Upload
vzssz
View
75
Download
0
Tags:
Embed Size (px)
DESCRIPTION
Presentation by NHP and NECA for the introduction of the 2014 Victorian Service and Installation Rules (SIR)
Citation preview
17/04/2014
1
1
VictorianService and Installation Rules
2014
22
Tonight we will cover:
the variations between the 2005 and the 2014 versions of the Service and Installation Rules.
go over certain selected areas within the new SIRs
remove confusion and Highlight areas where major non-compliance often occurs.
Service and Installation Rules NECAJanuary - February - March 2014
Welcome
33
Where do the Service and Installation Rules (SIR) fit in?
Under the Sale and Distribution Code, Known as the Distributors reasonable technical requirements.
Traditionally cover off supply connection methods, metering and supply arrangements.
Service and Installation Rules NECAJanuary - February - March 2014
SIR Fit
44
Service and Installation Rules NECAJanuary - February - March 2014
Compliance
Do I need to comply with the SIRs are they mandatory?
Yes you shall comply;
If you do not comply then FIP (fuse in pocket) usually applies. No Supply.
For safe connection and metering of electrical installations you are required to comply with the Sale and Distribution Code.
Remember any delays will effect your customer.
55
Service and Installation Rules NECAJanuary - February - March 2014
Application
The Victorian Service & Installation Rules apply to all connections to the electricity supply networks operated by Electricity Distributors: CitiPower, Jemena Electricity Network, Powercor Australia Ltd, SP AusNet and United Energy.
The objective of these Rules is to: provide Victorian electricity customers with industry agreed reasonable
technical requirements that; meet all legislative and Electricity Distribution Code requirements
for the supply and metering related aspects of any connection to the Victorian Distributors electricity supply networks.
66
Service and Installation Rules NECAJanuary - February - March 2014
Public Notice - Availability of the 2014 Service and Installation RulesThe 2014 SIR are applicable from 1st January 2014 with a three month period of transition allowing the trade to adopt and employ the changes in the new document. There may be exceptional circumstances, if a connection post 31st March 2014 exists where a REC wishes to have the 2005 rules applied an SIR exemptions must be submitted by a written request detailing the reasons why non-compliance with the 2014 Rules is sought.
An exception to the 2005 Rules will not be automatically granted, electrical work associated with the exception should be discontinued until approval from the Distributor is received.
17/04/2014
2
77
Service and Installation Rules NECAJanuary - February - March 2014
Service and Installation Rules Committee.
Members of the SIR rewrite Committee are; The five Distributions Companies.
Each permitted two representatives. Institute of Electrical Inspectors Australia.
Mark Aitken Energy Safe Victoria.
Simon OLeary National Electrical and Communications Association (NECA)
Victoria. Brian Cross (Twin Electrics) Roy Sands NECA Victoria.
88
Service and Installation Rules NECAJanuary - February - March 2014
Changes General - Major
Metering
The arrival of Smart Meters has altered;
the numbers of meters on a panel
separate time clocks no longer required on a meter panel
Location of metering neutral Link
New remote read meters (Smart Meters) now require;
an aerial location
communication gear etc.
99
Service and Installation Rules NECAJanuary - February - March 2014
Changes General Major cont.
Protection Devices
The Safety Installation Regulations changed the Mandatory location of Supply Protection Devices, Supply Capacity Control Devices and Occupancy Disconnection Devices.
1010
Service and Installation Rules NECAJanuary - February - March 2014
2014 SIRs General
Document Sections
Same as 2005 edition minimal rearrangement. Code of practice Fuse Removal rewritten.
Ok - but distributors must train call center people (ESV requirement.)
Indexs Main index at front of book. Each section has a detailed index at the front of each section.
1111
Service and Installation Rules NECAJanuary - February - March 2014
2014 SIRs General
Table and Figure numbers;
Table and figure numbers have been renumbered to reflect the clause that they refer too, where a clause has more than one, table or figure then they are numbered in order prefixed by the identification table or figure and clause number i.e.
Figure 7.4-A Figure 7.4-B. Figure 7.4-C Table 7.4-1 Figure 7.4-D etc..
1212
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section One (1)
Clause 1.3 (definitions) New Advanced Metering Infrastructure (AMI) Renamed Determined Maximum Demand to Allocated Maximum
Demand. New Common Area. New - Occupancy Disconnection Device. New - Owners Corporation. New Private Aerial Line added to align with Electricity Safety Act. Replaced - Private Overhead Electricity Line (POEL) with Private
Aerial Line.
17/04/2014
3
1313
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section One (1) cont.
Clause 1.3 (definitions) Continued. Renamed Supply Connection Facility to Service Connection
Facility.
Renamed Service Protection Device to Supply Protection Device.
Removed Supply Disconnection Device.
Removed Underground Reticulated Distribution (URD) Now - Network Underground.
1414
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Four (4) old section (5). Subdivisions clause title 2005
changed to Multiple Occupancy Buildings or Subdivisions (application)
2005 Clause rewritten to clarify the intent and application. Forms;
Electrical Work Request - Updated.
Application for Abolishment of Electricity Supply Updated.
Reconnection of Electricity Supply New Form.
Photovoltaic (Solar) Generator Connection Form. New Form Note: - not in SIR Book available from each Distributor. Limitations (in part);
Not more than 4.6 or 5Kw single phase. Not more than 30% load of supplying transformer.
1515
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Five (5) old section (4).
Section 5 of the 2014 edition is the old section and has been expanded to now include clauses located throughout sections of the 2005 book.
This has achieved the grouping of all the common requirements into the one section.
Section 5 now contains; (Formerly section 7 of 2005 edition) No Go Zone Underground Cables Sub Stations Poles & Overhead lines Service pits Supply Isolation
1616
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Five (5) old section (4). Section 5 now contains;
Sealing and Locking from section 8 of the 2005 edition Redrafted Clause to make intention clear.
1.6mm to 2.00mm hole for seals to be provided. Segregation from section 8 of the 2005 edition
Redrafted Clause to make intention clear permanent Provision for Sealing - New Clause
Passage for sealing now required to be double insulated or segregated from live parts.
Provision for padlock - New Clause Requirement now for 6mm diameter hole to be provide for
Distribution company padlock. Private electric lines on public land from section 7 of the 2005
edition Equipment required to be accepted Amended clause
Clause now specifies the meter temperature limits and operating range
1717
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Five (5) old section (4).
Private Aerial Lines ( PAL ) New Clause Clause includes the requirement of the Electrical Safety Act and
Regulations in relation to low bush fire and high bush fire risk areas Construction of PAL to be in accordance with the Act, Regulations
and the Wiring Rules Included the requirement for fault and emergency restoration of the
defective PAL Advise that serious non-compliance will be disconnected on
declared days of total fire ban.
1818
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6) Alternative Supplies. Supply Arrangement Diagrams amended.
Second last paragraph now includes location and operation of alternative supply, e.g. Solar Installations.
Alternativesuppliesare: anelectricitysupplydirectfromgeneratorsorotherequipmentwhichprovideanelectricitysupplynotdeliveredbyaDistributionNetwork.
Thesealternativesuppliesincludeembeddedgenerators,standbygenerators,regenerativebrakingsystems,inverterconnectedgeneratorsusingvariousenergysourcessuchasphotovoltaic,windorfuelcell,uninterruptiblepowersupplies(UPS)andenergystoragesystems.
Note:AnembeddedgeneratorisdefinedasageneratorthatcanelectricallyconnecttoorsynchronisewiththedistributionnetworkorisregisteredwiththeAustralianEnergyMarketOperator(AEMO).
17/04/2014
4
1919
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6) Alternative Supplies.
All alternative supplies must comply with The Electricity Safety Act and (Installations)Regulations, Codes made under the Electrical Industry Act and relevant AustralianStandards and these Rules.
A host of additional standards are also applicable to components and sub systemsincluding rotation machines, earthing, switchgear and fuses, transformers, cabling,labelling etc. Alternative supplies that are also embedded generators must comply withCodes made under the National Electricity Rules and specific Generator ConnectionStandards issued by each Distributor.
2020
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6) Alternative Supplies.Generally all alternative supplies shall:
* Be arranged to disconnect from and not back energise the Distributor'snetwork and service and metering equipment if electricity supply from thenetwork is de-energised (unless explicitly allowed by the Distributor).
* Have electrical characteristics compatible with the relevant Distributor'snetwork
* Not interfere with supply quality to other customers or the Distributor'snetwork.
* Not adversely affect the safety of Distributor employees, customers or the public.
* Not be connected on the line side of metering equipment. * Not create a break in the neutral conductor between the Distributor's
network and the MEN connection.
2121
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6) Alternate Supplies.
IsolationdevicesshallbeinstalledinaccordancewithAustralianStandards,butshallalsosatisfythefollowing:* Isolation devices shall be located either on the switchboard to which the
inverter ac. output connects or as close as practical to the switchboard andcannot be located in a difficult to find position.
* The isolation device must be capable of locking in the open position using aPadlock with a hasp/shaft diameter up to 5.5mm without requiring additionalapparatus. If a locking device (e.g. "lock dog") is added to a MCB as a methodof locking, it shall be permanently secured in an appropriate position.
Isolation Devices
2222
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6) Alternate Supplies.
d) For a multiple occupancy installation, a label shall be installed at theprotection devices within un-rnetered switchboards for all circuits that supplyan occupancy containing an inverter system.e) At the main switchboard and all distribution switchboards to which theembedded generator is connected.Where a switchboard is located directly adjacent to a metering panel onelabel may be adequate if the label is clearly visible when working on themetering panel or the switchboard.Sample labels are shown in Figure 6.9-A, (Typical LabellingRequirement). Additional labelling within an installation will also be requiredto comply with AS3000, AS4777 and other Australian Standards applicableto generation systems.
2323
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6).
Supply Protection requirements
The Electricity Safety Act requires service lines to be protected by protective equipment that can isolate each of the active conductors of an electrical installation and prescribes their location.
For Overhead supplies Network Overhead
Underground URD supplies Network Underground
Supplied direct from a sub-station sub-stations
2424
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6). Supply Protection Devices (SPD).
Main Principle to be achieved.
The customer shall install and maintain an assembly to accommodate supply protection device/s (SPD) in accordance with the Electricity Safety (Installations) Regulations, these Rules and the obligations of the Distributor to connect and disconnect electrical installations.
17/04/2014
5
2525
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6). Supply Protection Devices (SPD).
A Supply Protection Device shall Minimise any adverse conditions which may affect other customers
electrical installations and the distribution system. The SPD must ensure adequate protection is provided up to the electrical protective equipment of the electrical installations they supply.
Note: In some cases Distributors may utilise their HV protection equipment for supply protection. It will be necessary to confirm the supply protection arrangement with the relevant distributor at the design stage of the electrical installation.
Also Enable the Distributor to connect, disconnect and isolate each active
conductor supplying the electrical installation for commercial and/or safety reasons; and not exceed one device per phase
2626
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6). Supply Protection Devices (SPD).
Assemblies to accommodate LV Supply Protection Devices (SPD)
The customer is responsible for the provision of an assembly to accommodate Supply Protective Device/s (SPD) provided by the Distributor. This equipment must be of an acceptable type as required by these Rules and shall be located and installed in accordance with the relevant requirements of the current Electricity Safety Act and Regulations.
Access
The assembly for the purpose of accommodating the SPD shall be installed in a position where convenient and unhindered access is readily available for the Distributor to safely operate and work on the device/s at all hours, unless otherwise agreed by the Distributor.
2727
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6). Supply Protection Devices (SPD).
SPDs and Assemblies
SPD/s and the assemblies shall in part:- (a) be of a type acceptable to the Service and Installation Rules
Management Committee or the relevant Distributor; conform to the requirements of the appropriate Australian or
International Standard for the type of device employed; (c) be installed in accordance with the requirements of the
Electricity Safety Act, Regulations and these Guidelines; (d) be installed so as to comply with the minimum height
requirement of consumers terminals connected to the distributors service cables,
2828
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6). Supply Protection Devices (SPD).
be selected with regard to the conditions, taking account of the nature of the supply (i.e. overhead, underground):
(f) have a rated short circuit current capacity equal to or greater than the prospective short circuit current at the point it is installed;
(g) have, or be installed with, facilities for sealing un-metered connections to prevent unauthorised access;
(h) be maintained by the customer in accordance with the manufacturers specifications.
2929
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6). Supply Protection Devices (SPD).
1.5.5.3.1 Acceptable Fuse Assemblies and Fuse Cartridges
NH Fuse Holder
1 PhaseFOLCB80A Max
Multiphase FOLCB
100A Max
PanelMounted Fuse
100A Max
2A Barrel Cartridge Diameter 22mm
2A-100A Max
Stick Operated FSD
Hand Operated FSD DIN Cartridges 63A-630A
NH Fuse Handles
3030
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6). Supply Protection Devices (SPD).
Fuse Cartridges All fuse cartridges shall be supplied by the Distributor. Subject to approval by the relevant Distributor, Miniature Combined
Fuse Switches may be used, however they shall be provided by the customer.
Fuse carrier assemblies rated at up to 100A shall be capable of accepting 22mm barrel fuse cartridges of Type 2a.
Fuse carrier assemblies rated in excess of 100A shall be suitable for use with Din type NH blade fuse cartridges.
All fuse cartridges to AS/NZS 60269.2.1, or a recognised equivalent
17/04/2014
6
3131
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6). Supply Protection Devices (SPD).
Assembly Types
Fused Overhead Line Connector Boxes
Panel Mounted Fuses
Panel mounted fuse base and carriers shall be of a minimumcontinuous rating of 100 Amp, 500 Volt
Fused Switch Disconnector (FSD)
Stick operated FSDs shall be suitable for mounting on either a pole or building faade
Hand operated FSDs shall be suitable for mounting within the standard service connection facility
3232
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6). Supply Protection Devices (SPD).
Prohibited Fuses
Stick Operated, Panel Mounted Fuses are a specific form of panel mounted fuse originally designed for mounting on a connection box mounted on the underside of a shop veranda.
These fuses are no longer acceptable for use as an SPD or occupancy disconnection device for new connections, alterations or additions to existing electrical installations.
3333
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6).Supply Capacity Control Device.
Supply Capacity (Maximum Demand by Limitation)
Supply Capacity Control Device (SCCD)
Capacity Control and types Electrical installations shall be arranged in accordance with the Wiring Rules
so as not to exceed 130% of the Distributors nominated supply capacity for more than 2 hours by one of the following means:
Moulded case circuit breakers with a fixed thermal trip unit setting of 130%.
Miniature circuit breakers with a fixed thermal trip unit setting of 145%.
These circuit breakers must be de-rated to achieve 130% of the nominated supply capacity.
Adjustable circuit breakers are acceptable provided the thermal trip unit is set to a level equal to the nominated supply capacity and the overload duration is set as agreed with the distributor.
3434
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6).Supply Capacity Control Device.
Maximum Demand Limitation Device/s (SCCD) Circuit breakers shall:
Be installed on the main switchboard in accordance with the Electricity Safety Act and Regulations, the Wiring Rules, and these Rules;
Be arranged to ensure the aggregate rating of the devices does not exceed the supply capacity where multiple devices are used; and
Be provide with a sealing facility when adjustable.
3535
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6).Supply Capacity Control Device.
Supply Capacity Control Device SCCD
The 2009 Safety Installation Regulations no longer permit a switch ahead of the Installation Main Switch/s.
-Therefore the SCCD cannot be located on the meter panel or meter board and shall be the Main Switch or the summation of the Main Switches, where multiple main switches are used.
3636
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Six (6).Supply Capacity Control Device.
Consumers Mains Overload and Short Circuit requirement
As per Clause 2.5.1.1 of AS/NZS3000:2007 consumers mains are to have overload and short circuit (overcurrent) protection.
This is best achieved by using circuit breaker/s as the Main Switch or summation of the Main Switches to be equal to or less than the current carrying capacity of the consumers mains.
Hint. Use the main switch/es as both consumers mains protection and the distribution companies SCCD.
17/04/2014
7
3737
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Seven (7).
General Statement 7.1. new
Type of Service new
Network - underground - new
Network - Overhead new
Sub-stations new
Selection of connection Type amended
Clause remains the same heading reflects the information contained within the clause.
3838
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Seven (7).
Overhead Services amended
Old clause 7.4, new title along with title changes for figures and tables.
Raiser bracket shown with closed loop, not hook as previous, where the maximum of 60 degree angle (vertical or horizontal) cannot be achieved.
Distances from POA to FSD 750mm, FOLCB 500mm max.
3939
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Seven (7).
Supply Protection Type and Location. What needs to be considered:
Capacity of the supply; Distribution reticulation system (OH or UG); or, Installation supplied directly from a distribution substation The type of SPA required; Who is responsible for providing the SPA; The location of the SPA and SPD.
40
SPD SupplyFromanAerialServiceCable
Supply Current Rating
Per Phase
Supply ToSupply
Protection Assemblies
Responsibility for the
provision of Supply
Protection Assembly
Supply Protection
Device Types
Provided by the
Distributor
SPD Location
1 Ph
17/04/2014
8
43
SPD SupplyFromanUndergroundServiceCableConnectedtoanUndergroundorOverhead
Distribution(NoPit)Supply Current Rating
Per Phase
Distributor Reticulation
Supply Protection
Assemblies
Responsibility for the provision
of Supply Protection Assembly
Supply Protection
Device Types Provided by
the Distributor
SPD location as Determined by the Distributor
>100A
URD Areas
FSDCustomer Sizes 00, 2
and 3 Din type NH fuses
1. As close as practicable to the applicable property boundary: or,2. at or within 3m of the consumers terminals (Supply Connection Facility) supplying UG consumers mains: or,3. in a position at or next to the distributors metering equipment.
O/H Areas
O/H AreasNote: (Dedicated service only)
Distributor On Distribution Company Pole
UG Service supplied directly from a SubstationNote: (Dedicated service line)
FSD or Circuit Breaker Distributor
Sizes 00, 2 and 3 Din type NH fuses or CB At the Substation
44
SPD SupplyFromanUndergroundServiceCableConnectedtoanUndergroundorOverhead
Distribution(NoPit)Supply Current Rating
Per Phase
Distributor Reticulation
Supply Protection
Assemblies
Responsibility for the provision
of Supply Protection Assembly
Supply Protection
Device Types Provided by
the Distributor
SPD location as Determined by the Distributor
>100A
URD Areas
FSD
Customer
Sizes 00, 2 and 3 Din type NH fuses
1. As close as practicable to the applicable property boundary: or,2. at or within 3m of the consumers terminals (Supply Connection Facility) supplying UG consumers mains: or,3. in a position at or next to the distributors metering equipment.O/H Areas
O/H AreasNote: (Dedicated service only)
Distributor On Distribution Company Pole
UG Service supplied directly from a SubstationNote: (Dedicated service line)
FSD or Circuit Breaker Distributor
Sizes 00, 2 and 3 Din type NH fuses or CB At the Substation
45
SPD SupplyfromanIndoor,Kiosk,GroundorPoleTypeSubstationlocatedwithinthepropertyitsupplies
Supply Current rating
Per Phase
Substation Type
Supply Protection Assemblies
Responsibility for the provision of
Supply Protection Assembly
Supply Protection
Device Types Provided by the
Distributor
SPD Location
>100A
Kiosk, Indoor, Ground Type
FSDMCCBACBHV Protection
Distributor
Sizes 00, 2 and 3 Din type NH fuses
Installed within the SubstationSee Note 1
MCCBACB
HV Protection
100A Pole Type 2
FOLCB
Customer
Type 2a Fuses
On Distribution Company Pole> 100A FSD Sizes 00, 2 and 3 Din type NH fuses
In some cases Distributors may utilise their HV protection equipment for service protection.It will be necessary to confirm the service protection arrangement with the relevant distributor at the design stage of the electrical installation.
Note1 Electricity Safety (Installations) Regulations, Regulation 235 Installation of protective equipment(3) In the case of electricity supplies provided directly from a substation, protective equipment must be installed within the substation.Note 2 The use of a pole mounted circuit breaker is not permitted to be used as a supply protection device for underground lines forming consumers mains
4646
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Seven (7). Electrical Installations on Public Land New.
New clause details to depth of labeling required for electrical installations located on public land.
Un-metered Consumers Mains and Sub-mains new
New clause gives information, guidance and requirements for Consumers Mains regarding;
Cables and conductors.
General
Prepared in accordance with the safety Act, Regulations, wiring Rules and the additional requirements of the SIR,s
ESR and Fire rated cables - not covered consult the Distributor
47
Changes SectionSeven(7).UNMETEREDMAINSANDSUBMAINS
ConductorTypes Softdrawncopperonlyupto16mmtobe7strands,greaterthan16mmandupto35mmtobe18strandsminimum.
ConductorSizes Sharedpitmax35mmSoleuseordedicatedpit50mmMeteringmin4mmmax35mm
Controlwiring2.5mm Colour anddoubleInsulation newrequirements
Colour CodesandSleeving,Useheatshrinkfixedsleeving,tapenotpermitted,Neutralblack,1st activeRed,2ndactiveWhite3rd ActiveBlue.
4848
Service and Installation Rules NECAJanuary - February - March 2014Changes - Section Seven (7).
Color Identification
SDI Cables - with Sheath
Minimum length of identification 100mm placed between 150mm and 250mm from end of cable.
SDI Cables no Sheath (One layer of reinforced insulation) colouridentification for entire length within terminating enclosure.
Sheathed Multi-core Cables
Correct colour of cores no additional requirements.
Incorrect colour of cores heat shrink entire length and crutch seal fitted.
Single Insulated Conductors
Coloured in accordance with the rule and entire length within terminating enclosure.
Joints in Un-metered Cables and Conductors table extended to include terminating facility sealing or padlock facility to be provided.
17/04/2014
9
49
Changes SectionSeven(7). UndergroundMainsandSubmains
MinimumInsulationResistance Nochange50Megohmreducingtominof5MegOhmoverdistance.
WiringSystems Samerequirements,oneconduitortwodifferentphasesineachconduit,cableslessthan95mm2shallnotbedirectburied.
Backfilling Backfillingoftrenchrequiredpriortosupplybeingconnected.
TerminationwithinaServicePit Nowincludestherequirementtotakeadequateprecautionsifhandlinglive conductors.
5050
Service and Installation Rules NECAJanuary - February - March 2014
Multiple Occupancy Buildings and Subdivision Supply Arrangements Section 7.
Required Information:
The customer must provide the following information; the electrical contractors electrical installation wiring plan
(as described in Section 7.8.3 of the current Victorian Service & Installation Rules); and
the plan of subdivision if already subdivided; or
the proposed plan of subdivision if the land is in the process of being subdivided; or
a prospective plan of subdivision showing all proposed lot boundaries and common property.
51
SupplyArrangementExample#1 Section7.
DualOccupancy: prospectivesubdivisionnotincorporatingcommonproperty;
ownerordevelopertoprovideadraftplanofsubdivision;
separatesuppliesmustbeprovided.
51
Service and Installation Rules NECAJanuary - February - March 2014
52
SupplyArrangementExample#2 Section7.
DualOccupancy: prospectivesubdivisionincorporatingcommonproperty;
singlesupplypoint; commonmeteringenclosure/main.
Service and Installation Rules NECAJanuary - February - March 2014
52
53
SupplyArrangementExample#3 Section7.
FourLotsubdivisionincorporatingcommonproperty: Landaffectedbythe
ownerscorporationincludeslots1,2andcommonproperty
Lots3and4arenotaffectedbytheOwnersCorporation,therefore,theycanbesuppliedseparately
53
Service and Installation Rules NECAJanuary - February - March 2014
54
SupplyArrangementExample#4 Section7. FourLotsubdivisionincorporatingcommonproperty: Landaffectedbyowners
corporationsincludeslots2,3,4andcommonproperty
Lot1isnotaffectedbyanyOwnersCorporation,therefore,itcanbesuppliedseparately
Lot1canbesuppliedeitheroverheadorunderground
54
Service and Installation Rules NECAJanuary - February - March 2014
17/04/2014
10
55
SupplyArrangementExample#5 Section7. FourLotsubdivisionincorporatingcommonproperty: landaffectedbytheowners
corporationincludeslots1,2,3,4andcommonproperty
singlesupplypoint commonmetering
enclosure/mainswitchboard
Service and Installation Rules NECAJanuary - February - March 2014
55 5656
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Seven (7). Multiple Occupancy Buildings and Subdivision Supply
Arrangements new
Plan
Provision of Plan by Customer.
Multiple Occupancy Buildings
Point of Supply
Consumers Terminals
Metering Arrangements
Possible Sub-division of Building or Land
Labeling
Wiring Arrangements
Un-metered Connections and Equipment.
5757
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering.
Timber Panels Boards Clause extended
Now includes the old Alterations and Additions requirements.
Meter Enclosures - Clause extended
Additional dot point re;
Construction and location, not to cause metering equipment to exceed it temperature limits.
5858
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering.
Protection Against Damage to, and Interference with Metering Equipment, - location of meter enclosure and the need to lock them.
Direct Connected Meter, Limits of Current Carrying Capacity amended
Was part of Determination of Meter Type in the 2005 edition.
Now requires maximum demand to be limited to 100Amps and not be exceeded.
Installations reaching 90Amps continuous to strongly consider installation of LV CT Metering.
5959
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering.
Meters Temperature Limits of Specified Operating Range amended
Now requires the temperature range to be complied with; Direct Connected Meter (class 1 or 1.5) -10 to +60oC
LV CT and HV Connected Metering (class 0.2 or 0.5) -10 to +45oC
Where meters are enclosed within switchboard the temperature rise above ambient is to be limited to;
Direct Connected meters 25oK
LV CT and HV Connected Meters 10oK
6060
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering.
Figure 8.9-A clause 8.9 Amended new figure
17/04/2014
11
6161
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering.
6262
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering. Specific Situation Requirements new clause applies to single
occupancies only.
Single Occupancy
Isolation single occupancy commercial only where there is no access (verandah) additional fuses permitted on meter panel.
Meter panels
All meters to be contained on a single meter panel.
Meter Locations
Domestic no change, same as previous
Commercial/Industrial new located outside unless no suitable external position available. (next slide)
Labelling no change, same as previous. address on meter panel.
6363
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering. Specific Situation Requirements new clause (Continued)
Meter Locations
Commercial/Industrial
New figure 8.10-B Small/Medium Individual Commercial/Industrial Installations Acceptable Meter Locations
Dot point 3 (three) of clause 8.10. within a suitable location in the building where suitable locations outside of the building do not exist.
6464
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering.
6565
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering.
Grouping of meters - New title
Was part of Multiple Occupancy Electrical Installations in the 2005 edition.
Clause reconfigured.
Table 8.10-2 - Amended)
Old Tables 8.2 and 8.3 consolidated into one table.
Occupancy Disconnection Device 8.10.12 (a) and (b) New clauses
Details when and where the devices are required.
6666
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering. LV Current Metering New Section/Clause numbers
Clearances Changed LV CT Meter panel heights.
17/04/2014
12
6767
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering.
C/T chamber busbars
C/T Enclosure General Specifies busbar arrangements within CT Enclosures.
Busbars shall be installed in the one direction within the C/T chamber i.e. enter the C/T chamber vertically then they remain vertical until the busbars have exited the C/T chamber.
6868
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering. C/T Fuses clause amended
Clause expanded to include the requirement for safe operation of fuse carriers.
6969
Service and Installation Rules NECAJanuary - February - March 2014
Changes - Section Eight (8) Metering.
Section 8 now includes new clause 8.12; - Metering Communications Equipment.
Communications Cabling, Communications equipment power cabling and antenna cabling.
Communications Devices.
External or Remote Antenna.
Customer and third party provided Communication Equipment (e.g. HAN repeater)
7070
Service and Installation Rules NECAJanuary - February - March 2014
Changes 2005 to 2014 SIRs.
The EndQuestion Time
(Metering Diagrams Follow)
7171
Service and Installation Rules NECAJanuary - February - March 2014
7272
Service and Installation Rules NECAJanuary - February - March 2014
17/04/2014
13
7373
Service and Installation Rules NECAJanuary - February - March 2014
7474
Service and Installation Rules NECAJanuary - February - March 2014
7575
Service and Installation Rules NECAJanuary - February - March 2014
7676
Service and Installation Rules NECAJanuary - February - March 2014
7777
Service and Installation Rules NECAJanuary - February - March 2014
7878
Service and Installation Rules NECAJanuary - February - March 2014
Changes 2005 to 2014 SIRs.
Direct connected meters
An approved panel mounted fuse/s adjacent to the occupancy meter.Current Transformer meters
An approved switch or circuit breaker.