LED luminaires and we have
proposed Ghidini 56 LED floodlights to replace the existing SON floodlights and
Designplan Pantheon 32w LED wall mounted luminaires. You can of course use the Stealth LED luminaires that you currently use however we feel that the Pantheon is a
more aesthetic luminaire that will look nicer in the entrance area.
We have simulated the canopy lighting using DIALux lighting design program and replacing the existing luminaires with LED types will provide an average illuminance of 30
lux.
Borders Hospital
Entrance Canopy
Partner for Contact: Ian GentlemanOrder No.: Company: Borders NHSCustomer No.:
Date: 10.02.2011Operator: Graham Lucas
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Canopy.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Table of contents
Borders HospitalProject Cover 1Table of contents 2Ghidini Illuminazione srl 102T Maximaestro
Luminaire Data Sheet 3Designplan Lighting D277/1X32LEDV2C04 Pantheon LED
Luminaire Data Sheet 4Exterior Scene 1
Luminaires (coordinates list) 53D Rendering 7Exterior Surfaces
Ground Element 1Surface 1
Isolines (E) 8Greyscale (E) 9Value Chart (E) 10
Page 2
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Canopy.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Ghidini Illuminazione srl 102T Maximaestro / Luminaire Data Sheet
See our luminaire catalog for an image of the luminaire.
Luminous emittance 1:
400
600
800
cd/klm 100%C0 - C180 C90 - C270
0° 15° 30°
45°
60°
75°
90°
105°105°
90°
75°
60°
45°
30° 15° 0°
Luminaire classification according to CIE: 100CIE flux code: 56 90 99 100 100
Due to missing symmetry properties, no UGR table can be displayed for this luminaire.
Page 3
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Canopy.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Designplan Lighting D277/1X32LEDV2C04 Pantheon LED / Luminaire Data Sheet
See our luminaire catalog for an image of the luminaire.
Luminous emittance 1:
100
150
200
250
cd/klm 48%C0 - C180 C90 - C270
0° 15° 30° 45°
60°
75°
90°
105°
120°
135°150°165°180°165°150°135°
120°
105°
90°
75°
60°
45° 30° 15° 0°
Luminaire classification according to CIE: 81CIE flux code: 28 61 86 81 47
Due to missing symmetry properties, no UGR table can be displayed for this luminaire.
Page 4
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Canopy.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Exterior Scene 1 / Luminaires (coordinates list)
Designplan Lighting D277/1X32LEDV2C04 Pantheon LED2000 lm, 32.0 W, 1 x 1 x LED (Correction Factor 1.000).
1 2 3 4 5 6
No. Position [m] Rotation [°]X Y Z X Y Z
1 2.000 0.150 3.600 0.0 0.0 90.02 6.000 0.150 3.600 0.0 0.0 90.03 10.000 0.150 3.600 0.0 0.0 90.04 14.000 0.150 3.600 0.0 0.0 90.05 18.000 0.150 3.600 0.0 0.0 90.06 22.000 0.150 3.600 0.0 0.0 90.0
Page 5
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Canopy.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Exterior Scene 1 / Luminaires (coordinates list)
Ghidini Illuminazione srl 102T Maximaestro3581 lm, 65.3 W, 1 x 1 x 56 LED Cluster (Correction Factor 1.000).
1 2 3 4 5
No. Position [m] Rotation [°]X Y Z X Y Z
1 4.000 0.150 3.600 50.0 180.0 -180.02 8.000 0.150 3.600 50.0 -180.0 180.03 12.000 0.150 3.600 50.0 -180.0 180.04 16.000 0.150 3.600 50.0 -180.0 180.05 20.000 0.150 3.600 50.0 -180.0 180.0
Page 6
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Canopy.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Exterior Scene 1 / 3D Rendering
Page 7
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Canopy.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Exterior Scene 1 / Ground Element 1 / Surface 1 / Isolines (E)
20
20
2020
20
3030
30
30303030
4040 40 40
40
404040
24.00 m0.00
6.00 m
0.00
Values in Lux, Scale 1 : 172Position of surface in external scene:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 11 x 5 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax30 11 52 0.376 0.216
Page 8
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Canopy.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Exterior Scene 1 / Ground Element 1 / Surface 1 / Greyscale (E)
20 30 40 lx
24.00 m0.00
6.00 m
0.00
Scale 1 : 172Position of surface in external scene:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 11 x 5 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax30 11 52 0.376 0.216
Page 9
Borders HospitalC:\Documents and Settings\grahamlucas\Projects\Borders Hospital Lighting 1254\Borders Hospital Canopy.dlx 10.02.2011
Marwood Electrical Company LimitedMaidstone RoadPaddock Wood, TonbridgeKent. TN12 6DR
Operator Graham LucasTelephone 07717 835035
Fax 0151 424 2928e-Mail [email protected]
Exterior Scene 1 / Ground Element 1 / Surface 1 / Value Chart (E)
22 35 40 42 43 42 42 43 39 36 22
25 35 46 43 52 43 52 43 47 37 25
19 27 31 34 34 35 34 34 31 28 19
15 22 26 29 29 30 29 29 26 23 15
11 17 20 22 23 23 22 22 19 17 11
24.00 m0.00
6.00 m
0.00
Values in Lux, Scale 1 : 172
Position of surface in external scene:Marked point:(0.000 m, 0.000 m, 0.000 m)
Grid: 11 x 5 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax30 11 52 0.376 0.216
Page 10
Maximaestro 5480.102.T.--
The Maestro series consists of EN AB 47100 die-cast aluminum, oxidation-resistant floodlights. Maximaestro is suitable for illuminating large areasranging from parking lots to parks, streets and bike paths. This type of device is available in a wide-ranging selection, including 70W, 150W and 250Wmetal halide, 300W halogen and 140W cosmowhite/cosmogold lamps. Combined with optics that are asymmetrical lengthways and transversely, itguarantees compliance with light pollution regulations.
Lamping 56W 56 Led Cut Off Diffuser type clearBase 56 Led 4000K Neutral white Lm/Cd 3600 lmInsulation class II Reflector orientability -Volt 220/240 Fixture adjustabilityHz 50/60 Cable entry Cable glandBallast/Transformer included Second cable entry -IP 65 Rough-in housing -IK 06 Distance -
Diffuser tech info Sodium calcium tempered glassVolume 0.000 m3
Diffuser temperatureWeight 7.7 Kg
Max static load preassure -Certifications
FINISHwhite
anthracite grey
RAL9006 grey
rust brown
Maximaestro 5480.102.T.--
Photometries
Accessories
SA1 wall bracket
SA2 column support Ø 76mm
SA3 column support Ø 89mm
SA4 column support Ø 76mm + column backet 500mm
SA5 column support Ø 89mm + column backet 500mm
SA6 column double support Ø 76mm
SA7 column double support Ø 89mm
SA8 column double support Ø 76mm + double bracket 500mm
SA9 column double support Ø 89mm + double bracket 500mm
Pantheon LEDIP65 / IK16
Pantheon with LEDs ensure a low maintenance, low energy solution to amenitylighting. Vandal and weather resistant for wall mounting. Die cast aluminiumback plate finished in matt black powder coat. Provision of conduit entry in back,gaskets provided.Aluminium reflector to increase forward light.Injection moulded frosted polycarbonate control lens held against silicone rubbergasket by hinged over centre catch.
D277/1X32LEDV2C04 32W (2000 lumens) Natural White 5.00kg
D277/1X18LEDV2C04 18W (1100 lumens) Natural White 5.00kg
Options/NotesFor white finish delete C04 and add suffix C31For silver finish delete C04 and add suffix C29For the addition of a photo electrical cell add suffix 479
Designplan Lighting Ltd - 6 Wealdstone Road - Kimpton Industrial Estate - Sutton - Surrey - United Kingdom - SM3 9RWTel: 020 8254 2000 - Fax: 020 8644 4253 - Sales Hotline: 020 8254 2020 - Email: [email protected] - Web: www.designplan.co.uk
Summary.
The luminaires we have proposed are modern energy efficient luminaires with electronic
control gear that utilise modern energy saving lamps and optics. These luminaires will be
more efficient than many of your existing luminaires and as such will save you money on
your electricity bill and produce savings in CO2 emissions.
Our quotation shows unit prices as you will need to decide on the quantities and types of
luminaire you use.
We trust this is of assistance to you please contact the writer Graham Lucas (M:07717
835035) or our Lighting Sales Engineer Ray Clarkson (M:07799 797760) should you wish
to discuss any aspect of this project.