5
NFPA-25 INSPECTION, TESTING AND MAINTENANCE OF WET PIPE FIRE SPRINKLER SYSTEM Information on this form covers the minimum requirements of NFPA 25-2011 for fire sprinkler systems connected to distribution systems not including supplemental tanks or fire pumps. Separate forms are available to inspect, test, and maintain the remainder of the fire protection systems. More frequent inspection, testing and maintenance may be necessary depending on the conditions of the occupancy and the water supply. Owner: _____________________________________________________________________________________ WO#: ____________________________ Report#: _______________________________ Owner’s Address: _________________________________________________________________________ Owner's Phone Number: _____________________________________________________ Property Being Evaluated: __________________________________________________________________________________________________________________________________________________ Property Address: ___________________________________________________________________________________________________ Time Of Inspection:_________________________________ Date of Work: ____________________________________ All responses refer to the current work (inspection, testing and maintenance) performed on this date. This work is (check one): Weekly Monthly Quarterly Semiannual Annual Fifth Year Part I – Owners Section Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No ____________________________________ _____________________________ _______________ Owner or Representative (Print) Signature. Date. Part II – Inspector’s Section Owner or Rep. not on site. A. INSPECTIONS 1. Daily and Weekly Items A. Control valves supervised with seals in correct (open or closed) position? Yes No N/A B. Backflow Preventers: 1. Valves in correct (open or closed) position? Yes No N/A 2. Sealed, locked or supervised & accessible? Yes No N/A 3. Relief port on RPZ device not discharging? Yes No N/A C. For freezer systems, is the gauge near the compressor reading the same as the gauge near the drypipe valve? Yes No N/A 2. Monthly Inspection ems in ddition o bove tems) A. Control valves with locks or electrical supervision in correct (open or closed) position? Yes No N/A B. Sprinkler wrench with spare sprinklers? Yes No N/A C. Gauges on wetpipe system in good condition and showing normal water supply pressure? Yes No N/A D. Alarm Valves: Gauges show normal supply water pressure, free from physical damage, valves in correct (open or closed) position and no leakage from retarding chamber or drains? Yes No N/A 3. Quarterly Inspection Items (in addition to above items) A. Pressure Reducing Valve: In open position, not leaking, maintaining downstream pressure per design criteria, and in good condition with hand wheels not broken? Yes No N/A Design criteria is not available B. Hydraulic nameplate (calculated systems) securely attached to riser and legible? Yes No N/A C. Fire Department Connection: Visible, accessible, couplings and swivels not damaged and rotate smoothly, plugs or caps in place and undamaged, gaskets in place and in good condition, identification sign(s) in place, check valve is not leaking, clapper is in place and operating properly and automatic drain valve in place and operating properly? Yes No N/A (If plugs or caps are not in place, inspect interior for obstructions.) D. Alarm devices free from physical damage? Yes No N/A 4. Annual Inspection Items A. Proper number and type of spare sprinklers? Yes No N/A B. Visible sprinklers: 1. Free of corrosion and physical damage? Yes No N/A 2. Free of obstructions to spray patterns? Yes No N/A 3. Free of foreign materials including paint? Yes No N/A 4. Liquid in all glass bulb sprinklers? Yes No N/A C. Visible pipe: 1. In good condition/no external corrosion? Yes No N/A 2. No mechanical damage and no leaks? Yes No N/A 3. Properly aligned and no external loads? Yes No N/A D. Visible pipe hangers and seismic braces not damaged or loose? Yes No N/A E. Hose, hose couplings and nozzles on sprinkler system passed inspection in accordance with NFPA 1962? NIC Yes No N/A F. Adequate heat in areas with wet piping? Yes No N/A G. Has an internal inspection of the pipe been performed by removing the flushing connection and one sprinkler near the end of a branch line within the last 5 years? NIC Yes No N/A (If the answer was "No", an internal inspection is required.) 5. Fifth Year Inspection Items A. Alarm valves and their associate strainers, filters and restriction orifices passed internal inspection? NIC Yes No N/A B. Check valves internally inspected and all parts operate properly, move freely and are in good condition? NIC Yes No N/A B.Testing The following tests are to be performed at the noted intervals. Report any failures on Part III of this form. 1. Quarterly Tests A. Mechanical water flow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed? Yes No N/A B. Post indicating valves opened until spring or torsion is felt in the rod, then closed back onequarter turn? Yes No N/A C. Main drain test for system downstream of backflow or pressure reducing valve: 1. Static Residual Return 2. Was flow observed? Yes No N/A 3. Are results comparable to previous test? Yes No N/A 2. Semiannual Test. A. Valve supervisory switches indicate movement? Yes No N/A B. Electrical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed? Yes No N/A ________ ________ ________ A. Is the building occupied? B. Has the occupancy classification and hazard of content remained The same since the last inspection? C. Are all fire protection systems in service? D. Has the system remained in service without modification since last inspection? E. Was the system free of actuation of devices or alarms since the last inspection? F. Weekly logs of inspections required by NFPA 25 on file? G. All deficiencies reported at last inspection corrected? H. I know the location and understand the operation of all control valves. I. I would like to have a copy of the NFPA 25 at an extra charge of $50.00 J. Owner or Rep. requests DynaFire to release information from inspections to the Underwriters of my insurance company. FORM ID: SPRK07 FP16481600012009 EF20000528 Florida PE 26483 NICET IV 99907 FPC15-000057 1 0 9 - B C o n c o r d D r i v e Casselberry, Florida Phone: 407- 830-6500 www.DynaFire.com 1-Riser=6-Floors Hampton Inn-Altamonte Altamonte Springs FL 32714 11238451 161 Douglas Ave (407) 331-0220 Hampton Inn-Altamonte 08/09/2016 10:00am EDT Altamonte Springs FL 32714 161 Douglas Ave 08/09/2016

NFPA-25 INSPECTION, TESTING AND …€¦ · nfpa-25 inspection, testing and maintenance of wet pipe fire sprinkler system ... nfpa 1962? yes nicno n/a

  • Upload
    vuthien

  • View
    302

  • Download
    4

Embed Size (px)

Citation preview

Page 1: NFPA-25 INSPECTION, TESTING AND …€¦ · nfpa-25 inspection, testing and maintenance of wet pipe fire sprinkler system ... nfpa 1962? yes nicno n/a

NFPA-25 INSPECTION, TESTING AND MAINTENANCE OF WET PIPE FIRE SPRINKLER SYSTEM Information on this form covers the minimum requirements of NFPA 25-2011 for fire sprinkler systems connected to distribution systems not including

supplemental tanks or fire pumps. Separate forms are available to inspect, test, and maintain the remainder of the fire protection systems. More frequent inspection, testing and maintenance may be necessary depending on the conditions of the occupancy and the water supply.

Owner:  _____________________________________________________________________________________        WO#:  ____________________________        Report#:  _______________________________  

Owner’s  Address:  _________________________________________________________________________  Owner's  Phone  Number:  _____________________________________________________ �

Property  Being  Evaluated:  __________________________________________________________________________________________________________________________________________________  

Property  Address:  ___________________________________________________________________________________________________  Time Of Inspection:_________________________________  

Date  of  Work:  ____________________________________        All � responses� refer � to � the � current �work (inspection, � testing � and �maintenance) � performed � on � this � date.  

This  work  is  (check  one):                    Weekly              Monthly              Quarterly                            Semiannual   Annual        Fifth  Year  

Part I – Owners Section

Yes� � � No�

Yes� � � No� Yes� � � No� Yes� � � No� Yes� � � No� Yes� � � No� Yes� � � No� Yes� � � No� Yes� � � No�

Yes� � � No�

____________________________________� � � � _____________________________� � � � � � _______________�Owner�or�Representative� � � � � � (Print)�        Signature.�

� � Date.�

Part II – Inspector’s Section Owner� or� Rep.� not� on� site.

A.� INSPECTIONS �1. � Daily � and �Weekly � Items �A.  Control  valves  supervised  with  seals  in  correct  (open  or  closed)

               position?                      Yes        No        N/A          B.  Backflow  Preventers:  

1.  Valves  in  correct  (open  or  closed)  position?            Yes        No        N/A  2.  Sealed,  locked  or  supervised  &  accessible?              Yes        No        N/A  3.  Relief  port  on  RPZ  device  not  discharging?            Yes        No        N/A  

       C.  For  freezer  systems,  is  the  gauge  near  the  compressor  reading  the                  same  as  the  gauge  near  the  dry-­‐pipe  valve?                  Yes                    No        N/A    2. �Monthly � Inspection �� � ems � � in �� ddition �� o �� bove �� tems) �A.  Control  valves  with  locks  or  electrical  supervision  in  correct  (open  or

               closed)  position?                Yes        No        N/A          B.  Sprinkler  wrench  with  spare  sprinklers?                Yes        No        N/A          C.  Gauges  on  wet-­‐pipe  system  in  good  condition  and  showing  normal                  water  supply  pressure?                Yes        No        N/A          D.  Alarm  Valves:  Gauges  show  normal  supply  water  pressure,                    free  from  physical  damage,  valves  in  correct  (open  or  closed)  position                    and  no  leakage  from  retarding  chamber  or  drains?                Yes        No        N/A  3.� Quarterly � Inspection � Items � (in � addition � to � above � items)�A.  Pressure  Reducing  Valve:  In  open  position,  not  leaking,  maintaining

               downstream  pressure  per  design  criteria,  and  in  good  condition  with                  hand  wheels  not  broken?                Yes        No        N/A  

                     Design  criteria  is  not  available          B.  Hydraulic  nameplate  (calculated  systems)  securely  attached  to  riser                  and  legible?                Yes                    No                    N/A          C.  Fire  Department  Connection:                  Visible,  accessible,  couplings  and  swivels  not  damaged  and  rotate                  smoothly,  plugs  or  caps  in  place  and  undamaged,  gaskets  in  place  and                  in  good  condition,  identification  sign(s)  in  place,  check  valve  is  not                  leaking,  clapper  is  in  place  and  operating  properly  and  automatic  drain                  valve  in  place  and  operating  properly?                  Yes                    No        N/A                  (If  plugs  or  caps  are  not  in  place,  inspect  interior  for  obstructions.)  

D.  Alarm  devices  free  from  physical  damage?                Yes        No        N/A  

4.� Annual � Inspection � Items �A.  Proper  number  and  type  of  spare  sprinklers?            Yes        No        N/A  B.  Visible  sprinklers:1.  Free  of  corrosion  and  physical  damage?              Yes        No        N/A    2.  Free  of  obstructions  to  spray  patterns?              Yes        No        N/A  3.  Free  of  foreign  materials  including  paint?            Yes        No        N/A  4.  Liquid  in  all  glass  bulb  sprinklers?              Yes        No        N/A  

       C.  Visible  pipe:  1.  In  good  condition/no  external  corrosion?              Yes        No        N/A  2.  No  mechanical  damage  and  no  leaks?            Yes        No        N/A  3.  Properly  aligned  and  no  external  loads?              Yes        No        N/A  

       D.  Visible  pipe  hangers  and  seismic  braces  not  damaged  or  loose?                Yes        No        N/A  

       E.  Hose,  hose  couplings  and  nozzles  on  sprinkler  system  passed                    inspection  in  accordance  with  NFPA  1962?                          NIC        Yes        No        N/A          F.  Adequate  heat  in  areas  with  wet  piping?                Yes        No        N/A          G.  Has  an  internal  inspection  of  the  pipe  been  performed  by  removing                  the  flushing  connection  and  one  sprinkler  near  the  end  of  a  branch                  line  within  the  last  5  years?                            NIC                    Yes                    No        N/A                  (If the answer was "No", an internal inspection is required.) 5.� Fifth � Year� Inspection � Items�A.  Alarm  valves  and  their  associate  strainers,  filters  and  restriction

               orifices  passed  internal  inspection?                          NIC        Yes        No        N/A          B.  Check  valves  internally  inspected  and  all  parts  operate  properly,  move                  freely  and  are  in  good  condition? NIC        Yes        No        N/A  

B.Testing �The following tests are to be performed at the noted intervals. Report any failures on Part III of this form.

1. � Quarterly � Tests �A.  Mechanical  water  flow  alarm  devices  passed  tests  by  opening  the

               inspector's  test  connection  or  bypass  connection  with  alarms  actuating                  and  flow  observed?                  Yes        No        N/A          B.  Post  indicating  valves  opened  until  spring  or  torsion  is  felt  in  the  rod,                  then  closed  back  one-­‐quarter  turn?                Yes        No        N/A          C.  Main  drain  test  for  system  downstream  of  backflow  or  pressure  reducing  valve:  

1.� Static          Residual � �          Return �

2.  Was  flow  observed?              Yes        No        N/A  3.  Are  results  comparable  to  previous  test?              Yes        No        N/A  

2.� Semiannual � Test. �A.  Valve  supervisory  switches  indicate  movement?            Yes    No        N/A  B.  Electrical  waterflow  alarm  devices  passed  tests  by  opening  the

                 inspector's  test  connection  or  bypass  connection  with  alarms  actuating                    and  flow  observed?                    Yes                    No          N/A  

________ ________________

A.  Is  the  building  occupied?                B.  Has  the  occupancy  classification  and  hazard  of  content  remained            The  same  since  the  last  inspection?��C.  Are  all  fire  protection  systems  in  service?���D.  Has  the  system  remained  in  service  without  modification  since  last  inspection?  E.  Was  the  system  free  of  actuation  of  devices  or  alarms  since  the  last  inspection?�F.  Weekly  logs  of  inspections  required  by  NFPA  25  on  file?���G.  All  deficiencies  reported  at  last  inspection  corrected?��H.  I  know  the  location  and  understand  the  operation  of  all  control  valves.���  I.    I  would  like  to  have  a  copy  of  the  NFPA  25  at  an  extra  charge  of  $50.00      J.    Owner  or  Rep.  requests  DynaFire  to  release  information  from  inspections  to  the            Underwriters  of  my  insurance  company.    

FORM ID: SPRK07

FP16481600012009 EF20000528 Florida PE 26483 NICET IV 99907 FPC15-000057

109-B Concord Drive Casselberry, Florida

Phone: 407-830-6500 www.DynaFire.com

1-Riser=6-FloorsHampton Inn-Altamonte

Altamonte Springs FL 32714

11238451

161 Douglas Ave (407) 331-0220

Hampton Inn-Altamonte

08/09/2016 10:00am EDT

Altamonte Springs FL 32714161 Douglas Ave

08/09/2016

Page 2: NFPA-25 INSPECTION, TESTING AND …€¦ · nfpa-25 inspection, testing and maintenance of wet pipe fire sprinkler system ... nfpa 1962? yes nicno n/a

NFPA  25  Wet  Pipe  Sprinkler  System  Report  (Page  2)  

3.  Annual  Test.A.  Main  drain  test:1. Static Residual Return

2.  Was  flow  observed?              Yes        No        N/A  3.  Are  results  comparable  to  previous  test?            Yes        No        N/A  

         B.  Are  all  sprinklers  date  1920  or  later?                  Yes        No        N/A            C.  Fast  response  sprinklers  20  or  more  years  old  replaced  or  successfully                    sample  tested  within  last  10  years?                Yes        No        N/AD. Standard response sprinklers 50 or more years old replaced or

                 successfully  sample  tested  within  last  10  years?                Yes        No        N/A            E.  Standard  response  sprinklers  75  or  more  years  old  replaced  or                    successfully  sample  tested  within  last  5  years?                Yes        No        N/A            F.  Dry-­‐type  sprinkler  replaced  or  successfully  sample  tested                    within  last  10  years?                Yes        No        N/A            G.  Specific  gravity  of  antifreeze  correct?                Yes        No        N/A            H.  All  control  valves  operated  through  full  range  and  returned  to  normal                    position?                Yes        No        N/A            I.  Backflow  devices  passed  backflow  test?                          NIC                    Yes        No        N/A            J.  Backflow  devices  passed  full  flow  test?                            NIC        Yes        No        N/A            K.  Pressure  reducing  valves  passed  partial  flow  test?    

NIC        Yes        No        N/A              4.  Test  to  be  done  every  third  year:Hose  (more  than  5  years  old)  connected  to  the  system  has  been  service  tested  in  accordance  with  NFPA  1962.  Water  discharged  and  water  flow  alarms  operated?  

NIC        Yes        No        N/A  5.  Test  to  be  done  every  5th  yearA.  Sprinklers  rated  above  High  temperature  tested?            NIC                    Yes       No        N/A  B.  Gauges  checked  by  calibrated  gauge  or  replaced?    Yes        No        N/A  C.  Pressure  reducing  valves  passed  full  flow  test?                      NIC                    Yes        No        N/A  

C.  Maintenance  1.  Regular  Maintenance  ItemsA.  If  sprinklers  have  been  replaced,  were  they  proper  replacements?

Yes                    No                    N/A        Cannot  Determine            B.  Used  hose  was  cleaned,  drained  and  dried  before  being  placed  back  in                    service? Hose  exposed  to  hazardous  materials  was  disposed  of  or                    decontaminated  in  an  approved  manner?    

             Yes                    No                    N/A        Cannot  Determine            C.  Systems  normally  filled  with  fresh  water  were  drained  and                    refilled  twice if  raw  water  got  into  the  system?    

             Yes                    No        N/A        Cannot  Determine            D.  If  any  of  the  following  were  discovered,  was  an  obstruction  investigation                    conducted?                            NIC        Yes                    No                  N/A  

1.  Defective  intake  screen  on  pump  with  suction  from  open  sources.  2.  Obstructive  material  discharged  during  water  flow  tests.3.  Foreign  materials  found  in  dry-­‐pipe  valves,  check  valves  or  pumps.4.  Foreign  material  in  water  during  drain  test  or  plugging  of  inspector's  test

                   connection.  5.  Plugging  of  pipe  or  sprinklers  found  during  activation  or  alteration.6.  Failure  to  flush  yard  piping  or  surrounding  public  mains  following  newinstallation  or  repairs.  

7.  Record  of  broken  mains  in  the  vicinity.8.  Abnormally  frequent  false-­‐tripping  of  dry-­‐pipe  valves.9.  System  is  returned  to  service  after  an  extended  period  out  of  service  (greater  than  one  year).  

10.  There  is  reason  to  believe  the  system  contains  sodium  silicate  or  itsderivatives  or  highly  corrosive  fluxes  in  copper  pipe  systems.

             E.  If  conditions  were  found  that  required  flushing,  was  flushing  of  system  conducted?                        NIC                    Yes                    No        N/A  

2.  Annual  Maintenance  ItemsA.  Operating  stem  of  all  OS&Y  valves  lubricated  completely  closed,  and

                   reopened?                      Yes                    No              N/A            B.  Sprinklers  and  spray  nozzles  protecting  commercial  cooking  equipment                    and  ventilating  systems  replaced  except  for  bulb-­‐type  which  show  no                signs  of  grease  buildup?                Yes        No        N/A  3.  Regular  Maintenance  ItemsA.  Alarm  panel  clear?            Yes        No        N/A  B.  System  left  in  service?            Yes        No        N/A  C.  Is  system  impaired?  (Impairment  program  put  into  place  per  NFPA-­‐25  &  

                   DynaFire  Protocols.)      Yes        No    

��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������

����������������������������������������������������������������������������������������������������������������������������������������������������������������������������

�����������������������  ��������������������������������������� �������������������������������������������������������� ���� ����� ���� ���������� ������� ��� ����� ����� ���� ����� ��� ��������������������������������������������������������������������������������������������

Date:_____________________________________  

������������������������_________________________________________�

����������� __________________________________________________

���������� ___________________________________________________�

�����������������������������:�

RED GREEN

Explain reason(s) and obstruction investigation finding in Part III

________ ________ ________

08/09/2016 10:00am EDT

Kevin Mancuso

141913

Room 611 painted 155 white QR residential 1/2" pendant head at entry. Room 308 painted 155 white QR residential 1/2" pendant head at entry.

Seals=14042,14041,14040,14039,14038, 14037,14036,14035,14034,14033,14032.

Page 3: NFPA-25 INSPECTION, TESTING AND …€¦ · nfpa-25 inspection, testing and maintenance of wet pipe fire sprinkler system ... nfpa 1962? yes nicno n/a

Work Order #:________________

Backflow Preventor Inspection Report

Customer Name:__________________________________________________________ Phone Number:____________

Property Address:___________________________________________________________________________________

Contractor: DynaFire Inc. License Number: FP 16481600012009

Location of Assembly:__________________________________________________ Domestic:______ Irrigation:______

Type of Assembly: RPZ DC DCDA PVB Size: _________Fire Main: ______ Bypass: ___________

Manufacturer: ___________________________ Model: _________________ Serial #: _________________

Meter: ______________________ Old Serial if applicable #: ___________ New Serial if applicable#: ____________

Check

Valve # 1

Relief

Valve

Check

Valve # 2

Pressure

Vacuum Breaker

Leaked: Leaked: Air Inlet:

Opened At:__________ PSI

Did Not Open

Closed Tight: Did Not Open: Closed Tight: Check Valve:

Leaked:

Differential Pressure

Across Check Valve

____________ PSI Opened

At:__________ PSI

Differential Pressure

Across Check Valve

____________ PSI

Cleaned Only: Cleaned Only: Cleaned Only: Cleaned Only:

Replaced: Replaced: Replaced: Replaced:

Rubber Kit Rubber Kit Rubber Kit Rubber Kit

Check Valve Assembly Check Valve

Assembly

Check Valve

Assembly

Check Valve

Assembly

Disc Disc Disc Disc

O-Rings O-Rings O-Rings O-Rings

Seat Seat Seat Seat

Spring Spring Spring Spring

Stem/Guide Stem/Guide Stem/Guide Stem/Guide

Retainer Retainer Retainer Retainer

Lock Nuts Lock Nuts Lock Nuts Lock Nuts

Other:_______________ Other:______________ Other:____________________ Other:______________________

Note: All Repairs shall be completed within thirty (30) days. Device Pass Device Fail

Remarks: _______________________________________________________________________________________________

I state that the information on this form is correct and reflects the proper operation and maintenance of the assembly.

Tester: _____________________ Certification # ________________________________ Date: __________________________

Gauge # _________________________ Date of Last Calibration: ____________________________________________

FORM ID: SPRK01

FP16481600012009 EF20000528 Florida PE 26483 NICET IV 99907 FPC15-000057

109-B Concord Drive Casselberry, Florida

Phone: 407-830-6500 www.DynaFire.com

11238451

Hampton Inn-Altamonte (407) 331-0220161 Douglas Ave

In front by road

✔ 6 X

Watts 757 MJ-3567

✔ ✔

3.0 4.2

Kevin Mancuso A09-15-10029 8-9-16

10151822 11/18/2015

Add New Page

Altamonte Springs FL 32714

Page 4: NFPA-25 INSPECTION, TESTING AND …€¦ · nfpa-25 inspection, testing and maintenance of wet pipe fire sprinkler system ... nfpa 1962? yes nicno n/a

Work Order #:________________

Backflow Preventor Inspection Report

Customer Name:__________________________________________________________ Phone Number:____________

Property Address:___________________________________________________________________________________

Contractor: DynaFire Inc. License Number: FP 16481600012009

Location of Assembly:__________________________________________________ Domestic:______ Irrigation:______

Type of Assembly: RPZ DC DCDA PVB Size: _________Fire Main: ______ Bypass: ___________

Manufacturer: ___________________________ Model: _________________ Serial #: _________________

Meter: ______________________ Old Serial if applicable #: ___________ New Serial if applicable#: ____________

Check

Valve # 1

Relief

Valve

Check

Valve # 2

Pressure

Vacuum Breaker

Leaked: Leaked: Air Inlet:

Opened At:__________ PSI

Did Not Open

Closed Tight: Did Not Open: Closed Tight: Check Valve:

Leaked:

Differential Pressure

Across Check Valve

____________ PSI Opened

At:__________ PSI

Differential Pressure

Across Check Valve

____________ PSI

Cleaned Only: Cleaned Only: Cleaned Only: Cleaned Only:

Replaced: Replaced: Replaced: Replaced:

Rubber Kit Rubber Kit Rubber Kit Rubber Kit

Check Valve Assembly Check Valve

Assembly

Check Valve

Assembly

Check Valve

Assembly

Disc Disc Disc Disc

O-Rings O-Rings O-Rings O-Rings

Seat Seat Seat Seat

Spring Spring Spring Spring

Stem/Guide Stem/Guide Stem/Guide Stem/Guide

Retainer Retainer Retainer Retainer

Lock Nuts Lock Nuts Lock Nuts Lock Nuts

Other:_______________ Other:______________ Other:____________________ Other:______________________

Note: All Repairs shall be completed within thirty (30) days. Device Pass Device Fail

Remarks: _______________________________________________________________________________________________

I state that the information on this form is correct and reflects the proper operation and maintenance of the assembly.

Tester: _____________________ Certification # ________________________________ Date: __________________________

Gauge # _________________________ Date of Last Calibration: ____________________________________________

FORM ID: SPRK01

FP16481600012009 EF20000528 Florida PE 26483 NICET IV 99907 FPC15-000057

109-B Concord Drive Casselberry, Florida

Phone: 407-830-6500 www.DynaFire.com

11238451

Hampton Inn-Altamonte (407) 331-0220161 Douglas Ave

In front by road

✔ 3/4" XWatts 007M3 205932

✔ ✔

3.2 2.2

Kevin Mancuso A09-15-10029 8-9-16

10151822 11/18/2015

Add New Page

Altamonte Springs FL 32714

Page 5: NFPA-25 INSPECTION, TESTING AND …€¦ · nfpa-25 inspection, testing and maintenance of wet pipe fire sprinkler system ... nfpa 1962? yes nicno n/a

Work Order #:________________

Backflow Preventor Inspection Report

Customer Name:__________________________________________________________ Phone Number:____________

Property Address:___________________________________________________________________________________

Contractor: DynaFire Inc. License Number: FP 16481600012009

Location of Assembly:__________________________________________________ Domestic:______ Irrigation:______

Type of Assembly: RPZ DC DCDA PVB Size: _________Fire Main: ______ Bypass: ___________

Manufacturer: ___________________________ Model: _________________ Serial #: _________________

Meter: ______________________ Old Serial if applicable #: ___________ New Serial if applicable#: ____________

Check

Valve # 1

Relief

Valve

Check

Valve # 2

Pressure

Vacuum Breaker

Leaked: Leaked: Air Inlet:

Opened At:__________ PSI

Did Not Open

Closed Tight: Did Not Open: Closed Tight: Check Valve:

Leaked:

Differential Pressure

Across Check Valve

____________ PSI Opened

At:__________ PSI

Differential Pressure

Across Check Valve

____________ PSI

Cleaned Only: Cleaned Only: Cleaned Only: Cleaned Only:

Replaced: Replaced: Replaced: Replaced:

Rubber Kit Rubber Kit Rubber Kit Rubber Kit

Check Valve Assembly Check Valve

Assembly

Check Valve

Assembly

Check Valve

Assembly

Disc Disc Disc Disc

O-Rings O-Rings O-Rings O-Rings

Seat Seat Seat Seat

Spring Spring Spring Spring

Stem/Guide Stem/Guide Stem/Guide Stem/Guide

Retainer Retainer Retainer Retainer

Lock Nuts Lock Nuts Lock Nuts Lock Nuts

Other:_______________ Other:______________ Other:____________________ Other:______________________

Note: All Repairs shall be completed within thirty (30) days. Device Pass Device Fail

Remarks: _______________________________________________________________________________________________

I state that the information on this form is correct and reflects the proper operation and maintenance of the assembly.

Tester: _____________________ Certification # ________________________________ Date: __________________________

Gauge # _________________________ Date of Last Calibration: ____________________________________________

FORM ID: SPRK01

FP16481600012009 EF20000528 Florida PE 26483 NICET IV 99907 FPC15-000057

109-B Concord Drive Casselberry, Florida

Phone: 407-830-6500 www.DynaFire.com

11238451

Hampton Inn-Altamonte (407) 331-0220161 Douglas Ave

Up front by road X✔ 4"

Watts 957 NC-1322

✔ ✔

12.22.6

3.0

Kevin Mancuso A09-15-10029 8-9-16

10151822 11/18/2015

Add New Page

Altamonte Springs FL 32714