NHP Presentation 2014 Victoria Service and Installation Rules

  • Upload
    vzssz

  • View
    75

  • Download
    0

Embed Size (px)

DESCRIPTION

Presentation by NHP and NECA for the introduction of the 2014 Victorian Service and Installation Rules (SIR)

Citation preview

  • 17/04/2014

    1

    1

    VictorianService and Installation Rules

    2014

    22

    Tonight we will cover:

    the variations between the 2005 and the 2014 versions of the Service and Installation Rules.

    go over certain selected areas within the new SIRs

    remove confusion and Highlight areas where major non-compliance often occurs.

    Service and Installation Rules NECAJanuary - February - March 2014

    Welcome

    33

    Where do the Service and Installation Rules (SIR) fit in?

    Under the Sale and Distribution Code, Known as the Distributors reasonable technical requirements.

    Traditionally cover off supply connection methods, metering and supply arrangements.

    Service and Installation Rules NECAJanuary - February - March 2014

    SIR Fit

    44

    Service and Installation Rules NECAJanuary - February - March 2014

    Compliance

    Do I need to comply with the SIRs are they mandatory?

    Yes you shall comply;

    If you do not comply then FIP (fuse in pocket) usually applies. No Supply.

    For safe connection and metering of electrical installations you are required to comply with the Sale and Distribution Code.

    Remember any delays will effect your customer.

    55

    Service and Installation Rules NECAJanuary - February - March 2014

    Application

    The Victorian Service & Installation Rules apply to all connections to the electricity supply networks operated by Electricity Distributors: CitiPower, Jemena Electricity Network, Powercor Australia Ltd, SP AusNet and United Energy.

    The objective of these Rules is to: provide Victorian electricity customers with industry agreed reasonable

    technical requirements that; meet all legislative and Electricity Distribution Code requirements

    for the supply and metering related aspects of any connection to the Victorian Distributors electricity supply networks.

    66

    Service and Installation Rules NECAJanuary - February - March 2014

    Public Notice - Availability of the 2014 Service and Installation RulesThe 2014 SIR are applicable from 1st January 2014 with a three month period of transition allowing the trade to adopt and employ the changes in the new document. There may be exceptional circumstances, if a connection post 31st March 2014 exists where a REC wishes to have the 2005 rules applied an SIR exemptions must be submitted by a written request detailing the reasons why non-compliance with the 2014 Rules is sought.

    An exception to the 2005 Rules will not be automatically granted, electrical work associated with the exception should be discontinued until approval from the Distributor is received.

  • 17/04/2014

    2

    77

    Service and Installation Rules NECAJanuary - February - March 2014

    Service and Installation Rules Committee.

    Members of the SIR rewrite Committee are; The five Distributions Companies.

    Each permitted two representatives. Institute of Electrical Inspectors Australia.

    Mark Aitken Energy Safe Victoria.

    Simon OLeary National Electrical and Communications Association (NECA)

    Victoria. Brian Cross (Twin Electrics) Roy Sands NECA Victoria.

    88

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes General - Major

    Metering

    The arrival of Smart Meters has altered;

    the numbers of meters on a panel

    separate time clocks no longer required on a meter panel

    Location of metering neutral Link

    New remote read meters (Smart Meters) now require;

    an aerial location

    communication gear etc.

    99

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes General Major cont.

    Protection Devices

    The Safety Installation Regulations changed the Mandatory location of Supply Protection Devices, Supply Capacity Control Devices and Occupancy Disconnection Devices.

    1010

    Service and Installation Rules NECAJanuary - February - March 2014

    2014 SIRs General

    Document Sections

    Same as 2005 edition minimal rearrangement. Code of practice Fuse Removal rewritten.

    Ok - but distributors must train call center people (ESV requirement.)

    Indexs Main index at front of book. Each section has a detailed index at the front of each section.

    1111

    Service and Installation Rules NECAJanuary - February - March 2014

    2014 SIRs General

    Table and Figure numbers;

    Table and figure numbers have been renumbered to reflect the clause that they refer too, where a clause has more than one, table or figure then they are numbered in order prefixed by the identification table or figure and clause number i.e.

    Figure 7.4-A Figure 7.4-B. Figure 7.4-C Table 7.4-1 Figure 7.4-D etc..

    1212

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section One (1)

    Clause 1.3 (definitions) New Advanced Metering Infrastructure (AMI) Renamed Determined Maximum Demand to Allocated Maximum

    Demand. New Common Area. New - Occupancy Disconnection Device. New - Owners Corporation. New Private Aerial Line added to align with Electricity Safety Act. Replaced - Private Overhead Electricity Line (POEL) with Private

    Aerial Line.

  • 17/04/2014

    3

    1313

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section One (1) cont.

    Clause 1.3 (definitions) Continued. Renamed Supply Connection Facility to Service Connection

    Facility.

    Renamed Service Protection Device to Supply Protection Device.

    Removed Supply Disconnection Device.

    Removed Underground Reticulated Distribution (URD) Now - Network Underground.

    1414

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Four (4) old section (5). Subdivisions clause title 2005

    changed to Multiple Occupancy Buildings or Subdivisions (application)

    2005 Clause rewritten to clarify the intent and application. Forms;

    Electrical Work Request - Updated.

    Application for Abolishment of Electricity Supply Updated.

    Reconnection of Electricity Supply New Form.

    Photovoltaic (Solar) Generator Connection Form. New Form Note: - not in SIR Book available from each Distributor. Limitations (in part);

    Not more than 4.6 or 5Kw single phase. Not more than 30% load of supplying transformer.

    1515

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Five (5) old section (4).

    Section 5 of the 2014 edition is the old section and has been expanded to now include clauses located throughout sections of the 2005 book.

    This has achieved the grouping of all the common requirements into the one section.

    Section 5 now contains; (Formerly section 7 of 2005 edition) No Go Zone Underground Cables Sub Stations Poles & Overhead lines Service pits Supply Isolation

    1616

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Five (5) old section (4). Section 5 now contains;

    Sealing and Locking from section 8 of the 2005 edition Redrafted Clause to make intention clear.

    1.6mm to 2.00mm hole for seals to be provided. Segregation from section 8 of the 2005 edition

    Redrafted Clause to make intention clear permanent Provision for Sealing - New Clause

    Passage for sealing now required to be double insulated or segregated from live parts.

    Provision for padlock - New Clause Requirement now for 6mm diameter hole to be provide for

    Distribution company padlock. Private electric lines on public land from section 7 of the 2005

    edition Equipment required to be accepted Amended clause

    Clause now specifies the meter temperature limits and operating range

    1717

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Five (5) old section (4).

    Private Aerial Lines ( PAL ) New Clause Clause includes the requirement of the Electrical Safety Act and

    Regulations in relation to low bush fire and high bush fire risk areas Construction of PAL to be in accordance with the Act, Regulations

    and the Wiring Rules Included the requirement for fault and emergency restoration of the

    defective PAL Advise that serious non-compliance will be disconnected on

    declared days of total fire ban.

    1818

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6) Alternative Supplies. Supply Arrangement Diagrams amended.

    Second last paragraph now includes location and operation of alternative supply, e.g. Solar Installations.

    Alternativesuppliesare: anelectricitysupplydirectfromgeneratorsorotherequipmentwhichprovideanelectricitysupplynotdeliveredbyaDistributionNetwork.

    Thesealternativesuppliesincludeembeddedgenerators,standbygenerators,regenerativebrakingsystems,inverterconnectedgeneratorsusingvariousenergysourcessuchasphotovoltaic,windorfuelcell,uninterruptiblepowersupplies(UPS)andenergystoragesystems.

    Note:AnembeddedgeneratorisdefinedasageneratorthatcanelectricallyconnecttoorsynchronisewiththedistributionnetworkorisregisteredwiththeAustralianEnergyMarketOperator(AEMO).

  • 17/04/2014

    4

    1919

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6) Alternative Supplies.

    All alternative supplies must comply with The Electricity Safety Act and (Installations)Regulations, Codes made under the Electrical Industry Act and relevant AustralianStandards and these Rules.

    A host of additional standards are also applicable to components and sub systemsincluding rotation machines, earthing, switchgear and fuses, transformers, cabling,labelling etc. Alternative supplies that are also embedded generators must comply withCodes made under the National Electricity Rules and specific Generator ConnectionStandards issued by each Distributor.

    2020

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6) Alternative Supplies.Generally all alternative supplies shall:

    * Be arranged to disconnect from and not back energise the Distributor'snetwork and service and metering equipment if electricity supply from thenetwork is de-energised (unless explicitly allowed by the Distributor).

    * Have electrical characteristics compatible with the relevant Distributor'snetwork

    * Not interfere with supply quality to other customers or the Distributor'snetwork.

    * Not adversely affect the safety of Distributor employees, customers or the public.

    * Not be connected on the line side of metering equipment. * Not create a break in the neutral conductor between the Distributor's

    network and the MEN connection.

    2121

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6) Alternate Supplies.

    IsolationdevicesshallbeinstalledinaccordancewithAustralianStandards,butshallalsosatisfythefollowing:* Isolation devices shall be located either on the switchboard to which the

    inverter ac. output connects or as close as practical to the switchboard andcannot be located in a difficult to find position.

    * The isolation device must be capable of locking in the open position using aPadlock with a hasp/shaft diameter up to 5.5mm without requiring additionalapparatus. If a locking device (e.g. "lock dog") is added to a MCB as a methodof locking, it shall be permanently secured in an appropriate position.

    Isolation Devices

    2222

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6) Alternate Supplies.

    d) For a multiple occupancy installation, a label shall be installed at theprotection devices within un-rnetered switchboards for all circuits that supplyan occupancy containing an inverter system.e) At the main switchboard and all distribution switchboards to which theembedded generator is connected.Where a switchboard is located directly adjacent to a metering panel onelabel may be adequate if the label is clearly visible when working on themetering panel or the switchboard.Sample labels are shown in Figure 6.9-A, (Typical LabellingRequirement). Additional labelling within an installation will also be requiredto comply with AS3000, AS4777 and other Australian Standards applicableto generation systems.

    2323

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6).

    Supply Protection requirements

    The Electricity Safety Act requires service lines to be protected by protective equipment that can isolate each of the active conductors of an electrical installation and prescribes their location.

    For Overhead supplies Network Overhead

    Underground URD supplies Network Underground

    Supplied direct from a sub-station sub-stations

    2424

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6). Supply Protection Devices (SPD).

    Main Principle to be achieved.

    The customer shall install and maintain an assembly to accommodate supply protection device/s (SPD) in accordance with the Electricity Safety (Installations) Regulations, these Rules and the obligations of the Distributor to connect and disconnect electrical installations.

  • 17/04/2014

    5

    2525

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6). Supply Protection Devices (SPD).

    A Supply Protection Device shall Minimise any adverse conditions which may affect other customers

    electrical installations and the distribution system. The SPD must ensure adequate protection is provided up to the electrical protective equipment of the electrical installations they supply.

    Note: In some cases Distributors may utilise their HV protection equipment for supply protection. It will be necessary to confirm the supply protection arrangement with the relevant distributor at the design stage of the electrical installation.

    Also Enable the Distributor to connect, disconnect and isolate each active

    conductor supplying the electrical installation for commercial and/or safety reasons; and not exceed one device per phase

    2626

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6). Supply Protection Devices (SPD).

    Assemblies to accommodate LV Supply Protection Devices (SPD)

    The customer is responsible for the provision of an assembly to accommodate Supply Protective Device/s (SPD) provided by the Distributor. This equipment must be of an acceptable type as required by these Rules and shall be located and installed in accordance with the relevant requirements of the current Electricity Safety Act and Regulations.

    Access

    The assembly for the purpose of accommodating the SPD shall be installed in a position where convenient and unhindered access is readily available for the Distributor to safely operate and work on the device/s at all hours, unless otherwise agreed by the Distributor.

    2727

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6). Supply Protection Devices (SPD).

    SPDs and Assemblies

    SPD/s and the assemblies shall in part:- (a) be of a type acceptable to the Service and Installation Rules

    Management Committee or the relevant Distributor; conform to the requirements of the appropriate Australian or

    International Standard for the type of device employed; (c) be installed in accordance with the requirements of the

    Electricity Safety Act, Regulations and these Guidelines; (d) be installed so as to comply with the minimum height

    requirement of consumers terminals connected to the distributors service cables,

    2828

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6). Supply Protection Devices (SPD).

    be selected with regard to the conditions, taking account of the nature of the supply (i.e. overhead, underground):

    (f) have a rated short circuit current capacity equal to or greater than the prospective short circuit current at the point it is installed;

    (g) have, or be installed with, facilities for sealing un-metered connections to prevent unauthorised access;

    (h) be maintained by the customer in accordance with the manufacturers specifications.

    2929

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6). Supply Protection Devices (SPD).

    1.5.5.3.1 Acceptable Fuse Assemblies and Fuse Cartridges

    NH Fuse Holder

    1 PhaseFOLCB80A Max

    Multiphase FOLCB

    100A Max

    PanelMounted Fuse

    100A Max

    2A Barrel Cartridge Diameter 22mm

    2A-100A Max

    Stick Operated FSD

    Hand Operated FSD DIN Cartridges 63A-630A

    NH Fuse Handles

    3030

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6). Supply Protection Devices (SPD).

    Fuse Cartridges All fuse cartridges shall be supplied by the Distributor. Subject to approval by the relevant Distributor, Miniature Combined

    Fuse Switches may be used, however they shall be provided by the customer.

    Fuse carrier assemblies rated at up to 100A shall be capable of accepting 22mm barrel fuse cartridges of Type 2a.

    Fuse carrier assemblies rated in excess of 100A shall be suitable for use with Din type NH blade fuse cartridges.

    All fuse cartridges to AS/NZS 60269.2.1, or a recognised equivalent

  • 17/04/2014

    6

    3131

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6). Supply Protection Devices (SPD).

    Assembly Types

    Fused Overhead Line Connector Boxes

    Panel Mounted Fuses

    Panel mounted fuse base and carriers shall be of a minimumcontinuous rating of 100 Amp, 500 Volt

    Fused Switch Disconnector (FSD)

    Stick operated FSDs shall be suitable for mounting on either a pole or building faade

    Hand operated FSDs shall be suitable for mounting within the standard service connection facility

    3232

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6). Supply Protection Devices (SPD).

    Prohibited Fuses

    Stick Operated, Panel Mounted Fuses are a specific form of panel mounted fuse originally designed for mounting on a connection box mounted on the underside of a shop veranda.

    These fuses are no longer acceptable for use as an SPD or occupancy disconnection device for new connections, alterations or additions to existing electrical installations.

    3333

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6).Supply Capacity Control Device.

    Supply Capacity (Maximum Demand by Limitation)

    Supply Capacity Control Device (SCCD)

    Capacity Control and types Electrical installations shall be arranged in accordance with the Wiring Rules

    so as not to exceed 130% of the Distributors nominated supply capacity for more than 2 hours by one of the following means:

    Moulded case circuit breakers with a fixed thermal trip unit setting of 130%.

    Miniature circuit breakers with a fixed thermal trip unit setting of 145%.

    These circuit breakers must be de-rated to achieve 130% of the nominated supply capacity.

    Adjustable circuit breakers are acceptable provided the thermal trip unit is set to a level equal to the nominated supply capacity and the overload duration is set as agreed with the distributor.

    3434

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6).Supply Capacity Control Device.

    Maximum Demand Limitation Device/s (SCCD) Circuit breakers shall:

    Be installed on the main switchboard in accordance with the Electricity Safety Act and Regulations, the Wiring Rules, and these Rules;

    Be arranged to ensure the aggregate rating of the devices does not exceed the supply capacity where multiple devices are used; and

    Be provide with a sealing facility when adjustable.

    3535

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6).Supply Capacity Control Device.

    Supply Capacity Control Device SCCD

    The 2009 Safety Installation Regulations no longer permit a switch ahead of the Installation Main Switch/s.

    -Therefore the SCCD cannot be located on the meter panel or meter board and shall be the Main Switch or the summation of the Main Switches, where multiple main switches are used.

    3636

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Six (6).Supply Capacity Control Device.

    Consumers Mains Overload and Short Circuit requirement

    As per Clause 2.5.1.1 of AS/NZS3000:2007 consumers mains are to have overload and short circuit (overcurrent) protection.

    This is best achieved by using circuit breaker/s as the Main Switch or summation of the Main Switches to be equal to or less than the current carrying capacity of the consumers mains.

    Hint. Use the main switch/es as both consumers mains protection and the distribution companies SCCD.

  • 17/04/2014

    7

    3737

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Seven (7).

    General Statement 7.1. new

    Type of Service new

    Network - underground - new

    Network - Overhead new

    Sub-stations new

    Selection of connection Type amended

    Clause remains the same heading reflects the information contained within the clause.

    3838

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Seven (7).

    Overhead Services amended

    Old clause 7.4, new title along with title changes for figures and tables.

    Raiser bracket shown with closed loop, not hook as previous, where the maximum of 60 degree angle (vertical or horizontal) cannot be achieved.

    Distances from POA to FSD 750mm, FOLCB 500mm max.

    3939

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Seven (7).

    Supply Protection Type and Location. What needs to be considered:

    Capacity of the supply; Distribution reticulation system (OH or UG); or, Installation supplied directly from a distribution substation The type of SPA required; Who is responsible for providing the SPA; The location of the SPA and SPD.

    40

    SPD SupplyFromanAerialServiceCable

    Supply Current Rating

    Per Phase

    Supply ToSupply

    Protection Assemblies

    Responsibility for the

    provision of Supply

    Protection Assembly

    Supply Protection

    Device Types

    Provided by the

    Distributor

    SPD Location

    1 Ph

  • 17/04/2014

    8

    43

    SPD SupplyFromanUndergroundServiceCableConnectedtoanUndergroundorOverhead

    Distribution(NoPit)Supply Current Rating

    Per Phase

    Distributor Reticulation

    Supply Protection

    Assemblies

    Responsibility for the provision

    of Supply Protection Assembly

    Supply Protection

    Device Types Provided by

    the Distributor

    SPD location as Determined by the Distributor

    >100A

    URD Areas

    FSDCustomer Sizes 00, 2

    and 3 Din type NH fuses

    1. As close as practicable to the applicable property boundary: or,2. at or within 3m of the consumers terminals (Supply Connection Facility) supplying UG consumers mains: or,3. in a position at or next to the distributors metering equipment.

    O/H Areas

    O/H AreasNote: (Dedicated service only)

    Distributor On Distribution Company Pole

    UG Service supplied directly from a SubstationNote: (Dedicated service line)

    FSD or Circuit Breaker Distributor

    Sizes 00, 2 and 3 Din type NH fuses or CB At the Substation

    44

    SPD SupplyFromanUndergroundServiceCableConnectedtoanUndergroundorOverhead

    Distribution(NoPit)Supply Current Rating

    Per Phase

    Distributor Reticulation

    Supply Protection

    Assemblies

    Responsibility for the provision

    of Supply Protection Assembly

    Supply Protection

    Device Types Provided by

    the Distributor

    SPD location as Determined by the Distributor

    >100A

    URD Areas

    FSD

    Customer

    Sizes 00, 2 and 3 Din type NH fuses

    1. As close as practicable to the applicable property boundary: or,2. at or within 3m of the consumers terminals (Supply Connection Facility) supplying UG consumers mains: or,3. in a position at or next to the distributors metering equipment.O/H Areas

    O/H AreasNote: (Dedicated service only)

    Distributor On Distribution Company Pole

    UG Service supplied directly from a SubstationNote: (Dedicated service line)

    FSD or Circuit Breaker Distributor

    Sizes 00, 2 and 3 Din type NH fuses or CB At the Substation

    45

    SPD SupplyfromanIndoor,Kiosk,GroundorPoleTypeSubstationlocatedwithinthepropertyitsupplies

    Supply Current rating

    Per Phase

    Substation Type

    Supply Protection Assemblies

    Responsibility for the provision of

    Supply Protection Assembly

    Supply Protection

    Device Types Provided by the

    Distributor

    SPD Location

    >100A

    Kiosk, Indoor, Ground Type

    FSDMCCBACBHV Protection

    Distributor

    Sizes 00, 2 and 3 Din type NH fuses

    Installed within the SubstationSee Note 1

    MCCBACB

    HV Protection

    100A Pole Type 2

    FOLCB

    Customer

    Type 2a Fuses

    On Distribution Company Pole> 100A FSD Sizes 00, 2 and 3 Din type NH fuses

    In some cases Distributors may utilise their HV protection equipment for service protection.It will be necessary to confirm the service protection arrangement with the relevant distributor at the design stage of the electrical installation.

    Note1 Electricity Safety (Installations) Regulations, Regulation 235 Installation of protective equipment(3) In the case of electricity supplies provided directly from a substation, protective equipment must be installed within the substation.Note 2 The use of a pole mounted circuit breaker is not permitted to be used as a supply protection device for underground lines forming consumers mains

    4646

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Seven (7). Electrical Installations on Public Land New.

    New clause details to depth of labeling required for electrical installations located on public land.

    Un-metered Consumers Mains and Sub-mains new

    New clause gives information, guidance and requirements for Consumers Mains regarding;

    Cables and conductors.

    General

    Prepared in accordance with the safety Act, Regulations, wiring Rules and the additional requirements of the SIR,s

    ESR and Fire rated cables - not covered consult the Distributor

    47

    Changes SectionSeven(7).UNMETEREDMAINSANDSUBMAINS

    ConductorTypes Softdrawncopperonlyupto16mmtobe7strands,greaterthan16mmandupto35mmtobe18strandsminimum.

    ConductorSizes Sharedpitmax35mmSoleuseordedicatedpit50mmMeteringmin4mmmax35mm

    Controlwiring2.5mm Colour anddoubleInsulation newrequirements

    Colour CodesandSleeving,Useheatshrinkfixedsleeving,tapenotpermitted,Neutralblack,1st activeRed,2ndactiveWhite3rd ActiveBlue.

    4848

    Service and Installation Rules NECAJanuary - February - March 2014Changes - Section Seven (7).

    Color Identification

    SDI Cables - with Sheath

    Minimum length of identification 100mm placed between 150mm and 250mm from end of cable.

    SDI Cables no Sheath (One layer of reinforced insulation) colouridentification for entire length within terminating enclosure.

    Sheathed Multi-core Cables

    Correct colour of cores no additional requirements.

    Incorrect colour of cores heat shrink entire length and crutch seal fitted.

    Single Insulated Conductors

    Coloured in accordance with the rule and entire length within terminating enclosure.

    Joints in Un-metered Cables and Conductors table extended to include terminating facility sealing or padlock facility to be provided.

  • 17/04/2014

    9

    49

    Changes SectionSeven(7). UndergroundMainsandSubmains

    MinimumInsulationResistance Nochange50Megohmreducingtominof5MegOhmoverdistance.

    WiringSystems Samerequirements,oneconduitortwodifferentphasesineachconduit,cableslessthan95mm2shallnotbedirectburied.

    Backfilling Backfillingoftrenchrequiredpriortosupplybeingconnected.

    TerminationwithinaServicePit Nowincludestherequirementtotakeadequateprecautionsifhandlinglive conductors.

    5050

    Service and Installation Rules NECAJanuary - February - March 2014

    Multiple Occupancy Buildings and Subdivision Supply Arrangements Section 7.

    Required Information:

    The customer must provide the following information; the electrical contractors electrical installation wiring plan

    (as described in Section 7.8.3 of the current Victorian Service & Installation Rules); and

    the plan of subdivision if already subdivided; or

    the proposed plan of subdivision if the land is in the process of being subdivided; or

    a prospective plan of subdivision showing all proposed lot boundaries and common property.

    51

    SupplyArrangementExample#1 Section7.

    DualOccupancy: prospectivesubdivisionnotincorporatingcommonproperty;

    ownerordevelopertoprovideadraftplanofsubdivision;

    separatesuppliesmustbeprovided.

    51

    Service and Installation Rules NECAJanuary - February - March 2014

    52

    SupplyArrangementExample#2 Section7.

    DualOccupancy: prospectivesubdivisionincorporatingcommonproperty;

    singlesupplypoint; commonmeteringenclosure/main.

    Service and Installation Rules NECAJanuary - February - March 2014

    52

    53

    SupplyArrangementExample#3 Section7.

    FourLotsubdivisionincorporatingcommonproperty: Landaffectedbythe

    ownerscorporationincludeslots1,2andcommonproperty

    Lots3and4arenotaffectedbytheOwnersCorporation,therefore,theycanbesuppliedseparately

    53

    Service and Installation Rules NECAJanuary - February - March 2014

    54

    SupplyArrangementExample#4 Section7. FourLotsubdivisionincorporatingcommonproperty: Landaffectedbyowners

    corporationsincludeslots2,3,4andcommonproperty

    Lot1isnotaffectedbyanyOwnersCorporation,therefore,itcanbesuppliedseparately

    Lot1canbesuppliedeitheroverheadorunderground

    54

    Service and Installation Rules NECAJanuary - February - March 2014

  • 17/04/2014

    10

    55

    SupplyArrangementExample#5 Section7. FourLotsubdivisionincorporatingcommonproperty: landaffectedbytheowners

    corporationincludeslots1,2,3,4andcommonproperty

    singlesupplypoint commonmetering

    enclosure/mainswitchboard

    Service and Installation Rules NECAJanuary - February - March 2014

    55 5656

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Seven (7). Multiple Occupancy Buildings and Subdivision Supply

    Arrangements new

    Plan

    Provision of Plan by Customer.

    Multiple Occupancy Buildings

    Point of Supply

    Consumers Terminals

    Metering Arrangements

    Possible Sub-division of Building or Land

    Labeling

    Wiring Arrangements

    Un-metered Connections and Equipment.

    5757

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering.

    Timber Panels Boards Clause extended

    Now includes the old Alterations and Additions requirements.

    Meter Enclosures - Clause extended

    Additional dot point re;

    Construction and location, not to cause metering equipment to exceed it temperature limits.

    5858

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering.

    Protection Against Damage to, and Interference with Metering Equipment, - location of meter enclosure and the need to lock them.

    Direct Connected Meter, Limits of Current Carrying Capacity amended

    Was part of Determination of Meter Type in the 2005 edition.

    Now requires maximum demand to be limited to 100Amps and not be exceeded.

    Installations reaching 90Amps continuous to strongly consider installation of LV CT Metering.

    5959

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering.

    Meters Temperature Limits of Specified Operating Range amended

    Now requires the temperature range to be complied with; Direct Connected Meter (class 1 or 1.5) -10 to +60oC

    LV CT and HV Connected Metering (class 0.2 or 0.5) -10 to +45oC

    Where meters are enclosed within switchboard the temperature rise above ambient is to be limited to;

    Direct Connected meters 25oK

    LV CT and HV Connected Meters 10oK

    6060

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering.

    Figure 8.9-A clause 8.9 Amended new figure

  • 17/04/2014

    11

    6161

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering.

    6262

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering. Specific Situation Requirements new clause applies to single

    occupancies only.

    Single Occupancy

    Isolation single occupancy commercial only where there is no access (verandah) additional fuses permitted on meter panel.

    Meter panels

    All meters to be contained on a single meter panel.

    Meter Locations

    Domestic no change, same as previous

    Commercial/Industrial new located outside unless no suitable external position available. (next slide)

    Labelling no change, same as previous. address on meter panel.

    6363

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering. Specific Situation Requirements new clause (Continued)

    Meter Locations

    Commercial/Industrial

    New figure 8.10-B Small/Medium Individual Commercial/Industrial Installations Acceptable Meter Locations

    Dot point 3 (three) of clause 8.10. within a suitable location in the building where suitable locations outside of the building do not exist.

    6464

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering.

    6565

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering.

    Grouping of meters - New title

    Was part of Multiple Occupancy Electrical Installations in the 2005 edition.

    Clause reconfigured.

    Table 8.10-2 - Amended)

    Old Tables 8.2 and 8.3 consolidated into one table.

    Occupancy Disconnection Device 8.10.12 (a) and (b) New clauses

    Details when and where the devices are required.

    6666

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering. LV Current Metering New Section/Clause numbers

    Clearances Changed LV CT Meter panel heights.

  • 17/04/2014

    12

    6767

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering.

    C/T chamber busbars

    C/T Enclosure General Specifies busbar arrangements within CT Enclosures.

    Busbars shall be installed in the one direction within the C/T chamber i.e. enter the C/T chamber vertically then they remain vertical until the busbars have exited the C/T chamber.

    6868

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering. C/T Fuses clause amended

    Clause expanded to include the requirement for safe operation of fuse carriers.

    6969

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes - Section Eight (8) Metering.

    Section 8 now includes new clause 8.12; - Metering Communications Equipment.

    Communications Cabling, Communications equipment power cabling and antenna cabling.

    Communications Devices.

    External or Remote Antenna.

    Customer and third party provided Communication Equipment (e.g. HAN repeater)

    7070

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes 2005 to 2014 SIRs.

    The EndQuestion Time

    (Metering Diagrams Follow)

    7171

    Service and Installation Rules NECAJanuary - February - March 2014

    7272

    Service and Installation Rules NECAJanuary - February - March 2014

  • 17/04/2014

    13

    7373

    Service and Installation Rules NECAJanuary - February - March 2014

    7474

    Service and Installation Rules NECAJanuary - February - March 2014

    7575

    Service and Installation Rules NECAJanuary - February - March 2014

    7676

    Service and Installation Rules NECAJanuary - February - March 2014

    7777

    Service and Installation Rules NECAJanuary - February - March 2014

    7878

    Service and Installation Rules NECAJanuary - February - March 2014

    Changes 2005 to 2014 SIRs.

    Direct connected meters

    An approved panel mounted fuse/s adjacent to the occupancy meter.Current Transformer meters

    An approved switch or circuit breaker.