Upload
cristian-cuevas
View
218
Download
3
Embed Size (px)
Citation preview
Experimental Thermal and Fluid Science 27 (2003) 781–787
www.elsevier.com/locate/etfs
New approach for performance testing of air-cooled condensing units
Cristian Cuevas 1, Eric L. Winandy *
Laboratory of Thermodynamics, University of Li�eege, Campus du Sart Tilman-Baat. B49, 4000 Li�eege, Belgium
Accepted 18 November 2002
Abstract
Condensing units are designed to work with the condenser-fan component working in open space. Testing condensing units in
these conditions presents several drawbacks: difficulty to find a really infinite plenum and to avoid air shortcuts around the con-
denser inlet which means temperature variations, impossibility to measure the mass flow rate passing through the condenser. On the
other hand, separating the condenser inlet and outlet plenums means a risk of not controlling the pressure difference between the two
plenums and then overfeeding or underfeeding the condenser.
This paper discusses the advantages and disadvantages to work in one way or in another. A method is presented to avoid
condenser over or underfeeding and guarantee a low air velocity profile.
Finally, an example of a flat-coil condensing unit tested with two different fans, variable refrigerant charge and evaporating
temperature is shown to illustrate the discussion.
� 2003 Elsevier Inc. All rights reserved.
Keywords: Flat-coil condensing units; Condenser; Compressor; Experimental procedure
1. Introduction
Condensing units are designed to work outside and
normally in an open space (Fig. 1a). In practice, this is
not always the case since obstacles may be present closeto the air-cooled condenser and significantly alter the
flow. Nevertheless, laboratory testing requires special
care for the air flow going through the condenser.
ASHRAE standards [1] is not very precise about this
matter as long as ‘‘no abnormal air flow is created over
the condensing unit’’. European Standards [2] is even
less precise except ‘‘the given performance must be ap-
plied to a clean condenser’’.
1.1. Open plenum test
Common practice is to put the condensing unit in a
room where the ambient air is maintained to the set
point temperature by an air-conditioning system (Fig.
1b). But this practice may let some doubt on the real air
*Corresponding author. Tel.: +32-4-366-4800; fax: +32-4-366-4812.
E-mail addresses: [email protected] (C. Cuevas), eric.winandy@
planetmail.com (E.L. Winandy).1 Tel.: +32-4-366-4825.
0894-1777/03/$ - see front matter � 2003 Elsevier Inc. All rights reserved.
doi:10.1016/S0894-1777(02)00315-1
flow to the condenser depending on the external venti-
lation system, position of ducts.
If ventilation rates are too strong, there may be some
kinds of jets on the condenser that would overfeed it
while if ventilation rates are too low, air will shortcutthrough the condenser which will increase temperature
variations and the condensing temperature level. As an
example, Fig. 2 shows temperature records 50 mm in
front of the condenser on the air-supply side in open
plenum mode for a 13 kW cooling capacity condensing
unit. It can be seen that when the external ventilation is
too low, air shortcuts outside the condenser can induce
temperature variations up to 2 K.Another drawback of this practice is that there is no
possibility to make any balance on the air-side of the
condenser.
1.2. Separate plenums method
The second method consists in separating the con-
densing unit inlet and outlet. This method has many
advantages, since a thermal balance on the air can be
performed beside the one on the refrigerant side. A
way to do it is to install the flat coil condenser in
some kind of duct and to control the flow going
Nomenclature
h specific enthalpy, J kg�1
_HH enthalpy flow, W
LMTD logarithmic mean temperature difference, K
M mass, kg_MM mass flow rate, kg s�1
N revolution speed, Hz
Dp pressure drop, Pa_QQ heat flow, W
SCC specific condenser capacity, WK�1
t temperature, �CUA global heat transfer coefficient, WK�1
v specific volume, m3 kg�1
V velocity, m/s
V volume, m3
_VV Volume flow rate, m3 s�1
_WW electric power, W
Greek symbols
D difference
e efficiency
Subscripts
a air
amb ambient
cd condensercor coriolis
cp compressor
eh electric heater
ev evaporator
ex exhaust
f saturated liquid
fan fan
g saturated gasis isentropic
loop water or air loop
nom nominal
pump pump
r refrigerant
R404a refrigerant R404a
room room
s isentropicsc sub-cooling
sh shaft
su supplied
sw swept
v volumetric
w water
Fig. 1. Air-cooled condenser configurations for testing.
782 C. Cuevas, E.L. Winandy / Experimental Thermal and Fluid Science 27 (2003) 781–787
through the condenser (Fig. 1c) as recommended for
an air-cooled condenser specific test [3,4]. The disad-
vantage of this method is that the air flow is far from
the ‘‘in-field’’ air mass flow since it goes straightly
through the condenser. Another disadvantage is that
the duct geometry has to be adapted each time a newcondensing unit is tested.
The method proposed here is presented in Fig. 1d
where two plenums are separated by a wall where the
condensing unit is placed. Low velocities in front of the
condenser guarantee to reproduce field conditions as
close as possible.
This method presents the disadvantage that air
plenum pressure before and after the condensing unit
must be controlled to be the same in order to main-
tain the same conditions as in a real situation. If this
condition is respected, the fan will work at nominal
conditions. Otherwise, overfeed or underfeed of thecondenser is possible if no precaution is taken. The
precautions to take care are given in the following
part.
2. Description of the test apparatus
2.1. Air network
The air flows through a closed loop driven by a fan
placed in the air channel outside the room. The air flows
from the hot side of the climatic room into the air
channel through cooling coils supplied with tap-water as
coolant. The cold side temperature is kept constant by
tuning the cooling water flow rate thanks to a regulating
valve driven by a PID controller. The controller tem-perature sensor is placed in the cold side of the room in
front of the supply air grill. This air grill provides a
uniform air velocity distribution at condenser inlet. The
air network is shown in Fig. 3.
Fig. 3. Air circulation in the test bench.
Cold side Hot side
cdap ,
roomap ,
Slope of plastic tape
Fig. 4. Pressure difference measurements in the climatic room.
Fig. 2. Inlet air temperature to the condensing unit.
∆
Fig. 5. Pressure difference and plastic-tape angle.
C. Cuevas, E.L. Winandy / Experimental Thermal and Fluid Science 27 (2003) 781–787 783
Air mass flow rate in the loop was adjusted by means
of a simple visual pressure-difference measuring element.
This measuring device consists in a strip or plastic tapeinstalled in a vertical hole in the wall separating the two
sides of the room. When the strip stays vertical, it means
there is no over-pressure in one of the two rooms.
Tests were performed to determine the sensitivity of
this simple visual element, which is used during the tests.
Thanks to a variable-speed fan, it was possible to adjust
precisely air mass flow rate. During the test, the con-
denser fan was switched on and the air mass flow ratethrough the room was tuned to generate positive and
negative pressure differences between the two sides of
the room. The pressure-differences are measured using
inclined-tube manometers with an accuracy of �1 Pa,
and the slope of the plastic-tape is estimated by ocular
inspection. Two pressure differences are measured: be-
tween the hot and the cold side of the room and between
the cold side of the room and the inside of the condensercasing (just after the coils). Details are shown in Fig. 4.
Fig. 5 shows the pressure difference between the two
rooms as a function of the slope. In the angle sensitivity
range of the hanging plastic tape, the pressure variation
is maximum �2 Pa. In this range the pressure drop
change on the condenser coils is about 2 Pa, as shown in
Fig. 5.
Assuming air mass flow rate through condenser is
proportional to the square root of pressure drop in the
condenser coils, then the ratio between actual and
784 C. Cuevas, E.L. Winandy / Experimental Thermal and Fluid Science 27 (2003) 781–787
nominal mass flow rate can be computed. This ratio is
shown on Fig. 5 as a function of strip slope. It can be
seen that air mass flow rate does not vary more than 1%
in the range )90� to 90� of slope. In conclusion, this tool
is enough to regulate air flow through the loop.
2.2. Water network
The evaporator is connected to a closed water circuit,
which includes an electric water heater outside the room
with a maximum heating capacity of 15 kW, a pump and
plastic connection tubes. The water loop is thermally
insulated. Electrical power can be adjusted in all therange.
2.3. The refrigerant network
The refrigerant network is shown in Fig. 6. It consists
in the condensing unit, a coaxial water heated evapo-
rator, a Coriolis mass flow meter, a thermostatic ex-
pansion valve and a sight glass. Refrigerant used isR404a.
The condensing unit is composed of an air-cooled
condenser, a scroll compressor and a refrigerant vessel.
It was tested with two different fans with different ro-
tation speeds. The compressor and condensing units
characteristics are detailed in Table 1.
Fig. 6. Test bench con
2.4. The measuring system
Temperatures are measured with type T thermocou-
ples (copper–copper–nickel) with an accuracy of 0.3 K.
Refrigerant mass flow rate is measured with a Coriolisflow meter with an accuracy of ð�0:25% of readingÞ þð�0:025% of _MMnomÞ, where _MMnom ¼ 0:27 kg/s. The flow
meter was installed in the liquid zone, so it was necessary
to ensure a good sub-cooling in order to avoid erroneous
measurement [6].
Pressures are measured with an accuracy of 0.2%.
Temperatures, pressures, mass flow rate and powers are
measured and recorded by a data acquisition systemwith a time period of 5 s.
3. Test analysis
3.1. Evaporator
The cooling capacity is obtained from the followingevaporator heat balance on water side:
_HHev ¼ _QQeh þ _WWpump þ _QQamb;ev ð1Þwhere _HHev is the cooling capacity (refrigerant enthalpy
flow rate extracted from the evaporator), _QQeh is the
electric power given to water by means of electric re-
nection diagram.
Table 1
Condensing unit characteristics
Compressor type Scroll
Compressor swept volume (m3/h) 14.5
Compressor RPM 2900
Nominal capacity (kW)� 13.09
Nominal power input (kW)� 3.95
Fans 1 & 2 diameter (cm) 42
Fans 1 & 2 N� vanes 4
Fan 1 RPM 1380
Fan 2 RPM 940
Fan 1 power (W) 240
Fan 2 power (W) 105
*Nominal conditions: tev ¼ 0 �C, tcd ¼ 40 �C and no sub-cooling.
C. Cuevas, E.L. Winandy / Experimental Thermal and Fluid Science 27 (2003) 781–787 785
sistances, _WWpump is the pumping power given to the
evaporator water network (93 W) and _QQamb;ev is the heat
flow rate transmitted from ambient to the evaporator.
This last term is given by
_QQamb;ev ¼ UAw;loop tamb;ev
�� ðtw;su;eh � tw;ex;ehÞ
2
�ð2Þ
A calibration of the water loop permitted to identify
heat transfer coefficient of the loop UAw;loop. It was
found:
UAw;loop ¼ 6 W=K ð3ÞThe refrigerant mass flow rate can be computed from:
_MMr ¼_HHev
ðhex;ev � hsu;evÞð4Þ
It is compared to the Coriolis mass flow rate for secu-
rity.
3.2. Compressor
The compressor balance in steady state is given by
_WWcp þ _HHcp þ _QQamb;cp ¼ 0 ð5ÞThe ambient losses of the compressor are determined
from this heat balance. It is necessary to evaluate them
since they are injected in the hot plenum and are part of
the condenser heat balance (Eq. (10)).The lubricant circulation is neglected here. Indeed,
when working with scroll compressors, oil concentration
is expected to be less than 1%.
In order to analyze compressor performances at dif-
ferent operating conditions, the volumetric and com-
pressor isentropic efficiencies are computed:
Volumetric efficiency is given by
em ¼_VVsu
NVswð6Þ
where Vsw is the swept volume and _VVsu is the volume flow
in the suction inlet:
_VVsu ¼ _MMmsu ð7Þ
Compressor global isentropic efficiency is given by
ecp;s ¼ws
wsh
ð8Þ
where ws is the isentropic work of compression and wsh
is the specific shaft work:
wsh ¼_WWsh
_MMð9Þ
3.3. Condenser
Calorimeter air balance allows us to calculate the air
flow rate passing through the condenser. Indeed we
have:
_MMaðha;su � ha;exÞ þ _HHr;cd þ _WWfan þ _QQamb;cp ¼ 0 ð10Þwhere ha;su is the air enthalpy in the cold room and ta;ex isthe air enthalpy in the hot room. _HHcd is the condenser
capacity (refrigerant enthalpy flow rate extracted from
the condenser) and _WWfan is the fan power given to the
ambient.
Treating the condenser as semi-isothermal heat ex-
changer (where the refrigerant has an infinite capacityflow rate), we can define an overall heat transfer coeffi-
cient UAcd by
_QQcd ¼ UAcd LMTDcd ð11Þwhere LMTDcd is the log-mean temperature difference
computed as [7]:
LMTDcd ¼ðta;ex;cd � ta;su;cdÞln
tcd�ta;su;cdtcd�ta;ex;cd
� � ð12Þ
where tcd is the condensing temperature computed by
tcd ¼tf;cd þ tg;cd
2ð13Þ
and ta;ex;cd is a corrected air temperature, which is re-
calculated by thermal balance on the condenser.
Since the condenser is also characterized by its
specific condenser capacity (SCC), this value is also
interesting for the manufacturer, even if the discussion
here will be based on the UAcd values. The SCC is
defined by
SCC ¼_QQcd
ðtg;cd � ta;su;cdÞsð14Þ
The refrigerant properties and the equations are solved
using EES [5].
4. Case study: condensing unit performance with two
different fans
In order to illustrate the method, the results obtained
on a condensing unit working with two different fans is
786 C. Cuevas, E.L. Winandy / Experimental Thermal and Fluid Science 27 (2003) 781–787
analyzed in this part. Furthermore, as a sensibility
analysis, the condensing unit was running at two dif-
ferent evaporating temperatures and for each one, the
refrigerant charge was varied in order to change the
condenser sub-cooling.The general results are presented in Table 2 and the
condenser specific results in Table 3.
4.1. Compressor
Fig. 7 shows the variation of the isentropic and vol-
umetric efficiencies. As it can be seen, the volumetric
efficiency decreases as the pressure ratio increases. It hasbeen shown that this trend can be explained by internal
heat transfers: the scroll chamber inlet density decreases
as the pressure ratio increases since the suction heating
up increases [9].
The isentropic efficiency presents the same variation
with the pressure ratio but the reason is quite different.
It is well known that, as soon as the external pressure
ratio becomes higher than the internal built-in one, theinternal efficiency start decreasing, as the pressure ratio
increases [8]. This effect is visible at the level of the
overall efficiency.
Table 2
General results
Test MR404A (kg) tev (�C) tcd (�C) D
1 (Fan 1) 9.358 )21.0 44.8
2 (Fan 1) 9.208 )21.4 44.1
3 (Fan 1) 9.678 )21.6 45.7
4 (Fan 1) 9.358 )0.5 55.6
5 (Fan 1) 9.208 )0.7 54.9
6 (Fan 1) 9.678 )1.2 57.1
7 (Fan 2) 9.204 )21.4 47.9
8 (Fan 2) 9.052 )20.6 47.8
9 (Fan 2) 9.424 )20.7 49.3
10 (Fan 2) 9.204 )0.9 61.6
11 (Fan 2) 9.052 0.2 61.5
12 (Fan 2) 9.424 )0.1 63.9
Table 3
Summary of the main values for the condenser
Test ta;su;cd (�C) ta;ex;cd (�C) Dtsc (�C) _QQcd (W)
1 (Fan 1) 32.0 38.0 6.0 8367
2 (Fan 1) 32.0 37.8 3.9 8197
3 (Fan 1) 32.0 38.2 9.1 8348
4 (Fan 1) 32.2 44.2 9.1 15576
5 (Fan 1) 32.1 44.0 6.9 15320
6 (Fan 1) 32.2 44.6 13.5 15647
7 (Fan 2) 32.2 41.4 3.3 8094
8 (Fan 2) 32.1 41.0 2.9 8310
9 (Fan 2) 32.2 41.5 8.1 8394
10 (Fan 2) 32.2 48.6 9.6 14805
11 (Fan 2) 32.4 49.7 5.4 15254
12 (Fan 2) 32.4 49.8 13.6 15456
4.2. Condenser
Table 3 shows a summary of the main values com-
puted for the condenser. In this Table, are given the
results obtained with two different fans.Quite constant air mass flow rates are obtained for
each fan: this is a good trace for confirming that the tests
were well carried out. Another information is given by
the order of magnitude: fan 1 has 46% more mass flow
rate than fan 2. Fan 1 has a mean air flow rate of 1.319
kg/s and fan 2 a mean airflow of 0.890 kg/s. For each
case, the difference between the mean values for the air
mass flow rate and the maximum and minimum value islower than �5%.
Supplementary measurements of the air mass flow
rate were carried out in order to confirm the results
obtained. The air velocity was measured at 4� 10
(rows� columns) points, 5 mm in front of the condenser
grid with a hot wire probe (10% accuracy). The sum-
mary is given in Table 4.
As it can be seen, the air mass flow rate measured viathe air velocity for the fan 1 and 2 agree well (about 10%
of difference) with the air mass flow rate computed via
the condenser balance.
tsc (�C) _MMcor (Kg/s) _QQeh (W) _WWcp (W)
6.0 0.0427 5629 3872
3.9 0.0420 5475 3854
9.1 0.0421 5584 3843
9.1 0.0962 11179 5644
6.9 0.0957 10946 5628
13.5 0.0961 11076 5615
3.3 0.0431 5210 3882
2.9 0.0425 5527 4001
8.1 0.0433 5483 3993
9.6 0.0946 10012 5990
5.4 0.1046 10089 5992
13.6 0.0963 10490 6253
_MMa (kg/s) LMTDcd (K) UAcd (W/K) SCC (W/K)
1.374 9.4 886 637
1.385 8.9 925 656
1.336 10.2 816 597
1.285 16.7 932 648
1.280 16.1 951 655
1.255 18.0 870 616
0.870 10.5 773 500
0.927 10.6 781 518
0.889 11.8 711 481
0.900 20.1 737 496
0.874 19.2 796 515
0.881 21.6 714 484
Fig. 8. Influence of the sub-cooling on the UAcd.
Fig. 7. Compressor isentropic and volumetric efficiencies.
Table 4
Measurement of the airflow rate
Fan 1 Fan 2
N (rpm) 1380 940
V a (m/s) 2.46 1.72_MMa (kg/s) 1.18 0.82
C. Cuevas, E.L. Winandy / Experimental Thermal and Fluid Science 27 (2003) 781–787 787
With the results obtained in these tests, the evolution
of the global heat transfer coefficient can be analyzed,
Fig. 8 shows the results. Of course the global UAcd
(assumed as one zone heat exchanger) depends on the
degree of sub-cooling. In general, when the sub-cooling
increases the global heat transfer coefficient of the con-denser decreases. This is observed for both fans.
The conclusion is that for the conditions reached
during the tests, the UAcd values decrease about 14 W/K
for each increasing of the sub-cooling of 1 K.
5. Conclusions
Two methods for testing condensing units are pre-
sented in this paper. Advantages and drawbacks of each
method are discussed and the precautions necessary totake into account for separate plenums methodology.
The main component of the condensing unit to study
here was the condenser. For this component, thermal
balance was developed in order to calculate the air mass
flow rate that passes through the condenser. With the
method proposed, the air mass flow rate can be pre-
dicted with a discrepancy lower than 5%. The air mass
flow rate computed by balance is compared with the airmass flow rate measured. There exists a good agreement
between both values, the difference being lower than
10%.
As an example, with the results presented in this
paper an analysis of the UAcd is shown in function of
the degree of sub-cooling. This parameter decreases with
the degree of sub-cooling of about 14 W/K per K of sub-
cooling.
Acknowledgement
This study has been supported by COPELAND Eu-
rope-Welkenraedt S.A.
References
[1] ASHRAE Standard 23-1978R. Methods of testing for rating
positive displacement refrigerant compressors and condensing
units, 1992.
[2] AFNOR European Standard EN 13215, Condensing units for
refrigeration––rating conditions, tolerances and presentation of
manufacturer�s performance data, June 2000.
[3] ASHRAE Standard 33-1978R. Methods of testing forced circula-
tion air cooling and air heating coils, 1999.
[4] AFNOR European Standard EN 1216, Heat exchangers––forced
circulation air-cooling and air-heating coils–test procedures for
establishing the performance, May 1999.
[5] EES. Engineering Equation Solver. Program developed by the
Department of Mechanical Engineering, University of Wisconsin-
Madison, 2000.
[6] P.J. Hawken, P.F. Hearty, C. Lemal, The influence of two-phase
flow on a coriolis effect mass flow meter, ASHRAE Trans. 91
(1985) 310–321, Part 1A.
[7] F. Incropera, D. DeWitt, Fundamentals of Heat and Mass
Transfer, John Wiley & Sons (1990).
[8] W.F. Stoecker, Industrial Refrigeration, Business News Publishing
Company, 1988.
[9] E. Winandy, C. Saavedra, J. Lebrun, Experimental analysis and
simplified modeling of an hermetic scroll refrigeration compressor,
Appl. Thermal Engng. 22 (2) (2002) 107–120.