2
 National Lightning Protection Corp. 4120 Brighton Boulevard, Unit A-37 Denver, Colorado 80216 800/628.2816 http://www.theprotectionsource.com L SHAPE CHEMICAL GROUND ROD LP-22E 07/02 PREVECTRON 4 EASE LIGHTNING PROTECTION SYSTEMS NOTES: THE GENERAL CONTRACTOR SHALL CLEARLY MARK ALL OTHER SYSTEMS BELOW GRADE PRIOR TO THE COMMENCEMENT OF THE GROUND SYSTEM INSTALLATION. 18" NLP #28 COPPER PIGTAIL FOR CONNECTION WITH DOWN CONDUCTOR OR GROUND LEAD. MAKE CONNECTION WITH BURNDY HYGROUND YGHC34C29 COPPER HIGH COMPRESSION CONNECTOR. NLP #TR-1 REINFORCED CONCRETE GROUND INSPECTION WELL WITH CAST IRON LID MARKED "GROUND". FOR LOCATIONS REQUIRING VANDAL RESISTANT LID USE NLP #TR-1/VR. MOUNT WELL FLUS H WITH FINISHED GRADE. COORDINATE INSTALLATION WITH THE GENERAL CONTRACTOR. FACTORY INSTALLED WELD CONNECTION NLP #C10L-2 8 L SHAPE CHEMICAL GROUND ELECTRODE CHEMICAL LEACHING HOLE BRACE ROD A MINIMUM OF 2" ABOVE THE BOTTOM OF THE TRENCH TO ALLOW C-ROD TO BE COMPLETELY ENCASED IN THE BACK FILL . TRENCH 12" WIDE X 11' 0" LONG X 30" DEEP. BACK FILL  AROUND C-ROD WITH SOIL, B ENTONITE, AND WATE R MIXTURE.

NFPA- L-shape Chemical Rod Dwg

Embed Size (px)

DESCRIPTION

grounding

Citation preview

  • National Lightning Protection Corp.4120 Brighton Boulevard, Unit A-37

    Denver, Colorado 80216800/628.2816

    http://www.theprotectionsource.com

    L SHAPE CHEMICAL GROUND RODLP-22E

    07/02 PREVECTRON 4 EASE LIGHTNING PROTECTION SYSTEMS

    NOTES:

    THE GENERAL CONTRACTOR SHALL CLEARLY MARK ALL OTHER SYSTEMS BELOW GRADE PRIOR TO THE COMMENCEMENT OF THE GROUND SYSTEM INSTALLATION.

    18" NLP #28 COPPER PIGTAIL FOR CONNECTION WITH DOWN CONDUCTOR OR GROUND LEAD. MAKE CONNECTION WITH BURNDY HYGROUND YGHC34C29 COPPER HIGH COMPRESSION CONNECTOR.

    NLP #TR-1 REINFORCED CONCRETE GROUND INSPECTION WELL WITH CAST IRON LID MARKED "GROUND". FOR LOCATIONS REQUIRING VANDAL RESISTANT LID USE NLP #TR-1/VR. MOUNT WELL FLUSH WITH FINISHED GRADE. COORDINATE INSTALLATION WITH THE GENERAL CONTRACTOR.

    FACTORY INSTALLED WELD CONNECTION

    NLP #C10L-28 L SHAPE CHEMICAL GROUND ELECTRODE

    CHEMICAL LEACHING HOLE

    BRACE ROD A MINIMUM OF 2" ABOVE THE BOTTOM OF THE TRENCH TO ALLOW C-ROD TO BE COMPLETELY ENCASED IN THE BACK FILL .

    TRENCH 12" WIDE X 11' 0" LONG X 30" DEEP. BACK FILL AROUND C-ROD WITH SOIL, BENTONITE, AND WATER MIXTURE.