Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 1
Conceptpower Modular80 and 100kVA
THE BEST WAY TO PREDICT THE FUTURE IS TO INVENT IT
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 2
Unique Power Protection Concept (PPC)
6 Key-Features at a Glance
Modularity
Redundancy
Scalability
Environmentally Friendly
Serviceability
Manageability
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 3
ConceptpowerTM Modular
First and unique hot swappable 3phase double conversion (VFI) UPS modular design
2 possible power ranges:
80 and 100kVA
Modularity
Welcome to the future of power protection
Batt. Batt.Charge
r
Static Bypass
Rect. Boost.
Inverter
Load
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 4
ConceptpowerTM Module
Front view 80-100kVA
Passive module includes:• Input filter• Output filter• Booster coils• Static By-pass
Active module includes:• Rectifier & Booster• Battery charger• Inverter• µProcessor control board
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 5
ConceptpowerTM Module
Front view 80-100kVADry contacts
NC/NO, D25P/Fconnection
EPO, Gen-on, Batt.temp.connector
LCD Display Panelconnector
Module Interfaceconnector
Smart port RS232
By-pass line fuses
ComBus Module to Module
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 6
ConceptpowerTM Module
Weight of the passive module80-100 kVA: 55-60 Kg
Size of the UPS module:667x412x834mm (WxHxD)
Weight of the active module80-100 kVA: 55-60 Kg
Size of the UPS module:667x412x834mm (WxHxD)
Rear view 80-100kVA
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 7
ConceptpowerTM Module
Inside view 80-100kVA
InverterBooster
Batt. Charger
DC Cap.
µ Control boardBy-pass
Input LCFIlter
OutputLC Filter
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 8
ConceptpowerTM Modular
Welcome to the future of power protection
Power modules: 80-100 kVA
Upgrade frame 300 kVA
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 9
ConceptpowerTM Modular
UPGRADE FRAMEPower modules: 80-100kVA
Limited up to 10 modules in parallel (> 10 modules on request)
Distribution section for the max. capacity (300kVA)
Space saving, 300kVA in 1.22 sqm.
No single point of failureUPS – module 2
Distribution300kVA
UPS – module 3
UPS – module 1
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 10
ConceptpowerTM Modular
UPGRADE FRAME DISTRIBUTION 300KVA
Modules output disconnects
Centralized MaintenanceBy-pass
Centralized SNMP Slot (Multidrop).
DPA extension bus
RS232, PFC, EPO
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 11
ConceptpowerTM Modular - Scalability
Optimized capital investment by extending your power protection capacity at a pace that fits your business on demand
Scalable performance of the power capacity and runtime by simply adding independent UPS or battery increments
Upgrade Frame (Vertical Scalability)(floor-saving-frame)
UPS – module 2
Distribution300kVA
UPS – module 3
UPS – module 1
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 12
No additional hardware for harmonic reduction is required
ConceptpowerTM Modular Environmentally Friendly
1997/06/03 10:54:36 5ms/div
(5ms/div) NORM:200kS/s
Input Voltage
Input Current
Sinewave input current (THD=7-9%)
Input PF=0.98 in a standard version
This means:
Smaller cables size and lower losses
Smaller fuses or Circuit Breakers
(no malfunction and false tripping)
No separate phase compensation required
No extra heating of transformer and generators oversized
6-pulse rectifier
12-pulse rectifier
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 13
The total annual operating costs for a Newave UPS can be >40% less compared to those for a previous generation
ConceptpowerTM Modular Environmentally Friendly
Highest double-conversion efficiency ESIS (Energy Saving Inverter Switching) up to 95% in on- line, double conversion mode
Load dependent audible noise
Wide input frequency windows (35-70Hz)
Low weight (3x100kVA: 700kg)
Compact size (3x100kVA: 1.22 sqm)
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 14
ConceptpowerTM Modular Environmentally Friendly
Product positioningCase 1: configuration required 2x200kVA redundant
Legacy 2x200kVA UPS configuration
6 Pulse UPS (2x1.24 sqm)
12 Pulse rectifier (2x0.55 sqm)
Harmonic Filter& PFC (2x0.55 sqm)
Total footprint required: 4.68 sqm
Total weight: >3500Kg
UPS –2UPS –1 12 Pulse 12 PulseHarmonicFilter &PFC
HarmonicFilter &PFCUPS –
module 2
Distribution
300kVA
UPS – module
3
UPS – module
1
Modular 3x100kVA
Total footprint
required: 1.22 sqm
Total weight: 700Kg
Distribution200kV
A
UPS –1
Distribution200kV
A
UPS –2
MAXI 2x200kVA
Total footprint required: 1.8 sqm
Total weight: 1280Kg
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 15
ConceptpowerTM Modular Environmentally Friendly
Product positioningCase 2: configuration required 2x500kVA redundant
UPS – module 2
Distributio
n300kV
A
UPS – module 3
UPS – module 1
Modular 6x100kVA
Total footprint
required: 2.44 sqm
Total weight: 1400Kg
UPS – module 5
Distributio
n300kV
A
UPS – module 6
UPS – module 4
Distribution
250kVA
UPS –1
MAXI 3x250kVA
Total footprint required: 2.7 sqm
Total weight: 1980Kg
Distribution
250kVA
UPS –2
Distribution
250kVA
UPS –3
Legacy 2x500kVA UPS configuration
12 Pulse UPS (2x2.1 sqm)
Harmonic Filter& PFC (2x0.88 sqm)
Total footprint required: 5.96 sqm
Total weight: >6200Kg
UPS –1& 12 Pulse
HarmonicFilter &PFC
UPS –2& 12 Pulse
HarmonicFilter &PFC
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 16
Battery cost saving
Flexible Battery Management (FBM)
Variable DC-voltage enabling the use of battery blocks (40-50 blocks of 12VDC)
Wide input voltage windows (-23%/+15% @100% load) (-30%/+15% @<80% load) (-40%/+15% @<60% load)
Less need for battery operation
Automatic battery test with algorithm CPU controlled Early warning in case of battery fault
Temperature compensation Increases battery lifetime
Ripple free through battery charger Longer battery life time
020406080
100120
0 2 4 6 8 10
Time
Rip
ple
s
LegacyUPS
0
0,2
0,4
0,6
0,8
1
0 2 4 6 8 10
Time
Rip
ple
s ConceptpowerUPS
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 17
Modular and hot-swappable design means minimizing service and maintenance cost and
Reduction of MTTR, maximize
your power protection
availability
Front access only
No needs for skilled personnel
on site
No need of spares, just modules
ConceptpowerTM Modular Serviceability
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 18
Redundant Power Management Display advances the Power Protection Manageability
Common data execution functions for parallel systems on redundant parallel PMD’s.
The complete parallel system may be managed by any one of the parallel PMD’s.
PMD consists of mimic diagram for system status, push buttons for single module and parallel system control and LCD for monitoring, event logs and diagnosis.
ConceptpowerTM Modular Manageability
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 19
ALARM
LINE 2
LINE 1
BATTERY
BY PASS
INV RESET ENTER
LCD Display ON / OFF
ON / OFF
ConceptpowerTM Module Display
Most important information available at first glance
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 20
Remote Signalling Panel (RSP)For Status and Alarm Remote Indications
Wavemon (CD)For Automatic Server shutdownand Monitoring. Cross Platform shutdown available
SNMP-card or Box for connection of UPS in Network Management systems
ConceptpowerTM Modular Remote Control and Shutdown
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 21
1. Optimize capital investment and available space Pay-as-you-grow solution lowers your capital costs and increases utilization rates, while innovative rack-based technology frees up space previously needed for infrastructure support.
2. Adapt to ever-changing power requirements No need to abandon previous investment when power density needs increase or if physically moving your data centre. Adapt to changing wattage requirements in your racks with single- or multi-branch rack-mount power distribution units.
3. Accelerate speed of deployment Electrical and physical modularity allows for rapid installation with minimal engineering.
4. Lower the cost of service contracts Simplicity of system design and intelligent modular parts lessen the dependency on expensive service contracts.
5. Increase availability Specifically engineered to deliver higher availability through proactively designed, building block architecture and reduced MTTR
10 reasons for buying ConceptpowerTM Modular
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 22
10 reasons for buying ConceptpowerTM Modular
6. Decrease mean-time-to-recovery (MTTR) Compartmentalize potential failures with system components consisting of intelligent, maintainable modules for quick fault recovery.
7. Plan for a power density that is increasing and unpredictable Eliminate hot spots in your data centre caused by higher power densities by targeting availability where you need it most.
8. Minimize points of failure between the UPS and the critical load Move redundancy closer to the load and prevent the majority of failures that cause critical load downtime.
9. Minimize human error Simplicity of design and intelligent modules increase system availability by mitigating human error: the number one cause of critical load downtime.
10. Decrease the operating costs With efficiency up to 95% (double conversion mode), the operating costs for a Conceptpower modular UPS can be >40% less compared to those for a previous generation
Newave SA, Switzerland – [email protected] - www.newaveups.com28/02/2006 23
Swiss Quality
• INNOVATIONINNOVATION
• SUPPORTSUPPORT
• QUALITYQUALITY
Power Protection Leader Through Innovation
TO PROTECT YOUR MISSION CRITICAL APPLICATIONS