34
E
A
114
F
C
D
269
B
72.515mm plain copper coil connections
9.6mm diameter holes
Unit Ref A B C D E F
mm mm mm mm mm mm
CC 2 620 577 620 620 577 524
CC 3 613 870 915 620 577 524
CC 4 1220 1177 1220 620 577 524
CC 6 1819 1776 1820 620 577 524
For further details, please refer to GA4957
Dimensions
Mounting Height:Height x Depth:Std Widths:Mounting:Heat options:Spec options:
up to 3.0 metres269mm x 620mm620, 915, 1220, 1820mm9.6mm fixing holes provided to accommodate threaded rod (rod by others)LPHW, ElectricFinish, colour, controls
CC Miniscreen ConvectorAn economy air curtain suited to ‘recessed’ applications in a ceiling grid or false ceiling.
The fixed core grille can be removed to gain access to internal components including fans and filter. The CC unit is supplied with a velocity enhancer to provide an outlet velocity of approximately 7m/s for use as a small air curtain. By removing this enhancer, the velocity reduces to 3m/s making the CC an effective convector heater.
CC Miniscreen, Issue B - 2016© Envirotec Ltd. Due to a policy of continuous development and improvement, the right is reserved to supply products which may differ from those described in this publication.
Coil
Unit Ref Width Air Vol Connection
mm m3/s mm
CC 2 W 598 0.1 15
CC 3 W 898 0.2 15
CC 4 W 1198 0.3 15
CC 6 W 1798 0.5 15
Flow / Return 82/71oCAir Off Flow PD Output
oC l/s kPa kW
35.6 0.06 0.3 2.54
35.9 0.12 1.3 5.12
36.0 0.18 3.2 7.74
36.4 0.30 11.1 13.2
Flow / Return 80/60oCAir Off Flow PD Output
oC l/s kPa kW
- - - -
31.0 0.05 0.3 3.93
31.8 0.08 0.8 6.18
32.7 0.14 2.8 10.87
Flow / Return 70/50oCAir Off Flow PD Output
oC l/s kPa kW
- - - -
25.7 0.03 0.1 2.63
27.7 0.06 0.5 4.70
28.8 0.11 1.9 8.48
Heater Output - LPHW
Note - all LPHW heater selections are based on high fan speed and a return temperature of 15oC.Please contact our sales department should you require a heater sized to different water or air-on temperatures.
Unit Ref Width Air Vol
mm m3/s
CC 2 E 598 0.1
CC 3 E 898 0.2
CC 4 E 1198 0.3
CC 6 E 1798 0.5
2 kWAir Off PH
oC
31.5 1
- -
- -
- -
Heater Output - Electric3 kW
Air Off PHoC
- -
27.4 1
23.3 1
20.0 1
6 kWAir Off PH
oC
- -
- -
31.5 1
24.9 1
9 kWAir Off PH
oC
- -
- -
- -
29.9 3
12 kWAir Off PH
oC
- -
- -
- -
34.8 3
Note - all electric heater selections are based on high fan speed and a return temperature of 15oC.PH = Phase.
Heater Output - Heat PumpA Heat Pump version of the CC Miniscreen is not available.
The CC Miniscreen is fitted with a fixed core egg-crate grille, finished as standard in gloss white powder coat RAL9010. Removing the grille assembly provides access to the 12mm filters, fans and controls when fitted.
An alternative Miniscreen is available with a hinged core grille - refer to the Envirotec HC range for further details.
Unit Ref Width Air Vol
mm m3/s
CC 2 598 0.1
CC 3 898 0.2
CC 4 1198 0.3
CC 6 1798 0.5
MotorPower FLC SC
kW Amps Amps
0.18 0.74 1.48
0.36 1.48 2.96
0.54 2.22 4.44
0.90 3.70 7.40
General DataWiring
LPHW & Ambient units wired to:GSS544/Transformer/RS (Single speed on/off remote mounted switch)
Electric units wired to:GSS575/2 Pole Fan/Transformer(Single speed and 2 heat settings)
WeightAmbient LPHW Electric
kg kg kg
18 20 19
28 30 30
39 41 40
59 63 61
Unit weights are approximate