STRAIGHT CHEMICAL GROUND RODLP-21E
07/02 PREVECTRON 4 EASE LIGHTNING PROTECTION SYSTEMS
NLP #TR-1 REINFORCED CONCRETE GROUND INSPECTION WELL WITH CAST IRON LID MARKED "GROUND". FOR LOCATIONS REQUIRING VANDAL RESISTANT LID USE NLP #TR-1/VR. MOUNT WELL FLUSH WITH FINISHED GRADE. COORDINATE INSTALLATION WITH THE GENERAL CONTRACTOR.
18" NLP #28 COPPER PIGTAIL FOR CONNECTION WITH DOWN CONDUCTOR OR GROUND LEAD. MAKE CONNECTION WITH BURNDY HYGROUND YGHC34C29 COPPER HIGH COMPRESSION CONNECTOR.
FACTORY INSTALLED WELD CONNECTION
BURIAL DEPTH INDICATOR
CHEMICAL LEACHING HOLE
NLP #C10S-28 CHEMICAL GROUND ELECTRODE
10" DIAMETER AUGURED HOLE BACK FILLED WITH SOIL BENTONITE AND WATER MIXTURE.
NOTES:
THE GENERAL CONTRACTOR SHALL CLEARLY MARK ALL OTHER SYSTEMS BELOW GRADE PRIOR TO THE COMMENCEMENT OF THE GROUND SYSTEM INSTALLATION.